About this file

This pre-solicitation notice describes a planned competitive negotiated procurement for Veteran Benefits Administration Regional Office renovations at the George H. Fallon Federal Building in Baltimore, Maryland. The project scope includes demolition, interior renovations for new tenant layouts including offices, workstations, file and storage rooms, and conference/training rooms. Associated mechanical, electrical, plumbing, fire protection and IT work is required. The project will be completed in four phases with a period of performance of 1,062 calendar days. The procurement will utilize a best value source selection method and be set aside for small businesses. Technical proposals are due by September 2021 with price proposals. A pre-proposal conference will be held in September 2021.

View the file

Other files

Show all 24

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Offers must acknowledge receipt of this amendment prior to the hour and date specified in the solicitation or as amended, by one of the following methods:

(a) By completing items 8 and 15, and returning or (c) By separate letter or electronic communication which includes a reference to the solicitation and amendment numbers. FAILURE OF YOUR ACKNOWLEDGMENT TO BE

RECEIVED AT THE PLACE DESIGNATED FOR THE RECEIPT OF OFFERS PRIOR TO THE HOUR AND DATE SPECIFIED MAY RESULT IN REJECTION OF YOUR OFFER. If by virtue of this amendment you desire to change an offer already submitted, such change may be made by letter or electronic communication, provided each letter or electronic communication makes reference to the solicitation and this amendment, and is received prior to the opening hour and date specified.

E. IMPORTANT: is required to sign this document and return copies to the issuing office.is notContractor

AMENDMENT OF SOLICITATION/MODIFICATION OF CONTRACT

1. CONTRACT ID CODE

5. PROJECT NUMBER (If applicable)

7. ADMINISTERED BY (If other than Item 6) CODE

STANDARD FORM 30 (REV. 11/2016)

Prescribed by GSA FAR (48 CFR) 53.243

FACILITY CODE

R10A. MODIFICATION OF CONTRACT/ORDER NUMBE

10B. DATED (SEE ITEM 13)

11. THIS ITEM ONLY APPLIES TO AMENDMENTS OF SOLICITATIONS

is not extended.is extended.The above numbered solicitation is amended as set forth in Item 14. The hour and date specified for receipt of Offers

12. ACCOUNTING AND APPROPRIATION DATA (If required) copies of the amendment; (b) By acknowledging receipt of this amendment on each copy of the offer submitted;

13. THIS ITEM APPLIES ONLY TO MODIFICATIONS OF CONTRACTS/ORDERS.

IT MODIFIES THE CONTRACT/ORDER NUMBER AS DESCRIBED IN ITEM 14.

CHECK ONE A. THIS CHANGE ORDER IS ISSUED PURSUANT TO: (Specify authority) THE CHANGES SET FORTH IN ITEM 14 ARE MADE IN THE CONTRACT ORDER

NUMBER IN ITEM 10A.

B. THE ABOVE NUMBERED CONTRACT/ORDER IS MODIFIED TO REFLECT THE ADMINISTRATIVE CHANGES (such as changes in paying office, appropriation data, etc.) SET FORTH IN ITEM 14, PURSUANT TO THE AUTHORITY OF FAR 43.103(b).

C. THIS SUPPLEMENTAL AGREEMENT IS ENTERED INTO PURSUANT TO AUTHORITY OF:

D. OTHER (Specify type of modification and authority)

15C. DATE SIGNED 16C. DATE SIGNED

CODE6. ISSUED BY

8. NAME AND ADDRESS OF CONTRACTOR (Number, street, county, State and ZIP Code) (X)

CODE

15B. CONTRACTOR/OFFEROR

(Signature of person authorized to sign)

16B. UNITED STATES OF AMERICA

(Signature of Contracting Officer)

Previous edition unusable

4.� REQUISITION/PURCHASE REQUISITION NUMBER�

9A. AMENDMENT OF SOLICITATION NUMBER

47PD0321R0022

9B. DATED (SEE ITEM 11)

09/30/2021

3PQNS3PQNS

GSA ACQUISITION SVCS NORTH - SSA SECTION

100 S. INDEPENDENCE MALL WEST

PHILADELPHIA, PA 19106-2320 USA

GSA ACQUISITION SVCS NORTH - SSA SECTION

100 S. INDEPENDENCE MALL WEST

PHILADELPHIA, PA 19106-2320 USA

15A. NAME AND TITLE OF SIGNER (Type or print)

X

16A. NAME AND TITLE OF CONTRACTING OFFICER (Type or print)

2. AMENDMENT/MODIFICATION NUMBER

3. EFFECTIVE DATE

11/18/2021

14. DESCRIPTION OF AMENDMENT/MODIFICATION (Organized by UCF section headings, including solicitation/contract subject matter where feasible.)

Veteran Benefits Administration Regional Office (VARO) Renovations at the George H. Fallon Federal Building in Baltimore,MD

PAGE OF PAGE

1 290

KimberlyADesant Typewriter Please see attached.

Please Note: In Amendment 004, the answers to questions 113, 128, & 133 reference documents issued with “Addendum 003”. “Addendum 003” was inadvertently omitted from Amendment 004. “Addendum 003” is attached to this amendment.

Also, question 110 states that the card readers and security system is by contractor. However, questions 142 & 174 state that the contractor is to provide conduit, backbox, & pullstring only.

This is a conflict. The correct answer is, the contractor will provide key card readers and the IT/AV infrastructure shown in the drawings.

In addition, Wage Determination MD20210031 (Rev. 9), dated 11/05/2021, is hereby incorporated into this solicitation and replaces Wage Determination MD20210031 (Rev. 8) in its entirety.

The proposal closing date has been extended from 11/24/2021 at 2:00 pm to 12/01/2021 at 2:00 pm, Philadelphia local time.

All other terms and conditions of this solicitation remain unchanged.

KimberlyADesant

3200 Lee Highway, Arlington, Virginia 22207 703.524.6616 www.mtfa.net

ADDENDUM #03

Project: VARO Reprogramming Development and Final Design Project

Date: Tuesday, November 09, 2021

Re: Addendum #03

Contents: Written Addendum (288 pages)

This addendum is supplementary to the drawings and specifications for the VARO Reprogramming Development and Final Design Project. All revisions, deletions, and additions shall be part of the contract as if originally shown in the drawings and specifications.

Narrative Summary of Addendum 03:

All revisions are clouded and are marked with a delta 1 (triangle symbol).

The items associated with the Fan Coil Unit Replacement Project is denoted with *FCU.

See all attachments.

DRAWINGS:

Item No. Dwg. Description

1. G-002 Re-issued drawing with clouded changes.

2. PD106 Re-issued drawing with clouded changes.

3. P-107 Re-issued drawing with clouded changes.

4. MD103 Re-issued drawing with clouded changes.

5. M-103 Re-issued drawing with clouded changes.

6. E-001 Re-issued drawing with clouded changes.

7. E-104 Re-issued drawing with clouded changes.

8. E-402 Re-issued drawing with clouded changes.

9. E-601 Re-issued drawing with clouded changes.

10. E-605 Re-issued drawing with clouded changes.

11. E-607 Re-issued drawing with clouded changes.

12. E-702 Add drawing sheet

KimberlyADesant

(included in Amendment 005)

Addendum #03 November 09, 2021

13. A-902 (*FCU) Re-issued drawing with clouded changes.

14. E-904 (*FCU) Re-issued drawing with clouded changes.

SPECIFICATIONS:

Item No. Section Paragraph Description

1 TOC N/A The TOC has been revised.

2 N/A N/A Remove all Division 22, 23, 26, and 27 specification sections and replace with the attached specification sections. (Division 22 has 6 sections, Division 23 has 29 sections, Division 26 has 10 sections, and Division 27 has 1 section.)

3 262416 N/A Add specification section 26416.

END OF NARRATIVE SUMMARY FOR ADDENDUM #03

DRAWING INDEX

FURNITURE DRAWING SET

(UNDER SEPARATE COVER )

FOR REFERENCE ONLY

Ÿ

100% CD SET

Ÿ Ÿ Ÿ Ÿ Ÿ Ÿ

Ÿ Ÿ Ÿ Ÿ Ÿ

Ÿ Ÿ Ÿ Ÿ Ÿ

Ÿ

Ÿ

Ÿ Ÿ

Ÿ Ÿ Ÿ Ÿ Ÿ

Ÿ Ÿ Ÿ Ÿ Ÿ

Ÿ Ÿ Ÿ Ÿ Ÿ

Ÿ Ÿ Ÿ Ÿ Ÿ

Ÿ Ÿ Ÿ Ÿ Ÿ

Ÿ Ÿ Ÿ Ÿ Ÿ

Ÿ Ÿ Ÿ Ÿ Ÿ

Ÿ Ÿ

Ÿ Ÿ Ÿ Ÿ Ÿ Ÿ Ÿ

Ÿ

Ÿ Ÿ Ÿ

Ÿ Ÿ

Ÿ

Ÿ Ÿ

Ÿ Ÿ

Ÿ

Ÿ

Ÿ Ÿ Ÿ Ÿ

Ÿ Ÿ Ÿ Ÿ

Ÿ Ÿ

Ÿ Ÿ

Ÿ Ÿ

Ÿ Ÿ

Ÿ Ÿ

Ÿ Ÿ

Ÿ Ÿ

Ÿ Ÿ

Ÿ

Ÿ

Ÿ

Ÿ

Ÿ Ÿ Ÿ Ÿ Ÿ Ÿ

Ÿ Ÿ Ÿ Ÿ

Ÿ Ÿ

Ÿ

Ÿ

Ÿ Ÿ

Ÿ Ÿ

Ÿ

Ÿ Ÿ Ÿ Ÿ Ÿ Ÿ

Ÿ Ÿ

Ÿ Ÿ Ÿ

Ÿ Ÿ Ÿ

Ÿ

Ÿ Ÿ Ÿ Ÿ Ÿ Ÿ Ÿ Ÿ Ÿ Ÿ

Ÿ Ÿ Ÿ Ÿ Ÿ Ÿ Ÿ Ÿ Ÿ Ÿ

Ÿ Ÿ

Ÿ Ÿ

Ÿ Ÿ Ÿ Ÿ Ÿ Ÿ

Ÿ

Ÿ Ÿ Ÿ Ÿ Ÿ

Ÿ Ÿ Ÿ Ÿ Ÿ

Ÿ Ÿ

Ÿ

Ÿ Ÿ Ÿ

Ÿ Ÿ

Ÿ Ÿ Ÿ

Ÿ

Ÿ

Ÿ

Ÿ

Ÿ

Ÿ

Ÿ

Ÿ

Ÿ

Ÿ

Ÿ Ÿ

Ÿ

Ÿ

Ÿ

Ÿ

Ÿ

Ÿ

45678910

D

E

F

G

(E)3"ST

(E)3"ST

(E)4"ST(E)3"ST

(E)8"ST UP& DN.

SK 1

(E)6"W

UP&DN.

(E)4"V UP&DN.

(E)4"W

UP&DN.

(E)1-/2"HW DN.

(E)1-1/2"CW DN.

(E)6"V UP&DN.

(E)3"CW DN.

(E)1/2"HW

(E)1-1/2"V 2 (E)1-1/2"CW

(E)4"CW

1-1/2"V

11-1/2"W 2

1/2"CW

(E)4"V UP&DN.

(E)1-/2"HW DN.

(E)1-1/2"CW DN.

1CAP

1/2"HW1CAP

(E)W

GENERAL NOTES

G1. VERIFY LOCATION AND DIMENSIONS OF EXISTING EQUIPMENT AND

COORDINATE ALL WORK PRIOR TO THE START OF CONSTRUCTION.

G2. COORDINATE SHUTDOWN, ISOLATION, AND DRAIN OF EXISTING UTILITY WITH

GSA BUILDING MANAGEMENT A MINIMUM OF 2-WEEKS IN ADVANCE.

PERFORM WORK DURING NON-WORKING HOURS.

1. REMOVE KITCHEN SINK AND APPURTENANCES COMPLETE. REMOVE

ASSOCIATED WASTE, VENT, DOMESTIC WATER PIPE, AND VALVES TO POINT

INDICATED AND CAP PIPE. PATCH AND REPAIR SLAB TO MATCH ADJACENT

SURFACES.

