VA Baltimore Construction Fan Coil Unit - DRAWINGS.pdf
PDF 12 MB Posted
- Solicitation number
- 47PD0321R0022
About this file
This document provides details on a pre-solicitation notice for renovations at the Veteran Benefits Administration Regional Office in Baltimore, Maryland. The General Services Administration seeks a construction firm to provide labor, materials, equipment and supervision for interior renovations including demolition, new tenant layouts with offices, workstations, storage and support rooms, and mechanical, electrical and fire protection work. The project will be completed in four phases with occupancy in adjacent suites, and has a period of performance of 1,062 calendar days. A competitive negotiated request for proposal will be issued seeking fixed price proposals, with technical factors being significantly more important than price in a best value evaluation. The solicitation is expected on September 10, 2021, with a pre-proposal conference on September 21, 2021 and proposals due by the specified date. The project has an estimated value over $10 million and will be set aside for small businesses.
View the file
Other files
Show all 24
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
U.S. GENERAL SERVICES ADMINISTRATION
PUBLIC BUILDINGS SERVICE | MID-ATLANTIC REGION
SENSITIVE BUT UNCLASSIFIED (SBU)
PROPERTY OF THE UNITED STATES GOVERNMENT
COPYING, DISSEMINATION, OR DISTRIBUTION OF THIS DOCUMENT TO UNAUTHORIZED
RECIPIENTS IS PROHIBITED
Do not remove this notice.
Properly destroy or return documents when no longer needed.
DEPARTMENT OF VETERANS AFFAIRS
VARO REPROGRAMMING DEVELOPMENT
AND FINAL DESIGN PROJECT
100% CD SET
100% CONSTRUCTION DOCUMENT SET
FOR
FAN COIL UNIT REPLACEMENT PROJECT
100% CD SET
Ÿ Ÿ
Ÿ Ÿ
Ÿ
Ÿ
Ÿ Ÿ
Ÿ Ÿ
Ÿ
Ÿ
Ÿ
Ÿ
ABBREVIATIONS
DRAWING SYMBOLS
SECURITY NOTICE
PROJECT TEAM
VICINITY MAP
LOCATION MAP
SENSITIVE BUT UNCLASSIFIED (SBU)
PROPERTY OF THE UNITED STATES GOVERNMENT
COPYING, DISSEMINATION, OR DISTRIBUTION OF
THIS DOCUMENT TO UNAUTHORIZED USERS IS
PROHIBITED.
DO NOT REMOVE THIS NOTICE.
PROPERLY DESTROY OR RETURN DOCUMENTS
WHEN NO LONGER NEEDED.
BALTIMORE HARBOR
E A
S T C
A S
E
W
A
S
H
I
N
G
T
O
N
B
L
V
D
NATIONAL AQUARIUM
N
M
O N
R O
E
S
T
M
A
R
T
I
N
U
T
H
E
R
K I N
G
J R
B
L
V
D
W
LOMBARD S
T
H O
P K
I N
S
P
L
S
C
H A
R L E
S
S
T
W B
ALTIM
ORE S
T
W P
RATT S
T
L I G
H T
S
T
N
C
A L V
E R
T
S
T
S
H
O W
A R
D
S
T
W F
AYETTE S
T
DRAWING INDEX
Ÿ
Ÿ Ÿ Ÿ
Ÿ
Ÿ Ÿ
Ÿ Ÿ
Ÿ
GENERAL NOTES FOR FAN COIL
UNIT REPLACEMENT PROJECT
HAZARDOUS MATERIALS
STATEMENT
KEY NOTES
CR ACR
A
CR
AD
S
S S
S
S S
S
S
S
S
S S
S
S S
S
S S
S
S
S
S
S S
S
S S
S
S
S S
S
S
S
S
S
S
S S
S
S S
S
S
SS
S
S
S S S
S
SS
S
SS
S S S S
S
S
SS
S
SSS
SS
S
SSS
S
S
S S
S S S
S
S
S
S S S
S
S
OS
OS
OS
OS
OS
OS
OS
OS
OS OS
OS
OS
OS
OS
OS
OS
OS
OSOS
OS
OS
SPSP
SP SP
LEGEND - EGRESS PLANS
SP SP
100% CD SET
PROFESSIONAL CERTIFICATION. I CERTIFY
THAT THESE DOCUMENTS WERE PREPARED
OR APPROVED BY ME, AND THAT I AM A DULY
LICENSED ARCHITECT UNDER THE LAWS OF
THE STATE OF MARYLAND, LICENSE NUMBER
9635, EXPIRATION DATE AUGUST 16, 2021.
CODE ANALYSIS (NEW WORK AREA ONLY)
PROFESSIONAL CERTIFICATION. I CERTIFY
THAT THESE DOCUMENTS WERE PREPARED
OR APPROVED BY ME, AND THAT I AM A DULY
LICENSED ENGINEER UNDER THE LAWS OF
THE STATE OF MARYLAND, LICENSE NUMBER
35646, EXPIRATION DATE MAY 11, 2022.
LS902
1 LIFE SAFETY- 12TH
1/8" = 1'-0"SCALE:
OCCUPANT LOAD
EGRESS CAPACITY
100% CD SET
PROFESSIONAL CERTIFICATION. I CERTIFY
THAT THESE DOCUMENTS WERE PREPARED
OR APPROVED BY ME, AND THAT I AM A DULY
LICENSED ARCHITECT UNDER THE LAWS OF
THE STATE OF MARYLAND, LICENSE NUMBER
9635, EXPIRATION DATE AUGUST 16, 2021.
PROFESSIONAL CERTIFICATION. I CERTIFY
THAT THESE DOCUMENTS WERE PREPARED
OR APPROVED BY ME, AND THAT I AM A DULY
LICENSED ENGINEER UNDER THE LAWS OF
OS
OS
D
I A
G
O
N
A
D
OS
OS
OS
OS
OS
LS903
LIFE SAFETY PLAN - 16TH
1/8" = 1'-0"SCALE:
100% CD SET
GENERAL CONTRACTOR TO REMOVE
EXIT SIGNS IN THIS SPACE IF DIRECTING
EGRESS INTO RENOVATION SCOPE OF
WORK (PLAN EAST).
KEY NOTES:
LS903
LIFE SAFETY PLAN - 16TH (CONTINUED)
1/8" = 1'-0"SCALE:
OCCUPANT LOAD
EGRESS CAPACITY
PROFESSIONAL CERTIFICATION. I CERTIFY
THAT THESE DOCUMENTS WERE PREPARED
OR APPROVED BY ME, AND THAT I AM A DULY
LICENSED ENGINEER UNDER THE LAWS OF
CWS
(E)
LC
SYMBOLS CONT. SYMBOLS CONT. GENERAL SYMBOLS
SYMBOLS
R
SP SPRINKLER PIPING
PIPE TURN UP
PIPE TURN DOWN
CONCENTRIC PIPE REDUCER
ECCENTRIC PIPE REDUCER
DIRECTION OF FLOW
PIPE CAP
PIPE CLEANOUT
WALL PIPE CLEANOUT
FLOOR CLEANOUT
FLOOR DRAIN
C.O.
W.C.O.
F.C.O.
FL.D.
GATE VALVE
GLOBE VALVE
SWING CHECK VALVE
TWO-WAY CONTROL VALVE
THREE-WAY CONTROL VALVE
STRAINER
UNION
PRESSURE REDUCING VALVE
SAFETY RELIEF VALVE
O.S.&Y VALVE
FLOW MEASURING VALVE
COMBINATION FLOW MEASURING
AND BALANCING VALVE
BALANCING VALVE
BALL VALVE
BUTTERFLY VALVE
MOTORIZED BUTTERFLY VALVE
BACKFLOW PREVENTER
MANUAL AIR VENT 3/8" BALL VALVEM.A.V.
THERMOMETER AND WELL
PRESSURE GAUGE
2-WAY PLUG VALVE
WYE STRAINER WITH CAPPED
BLOWDOWN VALVE
FLEXIBLE PIPING CONNECTION
PIPE EXPANSION JOINT
RECTANGULAR DUCT
SIZE TRANSITION
RIGID ROUND DUCT
SIZE TRANSITION
DUCT TRANSITION FROM
SQUARE TO ROUND
DUCT WITH 1/2"x1/2" WOVEN WIRE
MESH SCREEN WITH HEMMED EDGES.
DUCT WITH SMOKE DETECTOR
SD
DUCT ELBOW WITH
TURNING VANES
FLEXIBLE DUCTWORK. 5 FEET MAXIMUM
LENGTH, SIZE AS INDICATED OR SCHEDULED
PLENUM SLOT DIFFUSER WITH FLEXIBLE
DUCT(5' MAXIMUM LENGTH) SAME SIZE AS
DIFFUSER NECK SIZE. DIFFUSER SIZE PER
SCHEDULE UNLESS OTHERWISE NOTED.
PROVIDE CONICAL SPIN-IN TAP WITH
BALANCING DAMPER AT RECTANGULAR DUCT.
NUMBER INDICATES BALANCING AIRFLOW CFM.
SQUARE CEILING DIFFUSER WITH FLEXIBLE
DUCT(5' MAXIMUM LENGTH) SAME SIZE AS
DIFFUSER NECK SIZE. DIFFUSER SIZE PER
SCHEDULE UNLESS OTHERWISE NOTED.
PROVIDE CONICAL SPIN-IN TAP WITH
BALANCING DAMPER AT CIRCULAR DUCT.
NUMBER INDICATES BALANCING AIRFLOW CFM.
CEILING REGISTER, SIZE PER SCHEDULE UNLESS
OTHERWISE NOTED. NUMBER INDICATES
BALANCING AIRFLOW CFM.
SUPPLY AIR DIFFUSER, 24x24 FACE AREA, SUITABLE FOR 2'x4' TILE CEILING.
PERFORATED CEILING PANEL, 24x24 FACE AREA, SUITABLE FOR 2'x4' TILE CEILING.
