This document consists of approved plans for a construction project managed by the Division of Facilities Construction and Management (DFCM) for the Utah State Hospital, a facility under the Department of Health & Human Services. The project involves the replacement of existing unit heaters at the Warehouse facility, identified as Project #27135420. This Stage II Invitation to Bid is restricted to contractors who have been prequalified under DFCM's Stage I Prequalification process and currently appear on the respective prequalified contractors list as of the solicitation date. The approved plans document provides the technical specifications and design requirements necessary for contractors to prepare accurate bids for the heating equipment replacement work.
The construction cost estimate for this project is $25,000.00. As a prequalified Stage II bidding opportunity, only eligible contractors meeting DFCM's prequalification criteria are permitted to submit bids. The approved plans serve as the binding technical documentation that contractors must use to scope, estimate, and execute the warehouse unit heater replacement project in compliance with state standards and requirements.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
PROVO, UTAH
C001
COVER SHEET
DFCM Project No. 27135420
CONSTRUCTION DOCUMENTS
Vicinity Map
SHEET INDEX
USH - WAREHOUSE UNIT
PROJECT SITE
PROVO, UTAH
NORTH
CONSULTANTS
North: ______ South: ______ East: ______ West: ______
Special Use and Occupancy (e.g. High Rise, Covered Mall): __________________
d) Unlimited Area Building: Yes ______ No ______ Code Section: ______ a a
3) Three Story: A (3)______
2) Two Story: A (2)________
1) One Story: ______
c) Total Allowable Area for:
N/A (NON-SEPARATED OCCUPANCIES)
b) Sum of the Ratio Calculations for Mixed Occupancies:
a) 0.25I = 100f F P 30
WstA I 100100 fIA t taA = A + +
Official for Complex Buildings. Including, but not limited to:
g) Fire Stopping, Including Tested Design Number.
f) Exterior and Interior Accessibility Route.
e) Fire Assembly Locator Sheet.
a) High Rise Requirements.
b) Atriums.
c) Performance Based Criteria.
d) Means or Egress Analysis.
2) Additional Code Information shall be provided at the discretion of the Building
Code Accessibility Chapters, the more restrictive requirement shall govern.
through - ADA Guidelines and specific reference to the International Building
1) In case of conflict with the U.S. Department of Justice Federal Registers Parts
FOOTNOTES:
d) Drinking Fountains: ______ Service Sinks: ______
c) Bath Tubs or Showers: ______
b) Lavatories - Required (m) ______ (f) ______ Provided (m) ______ (f) ______
a) Water Closets - Required (m) ______ (f) ______ Provided (m) ______ (f) _____
M. Minimum Number of Required Plumbing Facilities:
Exit Width Required: ______ Exit Width Provided: ______
Element Hours Assembly ListingListing
Element AssemblyHours
Smoke Partitions Fire Partitions
Exterior Bearing Walls Interior Bearing Walls Exterior Non-Bearing Walls Structural Frame Partitions - Permanent Fire Barriers
Floors - Ceiling Floors Roofs - Ceiling Roofs Exterior Doors and Windows Shaft Enclosures Fire Walls
BAHTBABABA
Design Wind Speed: ______ mphB. Seismic Design Category: ______
L. Design Occupant Load: ______
K. Fire Resistance Rating Requirements for Building Elements (hours).
Area Modifications:J:
_____________________________________________________Tabular Area:I:
per Floor (square feet): _________________________________________Actual AreaH:
Number of Stories: ______ Building Height: ___________G:
Required: ______ Provided: _________ Type of Sprinkler System: __________
Sprinklers:F:
Mixed Occupancies: ______ Nonseparated Uses: ______E.
separation distance (in hours):
Requirements for the Exterior Walls based on the fireFire Resistance RatingD.
C. Type of Construction (circle one):
Change in Use: Yes ______ No ______ Mixed Occupancy: Yes ______ No ______
Guildelines ADA Accessibility Building Conservation Uniform Code for National Electrical Code
Conservation Code International Energy International Fire Code International Plumbing Code International Mechanical Code International Building Code
YearYear
APPLICABLE CODES
A. Occupancy and Group: _______ ________ ________ ________ ________
CODE ANALYSIS
N
N N
S-1
X X
NO
90D
NR NR NR NR
NO
YES YES NFPA 13
1 24' - 0"
11,925
N/A
3) Deferred Submittals:
a) Seismic Bracing for Mechanical and Electrical. Work related to the deferred
N/A
N/AX
17,500 submittals shall not commence until the building official has approved the submittal.
17,500 N/A N/A
20241300 East Center Street Provo, Utah 84603
HEATERS REPLACEMENT
07/16/2026
260447
JB
REVISIONS
SHEET CONTENTS
RESOLUT PROJECT #:
CHECKED BY:
DRAWN BY:
CURRENT/ISSUE DATE:A
B
C
D
E
1 2 3 4 5 6
U
SH
W
A R
EH
O
U
SE
U N
IT
H
EA
TE
R S
R
EP
LA
C
EM
EN
T
E as t C en te r S tre et P ro vo
, U ta h
181 East 5600 South Murray, UT 84107
801.530.3148 T
801.530.3150 F
181 E 5600 S, Murray, UT 84107 | (801) 530-3148 info@resolutgroup.com | resolutgroup.com
Project #: 260447
DFCM APPROVAL STAMP
No. 8325442-2202
JACOB D.
BECK
07-16-26
JD
NO
72"
DIVISION OF FACILITIES
CONSTRUCTION AND
MANAGEMENT
Jason Van Ausdal
09/03/2026
REVIEWED FOR CODE
COMPLIANCE
LEGEND OF MECHANICAL SYMBOLS AND ABBREVIATIONS
MECHANICAL PLUMBING PLUMBING CONT. LINETYPES LINETYPES CONT.
SYMBOLS
FIRE
M001
JD
MECHANICAL
SYMBOLS AND
ABBREVIATIONS
07/16/2026
260447
JB
REVISIONS
SHEET CONTENTS
RESOLUT PROJECT #:
CHECKED BY:
DRAWN BY:
CURRENT/ISSUE DATE:A
B
C
D
E
1 2 3 4 5 6
U
SH
W
A R
EH
O
U
SE
U N
IT
H
EA
TE
R S
R
EP
LA
C
EM
EN
T
E as t C en te r S tre et P ro vo
, U ta h
181 East 5600 South Murray, UT 84107
801.530.3148 T
801.530.3150 F
181 E 5600 S, Murray, UT 84107 | (801) 530-3148 info@resolutgroup.com | resolutgroup.com
Project #: 260447
DFCM APPROVAL STAMP
No. 8325442-2202
JACOB D.
BECK
07-16-26
JD
DIVISION OF FACILITIES
CONSTRUCTION AND
MANAGEMENT
Jason Van Ausdal
09/03/2026
T
T
T
(E) G"
(E) G"
(E) G"
UH
UH
UH
T
T
T
M501
TYP.
(E) G"
(E) G"
(E) G"
3/4"
3/4"
3/4"
M101
LEVEL 1
MECHANICAL PLANS
07/16/2026
260447
JB
REVISIONS
SHEET CONTENTS
RESOLUT PROJECT #:
CHECKED BY:
DRAWN BY:
CURRENT/ISSUE DATE:A
B
C
D
E
1 2 3 4 5 6
U
SH
W
A R
EH
O
U
SE
U N
IT
H
EA
TE
R S
R
EP
LA
C
EM
EN
T
E as t C en te r S tre et P ro vo
, U ta h
181 East 5600 South Murray, UT 84107
801.530.3148 T
801.530.3150 F
181 E 5600 S, Murray, UT 84107 | (801) 530-3148 info@resolutgroup.com | resolutgroup.com
Project #: 260447
DFCM APPROVAL STAMP
No. 8325442-2202
JACOB D.
BECK
07-16-26
JD
KEYED NOTES#
1. DEMOLISH AND REMOVE EXISTING UNIT HEATER, THERMOSTAT
AND ASSOCIATED FLUES.
2. CONNECT TO EXISTING GAS PIPING. FIELD VERIFY EXISTING
CONDITIONS.
3. PROVIDE AND INSTALL THERMOSTAT. TYPICAL.
4. PROVIDE AND INSTALL NEW FLUE THROUGH ROOF. INSTALL
PER MANUFACTURERS RECOMMENDATIONS. FLASH AND SEAL
ROOF PENETRATION TO MATCH EXISTING. FIELD VERIFY.
DIVISION OF FACILITIES
CONSTRUCTION AND
MANAGEMENT
Jason Van Ausdal
09/03/2026
M501
JD
MECHANICAL
DETAILS &
SCHEDULES
07/16/2026
260447
JB
REVISIONS
SHEET CONTENTS
RESOLUT PROJECT #:
CHECKED BY:
DRAWN BY:
CURRENT/ISSUE DATE:A
B
C
D
E
1 2 3 4 5 6
U
SH
W
A R
EH
O
U
SE
U N
IT
H
EA
TE
R S
R
EP
LA
C
EM
EN
T
E as t C en te r S tre et P ro vo
, U ta h
181 East 5600 South Murray, UT 84107
801.530.3148 T
801.530.3150 F
181 E 5600 S, Murray, UT 84107 | (801) 530-3148 info@resolutgroup.com | resolutgroup.com
Project #: 260447
DFCM APPROVAL STAMP
No. 8325442-2202
JACOB D.
BECK
07-16-26
JD
FUEL FIRED UNIT HEATER SCHEDULE
ELECTRICAL
INPUT OUTPUT
MANUFACTURER FLUE AIRFLOW HEATING HEATING MOTOR MOTOR
AND SIZE RATE LOAD LOAD SIZE SPEED TOTAL
ID MODEL NUMBER LOCATION TYPE (IN) (CFM) (MBH) (BTU/H) (HP) (RPM) AMPS VOLT/PH/HZ NOTES
UH-1 MODINE PDP-200 SEE PLANS NATURAL GAS 7 2870 200 140 1/6 1750 5.1 115/1/60 1, 2
1. GAS HEATING INPUT AT SEA LEVEL, ALL OTHER CAPACITIES AT ELEVATION.
2. SEALED COMBUSTION.
DIVISION OF FACILITIES
CONSTRUCTION AND
MANAGEMENT
Jason Van Ausdal
09/03/2026
EV EV
DO
TV
J
FB PT
J
X##
TC
CR
D
F
M
VFD
XX
POWER SYMBOLS LEGEND
SYMBOL DEVICE/FIXTURE DESCRIPTION MOUNTING NOTES
S
WALL MOUNTED RECEPTACLE
SWITCHED RECEPTACLE
EMERGENCY RECEPTACLE
GROUND FAULT RECEPTACLE
RECEPTACLE MODIFIERS:
##": HEIGHT AFF O.C.