2. PIPING LOCATED IN CEILING OF FLOOR BELOW.

3. REMOVE INSULATION, VAPOR BARRIER/JACKET COMPLETE TO POINTS

INDICATED ON EXISTING STORM AND DOMESTIC WATER PIPING. INSPECT

PIPING AND REPORT ANY VISUAL SIGNS OF LEAKS OR OTHER INTEGRITY

ISSUES TO CONTRACTING OFFICER.

4. DEMOLISH EXISTING CHASE WALL TO FACILITATE CONNECTION TO EXISTING

WASTE PIPE STACK WITHIN THE PIPE CHASE. LOCATION OF EXISTING

WASTE PIPE AS INDICATED IS BASED ON RECORD DOCUMENTS. SURVEY

AND COORDINATE ACTUAL LOCATION OF STACK IN FIELD.

NOTES

SUMMER

CONSULTANTS

I N C O R P O R A T E D

SUMMER

CONSULTANTS

PROFESSIONAL CERTIFICATION. I HEREBY CERTIFY

THAT THESE DOCUMENTS WERE PREPARED OR

APPROVED BY ME, AND THAT I AM A DULY LICENSED

PROFESSIONAL ENGINEER UNDER THE LAWS OF THE

STATE OF MARYLAND, LICENSE NO. 45592, EXPIRATION

DATE: 05 JUNE 2022.

FI

LE

N

AM

E:

OU

R

RE

F:

PL

OT

D

AT

E:

/8/

4:

:47

P M

4.2

PD

6-

.D

W G

N

8'0 16' 1/8"=1'-0"

SIXTEENTH FLOOR PLAN - DEMOLITION1

1 ADDENDUM 3 11/09/21

GENERAL NOTES

G1. ALL WORK SHALL BE NEW AND PROVIDED UNDER THIS CONTRACT UNLESS

SPECIFICALLY MARKED "EXISTING", "EXIST.", OR "(E)"

G2. VERIFY LOCATION AND DIMENSIONS OF EXISTING EQUIPMENT AND

COORDINATE ALL WORK PRIOR TO THE START OF CONSTRUCTION.

G3. COORDINATE SHUTDOWN, ISOLATION, AND DRAIN OF EXISTING UTILITY WITH

GSA BUILDING MANAGEMENT A MINIMUM OF 2-WEEKS IN ADVANCE.

PERFORM WORK DURING NON-WORKING HOURS.

NOTES

1. PIPING LOCATED IN CEILING OF FLOOR BELOW.

2. INSULATE EXISTING STORM AND DOMESTIC WATER PIPING TO POINTS

INDICATED.

3. PROVIDE FIELD-FABRICATED DRAIN PAN UNDER EXISTING PIPING TO

EXTENTS INDICTED.

4. PROVIDE 1/2" PLENUM RATED TUBING FROM DRAIN PAN, ACROSS IT ROOM

WALL BARRIER, AND SPILL ONTO CEILING TILE IN VISIBLE LOCATION.

5. EXTEND CONDENSATE PIPING TO TAIL-PIPE OF EXISTING DRINKING

FOUNTAIN. FIRESTOP, PATCH AND REPAIR EXISTING CHASE WALL.

6. NOT USED.

7. CORE DRILL EXISTING CONCRETE SLAB FOR PIPE PENETRATION.

COORDINATE CORE DRILL WITH STRUCTURE BELOW.

8. EXTEND DOMESTIC WATER PIPING TO SINK WITHIN CASEWORK.

45678910

D

E

F

G

(E)3"ST

(E)3"ST

(E)4"ST(E)3"ST

(E)8"ST UP& DN.

(E)4"V

UP&DN.

(E)4"W

UP&DN.

(E)1-/2"HW DN.

(E)1-1/2"CW DN.

(E)6"V UP&DN.

(E)1/2"HW

(E)1-1/2"V

(E)1-1/2"CW

(E)4"CW

REF.

1(E)1-1/2"W

1/2"CW

1/2"HW

3/4"CW

1-1/2"W

C.O.P-3

P-6

(E)4"CW DN.

AC

16-4

71-1/2"W

1-1/2"V

2 3

(E)DRINKING FOUNTAIN

(E)W

SUMMER

CONSULTANTS

I N C O R P O R A T E D

SUMMER

CONSULTANTS

160008

160001 160002

160004

160003

160005

160006

160007

160016 160014

160009160010

160017

160011

160013

N

8'0 16' 1/8"=1'-0"

SIXTEENTH FLOOR PLAN1

160012

PROFESSIONAL CERTIFICATION. I HEREBY CERTIFY

THAT THESE DOCUMENTS WERE PREPARED OR

APPROVED BY ME, AND THAT I AM A DULY LICENSED

PROFESSIONAL ENGINEER UNDER THE LAWS OF THE

STATE OF MARYLAND, LICENSE NO. 45592, EXPIRATION

DATE: 05 JUNE 2022.

FI

LE

N

RE

F:

PL

OT

D

AT

E:

/8/

4:

:54

P M

4.2

P-

7-

.D

W G

H

G

F

E

D

C

A

A

AD

H

G

F

E

D

C

A

A

AD

(E)VAV

(E)38x16

(E)VAV

(E)VAV

(E)VAV

(E)VAV

(E)VAV

(E)VAV

(E)16x8

(E )1

6x

(E )1

6x

(E)12x10

(E)8"Ø (E)8"Ø

(E)8"Ø (E)8"Ø

(E )8 x1

(E)12x14

(E)6"Ø (E)8"Ø

(E )8

"Ø

(E )8 x1

(E )1

2x

(E)8"Ø (E)8"Ø

(E)14x12

(E)8"Ø

(E)VAV

(E)VAV

(E)14x10 (E)12x10 (E)8x10 (E)6x8

(E )6 x1

(E )1

0x

(E)12x12

(E )1

0x

(E)12x12

(E)16x12

(E )1

0x

(E)6x6 (E)8x10

(E)8"Ø

(E )3

0x

(E)10"Ø

(E)8x8

(E)8x8

(E)CUH

(E )1

0x

(E)8x8

(E)6"Ø

(E)6x12

(E )6 x1

(E)2-1/2"HWR

(E)2-1/2"HWS

(E)2-1/2"HWR

& (E) 1"HWS

(E)3/4"HWS&R

(E)1"HWS

(E)1-1/4"HWS

T (E)

(E)2-1/2"HWR (E)2"HWR

(E)1-1/4"HWS

(E)2"HWR

T(E)

T (E) 8"Ø

4"HWS&R

UP&DN.

(E)8x12

(E)8Ø

8x10

8x10

6x8

6x8

6x12

6x8

(E)8x12 (E)8x12 (E)6x12(E)10x12

(E)12x14

(E)6x10

16x14

8x8

8x14

(E)8x12

(E)10x12

(E)10x10 (E)8x12

6x10

12x12

10x8

8x6

8x10

(E)12x12

2"HWS&R

(E)CWS&R

(E)CWS&R

(E)HWS&R

(E)HWS&R

(E)HWS&R

(E)1-1/2"CWS&R

3/4"HWS&R

2"HWS&R

(E)2"HWS&R

(E)CWS&R UP&DN

(E)HWS&R UP&DN

VAV

VAV

VAV

VAV

VAV

(E )3

0x

14x10

6x8

(E)36x12RA

(E )3

6x

RA

(E )3

0x

SA

(E )3

6x

RA

(E )2

4x

SA

(E

)3 8x

SA

(E)2"HWS&1-1/2"HWR

3/4"HWS&R

8x12

14x10

(E)6"CWS&R

UP&DN

(E)2-1/2"HWS

2 2

4 2

(E)14x14

VAV3

3/4"HWS&R 4

T

T

T

T

T5 T

5 6

6x8 2

(E)RG

(E)RG 1

(E)RG

(E)RG

(E)RG

GENERAL NOTES

G1. VERIFY LOCATION AND DIMENSIONS OF EXISTING EQUIPMENT AND

COORDINATE ALL WORK PRIOR TO THE START OF CONSTRUCTION.

G2. COORDINATE SHUTDOWN, ISOLATION, AND DRAIN OF EXISTING UTILITY WITH

GSA BUILDING MANAGEMENT A MINIMUM OF 2-WEEKS IN ADVANCE.

PERFORM WORK DURING NON-WORKING HOURS.

G3. ALL EXISTING TO REMAIN SUPPLY AND RETURN AIR DUCTWORK SHALL BE

CLEANED PER SPECIFICATIONS.

NOTES

1. REMOVE AIR DEVICE AND APPURTENANCES COMPLETE.

2. REMOVE DUCTWORK AND ASSOCIATED INSULATION, HANGERS, SUPPORTS,

AND APPURTENANCES TO POINT INDICATED.

3. CAREFULLY REMOVE VAV BOX AND ASSOCIATED HEATING COIL, CONTROLS,

HANGERS, SUPPORTS, AND APPURTENANCES COMPLETE. DELIVER VAV BOX,

AND CONTROLLER TO GSA DESIGNATED LOCATION ON THE 17TH FLOOR.

4. REMOVE PIPING AND ASSOCIATED INSULATION, VALVES, HANGERS, AND

APPURTENANCES TO POINT INDICATED. CAP PIPING AT POINT INDICATED.

5. DEMOLISH THERMOSTAT AND ASSOCIATED BACKBOX, CONDUIT, WIRING,

AND APPURTENANCES COMPLETE.

6. RETAIN THERMOSTAT FOR REINSTALLATION.

7. CAREFULLY REMOVE VAV BOX AND ASSOCIATED HEATING COIL, CONTROLS,

HANGERS, SUPPORTS, AND APPURTENANCES COMPLETE. RETAIN VAV BOX

FOR RELOCATION.

6 5 4 36 5 4 3

SUMMER

CONSULTANTS

I N C O R P O R A T E D

SUMMER

CONSULTANTS

N

8'0 16' 1/8"=1'-0"

SECOND FLOOR (EAST) - DEMOLITION1

FI

LE

N

RE

F:

PL

OT

D

AT

E:

/8/

4:

:06

P M

4.2

MD

3-

.D

W G

PROFESSIONAL CERTIFICATION. I HEREBY CERTIFY

THAT THESE DOCUMENTS WERE PREPARED OR

APPROVED BY ME, AND THAT I AM A DULY LICENSED

PROFESSIONAL ENGINEER UNDER THE LAWS OF THE

STATE OF MARYLAND, LICENSE NO. 45592, EXPIRATION

DATE: 05 JUNE 2022.

1 ADDENDUM 3 11/09/21

GENERAL NOTES

G1. ALL WORK SHALL BE NEW AND PROVIDED UNDER THIS CONTRACT UNLESS

SPECIFICALLY MARKED "EXISTING", "EXIST.", OR "(E)"

G2. VERIFY LOCATION AND DIMENSIONS OF EXISTING EQUIPMENT AND

COORDINATE ALL WORK PRIOR TO THE START OF CONSTRUCTION.

G3. ALL AIR DEVICES ARE CD-1 UNLESS OTHERWISE INDICATED.

NOTES

1. AIR TRANSFER DUCT. REFER TO DETAIL 6 ON SHEET M-501. SIZE TRANSFER

IN ACCORDANCE WITH SCHEDULE BASED ON SUM OF ROOM AIRFLOW

UNLESS OTHERWISE NOTED.

2. REINSTALL RETAINED VAV BOX. PROVIDE CONTROL VALVE AND EXTEND

CONTROLS TO LOCATION INDICATED.

3. REINSTALL RETAINED THERMOSTAT. EXTEND WIRING TO LOCATION

INDICATED. REWIRE TO OPERATE AS BEFORE.

4. BALANCE AIR DEVICE TO INDICATED AIRFLOW.

5. FIRESTOP PENETRATION.

6. COORDINATE ROUTING OF PIPING THROUGH EXISTING CEILING IN OCCUPIED

SPACE. COORDINATE PIPE ROUTING WITH EXISTING UTILITIES.

7. INDICATED AREA IS PART OF AN EXISTING VERTICAL CHASE THAT IS OPEN

FROM THE BASEMENT TO THE UNDERSIDE OF THE 3RD FLOOR SLAB.

