This is an asbestos survey and lead-based paint sampling report prepared by CTL|Thompson, Inc. for Boulder County Public Works regarding the Copper Door Facility located at 1770 21st Street in Boulder, Colorado. The survey was conducted to identify asbestos-containing materials (ACM) and lead-based paint prior to the building's demolition. The subject property is a 15,168-square-foot, three-story apartment building constructed in 1972 with a 1998 addition. Certified CDPHE Asbestos Inspectors Benjamin Rief (#30857) and Kendal Fosbaugh (#28216) performed the survey during multiple site visits on March 10, 11, 16, 17, and April 2, 2026. The inspection involved collecting 126 bulk samples of suspect materials from various building systems, including wall and ceiling systems, flooring systems, thermal systems, and miscellaneous/roofing systems, with samples submitted to EMSL Analytical Inc. for polarized light microscopy (PLM) analysis.
The survey identified extensive asbestos-containing materials throughout the building, including popcorn texture on approximately 15,000 square feet of ceilings, orange peel texture on approximately 36,240 square feet of walls, asbestos floor tile and mastic in office and bathroom areas, pipe cement and insulation in thermal systems, and fire doors containing asbestos. Additionally, cove base mastic, shower tile mastic, and other miscellaneous materials were identified as ACM requiring abatement. The report notes that while Category I nonfriable floor tile and mastic may typically remain in place if kept in nonfriable condition, Boulder's deconstruction requirements mandate recycling at least 75 percent of certain building materials, and practical demolition conditions suggest inclusion of flooring materials in abatement work. All identified ACM will require removal by a General Abatement Contractor (GAC) prior to demolition in compliance with EPA NESHAP regulations and CDPHE requirements.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
CTL | Thompson, Inc.
Denver, Fort Collins, Colorado Springs, Glenwood Springs, Pueblo, Summit County – Colorado
Cheyenne, Wyoming and Bozeman, Montana
ASBESTOS SURVEY AND LEAD-BASED
PAINT SAMPLING FOR DEMOLITION
COPPER DOOR FACILITY
1770 21st Street Boulder, Colorado 80302
Prepared for:
BOULDER COUNTY PUBLIC WORKS
PO Box 471
Boulder, Colorado 80306
Attention:
Joe May
Project No. DN52,856.000-221-R1
April 22, 2026 https://ctlthompson.com/ https://ctlthompson.com/denver https://www.ctlthompson.com/fortcollins https://www.ctlthompson.com/coloradosprings https://www.ctlthompson.com/glenwoodsprings https://www.ctlthompson.com/pueblo https://www.ctlthompson.com/summitcounty https://www.ctlthompson.com/cheyenne https://www.ctlthompson.com/bozeman
BOULDER COUNTY OUBLIC WORKS
LIMITED ASBESTOS SURVEY
COPPER DOOR FACILITY – 1770 21ST STREET
CTL|T PROJECT NO. DN52856.000-221-R1
TABLE OF CONTENTS
ACRONYMS ................................................................................................................................ i
1.0 INTRODUCTION
2.0 ASBESTOS METHODOLOGY
3.0 ASBESTOS INSPECTION PROCEDURE
3.1 Asbestos Sample Collection
3.2 Asbestos Sample Analysis
4.0 ASBESTOS REGULATORY CRITERIA
5.0 ASBESTOS INSPECTION RESULTS
5.1 Asbestos Containing Material
5.2 Trace / OSHA Regulated Material
6.0 LEAD PAINT SAMPLING
7.0 REGULATED BUILDING MATERIALS / HAZARDOUS MATERIALS
8.0 LIMITATIONS
SUMMARY OF FEDERAL AND STATE ASBESTOS REGULATIONS
TABLE 1 – ASBESTOS RESULTS FOR HOMOGENOUS MATERIALS
FIS. 1A THROUGH 1C – APPROXIMATE SAMPLE LOCATIONS
FIG. 2 – TEXTURE ACM LOCATIONS – FIRST FLOOR
FIG. 3 – TEXTURE ACM LOCATIONS – SECOND FLOOR
FIG. 4 – TEXTURE ACM LOCATIONS – THIRD FLOOR
FIG. 5 – FLOORING ACM LOCATIONS – FIRST FLOOR
FIG. 6 – FLOORING ACM LOCATIONS – SECOND FLOOR
FIG. 7 – FLOORING ACM LOCATIONS – THIRD FLOOR
FIG. 8 – OTHER ACM LOCATIONS – FIRST FLOOR
FIG. 9 – OTHER ACM LOCATIONS – SECOND FLOOR
FIG. 10 – OTHER ACM LOCATIONS – THIRD FLOOR
APPENDIX A – SITE PHOTOGRAPHS
APPENDIX B – ASBESTOS LABORATORY RESULTS AND CHAINS OF CUSTODY
APPENDIX C – LEAD LABORATORY RESULTS AND CHAINS OF CUSTODY
APPENDIX D – CDPHE REGULATED BUILDING MATERIALS INFORMATION
APPENDIX E – CTL|THOMPSON CERTIFICATIONS
BOULDER COUNTY OUBLIC WORKS i of i
COPPER DOOR FACILITY – 1770 21ST STREET
CTL|T PROJECT NO. DN52856.000-221-R1
ACRONYMS
ACBM Asbestos Containing Building Materials
ACM Asbestos Containing Materials
AHERA Asbestos Hazard Emergency Response Act
EPA Environmental Protection Agency
HA Homogeneous Area
HEPA High Efficiency Particulate Air
HVAC Heating Ventilation and Air Conditioning
NESHAP National Emission Standards for Hazardous Air Pollutants
O&M Operations and Maintenance
OSHA Occupational Safety and Health Administration
PCM Phase Contrast Microscopy
PLM Polarized Light Microscopy
PPM Parts Per Million
RBM Regulated Building Material
TEM Transmission Electron Microscopy
TSI Thermal System Insulation
BOULDER COUNTY OUBLIC WORKS 1 of 12
COPPER DOOR FACILITY – 1770 21ST STREET
CTL|T PROJECT NO. DN52856.000-221-R1
1.0 INTRODUCTION
Boulder County Public Works retained CTL|Thompson, Inc. (CTL|T) to perform an asbestos survey for the demolition of 1770 21st Street in Boulder, Colorado.
The subject property is a 3-story apartment type building with a newER addition on the southwest corner of the first floor. The building is currently unoccupied. The building is approxi-mately 15,168 square feet and was constructed in 1972, with the addition constructed in 1998.
The building is heated by hot water radiant heat and cooled by three roof-mounted swamp cool-ers.
The building is being considered for demolition. Mr. Benjamin Rief and Mr. Kendal
Fosbaugh, certified CDPHE Asbestos Inspectors #30857 and #28216, performed the asbestos sur-vey on March 10, 11, 16, 17, and April 2, 2026. We observed and sampled suspect asbestos con-taining building materials (ACBM) in the structure. All observed suspect ACBM were sampled in general accordance with AHERA regulations.
2.0 ASBESTOS METHODOLOGY
The purpose of the asbestos inspection was to identify the condition and location of friable and non-friable asbestos materials that are present in the building. During the asbestos materials survey, CTL|T performed the following tasks:
• Inspected accessible areas for suspected asbestos materials;
• Determined friability of suspected asbestos materials by touching;
• Developed a sampling plan for each material based on the homogeneous material type, friability, accessibility, and material locations;
• Assessed the condition and potential hazards of the suspected asbestos materials;
• Collected samples of suspected homogeneous and non-homogeneous materials and submitted them for laboratory analysis by Polarized Light Microscopy (PLM);
and,
• Documented findings and inspection protocol in accordance with accepted industry standards.
