41055-081_PS22_includes_OFE_DRAWING_PUMP_C.P._RTU.pdf
PDF 1 MB Posted
- Attached to
- ITB# 202536 Purchase of Submersible Pumps and Control Panel to Upgrade Pump Station #22 - RE-BID
- Solicitation number
- 202536
- Issued by
- Miami-Dade County, Florida
About this file
This document is an electrical design set for the City of Homestead Pump Station 22 Upgrades, prepared by Hazen and Sawyer, a professional engineering firm located in Coral Gables, Florida. The project involves comprehensive electrical system upgrades for a municipal pump station, including electrical notes, legends, single line risers, control panel schematics, and detailed electrical drawings. The design is dated June 2025 and covers a complete electrical infrastructure overhaul, including a new 125 kW emergency standby generator, automatic transfer switch, local control panel, SCADA system integration, and associated electrical equipment for a water/wastewater infrastructure project.
The electrical design includes specific technical specifications for conduit systems, conductors, grounding, instrumentation, and control systems. The project's electrical load calculations show a total connected load of approximately 152 kVA, with available fault current calculated at 46,805 amps. The design incorporates multiple safety and operational features, such as emergency stop buttons, arc-flash hazard warning labels, surge protection devices, and compliance with National Electrical Code (NEC) 2020 edition and other relevant standards. The electrical system is designed to support pump station operations, including three submersible pumps, site lighting, receptacles, control systems, and telemetry equipment, with a focus on reliability, safety, and modern electrical infrastructure standards.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
DESIGNED
DRAWN
CHECKED
PROJ. ENGR.
DATENo. ISSUED FOR BY
CAD REFERENCE:
ENGINEERS PROJECT:
CLIENTS PROJECT:
CONTRACT:
41055-081
REF. No.
DRAWING:
SHEET:
DATE:
OF
P.E.
DRAWING.
THE SCALE BAR
SHOWN BELOW
MEASURES ONE
INCH LONG ON
THE ORIGINAL
CITY OF HOMESTEAD
HAZEN AND SAWYER
999 PONCE de LEON BLVD, SUITE 1150
CORAL GABLES, FLORIDA 33134
LICENSE No.: 2771 BI
D S
ET
JOHN C. BURKE
17301
PUMP STATION 22 UPGRADES
JUNE 2025
41055-081
J.M.B.
J.M.B.
E001J.C.B.
41055-081-E-01.DWG
C.L.K.
ELECTRICAL NOTES
La st s av ed : 4
/1 1/
:0
PM
B y:
jb ro ad Pl ot te d:
/2 6/
:4
PM
File Path: C:\Users\Jbroad\DC\ACCDocs\Hazen and Sawyer\41055-081-PS 22 and FM Upgrades\Project Files\01_Design\Elec\41055-081-E-01.dwg
BASIC ELECTRICAL REQUIREMENTS:
1. SCOPE OF WORK
1.1. THE SCOPE OF WORK SHALL BE AS DESCRIBED IN SPECIFICATION
SECTION 16050.
1.2. THE CONTRACTOR SHALL OBTAIN ALL NECESSARY PERMITS,
INSPECTIONS AND APPROVALS AND TO INCLUDE ALL FEES AS PART OF
HIS BID IF NOT OTHERWISE NOTED.
1.3. THE CONTRACTOR SHALL, BEFORE SUBMITTING HIS BID, VISIT THE SITE
OF THE PROJECT AND BECOME FAMILIAR WITH THE EXISTING
CONDITIONS. NO ALLOWANCE WILL BE MADE FOR EXISTING CONDITIONS
OR FAILURE OF THE CONTRACTOR TO OBSERVE THEM.
1.4. IT IS THE CONTRACTOR'S RESPONSIBILITY TO COORDINATE WITH ALL
LOCAL UTILITIES, INCLUDING THE POWER AND TELEPHONE UTILITIES TO
MEET ALL OF THEIR INSTALLATION REQUIREMENTS. ALL FEES, LABOR,
EQUIPMENT OR MATERIALS NECESSARY TO MEET THESE
REQUIREMENTS IS TO BE INCLUDED IN THE BID. THE CONTRACTOR
SHALL OBTAIN, DELIVER AND INSTALL ALL CONDUITS, PULL-BOXES AND
EQUIPMENT AS REQUIRED BY THE UTILITIES TO THEIR SPECIFICATIONS.
1.5. THE CONTRACTOR SHALL COORDINATE HIS WORK WITH THE ENGINEER
AND OWNER.
1.6. THE CONTRACTOR SHALL PROVIDE ALL MATERIALS AND LABOR TO
INSTALL THE ELECTRICAL SYSTEMS AS INDICATED ON THE DRAWINGS
AND FURTHER DETAILED IN THE SPECIFICATIONS. ITEMS NOT SHOWN
BUT OBVIOUSLY NECESSARY FOR COMPLETION OF THE WORK SHALL BE
INCLUDED.
1.7. ALL EQUIPMENT AND MATERIAL SHALL BE NEW, UNUSED AND U.L.
LISTED. ALL REFERENCES TO A PARTICULAR MANUFACTURER ARE
GIVEN ON AN "APPROVED EQUAL" BASIS UNLESS OTHERWISE NOTED.
1.8. THE CONTRACTOR IS RESPONSIBLE TO TEST ALL SYSTEMS INSTALLED
OR MODIFIED UNDER THIS PROJECT AND REPAIR OR REPLACE ALL
DEFECTIVE WORK TO THE SATISFACTION OF THE ENGINEER AND
OWNER.
1.9. ALL EQUIPMENT FURNISHED AND INSTALLED BY THE CONTRACTOR
SHALL BE GUARANTEED AGAINST DEFECTS IN MATERIAL AND
WORKMANSHIP FOR A PERIOD OF ONE YEAR FROM DATE OF
ACCEPTANCE UNLESS OTHERWISE NOTED.
1.10. SHOP DRAWINGS SHALL BE SUBMITTED FOR ALL ELECTRICAL &
CONTROL EQUIPMENT AND MATERIAL.
2. CODES AND STANDARDS
2.1. THE INSTALLATION SHALL BE IN ACCORDANCE WITH THE MINIMUM
FOLLOWING STANDARDS AND CODES:
2.2. NATIONAL FIRE PROTECTION ASSOCIATION (NFPA)
2.3. NATIONAL ELECTRICAL CODE (NEC) 2020 EDITION)
2.4. NATIONAL ELECTRICAL SAFETY CODE, (NFPA 70E 2024 EDITION)
STANDARD FOR FIRE PROTECTION IN WASTEWATER TREATMENT AND
COLLECTION FACILITIES, (NFPA 820 2024 EDITION)
2.5. OTHER NFPA CODES AS APPLICABLE
2.6. FLORIDA BUILDING CODE (FBC 2023 EDITION)
2.7. LOCAL CODES, CITY CODES REQUIRED BY THE AUTHORITY HAVING
JURISDICTION.
2.8. AMERICAN NATIONAL STANDARDS INSTITUTE (ANSI)
2.9. NATIONAL ELECTRICAL MANUFACTURERS ASSOCIATION (NEMA)
2.10. INSTITUTE OF ELECTRICAL AND ELECTRONIC ENGINEERS (IEEE)
2.11. INSULATED CABLE ENGINEERS ASSOCIATION (ICEA)
2.12. OCCUPATIONAL SAFETY AHD HEALTH ACT (OSHA)
2.13. AMERICAN SOCIETY FOR TESTING AND MATERIALS (ASTM)
2.14. UNDERWRITERS LABORATORIES (UL) LISTING AND LABELING FOR ALL
MATERIALS AND EQUIPMENT WHERE APPLICABLE STANDARDS EXIST
3. GENERAL ITEMS
3.1. ALL CIRCUITS SHALL BE IDENTIFIED IN JUNCTION BOXES, PULL BOXES
3.2. ALL LOCATIONS OF EQUIPMENT, PANELS ETC. ARE SHOWN FOR
ILLUSTRATION PURPOSES. CONTRACTOR SHALL VERIFY AND
COORDINATE EXACT LOCATION AND SIZE WITH ALL SUBCONTRACTORS
AND EQUIPMENT SUPPLIERS PRIOR TO ANY INSTALLATION AND THEN
INSTALL AS SUCH WITH CORRESPONDING CONDUIT STUB-UPS.
