415_480V_PUMP_STATION_RACK_FRONT.pdf
PDF 245 KB Posted
- Attached to
- Pump Station Renewal & Replacement D25 - Phase I
- Solicitation number
- CC-6690-25/TAD
- Issued by
- Seminole County, Florida
About this file
This technical diagram is from the Seminole County Utilities Department - Utilities Engineering Division, depicting a detailed schematic for a 480V Pump Station Rack Front electrical configuration. The drawing provides a comprehensive plan and front elevation view of an electrical installation, featuring key components such as a Power Control Panel (PCP), non-fused and fused disconnects, a demarcation enclosure, and various electrical conduits and mounting hardware. The diagram includes specific technical specifications for component placement, grounding systems, conduit transitions, and positioning requirements.
The technical drawing includes several critical technical notes, emphasizing that the diagram is not project-specific and must be modified and approved by a Florida licensed professional engineer. Specific requirements include conduit sizing (minimum 2" with 40% fill capacity), grounding and bonding per NEC standards, use of rigid aluminum conduit above grade with PVC Schedule 80 below grade or slab, and corrosion protection for metallic components. The diagram specifies precise dimensional requirements for component placement, such as generator receptacle access height (72" maximum, 24" minimum) and various mounting heights and clearances for electrical equipment.
View the file
Other files
Show all 13
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
SPD
FUSED DISC.METER
PCP
(60"Hx36"Wx16"D)
RESERVED
FOR ATS
DEMARCATION ENCLOSURE
(TYP 3 FOR DUPLEX)
M
IN
. 3 6"
O R
AS
R
EQ
. B
Y C
O D
E O
R W
IN
D
L O
AD
PLAN VIEW
NON-FUSED
DISC.
FRONT ELEVATION
CONDUITS TO
WET WELL
NOTES:
1. THIS DIAGRAM IS NOT PROJECT SPECIFIC. A DIAGRAM SHALL BE MODIFIED AND APPROVED BY A FLORIDA LICENSED
PROFESSIONAL ENGINEER
2. DETAILS 415, 416, 418, 421, & 422 ARE A SET AND ACCOMPANY EACH OTHER.
3. PUMP MOTOR CONDUIT SHALL BE SIZED TO ACCOMMODATE 40% CONDUIT FILL, MINIMUM SIZE SHALL BE 2".
4. GROUNDING AND BONDING SYSTEM SHALL BE INSTALLED AS PER THE NEC, REF. DETAILS 411 & 412.
5. RIGID ALUMINUM CONDUIT SHALL BE USED ABOVE GRADE, TRANSITION TO PVC SCH 80 BELOW GRADE OR SLAB.
6. PROVIDE CORROSION PROTECTION AT ALL METALLIC CONDUIT AND POSTS SET IN CONC. OR DIRECT BURIED.
WATERTIGHT ALUM.
HUB (TYP)
RIGID ALUM. CONDUIT,
TYP ABOVE GRADE
TRANSITION TO
SCH 80 PVC BELOW
GRADE OR SLAB
PROVIDE CLEAR
ACCESS TO GEN.
RECEPTICAL
" M
AX
M
IN
PCP
(60"Hx36"Wx16"D)
DEMARCATION
ENCLOSURE
(TYP 3 FOR
DUPLEX)
P1 P2LI/PI
3" STAINLESS STEEL
316 POST (TYP)
1-1/2" STAINLESS STEEL
316 CHANNEL WITH
STAINLESS STEEL "U"
BOLTS, LOCK WASHERS
AND NUTS (TYP)
STAINLESS STEEL CAP
OR PLUG (TYP)
" M
IN
" M
AX
M
IN
TYPE EYSR
SEAL-OFFS (TYP)
PANEL & RACK
GROUNDING
PM
POWER MONITOR ENCLOSURE
POWER MONITOR
ENCLOSURE
(8"Hx8"Wx6"D)
NEMA 4X STAINLESS STEEL
POWDER COATED WHITE
NEMA 4X STAINLESS STEEL
POWDER COATED WHITE
DATE:
FIGURE:
SEMINOLE COUNTY UTILITIES DEPARTMENT - UTILITIES ENGINEERING DIVISION
480V PUMP STATION RACK FRONT
XX/XX/XX
alaforce Architect
| Sheets and Views |
| 415 480V PUMP STATION RACK FRONT |