41055-081S16900-OFE_CONTROL_PANEL_SPECS.pdf
PDF 88 KB Posted
- Attached to
- ITB# 202536 Purchase of Submersible Pumps and Control Panel to Upgrade Pump Station #22 - RE-BID
- Solicitation number
- 202536
- Issued by
- Miami-Dade County, Florida
About this file
This document is a technical specification section for a Submersible Pump Level Control Panel for the City of Homestead's Pump Station 22 Upgrade project. The specification details the requirements for a triplex pump level control panel that will control the operation of three pumps using two modes: primary level control via RTU or Float mode during RTU failure. The control panel must include a white powder-coated Nema 4X-304 Stainless Steel enclosure, stainless steel hardware, main and generator circuit breakers, motor starters, level indicators, auxiliary circuit breakers, fuses, lightning and surge protection, phase detectors, control power transformer, LED pilot lamps, elapsed time hour meters, alternator, hand switches, relays, terminal strips, wire gutters, alarm bell and light, generator outlet, and float control with override switches.
The specification provides detailed technical requirements for the panel's components, including specific manufacturer recommendations such as Square D or approved equal for circuit breakers, motor controllers, terminal blocks, relays, and switches. The float switches must be direct acting with a sealed 5-inch diameter plastic casing, mercury tilt switches, and molybdenum contacts. The panel must be built by a shop with a minimum of 5 years of panel building experience and UL-508 or UL-698A certification. Surge protection will be a Ditek Model D100 or approved equal, and all status and control signals will be communicated via the SCADA system equipment. The electrical cable for float switches shall be PVC type STO #18-3 conductors, with a minimum cable length of 30 feet.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
41055-081S16900-OFE/6/27/2025 16900-1 Pump Station 22 Upgrade City of Homestead
SECTION 16900 - SUBMERSIBLE PUMP LEVEL CONTROL PANEL (OFE)
PART 1 – GENERAL
1.01 THE REQUIREMENT
A. Furnish a complete triplex pump level control panel ready for installation by the Contractor.
The panel shall include, but not be limited to the following components:
1.02 RELATED TECHNICAL DOCUMENTS
A. Drawings and General Provisions of the Contract, including General and Supplementary Conditions, and Division 1 Specification Sections, apply to work of this Section. Other Specification Sections related to work specified in this Section are as follows:
1. All electrical sections (Division 16).
2. All instrumentation sections (Division 17).
PART 2 – PRODUCTS
2.01 CONTROL PANEL
A. The Triplex Pump Control Panel shall be designed and built as integrated, prewired equipment. It shall control the operation of three pumps via two modes of operation, primary level control via RTU or Float mode during RTU failure.
B. The control panel shall include but not be limited to the following: (see drawings for more details)
1. White powder coated Nema 4X-304 Stainless Steel enclosure
2. All hardware shall be stainless steel.
3. Main and generator circuit breakers
4. Motor starters (controllers)
5. Level indicator
6. Auxiliary circuit breakers
7. Fuses
8. Lightning and surge protection
9. Phase detectors for each motor
10. Control power transformer
11. Pilot lamps shall be High Brightness LED type
41055-081S16900-OFE/6/27/2025 16900-2 Pump Station 22 Upgrade
12. Elapsed time hour meters for each pump. See drawings for quantity and functions.
13. Alternator
14. Hand switches
15. Relays
16. Terminal strips
17. Wire gutters
18. Alarm bell and light
19. Generator Outlet
20. Indicator lamp test pushbutton or push to test lamps
21. Float control with momentary override switches for testing.
22. Plus all other devices shown on the plans.
23. Intrinsically safe barriers for float switches
24. The above equipment shall be properly sized and configured for the station. See drawings for electrical load requirements.
C. Circuit breakers shall be thermal magnetic, molded case, Square D, type FA, or approved equal.
D. Motor controllers shall be sized as indicated on the Plans, with overloads to match the supplied motors. Two sets of N.O/N.C. spare contacts shall be provided in the sewage pump starter. Motor controllers to be Square D, Cutler Hammer or equal.
E. All external wiring shall terminate in a terminal block, Square D type G class 9080, or approved equal. Terminal blocks shall be laid out and numbered as shown on the drawings.
F. Relays shall be socket-mounted for ease of replacement, Square D type K Class 8501, or approved equal.
G. Lamps (LED high brightness type), push buttons and switches shall be heavy duty oil-tight/watertight, Square D, type K Class 9001, or approved equal.
H. Elapsed time meters (ETM) shall be provided to indicate total running time of each sewage pump under various scenarios. See drawings for list and functions. ETM shall show "hours" and "tenths of hours". Meters shall be Eagle Signal Series HK or approved equal.
I. The duplex pump level control panel shall be by a UL-508 or UL-698A as appropriate for panel. Shop shall have a minimum of 5 years panel building experience with UL certification.