BOULDER COUNTY OUBLIC WORKS 2 of 12
COPPER DOOR FACILITY – 1770 21ST STREET
3.0 ASBESTOS INSPECTION PROCEDURE
Homogeneous suspect asbestos materials were identified by visually inspecting the following systems:
• Wall/ceiling systems;
• Flooring systems;
• Thermal systems; and
• Miscellaneous / Roofing systems.
Based on our inspection, the following types of suspect asbestos-containing materials were identified and sampled:
• Wall and Ceiling Systems o Drywall / Texture – 34 Samples o Joint Compound – 4 Samples o Cove Base Mastic – 10 Samples
• Flooring Systems o Floor Tile / Mastic – 12 Samples o Carpet Mastic – 14 Samples o Vinyl – 2 Samples o Rubber Threshold Mastic - 4
• Thermal Systems o Blown in Insulation – 6 Samples o Fire Door – 2 Samples o Water Heater Insulation – 3 Samples o Boiler/Radiator Pipe Insulation – 3 Samples o Pipe Dope – 2 Samples
BOULDER COUNTY OUBLIC WORKS 3 of 12
COPPER DOOR FACILITY – 1770 21ST STREET
• Miscellaneous / Roofing Systems o Roof Shingles – 2 Samples o Bath Tile – 2 Samples o Vinyl – 2 Samples o Sink Coating / Mastic – 2 Samples o Caulking – 10 Samples o Window Glazing – 4 Samples o Countertop Mastic – 8 Samples
The inspection did involve limited destructive observation methods; this generally consisted of placing small holes in walls/floors and collecting samples of various materials. Although destructive observations and sampling were conducted, there may be areas warranting further investigation. If additional suspect materials are encountered during the demolition, CTL|T should be contacted for additional sampling.
3.1 Asbestos Sample Collection
CTL|T collected bulk samples of the suspected friable ACBM and non-friable RACM (that would become friable during demolition) asbestos materials in a random and representative manner as defined by the U.S. Environmental Protection Agency (EPA) statistical sampling methods. Friable surfacing materials, if present, were sampled in general accordance with the random sampling procedures presented in EPA Publication EPA560/5-85-030a (also known as the “Pink Book”). The collected samples were packaged in sealed and labeled containers.
3.2 Asbestos Sample Analysis
The bulk samples of suspected asbestos materials were submitted to EMSL Analytical
Inc. for analysis. EMSL is accredited by the National Voluntary Laboratory Accreditation Program
(NVLAP) (Lab Code NVLAP Lab Code 200828-0).
BOULDER COUNTY OUBLIC WORKS 4 of 12
COPPER DOOR FACILITY – 1770 21ST STREET
CTL|T PROJECT NO. DN52856.000-221-R1
Individual layers of the suspect asbestos samples were analyzed by Polarized Light Mi-croscopy (PLM) to determine asbestos type and content. Unused portions of the samples were archived for 60 days, unless the client requested special handling. By regulation, any single pos-itive asbestos sample classifies the entire homogeneous material as asbestos-containing and additional analysis is not required.
4.0 ASBESTOS REGULATORY CRITERIA
According to the Occupational Safety and Health Administration (OSHA), the Environmen-tal Protection Agency (EPA), and the Colorado Department of Public Health and Environment
(CDPHE), samples with asbestos concentrations greater than one percent (1%) are classified as asbestos-containing materials and are a regulated material. If a building structure is scheduled for renovation or demolition, friable samples that contain trace amounts of asbestos (1% or less) must be further analyzed by a more accurate point-count analysis to determine if they exceed the
1% threshold, or the materials must be assumed to contain asbestos and be classified as a reg-ulated material.
The EPA and OSHA distinguish between friable and non-friable forms of asbestos mate-rials. Friable materials can be crumbled or reduced to powder by hand pressure when dry. Non-friable materials cannot be crumbled, pulverized, or reduced to powder by hand pressure when dry. Friable materials are more likely to be released into the air, especially if impacted or damaged during normal use, renovation, or demolition of a building. Therefore, the distinction between fri-able and non-friable asbestos materials is important. The EPA further segregates non-friable as-bestos materials into Category I or Category II. Category I non-friable asbestos materials include resilient floor coverings, asphalt roofing products, packings, and gaskets. Removal of these as-bestos materials is not required prior to demolition of a building, as long as they are in good condition and not friable and/or rendered friable. Category II asbestos materials are all other non-friable asbestos materials and may be required to be removed prior to demolition of a building if those materials will be rendered friable. All ACM that will be disturbed during a renovation must be abated.
Whether removed or remaining in a structure during demolition, the confirmed or presumed asbestos materials are subject to EPA National Emission Standards for Hazardous Air Pollutants
(NESHAP) and OSHA regulations. In 40 CFR 61.145, NESHAP requires that each owner or
BOULDER COUNTY OUBLIC WORKS 5 of 12
COPPER DOOR FACILITY – 1770 21ST STREET
CTL|T PROJECT NO. DN52856.000-221-R1
operator of a demolition activity provide the administrator with written notice of intent. The CDPHE has implemented the NESHAP program.
5.0 ASBESTOS INSPECTION RESULTS
CTL|T completed a survey of the building. Results of the asbestos analyses for the homogeneous materials collected from the building by CTL|T are summarized below. Laboratory reports for the samples collected by CTL|T are presented in Appendix B.
CTL|T collected one hundred and twenty-six (126) samples of suspect ACM from the building.
5.1 Asbestos Containing Material
Our survey identified the following ACM:
• Wall and Ceiling Systems o Popcorn Texture (white) – HA1 - Ceilings – approx. 15,000 square feet
(essentially the entire building except the boiler and storage rooms) o Overspray (white) – HA32 - approx. 2,000 square feet - visible on wood trusses in attic (above ceiling hatch on 3rd floor hallway) and on HVAC components visible at floor level behind access hatches in the hallways.
o Orange Peel Texture (yellow) – HA2 - Hallway and Stairwell walls – approx.
8,400 square feet o Orange Peel Texture (white) – HA3 - Residence Rooms walls – approx.
27,400 square feet o Orange Peel Texture (green) – HA4 - Security Office walls – approx. 440 square feet o Joint compound on all walls – HA9 - assumed that – for anywhere there are textured walls – this will also be abated. See Section 5.2 for further discussion where untextured.
BOULDER COUNTY OUBLIC WORKS 6 of 12
COPPER DOOR FACILITY – 1770 21ST STREET
• Floor Systems o Green speckled 12x12 floor tile and mastic below – HA12 - Offices in northeast corner of each floor – approx. 150 square feet o Brown speckled 12x12 floor tile and mastic below – HA13 - Bathrooms in offices in northeast corner of each floor – approx. 90 square feet o White speckled 12x12 floor tile and mastic below – HA26 - Under carpet in
1st floor office in northeast corner– approx. 40 square feet
• Thermal Systems o Pipe Cement – HA42 - White cement coating pipes exiting boiler – approx.
5 linear feet o Pipe “Sealant” – HA49 - Associated with pipe insulation penetrating down beneath the slab in the boiler room; this material point-counted to less than 0.25% asbestos and so may or may not be “Trace”, but appears to have been picked up on only one of our three insulation samples; by rule we have to assume that this is ACM until further observation and sampling is performed, and this will necessitate at least some destruction of the concrete slab. At present we assume approximately 400 linear feet beneath the first floor slab, until further observation is performed.
