41055-081_PS22_includes_OFE_DRAWING_PUMP_C.P._RTU.pdf

PDF 1 MB Posted

Attached to
ITB# 202536 Purchase of Submersible Pumps and Control Panel to Upgrade Pump Station #22 - RE-BID
Solicitation number
202536
Issued by
Miami-Dade County, Florida

About this file

This is a technical electrical drawing and specification document prepared by Hazen and Sawyer for the City of Homestead, Florida, detailing the electrical design for Pump Station #22 upgrades under Contract 41055-081. The project encompasses the installation of electrical infrastructure including a 125 kW standby emergency generator rated at 480V three-phase, a local control panel with integral loads, a SCADA/Remote Telemetry Unit (RTU) system, three submersible pumps with associated motor controls, instrumentation systems, and lighting. The electrical scope includes service entrance equipment rated at 200 amps with an automatic transfer switch, motor circuit breakers, disconnect switches, control panels meeting UL 508A standards, conduit installation (both above and below grade), grounding systems, fire alarm and emergency shut-off systems, and arc-flash hazard labeling. All materials and equipment must be new, unused, and UL-listed, with the contractor responsible for shop drawing submissions, system testing, and provision of operation and maintenance manuals. The installation must comply with the National Electrical Code (NEC 2020), National Fire Protection Association (NFPA) standards including NFPA 70E (2024) and NFPA 820 (2024), Florida Building Code (2023), and local authority requirements. The contractor must obtain all necessary permits, conduct site visits before bidding, coordinate with utilities and all trades, restore disturbed areas, and guarantee all equipment for one year from acceptance.

The electrical design specifies comprehensive requirements for conduit installation, grounding, and instrumentation to support the pump station's operational needs in a Class 1 Division 1 hazardous location environment. Power distribution utilizes three-phase 480V service with conduit separation requirements based on voltage levels, ranging from one foot for 120V to three feet for 4160V instrumentation separation. The design incorporates sealed-off connections for all conduits penetrating the wet well, PVC-coated rigid metal conduit below grade, and copper conductors exclusively (no aluminum permitted). Grounding systems must achieve a maximum 48-hour dry resistance of 10 ohms, with all grounding connections using exothermic welds. Specialized instrumentation includes flow meters, pressure transducers, and level transmitters connected via separate conduits with surge protection and dedicated ground rods. The contractor bears full responsibility for coordinating with local utilities including power and telephone providers, meeting all their specifications without additional cost to the owner, and for resolving any design conflicts with other trades at no extra expense. Record drawings, including a laminated single-line diagram, must be provided within 30 days of station acceptance.

View the file

Other files

Show all 11

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

DESIGNED

DRAWN

CHECKED

PROJ. ENGR.

DATENo. ISSUED FOR BY

CAD REFERENCE:

ENGINEERS PROJECT:

CLIENTS PROJECT:

CONTRACT:

41055-081

REF. No.

DRAWING:

SHEET:

DATE:

OF

P.E.

DRAWING.

THE SCALE BAR

SHOWN BELOW

MEASURES ONE

INCH LONG ON

THE ORIGINAL

CITY OF HOMESTEAD

HAZEN AND SAWYER

999 PONCE de LEON BLVD, SUITE 1150

CORAL GABLES, FLORIDA 33134

LICENSE No.: 2771 BI

D S

ET

JOHN C. BURKE

17301

PUMP STATION 22 UPGRADES

JUNE 2025

41055-081

J.M.B.

J.M.B.

E001J.C.B.

41055-081-E-01.DWG

C.L.K.

ELECTRICAL NOTES

La st s av ed : 4

/1 1/

:0

PM

B y:

jb ro ad Pl ot te d:

/2 6/

:4

PM

File Path: C:\Users\Jbroad\DC\ACCDocs\Hazen and Sawyer\41055-081-PS 22 and FM Upgrades\Project Files\01_Design\Elec\41055-081-E-01.dwg

BASIC ELECTRICAL REQUIREMENTS:

1. SCOPE OF WORK

1.1. THE SCOPE OF WORK SHALL BE AS DESCRIBED IN SPECIFICATION

SECTION 16050.

1.2. THE CONTRACTOR SHALL OBTAIN ALL NECESSARY PERMITS,

INSPECTIONS AND APPROVALS AND TO INCLUDE ALL FEES AS PART OF

HIS BID IF NOT OTHERWISE NOTED.

1.3. THE CONTRACTOR SHALL, BEFORE SUBMITTING HIS BID, VISIT THE SITE

OF THE PROJECT AND BECOME FAMILIAR WITH THE EXISTING

CONDITIONS. NO ALLOWANCE WILL BE MADE FOR EXISTING CONDITIONS

OR FAILURE OF THE CONTRACTOR TO OBSERVE THEM.

1.4. IT IS THE CONTRACTOR'S RESPONSIBILITY TO COORDINATE WITH ALL

LOCAL UTILITIES, INCLUDING THE POWER AND TELEPHONE UTILITIES TO

MEET ALL OF THEIR INSTALLATION REQUIREMENTS. ALL FEES, LABOR,

EQUIPMENT OR MATERIALS NECESSARY TO MEET THESE

REQUIREMENTS IS TO BE INCLUDED IN THE BID. THE CONTRACTOR

SHALL OBTAIN, DELIVER AND INSTALL ALL CONDUITS, PULL-BOXES AND

EQUIPMENT AS REQUIRED BY THE UTILITIES TO THEIR SPECIFICATIONS.

1.5. THE CONTRACTOR SHALL COORDINATE HIS WORK WITH THE ENGINEER

AND OWNER.

1.6. THE CONTRACTOR SHALL PROVIDE ALL MATERIALS AND LABOR TO

INSTALL THE ELECTRICAL SYSTEMS AS INDICATED ON THE DRAWINGS

AND FURTHER DETAILED IN THE SPECIFICATIONS. ITEMS NOT SHOWN

BUT OBVIOUSLY NECESSARY FOR COMPLETION OF THE WORK SHALL BE

INCLUDED.

1.7. ALL EQUIPMENT AND MATERIAL SHALL BE NEW, UNUSED AND U.L.

LISTED. ALL REFERENCES TO A PARTICULAR MANUFACTURER ARE

GIVEN ON AN "APPROVED EQUAL" BASIS UNLESS OTHERWISE NOTED.

1.8. THE CONTRACTOR IS RESPONSIBLE TO TEST ALL SYSTEMS INSTALLED

OR MODIFIED UNDER THIS PROJECT AND REPAIR OR REPLACE ALL

DEFECTIVE WORK TO THE SATISFACTION OF THE ENGINEER AND

OWNER.

1.9. ALL EQUIPMENT FURNISHED AND INSTALLED BY THE CONTRACTOR

SHALL BE GUARANTEED AGAINST DEFECTS IN MATERIAL AND

WORKMANSHIP FOR A PERIOD OF ONE YEAR FROM DATE OF

ACCEPTANCE UNLESS OTHERWISE NOTED.

1.10. SHOP DRAWINGS SHALL BE SUBMITTED FOR ALL ELECTRICAL &

CONTROL EQUIPMENT AND MATERIAL.

2. CODES AND STANDARDS

2.1. THE INSTALLATION SHALL BE IN ACCORDANCE WITH THE MINIMUM

FOLLOWING STANDARDS AND CODES:

2.2. NATIONAL FIRE PROTECTION ASSOCIATION (NFPA)

2.3. NATIONAL ELECTRICAL CODE (NEC) 2020 EDITION)

2.4. NATIONAL ELECTRICAL SAFETY CODE, (NFPA 70E 2024 EDITION)

STANDARD FOR FIRE PROTECTION IN WASTEWATER TREATMENT AND

COLLECTION FACILITIES, (NFPA 820 2024 EDITION)

2.5. OTHER NFPA CODES AS APPLICABLE

2.6. FLORIDA BUILDING CODE (FBC 2023 EDITION)

2.7. LOCAL CODES, CITY CODES REQUIRED BY THE AUTHORITY HAVING

JURISDICTION.