41055-081S16900-OFE/6/27/2025 16900-3 Pump Station 22 Upgrade
2.02 SUSPENDED FLOAT SWITCHES
A. Level switches of the direct acting float-operated design shall be comprised of a sealed, approximately 5-inch diameter plastic casing float, containing mercury tilt switches. Unless otherwise specified, media specific gravity is .95 to 1.05. Switches shall be one normally open and one normally closed 5A-115V AC capacity. Float Switch shall have molybdenum contacts sealed in a double-walled float of plastic material resistant to inorganic salt solutions, alkalis, and mineral acids.
B. Float hangers and supports shall be provided as shown on the installation detail drawings.
C. The Electrical Cable shall be PVC type STO #18-3 conductors. Cable lengths shall be field verified prior to ordering with a minimum of 30 feet in length.
D. Switch shall be Flygt, Anchor Scientific, or approved equal.
2.03 SURGE SUPPRESSION
A. Surge protection shall be a Ditek Model D100 or approved equal.
2.04 REMOTE TELEMETRY SIGNALS
A. All status and or control signals listed on drawing as signals to be communicated via the SCADA system equipment shall be terminated on termination strips numbered as indicated on the electrical drawings.
- - END OF SECTION - -
| PART 1 – GENERAL |
| 1.01 THE REQUIREMENT |
| A. Furnish a complete triplex pump level control panel ready for installation by the Contractor. The panel shall include, but not be limited to the following components: |
| 1.02 RELATED technical DOCUMENTS |
| A. Drawings and General Provisions of the Contract, including General and Supplementary Conditions, and Division 1 Specification Sections, apply to work of this Section. Other Specification Sections related to work specified in this Section are as fol... |
| 1. All electrical sections (Division 16). |
| 2. All instrumentation sections (Division 17). |
| PART 2 – PRODUCTS |
| 2.01 Control panel |
| A. The Triplex Pump Control Panel shall be designed and built as integrated, prewired equipment. It shall control the operation of three pumps via two modes of operation, primary level control via RTU or Float mode during RTU failure. |
| B. The control panel shall include but not be limited to the following: (see drawings for more details) |
| 1. White powder coated Nema 4X-304 Stainless Steel enclosure |
| 2. All hardware shall be stainless steel. |
| 3. Main and generator circuit breakers |
| 4. Motor starters (controllers) |
| 5. Level indicator |
| 6. Auxiliary circuit breakers |
| 7. Fuses |
| 8. Lightning and surge protection |
| 9. Phase detectors for each motor |
| 10. Control power transformer |
| 11. Pilot lamps shall be High Brightness LED type |
| 12. Elapsed time hour meters for each pump. See drawings for quantity and functions. |
| 13. Alternator |
| 14. Hand switches |
| 15. Relays |
| 16. Terminal strips |
| 17. Wire gutters |
| 18. Alarm bell and light |
| 19. Generator Outlet |
| 20. Indicator lamp test pushbutton or push to test lamps |
| 21. Float control with momentary override switches for testing. |
| 22. Plus all other devices shown on the plans. |
| 23. Intrinsically safe barriers for float switches |
| 24. The above equipment shall be properly sized and configured for the station. See drawings for electrical load requirements. |
| C. Circuit breakers shall be thermal magnetic, molded case, Square D, type FA, or approved equal. |
| D. Motor controllers shall be sized as indicated on the Plans, with overloads to match the supplied motors. Two sets of N.O/N.C. spare contacts shall be provided in the sewage pump starter. Motor controllers to be Square D, Cutler Hammer or equal. |
| E. All external wiring shall terminate in a terminal block, Square D type G class 9080, or approved equal. Terminal blocks shall be laid out and numbered as shown on the drawings. |
| F. Relays shall be socket-mounted for ease of replacement, Square D type K Class 8501, or approved equal. |
| G. Lamps (LED high brightness type), push buttons and switches shall be heavy duty oil-tight/watertight, Square D, type K Class 9001, or approved equal. |
| H. Elapsed time meters (ETM) shall be provided to indicate total running time of each sewage pump under various scenarios. See drawings for list and functions. ETM shall show "hours" and "tenths of hours". Meters shall be Eagle Signal Series HK or app... |
| I. The duplex pump level control panel shall be by a UL-508 or UL-698A as appropriate for panel. Shop shall have a minimum of 5 years panel building experience with UL certification. |
| 2.02 SUSPENDED FLOAT SWITCHES |
| A. Level switches of the direct acting float-operated design shall be comprised of a sealed, approximately 5-inch diameter plastic casing float, containing mercury tilt switches. Unless otherwise specified, media specific gravity is .95 to 1.05. Switc... |
| B. Float hangers and supports shall be provided as shown on the installation detail drawings. |
| C. The Electrical Cable shall be PVC type STO #18-3 conductors. Cable lengths shall be field verified prior to ordering with a minimum of 30 feet in length. |
| D. Switch shall be Flygt, Anchor Scientific, or approved equal. |
| 2.03 SURGE SUPPRESSION |
| A. Surge protection shall be a Ditek Model D100 or approved equal. |
| 2.04 REMOTE TELEMETRY SIGNALs |
| A. All status and or control signals listed on drawing as signals to be communicated via the SCADA system equipment shall be terminated on termination strips numbered as indicated on the electrical drawings. |
| - - END OF SECTION - - |