472-19320.JBB_Alger Correctional Showers Bid Drawings 3-21-25 PT2.pdf

PDF 11 MB Posted

Attached to
472/19320. JBB; Alger C. F. - Shower Renovations
Solicitation number
RFQ 171 250000000316 3
Issued by
Alger County, Michigan

About this file

This document is a comprehensive bid set of architectural and engineering drawings for shower renovation work at Alger Correctional Facility, a state of Michigan facility administered by the Department of Technology, Management and Budget, State Facilities Administration, Design and Construction Division. The project (472/19320.JBB) involves the renovation of shower facilities across multiple housing units (Spruce, Birch, Maple, Cedar, and Pine buildings) at the correctional facility. The scope of work encompasses the provision and installation of new shower enclosures with integrated I-CON control systems, new electrical lighting fixtures with security features, new HVAC exhaust systems with roof-mounted fans, updated plumbing infrastructure including tempered water distribution and sanitary drainage modifications, and associated structural openings. The drawings indicate that work must be phased to maintain operational showers at all times, with only one set of showers per housing unit shut down at any given time, except for the unoccupied Birch unit where all showers may be replaced simultaneously. The contractor must coordinate closely with facility management, secure work areas from inmate access at shift end, and provide two escorts as needed for simultaneous work in multiple housing units.

The bid set specifies that all work shall conform to the Michigan Mechanical Code, Michigan Plumbing Code, and applicable standards including NFPA regulations for sprinkler system modifications. Key electrical requirements include installation of new 20-ampere circuit breakers for shower control transformers and exhaust fans, reuse of existing circuits where possible, and specification of tamper-proof fasteners in inmate-accessible areas. HVAC work requires balancing exhaust rates to 150 CFM per shower and coordination with shower enclosure manufacturers for proper ductwork connections. Plumbing modifications must maintain the existing Symmons 7000 Tempcontrol master mixing valve system and accommodate new I-CON Nexus X12 4-shower controllers with solenoid valves. The plans show detailed floor plans at 1/4" scale for all areas, mechanical symbols and abbreviations, phasing notes, and general notes addressing site security, recycling tracking, field verification requirements, and notification procedures for hot work and utility shutdowns. The review date is March 14, 2025, with the plan review set dated March 21, 2025, and this is the bid set version of the construction documents.

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

ELECTRICAL KEY NOTES

PROVIDE AND INSTALL NEW LIGHT FIXTURE. RE-USE

EXISTING CIRCUIT. REFER TO SHEET E-100 FOR LIGHT

FIXTURE SCHEDULE.

PROVIDE AND INSTALL NEW LOCK SWITCH (LEGRAND MODEL

NUMBER PS20AC1WL OR APPROVED EQUAL). PROVIDE NEW

SECURITY COVER PLATE AND SECURITY SCREWS. RE-USE

EXISTING CIRCUIT.

PROVIDE AND INSTALL NEW LIGHT FIXTURE. FEED FROM

EXISTING LIGHTING CIRCUIT OUTSIDE OF SHOWER STALL.

REFER TO SHEET E-100 FOR LIGHT FIXTURE SCHEDULE.

LA

LB LB

LA

LB LB

LA

1 1

LC LC

LC LC

LA

1 1

LC LC

LC LC

3 3

JC

/E

N G

B Y

IN

D

EX

PC

A

D R

AW

N

B Y

D

ES

IG

N

ED

B

Y

D E

P A

R T

M E

N T

O F

T E

C H

N O

L O

G Y

M

A N

A G

E M

E N

T A

N D

B U

D G

E T

S T

A T

E O

F M

IC

H

IG

A

N

A D

A M

P L

A C

H R

A N

C A

R B

D

IR

E

C T

O R

S T

A T

E F

A C

IL

IT

IE

S

A D

M

IN

IS

T

R A

T

IO

N

D E

S

IG

N A

N D

C O

N S

T R

U C

T

IO

N D

IV

IS

IO

N

PR

O

JE

C

T D

ES

C

R

IP

TI

O

N

PR

O

JE

C T

N O

2/

0.

JB

B

AR

C

H

IT

EC

TS

EN

G

IN

EE

R S

M A

T R

I X

SH

O

W

ER

R

EN

O

VA

TI

O

N S

AL

G

ER

C

O R

R

EC

TI

O

N

AL

F

AC

IL

IT

Y

KEY PLAN

SCALE: NTS

wing 'A' wing 'C'

LOWER LEVEL

PLAN

NORTH

wing 'B' wing 'D'

UPPER LEVEL

R ev ie w

D

AT

E

/1

4/

PL

AN

R

EV

IE

W S

ET

/2

1/

BI

D S

ET

D

R K

EL

EC

TR

IC

AL

FL

O O

R P

LA

N

N

EW

L

IG

H

TI

N G

JF

S

E-

SCALE: 1/4" = 1'-0"

0 1 5 10

SCALE: 1/4" = 1'-0"

0 1 5 10

SCALE: 1/4" = 1'-0"

0 1 5 10

SCALE: 1/4" = 1'-0"

0 1 5 10

FIRST FLOOR PLAN - BUILDING SPRUCE-

AREA A - ELECTRICAL LIGHTING - NEW

SECOND FLOOR PLAN - BUILDING SPRUCE-

AREA B - ELECTRICAL LIGHTING - NEW

FIRST FLOOR PLAN - BUILDING SPRUCE-

AREA C - ELECTRICAL LIGHTING - NEW

SECOND FLOOR PLAN - BUILDING SPRUCE-

AREA D - ELECTRICAL LIGHTING - NEW

N N

PROVIDE AND INSTALL NEW LIGHT FIXTURE. RE-USE

EXISTING CIRCUIT. REFER TO SHEET E-100 FOR LIGHT

FIXTURE SCHEDULE.

PROVIDE AND INSTALL NEW LOCK SWITCH (LEGRAND MODEL

NUMBER PS20AC1WL OR APPROVED EQUAL). PROVIDE NEW

SECURITY COVER PLATE AND SECURITY SCREWS. RE-USE

EXISTING CIRCUIT.

2 2

LA

LB LB

2 2

LA

LB LB

2 21

LBLA LB

2 2

LA

LB LB

JC

/E

N G

B Y

IN

D

EX

PC

A

D R

AW

N

B Y

D

ES

IG

N

ED

B

Y

D E

P A

R T

M E

N T

O F

T E

C H

N O

L O

G Y

M

A N

A G

E M

E N

T A

N D

B U

D G

E T

S T

A T

E O

F M

IC

H

IG

A

N

A D

A M

P L

A C

H R

A N

C A

R B

D

IR

E

C T

O R

S T

A T

E F

A C

IL

IT

IE

S

A D

M

IN

IS

T

R A

T

IO

N

D E

S

IG

N A

N D

C O

N S

T R

U C

T

IO

N D

IV

IS

IO

N

PR

O

JE

C

T D

ES

C

R

IP

TI

O

N

PR

O

JE

C T

N O

2/

0.

JB

B

AR

C

H

IT

EC

TS

EN

G

IN

EE

R S

M A

T R

I X

SH

O

W

ER

R

EN

O

VA

TI

O

N S

AL

G

ER

C

O R

R

EC

TI

O

N

AL

F

AC

IL

IT

Y

KEY PLAN

SCALE: NTS

wing 'A' wing 'C'

LOWER LEVEL

PLAN

NORTH

wing 'B' wing 'D'

UPPER LEVEL

R ev ie w

D

AT

E

/1

4/

PL

AN

R

EV

IE

W S

ET

/2

1/

BI

D S

ET

D

R K

EL

EC

TR

IC

AL

FL

O O

R P

LA

N

N

EW

L

IG

H

TI

N G

JF

S

E-

SCALE: 1/4" = 1'-0"

0 1 5 10

SCALE: 1/4" = 1'-0"

0 1 5 10

SCALE: 1/4" = 1'-0"

0 1 5 10

SCALE: 1/4" = 1'-0"

0 1 5 10

FIRST FLOOR PLAN - BUILDING BIRCH, MAPLE, PINE -

AREA A - ELECTRICAL NEW

SECOND FLOOR PLAN - BUILDING BIRCH, MAPLE, PINE -

AREA B - ELECTRICAL NEW

FIRST FLOOR PLAN - BUILDING BIRCH, MAPLE, PINE -

AREA C - ELECTRICAL NEW

SECOND FLOOR PLAN - BUILDING BIRCH, MAPLE, PINE -

AREA D - ELECTRICAL NEW

N

BIRCH MAPLE PINE

(ALT 1) (ALT 1)

N N N

BIRCH MAPLE PINE

(ALT 1) (ALT 1)

N N

N

BIRCH MAPLE PINE

(ALT 1) (ALT 1)

N N N

BIRCH MAPLE PINE

(ALT 1) (ALT 1)

J

(4) 3/4" CND RACEWAY

FOR TOUCH SENSOR

CABLE

(1) 3/4" CND RACEWAY FOR TOUCH

SENSOR CABLE

TO

UPPER

LEVEL

(2) 3/4" CND FOR TOUCH SENSOR

CABLE

(2) #12

(1) #10 GRD

(1) 3/4" CND

TO PANEL 'RPC',

CIRCUIT #41 IN

ELECTRICAL ROOM.

REFER TO SHEET E-502

FOR LOCATION.

ICON SHOWER CONTROLLER

COORDINATE WITH PLUMBING

CONTRACTOR FOR LOCATION

AND REFER TO P-400 FOR

MODEL NUMBER

LOW VOLTAGE

TRANSFORMER

1. ELECTRICAL CONTRACTOR TO PROVIDE A 3/4" RACEWAY FROM I-CON

SHOWER CONTROLLER TO TOUCH SENSOR LOCATION. THIS

RACEWAY WILL BE USED FOR FISHING LOW VOLTAGE SENSOR

CABLES TO EXACT SENSOR LOCATION. COORDINATE WITH OTHER

TRADES IN FEILD.

GENERAL ELECTRICAL NOTES

TO

LOWER

LEVEL

(1) 3/4" CND RACEWAY FOR TOUCH

SENSOR CABLE

EF-1

120V 1Ø, 1/3HP

(LOCATED ON ROOF)

RPC-40

(2) #12

(1) #12 GRD

(1) 3/4" CND

TO ELECTRICAL

ROOM. REFER TO

SHEET E-502 FOR

LOCATION.

TO

LOWER

LEVEL

(1) 3/4" CND

RACEWAY FOR

TOUCH SENSOR

CABLE

EF-2

120V 1Ø, 1/3HP

RPC-42

(2) #12

(1) #12 GRD

(1) 3/4" CND

TO ELECTRICAL

ROOM. REFER

TO SHEET E-502

FOR LOCATION.

(1) 3/4" CND RACEWAY FOR TOUCH

(1) 3/4" CND

RACEWAY FOR

TOUCH SENSOR

CABLE

TO PANEL 'RPC',

CIRCUIT #39 IN

ELECTRICAL ROOM.

REFER TO SHEET

E-502 FOR LOCATION.

TO

UPPER

LEVEL

(2) 3/4" CND FOR TOUCH

SENSOR CABLE

ICON SHOWER CONTROLLER

COORDINATE WITH PLUMBING

CONTRACTOR FOR LOCATION

AND REFER TO P-400 FOR

MODEL NUMBER

LOW VOLTAGE

TRANSFORMER

2(2) #12

(1) #10 GRD

(1) 3/4" CND

ELECTRICAL KEY NOTES

PROVIDE AND INSTALL NEW CIRCUIT FROM EXISTING PANEL

"RPC" LOCATED IN ELECTRICAL ROOM FOR NEW EXHAUST FAN

ON ROOF. PROVIDE AND INSTALL ALL CONDUIT, WIRE,

HARDWARE, THERMAL OVERLOAD SWITCHES, STARTERS

PROVIDE AND INSTALL LOCAL SERVICE LOCKABLE SWITCH.

COORDINATE FINAL LOCATION OF SERVICE SWITCH WITH

OWNER TO ENSURE MOST USER AND APPLICATION FRIENDLY

LOCATION.

PROVIDE AND INSTALL NEW CIRCUIT FROM EXISTING PANEL

"RPC" LOCATED IN ELECTRICAL ROOM FOR NEW 120V-1PH

500VA LOW VOLTAGE TRANSFORMER. PROVIDE AND INSTALL

ALL CONDUIT, WIRE, AND HARDWARE AS REQUIRED. REFER

TO SHEET E-502 FOR PANEL LOCATIONS.

RE-INSTALL EXISTING TOUCH SCREEN PHONE. MODIFY

CONDUIT AND WIRE AS REQUIRED.

PROVIDE AND INSTALL NEW SURFACE MOUNT CONDUIT,

HARDWARE, AND BOX TO RELOCATE EXISTING DEVICE SHOWN

ON SHEET E-300. EXTEND WIRE AS REQUIRED.

JC

/E

N G

B Y

IN

D

EX

PC

A

D R

AW

N

B Y

D

ES

IG

N

ED

B

Y

D E

P A

R T

M E

N T

O F

T E

C H

N O

L O

G Y

M

A N

A G

E M

E N

T A

N D

B U

D G

E T

S T

A T

E O

F M

IC

H

IG

A

N

A D

A M

P L

A C

H R

A N

C A

R B

D

IR

E

C T

O R

S T

A T

E F

A C

IL

IT

IE

S

A D

M

IN

IS

T

R A

T

IO

N

D E

S

IG

N A

N D

C O

N S

T R

U C

T

IO

N D

IV

IS

IO

N

PR

O

JE

C

T D

ES

C

R

IP

TI

O

N

PR

O

JE

C T

N O

2/

0.