2.8. AMERICAN NATIONAL STANDARDS INSTITUTE (ANSI)

2.9. NATIONAL ELECTRICAL MANUFACTURERS ASSOCIATION (NEMA)

2.10. INSTITUTE OF ELECTRICAL AND ELECTRONIC ENGINEERS (IEEE)

2.11. INSULATED CABLE ENGINEERS ASSOCIATION (ICEA)

2.12. OCCUPATIONAL SAFETY AHD HEALTH ACT (OSHA)

2.13. AMERICAN SOCIETY FOR TESTING AND MATERIALS (ASTM)

2.14. UNDERWRITERS LABORATORIES (UL) LISTING AND LABELING FOR ALL

MATERIALS AND EQUIPMENT WHERE APPLICABLE STANDARDS EXIST

3. GENERAL ITEMS

3.1. ALL CIRCUITS SHALL BE IDENTIFIED IN JUNCTION BOXES, PULL BOXES

3.2. ALL LOCATIONS OF EQUIPMENT, PANELS ETC. ARE SHOWN FOR

ILLUSTRATION PURPOSES. CONTRACTOR SHALL VERIFY AND

COORDINATE EXACT LOCATION AND SIZE WITH ALL SUBCONTRACTORS

AND EQUIPMENT SUPPLIERS PRIOR TO ANY INSTALLATION AND THEN

INSTALL AS SUCH WITH CORRESPONDING CONDUIT STUB-UPS.

3.3. SEE OTHER DISCIPLINE DRAWINGS FOR COORDINATION OF ALL

DRAWINGS. ANY CONFLICTS SHALL BE BROUGHT TO THE ENGINEER'S

ATTENTION AND MOVEMENT OF CONDUITS OR OTHER ELECTRICAL

EQUIPMENT SHALL BE ACCOMPLISHED WITHOUT ANY ADDITIONAL COST

FOR THE OWNER.

3.4. THE CONTRACTOR SHALL BE RESPONSIBLE FOR ALL CONDUIT AND

WIRING INSTALLATION FOR ALL VENDOR PROVIDED EQUIPMENT

(PACKAGE SYSTEMS). IF THE SHOP DRAWINGS DIFFER FROM THE

DESIGNED FACILITIES, THE CONTRACTOR SHALL REDESIGN THE

FACILITIES AND SUBMIT THE REVISED DESIGN FOR THE ENGINEER'S

APPROVAL ALONG WITH THE SHOP DRAWINGS. THERE SHALL BE NO

ADDITIONAL COST TO THE OWNER FOR THE REDESIGN NOR FOR ANY

ADDITIONAL CONDUITS AND WIRING. DURING SUBMITTAL THE CONTRACTOR

SHALL VERIFY ALL SUPPLIED BREAKER SIZES FOR ALL PACKAGED SYSTEMS SUCH

AS HVAC, EXHAUST FANS, MIXERS, CHEMICAL PUMPS ETC. AND MODIFY ALL

BREAKERS IN MCC'S AND PANELBOARDS ACCORDINGLY WITHOUT ANY

ADDITIONAL COST TO THE OWNER.

3.5. CONTRACTOR SHALL RESTORE SIDEWALKS, ROADWAYS, SOD AND

SPRINKLER SYSTEM PIPING TO MATCH EXISTING, AFTER THE

COMPLETION OF THE CONDUIT AND PULLBOX INSTALLATION.

3.6. ELECTRICAL EQUIPMENT SHALL BE DEFINED AS ANY ELECTRICAL

DEVICE USED IN CONJUNCTION WITH OTHER EQUIPMENT REQUIRING

ELECTRICITY FOR OPERATION. THIS INCLUDES BUT IS NOT LIMITED TO:

DISCONNECT SWITCHES, JUNCTION BOXES, PANELBOARDS,

TRANSFORMERS, LIGHTING FIXTURES, MOTOR STARTERS, SWITCHGEAR,

MOTOR CONTROL CENTERS, CONTROLS, LOCAL CONTROL PANELS.

3.7. ALL REFERENCES TO STAINLESS STEEL (SS) SHALL MEAN TYPE 316

STAINLESS STEEL UNLESS OTHERWISE NOTED.

3.8. ALL ELECTRICAL EQUIPMENT IN DESIGNATED CORROSIVE AREAS SHALL

BE NEMA 4X 316 STAINLESS STEEL OR NON-METALLIC (FRP).

3.9. OUTDOOR LIGHTING FIXTURES SHALL BE COPPER FREE ALUMINUM.

3.10. CONTRACTOR SHALL PROVIDE AS PART OF THE ELECTRICAL SUBMITTAL,

A LAYOUT OF THE ELECTRICAL ROOM SHOWING SIZES OF ALL

EQUIPMENT INCLUDING LIGHTING, AND HVAC WITH THEIR SPATIAL

RELATIONSHIPS.

3.11. CONTRACTOR SHALL PROVIDE AND INSTALL WIRE ID TAGS ON ALL

WIRING THAT INTERFACES WITH OTHER EQUIPMENT. INSTRUMENTATION

WIRING SHALL BE AS SHOWN FOR THE DFS SCHEDULE ON DRAWING ###.

4. OPERATION AND MAINTENANCE MANUALS

4.1. CONTRACTOR SHALL PROVIDE AN OPERATION AND MAINTENANCE

MANUAL PER FBC EC C405.7.4.2 INCLUDING:

4.1.1. SUBMITTAL DATA STATING EQUIPMENT RATING AND SELECTED OPTION

FOR EACH PIECE OF EQUIPMENT REQUIRING MAINTENANCE.

4.1.2. OPERATION AND MAINTENANCE MANUALS FOR EACH PIECE OF

EQUIPMENT REQUIRING MAINTENANCE. REQUIRED ROUTINE

MAINTENANCE ACTIONS SHALL BE CLEARLY IDENTIFIED

4.1.3. NAMES AND ADDRESSES OF AT LEAST ONE QUALIFIED SERVICE AGENCY

SEE SPECIFICATIONS FOR ADDITIONAL DETAILS

5. PROJECT CLOSEOUT

5.1. CONTRACTOR SHALL PROVIDE RECORD DRAWINGS TO THE OWNER AND

ENGINEER WITHIN 30 DAYS OF PUMP STATION ACCEPTANCE. THESE

SHALL INCLUDE PER FBC EC C405.7.4.1:

5.2. A LAMINATED AND FRAMED MINIMUM 11X17 INCH SINGLE LINE DIAGRAM

OF THE SITE ELECTRICAL SYSTEM SHALL BE PROVIDED FOR

INSTALLATION ADJACENT TO THE MAIN ELECTRICAL GEAR.

5.3. PLAN VIEWS OF COMPLETE PUMP STATION

6. RACEWAYS:

6.1. CONDUITS RUN IN PARALLEL: INSTRUMENTATION CONDUITS SHALL HAVE

A MINIMUM SEPARATION FROM POWER CONDUITS AS INDICATED IN

TABLE WHETHER CONCRETE ENCASED DUCT BANKS, DIRECT BURIED,

SURFACE OR RACKS:

VOLTAGE DISTANCE

6.1.1. 4160V 3 FT

6.1.2. 480V 2 FT

6.1.3. 120V 1 FT

6.2. NOT ALL CONDUITS SHOWN ON RISER AND ONE-LINE DIAGRAMS ARE

SHOWN ON BUILDING LAYOUTS. CONTRACTOR SHALL SUPPLY ALL

CONDUITS AND CABLES AS SHOWN ON RISERS AND ONE-LINE

DIAGRAMS.

6.3. EXPOSED RUNS OF CONDUITS SHALL BE INSTALLED WITH RUNS

PARALLEL OR PERPENDICULAR TO WALLS, STRUCTURAL MEMBERS OR

INTERSECTIONS OF VERTICAL PLANES AND CEILINGS, WITH RIGHT

ANGLE TURNS CONSISTING OF SYMMETRICAL BENDS OR PULL BOXES

AS INDICATED ON THE DRAWINGS. BENDS AND OFFSETS SHALL BE

AVOIDED WHERE POSSIBLE.

