46 - Example SABER Design Intent Drawing Set Level 1_20 Nov.pdf
PDF 7 MB Posted
- Attached to
- SABER IDIQ
- Solicitation number
- FA486125R0003
About this file
These documents are design and engineering drawings for the construction of a Visitor Control Center (VCC) Building 697 at Nellis Air Force Base in Nevada. The project involves constructing a new single-story facility with multiple functional spaces including a lobby, ID processing area, offices, restrooms, mechanical/electrical rooms, and a covered entry. The design drawings cover civil, architectural, structural, mechanical, electrical, plumbing, and telecommunications systems, with a total site disturbance of approximately 0.97 acres.
Key technical details include a ground-polished concrete floor, stucco exterior with Sierra Tan color, concrete roof tiles in Desert Terra Cotta, and interior finishes featuring paint in Queen Anne's Lace and Spare White colors. The building will have various system installations such as HVAC with supply and return air diffusers, electrical lighting and power systems, telecommunications infrastructure including fiber optic cabling, and plumbing fixtures. The project is associated with Air Combat Command and has a contract number of FA486120D0008 with a task order number of FA486120F0354, indicating a federal government construction project for a military installation.
View the file
Other files
Show 40 more
50 files listed here. See the rest on GovTribe.
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
D
2 3
C
A
B
D E
S C
R
IP
T
IO
N D
A T
E M
A R
K
SHEET ID
S O
L
IC
IT
A
T
IO
N N
O
D R
A W
N
B Y
C H
E C
K E
D B
Y
D E
S
IG
N B
Y
C O
N T
R A
C T
N O
S
IZ
E
A N
S I D
F
IL
E N
A M
E
D E
S
IG
N E
N G
IN
E
E R
IN
G
O F
F
IC
E
N E
L L
IS
A
F B
N
E V
A D
A
A
IR
C O
M B
A T
C O
M M
A N
D
IS
S
U E
D A
T E
6 7 8 9 10
E
F
G
CONTRACT NO.: FA486120D0008
TASK ORDER NO.: FA486120F0354
ISSUE DATE:
NELLIS AIR FORCE BASE, NEVADA
RKMF170097
CONSTRUCT VISITOR CONTROL CENTER B697
S
G -0
.D
W G
G-000
N E
L L
IS
A
IR
F O
R C
E B
A S
E N
E V
A
A
V C
C B
U
IL
D
IN
G
R K
M F
A
IR
C O
M B
A T
C O
M M
A N
D
C O
V E
R P
A G
E
DRAWING INDEX
SHEET NUMBER SHEET NAME
GENERAL
G-000 COVER PAGE
C-002 GENERAL CIVIL NOTES
CIVIL
CD101 EXISITNG CONDITIONS AND DEMOLITION PLAN
CS101 CIVIL SITE PLAN
CU101 UTILITY PLAN
STRUCTURAL
ARCHITECTURAL
A-001 ARCHITECTURAL SYMBOLS & ABBREVIATIONS
A-101 FIRST FLOOR PLAN
A-602 FINISH SCHEDULE & LEGEND
FIRE PROTECTION
PLUMBING
P-001 PLUMBING LEGEND & ABBREVIATIONS
P-101 PLUMBING FIRST FLOOR PLAN
MECHANICAL
M-001 MECHANICAL LEGEND & ABBREVIATIONS
M-002 MECHANICAL GENERAL NOTES
M-101 MECHANICAL FLOOR PLAN
ELECTRICAL
E-001 ELECTRICAL LEGEND & SYMBOLS
EL101 ELECTRICAL LIGHTING FLOOR PLAN
EP101 ELECTRICAL POWER FLOOR PLAN
TELECOMMUNICATIONS
T-001 TELECOMMUNICATIONS LEGEND & ABBREVIATIONS
T-101 TELECOMMUNICATIONS FLOOR PLAN
LEVEL 1 DESIGN SUBMITTAL
T-601 TELECOMMUNICATIONS OSP RISER DIAGRAM
G-003 HAUL ROUTE AND STORAGE SITE
NELLIS AIR FOCE BASE
PROJECT SITE
HAUL ROUTE
E MINOT AVE
ELLSWORTH AVE
TYNDALL
A
VE
BUILDING 451
HAUL R
OUTE
LAYDOWN AREA
SHEET ID
D R
AW
N
B Y:
D
ES
IG
N
ED
B
Y:
SI
ZE
C H
EC
KE
D B
Y:
AN
SI
D
C O
N
TR
AC
T
N O
SO
LI
C
IT
AT
IO
N N
O
N
3 5 7 9 11 13 15 17 19
L
J
G
E
C
A
D
AT
E M
AR
K
D
ES
C R
IP
TI
O N
Fi le
P at h:
Pl ot D at e:
2 4 6 8 10 12 14 16 18 20
P
M
K
H
F
D
B
R :\d
3\
N
EL
LI
S
- B
LD
G
AR
C
H
IT
EC
TU
R E.
rv t
8/
/2
4:
:1
PM
G-003
SU
BM
IT
TE
D B
Y:
IS
SU
E D
AT
E:
SP
EC
N O
D
ES
IG
N
F
IL
E N
O
N
EL
LI
S
AI
R
F O
R C
E
BA
SE
, N
EV
AD
A
BU
IL
D
IN
G
A D
AS
W
AD
IT
IO
N
R
KM
F9
H
AU
L R
O U
TE
A
ST
O R
AG
E
SI
TE
9-
-0
PLAN NORTH
NTS3 STATE OF NEVADA
NTS2 NELLIS AIR FORCE BASE
NTS1 PROJECT SITE
US Army Corps of Engineers ®
LEVEL 1 DESIGN SUBMITTAL
U S
AR
M
Y C
O R
PS
O
F
EN
G
IN
EE
R
S
SA
C R
AM
EN
TO
D
IS
TR
IC
T
J S
TR
EE
T
SA
C R
AM
EN
TO
, C
A
CONTRACTOR
ACCESS AT
AREA 2 GATE
Las Vegas Blvd N. H wy 604
E. Minot Ave
El lsw or th
A ve
Swaab Blvd
PROJECT SITE
HAUL ROUTE VIA
ELLSWORTH AVE
Ellsworth Ave
SO
LI
C
IT
AT
IO
N N
O
D
ES
IG
N
ED
B
Y:
D
ES
C R
IP
TI
O N
M
AR
K
SI
ZE
D
AT
E
C H
EC
KE
D B
Y:
D R
AW
N
B Y:
G
2 3 4 5 6 7 8 9 10
F
E
D
C
B
A SHEET ID
D
ES
IG
N
E N
G
IN
EE
R
IN
G
O
FF
IC
E
N
EL
LI
S
AF
B, N
EV
AD
A
AI
R
C O
M
BA
T C
O M
M
AN
D C
O N
TR
AC
T N
O
IS
SU
E D
FI
LE
N
AM
E
AN
SI
D
95% DESIGN RESUBMITTAL - NOT FOR CONSTRUCTION
SU
BM
IT
TE
D
Y:
EL
LI
S
AI
R
F O
R C
E
BA
SE
VI
SI
TO
R C
O N
TR
O
L C
EN
TE
R B
U
IL
D
IN
G
R
KM
F1
AI
R
C O
M
BA
T C
O M
M
AN
D
G
EN
ER
AL
C
IV
IL
N
O
TE
S
C-002
GENERAL CIVIL DEMOLITION NOTES
1. CONTRACTOR SHALL COMPLETE A WORK CLEARANCE REQUEST PRIOR TO
CONSTRUCTION PER PROJECT SPECIFICATIONS. PROCEED WITH EXTREME
CAUTION WHEN EXCAVATING.
2. BEFORE DEMOLISHING ANY UTILITY, THE CONTRACTOR SHALL ENSURE THAT
THERE IS AN ACTIVE LINE TO REPLACE THE FUNCTION OF THE UTILITY BEING
REMOVED IF SERVICE IS FOR OCCUPIED FACILITIES.
3. CONTRACTOR SHALL STOP WORK AND NOTIFY THE CONTRACTING OFFICER OF
ANY UNFORESEEN UTILITY CONFLICTS AS SOON AS DISCOVERED.
4. CONTRACTOR SHALL SAW-CUT A SMOOTH STRAIGHT EDGE ON ANY PAVEMENT
PROPOSED FOR DEMOLITION PRIOR TO ITS REMOVAL. BEFORE CONNECTING
PROPOSED PAVEMENT TO EXISTING PAVEMENT, THE CONTRACTOR SHALL
ENSURE THAT THE EDGE OF EXISTING PAVEMENT IS STRAIGHT AND UNIFORM
PRIOR TO RE-PAVING.
GENERAL CIVIL NOTES
1. EXISTING CONDITIONS INFORMATION IS BASED ON A TOPOGRAPHICAL AND
PHYSICAL DESIGN SURVEY PROVIDED BY: DIAMONDBACK LAND SURVEYING,
CONDUCTED IN JANUARY-FEBRUARY 2021.
2. EXISTING SURFACE INFORMATION, IMPROVEMENTS, APPURTENANCES, AND
ABOVE-GRADE CONSTRUCTION AS SHOWN ON THESE PLANS IS BASED ON
THE FIELD SURVEY REFERENCED ABOVE. UNDERGROUND UTILITY LINEWORK
SHOWN IS BASED ON DOCUMENTATION AND GIS INFORMATION PROVIDED BY
NELLIS AFB, AS WELL AS UTILITY LOCATES PERFORMED PRIOR TO FIELD
SURVEY. DISCREPANCIES MAY EXIST BETWEEN FIELD-SURVEYED SURFACE
UTILITY STRUCTURES AND THE UNDERLYING UTILITY LINEWORK.
CONTRACTOR SHALL FIELD-VERIFY ALL EXISTING CONDITIONS PRIOR TO
CONSTRUCTION.
3. CONTRACTOR SHALL RETAIN A SURVEYOR LICENSED IN NEVADA TO SURVEY
PROJECT IMPROVEMENTS. IF BENCHMARKS SHOWN ARE IN AREAS THAT
REQUIRE DEMOLITION, OTHER BENCHMARKS SHALL BE ESTABLISHED BEFORE
DEMOLITION AND CONSTRUCTION WORK BEGINS. CONTRACTOR SHALL
SUPPLY CERTIFIED CONTROL POINT DATA TO THE CONTRACTING OFFICER
PRIOR TO DEMOLITION ACTIVITIES AND AFTER COMPLETION OF
CONSTRUCTION.
4. BENCHMARK FOR CONSTRUCTION HAS BEEN PROVIDED ON SHEET CD101.
5. TOTAL DISTURBED ACREAGE = ± 0.97 AC
6. THE CONTRACTOR SHALL COMPLETE AND FILE AF 103 DIG PERMIT AND SHALL
ALSO CONTACT NEVADA 811 CALL BEFORE YOU DIG.
7. A GEOTECHNICAL INVESTIGATION WAS COMPLETED AND A REPORT
PROVIDED FOR THE PROJECT SITE BY UNIVERSAL ENGINEERING SCIENCES,
DATED MARCH 22, 2021.
8. THERE ARE NO KNOWN WETLANDS OR STREAMS WITHIN 200 FT OF THE
PROJECT SITE.
9. ALL NEW AND EXISTING PAVEMENTS USED BY THE CONTRACTOR DURING
CONSTRUCTION SHALL BE REPLACED AS NEEDED TO THE SATISFACTION OF
THE GOVERNMENT AT NO ADDITIONAL COST.
10. CONTRACTOR ACCESS TO NELLIS AFB IS RESTRICTED TO GATE(S) AS SHOWN.
CONTRACTOR SHALL COORDINATE WITH NELLIS AFB FOR REQUIREMENTS.
11. DISPOSAL AREAS FOR RUBBLE, UNSUITABLE OR EXCESS SOIL MATERIALS, OR
OTHER CONSTRUCTION DEBRIS ARE NOT AVAILABLE ON NELLIS AFB FOR THE
CONTRACTOR'S USE. DISPOSAL MUST BE PROVIDED BY THE CONTRACTOR AT
LAWFUL CONTRACTOR-PROVIDED SITES OFF GOVERNMENT-CONTROLLED
LANDS.
12. CONTRACTOR SHALL FIELD-VERIFY EXISTING CONDITIONS PRIOR TO START
OF WORK TO AVOID DAMAGE TO EXISTING UTILITIES AND/OR SITE FEATURES.
