Amendment 005 SF30.pdf
PDF 6 MB Posted
- Solicitation number
- 47PD0321R0022
About this file
This pre-solicitation notice describes a planned competitive negotiated procurement for Veteran Benefits Administration Regional Office renovations at the George H. Fallon Federal Building in Baltimore, Maryland. The project scope includes demolition, interior renovations for new tenant layouts including offices, workstations, file and storage rooms, and conference/training rooms. Associated mechanical, electrical, plumbing, fire protection and IT work is required. The project will be completed in four phases with a period of performance of 1,062 calendar days. The procurement will utilize a best value source selection method and be set aside for small businesses. Technical proposals are due by September 2021 with price proposals. A pre-proposal conference will be held in September 2021.
View the file
Other files
Show all 24
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Offers must acknowledge receipt of this amendment prior to the hour and date specified in the solicitation or as amended, by one of the following methods:
(a) By completing items 8 and 15, and returning or (c) By separate letter or electronic communication which includes a reference to the solicitation and amendment numbers. FAILURE OF YOUR ACKNOWLEDGMENT TO BE
RECEIVED AT THE PLACE DESIGNATED FOR THE RECEIPT OF OFFERS PRIOR TO THE HOUR AND DATE SPECIFIED MAY RESULT IN REJECTION OF YOUR OFFER. If by virtue of this amendment you desire to change an offer already submitted, such change may be made by letter or electronic communication, provided each letter or electronic communication makes reference to the solicitation and this amendment, and is received prior to the opening hour and date specified.
E. IMPORTANT: is required to sign this document and return copies to the issuing office.is notContractor
AMENDMENT OF SOLICITATION/MODIFICATION OF CONTRACT
1. CONTRACT ID CODE
5. PROJECT NUMBER (If applicable)
7. ADMINISTERED BY (If other than Item 6) CODE
STANDARD FORM 30 (REV. 11/2016)
Prescribed by GSA FAR (48 CFR) 53.243
FACILITY CODE
R10A. MODIFICATION OF CONTRACT/ORDER NUMBE
10B. DATED (SEE ITEM 13)
11. THIS ITEM ONLY APPLIES TO AMENDMENTS OF SOLICITATIONS
is not extended.is extended.The above numbered solicitation is amended as set forth in Item 14. The hour and date specified for receipt of Offers
12. ACCOUNTING AND APPROPRIATION DATA (If required) copies of the amendment; (b) By acknowledging receipt of this amendment on each copy of the offer submitted;
13. THIS ITEM APPLIES ONLY TO MODIFICATIONS OF CONTRACTS/ORDERS.
IT MODIFIES THE CONTRACT/ORDER NUMBER AS DESCRIBED IN ITEM 14.
CHECK ONE A. THIS CHANGE ORDER IS ISSUED PURSUANT TO: (Specify authority) THE CHANGES SET FORTH IN ITEM 14 ARE MADE IN THE CONTRACT ORDER
NUMBER IN ITEM 10A.
B. THE ABOVE NUMBERED CONTRACT/ORDER IS MODIFIED TO REFLECT THE ADMINISTRATIVE CHANGES (such as changes in paying office, appropriation data, etc.) SET FORTH IN ITEM 14, PURSUANT TO THE AUTHORITY OF FAR 43.103(b).
C. THIS SUPPLEMENTAL AGREEMENT IS ENTERED INTO PURSUANT TO AUTHORITY OF:
D. OTHER (Specify type of modification and authority)
15C. DATE SIGNED 16C. DATE SIGNED
CODE6. ISSUED BY
8. NAME AND ADDRESS OF CONTRACTOR (Number, street, county, State and ZIP Code) (X)
CODE
15B. CONTRACTOR/OFFEROR
(Signature of person authorized to sign)
16B. UNITED STATES OF AMERICA
(Signature of Contracting Officer)
Previous edition unusable
4.� REQUISITION/PURCHASE REQUISITION NUMBER�
9A. AMENDMENT OF SOLICITATION NUMBER
47PD0321R0022
9B. DATED (SEE ITEM 11)
09/30/2021
3PQNS3PQNS
GSA ACQUISITION SVCS NORTH - SSA SECTION
100 S. INDEPENDENCE MALL WEST
PHILADELPHIA, PA 19106-2320 USA
GSA ACQUISITION SVCS NORTH - SSA SECTION
100 S. INDEPENDENCE MALL WEST
PHILADELPHIA, PA 19106-2320 USA
15A. NAME AND TITLE OF SIGNER (Type or print)
X
16A. NAME AND TITLE OF CONTRACTING OFFICER (Type or print)
2. AMENDMENT/MODIFICATION NUMBER
3. EFFECTIVE DATE
11/18/2021
14. DESCRIPTION OF AMENDMENT/MODIFICATION (Organized by UCF section headings, including solicitation/contract subject matter where feasible.)
Veteran Benefits Administration Regional Office (VARO) Renovations at the George H. Fallon Federal Building in Baltimore,MD
PAGE OF PAGE
1 290
KimberlyADesant Typewriter Please see attached.
Please Note: In Amendment 004, the answers to questions 113, 128, & 133 reference documents issued with “Addendum 003”. “Addendum 003” was inadvertently omitted from Amendment 004. “Addendum 003” is attached to this amendment.
Also, question 110 states that the card readers and security system is by contractor. However, questions 142 & 174 state that the contractor is to provide conduit, backbox, & pullstring only.
This is a conflict. The correct answer is, the contractor will provide key card readers and the IT/AV infrastructure shown in the drawings.
In addition, Wage Determination MD20210031 (Rev. 9), dated 11/05/2021, is hereby incorporated into this solicitation and replaces Wage Determination MD20210031 (Rev. 8) in its entirety.
The proposal closing date has been extended from 11/24/2021 at 2:00 pm to 12/01/2021 at 2:00 pm, Philadelphia local time.
All other terms and conditions of this solicitation remain unchanged.
KimberlyADesant
3200 Lee Highway, Arlington, Virginia 22207 703.524.6616 www.mtfa.net
ADDENDUM #03
Project: VARO Reprogramming Development and Final Design Project
Date: Tuesday, November 09, 2021
Re: Addendum #03
Contents: Written Addendum (288 pages)
This addendum is supplementary to the drawings and specifications for the VARO Reprogramming Development and Final Design Project. All revisions, deletions, and additions shall be part of the contract as if originally shown in the drawings and specifications.
Narrative Summary of Addendum 03:
All revisions are clouded and are marked with a delta 1 (triangle symbol).
The items associated with the Fan Coil Unit Replacement Project is denoted with *FCU.
See all attachments.
DRAWINGS:
Item No. Dwg. Description
1. G-002 Re-issued drawing with clouded changes.
2. PD106 Re-issued drawing with clouded changes.
3. P-107 Re-issued drawing with clouded changes.
4. MD103 Re-issued drawing with clouded changes.
5. M-103 Re-issued drawing with clouded changes.
6. E-001 Re-issued drawing with clouded changes.
7. E-104 Re-issued drawing with clouded changes.
8. E-402 Re-issued drawing with clouded changes.
9. E-601 Re-issued drawing with clouded changes.
10. E-605 Re-issued drawing with clouded changes.
11. E-607 Re-issued drawing with clouded changes.
12. E-702 Add drawing sheet
KimberlyADesant
(included in Amendment 005)
Addendum #03 November 09, 2021
13. A-902 (*FCU) Re-issued drawing with clouded changes.
14. E-904 (*FCU) Re-issued drawing with clouded changes.
SPECIFICATIONS:
Item No. Section Paragraph Description
1 TOC N/A The TOC has been revised.
2 N/A N/A Remove all Division 22, 23, 26, and 27 specification sections and replace with the attached specification sections. (Division 22 has 6 sections, Division 23 has 29 sections, Division 26 has 10 sections, and Division 27 has 1 section.)
3 262416 N/A Add specification section 26416.
END OF NARRATIVE SUMMARY FOR ADDENDUM #03
DRAWING INDEX
FURNITURE DRAWING SET
(UNDER SEPARATE COVER )
FOR REFERENCE ONLY
Ÿ
100% CD SET
Ÿ Ÿ Ÿ Ÿ Ÿ Ÿ
Ÿ Ÿ Ÿ Ÿ Ÿ
Ÿ Ÿ Ÿ Ÿ Ÿ
Ÿ
Ÿ
Ÿ Ÿ
Ÿ Ÿ Ÿ Ÿ Ÿ
Ÿ Ÿ Ÿ Ÿ Ÿ
Ÿ Ÿ Ÿ Ÿ Ÿ
Ÿ Ÿ Ÿ Ÿ Ÿ
Ÿ Ÿ Ÿ Ÿ Ÿ
Ÿ Ÿ Ÿ Ÿ Ÿ
Ÿ Ÿ Ÿ Ÿ Ÿ
Ÿ Ÿ
Ÿ Ÿ Ÿ Ÿ Ÿ Ÿ Ÿ
Ÿ
Ÿ Ÿ Ÿ
Ÿ Ÿ
Ÿ
Ÿ Ÿ
Ÿ Ÿ
Ÿ
Ÿ
Ÿ Ÿ Ÿ Ÿ
Ÿ Ÿ Ÿ Ÿ
Ÿ Ÿ
Ÿ Ÿ
Ÿ Ÿ
Ÿ Ÿ
Ÿ Ÿ
Ÿ Ÿ
Ÿ Ÿ
Ÿ Ÿ
Ÿ
Ÿ
Ÿ
Ÿ
Ÿ Ÿ Ÿ Ÿ Ÿ Ÿ
Ÿ Ÿ Ÿ Ÿ
Ÿ Ÿ
Ÿ
Ÿ
Ÿ Ÿ
Ÿ Ÿ
Ÿ
Ÿ Ÿ Ÿ Ÿ Ÿ Ÿ
Ÿ Ÿ
Ÿ Ÿ Ÿ
Ÿ Ÿ Ÿ
Ÿ
Ÿ Ÿ Ÿ Ÿ Ÿ Ÿ Ÿ Ÿ Ÿ Ÿ
Ÿ Ÿ Ÿ Ÿ Ÿ Ÿ Ÿ Ÿ Ÿ Ÿ
Ÿ Ÿ
Ÿ Ÿ
Ÿ Ÿ Ÿ Ÿ Ÿ Ÿ
Ÿ
Ÿ Ÿ Ÿ Ÿ Ÿ
Ÿ Ÿ Ÿ Ÿ Ÿ
Ÿ Ÿ
Ÿ
Ÿ Ÿ Ÿ
Ÿ Ÿ
Ÿ Ÿ Ÿ
Ÿ
Ÿ
Ÿ
Ÿ
Ÿ
Ÿ
Ÿ
Ÿ
Ÿ
Ÿ
Ÿ Ÿ
Ÿ
Ÿ
Ÿ
Ÿ
Ÿ
Ÿ
45678910
D
E
F
G
(E)3"ST
(E)3"ST
(E)4"ST(E)3"ST
(E)8"ST UP& DN.
SK 1
(E)6"W
UP&DN.
(E)4"V UP&DN.
(E)4"W
UP&DN.
(E)1-/2"HW DN.
(E)1-1/2"CW DN.
(E)6"V UP&DN.
(E)3"CW DN.
(E)1/2"HW
(E)1-1/2"V 2 (E)1-1/2"CW
(E)4"CW
1-1/2"V
11-1/2"W 2
1/2"CW
(E)4"V UP&DN.
(E)1-/2"HW DN.
(E)1-1/2"CW DN.
1CAP
1/2"HW1CAP
(E)W
GENERAL NOTES
G1. VERIFY LOCATION AND DIMENSIONS OF EXISTING EQUIPMENT AND
COORDINATE ALL WORK PRIOR TO THE START OF CONSTRUCTION.
G2. COORDINATE SHUTDOWN, ISOLATION, AND DRAIN OF EXISTING UTILITY WITH
GSA BUILDING MANAGEMENT A MINIMUM OF 2-WEEKS IN ADVANCE.
PERFORM WORK DURING NON-WORKING HOURS.