6.4. THE DRAWINGS ARE NOT INTENDED TO SHOW THE EXACT LOCATION OF

CONDUIT RUNS. THESE ARE TO BE COORDINATED WITH THE OTHER

TRADES SO THAT CONFLICTS ARE AVOIDED PRIOR TO INSTALLATIONS.

6.5. CONTRACTOR SHALL CORE DRILL EXISTING CONCRETE WALLS, FLOORS,

MANHOLES, HAND HOLES AND PULL BOXES FOR CONDUIT

PENETRATIONS. SEAL PENETRATIONS WITH NON-SHRINK GROUT OR

APPROPRIATE FIRE RATED DEVICES WHERE APPLICABLE.

6.6. ALL CONDUITS PENETRATING RATED FIRE WALLS OR RATED FIRE

FLOORS SHALL BE INSTALLED WITH U.L. APPROVED DEVICES AND OR

FIRE RATED SEALING COMPOUND TO MAINTAIN THE FIRE RATING OF THE

WALL OR FLOOR PENETRATED.

6.7. PROVIDE CONDUIT DUCT SEAL AT ALL CONDUIT ENDS.

6.8. ALL SPARE, ABANDONED, OR EMPTY CONDUITS SHALL BE SEALED WITH

A CAP AT BOTH ENDS AND A PULL STRING INSTALLED WITH

IDENTIFICATION OF OTHER END LOCATION AT BOTH ENDS.

6.9. FLEXIBLE CONDUITS SHALL BE USED TO TERMINATE ALL MOTORS AND

OTHER VIBRATING EQUIPMENT AND SHALL BE BETWEEN 18" AND 36" IN

LENGTH.

6.10. ALL METALLIC CONDUITS BELOW GRADE TO A MINIMUM ELEVATION OF

12 INCHES ABOVE GRADE SHALL BE PVC COATED RIGID METAL CONDUIT

(RMC).

6.11. ALL METALLIC CONDUITS 12 INCHES AND GREATER ABOVE GRADE SHALL

BE RMC.

6.12. ALL REFERENCES TO RMC SHALL MEAN RIGID GALVANIZED STEEL

CONDUIT (RGS) UNLESS OTHERWISE NOTED.

6.13. ALL REFERENCES TO PVC COATED RMC SHALL MEAN PVC COATED RIGID

GALVANIZED STEEL CONDUIT (RGS) UNLESS OTHERWISE NOTED.

6.14. ALUMINUM CONDUIT SHALL NOT BE USED FOR INSTRUMENTATION

WIRING.

7. DUCT BANKS & MANHOLES

7.1. LOCATIONS OF MANHOLES, HANDHOLES AND PULL BOXES ARE

APPROXIMATE. CONTRACTOR SHALL COORDINATE EXACT LOCATION

WITH EXISTING AND NEW PIPING OR CONDUIT AND ADJUST

ACCORDINGLY.

7.2. COLORED WARNING TAPE 6" WIDE SHALL BE INSTALLED 8" BELOW

FINISHED GRADE DIRECTLY ABOVE ALL UNDERGROUND YARD CONDUITS

ACCORDING TO THE FOLLOWING SCHEDULE:

7.2.1. POWER: RED

7.2.2. ALL OTHER CONDUITS: GREEN

7.3. ALL EXCAVATIONS FOR CONDUITS, HANDHOLES, MANHOLES AND

PULLBOXES NEAR EXISTING PIPING, CONDUIT AND EQUIPMENT SHALL BE

HAND EXCAVATED AND COORDINATED WITH PLANT ENGINEER.

7.4. MINIMUM DEPTH FROM TOP OF DUCT BANKS OR CONDUITS TO FINISHED

GRADE SHALL BE 24" UNLESS OTHERWISE NOTED.

7.5. IF CONCRETE ENCASED DUCT BANKS INCLUDE POWER WITH ANY TYPE

OF SIGNALS EXCEPT FIBER OPTIC CABLE, ALL CONDUITS SHALL BE

METALLIC.

7.6. CONCRETE DUCT BANKS WITH POWER ONLY WIRING MAY BE PVC

UNLESS OTHERWISE NOTED ON THE DRAWINGS.

7.7. SLOPE DUCT BANKS A MINIMUM 3 INCHES PER 100 FEET DOWN AWAY

FROM BUILDINGS.

7.8. DUCT BANK CONCRETE SHALL BE MINIMUM CLASS C 2500 PSI

8. CONDUCTORS:

8.1. ALUMINUM CONDUCTORS SHALL NOT BE USED FOR THIS PROJECT.

8.2. CONDUCTOR PULLING TENSIONS SHALL NOT EXCEED MANUFACTURER'S

RECOMMENDATION. CONTRACTOR SHALL INSTALL PULL BOXES TO MEET

MANUFACTURER'S REQUIREMENTS.

8.3. COPPER CONDUCTORS FOR POWER WIRING WITH A VOLTAGE GREATER

THAN 240V TO GROUND SHALL BE XHHW-2. OTHER POWER WIRING

SHALL BE EITHER XHHW OR THWN STRANDED COPPER WIRING.

8.4. BRANCH CIRCUITS EXCEEDING 100 FT IN LENGTH SHALL BE WIRED WITH

MINIMUM #10 AWG COPPER WIRES. CONTRACTOR SHALL VERIFY

REQUIRED WIRE SIZE WITH VOLTAGE DROP CALCULATIONS.

8.5. BOXES

8.6. ALL ENCLOSURES, TJB, WIREWAY, PULL BOXES ETC. SHALL CONTAIN A

GROUNDING BUS. CONNECT ALL RACEWAY BONDS TO THIS BUS VIA

GROUNDING BUSHING AND EXTEND BONDING JUMPER FROM THIS BUS

TO THE ENCLOSURE.

8.7. ALL JUNCTIONS BOXES, LOCAL CONTROL PANELS, DISCONNECT

SWITCHES AND INSTALLATION HARDWARE INSTALLED OUTDOORS SHALL

BE 316 STAINLESS STEEL.

9. PANELS

9.1. ALL CONTROL PANELS SHALL BE CONSTRUCTED BY A UL 508A

APPROVED PANEL VENDOR AND SHALL BEAR A UL 508A LABEL ON THE

PANEL.

9.2. TYPEWRITTEN AND LAMINATED PANEL SCHEDULES SHALL BE INSTALLED

IN EACH PANELBOARD, AND TYPEWRITTEN TERMINAL BLOCK

SCHEDULES IN EACH CONTROL CABINET.

9.3. ALL PANELBOARDS SHALL INCLUDE AN INTEGRAL FACTORY INSTALLED

SURGE PROTECTION DEVICES (SPD AKA TVSS).

9.4. CONTRACTOR SHALL BALANCE PANELBOARD LOADS AT THE END OF THE

PROJECT.

10. GROUNDING

10.1. GROUNDING SHALL BE INSTALLED IN ACCORDANCE WITH NEC, ARTICLE

250. THE GROUNDING SYSTEM TEST SHALL NOT EXCEED A 48 HOUR

SPAN DRY RESISTANCE OF 10 OHMS. ADDITIONAL GROUNDING TO MEET

THIS REQUIREMENT SHALL BE INSTALLED AT NO EXTRA COST.

GROUNDING AND BONDING CONNECTIONS SHALL NOT BE PAINTED. ALL

GROUNDING CONNECTIONS SHALL BE EXOTHERMIC UNLESS

SPECIFICALLY INDICATED OTHERWISE.

10.2. AN EQUIPMENT GROUND WIRE SIZED PER NEC SHALL BE PULLED IN ALL

ELECTRICAL CONDUITS, POWER AND CONTROL, WHETHER OR NOT

INDICATED ON THE PLANS.

11. INSTRUMENTATION

11.1. INSTRUMENTATION IS LOW VOLTAGE SIGNALS SUCH AS 4-20MA,

TELEPHONE COMMUNICATION, FIRE ALARM COMMUNICATION. POWER

CONDUITS SHALL ONLY CROSS INSTRUMENTATION CONDUIT

PERPENDICULARLY AT RIGHT ANGLES WITH 6" SEPARATION.