3.3. SEE OTHER DISCIPLINE DRAWINGS FOR COORDINATION OF ALL
DRAWINGS. ANY CONFLICTS SHALL BE BROUGHT TO THE ENGINEER'S
ATTENTION AND MOVEMENT OF CONDUITS OR OTHER ELECTRICAL
EQUIPMENT SHALL BE ACCOMPLISHED WITHOUT ANY ADDITIONAL COST
FOR THE OWNER.
3.4. THE CONTRACTOR SHALL BE RESPONSIBLE FOR ALL CONDUIT AND
WIRING INSTALLATION FOR ALL VENDOR PROVIDED EQUIPMENT
(PACKAGE SYSTEMS). IF THE SHOP DRAWINGS DIFFER FROM THE
DESIGNED FACILITIES, THE CONTRACTOR SHALL REDESIGN THE
FACILITIES AND SUBMIT THE REVISED DESIGN FOR THE ENGINEER'S
APPROVAL ALONG WITH THE SHOP DRAWINGS. THERE SHALL BE NO
ADDITIONAL COST TO THE OWNER FOR THE REDESIGN NOR FOR ANY
ADDITIONAL CONDUITS AND WIRING. DURING SUBMITTAL THE CONTRACTOR
SHALL VERIFY ALL SUPPLIED BREAKER SIZES FOR ALL PACKAGED SYSTEMS SUCH
AS HVAC, EXHAUST FANS, MIXERS, CHEMICAL PUMPS ETC. AND MODIFY ALL
BREAKERS IN MCC'S AND PANELBOARDS ACCORDINGLY WITHOUT ANY
ADDITIONAL COST TO THE OWNER.
3.5. CONTRACTOR SHALL RESTORE SIDEWALKS, ROADWAYS, SOD AND
SPRINKLER SYSTEM PIPING TO MATCH EXISTING, AFTER THE
COMPLETION OF THE CONDUIT AND PULLBOX INSTALLATION.
3.6. ELECTRICAL EQUIPMENT SHALL BE DEFINED AS ANY ELECTRICAL
DEVICE USED IN CONJUNCTION WITH OTHER EQUIPMENT REQUIRING
ELECTRICITY FOR OPERATION. THIS INCLUDES BUT IS NOT LIMITED TO:
DISCONNECT SWITCHES, JUNCTION BOXES, PANELBOARDS,
TRANSFORMERS, LIGHTING FIXTURES, MOTOR STARTERS, SWITCHGEAR,
MOTOR CONTROL CENTERS, CONTROLS, LOCAL CONTROL PANELS.
3.7. ALL REFERENCES TO STAINLESS STEEL (SS) SHALL MEAN TYPE 316
STAINLESS STEEL UNLESS OTHERWISE NOTED.
3.8. ALL ELECTRICAL EQUIPMENT IN DESIGNATED CORROSIVE AREAS SHALL
BE NEMA 4X 316 STAINLESS STEEL OR NON-METALLIC (FRP).
3.9. OUTDOOR LIGHTING FIXTURES SHALL BE COPPER FREE ALUMINUM.
3.10. CONTRACTOR SHALL PROVIDE AS PART OF THE ELECTRICAL SUBMITTAL,
A LAYOUT OF THE ELECTRICAL ROOM SHOWING SIZES OF ALL
EQUIPMENT INCLUDING LIGHTING, AND HVAC WITH THEIR SPATIAL
RELATIONSHIPS.
3.11. CONTRACTOR SHALL PROVIDE AND INSTALL WIRE ID TAGS ON ALL
WIRING THAT INTERFACES WITH OTHER EQUIPMENT. INSTRUMENTATION
WIRING SHALL BE AS SHOWN FOR THE DFS SCHEDULE ON DRAWING ###.
4. OPERATION AND MAINTENANCE MANUALS
4.1. CONTRACTOR SHALL PROVIDE AN OPERATION AND MAINTENANCE
MANUAL PER FBC EC C405.7.4.2 INCLUDING:
4.1.1. SUBMITTAL DATA STATING EQUIPMENT RATING AND SELECTED OPTION
FOR EACH PIECE OF EQUIPMENT REQUIRING MAINTENANCE.
4.1.2. OPERATION AND MAINTENANCE MANUALS FOR EACH PIECE OF
EQUIPMENT REQUIRING MAINTENANCE. REQUIRED ROUTINE
MAINTENANCE ACTIONS SHALL BE CLEARLY IDENTIFIED
4.1.3. NAMES AND ADDRESSES OF AT LEAST ONE QUALIFIED SERVICE AGENCY
SEE SPECIFICATIONS FOR ADDITIONAL DETAILS
5. PROJECT CLOSEOUT
5.1. CONTRACTOR SHALL PROVIDE RECORD DRAWINGS TO THE OWNER AND
ENGINEER WITHIN 30 DAYS OF PUMP STATION ACCEPTANCE. THESE
SHALL INCLUDE PER FBC EC C405.7.4.1:
5.2. A LAMINATED AND FRAMED MINIMUM 11X17 INCH SINGLE LINE DIAGRAM
OF THE SITE ELECTRICAL SYSTEM SHALL BE PROVIDED FOR
INSTALLATION ADJACENT TO THE MAIN ELECTRICAL GEAR.
5.3. PLAN VIEWS OF COMPLETE PUMP STATION
6. RACEWAYS:
6.1. CONDUITS RUN IN PARALLEL: INSTRUMENTATION CONDUITS SHALL HAVE
A MINIMUM SEPARATION FROM POWER CONDUITS AS INDICATED IN
TABLE WHETHER CONCRETE ENCASED DUCT BANKS, DIRECT BURIED,
SURFACE OR RACKS:
VOLTAGE DISTANCE
6.1.1. 4160V 3 FT
6.1.2. 480V 2 FT
6.1.3. 120V 1 FT
6.2. NOT ALL CONDUITS SHOWN ON RISER AND ONE-LINE DIAGRAMS ARE
SHOWN ON BUILDING LAYOUTS. CONTRACTOR SHALL SUPPLY ALL
CONDUITS AND CABLES AS SHOWN ON RISERS AND ONE-LINE
DIAGRAMS.
6.3. EXPOSED RUNS OF CONDUITS SHALL BE INSTALLED WITH RUNS
PARALLEL OR PERPENDICULAR TO WALLS, STRUCTURAL MEMBERS OR
INTERSECTIONS OF VERTICAL PLANES AND CEILINGS, WITH RIGHT
ANGLE TURNS CONSISTING OF SYMMETRICAL BENDS OR PULL BOXES
AS INDICATED ON THE DRAWINGS. BENDS AND OFFSETS SHALL BE
AVOIDED WHERE POSSIBLE.
6.4. THE DRAWINGS ARE NOT INTENDED TO SHOW THE EXACT LOCATION OF
CONDUIT RUNS. THESE ARE TO BE COORDINATED WITH THE OTHER
TRADES SO THAT CONFLICTS ARE AVOIDED PRIOR TO INSTALLATIONS.
6.5. CONTRACTOR SHALL CORE DRILL EXISTING CONCRETE WALLS, FLOORS,
MANHOLES, HAND HOLES AND PULL BOXES FOR CONDUIT
PENETRATIONS. SEAL PENETRATIONS WITH NON-SHRINK GROUT OR
APPROPRIATE FIRE RATED DEVICES WHERE APPLICABLE.