1. REMOVE KITCHEN SINK AND APPURTENANCES COMPLETE. REMOVE
ASSOCIATED WASTE, VENT, DOMESTIC WATER PIPE, AND VALVES TO POINT
INDICATED AND CAP PIPE. PATCH AND REPAIR SLAB TO MATCH ADJACENT
SURFACES.
2. PIPING LOCATED IN CEILING OF FLOOR BELOW.
3. REMOVE INSULATION, VAPOR BARRIER/JACKET COMPLETE TO POINTS
INDICATED ON EXISTING STORM AND DOMESTIC WATER PIPING. INSPECT
PIPING AND REPORT ANY VISUAL SIGNS OF LEAKS OR OTHER INTEGRITY
ISSUES TO CONTRACTING OFFICER.
4. DEMOLISH EXISTING CHASE WALL TO FACILITATE CONNECTION TO EXISTING
WASTE PIPE STACK WITHIN THE PIPE CHASE. LOCATION OF EXISTING
WASTE PIPE AS INDICATED IS BASED ON RECORD DOCUMENTS. SURVEY
AND COORDINATE ACTUAL LOCATION OF STACK IN FIELD.
NOTES
SUMMER
CONSULTANTS
I N C O R P O R A T E D
SUMMER
CONSULTANTS
PROFESSIONAL CERTIFICATION. I HEREBY CERTIFY
THAT THESE DOCUMENTS WERE PREPARED OR
APPROVED BY ME, AND THAT I AM A DULY LICENSED
PROFESSIONAL ENGINEER UNDER THE LAWS OF THE
STATE OF MARYLAND, LICENSE NO. 45592, EXPIRATION
DATE: 05 JUNE 2022.
FI
LE
N
AM
E:
OU
R
RE
F:
PL
OT
D
AT
E:
/8/
4:
:47
P M
4.2
PD
6-
.D
W G
N
8'0 16' 1/8"=1'-0"
SIXTEENTH FLOOR PLAN - DEMOLITION1
1 ADDENDUM 3 11/09/21
GENERAL NOTES
G1. ALL WORK SHALL BE NEW AND PROVIDED UNDER THIS CONTRACT UNLESS
SPECIFICALLY MARKED "EXISTING", "EXIST.", OR "(E)"
G2. VERIFY LOCATION AND DIMENSIONS OF EXISTING EQUIPMENT AND
COORDINATE ALL WORK PRIOR TO THE START OF CONSTRUCTION.
G3. COORDINATE SHUTDOWN, ISOLATION, AND DRAIN OF EXISTING UTILITY WITH
GSA BUILDING MANAGEMENT A MINIMUM OF 2-WEEKS IN ADVANCE.
PERFORM WORK DURING NON-WORKING HOURS.
NOTES
1. PIPING LOCATED IN CEILING OF FLOOR BELOW.
2. INSULATE EXISTING STORM AND DOMESTIC WATER PIPING TO POINTS
INDICATED.
3. PROVIDE FIELD-FABRICATED DRAIN PAN UNDER EXISTING PIPING TO
EXTENTS INDICTED.
4. PROVIDE 1/2" PLENUM RATED TUBING FROM DRAIN PAN, ACROSS IT ROOM
WALL BARRIER, AND SPILL ONTO CEILING TILE IN VISIBLE LOCATION.
5. EXTEND CONDENSATE PIPING TO TAIL-PIPE OF EXISTING DRINKING
FOUNTAIN. FIRESTOP, PATCH AND REPAIR EXISTING CHASE WALL.
6. NOT USED.
7. CORE DRILL EXISTING CONCRETE SLAB FOR PIPE PENETRATION.
COORDINATE CORE DRILL WITH STRUCTURE BELOW.
8. EXTEND DOMESTIC WATER PIPING TO SINK WITHIN CASEWORK.
45678910
D
E
F
G
(E)3"ST
(E)3"ST
(E)4"ST(E)3"ST
(E)8"ST UP& DN.
(E)4"V
UP&DN.
(E)4"W
UP&DN.
(E)1-/2"HW DN.
(E)1-1/2"CW DN.
(E)6"V UP&DN.
(E)1/2"HW
(E)1-1/2"V
(E)1-1/2"CW
(E)4"CW
REF.
1(E)1-1/2"W
1/2"CW
1/2"HW
3/4"CW
1-1/2"W
C.O.P-3
P-6
(E)4"CW DN.
AC
16-4
71-1/2"W
1-1/2"V
2 3
(E)DRINKING FOUNTAIN
(E)W
SUMMER
CONSULTANTS
I N C O R P O R A T E D
SUMMER
CONSULTANTS
160008
160001 160002
160004
160003
160005
160006
160007
160016 160014
160009160010
160017
160011
160013
N
8'0 16' 1/8"=1'-0"
SIXTEENTH FLOOR PLAN1
160012
PROFESSIONAL CERTIFICATION. I HEREBY CERTIFY
THAT THESE DOCUMENTS WERE PREPARED OR
APPROVED BY ME, AND THAT I AM A DULY LICENSED
PROFESSIONAL ENGINEER UNDER THE LAWS OF THE
STATE OF MARYLAND, LICENSE NO. 45592, EXPIRATION
DATE: 05 JUNE 2022.
FI
LE
N
RE
F:
PL
OT
D
AT
E:
/8/
4:
:54
P M
4.2
P-
7-
.D
W G
H
G
F
E
D
C
A
A
AD
H
G
F
E
D
C
A
A
AD
(E)VAV
(E)38x16
(E)VAV
(E)VAV
(E)VAV
(E)VAV
(E)VAV
(E)VAV
(E)16x8
(E )1
6x
(E )1
6x
(E)12x10
(E)8"Ø (E)8"Ø
(E)8"Ø (E)8"Ø
(E )8 x1
(E)12x14
(E)6"Ø (E)8"Ø
(E )8
"Ø
(E )8 x1
(E )1
2x
(E)8"Ø (E)8"Ø
(E)14x12
(E)8"Ø
(E)VAV
(E)VAV
(E)14x10 (E)12x10 (E)8x10 (E)6x8
(E )6 x1
(E )1
0x
(E)12x12
(E )1
0x
(E)12x12
(E)16x12
(E )1
0x
(E)6x6 (E)8x10
(E)8"Ø
(E )3
0x
(E)10"Ø
(E)8x8
(E)8x8
(E)CUH
(E )1
0x
(E)8x8
(E)6"Ø
(E)6x12
(E )6 x1
(E)2-1/2"HWR
(E)2-1/2"HWS
(E)2-1/2"HWR
& (E) 1"HWS
(E)3/4"HWS&R
(E)1"HWS
(E)1-1/4"HWS
T (E)
(E)2-1/2"HWR (E)2"HWR
(E)1-1/4"HWS
(E)2"HWR
T(E)
T (E) 8"Ø
4"HWS&R
UP&DN.
(E)8x12
(E)8Ø
8x10
8x10
6x8
6x8
6x12
6x8
(E)8x12 (E)8x12 (E)6x12(E)10x12
(E)12x14
(E)6x10
16x14
8x8
8x14
(E)8x12
(E)10x12
(E)10x10 (E)8x12
6x10
12x12
10x8
8x6
8x10
(E)12x12
2"HWS&R
(E)CWS&R
(E)CWS&R
(E)HWS&R
(E)HWS&R
(E)HWS&R
(E)1-1/2"CWS&R
3/4"HWS&R
2"HWS&R
(E)2"HWS&R
(E)CWS&R UP&DN
(E)HWS&R UP&DN
VAV
VAV
VAV
VAV
VAV
(E )3
0x
14x10
6x8
(E)36x12RA
(E )3
6x
RA
(E )3
0x
SA
(E )3
6x
RA
(E )2
4x
SA
(E
)3 8x
SA
(E)2"HWS&1-1/2"HWR
3/4"HWS&R
8x12
14x10
(E)6"CWS&R
UP&DN
(E)2-1/2"HWS
2 2
4 2
(E)14x14
VAV3
3/4"HWS&R 4
T
T
T
T
T5 T
5 6
6x8 2
(E)RG
(E)RG 1
(E)RG
(E)RG
(E)RG
GENERAL NOTES
G1. VERIFY LOCATION AND DIMENSIONS OF EXISTING EQUIPMENT AND
COORDINATE ALL WORK PRIOR TO THE START OF CONSTRUCTION.
G2. COORDINATE SHUTDOWN, ISOLATION, AND DRAIN OF EXISTING UTILITY WITH
GSA BUILDING MANAGEMENT A MINIMUM OF 2-WEEKS IN ADVANCE.
PERFORM WORK DURING NON-WORKING HOURS.
G3. ALL EXISTING TO REMAIN SUPPLY AND RETURN AIR DUCTWORK SHALL BE
CLEANED PER SPECIFICATIONS.
NOTES
1. REMOVE AIR DEVICE AND APPURTENANCES COMPLETE.
2. REMOVE DUCTWORK AND ASSOCIATED INSULATION, HANGERS, SUPPORTS,
AND APPURTENANCES TO POINT INDICATED.
3. CAREFULLY REMOVE VAV BOX AND ASSOCIATED HEATING COIL, CONTROLS,
HANGERS, SUPPORTS, AND APPURTENANCES COMPLETE. DELIVER VAV BOX,
AND CONTROLLER TO GSA DESIGNATED LOCATION ON THE 17TH FLOOR.
4. REMOVE PIPING AND ASSOCIATED INSULATION, VALVES, HANGERS, AND
APPURTENANCES TO POINT INDICATED. CAP PIPING AT POINT INDICATED.
5. DEMOLISH THERMOSTAT AND ASSOCIATED BACKBOX, CONDUIT, WIRING,
AND APPURTENANCES COMPLETE.
6. RETAIN THERMOSTAT FOR REINSTALLATION.
7. CAREFULLY REMOVE VAV BOX AND ASSOCIATED HEATING COIL, CONTROLS,
HANGERS, SUPPORTS, AND APPURTENANCES COMPLETE. RETAIN VAV BOX
FOR RELOCATION.
6 5 4 36 5 4 3
SUMMER
CONSULTANTS
I N C O R P O R A T E D
SUMMER
CONSULTANTS
N
8'0 16' 1/8"=1'-0"
SECOND FLOOR (EAST) - DEMOLITION1
FI
LE
N
RE
F:
PL
OT
D
AT
E:
/8/
4:
:06
P M
4.2
MD
3-
.D
W G
PROFESSIONAL CERTIFICATION. I HEREBY CERTIFY
THAT THESE DOCUMENTS WERE PREPARED OR
APPROVED BY ME, AND THAT I AM A DULY LICENSED
PROFESSIONAL ENGINEER UNDER THE LAWS OF THE
STATE OF MARYLAND, LICENSE NO. 45592, EXPIRATION
DATE: 05 JUNE 2022.
1 ADDENDUM 3 11/09/21
GENERAL NOTES
G1. ALL WORK SHALL BE NEW AND PROVIDED UNDER THIS CONTRACT UNLESS
SPECIFICALLY MARKED "EXISTING", "EXIST.", OR "(E)"
G2. VERIFY LOCATION AND DIMENSIONS OF EXISTING EQUIPMENT AND
COORDINATE ALL WORK PRIOR TO THE START OF CONSTRUCTION.
G3. ALL AIR DEVICES ARE CD-1 UNLESS OTHERWISE INDICATED.
NOTES
1. AIR TRANSFER DUCT. REFER TO DETAIL 6 ON SHEET M-501. SIZE TRANSFER
IN ACCORDANCE WITH SCHEDULE BASED ON SUM OF ROOM AIRFLOW
UNLESS OTHERWISE NOTED.
2. REINSTALL RETAINED VAV BOX. PROVIDE CONTROL VALVE AND EXTEND
CONTROLS TO LOCATION INDICATED.
3. REINSTALL RETAINED THERMOSTAT. EXTEND WIRING TO LOCATION
INDICATED. REWIRE TO OPERATE AS BEFORE.
4. BALANCE AIR DEVICE TO INDICATED AIRFLOW.
5. FIRESTOP PENETRATION.
6. COORDINATE ROUTING OF PIPING THROUGH EXISTING CEILING IN OCCUPIED
SPACE. COORDINATE PIPE ROUTING WITH EXISTING UTILITIES.