11.2. THE POWER AND SIGNAL SIDES OF ALL EXTERIOR INSTALLED

INSTRUMENTATION SHALL HAVE SURGE PROTECTION AND SHALL BE

GROUNDED TO A SEPARATE GROUND ROD AT THE INSTRUMENT.

11.3. INSTRUMENTATION GROUND SHALL BE A #6 AWG COPPER CONNECTED

TO THE GROUND GRID OR CONNECTED TO A DRIVEN GROUND. #6

GROUND WIRE SHALL BE INSTALLED IN CONDUIT WHERE EXPOSED.

GROUND RODS SHALL BE 5/8" OR 3/4" BY A MINIMUM OF 20' IN LENGTH,

AS INDICATED ON THE DRAWINGS.

11.4. CONTRACTOR SHALL INSTALL A SWITCH TO DISCONNECT POWER AT

EACH FOUR WIRE INSTRUMENT. ALL INSTRUMENTATION WIRING SHALL

BE TERMINATED, LOOP TESTED LOCALLY AND BETWEEN THE BASE

STATION AND LOCAL PUMP STATION PRIOR TO FINAL STARTUP AND

ACCEPTANCE.

12. SIGNAGE

12.1. CONTRACTOR SHALL PROVIDE SIGNAGE PER NEC 110.24 AND NEC 702.7

AT THE SERVICE ENTRANCE EQUIPMENT.

12.2. CONTRACTOR SHALL PROVIDE SIGNAGE PER NFPA 110 FOR THE

EMERGENCY SHUT-OFF BUTTON LOCATED ON THE NORTH EAST

OUTSIDE CORNER OF THE ELECTRICAL BUILDING.

12.3. CONTRACTOR SHALL PROVIDE SIGNAGE PER NFPA 704 FOR THE FUEL

SUPPLY.

12.4. CONTRACTOR SHALL PROVIDE AND INSTALL ARC-FLASH HAZARD

WARNING LABELS PER NEC 110.16 AND 110.21. THESE RULES APPLY AS A

MINIMUM TO SWITCHBOARDS, SWITCHGEAR, PANELBOARDS, MOTOR

CONTROL CENTERS, INDUSTRIAL CONTROL PANELS, METER SOCKET

ENCLOSURES, AND ENCLOSED CIRCUIT BREAKERS.

13. ELECTRICAL DEVICES (SW AND RECP)

13.1. ALL RECEPTACLES SHALL BE INSTALLED 18" AFF UNLESS OTHERWISE

NOTED. LIGHT SWITCHES SHALL BE MOUNTED 48" AFF UNLESS

OTHERWISE NOTED.

13.2. ALL RECEPTACLES WITHIN 6' OF A SINK SHALL BE GFI.

13.3. CONTRACTOR SHALL PROVIDE, INSTALL, TERMINATE AND TEST NEW STATION

TELEMETRY EQUIPMENT. SEE DATA FLOW SCADA SYSTEMS (DFS) NOTES

BELOW.

ABBREVIATIONS

ABBR. DESCRIPTION

A AMMETER, AMPERE

AC ALTERNATING CURRENT

ACL ACROSS THE LINE MOTOR

STARTER

AF CB AMPERE FRAME SIZE

AFD ADJUSTABLE FREQUENCY DRIVE

AFF ABOVE FINISHED FLOOR

AFG ABOVE FINISHED GRADE

AHJ AUTHORITY HAVING

JURISTICTION

AIC SYMM. AMPS INTERRUPTING

CAP.

AL ALUMINUM

ARC ALUMINUM RIGID CONDUIT

AS AMMETER SENSOR OR SWITCH

ASYM ASYMMETRICAL

AT CB AMPERE TRIP SETTING

ATS AUTOMATIC TRANSFER SWITCH

AUX AUXILIARY

AWG AMERICAN WIRE GAUGE

BC BARE COPPER

BCG BATTERY CHARGER

BSDG BUILDING

C CONDUIT, CONTACTOR

CB CIRCUIT BREAKER

CDB CONC ENCASED DUCT BANK

CKT CIRCUIT

CMS/CS COMBINATION MOTOR STARTER

CNTL CONTROL

C.O. CONDUIT ONLY

CONC CONCRETE

CPT CONTROL POWER

TRANSFORMER

CR CONTROL RELAY

CT CURRENT TRANSFORMER

D DUCT BANK

DC DIRECT CURRENT

DEF DIESEL EXHAUST FLUID

DPM DIGITAL POWER MONITOR

DS DISCONNECT SWITCH

EC EMPTY CONDUIT

ECDB EX CONC ENCASED DUCT BANK

ECP EQUIPMENT CONTROL PANEL

EF EXHAUST FAN

EG EMERGENCY GENERATOR

EMH ELECT MANHOLE (SEE MAS)

EMT ELECTRICAL METAL TUBING

ENCL ENCLOSURE

EPB EXISTING PULLBOX

EPC ELECTRIC POWER CENTER

EQUIP EQUIPMENT

ERMC-A ELECTRICAL RIGID METAL

CONDUIT - ALUMINUM

ERMC-S ELECTRICAL RIGID METAL

CONDUIT - STEEL

ESB EMERGENCY STOP BUTTON

ETM ELAPSED TIME METER

EX EXISTING

FDR FEEDER

F,FU FUSE

FI FLOW INDICATOR

FLA FULL LOAD AMPS

FLEX FLEXIBLE CONDUIT

FLR FLOOR

FLUOR FLUORESCENT

FLVC FULL VOLTAGE LIGHTING

CONTACTOR

FM FLOW METER

F.O. FAIL OPEN

FOC FIBER OPTIC CABLE

FS FLOW SWITCH

FT FLOW TRANSMITTER

FUT FUTURE

FVNR FULL VOLTAGE NON-REVERSING

G GREEN, GROUND

GALV GALVANIZED

GC GROUNDED CONDUCTOR

GDR GROUNDING RESISTOR

GEC GROUNDING ELECTRODE

CONDUCTOR

GEN GENERATOR

GFCI GROUND FAULT

CIRCUITINTERRUPTER

GFR GROUND FAULT RELAY

GND GROUND

GRS/RM

C

GALVANIZED RIGID STEEL

(CONDUIT)

GTB GENERATOR TIE BREAKER

ABBREVIATIONS

ABBR. DESCRIPTION

HH HANDHOLE

HID HIGH INTENSITY DISCHARGE

HOA HAND/OFF/AUTO

HOR HAND/OFF/REMOTE

HP HORSEPOWER

HPS HIGH PRESSURE SODIUM

HTR HEATER

HV HIGH VOLTAGE

HVAC HEAT, VENTILATION, AIR COND.

