Addendum_#1_-_PS_22_Upgrades_Bid_Set_Drawings_(8-15-25).pdf
PDF 7 MB Posted
- Attached to
- ITB# 202536 Purchase of Submersible Pumps and Control Panel to Upgrade Pump Station #22 - RE-BID
- Solicitation number
- 202536
- Issued by
- Miami-Dade County, Florida
About this file
This document is a comprehensive bid set for the City of Homestead's Pump Station 22 Upgrades project, prepared by Hazen and Sawyer, a professional engineering firm located in Coral Gables, Florida. The project involves a complete upgrade of Pump Station 22, located on E Mowry Drive in Homestead, and includes detailed engineering drawings spanning 22 sheets covering civil, mechanical, structural, and electrical aspects of the renovation. The bid set is dated July 2025 and provides extensive technical specifications for replacing existing infrastructure, including submersible pumps, piping, electrical systems, control panels, and site improvements. The project scope encompasses demolition of existing equipment, installation of new submersible sewage pumps, upgrade of yard piping, electrical systems, and associated site work.
The project is funded through the City of Homestead's Public Works Department, with an engineering project number of 41055-081. The bid set includes detailed technical specifications for equipment, including a 125 kW generator, submersible pumps, electrical systems, and control infrastructure. The drawings specify precise technical requirements for each component, including electrical load calculations, grounding specifications, and instrumentation details. The project appears to be designed to improve the capacity, reliability, and operational efficiency of the existing pump station, with comprehensive plans for electrical, mechanical, and civil infrastructure upgrades. The technical complexity and detailed specifications suggest a substantial municipal infrastructure investment aimed at modernizing critical wastewater infrastructure.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
LOCATION MAP
CITY COUNCIL
STEVEN D. LOSNER Mayor SEAN L. FLETCHER Vice Mayor TOM DAVIS Council Member LARRY ROTH Council Menber JENIFER N. BAILEY Council Member ERICA G. ÁVILA Council Member CLEMENTE CANABAL Council Member
CITY OF HOMESTEAD
DRAWING No. G-01
SHEET 1 OF 22
PUBLIC WORKS DEPARTMENT
ENGINEER'S PROJECT No.: 41055-081
PUMP STATION 22 UPGRADES
BID SET
JULY 2025
HAZEN AND SAWYER
999 PONCE de LEON BLVD, SUITE 1150
CORAL GABLES, FLORIDA 33134
LICENSE No.: 2771
E MOWRY DRIVE
SW 320TH STREET
PUMP STATION 22
PROJECT SITE
BI
D
S
ET
SHEET LIST TABLE
SHEET NUMBER SHEET TITLE SHEET DESCRIPTION
GENERAL
1 G-01 COVER SHEET
2 G-02 ABREVIATIONS AND SYMBOLS
CIVIL
3 C-01 PS 22 EXISTING BYPASS SYSTEM AND DEMOLITION PLANS
4 C-02 PS 22 PROPOSED YARD PIPING AND SITE PLAN
5 C-03 PAVEMENT RESTORATION
6 C-04 CIVIL DETAILS SHEET 1
7 C-05 CIVIL DETAILS SHEET 2
8 C-06 CIVIL DETAILS SHEET 3
9 C-07 CIVIL DETAILS SHEET 4
MECHANICAL
10 M-01 PUMP STATION 22 PLAN
11 M-02 PUMP STATION 22 SECTION SHEET 1
12 M-03 PUMP STATION 22 SECTION SHEET 2
13 M-04 MECHANICAL DETAILS SHEET 1
14 M-05 MECHANICAL DETAILS SHEET 2
STRUCTURAL
15 S-01 STRUCTURAL NOTES
16 S-02 STRUCTURAL PUMP STATION PLAN
17 S-03 STRUCTURAL PUMP STATION SECTION
ELECTRICAL
18 E-01 ELECTRICAL NOTES
19 E-02 ELECTRICAL LEGENDS AND SYMBOLS
20 E-03 ELECTRICAL SCHEDULES AND DETAILS
21 E-04 LOCAL CONTROL PANEL - SHEET 1
22 E-05 LOCAL CONTROL PANEL - SHEET 2
DESIGNED
DRAWN
CHECKED
PROJ. ENGR.
DATENo. ISSUED FOR BY
CAD REFERENCE:
ENGINEERS PROJECT:
CLIENTS PROJECT:
CONTRACT:
41055-081
REF. No.
DRAWING:
SHEET:
DATE:
OF
P.E.
DRAWING.
THE SCALE BAR
SHOWN BELOW
MEASURES ONE
INCH LONG ON
THE ORIGINAL
CITY OF HOMESTEAD
HAZEN AND SAWYER
999 PONCE de LEON BLVD, SUITE 1150
CORAL GABLES, FLORIDA 33134
LICENSE No.: 2771 BI
D S
ET
CHRISTOPHER L. KISH
55480
PUMP STATION 22 UPGRADES
JULY 2025
41055-081
RESTRAINED JOINTRJ
FORCE MAIN (WASTEWATER)FM
RESTRAINEDREST.