CONTRACTOR SHALL PROTECT ALL EXISTING UTILITIES AND SITE FEATURES
DESIGNATED TO REMAIN THROUGHOUT CONSTRUCTION. ANY DAMAGE TO
EXISTING UTILITIES AND/OR SITE FEATURES CAUSED BY THE CONTRACTOR
SHALL BE REPAIRED BY THE CONTRACTOR TO THE SATISFACTION OF THE
CONTRACTING OFFICER AT NO COST TO THE GOVERNMENT. ANY DAMAGE BY
CONTRACTOR SHALL BE REPORTED IMMEDIATELY AND SENT TO THE
CONTRACTING OFFICER. AS DETERMINED BY THE CONTRACTING OFFICER,
THE CONTRACTOR CAN BE ORDERED TO IMMEDIATELY REPAIR DAMAGE
CAUSED BY THE CONTRACTOR TO THE SATISFACTION OF THE CONTRACTING
OFFICER AT NO COST TO THE GOVERNMENT.
13. ALL CONTRACTOR TRAFFIC MUST STAY ON DESIGNATED HAUL ROUTE
ROADWAYS AT ALL TIMES WHILE TRAVELING TO AND FROM THE PROJECT
SITE. AT NO TIME SHALL THE HAUL ROUTE BECOME A PARKING/STAGING
AREA FOR ANY CONTRACTOR VEHICLES OR EQUIPMENT.
14. AREAS FOR CONTRACTOR USE ARE RESTRICTED TO THOSE LOCATIONS
SHOWN. CONTRACTOR SHALL BE RESPONSIBLE FOR FENCING, SECURITY,
FIELD OFFICE AND OTHER REQUIREMENTS AS PROVIDED IN THE
SPECIFICATIONS. AREAS SHALL BE RESTORED TO PRE-EXISTING CONDITION
UPON COMPLETION OF THE PROJECT.
15. CONTRACTOR SHALL PROTECT ALL PAVEMENTS AND EXISTING UTILITIES
DESIGNATED TO REMAIN FROM ALL HEAVY EQUIPMENT. PROVIDE TRAFFIC
CONTROL MEASURES PER PROJECT SPECIFICATIONS.
16. ANY ITEMS WHICH ARE DAMAGED AND NEED TO BE REPLACED SHALL MEET
THE PROJECT SPECIFICATION REQUIREMENTS FOR THE APPLICABLE
MATERIALS OR SYSTEM AT NO ADDITIONAL COST TO THE GOVERNMENT.
17. CONTRACTOR SHALL PREPARE AND SUBMIT A CONSTRUCTION PHASE
TRAFFIC CONTROL PLAN TO NELLIS AFB PERSONNEL FOR APPROVAL PRIOR
TO CONSTRUCTION.
18. EROSION CONTROL MEASURES SHALL BE IN PLACE PRIOR TO PERFORMING
ANY LAND DISTURBING ACTIVITIES OR DEMOLITION.
19. THE LIMITS OF CONSTRUCTION AS SHOWN ON THE CONTRACT PLANS SHALL
NOT BE ADJUSTED WITHOUT PRIOR APPROVAL FROM THE CONTRACTING
OFFICER.
20. ALL MATERIALS WHICH ARE REMOVED AND NOT TO BE REUSED OR SALVAGED
SHALL BECOME THE PROPERTY OF THE CONTRACTOR AND SHALL BE
REMOVED FROM GOVERNMENT PROPERTY.
21. ALL EXCAVATION SHALL BE PERFORMED SO THAT THE SITE AND THE AREA
IMMEDIATELY SURROUNDING THE SITE WHICH AFFECT OPERATIONS ARE
CONTINUALLY AND EFFECTIVELY DRAINED DURING ALL PHASES OF
CONSTRUCTION.
22.SURPLUS MATERIAL OR OTHER SOIL MATERIAL NOT REQUIRED OR SUITABLE
FOR FILLING OR BACKFILLING SHALL BE REMOVED FROM THE PROJECT SITE
AND DISPOSED OF IN AN APPROVED DISPOSAL AREA BY THE CONTRACTOR.
GENERAL CIVIL SITE NOTES
1. CONTRACTOR SHALL FURNISH AND MAINTAIN ANY AND ALL NECESSARY
BARRICADES AROUND THE WORK AND PROVIDE PROTECTION AGAINST WATER
DAMAGE, DUST MIGRATION, AND SOIL EROSION PER PROJECT CONTRACT
DOCUMENTS AND NELLIS AFB REQUIREMENTS.
2. ALL BUILDING DIMENSIONS SHALL BE CHECKED AND COORDINATED WITH THE
ARCHITECTURAL PLANS.
3. PAVEMENT MARKING SHALL BE PAINTED ON PAVEMENT AT LOCATIONS SHOWN.
4. ALL SIGNAGE SHALL CONFORM TO THE MUTCD STANDARDS AND SPECIFICATIONS.
GENERAL CIVIL UTILITY NOTES
1. CONTRACTOR SHALL VERIFY LOCATIONS AND ELEVATIONS OF EXISTING
UTILITIES PRIOR TO CONSTRUCTION ACTIVITIES. CONTRACTOR SHALL BE
RESPONSIBLE FOR CONTACTING ALL UTILITY COMPANIES THAT POTENTIALLY
HAVE EXISTING UTILITIES ON-SITE AND DETERMINE APPLICABLE REQUIREMENTS.
2. ALL CONNECTIONS TO EXISTING UTILITIES AND ALL UTILITY INSTALLATIONS
SHALL BE IN COMPLIANCE WITH PROJECT CONTRACT DOCUMENTS AND NELLIS
AFB REQUIREMENTS.
3. THE CONTRACTOR SHALL BE RESPONSIBLE FOR COORDINATING CIVIL SITE
WORKS ACROSS ALL DISCIPLINES ASSOCIATED WITH THE PERFORMANCE OF
THIS PROJECT.
4. ANY EXISTING UTILITY STRUCTURES AND/OR APPURTENANCES WHICH ARE IN
THE AREA OF CONSTRUCTION AND WHICH WILL REMAIN SHALL BE ADJUSTED TO
FINAL GRADE.
GENERAL CIVIL GRADING AND DRAINAGE NOTES
1. ALL GRADING AND SITE PREPARATION SHALL CONFORM TO THE PROJECT
SPECIFICATIONS.
2. CONTRACTOR SHALL MARK, AND PROTECT WITH FENCE, ALL BENCHMARKS
DESIGNATED TO REMAIN.
3. ALL CUT AND FILL SLOPES SHALL BE 3:1 OR FLATTER.
4. ALL SPOT ELEVATIONS SHOWN ARE FINISHED GRADE, UNLESS NOTED
OTHERWISE.
5. SITE GRADING SHALL NOT PROCEED UNTIL EROSION CONTROL MEASURES HAVE
BEEN INSTALLED AND PERMITS OBTAINED PER PROJECT CONTRACT DOCUMENTS
AND NELLIS AFB REQUIREMENTS.
6. CONTRACTOR SHALL ENSURE POSITIVE DRAINAGE OF ALL SURFACE RUNOFF
DURING CONSTRUCTION.
7. CONTRACTOR SHALL BLEND ALL NEW EARTHWORK SMOOTHLY TO TRANSITION
BACK TO EXISTING GRADE.
8. PROPOSED CONTOURS SHOWN IN ROADWAYS, DRIVEWAYS AND SIDEWALKS
REFLECT THE FINISHED ELEVATIONS OF THE ASPHALT AND CONCRETE.
LEVEL 2 DESIGN SUBMITTAL
PROJECT LIMITS
SWAAB BLVD.
D U
N N
IN
G
C
IR
C
LE
SITE ACCESS
PROJECT LIMITS
A1 EXISTING CONDITIONS AND DEMOLITION PLAN
SCALE: 1" = 20' 20' 40'0
NORTH
PLAN
SHEET KEYNOTES
1. REMOVE AND DEMOLISH APPROXIMATELY 107 LF OF EXISTING BASE
PERIMETER WALL
2. INSTALL TEMPORARY PERIMETER FENCE BEFORE DEMOLITION OF
EXISTING BASE PERIMETER WALL
3. REMOVE EXISTING BOULDER(S) AS NECESSARY FOR NEW CONCRETE
WALK CONSTRUCTION
4. RELOCATE EXISTING BENCHES AS NECESSARY
1. NO SURVEY OR EXISTING CAD FILES WERE PROVIDED. UTILITY
INFORMATION PROVIDED BY NELLIS AFB GIS.
GENERAL NOTES
SO
LI
C
IT
AT
IO
N N
O
D
ES
IG
N
ED
B
Y:
D
ES
C R
IP
TI
O N
M
AR
K
SI
ZE
D
AT
E
C O
N
TR
AC
T
N O
C
H
EC
KE
D
B Y:
D R
AW
N
B Y:
G
2 3 4 5 6 7 8 9 10
F
E
D
C
B
A SHEET ID
C
ES
REA
DY
W I L
LI
NG
AB
LE
D
ES
IG
N
E N
G
IN
EE
R
IN
G
O
FF
IC
E
N
EL
LI
S
AF
B, N
EV
AD
A
AI
R
C O
M
BA
T C
O M
M
AN
D
.IS
SU
E D
LE
N
AM
E
AN
SI
D
D
AW
SO
N
SU
BM
IT
TE
D
EL
LI
S
AI
R
F O
R C
E
BA
SE
VC
C B
U
IL
D
IN
G
R
KM
F1
AI
R C
O M
BA
T
C O
M M
AN
D
EX
IS
IT
N
G C
O N
D
IT
IO
N
S
AN
D D
EM
O
LI
TI
O N
P
LA
N
CD101
LEVEL 1 DESIGN SUBMITTAL
H
VA
C
VISITOR
CONTROL
CENTER
PROJECT LIMITS
±94.71'
86' MIN.
±92'
86' MIN.
±3 5'
' M
IN
SWAAB BLVD.
D U
N N
IN
G
C
IR
C
LE
LAYDOWN AREA
EXISTING BASE
PERIMETER WALL
EXISTING BASE
PERIMETER WALL
SITE ACCESS
8'
5'
PROJECT LIMITS
A1 CIVIL SITE PLAN
SCALE: 1" = 20' 20' 40'0
NORTH
PLAN
SHEET KEYNOTES
1. NEW PERIMETER WALL (REFER TO STRUCTURAL PLANS)
2. TEMPORARY PERIMETER FENCE
3. CONCRETE SIDEWALK
4. SCREEN WALL (REFER TO ARCHITECTURAL PLANS)
1. NO SURVEY OR EXISTING CAD FILES WERE PROVIDED. UTILITY
INFORMATION PROVIDED BY NELLIS AFB GIS.
GENERAL NOTES
SO
LI
C
IT
AT
IO
N N
O
D
ES
IG
N
ED
B
Y:
D
ES
C R
IP
TI
O N
M
AR
K
SI
ZE
SU
BM
IT
TE
D B
Y:
D
AT
E
C O
N
TR
AC
T
N O
C
H
EC
KE
D
B Y:
D R
AW
N
B Y:
G
2 3 4 5 6 7 8 9 10
F
E
D
C
B
A SHEET ID
C
ES
REA
DY
W
IL
LI
NG
AB
LE
D
ES
IG
N
E N
G
IN
EE
R
IN
G
O
FF
IC
E
N
EL
LI
S
AF
B, N
EV
AD
A
AI
R
C O
M
BA
T C
O M
M
AN
D
.IS
SU
E D
LE
N
AM
E
AN
SI
D
D
AW
SO
N
N
EL
LI
S
AI
R
F O
R C
E
BA
SE
V
BU
IL
D
IN
G
R
KM
F1
AI
R
C O
M
BA
T C
O M
M
AN
D
C
IV
IL
S
IT
E
PL
AN
CS101
H
VA
C
VISITOR
CONTROL
CENTER
100LF SANITARY SEWER
51.1LF SANITARY SEWER
23.1LF SANITARY SEWER
251.8LF WATER
18.9LF FIRE LATERAL
28.1LF WATER
W W
W W
W W
W W
W W
W W
W W
W W
W W
W
W W
E E E E E E E E E E E
E E E E E E E E E E E E E E E E E E E E E E E
E E
E E
E E
E E
E E
E E
E E
E E
E E
E E
E E
E E
E E
E
SA
N
SA
N
SA
N
SA
N
SA
N
SA
N
SA
N
SA
N
SA
N
SA
N
SA
N
SA
N
SA
N
SAN SAN SAN
E E
CO
CO
S
CO
M
M
CO
M
M
CO
M
M
CO
M
M
CO
M
M
CO
M
M
CO
M
M
CO
M
M
CO
M
M
CO
M
M
CO
M
M
CO
M
M
CO
M
M
CO
M
M
CO
M
M
COMM
COMM
C O
M M
C O
M M
C O
M M
C O
M M
C O
M M
C O
M M
C O
M M
C O
M M
C O
M M
C O
M M
C O
M M
C O
M M
C O
M M
C O
M M
COMM COMM COMM
C
C
C
C
COMM HH
213A
COMM HH
219B
COMM HH
219C
E
E E
EE E E E E E E E E E E E E
E
CO
W W W W W W W W W W W W W W W W W W W W W W W W W W W W W W W W
EE E
14.8LF WATER
14.1LF WATER
7 6
223LF
93LF
167LF
100LF SANITARY SEWER
46LF
PROJECT LIMITS
SWAAB BLVD.