CENTRIFUGAL FAN OR
PUMP BY APPLICATION
DOOR LOUVER
3/4" DOOR UNDERCUT
RETURN AIR SYMBOL
NUMBER INDICATES CFM
SUPPLY AIR SYMBOL
NUMBER INDICATES CFM
THERMOSTAT
U
L
CR
HUMIDITY SENSOR
DOMESTIC COLD WATERCW
CWR CHILLED WATER RETURN
CHILLED WATER SUPPLY
CONDENSATE DRAIND
FIRE LINE PIPINGF
DUAL TEMPERATURE WATER RETURNHCR
DUAL TEMPERATURE WATER SUPPLYHCS
HW DOMESTIC HOT WATER
HWC HOT WATER CIRCULATING
HWR HEATING WATER RETURN
HEATING WATER SUPPLYHWS
DETAIL IDENTIFICATION
SECTION IDENTIFICATION
ELEVATION IDENTIFICATION
DETAIL/SECTION IDENTIFICATION
M-501
NORTH ARROW
COLUMN BUBBLE
DESIGNATION
REVISION CLOUD WITH REVISION
NUMBER DESIGNATION
BREAKLINE
MATCHLINE DESIGNATIONM A T C H L I N E A-A
DEMOLITION LINETYPE
CENTERLINE
CENTERLINE SYMBOL
EXISTING
POINT OF CONNECTION TO EXISTING
POINT OF TERMINATION OF REMOVAL
NOTE NUMBER
EXHAUST OR RETURN DUCT UP
EXHAUST OR RETURN DUCT DOWN
SUPPLY DUCT UP
SUPPLY DUCT DOWN
DUCT WITH ACOUSTICAL SOUND LINING
ROUND DUCT UP
ROUND DUCT DOWN
DUCT WITH FIRE DAMPER AND
MINIMUM 16x16 ACCESS DOORF.D.&A.D.
A.D.
DUCT WITH ACCESS DOOR,
MINIMUM 16x16
DUCT WITH MANUAL BALANCING DAMPER.
PROVIDE ACCESS DOOR MINIMUM (DUCT
WIDTH MINUS 2") WIDE BY 16" LONG.M.B.D.
DUCT WITH MOTOR OPERATED DAMPER
M.O.D.
DUCT WITH FLEXIBLE CONNECTION
DUCT WITH SOUND ATTENUATOR
UP DUCT TRANSITION UP
DUCT TRANSITION DOWNDN.
DUCT RISERISE
T
H
M-101 M-501
M-101 M-501
M-101 M-501
M
F.D. FIRE DAMPER
FLA FULL LOAD AMPS
FL.D. FLOOR DRAIN
FLR. FLOOR
FPM FEET PER MINUTE
FT. FEET
F.V. FACE VELOCITY
GAL. GALLON
GPM GALLONS PER MINUTE
H.C. HEATING COIL
HP HORSEPOWER
HW DOMESTIC HOT WATER
HWR HEATING WATER RETURN
HWS HEATING WATER SUPPLY
Hz HERTZ
IN. INCHES
JC JANITORS CLOSET
L.A.T. LEAVING AIR TEMPERATURE
LBS. POUNDS
LBS./HR POUNDS PER HOUR
L.D.B. LEAVING DRY BULB
L.W.T. LEAVING WATER TEMPERATURE
MAX. MAXIMUM
M.B.D. MANUAL BALANCING DAMPER
MER MECHANICAL EQUIPMENT ROOM
MIN. MINIMUM
M.O.D. MOTOR OPERATED DAMPER
NC NOISE CRITERIA
N.C. NORMALLY CLOSED
N.I.C. NOT IN CONTRACT
N.O. NORMALLY OPEN
O.A. OUTSIDE AIR
O.C. ON CENTER
O.S.D. OPEN SITE DRAIN
P.D. PRESSURE DROP
PH PHASE
PRV PRESSURE RELIEF VALVE
PSI POUNDS PER SQUARE INCH
PSIG POUNDS PER SQUARE INCH GAUGE
PVC POLYVINYL CHLORIDE
R.A. RETURN AIR
R.G. RETURN GRILLE
RLA RUNNING LOAD AMPS
RPM REVOLUTIONS PER MINUTE
S.A. SUPPLY AIR
SD SMOKE DETECTOR
S.P. STATIC PRESSURE
S.S. STAINLESS STEEL
T.G. TOP GRILLE
T.O.C. TOP OF CONCRETE
T.O.G. TOP OF GRADE
T.O.S. TOP OF STEEL
T.R. TOP REGISTER
TYP. TYPICAL
UH UNIT HEATER
V VOLTS
VAV VARIABLE AIR VOLUME
VOL. VOLUME
W.B. WET BULB
W.C. WATERCOLUMN
W.G. WATER GAUGE
MECHANICAL PIPE
RISER DESIGNATION
RISER NUMBER
SHEET NUMBER WHERE
DETAIL IS TAKEN
SHEET NUMBER WHERE
DETAIL IS DRAWN
NUMBER INDICATES
DETAIL
N
ARROW INDICATES
TRUE NORTH AND/OR
PROJECT NORTH
SHEET NUMBER WHERE
DETAIL/SECTION IS DRAWN
NUMBER INDICATES
DETAIL/SECTION
SHEET NUMBER WHERE
ELEVATION IS TAKEN
SHEET NUMBER WHERE
ELEVATION IS DRAWN
NUMBER INDICATES
ELEVATION
INDICATES DIRECTION
OF ELEVATION VIEW
INDICATES DIRECTION
OF CUTTING PLANE
NUMBER INDICATES
SECTION
SHEET NUMBER WHERE
SECTION IS DRAWN
SHEET NUMBER WHERE
SECTION IS TAKEN
ABBREVIATIONS CONT.
A.D. ACCESS DOOR
A.F.F. ABOVE FINISHED FLOOR
AHU AIR HANDLING UNIT
ARCH. ARCHITECTURAL
A.P. ACCESS PANEL
APPROX. APPROXIMATELY
BHP BRAKE HORSEPOWER
BTU BRITISH THERMAL UNITS
BTUH BRITISH THERMAL UNITS PER HOUR
C COMMON
C.C. COOLING COIL
C.D. CEILING DIFFUSER
CFM CUBIC FEET PER MINUTE
C.G. CEILING GRILLE
CGR CHILLED GLYCOL RETURN
CGS CHILLED GLYCOL SUPPLY
C.O. CLEANOUT
C.R. CEILING REGISTER
CW DOMESTIC COLD WATER
D.B. DRY BULB
db DECIBEL
DDC DIRECT DIGITAL CONTROL
DESIG. DESIGNATION
DIA DIAMETER
DN. DOWN
(E) EXISTING
E.A.T. ENTERING AIR TEMPERATURE
E.D.B. ENTERING DRY BULB
EFF. EFFICIENCY
E.G. EXHAUST GRILLE
ELEV. ELEVATION/ELEVATOR
ENT. ENTERING
E.S.P. EXTERNAL STATIC PRESSURE
E.W.B. ENTERING WET BULB
E.W.T. ENTERING WATER TEMPERATURE
EXIST. EXISTING
°F DEGREES FAHRENHEIT
FCU FAN COIL UNIT
ABBREVIATIONS
SUMMER
CONSULTANTS
I N C O R P O R A T E D
SUMMER
CONSULTANTS
FI
LE
N
AM
E:
OU
R
RE
F:
PL
OT
D
AT
E:
4/5
/20
2:
:25 P
M
4.2
M-
1.D W
G
PROFESSIONAL CERTIFICATION. I HEREBY CERTIFY
THAT THESE DOCUMENTS WERE PREPARED OR
APPROVED BY ME, AND THAT I AM A DULY LICENSED
PROFESSIONAL ENGINEER UNDER THE LAWS OF THE
STATE OF MARYLAND, LICENSE NO. 45592, EXPIRATION
DATE: 05 JUNE 2022.
45678910
E
F
G
(E)10x6
(E)6x8
(E)22x10
(E)14x12
(E )1
8x
TYP. OF 18
(E)10x10
(E )1
8x
(E)14x12
(E )1
4x
(E )1
0x
(E)18x10
(E)8x10
(E)12x10
(E)18x10 (E)18x10
(E)14x14
12x8
(E)12x10
(E)8x12 (E)14x14 (E)14x14
(E )1
4x
(E)14x12
DN
(E)24x8 (E)24x8
(E )1
2x
(E)6Ø
(E)16x10
(E)10x10
(E)10x10
(E )1
4x
(E)24x8TRANSFER
(E)RG
(E)RG
(E)CD (E)CD
(E)CD
(E)CD
(E)RG
(E)RG
(E)RG
(E)CD
(E)RG
(E)CD (E)CD
(E)CD
(E)CD
(E)CD
(E)CD (E)CD
(E)CD (E)CD
(E)CD(E)RG
(E)RG(E)CD (E)CD
(E)CD
(E)CD
(E)CD
(E)CD
(E)RG
(E)CD(E)CD
(E)CD
(E)CD
(E)CD
(E)RG
(E)CD
(E)CD
(E)RG
(E)RG
(E)RG
(E)CD
(E)CD
(E)CD
(E)CD
(E)10x10
(E)CD
(E)18x10
(E)RG
(E)RG
(E)RG
(E)RG
(E)CD
(E)CD
(E)RG
(E)RG
(E)12x10
(E)12x10
TYP. OF 181
TYP. OF 341
(E)6x8
FCU 1
FCU 1
FCU1
FCU1
FCU 1
FCU 1
FCU1
FCU 1
FCU 1
FCU1
(E)6"Ø
T
T
2 T 2T
T 2
T
T
T2
T
T
T
GENERAL NOTES
G1. VERIFY LOCATION AND DIMENSIONS OF EXISTING EQUIPMENT AND
COORDINATE ALL WORK PRIOR TO THE START OF CONSTRUCTION.
G2. REFER TO SHEET MD903 FOR ASSOCIATED PIPING DEMOLITION.