WP: WEATHERPROOF W/ IN-USE COVER
T: TAMPER-PROOF
U: RECEPTACLE WITH USB OUTLET
G: GROUND FAULT PROTECTED @ BREAKER
H: HOSPITAL GRADE
18"
18"
D Q SP
18"
18"
RECEPTACLE (SPECIFIC HEIGHT)
ISOLATED GROUND RECEPTACLE
7, 25, 30
7, 8
18"
SWITCH MODIFIERS:
K: KEYED
T: TIMER
M: MANUAL STARTER THERMAL
OVERLOAD SWITCH
EMERGENCY POWER OFF PUSH BUTTON
DOOR OPENER PUSH PLATE
ELECTRICAL POWER METER
FUSED DISCONNECT SWITCH
TOMBSTONE RECEPTACLE
CORD REEL, DEVICE VARIES
CORD DROP, DEVICE VARIES
MULTI-OUTLET ASSEMBLY
FILLED SQUARES INDICATE 120V OUTLET
OPEN SQUARES INDICATE WITH USB
SINGLE / DUAL PORT ELECTRICAL VEHICLE
CHARGER
POWER POLE
NON-FUSED DISCONNECT SWITCH
MAGNETIC STARTER
MAGNETIC STARTER WITH FUSED DISCONNECT
PUSHBUTTON
VARIABLE FREQUENCY DRIVE
TRANSFORMER:
SEE SINGLE-LINE DIAGRAM FOR DESCRIPTION &
REQUIREMENTS.
GENERAL LEGEND
SYMBOL DESCRIPTION NOTES
SOLID ARCHED LINES INDICATE UNSWITCHED
POWER CIRCUITING
DASHED ARCHED LINES INDICATE SWITCHED
POWER CIRCUITING
ONE CIRCUIT, HOME RUN TO PANEL
SYMBOL DEVICE/FIXTURE DESCRIPTION MOUNTING NOTES
4" CONCRETE
BASE
POWER DISTRIBUTION PANEL 6'-6" TO TOP
FLUSH PANELBOARD 6'-6" TO TOP
SURFACE PANELBOARD 6'-6" TO TOP
TWO CIRCUITS, HOME RUN TO PANEL -
THREE CIRCUITS, HOME RUN TO PANEL -
CONDUIT RUN CONCEALED IN FLOOR OR GROUND -
CONDUIT RUN CONCEALED IN WALL OR CEILING -
CONDUIT UP -
CONDUIT DOWN -
CONDUIT STUB LOCATION CAP CONDUIT
CONDUIT / CIRCUIT CONTINUATION -
GROUND BUS BAR
CABLE TRAY
SOLID BOTTOM
LADDER
BASKET
MOUNTING
AS NOTED
7+18"
EQUIPMENT CEILING RACK
EQUIPMENT CABINET/RACK
EQUIPMENT 2-POST CABINET/RACK
TELEPHONE DEMARCATION BOARD +18"
FLOOR 18,
SEE SPEC.
WALL / FLOOR 18,
SEE SPEC.
CEILING
EXISTING --
DEMO --
TEMPORARY --
NEW --
CONDUIT
OHP: OVERHEAD POWER SERVICE
UGP: UNDERGROUND POWER
SERVICE
UGF: UNDERGROUND FIBER
SERVICE
TEL: TELEPHONE SERVICE
POWER DISTRIBUTION EQUIPMENT SYMBOLS
CONTROLLED RECEPTACLE 7, 8+18" OR AS
NOTED
SPD PROTECTED RECEPTACLE 7+18" OR AS
NOTED
TIME CLOCK +48"
NOT IN CONTRACT --
MAGNETIC STARTER WITH BREAKER DISCONNECT
CEILING MOUNTED RECEPTACLE CEILING
TV BACKBOX FLAT PANEL
HEIGHT +12"
NOTES:
1. HATCHED FILL INDICATES SWITCHBOARD OR POWER
DISTRIBUTION PANEL.
2. SOLID FILL INDICATES BRANCH PANEL OR LOAD CENTER.
3. DASHED BOX INDICATES CODE-REQUIRED CLEARANCE
(WIDTH & DEPTH).
4. DOOR INDICATES FRONT OF RECESSED PANEL.
H P
1A
LP
1A
M D
P
SB1
POWER TAGS LEGEND
GENERAL LEGEND
SYMBOL DESCRIPTION NOTESMOUNTING
KEYNOTE
ROOM NAME & NUMBER
DIAGRAM TAG
MATCH LINE TAG
ROOM NAME & NUMBER W/ ZONE I.D.
JUNCTION BOX
x
S: SIMPLEX D: DUPLEX
Q: FOURPLEX SP: SPECIAL PURPOSE
FLOOR BOX / POKE-THRU
- SEE SCHEDULE FOR TYPE INFORMATION
EQUIPMENT SYSTEM PANELS
ACS: ACCESS CONTROL PANEL
ATS: AUTOMATIC TRANSFER SWITCH
IDS: INTRUSION DETECTION PANEL
PSP: POWER SUPPLY PANEL
RP#: LIGHTING PANEL
DAS: DISTRIBUTED ANTENNA SYSTEM
ERCCS: FIRST RESPONDERS RADIO SYSTEM
CATV: CABLE TV CONTENT EQUIPMENT
7, 8, 13
CEILING
CEILING
+46"OR AS
NOTED
7, REFER TO
SPEC
+46" 7
+46" 7
9, 10
9, 10, 11
+72" TO TOP
+60" TO TOP
18, SEE SPEC.
7, 22
Space
Space
XX
DEVICES WITH A CHEVRON INDICATE TO
COORDINATE WITH MILLWORK PRIOR TO ROUGH-IN.
ELEVATION TAG. HATCHED AREA INDICATES
WHICH WALL, NUMBER INDICATES VIEW, AND
CENTER NUMBER INDICATES WHICH SHEET.
REVISION CLOUD DELTA. SHOWN WITH CLOUD
AND INDICATES A CHANGE PER THE TITLE BLOCK.
TAG FOR MECHANICAL, KITCHEN, AND SHOP
DEVICES. REFER TO SCHEDULES FOR INFO.
9, 10, 11
9, 10, 11
+46" 7
9, 10
+46" 7
+60" TO TOP
+60" TO TOP
+60" TO TOP
+60" TO TOP
+60" TO TOP 9, 10, 11
+60" TO TOP
FLOOR
AS NOTED 20
25, 30
+46" 7
COUNTER TOP
MATCH LINE
SEE -/---
32" OR AS
INDICATED
L I C
E N
S E D
P
ROFESS IONA
L
E N
G I N
E E
R
14275529
S
T A
T E OF U
TA
H
SANG TRUONG
No.
Project #: 260447
DFCM APPROVAL STAMP
181 East 5600 South Murray, UT 84107
801.530.3148 T
801.530.3150 F
A
B
C
D
E
1 2 3 4 5 6
07/16/2026
260447
ST
REVISIONS
SHEET CONTENTS
RESOLUT PROJECT #:
CHECKED BY:
DRAWN BY:
CURRENT/ISSUE DATE:
Resolut Group, 2025
Original drawings remain the property of the Engineer and as such the Engineer retains total ownership and control. The design represented by these drawings are sold to the client for a one time use, unless otherwise agreed upon in writing by the
Engineer.
C
U S
H
W A
R E
H O
U S
E U
N
IT
H E
A T
E R
S R
E P
L A
C E
M E
N T
E a s t
C e n te r S tr e e t
P ro v o
U ta h
SE
ELECTRICAL TITLE
SHEET
E001
ELECTRICAL ABBREVIATIONS INDEX
ABBREV. DESCRIPTION
A AMPS
AC ALTERNATING CURRENT
ACLG ABOVE CEILING
ADC ANALOG-TO-DIGITAL
CONVERTER
AF AMP FRAME
AFC AVAILABLE FAULT CURRENT
AFCI ARC FAULT CIRCUIT
INTERRUPTER
AFF / A.F.F. ABOVE FINISH FLOOR
AFG ABOVE FINISHED GRADE
AHU AIR HANDLING UNIT
AIC AMPS INTERRUPTING CAPACITY
AL ALUMINUM
ALT ALTERNATE
AM AMPS METER
AMP AMPERE
AMPL AMPLIFIER
ANN ANNUNCIATOR
AOE AUDIO-OVER-ETHERNET
APPROX APPROXIMATELY
AQ-STAT AQUASTAT
ARCH ARCHITECT, ARCHITECTURAL
AS AMP SWITCH
AT AMP TRIP
ATS AUTOMATIC TRANSFER SWITCH
AUTO AUTOMATIC
AUX AUXILIARY
AV AUDIOVISUAL
AWG AMERICAN WIRE GAUGE
BATT BATTERY
BC BARE COPPER
BD BOARD
BFC BELOW FINISHED CEILING
BFG BELOW FINISHED GRADE
BLDG BUILDING
BMS BUILDING MANAGEMENT
SYSTEM
BPM BEATS-PER-MINUTE
C, CND CONDUIT
C.O. CONDUIT ONLY
C/W COMPLETE WITH
CAB CABINET
CAT CATEGORY CABLE
CAT# CATALOG
CATB COMMUNITY ANTENNA
TELEVISION
CATV CABLE TELEVISION
CB CIRCUIT BREAKER
CCTV CLOSED CIRCUIT TELEVISION
CF CREST FACTOR
CKT CIRCUIT
CLG CEILING
CMPR COMPRESSOR
CNTR CONTRACTOR
CO CONDUIT ONLY
CODEC CODER-DECORDER
COMB COMBINATION
CONN CONNECTION
CONST CONSTRUCTION
CONT CONTINUATION OR CONTINUOUS
CONV CONVECTOR
CP CIRCULATING PUMP
CRT COMPUTER TERMINAL
CT CURRENT TRANSFORMER
CU COPPER
CV CONSTANT VOLTAGE
DAC DIGITAL-TO-ANALOG
CONVERTER
DB DECIBEL
DBFS DB REF. FULL SCALE
DBM DB REF. 0.001 WATT
DBU DB REF. 0.775 V
DBV DB REF. 1 V
DC DIRECT CURRENT
DCP DOMESTIC CIRCULATING PUMP
DED DEDICATED
DEPT DEPARTMENT
DET DETAIL
DFA DROP FROM ABOVE
DIA DIAMETER
DISC DISCONNECT
DIST DISTRIBUTION
DN DOWN
DPR DAMPER
DR DYNAMIC RANGE
DS DISCONNECT SWITCH
DT DOUBLE THROW
DWG DRAWING
E EXISTING TO REMAIN
EC ELECTRICAL CONTRACTOR
EF EXHAUST FAN
EG EMERGENCY GENERATOR
ELEC ELECTRIC, ELECTRICAL
ELEV ELEVATOR
ELU EMERGENCY LIGHTING UNIT
EM EMERGENCY/EGRESS BATTERY
EMI ELECTRO-MAGNETIC
INTERFERENCE
EMS ENERGY MANAGEMENT SYSTEM
EMT ELECTRICAL METALLIC TUBING
EN EXISTING TO BE REPLACED
WITH NEW
ENT ELEC. NON-METAL. TUBING
EP ELECTRIC PNEUMATIC
EQUIP EQUIPMENT
ER EXISTING TO BE RELOCATED
ES SOURCE VOLTAGE
EWC ELECTRIC WATER COOLER
EX EXISTING TO BE REMOVED AND
OFFERED UP TO THE OWNER
FOR FIRST RIGHTS OF REFUSAL.