D U
N N
IN
G
C
IR
C
LE
PROJECT LIMITS
EXISTING WATER LINE
132.4LF WATER10LF WATER
E E
COMM
E E
W W
SAN
EXISTING PROPOSED
COMMUNICATIONS
ELECTRIC/POWER
WATER
SANITARY SEWER
UTILITY LINE LEGEND
C COMM HAND HOLE
TRANSFORMER
EELEC SWITCH
FIRE HYDRANT
WATER FITTING
WATER VALVE
COSEWER CLEANOUT
S SEWER MANHOLE
UTILITY SYMBOL LEGEND
E ELEC MANHOLE
A1 UTILITY PLAN
SCALE: 1" = 20' 20' 40'0
NORTH
PLAN
SHEET KEYNOTES
1. SANITARY SEWER SERVICE
2. WATER SERVICE LINE
3. FIRE HYDRANT
4. SANITARY SEWER CLEANOUT
5. CONNECT SANITARY SERVICE LINE TO EXISTING MANHOLE
6. ELECTRIC SWITCH (REF. SHEET ES601)
7. DUCT BANK (REF. SHEET ES601)
8. TRANSFORMER (REF. SHEET ES601)
9. COMM DUCT BANK (REF. SHEET T-601)
10. ELECTRIC MANHOLE (REF. SHEET ES601)
1. NO SURVEY OR EXISTING CAD FILES WERE PROVIDED. UTILITY
INFORMATION PROVIDED BY NELLIS AFB GIS.
GENERAL NOTES
SO
LI
C
IT
AT
IO
N N
O
D
ES
IG
N
ED
B
Y:
D
ES
C R
IP
TI
O N
M
AR
K
SI
ZE
SU
BM
IT
TE
D B
Y:
D
AT
E
C O
N
TR
AC
T
N O
C
H
EC
KE
D
B Y:
D R
AW
N
B Y:
G
2 3 4 5 6 7 8 9 10
F
E
D
C
B
A SHEET ID
C
ES
REA
DY
W
IL
LIN
G
AB
LE
D
ES
IG
N
E N
G
IN
EE
R
IN
G
O
FF
IC
E
N
EL
LI
S
AF
B, N
EV
AD
A
AI
R
C O
M
BA
T C
O M
M
AN
D
.IS
SU
E D
LE
N
AM
E
AN
SI
D
D
AW
SO
N
N
EL
LI
S
AI
R
F O
R C
E
BA
SE
VC
B U
IL
D
IN
G
R
KM
F1
AI
R C
O M
BA
T
C O
M M
AN
D
U
TI
LI
TY
P
LA
N
CU101
GENERAL NOTES
THE CONTRACTOR SHALL PROVIDE COMPLETE PROJECT SYSTEMS AND
COMPONENTS AND COMPLY WITH ALL REQUIREMENTS ON THE PROJECT
DOCUMENTS. THE PROJECT DOCUMENTS REFERS TO THE DRAWINGS,
SPECIFICATIONS, AND OTHER DOCUMENTS ISSUED BY THE
ARCHITECT/ENGINEER.
CONTRACTOR SHALL WORK WITHIN THE AREA INDICATED IN THE PROJECT
DOCUMENTS AND COMPLY WITH ALL APPLICABLE BUILDING CODES,
REGULATIONS, AND ORDINANCE REQUIREMENTS. OCCUPANTS ADJACENT/IN THE
PROJECT AREA SHALL CONTINUE UNINTERRUPTED OCCUPANCY DURING
CONSTRUCTION OF THE PROJECT.
CONTRACTOR SHALL VERIFY FIELD CONDITIONS AND COORDINATE WITH THE
PROJECT DOCUMENTS PRIOR TO PROCEEDING WITH THE WORK.
CONTRACTOR SHALL COORDINATE THE WORK WITH EQUIPMENT, FURNISHINGS,
AND SYSTEMS PROVIDED BY THE OWNER.
1.
2.
3.
4.
GENERAL NOTES: DIMENSIONS:
DIMENSIONS ARE INDICATED TO THE NORMAL FACE OF CMU WALL, FACE OF
STUD, UNO.
ALIGNMENT OF PARTITIONS AND FINISHES AS SCHEDULED ALL BE STRAIGHT,
TRUE & PLUMB. THE PRIORITY FOR PROJECT DIMENSIONS SHALL BE THE
FOLLOWING:
MIN. DIMENSIONS FOR ACCESSIBILITY CLEARANCE & BUILDING CODE
REQUIREMENTS
LARGE SCALE DETAILS
SMALL SCALE DETAILS
ENLARGED VIEWS
FLOOR PLANS AND ELEVATIONS
FLOOR ELEVATIONS ARE INDICATED TO THE TOP OF THE CONCRETE TOPPING
SLAB, UNLESS OTHERWISE NOTED.
VERTICAL DIMENSIONS ARE INDICATED FROM THE FLOOR ELEVATION TO
FACE OF FINISHED MATERIAL AT THE DIMENSION POINT (ABOVE FINISH
FLOOR - "AFF").
CEILING HEIGHTS ARE INDICATED FROM THE FLOOR ELEVATION TO THE FACE
OF SUSPENDED CEILING SYSTEM OR FACE OF FINISH MATERIAL AS
SCHEDULED (AFF).
DIMENSIONS SHOWN ON THE DRAWINGS INDICATE THE REQUIRED SIZE,
CLEARANCE, AND DIMENSIONAL RELATIONSHIP BETWEEN PROJECT SYSTEMS
AND COMPONENTS. DIMENSIONS SHALL NOT BE DETERMINED BY SCALING
THE DRAWINGS.
1.
2.
A.
B.
C.
D.
E.
3.
4.
5.
6.
DEFINITIONS:
"TYPICAL" OR "TYP" INDICATES IDENTICAL COMPLETE
SYSTEMS SHALL BE PROVIDED FOR EACH OCCURRENCE OF
THE CONDITION.
"SIMILAR" INDICATES TO PROVIDE COMPLETE SYSTEM AND
COMPONENTS COMPARABLE TO THE CHARACTERISTICS OF
DETAIL NOTES AND ADJUSTED FOR SUITABILITY TO ACTUAL
CONDITION.
"ALIGN" MEANS TO PROVIDE FINISHED SURFACES THAT ARE
IN THE SAME PLANE.
1.
2.
3.
WALL SECTION
ELEVATION MARKER
BUILDING SECTION
SECTION NUMBER
SHEET NUMBER
DETAILS
DETAIL NUMBER
SHEET NUMBER
PLAN OR DETAILS NUMBER
SHEET NUMBER
INTERIOR ELEVATION
KEYNOTE
REVISION DELTA
ELEVATION NUMBER
SHEET NUMBER
ENLARGED PLAN AND
DETAIL REFERENCE
SECTION NUMBER
SHEET NUMBER
DOOR TAG
EXTERIOR ELEVATION
ELEVATION NUMBER
SHEET NUMBER
WALL TAG
CEILING TAG
XXX
X
1 Ref
XXX
X
XXX
XX
X'-XX" AFF
X
LEVEL
ELEVATION
VIEW TITLES
SCALE
COLUMN GRID
ROOM NAME &
NUMBER
X
VIEW NAME
1/8" = 1'-0"
WITH SCALE
0 2' 4' 8' 16'
X
X
ROOM NAME
XXX
X
VIEW NAME
N.T.S.X
VIEW NAME
WITHOUT SCALE
NOT TO SCALE
XXX
XXX
XXX
SYMBOL LEGENDS
SAND
RIGID INSULATION
PRECAST CONCRETE
STUCCO
METAL STUD PARTITION
MARBLE
GYPSUM BOARD
GRANULAR MATERIAL
EARTH
CMU
CONCRETE
BATT INSULATION
METAL
LEGEND
RC REINFORCED CONCRETE
RCP REFLECTED CEILING
PLAN
RD ROOF DRAIN
RE: REFER
TO/REFERENCE/SEE
REINF REINFORCE (D) , (ING)
RFBF RADIO FREQUENCY
BARRIER FABRIC
SC SCALE
SECT SECTION
SHT SHEET
SIM SIMILAR
EA EACH
EIFS EXTERIOR INSULATION
FINISH SYSTEM
EJ EXPANSION JOINT
ELEV ELEVATION(S)
EQ EQUAL
EQUIP EQUIPMENT
EXH EXHAUST
EXIST EXISTING
EXP EXPOSED
EXT EXTERIOR
FEC FIRE EXTINGUISHER CABINET
FF FINISHED FACE/FLOOR
FIN FINISH (ED)
FLR FLOOR (ING)
FND FOUNDATION
AFF ABOVE FINISH
FLOOR
ALT ALTERNATE
ARCH ARCHITECT /
ARCHITECTURAL
BLDG BUILDING
BM BEAM
BO BOTTOM OF
BOT BOTTOM
N NORTH
NIC NOT IN CONTRACT
NO. NUMBER
NTS NOT TO SCALE
OC ON CENTER (S)
OD OUTSIDE DIAMETER
OPNG OPENING
OPP OPPOSITE
PC PRECAST CONCRETE
P.L. PROPERTY LINE
PL PLATE
PLAS PLASTER
PR PAIR
PT POINT
CEM CEMENT
CHNL CHANNEL (S)
CIP CAST IN PLACE
CJ CONTROL JOINT
CL CENTERLINE
CLG CEILING
CMU CONCRETE MASONRY UNIT
COL COLUMN
CONC CONCRETE
CONSTRCONSTRUCTION
CONT CONTINUOUS
DEPT DEPARTMENT
DET DETAIL
DIA DIAMETER
DIM DIMENSION
DWG DRAWING
INCL INCLUDE (D) , (ING)
INFO INFORMATION
INSUL INSULATE (ED) , (ION)
INCL INCLUDE (D) , (ING)
INFO INFORMATION
INSUL INSULATE (ED) , (ION)
JST JOIST
JT JOINT
MAX MAXIMUM
MECH MECHANICAL
MEMB MEMBRANE
MFR MANUFACTURE (R)
MIN MINIMUM
MISC MISCELLANEOUS
ABBREVIATIONS
SPEC SPECIFICATION (S)
SQ SQUARE
STL STEEL
STRUC STRUCTURAL
TOC TOP OF CONCRETE
TYP TYPICAL
UBC UNIFORM BUILDING CODE
UNO UNLESS NOTED OTHERWISE
(V) VERTICAL
VB VAPOR BARRIER
WPR WATERPROOF
WR WATER RESISTANT
W/ WITH
FOC FACE CONCRETE
FOS FACE OF STUD
FT FOOT / FEET
FTG FOOTING
GFGI GOVERNMENT FURNISHED
GOVERNMENT INSTALLED
GEN GENERAL
GL GLASS / GLAZING
GR GRADE
GWB GYPSUM WALL BOARD
(H) / HORIZ/ HORIZONTAL
HM HOLLOW METAL
HR HOUR
HT HEIGHT
TYPICAL MOUNTING HEIGHTS:
PHONE / THERMOSTAT / SWITCH / OUTLET / VISUAL ALARM LOCATIONS
SWITCHES @
PUBLIC LOCATIONS
TYPICAL POWER GROUPINGHANDRAILS FOR STAIR/RAMP TYPICAL BRAILLE ROOM SIGN
MIN.
1' - 0"
MIN.
1' - 0"
RAMP 1:12
MAX.
HANDRAIL, 250
FT./LB MIN.
FORCE IN ANY
DIRECTION
BRACKET AT
END CONDITION
LIGHT SWITCH
VISUAL ALARM/
STROBE
THERMOSTAT
LIGHTSWITCH
5"
8" 8"
COMMON POWER
DATA
ISOLATED
GROUND
POWER OR
TELEPHONE
TYPICAL DOOR,
RE: PLANS
ROOM SIGNAGE
LOCATION: HOLD ROOM
SIGN 2" OFF FRAME
UNLESS NOTED
M
IN
2"
COUNTER & UNDERCOUNTER
2' - 0" MAX.