HZ HERTZ (FREQUENCY)

IC INTERRUPTING CAPACITY

ID INSIDE DIAMETER

IMC INTERMEDIATE METAL CONDUIT

INST INSTANTANEOUS

I/O INPUT / OUTPUT SIGNALS

IP INSTRUMENT PANEL

JB JUNCTION BOX

K KEY OR KIRK KEY INTERLOCK

kcmil 1000 CIRCULAR MILS kV KILOVOLTS kVA KILOVOLT-AMPERE kVAR KILOVOLT-AMPERE REACTIVE kW KILOWATT kWh KILOWATT-HOUR

LA LIGHTING ARRESTER

LC LOAD CENTER

LCP LOCAL CONTROL PANEL

LCS LOCAL CONTROL STATION

LFMC LIQUID TIGHT FLEX METAL

CONDUIT

LP-# LIGHTING PANEL NUMBER #

LR LOCAL/REMOTE OR LATCHING

RELAY

LRA LOCKED ROTOR AMPS

LS LIMIT SWITCH

LTC LIGHTING CONTACTOR

LTG LIGHTING

LV LOW VOLTAGE

M MOTOR OR MOTOR CONTACTOR

MAS MAINTENANCE ACCESS

STRUCTURE

MA MILLIAMPS

MAX MAXIMUM

MBS MANUAL BYPASS SWITCH

MC METAL CLAD

MCA MAXIMUM CIRCUIT AMPS

MCB MAIN CIRCUIT BREAKER

MCC MOTOR CONTROL CENTER

MCP MASTER CONTROL PANEL

MDP MAIN DISTRIBUTION PANEL

MERC MERCURY VAPOR

MFG MANUFACTURER

MFR MULTI-FUNCTIONAL RELAY

MGB MAIN GROUNDING BUS

MJB MOTOR JUNCTION BOX

MLO MAIN LUGS ONLY

MOCP MAXIMUM OVERCURRENT

PROTECTION

MOV MOTOR OPERATED VALVE

MPZ MINI-POWER ZONE

MSC MFR SUPPLIED CABLE

MSH MOTOR SPACE HEATER

MTS MANUAL TRANSFER SWITCH

MT MOUNT

MTD MOTOR TEMPERATURE

DETECTOR

MV MEDIUM VOLTAGE

N NEUTRAL

NA NOT APPLICABLE

NC NORMALLY CLOSED

NEMA NATIONAL ELEC. MFR. ASSOC.

NF NON-FUSED

NIC NOT IN CONTRACT

NO NORMALLY OPEN

NP NAMEPLATE

NTS NOT TO SCALE

OC OCCUPANCY CONTROL

OD OUTSIDE DIAMETER

OL OVERLOAD

OH OVERHEAD

OWS OPERATOR WORK STATION

ABBREVIATIONS

ABBR. DESCRIPTION

P POLE

PB PULL BOX OR PUSH BUTTON

PC PHOTOCELL

PCP PROCESS CONTROL PANEL

PF POWER FACTOR

PH PHASE

PLC PROGRAMMABLE LOGIC

CONTROLLER

PMU POWER MONITOR UNIT

PNL PANEL

PP POWER PANEL (480VAC)

PR PAIR

PS PRESSURE SWITCH

PT POTENTIAL TRANSFORMER

PVC POLYVINYL CHLORIDE CONDUIT

PWR POWER

RCPT RECEPTACLE

REF REFERENCE

REQD REQUIRED

RGS RIGID GALVANIZED STEEL

CONDUIT

RMC RIGID METAL CONDUIT

RM ROOM

RMS ROOT MEAN SQUARE

RS RIGID STEEL

RTD RESISTANCE TEMPERATURE

DETECTOR

RTU REMOTE TELEMETRY UNIT

SA SURGE ARRESTER

SC SURGE CAPACITOR

SEC SECONDARY

SEL SELECTOR

SF SUPPLY FAN

SH SPACE HEATER

SLC SITE LIGHTING CONTROLLER

SLD SINGLE LINE DIAGRAM

SMH SIGNAL MAINTENANCE HOLE

S/N SOLID NEUTRAL

SPEC SPECIFICATIONS

SPD SURGE PROTECTIVE DEVICE

SSRVS SOLID STATE REDUCED VOLTAGE

ST.

SST STAINLESS STEEL

SUB SUBSTATION

SV SOLENOID VALVE

SW SWITCH

SWBD SWITCHBOARD

SWGR SWITCHGEAR

SYM SYMMETRICAL

SYS SYSTEM

T THERMOSTAT

TB TERMINAL BLOCK

TD TIME DELAY RELAY

TEL TELEPHONE

TEMP TEMPERATURE

TJB TERMINAL JUNCTION BOX

TSH TEMPERATURE SWITCH - HIGH

TSP TWISTED SHIELDED PAIR

TVSS TRANSIENT VOLTAGE SURGE

SUPPR.

TYP TYPICAL

UGE UNDERGROUND ELECTRIC UTILITY

U/G UNDERGROUND

UPS UNINTERRUPTIBLE POWER SUPPLY

UVR UNDERVOLTAGE RELAY

V VOLT OR VOLTMETER

VA VOLTAMPERE

VAR VOLTAMPERE REACTIVE

VFD VARIABLE FREQUENCY DRIVE

VS VOLTMETER SWITCH

W WATT

WHD WATTHOUR DEMAND METER

WP WEATHER PROOF

WS WORK STATION

WW WIREWAY

XFMR TRANSFORMER

XMTR TRANSMITTER

XP EXPLOSION PROOF

Z IMPEDANCE

J

F

F

W

FIRE ALARM STROBE LIGHT

FIRE ALARM PULL STATION

TELEPHONE/DATA RECEPTACLE MOUNTED FLUSH IN FLOOR

ELEVATOR WARNING LIGHT

LPA-2

YCX

DB

X

X

[B2]

P-

CRE-

D- K-

CONDUIT, STUBBED AND CAPPED AS SHOWN

GROUND WIRE, 4/O CU UNLESS OTHERWISE NOTED

DIRECT BURIED CONDUIT

THREE WAY

FOUR WAY

WEATHERPROOF

3-

WP-

4-

DOUBLE POLE2-

YARD CONDUIT. REFER TO YARD CONDUIT SCHEDULE

KEY OPERATED

CORROSION

PILOT LIGHT

RESISTANT

DIMMER

UNDERGROUND CONDUIT AND CONDUCTORS*

LIGHTING FIXTURE POWER AND SWITCHING LEGEND

EXPOSED CONDUIT AND CONDUCTORS*

HOME RUN - PANEL AND CIRCUIT NUMBER SHOWN

RECEPTACLE, SPECIAL PURPOSE - AMPERAGE AS INDICATED.

CONDUIT/CONDUCTOR - REFER TO CIRCUIT SCHEDULE

X

X

X

X

TERMINAL JUNCTION BOX

LIGHTING PANELBOARD "L(X)"

20A DUPLEX RECEPTACLE UNLESS SPECIFIED OTHERWISE

20A QUADRAPLEX RECEPTACLE - UNLESS SPECIFIED OTHERWISE

20A DUPLEX RECEPTACLE - UNLESS SPECIFIED OTHERWISE.

LOCATED ABOVE COUNTER TOP

CONDUIT CHASE

CONCRETE ENCASED DUCT BANK

CEILING MOUNTED DOWNLIGHT LUMINAIRE - SEE SCHEDULE FOR TYPE

FLUORESCENT LUMINAIRE, SURFACE OR LAY IN TYPE SEE

SCHEDULE FOR TYPE

LUMINAIRE AND POLE - SEE SCHEDULE FOR TYPE

WALL MOUNTED LUMINAIRE - SEE SCHEDULE FOR TYPE

EXIT LIGHTS - SOLID SECTION IS DIRECTION OF FACE

SEE SCHEDULE FOR TYPE

EMERGENCY LIGHT WITH BATTERY PACK

SEE SCHEDULE FOR TYPE

JUNCTION BOX NEMA 12 ENCLOSURE UNLESS INDICATED

OTHERWISE. 4X = NEMA 4X SS

TELEPHONE/DATA RECEPTACLE (OUTLET BOX, 18" AFF) W -

WALL MOUNTED, 54" AFF

FAAP

SD HD

SD

D

FIRE ALARM CONTROL PANEL

FIRE ALARM SMOKE OR HEAT DETECTOR

FIRE ALARM ANNUNCIATOR PANEL

DUCT SMOKE DETECTOR

WH WATER HEATER

GROUND ROD - 5/8" x 20' COPPER CLAD

UNLESS OTHERWISE NOTED

GROUND ROD IN TEST WELL - 5/8" x 20' COPPER CLAD

UNLESS OTHERWISE NOTED

X = FIXTURE TYPE

# = CIRCUIT NUMBER

WP - WEATHERPROOF C - CLOCK HANGER

TL - TWIST LOCK CRE - CORROSION RESISTANT

GFCI - GROUND FAULT INTERRUPTER FTC - FULL TIME COVER

A - AMBER

B - BLUE

C - CLEAR

R - RED

G - GREEN

W - WHITE

SCHEMATIC DIAGRAMS ONLY

INDICATING LIGHT - LETTER INDICATES COLOR

PUSH TO TEST AND CONNECT INDICATING LIGHT

C - CLEAR

A

W - WHITE

B - BLUE

A - AMBER G - GREEN

R - RED

TVSS

CPT

120V

(3)

GFR

0-600V

X

TRANSFORMER, VOLTAGES, PHASE AND RATING

INDICATED AS APPLICABLE

CURRENT TRANSFORMER, NUMBER OF WINDINGS

INDICATED

DRAWOUT FUSED SWITCH, LOW OR MEDIUM VOLTAGE

600= FRAME RATING, 400=FUSE RATING

DRAWOUT CIRCUIT BREAKER, MEDIUM VOLTAGE 600=

FRAME RATING, 400=TRIP SETTING

DRAWOUT CIRCUIT BREAKER, LOW VOLTAGE 600=

FRAME RATING, 400=TRIP SETTING

LIGHTNING ARRESTER

CAPACITOR OR SURGE CAPACITOR

FUSE

TRANSIENT VOLTAGE SURGE SUPPRESSION

GROUND

CONTROL TRANSFORMER

GROUND FAULT RELAY WITH C.T.