PROPERLY AND LEGALLY
DISPOSE OF MATERIAL IF
REFUSED
FA FIRE ALARM
FABP FIRE ALARM BOOSTER PANEL
FACP FIRE ALARM CONTROL PANEL
FC FOOT CANDLE
FCU FAN COIL UNIT
FIR FINITE IMPULSE RESPONSE
FILTER
FIXT FIXTURE
FLR FLOOR
FLUOR FLUORESCENT
FMC FLEXIBLE METAL CONDUIT
FU FUSE
FUDS FUSE SAFETY DISCONNECT
SWITCH
GA GAUGE
GAL GALLON
GALV GALVANIZED
GC GENERAL CONTRACTOR
ABBREV. DESCRIPTION
GEC GRND. ELEC. COND. AT SES
GEN GENERATOR
GFCI GROUND FAULT CURRENT
INTERRUPTER
GFI GROUND FAULT INTERRUPTER
GFP GROUND FAULT PROTECTOR
GND GROUND
GRC GALVANIZED RIGID CONDUIT
GYP BD GYPSUM BOARD
HOA HAND-OFF-AUTOMATIC SWITCH
HORIZ HORIZONTAL
HP HORSE POWER
HPF HIGH POWER FACTOR
HT HEIGHT
HTG HEATING
HTR HEATER
HV HIGH VOLTAGE
HVAC HEATING, VENTILATING & AIR
CONDITIONING
HZ HERTZ
I/W INTERLOCK WITH
IC INTERRUPTING CAPACITY
IFC INTERNATIONAL FIRE CODE
IG ISOLATED GROUND
IIR INFINITE IMPULSE RESPONSE
FILTER
IMC INTERMEDIATE METALLIC
CONDUIT
INCAND INCANDESCENT
IR INFRARED
IT TOTAL CURRENT
J-BOX JUNCTION BOX
KCMIL 1000 CIRCULAR MILS (MCM)
KHZ THOUSANDS OF HZ
KV KILOVOLT
KVA KILOVOLT AMPERES
KVAR KILOVARS
KW KILOWATT
KWH KILOWATT HOUR
LCS C-WEIGHTED SLOW SOUND
LEVEL
LEQ EQUIVALENT SOUND LEVEL
LFMC LIQUID-TIGHT FLEX.
METAL. COND.
LFNC LIQUID-TIGHT FLEX. NON-METAL.
COND.
LOC LOCATE OR LOCATION
LP, SPL SOUND PRESSURE LEVEL
LRA LOCKED ROTOR AMPS
LT LIGHT
LTG LIGHTING
LTNG LIGHTNING
LU LOUDNESS UNIT METERING
LUFS LOUDNESS UNIT FULL SCALE
LV LOW VOLTAGE
M/C MOMENTARY CONTACT
MAC MEDIA ACCESS CONTROL
MAG.S MAGNETIC STARTER
MAX MAXIMUM
MB MAIN BUS
MC MECHANICAL CONTRACTOR
MCA MINIMUM CIRCUIT AMPS
MCB MAIN CIRCUIT BREAKER
MCC MOTOR CONTROL CENTER
MCM 1000 CIRCULAR MILLS
MDC MAIN DISTRIBUTION CENTER
MDP MAIN DISTRIBUTION PANEL
MEP MECHANICAL, ELECTRICAL, AND
PLUMBING
MFR MANUFACTURER
MFS MAIN FUSED DISCONNECT
SWITCH
MH MANHOLE
MIC MICROPHONE
MIN MINIMUM
MISC MISCELLANEOUS
MLO MAIN LUGS ONLY
MMS MANUAL MOTOR STARTER
MNF MANUFACTURER
MOA MULTI-OUTLET ASSEMBLY
MSBD MAIN SWITCHBOARD
MSP MOTOR STARTER PANELBOARD
MSS MOTOR STARTER SWITCH
MTG MOUNTING
MTR MOTOR
MTS MANUAL TRANSFER SWITCH
N NEW
N.I.C. NOT IN CONTRACT
N/A NOT APPLICABLE
N1 NEMA 1
N3R NEMA 3R
NAC NOTIFICATION APPLIANCE
CIRCUIT PANEL
NC NORMALLY CLOSED
NEC NATIONAL ELECTRICAL CODE
NEMA NATIONAL ELECT.
MANUFAC. ASSOC.
NFDS NON-FUSED SAFETY
DISCONNECT SWITCH
NFPA NATIONAL FIRE PROTECTION
ASSOC.
NL NIGHT LIGHT, BYPASS LOCAL
SWITCHING
NO NORMALLY OPENED
NPF NORMAL POWER FACTOR
NTS NOT TO SCALE
NVR NETWORK VIDEO RECORDER
OC ON CENTER
OH OVERHEAD
OL OVERLOADS
OS & Y OUTSIDE SCREW & YOKE
OSI OPEN SYSTEM INTEGRATION
PA PASCAL
PB PUSHBUTTON
PBB PRIMARY BONDING BUSBAR
PC PLUMBING CONTRACTOR
PCM PULSE CODE MODULATION
PDU POWER DISTRIBUTION UNIT
PE PNEUMATIC ELECTRIC
PED PEDESTAL
PF POWER FACTOR
PFR PHASE FAILURE RELAY
PIV POST INDICATING VALVE
PLEN PLENUM
PNL PANEL
POC POINT OF CONNECTION
POE POWER OVER ETHERNET
POS POINT OF SALE
PP POWER POLE
PPM PEAK PROGRAM METER
PR PAIR
PRI PRIMARY
PROJ PROJECTION
ABBREV. DESCRIPTION
PRV POWER ROOF VENTILATOR
PSI POUNDS-PER-SQUARE-INCH
PT POTENTIAL TRANSFORMER
PTP POINT TO POINT
PTZ PAN, TILT, AND ZOOM
PVC POLYVINYL CHLORIDE CONDUIT
PWR POWER
QUAN QUANTITY
R RESISTANCE
RECEP, RECPT RECEPTACLE
REQ,REQD REQUIRED
REX REQUEST TO EXIT
RF RADIO FREQUENCY
RFM ROOF MOUNTED
RL LOAD RESISTANCE
RLA RATED LOAD AMPS
RM ROOM
RMC RIGID METALLIC CONDUIT
RMP ROCKY MOUNTAIN POWER
RMS ROOT MEAN SQUARE
RNC RIGID NON-METALLIC COND.
RPM ROTATIONS-PER-MINUTE
RS SOURCE RESISTANCE
RT TOTAL RESISTANCE
RTU ROOF TOP UNIT
RX RECEIVER
S/N SOLID NEUTRAL
S/S STOP/START PUSHBUTTONS
SBB SECONDARY BONDING BUSBAR
SBG SUPPLEMENTARY BONDING
GRID
SBJ SYSTEM BONDING JUMPER
SC SURFACE CONDUIT
SCA SHORT CIRCUIT AMPERES
SDI SERIAL DIGITAL INTERFACE
SE SERVICE ENTRANCE
SEC SECONDARY
SES SMOKE EVACUATION SYSTEM
SHT SHEET
SIM SIMILAR
SLD SINGLE-LINE DIAGRAM
SNR SIGNAL-TO-NOISE RATIO
SP SPARE
SPDIF SONY PHILLIPS DIGITAL
INTERFACE
SPEC SPECIFICATIONS
SPKR LOUDSPEAKER
SPL SOUND PRESSURE LEVEL
SPP SINGLE-POINT POWER
SR SURFACE RACEWAY
SS SELECTOR SWITCH
SSW SELECTOR SWITCH
STA STATION
STD STANDARD
STP SHIELDED TWISTED PAIR
SURF SURFACE MOUNTED
SW SWITCH
SWBD SWITCHBOARD
SWGR SWITCHGEAR
SYM SYMMETRICAL
SYS SYSTEM
TBB TELECOMMUNICATIONS
BONDING BACKBONE
TBC TELECOMMUNICATIONS
BONDING CONDUCTOR
TC TEMP. CONTROL CONTR.
TEL TELEPHONE
TERM TERMINAL
TL TWIST LOCK
TR TAMPER RESISTANT
T-STAT THERMOSTAT
TTB TELEPHONE TERMINAL BOARD
TTC TELEPHONE TERMINAL CABINET
TV TELEVISION
TVTC TELEVISION TERMINAL
TX TRANSMITTER
TYP TYPICAL
UC UNDER COUNTER
UE UNDERGROUND ELECTRICAL
UG UNDERGROUND
UH UNIT HEATER
UNO UNLESS NOTED OTHERWISE
UPS UNINTERRUPTED POWER
SUPPLY
UT UNDERGROUND TELEPHONE
UTIL UTILITY
UTP UNSHIELDED TWISTED PAIR
UV ULTRAVIOLET
V VOLT (KV-KILOVOLT)
VA VOLT/AMPS
VA/R, VAR VOLT-AMPS/REACTIVE
VAC VOLTS ALTERNATING CURRENT
VDC VOLTS DC CURRENT
VDT VIDEO DISPLAY TERMINAL
VERT VERTICAL
VFD VARIABLE FREQUENCY DRIVE
VI VOLUME INDICATOR
VIF VERIFY IN FIELD
VM VOLT METER
VOL VOLUME
VU VOLUME UNIT
W WATTS
W/ WITH
W/O WITHOUT
WG WIRE GUARD
WH WATTHOUR METER
WP WEATHERPROOF/NEMA 3R
XFMR TRANSFORMER
XFMR SW SW TRANSFER SWITCH
XFR TRANSFER
XL X-CONNECTOR LOCKING
XLR X-CONNECTOR LOCKING
RUBBERIZED
XP EXPLOSION PROOF
XR EXISTING TO BE REMOVED
1P ONE-POLE
2P TWO-POLE
3P THREE-POLE
4P FOUR-POLE
∠ ANGLE
& AND
@ AT
° DEGREE
▲ DELTA
', FT FOOT, FEET
", IN INCH, INCHES
# NUMBER
Ω, OHM UNIT OF ELECTRICAL
RESISTANCE
Ø, PH PHASE
℄, CTR CENTER LINE, CENTER
P PLATE
SYMBOL LEGEND GENERAL NOTES
1. REFER TO LUMINAIRE SCHEDULE FOR FIXTURE TYPES, MOUNTING REQUIREMENTS, WATTAGE
& DETAILS.
2. WIRE LIGHT FIXTURE FROM ADJACENT JUNCTION BOX.
3. CONNECT NEAREST UN-SWITCHED HOT CONDUCTOR TO EMERGENCY BALLAST.
4. LIGHT FIXTURES ARE SCALED WITHIN THE DRAWINGS BASED ON ACTUAL DIMENSIONS.
5. REFER TO DRAWINGS FOR DIRECTIONAL ARROWS.
6. SUBSCRIPT INDICATES FIXTURES TO BE CONTROLLED.
7. HEIGHT MEASURED TO CENTER LINE OF THE BOX FROM THE FINISHED FLOOR.
8. NOT USED.
9. NEMA TYPE 'ND' NON-FUSED UNLESS NOTED 'F' (FUSED). USE HEAVY DUTY (HD) DEVICE FOR
480 VOLT.
10. SIZE TO THE EQUIPMENT BEING CONTROLLED.
11. PROVIDE H.O.A. & S.S. PUSHBUTTONS AS REQUIRED.
12. DOUBLE ARROWS INDICATES A DOUBLE FACE UNIT.
13. FOR WATER COOLER LOCATION, REFER TO DIAGRAM R002. FOR ALL OTHER LOCATIONS,
MOUNT AT +16" TO BOTTOM OF BOX FROM FINISHED FLOOR, OR AS NOTED.