7. INDICATED AREA IS PART OF AN EXISTING VERTICAL CHASE THAT IS OPEN
FROM THE BASEMENT TO THE UNDERSIDE OF THE 3RD FLOOR SLAB.
PROVIDE ALL EQUIPMENT REQUIRED IN ORDER TO MAKE UTILITY
CONNECTIONS AS INDICATED. ACCESS TO THE SHAFT IS THROUGH AN
ACCESS PANEL AT THE BASEMENT LEVEL WITHIN THE ADJACENT
STAIRWELL.
8. NOT USED.
9. PROVIDE DUCT CONNECTION FOR SERVER RACK EXHAUST. COORDINATE
EXACT LOCATION OF SERVER RACK, EXHAUST CONNECTION, AND CABLE
TRAY IN-FIELD.
1-1/2"CWS/R
6"PAD
(E )8 x1
8x6 SG-1
AC
2E-01
M-502
24x12 T
SD
24x24DN
DD
RG-1
34x40DN
6"PAD
AC
2E-02
M-502
FPB
2E-04
(E )3
0x
SA
(E
)3 0x
SA
10x10
T
T
AC
2E-03
T
SD
934x16
24x12
2"CWS&R 1-1/2"CWS&R
3/4"HWS&R
SD
H
G
F
E
D
C
H
G
F
E
D
C
(E)VAV
(E)38x16 (E)VAV
(E)VAV
(E)VAV
(E)VAV
(E)16x8
(E )1
6x
(E )1
6x
(E)12x10
(E)8"Ø (E)8"Ø
(E)8"Ø (E)8"Ø
(E )8 x1
(E)12x14
(E)6"Ø (E)8"Ø
(E )8
"Ø
(E )1
2x
(E)8"Ø (E)8"Ø
(E)14x12
(E)8"Ø
(E)VAV
(E)VAV
(E)14x10 (E)12x10 (E)8x10 (E)6x8
(E )6 x1
(E )1
0x
(E)12x12
(E )1
0x
(E)12x12
(E)16x12
(E )1
0x
(E)6x6 (E)8x10
(E)8"Ø
(E)10"Ø
(E)8x8
(E)8x8
(E)CUH
(E )1
0x
(E)8x8
(E)6"Ø
(E)6x12
(E )6 x1
4"HWS&R
UP&DN.
(E)1"HWS
(E)1-1/4"HWS
T (E)
(E)2-1/2"HWR (E)2"HWR
(E)1-1/4"HWS
(E)2"HWR
T(E)
T (E)
(E)VAV
(E)6"CWS&R
UP&DN
(E)2-1/2"HWR
(E)VAV
(E)2-1/2"HWR
& (E) 1"HWS
(E)8x10
(E)3/4"HWS&R
8x6
2"CWS&R
RG-1
RG-1
120 65
LS-1
LS-1
LS-1
LS-1
RG-1
RG-1
LS-1
LS-1
LS-1
LS-1
M-103
M-103
(E)1-1/2"CWS&R
(E)2-1/2"HWS
(E)8x12
(E)8Ø
(E)8x12 (E)8x12 (E)6x12(E)10x12
(E)12x14
(E)6x10 (E)8x12
(E)10x12
(E)10x10 (E)8x12
(E)12x12
(E)CWS&R
(E)CWS&R
(E)HWS&R
(E)HWS&R
(E)HWS&R
(E)CWS&R UP&DN
(E)HWS&R UP&DN
(E )3
0x
(E )3
0x
SA
(E )3
6x
RA
(E)36x12RA
(E )3
6x
RA
(E )2
4x
SA
(E)2"HWS&1-1/2"HWR
22x14
(E)14x14 30x14SA
(E)36x30RA UP
SPLIT 18&12
(E)30x36SA UP
SPLIT 18&18
22x14
6x8 x1 x1
FPB
2E-06
FPB
2E-02
RG-1
FPB
2E-01
6x8
12x10
12x10 x1 x1
RISERISE
6x
2"HWS&R
10x10
2"HWS&R
x1
14x10
8x8
8x8
VAV
7-11
FPB
2E-05
195 4
195 4
195 4
220 4200 4200 4220420042004
250 4
250 4
6x8
6x
6x
18548x8
T
FPB-2E-05
T
FPB-2E-06
T
T
FPB-2E-02
(E)RG
(E)RG
(E)RG
(E)RG
(E)RG
2"CWS&R
2"
CW
S& R
1-1/2"CWS&R6
1-1/2"CWS&R 6
2"CWS&R 6
T
6 5 4 36 5 4 3
FF
SUMMER
CONSULTANTS
I N C O R P O R A T E D
SUMMER
CONSULTANTS
025007
025008
025006
025011
025004
025003
025005
025012 025013025014
025017
025015 025016
025001
025002
025019
025020
025018
025024 025010
025009
N
8'0 16' 1/8"=1'-0"
SECOND FLOOR PLAN (EAST)3
8'0 4' 1/4"=1'-0"
SECOND FLOOR - IT ROOM 025010
ENLARGED PLAN
M-1031
8'0 4' 1/4"=1'-0"
ROOMS 025027, 025028, & 025031
ENLARGED PLAN - SECOND FLOOR
M-1032
025022
025021
025031
025027
025026
025029025030
025032
025025
025027
025032
025031
025028
025026
025017
025009
025015
FI
LE
N
RE
F:
PL
OT
D
AT
E:
/8/
4:
:34
P M
4.2
M-
3-
.D
W G
PROFESSIONAL CERTIFICATION. I HEREBY CERTIFY
THAT THESE DOCUMENTS WERE PREPARED OR
APPROVED BY ME, AND THAT I AM A DULY LICENSED
PROFESSIONAL ENGINEER UNDER THE LAWS OF THE
STATE OF MARYLAND, LICENSE NO. 45592, EXPIRATION
DATE: 05 JUNE 2022.
025024
1 ADDENDUM 3 11/09/21
(E)4"HWS&R
UP&DN.
(E)4"CWS&R
UP&DN.
(E)
(E)2"HWS
10x10
(E)EG (TYP.)
(E)30x30
UP&DN
(E)14x12 (E)12x8
(E )1
0x
7 5
(E)F.D.
(E) PIPE/DUCT
CHASE OPEN
TO BASEMENT
(E)F.D.
RG-1RG-1
LS-1
LS-1
LS-1
LS-1
LS-1
LS-1
LS-1
LS-1
LS-1
LS-1
LS-1
LS-1
LS-1
RG-1
RG-1
LS-1
LS-1
LS-1
RG-1
RG-1
LS-2
LS-2
LS-2
LS-2
RG-1
LS-1
RG-1
LS-1
RG-1
LS-1
RG-1
LS-1
RG-1
LS-1
LS-1
LS-1
LS-1
RG-1
RG-1
RG-1
RG-1
LS-1
LS-1
LS-1
LS-1
LS-1
LS-1
LS-1
RG-1
RG-1
RG-1
LS-1
LS-1
LS-1
LS-1
LS-1
LS-1
LS-1
LS-1
LS-1
LS-1
LS-1
LS-1
LS-1
LS-1
RG-1
LS-1
LS-1
RG-1
RG-1
RG-1
RG-1 RG-1
RG-1
RG-1
RG-1
RG-1
RG-1
RG-1
RG-1
RG-1
RG-1
RG-1
2-1/2"CWS&R
100 100
100 100 100
100 100
100 100 100
FPB
2W-12A
FPB
2W-04A
FPB
2W-08A
110 110
110 110
110110
110 110
80 80 80 110 110
808085
FPB
2W-17A
FPB
2W-17B
505050
90 90
160160160
FPB
2W-04B
160160
FPB
2W-05B
FPB
2W-05A
FPB
2W-06A
FPB
2W-06B
FPB
2W-08B
FPB
2W-12B
FPB
2W-12C
FPB
2W-12D
FPB
2W-12E
FPB
2W-12F
FPB
2W-12G
FPB
2W-12H
FPB
2W-12J
12x10 10x10 8x8
12x10 10x10 8x8
14x12
8x8 10 x1
12x12 10x8
6" Ø
SPLIT EQ.
SPLIT EQ.
SPLIT EQ.
8x8 x1 x1
6x8 x1 x1
6"Ø
8x8
12x10 x1
8x x1
8x
12x10 x1
10x10 x8
10x8 8x8
14x12 12x12
8x
10x8 x8 x8
6x
6" Ø
12x10
6x8 x1 x1
6"Ø
6x
6"Ø x8
8x8 6x8
14x12 10x8
8x86"Ø
SPLIT 7&3
8x8
6"Ø4x8
6"Ø
12x10 10x10
8x x8
8x6
4x
8 SPLIT 3&5
6"Ø
6"Ø
6"Ø
6" Ø x1
8x814x12 12x10
6" Ø
10x10 10x8 8"Ø
10x10 10x8
8"Ø
12x8
RG-1
12x6 x1
10x88"Ø
10x5
10x10 x1
8x
7x
24x12 18x12 12x8
8x8 x8 x8
8x
6"Ø x8
10x8 x1 x8
10x8 8x8 6"Ø
6x
10x8
10x8
SPLIT EQ.
6"Ø
6x8 6"Ø10x8
16x12 12x10
8x x8
8x
6" Ø
12x10
12x10 8x8 SPLIT EQ.
10x10
12x8
6x8 x1
8x
8x8
8x x1
6"Ø
14x10 14x10 x8
8x
SPLIT EQ.
T
8x8 x1
22x1816x1616x16 x1 x1
14x12
34x1428x1220x1212x12
24x1220x10 14x10
8x8
6"Ø 6"Ø
14x12 x1 x1 x1 x1 x1
16x10
SPLIT EQ.
36x16 44x18
54x24 SPLIT 21&33
3/4"HWS&R
8x
8x68x4
RG-1
LS-1
2 2
RG-1
(E)2-1/2"HWS&R
HWS&R
TX-02-2
EF-02-1
EG-3
FPB
2W-10
FPB
2W-11
FPB
2W-09 FPB
2W-07
FPB
2W-13
FPB
2W-14
FPB
2W-01
12x812 x8
1"CWS&R
1"CWS&R
14x8
(E)F.D.
(E)F.D.
104x16 9
FPB
2W-18
FPB
2W-19
FPB
2W-16
1-1/2"HWS
1"HWS 1"HWS
1/2"HWR
1"HWR
1-1/4"HWR
1-1/2"HWR
1-1/2"HWR
2"HWR
2-1/2"HWR
FPB
2W-03
FPB
2W-02
FPB
2W-20
86x20UP
CAV
8-06
6" Ø
6" Ø
DPT-8A
DPT-8B
3 10x10 AD
T
T
T
T
16 T
T
T
T
T
T
T
T
T
T
T T
T 2W-06B
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
2W-12J
2W-12F
2W-14
2W-13 2W-07
2W-09
2W-12E
2W-12D
2W-12H
2W-12G
2W-11
2W-10
2W-08A
2W-03
2W-02
2W-08B
2W-04A
2W-04B
2W-05A
2W-06A
2W-05B
2W-06B
8-06
2W-17B
2W-17A
2W-16
2W-18
2W-20
2W-12C 2W-12B
EG-2
GENERAL NOTES
G1. ALL WORK SHALL BE NEW AND PROVIDED UNDER THIS CONTRACT UNLESS
SPECIFICALLY MARKED "EXISTING", "EXIST.", OR "(E)"
G2. VERIFY LOCATION AND DIMENSIONS OF EXISTING EQUIPMENT AND
COORDINATE ALL WORK PRIOR TO THE START OF CONSTRUCTION.
G3. ALL AIR DEVICES ARE CD-1 UNLESS OTHERWISE INDICATED.
NOTES
1. PROVIDE MANBAR BARRIER. REFER TO DETAIL 2 ON SHEET M-501.
2. AIR TRANSFER DUCT. REFER TO DETAIL 6 ON SHEET M-501. SIZE TRANSFER
IN ACCORDANCE WITH SCHEDULE BASED ON SUM OF ROOM AIRFLOW
UNLESS OTHERWISE NOTED.
3. PROVIDE 12x12 ACCESS PANEL UON.
4. BALANCE FAN AND AIR DEVICE AT DESIGN AIRFLOW WITH 1.5"W.G. ACROSS
FILTER BANK BY FALSELY LOADING FILTERS AT TIME OF BALANCE.