PROVIDE ALL EQUIPMENT REQUIRED IN ORDER TO MAKE UTILITY

CONNECTIONS AS INDICATED. ACCESS TO THE SHAFT IS THROUGH AN

ACCESS PANEL AT THE BASEMENT LEVEL WITHIN THE ADJACENT

STAIRWELL.

8. NOT USED.

9. PROVIDE DUCT CONNECTION FOR SERVER RACK EXHAUST. COORDINATE

EXACT LOCATION OF SERVER RACK, EXHAUST CONNECTION, AND CABLE

TRAY IN-FIELD.

1-1/2"CWS/R

6"PAD

(E )8 x1

8x6 SG-1

AC

2E-01

M-502

24x12 T

SD

24x24DN

DD

RG-1

34x40DN

6"PAD

AC

2E-02

M-502

FPB

2E-04

(E )3

0x

SA

(E

)3 0x

SA

10x10

T

T

AC

2E-03

T

SD

934x16

24x12

2"CWS&R 1-1/2"CWS&R

3/4"HWS&R

SD

H

G

F

E

D

C

H

G

F

E

D

C

(E)VAV

(E)38x16 (E)VAV

(E)VAV

(E)VAV

(E)VAV

(E)16x8

(E )1

6x

(E )1

6x

(E)12x10

(E)8"Ø (E)8"Ø

(E)8"Ø (E)8"Ø

(E )8 x1

(E)12x14

(E)6"Ø (E)8"Ø

(E )8

"Ø

(E )1

2x

(E)8"Ø (E)8"Ø

(E)14x12

(E)8"Ø

(E)VAV

(E)VAV

(E)14x10 (E)12x10 (E)8x10 (E)6x8

(E )6 x1

(E )1

0x

(E)12x12

(E )1

0x

(E)12x12

(E)16x12

(E )1

0x

(E)6x6 (E)8x10

(E)8"Ø

(E)10"Ø

(E)8x8

(E)8x8

(E)CUH

(E )1

0x

(E)8x8

(E)6"Ø

(E)6x12

(E )6 x1

4"HWS&R

UP&DN.

(E)1"HWS

(E)1-1/4"HWS

T (E)

(E)2-1/2"HWR (E)2"HWR

(E)1-1/4"HWS

(E)2"HWR

T(E)

T (E)

(E)VAV

(E)6"CWS&R

UP&DN

(E)2-1/2"HWR

(E)VAV

(E)2-1/2"HWR

& (E) 1"HWS

(E)8x10

(E)3/4"HWS&R

8x6

2"CWS&R

RG-1

RG-1

120 65

LS-1

LS-1

LS-1

LS-1

RG-1

RG-1

LS-1

LS-1

LS-1

LS-1

M-103

M-103

(E)1-1/2"CWS&R

(E)2-1/2"HWS

(E)8x12

(E)8Ø

(E)8x12 (E)8x12 (E)6x12(E)10x12

(E)12x14

(E)6x10 (E)8x12

(E)10x12

(E)10x10 (E)8x12

(E)12x12

(E)CWS&R

(E)CWS&R

(E)HWS&R

(E)HWS&R

(E)HWS&R

(E)CWS&R UP&DN

(E)HWS&R UP&DN

(E )3

0x

(E )3

0x

SA

(E )3

6x

RA

(E)36x12RA

(E )3

6x

RA

(E )2

4x

SA

(E)2"HWS&1-1/2"HWR

22x14

(E)14x14 30x14SA

(E)36x30RA UP

SPLIT 18&12

(E)30x36SA UP

SPLIT 18&18

22x14

6x8 x1 x1

FPB

2E-06

FPB

2E-02

RG-1

FPB

2E-01

6x8

12x10

12x10 x1 x1

RISERISE

6x

2"HWS&R

10x10

2"HWS&R

x1

14x10

8x8

8x8

VAV

7-11

FPB

2E-05

195 4

195 4

195 4

220 4200 4200 4220420042004

250 4

250 4

6x8

6x

6x

18548x8

T

FPB-2E-05

T

FPB-2E-06

T

T

FPB-2E-02

(E)RG

(E)RG

(E)RG

(E)RG

(E)RG

2"CWS&R

2"

CW

S& R

1-1/2"CWS&R6

1-1/2"CWS&R 6

2"CWS&R 6

T

6 5 4 36 5 4 3

FF

SUMMER

CONSULTANTS

I N C O R P O R A T E D

SUMMER

CONSULTANTS

025007

025008

025006

025011

025004

025003

025005

025012 025013025014

025017

025015 025016

025001

025002

025019

025020

025018

025024 025010

025009

N

8'0 16' 1/8"=1'-0"

SECOND FLOOR PLAN (EAST)3

8'0 4' 1/4"=1'-0"

SECOND FLOOR - IT ROOM 025010

ENLARGED PLAN

M-1031

8'0 4' 1/4"=1'-0"

ROOMS 025027, 025028, & 025031

ENLARGED PLAN - SECOND FLOOR

M-1032

025022

025021

025031

025027

025026

025029025030

025032

025025

025027

025032

025031

025028

025026

025017

025009

025015

FI

LE

N

RE

F:

PL

OT

D

AT

E:

/8/

4:

:34

P M

4.2

M-

3-

.D

W G

PROFESSIONAL CERTIFICATION. I HEREBY CERTIFY

THAT THESE DOCUMENTS WERE PREPARED OR

APPROVED BY ME, AND THAT I AM A DULY LICENSED

PROFESSIONAL ENGINEER UNDER THE LAWS OF THE

STATE OF MARYLAND, LICENSE NO. 45592, EXPIRATION

DATE: 05 JUNE 2022.

025024

1 ADDENDUM 3 11/09/21

(E)4"HWS&R

UP&DN.

(E)4"CWS&R

UP&DN.

(E)

(E)2"HWS

10x10

(E)EG (TYP.)

(E)30x30

UP&DN

(E)14x12 (E)12x8

(E )1

0x

7 5

(E)F.D.

(E) PIPE/DUCT

CHASE OPEN

TO BASEMENT

(E)F.D.

RG-1RG-1

LS-1

LS-1

LS-1

LS-1

LS-1

LS-1

LS-1

LS-1

LS-1

LS-1

LS-1

LS-1

LS-1

RG-1

RG-1

LS-1

LS-1

LS-1

RG-1

RG-1

LS-2

LS-2

LS-2

LS-2

RG-1

LS-1

RG-1

LS-1

RG-1

LS-1

RG-1

LS-1

RG-1

LS-1

LS-1

LS-1

LS-1

RG-1

RG-1

RG-1

RG-1

LS-1

LS-1

LS-1

LS-1

LS-1

LS-1

LS-1

RG-1

RG-1

RG-1

LS-1

LS-1

LS-1

LS-1

LS-1

LS-1

LS-1

LS-1

LS-1

LS-1

LS-1

LS-1

LS-1

LS-1

RG-1

LS-1

LS-1

RG-1

RG-1

RG-1

RG-1 RG-1

RG-1

RG-1

RG-1

RG-1

RG-1

RG-1

RG-1

RG-1

RG-1

RG-1

2-1/2"CWS&R

100 100

100 100 100

100 100

100 100 100

FPB

2W-12A

FPB

2W-04A

FPB

2W-08A

110 110

110 110

110110

110 110

80 80 80 110 110

808085

FPB

2W-17A

FPB

2W-17B

505050

90 90

160160160

FPB

2W-04B

160160

FPB

2W-05B

FPB

2W-05A

FPB

2W-06A

FPB

2W-06B

FPB

2W-08B

FPB

2W-12B

FPB

2W-12C

FPB

2W-12D

FPB

2W-12E

FPB

2W-12F

FPB

2W-12G

FPB

2W-12H

FPB

2W-12J

12x10 10x10 8x8

12x10 10x10 8x8

14x12

8x8 10 x1

12x12 10x8

6" Ø

SPLIT EQ.

SPLIT EQ.

SPLIT EQ.

8x8 x1 x1

6x8 x1 x1

6"Ø

8x8

12x10 x1

8x x1

8x

12x10 x1

10x10 x8

10x8 8x8

14x12 12x12

8x

10x8 x8 x8

6x

6" Ø

12x10

6x8 x1 x1

6"Ø

6x

6"Ø x8

8x8 6x8

14x12 10x8

8x86"Ø

SPLIT 7&3

8x8

6"Ø4x8

6"Ø

12x10 10x10

8x x8

8x6

4x

8 SPLIT 3&5

6"Ø

6"Ø

6"Ø

6" Ø x1

8x814x12 12x10

6" Ø

10x10 10x8 8"Ø

10x10 10x8

8"Ø

12x8

RG-1

12x6 x1

10x88"Ø

10x5

10x10 x1

8x

7x

24x12 18x12 12x8

8x8 x8 x8

8x

6"Ø x8

10x8 x1 x8

10x8 8x8 6"Ø

6x

10x8

10x8

SPLIT EQ.

6"Ø

6x8 6"Ø10x8

16x12 12x10

8x x8

8x

6" Ø

12x10

12x10 8x8 SPLIT EQ.

10x10

12x8

6x8 x1

8x

8x8

8x x1

6"Ø

14x10 14x10 x8

8x

SPLIT EQ.

T

8x8 x1

22x1816x1616x16 x1 x1

14x12

34x1428x1220x1212x12

24x1220x10 14x10

8x8

6"Ø 6"Ø

14x12 x1 x1 x1 x1 x1

16x10

SPLIT EQ.

36x16 44x18

54x24 SPLIT 21&33

3/4"HWS&R

8x

8x68x4

RG-1

LS-1

2 2

RG-1

(E)2-1/2"HWS&R

HWS&R

TX-02-2

EF-02-1

EG-3

FPB

2W-10

FPB

2W-11

FPB

2W-09 FPB

2W-07

FPB

2W-13

FPB

2W-14

FPB

2W-01

12x812 x8

1"CWS&R

1"CWS&R

14x8

(E)F.D.

(E)F.D.

104x16 9

FPB

2W-18

FPB

2W-19

FPB

2W-16

1-1/2"HWS

1"HWS 1"HWS

1/2"HWR

1"HWR

1-1/4"HWR

1-1/2"HWR

1-1/2"HWR

2"HWR

2-1/2"HWR

FPB

2W-03

FPB

2W-02

FPB

2W-20

86x20UP

CAV

8-06

6" Ø

6" Ø

DPT-8A

DPT-8B

3 10x10 AD

T

T

T

T

16 T

T

T

T

T

T

T

T

T

T

T T

T 2W-06B

T

T

T

T

T

T

T

T

T

T

T

T

T

T

T

2W-12J

2W-12F

2W-14

2W-13 2W-07

2W-09

2W-12E

2W-12D

2W-12H

2W-12G

2W-11

2W-10

2W-08A

2W-03

2W-02

2W-08B

2W-04A

2W-04B

2W-05A

2W-06A

2W-05B

2W-06B

8-06

2W-17B

2W-17A

2W-16

2W-18

2W-20

2W-12C 2W-12B

EG-2

GENERAL NOTES

G1. ALL WORK SHALL BE NEW AND PROVIDED UNDER THIS CONTRACT UNLESS

SPECIFICALLY MARKED "EXISTING", "EXIST.", OR "(E)"

G2. VERIFY LOCATION AND DIMENSIONS OF EXISTING EQUIPMENT AND

COORDINATE ALL WORK PRIOR TO THE START OF CONSTRUCTION.

G3. ALL AIR DEVICES ARE CD-1 UNLESS OTHERWISE INDICATED.

NOTES

1. PROVIDE MANBAR BARRIER. REFER TO DETAIL 2 ON SHEET M-501.

2. AIR TRANSFER DUCT. REFER TO DETAIL 6 ON SHEET M-501. SIZE TRANSFER

IN ACCORDANCE WITH SCHEDULE BASED ON SUM OF ROOM AIRFLOW

UNLESS OTHERWISE NOTED.

3. PROVIDE 12x12 ACCESS PANEL UON.

4. BALANCE FAN AND AIR DEVICE AT DESIGN AIRFLOW WITH 1.5"W.G. ACROSS

FILTER BANK BY FALSELY LOADING FILTERS AT TIME OF BALANCE.