14. ARROWS SHOWN ON DEVICE INDICATE AIMING DIRECTION.
15. COORDINATE WITH DOOR HARDWARE SUPPLIER.
16. MOUNT ON TRACK OF OVERHEAD DOOR, 6" FROM TOP OF DOOR, UNLESS OVERHEAD DOOR IS
A ROLL UP DOOR, THEN MOUNT PER MANUFACTURER'S INSTRUCTIONS.
17. INSTALL DEVICES PER MANUFACTURER'S INSTALLATION INSTRUCTIONS.
18. DASHED LINE INDICATES EQUIPMENT CLEARANCES. ARROW INDICATES FRONT OF RACK.
19. HEIGHT MEASURED TO BOTTOM OF THE DEVICE FROM FINISHED FLOOR.
20. PROVIDE MUD RING &/OR BOX COVER APPROPRIATE FOR DEVICE/FIXTURE SERVED.
21. REFER TO DIAGRAMS, ELEVATIONS, & SCHEDULES FOR CUSTOM ROUGH-IN REQUIREMENTS.
22. ROUGH-IN TO BE HORIZONTAL.
23. REFER TO MANUFACTURER'S RECOMMENDED CABLE REQUIREMENTS FOR EXACT CABLE
REQUIRED.
24. FOLLOW BICSI STANDARDS FOR CABLE ROUTING & DISTANCES.
25. SUBSCRIPT INDICATES NEMA CONFIGURATION.
26. USE A 4" X 4" BOX WITH A MUD RING TO MATCH THE DEVICE & INSTALLATION.
27. USE WITH POWER PACK.
28. PROVIDE UL LISTED DEVICE COMPATIBLE WITH THE FIRE ALARM PANEL/SYSTEM.
29. CAMERA TYPES ARE INDICATED INSIDE THE CAMERA SYMBOL.
30. SOLID BOX AROUND DEVICE INDICATES INSTALLED IN FLOOR. DASHED BOX AROUND DEVICE
INDICATES INSTALLED IN CEILING.
31. WALL DEVICES NOTED WITH A CHEVRON INDICATE THE PROPOSED INSTALLATION HEIGHT.
COORDINATE WITH MILLWORK SHOP DRAWINGS & ELEVATIONS FOR HEIGHT.
ELECTRICAL SHEET INDEX
SHEET NUMBER SHEET NAME
E001 ELECTRICAL TITLE SHEET
E101 LEVEL 1 ELECTRICAL FLOOR PLANS
ELECTRICAL GENERAL NOTES
1. GENERAL SCOPE & COMPLIANCE
A. INSTALL COMPLETE, OPERABLE ELECTRICAL SYSTEMS AS SHOWN AND SPECIFIED. BID
SHALL INCLUDE ALL WORK, MATERIALS, AND COORDINATION NECESSARY FOR A FULLY
FUNCTIONAL INSTALLATION.
B. ALL WORK SHALL COMPLY WITH THE NEC, NFPA 72, IBC/IFC, APPLICABLE LOCAL AND
STATE CODES, AHJ REQUIREMENTS, AND INDUSTRY STANDARDS.
C. ALL EQUIPMENT SHALL BE NEW, LISTED, AND LABELED BY A NATIONALLY RECOGNIZED
TESTING LABORATORY (E.G., UL, ETL) FOR ITS INTENDED USE.
D. ALL EQUIPMENT PROVIDED SHALL BE NEW, LISTED, AND LABELED BY A NATIONALLY
RECOGNIZED TESTING LABORATORY (NRTL).
E. FINAL INSTALLATION SHALL BE FREE OF DEFECTS AND APPROVED BY THE AHJ, OWNER,
ARCHITECT, AND ENGINEER.
F. THE ELECTRICAL SYSTEMS DEFINED BY THESE PLANS AND SPECIFICATIONS SHALL BE
CONSTRUCTED AS COMPLETE AND OPERABLE SYSTEMS AND BID WITH THIS INTENT.
G. CONTRACTOR SHALL VISIT THE SITE AND REVIEW ALL APPLICABLE CONTRACT
DOCUMENTS, INCLUDING ARCHITECTURAL, MECHANICAL, STRUCTURAL, AND OTHER
TRADE DRAWINGS, TO COORDINATE LOCATIONS, DIMENSIONS, AND REQUIREMENTS. NO
ADDITIONAL COSTS WILL BE ALLOWED FOR FAILURE TO COORDINATE.
H. CONTRACTOR SHALL VERIFY ALL EQUIPMENT DIMENSIONS, ELECTRICAL LOADS
(VOLTAGE, PHASE, CONNECTION REQUIREMENTS, ETC.), AND ROUGH-IN LOCATIONS
BEFORE INSTALLATION. VERIFY NEC CODE CLEARANCES AROUND ALL ELECTRICAL
EQUIPMENT.
I. ALL WORK SHALL CONFORM TO LOCAL AND STATE CODES, THE LATEST EDITION OF THE
NEC, AND ALL APPLICABLE INDUSTRY STANDARDS.
J. ELECTRICAL DRAWINGS ARE DIAGRAMMATIC/SCHEMATIC IN NATURE AND REPRESENT
THE GENERAL SCOPE OF WORK. RACEWAY ROUTING, UNLESS SPECIFICALLY SHOWN,
SHALL BE FIELD-DETERMINED IN COORDINATION WITH OTHER TRADES.
K. COORDINATE WITH ALL APPLICABLE SPECIFICATIONS, INCLUDING SECTION 265100
(16510) FOR REQUIRED COORDINATION MEETINGS WITH MECHANICAL AND CEILING
CONTRACTORS.
2. DRAWINGS & COORDINATION
A. ELECTRICAL DRAWINGS ARE DIAGRAMMATIC, SHOWING GENERAL SCOPE AND INTENT
ONLY. EXACT ROUTING, BENDS, PULL BOXES, AND OTHER INSTALLATION DETAILS ARE
THE CONTRACTOR’S RESPONSIBILITY.
B. CONSULT ARCHITECTURAL REFLECTED CEILING PLANS FOR FIXTURE/DEVICE
LOCATIONS, MECHANICAL PLANS FOR COORDINATED PENETRATIONS, AND SHOP
DRAWINGS FOR EQUIPMENT DIMENSIONS.
C. COORDINATE WITH ALL OTHER TRADES BEFORE ROUGH-IN TO AVOID CONFLICTS WITH
DUCTWORK, PIPING, STRUCTURE, AND EQUIPMENT.
D. ARCHITECTURAL AND MECHANICAL PLANS ARE PART OF THE ELECTRICAL DOCUMENTS
WHERE THEY PERTAIN TO ELECTRICAL WORK.
E. NO ADDITIONAL COST WILL BE ALLOWED FOR FIELD CONFLICTS OR EQUIPMENT
DIMENSION VARIATIONS DUE TO FAILURE TO COORDINATE.
3. PRE-BID & PRE-INSTALLATION REQUIREMENTS
A. VISIT THE SITE, REVIEW ALL CONTRACT DOCUMENTS, AND VERIFY EXISTING
CONDITIONS BEFORE BIDDING.
B. NOTIFY THE ENGINEER IN WRITING OF ERRORS, OMISSIONS, OR CONFLICTS PRIOR TO
BID. CHANGES WILL BE ISSUED VIA PRE-BID ADDENDUM.
C. VERIFY ALL ELECTRICAL LOADS, VOLTAGES, PHASES, AND CONNECTION
REQUIREMENTS FOR NEW AND EXISTING EQUIPMENT TO BE REUSED.
D. OBTAIN AND REVIEW WIRING DIAGRAMS FROM EQUIPMENT SUPPLIERS BEFORE ROUGH-
IN.
4. CLEARANCES & CODE-REQUIRED SPACE
A. MAINTAIN NEC-REQUIRED WORKING CLEARANCES AROUND ALL ELECTRICAL
EQUIPMENT.
B. IF CLEARANCE ISSUES ARE FOUND, NOTIFY THE DESIGNER IMMEDIATELY. IF
DISCOVERED AFTER INSTALLATION, RELOCATE AT THE CONTRACTOR’S EXPENSE
UNLESS OTHERWISE DIRECTED.
C. DO NOT ALLOW FOREIGN PIPING, DUCTWORK, OR UNRELATED EQUIPMENT IN
ELECTRICAL ROOMS OR ABOVE/BELOW ELECTRICAL EQUIPMENT.
5. MATERIALS & INSTALLATION STANDARDS
A. MINIMUM CONDUIT SIZE: 3/4".
a. INTERIOR: EMT WITH SET-SCREW FITTINGS.
b. EXTERIOR: EMT WITH COMPRESSION GLAND TYPE FITTINGS.
c. UNDERGROUND: PVC (SCH40) WITH GRC ELBOWS AND RISERS WRAPPED IN
CORROSION-RESISTANT MATERIAL WHERE IN DIRECT SOIL CONTACT.
B. PROVIDE SEPARATE INSULATED EQUIPMENT GROUNDING CONDUCTORS IN ALL
CONDUITS; CONDUIT SHALL NOT BE USED AS A GROUNDING CONDUCTOR.
C. COPPER CONDUCTORS, 600V RATED, THHN/THWN-2: #10 AWG AND SMALLER SOLID.
#8 AWG AND LARGER STRANDED. INCREASE CONDUCTOR SIZE TO #10 FOR 20A RUNS
OVER 125 FEET.
D. FLEXIBLE/SEALTITE CONDUIT LIMITED TO 6 FEET FOR FIXTURE AND MOTOR
CONNECTIONS AS NOTED OR VIBRATION-PRONE EQUIPMENT.
E. ALL EMPTY CONDUITS/RACEWAYS SHALL HAVE NYLON BUSHINGS AND 200 LB-RATED
PULL STRINGS.
F. SECURE CONDUIT AND BOXES TO STRUCTURE PER INDUSTRY STANDARDS. EXPOSED
CONDUIT SHALL BE PLUMB, LEVEL, PARALLEL TO BUILDING LINES, AND PAINTED TO
MATCH ADJACENT FINISHES IF VISIBLE.
G. CONDUITS/RACEWAYS SHALL BE CONCEALED WHERE PRACTICABLE. EXPOSED
CONDUIT/RACEWAY SHALL BE PAINTED TO MATCH ADJACENT SURFACES.
H. WIRING DEVICES SHALL BE WHITE WITH STAINLESS STEEL COVER PLATES UNLESS
OTHERWISE NOTED.
I. CONDUCTORS SHALL BE COPPER.
J. CAP AND LABEL ALL EMPTY CONDUIT TO REMAIN.
1. DEVICE & EQUIPMENT PLACEMENT
A. MOUNT WIRING DEVICES ABOVE BACKSPLASHES UNLESS SERVING UNDER-COUNTER
EQUIPMENT.