COUNTER
DEPTH
OVER COUNTER
OUTLET
THERMOSTAT6"
LIGHTSWITCH
& DIMMERS
EQUAL EQUAL
TYPICAL POWER & SWITCH GROUPING
BETWEEN DOORS, COLUMNS AND OPENINGS
WALL, COLUMN
OR OPENING
THERMOSTAT
LIGHTSWITCH
& DIMMERS
TYPICAL POWER & SWITCH
GROUPING AT CORNERS
EDGE OF WALL
8" 8"
8"
COMMON
POWER
DATA/ AV
CLUSTER
ISOLATED GROUND
POWER OR TELEPHONE
8" 8"
TYPICAL POWER GROUPING
ABOVE MILLWORK
8" 8"
PROVIDE
GROMMETS
@ EACH GROUP
WORK-SURFACE
8"
TYPICAL POWER GROUPING
BELOW MILLWORK
TYPICAL POWER GROUPING
AT CREDENZAS OR COUNTERS
8"8" 8"
PROVIDE GROMMETS
@ EACH. GROUP
TYPICAL MOUNTING HEIGHT GENERAL NOTES:
1. THESE MOUNTING HEIGHT DRAWINGS SHALL GOVERN
UNLESS OTHERWISE NOTED ON THE DRAWING
PLANS, ELEVATIONS, MILLWORK ELEVATIONS AND
SECTIONS.
2. MOUNTING HEIGHTS FOR THE THERMOSTATS APPLY
WHEN ADJUSTABLE BY ROOM OCCUPANTS. FOR
SENSOR AND NON-ADJUSTABLE THERMOSTATS,
VERIFY WITH MECHANICAL.
3. MOUTNTING HEIGHTS FOR POWER SHALL BE
VERIFIED WITH ELECTRICAL.
UNDER COUNTER
OUTLET
M A
X
BASELINE OF TOP
LINE OF SIGNAGE
TEXT
BASELINE OF
BOTTOM LINE
OF SIGNAGE
TEXT
7"
(NTS) NOT ALL ITEMS ARE IN PROJECT
STEEL COUNTER SUPPORT
BRACKET, 5 FT MAX., BEYONDT
Y P
4" TYP APRON, RE: ELEV
6"
TYPICAL MOUNTING HEIGHTS
D
2 3
C
A
B
D E
S C
R
IP
T
IO
N D
A T
E M
A R
K
SHEET ID
S O
L
IC
IT
A
T
IO
N N
O
D R
A W
N B
Y
C H
E C
K E
D B
Y
D E
S
IG
N B
Y
S U
B M
IT
T
E
C O
N T
R A
C T
N O
S
IZ
E
A N
S I D
F
IL
E N
A M
E
D E
S
IG
N E
N G
IN
E
E R
IN
G
O F
F
IC
E N
E L
L
IS
A F
B N
E V
A D
A
A
IR
C O
M B
A T
C O
M M
A N
D
IS
S
U E
D A
T E
6 7 8 9 10
E
F
G
A -0
.D W
G
A-001
N E
L L
IS
A
IR
F O
R C
E B
A S
E N
E V
A D
A
V C
C B
U
IL
D
IN
G
R K
M F
A
IR
C O
M B
A T
C O
M M
A N
D
A R
C H
IT
E
C T
U R
A L
S Y
M B
O L S
A
B B
R E
V
IA
T
IO
N S
2 3 4
B
C
D
10' - 8" 22' - 8"
20' - 0"
VESTIBULE
STORAGE
LOBBY
ID PROCESSING
OFFICE
MECH/ELEC.
COMM.
JAN
MEN
WOMEN
B1
A-201
C1
A-201
C1
A-202
B1
A-202 6
53' - 4"
2' - 0" 2' - 0"
16' - 4"
6' - 0" 10' - 0" 4"
3' - 0" 3' - 0" 3' - 7" 15' - 8"
3' - 0" 4' - 6" 2' - 1" 3' - 8" 12' - 0"
6' - 0" 10' - 0" 6' - 8"
2' - 8" 6' - 8"
1' - 8" 3' - 4" 12' - 6" 3' - 4"
8' - 0" 1' - 4" 7' - 0" 1' - 1"
109 108
102A 103A
102B 103B
105106107
10' - 8" 6' - 0" 6' - 8"
B1
A-301
A-502 D3 A-501 D2
A1
A-302
8' - 0" 6' - 8"
2' - 8" 6' - 8"
A1
A-301
A-401
D1
A-501
D3
A-502D2 D1
B1
A-501
D1
B2
A-501
A
A
A B
C
B
8'-0" HIGH BASE
PERIMETER CMU
WALL PER CIVIL
4' - 2" 15' - 10"
8'-0" HIGH BASE
PERIMETER CMU
WALL PER CIVIL
4'-8" HIGH
CMU SCREEN
WALL
S-1
S-4
T-2
S-3
D-1
S-4
D-1
S-4
T-3
TS-1
TS-1 TS-1
CGP
PT-1
RB-1
ACT-1
CGP
PT-1
RB-1
ACT-1
CT-1
PT-1/CT-2
CT-1
PT-2
CT-1
PT-1/CT-2
CT-1
PT-2
CT-1
PT-1/CT-2
CT-1
PT-2
CS
PT-1
RB-1
N/A
CS
PT-1
RB-1
N/A
CGP
PT-1
RB-1
ACT-1
CGP
PT-1
RB-1
ACT-1
CGP
PT-1
RB-1
ACT-1
CR-1
CR-1
CR-1
CR-1
PT-2
PT-2
A-502
B2
EM-1
A L
IG
N
M12 A4
M12A4A4
A4
M12 M12
M12
M12
M12
A4 A4
M12
M12 M12
M12
A4
A4
M12M12
22' - 8"
MECH YARD
PATIO
COVERED ENTRY
1. DIMENSIONS ARE FROM FINISH MATERIAL, TYP.
2. CR-1, CHAIR RAIL RE: FINISH LEGEND
3. FURNITURE LISTED BELOW IS GOVERNMENT
FURNISHED GOVERMENT INSTALLED (GFGI)
4. REFER TO DETAILS SHEET FOR CASEWORK DETAILS
5. TS-1, FOR TRANSITION DETAILS RE: A-501
6. EM-1, FOR ENTRY MAT RE: FINISH LEGEND
9. MTB-1, METAL VENETIAN BLINDS AT ALL WINDOWS,
RE: FINISH LEGEND
GENERAL NOTES
1. COPIER, GFGI
2. REFRIGERATOR, GFGI
3. COMPUTER SCREEN, GFGI
4. COFFEE MAKER, GFGI
5. 5'-0"L X 1'-0"W WATERPROOF SHELVING, GFGI
SHEET KEYNOTES
1. D-1, L-SHAPED WORKSTATION, GFGI
2. T-1, TV TABLE, GFGI
3. T-2, BREAK ROOM TABLE, GFGI
4. T-3, 8'-0"X2'-6" SIGN-IN KIOSK WITH "WATERFALL" EDGE,
GFGI
5. S-1, GUEST SEATING, GFGI
6. S-2, HIGH TASK CHAIR, GFGI
7. S-3, BREAKROOM STACKING SEAT, GFGI
8. S-4, EXECUTIVE SEATING, GFGI
FURNITURE
FLOOR FINISH
LEGEND
CEILING FINISH
WALL FINISH
BASE FINISH
XXX-X
XXX-X
XXX-X
XXX-X
XXX PARTITION TYPE
D
2 3
C
A
B
D E
S C
R
IP
T
IO
N D
A T
E M
A R
K
SHEET ID
S O
L
IC
IT
A
T
IO
N N
O
D R
A W
N B
Y
C H
E C
K E
D B
Y
D E
S
IG
N B
Y
S U
B M
IT
T
C O
N T
R A
C T
N O
S
IZ
E
A N
S I D
F
IL
E N
A M
E
D E
S
IG
N E
N G
IN
E
E R
IN
G
O F
F
IC
E N
E L
L
IS
A F
B N
E V
A D
A
A
IR
C O
M B
A T
C O
M M
A N
D
IS
S
U E
D A
T E
6 7 8 9 10
E
F
G
A -1
.D W
G
A-101
N E
L L
IS
A
IR
F O
R C
E B
A S
E N
E V
A
C B
U
IL
D
IN
G
R K
M F
A
IR
C O
M B
A T
C O
M M
A N
D
F
IR
S T
F L
O O
R P
L A
N
1/4" = 1'-0"A1
FLOOR PLAN
NORTH
0 1' 2' 4' 8'
FLOORING
CONCRETE (CGP)
CGP-1-CONCRETE, GROUND AND POLISHED TEXTURE; COLOR: GRAY WITH LIGHT AND
DARK BEIGE AGGREGATES
CONCRETE SEALED (CS)
CS-1- BROOM FINISH CLEAR CONRETE FLOOR SEALER SHERWIN WILLIAMS CONCRETE AND
TERRAZZO SEALER, CLEAR
CERAMIC TILE (CT)
CT-1-DALTILE;CITY VIEW;COLORBODY PORCELAIN;HARBOUR MIST; CY01;12X12 FIELD TILE
(ACTUAL DIMENSIONS 11 5/8" X 11 5/8" X 3/8")
ENTRY MAT (EM)
EM-1, LOOSE LAY CARPETED ENTRANCE MAT, SIZE: 6'-0" X 8'-0", COLOR: TBD
WALL FINISHES
PAINT (PT)
PT-1-SHERWIN WILLIAMS; COLOR:SW 6420 QUEEN ANNE'S LACE
PT-2-SHERWIN WILLIAMS; COLOR:SW TBD
CERAMIC TILE (CT)
CT-2-DALTILE;CITY VIEW;COLORBODY PORCELAIN;HARBOUR MIST; CY01;12X12 FIELD TILE
(ACTUAL DIMENSIONS 11 5/8" X 11 5/8" X 3/8")
MISCELLANEOUS FINISHES
SOLID SURFACE (SS)
SS-1-LG HAUSYS; HI-MACS;VIATERA;COLOR: CARINA T018
QUARTZ (QTZ)
QTZ-1-LG HAUSYS;VIATERA;QUARTZ;COLOR: STELLA
METAL WINDOW BLINDS (MTB)
MTB-1 HUNTER DOUGLAS, METAL VENETIAN BLINDS, WITH DE-LIGHT FEATURE, SIZE: 1" SLAT, FINISH: BRUSHED NICKEL
SIGNAGE (S)
S-1-BRAND TBD ;TO FOLLOW UFC 3-120-01 DESIGN; STANDARDS, COLOR: WHITE AND BLACK,
RE: SIGNAGE DETAILS
WALL SWITCH HANDLES, STANDARD RECEPTACLE BODIES AND ELECTRICAL
DEVICE COVER PLATES
WHITE
TRANSITION STRIP (TS)
TS-1-TRANSITION STRIP LVT TO SC;RE: DETAIL TBD/A-501
CHAIR RAIL (CR)
CR-1 KOROSEAL, KOROGUARD CHAIR RAIL, BW50, SIZE: 4"H,COLOR: MAPLE RED OAK (MS)
PHOTO BACKDROP (PBD)
PBD-1 ROLLEASY BACKGROUND SYSTEM, CEILING MOUNTED PHOTO BACKDROP, SIZE: 2 1/2" ,
COLOR: BLACK
PLASTIC LAMINATE (PLAM)
PLAM-1-WILSONART;COLOR:D96-60;SHADOW;MATTE FINISH
FIXED WOOD PANEL (WD)
WD-1-PREMIUM GRADE WOOD, STAINED, COLOR: EXPRESSO
1. THE MANUFACTURER'S NAMES AND THEIR PRODUCTS
REFERENCED ONLY INDICATE THE COLOR, TEXTURE,
AND PATTERN REQUIRED FOR THE MATERIALS LISTED.
THE PRODUCTS FURNISHED SHALL MEET THE COLOR,
TEXTURE, AND PATTERN INDICATED AS WELL AS THE
MATERIAL QUALITY AND PERFORMANCE SPECIFIED IN
THE APPLICABLE TECHNICAL SPECIFICATIONS. THE
USE OF MANUFACTURER'S NAMES AND PRODUCTS DO
NOT PRECLUDE THE USE OF OTHER MANUFACTURER'S
PRODUCTS OF APPROVED EQUAL COLOR, TEXTURE,
AND/OR PATTERN IF ALL OTHER REQUIREMENTS ARE
MET.
2. VISIBLE GRILLES, DIFFUSERS, AND OTHER
MECHANICAL RELATED FINISH OPENING DEVICES
INCLUDING FIRE ALARMS SHALL BE PAINTED TO MATCH
THE COLOR OF THE ADJACENT SURFACE.
3. REFER TO APPROPRIATE ARCHITECTURAL AND
INTERIOR DRAWINGS AND DETAILS TO PROPERLY
ASSESS THE FULL EXTENT OF WORK REQUIRED.