JB

B

AR

C

H

IT

EC

TS

EN

G

IN

EE

R S

M A

T R

I X

SH

O

W

ER

R

EN

O

VA

TI

O

N S

AL

G

ER

C

O R

R

EC

TI

O

N

AL

F

AC

IL

IT

Y

KEY PLAN

SCALE: NTS

wing 'A' wing 'C'

LOWER LEVEL

PLAN

NORTH

wing 'B' wing 'D'

UPPER LEVEL

R ev ie w

D

AT

E

/1

4/

PL

AN

R

EV

IE

W S

ET

/2

1/

BI

D S

ET

D

R K

EL

EC

TR

IC

AL

FL

O O

R P

LA

N

N

EW

P O

W

ER

JF

S

E-

SCALE: 1/4" = 1'-0"

0 1 5 10

SCALE: 1/4" = 1'-0"

0 1 5 10

SCALE: 1/4" = 1'-0"

0 1 5 10

SCALE: 1/4" = 1'-0"

0 1 5 10

FIRST FLOOR PLAN - BUILDING SPRUCE-

AREA C - ELECTRICAL POWER - NEW

SECOND FLOOR PLAN - BUILDING SPRUCE-

AREA D - ELECTRICAL POWER - NEW

FIRST FLOOR PLAN - BUILDING SPRUCE-

AREA A - ELECTRICAL POWER - NEW

SECOND FLOOR PLAN - BUILDING SPRUCE-

AREA B - ELECTRICAL POWER - NEWN N

1. ELECTRICAL CONTRACTOR TO PROVIDE A 3/4" RACEWAY FROM I-CON

SHOWER CONTROLLER TO TOUCH SENSOR LOCATION. THIS

RACEWAY WILL BE USED FOR FISHING LOW VOLTAGE SENSOR

CABLES TO EXACT SENSOR LOCATION. COORDINATE WITH OTHER

TRADES IN FEILD.

GENERAL ELECTRICAL NOTES

TO UPPER LEVEL

TO PANEL 'RPC', CIRCUIT

#41 IN ELECTRICAL ROOM.

REFER TO SHEET E-503 FOR

LOCATION.

(1) 3/4" CND RACEWAY FOR

TOUCH SENSOR CABLE

(2) 3/4" CND FOR TOUCH

SENSOR CABLE

ICON SHOWER CONTROLLER

COORDINATE WITH PLUMBING

CONTRACTOR FOR LOCATION

AND REFER TO P-401 FOR

MODEL NUMBER LOW VOLTAGE

TRANSFORMER

(2) #12

(1) #10 GRD

(1) 3/4" CND

TO LOWER LEVEL

(2) #12 2 CONDUCTOR AWG PLENUM

RATED LOW VOLTAGE CABLES

(1) 3/4" CND

EF-3

120V 1Ø, 1/3HP

RPC-42

(2) #12

(1) #12 GRD

(1) 3/4" CND

TO ELECTRICAL ROOM.

REFER TO SHEET

E-503FOR LOCATION.

TO LOWER LEVEL

(1) 3/4" CND RACEWAY FOR

TOUCH SENSOR CABLE

EF-4

120V 1Ø, 1/3HPRPC-40

(2) #12

(1) #12 GRD

(1) 3/4" CND

TO ELECTRICAL ROOM.

REFER TO SHEET E-503

FOR LOCATION.

TO UPPER LEVEL

TO PANEL 'RPC', CIRCUIT

#39 IN ELECTRICAL ROOM.

REFER TO SHEET E-503 FOR

LOCATION.

(1) 3/4" CND RACEWAY FOR

TOUCH SENSOR CABLE

(2) 3/4" CND FOR

TOUCH SENSOR

CABLE

ICON SHOWER CONTROLLER

COORDINATE WITH PLUMBING

CONTRACTOR FOR LOCATION

AND REFER TO P-401 FOR

MODEL NUMBER

LOW VOLTAGE

TRANSFORMER

(2) #12

(1) #10 GRD

(1) 3/4" CND

ELECTRICAL KEY NOTES

PROVIDE AND INSTALL NEW CIRCUIT FROM EXISTING PANEL

"RPC" LOCATED IN ELECTRICAL ROOM FOR NEW EXHAUST FAN

ON ROOF. PROVIDE AND INSTALL ALL CONDUIT, WIRE,

HARDWARE, THERMAL OVERLOAD SWITCHES, STARTERS

PROVIDE AND INSTALL LOCAL SERVICE LOCKABLE SWITCH.

COORDINATE FINAL LOCATION OF SERVICE SWITCH WITH

OWNER TO ENSURE MOST USER AND APPLICATION FRIENDLY

LOCATION.

PROVIDE AND INSTALL NEW CIRCUIT FROM EXISTING PANEL

"RPC" LOCATED IN ELECTRICAL ROOM FOR NEW 120V-1PH

500VA LOW VOLTAGE TRANSFORMER. PROVIDE AND INSTALL

ALL CONDUIT, WIRE, AND HARDWARE AS REQUIRED. REFER

TO SHEET E-502 FOR PANEL LOCATIONS.

RE-INSTALL EXISTING TOUCH SCREEN PHONE. MODIFY

CONDUIT AND WIRE AS REQUIRED.

PROVIDE AND INSTALL NEW SURFACE MOUNT CONDUIT,

HARDWARE, AND BOX TO RELOCATE EXISTING DEVICE SHOWN

ON SHEET E-300. EXTEND WIRE AS REQUIRED.

JC

/E

N G

B Y

IN

D

EX

PC

A

D R

AW

N

B Y

D

ES

IG

N

ED

B

Y

D E

P A

R T

M E

N T

O F

T E

C H

N O

L O

G Y

M

A N

A G

E M

E N

T A

N D

B U

D G

E T

S T

A T

E O

F M

IC

H

IG

A

N

A D

A M

P L

A C

H R

A N

C A

R B

D

IR

E

C T

O R

S T

A T

E F

A C

IL

IT

IE

S

A D

M

IN

IS

T

R A

T

IO

N

D E

S

IG

N A

N D

C O

N S

T R

U C

T

IO

N D

IV

IS

IO

N

PR

O

JE

C

T D

ES

C

R

IP

TI

O

N

PR

O

JE

C T

N O

2/

0.

JB

B

AR

C

H

IT

EC

TS

EN

G

IN

EE

R S

M A

T R

I X

SH

O

W

ER

R

EN

O

VA

TI

O

N S

AL

G

ER

C

O R

R

EC

TI

O

N

AL

F

AC

IL

IT

Y

KEY PLAN

SCALE: NTS

wing 'A' wing 'C'

LOWER LEVEL

PLAN

NORTH

wing 'B' wing 'D'

UPPER LEVEL

R ev ie w

D

AT

E

/1

4/

PL

AN

R

EV

IE

W S

ET

/2

1/

BI

D S

ET

D

R K

JF

S

E-

SCALE: 1/4" = 1'-0"

0 1 5 10

SCALE: 1/4" = 1'-0"

0 1 5 10

SCALE: 1/4" = 1'-0"

0 1 5 10

SCALE: 1/4" = 1'-0"

0 1 5 10

FIRST FLOOR PLAN - BUILDING BIRCH, MAPLE, PINE -

AREA A - ELECTRICAL NEW

SECOND FLOOR PLAN - BUILDING BIRCH, MAPLE, PINE -

AREA B - ELECTRICAL NEW

FIRST FLOOR PLAN - BUILDING BIRCH, MAPLE, PINE -

AREA C - ELECTRICAL NEW

SECOND FLOOR PLAN - BUILDING BIRCH, MAPLE, PINE -

AREA D - ELECTRICAL NEW

EL

EC

TR

IC

AL

FL

O O

R P

LA

N

N

EW

P O

W

ER

N

BIRCH MAPLE PINE

(ALT 1) (ALT 1)

N NN

BIRCH MAPLE PINE

(ALT 1) (ALT 1)

N N

N

BIRCH MAPLE PINE

(ALT 1) (ALT 1)

N N N

BIRCH MAPLE PINE

PROVIDE WRITTEN AS-CONSTRUCTED DOCUMENTS AS PART

OF CLOSE OUT DOCUMENTS. PROVIDE AND INSTALL

PERMANENTLY FIXED LABELS AND UPDATE PANEL SCHEDULES

ACCORDINGLY. PROVIDE TYPED PANEL SCHEDULES.

INSTALL NEW 20A/1P CIRCUIT BREAKER IN EXISTING BLANK

SPACES, CIRCUITS #39 AND #41 FOR SHOWER CONTROL LOW

VOLTAGE TRANSFORMERS.

INSTALL NEW 20A/1P CIRCUIT BREAKER IN EXISTING BLANK

SPACES, CIRCUITS #40 AND #42 FOR NEW EXHAUST FANS.

ELECTRICAL

ROOM

AREA OF WORK ON

UPPER AND LOWER

LEVELS

AREA OF WORK ON

UPPER AND LOWER

LEVELS

RPA

208/120V 3Ø

RPB

208/120V 3Ø

RPC

208/120V 3Ø

RPD

208/120V 3Ø

RPX

208/120V 3Ø

EMDP

480V 3Ø

D R

K H

O U

SI

N

G U

N

IT

EL

EC

TR

IC

AL

R

O O

M S

JF

S

E-

SECOND FLOOR PLAN - BUILDING SPRUCE -

ELECTRICAL NEW

N

JC

/E

N G

B Y

IN

D

EX

PC

A

D R

AW

N

B Y

D

ES

IG

N

ED

B

Y

D E

P A

R T

M E

N T

O F

T E

C H

N O

L O

G Y

M

A N

A G

E M

E N

T A

N D

B U

D G

E T

S T

A T

E O

F M

IC

H

IG

A

N

A D

A M

P L

A C

H R

A N

C A

R B

D

IR

E

C T

O R

S T

A T

E F

A C

IL

IT

IE

S

A D

M

IN

IS

T

R A

T

IO

N

D E

S

IG

N A

N D

C O

N S

T R

U C

T

IO

N D

IV

IS

IO

N

PR

O

JE

C

T D

ES

C

R

IP

TI

O

N

PR

O

JE

C T

N O

2/

0.

JB

B

AR

C

H

IT

EC

TS

EN

G

IN

EE

R S

M A

T R

I X

SH

O

W

ER

R

EN

O

VA

TI

O

N S

AL

G

ER

C

O R

R

EC

TI

O

N

AL

F

AC

IL

IT

Y R ev ie w D

AT

E

/1

4/

PL

AN

R

EV

IE

W S

ET

/2

1/

BI

D S

ET

SCALE: 1/8" = 1'-0"

0 1 5 10 20

PROVIDE WRITTEN AS-CONSTRUCTED DOCUMENTS AS PART

OF CLOSE OUT DOCUMENTS. PROVIDE AND INSTALL

PERMANENTLY FIXED LABELS AND UPDATE PANEL SCHEDULES

ACCORDINGLY. PROVIDE TYPED PANEL SCHEDULES.

INSTALL NEW 20A/1P CIRCUIT BREAKER IN EXISTING BLANK

SPACES, CIRCUITS #39 AND #41 FOR SHOWER CONTROL LOW

VOLTAGE TRANSFORMERS.

INSTALL NEW 20A/1P CIRCUIT BREAKER IN EXISTING BLANK

SPACES, CIRCUITS #40 AND #42 FOR NEW EXHAUST FANS.

ELECTRICAL

ROOM

AREA OF WORK ON

UPPER AND

LOWER LEVELS

AREA OF WORK ON

UPPER AND

LOWER LEVELS

RPX

208/120V 3Ø

RPA

208/120V 3Ø

RPB

208/120V 3Ø

RPC

208/120V 3Ø

RPD

208/120V 3Ø

D R

K H

O U

SI

N

G U

N

IT

EL

EC

TR

IC

AL

R

O O

M S

JF

S

E-

3SECOND FLOOR PLAN - BUILDING BIRCH, MAPLE, PINE

ELECTRICAL NEW

N

JC

/E

N G

B Y

IN

D

EX

PC

A

D R

AW

N

B Y

D

ES

IG

N

ED

B

Y

D E

P A

R T

M E

N T

O F

T E

C H

N O

L O

G Y

M

A N

A G

E M

E N

T A

N D

B U

D G

E T

S T

A T

E O

F M

IC

H

IG

A

N

A D

A M

P L

A C

H R

A N

C A

R B

D

IR

E

C T

O R

S T

A T

E F

A C

IL

IT

IE

S

A D

M

IN

IS

T

R A

T

IO

N

D E

S

IG

N A

N D

C O

N S

T R

U C

T

IO

N D

IV

IS

IO

N

PR

O

JE

C

T D

ES

C

R

IP

TI

O

N

PR

O

JE

C T

N O

2/

0.