B. INSTALL SWITCHES, RECEPTACLES, AND CONTROLS AT ADA-COMPLIANT HEIGHTS.
C. OFFSET DEVICES ON OPPOSITE SIDES OF A WALL AT LEAST 12" TO REDUCE SOUND
TRANSMISSION.
D. COORDINATE FURNITURE LAYOUTS FOR FLOOR BOX AND POKE-THRU LOCATIONS
BEFORE ROUGH-IN.
E. LABEL ALL RECEPTACLE AND SWITCH FACEPLATES WITH CIRCUIT ID (XX-XX FORMAT).
F. PROVIDE TAMPER-RESISTANT RECEPTACLES AT ALL CODE-REQUIRED AND CHILD-
ACCESSIBLE LOCATIONS.
G. PROVIDE GFCI PROTECTION PER NEC, IN BATHROOMS, KITCHENS, OUTDOORS, WITHIN 6
FEET OF SINKS, AND WHERE REQUIRED FOR DIAGNOSTIC EQUIPMENT, TOOLS, OR
LIGHTING.
H. CIRCUITS EXTENDING OVER 70' FOR 120 VOLT AND 115' FOR 277 VOLT 20 AMP CIRCUITS
SHALL BE RUN WITH CONDUCTORS PER TABLE BELOW.
a. THESE ARE BASED ON MAXIMUM LENGTH OF CIRCUIT.
b. PERFORM VOLTAGE DROP CALCULATIONS AND PROVIDE CONDUCTOR SIZE TO
KEEP BRANCH CIRCUIT VOLTAGE DROP LESS THAN 3% WITH A 15 AMP LOAD.
c. CONTRACTOR SHALL ENSURE THAT THE INSTALLATION OF EACH BRANCH CIRCUIT
STAYS WITHIN 3% VOLTAGE DROP FOR A 15 AMP LOAD. IF
NECESSARY,CONTRACTOR SHALL INCREASE WIRE AND CONDUIT SIZE TO MEET
THE STANDARD AT NO ADDITIONAL COST TO OWNER.
I. MAINTAIN ELECTRICAL CONTINUITY TO REMAINING EQUIPMENT WHEN REMOVING
EXISTING EQUIPMENT.
J. ALL PENETRATIONS OF FIRE-RATED ASSEMBLIES (FLOORS, WALLS, CEILINGS) SHALL BE
SEALED WITH APPROVED FIRE-STOPPING MATERIALS TO MAINTAIN THE FIRE RATING.
K. EXTERIOR OUTLETS SHALL HAVE CAST COVERS WITH FLIP-TYPE LIDS UNLESS
OTHERWISE NOTED. ALL WP OUTLET HOODS SHALL BE EXTRA-DUTY, WHILE-IN-USE
TYPE, AND LOW-PROFILE WHERE PRACTICAL.
2. SPECIAL SYSTEMS
A. PROVIDE ADDRESSABLE FIRE ALARM SYSTEM PER NFPA 72, IBC/IFC, AND LOCAL CODES.
INCLUDE MONITORING OF SPRINKLER/TAMPER SWITCHES, AHU DUCT DETECTORS (>2000
CFM), PULL STATIONS AT EXITS, AND HEAT/SMOKE DETECTION AS SHOWN. SUBMIT
SHOP DRAWINGS FOR APPROVAL BEFORE INSTALLATION.
B. PROVIDE STRUCTURED CABLING FROM TELECOM/DATA/CATV OUTLETS TO THE MAIN
RACK/BOARD, WITH LABELING AT BOTH ENDS. INSTALL IN CONDUIT UNLESS ABOVE
ACCESSIBLE CEILINGS. USE PLENUM-RATED CABLE IN PLENUM SPACES.
C. PROVIDE HEAVY-DUTY FUSED DISCONNECTS.
D. SUBMIT SCALED LAYOUTS OF ELECTRICAL ROOMS (1/4" = 1') BASED ON FINAL
EQUIPMENT SUBMITTALS.
E. OBTAIN ALL WIRING DIAGRAMS FOR EQUIPMENT FROM SUPPLIERS BEFORE ROUGH-IN.
F. COORDINATE WITH EQUIPMENT SUPPLIERS FOR EXACT EQUIPMENT LOCATIONS AND
ELECTRICAL CONNECTIONS PRIOR TO ROUGH-IN.
G. THE ELECTRICAL CONTRACTOR SHALL MAKE FINAL EQUIPMENT CONNECTIONS UNLESS
OTHERWISE DIRECTED.
3. PENETRATIONS & SEALING
A. SEAL ALL PENETRATIONS OF FIRE-RATED FLOORS, WALLS, AND CEILINGS WITH
APPROVED FIRESTOP SYSTEMS TO MAINTAIN RATING.
B. ROOF PENETRATIONS FOR CONDUIT SHALL USE SEALED ROOF JACKS COMPATIBLE
WITH THE ROOF WARRANTY.
C. UNDERGROUND/UNDERFLOOR CONDUITS SHALL BE AT LEAST 24" BELOW GRADE/SLAB
UNLESS NOTED OTHERWISE.
D. ALL PENETRATIONS OF FIRE-RATED ASSEMBLIES (FLOORS, WALLS, CEILINGS) SHALL BE
SEALED WITH APPROVED FIRE-STOPPING MATERIALS TO MAINTAIN THE FIRE RATING.
4. TESTING, CLEANING, & TURNOVER
A. TEST AND VERIFY PROPER OPERATION OF ALL ELECTRICAL SYSTEMS AT COMPLETION.
B. CLEAN ALL FIXTURES, DEVICES, AND EQUIPMENT; REMOVE LABELS, DIRT, PAINT,
GREASE, AND DEBRIS BEFORE FINAL ACCEPTANCE.
C. PROVIDE ALL O&M MANUALS AND AS-BUILT DRAWINGS WITH WIRING DIAGRAMS INSIDE
EQUIPMENT AND IN THE PROJECT CLOSEOUT DOCUMENTS.
MAXIMUM LENGTH
20 AMP MINIMUM BRANCH CIRCUIT CONDUCTOR SIZING
BRANCH CIRCUIT VOLTAGE
CONDUCTOR LENGTH (FT) 120 VOLT 277 VOLT
<70 MIN. #12 AWG
70 - 115
115 - 170
170 - 270
271 - 380
>380
MIN. #12 AWG
MIN. #10 AWG MIN. #12 AWG
MIN. #8 AWG MIN. #10 AWG
MIN. #6 AWG MIN. #8 AWG
NOTE B MIN. #8 AWG
NOTE B NOTE B
ELECTRICAL GENERAL PROVISIONS
DESCRIPTION OF WORK: EXTENT OF ELECTRICAL WORK IS INDICATED ON DRAWINGS. PROVIDE ALL LABOR, MATERIALS, EQUIPMENT, SUPERVISION AND SERVICE NECESSARY FOR A COMPLETE ELECTRICAL SYSTEM. WORK
INCLUDES, BUT IS NOT NECESSARILY LIMITED TO THE FOLLOWING ITEMS:
• ELECTRICAL CONNECTIONS FOR EQUIPMENT
• CONDUCTORS AND CABLES
• GROUNDING
• SUPPORTING DEVICES
• CONDUIT RACEWAYS
• ELECTRICAL BOXES AND FITTINGS
• RACEWAYS SYSTEMS
• ELECTRICAL SEISMIC CONTROL
• ELECTRICAL IDENTIFICATION
• SWITCHGEAR AND SWITCHBOARDS
• PANELBOARDS
• SERVICE ENTRANCE
• WIRING DEVICES
• OVERCURRENT PROTECTIVE DEVICES
• MOTOR AND CIRCUIT DISCONNECTS
• MOTOR STARTERS
• VARIABLE FREQUENCY DRIVES
• EMERGENCY ELECTRICAL SYSTEMS
• DEMOLITION
INTERPRETATION OF DRAWINGS AND SPECIFICATIONS: BEFORE BIDDING, CONTRACTOR SHALL FAMILIARIZE
THEMSELVES WITH THE DRAWINGS, SPECIFICATIONS AND PROJECT SITE.
VISIT THE SITE DURING THE BIDDING PERIOD TO DETERMINE EXISTING CONDITIONS AFFECTING ELECTRICAL AND
OTHER WORK, ALL COSTS ARISING FROM SITE CONDITIONS AND/OR PREPARATION SHALL BE INCLUDED IN THE
BASE BID. NO ADDITIONAL CHARGES WILL BE ALLOWED DUE TO INADEQUATE SITE INSPECTION.
QUALITY ASSURANCE: PERFORM WORK IN ACCORDANCE WITH THE NATIONAL ELECTRICAL CODE (NEC). COMPLY
WITH REQUIREMENTS FOR STATE AND LOCAL ORDINANCES. OBTAIN ALL PERMITS, INSPECTIONS, ETC FOR
AUTHORITY HAVING JURISDICTION (AHJ). EMPLOY ONLY QUALIFIED CRAFTSMEN WITH AT LEAST THREE (3) YEARS
OF EXPERIENCE. WORKMANSHIP SHALL BE NEAT, HAVE A GOOD MECHANICAL APPEARANCE AND CONFORM TO
BEST ELECTRICAL STATE CONTRACTING LICENSE. PROVIDE EQUIPMENT AND MATERIALS THAT ARE
UNDERWRITERS LABORATORIES INC. (UL) LISTED AND LABELED.
SUBMITTALS: AFTER THE CONTRACT IS AWARDED BUT PRIOR TO MANUFACTURE OR INSTALLATION OF ANY
EQUIPMENT, PREPARE COMPLETE SHOP DRAWINGS.
1. PROVIDE SUBMITTALS IN PORTABLE DOCUMENT FORMAT (PDF).
2. DOCUMENTS MUST BE ELECTRONICALLY BOOKMARKED AND KEYWORD SEARCHABLE USING
(HTTP://ADOBE.COM/ACROBAT) ADOBE ACROBAT OR BLUEBEAM REVU
(HTTP://BLUEBEAM.COM) FOR EACH RELEVANT SECTION. (I.E. INCLUDE ELECTRONIC BOOKMARKS
SEPARATION “LIGHT FIXTURES” FROM “PANELBOARDS”.)
3. ELECTRONICALLY HIGHLIGHT ALL OPTIONS FOR LIGHT FIXTURES, ELECTRICAL EQUIPMENT, ETC.
MANUAL HIGHLIGHTING AND SCANNING OF THE DOCUMENTS IS NOT ACCEPTABLE AND WILL NOT BE
REVIEWED.
4. PROVIDE ONLY COMPLETED CUTSHEETS FOR ALL FIXTURE AND EQUIPMENT TYPES. BLANK
CUTSHEETS SUBMITTED WITH A SCHEDULE ARE NOT ACCEPTABLE AND WILL NOT BE REVIEWED.
5. A MAXIMUM OF ONE SUBMITTAL PER SPECIFICATION SECTION IS ALLOWED, IT IS NOT ACCEPTABLE TO
PROVIDE PRODUCT BY PRODUCT SUBMITTAL. SINGLE PRODUCT SUBMITTALS WILL NOT BE REVIEWED.