SPECIFICALLY REFER TO THE REFLECTED CEILING
PLANS, AND BUILDING SECTIONS TO DETERMINE
HEIGHTS OF REQUIRED WALL MATERIALS, SPECIAL
CONDITIONS AND STRUCTURES, ETC.
4. REFER TO EXTERIOR ELEVATIONS FOR EXTERIOR
FINISH SELECTIONS.
5. PAINT ALL SOFFIT AND OVERHEAD CONDITIONS TO
MATCH ADJACENT SURFACES.
GENERAL NOTESCEILING FINISHES
ACOUSTIC CEILING TILE (ACT)
ACT-1-ARMSTRONG; 2'-0" X 2'-0" CEILING TILE; #1713 SCHOOL ZONE, FINE FISSURED, COLOR:WHITE;
7/8" EXPOSED TEE SUSPENSION SYSTEM; COLOR: WHITE
ACT-2 ARMSTRONG CEILINGS FORMATION; CEILING CLOUD; SIZE: 6'-0"X10'-0"X4"
PAINTED CEILING (PT)
PT-3-SHERWIN WILLIAMS; COLOR:SW 6023 SPARE WHITE;FOR FINISH RE:SPECS
BASE TREATMENTS
RESILIENT BASE (RB)
RB-1-ROPPE RUBBER FLOORING; 6" HIGH RUBBER COVE BASE; COLOR: 114 LUNAR DUST
CERAMIC TILE BASE (CT)
CT-4-DALTILE;CITY VIEW; COLORBODY PORCELAIN;HARBOUR MIST ACCENT;CY01;COVE BASE;
S-36C9T; 6" X 12" X 3/8"
FINISH LEGEND
EXTERIOR FINISHES
GUTTER (GT)
GT-1-GUTTERS, OPEN ENDED METAL GUTTER;COLOR: FACTORY FINISH SHALL MATCH
DREXEL METAL'S SIERRA TAN
STUCCO (ST)
ST-1-STUCCO, COLOR: SIERRA TAN
CONCRETE ROOF TILE (CRT)
CRT-1 - FLAT CONCRETE ROOF TILE; BORAL, SERIES: SAXONY 900 SLATE; SIZE: 12" X 17";
COLOR: DESERT TERRA COTTA
EXTERIOR PAINT (EPT)
EPT-1-SHERWIN WILLIAMS; COLOR:SW 7713 TAWNY TAN
CT-1, CERAMIC TILE SC-1,
SEALED
CONCRETE
CL DOOR
SCHLUTER
RENO-RAMP/-K
TRANSITION
3 125/256"
D
2 3
C
A
B
D E
S C
R
IP
T
IO
N D
A T
E M
A R
K
SHEET ID
S O
L
IC
IT
A
T
IO
N N
O
D R
A W
N B
Y
C H
E C
K E
D B
Y
D E
S
IG
N B
Y
S U
B M
IT
T
C O
N T
R A
C T
N O
S
IZ
E
A N
S I D
F
IL
E N
A M
E
D E
S
IG
N E
N G
IN
E
E R
IN
G
O F
F
IC
E N
E L
L
IS
A F
B N
E V
A D
A
A
IR
C O
M B
A T
C O
M M
A N
D
IS
S
U E
D A
T E
6 7 8 9 10
E
F
G
A -6
.D W
G
A-602
N E
L L
IS
A
IR
F O
R C
E B
A S
E N
E V
A
C B
U
IL
D
IN
G
R K
M F
A
IR
C O
M B
A T
C O
M M
A N
D
F
IN
IS
H
S C
H E
D U
L E
L
E G
E N
D
ROOM SCHEDULE
Name Number FLOOR FINISH WALL FINISH - EAST WALL FINISH - NORTH WALL FINISH - SOUTH WALL FINISH - WEST Base Finish CEILING FINISH CEILING HEIGHT CEILING MATERIAL COMMENTS
VESTIBULE 100 CGP PT-1 PT-1 PT-1 PT-1 RB-1 ACT-1 9'-0" ACT-1
LOBBY 101 CGP PT-1 PT-1 PT-2 PT-1 RB-1 ACT-1 10'-0" ACT-1
ID PROCESSING 102 CGP PT-1 PT-1/PT-2 PT-1 PT-1 RB-1 ACT-1 9'-0" ACT-1
OFFICE 103 CGP PT-1 PT-1 PT-1 PT-1 RB-1 ACT-1 9'-0" ACT-1
STORAGE 104 CGP PT-1 PT-1 PT-1 PT-1 RB-1 ACT-1 9'-0" ACT-1
JAN 105 CT-1 PT-1/CT-2 PT-1/CT-2 PT-1/CT-2 PT-1/CT-2 CT-1 PT-2 8'-0" GWB
MEN 106 CT-1 PT-1/CT-2 PT-1/CT-2 PT-1/CT-2 PT-1/CT-2 CT-1 PT-2 8'-0" GWB
WOMEN 107 CT-1 PT-1/CT-2 PT-1/CT-2 PT-1/CT-2 PT-1/CT-2 CT-1 PT-2 8'-0" GWB
COMM. 108 CS PT-1 PT-1 PT-1 PT-1 RB-1 N/A N/A N/A
MECH/ELEC. 109 CS PT-1 PT-1 PT-1 PT-1 RB-1 N/A N/A N/A
COVERED ENTRY 110 N/A N/A N/A N/A N/A N/A N/A N/A N/A
3" = 1'-0"A1
CT TO SC TRANSITION
0 1 1/2" 3" 6" 12"
PIPING SYSTEMS
GENERAL SYMBOLS
CONNECT NEW TO
EXISTING AT THIS POINT
DEMOLISH TO THIS POINT
# KEYNOTE
EQUIPMENT DESIGNATIONDWH-1
PLUMBING FIXTURE
DESIGNATION
P-1
DOMESTIC HOT WATER 120F
SANITARY SEWER (ABOVE SLAB)
SANITARY VENT
SS
V
DOMESTIC HOT WATER CIRCULATION
DOMESTIC COLD WATER
1.
2.
SANITARY SEWER (BELOW GROUND)SS
PIPING
FLOOR SINK
FLOOR DRAIN
ROOF DRAIN
HOSE BIBB AND WALL HYDRANT (PLAN)
LINE CLEANOUT
WALL CLEANOUT
VALVE, SEE
SPECIFICATIONS FOR VALVE
TYPE
CHECK VALVE
TWO WAY CONTROL VALVE
THREE WAY CONTROL VALVE
BALANCING VALVE
SOLENOID CONTROL VALVE
PRESSURE REDUCING VALVE
FLEXIBLE CONNECTION
TEST PLUG
PRESSURE GAUGE
MANUAL AIR VENT
PIPE BREAK
DIRECTION OF FLOW
PIPE UP
PIPE DOWN
PIPE T DOWN
PIPE T UP
PIPE CAP
UNION
REDUCER
PIPE ANCHOR
PIPE GUIDE
STRAINER
STRAINER WITH VALVE
AND HOSE CONNECTION
THERMOMETER OR SIGHT GLASS
PIPE SLOPE
BUTTERFLY VALVE
BALL VALVE
FLOOR, SURFACE & GROUND CLEANOUT
GAS PRESSURE REGULATING VALVE
GAS SHUTOFF VALVE
EARTHQUAKE VALVE
MUD VALVE
SOME ABBREVIATIONS AND SYMBOLS SHOWN ON THIS
SHEET MAY NOT BE USED IN THIS DRAWING SET.
ISOMETRIC DRAWINGS FOR DOMESTIC WATER AND
SANITARY SEWER ARE DIAGRAMMATIC AND ARE
INTENDED TO CONVEY SCOPE AND GENERAL
ARRANGEMENT ONLY. CONTRACTOR IS REPOSNIBLE
FOR FIELD VERIFICATION, FIELD ADJUSTMENTS AND
COORDINATION WITH ALL OTHER DISCIPLINES. ALL
PIPING SHALL BE INSTALLED PER MANUFACTURERS’
RECOMMENDATIONS, CONTRACT
SPECIFICATIONS/DOCUMENTS, APPLICABLE CODES AND
REGULATIONS.
HOSE BIBB AND WALL HYDRANT (DIAGRAM)
DIELECTRIC UNION
FLANGE
BLIND FLANGE
GENERAL NOTES
HB
PLUMBING ABBREVIATIONS PLUMBING SYMBOLS
HWC
HW
CW
LCO LINE CLEANOUT
MA MEDICAL AIR
MAX MAXIMUM
MBH THOUSAND BTU PER HOUR
MCA MINIMUM CIRCUIT AMPACITY
MIN MINIMUM
N NITROGEN
NC NORMALLY CLOSED
NO NORMALLY OPEN
NTS NOT TO SCALE
O2 OXYGEN
OD OVER FLOW DRAIN
P PUMP
PD PRESSURE DROP
PH PHASE
PRV PRESSURE REDUCING VALVE
RD ROOF DRAIN
RH RADIANT HEAT
RO REVERSE OSMOSIS
RPBFP REDUCED PRESSURE BACKFLOW
PREVENTER
RPM REVOLUTIONS PER MINUTE
S.P. STATIC PRESSURE
SD STORM DRAIN
SP SUMP PUMP
SS SANITARY SEWER
STD STANDARD
SW SOFT WATER
TDH TOTAL DYNAMIC HEAD
TYP TYPICAL
UNO UNLESS NOTED OTHERWISE
V VOLTS
V SANITARY VENT
VA VACUUM
VFD VARIABLE FREQUENCY DRIVE
VTR VENT THROUGH ROOF
W WASTE
WC WATER COLUMN
WCO WALL CLEANOUT
WG WATER GUAGE
WH WALL HYDRANT
WHA WATER HAMMER ARRESTER
ADJ ADJUSTABLE
AFF ABOVE FINISHED FLOOR
AMPS AMPERES
AS AIR SEPARATOR
AWS AUTOMATIC WATER SOFTENER
B BOILER
B.O.P. BOTTOM OF PIPE
BB BASEBOARD
BD BUILDING DRAIN
BFP BACKFLOW PREVENTER
BHP BRAKE HORSEPOWER
BTU BRITISH THERMAL UNIT
C COMMON
CA COMPRESSED AIR
CA (OF) COMPRESSED AIR OIL FREE
CD CONDENSATE DRAIN
CIRC CIRCULATING
CO CLEANOUT
CP CIRCULATING PUMP
CW DOMESTIC COLD WATER
DDC DIRECT DIGITAL CONTROL
DEG DEGREES
DEG F DEGREES FAHRENHEIT
DF DIESEL FUEL
DHW DOMESTIC HOT WATER
DI DIONIZED WATER
DN DOWN
DWH DOMESTIC HOT WATER HEATER
DXE DOMESTIC HOT WATER HEAT
EXCHANGER
EA EACH
ET EXPANSION TANK
EWH ELECTRIC WATER HEATER
F FAHRENHEIT
FCO FLOOR CLEANOUT
FD FLOOR DRAIN
FPM FEET PER MINUTE
G NATURAL GAS
GA GAUGE
GAS GASOLINE
GCO GRADE CLEANOUT
GR GREASE WASTE
HB HOSE BIBB
HD HUB DRAIN
HW DOMESTIC HOT WATER
HWC DOMESTIC HOT WATER,
CIRCULATING
Hz HERTZ
I.E. INVERT ELEVATION
kPA KILOPASCALS kW KILOWATT
D
2 3
C
A
B
DE
SC
RI
PT
IO
N
DA
TE
M
AR
K
SHEET ID
SO
LI
CI
TA
TI
O
N
NO
CO
NT
RA
CT
N O
SI
ZE
AN
SI
D
FI
LE
N
AM
E:
D
ES
IG
N
E N
G
IN
EE
R
IN
G
O
FF
IC
E
N
EL
LI
S
AF
B
, N
EV
AD
A
AI
R
C O
M B
AT
C
O M
M
AN
D
IS
SU
E
DA
TE
6 7 8 9 10
E
F
G
DE
SI
G N
BY
DR
AW
N
BY
CH
EC
KE
D
BY
SU
BM
IT
TE
D
P-
1.
DW
G
P-001
N
EL
LI
S
AI
R
F O
R C
E
BA
SE
, N
EV
AD
A
VC
C B
U
IL
D
IN
G
R
KM
F1
D
ES
IG
N E
N G
IN
EE
R
IN
G
O
FF
IC
E
PL
U
M
BI
N G
L
EG
EN
D
A
BB
R
EV
IA
TI
O
N
P-1 P-1
P-2
P-3
P-3
P-4A P-4
P-5
1 1/2" CW
4" SS
IE = 96.50'
LOBBY
VESTIBULE
STORAGE
OFFICE
ID PROCESSING
JAN
MEN
106WOMEN
MECH/ELEC.