NOTES
1. REMOVE FAN COIL UNIT AND ASSOCIATED DUCTWORK, INSULATION,
CONTROLS, HANGERS, SUPPORTS, AND APPURTENANCES COMPLETE TO
POINT INDICATED.
2. REMOVE THERMOSTAT AND ASSOCIATED CONTROLS, WIRING, SUPPORTS,
AND APPURTENANCES COMPLETE. SUMMER
CONSULTANTS
I N C O R P O R A T E D
SUMMER
CONSULTANTS
N
8'0 16' 1/8"=1'-0"
TWELFTH FLOOR PLAN - HVAC - DEMOLITION
FI
LE
N
RE
F:
PL
OT
D
AT
E:
4/5
/20
2:
:32 P
M
4.2
MD
2-
.D W
G
PROFESSIONAL CERTIFICATION. I HEREBY CERTIFY
THAT THESE DOCUMENTS WERE PREPARED OR
APPROVED BY ME, AND THAT I AM A DULY LICENSED
PROFESSIONAL ENGINEER UNDER THE LAWS OF THE
GENERAL NOTES
G1. VERIFY LOCATION AND DIMENSIONS OF EXISTING EQUIPMENT AND
COORDINATE ALL WORK PRIOR TO THE START OF CONSTRUCTION.
G3. COORDINATE UTILITY SHUTDOWN WITH CONTRACTING OFFICE A
MINIMUM 2-WEEKS IN ADVANCE.
NOTES
1. REMOVE FAN COIL UNIT AND ASSOCIATED CONTROLS, HANGERS,
SUPPORTS, AND APPURTENANCES COMPLETE.
2. REMOVE PIPING AND ALL ASSOCIATED VALVES, CONTROLS,
INSULATION, HANGERS, SUPPORTS, AND APPURTENANCES
COMPLETE TO POINTS INDICATED.
3. REMOVE DUAL TEMPERATURE SUPPLY AND RETURN, AND
CONDENSATE DRAIN PIPING BACK TO INTERIOR OF WALL. REFER
TO GENERAL CONSTRUCTION PLANS FOR ADDITIONAL DETAILS.
4. INDICATED PIPING IS IN CEILING OF LEVEL BELOW.
45678910
D
E
F
G
45678910
D
E
F
G
45678910
D
E
F
G
(E)HCS&R
(E)CO
TYP. OF 182
(E)1"CWR (E)1-1/2"CWS
(E)1-1/4"CWR
(E)1"CWR (E)1-1/2"CWS
(E)1-1/2"D
(E)2"HCS&R
(E)CWS&R
(E)1"HCR
(E)1"HCR
(E)1"HCR
(E)1"HCS&R
(E)1"D
(E)HCS
(E)CO
(E)CO
3 3 3 3
3 333
33333333
(E)1"CWS
(E)1"CWS
(E)1"D
(E)3/4"HCS
(E)1"D
(E)3/4"CWS
(E)3/4"CWR(E)1"D
(E)1"CWS
(E)1"CWS
(E)1"CWS&R
(E)1"CWS&R
(E)1"CWS&R
(E)3/4"CWS&R
(E)3/4"CWS&R
(E)1"D
TYP. OF 182
TYP. OF 342(E)CO(E)CO
1 1
1 (E)3/4"CWS&R
(E)1-1/4"CWR
4(E)2"HCR 4(E)1-1/4"HCR (E)3/4"HCS 4
4 (E)HCR 4
(E)1"D 4
(E)1"D4
(E)1"D4
(E)1"D4
(E)1"D4 4 4(E)1"HCR (E)3/4"HCS(E)1"D4 4 4(E)1"HCR (E)3/4"HCS
(E)1"D4 4 4
FCU
FCU
FCU
FCU
FCU
FCU
FCU
FCU
FCU
1 FCU
(E)1"CWS&R
(E)1"HCS 4
(E)3/4"HCS 4
(E)3/4"HCS 4
(E)HCS
(E)HCR (E)HCR
(E)HCS
(E)1"D4
(E)1"D4
(E)CO
1 FCU
SUMMER
CONSULTANTS
I N C O R P O R A T E D
SUMMER
CONSULTANTS
N
8'0 16' 1/8"=1'-0"
TWELFTH FLOOR PLAN - PIPING - DEMOLITION
FI
LE
N
RE
F:
PL
OT
D
AT
E:
4/5
/20
2:
:38 P
M
4.2
MD
3-
.D W
G
PROFESSIONAL CERTIFICATION. I HEREBY CERTIFY
THAT THESE DOCUMENTS WERE PREPARED OR
APPROVED BY ME, AND THAT I AM A DULY LICENSED
PROFESSIONAL ENGINEER UNDER THE LAWS OF THE
COORDINATE ALL WORK PRIOR TO THE START OF CONSTRUCTION.
1. REMOVE FAN COIL UNIT AND ASSOCIATED PIPING, INSULATION, HANGERS,
SUPPORTS, DAMPERS, CONTROLS AND APPURTENANCES COMPLETE.
2. REMOVE PIPING, INSULATION, HANGERS, VALVES AND APPURTENANCES TO
POINT INDICATED. PREPARE PIPING TO CONNECT TO NEW EQUIPMENT.
3. INDICATED PIPING LOCATED ON FLOOR BELOW. ISOLATION VALVES FOR
AREA OF WORK IS LOCATED IN CEILING OF FLOOR BELOW.
NOTES
GENERAL NOTES
G1. VERIFY LOCATION AND DIMENSIONS OF EXISTING EQUIPMENT AND
COORDINATE ALL WORK PRIOR TO THE START OF CONSTRUCTION.
1. REMOVE FAN COIL UNIT AND ASSOCIATED PIPING, INSULATION, HANGERS,
SUPPORTS, DAMPERS, CONTROLS AND APPURTENANCES COMPLETE.
2. REMOVE PIPING, INSULATION, HANGERS, VALVES AND APPURTENANCES TO
POINT INDICATED. PREPARE PIPING TO CONNECT TO NEW EQUIPMENT.
3. INDICATED PIPING LOCATED ON FLOOR BELOW. ISOLATION VALVES FOR
AREA OF WORK IS LOCATED IN CEILING OF FLOOR BELOW.
NOTES
45678910
E
F
G
TYP. OF 42 1
2 2 2 2 2
2222 2 2 2 2 2
(E)1"D
(E)1"D (E)1"D(E)1"D(E)1"D(E)1"D (E)3/4"HCS
(E)2"HCS&R
(E)1-1/4"HCS&R
(E)2"HCR
(E)1-1/4"HCS&R
(E)2"HCR
(E)1-1/4"HCS&R
(E)2"HCR
TYP. OF 42 1
2 2 2 2 2
2222 2 2 2 2 2
(E)1"D
(E)1"D (E)1"D(E)1"D(E)1"D(E)1"D (E)3/4"HCS
(E)2"HCS&R
(E)1-1/4"HCS&R
(E)2"HCR
(E)1-1/4"HCS&R
(E)2"HCR
(E)1-1/4"HCS&R
(E)2"HCR
SUMMER
CONSULTANTS
I N C O R P O R A T E D
SUMMER
CONSULTANTS
N
8'0 16' 1/8"=1'-0"
SIXTEENTH FLOOR PLAN - PIPING - DEMOLITION
FI
LE
N
RE
F:
PL
OT
D
AT
E:
4/5
/20
2:
:46 P
M
4.2
MD
4-
.D W
G
PROFESSIONAL CERTIFICATION. I HEREBY CERTIFY
THAT THESE DOCUMENTS WERE PREPARED OR
APPROVED BY ME, AND THAT I AM A DULY LICENSED
PROFESSIONAL ENGINEER UNDER THE LAWS OF THE
COORDINATE ALL WORK PRIOR TO THE START OF CONSTRUCTION.
G2. REFER TO SHEET M-903 FOR ASSOCIATED PIPING.
NOTES
1. BALANCE FCU TO MAXIMUM SCHEDULED AIRFLOW. EQUALLY DISTRIBUTE
AIR TO ALL CONNECTED AIR DEVICES.
2. REFER TO SCHEDULES FOR OUTDOOR AIR BALANCE VALVE.
45678910
D
E
F
G
(E)10x6
(E)6x8
(E)22x10
(E)14x12
(E )1
8x
TYP. OF 18
(E)10x10
(E )1
8x
(E)14x12
(E )1
4x
(E )1
0x
(E)18x10
(E)8x10
(E)12x10
(E)18x10 (E)18x10
(E)12x10
(E)8x12 (E)14x14 (E)14x14
(E )1
4x
(E)14x12
DN
(E)24x8 (E)24x8
(E )1
2x
(E)6Ø
(E)16x10
(E)10x10
(E)10x10
(E )1
4x
(E)24x8TRANSFER
(E)RG
(E)RG
(E)CD
(E)CD
(E)CD(E)CD
(E)RG
(E)RG
(E)RG
(E)CD
(E)RG
(E)CD
(E)CD
(E)CD
(E)CD (E)CD
(E)CD (E)CD
(E)CD(E)RG
(E)RG(E)CD (E)CD
(E)CD
(E)CD
(E)CD(E)CD
(E)RG
(E)CD
(E)CD
(E)CD
(E)CD
(E)CD
(E)RG (E)CD
(E)RG
(E)RG
(E)RG
(E)CD
(E)CD
(E)CD
(E)CD
(E)10x10
(E)CD
(E)18x10
(E)RG
(E)RG
(E)RG
(E)RG
(E)CD
(E)CD
(E)RG
(E)RG
(E)12x10
(E)12x10
TYP. OF 181
TYP. OF 341
(E)6x8
10x10
8"Ø
12x8
14x14 8x12
6"Ø
16x10
6"Ø
14x12
12x822x1010x12
12x8
14x12
10x6
8"Ø
(E)6"Ø
12x14
(E)14x12 (E)CD
(E)CD
(E)CD(E)CD
(E)CD
(E)CD
12x10
(E)CD
1 1
FCU
12-04
FCU
12-03
FCU
12-02
FCU
12-01
FCU
12-05
FCU
12-06
FCU
12-07
FCU
12-08
FCU
12-09
FCU
12-10
FCU
12-11
12x8 2
12x8 22
10x82
SUMMER
CONSULTANTS
I N C O R P O R A T E D
SUMMER
CONSULTANTS
N
8'0 16' 1/8"=1'-0"
TWELFTH FLOOR PLAN - HVAC
FI
LE
N
RE
F:
PL
OT
D
AT
E:
4/5
/20
2:
:53 P
M
4.2
M-
2-
.D W
G
PROFESSIONAL CERTIFICATION. I HEREBY CERTIFY
THAT THESE DOCUMENTS WERE PREPARED OR
APPROVED BY ME, AND THAT I AM A DULY LICENSED
PROFESSIONAL ENGINEER UNDER THE LAWS OF THE
COORDINATE ALL WORK PRIOR TO THE START OF CONSTRUCTION.