• Other Miscellaneous Systems o Black cove base mastic/mud – HA7 – Hallways and stairwells - approx. 250 square feet o White cove base mastic/mud – HA8 – resident rooms - approx. 350 square feet o Fire Doors – HA18 - Entrances, and doors exiting stairwells and boiler room
– approx. 300 square feet (12 doors) o White speckled 4x4 shower tile mastic – HA15 - Bathrooms on north side of building – approx. 160 square feet
These materials will require abatement by a General Abatement Contractor (GAC) for dem-olition in Boulder; we note that typically, Category I nonfriable floor tile and mastic can stay in place provided they remain in generally nonfriable condition (the other materials to be abated are either
BOULDER COUNTY OUBLIC WORKS 7 of 12
COPPER DOOR FACILITY – 1770 21ST STREET
CTL|T PROJECT NO. DN52856.000-221-R1
friable, would become friable, or are adhered to friable materials). However, City of Boulder decon-struction requirements, found at: https://bouldercolorado.gov/services/sustainable-deconstruction-requirements outlines the need for recycling at least 75% of some building materials (though this may or may not be subject to discussions with the City). In addition, it may be challenging for the contractor to keep flooring materials on the 2nd and 3rd floors in relatively nonfriable condition during demolition. Furthermore, the GAC will need to abate walls and ceilings regardless – along with cove base and shower tile adhering - and will have containments erected where flooring and other materials can be included in abatement relatively easily.
5.2 Trace / OSHA Regulated Material
The following materials were point-counted to <0.25% Chrysotile asbestos:
• An exterior window glazing on the 3rd floor east stairwell; minimal - approx. (one) 1 square foot;
• A mastic beneath the faux wood vinyl flooring in the kitchens; approx. 720 square feet; and,
• Joint Compound – Drywall System - approx. 700 square feet untextured in the boiler and storage rooms.
Materials with any amount of asbestos are still regulated by OSHA, but these materials are not regulated by CDPHE. Specifications for demolition should identify the trace materials and es-tablish a scope of work compliant with EPA, OSHA, State, and local regulations. We also recom-mend removal of all visible debris found on the ground surface so as to avoid any asbestos-in-soils issue after demolition.
There is some interpretation as to how City of Boulder requirements mesh with EPA and
CDPHE asbestos/demolition regulations; we offer these points for consideration for trace (1% or less asbestos) where often these would otherwise be left in place as demo waste:
• If the Trace material is chosen to not be abated – for example the window glazing – care should be taken not to mix these trace materials in with recycled materials.
• The FAQ guidance at the Boulder website, in reference to “non-friable, non-regu-lated, or trace asbestos”, simply states the need to talk with the City before starting deconstruction.
https://bouldercolorado.gov/services/sustainable-deconstruction-requirements https://bouldercolorado.gov/services/sustainable-deconstruction-requirements
BOULDER COUNTY OUBLIC WORKS 8 of 12
COPPER DOOR FACILITY – 1770 21ST STREET
CTL|T PROJECT NO. DN52856.000-221-R1
• CTL|T spoke with a CDPHE representative on April 21, 2026, who clarified that -though they do regulate ACM flooring materials - they do not regulate, per se, Trace materials, nor does EPA, but suggested that consideration and/or notice be given to:
o The landfill / ultimate recipient of demo materials;
o OSHA. Worker protection should be of utmost priority regardless of deci-sions made on disposal or recycling, particularly when creating dust (e.g.
cutting or grinding of concrete) with any amount of asbestos adhering to it;
and, o Local requirements (stated above).
A summary of asbestos sample results can be found in Table 1, and sample locations can be found on Figures 1A thru 1C. Asbestos sample lab results and chain of custody can be found in Appendix B.
6.0 LEAD PAINT SAMPLING
Since the building is planned for a demolition, the building waste is planned to be placed in a landfill, we conducted sampling for lead containing paint.
CTL|T collected eight (8) paint samples as follows:
• Pb1 – White Exterior = 120 ppm
• Pb2 – Yellow Exterior = <64 ppm
• Pb3 – White Resident Rooms = <64 ppm
• Pb4 – Yellow Hallway = <64 ppm
• Pb5 – Blue Stair Rails / Window Frames = 160 ppm
• Pb6 – Blue Addition = <64 ppm
• Pb7 – White Addition = <64 ppm
• Pb8 – Green Security Office = <64 ppm
Lead was detected in the eight paint samples. Two of the lead paint samples resulted in a lead concentration above 20 times the TCLP hazardous waste limit of 5 parts per million (5ppm), or 0.01% / 100 ppm. Considering the laboratory results and implied “20 times TCLP waiver of
TCLP sampling”, referenced in section 1.2 of TCLP Method 1311, required under 40 CFR 261.24, BOULDER COUNTY OUBLIC WORKS 9 of 12
COPPER DOOR FACILITY – 1770 21ST STREET
CTL|T PROJECT NO. DN52856.000-221-R1
lead TCLP sampling will be necessary for disposal of the painted components. We are currently awaiting the results of this analysis and will provide them when they are received from the labor-atory.
Paint sample locations can be found on Figure 1. Paint sample lab results and chain of custody can be found in Appendix C.
7.0 REGULATED BUILDING MATERIALS / HAZARDOUS MATERIALS
We did observe regulated building materials that should be removed properly prior to the demolition of the building. These materials include:
• (1) Mini Refrigerator (2nd Floor Office)
• (23) Fire-Extinguishers
• (23) Window A/C units
• (1) Condenser
• (25) 8 feet or higher, 2-foot fluorescent light bulbs (Addition)
• (13) 8 feet or higher, fluorescent light ballast (Addition)
• (52) 8 feet or higher, 2-foot fluorescent light bulbs (Original Building)
• (17) 8 feet or higher, fluorescent light ballast (Original Building)
8.0 LIMITATIONS
This report was prepared for the use of Boulder County Public Works in assessing asbestos for the demolition of 1770 21st Street in Boulder, Colorado. Observations made were with limited intrusiveness and of readily visible or exposed building materials. Our services were performed with limited destructive sampling; thus, our services are not intended to guarantee or certify the absence of asbestos.
This report is not to be used as a bid document for the removal, repair, encapsulation, enclosure, or Operations and Maintenance (O&M) of asbestos containing materials. CDPHE certified individuals from our firm can prepare a scope of work, bid documents, removal and repair methods/procedures, specifications, designs and O&M plans if desired.
BOULDER COUNTY OUBLIC WORKS 10 of 12
COPPER DOOR FACILITY – 1770 21ST STREET
CTL|T PROJECT NO. DN52856.000-221-R1
The accuracy and reliability of environmental studies are a reflection of the number and type of samples taken and extent of the analyses conducted and are thus inherently limited to and dependent upon the resources expended. An independent laboratory performed laboratory analysis. CTL|T is not responsible for the accuracy of data presented by others.
We believe we performed the survey in a manner consistent with the level of care and expertise exercised by members of the asbestos inspection and assessment profession. CTL|T does not imply or guarantee that every suspect asbestos material on or in the buildings has been identified or sampled. Historically, asbestos has been used extensively in the United States. This inspection is intended to identify those components that are reasonably suspect and hence most likely to be asbestos materials in quantities subject to regulation based on existing industry and regulatory standards. If additional asbestos materials or asbestos-suspect materials are encountered, work should be stopped, and an additional inspection performed.
If we can be of further service discussing the contents of this report, please call us
CTL|THOMPSON, INC.
Asbestos Consulting Firm No.: ACF-14870
Benjamin Rief Staff Geologist Certified Asbestos Inspector #30857 brief@ctlthompson.com
Kendal Fosbaugh Environmental Technician Certified Asbestos Inspector #28216 kfosbaugh@ctlthompson.com
Reviewed by:
Matthew L. Wardlow, P.E.