3" FCO UNDER
DRINKING FOUNTAIN
3" FD 3" FD
3" FS
1 2 3 4
D
C
B
A
P-6
COMM.
PATIO
1" CW
WH WH
3/4" CW
3/4" CW
EWH-04
EWH-03
EWH-02
EWH-01
D
2 3
C
A
B
D E
S C
R
IP
T
IO
N D
A T
E M
A R
K
SHEET ID
S O
L
IC
IT
A
T
IO
N N
O
D R
A W
N B
Y
C H
E C
K E
D B
Y
D E
S
IG
N B
Y
S U
B M
IT
T
C O
N T
R A
C T
N O
S
IZ
E
A N
S I D
F
IL
E N
A M
E
D E
S
IG
N E
N G
IN
E
E R
IN
G
O F
F
IC
E
N E
L L
IS
A
F B
N
E V
A D
A
A
IR
C O
M B
A T
C O
M M
A N
D
IS
S
U E
D A
T E
6 7 8 9 10
E
F
G
P -1
.D W
G
P-101
N E
L L
IS
A
IR
F O
R C
E B
A S
E N
E V
A
C B
U
IL
D
IN
G
R K
M F
D E
S
IG
N E
N G
IN
E
E R
IN
G
O F
F
IC
E
P L U
M B
IN
G
F
IR
S T
F L O
O R
P L A
N
1/4" = 1'-0"A1
PLUMBING FIRST FLOOR PLAN
NORTH
350 CFM
SD-1, 10ø
TYPE, REFER TO DIFFUSER,
REGISTER AND GRILLE
SCHEDULE
AIR QUANTITY
GENERAL SYMBOLS
DUCTWORK
M
12x12
BD
MOTORIZED DAMPER
BACKDRAFT OR
BAROMETRIC DAMPER
SUPPLY AIR - DUCT DOWN
EXHAUST AIR - DUCT
DOWN
RETURN AIR - DUCT DOWN
RECTANGULAR INSIDE BRANCH DUCT
SIZE (FIRST FIGURE IS SIDE SHOWN)
FLEXIBLE DUCT CONNECTION
DIRECTION OF FLOW
MANUAL VOLUME DAMPER
MITERED ELBOW WITH
TURNING VANES
RADIUS ELBOW WITHOUT
TURNING VANES, UNLESS NOTED
OTHERWISE
RECTANGULAR MAIN DUCT
WITH RECTANGULAR
BRANCH, BOOT FITTING
ROUND MAIN DUCT WITH
ROUND BRANCH, CONICAL
FITTING
RETURN AIR - DUCT UP
SUPPLY AIR - DUCT UP
DIFFUSERS, REGISTER AND GRILLE
CEILING SUPPLY AIR DIFFUSER 4-WAY
THROW UNLESS OTHERWISE INDICATED
(SHADED QUADRANT INDICATES NO
FLOW)
CEILING RETURN AIR GRILLE
SIDEWALL AIR OUTLET
SIDEWALL AIR INLET
FIRE PROTECTION
FIRE DAMPER
CEILING EXHAUST AIR GRILLE
FLEXIBLE DUCTWORK
NECK SIZE (IN.)
EXHAUST AIR - DUCT UP
SMOKE DAMPER
FIRE/ SMOKE DAMPER
CONNECT NEW TO
EXISTING AT THIS
POINT
DEMOLISH TO THIS
POINT
# KEYNOTE
EQUIPMENT DESIGNATIONAHU-1RECTANGULAR MAIN DUCT WITH
ROUND BRANCH, CONICAL
FITTING
RECTANGULAR MAIN DUCT WITH
ROUND BRANCH, 45° FITTING
MANUAL VOLUME DAMPER
1. SOME ABBREVIATIONS AND SYMBOLS SHOWN
ON THIS SHEET MAY NOT BE USED IN THIS
DRAWING SET.
CONTROLS SYMBOLS (CONTINUED)
12Ø ROUND INSIDE BRANCH DUCT SIZE
(TYP. #)
QUANTITY
36x24 SA
RECTANGULAR INSIDE MAIN DUCT
SIZE (FIRST FIGURE IS SIDE SHOWN)
24Ø SA ROUND INSIDE MAIN DUCT SIZE
AIR DEVICE DESIGNATION
CONTROL PANEL
MANUAL DAMPER
CONTROLS SYMBOLS (CONTINUED)
VARIABLE SPEED MOTOR
CONTROLLER
TWO WAY CONTROL VALVE
THREE WAY CONTROL VALVE
STARTER
HOT WATER HEATING COIL
CHILLED WATER COOLING COIL
SPACE THERMOSTAT - MOUNT
BOTTOM AT 4'-6" ABOVE FLOOR
UNIT MOUNTED THERMOSTAT
DIGITAL OUTPUT
DIGITAL INPUT
ANALOG INPUT
ANALOG OUTPUT
SPACE TEMPERATURE SENSOR -
MOUNT BOTTOM AT 4'-6" ABOVE
FLOOR
SPACE OCCUPANCY SENSOR -
COORDINATE WITH ELECTRICAL
SPACE HUMIDITY SENSOR -
MOUNT BOTTOM AT 4'-6" ABOVE
FLOOR
SPACE CARBON MONOXIDE SENSOR
SPACE CARBON DIOXIDE
SENSOR - MOUNT BOTTOM AT
4'-6" ABOVE FLOOR
ELECTRICAL WIRING
CONDUCTORS AS REQUIRED
T
OS
HS
CO
C02
T
T
DI
DO
AI
AO
C NC
NO
STARTER
VSD
H
C
C
C
INTERLOCK WIRING
VARIABLE SPEED MOTOR
CONTROLLERVFD
FILTER
PUMP
ULTRAVIOLET CONTROLLERUVC
SPACE DIFFERENTIAL PRESSURE
INDICATOR - MOUNT BOTTOM AT
4'-6" ABOVE FLOOR
P
DIFFERENTIAL PRESSURE TRANSMITTER
CONTACT
CONTROL PANEL -
MOUNT CONTROL PANEL AT 4'8" ABOVE
FLOOR TO CENTER OF CONTROL PANEL
EMERGENCY POWER OFF SWITCH -
MOUNT BOTTOM AT 4'-0" ABOVE FLOOR
BOILER POWER OFF SWITCH -
MOUNT BOTTOM AT 4'-0" ABOVE
FLOOR
MANUAL OVERRIDE SWITCH -
MOUNT BOTTOM AT 4'-0" ABOVE
FLOOR
DPT
CP
EPO
BPO
OR
FA FIRE ALARM CONTROL MODULE
S START/STOP
GENERAL NOTES
S
F
FS
DUCTWORK (CONTINUED)
CONTROLS SYMBOLS
STRAP ON AQUASTAT
FLOW PROVING SWITCH DIFFERENTIAL PRESSURE
CARBON DIOXIDE DETECTOR
CARBON MONOXIDE DETECTOR
FLUID FLOW TRANSMITTER
FLUID FLOW MEASURING DEVICE
CONTROL DAMPER
PNEUMATIC MAIN
FLOW PROVING SWITCH PADDLE TYPE
CURRENT SENSING RELAY
RELAY
SMOKE DETECTOR
TEMPERATURE SENSOR
DIFFERENTIAL PRESSURE SWITCH
ELECTRIC PNEUMATIC TRANSDUCER
AIR FLOW TRANSMITTER
AIR FLOW MEASURING STATION
OCCUPANCY SENSOR
DAMPER ACTUATOR END SWITCH
HUMIDITY SENSOR
M
EPT
SD
CO
CO2
AM
T
FPS
CSR
R
DPS
FMT
FPS
AS
AFT
OS
ES
H
DPT DIFFERENTIAL PRESSURE TRANSMITTER
FLOW SENSORFS
A GENERAL ALARM
SPEED INDICATIONSPD
kPa KILOPASCALS kW KILOWATT
L LOUVER
LAT LEAVING AIR
TEMPERATURE
LDB LEAVING DRY BULB
TEMPERATURE
LRA LOCKED ROTOR AMPS
LVG LEAVING
LWB LEAVING WET BULB
TEMPERATURE
LWT LEAVING WATER
TEMPERATUTE
MAX MAXIMUM
MBH THOUSAND BTU PER
HOUR
MC MECHANICAL
CONTRACTOR
MCA MINIMUM CIRCUIT
AMPACITY
MIN MINIMUM
MUA MAKE-UP AIR
NC NORMALLY CLOSED
NO NORMALLY OPEN
NTS NOT TO SCALE
OA/OSA OUTSIDE AIR
OAT OUTSIDE AIR
TEMPERATURE
P PUMP
Pa PASCALS
PD PRESSURE DROP
PF PRE FILTER
PH PHASE
PSI POUNDS PER SQUARE
INCH
PSIG PSI GUAGE
RA RETURN AIR
RD RETURN DIFFUSER
(GRILLE)
RH RELATIVE HUMIDITY
RHC REHEAT COIL
RLA RUNNING LOAD AMPS
RPM REVOLUTIONS PER
MINUTE
SA SUPPLY AIR
SD SUPPLY DIFFUSER
SF SUPPLY FAN
SG SUPPLY GRILLE
SP STATIC PRESSURE
SR SUPPLY REGISTER
TEMP TEMPERATURE
TG TRANSFER GRILLE
TSP TOTAL STATIC PRESSURE
TYP TYPICAL
UH UNIT HEATER
UMCS UTILITY MONITORING AND
CONTROL SYSTEM
UNO UNLESS NOTED
OTHERWISE
V VOLTS
WB WET BULB
TEMPERATURE
WC WATER COLUMN
WG WATER GUAGE
ADJ ADJUSTABLE
AFF ABOVE FINISHED FLOOR
ATC ACOUSTICAL TILE
CEILING
AV AIR VENT
B.O.D. BOTTOM OF DUCT
B.O.P. BOTTOM OF PIPE
BAS BUILDING AUTOMATION
SYSTEM
BDD BACK DRAFT DAMPER
BHP BRAKE HORSPOWER
BMS BUILDING MANAGEMENT
SYSTEM
BTU BRITISH THERMAL UNIT
BTUH BTU PER HOUR
CC COOLING COIL
CD CONDENSATE DRAIN
CFM CUBIC FEET PER MINUTE
CO CARBON MONOXIDE
CO2 CARBON DIOXIDE
COND CONDENSATE
CW DOMESTIC COLD WATER
DB DRY BULB
dB DECIBELS
DDC DIRECT DIGITALCONTROL
DEG DEGREES
DEG F DEGREES FAHRENHEIT
DN DOWN
EA EXHAUST AIR
EAT ENTERING AIR
TEMPERATURE
EAU EXHAUST AIR UNIT
EDB ENTERING DRY BULB
TEMPERATURE
EF EXHAUST FAN
EG EXHAUST GRILLE
EMCS ENERGY MANAGEMENT
CONTROL SYSTEM
ERV ENERGY RERCOVERY
VENTILATOR
ESP EXTERNAL STATIC
PRESSURE
ET EXPANSION TANK
EWB ENTERING WET BULB
TEMPERATURE
EWT ENTERING WATER
TEMPERATURE
F DEGREES FAHRENHEIT
FD FIRE DAMPER
FF FINAL FILTER
FLA FULL LOAD AMPS
FPM FEET PER MINUTE
FT FEET
FT HD FEET HEAD
GA GAUGE
GC GENERAL CONTRACTOR
GPM GALLONS PER MINUTE
HC HEATING COIL
HP HORSEPOWER
HP HEAT PUMP
HR HOUR
HRCP HEAT RECOVERY PUMP
HX HEAT EXCHANGER
Hz HERTZ
IAQ INDOOR AIR QUALITY
IN W.G. INCHES OF WATER
GAUGE
D
2 3
C
A
B
D E
S C
R
IP
T
IO
N D
A T
E M
A R
K
SHEET ID
S O
L
IC
IT
A
T
IO
N N
O
D R
A W
N B
Y
C H
E C
K E
D B
Y
D E
S
IG
N B
Y
S U
B M
IT
T
C O
N T
R A
C T
N O
S
IZ
E
A N
S I D
F
IL
E N
A M
E
D E
S
IG
N E
N G
IN
E
E R
IN
G
O F
F
IC
E N
E L
L
IS
A F
B N
E V
A D
A
A
IR
C O
M B
A T
C O
M M
A N
D
IS
S
U E
D A
T E
6 7 8 9 10
E
F
G
M -0
.D
W G
M-001
N E
L L
IS
A
IR
F O
R C
E B
A S
E N
E V
A D
A
V C
C B
U
IL
D
IN
G
R K
M F
D E
S
IG
N E
N G
IN
E
E R
IN
G
O F
F
IC
E
M E
C H
A N
IC
A
L L
E G
E N
D
A B
B R
E V
IA
T
IO
N
1. THESE LEGENDS ARE COMPOSED OF STANDARD SYMBOLS AND ARE PERTINENT TO THE
CONDITIONS ON THIS SET OF DRAWINGS TO THE EXTENT APPLICABLE. ADDITIONAL
LEGENDS AND/OR OTHER LEGENDS MAY APPEAR IN THIS SET OF DRAWINGS TO INDICATE
SPECIFIC CONDITIONS IN LIEU OF SYMBOLS SHOWN.