6.6. ALL CONDUITS PENETRATING RATED FIRE WALLS OR RATED FIRE
FLOORS SHALL BE INSTALLED WITH U.L. APPROVED DEVICES AND OR
FIRE RATED SEALING COMPOUND TO MAINTAIN THE FIRE RATING OF THE
WALL OR FLOOR PENETRATED.
6.7. PROVIDE CONDUIT DUCT SEAL AT ALL CONDUIT ENDS.
6.8. ALL SPARE, ABANDONED, OR EMPTY CONDUITS SHALL BE SEALED WITH
A CAP AT BOTH ENDS AND A PULL STRING INSTALLED WITH
IDENTIFICATION OF OTHER END LOCATION AT BOTH ENDS.
6.9. FLEXIBLE CONDUITS SHALL BE USED TO TERMINATE ALL MOTORS AND
OTHER VIBRATING EQUIPMENT AND SHALL BE BETWEEN 18" AND 36" IN
LENGTH.
6.10. ALL METALLIC CONDUITS BELOW GRADE TO A MINIMUM ELEVATION OF
12 INCHES ABOVE GRADE SHALL BE PVC COATED RIGID METAL CONDUIT
(RMC).
6.11. ALL METALLIC CONDUITS 12 INCHES AND GREATER ABOVE GRADE SHALL
BE RMC.
6.12. ALL REFERENCES TO RMC SHALL MEAN RIGID GALVANIZED STEEL
CONDUIT (RGS) UNLESS OTHERWISE NOTED.
6.13. ALL REFERENCES TO PVC COATED RMC SHALL MEAN PVC COATED RIGID
GALVANIZED STEEL CONDUIT (RGS) UNLESS OTHERWISE NOTED.
6.14. ALUMINUM CONDUIT SHALL NOT BE USED FOR INSTRUMENTATION
WIRING.
7. DUCT BANKS & MANHOLES
7.1. LOCATIONS OF MANHOLES, HANDHOLES AND PULL BOXES ARE
APPROXIMATE. CONTRACTOR SHALL COORDINATE EXACT LOCATION
WITH EXISTING AND NEW PIPING OR CONDUIT AND ADJUST
ACCORDINGLY.
7.2. COLORED WARNING TAPE 6" WIDE SHALL BE INSTALLED 8" BELOW
FINISHED GRADE DIRECTLY ABOVE ALL UNDERGROUND YARD CONDUITS
ACCORDING TO THE FOLLOWING SCHEDULE:
7.2.1. POWER: RED
7.2.2. ALL OTHER CONDUITS: GREEN
7.3. ALL EXCAVATIONS FOR CONDUITS, HANDHOLES, MANHOLES AND
PULLBOXES NEAR EXISTING PIPING, CONDUIT AND EQUIPMENT SHALL BE
HAND EXCAVATED AND COORDINATED WITH PLANT ENGINEER.
7.4. MINIMUM DEPTH FROM TOP OF DUCT BANKS OR CONDUITS TO FINISHED
GRADE SHALL BE 24" UNLESS OTHERWISE NOTED.
7.5. IF CONCRETE ENCASED DUCT BANKS INCLUDE POWER WITH ANY TYPE
OF SIGNALS EXCEPT FIBER OPTIC CABLE, ALL CONDUITS SHALL BE
METALLIC.
7.6. CONCRETE DUCT BANKS WITH POWER ONLY WIRING MAY BE PVC
UNLESS OTHERWISE NOTED ON THE DRAWINGS.
7.7. SLOPE DUCT BANKS A MINIMUM 3 INCHES PER 100 FEET DOWN AWAY
FROM BUILDINGS.
7.8. DUCT BANK CONCRETE SHALL BE MINIMUM CLASS C 2500 PSI
8. CONDUCTORS:
8.1. ALUMINUM CONDUCTORS SHALL NOT BE USED FOR THIS PROJECT.
8.2. CONDUCTOR PULLING TENSIONS SHALL NOT EXCEED MANUFACTURER'S
RECOMMENDATION. CONTRACTOR SHALL INSTALL PULL BOXES TO MEET
MANUFACTURER'S REQUIREMENTS.
8.3. COPPER CONDUCTORS FOR POWER WIRING WITH A VOLTAGE GREATER
THAN 240V TO GROUND SHALL BE XHHW-2. OTHER POWER WIRING
SHALL BE EITHER XHHW OR THWN STRANDED COPPER WIRING.
8.4. BRANCH CIRCUITS EXCEEDING 100 FT IN LENGTH SHALL BE WIRED WITH
MINIMUM #10 AWG COPPER WIRES. CONTRACTOR SHALL VERIFY
REQUIRED WIRE SIZE WITH VOLTAGE DROP CALCULATIONS.
8.5. BOXES
8.6. ALL ENCLOSURES, TJB, WIREWAY, PULL BOXES ETC. SHALL CONTAIN A
GROUNDING BUS. CONNECT ALL RACEWAY BONDS TO THIS BUS VIA
GROUNDING BUSHING AND EXTEND BONDING JUMPER FROM THIS BUS
TO THE ENCLOSURE.
8.7. ALL JUNCTIONS BOXES, LOCAL CONTROL PANELS, DISCONNECT
SWITCHES AND INSTALLATION HARDWARE INSTALLED OUTDOORS SHALL
BE 316 STAINLESS STEEL.
9. PANELS
9.1. ALL CONTROL PANELS SHALL BE CONSTRUCTED BY A UL 508A
APPROVED PANEL VENDOR AND SHALL BEAR A UL 508A LABEL ON THE
PANEL.
9.2. TYPEWRITTEN AND LAMINATED PANEL SCHEDULES SHALL BE INSTALLED
IN EACH PANELBOARD, AND TYPEWRITTEN TERMINAL BLOCK
SCHEDULES IN EACH CONTROL CABINET.
9.3. ALL PANELBOARDS SHALL INCLUDE AN INTEGRAL FACTORY INSTALLED
SURGE PROTECTION DEVICES (SPD AKA TVSS).
9.4. CONTRACTOR SHALL BALANCE PANELBOARD LOADS AT THE END OF THE
PROJECT.
10. GROUNDING
10.1. GROUNDING SHALL BE INSTALLED IN ACCORDANCE WITH NEC, ARTICLE
250. THE GROUNDING SYSTEM TEST SHALL NOT EXCEED A 48 HOUR
SPAN DRY RESISTANCE OF 10 OHMS. ADDITIONAL GROUNDING TO MEET
THIS REQUIREMENT SHALL BE INSTALLED AT NO EXTRA COST.
GROUNDING AND BONDING CONNECTIONS SHALL NOT BE PAINTED. ALL
GROUNDING CONNECTIONS SHALL BE EXOTHERMIC UNLESS
SPECIFICALLY INDICATED OTHERWISE.
10.2. AN EQUIPMENT GROUND WIRE SIZED PER NEC SHALL BE PULLED IN ALL
ELECTRICAL CONDUITS, POWER AND CONTROL, WHETHER OR NOT
INDICATED ON THE PLANS.
11. INSTRUMENTATION
11.1. INSTRUMENTATION IS LOW VOLTAGE SIGNALS SUCH AS 4-20MA,
TELEPHONE COMMUNICATION, FIRE ALARM COMMUNICATION. POWER
CONDUITS SHALL ONLY CROSS INSTRUMENTATION CONDUIT
PERPENDICULARLY AT RIGHT ANGLES WITH 6" SEPARATION.
11.2. THE POWER AND SIGNAL SIDES OF ALL EXTERIOR INSTALLED
INSTRUMENTATION SHALL HAVE SURGE PROTECTION AND SHALL BE
GROUNDED TO A SEPARATE GROUND ROD AT THE INSTRUMENT.
11.3. INSTRUMENTATION GROUND SHALL BE A #6 AWG COPPER CONNECTED
TO THE GROUND GRID OR CONNECTED TO A DRIVEN GROUND. #6
GROUND WIRE SHALL BE INSTALLED IN CONDUIT WHERE EXPOSED.