Environmental Department Manager Certified Asbestos Inspector #775 mwardlow@ctlthompson.com
Via e-mail: jmay@bouldercounty.gov mailto:brief@ctlthompson.com mailto:kfosbaugh@ctlthompson.com mailto:mwardlow@ctlthompson.com mailto:jmay@bouldercounty.gov
COPPER DOOR FACILITY 11 of 12
1770 21ST STREET, BOULDER CO
SUMMARY OF FEDERAL AND STATE ASBESTOS REGULATIONS
OSHA: U.S. Department of Labor, Occupational Safety, and Health Administration, including but not limited to:
• Occupational Exposure to Asbestos, Tremolite, Anthophyllite, and Actinolite;
• Final Rules Title 29, Part 1910, Section 1325 and Part 1926, Section 1101 of the Code of Federal Regulations;
• Respiratory Protection Standard Title 29, Part 1910, Section 134 of the Code of Federal Regulations;
• Construction Industry Title 29, Part 1926, of the Code of Federal Regulations;
• Access to Employee Exposure and Medical Records Title 29, Part 1910, Section 2 of the Code of Federal Regulations;
• Hazard Communication Title 29, Part 1926 Section 59 of the Code of Federal Regulations; and
• Specifications for Accident Prevention Signs and Tags Title 29, Part 1910, Section 145 of the Code of Federal Regulations.
DOT: U.S. Department of Transportation, including but not limited to:
• Hazardous Substances Title 29, Part 171 and 172 of the Code of Federal Regulations.
EPA: U.S. Environmental Protection Agency, including but not limited to:
• Asbestos Hazard Emergency Response Act (AHERA) Regulation;
• Asbestos Containing Materials in Schools Final Rule & Notice Title 40, Part 763 Sub-part E of the Code of Federal Regulations;
• Training Requirements of (AHERA) Regulation;
• Asbestos Containing Materials in Schools Final Rule & Notice Title 40, Part 763, Sub-part E, Appendix C of the Code of Federal Regulations;
COPPER DOOR FACILITY 12 of 12
1770 21ST STREET, BOULDER CO
• National Emission Standard for Hazardous Air Pollutants (NESHAPS); and
• National Emission Standard for Asbestos Title 40, Part 61, Sub-part A, Sub-part M (Revised Sub-part B) of the Code of Federal Regulations.
CDPHE: Colorado Department of Public Health and Environment, including but not limited to:
• Air Quality Control Commission, Regulation No. 8, Part B “Emissions Standards for Asbestos”; and
• Hazardous Materials and Waste Management Division, 6 CCR 1007-2, Section 5 “Asbestos Waste Management.”
STAIR
! 161 SF!
SUPPORT
! 258SF !
CONFERENCE
SUPPORT
Till]IT
CONFERENCE
TOILET C
! 68SF !
MECH
! 135SF!
CONFERENCE
(1
STORAGE
CORR
!379SF!
STORAGE
SUPPORT
Till]IT
SUPPORT
!258SF!
LEGEND
L.___J
D
ORGANIZATION BLDG GROSS PERSONNEL
1,427
1,478
CMI-Core Civic cONTRACTOR
APARTMENT
ONTRACTOR
SUPPORT
COMMUNITY
SERVICE CORRIDOR
BUILDING SUPPORT
BUILDING GROSS: 15,168 SF
FLOOR GROSS: 5,612 SF
SCALE: 1 "=1 O'
FACILITY OCCUPATION STUDY
BOULDER COUNTY
BOULDER COUNTY TRANSITION CENTER
(BCTC) - (COPPER DOOR)
1770 21st STREET
1 ST FLOOR PLAN VIEW
1-)� SURVEY DATE:
File No:
Boulder County Transition Center HOR
1/31/17 o, SHEET 1 OF 3 kemery Text Box kemery Text Box kemery Text Box 103, 104 kemery Text Box kemery Text Box kemery Text Box kemery Text Box kemery Text Box kemery Text Box kemery Text Box kemery Text Box kemery Text Box kemery Text Box kemery Text Box kemery Text Box kemery Text Box kemery Text Box kemery Text Box kemery Text Box 111, 112, kemery Text Box kemery Text Box 109, kemery Text Box kemery Text Box kemery Text Box kemery Text Box kemery Text Box kemery Text Box kemery Text Box kemery Text Box kemery Text Box kemery Text Box kemery Text Box kemery Text Box kemery Text Box kemery Text Box kemery Text Box kemery Text Box kemery Text Box kemery Text Box 67, 68 kemery Text Box 57, 58, kemery Text Box kemery Text Box kemery Text Box kemery Text Box kemery Text Box kemery Text Box kemery Text Box kemery Text Box kemery Text Box kemery Text Box kemery Text Box kemery Text Box kemery Text Box kemery Text Box kemery Text Box kemery Rectangle kemery Rectangle kemery Rectangle kemery Rectangle kemery Rectangle kemery Rectangle kemery Rectangle kemery Rectangle kemery Rectangle kemery Rectangle kemery Rectangle kemery Rectangle kemery Rectangle kemery Rectangle kemery Rectangle kemery Rectangle kemery Rectangle kemery Rectangle kemery Rectangle kemery Rectangle kemery Rectangle kemery Rectangle kemery Rectangle kemery Rectangle kemery Rectangle kemery Rectangle kemery Rectangle kemery Rectangle kemery Rectangle kemery Rectangle kemery Rectangle kemery Rectangle kemery Rectangle kemery Rectangle kemery Rectangle kemery Rectangle kemery Rectangle kemery Rectangle kemery Text Box Pb1 kemery Text Box Pb2 kemery Text Box Pb3 kemery Text Box Pb4 kemery Text Box Pb5 kemery Text Box Pb6 kemery Text Box Pb7 kemery Text Box Pb8 kemery Text Box kemery Text Box kemery Rectangle kemery Text Box # = Asbestos Samples # = Paint Samples # = Roof Samples # = Asbestos Containing Material (>1% Asbestos) # = Trace Asbestos (≤1% Asbestos) kemery Text Box kemery Text Box Figure 1A Approximate Sample Locations 1770 21st Street
DN52856.000-221-R1
kemery Text Box kemery Text Box kemery Text Box kemery Text Box kemery Text Box 124, 125, 126, kemery Text Box kemery Ellipse kemery Ellipse
Text Box kemery Text Box kemery Text Box kemery Text Box kemery Text Box kemery Text Box kemery Text Box kemery Text Box kemery Text Box kemery Text Box kemery Text Box kemery Text Box kemery Text Box kemery Text Box kemery Text Box kemery Text Box kemery Text Box kemery Text Box kemery Text Box kemery Text Box kemery Text Box kemery Text Box kemery Rectangle kemery Rectangle kemery Rectangle kemery Rectangle kemery Rectangle kemery Rectangle kemery Rectangle kemery Rectangle kemery Rectangle kemery Rectangle kemery Rectangle kemery Rectangle kemery Rectangle kemery Rectangle kemery Rectangle kemery Rectangle kemery Rectangle kemery Rectangle kemery Rectangle kemery Rectangle kemery Rectangle kemery Rectangle kemery Rectangle kemery Rectangle kemery Rectangle kemery Rectangle kemery Rectangle kemery Rectangle kemery Rectangle kemery Rectangle kemery Rectangle kemery Rectangle kemery Rectangle kemery Rectangle kemery Rectangle kemery Rectangle kemery Rectangle kemery Rectangle kemery Rectangle kemery Rectangle kemery Rectangle kemery Rectangle kemery Rectangle kemery Rectangle kemery Rectangle kemery Rectangle kemery Rectangle kemery Rectangle kemery Rectangle kemery Rectangle kemery Rectangle kemery Text Box kemery Rectangle kemery Text Box Figure 1B Approximate Sample Locations 1770 21st Street
DN52856.000-221-R1