5. 24x24 ACCESS PANEL LOCATED IN STAIRWELL ON GROUND LEVEL.
6. REINSTALL FIRE/SMOKE DETECTOR AND TEST INDICATOR. REFER TO FIRE
ALARM PLANS FOR DETAILS.
7. BALANCE EXISTING AIR DEVICE TO INDICATED AIRFLOW.
8. COORDINATE FAN POWERED VAV BOX CONTROLLER, FILTER, AND
MAINTENANCE ACCESS WITH PENDENT MOUNTED MOONRING LIGHTS HUNG
BELOW CEILING. REFER TO ELECTRICAL LIGHTING AND ARCHITECTURAL
CEILING PLANS FOR ADDITIONAL DETAILS.
9. BALANCE RETURN AIR PER RISER ON SHEET M-105.
10. NOT USED.
11. PROVIDE FILTER BANK SIZED FOR MERV 13 FLAT FILTER. PROVIDE FILTER
ACCESS DOOR WITH CAMLOCK AND PRESSURE TIGHT SEAL. PROVIDE
MERV-8 PRE-FILTER UPSTRAM OF MERV 13 FILTERS. PROVIDE FILTER
GAUGE AT FILTER BANK FOR EACH FILTER.
12. TERMINATE EXHAUST WITH 1/2 INCH WIRE MESH AT BELLMOUTH OPENING.
13. PROVIDE MOTORIZED DAMPER IN EXHAUST OUTLET. INTERLOCK EXHAUST
FAN AND DAMPER WITH EMERGENCY WALL PUSH BUTTON WITHIN MAIL
ROOM. WHEN EMERGENCY WALL PUSH BUTTON IS ENABLED, DAMPER
SHALL CLOSE.
14. PROVIDE 10-INCH SINGLE BLADE MOTORIZED DAMPER IN SUPPLY INLET TO
FPB-2W-15. INTERLOCK DAMPER WITH EMERGENCY WALL PUSH BUTTON
WITHIN MAILROOM. WHEN EMERGENCY WALL PUSH BUTTON IS ENABLED,
DAMPER SHALL CLOSE. PROVIDE PUSH BUTTON WITH HINGED COVER.
PROVIDE PLACARD OVER PUSH BUTTON THAT READS, "EMERGENCY ROOM
HVAC OFF".
15. PROVIDE DIFFERENTIAL PRESSURE TRANSMITTER IN LOCATION INDICATED.
MODIFY SEQUENCE TO CONTROL SYSTEM FAN ON WORST-CASE. REFER TO
CONTROLS SHEETS FOR ADDITIONAL INFORMATION.
16. COORDINATE THERMOSTAT MOUNTING HEIGHT WITH SYSTEMS FURNITURE.
111213141516 111213141516
H
G
F
E
D
C
H
G
F
E
D
C
SUMMER
CONSULTANTS
I N C O R P O R A T E D
SUMMER
CONSULTANTS
N
8'0 16' 1/8"=1'-0"
SECOND FLOOR PLAN (WEST)1
020028
020001
020031
020030
020029
020032
020027
020025
020026
020033
020034020037
020036
020035
020024
020001
020003
020004
020038
020023
020022
020021
020020
020019
020008
020007
020006
020018
020005 020002
020012
020013
020014
020015
020016
020017 020011
020010
020009
FI
LE
N
RE
F:
PL
OT
D
AT
E:
/8/
4:
:50
P M
4.2
M-
4-
.D
W G
PROFESSIONAL CERTIFICATION. I HEREBY CERTIFY
THAT THESE DOCUMENTS WERE PREPARED OR
APPROVED BY ME, AND THAT I AM A DULY LICENSED
PROFESSIONAL ENGINEER UNDER THE LAWS OF THE
STATE OF MARYLAND, LICENSE NO. 45592, EXPIRATION
DATE: 05 JUNE 2022.
SUMMER
CONSULTANTS
I N C O R P O R A T E D
SUMMER
CONSULTANTS
ELECTRICAL SYMBOLS
RECESSED 2' x 2' LUMINAIRE, SUBSCRIPT INDICATES CONTROL SWITCH
SD
SOC
S
A LUMINAIRE FIXTURE TYPE, REFER TO LUMINAIRE SCHEDULE.
SINGLE FACED EXIT SIGN.
DOUBLE FACED EXIT SIGN.
COPPER GROUNDING BUS BAR.
RECESSED 6'' LED DOWN LIGHT, SUBSCRIPT INDICATES CONTROL SWITCH
OS
ELECTRICAL SYMBOLS CONTINUED
SYSTEMS FURNITURE POWER FEED, WALL-RECESSED MOUNTED @ 18” AFF; GALVANIZED
PRESSED STEEL JUNCTION BOX, 4-1/2" LONG x 4-1/2" WIDE x 1-1/2" DEEP. MAKE ALL FINAL
CONNECTIONS TO POWER WHIP FURNISHED WITH SYSTEMS FURNITURE.
J JUNCTION BOX 4" SQUARE X 2-1/8" DEEP GALVANIZED PRESSED STEEL,
MOUNTED ABOVE SUSPENDED TILE CEILING.
RECESSED 2' x 2' EMERGENCY LUMINAIRE
RECESSED 6'' EMERGENCY LED DOWN LIGHT
DESIGNATION FOR TELECOM AND VOICE PATCH PANEL. D FOR DATA, V
FOR VOICE. NUMBER CORRESPONDS TO BOTH DATA AND VOICE PATCH
PANELS. LETTER INDICATES SPECIFIC DATA OR VOICE PANEL.
D/V (A)(B) #
4'' CUTOUT SLEEVE AND REMOVABLE FIRE STOP PILLOWS FOR
COMMUNICATION CABLE.
HORIZONTAL CABLE TRAY, CABLOFIL CF 54/400.
AIPHONE OR EQUIVALENT DEVICE.
EM2 PANEL NAME TO WHICH CIRCUITS RUN.
AS SHOWN ABOVE.
IN WALLS AND CEILING, ALL OTHER CHARACTERISTICS SAME
BRANCH CIRCUIT CONDUIT AND CONDUCTORS RUN CONCEALED
#10
EM2
#10
1,3,5
WIRE SIZE IN AWG. SIZE NOT SHOWN INDICATES #12 AWG.
CIRCUIT BREAKERS IN PANEL SERVING THESE CIRCUITS.
EM2
1,3,5
#10
HOME RUN TO PANEL. NUMBER OF ARROWS INDICATE
2 CIRCUIT CONDUCTORS PLUS A GROUND CONDUCTOR.
CONDUCTORS IN RACEWAY. NO SLASH MARKS INDICATE
NUMBER OF SLASH MARKS INDICATE THE NUMBER OF
GREEN GROUND CONDUCTOR RUN IN RACEWAY.
THE NUMBER OF CIRCUITS.
a
COMBINATION POWER/TELECOMMUNICATIONS RECESSED POKE-THROUGH DEVICE IN RAISED
ACCESS FLOOR. PROVIDE A POKE-THROUGH DEVICE WITH (4) PRE-WIRED 20A, 125V
RECEPTACLES (2) OPENINGS FOR STANDARD TELECOM JACKS. PROVIDE ASSOCIATED
TWO-SECTION JUNCTION BOX WITHIN THE CEILING SPACE BELOW. FOR THE
TELECOMMUNICATIONS SIDE OF THE JUNCTION BOX, PROVIDE A 1" EMT CONDUIT ROUTED IN
FLOOR FROM FITTING TO NEAREST WALL AND UP TO CEILING ABOVE WITH PULL STRING, (2)
CAT6E CABLE, AND CONDUIT BUSHING FOR THE POWER SIDE OF THE JUNCTION BOX, SEE THE
POWER DRAWINGS FOR THE BRANCH CIRCUIT WIRING. DEVICE SHALL BE A U.L. RATED
ASSEMBLY FOR FLOOR PENETRATIONS. FINISH COLOR AND MATERIAL SHALL BE CHOSEN BY
ARCHITECT FROM MANUFACTURER'S FULL RANGE. SEE ARCHITECTURAL DRAWINGS FOR
FLOOR TYPES AND FINISHES FOR COORDINATION.
TELEPHONE OUTLET, 4" SQUARE x 2-1/8" DEEP GALVANIZED PRESSED STEEL, RECESSED
MOUNTED AT 18" ABOVE FINISHED FLOOR, WITH COVER PLATE AND 1 RJ45 JACK.
PROVIDE 3/4" CONDUIT WITH NYLON PULL STRING CONCEALED IN WALL UP TO ABOVE
SUSPENDED TILE CEILING. PROVIDE 1 CAT6 CABLE FOR VOICE. MAKE ALL FINAL
CONNECTIONS.
CEILING MOUNTED MOTION SENSOR, COMBINATION ULTRASONIC/ PASSIVE
INFRARED (PIR) DEVICE WITH ADJUSTABLE TIME DELAY 5 TO 15 MINUTES.
WALL MOUNTED OCCUPANCY SENSOR, COMBINATION ULTRASONIC/ PASSIVE
INFRARED (PIR) DEVICE WITH ADJUSTABLE TIME DELAY 5 TO 15 MINUTES.
CEILING MOUNTED OCCUPANCY SENSOR, COMBINATION ULTRASONIC/ PASSIVE
INFRARED (PIR) DEVICE WITH ADJUSTABLE TIME DELAY 5 TO 30 MINUTES.
WALL MOUNTED COMBINATION SWITCH AND OCCUPANCY SENSOR. 20 AMPERE,
120/277V, A.C. ONLY, RECESS MOUNTED AT 48" ABOVE FINISHED FLOOR. DUAL
TECHNOLOGY SENSOR SHALL BE FIELD ADJUSTABLE BETWEEN VACANCY AND
OCCUPANCY SENSOR MODES.
DIMMER SWITCH. 20 AMPERE, 120/277V, A.C. ONLY, RECESS MOUNTED AT 48"
ABOVE FINISHED FLOOR.
QUADRUPLEX RECEPTACLE, 20 AMPERE, 125 VOLT GROUNDING TYPE, NEMA
5-20R CONFIGURATION, RECESSED GROUND MOUNTED.
SWITCH, FLUSH TUMBLER TYPE, SINGLE POLE, 20 AMPERE, 120/277V, A.C.
ONLY, RECESS MOUNTED AT 48" ABOVE FINISHED FLOOR.
DUPLEX RECEPTACLE, 20 AMPERE, 125 VOLT GROUNDING TYPE, NEMA 5-20R
CONFIGURATION, RECESS MOUNTED IN 4" SQUARE x 2-1/2" DEEP PRESSED STEEL
JUNCTION BOX AT 6" ABOVE FINISHED FLOOR.
SECURITY CARD READER. RECESS MOUNTED AT 48" ABOVE FINISHED FLOOR.
SECURITY KEYPAD. RECESS MOUNTED AT 48" ABOVE FINISHED FLOOR.
CEILING-MOUNTED "REQUEST TO EXIT" PASSIVE INFRARED SENSOR.
CR
KP
DB
REX
PIR
OS
CEILING MOUNTED SECURITY GLASS BREAK SENSOR.GB
MD
SF
UNIVERSAL MOUNTED EXIT LIGHT, SINGLE OR DOUBLE FACED WITH DIRECTIONAL
CHEVRON ARROWS AS SHOWN, LIGHTING FIXTURE TYPE AS NOTED:
ABBREVIATIONS
SHEET SYMBOLS
AMPERES.A
AF
AFF
AHU
AT
ATS
AWG
BLDG.
C/B
EC
EMT
(E),EX.
(ETR)
FLA
GFCI
GFI GROUND FAULT INTERRUPTER.
GOVERNMENT FURNISHED, CONTRACTOR INSTALLED.
FULL LOAD AMPERES.
EXISTING TO REMAIN.
EXISTING.
ELECTRICAL METALLIC TUBING.
EMPTY CONDUIT.
CIRCUIT BREAKER.
BUILDING.
AMERICAN WIRE GAUGE.
AUTOMATIC TRANSFER SWITCH.
TRIP SIZE IN AMPERES.
AIR HANDLING UNIT.