A. ELECTRICAL CONNECTIONS FOR EQUIPMENT
B. CONDUCTORS AND CABLES
C. GROUNDING
D. SUPPORTING DEVICES
E. CONDUIT RACEWAYS
F. ELECTRICAL BOXES AND FITTINGS
G. RACEWAYS SYSTEMS
H. ELECTRICAL SEISMIC CONTROL
I. ELECTRICAL IDENTIFICATION
J. SWITCHGEAR AND SWITCHBOARDS
K. PANELBOARDS
L. SERVICE ENTRANCE
M. WIRING DEVICES
N. OVERCURRENT PROTECTIVE DEVICES
O. MOTOR AND CIRCUIT DISCONNECTS
P. MOTOR STARTERS
6. PRODUCTS: PRODUCTS ARE SPECIFIED BY MANUFACTURE NAME, DESCRIPTION AND/OR CATALOG
NUMBER. PROVIDE PRODUCTS OF MANUFACTURERS SPECIFIED. SUBSTITUTIONS WILL BE CONSIDERED
IF A DUPLICATE WRITTEN APPLICATION IS SUBMITTED. NO MATERIAL MAY BE SUBSTITUTED AFTER THE
BID OPENING. PROVIDE BLOCK OUTS, SLEEVES, ETC. REQUIRED FOR INSTALLATION OF WORK
SPECIFIED.
7. RECORD DRAWINGS: MAINTAIN ON A DAILY BASIS, A COMPLETE SET OF RECORD DRAWINGS, REFLECTING AN ACCURATE DIMENSIONAL RECORD OF ALL BURIED OR CONCEALED WORK. MARK
RECORD DRAWINGS TO SHOW THE PRECISE LOCATION OF CONCEALED WORK AND EQUIPMENT,
INCLUDING CONCEALED OR EMBEDDED CONDUIT AND JUNCTION BOXES AND ALL CHANGES AND
DEVIATIONS IN THE WORK FROM THAT SHOWN ON THE CONTRACT DOCUMENTS.
8. OPERATION AND MAINTENANCE MANUALS: PROVIDE OPERATION AND MAINTENANCE DATA BOOKS FOR
ALL EQUIPMENT AND MATERIALS FURNISHED UNDER THIS DIVISION.
9. GUARANTEE: ENSURE THAT ELECTRICAL SYSTEMS INSTALLED UNDER THIS CONTRACT IS IN PROPER
WORKING ORDER AND IN COMPLIANCE WITH DRAWINGS, SPECIFICATIONS, AND/OR AUTHORIZED
CHANGES, WITHOUT ADDITIONAL CHARGE, REPLACE ANY WORK OR MATERIALS WHICH DEVELOP
DEFECTS, EXCEPT FROM ORDINARY WEAR AND TEAR, WITHIN ONE YEAR FROM THE DATE OF
SUBSTANTIAL COMPLETION.
10. FIRE PROTECTION SEALS: SEAL ALL PENETRATIONS FOR WORK OF THIS SECTION THROUGH FIRE
RATED FLOORS, WALLS, CEILINGS TO PREVENT THE SPREAD OF SMOKE, FIRE, TOXIC GAS, OR WATER
THROUGH THE PENETRATION EITHER BEFORE, DURING OR AFTER FIRE.
11. POWER OUTAGES: ALL POWER OUTAGES REQUIRED FOR EXECUTION OF THIS WORK SHALL OCCUR
DURING NON-STANDARD WORKING HOURS AND AT THE CONVENIENCE OF THE OWNER. INCLUDE ALL
COSTS FOR OVERTIME WORK IN BID.
12. EXCAVATING FOR ELECTRICAL WORK: LOCATE AND PROTECT EXISTING UTILITIES AND OTHER
UNDERGROUND WORK. PERFORM EXCAVATION IN A MANNER WHICH PROTECTS WALLS, FOOTINGS AND
OTHER STRUCTURAL MEMBERS.
13. CONCRETE BASES: PROVIDE 4” CONCRETE BASES FOR ELECTRICAL EQUIPMENT.
14. ROOF PENETRATIONS: PROVIDE ROOF JACK, SIZED TO FIT TIGHTLY TO RACEWAY FOR WEATHERTIGHT
SEAL.
ELECTRICAL CONNECTIONS FOR EQUIPMENT
1. VERIFY EXACT LOAD AND LOCATION OF ALL EQUIPMENT BEFORE ROUGH-IN FOR EACH ELECTRICAL
CONNECTION. PROVIDE COMPLETE ASSEMBLY OF MATERIAL, INCLUDING BUT NOT NECESSARILY
LIMITED TO, RACEWAYS, CONDUCTORS, CORDS, CORD CAPS, PLUGS, WIRING DEVICES, PRESSURE
CONNECTORS, TERMINALS (LUGS), ELECTRICAL INSULATION TAPE, HEAT-SHRINKABLE INSULATION
TUBING, CABLE TIES, SOLDERLESS WIRE NUTS, AND OTHER ITEMS AND ACCESSORIES AS NEEDED TO
COMPLETE SPLICES, TERMINATIONS, AND CONNECTIONS AS REQUIRED. FOR PERMANENTLY
INSTALLED FIXED EQUIPMENT, PROVIDE FLEXIBLE SEAL-TITE CONNECTIONS. FOR MOVABLE AND/OR
PORTABLE EQUIPMENT, PROVIDE WIRE DEVICE, CORD CAP, AND MULTI-CONDUCTOR CORD.
CONDUCTORS AND CABLES
1. PROVIDE FACTORY FABRICATED CONDUCTORS FOR SIZES, RATINGS, MATERIAL, AND TYPES
INDICATED FOR EACH SERVICE. PROVIDE COPPER CONDUCTORS, WITH THHN/THWN INSULATION. SIZE
ALL CONDUCTORS IN ACCORDANCE WITH NEC: MINIMUM SIZE TO BE #12 AWG. PROVIDE STRANDED
CONDUCTORS FOR #8 AWG AND LARGER.
2. THE FOLLOWING COLOR SCHEME SHALL BE USED:
3. MC CABLE:
A. MC CABLE IS ACCEPTABLE FOR ALL BRANCH CIRCUITS INSTALLED IN GYPSUM WALLBOARD
WALLS FROM THE HOME RUN DEVICE BOX TO THE LAST DEVICE BOX ON THE BRANCH CIRCUIT
AND ALL BOXES IN BETWEEN, FROM THE HOME RUN DEVICE BOX TO THE BRANCH PANEL, THE
CIRCUIT SHALL BE INSTALLED IN AN APPROVED RACEWAY. MC CABLE IS ACCEPTABLE FOR ALL
LIGHT FIXTURE WHIPS NOT LONGER THAN SIX FEET IN LENGTH. LOCATED IN REMOVABLE GRID
CEILINGS. MC CABLE IS UNACCEPTABLE TO BE INSTALLED FROM LIGHT FIXTURE TO LIGHT
FIXTURE. ALL MC CABLE SHALL BE PROVIDED WITH ANTI SHORT FITTINGS.
B. THE USE OF MC-PCS CABLE IS ACCEPTABLE FOR LIGHT FIXTURE WHIPS UTILIZING 0-10V
CONTROL SCHEMES, NOT LONGER THAN 72” IN LENGTH, LOCATED ABOVE REMOVABLE GRID
CEILINGS. ALL MC CABLE SHALL BE PROVIDED WITH ANTI-SHORT FITTINGS.
a. ACCEPTABLE MANUFACTURERS
• AFC – MC LUMINARY CABLE
• ENCORE – MC-LED LIGHTING CABLE
• SOUTHWIRE – MC-PCS DUO
GROUNDING
• PROVIDE GROUNDING AND BONDING OF ALL ELECTRICAL AND COMMUNICATION APPARATUS,
MACHINERY, APPLIANCES, BUILDING COMPONENTS, AND ITEMS REQUIRED BY THE NEC TO PROVIDE A
PERMANENT, CONTINUOUS LOW IMPEDANCE, GROUNDING SYSTEM. PROVIDE AN NEC
BONDING/GROUNDING CONDUCTOR IN ALL RACEWAYS USE FOR POWER DISTRIBUTION.
SUPPORTING DEVICES
• PROVIDE SUPPORTS, ANCHORS, SLEEVES AND SEALS AS REQUIRED FOR A COMPLETE RACEWAY
SUPPORT SYSTEM, INCLUDING BUT NOT LIMITED TO: CLEVIS HANGERS, RISER CLAMPS, C-CLAMPS, BEAM CLAMPS, ONE- AND TWO-HOLE CONDUIT STRAPS, OFFSET CONDUIT CLAMPS, EXPANSION
ANCHORS, TOGGLE BOLTS, THREADED RODS, U-CHANNEL STRUT SYSTEM, AND ALL OTHER
ASSOCIATED ACCESSORIES. INSTALL IN ACCORDANCE WITH MANUFACTURER’S WRITTEN
INSTRUCTIONS AND WITH RECOGNIZED INDUSTRY PRACTICES TO ENSURE SUPPORTING DEVICES
COMPLY WITH REQUIREMENTS. PROVIDE RIGID ATTACHMENT OF ALL FLOOR MOUNTED EQUIPMENT TO
THE FLOOR SLAB OR STRUCTURAL SYSTEM.
CONDUIT RACEWAYS
1. PROVIDE METAL CONDUIT, TUBING, AND FITTINGS OF TYPES, GRADES, SIZES, AND WEIGHTS (WALL
THICKNESS) AS REQUIRED; WITH MINIMUM TRADE SIZE OF 3/4”. INSTALL ELECTRICAL RACEWAY
SYSTEMS IN ACCORDANCE WITH MANUFACTURER’S WRITTEN INSTRUCTIONS AND APPLICABLE
REQUIREMENTS OF NEC AND NECA “STANDARD OF INSTALLATION” IN ACCORDANCE WITH THE
FOLLOWING:
A. FEEDERS: INSTALL FEEDERS RATED 100 AMPS AND GREATER, IN ELECTRICAL METALLIC CONDUIT
(EMT); WHERE BURIED BELOW GRADE, INSTALL IN CONCRETE ENCASED N0N-METALIC CONDUIT
OR DUCT (SCHEDULE 40 PVC).
B. BRANCH CIRCUITS, AND INDIVIDUAL EQUIPMENT CIRCUITS RATED LESS THAT 100 AMPS; INSTALL
IN ELECTRICAL METALLIC TUBING (EMT). WHERE LOCATED IN POURED WALLS, BELOW CONCRETE
SLAB-ON-GRADE, OR IN EARTH FILL, INSTALL IN NON-METALLIC PLASTIC DUCT (SCHEDULE 40
PVC). ENCASE NON-METALLIC PLASTIC DUCT 1-1/4” AND LARGER IN CONCRETE.
C. PROVIDE RIGID METAL CONDUIT (RMC) FOR ALL BENDS IN BURIED CONDUIT GREATER THAN 30
DEGREES. PROVIDE PROTECTIVE COATING FOR RIGID METAL CONDUIT BENDS.
D. INSTALL FLEXIBLE CONDUIT FOR CONNECTIONS TO MOTORS, TRANSFORMERS, AND OTHER
ELECTRICAL EQUIPMENT WHERE SUBJECT TO MOVEMENT AND VIBRATIONS.