G3. COORDINATE UTILITY SHUTDOWN WITH CONTRACTING OFFICE A
MINIMUM 2-WEEKS IN ADVANCE.
NOTES
1. PROVIDE FAN COIL UNIT. REFER TO SCHEDULES FOR ADDITIONAL
INFORMATION.
2. EXTEND PIPING FROM WALL CAVITY TO FAN COIL UNIT.
3. INDICATED PIPING IS IN CEILING OF LEVEL BELOW.
4. COORDINATE INSTALLATION OF FCU SUCH THAT CONDENSATE
DRAINS VIA GRAVITY ONLY WITHOUT THE NEED FOR A
CONDENSATE PUMP.
45678910
D
E
F
G
(E)HCS&R
(E)CO
TYP. OF 181
(E)1"CWR (E)1-1/2"CWS
(E)1-1/4"CWR
(E)1"CWR (E)1-1/2"CWS
(E)1-1/2"D
(E)2"HCS&R
(E)CWS&R
(E)1"HCR
(E)1"HCR
(E)1"HCR
(E)1"HCS&R
(E)1"D
(E)HCS (E)CO
(E)CO
(E)CO
(E)1"CWS
(E)1"CWS
(E)1"D
(E)3/4"HCS
(E)3/4"CWS&R(E)1"D
1"CWS
(E)1"CWR
(E)1"CWS&R
(E)1"CWS&R
(E)1"CWS&R
(E)3/4"CWS&R
(E)3/4"CWS&R
(E)1"D
TYP. OF 341
(E)CO
(E)3/4"CWS&R
(E)1-1/4"CWR
3(E)2"HCR 3(E)1-1/4"HCR (E)3/4"HCS 3
3 (E)HCR 3
(E)1"D 3
(E)1"D3
(E)1"D3
(E)1"D3
(E)1"D3 3 3(E)1"HCR (E)3/4"HCS
(E)1"D3
3 3(E)1"HCR (E)3/4"HCS
(E)1"D3 3 3
(E)1"CWS&R
(E)1"HCS3
(E)3/4"HCS 3
(E)3/4"HCS 3
(E)HCS
(E)HCR (E)HCR
(E)HCS
(E)1"D3
(E)2"D3
(E)CO
23/4"CWS&R
1"D
(E)3/4"CWS&R(E)1"D
2 3/4"CWS&R
1"D
(E)1'D
2 3/4"CWS&R
1"D
2 3/4"CWS&R1"D
FCU
12-04
FCU
12-03
FCU
12-02
FCU
12-01
FCU
12-05
FCU
12-06
FCU
12-07
FCU
12-08
FCU
12-09
FCU
12-10
FCU
12-11
22 2 2 2
2 2
2 2
1 TYP.OF 18
22222222
FCU
12-E
FCU
12-E
FCU
12-E
1 1
M-905 TYP. OF 35 4
1"CWS&R
3/4"CWS&R
1"D
1"CWS&R
1"D1"CWS&R 3/4"CWS&R
1"D
1"D
1"D
SUMMER
CONSULTANTS
I N C O R P O R A T E D
SUMMER
CONSULTANTS
N
8'0 16' 1/8"=1'-0"
TWELFTH FLOOR PLAN - PIPING
FI
LE
N
RE
F:
PL
OT
D
AT
E:
4/5
/20
2:
:59 P
M
4.2
M-
3-
.D W
G
PROFESSIONAL CERTIFICATION. I HEREBY CERTIFY
THAT THESE DOCUMENTS WERE PREPARED OR
APPROVED BY ME, AND THAT I AM A DULY LICENSED
PROFESSIONAL ENGINEER UNDER THE LAWS OF THE
E
F
G
TYP. OF 42
2 2 2 2 2
2222 2 2 2 2 2
FCU
16-E
1 1
M-905TYP. OF 35
GENERAL NOTES
NOTES
G1. ALL WORK SHALL BE NEW AND PROVIDED UNDER THIS CONTRACT UNLESS
SPECIFICALLY MARKED "EXISTING", "EXIST.", OR "(E)".
G2. VERIFY LOCATION AND DIMENSIONS OF EXISTING EQUIPMENT AND
COORDINATE ALL WORK PRIOR TO THE START OF CONSTRUCTION.
1. PROVIDE FAN COIL UNIT. REFER TO SCHEDULES FOR ADDITIONAL
INFORMATION.
2. EXTEND PIPING FROM WALL CAVITY TO FAN COIL UNIT.
160008
160001
160002
160004 160005
160006 160017
160015
160014
160010
160016 160013
160009
SUMMER
CONSULTANTS
I N C O R P O R A T E D
SUMMER
CONSULTANTS
N
8'0 16' 1/8"=1'-0"
SIXTEENTH FLOOR PLAN - PIPING
160003
160007
160012160011
FI
LE
N
RE
F:
PL
OT
D
AT
E:
4/6
/20
:02
:35 A
M
4.2
M-
4-
.D W
G
PROFESSIONAL CERTIFICATION. I HEREBY CERTIFY
THAT THESE DOCUMENTS WERE PREPARED OR
APPROVED BY ME, AND THAT I AM A DULY LICENSED
PROFESSIONAL ENGINEER UNDER THE LAWS OF THE
(E)ENCLOSURE
REMOVABLE COVER
SS DRAIN PAN
FILTER FRAME WITH
BOTTOM INLET
(E)INTERIOR WALL
(E)WINDOW
(E)SUPPLY GRILLE
FAN SPEED
CONTROLLER
J
LIQUID-TIGHT
CONDUIT (TYP)
FACTORY MOUNTED
ASC CONTROLLER
SS DRAIN PAN
(TYP)
FILTER FRAME
COLLAR
(TYP)
(E)ENCLOSURE GRILLE
FCU
(E)FLOOR (E)FLOOR
3/4"D
3/4"DTS&R DISCHARGE DUCT
CONNECT TO GRILLE
(TYP)
(E)CUSTOM ENCLOSURE
M-905 TYP.11" (VIF)
FCU
J
JUNCTION BOX
(TYP)
DUAL-TEMPERATURE COIL
MAX WIDTH 20"
MAX WIDTH 9"
MAX HEIGHT 22"
MAX DEPTH 9.6"
3 1/2"
SUMMER
CONSULTANTS
I N C O R P O R A T E D
SUMMER
CONSULTANTS
D
PRIMARY
DRAIN PAN
FILTER
DUAL-TEMPERATURE COIL
FAN FAN DT
R
DT
S
1/4" M.A.V.
SEE PLAN FOR
PIPE SIZES
R.A. OPENING
SS DRAIN
PAN
NO SCALE
VERTICAL FAN COIL UNIT PIPING
DETAIL
M-9052
FACTORY PIPED
AND TESTED
4'0 2' 1/2"=1'-0"
VERTICAL FAN COIL UNIT
DETAIL
M-903, M-9041
FAN COIL UNIT SCHEDULE
UNIT NO. TYPE AIRFLOW
(CFM)
O.A.
AIRFLOW
(CFM)
E.S.P.
(IN. W.G.)
MOTOR
HP
ELEC.
DATA
(V/PH/HZ)
MAX AIR P.D. AT MAX
CFM INCLUDING
COOLING COIL
(IN. W.G.)
SOUND
RATING
COOLING
MAX DIMENSIONS
PIPE
RUNOUT
SIZES
(IN.)
NOTESTOTAL CAP.
(MBH)
SENS CAP.
(MBH)
FLOW
(GPM)
MAX P.D.
(FT. W.G.)
FCU-12-01 FC1 300 75 0.4 1/3 277/1/60 0.5 A 6.6 6.2 1.3 5.0 34"Wx34"Lx18"H 3/4"
FCU-12-02 FC1 810 205 0.4 1/3 277/1/60 0.5 B 21.7 20.5 4.3 5.0 48"Wx34"Lx18"H 1"
FCU-12-03 FC1 300 75 0.4 1/3 277/1/60 0.5 A 6.6 6.2 1.3 5.0 34"Wx34"Lx18"H 3/4"
FCU-12-04 FC1 310 80 0.4 1/3 277/1/60 0.5 A 9.8 9.2 1.9 5.0 34"Wx34"Lx18"H 3/4"
FCU-12-05 FC1 1250 315 0.4 1/3 277/1/60 0.5 C 30.5 28.7 6.1 5.0 53"Wx34"Lx18"H 1"
FCU-12-06 FC1 900 225 0.4 1/3 277/1/60 0.5 B 21.7 20.5 4.3 5.0 48"Wx34"Lx18"H 1"
FCU-12-07 FC1 800 200 0.4 1/3 277/1/60 0.5 B 17.4 16.4 3.5 5.0 48"Wx34"Lx18"H 1"
FCU-12-08 FC1 400 100 0.4 1/3 277/1/60 0.5 A 9.8 9.2 1.9 5.0 34"Wx34"Lx18"H 3/4"
FCU-12-09 FC1 1200 300 0.4 1/3 277/1/60 0.5 C 25.5 23.9 5.1 5.0 53"Wx34"Lx18"H 1"
FCU-12-10 FC1 1100 275 0.4 1/3 277/1/60 0.5 C 25.5 23.9 5.1 5.0 53"Wx34"Lx18"H 1"
FCU-12-11 FC1 400 100 0.4 1/3 277/1/60 0.5 A 9.8 9.2 1.9 5.0 34"Wx34"Lx18"H 3/4"
FCU-12-E FC2 220 - 0.0 .125 115/1/60 3.6 - 3.6 3.6 1.0 10 REFER TO DETAIL -
FCU-16-E FC2 220 - 0.0 .125 115/1/160 3.6 - 3.6 3.6 1.0 1.0 REFER TO DETAIL -
NOTES:
A. FC1 - 2 PIPE, HORIZONTAL, CONCEALED WITH FACTORY ENCLOSURE.
FC2 - VERTICAL CONCEALED, ECM MOTOR
B. SEE SOUND REQUIREMENTS SCHEDULE.
C. BASED ON 80°F. D.B. AND 67°F. W.B. ENTERING AIR AND SCHEDULE
CFM AT HIGH SPEED.