JB

B

AR

C

H

IT

EC

TS

EN

G

IN

EE

R S

M A

T R

I X

SH

O

W

ER

R

EN

O

VA

TI

O

N S

AL

G

ER

C

O R

R

EC

TI

O

N

AL

F

AC

IL

IT

Y R ev ie w D

AT

E

/1

4/

PL

AN

R

EV

IE

W S

ET

/2

1/

BI

D S

ET

SCALE: 1/8" = 1'-0"

0 1 5 10 20

BIRCH MAPLE PINE

NN

GENERAL HVAC NOTES

MECHANICAL SYMBOLS LEGEND

HVAC DUCTWORK

MISCELLANEOUS NOTES

HVAC DUCTWORK SYMBOLS HVAC DUCTWORK & DIFFUSER TAGS

MECHANICAL ABBREVIATIONS

AFF ABOVE FINISH FLOOR

AC AIR COMPRESSOR

AHU AIR HANDLING UNIT

AS AIR SEPARATOR

A.T.C. ARCHITECTURAL TRADES CONTRACTOR

B BOILER

B.A.S. BUILDING AUTOMATION SYSTEM

CAF COMBUSTION AIR FAN

CC COOLING COIL

CFM CUBIC FEET PER MINUTE

CHLR CHILLER

CHP CONSOLE HEAT PUMP

CONV CONVECTOR

CT COOLING TOWER

CU CONDENSING UNIT

CUH CABINET UNIT HEATER

CV CONTROL VALVE

CWP CHILLED WATER PUMP

DB DRY BULB

DFU DUCT FURNACE

DIA DIAMETER

DN DOWN

DPR DAMPER

DS DUCT SILENCER

EAT ENTERING AIR TEMPERATURE

EF EXHAUST FAN

EG EXHAUST GRILLE

E.T.C. ELECTRICAL TRADES CONTRACTOR

EVR EVAPORATOR

EWT ENTERING WATER TEMPERATURE

EXH EXHAUST

EXIST EXISTING

FF FINISH FLOOR

FPM FEET PER MINUTE

FT FEET

FTR FINNED TUBE RADIATION

FU FURNACE

GAL GALLON

GFRH GAS FIRED RADIANT HEATER

GR GRILLE

H HUMIDIFIER

HC HEATING COIL

HD HEAD (FT)

HP HORSE POWER

HHP HORIZONTAL HEAT PUMP

HTG HEATING

HVAC HEATING, VENTILATION, & AIR CONDITIONING

HWP HEATING WATER PUMP

HX HEAT EXCHANGER

ID INSIDE DIAMETER

I.E. INVERT ELEVATION

IAH INTAKE HOOD

LAT LEAVING AIR TEMPERATURE

LH LATENT HEAT (MBH)

LWT LEAVING WATER TEMPERATURE

MAX MAXIMUM

MBH BTU PER HOUR (THOUSAND)

MIN MINIMUM

M.T.C. MECHANICAL TRADES CONTRACTOR

N.C. NOISE CRITERIA

NFPA NATIONAL FIRE PROTECTION ASSOCIATION

NTS NOT TO SCALE

P PUMP

PCR PUMPED CONDENSATE RETURN

PD PRESSURE DROP

RCP RADIANT CEILING PANEL

REQ'D REQUIRED

RG RETURN GRILLE

RH RELATIVE HUMIDITY

RLH RELIEF HOOD

RTU ROOF TOP UNIT

SD SUPPLY DIFFUSER

SF SUPPLY FAN

SG SUPPLY GRILLE

SH SENSIBLE HEAT (MBH)

SM SHEET METAL

SQ. FT. SQUARE FEET

SST SATURATED SUCTION TEMPERATURE

STR STRAINER

TC TOTAL COOLING (MBH)

TCL TEMPERATURE CONTROL

T&P TEMPERATURE & PRESSURE RELIEF VALVE

TYP TYPICAL

UH UNIT HEATER

VAV VARIABLE AIR VOLUME BOX

VRH VARIABLE AIR VOLUME REHEAT BOX

FPVAV FAN POWERED VARIABLE AIR VOLUME BOX

V.F.D VARIABLE FREQUENCY DRIVE

ZD ZONE DAMPER

X-SA EXISTING ITEM (EXISTING SUPPLY AIR DUCT)

ITEM

EXISTING

SUPPLY AIR DUCT

EXIST SUPPLY AIR DUCT

RETURN AIR DUCT

EXIST RETURN AIR DUCT

OUTSIDE AIR DUCT

EXIST OUTSIDE AIR DUCT

EXHAUST AIR DUCT

EXIST EXHAUST AIR DUCT

SUPPLY AIR DUCT RISER

RETURN AIR DUCT RISER

OUTSIDE AIR DUCT RISER (AS NOTED)

EXHAUST AIR DUCT

INSULATED DUCTWORK (AS NOTED)

SUPPLY AIR DIFFUSER (SQUARE)

SUPPLY AIR DIFFUSER (INLINE)

SURFACE MTD. GRILLE

SUPPLY AIR DIFFUSER (ROUND)

DEMOLITION

POINT OF CONNECTION BETWEEN NEW AND

EXISTING

POINT OF EXISTING TO REMAIN AND EXISTING

TO BE REMOVED

INDICATES PLAN NOTE

INDICATES DEMOLITION NOTE

DETAIL BUBBLE

DETAIL NUMBER

PAGE LOCATION INDICATES

DIRECTION OF DETAIL SECTION

X

X

XX

XXXX

XX

XXXX

SA

OA

X-OA

X-EA

EA

X-SA

X-RA

RA

TAG CFM

NECK REMARKS

SIZE

SD-1 250

8"ø ---

PHASING NOTES

GENERAL INFORMATION:

A. EXISTING WATER SERVICE SHALL REMAIN ACTIVE AND

FUNCTIONAL DURING CONSTRUCTION. INDIVIDUAL RISERS CAN

BE SHUTDOWN AS NEEDED, COORDINATE WITH OWNER PRIOR

TO BRANCH SHUTDOWNS.

B. PHASING NOTES ARE INTENDED FOR GENERAL SEQUENCE OF

CONSTRUCTION. CONTRACTOR TO COORDINATE WITH

DRAWINGS FOR SPECIFIC DETAILS FOR DEMOLITION &

INSTALLATION OF ALL NEW EQUIPMENT, PIPING, AND

ACCESSORIES.

C. ALL RISER SHUTDOWNS TO BE CLOSELY COORDINATED WITH

THE OWNER.

D. ONLY ONE SET OF SHOWERS PER HOUSING UNIT SHALL BE

UPGRADED AT A TIME. SIX SHOWERS TO REMAIN IN SERVICE

AT ALL TIMES.

E. THE OWNER WILL PROVIDE A MAXIMUM OF 2 ESCORTS WITH

THE ANTICIPATION THAT WORK IN TWO DIFFERENT HOUSING

UNITS WILL BE HAPPENING SIMULTANEOUSLY.

F. FOR ALL HOUSING UNITS ON THIS PROJECT ONLY ONE

SET/PAIR OF SHOWERS CAN BE SHUT DOWN AND WORKED

ON AT ANY ONE TIME PER HOUSING UNIT, EXCEPT FOR

BIRCH. THE REMAINING THREE SETS/PAIRS OF SHOWERS

ARE TO BE FULLY OPERATIONAL. THE REPLACED SHOWERS

MUST BE FULLY INSPECTED, APPROVED, AND MADE

OPERABLE, BEFORE THE CONTRACTOR CAN MOVE TO THE

NEXT SET/PAIR OF SHOWERS TO BEGIN WORK.

G. CONTRACTOR TO BEGIN CONSTRUCTION IN HOUSING UNIT

BIRCH AS THE HOUSING UNIT IS CURRENTLY UNOCCUPIED.

G.A. HOUSING UNIT BIRCH IS UNOCCUPIED AT THE TIME OF

CONSTRUCTION, THE CONTRACTOR WILL HAVE

ACCESS AND THE ABILITY TO REPLACE ALL THE

SHOWERS AT ONE TIME.

3 ROOF MOUNTED EXHAUST FAN DETAIL

SCALE: NTS

ROOF OPENING FRAMING BY

GENERAL TRADES

SPUN ALUMINUM FAN

HOUSING

ALUMINUM BIRD SCREEN ALL

AROUND

SECURE FAN TO CURB WITH

SHEET METAL SCREWS 12"

O.C. ALL AROUND

REFER TO DRAWINGS FOR

DUCT SIZE

24" HIGH INSULATED PRE-

FAB. ROOF CURB

FAN IMPELLAR

DIRECT DRIVE MOTOR

COUNTER FLASHING

ROOFING MATERIAL BACKDRAFT

DAMPER

FRAME

VANED ELBOW

LOCKING LUG

2-1/4"R

4-1/2"R

TURNING VANE

NOTES:

1. LOCKING LUGS INTEGRAL WITH VANE

2. MAXIMUM UNSUPPORTED VANE LENGTH 48"

3. FRAMES - BOLTED OR RIVETED TO ELBOW

4. VANES AND FRAMES - SAME GAUGE AS ELBOW

2 1/4"

3 1/2"

HANGER STRAPS HANGER RODS

STRAP HANGER TRAPEZE HANGER

NO POP RIVETS ALLOWED,

USE SELF-TAPPING

SHEETMETAL SCREWS ONLY

(TYP)

NOTE:

90° ELBOW SHOWN SIMILAR

RADIUS CONSTRUCTION FOR

ALL ANGLES

R

R

OFFSET

ELBOW

FULL RADIUS

(R=W)

FLOW

AIR

TRANSITION - CONTRACTION FLOW

TRANSITION - DIVERGING FLOW

FLOW

AIR

W

W

R=1/ W

W

TURNING VANES FORSQUARE

ELBOW DETAIL

SCALE: NTS

4 DUCT HANGER DETAIL

SCALE: NTS

RECTANGULAR TRANSITIONS, OFFSETS,

AND ELBOWS

SCALE: NTS

5 DUCT TRANSITION DETAIL

SCALE: NTS

NOTES:

1. "ALTERNATE" FITTINGS SHALL BE

ACCEPTABLE ONLY WHEN DUCT HEIGHT

DOES NOT PERMIT THE USE OF

"PERMITTED" FULL SIZE BELLMOUTH

CONNECTION

2. THIS DETAIL APPLIES TO SINGLE TAKEOFFS

TO DIFFUSER AS WELL AS BRANCH

TAKEOFFS. IT ALSO APPLIES TO TAKEOFFS

IN THE HORIZONTAL AS WELL AS THE

VERTICAL DIRECTION.

DUCT SIZE:

(SEE PLANS)

ALTERNATE 1

TAKE-OFF DETAIL

ALTERNATE 2

TAKE-OFF DETAIL

(WHEN OTHERS DO NOT FIT)

RECTANGULAR TO ROUND

BOOT CONNECTIONMINI-BELLMOUTH CONNECTION

MANUAL VOLUME

DAMPER TYPICAL AT

ALL DUCT

TAKE-OFFS

VDVD

MAIN DUCT

AIR FLOW

6" min.

RADIUS ELBOW

1. LOCATE EXHAUST OUTLETS OF VENTILATION SYSTEMS AT LEAST 10 FEET

FROM OUTDOOR AIR INTAKES.

2. ALL EXISTING SYSTEMS (INCLUDING EXHAUST FANS AIR HANDLING UNITS;

PUMPS) THAT SERVES AREAS BEING RENOVATED SHALL BE REBALANCED AS

REQUIRED.

3. NOTIFY OWNER OF ANY PIPING OR DUCTWORK DEMOLITION THAT MAY

AFFECT NORMAL OPERATION OF OTHER AREAS.

4. FIELD VERIFY LOCATIONS OF EXISTING DUCTWORK OR PIPING THAT MAY

CONFLICT WITH NEW CONSTRUCTION AND NOTIFY ENGINEER .

5. PROVIDE BALANCE DAMPERS FOR EACH DIFFUSER/GRILLE AND BRANCH

DUCT.

6. PROVIDE FLEXIBLE DUCT IN ACCESSIBLE CEILINGS. 6 FT MAX LENGTH. KEEP

BENDS TO A MINIMUM.

7. FIRE DAMPERS & COMBINATION FIRE/SMOKE DAMPERS SHALL MATCH

RATING OF WALL. UNLESS NOTED OTHERWISE.

8. CONTRACTOR SHALL COORDINATE ALL WORK WITH OTHER DISCIPLINES

PRIOR TO CONSTRUCTION TO AVOID CONFLICTS.

9. OFFSET PIPING TO ACCOMMODATE LARGE DUCTWORK.

10. THE CONTRACTOR SHALL FIELD VERIFY THE SIZES, LOCATION, ELEVATIONS,

AND DETAILS OF ALL EXISTING CONDITIONS THAT MAY AFFECT THE WORK.

11. THE CONTRACTOR SHALL BE RESPONSIBLE FOR MAINTAINING THE

INTEGRITY OF ALL EQUIPMENT AND MATERIALS IN A "NEW" CONDITION

DURING CONSTRUCTION.

12. ALL WORK SHALL BE PERFORMED BY LICENSED CONTRACTORS AND

SUBCONTRACTORS AS REQUIRED BY LAW.

13. ALL WORK SHALL CONFORM TO MICHIGAN MECHANICAL CODE, LATEST

APPLICABLE EDITION.

14. CONTRACTOR SHALL USE LOW PRESSURE LOSS DUCT FITTINGS IN

ACCORDANCE WITH SMACNA. (WYES, RADIUSED OR VANED TEES, ETC.)

DUCTWORK SHALL BE GALVANIZED SHEET METAL, MIN. 26 GA.

15. ALL DUCT DIMENSIONS SHOWN ARE INSIDE CLEAR DIMENSION. INCREASE

DUCT SIZE FOR LINING.

16. IF THERE IS CONFLICTING INFORMATION IN THE PLANS OR SPECIFICATIONS

THE MORE STRINGENT AND GREATER COST ITEM SHALL BE USED.