GROUND RODS SHALL BE 5/8" OR 3/4" BY A MINIMUM OF 20' IN LENGTH,
AS INDICATED ON THE DRAWINGS.
11.4. CONTRACTOR SHALL INSTALL A SWITCH TO DISCONNECT POWER AT
EACH FOUR WIRE INSTRUMENT. ALL INSTRUMENTATION WIRING SHALL
BE TERMINATED, LOOP TESTED LOCALLY AND BETWEEN THE BASE
STATION AND LOCAL PUMP STATION PRIOR TO FINAL STARTUP AND
ACCEPTANCE.
12. SIGNAGE
12.1. CONTRACTOR SHALL PROVIDE SIGNAGE PER NEC 110.24 AND NEC 702.7
AT THE SERVICE ENTRANCE EQUIPMENT.
12.2. CONTRACTOR SHALL PROVIDE SIGNAGE PER NFPA 110 FOR THE
EMERGENCY SHUT-OFF BUTTON LOCATED ON THE NORTH EAST
OUTSIDE CORNER OF THE ELECTRICAL BUILDING.
12.3. CONTRACTOR SHALL PROVIDE SIGNAGE PER NFPA 704 FOR THE FUEL
SUPPLY.
12.4. CONTRACTOR SHALL PROVIDE AND INSTALL ARC-FLASH HAZARD
WARNING LABELS PER NEC 110.16 AND 110.21. THESE RULES APPLY AS A
MINIMUM TO SWITCHBOARDS, SWITCHGEAR, PANELBOARDS, MOTOR
CONTROL CENTERS, INDUSTRIAL CONTROL PANELS, METER SOCKET
ENCLOSURES, AND ENCLOSED CIRCUIT BREAKERS.
13. ELECTRICAL DEVICES (SW AND RECP)
13.1. ALL RECEPTACLES SHALL BE INSTALLED 18" AFF UNLESS OTHERWISE
NOTED. LIGHT SWITCHES SHALL BE MOUNTED 48" AFF UNLESS
OTHERWISE NOTED.
13.2. ALL RECEPTACLES WITHIN 6' OF A SINK SHALL BE GFI.
13.3. CONTRACTOR SHALL PROVIDE, INSTALL, TERMINATE AND TEST NEW STATION
TELEMETRY EQUIPMENT. SEE DATA FLOW SCADA SYSTEMS (DFS) NOTES
BELOW.
ABBREVIATIONS
ABBR. DESCRIPTION
A AMMETER, AMPERE
AC ALTERNATING CURRENT
ACL ACROSS THE LINE MOTOR
STARTER
AF CB AMPERE FRAME SIZE
AFD ADJUSTABLE FREQUENCY DRIVE
AFF ABOVE FINISHED FLOOR
AFG ABOVE FINISHED GRADE
AHJ AUTHORITY HAVING
JURISTICTION
AIC SYMM. AMPS INTERRUPTING
CAP.
AL ALUMINUM
ARC ALUMINUM RIGID CONDUIT
AS AMMETER SENSOR OR SWITCH
ASYM ASYMMETRICAL
AT CB AMPERE TRIP SETTING
ATS AUTOMATIC TRANSFER SWITCH
AUX AUXILIARY
AWG AMERICAN WIRE GAUGE
BC BARE COPPER
BCG BATTERY CHARGER
BSDG BUILDING
C CONDUIT, CONTACTOR
CB CIRCUIT BREAKER
CDB CONC ENCASED DUCT BANK
CKT CIRCUIT
CMS/CS COMBINATION MOTOR STARTER
CNTL CONTROL
C.O. CONDUIT ONLY
CONC CONCRETE
CPT CONTROL POWER
TRANSFORMER
CR CONTROL RELAY
CT CURRENT TRANSFORMER
D DUCT BANK
DC DIRECT CURRENT
DEF DIESEL EXHAUST FLUID
DPM DIGITAL POWER MONITOR
DS DISCONNECT SWITCH
EC EMPTY CONDUIT
ECDB EX CONC ENCASED DUCT BANK
ECP EQUIPMENT CONTROL PANEL
EF EXHAUST FAN
EG EMERGENCY GENERATOR
EMH ELECT MANHOLE (SEE MAS)
EMT ELECTRICAL METAL TUBING
ENCL ENCLOSURE
EPB EXISTING PULLBOX
EPC ELECTRIC POWER CENTER
EQUIP EQUIPMENT
ERMC-A ELECTRICAL RIGID METAL
CONDUIT - ALUMINUM
ERMC-S ELECTRICAL RIGID METAL
CONDUIT - STEEL
ESB EMERGENCY STOP BUTTON
ETM ELAPSED TIME METER
EX EXISTING
FDR FEEDER
F,FU FUSE
FI FLOW INDICATOR
FLA FULL LOAD AMPS
FLEX FLEXIBLE CONDUIT
FLR FLOOR
FLUOR FLUORESCENT
FLVC FULL VOLTAGE LIGHTING
CONTACTOR
FM FLOW METER
F.O. FAIL OPEN
FOC FIBER OPTIC CABLE
FS FLOW SWITCH
FT FLOW TRANSMITTER
FUT FUTURE
FVNR FULL VOLTAGE NON-REVERSING
G GREEN, GROUND
GALV GALVANIZED
GC GROUNDED CONDUCTOR
GDR GROUNDING RESISTOR
GEC GROUNDING ELECTRODE
CONDUCTOR
GEN GENERATOR
GFCI GROUND FAULT
CIRCUITINTERRUPTER
GFR GROUND FAULT RELAY
GND GROUND
GRS/RM
C
GALVANIZED RIGID STEEL
(CONDUIT)
GTB GENERATOR TIE BREAKER
ABBREVIATIONS
ABBR. DESCRIPTION
HH HANDHOLE
HID HIGH INTENSITY DISCHARGE
HOA HAND/OFF/AUTO
HOR HAND/OFF/REMOTE
HP HORSEPOWER
HPS HIGH PRESSURE SODIUM
HTR HEATER
HV HIGH VOLTAGE
HVAC HEAT, VENTILATION, AIR COND.
HZ HERTZ (FREQUENCY)
IC INTERRUPTING CAPACITY
ID INSIDE DIAMETER
IMC INTERMEDIATE METAL CONDUIT
INST INSTANTANEOUS
I/O INPUT / OUTPUT SIGNALS
IP INSTRUMENT PANEL
JB JUNCTION BOX
K KEY OR KIRK KEY INTERLOCK
kcmil 1000 CIRCULAR MILS kV KILOVOLTS kVA KILOVOLT-AMPERE kVAR KILOVOLT-AMPERE REACTIVE kW KILOWATT kWh KILOWATT-HOUR
LA LIGHTING ARRESTER
LC LOAD CENTER
LCP LOCAL CONTROL PANEL
LCS LOCAL CONTROL STATION
LFMC LIQUID TIGHT FLEX METAL
CONDUIT
LP-# LIGHTING PANEL NUMBER #
LR LOCAL/REMOTE OR LATCHING
RELAY
LRA LOCKED ROTOR AMPS
LS LIMIT SWITCH
LTC LIGHTING CONTACTOR
LTG LIGHTING
LV LOW VOLTAGE
M MOTOR OR MOTOR CONTACTOR
MAS MAINTENANCE ACCESS
STRUCTURE
MA MILLIAMPS
MAX MAXIMUM
MBS MANUAL BYPASS SWITCH
MC METAL CLAD
MCA MAXIMUM CIRCUIT AMPS
MCB MAIN CIRCUIT BREAKER
MCC MOTOR CONTROL CENTER
MCP MASTER CONTROL PANEL
MDP MAIN DISTRIBUTION PANEL
MERC MERCURY VAPOR
MFG MANUFACTURER
MFR MULTI-FUNCTIONAL RELAY
MGB MAIN GROUNDING BUS
MJB MOTOR JUNCTION BOX
MLO MAIN LUGS ONLY
MOCP MAXIMUM OVERCURRENT
PROTECTION
MOV MOTOR OPERATED VALVE
MPZ MINI-POWER ZONE
MSC MFR SUPPLIED CABLE
MSH MOTOR SPACE HEATER
MTS MANUAL TRANSFER SWITCH
MT MOUNT
MTD MOTOR TEMPERATURE
DETECTOR
MV MEDIUM VOLTAGE
N NEUTRAL
NA NOT APPLICABLE
NC NORMALLY CLOSED
NEMA NATIONAL ELEC. MFR. ASSOC.