kemery Text Box 122, 123 kemery Rectangle kemery Text Box # = Asbestos Samples # = Paint Samples # = Roof Samples # = Asbestos Containing Material (>1% Asbestos) # = Trace Asbestos (≤1% Asbestos) kemery Text Box kemery Text Box kemery Text Box kemery Text Box kemery Text Box kemery Text Box kemery Text Box kemery Text Box kemery Text Box kemery Text Box kemery Text Box kemery Text Box kemery Text Box kemery Text Box kemery Text Box kemery Text Box 70 72 kemery Text Box kemery Text Box kemery Text Box kemery Text Box kemery Text Box kemery Text Box kemery Text Box 116, 117 kemery Text Box kemery Text Box kemery Text Box kemery Text Box kemery Text Box 78, 79 kemery Rectangle kemery Rectangle kemery Rectangle kemery Rectangle kemery Rectangle kemery Rectangle kemery Rectangle kemery Rectangle kemery Rectangle kemery Rectangle kemery Rectangle kemery Rectangle kemery Rectangle kemery Rectangle kemery Rectangle kemery Text Box kemery Rectangle kemery Rectangle kemery Rectangle kemery Rectangle kemery Rectangle kemery Rectangle kemery Rectangle kemery Rectangle kemery Rectangle kemery Rectangle kemery Rectangle kemery Rectangle kemery Rectangle kemery Rectangle kemery Rectangle kemery Rectangle kemery Rectangle kemery Rectangle kemery Rectangle kemery Rectangle kemery Rectangle kemery Rectangle kemery Rectangle kemery Rectangle kemery Rectangle kemery Rectangle kemery Rectangle kemery Rectangle kemery Rectangle kemery Rectangle kemery Rectangle kemery Rectangle kemery Rectangle kemery Rectangle kemery Rectangle kemery Rectangle kemery Rectangle kemery Text Box Figure 1C Approximate Sample Locations 1770 21st Street
DN52856.000-221-R1
kemery Rectangle kemery Text Box # = Asbestos Samples # = Paint Samples # = Roof Samples # = Asbestos Containing Material (>1% Asbestos) # = Trace Asbestos (≤1% Asbestos) kemery Text Box kemery Ellipse kemery Ellipse kemery Ellipse
COPPER DOOR BUILDING
1770 21ST STREET
DN52856.000-221-R1
FIGURE 2
FLOOR 1 - TEXTURE ACM LOCATIONS
kemery Polygon kemery Rectangle kemery Rectangle kemery Rectangle kemery Rectangle kemery Rectangle kemery Rectangle kemery
= Popcorn Ceiling & ACM Wall Texture (HA 1-4)
DN52856.000-221-R1
FIGURE 3
FLOOR 2 - TEXTURE ACM LOCATIONS
kemery Polygon kemery Polygon kemery Polygon kemery Rectangle kemery
= Popcorn Ceiling & ACM Wall Texture (HA 1-4)
DN52856.000-221-R1
FIGURE 4
FLOOR 3 - TEXTURE ACM LOCATIONS
kemery Rectangle kemery Text Box = Popcorn Ceiling & ACM Wall Texture (HA 1-4) kemery Polygon kemery Polygon
Polygon
DN52856.000-221-R1
FIGURE 5
FLOOR 1 - FLOORING AND OTHER ACM LOCATIONS
kemery Rectangle kemery Rectangle kemery Rectangle kemery Rectangle kemery Rectangle kemery Rectangle kemery Rectangle kemery Rectangle kemery Rectangle kemery Text Box = 12 x 12 Brown Floor Tile (HA 13) kemery Rectangle kemery Text Box = 12 x 12 Green Floor Tile (HA 12) kemery Rectangle kemery Text Box = 12 x 12 White Floor Tile (HA 26) kemery Text Box = White Shower Tile (HA 15)
Rectangle
DN52856.000-221-R1
FIGURE 6
FLOOR 2 - FLOORING AND OTHER ACM LOCATIONS
kemery Polygon kemery Rectangle kemery Rectangle kemery Rectangle kemery Rectangle kemery Rectangle kemery Rectangle kemery Rectangle kemery Text Box = 12 x 12 Brown Floor Tile (HA 13) kemery Rectangle kemery Text Box = 12 x 12 Green Floor Tile (HA 12) kemery Rectangle kemery
= White Shower Tile (HA 15)
DN52856.000-221-R1
FIGURE 7
FLOOR 3 - FLOORING AND OTHER ACM LOCATIONS
kemery Polygon kemery Rectangle kemery Rectangle kemery Rectangle kemery Rectangle kemery Rectangle kemery Rectangle kemery Rectangle kemery Text Box = 12 x 12 Brown Floor Tile (HA 13) kemery Rectangle kemery Text Box = 12 x 12 Green Floor Tile (HA 12) kemery Rectangle kemery
= White Shower Tile (HA 15)
DN52856.000-221-R1
FIGURE 8
FLOOR 1 - OTHER ACM LOCATIONS
kemery Rectangle kemery Rectangle kemery Rectangle kemery Polygon kemery Rectangle kemery Text Box = Fire Door (HA 18) kemery Rectangle kemery Text Box = Pipe Cement (HA 42) kemery Rectangle kemery Text Box = Black Cove Base (HA 8) kemery Rectangle kemery Rectangle kemery Rectangle kemery Text Box = White Cove Base (HA 7) kemery Rectangle kemery Rectangle kemery Rectangle kemery Rectangle kemery Rectangle kemery Rectangle kemery Rectangle kemery Rectangle kemery Rectangle kemery Rectangle kemery Rectangle kemery Rectangle kemery Rectangle kemery Rectangle kemery Rectangle kemery Rectangle kemery Rectangle kemery Rectangle kemery Rectangle kemery Rectangle kemery Rectangle kemery Rectangle kemery Rectangle kemery Rectangle kemery Rectangle kemery Rectangle kemery Rectangle kemery Rectangle kemery Polygon kemery Polygon kemery Rectangle kemery Rectangle kemery Polygon kemery Rectangle kemery Rectangle kemery Rectangle kemery Rectangle kemery Rectangle kemery Rectangle kemery Rectangle kemery Rectangle kemery Rectangle kemery Rectangle kemery Rectangle kemery Rectangle kemery Rectangle kemery Rectangle kemery Rectangle kemery Rectangle kemery Rectangle kemery Rectangle kemery Rectangle kemery Rectangle kemery Rectangle kemery Rectangle kemery Rectangle kemery Rectangle kemery Rectangle mwardlow Rectangle mwardlow Rectangle mwardlow Rectangle mwardlow Rectangle mwardlow Line mwardlow Text Box mwardlow Line mwardlow Text Box mwardlow Text Box mwardlow Line mwardlow Text Box = Pipe Sealant Beneath Slab (HA 49) mwardlow
DN52856.000-221-
FIGURE 9
FLOOR 2 - OTHER MISC. ACM LOCATIONS
kemery Polygon kemery Polygon kemery Polygon kemery Polygon kemery Polygon kemery Polygon kemery Polygon kemery Polygon kemery Polygon kemery Polygon kemery Polygon kemery Polygon kemery Polygon kemery Polygon kemery Polygon kemery Polygon kemery Polygon kemery Polygon kemery Polygon kemery Polygon kemery Polygon kemery Polygon kemery Polygon kemery Polygon kemery Polygon kemery Polygon kemery Polygon kemery Polygon kemery Polygon kemery Polygon kemery Polygon kemery Polygon kemery Polygon kemery Polygon kemery Polygon kemery Polygon kemery Polygon kemery Polygon kemery Polygon kemery Polygon kemery Polygon kemery Polygon kemery Polygon kemery Polygon kemery Polygon kemery Polygon kemery Polygon kemery Polygon kemery Polygon kemery Polygon kemery Polygon kemery Polygon kemery Polygon kemery Polygon kemery Polygon kemery Polygon kemery Rectangle kemery Rectangle kemery Rectangle kemery Text Box = Fire Door (HA 18) kemery Rectangle kemery Text Box = Black Cove Base (HA 8) kemery Rectangle kemery
= White Cove Base (HA 7)
DN52856.000-221-R
FIGURE 10
FLOOR 3 - OTHER MISC. ACM LOCATIONS
kemery Rectangle kemery Polygon kemery Polygon kemery Polygon kemery Polygon kemery Polygon kemery Polygon kemery Polygon kemery Polygon kemery Polygon kemery Polygon kemery Polygon kemery Polygon kemery Polygon kemery Polygon kemery Polygon kemery Polygon kemery Polygon kemery Polygon kemery Polygon kemery Polygon kemery Polygon kemery Polygon kemery Polygon kemery Polygon kemery Polygon kemery Polygon kemery Polygon kemery Polygon kemery Polygon kemery Polygon kemery Polygon kemery Polygon kemery Polygon kemery Polygon kemery Polygon kemery Polygon kemery Polygon kemery Polygon kemery Polygon kemery Polygon kemery Polygon kemery Polygon kemery Polygon kemery Polygon kemery Polygon kemery Polygon kemery Polygon kemery Rectangle kemery Polygon kemery Polygon kemery Polygon kemery Rectangle kemery Rectangle kemery Rectangle kemery Rectangle kemery Rectangle kemery Rectangle kemery Rectangle kemery Text Box = Fire Door (HA 18) kemery Rectangle kemery Text Box = Black Cove Base (HA 8) kemery Rectangle kemery
= White Cove Base (HA 7)
BOULDER COUNTY OUBLIC WORK
COPPER DOOR FACILITY – 1770 21ST STREET
CTL|T PROJECT NO. DN52856.000-221-R1
APPENDIX A
SITE PHOTOGRAPHS
CTL Project No. DN52856.000-221
Description: General view of the south side of the building
Description: General view of the south side of the building
Description: General view of the exterior of the addition
Description: General view of the north side of the building
Description: Front lobby and security office.