ABOVE FINISHED FLOOR.
FRAME SIZE IN AMPERES.
GRD.
HOA
KAIC
KW KILO-WATTS.
THOUSAND AMPERE INTERRUPTING CAPACITY.
HAND-OFF-AUTOMATIC SELECTOR SWITCH.
GROUND CONDUCTOR.
M.L.O.
N.C.
N.E.C.
NEMA
NFSS
N.O.
P
PH.
PVC
RGS
U.L.
V
VFD
WP WEATHERPROOF, OR NEMA 3R ENCLOSURE.
VARIABLE FREQUENCY DRIVE.
VOLTAGE.
UNDERWRITER'S LABORATORIES.
RIGID GALVANIZED STEEL.
POLY-VINYL CHLORIDE.
NUMBER OF PHASES.
NUMBER OF POLES.
NORMALLY OPEN.
NON-FUSED SAFETY SWITCH.
NATIONAL ELECTRICAL MANUFACTURER'S ASSOCIATION.
NATIONAL ELECTRICAL CODE.
NORMALLY CLOSED.
MAIN LUGS ONLY.
FD FIRE DAMPER.
SD SMOKE DAMPER.
AV AUDIO/VISUAL DEDICATED OUTLET. MOUNT AT +55" AFF.
CEILING MOUNTED SPEAKER.SP
TELE/POWER POLE FOR SYSTEMS FURNITURE CONNECTION.PP
COMBINATION TELEPHONE AND DATA OUTLET, 4" SQUARE x 2-1/8" DEEP GALVANIZED
PRESSED STEEL, RECESSED MOUNTED AT 18" ABOVE FINISHED FLOOR, WITH COVER
PLATE AND 2 RJ45 JACKS. PROVIDE 1" CONDUIT WITH NYLON PULL STRING CONCEALED
IN WALL UP TO ABOVE SUSPENDED TILE CEILING. PROVIDE 2 CAT6 CABLES FOR VOICE
AND DATA. MAKE ALL FINAL CONNECTIONS.
AIP
a
GFI DUPLEX RECEPTACLE WITH GROUND FAULT CIRCUIT INTERRUPTER AND
NEMA 3R IN-USE WEATHERPROOF ENCLOSURE, 20 AMPERE, 125 VOLT
GROUNDING TYPE, NEMA 5-20R CONFIGURATION, SURFACE MOUNTED IN 4"
SQUARE x 2-1/8" DEEP PRESSED STEEL JUNCTION BOX AT 18" ABOVE
FINISHED FLOOR.
WP
GFI
DUPLEX RECEPTACLE WITH GROUND FAULT CIRCUIT INTERRUPTER, 20
AMPERE, 125 VOLT GROUNDING TYPE, NEMA 5-20R CONFIGURATION, RECESS
MOUNTED IN 4" SQUARE x 2-1/8" DEEP PRESSED STEEL JUNCTION BOX AT 18"
ABOVE FINISHED FLOOR.
GFI
DUPLEX RECEPTACLE WITH GROUND FAULT CIRCUIT INTERRUPTER, 20
AMPERE, 125 VOLT GROUNDING TYPE, NEMA 5-20R CONFIGURATION, RECESS
MOUNTED IN 4" SQUARE x 2-1/8" DEEP PRESSED STEEL JUNCTION BOX AT 8"
ABOVE COUNTERTOP.
QUADRUPLEX RECEPTACLE, 20 AMPERE, 125 VOLT GROUNDING TYPE, NEMA
5-20R CONFIGURATION, RECESS MOUNTED IN 4" SQUARE x DEEP PRESSED
STEEL JUNCTION BOX AT 18" ABOVE 2-1/8" FINISHED FLOOR.
QUADRUPLEX RECEPTACLE, 20 AMPERE, 125 VOLT GROUNDING TYPE, NEMA
5-20R CONFIGURATION, SURFACE MOUNTED IN 4" SQUARE x 2-1/8" DEEP
PRESSED STEEL JUNCTION BOX AT 18" ABOVE FINISHED FLOOR.
SPECIAL DEDICATED OUTLET, NEMA CONFIGURATION AS NOTED ON FLOOR
PLAN, RECESS MOUNTED IN 4" SQUARE x 2-1/8" DEEP PRESSED STEEL
JUNCTION BOX AT 18" ABOVE FINISHED FLOOR.
3-WAY LIGHT SWITCH, SINGLE POLE, 20 AMPERE, 120/277V, A.C.
ONLY, RECESS MOUNTED AT 48" ABOVE FINISHED FLOOR.
S3
BRANCH CIRCUIT CONDUIT AND CONDUCTORS RUN EXPOSED. SIZE IN
ACCORDANCE WITH N.E.C. RACEWAY SHALL BE MINIMUM 3/4"
CONDUIT, AND WIRE SHALL BE MINIMUM SIZE #12 AWG COPPER WITH
THHN INSULATION, UNLESS OTHER SIZES ARE SPECIFICALLY NOTED.
HEAVY DUTY ENCLOSED SAFETY SWITCH, SEE MOTOR AND EQUIPMENT
SCHEDULE FOR SIZES AND CHARACTERISTICS.
MOTOR, SEE MOTOR AND EQUIPMENT SCHEDULE FOR SIZES AND
CHARACTERISTICS.
P PUSH PLATE FOR AUTOMATIC DOOR OPENER. RECESS MOUNTED AT 36" ABOVE
FINISHED FLOOR.
SOC WALL MOUNTED COMBINATION DIMMER SWITCH AND OCCUPANCY SENSOR. 20
AMPERE, 120/277V, A.C. ONLY, RECESS MOUNTED AT 48" ABOVE FINISHED FLOOR.
DUAL TECHNOLOGY SENSOR SHALL BE FIELD ADJUSTABLE BETWEEN VACANCY
AND OCCUPANCY SENSOR MODES.
D
IC INTERCOM/COMMUNICATION DEVICE USED TO COMMUNICATE
BETWEEN ROOMS.
ELECTRICAL SYMBOLS CONTINUED
R WIRELESS CEILING-MOUNTED MICROPHONE. TO BE INSTALLED BY A/V TECHNICIAN. FOR
REFERENCE ONLY.
COMBINATION POWER/ DATA/ AUDIO/VISUAL FLOOR BOX.
PROVIDE (3) ADJACENT 4-13/16”X 4-1/8” X 2-1/2” JUNCTION BOXES RECESSED IN CONCRETE ON TOP
OF WALKER DUCT CHANNEL SYSTEM. PROVIDE (1)FLOORBOX WITH (4) PRE-WIRED 20A 125V
RECEPTACLES, (1) FLOORBOX WITH (2) STANDARD RJ45 TELECOM JACKS, (1)FLOORBOX WITH (2)
HDMI JACKS. ROUTE POWER CONDUCTORS THROUGH DESIGNATED WALKER DUCT POWER
CHANNEL BACK TO NEAREST WALKER ZONE DISTRIBUTION BOX. ROUTE CABLES THROUGH
DESIGNATED WALKER DUCT CHANNEL BACK TO NEAREST WALKER ZONE DISTRIBUTION BOX.
ROUTE AUDIO/VISUAL CABLES THROUGH DESIGNATED WALKER DUCT CHANNEL BACK TO
CEILING-MOUNTED WALKER ZONE DISTRIBUTION BOX. PROVIDE UL LISTED FIRE STOPPING TO
MAINTAIN RATING OF ALL PENETRATIONS. REFER TO STRUCTURAL DRAWINGS FOR PENETRATION
REQUIREMENTS.
COMBINATION TELEPHONE AND DATA OUTLET, RECESSED MOUNTED IN SYSTEMS
FURNITURE, WITH COMPATIBLE COVER PLATE AND 2 RJ45 JACKS. PROVIDE 2 CAT6A
CABLES FOR VOICE AND DATA FROM NEAREST FLOOR-MOUNTED SYSTEMS FURNITURE
FEED. MAKE ALL FINAL CONNECTIONS.
S
SYSTEMS FURNITURE POWER FEED, PROVIDE GALVANIZED PRESSED STEEL
JUNCTION BOX, 4-13/16”X 4-1/8” X 2-1/2” RECESSED IN CONCRETE ON TOP OF WALKER
DUCT CHANNEL SYSTEM. MAKE ALL FINAL CONNECTIONS TO POWER WHIP
FURNISHED WITH SYSTEMS FURNITURE. ROUTE CONDUCTORS FROM JUNCTION BOX
THROUGH DESIGNATED WALKER DUCT POWER CHANNEL BACK TO NEAREST
WALKER ZONE DISTRIBUTION BOX. PROVIDE UL LISTED FIRE STOPPING TO MAINTAIN
RATING OF ALL PENETRATIONS. REFER TO STRUCTURAL DRAWINGS FOR
PENETRATION REQUIREMENTS.
SF
COMMUNICATIONS FEED FOR SYSTEMS FURNITURE. PROVIDE GALVANIZED PRESSED
STEEL JUNCTION BOX, 4-13/16”X 4-1/8” X 2-1/2” RECESSED IN CONCRETE ON TOP OF
WALKER DUCT TELECOMMUNICATIONS CHANNEL SYSTEM. ROUTE CABLES THROUGH
DESIGNATED WALKER DUCT CHANNEL BACK TO NEAREST WALKER ZONE
DISTRIBUTION BOX. PROVIDE UL LISTED FIRE STOPPING TO MAINTAIN RATING OF ALL
PENETRATIONS. REFER TO STRUCTURAL DRAWINGS FOR PENETRATION
REQUIREMENTS.
WALKER DUCT ZONE DISTRIBUTION BOX FOR POWER, PROVIDE GALVANIZED
PRESSED STEEL JUNCTION BOX, 8-5/8” X 4-1/2” X 1-1/2” ABOVE CEILING. PROVIDE
1-1/2'' CONDUIT FROM DISTRIBUTION BOX BACK TO DESIGNATED ELECTRICAL
CLOSET.
WP
WALKER DUCT ZONE DISTRIBUTION BOX FOR TELECOMMUNICATIONS/DATA, PROVIDE
GALVANIZED PRESSED STEEL JUNCTION BOX, 8-5/8” X 4-1/2” X 1-1/2” ABOVE CEILING.
PROVIDE 1-1/2'' CONDUIT FROM DISTRIBUTION BOX BACK TO DESIGNATED
TELECOMMUNICATIONS/CLOSET.
WD
AV
SYSTEMS FURNITURE TELECOMMUNICATIONS FEED, WALL-RECESSED MOUNTED @
18” AFF; GALVANIZED PRESSED JUNCTION BOX, 4-1/2" LONG x 4-1/2" WIDE x 1-1/2"
DEEP. PROVIDE A 1" EMT CONDUIT ROUTED CONCEALED TO THE CEILING ABOVE
WITH PULL STRING, (2) CAT6A CABLES, AND CONDUIT BUSHING FOR
TELECOMMUNICATIONS CABLE. MAKE ALL FINAL CONNECTIONS TO SYSTEMS
FURNITURE DATA OUTLETS.
SECURITY CAMERA
WALKER DUCT ZONE DISTRIBUTION BOX FOR AUDIO/VISUAL, PROVIDE GALVANIZED
PRESSED STEEL JUNCTION BOX, 8-5/8” X 4-1/2” X 1-1/2” RECESSED IN CONCRETE ON
TOP OF WALKER DUCT CHANNEL SYSTEM. PROVIDE 1-1/2'' CONDUIT FROM ZONE
DISTRIBUTION BOX TO DISTRIBUTION BOX ABOVE CEILING.
WAV
SMOKE DAMPER STATUS INDICATOR.RTS
AC AIR CONDITIONING UNIT.
VAV VARIABLE AIR VOLUME BOX.
FPB FAN POWERED BOX.
FCU FAN COIL UNIT.
MANUAL "REQUEST TO EXIT" BUTTON. RECESS MOUNTED AT 48" ABOVE FINISHED FLOOR,
UNLESS OTHERWISE NOTED.
DURESS NOTIFICATION BUTTON WITH POLYCARBONATE COVER. MOUNTED UNDER DESK.
PROVIDE SURFACE MOUNTED RACEWAY TO CONCEAL ALL WIRING. MAKE ALL FINAL
CONNECTIONS.