D. BASED ON CHILLED WATER ENTERING AT 45°F WITH A 10°F
TEMPERATURE DIFFERENCE.
E. INSTALL PER DETAIL 3 ON SHEET M-905.
F. INSTALL PER DETAILS 1 AND 2 ON SHEET M-905.
G. SET UNITS TO MEDIUM SPEED AT BAS.
H. BASES OF DESIGN: DAIKIN FCVH102 WITH CUSTOM SHORTENED
SUB-BASE (-1.5-INCHES), RAISED CONDENSATE DRAIN CONNECTION
(+1.5-INCHES), RAISED VALVE PACKAGE (+1.0-INCHES), AND BOTTOM
FILTER RETURN OPENING.
I. CONTROL CONTRACTOR'S APPLICATION SPECIFIC CONTROLLER
SHALL BE SHIPPED LOOSE TO THE FAN COIL UNIT MANUFACTURER'S
FACTORY FOR MOUNTING AND WIRING.
J. BASIS OF DESIGN: TRANE MODEL THHP
E
E
E
E
E
E
E
E
E
E
B
F
A
F
SOUND REQUIREMENTS
DESIGNATION IN
FAN COIL UNITS
SCHEDULE
MAXIMUM SOUND POWER LEVELS:
dB re 10^(-12) WATTS
OCTAVE BAND 2 3 4 5 6 7
Hz 125 250 500 1000 2000 4000
A DISCHARGE L 66 62 62 59 57 54
B DISCHARGE L 69 67 65 64 62 59
C DISCHARGE L 80 68 65 65 63 60
NOTES
A. ALL SOUND DATA SHALL BE MEASURED IN ACCORDANCE WITH ARI
STANDARD 880 WITH A 1.0" W.G. PRESSURE DIFFERENCE BETWEEN
INLET AND OUTLET AT MAXIMUM FLOW, UNLESS OTHERWISE NOTED.
N.C.
TWO-PIPE FAN COIL UNIT WITH
COOLING COIL. HANG BOX FROM
STRUCTURE WITH FOUR 3/8"
THREADED RODS AND VIBRATION
ISOLATORS.
SUPPLYRETURN
SECONDARY DRAIN PAN WITH FLOAT
AND AUTOMATIC CUT OUT SWITCH
PROVIDE DUCTED RETURN W/ 2"
ACOUSTICAL LINING. REFER TO PLANS FOR
DUCT SIZING AND CONFIGURATION.
FAN COIL UNIT WITH FACTORY
FURNISHED FILTER AND FILTER FRAME
AUTOMATIC CONTROL VALVE
MAX 5 PSI (35kPa) P.D.
SEE PLANS
FOR PIPE SIZE
COMBINATION FLOW MEASURING
AND BALANCING VALVE
LOW PRESSURE DUCTWORK
SEE FLOOR PLAN FOR
CONFIGURATION AND SIZES
1" COPPER DRAIN. REFER TO
PLANS FOR CONTINUATION
s36" M
IN.
DISCHARGE
AIR SENSOR
M-905
FI
LE
N
RE
F:
PL
OT
D
AT
E:
4/5
/20
2:
:11 P
M
4.2
M-
5.D W
G
PROFESSIONAL CERTIFICATION. I HEREBY CERTIFY
THAT THESE DOCUMENTS WERE PREPARED OR
APPROVED BY ME, AND THAT I AM A DULY LICENSED
PROFESSIONAL ENGINEER UNDER THE LAWS OF THE
STATE OF MARYLAND, LICENSE NO. 45592, EXPIRATION
DATE: 05 JUNE 2022.
G
G
G
G
G
G
G
G
G G
G
G G
H H
I I
E
A
D
NO SCALE
HORIZONTAL FAN COIL UNIT
DETAIL
M-9053
2"MIN
UNIT CASING
FAN COIL/AC UNIT
INSULATED DRAIN PAN
1" CONDENSATE DRAIN
DRAIN
POSSIBLE
AS CLOSE AS
FLOOR
SLOPE
THREADED
UNION
NO SCALE
CONDENSATE DRAIN TRAP
DETAIL
M-9054
J
J
J
J
J
J
J
J
J
J
J
M
ES-#
GENERAL REQUIREMENTS
1. PROVIDE THE FOLLOWING AUTOMATIC ALARM AT OWS EVERY MARCH 1ST AND SEPTEMBER
1ST: "IN CONFORMANCE WITH THE PBS P100, EXECUTIVE ORDERS AND IN ORDER TO SAVE
ENERGY, BUILDING SENSORS MUST BE CALIBRATED AT REGULAR INTERVALS. OUTSIDE AIR,
DUCT, AND UNIT-MOUNTED TEMPERATURE, HUMIDITY, AND ENTHALPY SENSORS SHOULD BE
CALIBRATED ANNUALL.Y C02 SENSORS (DUCT AND/OR ROOM MOUNTED) SHOULD BE
CALIBRATED BI-ANNUALLY."
2. INTEGRATE ALL CONTROL POINTS INDICATED IN THE DESIGN DOCUMENTS WITHIN THE
EXISTING FRONT-END BUILDING AUTOMATION SYSTEM AT THE FALLON FEDERAL BUILDING.
2.1. DEMOLISH EXISTING PEMs LOCATED WITHIN AREAS OF CONSTRUCTION ON FAN
POWERED VAV BOXES AND FAN COIL UNITS AS INDICATED ON DEMOLITION PLANS.
2.2. INTERCEPT PEM WIRING BUS BETWEEN GLOBAL CONROL MODULE (GEM), AND WIRE ALL
NEW FAN POWERED VAV BOXES / FAN COIL UNITS TO THE EXISTING BUS. EXTEND THE
BUS TO EACH NEW TERMINAL UNIT, AND DAISY-CHAIN THE EQUIPMENT APPLICATION
SPECIFIC CONTROLLERS TOGETHER. WIRE AND PROGRAM ALL NEW TERMINAL UNITS TO
OPERATE PER THE SEQUENCE OF OPERATION.
2.3. UPDATE THE EXISTING FRONT-END OPERATOR WORKSTATION GRAPHICS AND ALARMS
PER SEQUENCE OF OPERATION TO REMOVE DEMOLISHED EQUIPMENT AND REFLECT
NEW EQUIPMENT.
2.4. REWIRE AND REPROGRAM EXISTING TO REMAIN TERMINAL EQUIPMENT ON MODIFIED
BUS. ALL EXISTING TO REMAIN EQUIPMENT SHALL OPERATE AS BEFORE.
DUCT MOUNTED ELECTRONIC TEMPERATURE SENSOR WITH
RIGID STEM ELEMENT. PROVIDE PER DETAIL 1/M-905/M-905.
PIPE MOUNTED INSERTION TYPE ELECTRONIC
TEMPERATURE SENSOR WITH WELL.
WALL-MOUNTED ELECTRONIC TEMPERATURE SENSOR
CURRENT SWITCH
END SWITCH
BINARY INPUT OR OUTPUT POINT
ANALOG INPUT OR OUTPUT POINT
NETWORK CONNECTION
THERMOMETER.
SYMBOLS & ABREVIATIONS
AI ANALOG INPUT
ANALOG OUTPUTAO
BI BINARY INPUT
BINARY OUTPUTBO
CLG COOLING
CHANGE OF VALUECOV
Cx COMMISSIONING
HEATINGHTG
I/O INPUT/OUTPUT
NETWORK VARIABLE INPUTNVI
NVO NETWORK VARIABLE OUTPUT
SETPOINTSP
HAND-OFF-AUTO SWITCH
MOTOR
NORMALLY OPEN CONTACTS
NORMALLY CLOSED CONTACTS
RELAY COIL
STARTER HOLDING COIL
THERMAL MOTOR SWITCH
PNEUMATIC TUBING
EXISTING PNEUMATIC TUBING
MOTOR STARTER
FAN OR PUMP, BY APPLICATION
EMERGENCY HVAC OFF (SYSTEM VARIABLE)
R#
OPPOSED BLADE DAMPER.D-#
D-# PARALLEL BLADE DAMPER.
A-#
DAMPER OR VALVE ACTUATOR.
2 WAY CONTROL VALVE (BALL OR GLOBE AS SPECIFIED).
V-#
3 WAY CONTROL VALVE (BALL OR GLOBE AS SPECIFIED).
V-#
HYDRONIC PIPING
AIR OR WATER FLOW PATH
FILTER OR COIL (AS LABELED)
JUNCTION BOX AND COVER
CONDUIT TO
FIELD PANEL
FLEXIBLE METAL
CONDUIT TO
OTHER DEVICES,
IF NEEDED
FLEXIBLE CONDUIT BETWEEN
JUNCTION BOX AND DEVICE
TO ALLOW REMOVAL, MINIMUM
LENGTH OF 3 FT.