Description: General view of a hallway.
Description: General view of stairwell.
Description: General view of the boiler room.
Description: Example of HA-1, Popcorn Texture.
Description: Example of HA-2, Orange Peel Texture (yellow).
Description: Example of HA-3, Orange Peel Texture (white).
Description: Example of HA-4, Orange Peel Texture (green)..
Description: Example of HA-7, Cove Base w/ mastic (black).
Description: Example of HA-8, Cove Base w/ mastic (white).
Description: Example of HA-9, Joint Compound.
Description: Example of HA-18, Fire Door.
Description: Example of HA-12, Floor Tile (green).
Description: Example of HA-13, Floor Tile (brown).
Description: Example of HA-15, Shower Tile (white).
Description: Example of HA-42, Pipe Dope (white cement).
Description: Inside boiler (to the extent it could be accessed).
Description: Example of HA-49, Pipe Insulation.
Description: Example of popcorn overspray on rafters in attic.
Description: Building envelope, fiberglass insulation.
COPPER DOOR FACILITY – 1770 21ST STREET
CTL|T PROJECT NO. DN52856.000-221-R1
APPENDIX B
ASBESTOS LABORATORY RESULTS AND CHAINS OF CUSTODY
EMSL Analytical, Inc.
1010 Yuma Street Denver, CO 80204
Tel/Fax: (303) 740-5700 / (303) 741-1400 http://www.EMSL.com / denverlab@emsl.com
222601309EMSL Order:
Customer ID: CTLT34
Customer PO:
Project ID:
Attention: Phone:Benjamin Rief (303) 825-0777
Fax:CTL Thompson
Received Date:1971 West 12th Avenue 03/19/2026 9:45 AM
Analysis Date:Denver, CO 80204 03/23/2026 - 03/25/2026
Collected Date: 03/10/2026
Project: Copper Door Facility / DN52856.000-221
Test Report: Asbestos Analysis of Bulk Materials via AHERA Method 40CFR 763 Subpart E
Appendix E supplemented with EPA 600/R-93/116 using Polarized Light Microscopy
Sample Description Appearance % Fibrous % Non-Fibrous
Non-Asbestos Asbestos
% Type
1-TXT-1
222601309-0001
None DetectedCa Carbonate
Non-fibrous (Other)
9%
91%
White
Non-Fibrous
Homogeneous
Popcorn ceiling
(white)
Inseparable paint/coating layer included in analysis.
HA: 1
1-TXT-2
222601309-0002
3% ChrysotileCa Carbonate
Non-fibrous (Other)
11%
86%
White
Non-Fibrous
Homogeneous
Popcorn ceiling
(white)
Inseparable paint/coating layer included in analysis.
HA: 1
1-TXT-3
222601309-0003
3% ChrysotileCa Carbonate
Non-fibrous (Other)
9%
88%
Beige
Non-Fibrous
Homogeneous
Popcorn ceiling
(white)
HA: 1
1-TXT-4
222601309-0004
3% ChrysotileCa Carbonate
Non-fibrous (Other)
10%
87%
Beige
Non-Fibrous
Homogeneous
Popcorn ceiling
(white)
HA: 1
1-TXT-5
222601309-0005
3% ChrysotileCa Carbonate
Non-fibrous (Other)
8%
89%
White
Non-Fibrous
Homogeneous
Popcorn ceiling
(white)
Inseparable paint / coating layer included in analysis
HA: 1
1-TXT-6
222601309-0006
3% ChrysotileCa Carbonate
Non-fibrous (Other)
8%
89%
White
Non-Fibrous
Homogeneous
Popcorn ceiling
(white)
Inseparable paint / coating layer included in analysis
HA: 1
1-TXT-7
222601309-0007
3% ChrysotileCa Carbonate
Non-fibrous (Other)
8%
89%
White
Non-Fibrous
Homogeneous
Popcorn ceiling
(white)
HA: 1
2-TXT-8-Texture
222601309-0008
2% ChrysotileCa Carbonate
Non-fibrous (Other)
6%
92%
White
Non-Fibrous
Heterogeneous
Orange peel texture
(yellow)
Multiple inseparable paint/texture layers analyzed as one.
HA: 2
2-TXT-8-Drywall
222601309-0008A
None DetectedGypsum
Non-fibrous (Other)
58%
30%
Cellulose
Glass
12%
<1%
White
Fibrous
Homogeneous
Orange peel texture
(yellow)
HA: 2
2-TXT-9-Texture
222601309-0009
2% ChrysotileCa Carbonate
Non-fibrous (Other)
6%
92%
White
Non-Fibrous
Heterogeneous
Orange peel texture
(yellow)
HA: 2
2-TXT-9-Drywall
222601309-0009A
None DetectedGypsum
Non-fibrous (Other)
60%
27%
Cellulose
Glass
13%
<1%
White
Fibrous
Homogeneous
Orange peel texture
(yellow)
HA: 2
Initial report from: 03/26/2026 09:49:36
Page 1 of 15ASB_PLM_0008_0002 - 2.31 Printed: 3/26/2026 7:49 AM
Tel/Fax: (303) 740-5700 / (303) 741-1400 http://www.EMSL.com / denverlab@emsl.com
222601309EMSL Order:
Customer ID: CTLT34
Customer PO:
Project ID:
Test Report: Asbestos Analysis of Bulk Materials via AHERA Method 40CFR 763 Subpart E
Appendix E supplemented with EPA 600/R-93/116 using Polarized Light Microscopy
Sample Description Appearance % Fibrous % Non-Fibrous
Non-Asbestos Asbestos
% Type
2-TXT-10-Texture
222601309-0010
3% ChrysotileCa Carbonate
Non-fibrous (Other)
6%
91%
White
Non-Fibrous
Heterogeneous
Orange peel texture
(yellow)
Multiple inseparable paint/texture layers analyzed as one.
HA: 2
2-TXT-10-Drywall
222601309-0010A
None DetectedGypsum
Non-fibrous (Other)
60%
28%
Cellulose
Glass
12%
<1%
Gray/White
Fibrous
Homogeneous
Orange peel texture
(yellow)
HA: 2
2-TXT-11-Texture
222601309-0011
3% ChrysotileCa Carbonate
Non-fibrous (Other)
7%
90%
White
Non-Fibrous
Heterogeneous
Orange peel texture
(yellow)
Multiple inseparable paint/texture layers analyzed as one.