PUSH-BUTTON SWITCH, MOMENTARY CONTACT,

NORMALLY OPEN

PUSH-BUTTON SWITCH, MOMENTARY CONTACT,

NORMALLY CLOSED

PUSH BUTTON SWITCH, MAINTAINED CONTACTS WITH

MECHANICAL INTERLOCK

REMOTE DEVICE

METER SCALE RANGE SHOWN IF REQUIRED

PM - PHASE MONITOR A - AMPS

P - POWER METER V - VOLTS

A

480V

E ELECTRICAL INTERLOCK

XFMR DRY

kVA 480-120/208V

3P/4W

O - OPEN CONTACT

X - CLOSED CONTACT

HAND

OOX 1

CKT.

OH

XOO

A

POSITION

X O

O O

OFF AUTO

O X

G

225400

M

4X

4X

4X

NOTC

TDx

Rx

CRx

LRx (L)

LC

CRx

4X

4X

4X

S M

F

PB

1"C, 1-25/C TYPE 1

1"C, 2#12, 1#12G

SYMBOL

OR

DESCRIPTION

CRx OR

NONFUSED DISCONNECT SWITCH, SIZE INDICATED, 3 POLE UNLESS

INDICATED OTHERWISE, NEMA 12 ENCLOSURE, 4X = NEMA 4X STAINLESS

STEEL

FUSED DISCONNECT SWITCH, SIZE INDICATED (60 = SWITCH RATING: 40 =

FUSE RATING) 3 POLE UNLESS INDICATED OTHERWISE, NEMA 12

ENCLOSURE, 4X = NEMA 4X STAINLESS STEEL

LIGHTING CONTACTOR, CURRENT RATING INDICATED, NEMA 12 ENCLOSURE

UNLESS INDICATED OTHERWISE. SEE CONTROL DIAGRAM FOR NUMBER OF

POLES. 4X = NEMA 4X TYPE 316 STAINLESS STEEL

MAGNETIC STARTER, NEMA SIZE INDICATED, NEMA 12 ENCLOSURE, UNLESS

INDICATED OTHERWISE. SEE CONTROL DIAGRAM. 4X = NEMA 4X STAINLESS

STEEL

COMBINATION (FUSE OR CIRCUIT BREAKER AS INDICATED). MAGNETIC

STARTER, NEMA SIZE INDICATED, NEMA 12 ENCLOSURE UNLESS INDICATED

OTHERWISE. SEE CONTROL SCHEMATIC DIAGRAM. 4X = NEMA 4X STAINLESS

STEEL

ELECTRIC RESISTANCE HEATER

ELAPSED TIME METER

CONTACT - NORMALLY OPEN WITH COIL INDICATED

CONTACT - NORMALLY CLOSED WITH COIL INDICATED

CONTROL RELAY, X=SEQUENTIAL NUMBER

LATCHING RELAY, X=SEQUENTIAL NUMBER L - LATCH, U - UNLATCH

TIME DELAY RELAY, X=SEQUENTIAL NUMBER NOTC=NORMALLY OPEN TIMED

CLOSED NOTO=NORMALLY OPEN TIMED OPEN AFTER CLOSE

NCTO = NORMALLY CLOSED TIMED OPEN; NCTC = NORMALLY CLOSED TIMED

CLOSED AFTER OPEN

TEMPERATURE

CLOSES ON FALLING

TEMPERATURE

SELECTOR SWITCH: MAINTAINED CONTACT WITH CONTACT POSITION

INDICATED, CHART IDENTIFIES OPERATION

THIS IS A STANDARD LEGEND SHEET. SOME SYMBOLS OR ABBREVIATIONS MAY

APPEAR ON THIS SHEET AND NOT BE UTILIZED ON PROJECT.

INDICATES RACEWAY AND CIRCUIT CONDUCTORS. FIRST NUMBER IS

RACEWAY SIZE. THE FOLLOWING NUMBERS ARE THE CONDUCTOR

QUANTITIES, SIZES, AND TYPES.

CONNECTION POINT TO EQUIPMENT SPECIFIED, FURNISHED AND INSTALLED

UNDER OTHER SECTIONS. RACEWAY, CONDUCTOR AND CONNECTION IN

THIS SECTION.

MANUAL MOTOR STARTER SWITCH, NEMA 4X UNLESS OTHERWISE NOTED.

NUMBER OF POLES AS REQUIRED.

PUSH-BUTTON STATION, NEMA 12 ENCLOSURE UNLESS INDICATED

OTHERWISE. 4X = NEMA 4X STAINLESS STEEL ENCLOSURE. SEE CONTROL

DIAGRAMS FOR TYPE PUSH BUTTON REQUIRED.

FUSED SWITCH, SWITCH AND FUSE CURRENT RATING

INDICATED, 3 POLE UNLESS INDICATED OTHERWISE.

CIRCUIT BREAKER, THERMAL MAGNETIC TRIP SHOWN,

3 POLE UNLESS INDICATED OTHERWISE.

MOTOR CIRCUIT PROTECTOR, MAGNETIC, 3 POLE

UNLESS INDICATED OTHERWISE.

MAGNETIC STARTER WITH NEMA SIZE INDICATED

OVERLOAD RELAY HEATER

MOTOR, SQUIRREL CAGE INDUCTION UNLESS

OTHERWISE NOTED - HORSEPOWER INDICATED

DISC SWITCH - FUSED, NON-FUSED

GENERATOR

ETM

or

60A 3P

60A 3P

DESCRIPTIONSYMBOL DESCRIPTIONSYMBOL

CONTROL RELAY, X = SEQUENTIAL NUMBER

DESCRIPTIONSYMBOL

X #

X

20A DUPLEX RECEPTACLE - UNLESS SPECIFIED OTHERWISE.

MOUNTED FLUSH IN FLOOR.

FIRE ALARM HORN/STROBE LIGHTF

X WALL SWITCH:

# - CIRCUIT

NO.

FACP

D

POWER PANELBOARD "H(X)"

ELECTRICAL LOCAL CONTROL PANELSLCP

CLOSES ON RISING

TEMPERATURE

"X" IS WIRING TYPE

"###" CONDUIT IDENTIFICATION

YYY-X###

"YYY" IS AREA (IF USED)

"X" IS WIRING TYPE

"###" CONDUIT IDENTIFICATION

"A" = ANALOG SIGNAL WIRING

"C" = DISCRETE OR CONTROL WIRING

"D" = DATA HIGHWAY (FOC)

"L" = POWER CONDUCTORS 120-240V

"H" = POWER CONDUCTORS 440-480V

"U" = UTILITY POWER

MCC - ASTERISK

INDIVIDUAL MOTOR CONTROLLER (SQUARE)

PANEL (HEXAGON)

FIELD (TRIANGLE)

X

La st s av ed : 4

/1 1/

:0

PM

B y:

jb ro ad Pl ot te d:

/2 6/

:4

PM

File Path: C:\Users\Jbroad\DC\ACCDocs\Hazen and Sawyer\41055-081-PS 22 and FM Upgrades\Project Files\01_Design\Elec\41055-081-E-02.dwg

DESIGNED

DRAWN

CHECKED

PROJ. ENGR.