NF NON-FUSED
NIC NOT IN CONTRACT
NO NORMALLY OPEN
NP NAMEPLATE
NTS NOT TO SCALE
OC OCCUPANCY CONTROL
OD OUTSIDE DIAMETER
OL OVERLOAD
OH OVERHEAD
OWS OPERATOR WORK STATION
ABBREVIATIONS
ABBR. DESCRIPTION
P POLE
PB PULL BOX OR PUSH BUTTON
PC PHOTOCELL
PCP PROCESS CONTROL PANEL
PF POWER FACTOR
PH PHASE
PLC PROGRAMMABLE LOGIC
CONTROLLER
PMU POWER MONITOR UNIT
PNL PANEL
PP POWER PANEL (480VAC)
PR PAIR
PS PRESSURE SWITCH
PT POTENTIAL TRANSFORMER
PVC POLYVINYL CHLORIDE CONDUIT
PWR POWER
RCPT RECEPTACLE
REF REFERENCE
REQD REQUIRED
RGS RIGID GALVANIZED STEEL
CONDUIT
RMC RIGID METAL CONDUIT
RM ROOM
RMS ROOT MEAN SQUARE
RS RIGID STEEL
RTD RESISTANCE TEMPERATURE
DETECTOR
RTU REMOTE TELEMETRY UNIT
SA SURGE ARRESTER
SC SURGE CAPACITOR
SEC SECONDARY
SEL SELECTOR
SF SUPPLY FAN
SH SPACE HEATER
SLC SITE LIGHTING CONTROLLER
SLD SINGLE LINE DIAGRAM
SMH SIGNAL MAINTENANCE HOLE
S/N SOLID NEUTRAL
SPEC SPECIFICATIONS
SPD SURGE PROTECTIVE DEVICE
SSRVS SOLID STATE REDUCED VOLTAGE
ST.
SST STAINLESS STEEL
SUB SUBSTATION
SV SOLENOID VALVE
SW SWITCH
SWBD SWITCHBOARD
SWGR SWITCHGEAR
SYM SYMMETRICAL
SYS SYSTEM
T THERMOSTAT
TB TERMINAL BLOCK
TD TIME DELAY RELAY
TEL TELEPHONE
TEMP TEMPERATURE
TJB TERMINAL JUNCTION BOX
TSH TEMPERATURE SWITCH - HIGH
TSP TWISTED SHIELDED PAIR
TVSS TRANSIENT VOLTAGE SURGE
SUPPR.
TYP TYPICAL
UGE UNDERGROUND ELECTRIC UTILITY
U/G UNDERGROUND
UPS UNINTERRUPTIBLE POWER SUPPLY
UVR UNDERVOLTAGE RELAY
V VOLT OR VOLTMETER
VA VOLTAMPERE
VAR VOLTAMPERE REACTIVE
VFD VARIABLE FREQUENCY DRIVE
VS VOLTMETER SWITCH
W WATT
WHD WATTHOUR DEMAND METER
WP WEATHER PROOF
WS WORK STATION
WW WIREWAY
XFMR TRANSFORMER
XMTR TRANSMITTER
XP EXPLOSION PROOF
Z IMPEDANCE
J
F
F
W
FIRE ALARM STROBE LIGHT
FIRE ALARM PULL STATION
TELEPHONE/DATA RECEPTACLE MOUNTED FLUSH IN FLOOR
ELEVATOR WARNING LIGHT
LPA-2
YCX
DB
X
X
[B2]
P-
CRE-
D- K-
CONDUIT, STUBBED AND CAPPED AS SHOWN
GROUND WIRE, 4/O CU UNLESS OTHERWISE NOTED
DIRECT BURIED CONDUIT
THREE WAY
FOUR WAY
WEATHERPROOF
3-
WP-
4-
DOUBLE POLE2-
YARD CONDUIT. REFER TO YARD CONDUIT SCHEDULE
KEY OPERATED
CORROSION
PILOT LIGHT
RESISTANT
DIMMER
UNDERGROUND CONDUIT AND CONDUCTORS*
LIGHTING FIXTURE POWER AND SWITCHING LEGEND
EXPOSED CONDUIT AND CONDUCTORS*
HOME RUN - PANEL AND CIRCUIT NUMBER SHOWN
RECEPTACLE, SPECIAL PURPOSE - AMPERAGE AS INDICATED.
CONDUIT/CONDUCTOR - REFER TO CIRCUIT SCHEDULE
X
X
X
X
TERMINAL JUNCTION BOX
LIGHTING PANELBOARD "L(X)"
20A DUPLEX RECEPTACLE UNLESS SPECIFIED OTHERWISE
20A QUADRAPLEX RECEPTACLE - UNLESS SPECIFIED OTHERWISE
20A DUPLEX RECEPTACLE - UNLESS SPECIFIED OTHERWISE.
LOCATED ABOVE COUNTER TOP
CONDUIT CHASE
CONCRETE ENCASED DUCT BANK
CEILING MOUNTED DOWNLIGHT LUMINAIRE - SEE SCHEDULE FOR TYPE
FLUORESCENT LUMINAIRE, SURFACE OR LAY IN TYPE SEE
SCHEDULE FOR TYPE
LUMINAIRE AND POLE - SEE SCHEDULE FOR TYPE
WALL MOUNTED LUMINAIRE - SEE SCHEDULE FOR TYPE
EXIT LIGHTS - SOLID SECTION IS DIRECTION OF FACE
SEE SCHEDULE FOR TYPE
EMERGENCY LIGHT WITH BATTERY PACK
SEE SCHEDULE FOR TYPE
JUNCTION BOX NEMA 12 ENCLOSURE UNLESS INDICATED
OTHERWISE. 4X = NEMA 4X SS
TELEPHONE/DATA RECEPTACLE (OUTLET BOX, 18" AFF) W -
WALL MOUNTED, 54" AFF
FAAP
SD HD
SD
D
FIRE ALARM CONTROL PANEL
FIRE ALARM SMOKE OR HEAT DETECTOR
FIRE ALARM ANNUNCIATOR PANEL
DUCT SMOKE DETECTOR
WH WATER HEATER
GROUND ROD - 5/8" x 20' COPPER CLAD
UNLESS OTHERWISE NOTED
GROUND ROD IN TEST WELL - 5/8" x 20' COPPER CLAD
UNLESS OTHERWISE NOTED
X = FIXTURE TYPE
# = CIRCUIT NUMBER
WP - WEATHERPROOF C - CLOCK HANGER
TL - TWIST LOCK CRE - CORROSION RESISTANT
GFCI - GROUND FAULT INTERRUPTER FTC - FULL TIME COVER
A - AMBER
B - BLUE
C - CLEAR
R - RED
G - GREEN
W - WHITE
SCHEMATIC DIAGRAMS ONLY
INDICATING LIGHT - LETTER INDICATES COLOR
PUSH TO TEST AND CONNECT INDICATING LIGHT
C - CLEAR
A
W - WHITE
B - BLUE
A - AMBER G - GREEN
R - RED
TVSS
CPT
120V
(3)
GFR
0-600V
X
TRANSFORMER, VOLTAGES, PHASE AND RATING
INDICATED AS APPLICABLE
CURRENT TRANSFORMER, NUMBER OF WINDINGS
INDICATED
DRAWOUT FUSED SWITCH, LOW OR MEDIUM VOLTAGE
600= FRAME RATING, 400=FUSE RATING
DRAWOUT CIRCUIT BREAKER, MEDIUM VOLTAGE 600=
FRAME RATING, 400=TRIP SETTING
DRAWOUT CIRCUIT BREAKER, LOW VOLTAGE 600=
FRAME RATING, 400=TRIP SETTING
LIGHTNING ARRESTER
CAPACITOR OR SURGE CAPACITOR
FUSE
TRANSIENT VOLTAGE SURGE SUPPRESSION
GROUND
CONTROL TRANSFORMER
GROUND FAULT RELAY WITH C.T.