RADIUSRAD, R
PRESSURE INDICATOR (GAUGE)PI
WITH OUTW/O
HIGH DENSITY POLYETHYLENEHDPE
GRAVITY DRAINGD
FIGUREFIG
DECANTDEC
BASIN DRAINBD
REINFORCED CONCRETE PIPERCP
CAST IRON PIPECIP
HAND INDICATING CONTROLLERHIC
THICKENED WASTE ACTIVATED SLUDGE
STA STATION
HIC HAND INDICATING CONTROL
SECTION LETTER
SECTION LETTER
DRAWING ON WHICH
SECTION APPEARS
SECTION WAS TAKEN
DRAWING ON WHICH
DETAIL NUMBER
DETAIL IS SHOWN
DRAWING FROM WHICH
RECIRCULATION
RETURN ACTIVATED SLUDGE
PROPERTY LINE
POTABLE WATER
POUNDS PER FOOT
FIN
FE
FL
GALV
FW FILTERED WATER
FIRE EXTINGUISHER
FLOOR
GALVANIZED
FINISH
RAS
RECIR
P/L, P
LBS/FT
PW
REQUIRED
REINFORCING
REHABILITATION
REDUCER
SANITARY
REUSE WATER
RIGHT OF WAY
SQUARE
SPECIFICATION
SHEET
SYMMETRICAL
STRUCTURAL
STEEL
STAINLESS STEEL
TO BE DETERMINED
SECTION
GR
HP
INJ
HORIZ
HWH
INFL
INJECTION
HIGH POINT
INFLUENT
HORIZONTAL
GRADE
HOT WATER HEATER
IF
INT
ISO
INSUL
IQ
INV
JT, J
LG
INVERT
IRRIGATION QUALITY
INSULATION
ISOLATION
INTERIOR
INSIDE FACE
LONG
JOINT
ID INSIDE DIAMETER
SYMM
STRUC
SPEC
SECT
SHT
SAN
REINF
REQ'D
R/W, ROW
RED
REHAB
STL
S.S.
SQ
RW
TBD
SECTION IDENTIFICATION
SECTION AND DETAIL IDENTIFICATION
DETAIL IDENTIFICATION
(1) DETAIL CALL-OUT ON DRAWING C-1 AS:
(2) ON DRAWING C-2 THIS DETAIL IDENTIFIED AS:(2) ON DRAWING C-2 THIS SECTION IS IDENTIFIED AS:
(1) SECTION CUT ON DRAWING C-1:
DRAWING ON WHICH
DETAIL IS SHOWN
STANDARD DETAILNUMBER
DETAIL IS CALLED OUT
DRAWING FROM WHICH
SOCIETY STANDARD SYMBOLS. SEE AMERICAN
INSTITUTE OF STEEL CONSTRUCTION MANUAL.
THICK
TEMPORARY
TYPICAL
TOP OF SLAB
VENT THROUGH ROOF
TEMPERATURE INDICATOR
TOP OF CONCRETE
WATER LEVEL
WATER
VERTICAL
WITH
WIDE
WELDED WIRE FABRIC
WASTE ACTIVATED SLUDGE
LINELN
LP
MH
LWL
MIN
MECH, M
MAX
MO
MFGR
MINIMUM
MASONRY OPENING
LOW WATER LEVEL
MECHANICAL
MAXIMUM
MANUFACTURER
MANHOLE
LOW POINT
W
No.
NTS
NIC
OC
OD
OF
OPNG OPENING
NOT IN CONTRACT
ON CENTER
NUMBER
NOT TO SCALE
OUTSIDE FACE
OUTSIDE DIAMETER
W/
WTR
WWF
W/L
WAS
VERT
VTR
TOC
TWAS
THK
TEMP
TOS
TYP
TI
POT POTABLE
NOTES:
STANDARD DETAIL IDENTIFICATION
(1) ELECTRICAL SYMBOLS SHOWN ON ELECTRICAL SHEETS.
(2) FOR WELDING SYMBOLS USE AMERICAN WELDING
(2) ON DRAWING C-4 THIS DETAIL IDENTIFIED AS:
(1) DETAIL CALL-OUT ON PLAN OR SECTION:
ARCHITECTURAL
BOTTOM
BLOCK
BID PACKAGE
BUILDING
BOTT
BLK.
ARCH.
B.P.
BLDG
BLIND FLANGE
AIR RELIEF VALVE
BALL VALVE
BUTTERFLY VALVE
BV
ARV
BF
BFV
VALVES, FITTINGS, ETC.
CENTER LINE
CATCH BASIN
CHECKERED
CLEAN OUT
CHLORINE
COLUMN
CLEAR
CO
CHLOR, CL
COL
CLR.
CC
C
CB
CHK'D
CONTINUOUS
CONSTRUCTION
CONCRETE
CONTRACTOR
DIAMETER
DIAGONAL
DETAIL
DIGESTER
DIA
CONT.
DIAG
DET
CONTR.
CONST.
CONC.
DIG
COMPANYCO.
CHECK VALVE
COUPLING
FLANGE
FITTING
FIRE HYDRANT
EXPANSION JOINT
CLV
CV
CPLG
EXP. JT.