17. DRAWINGS INDICATE REQUIRED SIZES AND POINTS OF TERMINATION OF

PIPES AND DUCTS AND SUGGESTED ROUTES. IT IS NOT INTENTION OF

DRAWINGS TO INDICATE ALL NECESSARY OFFSETS. INSTALL WORK IN

MANNER TO CONFORM TO STRUCTURE, AVOID OBSTRUCTIONS, PRESERVE

HEADROOM AND KEEP OPENINGS AND PASSAGEWAYS CLEAR. DO NOT

SCALE FROM DRAWINGS.

18. ALL AREAS OF WORK MUST BE SECURED AND INACCESSIBLE TO INMATES

DURING CONSTRUCTION. THE CONTRACTOR MUST SECURE EACH AREA OF

WORK AT THE END OF EACH SHIFT.

19. CONTRACTOR TO TRACK AND PROVIDE PAPERWORK TO OWNER OF THE

AMOUNT OF MATERIAL BEING RECYCLED THROUGHOUT THE PROJECT.

20. CONTRACTOR TO PATCH AND PAINT EXISTING CEILINGS AND WALLS AS

NEEDED TO MATCH EXISTING WHERE DEMOLITION AND/OR NEW WORK IS

COMPLETED.

21. ALL FASTENERS USED IN AREAS EXPOSED TO INMATES SHALL USE

TAMPERPROOF SCREWS.

22. CONTRACTOR TO VERIFY WITH I-CON OR PRE-APPROVED SHOWER

ENCLOUSRE MANUFACTURER FOR THE LOCATION OF THE SHOWER

ENCLOSURE BUILT-IN EXHAUST GRILLES.

23. CONTRACTOR TO FIELD VERIFY LOCATIONS WHERE THE NEW EXHAUST

DUCTWORK WILL PENETRATE THE EXISTING BLOCK WALL TO CONNECT TO

THE SHOWER ENCLOSURE EXHAUST GRILLE. CONTRACTOR TO VERIFY THAT

THE NEW EXHAUST DUCTWORK WILL NOT INTERFERE WITH ANY EXISTING

FIELD CONDITIONS OR ANY NEW UTILITIES ROUTED IN THE CHASE SPACE.

24. CONTRACTOR TO NOTIFY THE FACILITY AT LEAST 1 DAY IN ADVANCE FOR

ANY HOT WORK TO ALLOW THE OWNER TO DISABLE THE FIRE ALARM.

JC

/E

N G

B Y

IN

D

EX

PC

A

D R

AW

N

B Y

D

ES

IG

N

ED

B

Y

D E

P A

R T

M E

N T

O F

T E

C H

N O

L O

G Y

M

A N

A G

E M

E N

T A

N D

B U

D G

E T

S T

A T

E O

F M

IC

H

IG

A

N

A D

A M

P L

A C

H R

A N

C A

R B

D

IR

E

C T

O R

S T

A T

E F

A C

IL

IT

IE

S

A D

M

IN

IS

T

R A

T

IO

N

D E

S

IG

N A

N D

C O

N S

T R

U C

T

IO

N D

IV

IS

IO

N

PR

O

JE

C

T D

ES

C

R

IP

TI

O

N

PR

O

JE

C T

N O

2/

0.

JB

B

AR

C

H

IT

EC

TS

EN

G

IN

EE

R S

M A

T R

I X

SH

O

W

ER

R

EN

O

VA

TI

O

N S

AL

G

ER

C

O R

R

EC

TI

O

N

AL

F

AC

IL

IT

Y R ev ie w D

AT

E

/1

4/

PL

AN

R

EV

IE

W S

ET

/2

1/

BI

D S

ET

JL

H

M

EC

H

AN

IC

AL

SY

M

BO

LS

AB

BR

EV

IA

TI

O

N S

N

O

TE

S

BR

H

M -1

X-6x8 SA UP X-6x8 RA UPX-RG ---

10x10 ---

X-RG ---

10x10 ---1

X-SD 50

12x12 ---

X-6x8 RA UP

X-6x8 RA DN

X-8x6 SA UP AND DN X-6x8 RA UP

X-6x8 RA UP AND DN

X-RG ---

10x10 ---

X-RG ---

10x10 ---1

X-SD 50

12x12 ---

X-6x8 RA UP X-6x8 RA DN

X-6x8 SA UP

X-8x6 SA DN

X-RG ---

10x10 ---

X-8x8 RA UP AND DN 1

X-SD 50

12x12 ---

X-RG ---

10x10 ---

X-RG ---

10x10 ---

X-RG ---

10x10 ---

X-6x8 SA UP X-6x8 RA UP

X-SD 50

12x12 ---

DEMOLITION NOTES

DISCONNECT, REMOVE, AND DEMO EXISTING RETURN GRILLE. ALTER EXISTING

DUCTWORK AS REQUIRED TO CONNECT TO NEW RETURN GRILLE.

DISCONNECT, REMOVE, AND DEMO EXISTING SUPPLY DIFFUSER. ALTER EXISTING

DUCTWORK AS REQUIRED TO CONNECT TO NEW SUPPLY DIFFUSER.

DISCONNECT, REMOVE, AND DEMO EXISTING SUPPLY DIFFUSER. CAP EXISTING

DUCTWORK ABOVE NEW CEILING AND ABANDON.

JC

/E

N G

B Y

IN

D

EX

PC

A

D R

AW

N

B Y

D

ES

IG

N

ED

B

Y

D E

P A

R T

M E

N T

O F

T E

C H

N O

L O

G Y

M

A N

A G

E M

E N

T A

N D

B U

D G

E T

S T

A T

E O

F M

IC

H

IG

A

N

A D

A M

P L

A C

H R

A N

C A

R B

D

IR

E

C T

O R

S T

A T

E F

A C

IL

IT

IE

S

A D

M

IN

IS

T

R A

T

IO

N

D E

S

IG

N A

N D

C O

N S

T R

U C

T

IO

N D

IV

IS

IO

N

PR

O

JE

C

T D

ES

C

R

IP

TI

O

N

PR

O

JE

C T

N O

2/

0.

JB

B

AR

C

H

IT

EC

TS

EN

G

IN

EE

R S

M A

T R

I X

SH

O

W

ER

R

EN

O

VA

TI

O

N S

AL

G

ER

C

O R

R

EC

TI

O

N

AL

F

AC

IL

IT

Y wing 'A' wing 'C'

LOWER LEVEL

wing 'B' wing 'D'

UPPER LEVEL

R ev ie w

D

AT

E

/1

4/

PL

AN

R

EV

IE

W S

ET

/2

1/

BI

D S

ET

FL

O

O R

P

LA

N

BU

IL

D

IN

G

SP

R U

C E

- H

VA

C D

EM

O

LI

TI

O N

N

FIRST FLOOR PLAN - BUILDING SPRUCE -

AREA A - HVAC DEMOLITION

SCALE: 1/4" = 1'-0"

0 1 5 10

SCALE: 1/4" = 1'-0"

0 1 5 10

SCALE: 1/4" = 1'-0"

0 1 5 10

SCALE: 1/4" = 1'-0"

0 1 5 10

N

SECOND FLOOR PLAN - BUILDING

SPRUCE - AREA B - HVAC DEMOLITION

N

FIRST FLOOR PLAN - BUILDING SPRUCE -

AREA C - HVAC DEMOLITION N

SECOND FLOOR PLAN - BUILDING

SPRUCE - AREA D - HVAC DEMOLITION JL

H

BR

H

M -3

X-SD ---

15x15 ---

X-RG ---

12x12 ---

X-12x10 SA UP

X-10x10 RA UP X-12x12 SA UP X-8x6 RA UP

X-SD ---

12x12 ---

X-SA

X-SD ---

15x15 ---

X-RG ---

12x12 ---

X-12x10 SA DN

X-10x10 RA DN X-8x6 RA UP

X-10x10 RA DN

X-SD ---

12x12 ---

X-SA

10x10 RA DN

X-RG ---

12x12 ---

X-12x10 SA DN

X-12x10 RA UP

X-8x6 RA UP

X-SD ---

15x15 ---

X-SD ---

12x12 ---

X-SA

X-12x10 SA UP

X-12x12 SA UP

X-8x6 RA UP X-10x10 RA UP

X-SD ---

15x15 ---

X-RG ---

12x12 ---1

X-SD ---

12x12 ---

X-SA

DEMOLITION NOTES

DISCONNECT, REMOVE, AND DEMO EXISTING RETURN GRILLE. ALTER EXISTING

DUCTWORK AS REQUIRED TO CONNECT TO NEW RETURN GRILLE.

DISCONNECT, REMOVE, AND DEMO EXISTING SUPPLY DIFFUSER. ALTER EXISTING

DUCTWORK AS REQUIRED TO CONNECT TO NEW SUPPLY DIFFUSER.

DISCONNECT, REMOVE, AND DEMO EXISTING SUPPLY DIFFUSER. CAP EXISTING

DUCTWORK ABOVE NEW CEILING AND ABANDON.

JC

/E

N G

B Y

IN

D

EX

PC

A

D R

AW

N

B Y

D

ES

IG

N

ED

B

Y

D E

P A

R T

M E

N T

O F

T E

C H

N O

L O

G Y

M

A N

A G

E M

E N

T A

N D

B U

D G

E T

S T

A T

E O

F M

IC

H

IG

A

N

A D

A M

P L

A C

H R

A N

C A

R B

D

IR

E

C T

O R

S T

A T

E F

A C

IL

IT

IE

S

A D

M

IN

IS

T

R A

T

IO

N

D E

S

IG

N A

N D

C O

N S

T R

U C

T

IO

N D

IV

IS

IO

N

PR

O

JE

C

T D

ES

C

R

IP

TI

O

N

PR

O

JE

C T

N O

2/

0.

JB

B

AR

C

H

IT

EC

TS

EN

G

IN

EE

R S

M A

T R

I X

SH

O

W

ER

R

EN

O

VA

TI

O

N S

AL

G

ER

C

O R

R

EC

TI

O

N

AL

F

AC

IL

IT

Y wing 'A' wing 'C'

LOWER LEVEL

wing 'B' wing 'D'

UPPER LEVEL

R ev ie w

D

AT

E

/1

4/

PL

AN

R

EV

IE

W S

ET

/2

1/

BI

D S

ET

JL

H

FL

O

O R

P

LA

N

BU

IL

D

IN

G S

BI

R

C H

, M

AP

LE

(A

LT

PI

N E(

AL

T

1)

H

VA

C D

EM

O

LI

TI

O N

BR

H

M -3

SCALE: 1/4" = 1'-0"

0 1 5 10

SCALE: 1/4" = 1'-0"

0 1 5 10

SCALE: 1/4" = 1'-0"

0 1 5 10

SCALE: 1/4" = 1'-0"

0 1 5 10

N

FIRST FLOOR PLAN - BUILDINGS BIRCH, MAPLE, PINE -

AREA A - HVAC DEMOLITION

BIRCH MAPLE PINE

(ALT 1) (ALT 1)

N N

N N N

SECOND FLOOR PLAN - BUILDINGS BIRCH, MAPLE,

PINE - AREA B - HVAC DEMOLITION

FIRST FLOOR PLAN - BUILDINGS BIRCH, MAPLE, PINE -

AREA C - HVAC DEMOLITION

SECOND FLOOR PLAN - BUILDINGS BIRCH, MAPLE, PINE -

AREA D - HVAC DEMOLITION

NN N N

N N N

BIRCH MAPLE PINE

(ALT 1) (ALT 1)

BIRCH MAPLE PINE

(ALT 1) (ALT 1)

BIRCH MAPLE PINE

RG-1 50

10x10 ---

RG-1 50

10x10 ---

X-6x8 SA UP X-6x8 RA UP

10x10 EA UP

SD-1 50

15x15 ---

8x6 EA DN TO

SHOWER EA GRILLE

OPENING (TYP. 2)

EG-1 100

8x6 ---

10x6 EA 2

6x6 EA

10x8 EA 2

RG-1 50

10x10 ---

RG-1 50

10x10 ---

X-6x8 RA UP

X-6x8 RA DN

X-8x6 SA UP AND DN X-6x8 RA UP

X-6x8 RA UP AND DN

12x12 EA UP

TO EF-1

(LOCATED ON

ROOF)

SD-1 50

15x15 ---

8x6 EA DN TO

SHOWER EA GRILLE

OPENING (TYP. 2)

10x6 EA

10x10 EA DN

4EG-1 100

8x6 ---

10x6 EA

RG-1 50

10x10 ---

RG-1 50

12x12 ---

X-6x8 RA UP X-6x8 RA DN

X-6x8 SA UP

X-8x6 SA DN

X-8x8 RA UP AND DN

12x12 EA UP

TO EF-2

(LOCATED ON

ROOF)

SD-1 50

15x15 ---

420x8 EA DN, 16x6 EA DN

THROUGH FLOOR

6x6 EA

8x6 EA DN TO

SHOWER EA GRILLE

OPENING (TYP. 2)

EG-1 100

8x6 ---

10x6 EA 2

20x8 EA

RG-1 50

12x12 ---

RG-1 50

10x10 ---

X-6x8 SA UP X-6x8 RA UP

16x6 EA UP

SD-1 50

15x15 ---

8x6 EA DN TO

SHOWER EA GRILLE

OPENING (TYP. 2)

EG-1 100

8x6 ---

10x6 EA

6x6 EA

HVAC KEY NOTES

INSTALL NEW ROOF MOUNTED EXHAUST FAN, ROOF

CURB, DUCTWORK, CONTROLS, AND ALL ASSOCIATED

ACCESSORIES IN THE LOCATION SHOWN.