PUSH-BUTTON SWITCH, MOMENTARY CONTACT,
NORMALLY OPEN
PUSH-BUTTON SWITCH, MOMENTARY CONTACT,
NORMALLY CLOSED
PUSH BUTTON SWITCH, MAINTAINED CONTACTS WITH
MECHANICAL INTERLOCK
REMOTE DEVICE
METER SCALE RANGE SHOWN IF REQUIRED
PM - PHASE MONITOR A - AMPS
P - POWER METER V - VOLTS
A
480V
E ELECTRICAL INTERLOCK
XFMR DRY
kVA 480-120/208V
3P/4W
O - OPEN CONTACT
X - CLOSED CONTACT
HAND
OOX 1
CKT.
OH
XOO
A
POSITION
X O
O O
OFF AUTO
O X
G
225400
M
4X
4X
4X
NOTC
TDx
Rx
CRx
LRx (L)
LC
CRx
4X
4X
4X
S M
F
PB
1"C, 1-25/C TYPE 1
1"C, 2#12, 1#12G
SYMBOL
OR
DESCRIPTION
CRx OR
NONFUSED DISCONNECT SWITCH, SIZE INDICATED, 3 POLE UNLESS
INDICATED OTHERWISE, NEMA 12 ENCLOSURE, 4X = NEMA 4X STAINLESS
STEEL
FUSED DISCONNECT SWITCH, SIZE INDICATED (60 = SWITCH RATING: 40 =
FUSE RATING) 3 POLE UNLESS INDICATED OTHERWISE, NEMA 12
ENCLOSURE, 4X = NEMA 4X STAINLESS STEEL
LIGHTING CONTACTOR, CURRENT RATING INDICATED, NEMA 12 ENCLOSURE
UNLESS INDICATED OTHERWISE. SEE CONTROL DIAGRAM FOR NUMBER OF
POLES. 4X = NEMA 4X TYPE 316 STAINLESS STEEL
MAGNETIC STARTER, NEMA SIZE INDICATED, NEMA 12 ENCLOSURE, UNLESS
INDICATED OTHERWISE. SEE CONTROL DIAGRAM. 4X = NEMA 4X STAINLESS
STEEL
COMBINATION (FUSE OR CIRCUIT BREAKER AS INDICATED). MAGNETIC
STARTER, NEMA SIZE INDICATED, NEMA 12 ENCLOSURE UNLESS INDICATED
OTHERWISE. SEE CONTROL SCHEMATIC DIAGRAM. 4X = NEMA 4X STAINLESS
STEEL
ELECTRIC RESISTANCE HEATER
ELAPSED TIME METER
CONTACT - NORMALLY OPEN WITH COIL INDICATED
CONTACT - NORMALLY CLOSED WITH COIL INDICATED
CONTROL RELAY, X=SEQUENTIAL NUMBER
LATCHING RELAY, X=SEQUENTIAL NUMBER L - LATCH, U - UNLATCH
TIME DELAY RELAY, X=SEQUENTIAL NUMBER NOTC=NORMALLY OPEN TIMED
CLOSED NOTO=NORMALLY OPEN TIMED OPEN AFTER CLOSE
NCTO = NORMALLY CLOSED TIMED OPEN; NCTC = NORMALLY CLOSED TIMED
CLOSED AFTER OPEN
TEMPERATURE
CLOSES ON FALLING
TEMPERATURE
SELECTOR SWITCH: MAINTAINED CONTACT WITH CONTACT POSITION
INDICATED, CHART IDENTIFIES OPERATION
THIS IS A STANDARD LEGEND SHEET. SOME SYMBOLS OR ABBREVIATIONS MAY
APPEAR ON THIS SHEET AND NOT BE UTILIZED ON PROJECT.
INDICATES RACEWAY AND CIRCUIT CONDUCTORS. FIRST NUMBER IS
RACEWAY SIZE. THE FOLLOWING NUMBERS ARE THE CONDUCTOR
QUANTITIES, SIZES, AND TYPES.
CONNECTION POINT TO EQUIPMENT SPECIFIED, FURNISHED AND INSTALLED
UNDER OTHER SECTIONS. RACEWAY, CONDUCTOR AND CONNECTION IN
THIS SECTION.
MANUAL MOTOR STARTER SWITCH, NEMA 4X UNLESS OTHERWISE NOTED.
NUMBER OF POLES AS REQUIRED.
PUSH-BUTTON STATION, NEMA 12 ENCLOSURE UNLESS INDICATED
OTHERWISE. 4X = NEMA 4X STAINLESS STEEL ENCLOSURE. SEE CONTROL
DIAGRAMS FOR TYPE PUSH BUTTON REQUIRED.
FUSED SWITCH, SWITCH AND FUSE CURRENT RATING
INDICATED, 3 POLE UNLESS INDICATED OTHERWISE.
CIRCUIT BREAKER, THERMAL MAGNETIC TRIP SHOWN,
3 POLE UNLESS INDICATED OTHERWISE.
MOTOR CIRCUIT PROTECTOR, MAGNETIC, 3 POLE
UNLESS INDICATED OTHERWISE.
MAGNETIC STARTER WITH NEMA SIZE INDICATED
OVERLOAD RELAY HEATER
MOTOR, SQUIRREL CAGE INDUCTION UNLESS
OTHERWISE NOTED - HORSEPOWER INDICATED
DISC SWITCH - FUSED, NON-FUSED
GENERATOR
ETM
or
60A 3P
60A 3P
DESCRIPTIONSYMBOL DESCRIPTIONSYMBOL
CONTROL RELAY, X = SEQUENTIAL NUMBER
DESCRIPTIONSYMBOL
X #
X
20A DUPLEX RECEPTACLE - UNLESS SPECIFIED OTHERWISE.
MOUNTED FLUSH IN FLOOR.
FIRE ALARM HORN/STROBE LIGHTF
X WALL SWITCH:
# - CIRCUIT
NO.
FACP
D
POWER PANELBOARD "H(X)"
ELECTRICAL LOCAL CONTROL PANELSLCP
CLOSES ON RISING
TEMPERATURE
"X" IS WIRING TYPE
"###" CONDUIT IDENTIFICATION
YYY-X###
"YYY" IS AREA (IF USED)
"X" IS WIRING TYPE
"###" CONDUIT IDENTIFICATION
"A" = ANALOG SIGNAL WIRING
"C" = DISCRETE OR CONTROL WIRING
"D" = DATA HIGHWAY (FOC)
"L" = POWER CONDUCTORS 120-240V
"H" = POWER CONDUCTORS 440-480V
"U" = UTILITY POWER
MCC - ASTERISK
INDIVIDUAL MOTOR CONTROLLER (SQUARE)
PANEL (HEXAGON)
FIELD (TRIANGLE)
X
La st s av ed : 4
/1 1/
:0
PM
B y:
jb ro ad Pl ot te d:
/2 6/
:4
PM
File Path: C:\Users\Jbroad\DC\ACCDocs\Hazen and Sawyer\41055-081-PS 22 and FM Upgrades\Project Files\01_Design\Elec\41055-081-E-02.dwg
DESIGNED
DRAWN
CHECKED
PROJ. ENGR.
