This notice provides details for a construction contract opportunity for Veteran Benefits Administration Regional Office renovations. The General Services Administration seeks a construction firm to complete interior renovations at the George H. Fallon Federal Building in Baltimore, Maryland. Renovations include demolition of existing offices and construction of new tenant layouts comprising offices, workstations, storage areas, and conference rooms. Mechanical, electrical, and fire protection system work are also required. The project will be completed over four phases while maintaining building occupancy. A competitive proposal process will be conducted, with technical factors significantly more important than price in the evaluation. Offerors should submit technical and price proposals by January 2022. The contract award is expected in early 2022 and has a performance period of 1,062 calendar days. The estimated value is over $10 million. The set-aside is for small businesses, and the applicable NAICS code is 236220.
View the file
Other files
Show all 24
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
(E)ENCLOSURE
REMOVABLE COVER
SS DRAIN PAN
FILTER FRAME WITH
BOTTOM INLET
(E)INTERIOR WALL
(E)WINDOW
(E)SUPPLY GRILLE
FAN SPEED
CONTROLLER
J
LIQUID-TIGHT
CONDUIT (TYP)
FACTORY MOUNTED
ASC CONTROLLER
SS DRAIN PAN
(TYP)
FILTER FRAME
COLLAR
(TYP)
(E)ENCLOSURE GRILLE
FCU
(E)FLOOR (E)FLOOR
3/4"D
3/4"DTS&R
DISCHARGE DUCT
CONNECT TO GRILLE
(TYP)
(E)CUSTOM ENCLOSURE
M-905 TYP.11" (VIF)
FCU
J
JUNCTION BOX
(TYP)
DUAL-TEMPERATURE COIL
MAX WIDTH 20"
MAX WIDTH 9"
MAX HEIGHT 22"
MAX DEPTH 9.6"
3 1/2"
FACTORY MOUNTED MOTOR
RATED TOGGLE DISCONNECT
SUMMER
CONSULTANTS
I N C O R P O R A T E D
SUMMER
CONSULTANTS
D
PRIMARY
DRAIN PAN
FILTER
DUAL-TEMPERATURE COIL
FAN FAN DT
R
DT
S
1/4" M.A.V.
SEE PLAN FOR
PIPE SIZES
R.A. OPENING
SS DRAIN
PAN
NO SCALE
VERTICAL FAN COIL UNIT PIPING
DETAIL
M-9052
FACTORY PIPED
AND TESTED
4'0 2' 1/2"=1'-0"
VERTICAL FAN COIL UNIT
DETAIL
M-903, M-9041
FAN COIL UNIT SCHEDULE
UNIT NO. TYPE AIRFLOW
(CFM)
O.A.
AIRFLOW
(CFM)
E.S.P.
(IN. W.G.)
MOTOR
HP
ELEC.
DATA
(V/PH/HZ)
MAX AIR P.D. AT MAX
CFM INCLUDING
COOLING COIL
(IN. W.G.)
SOUND
RATING
COOLING
MAX DIMENSIONS
PIPE
RUNOUT
SIZES
(IN.)
NOTESTOTAL CAP.
(MBH)
SENS CAP.
(MBH)
FLOW
(GPM)
MAX P.D.
(FT. W.G.)
FCU-12-01 FC1 300 75 0.4 1/3 277/1/60 0.5 A 6.6 6.2 1.3 5.0 34"Wx34"Lx18"H 3/4"
FCU-12-02 FC1 810 205 0.4 1/3 277/1/60 0.5 B 21.7 20.5 4.3 5.0 48"Wx34"Lx18"H 1"
FCU-12-03 FC1 300 75 0.4 1/3 277/1/60 0.5 A 6.6 6.2 1.3 5.0 34"Wx34"Lx18"H 3/4"
FCU-12-04 FC1 310 80 0.4 1/3 277/1/60 0.5 A 9.8 9.2 1.9 5.0 34"Wx34"Lx18"H 3/4"
FCU-12-05 FC1 1250 315 0.4 1/3 277/1/60 0.5 C 30.5 28.7 6.1 5.0 53"Wx34"Lx18"H 1"
FCU-12-06 FC1 900 225 0.4 1/3 277/1/60 0.5 B 21.7 20.5 4.3 5.0 48"Wx34"Lx18"H 1"
FCU-12-07 FC1 800 200 0.4 1/3 277/1/60 0.5 B 17.4 16.4 3.5 5.0 48"Wx34"Lx18"H 1"
FCU-12-08 FC1 400 100 0.4 1/3 277/1/60 0.5 A 9.8 9.2 1.9 5.0 34"Wx34"Lx18"H 3/4"
FCU-12-09 FC1 1200 300 0.4 1/3 277/1/60 0.5 C 25.5 23.9 5.1 5.0 53"Wx34"Lx18"H 1"
FCU-12-10 FC1 1100 275 0.4 1/3 277/1/60 0.5 C 25.5 23.9 5.1 5.0 53"Wx34"Lx18"H 1"
FCU-12-11 FC1 400 100 0.4 1/3 277/1/60 0.5 A 9.8 9.2 1.9 5.0 34"Wx34"Lx18"H 3/4"
FCU-12-E FC2 220 - 0.0 .125 115/1/60 3.6 D 3.6 3.6 1.0 10 REFER TO DETAIL -
FCU-16-E FC2 220 - 0.0 .125 115/1/160 3.6 D 3.6 3.6 1.0 1.0 REFER TO DETAIL -
NOTES:
A. FC1 - 2 PIPE, HORIZONTAL, CONCEALED WITH FACTORY ENCLOSURE.
FC2 - VERTICAL CONCEALED, ECM MOTOR
B. SEE SOUND REQUIREMENTS SCHEDULE.
C. BASED ON 80°F. D.B. AND 67°F. W.B. ENTERING AIR AND SCHEDULE
CFM AT HIGH SPEED.