CONTRACTOR TO PATCH NEW ROOF PENETRATION

TO MATCH EXISTING, SEAL WATER TIGHT, AND

MAINTAIN ANY EXISTING ROOF WARRANTIES.

COORDINATE WITH THE STRUCTURAL DRAWINGS FOR

LOCATION OF THE NEW PENETRATION. INSTALL

LOCAL ON/OFF SWITCH FOR EXHAUST FAN IN

LOCATION SHOWN.

INSTALL NEW EXHAUST AIR DUCTWORK AND ALL

ASSOCIATED ACCESSORIES IN THE LOCATION

SHOWN.

ROUTE NEW EXHAUST DUCTWORK TO NEW SHOWER

ENCLOSURE. CONNECT THE EXHAUST DUCTWORK TO

SHOWER ENCLOSURE INTEGRATED EXHAUST AIR

GRILLE. EXHAUST CONNECTION LOCATION TO BE

COORDINATED WITH SHOWER ENCLOSURE

MANUFACTURER. CONTRACTOR BALANCE THE

EXHAUST RATE TO 150 CFM FOR EACH SHOWER.

COORDINATE WITH THE STRUCTURAL DRAWINGS FOR

LOCATION OF THE NEW PENETRATION.

INSTALL NEW RETURN GRILLE AT LOCATION SHOWN.

ALTER EXISTING RETURN AIR DUCTWORK AS

REQUIRED TO CONNECT TO NEW EXHAUST GRILLE .

BALANCE TO CFM SHOWN.

INSTALL NEW SUPPLY DIFFUSER AT LOCATION

SHOWN. ALTER EXISTING SUPPLY DUCTWORK AS

REQUIRED TO CONNECT TO NEW SUPPLY GRILLE.

BALANCE TO CFM SHOWN.

BOTTOM EDGE OF EXHAUST GRILL SHALL BE

INSTALLED AT LEAST 6" ABOVE FINISHED FLOOR.

GENERAL HVAC NOTES

1. MODIFY THE EXISTING SPRINKLER PIPING PER NFPA

13 AS REQUIRED TO ACCOMMODATE NEW DUCTWORK,

DOMESTIC WATER PIPING, LIGHTING, AND CEILING.

2. CONTRACTOR TO COORDINATE NEW EXHAUST AIR

DUCT ROUTING TO ACCOMMODATE EXISTING

STRUCTURAL I-BEAM LOCATED IN THE CHASE SPACE

BEHIND SHOWERS.

3. ALL ROOF PENETRATIONS ARE TO BE SEALED WATER

TIGHT, MATCH EXISTING, AND MAINTAIN EXISTING

ROOF WARRANTIES. EXISTING ROOF WARRANTY BY

McGRATH ROOFING (PHONE #: 906-482-7107).

4. CONTRACTOR IS RESPONSIBLE FOR THE REMOVAL

AND PATCHING OF THE EXISTING HARD LID CEILING

AS REQUIRED TO COMPLETE THEIR WORK.

CONTRACTOR TO PATCH, PRIME, AND PAINT CEILING

AS REQUIRED PER THE ARCHITECTURAL DRAWINGS

TO MATCH EXISTING.

5. CONTRACTOR TO COORDINATE ALL DIFFUSER

LOCATIONS AND SIZES PRIOR TO NEW CEILING

INSTALLATION.

JC

/E

N G

B Y

IN

D

EX

PC

A

D R

AW

N

B Y

D

ES

IG

N

ED

B

Y

D E

P A

R T

M E

N T

O F

T E

C H

N O

L O

G Y

M

A N

A G

E M

E N

T A

N D

B U

D G

E T

S T

A T

E O

F M

IC

H

IG

A

N

A D

A M

P L

A C

H R

A N

C A

R B

D

IR

E

C T

O R

S T

A T

E F

A C

IL

IT

IE

S

A D

M

IN

IS

T

R A

T

IO

N

D E

S

IG

N A

N D

C O

N S

T R

U C

T

IO

N D

IV

IS

IO

N

PR

O

JE

C

T D

ES

C

R

IP

TI

O

N

PR

O

JE

C T

N O

2/

0.

JB

B

AR

C

H

IT

EC

TS

EN

G

IN

EE

R S

M A

T R

I X

SH

O

W

ER

R

EN

O

VA

TI

O

N S

AL

G

ER

C

O R

R

EC

TI

O

N

AL

F

AC

IL

IT

Y wing 'A' wing 'C'

LOWER LEVEL

wing 'B' wing 'D'

UPPER LEVEL

R ev ie w

D

AT

E

/1

4/

PL

AN

R

EV

IE

W S

ET

/2

1/

BI

D S

ET

JL

H

BR

H

M -4

N

FIRST FLOOR PLAN - BUILDING SPRUCE -

AREA A - HVAC NEW

SCALE: 1/4" = 1'-0"

0 1 5 10

SCALE: 1/4" = 1'-0"

0 1 5 10

SCALE: 1/4" = 1'-0"

0 1 5 10

SCALE: 1/4" = 1'-0"

0 1 5 10

N

SECOND FLOOR PLAN - BUILDING

SPRUCE - AREA B - HVAC NEW

N

FIRST FLOOR PLAN - BUILDING SPRUCE -

AREA C - HVAC NEW N

SECOND FLOOR PLAN - BUILDING

SPRUCE - AREA D - HVAC NEW

FL

O

O R

P

LA

N

BU

IL

D

IN

G

SP

R U

C E

- H

VA

C N

EW

SD-1 50

15x15 ---

RG-1 50

12x12 ---5

X-12x10 SA UP

X-10x10 RA UP X-12x12 SA UP X-8x6 RA UP

X-SA

12x8 EA UP

8x6 EA TO SHOWER

EA GRILLE OPENING

(TYP. 2)

2 EG-1 50

12x12 TYP. 2

6x10 EA 2

6x6 EA

CAP

6x6 EA

SD-1 50

15x15 ---

RG-1 50

12x12 ---5

X-12x10 SA DN

X-10x10 RA DN X-8x6 RA UP

X-10x10 RA DN

X-SA

12x12 EA UP TO EF-3

(MOUNTED ON ROOF)

8x6 EA TO SHOWER

EA GRILLE OPENING

(TYP. 2)

12x12 EA UP, 12x8 EA

DN THROUGH FLOOR

6x6 EA

6x10 EA 2

EG-1 50

12x12 TYP. 2

CAP

6x6 EA

SD-1 50

15x15 ---

RG-1 50

12x12 ---

10x10 RA DN

X-12x10 SA DN

X-12x10 RA UP

X-8x6 RA UP

X-SA

12x12 EA UP TO EF-4

(MOUNTED ON ROOF)

8x6 EA TO SHOWER

EA GRILLE OPENING

(TYP. 2)

2EG-1 50

12x12 TYP. 2

12x12 EA UP, 12x8 EA

DN THROUGH FLOOR

6x6 EA

6x10 EA2

6x6 EA 2

CAP

RG-1 50

12x12 ---

X-12x10 SA UP

X-12x12 SA UP

X-8x6 RA UP X-10x10 RA UP

X-SA

SD-1 50

15x15 ---6

12x8 EA UP

8x6 EA TO SHOWER

EA GRILLE OPENING

(TYP. 2)

6x6 EA

6x10 EA2

6x6 EA 2

CAP

EG-1 50

12x12 TYP. 2

HVAC KEY NOTES

INSTALL NEW ROOF MOUNTED EXHAUST FAN, ROOF

CURB, DUCTWORK, CONTROLS, AND ALL ASSOCIATED

ACCESSORIES IN THE LOCATION SHOWN.

CONTRACTOR TO PATCH NEW ROOF PENETRATION

TO MATCH EXISTING, SEAL WATER TIGHT, AND

MAINTAIN ANY EXISTING ROOF WARRANTIES.

COORDINATE WITH THE STRUCTURAL DRAWINGS FOR

LOCATION OF THE NEW PENETRATION. INSTALL

LOCAL ON/OFF SWITCH FOR EXHAUST FAN IN

LOCATION SHOWN.

INSTALL NEW EXHAUST AIR DUCTWORK AND ALL

ASSOCIATED ACCESSORIES IN THE LOCATION

SHOWN.

ROUTE NEW EXHAUST DUCTWORK TO NEW SHOWER

ENCLOSURE. CONNECT THE EXHAUST DUCTWORK TO

SHOWER ENCLOSURE INTEGRATED EXHAUST AIR

GRILLE. EXHAUST CONNECTION LOCATION TO BE

COORDINATED WITH SHOWER ENCLOSURE

MANUFACTURER. CONTRACTOR BALANCE THE

EXHAUST RATE TO 150 CFM FOR EACH SHOWER.

COORDINATE WITH THE STRUCTURAL DRAWINGS FOR

LOCATION OF THE NEW PENETRATION.

INSTALL NEW RETURN GRILLE AT LOCATION SHOWN.

ALTER EXISTING RETURN AIR DUCTWORK AS

REQUIRED TO CONNECT TO NEW EXHAUST GRILLE .

BALANCE TO CFM SHOWN.

INSTALL NEW SUPPLY DIFFUSER AT LOCATION

SHOWN. ALTER EXISTING SUPPLY DUCTWORK AS

REQUIRED TO CONNECT TO NEW SUPPLY GRILLE.

BALANCE TO CFM SHOWN.

GENERAL HVAC NOTES

1. MODIFY THE EXISTING SPRINKLER PIPING PER NFPA

13 AS REQUIRED TO ACCOMMODATE NEW DUCTWORK,

DOMESTIC WATER PIPING, LIGHTING, AND CEILING.

2. CONTRACTOR TO COORDINATE NEW EXHAUST AIR

DUCT ROUTING TO ACCOMMODATE EXISTING

STRUCTURAL I-BEAM LOCATED IN THE CHASE SPACE

BEHIND SHOWERS.

3. ALL ROOF PENETRATIONS ARE TO BE SEALED WATER

TIGHT, MATCH EXISTING, AND MAINTAIN EXISTING

ROOF WARRANTIES. EXISTING ROOF WARRANTY BY

McGRATH ROOFING (PHONE #: 906-482-7107).

4. CONTRACTOR IS RESPONSIBLE FOR THE REMOVAL

AND PATCHING OF THE EXISTING HARD LID CEILING

AS REQUIRED TO COMPLETE THEIR WORK.

CONTRACTOR TO PATCH, PRIME, AND PAINT CEILING

AS REQUIRED PER THE ARCHITECTURAL DRAWINGS

TO MATCH EXISTING.

5. CONTRACTOR TO COORDINATE ALL DIFFUSER

LOCATIONS AND SIZES PRIOR TO NEW CEILING

INSTALLATION.

6. VERIFY LOCATION OF THE NEW DUCTWORK THAT WILL

EXIT STRAIGHT OUT THE BACK OF THE SHOWER

CABINET THROUGH THE EXISTING BLOCK WALL AND

WILL NOT COLLIDE WITH ANY EXISTING PIPES OR

CONDUIT. LOCATION OF THE EXHAUST PERFORATIONS

MAY VARY FROM SHOWER CABINET TO SHOWER

CABINET.

X-12x10 SA UP

X-10x10 RA UP X-12x12 SA UP X-8x6 RA UP

X-SA

SD-1 50

15x15 ---

RG-1 50

12x12 ---5

12x8 EA UP

8x6 EA TO SHOWER

EA GRILLE OPENING

(TYP. 2)

2 EG-1 50

12x12 TYP. 2

6x10 EA 2

6x6 EA2

CAP

6x6 EA

JC

/E

N G

B Y

IN

D

EX

PC

A

D R

AW

N

B Y

D

ES

IG

N

ED

B

Y

D E

P A

R T

M E

N T

O F

T E

C H

N O

L O

G Y

M

A N

A G

E M

E N

T A

N D

B U

D G

E T

S T

A T

E O

F M

IC

H

IG

A

N

A D

A M

P L

A C

H R

A N

C A

R B

D

IR

E

C T

O R

S T

A T

E F

A C

IL

IT

IE

S

A D

M

IN

IS

T

R A

T

IO

N

D E

S

IG

N A

N D

C O

N S

T R

U C

T

IO

N D

IV

IS

IO

N

PR

O

JE

C

T D

ES

C

R

IP

TI

O

N

PR

O

JE

C T

N O

2/

0.