E. PROVIDE “OZ” EXPANSION FITTINGS ON ALL CONDUITS CROSSING BUILDING EXPANSION JOINTS, BOTH IN SLAB AND SUSPENDED.
F. DUCT BANKS” PROVIDE DUCT BANK CONSTRUCTION AS INDICATED USING 3000 PSI CONCRETE
WITH RED MARKER DYE. INSTALL #4 REINFORCING BAR IN EACH CORNER OF DUCT BANK.
PROVIDE MINIMUM OF 4” CONCRETE COVER ON ALL SIDES OF EXTERIOR CONDUITS.
ELECTRICAL BOXES AND FITTINGS
1. PROVIDE ONE PIECE GALVANIZED FLAT ROLLED SHEET STEEL INTERIOR OUTLET WIRING BOXES, CORROSION-RESISTANT CAST-METAL WEATHERPROOF OUTLET WIRING BOXES, CODE GAUGE SHEET
STEEL JUNCTION AND PULL BOXES, GALVANIZED CAST IRON CONDUIT BODIES, CORROSION-RESISTANT
PUNCH-STEEL BOX KNOCKOUT CLOSURES, CONDUIT LOCKOUTS AND MALLEABLE STEEL CONDUIT
BUSHINGS AND OFFSET CONNECTORS, AND ALL ACCESSORIES AS REQUIRED TO SUIT EACH
RESPECTIVE LOCATION AND INSTALLATION. FASTEN BOXES RIGIDLY TO SUBSTRATES OR STRUCTURAL
SURFACES TO WHICH ATTACHED, OR SOLIDLY EMBED ELECTRICAL BOXES IN CONCRETE OR MASONRY.
USE BAR HANGERS FOR STUD CONSTRUCTION.
2. FLOOR BOXES – PROVIDE LEVELING AND FULLY ADJUSTABLE FLOOR SERVICE RECEPTACLE OUTLETS
AND FITTINGS OF TYPE AND RATINGS AS INDICATED ON THE DRAWINGS. ALL BOXES SHALL COMPLY
WITH UL STANDARD UL514A.
RACEWAY SYSTEMS
1. EXTENT OF RACEWAYS IS INDICATED BY DRAWINGS AND SCHEDULES.
2. COMPLY WITH APPLICABLE PORTIONS OF NEMA STANDARDS PERTAINING TO RACEWAYS. COMPLY
WITH APPLICABLE PORTIONS OF UL SAFETY STANDARDS PERTAINING TO ELECTRICAL RACEWAY
SYSTEMS AND PROVIDE PRODUCTS AND COMPONENTS WHICH HAVE BEEN UL-LISTED AND LABELED.
COMPLY WITH NEC REQUIREMENTS AS APPLICABLE TO CONSTRUCTION AND INSTALLATION OF
RACEWAY SYSTEMS.
3. PROVIDE SURFACE RACEWAYS OF SIZES AND CHANNELS INDICATED. PROVIDE FITTINGS INDICATED
WHICH MATCH AND MATE WITH RACEWAY. PROVIDE RECEPTACLES ON CENTERS AS INDICATED ON
DRAWINGS OR AS DIRECTED BY ENGINEER.
4. PROVIDE CABLE TRAY SYSTEMS OF SIZES, TYPES AND CAPACITIES INDICATED, AND MEETING ALL
REQUIREMENTS OF NEMA VE-1. TRAYS TO BE PROVIDED INCLUDE BUT ARE NOT NECESSARILY LIMITED
TO THE FOLLOWING:
A. FITTINGS, GROUNDING STRAPS, CABLE FALLS, ETC.
5. INSTALL ELECTRICAL RACEWAYS WHERE INDICATED; IN ACCORDANCE WITH MANUFACTURERS
WRITTEN INSTRUCTIONS, APPLICABLE REQUIREMENTS OF NEC AND NECA “STANDARDS OF
INSTALLATION”, AND COMPLYING WITH RECOGNIZED INDUSTRY PRACTICES.
6. INSTALL ELECTRICAL RACEWAYS LEVEL AND SQUARE TO BUILDING ELEMENTS AND AT PROPER
ELEVATIONS/HEIGHTS.
ELECTRICAL SEISMIC CONTROL
1. PROVIDE SEISMIC CONTROL EQUIPMENT INCLUDING BUT NOT LIMITED TO: VIBRATION ISOLATORS, FLEXIBLE CONNECTIONS, RIGID STEEL FRAMES, ANCHORS, INSERTS AND ATTACHMENTS, SEISMIC
SNUBBER AND BRACING TO MEET THE REQUIREMENTS FOR THE PROJECT SITE AS DESIGNED BY A
PROFESSIONAL ENGINEER LICENSED IN THE STATE WHERE THE PROJECT IS LOCATED.
2. THE ABOVE REFERENCED ENGINEER SHALL DETERMINE SPECIFIC REQUIREMENTS FOR EQUIPMENT
ANCHORAGE AND RESTRAINTS, LOCATIONS AND SIZES BASED ON SHOP DRAWINGS FOR THE
ELECTRICAL EQUIPMENT WHICH HAVE BEEN SUBMITTED.
3. THE DIVISION 26 CONTRACTOR SHALL REQUIRE ALL EQUIPMENT SUPPLIER FURNISHED EQUIPMENT
THAT MEETS THE SEISMIC CODE, WITH BASES/SKIDS/CURBS DESIGNED TO RECEIVE SEISMIC BRACING
AND/OR ANCHORAGE.
4. SPRING ISOLATED EQUIPMENT: ALL VIBRATION ISOLATED EQUIPMENT SHALL BE MOUNTED ON RIGID
STEEL FRAMES OR CONCRETE BASES. EACH SPRING MOUNTED BASE SHALL HAVE A MINIMUM OF FOUR
ALL-DIRECTIONAL SEISMIC SNUBBERS THAT ARE DOUBLE ACTING AND LOCATED AS CLOSE TO THE
VIBRATION ISOLATORS AS POSSIBLE TO FACILITATE ATTACHMENT BOTH TO THE BASE AND THE
STRUCTURE.
5. NON-ISOLATED EQUIPMENT: THE DIVISION 26 CONTRACTOR SHALL BE RESPONSIBLE FOR
THOROUGHLY REVIEWING ALL DRAWINGS AND SPECIFICATIONS TO DETERMINE ALL EQUIPMENT TO BE
RESTRAINED. THIS CONTRACTOR SHALL BE RESPONSIBLE FOR CERTIFYING THAT THIS EQUIPMENT IS
MOUNTED AND BRACED.
6. CONDUIT: A RIGID CONDUIT SYSTEM SHALL NOT BE BRACED TO DISSIMILAR PARTS OF THE BUILDING
OR TWO DISSIMILAR BUILDING SYSTEMS THAT MAY RESPOND IN A DIFFERENT MODE DURING AN
EARTHQUAKE. EXAMPLE: WALLS AND A ROOF; SOLID CONCRETE WALL AND A METAL DECK WITH
LIGHTWEIGHT CONCRETE FILL. UNBRACED CONDUIT ATTACHED TO IN-LINE EQUIPMENT SHALL BE
PROVIDED WITH ADEQUATE FLEXIBILITY TO ACCOMMODATE DIFFERENTIAL DISPLACEMENTS. PROVIDE
LARGE ENOUGH PIPE SLEEVES THROUGH WALLS OR FLOORS TO ALLOW FOR ANTICIPATED
DIFFERENTIAL MOVEMENTS.
7. CABLE TRAY: CABLE TRAYS SHALL BE SUSPENDED FROM ROD HANGERS AND HANGERS THAT ARE 12”
IN LENGTH OR LONGER FROM POINT ROD ATTACHES TO TRAY, TO THE POINT ROD CONNECTS
LOCATED AS CLOSE TO THE VIBRATION ISOLATORS AS POSSIBLE TO THE SUPPORTING STRUCTURE
BOTH TO THE BASE AND TO THE VIBRATION ISOLATORS AS POSSIBLE TO FACILITATE ATTACHMENT
AND THE STRUCTURE.
8. NON-ISOLATED EQUIPMENT: THE DIVISION 26 CONTRACTOR SHALL BE RESPONSIBLE FOR
THOROUGHLY REVIEWING ALL DRAWINGS AND SPECIFICATIONS TO DETERMINE ALL EQUIPMENT TO BE
RESTRAINED. THIS CONTRACTOR SHALL BE RESPONSIBLE FOR CERTIFYING THAT THIS EQUIPMENT IS
MOUNTED AND BRACED.
ELECTRICAL IDENTIFICATION
1. PROVIDE ELECTRICAL IDENTIFICATION PRODUCTS FOR BURIED ELECTRICAL LINES, ARC-FLASH
HAZARD LABELS (ANSI Z535.4), SOURCE OF SUPPLY LABELS, AVAILABLE FAULT CURRENT LABELS AND
EMERGENCY OPERATING SIGNS TO EQUIPMENT INSTALLED AS PART OF THIS PROJECT.
2. COLOR ADHESIVE MARKING TAPE FOR RACEWAYS, WIRES AND CABLES: SELF-ADHESIVE VINYL TAPE
NOT LESS THAN 3 MILLS THICK BY 1” TO 2” IN WIDTH.
3. UNDERGROUND LINE MARKING TAPE: PERMANENT, BRIGHT COLORED, CONTINUOUS-PRINTED, PLASTIC
TAPE COMPOUNDED FOR DIRECT-BURIAL SERVICE NOT LESS THAN 6” WIDE BY 4 MILLS THICK.
4. ENGRAVED, PLASTIC LAMINATED LABELS, SIGNS AND INSTRUCTION PLATES: ENGRAVING STOCK
PLASTIC LAMINATE, 1/16” MINIMUM THICKNESS FOR SIGNS UP TO 20” SQUARE, OR 8” IN LENGTH; 1/8”
FOR LARGER SIZES. ENGRAVED LEGEND IN 1/4” HIGH WHITE LETTERS ON BLACK FACE.
5. PROVIDE LABELS ON COVER PLATES INDICATING SOURCE OF POWER (I.E. PANEL – CIRCUIT #) TO
COMPLY WITH NEC 408.4.
6. PROVIDE CIRCUIT DIRECTORY THAT CLEARLY IDENTIFIES EACH AND EVERY CIRCUIT, TO COMPLY WITH
NEC 408.
7. CONDUIT IDENTIFICATION
1. IDENTIFY RACEWAYS OF SYSTEMS WITH COLOR CODING. ACCEPTABLE MEANS OF COLOR
IDENTIFICATION ARE AS FOLLOWS:
A. COLORED ADHESIVE MARKING TAPE
B. FIELD PAINTED FITTINGS IE: COUPLINGS AND CONNECTORS
C. COLOR RACEWAYS FOR THE FOLLOWING SYSTEMS:
FIRE ALARM SYSTEM: RED
SOUND/IC: BLUE
TELEPHONE: YELLOW
DATA: GREEN
SECURITY: ORANGE
1. IDENTIFY JUNCTION, PULL AND CONNECTION BOXES
A. PROVIDE COVERPLATES FOR SYSTEMS JUNCTION, PULL AND CONNECTIONS BOXES
PAINTED TO MATCH REQUIREMENTS ABOVE.