5. 24x24 ACCESS PANEL LOCATED IN STAIRWELL ON GROUND LEVEL.

6. REINSTALL FIRE/SMOKE DETECTOR AND TEST INDICATOR. REFER TO FIRE

ALARM PLANS FOR DETAILS.

7. BALANCE EXISTING AIR DEVICE TO INDICATED AIRFLOW.

8. COORDINATE FAN POWERED VAV BOX CONTROLLER, FILTER, AND

MAINTENANCE ACCESS WITH PENDENT MOUNTED MOONRING LIGHTS HUNG

BELOW CEILING. REFER TO ELECTRICAL LIGHTING AND ARCHITECTURAL

CEILING PLANS FOR ADDITIONAL DETAILS.

9. BALANCE RETURN AIR PER RISER ON SHEET M-105.

10. NOT USED.

11. PROVIDE FILTER BANK SIZED FOR MERV 13 FLAT FILTER. PROVIDE FILTER

ACCESS DOOR WITH CAMLOCK AND PRESSURE TIGHT SEAL. PROVIDE

MERV-8 PRE-FILTER UPSTRAM OF MERV 13 FILTERS. PROVIDE FILTER

GAUGE AT FILTER BANK FOR EACH FILTER.

12. TERMINATE EXHAUST WITH 1/2 INCH WIRE MESH AT BELLMOUTH OPENING.

13. PROVIDE MOTORIZED DAMPER IN EXHAUST OUTLET. INTERLOCK EXHAUST

FAN AND DAMPER WITH EMERGENCY WALL PUSH BUTTON WITHIN MAIL

ROOM. WHEN EMERGENCY WALL PUSH BUTTON IS ENABLED, DAMPER

SHALL CLOSE.

14. PROVIDE 10-INCH SINGLE BLADE MOTORIZED DAMPER IN SUPPLY INLET TO

FPB-2W-15. INTERLOCK DAMPER WITH EMERGENCY WALL PUSH BUTTON

WITHIN MAILROOM. WHEN EMERGENCY WALL PUSH BUTTON IS ENABLED,

DAMPER SHALL CLOSE. PROVIDE PUSH BUTTON WITH HINGED COVER.

PROVIDE PLACARD OVER PUSH BUTTON THAT READS, "EMERGENCY ROOM

HVAC OFF".

15. PROVIDE DIFFERENTIAL PRESSURE TRANSMITTER IN LOCATION INDICATED.

MODIFY SEQUENCE TO CONTROL SYSTEM FAN ON WORST-CASE. REFER TO

CONTROLS SHEETS FOR ADDITIONAL INFORMATION.

16. COORDINATE THERMOSTAT MOUNTING HEIGHT WITH SYSTEMS FURNITURE.

111213141516 111213141516

H

G

F

E

D

C

H

G

F

E

D

C

SUMMER

CONSULTANTS

I N C O R P O R A T E D

SUMMER

CONSULTANTS

N

8'0 16' 1/8"=1'-0"

SECOND FLOOR PLAN (WEST)1

020028

020001

020031

020030

020029

020032

020027

020025

020026

020033

020034020037

020036

020035

020024

020001

020003

020004

020038

020023

020022

020021

020020

020019

020008

020007

020006

020018

020005 020002

020012

020013

020014

020015

020016

020017 020011

020010

020009

FI

LE

N

RE

F:

PL

OT

D

AT

E:

/8/

4:

:50

P M

4.2

M-

4-

.D

W G

PROFESSIONAL CERTIFICATION. I HEREBY CERTIFY

THAT THESE DOCUMENTS WERE PREPARED OR

APPROVED BY ME, AND THAT I AM A DULY LICENSED

PROFESSIONAL ENGINEER UNDER THE LAWS OF THE

STATE OF MARYLAND, LICENSE NO. 45592, EXPIRATION

DATE: 05 JUNE 2022.

SUMMER

CONSULTANTS

I N C O R P O R A T E D

SUMMER

CONSULTANTS

ELECTRICAL SYMBOLS

RECESSED 2' x 2' LUMINAIRE, SUBSCRIPT INDICATES CONTROL SWITCH

SD

SOC

S

A LUMINAIRE FIXTURE TYPE, REFER TO LUMINAIRE SCHEDULE.

SINGLE FACED EXIT SIGN.

DOUBLE FACED EXIT SIGN.

COPPER GROUNDING BUS BAR.

RECESSED 6'' LED DOWN LIGHT, SUBSCRIPT INDICATES CONTROL SWITCH

OS

ELECTRICAL SYMBOLS CONTINUED

SYSTEMS FURNITURE POWER FEED, WALL-RECESSED MOUNTED @ 18” AFF; GALVANIZED

PRESSED STEEL JUNCTION BOX, 4-1/2" LONG x 4-1/2" WIDE x 1-1/2" DEEP. MAKE ALL FINAL

CONNECTIONS TO POWER WHIP FURNISHED WITH SYSTEMS FURNITURE.

J JUNCTION BOX 4" SQUARE X 2-1/8" DEEP GALVANIZED PRESSED STEEL,

MOUNTED ABOVE SUSPENDED TILE CEILING.

RECESSED 2' x 2' EMERGENCY LUMINAIRE

RECESSED 6'' EMERGENCY LED DOWN LIGHT

DESIGNATION FOR TELECOM AND VOICE PATCH PANEL. D FOR DATA, V

FOR VOICE. NUMBER CORRESPONDS TO BOTH DATA AND VOICE PATCH

PANELS. LETTER INDICATES SPECIFIC DATA OR VOICE PANEL.

D/V (A)(B) #

4'' CUTOUT SLEEVE AND REMOVABLE FIRE STOP PILLOWS FOR

COMMUNICATION CABLE.

HORIZONTAL CABLE TRAY, CABLOFIL CF 54/400.

AIPHONE OR EQUIVALENT DEVICE.

EM2 PANEL NAME TO WHICH CIRCUITS RUN.

AS SHOWN ABOVE.

IN WALLS AND CEILING, ALL OTHER CHARACTERISTICS SAME

BRANCH CIRCUIT CONDUIT AND CONDUCTORS RUN CONCEALED

#10

EM2

#10

1,3,5

WIRE SIZE IN AWG. SIZE NOT SHOWN INDICATES #12 AWG.

CIRCUIT BREAKERS IN PANEL SERVING THESE CIRCUITS.

EM2

1,3,5

#10

HOME RUN TO PANEL. NUMBER OF ARROWS INDICATE

2 CIRCUIT CONDUCTORS PLUS A GROUND CONDUCTOR.

CONDUCTORS IN RACEWAY. NO SLASH MARKS INDICATE

NUMBER OF SLASH MARKS INDICATE THE NUMBER OF

GREEN GROUND CONDUCTOR RUN IN RACEWAY.

THE NUMBER OF CIRCUITS.

a

COMBINATION POWER/TELECOMMUNICATIONS RECESSED POKE-THROUGH DEVICE IN RAISED

ACCESS FLOOR. PROVIDE A POKE-THROUGH DEVICE WITH (4) PRE-WIRED 20A, 125V

RECEPTACLES (2) OPENINGS FOR STANDARD TELECOM JACKS. PROVIDE ASSOCIATED

TWO-SECTION JUNCTION BOX WITHIN THE CEILING SPACE BELOW. FOR THE

TELECOMMUNICATIONS SIDE OF THE JUNCTION BOX, PROVIDE A 1" EMT CONDUIT ROUTED IN

FLOOR FROM FITTING TO NEAREST WALL AND UP TO CEILING ABOVE WITH PULL STRING, (2)

CAT6E CABLE, AND CONDUIT BUSHING FOR THE POWER SIDE OF THE JUNCTION BOX, SEE THE

POWER DRAWINGS FOR THE BRANCH CIRCUIT WIRING. DEVICE SHALL BE A U.L. RATED

ASSEMBLY FOR FLOOR PENETRATIONS. FINISH COLOR AND MATERIAL SHALL BE CHOSEN BY

ARCHITECT FROM MANUFACTURER'S FULL RANGE. SEE ARCHITECTURAL DRAWINGS FOR

FLOOR TYPES AND FINISHES FOR COORDINATION.

TELEPHONE OUTLET, 4" SQUARE x 2-1/8" DEEP GALVANIZED PRESSED STEEL, RECESSED

MOUNTED AT 18" ABOVE FINISHED FLOOR, WITH COVER PLATE AND 1 RJ45 JACK.

PROVIDE 3/4" CONDUIT WITH NYLON PULL STRING CONCEALED IN WALL UP TO ABOVE

SUSPENDED TILE CEILING. PROVIDE 1 CAT6 CABLE FOR VOICE. MAKE ALL FINAL

CONNECTIONS.

CEILING MOUNTED MOTION SENSOR, COMBINATION ULTRASONIC/ PASSIVE

INFRARED (PIR) DEVICE WITH ADJUSTABLE TIME DELAY 5 TO 15 MINUTES.

WALL MOUNTED OCCUPANCY SENSOR, COMBINATION ULTRASONIC/ PASSIVE

INFRARED (PIR) DEVICE WITH ADJUSTABLE TIME DELAY 5 TO 15 MINUTES.

CEILING MOUNTED OCCUPANCY SENSOR, COMBINATION ULTRASONIC/ PASSIVE

INFRARED (PIR) DEVICE WITH ADJUSTABLE TIME DELAY 5 TO 30 MINUTES.

WALL MOUNTED COMBINATION SWITCH AND OCCUPANCY SENSOR. 20 AMPERE,

120/277V, A.C. ONLY, RECESS MOUNTED AT 48" ABOVE FINISHED FLOOR. DUAL

TECHNOLOGY SENSOR SHALL BE FIELD ADJUSTABLE BETWEEN VACANCY AND

OCCUPANCY SENSOR MODES.

DIMMER SWITCH. 20 AMPERE, 120/277V, A.C. ONLY, RECESS MOUNTED AT 48"

ABOVE FINISHED FLOOR.

QUADRUPLEX RECEPTACLE, 20 AMPERE, 125 VOLT GROUNDING TYPE, NEMA

5-20R CONFIGURATION, RECESSED GROUND MOUNTED.

SWITCH, FLUSH TUMBLER TYPE, SINGLE POLE, 20 AMPERE, 120/277V, A.C.

ONLY, RECESS MOUNTED AT 48" ABOVE FINISHED FLOOR.

DUPLEX RECEPTACLE, 20 AMPERE, 125 VOLT GROUNDING TYPE, NEMA 5-20R

CONFIGURATION, RECESS MOUNTED IN 4" SQUARE x 2-1/2" DEEP PRESSED STEEL

JUNCTION BOX AT 6" ABOVE FINISHED FLOOR.

SECURITY CARD READER. RECESS MOUNTED AT 48" ABOVE FINISHED FLOOR.

SECURITY KEYPAD. RECESS MOUNTED AT 48" ABOVE FINISHED FLOOR.

CEILING-MOUNTED "REQUEST TO EXIT" PASSIVE INFRARED SENSOR.

CR

KP

DB

REX

PIR

OS

CEILING MOUNTED SECURITY GLASS BREAK SENSOR.GB

MD

SF

UNIVERSAL MOUNTED EXIT LIGHT, SINGLE OR DOUBLE FACED WITH DIRECTIONAL

CHEVRON ARROWS AS SHOWN, LIGHTING FIXTURE TYPE AS NOTED:

ABBREVIATIONS

SHEET SYMBOLS

AMPERES.A

AF

AFF

AHU

AT

ATS

AWG

BLDG.

C/B

EC

EMT

(E),EX.

(ETR)

FLA

GFCI

GFI GROUND FAULT INTERRUPTER.

GOVERNMENT FURNISHED, CONTRACTOR INSTALLED.

FULL LOAD AMPERES.

EXISTING TO REMAIN.

EXISTING.

ELECTRICAL METALLIC TUBING.

EMPTY CONDUIT.

CIRCUIT BREAKER.

BUILDING.

AMERICAN WIRE GAUGE.

AUTOMATIC TRANSFER SWITCH.

TRIP SIZE IN AMPERES.

AIR HANDLING UNIT.

ABOVE FINISHED FLOOR.