JB

B

AR

C

H

IT

EC

TS

EN

G

IN

EE

R S

M A

T R

I X

SH

O

W

ER

R

EN

O

VA

TI

O

N S

AL

G

ER

C

O R

R

EC

TI

O

N

AL

F

AC

IL

IT

Y wing 'A' wing 'C'

LOWER LEVEL

wing 'B' wing 'D'

UPPER LEVEL

R ev ie w

D

AT

E

/1

4/

PL

AN

R

EV

IE

W S

ET

/2

1/

BI

D S

ET

JL

H

BR

H

M -4

SCALE: 1/4" = 1'-0"

0 1 5 10

SCALE: 1/4" = 1'-0"

0 1 5 10

SCALE: 1/4" = 1'-0"

0 1 5 10

SCALE: 1/4" = 1'-0"

0 1 5 10

FL

O

O R

P

LA

N

BU

IL

D

IN

G S

BI

R

C H

, M

AP

LE

(A

LT

PI

N E(

AL

T

1)

H

VA

C N

EW

FIRST FLOOR PLAN - BUILDINGS BIRCH & MAPLE -

AREA A - HVAC NEW

SECOND FLOOR PLAN - BUILDINGS BIRCH, MAPLE,

PINE - AREA B - HVAC NEW

SECOND FLOOR PLAN - BUILDINGS BIRCH, MAPLE, PINE -

AREA D - HVAC NEW

FIRST FLOOR PLAN - BUILDINGS BIRCH, MAPLE, PINE -

AREA C - HVAC NEW

N

BIRCH MAPLE

(ALT 1)

N

NN N N

N

BIRCH MAPLE PINE

(ALT 1) (ALT 1)

N N

N N N

N

PINE

(ALT 1)

SCALE: 1/4" = 1'-0"

0 1 5 10

FIRST FLOOR PLAN - BUILDING

PINE - AREA A - HVAC NEW

BIRCH MAPLE PINE

(ALT 1) (ALT 1)

PLUMBING ABBREVIATIONS

PLUMBING SYMBOLS LEGEND

PLUMBING PIPING PLUMBING EQUIPMENT

1. ALL PLUMBING WORK SHALL CONFORM TO MICHIGAN

PLUMBING CODE, LATEST APPLICABLE EDITION.

2. INSTALL ALL EQUIPMENT, MATERIALS, AND

ACCESSORIES PER MANUFACTURERS WRITTEN

INSTRUCTIONS.

3. INSTALL ISOLATION BALL VALVES @ ALL FIXTURE

WATER SUPPLY LINES.

4. CONTRACTOR TO VERIFY LOCATIONS OF EXISTING

UNDERGROUND UTILITIES BEFORE BEGINNING WORK.

5. CONTRACTOR SHALL DEMOLISH & REMOVE EXISTING

PIPING, FITTINGS, & EQUIPMENT AS REQUIRED FOR NEW

INSTALLATIONS. VALVE & CAP PIPING TO REMAIN.

6. FIELD VERIFY LOCATIONS OF EXISTING PIPING THAT

MAY CONFLICT WITH NEW CONSTRUCTION AND

RELOCATE AS NEEDED.

7. NOTIFY OWNER OF ANY PIPING DEMOLITION THAT MAY

AFFECT NORMAL OPERATION OF OTHER AREAS.

8. ALL FLOOR DRAINS TO BE EQUIPPED WITH TRAP

PRIMERS OR APPROVED TRAP SEALS.

9. 1% SLOPE FOR ALL SANITARY PIPING.

10. THE CONTRACTOR SHALL FIELD VERIFY THE SIZES,

LOCATION, ELEVATIONS, AND DETAILS OF ALL EXISTING

CONDITIONS THAT MAY AFFECT THE WORK.

11. THE CONTRACTOR SHALL BE RESPONSIBLE FOR

MAINTAINING THE INTEGRITY OF ALL EQUIPMENT AND

MATERIALS IN A "NEW" CONDITION DURING

CONSTRUCTION.

12. ALL WORK SHALL BE PERFORMED BY LICENSED

CONTRACTORS AND SUBCONTRACTORS AS REQUIRED

BY LAW.

13. DESIGN AND CONSTRUCTION SHALL BE IN

ACCORDANCE WITH THE CODES AND REGULATIONS

ENFORCED BY LOCAL BUILDING OFFICIALS.

14. IF THERE IS CONFLICTING INFORMATION IN THE PLANS

OR SPECIFICATIONS THE MORE STRINGENT AND

GREATER COST ITEM SHALL BE USED.

15. DRAWINGS INDICATE REQUIRED SIZES AND POINTS OF

TERMINATION OF PIPES AND SUGGESTED ROUTES. IT IS

NOT INTENTION OF DRAWINGS TO INDICATE ALL

NECESSARY OFFSETS. INSTALL WORK IN MANNER TO

CONFORM TO STRUCTURE, AVOID OBSTRUCTIONS,

PRESERVE HEADROOM AND KEEP OPENINGS AND

PASSAGEWAYS CLEAR. DO NOT SCALE FROM

DRAWINGS.

16. ALL AREAS OF WORK MUST BE SECURED AND

INACCESSIBLE TO INMATES DURING CONSTRUCTION.

THE CONTRACTOR MUST SECURE EACH AREA OF WORK

AT THE END OF EACH SHIFT.

17. SHOWER SUPPLIER SHALL FIELD VERIFY THE EXISTING

HEIGHT, WIDTH, AND DEPTH FOR EACH SHOWER

CABINET LOCATION PRIOR TO SUBMITTING SHOP

DRAWINGS

GENERAL PLUMBING NOTES

MISCELLANEOUS NOTES

PLUMBING VALVES

POINT OF CONNECTION BETWEEN NEW AND

EXISTING

POINT OF EXISTING TO REMAIN AND EXISTING

TO BE REMOVED

INDICATES PLAN NOTE

INDICATES DEMOLITION NOTE

DETAIL BUBBLE

DETAIL NUMBER

PAGE LOCATION INDICATES

DIRECTION OF DETAIL SECTION

AD AREA DRAIN

ASR AUTOMATIC SPRINKLER RISER

BFS BELOW FLOOR SLAB

BWV BACK WATER VALVE

CB CATCH BASIN

CI CAST IRON

CO CLEAN OUT

CV CONTROL VALVE

DF DRINKING FOUNTAIN

DIA DIAMETER

DN DOWN

DWH DOMESTIC WATER HEATER

E.T.C. ELECTRICAL TRADES CONTRACTOR

EWC ELECTRIC WATER COOLER

EXIST EXISTING

FD FLOOR DRAIN

FC FINAL CONNECTIONS

FDC FIRE DEPT. CONNECTION

FF FINISH FLOOR

FHV FIRE HOSE VALVE

FT FEET

GAL GALLON

GD GARBAGE DISPOSAL

GI GREASE INTERCEPTOR

GPH GALLONS PER HOUR

GPM GALLONS PER MINUTE

HB HOSE BIB

HD HEAD (FT)

HP HORSE POWER

ID INSIDE DIAMETER

I.E. INVERT ELEVATION

LAV LAVATORY

LT LAUNDRY TRAY

MA MEDICAL AIR

MAX MAXIMUM

MGC MEDICAL GAS CONSOLE

MH MAN HOLE

MIN MINIMUM

MS MOP SINK

M.T.C. MECHANICAL TRADES CONTRACTOR

NTS NOT TO SCALE

ORD OVERFLOW ROOF DRAIN

OXY OXYGEN

P PUMP

PD PRESSURE DROP

PVC POLY-VINYL-CHLORIDE

RC RAIN CONDUCTOR

RD ROOF DRAIN

RI ROUGH-IN

REQ'D REQUIRED

SAN SANITARY

SHWR SHOWER

SK SINK

SP STAND PIPE

SQ. FT. SQUARE FEET

SS SERVICE SINK

ST STORM

S&W STOP & WASTE

STR STRAINER

SV STACKED VENT

TYP. TYPICAL

UR URINAL

VB VACUUM BREAKER

VS VENT STACK

V.F.D VARIABLE FREQUENCY DRIVE

VTR VENT THRU ROOF

W WASTE

WB WET BULB

WC WATER CLOSET

WH WALL HYDRANT

WS WASTE STACK

W&V WASTE AND VENT

X-CW EXIST. CW PIPING

ITEM

EXISTING

COLD WATER

COLD WATER BELOW FINISH SLAB

TEMPERED WATER

SANITARY WASTE

SANITARY WASTE BELOW FINISH SLAB

VENT PIPING

VENT PIPING BELOW FINISH SLAB

DEMOLITION

GATE VALVE

SOLENOID VALVE

FLOW DIRECTION

PIPING DROP

PIPING RISE

FLOOR CLEANOUT

INLINE PIPING DROP

INLINE PIPING RISE

PIPING TEE

PIPING ELBOW

INLINE CLEANOUT

PLUMBING TRAP

CONNECTION

FLOOR DRAIN & FLOOR SINK

PIPE CAP

PIPE BREAK

X

X

XX

XXXX

XX

XXXX

CW

CW

TW

SAN

SAN

V

V

PHASING NOTES

GENERAL INFORMATION:

A. EXISTING WATER SERVICE SHALL REMAIN ACTIVE AND

FUNCTIONAL DURING CONSTRUCTION. INDIVIDUAL RISERS CAN

BE SHUTDOWN AS NEEDED, COORDINATE WITH OWNER PRIOR

TO BRANCH SHUTDOWNS.

B. PHASING NOTES ARE INTENDED FOR GENERAL SEQUENCE OF

CONSTRUCTION. CONTRACTOR TO COORDINATE WITH

DRAWINGS FOR SPECIFIC DETAILS FOR DEMOLITION &

INSTALLATION OF ALL NEW EQUIPMENT, PIPING, AND

ACCESSORIES.

C. ALL RISER SHUTDOWNS TO BE CLOSELY COORDINATED WITH

THE OWNER.

D. ONLY ONE SET OF SHOWERS PER HOUSING UNIT SHALL BE

UPGRADED AT A TIME. SIX SHOWERS TO REMAIN IN SERVICE

AT ALL TIMES.

E. THE OWNER WILL PROVIDE A MAXIMUM OF 2 ESCORTS WITH

THE ANTICIPATION THAT WORK IN TWO DIFFERENT HOUSING

UNITS WILL BE HAPPENING SIMULTANEOUSLY.

F. FOR ALL HOUSING UNITS ON THIS PROJECT ONLY ONE

SET/PAIR OF SHOWERS CAN BE SHUT DOWN AND WORKED

ON AT ANY ONE TIME PER HOUSING UNIT, EXCEPT FOR

BIRCH. THE REMAINING THREE SETS/PAIRS OF SHOWERS

ARE TO BE FULLY OPERATIONAL. THE REPLACED SHOWERS

MUST BE FULLY INSPECTED, APPROVED, AND MADE

OPERABLE, BEFORE THE CONTRACTOR CAN MOVE TO THE

NEXT SET/PAIR OF SHOWERS TO BEGIN WORK.

G. CONTRACTOR TO BEGIN CONSTRUCTION IN HOUSING UNIT

BIRCH AS THE HOUSING UNIT IS CURRENTLY UNOCCUPIED.

G.A. HOUSING UNIT BIRCH IS UNOCCUPIED AT THE TIME OF

CONSTRUCTION, THE CONTRACTOR WILL HAVE

ACCESS AND THE ABILITY TO REPLACE ALL THE

SHOWERS AT ONE TIME.

X-ICON CONTROLLER

X-WOOD MOUNT

X-SOLENOID

VALVE (TYP.4)

X-1/2" TW

X-3/4" TW

X-3/4" TW

X-1/2" TW TO FIRST

FLOOR X-SHOWER

X-1/2" TW TO FIRST

FLOOR X-SHOWER

X-1/2" TW

X-1/2" TW UP TO

SECOND FLOOR

X-SHOWER

DEMOLISH EXISTING CONTROL

WIRING BACK TO ASSOCIATED

SHOWER BUTTON (TYP.4)

ICON CONTROLLER

X-WOOD MOUNT

SOLENOID

VALVE (TYP.4)

X-1/2" TW

X-3/4" TW

X-1/2" TW UP TO

SECOND FLOOR

X-SHOWER

X-3/4" TW

X-1/2" TW TO FIRST

FLOOR X-SHOWER

X-1/2" TW TO FIRST

FLOOR X-SHOWER

X-1/2" TW

EXTEND I-CON CONTROL

WIRING TO ASSOCIATED

SHOWER BUTTON (TYP.4)

SCALE: NTS

I-CON CONTROLLER SYSTEM PIPING

DETAIL - BUILDINGS ASPEN, BIRCH,

CEDAR, MAPLE, PINE - NEW

SCALE: NTS

SOLENOID

VALVE (TYP.4)

1/2" TW TO FIRST

FLOOR SHOWER

1/2" TW TO SECOND

FLOOR SHOWER

1ST FLOOR

CEILING

CEILING

2ND FLOOR

I-CON CONTROLLER

(REFER TO SHEET P-400

& P-401 FOR LOCATIONS)

X-1" TW

X-1" TW

1" TW

1" TW

2ND FLR

MECHANICAL RM.

1ST FLR

MECHANICAL RM.

EXTEND I-CON CONTROL

WIRING TO ASSOCIATED

SHOWER BUTTON (TYP.4)

I-CON CONTROLLER SYSTEM

PIPING DETAIL - SPRUCE - NEW

SCALE: NTS

I-CON CONTROLLER SYSTEM PIPING

DETAIL - BUILDINGS ASPEN, BIRCH,

CEDAR, MAPLE, PINE - DEMOLITION

JC

/E

N G

B Y

IN

D

EX

PC

A

D R

AW

N

B Y

D

ES

IG

N

ED

B

Y

D E

P A

R T

M E

N T

O F

T E

C H

N O

L O

G Y

M

A N

A G

E M

E N

T A

N D

B U

D G

E T

S T

A T

E O

F M

IC

H

IG

A

N

A D

A M

P L

A C

H R

A N

C A

R B

D

IR

E

C T

O R

S T

A T

E F

A C

IL

IT

IE

S

A D

M

IN

IS

T

R A

T

IO

N

D E

S

IG

N A

N D

C O

N S

T R

U C

T

IO

N D

IV

IS

IO

N

PR

O

JE

C

T D

ES

C

R

IP

TI

O

N

PR

O

JE

C T

N O

2/

0.