DATENo. ISSUED FOR BY

CAD REFERENCE:

ENGINEERS PROJECT:

CLIENTS PROJECT:

CONTRACT:

41055-081

REF. No.

DRAWING:

SHEET:

DATE:

OF

P.E.

DRAWING.

THE SCALE BAR

SHOWN BELOW

MEASURES ONE

INCH LONG ON

THE ORIGINAL

CITY OF HOMESTEAD

HAZEN AND SAWYER

999 PONCE de LEON BLVD, SUITE 1150

CORAL GABLES, FLORIDA 33134

LICENSE No.: 2771 BI

D S

ET

JOHN C. BURKE

17301

PUMP STATION 22 UPGRADES

JUNE 2025

41055-081

J.M.B.

J.M.B.

E002J.C.B.

41055-081-E-02.DWG

C.L.K.

ELECTRICAL LEGENDS AND SYMBOLS

PUMP STATION WET WELL IS CLASSIFIED AS A CLASS 1

DIVISION 1 HAZARDOUS LOCATION.

SEAL-OFF CONNECTIONS FOR ALL CONDUITS

PENETRATING TO OR FROM THE WET WELL SHALL COMPLY

WITH AND BE INSTALLED PER NEC 501-5-B.

LCP INTEGRAL LOADS

CKT DESC VA BKR WIRES CONDUIT

CB1 LCP 400 1P-20 2#12, 1#12G NA

CB2 LCP LTG & RECP 460 1P-20 2#12, 1#12G NA

CB3 SCADA 360 1P-20 NA NA

CB4 BIRD CAGE LEVEL 150 1P-20 2#12, 1#12G NA

CB5 MAG FLOW MTR 360 1P-20 2#12, 1#12G NA

CB6 SITE LIGHTING 180 1P-20 2#12, 1#12G 3/4 "PVC80

CB7 GEN ENG BLOCK HEATER 100 1P-20 2#12, 1#12G NA

CB8 GENERATOR HEATER 1000 1P-20 2#12, 1#12G

AS REQUIRED

CB9 BATTERY CHARGER 360 1P-20 2#12, 1#12G

CB10 LIGHTING 180 1P-20 2#12, 1#12G

CB11 RECEPTACLES 360 1P-20 2#12, 1#12G

TOTAL 3510

120V SCHEDULE SHOWN FOR GENERAL INFO ONLY. CIRCUIT BREAKERS ARE AN

INTEGRAL PART OF THE VENDOR PROVIDED CONTROL PANEL.

2P-15A

MOTOR CIRCUIT BREAKERS SHALL BE

ABLE TO BE LOCKED IN THE OPEN POSITION

3P-200A

EMERGENCY

BREAKER

3P-200A MAIN

BREAKER

CONTROL PANEL SHALL BE

LABELED PER UL-508-A

(3)#4, (3)#10, (1)#8 1-1/2"C

FLT2

FLT1

LCP

CONTROL

SECTION

INTRINSICALLY

SAFE

(12) #14, 1"C

(2) INTEGRAL FLOAT

CABLES, 1"C

353535

La st s av ed : 6

/2 6/

:3

PM

B y:

jb ro ad Pl ot te d:

/2 6/

:4

PM

File Path: C:\Users\Jbroad\DC\ACCDocs\Hazen and Sawyer\41055-081-PS 22 and FM Upgrades\Project Files\01_Design\Elec\41055-081-E-03.dwg

SCADA / RTU SYSTEM IN SEPARATE

WHITE POWDER COATED 304 SS

ENCLOSURE

DISCRETE STATUS AND CONTROL SIGNALS BETWEEN LCP

CONTROL SECTION AND THE SCADA SYSTEM.

ANALOG STATUS AND CONTROL SIGNALS BETWEEN LCP

CONTROL SECTION AND THE SCADA SYSTEM.

2#12, 1#12G

FE

PE

FIT

MANUFACTURERS INTEGRAL CABLE. COORDINATE

WITH MANUFACTURER FOR CONDUIT SIZE REQUIRED.

MINIMUM SIZE SHALL BE 3/4".

PVC COATED RGS FOR ALL ANALOG SIGNALS.

PS DISCHARGE

FLOW

DISCHARGE

HEADER

PRESSURE

120VAC

M

# - REFER TO INSTRUMENTATION

SPECIFICATIONS FOR INSTRUMENT ID

TAG NUMBERS AND ADDITIONAL DETAILS

LE

WET WELL LEVEL

TRANSDUCER

(BIRD CAGE)

LIT

120VAC

LEVEL

TO SCADA SYSTEM SECTION

(5) INTEGRAL FLOAT

CABLES, 2"C

ANTENNA

SEE DWG E-06 FOR ANTENNA

AND MAST DETAILS

LOCAL CONTROL PANEL VENDOR SHALL CONFIRM SIZE OF

CIRCUIT BREAKERS RECOMMENDED BY THE PUMP VENDOR.

M

DESIGNED

DRAWN

CHECKED

PROJ. ENGR.

DATENo. ISSUED FOR BY

CAD REFERENCE:

ENGINEERS PROJECT:

CLIENTS PROJECT:

CONTRACT:

41055-081

REF. No.

DRAWING:

SHEET:

DATE:

OF

P.E.

DRAWING.

THE SCALE BAR

SHOWN BELOW

MEASURES ONE

INCH LONG ON

THE ORIGINAL

CITY OF HOMESTEAD

HAZEN AND SAWYER

999 PONCE de LEON BLVD, SUITE 1150

CORAL GABLES, FLORIDA 33134

LICENSE No.: 2771 BI

D S

ET

JOHN C. BURKE

17301

PUMP STATION 22 UPGRADES

JUNE 2025

41055-081

J.M.B.

J.M.B.

E003J.C.B.

41055-081-E-03.DWG

C.L.K.

ELECTRICAL SINGLE LINE RISER

INCOMING

HES PRIMARY

EXISTING PRIMARY SIDE

CONDUITS AND WIRING

EXISTING 500kVA, 13.2kV-480V, 3ɸ

UTILITY SERVICE TRANSFORMER

SIZED AND PROVIDED BY HES

HES

3/4"C, 3#14, 1#14G

ST

GEN SET

GCP-1

AUX LOADS POWERED

FROM INTEGRAL

LIGHTING PANEL

STANDBY EMERGENCY RATED

GENERATOR

125 kW, 156.2 kVA 188 AMPS

480V, 3PH, 4W+GND

N

GND

ESB ARE PUSH-PULL MOUNTED BUTTONS,

FURNISHED AND INSTALLED BY THE CONTRACTOR,

MOUNTED ADJACENT TO THE EQUIPMENT. ONE "ESB"

SHALL OPEN THE UTILITY MAIN AND ONE SHALL

OPEN THE GENERATOR MAIN BREAKERS AND SHALL

SHUT DOWN THE GENERATOR DIESEL ENGINE

3/4"C, FOC TO SCADA

GENERATOR RUNNING

GENERATOR PRE-ALARMS

GENERATOR FAULT

GENERATOR FUEL TANK LEVEL

ESB

L

S1 S2

SHUNT

TRIP

CROUSE HINDS

ARKTITE GENERATOR

RECEPTACLE MODEL

#AR4041-S22

SEE MECHANICAL

DRAWINGS FOR

EQUIPMENT RACK

ELEVATIONS AND

RECOMMENDED

ORIENTATION

HOMESTEAD PS-22 SERVICE LOAD CALCULATIONS

LOAD DESCRIPTION CONNECTED

kVA

CONNECTED

AMPS

OPERATING

AMPS

35 46 41 35 46 41 35 46 41

7.5 16 11 5 10 8

9 12 8

STATUS AND CONTROL SIGNALS BETWEEN GENERATOR AND

THE SCADA SYSTEM.