DATENo. ISSUED FOR BY
CAD REFERENCE:
ENGINEERS PROJECT:
CLIENTS PROJECT:
CONTRACT:
41055-081
REF. No.
DRAWING:
SHEET:
DATE:
OF
P.E.
DRAWING.
THE SCALE BAR
SHOWN BELOW
MEASURES ONE
INCH LONG ON
THE ORIGINAL
CITY OF HOMESTEAD
HAZEN AND SAWYER
999 PONCE de LEON BLVD, SUITE 1150
CORAL GABLES, FLORIDA 33134
LICENSE No.: 2771 BI
D S
ET
JOHN C. BURKE
17301
PUMP STATION 22 UPGRADES
JUNE 2025
41055-081
J.M.B.
J.M.B.
E002J.C.B.
41055-081-E-02.DWG
C.L.K.
ELECTRICAL LEGENDS AND SYMBOLS
PUMP STATION WET WELL IS CLASSIFIED AS A CLASS 1
DIVISION 1 HAZARDOUS LOCATION.
SEAL-OFF CONNECTIONS FOR ALL CONDUITS
PENETRATING TO OR FROM THE WET WELL SHALL COMPLY
WITH AND BE INSTALLED PER NEC 501-5-B.
LCP INTEGRAL LOADS
CKT DESC VA BKR WIRES CONDUIT
CB1 LCP 400 1P-20 2#12, 1#12G NA
CB2 LCP LTG & RECP 460 1P-20 2#12, 1#12G NA
CB3 SCADA 360 1P-20 NA NA
CB4 BIRD CAGE LEVEL 150 1P-20 2#12, 1#12G NA
CB5 MAG FLOW MTR 360 1P-20 2#12, 1#12G NA
CB6 SITE LIGHTING 180 1P-20 2#12, 1#12G 3/4 "PVC80
CB7 GEN ENG BLOCK HEATER 100 1P-20 2#12, 1#12G NA
CB8 GENERATOR HEATER 1000 1P-20 2#12, 1#12G
AS REQUIRED
CB9 BATTERY CHARGER 360 1P-20 2#12, 1#12G
CB10 LIGHTING 180 1P-20 2#12, 1#12G
CB11 RECEPTACLES 360 1P-20 2#12, 1#12G
TOTAL 3510
120V SCHEDULE SHOWN FOR GENERAL INFO ONLY. CIRCUIT BREAKERS ARE AN
INTEGRAL PART OF THE VENDOR PROVIDED CONTROL PANEL.
2P-15A
MOTOR CIRCUIT BREAKERS SHALL BE
ABLE TO BE LOCKED IN THE OPEN POSITION
3P-200A
EMERGENCY
BREAKER
3P-200A MAIN
BREAKER
CONTROL PANEL SHALL BE
LABELED PER UL-508-A
(3)#4, (3)#10, (1)#8 1-1/2"C
FLT2
FLT1
LCP
CONTROL
SECTION
INTRINSICALLY
SAFE
(12) #14, 1"C
(2) INTEGRAL FLOAT
CABLES, 1"C
353535
La st s av ed : 6
/2 6/
:3
PM
B y:
jb ro ad Pl ot te d:
/2 6/
:4
PM
File Path: C:\Users\Jbroad\DC\ACCDocs\Hazen and Sawyer\41055-081-PS 22 and FM Upgrades\Project Files\01_Design\Elec\41055-081-E-03.dwg
SCADA / RTU SYSTEM IN SEPARATE
WHITE POWDER COATED 304 SS
ENCLOSURE
DISCRETE STATUS AND CONTROL SIGNALS BETWEEN LCP
CONTROL SECTION AND THE SCADA SYSTEM.
ANALOG STATUS AND CONTROL SIGNALS BETWEEN LCP
CONTROL SECTION AND THE SCADA SYSTEM.
2#12, 1#12G
FE
PE
FIT
MANUFACTURERS INTEGRAL CABLE. COORDINATE
WITH MANUFACTURER FOR CONDUIT SIZE REQUIRED.
MINIMUM SIZE SHALL BE 3/4".
PVC COATED RGS FOR ALL ANALOG SIGNALS.
PS DISCHARGE
FLOW
DISCHARGE
HEADER
PRESSURE
120VAC
M
# - REFER TO INSTRUMENTATION
SPECIFICATIONS FOR INSTRUMENT ID
TAG NUMBERS AND ADDITIONAL DETAILS
LE
WET WELL LEVEL
TRANSDUCER
(BIRD CAGE)
LIT
120VAC
LEVEL
TO SCADA SYSTEM SECTION
(5) INTEGRAL FLOAT
CABLES, 2"C
ANTENNA
SEE DWG E-06 FOR ANTENNA
AND MAST DETAILS
LOCAL CONTROL PANEL VENDOR SHALL CONFIRM SIZE OF
CIRCUIT BREAKERS RECOMMENDED BY THE PUMP VENDOR.
M
DESIGNED
DRAWN
CHECKED
PROJ. ENGR.
DATENo. ISSUED FOR BY
CAD REFERENCE:
ENGINEERS PROJECT:
CLIENTS PROJECT:
CONTRACT:
41055-081
REF. No.
DRAWING:
SHEET:
DATE:
OF
P.E.
DRAWING.
THE SCALE BAR
SHOWN BELOW
MEASURES ONE
INCH LONG ON
THE ORIGINAL
CITY OF HOMESTEAD
HAZEN AND SAWYER
999 PONCE de LEON BLVD, SUITE 1150
CORAL GABLES, FLORIDA 33134
LICENSE No.: 2771 BI
D S
ET
JOHN C. BURKE
17301
PUMP STATION 22 UPGRADES
JUNE 2025
41055-081
J.M.B.
J.M.B.
E003J.C.B.
41055-081-E-03.DWG
C.L.K.
ELECTRICAL SINGLE LINE RISER
INCOMING
HES PRIMARY
EXISTING PRIMARY SIDE
CONDUITS AND WIRING
EXISTING 500kVA, 13.2kV-480V, 3ɸ
UTILITY SERVICE TRANSFORMER
SIZED AND PROVIDED BY HES
HES
3/4"C, 3#14, 1#14G
ST
GEN SET
GCP-1
AUX LOADS POWERED
FROM INTEGRAL
LIGHTING PANEL
STANDBY EMERGENCY RATED
GENERATOR
125 kW, 156.2 kVA 188 AMPS
480V, 3PH, 4W+GND
N
GND
ESB ARE PUSH-PULL MOUNTED BUTTONS,
FURNISHED AND INSTALLED BY THE CONTRACTOR,
MOUNTED ADJACENT TO THE EQUIPMENT. ONE "ESB"
SHALL OPEN THE UTILITY MAIN AND ONE SHALL
OPEN THE GENERATOR MAIN BREAKERS AND SHALL
SHUT DOWN THE GENERATOR DIESEL ENGINE
3/4"C, FOC TO SCADA
GENERATOR RUNNING
GENERATOR PRE-ALARMS
GENERATOR FAULT
GENERATOR FUEL TANK LEVEL
ESB
L
S1 S2
SHUNT
TRIP
CROUSE HINDS
ARKTITE GENERATOR
RECEPTACLE MODEL
#AR4041-S22
SEE MECHANICAL
DRAWINGS FOR
EQUIPMENT RACK
ELEVATIONS AND
RECOMMENDED
ORIENTATION
HOMESTEAD PS-22 SERVICE LOAD CALCULATIONS
LOAD DESCRIPTION CONNECTED
kVA
CONNECTED
AMPS
OPERATING
AMPS
35 46 41 35 46 41 35 46 41
7.5 16 11 5 10 8
9 12 8
STATUS AND CONTROL SIGNALS BETWEEN GENERATOR AND
THE SCADA SYSTEM.