B. FOR POWER AND LIGHTING JUNCTION BOXES LABEL WITH IDENTITY OF CONTAINED
CIRCUITS.
WIRING DEVICES
1. PROVIDE SPEC GRADE FACTORY-FABRICATED WIRING DEVICES, IN TYPE, AND ELECTRICAL RATINGS
FOR APPLICATIONS INDICATING AND COMPLYING WITH NEMA STDS PUB NO. WD-1. PROVIDE HEAVY
DUTY SPECIFICATION GRADE, 20-AMPERES RATED, GROUNDING TYPE CONVENIENCE OUTLETS.
PROVIDE 20-AMPRESE RATED TOGGLE SWITCHES. CONSTRUCT WIRING DEVICE OF HEAVY-DUTY HIGH
IMPACT NYLON AND PROVIDE COVER PATES TO MATCH. PROVIDE DEVICES AND COLORS SELECTED BY
ARCHITECT.
2. PROVIDE THE FOLLOWING:
A. CONTROLLED RECEPTACLE - NEMA 5-20R TO COMPLY WITH NEC 406.3(F).
B. GROUND FAULT INTERRUPTER - NEMA 5020R WITH 5 MILIAMPERIS GROUND FAULT TRIP LEVEL.
C. USB RECEPTACLE - NEMA 5-20R WITH (2) USB, 5VDC, 2.0 AND 3.0 TYPE A AND TYPE C PORTS.
D. TAMPER RESISTANT RECEPTACLE - NEMA 5-20R TO COMPLY WITH NEC 406.12.
E. WEATHER-RESISTANT RECEPTACLE - NEMA 5-20R TO COMPLY WITH NEC 406.9.
F. WEATHER PROTECTIVE DEVICE ENCLOSURE - PROVIDE IN-USE COVER TO COMPLY WITH NEC
406.9.
OVERCURRENT PROTECTIVE DEVICES
1. PROVIDE OVERCURRENT PROTECTIVE DEVICES OF THE SAME MANUFACTURER AS THE SWITCHBOARD
AND/OR PANELBOARD MANUFACTURER. PROVIDE FACTORY ASSEMBLED DEVICES OF AMPERAGE,
VOLTAGE, AND RMS INTERRUPTING RATING SHOWN. PROVIDE DEVICES AS FOLLOWS:
A. MOLDED CASE THERMAL TRIP CIRCUIT BREAKERS:
a. PROVIDE FACTORY-ASSEMBLED BOLT-ON MOLDED CASE CIRCUIT BREAKER WITH
PERMANENT THERMAL TRIP AND ADJUSTABLE INSTANTANEOUS MAGNETIC TRIP IN EACH
POLE. SERIES RATING IS NOT ACCEPTABLE. CONSTRUCT BREAKERS FOR MOUNTING AND
OPERATING IN ANY PHYSICAL POSITION AND IN AN AMBIENT TEMPERATURE OF 40 DEGREES
C.
b. CIRCUIT BREAKERS 15 AMPS THROUGH 599 AMPS SHALL BE MOLDED CASE THERMAL
CIRCUIT BREAKERS
B. MOLDED CASE SOLID STATE CIRCUIT BREAKERS
a. PROVIDE FACTORY ASSEMBLED BOLT-ON MOLDED CASE CIRCUIT BREAKERS UL LISTED
FOR APPLICATION AT 100% OF THEIR RATED CONTINUOUS AMPERE RATING.
b. CIRCUIT BREAKERS 600 AMPS THROUGH 1199 AMPS SHALL BE MOLDED CASE SOLID-STATE
CIRCUIT BREAKERS.
c. SOLID-STATE TRIP MECHANISMS SHALL HAVE THE FOLLOWING FUNCTIONS:
ADJUSTABLE LONG TIME AMPERE RATING; ADJUSTABLE LONG TIME DELAY; SHORT TIME
PICK-UP; ADJUSTABLE SHORT TIME DELAY; ADJUSTABLE INSTANTANEOUS PICK-UP.
C. INSULATED CASE CIRCUIT BREAKERS
a. PROVIDE FACTORY ASSEMBLED BOLT-ON INSULATED CASE CIRCUIT BREAKERS WITH SOLID-
STATE TRIP APPLICATION AT 100% OF THEIR CONTINUOUS AMPERE RATING.
b. CIRCUIT BREAKERS 1200 AMPS AND LARGER SHALL BE INSULATED CASE CIRCUIT
BREAKERS.
MOTOR AND CIRCUIT DISCONNECTS
1. PROVIDE HEAVY-DUTY TYPE SAFETY SWITCHES; FUSIBLE OR NON-FUSIBLE AS INDICATED. PROVIDE
SWITCHES RATED AT 600 VOLTS, 60 HZ.; INCORPORATING QUICK-MAKE, QUICK-BREAK TYPE
MECHANISMS. EQUIP WITH OPERATING HANDLE THAT IS CAPABLE OF BEING PADLOCKED IN THE OFF
POSITION. PROVIDE NEMA ENCLOSURE RATINGS BASED ON LOCATION OF INSTALLATION.
MOTOR STARTER
1. PROVIDE FACTORY ASSEMBLED, AC-NON-RESERVING MAGNETIC STARTERS RATED AT 600V WITH
THERMAL OVERLOAD PROTECTION IN ALL PHASES. MOUNT HAND-OFF-AUTO SWITCH, RED PILOT LIGHT, AND RESET BUTTON IN FACE OF ENCLOSURE. PROVIDE NEMA ENCLOSURES RATINGS BASED ON
LOCATION OF INSTALLATION.
DEMOLITION
1. PROVIDE DEMOLITION WORK AS INDICATED BY DRAWINGS. THE INTENT OF THE DRAWINGS IS TO
INDICATE MAJOR ITEMS AFFECTED AND NOT TO SHOW EVERY DEVICE AFFECTED BY DEMOLITION
WORK.
A. THE NEW ELECTRICAL EQUIPMENT AND APPARATUS SHALL BE COORDINATED AND CONNECTED
INTO THE EXISTING SYSTEM AS REQUIRED.
a. THE EXISTING ELECTRICAL DEVICES, CONDUIT AND/OR EQUIPMENT THAT FOR ANY REASON
OBSTRUCTS CONSTRUCTION SHALL BE RELOCATED.
b. ALL EXISTING ELECTRICAL EQUIPMENT AND SYSTEMS IN PORTIONS OF THE BUILDING NOT
BEING REMODELED SHALL BE KEPT OPERATIONAL, IN SERVICE AND IN WORKING CONDITION
THROUGHOUT THE ENTIRE CONSTRUCTION PERIOD. RESTORE ANY CIRCUITS AND SYSTEMS
INTERRUPTED.
c. EXISTING RACEWAY MAY BE RE-USED WHERE POSSIBLE IN PLACE. ALL CIRCUITS AND WIRE
THAT ARE NOT RE-USED SHALL BE REMOVED BACK TO PANEL BOARD. WHERE IT SHALL BE
LABELED AS SPARE. RE-USED RACEWAY SHALL MEET ALL REQUIREMENTS FOR NEW
INSTALLATION.
ELECTRICAL SPECIFICATIONS
CONDUCTOR 240/120 V SYSTEM 208/120 V SYSTEM 480/277 V SYSTEM
PHASE A
PHASE B
PHASE C
SHARED/SINGLE
NEUTRAL
NEUTRAL A
(DEDICATED)
NEUTRAL B
(DEDICATED)
NEUTRAL C
(DEDICATED)
ISOLATED GROUND
EQUIPMENT GROUND
BLACK
RED
BLUE
WHITE
WHITE W/ BLACK
STRIPE
WHITE W/ RED
STRIPE
WHITE W/ BLUE
STRIPE
GREEN W/ YELLOW
STRIPE
GREEN
BLACK
RED
BLUE
WHITE
WHITE W/ BLACK
STRIPE
WHITE W/ RED
STRIPE
WHITE W/ BLUE
STRIPE
GREEN W/
YELLOW STRIPE
GREEN
BROWN
ORANGE
YELLOW
GRAY
GRAY W/ BROWN
STRIPE
GRAY W/ ORANGE
STRIPE
GRAY W/ YELLOW
STRIPE
GREEN W/ YELLOW
STRIPE
GREEN
DIVISION OF FACILITIES
CONSTRUCTION AND
MANAGEMENT
Jason Van Ausdal
09/03/2026
VISTOR WALK-IN
OFFICE
WORK AREA /
STORAGE
UTILITY ROOM
RECEIVING AREA/
EQUIPMENT
HOLDING
COOL STORAGE
STORAGE
STORAGE
T
T
T
VISTOR WALK-IN
OFFICE
WORK AREA /
STORAGE
UTILITY ROOM
RECEIVING AREA/
EQUIPMENT
HOLDING
COOL STORAGE
STORAGE
STORAGE
T
T
T
D1
D1
D1
UH-1
UH-1
UH-1
P1
P1
P1
L I C
E N
S E D
P
ROFESS IONA
L
E N
G I N
E E
R
14275529
S
T A
T E OF U
TA
H
SANG TRUONG
No.
Project #: 260447
DFCM APPROVAL STAMP
181 East 5600 South Murray, UT 84107
801.530.3148 T
801.530.3150 F
A
B
C
D
E
1 2 3 4 5 6
07/16/2026
260447
ST
REVISIONS
SHEET CONTENTS
RESOLUT PROJECT #:
CHECKED BY:
DRAWN BY:
CURRENT/ISSUE DATE:
Resolut Group, 2025
Original drawings remain the property of the Engineer and as such the Engineer retains total ownership and control. The design represented by these drawings are sold to the client for a one time use, unless otherwise agreed upon in writing by the
Engineer.
C
U S
H
W A
R E
H O
U S
E U
N
IT
H E
A T
E R
S R
E P
L A
C E
M E
N T
E a s t
C e n te r S tr e e t
P ro v o
U ta h
SE
LEVEL 1 ELECTRICAL
FLOOR PLANS
E101
1/8" = 1'-0"
LEVEL 1 ELECTRICAL DEMOLITION PLAN
ELECTRICAL DEMOLITION NOTES
1. REFERENCE & COORDINATION
A. REFER TO ARCHITECTURAL DRAWINGS AND SPECIFICATIONS FOR DEMOLITION AND
CONSTRUCTION PHASES. COORDINATE ALL ELECTRICAL WORK WITH GENERAL
CONSTRUCTION REQUIREMENTS, DOOR RELOCATIONS, AND WALL MODIFICATIONS.
B. EXISTING DEVICES/EQUIPMENT SHOWN IN GRAY ARE EXISTING TO REMAIN. PRESERVE
AND PROTECT.
C. CONTRACTOR TO COORDINATE WITH OWNER FOR ITEMS TO BE SALVAGED PRIOR TO
DEMOLITION. CONTRACTOR RESPONSIBLE FOR DISPOSING OF ANY MATERIAL THAT THE
OWNER DOES NOT WANT TO KEEP.
D. DEVICES SHOWN ON DEMOLITION SHEETS ARE GATHERED FROM AS-BUILT DRAWINGS
AND FIELD…