FRAME SIZE IN AMPERES.

GRD.

HOA

KAIC

KW KILO-WATTS.

THOUSAND AMPERE INTERRUPTING CAPACITY.

HAND-OFF-AUTOMATIC SELECTOR SWITCH.

GROUND CONDUCTOR.

M.L.O.

N.C.

N.E.C.

NEMA

NFSS

N.O.

P

PH.

PVC

RGS

U.L.

V

VFD

WP WEATHERPROOF, OR NEMA 3R ENCLOSURE.

VARIABLE FREQUENCY DRIVE.

VOLTAGE.

UNDERWRITER'S LABORATORIES.

RIGID GALVANIZED STEEL.

POLY-VINYL CHLORIDE.

NUMBER OF PHASES.

NUMBER OF POLES.

NORMALLY OPEN.

NON-FUSED SAFETY SWITCH.

NATIONAL ELECTRICAL MANUFACTURER'S ASSOCIATION.

NATIONAL ELECTRICAL CODE.

NORMALLY CLOSED.

MAIN LUGS ONLY.

FD FIRE DAMPER.

SD SMOKE DAMPER.

AV AUDIO/VISUAL DEDICATED OUTLET. MOUNT AT +55" AFF.

CEILING MOUNTED SPEAKER.SP

TELE/POWER POLE FOR SYSTEMS FURNITURE CONNECTION.PP

COMBINATION TELEPHONE AND DATA OUTLET, 4" SQUARE x 2-1/8" DEEP GALVANIZED

PRESSED STEEL, RECESSED MOUNTED AT 18" ABOVE FINISHED FLOOR, WITH COVER

PLATE AND 2 RJ45 JACKS. PROVIDE 1" CONDUIT WITH NYLON PULL STRING CONCEALED

IN WALL UP TO ABOVE SUSPENDED TILE CEILING. PROVIDE 2 CAT6 CABLES FOR VOICE

AND DATA. MAKE ALL FINAL CONNECTIONS.

AIP

a

GFI DUPLEX RECEPTACLE WITH GROUND FAULT CIRCUIT INTERRUPTER AND

NEMA 3R IN-USE WEATHERPROOF ENCLOSURE, 20 AMPERE, 125 VOLT

GROUNDING TYPE, NEMA 5-20R CONFIGURATION, SURFACE MOUNTED IN 4"

SQUARE x 2-1/8" DEEP PRESSED STEEL JUNCTION BOX AT 18" ABOVE

FINISHED FLOOR.

WP

GFI

DUPLEX RECEPTACLE WITH GROUND FAULT CIRCUIT INTERRUPTER, 20

AMPERE, 125 VOLT GROUNDING TYPE, NEMA 5-20R CONFIGURATION, RECESS

MOUNTED IN 4" SQUARE x 2-1/8" DEEP PRESSED STEEL JUNCTION BOX AT 18"

ABOVE FINISHED FLOOR.

GFI

DUPLEX RECEPTACLE WITH GROUND FAULT CIRCUIT INTERRUPTER, 20

AMPERE, 125 VOLT GROUNDING TYPE, NEMA 5-20R CONFIGURATION, RECESS

MOUNTED IN 4" SQUARE x 2-1/8" DEEP PRESSED STEEL JUNCTION BOX AT 8"

ABOVE COUNTERTOP.

QUADRUPLEX RECEPTACLE, 20 AMPERE, 125 VOLT GROUNDING TYPE, NEMA

5-20R CONFIGURATION, RECESS MOUNTED IN 4" SQUARE x DEEP PRESSED

STEEL JUNCTION BOX AT 18" ABOVE 2-1/8" FINISHED FLOOR.

QUADRUPLEX RECEPTACLE, 20 AMPERE, 125 VOLT GROUNDING TYPE, NEMA

5-20R CONFIGURATION, SURFACE MOUNTED IN 4" SQUARE x 2-1/8" DEEP

PRESSED STEEL JUNCTION BOX AT 18" ABOVE FINISHED FLOOR.

SPECIAL DEDICATED OUTLET, NEMA CONFIGURATION AS NOTED ON FLOOR

PLAN, RECESS MOUNTED IN 4" SQUARE x 2-1/8" DEEP PRESSED STEEL

JUNCTION BOX AT 18" ABOVE FINISHED FLOOR.

3-WAY LIGHT SWITCH, SINGLE POLE, 20 AMPERE, 120/277V, A.C.

ONLY, RECESS MOUNTED AT 48" ABOVE FINISHED FLOOR.

S3

BRANCH CIRCUIT CONDUIT AND CONDUCTORS RUN EXPOSED. SIZE IN

ACCORDANCE WITH N.E.C. RACEWAY SHALL BE MINIMUM 3/4"

CONDUIT, AND WIRE SHALL BE MINIMUM SIZE #12 AWG COPPER WITH

THHN INSULATION, UNLESS OTHER SIZES ARE SPECIFICALLY NOTED.

HEAVY DUTY ENCLOSED SAFETY SWITCH, SEE MOTOR AND EQUIPMENT

SCHEDULE FOR SIZES AND CHARACTERISTICS.

MOTOR, SEE MOTOR AND EQUIPMENT SCHEDULE FOR SIZES AND

CHARACTERISTICS.

P PUSH PLATE FOR AUTOMATIC DOOR OPENER. RECESS MOUNTED AT 36" ABOVE

FINISHED FLOOR.

SOC WALL MOUNTED COMBINATION DIMMER SWITCH AND OCCUPANCY SENSOR. 20

AMPERE, 120/277V, A.C. ONLY, RECESS MOUNTED AT 48" ABOVE FINISHED FLOOR.

DUAL TECHNOLOGY SENSOR SHALL BE FIELD ADJUSTABLE BETWEEN VACANCY

AND OCCUPANCY SENSOR MODES.

D

IC INTERCOM/COMMUNICATION DEVICE USED TO COMMUNICATE

BETWEEN ROOMS.

ELECTRICAL SYMBOLS CONTINUED

R WIRELESS CEILING-MOUNTED MICROPHONE. TO BE INSTALLED BY A/V TECHNICIAN. FOR

REFERENCE ONLY.

COMBINATION POWER/ DATA/ AUDIO/VISUAL FLOOR BOX.

PROVIDE (3) ADJACENT 4-13/16”X 4-1/8” X 2-1/2” JUNCTION BOXES RECESSED IN CONCRETE ON TOP

OF WALKER DUCT CHANNEL SYSTEM. PROVIDE (1)FLOORBOX WITH (4) PRE-WIRED 20A 125V

RECEPTACLES, (1) FLOORBOX WITH (2) STANDARD RJ45 TELECOM JACKS, (1)FLOORBOX WITH (2)

HDMI JACKS. ROUTE POWER CONDUCTORS THROUGH DESIGNATED WALKER DUCT POWER

CHANNEL BACK TO NEAREST WALKER ZONE DISTRIBUTION BOX. ROUTE CABLES THROUGH

DESIGNATED WALKER DUCT CHANNEL BACK TO NEAREST WALKER ZONE DISTRIBUTION BOX.

ROUTE AUDIO/VISUAL CABLES THROUGH DESIGNATED WALKER DUCT CHANNEL BACK TO

CEILING-MOUNTED WALKER ZONE DISTRIBUTION BOX. PROVIDE UL LISTED FIRE STOPPING TO

MAINTAIN RATING OF ALL PENETRATIONS. REFER TO STRUCTURAL DRAWINGS FOR PENETRATION

REQUIREMENTS.

COMBINATION TELEPHONE AND DATA OUTLET, RECESSED MOUNTED IN SYSTEMS

FURNITURE, WITH COMPATIBLE COVER PLATE AND 2 RJ45 JACKS. PROVIDE 2 CAT6A

CABLES FOR VOICE AND DATA FROM NEAREST FLOOR-MOUNTED SYSTEMS FURNITURE

FEED. MAKE ALL FINAL CONNECTIONS.

S

SYSTEMS FURNITURE POWER FEED, PROVIDE GALVANIZED PRESSED STEEL

JUNCTION BOX, 4-13/16”X 4-1/8” X 2-1/2” RECESSED IN CONCRETE ON TOP OF WALKER

DUCT CHANNEL SYSTEM. MAKE ALL FINAL CONNECTIONS TO POWER WHIP

FURNISHED WITH SYSTEMS FURNITURE. ROUTE CONDUCTORS FROM JUNCTION BOX

THROUGH DESIGNATED WALKER DUCT POWER CHANNEL BACK TO NEAREST

WALKER ZONE DISTRIBUTION BOX. PROVIDE UL LISTED FIRE STOPPING TO MAINTAIN

RATING OF ALL PENETRATIONS. REFER TO STRUCTURAL DRAWINGS FOR

PENETRATION REQUIREMENTS.

SF

COMMUNICATIONS FEED FOR SYSTEMS FURNITURE. PROVIDE GALVANIZED PRESSED

STEEL JUNCTION BOX, 4-13/16”X 4-1/8” X 2-1/2” RECESSED IN CONCRETE ON TOP OF

WALKER DUCT TELECOMMUNICATIONS CHANNEL SYSTEM. ROUTE CABLES THROUGH

DESIGNATED WALKER DUCT CHANNEL BACK TO NEAREST WALKER ZONE

DISTRIBUTION BOX. PROVIDE UL LISTED FIRE STOPPING TO MAINTAIN RATING OF ALL

PENETRATIONS. REFER TO STRUCTURAL DRAWINGS FOR PENETRATION

REQUIREMENTS.

WALKER DUCT ZONE DISTRIBUTION BOX FOR POWER, PROVIDE GALVANIZED

PRESSED STEEL JUNCTION BOX, 8-5/8” X 4-1/2” X 1-1/2” ABOVE CEILING. PROVIDE

1-1/2'' CONDUIT FROM DISTRIBUTION BOX BACK TO DESIGNATED ELECTRICAL

CLOSET.

WP

WALKER DUCT ZONE DISTRIBUTION BOX FOR TELECOMMUNICATIONS/DATA, PROVIDE

GALVANIZED PRESSED STEEL JUNCTION BOX, 8-5/8” X 4-1/2” X 1-1/2” ABOVE CEILING.

PROVIDE 1-1/2'' CONDUIT FROM DISTRIBUTION BOX BACK TO DESIGNATED

TELECOMMUNICATIONS/CLOSET.

WD

AV

SYSTEMS FURNITURE TELECOMMUNICATIONS FEED, WALL-RECESSED MOUNTED @

18” AFF; GALVANIZED PRESSED JUNCTION BOX, 4-1/2" LONG x 4-1/2" WIDE x 1-1/2"

DEEP. PROVIDE A 1" EMT CONDUIT ROUTED CONCEALED TO THE CEILING ABOVE

WITH PULL STRING, (2) CAT6A CABLES, AND CONDUIT BUSHING FOR

TELECOMMUNICATIONS CABLE. MAKE ALL FINAL CONNECTIONS TO SYSTEMS

FURNITURE DATA OUTLETS.

SECURITY CAMERA

WALKER DUCT ZONE DISTRIBUTION BOX FOR AUDIO/VISUAL, PROVIDE GALVANIZED

PRESSED STEEL JUNCTION BOX, 8-5/8” X 4-1/2” X 1-1/2” RECESSED IN CONCRETE ON

TOP OF WALKER DUCT CHANNEL SYSTEM. PROVIDE 1-1/2'' CONDUIT FROM ZONE

DISTRIBUTION BOX TO DISTRIBUTION BOX ABOVE CEILING.

WAV

SMOKE DAMPER STATUS INDICATOR.RTS

AC AIR CONDITIONING UNIT.

VAV VARIABLE AIR VOLUME BOX.

FPB FAN POWERED BOX.

FCU FAN COIL UNIT.

MANUAL "REQUEST TO EXIT" BUTTON. RECESS MOUNTED AT 48" ABOVE FINISHED FLOOR,

UNLESS OTHERWISE NOTED.

DURESS NOTIFICATION BUTTON WITH POLYCARBONATE COVER. MOUNTED UNDER DESK.

PROVIDE SURFACE MOUNTED RACEWAY TO CONCEAL ALL WIRING. MAKE ALL FINAL

CONNECTIONS.