2. PROVIDE ALL MATERIALS AND EQUIPMENT AND PERFORM ALL LABOR REQUIRED TO
INSTALL COMPLETE AND OPERABLE MECHANICAL SYSTEMS AS INDICATED ON THE
DRAWINGS, AS SPECIFIED AND AS REQUIRED BY APPLICABLE CODES AND REGULATIONS.
3. CONTRACT DOCUMENT DRAWINGS FOR MECHANICAL WORK (HVAC, PLUMBING, AND FIRE
PROTECTION) ARE DIAGRAMMATIC AND ARE INTENDED TO CONVEY SCOPE AND GENERAL
ARRANGEMENT ONLY. THE DRAWINGS DO NOT NECESSARILY INDICATE EVERY REQUIRED
DUCT, PIPE, OFFSET, FITTING, TRANSITION, ETC. REGARDLESS HOW INDICATED, THE
CONTRACTOR SHALL COORDINATE THE PIPING, DUCTWORK AND EQUIPMENT LOCATIONS
AND ROUTES IN ACCORDANCE WITH ALL MANUFACTURER'S RECOMMENDATIONS AND AS
REQUIRED TO PROVIDE SERVICE AND MAINTENANCE CLEARANCE. PROVIDE ITEMS NOT
SPECIFICALLY MENTIONED IN SPECIFICATIONS OR NOTED ON THE DRAWINGS, BUT WHICH
ARE NECESSARY TO MAKE A COMPLETE AND OPERATIONAL WORKING INSTALLATION.
PROVIDE ALTERNATE PIPING ROUTES, DUCTWORK ROUTES, ADDITIONAL OFFSETS AND/OR
FITTINGS AS REQUIRED FOR DUCTWORK AND PIPING.
4. COORDINATE ALL EQUIPMENT CONNECTIONS WITH MANUFACTURER'S CERTIFIED
DRAWINGS. COORDINATE AND PROVIDE ALL DUCT AND PIPING TRANSITIONS REQUIRED
FOR FINAL EQUIPMENT CONNECTIONS TO FURNISHED EQUIPMENT.
5. INSTALL ALL MECHANICAL EQUIPMENT AND APPURTENANCES IN ACCORDANCE WITH
MANUFACTURER'S RECOMMENDATIONS, CONTRACT DOCUMENTS, AND APPLICABLE
CODES AND REGULATIONS. PROVIDE PROPER UTILITIES AND FINAL CONNECTIONS PER
MANUFACTURER'S RECOMMENDATIONS. FINAL CONNECTION SHALL INCLUDE ANY
ADAPTERS, NIPPLES, SHUTOFF VALVES, PRESSURE REGULATING VALVES, DIRT LEGS,
SHOCK ABSORBERS, BACKFLOW PREVENTION DEVICES, ETC., AS REQUIRED TO PROVIDE
A FULLY OPERATIONAL SYSTEM. CONNECT ALL EQUIPMENT DRAINS FULL SIZE TO HUB
AND/OR FLOOR DRAIN WITH MINIMUM 1 INCH GAP FOR INDIRECT CONNECTION, UNLESS
OTHERWISE NOTED.
6. PROVIDE VIBRATION ISOLATION FOR ALL MECHANICAL EQUIPMENT TO PREVENT
TRANSMISSION OF VIBRATION TO BUILDING STRUCTURE. PROVIDE VIBRATION ISOLATORS
FOR ALL PIPING SUPPORTS CONNECTED TO AND WITHIN 50 FEET OF ISOLATED
EQUIPMENT (EXCEPT AT BASE ELBOW SUPPORTS AND ANCHOR POINTS) THROUGHOUT
MECHANICAL EQUIPMENT ROOMS.
7. THE LOCATION OF EXISTING UTILITIES SHOWN IS AN APPROXIMATION ONLY. THE
CONTRACTOR SHALL DETERMINE THE EXACT LOCATION OF ALL EXISTING UTILITIES
BEFORE COMMENCING WORK. THE CONTRACTOR SHALL PAY FOR AND REPAIR ALL
DAMAGES CAUSED BY FAILURE TO EXACTLY LOCATE AND PRESERVE ANY AND ALL
UTILITIES UNLESS OTHERWISE INDICATED. IF IT BECOMES NECESSARY DURING
DEMOLITION TO TEMPORARILY REMOVE ANY EQUIPMENT, PIPING, ETC. WHICH IS NOT
SPECIFICALLY NOTED TO BE REMOVED (THEREBY IMPLYING THAT THEY ARE TO BE LEFT
FOR FUTURE USE), REINSTALL SAID SYSTEMS TO FULLY OPERABLE CONDITION IN THEIR
ORIGINAL LOCATIONS.
8. WHEN MECHANICAL WORK (HVAC, PLUMBING, SHEET METAL, FIRE PROTECTION, ETC.) IS
SUBCONTRACTED, IT SHALL BE THE GENERAL CONTRACTOR’S RESPONSIBILITY TO
COORDINATE SUBCONTRACTORS AND THE ASSOCIATED CONTRACTS. WHEN
DISCREPANCIES ARISE PERTAINING TO WHICH CONTRACTOR PROVIDES A PARTICULAR
ITEM OF THE MECHANICAL CONTRACT OR WHICH CONTRACTOR PROVIDES FINAL
CONNECTIONS FOR A PARTICULAR ITEM OF THE MECHANICAL CONTRACT, IT SHALL BE
BROUGHT TO THE ATTENTION OF THE GENERAL CONTRACTOR, WHOSE DECISION SHALL
BE FINAL.
9. MECHANICAL PLANS INDICATE ONLY THE APPROXIMATE LOCATION OF ARCHITECTURAL,
INTERIOR, FURNISHINGS, ELECTRICAL, MECHANICAL AND OTHER EQUIPMENT, AS WELL AS
THE RELATED MECHANICAL REQUIREMENTS NECESSARY TO SUPPORT AND ACCESS SUCH
EQUIPMENT. THE FINAL POSITIONING OF THESE ITEMS IS DEPENDENT UPON THE
EQUIPMENT PROVIDED BY CONTRACTOR IN ACCORDANCE WITH ALL RELEVANT BUILDING
CODES AND MUST BE DETERMINED BY THE PROJECT SITE CONDITIONS. THE
CONTRACTOR SHALL BE RESPONSIBLE FOR COORDINATING WORK BETWEEN
SUBCONTRACTORS AND CRAFTS IN THIS REGARD, AND PROVIDING NECESSARY SPACE
ALLOCATION AND DIMENSIONS IN A TIMELY MANNER TO ALL PARTIES INVOLVED TO
ENSURE PROPER COORDINATION.
10. COORDINATE CONSTRUCTION OF ALL MECHANICAL WORK WITH ARCHITECTURAL,
STRUCTURAL, CIVIL, ELECTRICAL WORK, ETC., SHOWN ON OTHER CONTRACT DOCUMENT
DRAWINGS.
11. ALL TESTS SHALL BE COMPLETED BEFORE ANY MECHANICAL EQUIPMENT OR PIPING
INSULATION IS APPLIED.
12. LOCATE ALL TEMPERATURE, PRESSURE, AND FLOW MEASURING DEVICES IN ACCESSIBLE
LOCATIONS WITH STRAIGHT SECTION OF PIPE OR DUCT UP- AND DOWNSTREAM AS
RECOMMENDED BY THE MANUFACTURER. EXTEND PROBES AND SENSING APPARATUS AS
NEEDED TO ACCOMMODATE PIPE AND DUCT INSULATION AND/OR COVERING.
13. TESTING, ADJUSTING, AND BALANCING AGENCY SHALL BE A MEMBER OF THE ASSOCIATED
AIR BALANCE COUNCIL (AABC) OR THE NATIONAL ENVIRONMENTAL BALANCING BUREAU
(NEBB). TESTING, ADJUSTING, AND BALANCING SHALL BE PERFORMED IN ACCORDANCE
WITH THE AABC OR NEBB STANDARDS.
14. WHERE TWO OR MORE ITEMS OF THE SAME TYPE OF EQUIPMENT ARE REQUIRED, THE
PRODUCT OF ONE MANUFACTURER SHALL BE USED, UNLESS SPECIFICALLY NOTED ON
DRAWINGS SCHEDULES.
15. FIELD VERIFY AND COORDINATE ALL DUCT AND PIPING DIMENSIONS BEFORE
FABRICATION.
16. CONCRETE HOUSEKEEPING PADS TO SUIT MECHANICAL EQUIPMENT SHALL BE SIZED AND
LOCATED BY THE MECHANICAL CONTRACTOR. MINIMUM CONCRETE PAD THICKNESS
SHALL BE 6 INCHES. PAD SHALL EXTEND BEYOND THE EQUIPMENT A MINIMUM OF 6 INCHES
ON EACH SIDE. CONCRETE HOUSEKEEPING PADS SHALL BE PROVIDED BY THE GENERAL
CONTRACTOR. IT SHALL BE THE RESPONSIBILITY OF THE MECHANICAL CONTRACTOR TO
COORDINATE SIZE AND LOCATION OF CONCRETE HOUSEKEEPING PADS WITH GENERAL
CONTRACTOR.
17. ALL MISCELLANEOUS STEEL REQUIRED TO ENSURE PROPER INSTALLATION AND AS
SHOWN IN DETAILS FOR PIPING, DUCTWORK, AND EQUIPMENT (UNLESS OTHERWISE
NOTED) SHALL BE FURNISHED AND INSTALLED BY THE MECHANICAL CONTRACTOR.
18. ALL DUCTWORK, PIPING AND EQUIPMENT SUPPORTED FROM STRUCTURAL STEEL SHALL
BE COORDINATED WITH GENERAL CONTRACTOR. ALL ATTACHMENTS TO STEEL BAR
JOISTS, TRUSSES, OR JOIST GIRDERS SHALL BE AT PANEL POINTS. PROVIDE BEAM
CLAMPS MEETING MSS STANDARDS. WELDING TO STRUCTURAL MEMBERS SHALL NOT BE
PERMITTED.
19. LOCATIONS AND SIZES OF ALL FLOOR, WALL, AND ROOF OPENINGS SHALL BE
COORDINATED WITH ALL OTHER TRADES INVOLVED. IT IS REQUIRED THAT THE
CONTRACTOR PHYSICALLY MEASURE ALL EXISTING OPENINGS AND DIMENSIONS BEFORE
ORDERING ANY EQUIPMENT.
20. ALL OPENINGS IN FIRE WALLS DUE TO DUCTWORK, PIPING, CONDUIT, ETC., SHALL BE FIRE
STOPPED WITH A PRODUCT SIMILAR TO 3M FIRE BARRIER SEALANT CP 25WB OR
APPROVED EQUAL. ALL OPENINGS ON FIRE WALLS SHALL BE PROVIDED WITH FIRE
DAMPER SUITABLE FOR THE WALL RATING AS REQUIRED BY INTERNATIONAL MECHANICAL
CODE AND NFPA 90A.
21. ALL STRUCTURAL PENETRATIONS (SLEEVES, BLOCKOUTS, ETC.) ARE TO BE LOCATED AND
COORDINATED IN THE FIELD IN RELATION TO THE REQUIREMENTS OF FINAL EQUIPMENT
AND FIXTURES SELECTED.
22. INTERIOR DUCT DIMENSIONS ARE SHOWN. EXTERIOR DUCT DIMENSIONS SHALL BE
LARGER TO ACCOMMODATE ACOUSTICAL DUCT LINER AS NEEDED.
23. ALL FLEXIBLE DUCT RUN-OUTS SHALL BE FACTORY PRE-INSULATED, NO LONGER THAN
5'-0".
24. ALL MITERED SHEET METAL ELBOWS IN SUPPLY DUCTWORK SHALL BE CONSTRUCTED
WITH AIRFOIL TURNING VANES.