LIGHTING MANAGEMENT SYSTEM WALL/DIMMER SWITCH. MOUNT AT 48'' AFF, UNLESS
OTHERWISE NOTED. BASIS OF DESIGN: ACUITY BRANDS NPODM SERIES WALLPOD.
LC
LIGHTING MANAGEMENT SYSTEM CONTROLLER. MOUNT AT 48'' AFF, UNLESS
OTHERWISE NOTED. BASIS OF DESIGN: ACUITY BRANDS FRESCO CONTROL SYSTEM
LC
LIGHTING MANAGEMENT SYSTEM OCCUPANCY SENSOR. MOUNT AT 48'' AFF, UNLESS
OTHERWISE NOTED. BASIS OF DESIGN: ACUITY BRANDS NCM PDT SERIES
LOS
VDB VIDEO DOOR BELL. RECESS MOUNTED AT 48" ABOVE FINISHED FLOOR. PROVIDE
BACKBOX AND CONDUIT WITH PULLSTRING.
DUPLEX RECEPTACLE, 20 AMPERE, 125 VOLT GROUNDING TYPE, NEMA 5-20R
CONFIGURATION, RECESS MOUNTED IN 4" SQUARE x 2-1/2" DEEP PRESSED
STEEL JUNCTION BOX, RECESSED IN CEILING.
JUNCTION BOX FOR A COMBINATION TELEPHONE AND DATA OUTLET, 4" SQUARE x
2-1/8" DEEP GALVANIZED PRESSED STEEL, RECESSED IN CEILING.
DUPLEX RECEPTACLE, 20 AMPERE, 125 VOLT GROUNDING TYPE, NEMA 5-20R
CONFIGURATION, RECESS MOUNTED IN 4" SQUARE x 2-1/8" DEEP PRESSED
STEEL JUNCTION BOX AT 8" ABOVE COUNTERTOP.
PROFESSIONAL CERTIFICATION. I HEREBY CERTIFY
THAT THESE DOCUMENTS WERE PREPARED OR
APPROVED BY ME, AND THAT I AM A DULY LICENSED
PROFESSIONAL ENGINEER UNDER THE LAWS OF THE
STATE OF MARYLAND, LICENSE NO. 49295, EXPIRATION
DATE: 12 MAY 2022.
S
FI
LE
N
RE
F:
PL
OT
D
AT
E:
/8/
4:
:55
P M
4.2
E-
1.D
W G
BREAKLINE
CL
NOTE REFERENCE NUMBER.
ROOM NUMBER DESIGNATION.
COLUMN LINE NUMBER.
DRAWING REVISION NUMBER.
CENTER LINE.
CONDUIT UP.
CONDUIT DOWN.DN
UP
DELTA CONFIGURATION.
WYE GROUNDING CONFIGURATION.
PHASE.Ø
NORTH ARROW
ARROW INDICATES TRUE NORTH
AND/OR PROJECT NORTHN
E101
N
8'0 1/8"=1'-0"
UNIQUE PLAN OR DETAIL
NUMBER ON THIS DRAWING NORTH ARROW
NAME OF PLAN OR DETAIL
ALL DRAWINGS WHERE
DETAIL IS REFERENCED
GRAPHIC SCALE OF
PLAN OR DETAIL
2-PART REFERENCE DETAIL IDENTIFICATION:
SHEET NUMBER WHERE
DETAIL/SECTION IS DRAWN
NUMBER INDICATES
DETAIL/SECTION
FLOOR PLAN
ED102, E-1022
FLOOR PLAN AND DETAIL TITLES:
NOTE REFERENCE NUMBER,
BOUNDARY/EXTENT AS INDICATED BY ARROW.
CONDUIT TURN DOWN.
SM
FRACTIONAL HORSEPOWER MANUAL MOTOR STARTER WITH SINGLE-POLE
TOGGLE DISCONNECT SWITCH, LOCKABLE TOGGLE GUARD, THERMAL
OVERLOAD RELAY, H-O-A SWITCH AND RED PILOT LIGHT IN 2-GANG SURFACE
MOUNTED NEMA 1 ENCLOSURE.
SM2
MOTOR-RATED TOGGLE SWITCH, 2-POLE, NON-REVERSING RATED FOR 1
HORSEPOWER (16 AMPERES CONTINUOUS CURRENT) @ 115-230/277 VOLTS IN
NEMA 1 ENCLOSURE WITH LOCKABLE TOGGLE GUARD. MOUNT ABOVE CEILING
ON STEEL SUPPORT CHANNEL ADJACENT TO EQUIPMENT SERVED.
COMBINATION MOTOR STARTER - ELECTRONIC MOTOR CIRCUIT PROTECTOR
(MCP) TYPE, FVNR,3-PHASE, NEMA SIZE 1, IN NEMA 1 ENCLOSURE WITH
208V-120V CONTROL TRANSFORMER WITH PRIMARY & SECONDARY FUSING,
120V AC COIL, H-O-A SWITCH, RED "ON" LED PUSH-TO-TEST PILOT
LIGHT AND (1) NORMALLY OPEN (N.O.) AND (1) NORMALLY CLOSED (N.C.)
AUXILIARY CONTACT.
CR
AV
PIR
PIR
P P
PIR
(E) (E) (E)CR
10 10
P
S
S S
S
S S S
S
SF
SF
SF
AV
AV
+55" AFF
PIR
E-401
E-401
S S
S S
S S S S S S S S S S S S S S S S
S S S
S S
S S
S S
S S S S
S S
S S
S S
S S
S S
S
SF SFS
S
S S
S S
S S
S S
S S
SF
S
S
S
S
S
S
SF
S
S
S
S
S
S
S
S
S
S
S
S
GFI GFI GFI GFI
GFI
GFI GFI
S S
S S
S S
S S
S S
S S
S S
S S
S S
CR
CR
PIR
PIR
AV
AV
AV
SM
PIR
S
S
S
S
S
SS
SS
SS
S
S
S
S S
S
S
FPB
2W-12A
FPB
2W-12B FPB
2W-12C
FPB
2W-12D
FPB
2W-12E
FPB
2W-12F
FPB
2-W12J
FPB
2W-12HFPB
2W-12G
FPB
2W-08A
FPB
2W-06A
FPB
2W-06B
FPB
2W-05A
FPB
2W-04A
FPB
2W-04B
FPB
2W-05B
FPB
2W-17A
FPB
2W-17B
FPB
2W-08B
SM
SM
SM
SM
SM
SM
J
J
J
WAV
2P-W3 1,3,5
2P-W3 7,9,11
2P-W3 13,15,172P-W3
19,21,23
2P-W3 25,27,29
2P-W3 2,4,6,38
2P-W3 14,16,18,40
2P-W3 8,10,12
2P-W3 20,22,24
2P-W3 26,28,30
2P-W3 26,28,30
2P-W3 31,33,35
2P-W3 49,51,53
S
SS
S
S
SF
SF
SF
2P-W3 50,52,54
2P-W3 56,58,60,62 62
2P-W3 55,57,59,61
2P-W3 63,65,67
2P-W3 69,71,73
2P-W3 37,39,41
2P-W3 42,44,46,48
2P-W3 75,77,79
2P-W3 64,66,68
SF
SF
2P-W3 76,78,80
2P-W3 70,72,74
2P-W2
2P-W2
2P-W2
2P-W2
2P-W2
2P-W2
2P-W2
2P-W2
2P-W2
2P-W2
2P-W2
2P-W2 23 11
GFI
GFI
GFI
GFI
E-104
9 9
2P-W2
2P-W2
2P-W2
2P-W2
2P-W2 20 2P-W2
2P-W2
2P-W2
2P-W2
2P-W2
2P-W2
2P-W2
2P-W2
2P-W2
2P-W2
2P-W2
2P-W2
2P-W2
2P-W2
2P-W2
2P-W2
SM
SM
SM
SM
SM
SM
SM
SM SM SM
SM
SM
SM
SM
SM
SM
SM
CRAIP
CR
CRAIP
AIP
CR
CR
DB13
DB13
DB13
DB13
DB13
DB13
DB13
DB13
DB13
DB13
DB13 DB13
DB 13
DB 13
2P-W2
2P-W2
2P-W2
2P-W2
2P-W2
2P-W2
2P-W2
2P-W2
2P-W2 2P-W2
2P-W2
2P-W3
+55" AFF
+55" AFF
+55" AFF
J
SF 2P-W3
43,45,47
(E)WALKER DUCT
(E)WALKER
DUCT
(E)WALKER
DUCT
(E)WALKER
DUCT
2L-W1
2L-W1
2L-W1
2L-W1
2L-W1
2L-W1
2L-W1
FPB
2W-09
FPB
2W-07
FPB
2W-13
FPB
2W-01
FPB
2W-14
FPB
2W-19
FPB
2W-18
FPB
2W-16
FPB
2W-11
FPB
2W-10
SM
SM
FPB
2W-20
FPB
2W-02
FPB
2W-03
2P-W2
2P-W2
2P-W2
2P-W2
TX-02-2
EF-02-1
SM2
SM SM SM SM
SM
SM
SM
SM
SM
SM
SM
SM
SM
2P-W2 45 2P-W2
46,48,50
SFSF
SFSFSF
SFSF SFSF
SFSF
SF
S
S
S
S
CR
AV
PIR
PIR
P P
PIR
(E) (E) (E)CR
10 10
P
S
S S
S
S S S
S
SF
SF
SF
AV
AV
+55" AFF
PIR
E-401
E-401
S S
S S
S S S S S S S S S S S S S S S S
S S S
S S
S S
S S
S S S S
S S
S S
S S
S S
S S
S
SF SFS
S
S S
S S
S S
S S
S S
SF
S
S
S
S
S
S
SF
S
S
S
S
S
S
S
S
S
S
S
S
GFI GFI GFI GFI
GFI
GFI GFI
S S
S S
S S
S S
S S
S S
S S
S S
S S
CR
CR
PIR
PIR
AV
AV
AV
SM
PIR
S
S
S
S
S
SS
SS
SS
S
S
S
S S
S
S
FPB
2W-12A
FPB
2W-12B FPB
2W-12C
FPB
2W-12D
FPB
2W-12E
FPB
2W-12F
FPB
2-W12J
FPB
2W-12HFPB
2W-12G
FPB
2W-08A
FPB
2W-06A
FPB
2W-06B
FPB
2W-05A
FPB
2W-04A
FPB
2W-04B
FPB
2W-05B
FPB
2W-17A
FPB
2W-17B
FPB
2W-08B
SM
SM
SM
SM
SM
SM
J
J
J
WAV
2P-W3 1,3,5
2P-W3 7,9,11
2P-W3 13,15,172P-W3
19,21,23
2P-W3 25,27,29
2P-W3 2,4,6,38
2P-W3 14,16,18,40
2P-W3 8,10,12
2P-W3 20,22,24
2P-W3 26,28,30
2P-W3 26,28,30
2P-W3 31,33,35
2P-W3 49,51,53
S
SS
S
S
SF
SF
SF
2P-W3 50,52,54
2P-W3 56,58,60,62 62
2P-W3 55,57,59,61
2P-W3 63,65,67
2P-W3 69,71,73
2P-W3 37,39,41
2P-W3 42,44,46,48
2P-W3 75,77,79
2P-W3 64,66,68
SF
SF
2P-W3 76,78,80
2P-W3 70,72,74
2P-W2
2P-W2
2P-W2
2P-W2
2P-W2
2P-W2
2P-W2
2P-W2
2P-W2
2P-W2
2P-W2
2P-W2 23 11
GFI
GFI
GFI
GFI
E-104
9 9
2P-W2
2P-W2
2P-W2
2P-W2
2P-W2 20 2P-W2
2P-W2
2P-W2
2P-W2
2P-W2
2P-W2
2P-W2
2P-W2
2P-W2
2P-W2
2P-W2
2P-W2
2P-W2
2P-W2
2P-W2
2P-W2
SM
SM
SM
SM
SM
SM
SM
SM SM SM
SM
SM
SM
SM
SM
SM
SM
CRAIP
CR
CRAIP
AIP
CR
CR
DB13
DB13
DB13
DB13
DB13
DB13
DB13
DB13
DB13
DB13
DB13 DB13
DB 13
DB 13
2P-W2
2P-W2
2P-W2
2P-W2
2P-W2
2P-W2
2P-W2
2P-W2
2P-W2 2P-W2
2P-W2
2P-W3
+55" AFF
+55" AFF
+55" AFF
J
SF 2P-W3
43,45,47
(E)WALKER DUCT
(E)WALKER
DUCT
(E)WALKER
DUCT
(E)WALKER
DUCT
2L-W1
2L-W1
2L-W1
2L-W1
2L-W1
2L-W1
2L-W1
FPB
2W-09
FPB
2W-07
FPB
2W-13
FPB
2W-01
FPB
2W-14
FPB
2W-19
FPB
2W-18
FPB
2W-16
FPB
2W-11
FPB
2W-10
SM
SM
FPB
2W-20
FPB
2W-02
FPB
2W-03
2P-W2
2P-W2
2P-W2
2P-W2
TX-02-2
EF-02-1
SM2
SM SM SM SM
SM
SM
SM
SM
SM
SM
SM
SM
SM
2P-W2 45 2P-W2
46,48,50
SFSF
SFSFSF
SFSF SFSF
SFSF
SF
S
S
S
S
H
G
F
E
D
C
10111213141516
020033
MAIL RM
+32" AFF
+32" AFF
+32" AFF
+32" AFF
+32" AFF
+32" AFF
C
SUMMER
CONSULTANTS
I N C O R P O R A T E D
SUMMER
CONSULTANTS
GENERAL NOTES
G1. ALL WORK SHALL BE NEW AND PROVIDED UNDER THIS
CONTRACT UNLESS SPECIFICALLY MARKED "EXISTING",
"EXIST.", OR "(E)".