PROVIDE BRACKET IN
ACCORDANCE WITH
NOTE: DO NOT USE DEVICE AS A JUNCTION BOX. DO NOT
WIRE THRU DEVICE TO OTHER DEVICES
18 GAUGE GALVANIZED SHEET METAL
BRACKET ATTACHED TO DUCT WITH
FOUR #8 x 0.75" SHEET METAL SCREWS
PROVIDE RIGID FIBERGLASS INSULATION
WITH VAPOR BARRIER, THICKNESS TO
MATCH ADJACENT INSULATION
SEAL VAPOR TIGHT WITH
VAPOR BARRIER MASTIC
ATTACH DEVICE TO BRACKET
WITH SHEET METAL SCREWS
PROVIDE RIGID FIBERGLASS INSULATION
WITH VAPOR BARRIER, THICKNESS TO
MATCH ADJACENT INSULATION
A O
H
TS-#
TS-#
CS-#
EHO
RS-#
BUTTERFLY VALVE.
SYMBOLS & ABBREVIATIONS
M-905
NO SCALE
DUCT MOUNTED SENSOR
DETAIL
NO SCALE
DEVICE MOUNTING BRACKET
DETAIL
M-9062
SUMMER
CONSULTANTS
I N C O R P O R A T E D
SUMMER
CONSULTANTS
FI
LE
N
RE
F:
PL
OT
D
AT
E:
4/5
/20
2:
:15 P
M
4.2
M-
6.D W
G
PROFESSIONAL CERTIFICATION. I HEREBY CERTIFY
THAT THESE DOCUMENTS WERE PREPARED OR
APPROVED BY ME, AND THAT I AM A DULY LICENSED
PROFESSIONAL ENGINEER UNDER THE LAWS OF THE
FLOW DIAGRAM
C
C
FAN
V-1 N.C.
GENERAL
FANS SHALL BE STARTED AND STOPPED BY BAS TIME CLOCK FUNCTION.
FAN SPEED SHALL BE CONTROLLED BY A MANUAL THREE SPEED SWITCH IN THE FCU CABINET.
ON A RISE IN ROOM TEMPERATURE ABOVE SETPOINT, AS SENSED BY WALL-MOUNTED SENSOR TS-RM, COOLING COIL VALVE V-1 SHALL MODULATE OPEN. ON A FALL IN TEMPERATURE THE REVERSE SHALL OCCUR.
SEQUENCE OF OPERATION
HORIZONTAL FAN COIL UNIT
OCCUPIED UNOCCUPIED
COOLING 80°F75°F
FAN COIL UNIT POINTS LIST
POINT NAME DESCRIPTION NETWORK
CONNECTION I/O TYPE
ALARMS TRENDING
FAIL
WARNING LIMIT Cx
FREQUENCY
OPERATING
FREQUENCYLOW HIGH LOW HIGH
FCU-X
FCU CONTROLLER X
ROOM TEMPERATURE AI 60°F 85°F 55°F 90°F 5min 15min
SUPPLY TEMPERATURE AI 80°F 5min 15min
CHILLED WATER CONTROL
VALVE AO 5min 15min
DRAIN PAN FLOAT SWITCH BI X COV COV
ALL POINTS INCLUDED ON LIST SHALL BE SHOWN ON THE OWS GRAPHICS.
TEMPERATURE
SETPOINT
SCHEDULE
APPLICATION
SPECIFIC
CONTROLLER
FLOW DIAGRAM
FAN
V-1 N.C.
GENERAL
FANS SHALL BE STARTED AND STOPPED BY BAS TIME CLOCK FUNCTION.
FAN SPEED SHALL BE CONTROLLED BY THE BAS THROUGH THE ASC CONTROLLER.
THE PERIMETER DUAL-TEMPERATURE FAN COIL UNITS ARE CONTROLLED THROUGH THE BUILDING AUTOMATION SYSTEM, AND ARE INDEXED TO HEATING OR COOLING MODE BASED UPON POLLING OF THE NORTH, SOUTH, EAST, OR WEST EXPOSURE. WHEN A MAJORITY OF THE UNITS ON ANY EXPOSURE CALL FOR HEATING OR COOLING, THE
ENTIRE TOWER'S EXPOSURE IS INDEXED TO THE MAJORITY'S MODE.
COOLING MODE: ON A RISE IN ROOM TEMPERATURE ABOVE SETPOINT, AS SENSED BY RETURN AIR SENSOR TS-RA, DUAL-TEMPERATURE COIL VALVE V-1 SHALL MODULATE OPEN. ON A FALL IN TEMPERATURE THE REVERSE
SHALL OCCUR.
HEATING MODE: ON A FALL IN ROOM TEMPERATURE ABOVE SETPOINT, AS SENSED BY RETURN AIR SENSOR TS-RA, DUAL-TEMPERATURE COIL VALVE V-1 SHALL MODULATE OPEN. ON A RISE IN TEMPERATURE THE REVERSE
SHALL OCCUR.
SEQUENCE OF OPERATION
VERTICAL FAN COIL UNIT
OCCUPIED UNOCCUPIED
COOLING 80°F75°F
FAN COIL UNIT POINTS LIST
POINT NAME DESCRIPTION NETWORK
CONNECTION I/O TYPE
ALARMS TRENDING
FAIL
WARNING LIMIT Cx
FREQUENCY
OPERATING
FREQUENCYLOW HIGH LOW HIGH
FCU-X
FCU CONTROLLER X
RETURN AIR TEMPERATURE AI 60°F 85°F 55°F 90°F 5min 15min
FAN STATUS X COV COV
DUAL TEMPERATURE WATER
CONTROL VALVE AO 5min 15min
ALL POINTS INCLUDED ON LIST SHALL BE SHOWN ON THE OWS GRAPHICS.
TEMPERATURE
SETPOINT
SCHEDULE
CAT6 BACNET
MS/TP FLOOR
NETWORK
APPLICATION
SPECIFIC
CONTROLLER
D
T
C
HEATING 65°F70°F
FL
TS-RM
TS-SA TS-RA
FACTORY WIRED
CAT6 BACNET
MS/TP FLOOR
NETWORK
TWELFTH OR SIXTEENTH FLOOR
(E)FCU (E)FCU (E)FCU
(E)FIBER OPTIC NETWORK
CONTROLS REPEATER
THIRTEENTH FLOOR OR PENTHOUSE
(E) FIBER OPTIC RISER DOWN
TO BUILDING MANAGERS
OFFICE ON THIRD FLOOR
(E)FIBER OPTIC
RISER UP TO
ENGINEERS OFFICE
IN PENTHOUSE
(E)FCU
REWIRE EXISTING FCUs
FROM EXISTING FCU
LOCAL AREA NETWORK
CONTROLS SYSTEM RISER DIAGRAM
(TWELTH & 16TH FLOORS)
NEW WORK
TWELFTH OR SIXTEENTH FLOOR
(E)FCU (E)FCU (E)FCU
(E)FIBER OPTIC NETWORK
CONTROLS REPEATER
(E)STANDALONE
DIGITAL CONTROLLER
THIRTEENTH FLOOR OR PENTHOUSE
(E) FIBER OPTIC RISER DOWN
TO BUILDING MANAGERS
OFFICE ON THIRD FLOOR
(E)FIBER OPTIC
RISER UP TO
ENGINEERS OFFICE
IN PENTHOUSE
FCU(E)FCU
DISCONNECT SERIES
WIRED FCUs FROM
EXISTING FCU LOCAL
AREA NETWORK
FCUFCU
DEMOLITION
FCU FCUFCUFCU
BACNET MS/TP
(E)JACE WITH
MULTIPLE RS-45
CHANNELS
(E)CAT6 RISER TO GSA
NETWORK SWITCH
REFER TO PLANS FOR NUMBER
OF FCUs ON EACH FLOOR
(E)STANDALONE
DIGITAL CONTROLLER
SUMMER
CONSULTANTS
I N C O R P O R A T E D
SUMMER
CONSULTANTS
FI
LE
N
RE
F:
PL
OT
D
AT
E:
4/5
/20
8:
:18 P
M
4.2
M-
7.D W
G
PROFESSIONAL CERTIFICATION. I HEREBY CERTIFY
THAT THESE DOCUMENTS WERE PREPARED OR
APPROVED BY ME, AND THAT I AM A DULY LICENSED
PROFESSIONAL ENGINEER UNDER THE LAWS OF THE
SUMMER
CONSULTANTS
I N C O R P O R A T E D
SUMMER
CONSULTANTS
ELECTRICAL SYMBOLS
S
ELECTRICAL SYMBOLS CONTINUED
J JUNCTION BOX 4" SQUARE X 2-1/8" DEEP GALVANIZED PRESSED STEEL,
MOUNTED ABOVE SUSPENDED TILE CEILING.
EM2 PANEL NAME TO WHICH CIRCUITS RUN.
AS SHOWN ABOVE.
IN WALLS AND CEILING, ALL OTHER CHARACTERISTICS SAME
BRANCH CIRCUIT CONDUIT AND CONDUCTORS RUN CONCEALED
#10
EM2
#10
1,3,5
WIRE SIZE IN AWG. SIZE NOT SHOWN INDICATES #12 AWG.
CIRCUIT BREAKERS IN PANEL SERVING THESE CIRCUITS.
EM2
1,3,5
#10
HOME RUN TO PANEL. NUMBER OF ARROWS INDICATE
2 CIRCUIT CONDUCTORS PLUS A GROUND CONDUCTOR.
CONDUCTORS IN RACEWAY. NO SLASH MARKS INDICATE
NUMBER OF SLASH MARKS INDICATE THE NUMBER OF
GREEN GROUND CONDUCTOR RUN IN RACEWAY.
THE NUMBER OF CIRCUITS.
CEILING MOUNTED OCCUPANCY SENSOR, COMBINATION ULTRASONIC/ PASSIVE
INFRARED (PIR) DEVICE WITH ADJUSTABLE TIME DELAY 5 TO 30 MINUTES.
SWITCH, FLUSH TUMBLER TYPE, SINGLE POLE, 20 AMPERE, 120/277V, A.C.