HA: 2
2-TXT-11-Drywall
222601309-0011A
None DetectedGypsum
Non-fibrous (Other)
60%
28%
Cellulose
Glass
12%
<1%
Gray/White
Fibrous
Homogeneous
Orange peel texture
(yellow)
HA: 2
2-TXT-12
222601309-0012
None DetectedNon-fibrous (Other)100%White
Non-Fibrous
Homogeneous
Orange peel texture
(yellow) only paint present
HA: 2
2-TXT-13
222601309-0013
2% ChrysotileCa Carbonate
Non-fibrous (Other)
10%
88%
White
Non-Fibrous
Homogeneous
Orange peel texture
(yellow)
HA: 2
2-TXT-14
222601309-0014
2% ChrysotileCa Carbonate
Non-fibrous (Other)
10%
88%
White
Non-Fibrous
Homogeneous
Orange peel texture
(yellow)
HA: 2
3-TXT-15
222601309-0015
2% ChrysotileNon-fibrous (Other)98%Beige
Non-Fibrous
Heterogeneous
Orange peel texture
(white)
Multiple inseparable paint/texture layers analyzed as one.
HA: 3
3-TXT-16-Texture
222601309-0016
2% ChrysotileCa Carbonate
Non-fibrous (Other)
7%
91%
Beige
Non-Fibrous
Heterogeneous
Orange peel texture
(white)
Multiple inseparable paint/texture layers analyzed as one.
HA: 3
3-TXT-16-Drywall
222601309-0016A
None DetectedGypsum
Non-fibrous (Other)
60%
27%
Cellulose13%White
Fibrous
Homogeneous
Orange peel texture
(white)
HA: 3
3-TXT-17-Texture
222601309-0017
2% ChrysotileCa Carbonate
Non-fibrous (Other)
6%
92%
White
Non-Fibrous
Heterogeneous
Orange peel texture
(white)
Multiple inseparable paint/texture layers analyzed as one.
HA: 3
3-TXT-17-Drywall
222601309-0017A
None DetectedGypsum
Non-fibrous (Other)
60%
29%
Cellulose
Glass
11%
<1%
White
Fibrous
Homogeneous
Orange peel texture
(white)
HA: 3
3-TXT-18-Texture
222601309-0018
2% ChrysotileCa Carbonate
Non-fibrous (Other)
7%
91%
White
Non-Fibrous
Heterogeneous
Orange peel texture
(white)
HA: 3
Page 2 of 15ASB_PLM_0008_0002 - 2.31 Printed: 3/26/2026 7:49 AM
Tel/Fax: (303) 740-5700 / (303) 741-1400 http://www.EMSL.com / denverlab@emsl.com
222601309EMSL Order:
Customer ID: CTLT34
Customer PO:
Project ID:
Test Report: Asbestos Analysis of Bulk Materials via AHERA Method 40CFR 763 Subpart E
Appendix E supplemented with EPA 600/R-93/116 using Polarized Light Microscopy
Sample Description Appearance % Fibrous % Non-Fibrous
Non-Asbestos Asbestos
% Type
3-TXT-18-Drywall
222601309-0018A
None DetectedGypsum
Non-fibrous (Other)
60%
30%
Cellulose
Glass
10%
<1%
White
Fibrous
Homogeneous
Orange peel texture
(white)
HA: 3
3-TXT-19-Texture
222601309-0019
None DetectedCa Carbonate
Non-fibrous (Other)
10%
90%
White
Non-Fibrous
Homogeneous
Orange peel texture
(white)
HA: 3
3-TXT-19-Drywall
222601309-0019A
None DetectedGypsum
Non-fibrous (Other)
60%
30%
Cellulose10%White
Fibrous
Heterogeneous
Orange peel texture
(white)
HA: 3
3-TXT-20-Texture
222601309-0020
2% ChrysotileCa Carbonate
Non-fibrous (Other)
10%
88%
White
Non-Fibrous
Homogeneous
Orange peel texture
(white)
HA: 3
3-TXT-20-Drywall
222601309-0020A
None DetectedGypsum
Non-fibrous (Other)
60%
30%
Cellulose10%White
Fibrous
Heterogeneous
Orange peel texture
(white)
HA: 3
3-TXT-21-Texture
222601309-0021
2% ChrysotileCa Carbonate
Non-fibrous (Other)
10%
88%
White
Non-Fibrous
Homogeneous
Orange peel texture
(white)
Inseparable paint / coating layer included in analysis
HA: 3
3-TXT-21-Drywall
222601309-0021A
None DetectedGypsum
Non-fibrous (Other)
60%
30%
Cellulose
Glass
10%
<1%
White
Fibrous
Heterogeneous
Orange peel texture
(white)
HA: 3
4-TXT-22
222601309-0022
2% ChrysotileCa Carbonate
Non-fibrous (Other)
7%
91%
White
Non-Fibrous
Heterogeneous
Orange peel texture
(green)
HA: 4
4-TXT-23
222601309-0023
2% ChrysotileCa Carbonate
Non-fibrous (Other)
6%
92%
White
Non-Fibrous
Heterogeneous
Orange peel texture
(green)
Multiple inseparable paint/texture layers analyzed as one.
HA: 4
4-TXT-24-Texture
222601309-0024
None DetectedCa Carbonate
Non-fibrous (Other)
10%
90%
White
Non-Fibrous
Homogeneous
Orange peel texture
(green)
Inseparable paint / coating layer included in analysis
HA: 4
4-TXT-24-Drywall
222601309-0024A
None DetectedGypsum
Non-fibrous (Other)
60%
30%
Cellulose10%Pink/Beige
Fibrous
Heterogeneous
Orange peel texture
(green)
HA: 4
5-CB-25
222601309-0025
None DetectedNon-fibrous (Other)100%Beige
Non-Fibrous
Homogeneous
Cove base w/ adhesive (gray)
No cove base present-adhesive analyzed.
HA: 5
5-CB-26
222601309-0026
None DetectedNon-fibrous (Other)100%Beige
Non-Fibrous
Homogeneous
Cove base w/ adhesive (gray) only adhesive present
HA: 5
Page 3 of 15ASB_PLM_0008_0002 - 2.31 Printed: 3/26/2026 7:49 AM
Tel/Fax: (303) 740-5700 / (303) 741-1400 http://www.EMSL.com / denverlab@emsl.com
222601309EMSL Order:
Customer ID: CTLT34
Customer PO:
Project ID:
Test Report: Asbestos Analysis of Bulk Materials via AHERA Method 40CFR 763 Subpart E
Appendix E supplemented with EPA 600/R-93/116 using Polarized Light Microscopy
Sample Description Appearance % Fibrous % Non-Fibrous
Non-Asbestos Asbestos
% Type
6-CB-27-Cove Base
222601309-0027
None DetectedNon-fibrous (Other)100%Green/Beige
Non-Fibrous
Homogeneous
Cove base w/ adhesive (green)
HA: 6
6-CB-27-Adhesive
222601309-0027A
None DetectedNon-fibrous (Other)100%Brown
Non-Fibrous
Homogeneous
Cove base w/ adhesive (green)
HA: 6
6-CB-28-Cove Base
222601309-0028
None DetectedNon-fibrous (Other)100%Green
Non-Fibrous
Homogeneous
Cove base w/ adhesive (green)
HA: 6
6-CB-28-Mastic
222601309-0028A
None DetectedNon-fibrous (Other)98%Wollastonite2%Brown
Non-Fibrous
Homogeneous
Cove base w/ adhesive (green)
HA: 6
7-CB-29-Cove Base
222601309-0029
None DetectedNon-fibrous (Other)100%Black
Non-Fibrous
Homogeneous
Cove base w/ adhesive (black)
HA: 7
7-CB-29-Adhesive
222601309-0029A
None DetectedNon-fibrous (Other)100%Yellow
Non-Fibrous
Homogeneous
Cove base w/ adhesive (black)
Inseparable mud layer included in analysis.
