413_240V_PUMP_STATION_RACK_FRONT.pdf
PDF 246 KB Posted
- Attached to
- Pump Station Renewal & Replacement D25 - Phase I
- Solicitation number
- CC-6690-25/TAD
- Issued by
- Seminole County, Florida
About this file
The document is a technical engineering diagram from the Seminole County Utilities Department - Utilities Engineering Division, specifically detailing a 240V Pump Station Rack Front configuration. The diagram provides a comprehensive plan and front elevation view of a utility rack system with multiple components including a Power Control Panel (PCP), Power Monitor (PM) enclosure, demarcation enclosures, conduit routing, and grounding specifications. The diagram is marked as Figure 413 and includes six critical technical notes emphasizing that the diagram is not project-specific and must be modified and approved by a Florida licensed professional engineer.
The technical drawing specifies precise dimensional and material requirements for the utility rack, including NEMA 4X stainless steel enclosures powder-coated white, stainless steel 316 posts and channels, rigid aluminum conduit transitioning to Schedule 80 PVC below grade, and specific grounding and bonding system requirements per NEC standards. Key installation parameters include minimum conduit sizes, corrosion protection specifications, clearance requirements for general receptacles, and detailed mounting and positioning guidelines for electrical infrastructure components. The diagram is designed to provide a standardized template for pump station electrical rack installations, with explicit instructions for adapting the design to specific project needs.
View the file
Other files
Show all 12
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
TVSS
FUSED DISC.METER
PCP
(60"Hx36"Wx16"D)
RESERVED
FOR ATS
DEMARCATION ENCLOSURE
(TYP 3 FOR DUPLEX)
DEMARCATION
ENCLOSURE
(TYP 3 FOR
DUPLEX)
P1 P2LI/PI
3" STAINLESS STEEL
316 POST (TYP)
1-1/2" STAINLESS STEEL
316 CHANNEL WITH
STAINLESS STEEL "U"
BOLTS, LOCK WASHERS
AND NUTS (TYP)
STAINLESS STEEL CAP
OR PLUG (TYP)
WATERTIGHT ALUM.
HUB (TYP)
RIGID ALUM. CONDUIT,
TYP ABOVE GRADE
TRANSITION TO
SCH 80 PVC BELOW
GRADE OR SLAB
" M
IN
" M
AX
M
IN
M
IN
. 3 6"
O R
AS
R
EQ
. B
Y C
O D
E O
R W
IN
D
L O
AD
PLAN VIEW
FRONT ELEVATION
PROVIDE CLEAR
ACCESS TO GEN.
RECEPTICAL
" M
AX
M
IN
CONDUITS TO
WET WELL
TYPE EYSR
SEAL-OFFS (TYP)
PANEL & RACK
GROUNDING
NOTES:
1. THIS DIAGRAM IS NOT PROJECT SPECIFIC. A DIAGRAM SHALL BE MODIFIED AND APPROVED BY A FLORIDA LICENSED
PROFESSIONAL ENGINEER
2. DETAILS 413, 414, 417, 419, & 420 ARE A SET AND ACCOMPANY EACH OTHER.
3. PUMP MOTOR CONDUIT SHALL BE SIZED TO ACCOMMODATE 40% CONDUIT FILL, MINIMUM SIZE SHALL BE 2".
4. GROUNDING AND BONDING SYSTEM SHALL BE INSTALLED AS PER THE NEC, REF. DETAILS 411 & 412.
5. RIGID ALUMINUM CONDUIT SHALL BE USED ABOVE GRADE, TRANSITION TO PVC SCH 80 BELOW GRADE OR SLAB.
6. PROVIDE CORROSION PROTECTION AT ALL METALLIC CONDUIT AND POSTS SET IN CONC. OR DIRECT BURIED.
PCP
(60"Hx36"Wx16"D)
PM
POWER MONITOR ENCLOSURE
POWER MONITOR
ENCLOSURE
(8"Hx8"Wx6"D)
NEMA 4X STAINLESS STEEL
POWDER COATED WHITE
NEMA 4X STAINLESS STEEL
POWDER COATED WHITE
DATE:
FIGURE:
SEMINOLE COUNTY UTILITIES DEPARTMENT - UTILITIES ENGINEERING DIVISION
240V PUMP STATION RACK FRONT
XX/XX/XX