LIGHTING MANAGEMENT SYSTEM WALL/DIMMER SWITCH. MOUNT AT 48'' AFF, UNLESS

OTHERWISE NOTED. BASIS OF DESIGN: ACUITY BRANDS NPODM SERIES WALLPOD.

LC

LIGHTING MANAGEMENT SYSTEM CONTROLLER. MOUNT AT 48'' AFF, UNLESS

OTHERWISE NOTED. BASIS OF DESIGN: ACUITY BRANDS FRESCO CONTROL SYSTEM

LC

LIGHTING MANAGEMENT SYSTEM OCCUPANCY SENSOR. MOUNT AT 48'' AFF, UNLESS

OTHERWISE NOTED. BASIS OF DESIGN: ACUITY BRANDS NCM PDT SERIES

LOS

VDB VIDEO DOOR BELL. RECESS MOUNTED AT 48" ABOVE FINISHED FLOOR. PROVIDE

BACKBOX AND CONDUIT WITH PULLSTRING.

DUPLEX RECEPTACLE, 20 AMPERE, 125 VOLT GROUNDING TYPE, NEMA 5-20R

CONFIGURATION, RECESS MOUNTED IN 4" SQUARE x 2-1/2" DEEP PRESSED

STEEL JUNCTION BOX, RECESSED IN CEILING.

JUNCTION BOX FOR A COMBINATION TELEPHONE AND DATA OUTLET, 4" SQUARE x

2-1/8" DEEP GALVANIZED PRESSED STEEL, RECESSED IN CEILING.

DUPLEX RECEPTACLE, 20 AMPERE, 125 VOLT GROUNDING TYPE, NEMA 5-20R

CONFIGURATION, RECESS MOUNTED IN 4" SQUARE x 2-1/8" DEEP PRESSED

STEEL JUNCTION BOX AT 8" ABOVE COUNTERTOP.

PROFESSIONAL CERTIFICATION. I HEREBY CERTIFY

THAT THESE DOCUMENTS WERE PREPARED OR

APPROVED BY ME, AND THAT I AM A DULY LICENSED

PROFESSIONAL ENGINEER UNDER THE LAWS OF THE

STATE OF MARYLAND, LICENSE NO. 49295, EXPIRATION

DATE: 12 MAY 2022.

S

FI

LE

N

RE

F:

PL

OT

D

AT

E:

/8/

4:

:55

P M

4.2

E-

1.D

W G

BREAKLINE

CL

NOTE REFERENCE NUMBER.

ROOM NUMBER DESIGNATION.

COLUMN LINE NUMBER.

DRAWING REVISION NUMBER.

CENTER LINE.

CONDUIT UP.

CONDUIT DOWN.DN

UP

DELTA CONFIGURATION.

WYE GROUNDING CONFIGURATION.

PHASE.Ø

NORTH ARROW

ARROW INDICATES TRUE NORTH

AND/OR PROJECT NORTHN

E101

N

8'0 1/8"=1'-0"

UNIQUE PLAN OR DETAIL

NUMBER ON THIS DRAWING NORTH ARROW

NAME OF PLAN OR DETAIL

ALL DRAWINGS WHERE

DETAIL IS REFERENCED

GRAPHIC SCALE OF

PLAN OR DETAIL

2-PART REFERENCE DETAIL IDENTIFICATION:

SHEET NUMBER WHERE

DETAIL/SECTION IS DRAWN

NUMBER INDICATES

DETAIL/SECTION

FLOOR PLAN

ED102, E-1022

FLOOR PLAN AND DETAIL TITLES:

NOTE REFERENCE NUMBER,

BOUNDARY/EXTENT AS INDICATED BY ARROW.

CONDUIT TURN DOWN.

SM

FRACTIONAL HORSEPOWER MANUAL MOTOR STARTER WITH SINGLE-POLE

TOGGLE DISCONNECT SWITCH, LOCKABLE TOGGLE GUARD, THERMAL

OVERLOAD RELAY, H-O-A SWITCH AND RED PILOT LIGHT IN 2-GANG SURFACE

MOUNTED NEMA 1 ENCLOSURE.

SM2

MOTOR-RATED TOGGLE SWITCH, 2-POLE, NON-REVERSING RATED FOR 1

HORSEPOWER (16 AMPERES CONTINUOUS CURRENT) @ 115-230/277 VOLTS IN

NEMA 1 ENCLOSURE WITH LOCKABLE TOGGLE GUARD. MOUNT ABOVE CEILING

ON STEEL SUPPORT CHANNEL ADJACENT TO EQUIPMENT SERVED.

COMBINATION MOTOR STARTER - ELECTRONIC MOTOR CIRCUIT PROTECTOR

(MCP) TYPE, FVNR,3-PHASE, NEMA SIZE 1, IN NEMA 1 ENCLOSURE WITH

208V-120V CONTROL TRANSFORMER WITH PRIMARY & SECONDARY FUSING,

120V AC COIL, H-O-A SWITCH, RED "ON" LED PUSH-TO-TEST PILOT

LIGHT AND (1) NORMALLY OPEN (N.O.) AND (1) NORMALLY CLOSED (N.C.)

AUXILIARY CONTACT.

CR

AV

PIR

PIR

P P

PIR

(E) (E) (E)CR

10 10

P

S

S S

S

S S S

S

SF

SF

SF

AV

AV

+55" AFF

PIR

E-401

E-401

S S

S S

S S S S S S S S S S S S S S S S

S S S

S S

S S

S S

S S S S

S S

S S

S S

S S

S S

S

SF SFS

S

S S

S S

S S

S S

S S

SF

S

S

S

S

S

S

SF

S

S

S

S

S

S

S

S

S

S

S

S

GFI GFI GFI GFI

GFI

GFI GFI

S S

S S

S S

S S

S S

S S

S S

S S

S S

CR

CR

PIR

PIR

AV

AV

AV

SM

PIR

S

S

S

S

S

SS

SS

SS

S

S

S

S S

S

S

FPB

2W-12A

FPB

2W-12B FPB

2W-12C

FPB

2W-12D

FPB

2W-12E

FPB

2W-12F

FPB

2-W12J

FPB

2W-12HFPB

2W-12G

FPB

2W-08A

FPB

2W-06A

FPB

2W-06B

FPB

2W-05A

FPB

2W-04A

FPB

2W-04B

FPB

2W-05B

FPB

2W-17A

FPB

2W-17B

FPB

2W-08B

SM

SM

SM

SM

SM

SM

J

J

J

WAV

2P-W3 1,3,5

2P-W3 7,9,11

2P-W3 13,15,172P-W3

19,21,23

2P-W3 25,27,29

2P-W3 2,4,6,38

2P-W3 14,16,18,40

2P-W3 8,10,12

2P-W3 20,22,24

2P-W3 26,28,30

2P-W3 26,28,30

2P-W3 31,33,35

2P-W3 49,51,53

S

SS

S

S

SF

SF

SF

2P-W3 50,52,54

2P-W3 56,58,60,62 62

2P-W3 55,57,59,61

2P-W3 63,65,67

2P-W3 69,71,73

2P-W3 37,39,41

2P-W3 42,44,46,48

2P-W3 75,77,79

2P-W3 64,66,68

SF

SF

2P-W3 76,78,80

2P-W3 70,72,74

2P-W2

2P-W2

2P-W2

2P-W2

2P-W2

2P-W2

2P-W2

2P-W2

2P-W2

2P-W2

2P-W2

2P-W2 23 11

GFI

GFI

GFI

GFI

E-104

9 9

2P-W2

2P-W2

2P-W2

2P-W2

2P-W2 20 2P-W2

2P-W2

2P-W2

2P-W2

2P-W2

2P-W2

2P-W2

2P-W2

2P-W2

2P-W2

2P-W2

2P-W2

2P-W2

2P-W2

2P-W2

2P-W2

SM

SM

SM

SM

SM

SM

SM

SM SM SM

SM

SM

SM

SM

SM

SM

SM

CRAIP

CR

CRAIP

AIP

CR

CR

DB13

DB13

DB13

DB13

DB13

DB13

DB13

DB13

DB13

DB13

DB13 DB13

DB 13

DB 13

2P-W2

2P-W2

2P-W2

2P-W2

2P-W2

2P-W2

2P-W2

2P-W2

2P-W2 2P-W2

2P-W2

2P-W3

+55" AFF

+55" AFF

+55" AFF

J

SF 2P-W3

43,45,47

(E)WALKER DUCT

(E)WALKER

DUCT

(E)WALKER

DUCT

(E)WALKER

DUCT

2L-W1

2L-W1

2L-W1

2L-W1

2L-W1

2L-W1

2L-W1

FPB

2W-09

FPB

2W-07

FPB

2W-13

FPB

2W-01

FPB

2W-14

FPB

2W-19

FPB

2W-18

FPB

2W-16

FPB

2W-11

FPB

2W-10

SM

SM

FPB

2W-20

FPB

2W-02

FPB

2W-03

2P-W2

2P-W2

2P-W2

2P-W2

TX-02-2

EF-02-1

SM2

SM SM SM SM

SM

SM

SM

SM

SM

SM

SM

SM

SM

2P-W2 45 2P-W2

46,48,50

SFSF

SFSFSF

SFSF SFSF

SFSF

SF

S

S

S

S

CR

AV

PIR

PIR

P P

PIR

(E) (E) (E)CR

10 10

P

S

S S

S

S S S

S

SF

SF

SF

AV

AV

+55" AFF

PIR

E-401

E-401

S S

S S

S S S S S S S S S S S S S S S S

S S S

S S

S S

S S

S S S S

S S

S S

S S

S S

S S

S

SF SFS

S

S S

S S

S S

S S

S S

SF

S

S

S

S

S

S

SF

S

S

S

S

S

S

S

S

S

S

S

S

GFI GFI GFI GFI

GFI

GFI GFI

S S

S S

S S

S S

S S

S S

S S

S S

S S

CR

CR

PIR

PIR

AV

AV

AV

SM

PIR

S

S

S

S

S

SS

SS

SS

S

S

S

S S

S

S

FPB

2W-12A

FPB

2W-12B FPB

2W-12C

FPB

2W-12D

FPB

2W-12E

FPB

2W-12F

FPB

2-W12J

FPB

2W-12HFPB

2W-12G

FPB

2W-08A

FPB

2W-06A

FPB

2W-06B

FPB

2W-05A

FPB

2W-04A

FPB

2W-04B

FPB

2W-05B

FPB

2W-17A

FPB

2W-17B

FPB

2W-08B

SM

SM

SM

SM

SM

SM

J

J

J

WAV

2P-W3 1,3,5

2P-W3 7,9,11

2P-W3 13,15,172P-W3

19,21,23

2P-W3 25,27,29

2P-W3 2,4,6,38

2P-W3 14,16,18,40

2P-W3 8,10,12

2P-W3 20,22,24

2P-W3 26,28,30

2P-W3 26,28,30

2P-W3 31,33,35

2P-W3 49,51,53

S

SS

S

S

SF

SF

SF

2P-W3 50,52,54

2P-W3 56,58,60,62 62

2P-W3 55,57,59,61

2P-W3 63,65,67

2P-W3 69,71,73

2P-W3 37,39,41

2P-W3 42,44,46,48

2P-W3 75,77,79

2P-W3 64,66,68

SF

SF

2P-W3 76,78,80

2P-W3 70,72,74

2P-W2

2P-W2

2P-W2

2P-W2

2P-W2

2P-W2

2P-W2

2P-W2

2P-W2

2P-W2

2P-W2

2P-W2 23 11

GFI

GFI

GFI

GFI

E-104

9 9

2P-W2

2P-W2

2P-W2

2P-W2

2P-W2 20 2P-W2

2P-W2

2P-W2

2P-W2

2P-W2

2P-W2

2P-W2

2P-W2

2P-W2

2P-W2

2P-W2

2P-W2

2P-W2

2P-W2

2P-W2

2P-W2

SM

SM

SM

SM

SM

SM

SM

SM SM SM

SM

SM

SM

SM

SM

SM

SM

CRAIP

CR

CRAIP

AIP

CR

CR

DB13

DB13

DB13

DB13

DB13

DB13

DB13

DB13

DB13

DB13

DB13 DB13

DB 13

DB 13

2P-W2

2P-W2

2P-W2

2P-W2

2P-W2

2P-W2

2P-W2

2P-W2

2P-W2 2P-W2

2P-W2

2P-W3

+55" AFF

+55" AFF

+55" AFF

J

SF 2P-W3

43,45,47

(E)WALKER DUCT

(E)WALKER

DUCT

(E)WALKER

DUCT

(E)WALKER

DUCT

2L-W1

2L-W1

2L-W1

2L-W1

2L-W1

2L-W1

2L-W1

FPB

2W-09

FPB

2W-07

FPB

2W-13

FPB

2W-01

FPB

2W-14

FPB

2W-19

FPB

2W-18

FPB

2W-16

FPB

2W-11

FPB

2W-10

SM

SM

FPB

2W-20

FPB

2W-02

FPB

2W-03

2P-W2

2P-W2

2P-W2

2P-W2

TX-02-2

EF-02-1

SM2

SM SM SM SM

SM

SM

SM

SM

SM

SM

SM

SM

SM

2P-W2 45 2P-W2

46,48,50

SFSF

SFSFSF

SFSF SFSF

SFSF

SF

S

S

S

S

H

G

F

E

D

C

10111213141516

020033

MAIL RM

+32" AFF

+32" AFF

+32" AFF

+32" AFF

+32" AFF

+32" AFF

C

SUMMER

CONSULTANTS

I N C O R P O R A T E D

SUMMER

CONSULTANTS

GENERAL NOTES

G1. ALL WORK SHALL BE NEW AND PROVIDED UNDER THIS

CONTRACT UNLESS SPECIFICALLY MARKED "EXISTING",

"EXIST.", OR "(E)".