25. ROUND DUCT SIZES TO DIFFUSERS SHALL BE THE SAME SIZE AS THE DIFFUSER NECK.
26. ACCESS DOORS SHALL BE PROVIDED IN THE DUCTWORK AT ALL AIR FLOW MEASURING
DEVICES, AUTOMATIC DAMPERS, FIRE DAMPERS, COILS, THERMOSTATS AND ANY OTHER
APPARATUS REQUIRING SERVICE AND INSPECTION. ENSURE ACCESS DOORS CAN BE
FULLY OPENED WITHOUT CONFLICTS AND ARE LARGE ENOUGH TO SERVICE THE ITEMS
BEHIND THE DOOR.
27. ALL MANUAL VOLUME CONTROL DAMPERS LOCATED ABOVE GYPBOARD CEILING OR
GYPBOARD CORRIDOR CAP SHALL INCLUDE RACK AND PINION CABLE CONTROL
ADJUSTMENT SYSTEM SO AS TO BE ADJUSTABLE WITH A SOCKET WRENCH FROM BELOW.
COORDINATE CEILING LOCATIONS WITH ARCHITECTURAL REFLECTED CEILING PLAN.
28. ALL MECHANICAL EQUIPMENT REQUIRING MAINTENANCE ACCESS SHALL BE PROVIDED
WITH MEANS OF ACCESS AS REQUIRED BY INTERNATIONAL MECHANICAL CODE, WHETHER
OR NOT SUCH PROVISION (SUCH AS AN ACCESS PANEL) IS SHOWN ON THE DRAWINGS. IN
ADDITION, VERIFY MANUFACTURER REQUIRED CLEARANCES ARE MAINTAINED.
COORDINATE WITH ARCHITECTURAL DISCIPLINE AS REQUIRED.
29. ALL EQUIPMENT, VALVES, FANS AND DAMPERS INSTALL ABOVE CEILINGS SHALL BE
ACCESSIBLE AND MEET MANUFACTURER'S CLEARANCE REQUIREMENTS FOR SERVICE AND
COIL PULL. COORDINATE ALL ACCESS PANELS IN CEILINGS OR WALLS WITH
ARCHITECTURAL DRAWINGS FOR PROPER INSTALLATION.
30. SEE PLUMBING PLANS FOR CONDENSATE DRAIN PIPING. COORDINATE SIZE AND ROUTING
WITH EQUIPMENT INSTALLED.
31. COORDINATE FINAL GRILLE, REGISTER AND DIFFUSER LAYOUT WITH ARCHITECTURAL
REFLECTED CEILING PLANS.
32. ALL PIPING, EQUIPMENT OR PORTIONS OF DUCTWORK VISIBLE THROUGH CEILING SLOTS,
GRILLES OR DIFFUSERS IN FINISHED AREAS SHALL BE PAINTED FLAT BLACK.
33. ALL DIFFUSERS INSTALLED IN LAY-IN CEILINGS SHALL BE FOUR-WAY PATTERN UNLESS
NOTED OTHERWISE. IN ALL CEILING DIFFUSERS IN CORRIDOR CEILINGS PROVIDE TWO-
WAY DIFFUSERS WITH BLOW PARALLEL TO WALL SURFACE. FOR CEILING DIFFUSERS
WITHIN THREE FEET OF THE WALL, OMIT FLOW VANES DISCHARGING TOWARDS THE
WALL(S).
34. ALL CONTROL WIRE AND CONDUIT SHALL COMPLY WITH THE NATIONAL ELECTRIC CODE
AND DIVISION 26 OF THE SPECIFICATIONS.
35. COORDINATE VOLTAGE AND PHASE OF ALL MECHANICAL EQUIPMENT WITH ELECTRICAL,
THE ELECTRICAL CONTRACTOR AND THE ELECTRICAL CONTRACT DOCUMENTS PRIOR TO
PURCHASE OF ANY EQUIPMENT.
36. DO NOT RUN PIPING THROUGH THE COMMUNICATIONS ROOM OR OVER ELECTRICAL
GEAR.
37. COORDINATE LOCATIONS OF ALL VARIABLE FREQUENCY DRIVES WITH ELECTRICAL
CONTRACTOR.
38. ALL VFD MOTORS SHALL HAVE FACTORY INSTALLED SHAFT GROUNDING RINGS, IF
FACTORY INSTALLATION IS NOT AN OPTION THEN SHAFT GROUNDING RINGS SHALL BE
PROVIDED AND FIELD INSTALLED.
39. PROVIDE SHUT-OFF AND BALANCING VALVES FOR ALL PIECES OF EQUIPMENT. PROVIDE
SHUT-OFF VALVES AT BRANCHES AND EQUIPMENT.
40. PROVIDE BALANCING DAMPERS AT ALL BRANCHES AND EACH INLET/OUTLET FOR ALL
SUPPLY AND EXHAUST DUCT SYSTEMS, EXCEPT AS NOTED OR PROHIBITED BY THE
INTERNATIONAL MECHANICAL CODE.
GENERAL MECHANICAL NOTES
D
2 3
C
A
B
D E
S C
R
IP
T
IO
N D
A T
E M
A R
K
SHEET ID
S O
L
IC
IT
A
T
IO
N N
O
D R
A W
N B
Y
C H
E C
K E
D B
Y
D E
S
IG
N B
Y
S U
B M
IT
T
C O
N T
R A
C T
N O
S
IZ
E
A N
S I D
F
IL
E N
A M
E
D E
S
IG
N E
N G
IN
E
E R
IN
G
O F
F
IC
E N
E L
L
IS
A F
B N
E V
A D
A
A
IR
C O
M B
A T
C O
M M
A N
D
IS
S
U E
D A
T E
6 7 8 9 10
E
F
G
M -0
.D
W G
M-002
N E
L L
IS
A
IR
F O
R C
E B
A S
E N
E V
A
C B
U
IL
D
IN
G
R K
M F
D E
S
IG
N E
N G
IN
E
E R
IN
G
O F
F
IC
E
M E
C H
A N
IC
A
L G
E N
E R
A L N
O T
E
F F F
A
2 3 4
B
C
DOAS-1
HP-1
SD-1
225 CFM
SD-1
225 CFM
SD-1
225 CFM
SD-1
225 CFM
x1
S
A
8x12 SA 14x12 SA ø
S A ø
S A ø
S A ø
S A
SD-1
130 CFM
SD-1
130 CFM
SD-1
200 CFM
SD-1
200 CFM
SD-1
200 CFM
SD-1
200 CFM
SD-1
100 CFM
18x12 SA 14x12 SA ø
S A ø
S A
RD-1
800 CFM
RD-1
630 CFM
RD-1
630 CFM
ø
O S
A
8ø OSA
SD-1
200 CFM
SD-1
50 CFM
ED-1
75 CFM
ED-1
75 CFM
ED-1
75 CFM
8x8 EA x8
E A
CU-1
AC-1
UH-1
VESTIBULE
LOBBY
ID PROCESSING
OFFICE
WOMEN
MEN
JAN
COMM.
MECH/ELEC.
T
SD-2
50 CFM
16x10 RA 24x12 RA
16x12 RA
18x20 RA x1
R
A
UH-2
6ø OSA
8x8 EA
8x8 EA
8" OSA DUCT
UP TO ROOF
(GH-1)
D
8" EA THROUGH WALL
PROVIDE WALL CAP
SD-4
150 CFM
D
2 3
C
A
B
D E
S C
R
IP
T
IO
N D
A T
E M
A R
K
SHEET ID
S O
L
IC
IT
A
T
IO
N N
O
D R
A W
N B
Y
C H
E C
K E
D B
Y
D E
S
IG
N B
Y
S U
B M
IT
T
C O
N T
R A
C T
N O
S
IZ
E
A N
S I D
F
IL
E N
A M
E
D E
S
IG
N E
N G
IN
E
E R
IN
G
O F
F
IC
E N
E L
L
IS
A F
B N
E V
A D
A
A
IR
C O
M B
A T
C O
M M
A N
D
IS
S
U E
D A
T E
6 7 8 9 10
E
F
G
M -1
.D
W G
M-101
N E
L L
IS
A
IR
F O
R C
E B
A S
E N
E V
A
C B
U
IL
D
IN
G
R K
M F
D E
S
IG
N E
N G
IN
E
E R
IN
G
O F
F
IC
E
M E
C H
A N
IC
A
L F
L O
O R
P L A
N
1/4" = 1'-0"A1
MECHANICAL FLOOR PLAN
GENERAL NOTES:
1. SEE SHEETS M-001 AND M-002 FOR LEGEND,
ABBREVIATIONS, AND GENERAL NOTES.
2. ALL DUCT IN FINISHED AREAS SHALL BE
CONCEALED.
3. EXTERNALLY INSULATE ALL DUCTWORK IN
ACCORDANCE WITH ASHRAE 90.1.
4. PROVIDE EQUIPMENT PADS FOR GROUND
MOUNTED EQUIPMENT.
MOLDED CASE CIRCUIT BREAKER, FIXED TRIP.
THREE POLE UNLESS DESIGNATED "1P" OR "2P"
MOLDED CASE CB OF A GIVEN FRAME SIZE
WITH ADJUSTABLE TRIP SETTINGS
NORMALLY OPEN MOMENTARY PUSHBUTTON
NORMALLY CLOSED MOMENTARY PUSHBUTTON
NORMALLY OPEN CONTACTS
NORMALLY CLOSED CONTACTS
ELECTRICAL METER
FUSE, SIZE AS INDICATED
SURGE ARRESTOR - VOLTAGE RATING AND
CLASS AS NOTED
GROUND CONNECTION - TO STANDARD ROD
TYPE ELECTRODE TO NEAREST STRUCTURE
STEEL
(#6 MIN. CONDUCTOR IF NOT SHOWN)
SS
ONE-LINE DIAGRAM SYMBOLS
POWER TRANSFORMER, DELTA-WYE
CONFIGURATION
MOTOR - EQUIPMENT SCHEDULE
IDENTIFICATION AS SHOWN
M
FUSED DISCONNECT SWITCH, SIZE AND
TYPE AS INDICATED IN SCHEDULE
DISCONNECT SWITCH, SIZE AND TYPE AS
INDICATED IN SCHEDULE
F
DISCONNECT SWITCH, FURNISHED WITH EQUIPMENT
MOTOR STARTER, SIZE AND TYPE AS
INDICATED IN SCHEDULE
MOTOR STARTER, FURNISHED WITH EQUIPMENT
COMBINATION MOTOR STARTER w/EXTERNALLY
OPERATED DISCONNECT
COMBINATION MOTOR STARTER w/EXTERNALLY
OPERATED DISCONNECT, FURNISHED WITH
EQUIPMENT
VFD VARIABLE FREQUENCY DRIVE
SHUNT TRIP SWITCH WITH SAFETY COVERST
CEILING MOUNTED LUMINAIRE
SINGLE POLE SWITCH
THREE WAY SWITCH
FOUR WAY SWITCH
DIMMER SWITCH
OCCUPANCY/VACANCY SENSOR0
D
ELECTRICAL PANELBOARD.
LIGHTING PLAN SYMBOLS
MISCELLANEOUS ELECTRICAL SYMBOLS
KEYNOTES
EQUIPMENT CONNECTION, REFER TO APPROPRIATE
SCHEDULE FOR ADDITIONAL INFORMATION.
POWER PLAN SYMBOLS
PHOTOCELL SENSOR
BUS DUCT OR CABLE TRAY RISER (PLAN VIEW)ENCLOSED CIRCUIT BREAKERCB
OCCUPANCY WALL SENSOR0
MAN HOLE - (EXTERIOR) - SIZED PER PLANS AND NEC.MH
HAND HOLE - (EXTERIOR) - SIZED PER PLANS AND NEC.HH
INDICATES PANELBOARD. ALL RECEPTACLE AND LIGHTING
BRANCH CIRCUITS IN ROOM SHALL BE CIRCUITED TO THIS
PANELBOARD. CIRCUIT NUMBER SHALL BE NEXT TO POWER OR
LIGHTING DEVICE. ALL CONDUITS SHALL CONTAIN A GREEN
INSULATED GROUND WIRE SIZED IN ACCORDANCE WITH NEC
TABLE 250.122, UNLESS OTHERWISE NOTED.
PP21
INDICATES PANELBOARD. ALL RECEPTACLE AND LIGHTING
BRANCH CIRCUITS IN ROOM SHALL BE CIRCUITED TO THIS
PANELBOARD. ALL CONDUITS SHALL CONTAIN A GREEN
INSULATED GROUND WIRE SIZED IN ACCORDANCE WITH NEC
TABLE 250.122, UNLESS OTHERWISE NOTED.
PP21-1,3,5
OR
HX-1
A1 a
TERMINATIONS
DISCONNECT SWITCH, FUSED
C…