JB

B

AR

C

H

IT

EC

TS

EN

G

IN

EE

R S

M A

T R

I X

SH

O

W

ER

R

EN

O

VA

TI

O

N S

AL

G

ER

C

O R

R

EC

TI

O

N

AL

F

AC

IL

IT

Y R ev ie w D

AT

E

/1

4/

PL

AN

R

EV

IE

W S

ET

/2

1/

BI

D S

ET

JL

H

PL

U

M

BI

N G

SY

M

BO

LS

AB

BR

EV

IA

TI

O

N S

N

O

TE

S

BR

H

P-

X-FD

X-1" TW UP AND DN

X-1" CW UP AND DN

X-4" SAN

UP AND DN

X-FD X-FD

X-1" TW

X-1/2" TW X-1/2" TW

1 1

X-FD

X-FD X-FD

X-1" TW UP AND DN

X-2" V UP

X-4" SAN

UP AND DN

X-2" CW UP

X-1" CW UP AND DN

X-1" TW

X-1" TW UP AND DN

X-1" CW UP AND DN

X-4" SAN DN

X-3" VTR

X-MS

X-FDX-FD 1

X-3/4" TW

X-1/2" TW

X-FDX-FD

X-MS

X-1" TW UP AND DN

X-1" CW UP AND DN

X-4" SAN UP

AND DN

X-2" V

X-3/4" TW

2 2

DEMOLITION NOTES

DISCONNECT, REMOVE, AND DEMO EXISTING FLOOR DRAIN. DEMO ASSOCIATED

SANITARY PIPING BACK AS REQUIRED TO CONNECT TO NEW SHOWER DRAIN.

DISCONNECT, REMOVE, AND DEMO EXISTING SHOWER HEAD AND TEMPERED

WATER CONTROLS. DEMO TEMPERED WATER PIPING BACK TO LOCATION SHOWN.

DEMO TEMPERED WATER SUPPLY PIPING BACK TO LOCATION SHOWN.

JC

/E

N G

B Y

IN

D

EX

PC

A

D R

AW

N

B Y

D

ES

IG

N

ED

B

Y

D E

P A

R T

M E

N T

O F

T E

C H

N O

L O

G Y

M

A N

A G

E M

E N

T A

N D

B U

D G

E T

S T

A T

E O

F M

IC

H

IG

A

N

A D

A M

P L

A C

H R

A N

C A

R B

D

IR

E

C T

O R

S T

A T

E F

A C

IL

IT

IE

S

A D

M

IN

IS

T

R A

T

IO

N

D E

S

IG

N A

N D

C O

N S

T R

U C

T

IO

N D

IV

IS

IO

N

PR

O

JE

C

T D

ES

C

R

IP

TI

O

N

PR

O

JE

C T

N O

2/

0.

JB

B

AR

C

H

IT

EC

TS

EN

G

IN

EE

R S

M A

T R

I X

SH

O

W

ER

R

EN

O

VA

TI

O

N S

AL

G

ER

C

O R

R

EC

TI

O

N

AL

F

AC

IL

IT

Y wing 'A' wing 'C'

LOWER LEVEL

wing 'B' wing 'D'

UPPER LEVEL

R ev ie w

D

AT

E

/1

4/

PL

AN

R

EV

IE

W S

ET

/2

1/

BI

D S

ET

P-

SCALE: 1/4" = 1'-0"

0 1 5 10

SCALE: 1/4" = 1'-0"

0 1 5 10

SCALE: 1/4" = 1'-0"

0 1 5 10

SCALE: 1/4" = 1'-0"

0 1 5 10

N

FIRST FLOOR PLAN - BUILDING SPRUCE -

AREA A - PLUMBING DEMOLITION N

SECOND FLOOR PLAN - BUILDING SPRUCE -

AREA B - PLUMBING DEMOLITION

N

FIRST FLOOR PLAN - BUILDING SPRUCE -

AREA C - PLUMBING DEMOLITION N

SECOND FLOOR PLAN - BUILDING SPRUCE -

AREA D - PLUMBING DEMOLITION

FL

O

O R

P

LA

N

BU

IL

D

IN

G

SP

R U

C E

- P

LU

M

BI

N G

D

EM

O

LI

TI

O

N

JL

H

BR

H

X-3/4" TW

X-1/2" TW

X-1/2" TW UP

X-FDX-FD

X-FD

X-FD

X-3" SAN UP

AND DOWN

X-3" V UP

AND DN

X-1/2" TW

P100X-I-CON SYSTEM

CONTROLLER

X-1/2" TW DN

X-3" SAN STACK

UP AND DOWN

X-3" V DN

X-FDX-FD

X-FD

X-FD

X-FD

X-FD

X-FD

X-3" SAN STACK

UP AND DOWN

X-3" V DN

X-1/2" TW DNX-1/2" TW UP

X-FD

X-FD

X-FD

X-3/4" TW DN

X-FD

X-3" SAN STACK

UP AND DOWN

X-3" V DN

X-1/2" TW

X-1/2" TW

P100

X-I-CON SYSTEM

CONTROLLER

DEMOLITION NOTES

DISCONNECT, REMOVE, AND DEMO EXISTING FLOOR DRAIN. DEMO ASSOCIATED

SANITARY PIPING BACK AS REQUIRED TO CONNECT TO NEW SHOWER DRAIN.

DISCONNECT, REMOVE, AND DEMO EXISTING SHOWER HEAD, I-CON SYSTEM

CONTROL BUTTON, SOLENOID VALVES, AND ASSOCIATED I-CON SYSTEM

CONTROLLER. DEMO EXISTING TEMPERED WATER SUPPLY PIPING BACK AS

REQUIRED FOR NEW SHOWER HEAD AND I-CON SYSTEM CONTROL BUTTON.

DISCONNECT, REMOVE, AND DEMO EXISTING FLOOR DRAIN. DEMO EXISTING

SANITARY PIPING BACK AS REQUIRED FOR NEW FLOOR DRAIN.

DISCONNECT, REMOVE, AND DEMO EXISTING MOP SINK AND ASSOCIATED FAUCET.

DEMO BACK EXISTING TEMPERED WATER AND SANITARY PIPING AS REQUIRED TO

EXTEND AND CONNECT TO NEW MOP SINK AT LOCATION SHOWN ON SHEET P-401

PINE-A. SALVAGE AND RELOCATE EXISTING MOP RACK TO NEW MOP SINK

LOCATION.

X-3/4" TW

X-1/2" TW

X-1/2" TW UP

X-FDX-FD

X-FD

X-FD

X-3" SAN UP

AND DOWN

X-3" V UP

AND DN

X-1/2" TW

P100X-I-CON SYSTEM

CONTROLLER

X-MS

X-3/4" TW DN

X-TW X-CW UP

AND DN

JC

/E

N G

B Y

IN

D

EX

PC

A

D R

AW

N

B Y

D

ES

IG

N

ED

B

Y

D E

P A

R T

M E

N T

O F

T E

C H

N O

L O

G Y

M

A N

A G

E M

E N

T A

N D

B U

D G

E T

S T

A T

E O

F M

IC

H

IG

A

N

A D

A M

P L

A C

H R

A N

C A

R B

D

IR

E

C T

O R

S T

A T

E F

A C

IL

IT

IE

S

A D

M

IN

IS

T

R A

T

IO

N

D E

S

IG

N A

N D

C O

N S

T R

U C

T

IO

N D

IV

IS

IO

N

PR

O

JE

C

T D

ES

C

R

IP

TI

O

N

PR

O

JE

C T

N O

2/

0.

JB

B

AR

C

H

IT

EC

TS

EN

G

IN

EE

R S

M A

T R

I X

SH

O

W

ER

R

EN

O

VA

TI

O

N S

AL

G

ER

C

O R

R

EC

TI

O

N

AL

F

AC

IL

IT

Y wing 'A' wing 'C'

LOWER LEVEL

wing 'B' wing 'D'

UPPER LEVEL

R ev ie w

D

AT

E

/1

4/

PL

AN

R

EV

IE

W S

ET

/2

1/

BI

D S

ET

P-

SCALE: 1/4" = 1'-0"

0 1 5 10

SCALE: 1/4" = 1'-0"

0 1 5 10

SCALE: 1/4" = 1'-0"

0 1 5 10

SCALE: 1/4" = 1'-0"

0 1 5 10

JL

H

BR

H

FL

O

O R

P

LA

N

BU

IL

D

IN

G S

BI

R

C H

, M

AP

LE

(A

LT

PI

N E(

AL

T

1)

PL

U

M

BI

N G

D

EM

O

LI

TI

O

N

FIRST FLOOR PLAN - BUILDINGS BIRCH, MAPLE, PINE -

AREA C - PLUMBING DEMOLITION

SECOND FLOOR PLAN - BUILDINGS BIRCH, MAPLE, PINE -

AREA D - PLUMBING DEMOLITION

SECOND FLOOR PLAN - BUILDINGS BIRCH, MAPLE, PINE -

AREA B - PLUMBING DEMOLITION

FIRST FLOOR PLAN - BUILDINGS BIRCH & MAPLE - AREA A -

PLUMBING DEMOLITION

N N

N N N

N N N

NN N N

SCALE: 1/4" = 1'-0"

0 1 5 10

FIRST FLOOR PLAN - BUILDING PINE -

AREA A - PLUMBING DEMOLITION

N

BIRCH MAPLE

(ALT 1)

BIRCH MAPLE PINE

(ALT 1) (ALT 1)

PINE

(ALT 1)

BIRCH MAPLE PINE

(ALT 1) (ALT 1)

X-FD

X-1" TW UP AND DN

X-1" CW UP AND DN

X-4" SAN

UP AND DN

1/2" TW

1" TW

P100

SHOWERSHOWER

X-FD

X-1" TW UP AND DN

X-2" V UP

X-4" SAN

UP AND DN

X-2" CW UP

X-1" CW UP AND DN

1/2" TW

1" TW

P100

SHOWER SHOWER

X-1" TW UP AND DN

X-1" CW UP AND DN

X-4" SAN DN

X-3" VTR

X-MS

1" TW

P100

SHOWER

X-MS

X-1" TW UP AND DN

X-1" CW UP AND DN

X-4" SAN UP

AND DN

X-2" V

1" TW

P100

SHOWER

1/2" TW

1/2" TW4

PLUMBING KEY NOTES

MODIFY EXISTING SHOWER SANITARY PIPING AS REQUIRED TO CONNECT TO NEW

SHOWER DRAIN. CONTRACTOR TO COORDINATE EXISTING DRAIN LOCATION WITH

MANUFACTURER PRIOR TO ORDERING.

ROUTE NEW 1/2" TEMPERED WATER PIPING AS SHOWN TO CONNECT TO NEW

SHOWER HEAD/CONTROLS PER THE MANUFACTURERS INSTALLATION

INSTRUCTIONS.

INSTALL NEW I-CON SYSTEM CONTROLLER (NEXUS X12 4, 4 SHOWER CONTROLLER,

STANDALONE) AND ASSOCIATED SOLENOID VALVES IN LOCATION SHOWN.

ROUTE NEW 1/2" TEMPERED WATER PIPING AS SHOWN TO CONNECT TO EXISTING

TEMPERED WATER PIPING.

GENERAL NOTES

1. REFER TO ARCHITECTURAL PLANS FOR SHOWER SPECIFICATIONS.

2. CONTRACTOR TO PURCHASE SHOWER ENCLOSURES, SOLENOID VALVES,

CONTROLLERS, SHOWER BUTTONS, AND SHOWER HEADS FROM I-CON.

3. MODIFY THE EXISTING SPRINKLER PIPING PER NFPA 13 AS REQUIRED TO

ACCOMMODATE NEW DUCTWORK, DOMESTIC WATER PIPING, LIGHTING, AND

CEILING.

4. VERIFY EXISTING DRAIN LOCATIONS TO ENSURE THEY WILL ALIGN WITH THE

FLOOR DRAINS IN THE NEW SHOWER CABINETS.

5. EXISTING MASTER MIXING VALVE IN MECHANICAL ROOM IS A SYMMONS 7

7000 TEMPCONTROL (ASSE 1017 & CSA B125.3-12 RATED).

JC

/E

N G

B Y

IN

D

EX

PC

A

D R

AW

N

B Y

D

ES

IG

N

ED

B

Y

D E

P A

R T

M E

N T

O F

T E

C H

N O

L O

G Y

M

A N

A G

E M

E N

T A

N D

B U

D G

E T

S T

A T

E O

F M

IC

H

IG

A

N

A D

A M

P L

A C

H R

A N

C A

R B

D

IR

E

C T

O R

S T

A T

E F

A C

IL

IT

IE

S

A D

M

IN

IS

T

R A

T

IO

N

D E

S

IG

N A

N D

C O

N S

T R

U C

T

IO

N D

IV

IS

IO

N

PR

O

JE

C

T D

ES

C

R

IP

TI

O

N

PR

O

JE

C T

N O

2/

0.