1"C,
(10) #10, (1)#10
SERVICE ENTRANCE
RATED MAIN BREAKER
NEMA 4X, 316 SS
AVAILABLE FAULT CURRENT AT HOMESTEAD PS-22
DESCRIPTION V PH kVA IMP FAULT
CALCULATED MAR, 2025
UTILITY TRANSFORMER 480 3 500 1.30% 46263
MOTOR CONTRIBUTION 480 3 90 25 542
TOTAL FAULT AMPS: 46805
(3) #6 AWG (PWR)
(2) #10 AWG (CTRL)
(1) #8 AWG (GND) (1)
#10 AWG (GC)
APPROX CABLE DIA.
1.22" BY PUMP MFG. IN
3" CONDUIT EA
MECHANICAL INTERLOCK
3P-90A 3P-90A 3P-90A
INTERFACE
TO SCADA
ESB
SPD
3#14, 1#14G
NN
UTILITY SERVICE
TRANSFORMER
ATS
GENERATOR
SET
TO LOAD
POWER AND GROUNDING DETAIL
NOT SEPARATELY DERIVED
NOTE:
1. NO NEUTRAL LOAD ON THE FEEDER WIRING THEREFORE THE
NEUTRAL CABLES SHALL BE SIZED PER NEC 250.66.
GG G
S1 S2
N
ATS 480V, 200A
3Ø, 3P, 3W / GND,
65kA
OPEN TRANSITION
CONTACTOR, NEMA 3R
(3)#3/0, (1)#4, 2"C
(3)#3/0, (1)#4, 2"CEXISTING BYPASS PUMPING ELECTRICAL
EQUIPMENT SHALL BE DEMOLISHED
AFTER NEW STATION ELECTRICAL
EQUIPMENT IS ACTIVATED AND
ACCEPTED BY THE OWNER. EXISTING
UTILITY CAN SHALL BE REUSED FOR
FINAL ELECTRICAL.
(3)#3/0, (1)#4, 2"C
(3)#3/0, (1)#4, 2"C
SERVICE ENTRANCE
RATED MAIN BREAKER
CB1 CB2 CB3 CB4 CB5 CB6 CB7 CB8 CB9 CB10 CB11
LCP IN SEPARATE WHITE
POWDER COATED 304 SS
ENCLOSURE
LOW LEVEL ALARM
HIGH LEVEL ALARM
FLOATS AND MOTORS
CONNECTION BOXES
ATS PROVIDED BY OTHERS AND
INSTALLED BY THE CONTRACTOR
CIRCUITS FOR AUXILIARY
EQUIPMENT
FUEL LEAK ALARM AND
GENERATOR ALARMS PANEL
BY GENERATOR VENDOR
PPUPPUPPU
CSO
PPU - PUMP PROTECTION UNIT (MiniCAS)
CSO - CONDUIT SEAL OFF FITTING
CSOCSOCSO
CSO
ANALOG LEVEL CONTROL
(-) 2.00
(-) 3.50
(-) 4.75
(-) 5.75
(-) 11.25
(-) 11.50
FLOATS LEVEL CONTROL
(-) 1.50
(-) 12.00
FI
PI
LI
EQUIPMENT FURNISHED BY OTHERS
INSTALLED BY THE CONTRACTOR
UTILITY SERVICE MAIN BREAKER
AUTOMATIC TRANSFER SWITCH
STATION LOCAL CONTROL PANEL
SCADA PANEL & ANTENNA
EMERGENCY BACKUP GENERATOR
SUBMERSIBLE PUMPS
GENERATOR
RECEPTACLE
LED
SIZE TRANSFORMER AND ASSOCIATED
CIRCUIT BREAKERS FOR LOAD.
MINIMUM SIZE SHALL BE 5kVA
3kVA 480-120
1 PH
DESIGNED
DRAWN
CHECKED
PROJ. ENGR.
DATENo. ISSUED FOR BY
CAD REFERENCE:
ENGINEERS PROJECT:
CLIENTS PROJECT:
CONTRACT:
41055-081
REF. No.
DRAWING:
SHEET:
DATE:
OF
P.E.
DRAWING.
THE SCALE BAR
SHOWN BELOW
MEASURES ONE
INCH LONG ON
THE ORIGINAL
CITY OF HOMESTEAD
HAZEN AND SAWYER
999 PONCE de LEON BLVD, SUITE 1150
CORAL GABLES, FLORIDA 33134
LICENSE No.: 2771 BI
D S
ET
JOHN C. BURKE
17301
PUMP STATION 22 UPGRADES
JUNE 2025
41055-081
J.M.B.
J.M.B.
E004J.C.B.
41055-081-E-04.DWG
C.L.K.
LOCAL CONTROL PANEL SCHEMATIC
La st s av ed : 6
/2 6/
:0
PM
B y:
jb ro ad Pl ot te d:
/2 6/
:4
PM
File Path: C:\Users\Jbroad\DC\ACCDocs\Hazen and Sawyer\41055-081-PS 22 and FM Upgrades\Project Files\01_Design\Elec\41055-081-E-04.dwg
ALARM TEST
R
ES
ET
RESET
RESET
RESET
DESIGNED
DRAWN
CHECKED
PROJ. ENGR.
DATENo. ISSUED FOR BY
CAD REFERENCE:
ENGINEERS PROJECT:
CLIENTS PROJECT:
CONTRACT:
41055-081
REF. No.
DRAWING:
SHEET:
DATE:
OF
P.E.
DRAWING.
THE SCALE BAR
SHOWN BELOW
MEASURES ONE
INCH LONG ON
THE ORIGINAL
CITY OF HOMESTEAD
HAZEN AND SAWYER
999 PONCE de LEON BLVD, SUITE 1150
CORAL GABLES, FLORIDA 33134
LICENSE No.: 2771 BI
D S
ET
JOHN C. BURKE
17301
PUMP STATION 22 UPGRADES
JUNE 2025
41055-081
J.M.B.
J.M.B.
E005J.C.B.
41055-081-E-05.DWG
C.L.K.
ELECTRICAL DETAILS
La st s av ed : 6
/2 6/
:0
PM
B y:
jb ro ad Pl ot te d:
/2 6/
:4
PM
File Path: C:\Users\Jbroad\DC\ACCDocs\Hazen and Sawyer\41055-081-PS 22 and FM Upgrades\Project Files\01_Design\Elec\41055-081-E-05.dwg
ELAPSED TIME RECORDERS
DUPLEX STATION FUNCTION RECORDER
PUMP 1 RUNNING ETM1
PUMP 2 RUNNING ETM2
PUMP 3 RUNNING ETM3
PUMPS 1, 2, & 3 RUNNING SIMULTANEOUSLY ETM4
PUMP 1 RUNNING DURING AGENCY SELECTED
TIME OF DAY RANGE ETM5
PUMP 2 RUNNING DURING AGENCY SELECTED
TIME OF DAY RANGE ETM6
PUMP 3 RUNNING DURING AGENCY SELECTED
TIME OF DAY RANGE ETM7
3" X 10' CONCRETE
FILLED SCHD. 120
GALV. STEEL PIPE
WITH PVC CAP
TYPICAL OF BOTH
SUPPORTS
2" X 20' SCHD. 120
GALV. STEEL PIPE
5/8"x10' COPPER
CLAD GROUND ROD
GRADE
#6 BARE
COPPER
GROUND
ANTENNA: SCALA PART
#: TY-900
MOUNTED ON 2" PIPE
ANTENNA CABLE SHALL
BE STRAPPED TO PIPE
AT 48" SPACING
5/8"x10' COPPER
CLAD GROUND ROD
#6 COPPER GROUND
FI
PI
LI
| Sheets and Views |
| E001 ELECTRICAL NOTES |
| E002 ELECTRICAL LEGENDS AND SYMBOLS |
| E003 ELECTRICAL SINGLE LINE RISER |
| E004 LOCAL CONTROL PANEL SCHEMATIC |
| E005 ELECTRICAL DETAILS |
File details come from the government source that posted it. Updated .