ONLY, RECESS MOUNTED AT 48" ABOVE FINISHED FLOOR.
DUPLEX RECEPTACLE, 20 AMPERE, 125 VOLT GROUNDING TYPE, NEMA 5-20R
CONFIGURATION, RECESS MOUNTED IN 4" SQUARE x 2-1/2" DEEP PRESSED
STEEL JUNCTION BOX AT 6" ABOVE FINISHED FLOOR.
SECURITY CARD READER. RECESS MOUNTED AT 48" ABOVE FINISHED FLOOR.CR
OS
ABBREVIATIONS
AMPERES.A
AF
AFF
AT
ATS
AWG
BLDG.
C/B
EC
EMT
(E),EX.
(ETR)
FLA
GFCI
GFI GROUND FAULT INTERRUPTER.
GOVERNMENT FURNISHED, CONTRACTOR INSTALLED.
FULL LOAD AMPERES.
EXISTING TO REMAIN.
EXISTING.
ELECTRICAL METALLIC TUBING.
EMPTY CONDUIT.
CIRCUIT BREAKER.
BUILDING.
AMERICAN WIRE GAUGE.
AUTOMATIC TRANSFER SWITCH.
TRIP SIZE IN AMPERES.
ABOVE FINISHED FLOOR.
FRAME SIZE IN AMPERES.
GRD.
KAIC
KW KILO-WATTS.
THOUSAND AMPERE INTERRUPTING CAPACITY.
GROUND CONDUCTOR.
M.L.O.
N.C.
N.E.C.
NEMA
NFSS
P
PH.
PVC
RGS
U.L.
V
WP WEATHERPROOF, OR NEMA 3R ENCLOSURE.
VOLTAGE.
UNDERWRITER'S LABORATORIES.
RIGID GALVANIZED STEEL.
POLY-VINYL CHLORIDE.
NUMBER OF PHASES.
NUMBER OF POLES.
NON-FUSED SAFETY SWITCH.
NATIONAL ELECTRICAL MANUFACTURER'S ASSOCIATION.
NATIONAL ELECTRICAL CODE.
NORMALLY CLOSED.
MAIN LUGS ONLY.
CEILING MOUNTED SPEAKER.SP
GFI DUPLEX RECEPTACLE WITH GROUND FAULT CIRCUIT INTERRUPTER AND
NEMA 3R IN-USE WEATHERPROOF ENCLOSURE, 20 AMPERE, 125 VOLT
GROUNDING TYPE, NEMA 5-20R CONFIGURATION, SURFACE MOUNTED IN 4"
SQUARE x 2-1/8" DEEP PRESSED STEEL JUNCTION BOX AT 18" ABOVE
FINISHED FLOOR.
WP
GFI DUPLEX RECEPTACLE WITH GROUND FAULT CIRCUIT INTERRUPTER, 20
AMPERE, 125 VOLT GROUNDING TYPE, NEMA 5-20R CONFIGURATION, RECESS
MOUNTED IN 4" SQUARE x 2-1/8" DEEP PRESSED STEEL JUNCTION BOX AT 8"
ABOVE COUNTERTOP.
BRANCH CIRCUIT CONDUIT AND CONDUCTORS RUN EXPOSED. SIZE IN
ACCORDANCE WITH N.E.C. RACEWAY SHALL BE MINIMUM 3/4"
CONDUIT, AND WIRE SHALL BE MINIMUM SIZE #12 AWG COPPER WITH
THHN INSULATION, UNLESS OTHER SIZES ARE SPECIFICALLY NOTED.
HEAVY DUTY ENCLOSED SAFETY SWITCH, SEE MOTOR AND EQUIPMENT
SCHEDULE FOR SIZES AND CHARACTERISTICS.
MOTOR, SEE MOTOR AND EQUIPMENT SCHEDULE FOR SIZES AND
CHARACTERISTICS.
P PUSH PLATE FOR AUTOMATIC DOOR OPENER. RECESS MOUNTED AT 36" ABOVE
FINISHED FLOOR.
ENCLOSED CIRCUIT BREAKER, SEE MOTOR AND EQUIPMENT
SCHEDULE FOR SIZES AND CHARACTERISTICS.
QUADRAPLEX RECEPTACLE, 20 AMPERE, 125 VOLT GROUNDING TYPE, NEMA
5-20R CONFIGURATION, RECESS MOUNTED IN 4" SQUARE x 2-1/8" DEEP
PRESSED STEEL JUNCTION BOX AT 18" ABOVE FINISHED FLOOR.
FI
LE
N
RE
F:
PL
OT
D
AT
E:
4/6
/20
:02
:43 A
M
4.2
E-
1.D W
G
PROFESSIONAL CERTIFICATION. I HEREBY CERTIFY
THAT THESE DOCUMENTS WERE PREPARED OR
APPROVED BY ME, AND THAT I AM A DULY LICENSED
PROFESSIONAL ENGINEER UNDER THE LAWS OF THE
STATE OF MARYLAND, LICENSE NO. 49295, EXPIRATION
DATE: 12 MAY 2022.
SHEET SYMBOLS
BREAKLINE
CL
NOTE REFERENCE NUMBER.
ROOM NUMBER DESIGNATION.
COLUMN LINE NUMBER.
DRAWING REVISION NUMBER.
CENTER LINE.
CONDUIT UP.
CONDUIT DOWN.DN
UP
DELTA CONFIGURATION.
WYE GROUNDING CONFIGURATION.
PHASE.Ø
NORTH ARROW
ARROW INDICATES TRUE NORTH
AND/OR PROJECT NORTHN
E101
N
8'0 1/8"=1'-0"
UNIQUE PLAN OR DETAIL
NUMBER ON THIS DRAWING
NAME OF PLAN OR DETAIL
ALL DRAWINGS WHERE
DETAIL IS REFERENCED
GRAPHIC SCALE OF
PLAN OR DETAIL
2-PART REFERENCE DETAIL IDENTIFICATION:
SHEET NUMBER WHERE
DETAIL/SECTION IS DRAWN
NUMBER INDICATES
DETAIL/SECTION
FLOOR PLAN
ED102, E-1022
FLOOR PLAN AND DETAIL TITLES:
NOTE REFERENCE NUMBER,
BOUNDARY/EXTENT AS INDICATED BY ARROW.
CONDUIT TURN DOWN.
MOTOR AND EQUIPMENT SCHEDULE
EQUIPMENT NAME HP KW RATED
VOLT. PHASE FLA
MOTOR CONTROLLER FEEDER LOCAL SWITCH
REMARKS
TYPE LOCAL CONTROL
WIRE
CONDUIT
TYPE
①
FRAME
SIZE POLES
NO. SIZE GRD.
FCU-12-01 1/3 - 277 1Ø 2.6A SEE MECHANICAL 2 #12 #12 3/4" MRT 15A 2
FCU-12-02 1/3 - 277 1Ø 2.6A SEE MECHANICAL 2 #12 #12 3/4" MRT 15A 2
FCU-12-03 1/3 - 277 1Ø 2.6A SEE MECHANICAL 2 #12 #12 3/4" MRT 15A 2
FCU-12-04 1/3 - 277 1Ø 2.6A SEE MECHANICAL 2 #12 #12 3/4" MRT 15A 2
FCU-12-05 1/3 - 277 1Ø 2.6A SEE MECHANICAL 2 #12 #12 3/4" MRT 15A 2
FCU-12-06 1/3 - 277 1Ø 2.6A SEE MECHANICAL 2 #12 #12 3/4" MRT 15A 2
FCU-12-07 1/3 - 277 1Ø 2.6A SEE MECHANICAL 2 #12 #12 3/4" MRT 15A 2
FCU-12-08 1/3 - 277 1Ø 2.6A SEE MECHANICAL 2 #12 #12 3/4" MRT 15A 2
FCU-12-09 1/3 - 277 1Ø 2.6A SEE MECHANICAL 2 #12 #12 3/4" MRT 15A 2
FCU-12-10 1/3 - 277 1Ø 2.6A SEE MECHANICAL 2 #12 #12 3/4" MRT 15A 2
FCU-12-11 1/3 - 277 1Ø 2.6A SEE MECHANICAL 2 #12 #12 3/4" MRT 15A 2
FCU-12-E - - 115 1Ø 1.2A SEE MECHANICAL 2 #12 #12 3/4" MRT 15A 2
FCU-16-E - - 115 1Ø 1.2A SEE MECHANICAL 2 #12 #12 3/4" MRT 15A 2
NOTES:
① NFSS - NON FUSED SAFETY SWITCH ② SEE MECHANICAL DRAWINGS FOR AUXILIARY
FSS - FUSED SAFETY SWITCH CONTACT REQUIREMENTS.
MRT - MOTOR RATED TOGGLE SWITCH
INT - INTEGRAL WITH MOTOR CONTROLLER
S
M
MOTOR-RATED TOGGLE SWITCH, 2-POLE, NON-REVERSING RATED FOR 1
HORSEPOWER (16 AMPERES CONTINUOUS CURRENT) @ 115-230/277 VOLTS IN
NEMA 1 ENCLOSURE WITH LOCKABLE TOGGLE GUARD. MOUNT ABOVE CEILING
ON STEEL SUPPORT CHANNEL ADJACENT TO EQUIPMENT SERVED.
1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
1 1 1 1 1 11 1 1 1 1 11 1 1 1 1 11 1 1 1 1 11 1 1 1 1 11 1 1 1
FCU 1
FCU1
FCU 1 FCU 1
FCU 1
FCU 1
FCU 1
FCU 1
FCU
1 FCUFCU 1
2 2
2 2 2
22 2
2 2
2 2 2
(E)IT ROOM
45678910
1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
D
E
F
G
SUMMER
CONSULTANTS
I N C O R P O R A T E D
SUMMER
CONSULTANTS
GENERAL NOTES
G1. VERIFY LOCATION AND DIMENSIONS OF EXISTING EQUIPMENT AND
COORDINATE ALL WORK PRIOR TO THE START OF CONSTRUCTION.