HA: 7
7-CB-30-Mastic
222601309-0030
None DetectedNon-fibrous (Other)100%Tan
Non-Fibrous
Homogeneous
Cove base w/ adhesive (black) no cove base present
HA: 7
7-CB-30-Mud
222601309-0030A
2% ChrysotileCa Carbonate
Non-fibrous (Other)
8%
90%
White
Non-Fibrous
Homogeneous
Cove base w/ adhesive (black)
HA: 7
8-CB-31-Cove Base
222601309-0031
None DetectedNon-fibrous (Other)100%White
Non-Fibrous
Homogeneous
Cove base w/ adhesive (white)
HA: 8
8-CB-31-Adhesive
222601309-0031A
None DetectedNon-fibrous (Other)100%Yellow
Non-Fibrous
Heterogeneous
Cove base w/ adhesive (white)
Inseparable paint and mud layers included in analysis.
HA: 8
8-CB-32-Cove Base
222601309-0032
None DetectedNon-fibrous (Other)100%White
Non-Fibrous
Homogeneous
Cove base w/ adhesive (white)
HA: 8
8-CB-32-Mastic
222601309-0032A
None DetectedNon-fibrous (Other)100%Tan/Beige
Non-Fibrous
Homogeneous
Cove base w/ adhesive (white)
HA: 8
8-CB-32-Mud
222601309-0032B
2% ChrysotileCa Carbonate
Non-fibrous (Other)
6%
92%
White
Non-Fibrous
Homogeneous
Cove base w/ adhesive (white)
Inseparable paint / coating layer included in analysis
HA: 8
9-JC-33
222601309-0033
None DetectedGypsum
Non-fibrous (Other)
60%
25%
Cellulose15%Gray
Fibrous
Homogeneous
Joint compound
Page 4 of 15ASB_PLM_0008_0002 - 2.31 Printed: 3/26/2026 7:49 AM
Tel/Fax: (303) 740-5700 / (303) 741-1400 http://www.EMSL.com / denverlab@emsl.com
222601309EMSL Order:
Customer ID: CTLT34
Customer PO:
Project ID:
Test Report: Asbestos Analysis of Bulk Materials via AHERA Method 40CFR 763 Subpart E
Appendix E supplemented with EPA 600/R-93/116 using Polarized Light Microscopy
Sample Description Appearance % Fibrous % Non-Fibrous
Non-Asbestos Asbestos
% Type
No joint compound present-drywall analyzed.
HA: 9
9-JC-34-Joint
Compound
222601309-0034
2% ChrysotileCa Carbonate
Non-fibrous (Other)
10%
88%
White
Non-Fibrous
Homogeneous
Joint compound
Inseparable paint / coating layer included in analysis
HA: 9
9-JC-34-Tape
222601309-0034A
None DetectedNon-fibrous (Other)3%Cellulose97%White/Beige
Fibrous
Homogeneous
Joint compound
HA: 9
10-T-35-Floor Tile
222601309-0035
None DetectedNon-fibrous (Other)100%Beige
Non-Fibrous
Homogeneous
Laminate tile 12x12
(off white)
HA: 10
10-T-35-Adhesive
222601309-0035A
None DetectedNon-fibrous (Other)100%Gray/Yellow
Non-Fibrous
Heterogeneous
Laminate tile 12x12
(off white)
Adhesive and leveler are inseparable and were analyzed as one.
HA: 10
10-T-36-Floor Tile
222601309-0036
None DetectedNon-fibrous (Other)100%White
Non-Fibrous
Homogeneous
Laminate tile 12x12
(off white)
HA: 10
10-T-36-Adhesive
222601309-0036A
None DetectedNon-fibrous (Other)100%Brown/Tan
Non-Fibrous
Homogeneous
Laminate tile 12x12
(off white)
HA: 10
10-T-36-Leveler
222601309-0036B
None DetectedNon-fibrous (Other)100%Gray
Non-Fibrous
Homogeneous
Laminate tile 12x12
(off white)
HA: 10
11-T-37-Floor Tile
222601309-0037
None DetectedNon-fibrous (Other)100%Gray
Non-Fibrous
Homogeneous
Laminate tile 12x12
(light gray)
HA: 11
11-T-37-Adhesive
222601309-0037A
None DetectedNon-fibrous (Other)100%Gray/Yellow
Non-Fibrous
Heterogeneous
Laminate tile 12x12
(light gray)
Adhesive and leveler are inseparable and were analyzed as one.
HA: 11
11-T-38-Floor Tile
222601309-0038
None DetectedNon-fibrous (Other)100%Gray
Non-Fibrous
Homogeneous
Laminate tile 12x12
(light gray)
HA: 11
11-T-38-Adhesive
222601309-0038A
None DetectedNon-fibrous (Other)100%Brown/Tan
Non-Fibrous
Homogeneous
Laminate tile 12x12
(light gray)
HA: 11
11-T-38-Leveler
222601309-0038B
None DetectedCa Carbonate
Non-fibrous (Other)
4%
96%
Gray
Non-Fibrous
Homogeneous
Laminate tile 12x12
(light gray)
Result includes a small amount of inseparable attached material
HA: 11
12-T-39-Floor Tile
222601309-0039
5% ChrysotileNon-fibrous (Other)95%Beige
Non-Fibrous
Homogeneous
Laminate tile 12x12
(green)
HA: 12
Page 5 of 15ASB_PLM_0008_0002 - 2.31 Printed: 3/26/2026 7:49 AM
Tel/Fax: (303) 740-5700 / (303) 741-1400 http://www.EMSL.com / denverlab@emsl.com
222601309EMSL Order:
Customer ID: CTLT34
Customer PO:
Project ID:
Test Report: Asbestos Analysis of Bulk Materials via AHERA Method 40CFR 763 Subpart E
Appendix E supplemented with EPA 600/R-93/116 using Polarized Light Microscopy
Sample Description Appearance % Fibrous % Non-Fibrous
Non-Asbestos Asbestos
% Type
12-T-39-Mastic
222601309-0039A
4% ChrysotileNon-fibrous (Other)96%Black
Non-Fibrous
Homogeneous
Laminate tile 12x12
(green)
HA: 12
12-T-39-Leveler
222601309-0039B
None DetectedCa Carbonate
Non-fibrous (Other)
5%
95%
Tan
Non-Fibrous
Homogeneous
Laminate tile 12x12
(green)
HA: 12
12-T-40-Tile
222601309-0040
4% ChrysotileNon-fibrous (Other)96%Green
Non-Fibrous
Homogeneous
Laminate tile 12x12
(green)
HA: 12
12-T-40-Mastic
222601309-0040A
5% ChrysotileNon-fibrous (Other)95%Black
Non-Fibrous
Homogeneous
Laminate tile 12x12
(green)
HA: 12
13-T-41-Floor Tile
222601309-0041
5% ChrysotileNon-fibrous (Other)95%Beige
Non-Fibrous
Homogeneous
Laminate tile 12x12
(brown)
HA: 13
13-T-41-Mastic
222601309-0041A
5% ChrysotileNon-fibrous (Other)95%Black
Non-Fibrous
Homogeneous
Laminate tile 12x12
(brown)
HA: 13
13-T-41-Leveler
222601309-0041B
None DetectedCa Carbonate
Non-fibrous (Other)
3%
97%
Tan
Non-Fibrous
Homogeneous
Laminate tile 12x12
(brown)
HA: 13
13-T-42-Tile
222601309-0042
5% ChrysotileNon-fibrous (Other)95%Brown/Beige
Non-Fibrous
Homogeneous
Laminate tile 12x12
(brown)
HA: 13
13-T-42-Mastic
222601309-0042A
7%…