JB

B

AR

C

H

IT

EC

TS

EN

G

IN

EE

R S

M A

T R

I X

SH

O

W

ER

R

EN

O

VA

TI

O

N S

AL

G

ER

C

O R

R

EC

TI

O

N

AL

F

AC

IL

IT

Y wing 'A' wing 'C'

LOWER LEVEL

wing 'B' wing 'D'

UPPER LEVEL

R ev ie w

D

AT

E

/1

4/

PL

AN

R

EV

IE

W S

ET

/2

1/

BI

D S

ET

P-

FL

O

O R

P

LA

N

BU

IL

D

IN

G

SP

R U

C E

- P

LU

M

BI

N G

N

EW

JL

H

BR

H

N

FIRST FLOOR PLAN - BUILDING SPRUCE -

AREA A - PLUMBING NEW

SCALE: 1/4" = 1'-0"

0 1 5 10

SCALE: 1/4" = 1'-0"

0 1 5 10

SCALE: 1/4" = 1'-0"

0 1 5 10

SCALE: 1/4" = 1'-0"

0 1 5 10

N

SECOND FLOOR PLAN - BUILDING

SPRUCE - AREA B - PLUMBING NEW

N

FIRST FLOOR PLAN - BUILDING SPRUCE -

AREA C - PLUMBING NEW N

SECOND FLOOR PLAN - BUILDING

SPRUCE - AREA D - PLUMBING NEW

X-3/4" TW

X-1/2" TW

X-1/2" TW UP

X-FD

X-3" SAN UP

AND DOWN

X-3" V UP

AND DN

X-1/2" TW

FD-1

SHOWER

P100

X-1/2" TW DN

X-3" SAN STACK

UP AND DOWN

X-3" V DN

X-FD

1 1

FD-1

SHOWER

X-3" SAN STACK

UP AND DOWN

X-3" V DN

X-1/2" TW DN

FD-1

SHOWER

X-1/2" TW UPX-3/4" TW DN

X-FD

X-3" SAN STACK

UP AND DOWN

X-3" V DN

X-1/2" TW

X-1/2" TW

FD-1

SHOWER

P100

PLUMBING KEY NOTES

MODIFY EXISTING SHOWER SANITARY PIPING AS REQUIRED TO CONNECT TO NEW

SHOWER DRAIN. CONTRACTOR TO COORDINATE EXISTING DRAIN LOCATION WITH

MANUFACTURER PRIOR TO ORDERING.

MODIFY EXISTING TEMPERED WATER PIPING AS REQUIRED TO CONNECT TO NEW

SHOWER HEAD.

INSTALL NEW I-CON SYSTEM CONTROLLER (NEXUS X12 4, 4 SHOWER CONTROLLER,

STANDALONE) IN LOCATION SHOWN.

MODIFY EXISTING SANITARY PIPING AS REQUIRED TO INSTALL NEW FLOOR DRAIN

FLUSH WITH NEW FLOORING AT LOCATION SHOWN.

ROUTE NEW 1/2" TEMPERED WATER PIPING AS SHOWN TO CONNECT TO NEW

SHOWER HEAD/CONTROLS PER THE MANUFACTURERS INSTALLATION

INSTRUCTIONS.

INSTALL NEW MOP SINK AND SALVAGED MOP RACK AT LOCATION SHOWN.

CONNECT NEW FAUCET TO 1/2" TEMPERED WATER AND 1/2" COLD WATER.

EXTEND AND CONNECT 1/2" COLD WATER TO EXISTING COLD WATER PIPE IN

MECHANICAL CLOSET ROOM.

GENERAL NOTES

1. REFER TO ARCHITECTURAL PLANS FOR SHOWER SPECIFICATIONS.

2. CONTRACTOR TO PURCHASE SHOWER ENCLOSURES, SOLENOID VALVES,

CONTROLLERS, SHOWER BUTTONS, AND SHOWER HEADS FROM I-CON.

3. MODIFY THE EXISTING SPRINKLER PIPING PER NFPA 13 AS REQUIRED TO

ACCOMMODATE NEW DUCTWORK, DOMESTIC WATER PIPING, LIGHTING, AND

CEILING.

4. VERIFY EXISTING DRAIN LOCATIONS TO ENSURE THEY WILL ALIGN WITH THE

FLOOR DRAINS IN THE NEW SHOWER CABINETS.

5. EXISTING MASTER MIXING VALVE IN MECHANICAL ROOM IS A SYMMONS 7

7000 TEMPCONTROL (ASSE 1017 & CSA B125.3-12 RATED).

X-3/4" TW

X-1/2" TW

X-1/2" TW UP

X-FD

X-3" SAN UP

AND DOWN

X-3" V UP

AND DN

X-TW X-CW UP

AND DN

FD-1

SHOWER

P100

1/2" TW

MS-1 6

1/2" TW

1/2" CW

JC

/E

N G

B Y

IN

D

EX

PC

A

D R

AW

N

B Y

D

ES

IG

N

ED

B

Y

D E

P A

R T

M E

N T

O F

T E

C H

N O

L O

G Y

M

A N

A G

E M

E N

T A

N D

B U

D G

E T

S T

A T

E O

F M

IC

H

IG

A

N

A D

A M

P L

A C

H R

A N

C A

R B

D

IR

E

C T

O R

S T

A T

E F

A C

IL

IT

IE

S

A D

M

IN

IS

T

R A

T

IO

N

D E

S

IG

N A

N D

C O

N S

T R

U C

T

IO

N D

IV

IS

IO

N

PR

O

JE

C

T D

ES

C

R

IP

TI

O

N

PR

O

JE

C T

N O

2/

0.

JB

B

AR

C

H

IT

EC

TS

EN

G

IN

EE

R S

M A

T R

I X

SH

O

W

ER

R

EN

O

VA

TI

O

N S

AL

G

ER

C

O R

R

EC

TI

O

N

AL

F

AC

IL

IT

Y wing 'A' wing 'C'

LOWER LEVEL

wing 'B' wing 'D'

UPPER LEVEL

R ev ie w

D

AT

E

/1

4/

PL

AN

R

EV

IE

W S

ET

/2

1/

BI

D S

ET

P-

SCALE: 1/4" = 1'-0"

0 1 5 10

SCALE: 1/4" = 1'-0"

0 1 5 10

SCALE: 1/4" = 1'-0"

0 1 5 10

SCALE: 1/4" = 1'-0"

0 1 5 10

JL

H

BR

H

FL

O

O R

P

LA

N

BU

IL

D

IN

G S

BI

R

C H

, M

AP

LE

(A

LT

PI

N E(

AL

T

1)

PL

U

M

BI

N G

N

EW

SECOND FLOOR PLAN - BUILDINGS BIRCH, MAPLE,

PINE - AREA B - PLUMBING NEW

FIRST FLOOR PLAN - BUILDINGS BIRCH & MAPLE - AREA A -

PLUMBING NEW

FIRST FLOOR PLAN - BUILDINGS BIRCH, MAPLE, PINE -

AREA C - PLUMBING NEW

SECOND FLOOR PLAN - BUILDINGS BIRCH, MAPLE, PINE -

AREA D - PLUMBING NEW

N N

N N N

N N N

N N N

FIRST FLOOR PLAN - BUILDING

PINE - AREA A - PLUMBING NEW

SCALE: 1/4" = 1'-0"

0 1 5 10

BIRCH MAPLE

(ALT 1)

BIRCH MAPLE PINE

(ALT 1) (ALT 1)

PINE

(ALT 1)

BIRCH MAPLE PINE

(ALT 1) (ALT 1)

NEW 12" x 12" OPENING

IN ROOF. REFER TO DETAIL

5/D-200. 8" x 12" OPENING

FOR EXHAUST DUCT WORK

TO FIRST FLOOR.

NEW 12" x 12" OPENING

IN ROOF.REFER TO DETAIL

5/D-200. 8" x 12" OPENING

FOR EXHAUST DUCT WORK

TO FIRST FLOOR.

NEW 8" x 12" OPENING

IN FLOOR ABOVE. REFER

TO DETAIL 5/D-200NEW 8" x 12" OPENING

IN FLOOR ABOVE. REFER

TO DETAIL 5/D-200

D-100

SECOND FLOOR PLAN - BUILDINGS ASPEN, BIRCH,

CEDAR, MAPLE, PINE - AREA B - DEMO PLAN 4

D-100

SECOND FLOOR PLAN - BUILDINGS ASPEN, BIRCH,

CEDAR, MAPLE, PINE - AREA D - DEMO PLAN

D-100

FIRST FLOOR PLAN - BUILDINGS ASPEN, BIRCH,

CEDAR, MAPLE, PINE - AREA A - DEMO PLAN 3

D-100

FIRST FLOOR PLAN - BUILDINGS ASPEN, BIRCH,

CEDAR, MAPLE, PINE - AREA C - DEMO PLAN

JC

/E

N G

B Y

IN

D

EX

PC

A

D R

AW

N

B Y

D

ES

IG

N

ED

B

Y

D E

P A

R T

M E

N T

O F

T E

C H

N O

L O

G Y

M

A N

A G

E M

E N

T A

N D

B U

D G

E T

S T

A T

E O

F M

IC

H

IG

A

N

A D

A M

P L

A C

H R

A N

C A

R B

D

IR

E

C T

O R

S T

A T

E F

A C

IL

IT

IE

S

A D

M

IN

IS

T

R A

T

IO

N

D E

S

IG

N A

N D

C O

N S

T R

U C

T

IO

N D

IV

IS

IO

N

PR

O

JE

C

T D

ES

C

R

IP

TI

O

N

PR

O

JE

C T

N O

EN

G

IN

EE

R S

R ev ie w

D

AT

E

SH

O W

ER

R

EN

O

VA

TI

O N

S

AL

G

ER

C O

R R

EC

TI

O N

AL

F

AC

IL

IT

Y

/2

1/

BI

D S

ET

D-100

M A

T R

I X

FA

X:

(5

) 4

-2

PH

O N

E:

(5

) 4

-2

LA

N

SI

N

G , M

I 4

E

. C

ES

AR

C

H

AV

EZ

A

VE

ad m in is tra to r@ m at rix ce in c.

co m M at rix

P ro je ct

N o.

.0

N

WC

H wing 'A' wing 'C'

LOWER LEVEL

wing 'B' wing 'D'

UPPER LEVEL

D-200

SECOND FLOOR PLAN - BUILDING SPRUCE -

AREA 'B' - HVAC NEW

D-200

FIRST FLOOR PLAN - BUILDING SPRUCE -

AREA 'C' - HVAC NEW

D-200

FIRST FLOOR PLAN - BUILDING SPRUCE -

AREA 'A' - HVAC NEW

D-200

SECOND FLOOR PLAN - BUILDING SPRUCE -

AREA 'D' - HVAC NEW

NEW 10" x 10" OPENING

IN FLOOR ABOVE. REFER

TO DETAIL 5/D-200

NEW 12" x 12" OPENING

IN ROOF. REFER TO DETAIL

5/D-200

NEW 8" x 12" OPENING

IN FLOOR. REFER TO DETAIL

5/D-200

NEW 8" x 12" OPENING

IN FLOOR ABOVE. REFER

TO DETAIL 5/D-200

NEW 10" x 10" OPENING

IN FLOOR. REFER TO DETAIL

5/D-200

NEW 12" x 12" OPENING

IN ROOF. REFER TO DETAIL

5/D-200

ERECTOR NOTE:

DO NOT OVER CUT CORNERS. EXACT LOCATION OF

OPENINGS IS FLEXIBLE. LOCATE IN OPEN CELLS OF

PRECAST PLANK TO MINIMIZE THE AMOUNT OF REBAR

AND WEB MATERIAL TO BE CUT. DRILL SMALL DIAMETER

PILOT HOLE IN EXISTING CONCRETE TO FIND OPEN CELL

LOCATIONS.

D-200

SECTION

CORRECT

INCORRECT

NEW OPEING

NEW OPEING

JC

/E

N G

B Y

IN

D

EX

PC

A

D R

AW

N

B Y

D

ES

IG

N

ED

B

Y

D E

P A

R T

M E

N T

O F

T E

C H

N O

L O

G Y

M

A N

A G

E M

E N

T A

N D

B U

D G

E T

S T

A T

E O

F M

IC

H

IG

A

N

A D

A M

P L

A C

H R

A N

C A

R B

D

IR

E

C T

O R

S T

A T

E F

A C

IL

IT

IE

S

A D

M

IN

IS

T

R A

T

IO

N

D E

S

IG

N A

N D

C O

N S

T R

U C

T

IO

N D

IV

IS

IO

N

PR

O

JE

C

T D

ES

C

R

IP

TI

O

N

PR

O

JE

C T

N O

EN

G

IN

EE

R S

R ev ie w

D

AT

E

SH

O W

ER

R

EN

O

VA

TI

O N

S

AL

G

ER

C O

R R

EC

TI

O N

AL

F

AC

IL

IT

Y

/2

1/

BI

D S

ET

D-200

M at rix P ro je ct N o.

.0

FA

X:

(5

) 4

-2

PH

O N

E:

(5

) 4

-2

LA

N

SI

N

G , M

I 4

E

. C

ES

AR

C

H

AV

EZ

A

VE

ad m in is tra to r@ m at rix ce in c.

co m

M A

T R

I X

N

WC

H wing 'A' wing 'C'

LOWER LEVEL

wing 'B' wing 'D'

UPPER LEVEL

Sheets and Views
Alger Shower_CDs-Legend G001
Alger Shower_CDs-Schedule G002
Alger Shower_CDs-Spruce Demo 101
Alger Shower_CDs-Cedar Demo 102
Alger Shower_CDs-Spruce Floor 103
Alger Shower_CDs-Cedar Floor 104
Alger Shower_CDs-Pine A - 105
Alger Shower_CDs-Spruce RCP 106
Alger Shower_CDs-Cedar RCP 107
Alger Shower_CDs-Pine A RCP 108

This is the start of the file's text. The full file is on GovTribe.

File details come from the government source that posted it. Updated .