G2. DEMOLITION DEFINITION: DISCONNECTION AND REMOVAL OF ASSOCIATED
CONDUCTORS SHALL CONSIST OF THE REMOVAL OF THE CONDUCTORS BACK
TO THE NEXT EXISTING DEVICE TO REMAIN. NEW CONDUIT AND
CONDUCTORS SHALL BE PROVIDED TO RECONNECT ANY EXISTING TO
REMAIN DEVICES INTERRUPTED BY THE DEMOLITION UNDER THIS PROJECT.
NOTES
1. DISCONNECT HVAC EQUIPMENT. RETAIN EXISTING CONDUCTOR FOR REUSE.
2. CAREFULLY DISCONNECT AND REMOVE LUMINAIRE TO ACCOMMODATE
DEMOLITION AND INSTALLATION OF HVAC EQUIPMENT. RETAIN LUMINAIRE
AND EXISTING CIRCUIT FOR REUSE.
N
8'0 16' 1/8"=1'-0"
TWELFTH FLOOR PLAN - DEMOLITION
FI
LE
N
RE
F:
PL
OT
D
AT
E:
4/6
/20
:02
:51 A
M
4.2
ED
2-
.D W
G
PROFESSIONAL CERTIFICATION. I HEREBY CERTIFY
THAT THESE DOCUMENTS WERE PREPARED OR
APPROVED BY ME, AND THAT I AM A DULY LICENSED
PROFESSIONAL ENGINEER UNDER THE LAWS OF THE
STATE OF MARYLAND, LICENSE NO. 49295, EXPIRATION
DATE: 12 MAY 2022.
E
F
G
1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
E-401
E-401
E-401
E-401
SUMMER
CONSULTANTS
I N C O R P O R A T E D
SUMMER
CONSULTANTS
GENERAL NOTES
G1. VERIFY LOCATION AND DIMENSIONS OF EXISTING EQUIPMENT
AND COORDINATE ALL WORK PRIOR TO THE START OF
CONSTRUCTION.
G2. DEMOLITION DEFINITION: DISCONNECTION AND REMOVAL OF
ASSOCIATED CONDUCTORS SHALL CONSIST OF THE REMOVAL OF
THE CONDUCTORS BACK TO THE NEXT EXISTING DEVICE TO
REMAIN. NEW CONDUIT AND CONDUCTORS SHALL BE PROVIDED
TO RECONNECT ANY EXISTING TO REMAIN DEVICES INTERRUPTED
BY THE DEMOLITION UNDER THIS PROJECT.
NOTES
1. DISCONNECT FAN COIL UNIT. RETAIN EXISTING CONDUCTORS FOR
REUSE.
N
8'0 16' 1/8"=1'-0"
SIXTEENTH FLOOR PLAN - POWER DEMOLITION
FI
LE
N
RE
F:
PL
OT
D
AT
E:
4/6
/20
:02
:59 A
M
4.2
ED
3-
.D W
G
PROFESSIONAL CERTIFICATION. I HEREBY CERTIFY
THAT THESE DOCUMENTS WERE PREPARED OR
APPROVED BY ME, AND THAT I AM A DULY LICENSED
PROFESSIONAL ENGINEER UNDER THE LAWS OF THE
1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
1 1 1 1 1 11 1 1 1 1 11 1 1 1 1 11 1 1 1 1 11 1 1 1 1 11 1 1 1
FCU 12-01
FCU 12-02
FCU 12-03 FCU 12-04
FCU 12-05
FCU 12-06
FCU 12-07
FCU 12-08
FCU 12-09
FCU 12-10
FCU 12-11
2 2
2 2 2
2 2 2
22 2
2 2
2 2 2
S
M
S
M
S
M
S
M
S
M
S
M
S
M
S
M
S
MS
M
S
M
1 1
FCU 12-E (TYP. OF 18)
FCU 12-E (TYP. OF 18)
FCU 12-E (TYP. OF 34)
45678910
1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
D
E
F
G
SUMMER
CONSULTANTS
I N C O R P O R A T E D
SUMMER
CONSULTANTS
GENERAL NOTES
G1. ALL WORK SHALL BE NEW AND PROVIDED UNDER THIS CONTRACT
UNLESS SPECIFICALLY MARKED "EXISTING", "EXIST.", OR "(E)".
G2. VERIFY LOCATION AND DIMENSIONS OF EXISTING EQUIPMENT AND
COORDINATE ALL WORK PRIOR TO THE START OF CONSTRUCTION.
NOTES
1. CONNECT TO EXISTING CIRCUITS RETAINED UNDER DEMOLITION.
SEE MOTOR AND EQUIPMENT SCHEDULE FOR FEEDER
CHARACTERISTICS AND REQUIREMENTS.
2. INSTALL EXISTING LUMINAIRE. CONNECT TO EXISTING CIRCUIT
RETAINED UNDER DEMOLITION.
N
8'0 16' 1/8"=1'-0"
TWELFTH FLOOR PLAN - POWER
FI
LE
N
RE
F:
PL
OT
D
AT
E:
4/6
/20
:03
:07 A
M
4.2
E-
2-
.D W
G
PROFESSIONAL CERTIFICATION. I HEREBY CERTIFY
THAT THESE DOCUMENTS WERE PREPARED OR
APPROVED BY ME, AND THAT I AM A DULY LICENSED
PROFESSIONAL ENGINEER UNDER THE LAWS OF THE
E
F
G
1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
E-401
E-401
E-401
E-401
FCU 16-E (TYP. OF 35)
FCU 16-E (TYP. OF 8)
SUMMER
CONSULTANTS
I N C O R P O R A T E D
SUMMER
CONSULTANTS
GENERAL NOTES
G1. ALL WORK SHALL BE NEW AND PROVIDED UNDER THIS
CONTRACT UNLESS SPECIFICALLY MARKED "EXISTING",
"EXIST.", OR "(E)".
G2. VERIFY LOCATION AND DIMENSIONS OF EXISTING EQUIPMENT
AND COORDINATE ALL WORK PRIOR TO THE START OF
CONSTRUCTION.
NOTES
1. CONNECT TO EXISTING CIRCUITS RETAINED UNDER
DEMOLITION. SEE MOTOR AND EQUIPMENT SCHEDULE FOR
FEEDER CHARACTERISTICS AND REQUIREMENTS.
160008
160001
160002
160004
160003 160005
160006
160007
160018
160015160014
160010 160009
160016
160011160019
160012
160013
N
8'0 16' 1/8"=1'-0"
SIXTEENTH FLOOR PLAN - POWER
FI
LE
N
RE
F:
PL
OT
D
AT
E:
4/6
/20
:03
:14 A
M
4.2
E-
3-
.D W
G
PROFESSIONAL CERTIFICATION. I HEREBY CERTIFY
THAT THESE DOCUMENTS WERE PREPARED OR
APPROVED BY ME, AND THAT I AM A DULY LICENSED
PROFESSIONAL ENGINEER UNDER THE LAWS OF THE
(E) PANEL
12U1
(E) PANEL
12PS
ELEC. RM
(E) ECB
12P2
(E) ECB
12P1
(E) XFMR
(E) BUS DUCT
(E) XFMR
(E) PANEL
12EP
(E) ECB
12EP
(E) PANEL
16P2
166E4
ELEC. RM
PANEL
16PS
F
(E) PANEL
16EP
(E) PANEL
16EL
(E) PANEL
16L1
ELEC. RM
168E3
(E) PANEL
16P4
(E) PANEL
16P3
ELEC. RM
161E1
(E) PANEL
16L2
(E) PANEL
16P1
166E1
ELEC. RM
E
(E) PANEL
12L2
(E) PANEL
12P4
(E) ECB
12P3
ELEC. RM (E) PANEL
12U2
(E) PANEL
12P3
(E) ECB
12P4
(E) XFMR
(E) BUS DUCT
PANEL
12P4A
(E) PANEL
12P1
ELEC. RM
(E) PANEL
12P1A
E
(E) PANEL
12P2
ELEC. RM
(E)NAC F
SUMMER
CONSULTANTS
I N C O R P O R A T E D
SUMMER
CONSULTANTS
G1. ALL WORK SHALL BE NEW AND PROVIDED UNDER THIS CONTRACT UNLESS
SPECIFICALLY MARKED "EXISTING", "EXIST.", OR "(E)".
G2. VERIFY LOCATION AND DIMENSIONS OF EXISTING EQUIPMENT AND
COORDINATE ALL WORK PRIOR TO THE START OF CONSTRUCTION.
GENERAL NOTES
FI
LE
N
RE
F:
PL
OT
D
AT
E:
4/6
/20
:03
:28 A
M
4.2
E-
4.D W
G
PROFESSIONAL CERTIFICATION. I HEREBY CERTIFY
THAT THESE DOCUMENTS WERE PREPARED OR
APPROVED BY ME, AND THAT I AM A DULY LICENSED
PROFESSIONAL ENGINEER UNDER THE LAWS OF THE
STATE OF MARYLAND, LICENSE NO. 49295, EXPIRATION
DATE: 12 MAY 2022.
8'0 4' 1/4"=1'-0"
ELEC. ROOM 1223
ED902,E-9021
8'0 4' 1/4"=1'-0"
ELEC. ROOM 1237
ED902,E-9022
8'0 4' 1/4"=1'-0"
ELEC. ROOM 1201
ED902,E-9023
8'0 4' 1/4"=1'-0"
ELEC. ROOM 1209
ED902,E-9024
8'0 4' 1/4"=1'-0"
ELEC. ROOM 161E1
ED903,E-9035
8'0 4' 1/4"=1'-0"
ELEC. ROOM 168E3
ED903,E-9036
8'0 4' 1/4"=1'-0"
ELEC. ROOM 166E1
ED903,E-9037
8'0 4' 1/4"=1'-0"
ELEC. ROOM 166E4
ED903,E-9038
File details come from the government source that posted it. Updated .