413_240V_PUMP_STATION_RACK_FRONT.pdf

PDF 246 KB Posted

Attached to
Pump Station Renewal & Replacement D25 - Phase I
Solicitation number
CC-6690-25/TAD
Issued by
Seminole County, Florida

About this file

This technical drawing is a detailed schematic for a 240V Pump Station Rack Front, prepared by the Seminole County Utilities Department - Utilities Engineering Division. The diagram provides a comprehensive plan and front elevation view of a pump station electrical infrastructure, including specific components such as a Power Control Panel (PCP), Power Monitor (PM) enclosure, demarcation enclosures, and associated electrical conduits and grounding systems. The drawing includes critical technical specifications for installation, with notes emphasizing that the diagram is not project-specific and must be modified and approved by a Florida Licensed Professional Engineer.

The technical drawing specifies precise dimensional requirements and installation guidelines for electrical components, including NEMA 4X stainless steel enclosures powder coated white, stainless steel posts and channels, watertight aluminum hubs, and rigid aluminum conduits. Key technical notes address conduit sizing (minimum 2" with 40% fill), grounding and bonding system installation per NEC standards, and corrosion protection requirements for metallic components set in concrete or directly buried. The schematic provides detailed measurements for component placement, such as generator receptacle access heights, conduit transitions, and minimum/maximum depths for underground installations.

View the file

Other files

Show all 13

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

TVSS

FUSED DISC.METER

PCP

(60"Hx36"Wx16"D)

RESERVED

FOR ATS

DEMARCATION ENCLOSURE

(TYP 3 FOR DUPLEX)

DEMARCATION

ENCLOSURE

(TYP 3 FOR

DUPLEX)

P1 P2LI/PI

3" STAINLESS STEEL

316 POST (TYP)

1-1/2" STAINLESS STEEL

316 CHANNEL WITH

STAINLESS STEEL "U"

BOLTS, LOCK WASHERS

AND NUTS (TYP)

STAINLESS STEEL CAP

OR PLUG (TYP)

WATERTIGHT ALUM.

HUB (TYP)

RIGID ALUM. CONDUIT,

TYP ABOVE GRADE

TRANSITION TO

SCH 80 PVC BELOW

GRADE OR SLAB

" M

IN

" M

AX

M

IN

M

IN

. 3 6"

O R

AS

R

EQ

. B

Y C

O D

E O

R W

IN

D

L O

AD

PLAN VIEW

FRONT ELEVATION

PROVIDE CLEAR

ACCESS TO GEN.

RECEPTICAL

" M

AX

M

IN

CONDUITS TO

WET WELL

TYPE EYSR

SEAL-OFFS (TYP)

PANEL & RACK

GROUNDING

NOTES:

1. THIS DIAGRAM IS NOT PROJECT SPECIFIC. A DIAGRAM SHALL BE MODIFIED AND APPROVED BY A FLORIDA LICENSED

PROFESSIONAL ENGINEER

2. DETAILS 413, 414, 417, 419, & 420 ARE A SET AND ACCOMPANY EACH OTHER.

3. PUMP MOTOR CONDUIT SHALL BE SIZED TO ACCOMMODATE 40% CONDUIT FILL, MINIMUM SIZE SHALL BE 2".

4. GROUNDING AND BONDING SYSTEM SHALL BE INSTALLED AS PER THE NEC, REF. DETAILS 411 & 412.

5. RIGID ALUMINUM CONDUIT SHALL BE USED ABOVE GRADE, TRANSITION TO PVC SCH 80 BELOW GRADE OR SLAB.

6. PROVIDE CORROSION PROTECTION AT ALL METALLIC CONDUIT AND POSTS SET IN CONC. OR DIRECT BURIED.

PCP

(60"Hx36"Wx16"D)

PM

POWER MONITOR ENCLOSURE

POWER MONITOR

ENCLOSURE

(8"Hx8"Wx6"D)

NEMA 4X STAINLESS STEEL

POWDER COATED WHITE

NEMA 4X STAINLESS STEEL

POWDER COATED WHITE

DATE:

FIGURE:

SEMINOLE COUNTY UTILITIES DEPARTMENT - UTILITIES ENGINEERING DIVISION

240V PUMP STATION RACK FRONT

XX/XX/XX

alaforce Architect

Sheets and Views
413 240V PUMP STATION RACK FRONT

File details come from the government source that posted it. Updated .