G2. VERIFY LOCATION AND DIMENSIONS OF EXISTING
EQUIPMENT AND COORDINATE ALL WORK PRIOR TO THE
START OF CONSTRUCTION.
G3. SYSTEM FURNITURE SHALL BE WIRED IN 3-3-2
CONFIGURATION, WITH THREE PHASE CONDUCTORS,
THREE NEUTRAL CONDUCTORS, AND TWO GROUND
CONDUCTORS.
NOTES
1. SEE MOTOR AND EQUIPMENT SCHEDULE FOR MOTOR AND
FEEDER CHARACTERISTICS.
2. EXISTING OUTLET RETAINED UNDER DEMOLITION. PROVIDE
TWO (2) NEW CAT-6E CABLES TO OUTLET.
3. PROVIDE HARD-WIRED CONNECTION TO MOTORIZED
PARTITION. MAKE ALL FINAL CONNECTIONS BETWEEN
PARTITION AND CONTROL SWITCH.
4. PROVIDE HARD-WIRED CONNECTION TO SECURITY AUDIBLE
DEVICE.
5. PROVIDE CEILING MOUNTED RECEPTACLE AND DATA
OUTLET TO SERVE CEILING PROJECTOR. COORDINATE
EXACT LOCATION WITH FINAL EQUIPMENT LAYOUT.
6. SWITCH FURNISHED WITH MOTORIZED SCREEN. MAKE ALL
FINAL CONNECTIONS BETWEEN SWITCH, SCREEN, AND
MOTOR.
7. PROVIDE 3-WAY LOW VOLTAGE KEY SWITCH WITH
LOCKABLE COVER FOR MOTORIZED PARTITION. MAKE ALL
FINAL CONNECTIONS BETWEEN SWITCHES AND MOTOR.
8. PROVIDE HARDWIRED CONNECTION TO LECTERN.
COORDINATE LOCATION WITH FINAL EQUIPMENT LAYOUT.
9. PROVIDE DEDICATED RECEPTACLE AND DATA OUTLET
RECESSED IN SYSTEMS FURNITURE TO SERVE PLOTTER.
10. PROVIDE RECEPTACLE AND COVER PLATE. CONNECT TO
EXISTING CONDUIT AND CONDUCTORS RETAINED UNDER
DEMOLITION. CONNECT RECEPTACLE TO PANEL AND
CIRCUIT NUMBER AS INDICATED.
11. PROVIDE (2) RECEPTACLES RECESSED IN SHELVES. MOUNT
RECEPTACLES AT 38" AFF AND 58" AFF.
12. REFER TO ARCHITECTURAL PLANS AND ELEVATIONS FOR
EXACT MOUNTING LOCATIONS.
13. FIELD LOCATE SECURITY DEVICE ON UNDERSIDE OF DESK.
PROVIDE SURFACE MOUNTED RACEWAY TO CONCEAL ALL
SECURITY WIRING. COORDINATE WITH ARCHITECTURAL
DRAWINGS.
N
8'0 16' 1/8"=1'-0"
SECOND FLOOR PLAN (WEST) - POWER1
N
8'0 16' 1/8"=1'-0"
PART PLAN - MAIL ROOM
E-1042
PROFESSIONAL CERTIFICATION. I HEREBY CERTIFY
THAT THESE DOCUMENTS WERE PREPARED OR
APPROVED BY ME, AND THAT I AM A DULY LICENSED
PROFESSIONAL ENGINEER UNDER THE LAWS OF THE
STATE OF MARYLAND, LICENSE NO. 49295, EXPIRATION
DATE: 12 MAY 2022.
FI
LE
N
RE
F:
PL
OT
D
AT
E:
/8/
4:
:16
P M
4.2
E-
4-
.D
W G
020028
020001
020031
020030
020029
020032
020027
020025
020026
020033
020034
020037
020036
020035
020024
020001
020003
020004
020038
020023
020022
020021
020020
020019
020008
020007
020006
020018
020005 020002
020012
020013
020014
020015
020016
020017
020011 020010 020009
1 ADDENDUM 3 11/09/21
TELECOMMUNICATIONS
GROUNDING BUS BAR
4' X 8' AC GRADE 3/4" PLYWOOD BACKBOARD.
REFER TO ARCHITECTURAL PLANS
FOR SPECIFICATIONS.
D
CABLOFIL 2" X 16" CF 54/400
CABLE TRAY.
PANEL
T025010
PANEL
P025010
AC 2E-01
CAMPUS INTERCONNECTING CONDUITS (QUANTITY 5)
WITH BUSHING AND FIRESTOP.
INTERDUCT FOR FIBER. TRADE SIZE 2.
TR INTERCONNECTING CONDUITS (QUANTITY 6)
WITH BUSHING AND FIRESTOP.
INTERDUCT FOR FIBER. TRADE SIZE 4.
CONDUIT SLEEVES WITH BUSHING AND FIRESTOP
FOR HORIZONTAL DISTRIBUTION
1,3,5
7,9,11
2,4,6
PANEL P025028
AC 2E-02
PANEL T025028 PANEL T02502722
CABLOFIL 2" X 16" CF 54/400
CABLE TRAY.
TWO (2) CONDUITS INTERCONNECTING NETWORK
SUPPORT CENTER WITH ENTRANCE FACILITY, TRADE SIZE 2.
TELECOMMUNICATIONS
GROUNDING BUS BAR
TELECOMMUNICATIONS
GROUNDING BUS BAR
1,3,5 7,9,11
13,15,17
2,4,6
1,3,5 7,9,1111
CABLOFIL 2" X 16" CF 54/400
CABLE TRAY.
1 8,10,12
AC 2E-03
1,3,5
AC 1-01
7,9,11
CAMPUS INTERCONNECTING CONDUITS (QUANTITY 5)
WITH BUSHING AND FIRESTOP.
INTERDUCT FOR FIBER. TRADE SIZE 2.
TR INTERCONNECTING CONDUITS (QUANTITY 6)
WITH BUSHING AND FIRESTOP.
INTERDUCT FOR FIBER. TRADE SIZE 4.
CONDUIT SLEEVES WITH BUSHING AND FIRESTOP
FOR HORIZONTAL DISTRIBUTION
CABLOFIL 2" X 16" CF 54/400
CABLE TRAY.
PANEL P010044
PANEL T010044
TELECOMMUNICATIONS
GROUNDING BUS BAR
4' X 8' AC GRADE 3/4"
PLYWOOD BACKBOARD.
REFER TO ARCHITECTURAL
PLANS FOR SPECIFICATIONS.
4' X 8' AC GRADE 3/4" PLYWOOD BACKBOARD.
REFER TO ARCHITECTURAL PLANS FOR
SPECIFICATIONS.
2,4,6
5 710
4' X 8' AC GRADE 3/4"
PLYWOOD BACKBOARD.
REFER TO ARCHITECTURAL
PLANS FOR SPECIFICATIONS.
AC 16-04
TWO (2) CONDUITS INTERCONNECTING NETWORK
SUPPORT CENTER WITH ENTRANCE FACILITY, TRADE SIZE 4.
CONDUIT SLEEVES WITH BUSHING AND FIRESTOP
FOR CABLING FROM WORK AREA DATA OUTLETS
AND TELECOMMUNICATIONS ROOMS.
VERTICAL CABLE MANAGER WITH DOOR.
ORTRONICS OR-MM10VMD706-W
6" VERTICAL CABLE MANAGEMENT CAGE.
CABLOFIL 2" X 16" CF 54/400
CABLE TRAY.
TELECOMMUNICATIONS
GROUNDING BUS BAR
PANEL
P160003PANEL
T160003
7,9,11
1,3,5
2,4,6
SUMMER
CONSULTANTS
I N C O R P O R A T E D
SUMMER
CONSULTANTS
GENERAL NOTES
G1. ALL WORK SHALL BE NEW AND PROVIDED UNDER THIS
CONTRACT UNLESS SPECIFICALLY MARKED "EXISTING",
"EXIST.", OR "(E)".
G2. VERIFY LOCATION AND DIMENSIONS OF EXISTING
EQUIPMENT AND COORDINATE ALL WORK PRIOR TO
THE START OF CONSTRUCTION.
NOTES
1. SEE MECHANICAL AND EQUIPMENT SCHEDULE FOR
MOTOR AND FEEDER CHARACTERISTICS.
2. SERVICE PANELBOARD FOR RACK POWER IN NETWORK
SUPPORT CENTER. IT LOAD ONLY. SHALL BE EQUIPPED
WITH SCHNEIDER EM3500 SERIES DIN RAIL METER OR
EQUIVALENT.
3. NOT USED.
4. NOT USED.
5. NOT USED.
6. SERVICE PANELBOARD FOR NON-IT LOADS, HVAC,
CONVENIENCE RECEPTACLES. SHALL BE EQUIPPED
WITH SCHNEIDER EM3500 SERIES DIN RAIL METER OR
EQUIVALENT.
7. CHATSWORTH CABINET WITH VERTICAL EXHAUST DUCT
(VED). VED WILL EXTEND TO SUSPENDED CEILING.
8. OR-MM20730-W. 30" DEEP CHANNEL 7'H. 45RU.
ORTRONICS MM20 CHANNEL RACK.
9. 30A 208V TWIST LOCK 8.5' AFF {WYE (5-WIRE)
CONFIGURED, 208V, 30A, THREE-PHASE, TERMINATING
IN A NEMA L21-30R LOCKING RECEPTACLE. THE
NEUTRAL CONDUCTOR IN EACH WHIP IS TO BE UPSIZED.
LOCATION IS APPROXIMATE.
10. UNLESS OTHERWISE NOTED ALL RECEPTACLES
SERVING DATA RACKS AND I.T. LOADS SHALL BE FED
FROM PANEL 'T010044'. HVAC EQUIPMENT, GENERAL
PURPOSE EQUIPMENT, CONVENIENCE RECEPTACLES,
ETC. SHALL BE FED FROM PANEL 'P010044'.
11. UNLESS OTHERWISE NOTED ALL RECEPTACLES
SERVING DATA RACKS AND I.T. LOADS SHALL BE FED
FROM PANEL 'T025028'. HVAC EQUIPMENT, GENERAL
PURPOSE EQUIPMENT, CONVENIENCE RECEPTACLES,
ETC. SHALL BE FED FROM PANEL 'P025028'.