D. BASED ON CHILLED WATER ENTERING AT 45°F WITH A 10°F
TEMPERATURE DIFFERENCE.
E. INSTALL PER DETAIL 3 ON SHEET M-905.
F. INSTALL PER DETAILS 1 AND 2 ON SHEET M-905.
G. SET UNITS TO MEDIUM SPEED AT BAS.
H. BASES OF DESIGN: DAIKIN FCVH102 WITH CUSTOM SHORTENED
SUB-BASE (-1.5-INCHES), RAISED CONDENSATE DRAIN CONNECTION
(+1.5-INCHES), RAISED VALVE PACKAGE (+1.0-INCHES), AND BOTTOM
FILTER RETURN OPENING.
I. CONTROL CONTRACTOR'S APPLICATION SPECIFIC CONTROLLER
SHALL BE SHIPPED LOOSE TO THE FAN COIL UNIT MANUFACTURER'S
FACTORY FOR MOUNTING AND WIRING.
J. BASIS OF DESIGN: TRANE MODEL THHP
K. PROVIDE WITH FACTORY MOUNTED MOTOR RATED TOGGLE
DISCONNECT SWITCH.
L. PROVIDE CONDENSATE OVERFLOW SWITCH FOR DRAIN PAN.
M. SET UNITS TO LOW SPEED AT BAS.
E
E
E
E
E
E
E
E
E
E
B
F
A
F
SOUND REQUIREMENTS
DESIGNATION IN
FAN COIL UNITS
SCHEDULE
MAXIMUM SOUND POWER LEVELS:
dB re 10^(-12) WATTS
NOTES
OCTAVE BAND 2 3 4 5 6 7
Hz 125 250 500 1000 2000 4000
A DISCHARGE L 66 62 62 59 57 54
B DISCHARGE L 69 67 65 64 62 59
C DISCHARGE L 80 68 65 65 63 60
D RADIATED L 51 54 53 53 50 44
NOTES
A. ALL SOUND DATA SHALL BE MEASURED IN ACCORDANCE WITH ARI
STANDARD 880 WITH A 1.0" W.G. PRESSURE DIFFERENCE BETWEEN
INLET AND OUTLET AT MAXIMUM FLOW, UNLESS OTHERWISE NOTED.
B. LISTED SOUND DATA AT LOW SPEED.
N.C.
TWO-PIPE FAN COIL UNIT WITH
COOLING COIL. HANG BOX FROM
STRUCTURE WITH FOUR 3/8"
THREADED RODS AND VIBRATION
ISOLATORS.
SUPPLYRETURN
SECONDARY DRAIN PAN WITH FLOAT
AND AUTOMATIC CUT OUT SWITCH
PROVIDE DUCTED RETURN W/ 2"
ACOUSTICAL LINING. REFER TO PLANS FOR
DUCT SIZING AND CONFIGURATION.
FAN COIL UNIT WITH FACTORY
FURNISHED FILTER AND FILTER FRAME
AUTOMATIC CONTROL VALVE
MAX 5 PSI (35kPa) P.D.
SEE PLANS
FOR PIPE SIZE
COMBINATION FLOW MEASURING
AND BALANCING VALVE
LOW PRESSURE DUCTWORK
SEE FLOOR PLAN FOR
CONFIGURATION AND SIZES
1" COPPER DRAIN. REFER TO
PLANS FOR CONTINUATION
s36" M
IN.
DISCHARGE
AIR SENSOR
M-905
FI
LE
N
AM
E:
OU
R
RE
F:
PL
OT
D
AT
E:
/18 /20
4:
:33
P M
4.2
M-
5.D
W G
PROFESSIONAL CERTIFICATION. I HEREBY CERTIFY
THAT THESE DOCUMENTS WERE PREPARED OR
APPROVED BY ME, AND THAT I AM A DULY LICENSED
PROFESSIONAL ENGINEER UNDER THE LAWS OF THE
STATE OF MARYLAND, LICENSE NO. 45592, EXPIRATION
DATE: 05 JUNE 2022.
G
G
G
G
G
G
G
G
G G
G H
H
I
I
E
A
D
NO SCALE
HORIZONTAL FAN COIL UNIT
DETAIL
M-9053
2"MIN
UNIT CASING
FAN COIL/AC UNIT
INSULATED DRAIN PAN
1" CONDENSATE DRAIN
DRAIN
POSSIBLE
AS CLOSE AS
FLOOR
SLOPE
THREADED
UNION
NO SCALE
CONDENSATE DRAIN TRAP
DETAIL
M-9054
J
J
J
J
J
J
J
J
J
J
J
B
1 ADDENDUM #1
K L
K L
10/19/2021
M
M