G2. VERIFY LOCATION AND DIMENSIONS OF EXISTING

EQUIPMENT AND COORDINATE ALL WORK PRIOR TO THE

START OF CONSTRUCTION.

G3. SYSTEM FURNITURE SHALL BE WIRED IN 3-3-2

CONFIGURATION, WITH THREE PHASE CONDUCTORS,

THREE NEUTRAL CONDUCTORS, AND TWO GROUND

CONDUCTORS.

NOTES

1. SEE MOTOR AND EQUIPMENT SCHEDULE FOR MOTOR AND

FEEDER CHARACTERISTICS.

2. EXISTING OUTLET RETAINED UNDER DEMOLITION. PROVIDE

TWO (2) NEW CAT-6E CABLES TO OUTLET.

3. PROVIDE HARD-WIRED CONNECTION TO MOTORIZED

PARTITION. MAKE ALL FINAL CONNECTIONS BETWEEN

PARTITION AND CONTROL SWITCH.

4. PROVIDE HARD-WIRED CONNECTION TO SECURITY AUDIBLE

DEVICE.

5. PROVIDE CEILING MOUNTED RECEPTACLE AND DATA

OUTLET TO SERVE CEILING PROJECTOR. COORDINATE

EXACT LOCATION WITH FINAL EQUIPMENT LAYOUT.

6. SWITCH FURNISHED WITH MOTORIZED SCREEN. MAKE ALL

FINAL CONNECTIONS BETWEEN SWITCH, SCREEN, AND

MOTOR.

7. PROVIDE 3-WAY LOW VOLTAGE KEY SWITCH WITH

LOCKABLE COVER FOR MOTORIZED PARTITION. MAKE ALL

FINAL CONNECTIONS BETWEEN SWITCHES AND MOTOR.

8. PROVIDE HARDWIRED CONNECTION TO LECTERN.

COORDINATE LOCATION WITH FINAL EQUIPMENT LAYOUT.

9. PROVIDE DEDICATED RECEPTACLE AND DATA OUTLET

RECESSED IN SYSTEMS FURNITURE TO SERVE PLOTTER.

10. PROVIDE RECEPTACLE AND COVER PLATE. CONNECT TO

EXISTING CONDUIT AND CONDUCTORS RETAINED UNDER

DEMOLITION. CONNECT RECEPTACLE TO PANEL AND

CIRCUIT NUMBER AS INDICATED.

11. PROVIDE (2) RECEPTACLES RECESSED IN SHELVES. MOUNT

RECEPTACLES AT 38" AFF AND 58" AFF.

12. REFER TO ARCHITECTURAL PLANS AND ELEVATIONS FOR

EXACT MOUNTING LOCATIONS.

13. FIELD LOCATE SECURITY DEVICE ON UNDERSIDE OF DESK.

PROVIDE SURFACE MOUNTED RACEWAY TO CONCEAL ALL

SECURITY WIRING. COORDINATE WITH ARCHITECTURAL

DRAWINGS.

N

8'0 16' 1/8"=1'-0"

SECOND FLOOR PLAN (WEST) - POWER1

N

8'0 16' 1/8"=1'-0"

PART PLAN - MAIL ROOM

E-1042

PROFESSIONAL CERTIFICATION. I HEREBY CERTIFY

THAT THESE DOCUMENTS WERE PREPARED OR

APPROVED BY ME, AND THAT I AM A DULY LICENSED

PROFESSIONAL ENGINEER UNDER THE LAWS OF THE

STATE OF MARYLAND, LICENSE NO. 49295, EXPIRATION

DATE: 12 MAY 2022.

FI

LE

N

RE

F:

PL

OT

D

AT

E:

/8/

4:

:16

P M

4.2

E-

4-

.D

W G

020028

020001

020031

020030

020029

020032

020027

020025

020026

020033

020034

020037

020036

020035

020024

020001

020003

020004

020038

020023

020022

020021

020020

020019

020008

020007

020006

020018

020005 020002

020012

020013

020014

020015

020016

020017

020011 020010 020009

1 ADDENDUM 3 11/09/21

TELECOMMUNICATIONS

GROUNDING BUS BAR

4' X 8' AC GRADE 3/4" PLYWOOD BACKBOARD.

REFER TO ARCHITECTURAL PLANS

FOR SPECIFICATIONS.

D

CABLOFIL 2" X 16" CF 54/400

CABLE TRAY.

PANEL

T025010

PANEL

P025010

AC 2E-01

CAMPUS INTERCONNECTING CONDUITS (QUANTITY 5)

WITH BUSHING AND FIRESTOP.

INTERDUCT FOR FIBER. TRADE SIZE 2.

TR INTERCONNECTING CONDUITS (QUANTITY 6)

WITH BUSHING AND FIRESTOP.

INTERDUCT FOR FIBER. TRADE SIZE 4.

CONDUIT SLEEVES WITH BUSHING AND FIRESTOP

FOR HORIZONTAL DISTRIBUTION

1,3,5

7,9,11

2,4,6

PANEL P025028

AC 2E-02

PANEL T025028 PANEL T02502722

CABLOFIL 2" X 16" CF 54/400

CABLE TRAY.

TWO (2) CONDUITS INTERCONNECTING NETWORK

SUPPORT CENTER WITH ENTRANCE FACILITY, TRADE SIZE 2.

TELECOMMUNICATIONS

GROUNDING BUS BAR

TELECOMMUNICATIONS

GROUNDING BUS BAR

1,3,5 7,9,11

13,15,17

2,4,6

1,3,5 7,9,1111

CABLOFIL 2" X 16" CF 54/400

CABLE TRAY.

1 8,10,12

AC 2E-03

1,3,5

AC 1-01

7,9,11

CAMPUS INTERCONNECTING CONDUITS (QUANTITY 5)

WITH BUSHING AND FIRESTOP.

INTERDUCT FOR FIBER. TRADE SIZE 2.

TR INTERCONNECTING CONDUITS (QUANTITY 6)

WITH BUSHING AND FIRESTOP.

INTERDUCT FOR FIBER. TRADE SIZE 4.

CONDUIT SLEEVES WITH BUSHING AND FIRESTOP

FOR HORIZONTAL DISTRIBUTION

CABLOFIL 2" X 16" CF 54/400

CABLE TRAY.

PANEL P010044

PANEL T010044

TELECOMMUNICATIONS

GROUNDING BUS BAR

4' X 8' AC GRADE 3/4"

PLYWOOD BACKBOARD.

REFER TO ARCHITECTURAL

PLANS FOR SPECIFICATIONS.

4' X 8' AC GRADE 3/4" PLYWOOD BACKBOARD.

REFER TO ARCHITECTURAL PLANS FOR

SPECIFICATIONS.

2,4,6

5 710

4' X 8' AC GRADE 3/4"

PLYWOOD BACKBOARD.

REFER TO ARCHITECTURAL

PLANS FOR SPECIFICATIONS.

AC 16-04

TWO (2) CONDUITS INTERCONNECTING NETWORK

SUPPORT CENTER WITH ENTRANCE FACILITY, TRADE SIZE 4.

CONDUIT SLEEVES WITH BUSHING AND FIRESTOP

FOR CABLING FROM WORK AREA DATA OUTLETS

AND TELECOMMUNICATIONS ROOMS.

VERTICAL CABLE MANAGER WITH DOOR.

ORTRONICS OR-MM10VMD706-W

6" VERTICAL CABLE MANAGEMENT CAGE.

CABLOFIL 2" X 16" CF 54/400

CABLE TRAY.

TELECOMMUNICATIONS

GROUNDING BUS BAR

PANEL

P160003PANEL

T160003

7,9,11

1,3,5

2,4,6

SUMMER

CONSULTANTS

I N C O R P O R A T E D

SUMMER

CONSULTANTS

GENERAL NOTES

G1. ALL WORK SHALL BE NEW AND PROVIDED UNDER THIS

CONTRACT UNLESS SPECIFICALLY MARKED "EXISTING",

"EXIST.", OR "(E)".

G2. VERIFY LOCATION AND DIMENSIONS OF EXISTING

EQUIPMENT AND COORDINATE ALL WORK PRIOR TO

THE START OF CONSTRUCTION.

NOTES

1. SEE MECHANICAL AND EQUIPMENT SCHEDULE FOR

MOTOR AND FEEDER CHARACTERISTICS.

2. SERVICE PANELBOARD FOR RACK POWER IN NETWORK

SUPPORT CENTER. IT LOAD ONLY. SHALL BE EQUIPPED

WITH SCHNEIDER EM3500 SERIES DIN RAIL METER OR

EQUIVALENT.

3. NOT USED.

4. NOT USED.

5. NOT USED.

6. SERVICE PANELBOARD FOR NON-IT LOADS, HVAC,

CONVENIENCE RECEPTACLES. SHALL BE EQUIPPED

WITH SCHNEIDER EM3500 SERIES DIN RAIL METER OR

EQUIVALENT.

7. CHATSWORTH CABINET WITH VERTICAL EXHAUST DUCT

(VED). VED WILL EXTEND TO SUSPENDED CEILING.

8. OR-MM20730-W. 30" DEEP CHANNEL 7'H. 45RU.

ORTRONICS MM20 CHANNEL RACK.

9. 30A 208V TWIST LOCK 8.5' AFF {WYE (5-WIRE)

CONFIGURED, 208V, 30A, THREE-PHASE, TERMINATING

IN A NEMA L21-30R LOCKING RECEPTACLE. THE

NEUTRAL CONDUCTOR IN EACH WHIP IS TO BE UPSIZED.

LOCATION IS APPROXIMATE.

10. UNLESS OTHERWISE NOTED ALL RECEPTACLES

SERVING DATA RACKS AND I.T. LOADS SHALL BE FED

FROM PANEL 'T010044'. HVAC EQUIPMENT, GENERAL

PURPOSE EQUIPMENT, CONVENIENCE RECEPTACLES,

ETC. SHALL BE FED FROM PANEL 'P010044'.

11. UNLESS OTHERWISE NOTED ALL RECEPTACLES

SERVING DATA RACKS AND I.T. LOADS SHALL BE FED

FROM PANEL 'T025028'. HVAC EQUIPMENT, GENERAL

PURPOSE EQUIPMENT, CONVENIENCE RECEPTACLES,

ETC. SHALL BE FED FROM PANEL 'P025028'.