1"C,

(10) #10, (1)#10

SERVICE ENTRANCE

RATED MAIN BREAKER

NEMA 4X, 316 SS

AVAILABLE FAULT CURRENT AT HOMESTEAD PS-22

DESCRIPTION V PH kVA IMP FAULT

CALCULATED MAR, 2025

UTILITY TRANSFORMER 480 3 500 1.30% 46263

MOTOR CONTRIBUTION 480 3 90 25 542

TOTAL FAULT AMPS: 46805

(3) #6 AWG (PWR)

(2) #10 AWG (CTRL)

(1) #8 AWG (GND) (1)

#10 AWG (GC)

APPROX CABLE DIA.

1.22" BY PUMP MFG. IN

3" CONDUIT EA

MECHANICAL INTERLOCK

3P-90A 3P-90A 3P-90A

INTERFACE

TO SCADA

ESB

SPD

3#14, 1#14G

NN

UTILITY SERVICE

TRANSFORMER

ATS

GENERATOR

SET

TO LOAD

POWER AND GROUNDING DETAIL

NOT SEPARATELY DERIVED

NOTE:

1. NO NEUTRAL LOAD ON THE FEEDER WIRING THEREFORE THE

NEUTRAL CABLES SHALL BE SIZED PER NEC 250.66.

GG G

S1 S2

N

ATS 480V, 200A

3Ø, 3P, 3W / GND,

65kA

OPEN TRANSITION

CONTACTOR, NEMA 3R

(3)#3/0, (1)#4, 2"C

(3)#3/0, (1)#4, 2"CEXISTING BYPASS PUMPING ELECTRICAL

EQUIPMENT SHALL BE DEMOLISHED

AFTER NEW STATION ELECTRICAL

EQUIPMENT IS ACTIVATED AND

ACCEPTED BY THE OWNER. EXISTING

UTILITY CAN SHALL BE REUSED FOR

FINAL ELECTRICAL.

(3)#3/0, (1)#4, 2"C

(3)#3/0, (1)#4, 2"C

SERVICE ENTRANCE

RATED MAIN BREAKER

CB1 CB2 CB3 CB4 CB5 CB6 CB7 CB8 CB9 CB10 CB11

LCP IN SEPARATE WHITE

POWDER COATED 304 SS

ENCLOSURE

LOW LEVEL ALARM

HIGH LEVEL ALARM

FLOATS AND MOTORS

CONNECTION BOXES

ATS PROVIDED BY OTHERS AND

INSTALLED BY THE CONTRACTOR

CIRCUITS FOR AUXILIARY

EQUIPMENT

FUEL LEAK ALARM AND

GENERATOR ALARMS PANEL

BY GENERATOR VENDOR

PPUPPUPPU

CSO

PPU - PUMP PROTECTION UNIT (MiniCAS)

CSO - CONDUIT SEAL OFF FITTING

CSOCSOCSO

CSO

ANALOG LEVEL CONTROL

(-) 2.00

(-) 3.50

(-) 4.75

(-) 5.75

(-) 11.25

(-) 11.50

FLOATS LEVEL CONTROL

(-) 1.50

(-) 12.00

FI

PI

LI

EQUIPMENT FURNISHED BY OTHERS

INSTALLED BY THE CONTRACTOR

UTILITY SERVICE MAIN BREAKER

AUTOMATIC TRANSFER SWITCH

STATION LOCAL CONTROL PANEL

SCADA PANEL & ANTENNA

EMERGENCY BACKUP GENERATOR

SUBMERSIBLE PUMPS

GENERATOR

RECEPTACLE

LED

SIZE TRANSFORMER AND ASSOCIATED

CIRCUIT BREAKERS FOR LOAD.

MINIMUM SIZE SHALL BE 5kVA

3kVA 480-120

1 PH

DESIGNED

DRAWN

CHECKED

PROJ. ENGR.

DATENo. ISSUED FOR BY

CAD REFERENCE:

ENGINEERS PROJECT:

CLIENTS PROJECT:

CONTRACT:

41055-081

REF. No.

DRAWING:

SHEET:

DATE:

OF

P.E.

DRAWING.

THE SCALE BAR

SHOWN BELOW

MEASURES ONE

INCH LONG ON

THE ORIGINAL

CITY OF HOMESTEAD

HAZEN AND SAWYER

999 PONCE de LEON BLVD, SUITE 1150

CORAL GABLES, FLORIDA 33134

LICENSE No.: 2771 BI

D S

ET

JOHN C. BURKE

17301

PUMP STATION 22 UPGRADES

JUNE 2025

41055-081

J.M.B.

J.M.B.

E004J.C.B.

41055-081-E-04.DWG

C.L.K.

LOCAL CONTROL PANEL SCHEMATIC

La st s av ed : 6

/2 6/

:0

PM

B y:

jb ro ad Pl ot te d:

/2 6/

:4

PM

File Path: C:\Users\Jbroad\DC\ACCDocs\Hazen and Sawyer\41055-081-PS 22 and FM Upgrades\Project Files\01_Design\Elec\41055-081-E-04.dwg

ALARM TEST

R

ES

ET

RESET

RESET

RESET

DESIGNED

DRAWN

CHECKED

PROJ. ENGR.

DATENo. ISSUED FOR BY

CAD REFERENCE:

ENGINEERS PROJECT:

CLIENTS PROJECT:

CONTRACT:

41055-081

REF. No.

DRAWING:

SHEET:

DATE:

OF

P.E.

DRAWING.

THE SCALE BAR

SHOWN BELOW

MEASURES ONE

INCH LONG ON

THE ORIGINAL

CITY OF HOMESTEAD

HAZEN AND SAWYER

999 PONCE de LEON BLVD, SUITE 1150

CORAL GABLES, FLORIDA 33134

LICENSE No.: 2771 BI

D S

ET

JOHN C. BURKE

17301

PUMP STATION 22 UPGRADES

JUNE 2025

41055-081

J.M.B.

J.M.B.

E005J.C.B.

41055-081-E-05.DWG

C.L.K.

ELECTRICAL DETAILS

La st s av ed : 6

/2 6/

:0

PM

B y:

jb ro ad Pl ot te d:

/2 6/

:4

PM

File Path: C:\Users\Jbroad\DC\ACCDocs\Hazen and Sawyer\41055-081-PS 22 and FM Upgrades\Project Files\01_Design\Elec\41055-081-E-05.dwg

ELAPSED TIME RECORDERS

DUPLEX STATION FUNCTION RECORDER

PUMP 1 RUNNING ETM1

PUMP 2 RUNNING ETM2

PUMP 3 RUNNING ETM3

PUMPS 1, 2, & 3 RUNNING SIMULTANEOUSLY ETM4

PUMP 1 RUNNING DURING AGENCY SELECTED

TIME OF DAY RANGE ETM5

PUMP 2 RUNNING DURING AGENCY SELECTED

TIME OF DAY RANGE ETM6

PUMP 3 RUNNING DURING AGENCY SELECTED

TIME OF DAY RANGE ETM7

3" X 10' CONCRETE

FILLED SCHD. 120

GALV. STEEL PIPE

WITH PVC CAP

TYPICAL OF BOTH

SUPPORTS

2" X 20' SCHD. 120

GALV. STEEL PIPE

5/8"x10' COPPER

CLAD GROUND ROD

GRADE

#6 BARE

COPPER

GROUND

ANTENNA: SCALA PART

#: TY-900

MOUNTED ON 2" PIPE

ANTENNA CABLE SHALL

BE STRAPPED TO PIPE

AT 48" SPACING

5/8"x10' COPPER

CLAD GROUND ROD

#6 COPPER GROUND

FI

PI

LI

Sheets and Views
E001 ELECTRICAL NOTES
E002 ELECTRICAL LEGENDS AND SYMBOLS
E003 ELECTRICAL SINGLE LINE RISER
E004 LOCAL CONTROL PANEL SCHEMATIC
E005 ELECTRICAL DETAILS

File details come from the government source that posted it. Updated .