12. UNLESS OTHERWISE NOTED ALL RECEPTACLES
SERVING DATA RACKS AND I.T. LOADS SHALL BE FED
FROM PANEL 'T025027'. HVAC EQUIPMENT, GENERAL
PURPOSE EQUIPMENT, CONVENIENCE RECEPTACLES,
ETC. SHALL BE FED FROM PANEL 'P025028' (LOCATED IN
ADJACENT ROOM).
13. UNLESS OTHERWISE NOTED ALL RECEPTACLES
SERVING DATA RACKS AND I.T. LOADS SHALL BE FED
FROM PANEL 'T025010'. HVAC EQUIPMENT, GENERAL
PURPOSE EQUIPMENT, CONVENIENCE RECEPTACLES,
ETC. SHALL BE FED FROM PANEL 'P025010'.
14. UNLESS OTHERWISE NOTED ALL RECEPTACLES
SERVING DATA RACKS AND I.T. LOADS SHALL BE FED
FROM PANEL 'T160003'. HVAC EQUIPMENT, GENERAL
PURPOSE EQUIPMENT, CONVENIENCE RECEPTACLES,
ETC. SHALL BE FED FROM PANEL 'P160003'.
8'0 4' 1/4"=1'-0"
SECOND FLOOR - EAST - TELECOM CLOSET
ROOM 025010
E-1033
8'0 4' 1/4"=1'-0"
ROOM 025027 IRM/IDF CLOSET
ROOM 025028 IRM COMPUTER ROOM
E-1032
FI
LE
N
RE
F:
PL
OT
D
AT
E:
/8/
4:
:36
P M
4.2
E-
2.D
W G
PROFESSIONAL CERTIFICATION. I HEREBY CERTIFY
THAT THESE DOCUMENTS WERE PREPARED OR
APPROVED BY ME, AND THAT I AM A DULY LICENSED
PROFESSIONAL ENGINEER UNDER THE LAWS OF THE
STATE OF MARYLAND, LICENSE NO. 49295, EXPIRATION
DATE: 12 MAY 2022.
8'0 4' 1/4"=1'-0"
FIRST FLOOR TELECOM CLOSET
ROOM 010044
E-1021
8'0 4' 1/4"=1'-0"
16TH FLOOR - IDF CLOSET
ROOM 160003
E-1054
1 ADDENDUM 3 11/09/21
I N C O R P O R A T E D
SUMMER
CONSULTANTS
GENERAL NOTES
G1. ALL WORK SHALL BE NEW AND PROVIDED UNDER THIS
CONTRACT UNLESS SPECIFICALLY MARKED "EXISTING",
"EXIST.", OR "(E)".
G2. VERIFY LOCATION AND DIMENSIONS OF EXISTING
EQUIPMENT AND COORDINATE ALL WORK PRIOR TO
THE START OF CONSTRUCTION.
NOTES
1. PROVIDE CIRCUIT BREAKER IN EXISTING PANELBOARD.
2. PANEL SCHEDULES TOTALS DO NOT INCLUDE EXISTING
LOADS.
(E)PANEL 'GP-W1-SEC. 1' SCHEDULE
MAIN BUS SIZE (AMPS): 225A INTERRUPT. RATING (KAIC): 10 NEUTRAL BUS SIZE: 100% MOUNTING TYPE: SURFACE MAIN BUS MATERIAL: COPPER VOLTAGE: 120 / 208 SECTION NO.: 1 OF 1 LOCATION: MAIN ELECTRICAL ROOM MAIN CIRCUIT BREAKER (AMPS): 100 PHASE: 3 WIRE: 4 ENCLOSURE TYPE: NEMA 1 BOLT-ON BRANCH CIRCUIT BREAKERS
CKT
NO. DESCRIPTION LOAD
TYPE
LOAD
(KVA)
BREAKER BREAKER LOAD
(KVA)
LOAD
TYPE DESCRIPTION CKT
NO.AMPS POLES POLES AMPS
1 (E)LOAD N 0.00 20 1 A 1 20 0.72 R (E)LOAD 2
3 (E)LOAD N 0.00 20 1 B 1 20 0.72 R (E)LOAD 4
5 (E)LOAD N 0.00 20 1 C 1 20 0.72 R (E)LOAD 6
7 (E)LOAD N 0.00 20 1 A 1 20 0.54 N (E)LOAD 8
9 (E)LOAD N 0.00 20 1 B 1 20 0.90 R (E)LOAD 10
11 (E)LOAD N 0.00 20 1 C 1 20 0.00 N (E)LOAD 12
13 (E)LOAD N 0.00 20 1 A 1 20 0.72 R (E)LOAD 14
15 (E)LOAD N 0.00 20 1 B 1 20 0.00 N (E)LOAD 16
17 (E)LOAD N 0.00 20 1 C 1 20 0.72 R (E)LOAD 18
19 (E)LOAD N 0.00 20 1 A 1 20 0.00 N (E)LOAD 20
21 (E)LOAD N 0.00 20 1 B 1 20 0.00 N (E)LOAD 22
23 (E)LOAD N 0.00 20 1 C 1 20 0.00 N (E)LOAD 24
25 (E)LOAD N 0.00 20 1 A 1 20 0.00 N (E)LOAD 26
27 (E)LOAD N 0.00 20 1 B 1 20 0.00 N (E)LOAD 28
29 (E)LOAD N 0.00 20 1 C 1 20 0.00 N (E)LOAD 30
31 N 0.00 20 1 A 1 20 0.60 N SYS. FURN RM GF0009 A 32
33 N 0.00 20 1 B 1 20 0.60 N SYS. FURN RM GF0009 B 34
35 (E)LOAD N 0.00 20 1 C 1 20 0.60 N SYS. FURN RM GF0009 C 36
37 N 0.00 20 1 A 1 20 0.60 N SYS. FURN RM GF0009 A 38
39 N 0.00 20 1 B 1 20 0.60 N SYS. FURN RM GF0009 B 40
41 (E)LOAD N 0.00 20 1 C 1 20 0.60 N SYS. FURN RM GF0009 C 42
CONNECTED LOAD PER PHASE (kVA) = 3.2 2.8 2.6 TOTAL CONNECTED LOAD = 8.6 KVA 24.0 AMPS
(AMPS) = 26.5 23.5 22.0 TOTAL DEMAND LOAD = 8.6 KVA 24.0 AMPS
LOAD TYPES: C = CONTINUOUS, R = RECEPTACLE, M = MOTOR, N = NON-CONTINUOUS
(E)PANEL 'GP-W2' SCHEDULE
MAIN BUS SIZE (AMPS): 125A INTERRUPT. RATING (KAIC): 10 NEUTRAL BUS SIZE: 100% MOUNTING TYPE: SURFACE MAIN BUS MATERIAL: COPPER VOLTAGE: 120 / 208 SECTION NO.: 1 OF 1 LOCATION: MAIN ELECTRICAL ROOM MAIN CIRCUIT BREAKER (AMPS): PHASE: 3 WIRE: 4 ENCLOSURE TYPE: NEMA 1 BOLT-ON BRANCH CIRCUIT BREAKERS
CKT
NO. DESCRIPTION LOAD
TYPE
LOAD
(KVA)
BREAKER BREAKER LOAD
(KVA)
LOAD
TYPE DESCRIPTION CKT
NO.AMPS POLES POLES AMPS
1 (E)LOAD N 0.00 -- 1 A 1 -- 0.00 N (E)LOAD 2
3 (E)LOAD N 0.00 -- 1 B 1 -- 0.00 N (E)LOAD 4
5 (E)LOAD N 0.00 -- 1 C 1 -- 0.00 N (E)LOAD 6
7 (E)LOAD N 0.00 -- 1 A 1 -- 0.00 N (E)LOAD 8
9 (E)LOAD N 0.00 -- 1 B 1 -- 0.00 N (E)LOAD 10
11 (E)LOAD N 0.00 -- 1 C 1 -- 0.00 N (E)LOAD 12
13 (E)LOAD N 0.00 -- 1 A 1 -- 0.00 N (E)LOAD 14
15 (E)LOAD N 0.00 -- 1 B 1 -- 0.00 N (E)LOAD 16
17 (E)LOAD N 0.00 -- 1 C 1 -- 0.00 N (E)LOAD 18
19 (E)LOAD N 0.00 -- 1 A 1 -- 0.00 N (E)LOAD 20
21 (E)LOAD N 0.00 -- 1 B 1 -- 0.00 N (E)LOAD 22
23 (E)LOAD N 0.00 -- 1 C 1 -- 0.00 N (E)LOAD 24
25 (E)LOAD N 0.00 -- 1 A 1 -- 0.00 N (E)LOAD 26
27 (E)LOAD N 0.00 -- 1 B 1 -- 0.00 N (E)LOAD 28
29 (E)LOAD N 0.00 -- 1 C 1 -- 0.00 N (E)LOAD 30
31 REC. RM GF0005 R 0.80 20 1 A 1 20 0.60 N REC. PLOTTER 32
33 REC. RM GF0005 R 0.72 20 1 B 1 20 0.60 N REC. PLOTTER 34
35 REC. RM GF0005 R 0.54 20 1 C 1 20 0.60 N REC. PLOTTER 36
37 SPARE N 0.00 -- 1 A 1 20 0.60 N REC. PLOTTER 38
39 SPARE N 0.00 -- 1 B 1 20 0.60 N REC. PLOTTER 40
41 REC. RM GF0010 R 1.80 20 1 C 1 20 0.60 N REC. PLOTTER 42
CONNECTED LOAD PER PHASE (kVA) = 2.0 1.9 3.5 TOTAL CONNECTED LOAD = 7.5 KVA 20.7 AMPS
(AMPS) = 16.7 16.0 29.5 TOTAL DEMAND LOAD = 7.5 KVA 20.7 AMPS
LOAD TYPES: C = CONTINUOUS, R = RECEPTACLE, M = MOTOR, N = NON-CONTINUOUS
PANEL 'P010044' SCHEDULE
MAIN BUS SIZE (AMPS): 100A INTERRUPT. RATING (KAIC): 10 NEUTRAL BUS SIZE: 100% MOUNTING TYPE: SURFACE MAIN BUS MATERIAL: COPPER VOLTAGE: 120 / 208 SECTION NO.: 1 OF 1 LOCATION: I.T ROOM 010043 MAIN CIRCUIT BREAKER (AMPS): 60A PHASE: 3 WIRE: 4 ENCLOSURE TYPE: NEMA 1 BOLT-ON BRANCH CIRCUIT BREAKERS
CKT
NO. DESCRIPTION LOAD
TYPE
LOAD
(KVA)
BREAKER BREAKER LOAD
(KVA)
LOAD
TYPE DESCRIPTION CKT
NO.AMPS POLES POLES AMPS
1 RECEPTACLES N 0.36 20 1 A
3 15
0.51 M
A/C UNIT 1-01
3 RECEPTACLES N 0.36 20 1 B 0.51 M 4
5 RECEPTACLES N 0.72 20 1 C 0.51 M 6
7 RECEPTACLES N 0.72 20 1 A
3 20
0.10 C
POWER METER
9 SPARE N 0.00 20 1 B 0.10 C 10
11 SPARE N 0.00 20 1 C 0.10 C 12
13 SPARE N 0.00 20 1 A 1 20 0.00 N SPARE 14
15 SPACE N 0.00 - 1 B 1 -- 0.00 N SPACE 16
17 SPACE N 0.00 - 1 C 1 -- 0.00 N SPACE 18
19 SPACE N 0.00 -- 1 A 1 -- 0.00 N SPACE 20
21 SPACE N 0.00 -- 1 B 1 -- 0.00 N SPACE 22
23 SPACE N 0.00 -- 1 C 1 -- 0.00 N SPACE 24
25 SPACE N 0.00 -- 1 A 1 -- 0.00 N SPACE 26
27 SPACE N 0.00 -- 1 B 1 -- 0.00 N SPACE 28
29 SPACE N 0.00 -- 1 C 1 -- 0.00 N SPACE 30
CONNECTED LOAD PER PHASE (kVA) = 1.7 1.0 1.3 TOTAL CONNECTED LOAD = 4.0 KVA 11.1 AMPS
(AMPS) = 14.1 8.1 11.1 TOTAL DEMAND LOAD = 4.4 KVA 12.4 AMPS
LOAD…