12. UNLESS OTHERWISE NOTED ALL RECEPTACLES

SERVING DATA RACKS AND I.T. LOADS SHALL BE FED

FROM PANEL 'T025027'. HVAC EQUIPMENT, GENERAL

PURPOSE EQUIPMENT, CONVENIENCE RECEPTACLES,

ETC. SHALL BE FED FROM PANEL 'P025028' (LOCATED IN

ADJACENT ROOM).

13. UNLESS OTHERWISE NOTED ALL RECEPTACLES

SERVING DATA RACKS AND I.T. LOADS SHALL BE FED

FROM PANEL 'T025010'. HVAC EQUIPMENT, GENERAL

PURPOSE EQUIPMENT, CONVENIENCE RECEPTACLES,

ETC. SHALL BE FED FROM PANEL 'P025010'.

14. UNLESS OTHERWISE NOTED ALL RECEPTACLES

SERVING DATA RACKS AND I.T. LOADS SHALL BE FED

FROM PANEL 'T160003'. HVAC EQUIPMENT, GENERAL

PURPOSE EQUIPMENT, CONVENIENCE RECEPTACLES,

ETC. SHALL BE FED FROM PANEL 'P160003'.

8'0 4' 1/4"=1'-0"

SECOND FLOOR - EAST - TELECOM CLOSET

ROOM 025010

E-1033

8'0 4' 1/4"=1'-0"

ROOM 025027 IRM/IDF CLOSET

ROOM 025028 IRM COMPUTER ROOM

E-1032

FI

LE

N

RE

F:

PL

OT

D

AT

E:

/8/

4:

:36

P M

4.2

E-

2.D

W G

PROFESSIONAL CERTIFICATION. I HEREBY CERTIFY

THAT THESE DOCUMENTS WERE PREPARED OR

APPROVED BY ME, AND THAT I AM A DULY LICENSED

PROFESSIONAL ENGINEER UNDER THE LAWS OF THE

STATE OF MARYLAND, LICENSE NO. 49295, EXPIRATION

DATE: 12 MAY 2022.

8'0 4' 1/4"=1'-0"

FIRST FLOOR TELECOM CLOSET

ROOM 010044

E-1021

8'0 4' 1/4"=1'-0"

16TH FLOOR - IDF CLOSET

ROOM 160003

E-1054

1 ADDENDUM 3 11/09/21

I N C O R P O R A T E D

SUMMER

CONSULTANTS

GENERAL NOTES

G1. ALL WORK SHALL BE NEW AND PROVIDED UNDER THIS

CONTRACT UNLESS SPECIFICALLY MARKED "EXISTING",

"EXIST.", OR "(E)".

G2. VERIFY LOCATION AND DIMENSIONS OF EXISTING

EQUIPMENT AND COORDINATE ALL WORK PRIOR TO

THE START OF CONSTRUCTION.

NOTES

1. PROVIDE CIRCUIT BREAKER IN EXISTING PANELBOARD.

2. PANEL SCHEDULES TOTALS DO NOT INCLUDE EXISTING

LOADS.

(E)PANEL 'GP-W1-SEC. 1' SCHEDULE

MAIN BUS SIZE (AMPS): 225A INTERRUPT. RATING (KAIC): 10 NEUTRAL BUS SIZE: 100% MOUNTING TYPE: SURFACE MAIN BUS MATERIAL: COPPER VOLTAGE: 120 / 208 SECTION NO.: 1 OF 1 LOCATION: MAIN ELECTRICAL ROOM MAIN CIRCUIT BREAKER (AMPS): 100 PHASE: 3 WIRE: 4 ENCLOSURE TYPE: NEMA 1 BOLT-ON BRANCH CIRCUIT BREAKERS

CKT

NO. DESCRIPTION LOAD

TYPE

LOAD

(KVA)

BREAKER BREAKER LOAD

(KVA)

LOAD

TYPE DESCRIPTION CKT

NO.AMPS POLES POLES AMPS

1 (E)LOAD N 0.00 20 1 A 1 20 0.72 R (E)LOAD 2

3 (E)LOAD N 0.00 20 1 B 1 20 0.72 R (E)LOAD 4

5 (E)LOAD N 0.00 20 1 C 1 20 0.72 R (E)LOAD 6

7 (E)LOAD N 0.00 20 1 A 1 20 0.54 N (E)LOAD 8

9 (E)LOAD N 0.00 20 1 B 1 20 0.90 R (E)LOAD 10

11 (E)LOAD N 0.00 20 1 C 1 20 0.00 N (E)LOAD 12

13 (E)LOAD N 0.00 20 1 A 1 20 0.72 R (E)LOAD 14

15 (E)LOAD N 0.00 20 1 B 1 20 0.00 N (E)LOAD 16

17 (E)LOAD N 0.00 20 1 C 1 20 0.72 R (E)LOAD 18

19 (E)LOAD N 0.00 20 1 A 1 20 0.00 N (E)LOAD 20

21 (E)LOAD N 0.00 20 1 B 1 20 0.00 N (E)LOAD 22

23 (E)LOAD N 0.00 20 1 C 1 20 0.00 N (E)LOAD 24

25 (E)LOAD N 0.00 20 1 A 1 20 0.00 N (E)LOAD 26

27 (E)LOAD N 0.00 20 1 B 1 20 0.00 N (E)LOAD 28

29 (E)LOAD N 0.00 20 1 C 1 20 0.00 N (E)LOAD 30

31 N 0.00 20 1 A 1 20 0.60 N SYS. FURN RM GF0009 A 32

33 N 0.00 20 1 B 1 20 0.60 N SYS. FURN RM GF0009 B 34

35 (E)LOAD N 0.00 20 1 C 1 20 0.60 N SYS. FURN RM GF0009 C 36

37 N 0.00 20 1 A 1 20 0.60 N SYS. FURN RM GF0009 A 38

39 N 0.00 20 1 B 1 20 0.60 N SYS. FURN RM GF0009 B 40

41 (E)LOAD N 0.00 20 1 C 1 20 0.60 N SYS. FURN RM GF0009 C 42

CONNECTED LOAD PER PHASE (kVA) = 3.2 2.8 2.6 TOTAL CONNECTED LOAD = 8.6 KVA 24.0 AMPS

(AMPS) = 26.5 23.5 22.0 TOTAL DEMAND LOAD = 8.6 KVA 24.0 AMPS

LOAD TYPES: C = CONTINUOUS, R = RECEPTACLE, M = MOTOR, N = NON-CONTINUOUS

(E)PANEL 'GP-W2' SCHEDULE

MAIN BUS SIZE (AMPS): 125A INTERRUPT. RATING (KAIC): 10 NEUTRAL BUS SIZE: 100% MOUNTING TYPE: SURFACE MAIN BUS MATERIAL: COPPER VOLTAGE: 120 / 208 SECTION NO.: 1 OF 1 LOCATION: MAIN ELECTRICAL ROOM MAIN CIRCUIT BREAKER (AMPS): PHASE: 3 WIRE: 4 ENCLOSURE TYPE: NEMA 1 BOLT-ON BRANCH CIRCUIT BREAKERS

CKT

NO. DESCRIPTION LOAD

TYPE

LOAD

(KVA)

BREAKER BREAKER LOAD

(KVA)

LOAD

TYPE DESCRIPTION CKT

NO.AMPS POLES POLES AMPS

1 (E)LOAD N 0.00 -- 1 A 1 -- 0.00 N (E)LOAD 2

3 (E)LOAD N 0.00 -- 1 B 1 -- 0.00 N (E)LOAD 4

5 (E)LOAD N 0.00 -- 1 C 1 -- 0.00 N (E)LOAD 6

7 (E)LOAD N 0.00 -- 1 A 1 -- 0.00 N (E)LOAD 8

9 (E)LOAD N 0.00 -- 1 B 1 -- 0.00 N (E)LOAD 10

11 (E)LOAD N 0.00 -- 1 C 1 -- 0.00 N (E)LOAD 12

13 (E)LOAD N 0.00 -- 1 A 1 -- 0.00 N (E)LOAD 14

15 (E)LOAD N 0.00 -- 1 B 1 -- 0.00 N (E)LOAD 16

17 (E)LOAD N 0.00 -- 1 C 1 -- 0.00 N (E)LOAD 18

19 (E)LOAD N 0.00 -- 1 A 1 -- 0.00 N (E)LOAD 20

21 (E)LOAD N 0.00 -- 1 B 1 -- 0.00 N (E)LOAD 22

23 (E)LOAD N 0.00 -- 1 C 1 -- 0.00 N (E)LOAD 24

25 (E)LOAD N 0.00 -- 1 A 1 -- 0.00 N (E)LOAD 26

27 (E)LOAD N 0.00 -- 1 B 1 -- 0.00 N (E)LOAD 28

29 (E)LOAD N 0.00 -- 1 C 1 -- 0.00 N (E)LOAD 30

31 REC. RM GF0005 R 0.80 20 1 A 1 20 0.60 N REC. PLOTTER 32

33 REC. RM GF0005 R 0.72 20 1 B 1 20 0.60 N REC. PLOTTER 34

35 REC. RM GF0005 R 0.54 20 1 C 1 20 0.60 N REC. PLOTTER 36

37 SPARE N 0.00 -- 1 A 1 20 0.60 N REC. PLOTTER 38

39 SPARE N 0.00 -- 1 B 1 20 0.60 N REC. PLOTTER 40

41 REC. RM GF0010 R 1.80 20 1 C 1 20 0.60 N REC. PLOTTER 42

CONNECTED LOAD PER PHASE (kVA) = 2.0 1.9 3.5 TOTAL CONNECTED LOAD = 7.5 KVA 20.7 AMPS

(AMPS) = 16.7 16.0 29.5 TOTAL DEMAND LOAD = 7.5 KVA 20.7 AMPS

LOAD TYPES: C = CONTINUOUS, R = RECEPTACLE, M = MOTOR, N = NON-CONTINUOUS

PANEL 'P010044' SCHEDULE

MAIN BUS SIZE (AMPS): 100A INTERRUPT. RATING (KAIC): 10 NEUTRAL BUS SIZE: 100% MOUNTING TYPE: SURFACE MAIN BUS MATERIAL: COPPER VOLTAGE: 120 / 208 SECTION NO.: 1 OF 1 LOCATION: I.T ROOM 010043 MAIN CIRCUIT BREAKER (AMPS): 60A PHASE: 3 WIRE: 4 ENCLOSURE TYPE: NEMA 1 BOLT-ON BRANCH CIRCUIT BREAKERS

CKT

NO. DESCRIPTION LOAD

TYPE

LOAD

(KVA)

BREAKER BREAKER LOAD

(KVA)

LOAD

TYPE DESCRIPTION CKT

NO.AMPS POLES POLES AMPS

1 RECEPTACLES N 0.36 20 1 A

3 15

0.51 M

A/C UNIT 1-01

3 RECEPTACLES N 0.36 20 1 B 0.51 M 4

5 RECEPTACLES N 0.72 20 1 C 0.51 M 6

7 RECEPTACLES N 0.72 20 1 A

3 20

0.10 C

POWER METER

9 SPARE N 0.00 20 1 B 0.10 C 10

11 SPARE N 0.00 20 1 C 0.10 C 12

13 SPARE N 0.00 20 1 A 1 20 0.00 N SPARE 14

15 SPACE N 0.00 - 1 B 1 -- 0.00 N SPACE 16

17 SPACE N 0.00 - 1 C 1 -- 0.00 N SPACE 18

19 SPACE N 0.00 -- 1 A 1 -- 0.00 N SPACE 20

21 SPACE N 0.00 -- 1 B 1 -- 0.00 N SPACE 22

23 SPACE N 0.00 -- 1 C 1 -- 0.00 N SPACE 24

25 SPACE N 0.00 -- 1 A 1 -- 0.00 N SPACE 26

27 SPACE N 0.00 -- 1 B 1 -- 0.00 N SPACE 28

29 SPACE N 0.00 -- 1 C 1 -- 0.00 N SPACE 30

CONNECTED LOAD PER PHASE (kVA) = 1.7 1.0 1.3 TOTAL CONNECTED LOAD = 4.0 KVA 11.1 AMPS

(AMPS) = 14.1 8.1 11.1 TOTAL DEMAND LOAD = 4.4 KVA 12.4 AMPS

LOAD…