FH
FLG, F
FTG
GATE VALVE
LONG RADIUS
MECHANICAL JOINT
HOSE BIBB
NATIONAL PIPE THREAD
PLUG VALVE
PUMP STATION
PLAIN END
GV
LR
MJ
HB
NPT
PE
PV
P.S.
FLOOR DRAINFD
CHLORINE GAS VALVE UNDER VACUUM
SYMBOLS
MOTOR OPERATED VALVE
BUTTERFLY VALVE/DAMPER
BALL VALVE
SOLENOID VALVE
PRESSURE REGULATING VALVE
PRESSURE REDUCING/RELIEF VALVE
THREE WAY VALVE
PLUG VALVE
GATE VALVE
HOSE BIBB (ELEVATION)
HOSE BIBB (PLAN)
CHECK VALVE
DOWN
DISCHARGE
DIMENSION
DOWEL
EACH WAY
EACH FACE
EACH END
EACH
DRAWING
EW
EF
EE
DWG
DISCH
DIM
DWL.
EA
DN
ELECTRIC
EFFLUENT
ECCENTRIC
ELEVATION
EXISTING
EQUIPMENT
EXHAUST
EXPANSION
EL, ELEV
EXIST
EQUIP
ELEC.
EFF
ECC
EXH
EXP
ROOF DRAIN
THREADED
FORCE MAIN
COPPER
PIPING
DUCTILE IRON PIPE
VACUUM
PRV
RD
THD
SOV
FM
DIP
CU
VAC
POLYVINYLCHLORIDE
IRON PIPE SIZE
AIR CONDITIONER
GENERAL
AIR SCOUR
ALUMINUM
GSP
IPS
PVC
A/C
AIR
AL, ALUM
SOLENOID OPERATED VALVE
GALVANIZED STEEL PIPE
PRESSURE RELIEF VALVE
EXTERIOREXT
ANGLE
APPROXIMATEAPPROX.
FLANGED JOINT
WELDED JOINT
PUSH-ON JOINT
MECHANICAL JOINT
GAUGE
CENTER TO CENTER
ABBREVIATIONS
CMP CORRUGATED METAL PIPE
DIAPHRAGM VALVE
FTG FOOTING
HWL HIGH WATER LEVEL
STD STANDARD
FIBERGLASS REINFORCED PIPEFRP
REINFORCED CONCRETE PRESSURE PIPERCPP
A C-2
SECTION A
C-1
C-2
DETAIL 1
C-1
C-4
DETAIL 2
ANCHOR BOLTAB
DRAIND
BACKWASH SUPPLYBS
BACKWASH WASTEBW
FEFF FILTER EFFLUENT
FINFL FILTER INFLUENT
WITH MOTOR OPERATORW/MO
CPLG, C COUPLING
PRESTRESSED CONCRETE CYLINDER PIPEPCCP
FT FOOT
LBS POUNDS
LAT. LATERIAL
L.P. LIGHT POLE
PROP PROPOSED
PSI POUNDS PER SQUARE INCH
L
PAVEMENTPVT
REVISIONREV
REJECT WATERRJW
SECTION LINESL
THREADED JOINT
VENTURI METER
FLAME ARRESTER
EXPANSION JOINT COUPLING
HARNESSED EXPANSION JOINT COUPLING
GROOVED COUPLING
MECHANICAL COUPLING
HARNESSED MECHANICAL COUPLING
UNION
MAGNETIC METER
NEW STRUCTURE OR UTILITY-THIS CONTRACT
FIRE HYDRANT
SEALED MANHOLE
MANHOLE
SCALE OF DRAWING PERMITS)
EXISTING PIPELINE (DOUBLE LINE IF
EXISTING STRUCTURE OR UTILITY
REDUCER (DOUBLE LINE)
REDUCER (SINGLE LINE)
PIPE SUPPORT
IF SCALE OF DRAWING PERMITS)
NEW PIPELINE-THIS CONTRACT (DOUBLE LINE
PO PUSH ON
LENGTHLGTH
LOC
M.B. MAILBOX
LOCATION
POINT OF CURVATUREP.C.
P.I. POINT OF INTERSECTION
POINT OF TANGENCYP.T.
SLUICE GATE
SLIDE GATE
STOP LOG
L
MECHANICAL COUPLINGMC
RESTRAINED JOINTRJ
DENOTES DIMENSIONS OR ELEVATIONS
DEPENDENT ON EQUIPMENT SUPPLIED.
DETAIL NUMBER
STANDARD DETAILNUMBER
NOTE: IF PLAN AND SECTION (OR DETAIL CALL-OUT
AND DETAIL) ARE SHOWN ON SAME DRAWING,
DRAWING NUMBER IS REPLACED BY A DASH.
C.L.K.
A.G.J.
G-02J.O.H.
41055-081-G-02.DWG
C.L.K.
ABREVIATIONS AND SYMBOLS
1. A HORIZONTAL DISTANCE OF AT LEAST 6 FEET, AND PREFERABLY 10 FEET (OUTSIDE TO OUTSIDE), SHALL BE MAINTAINED BETWEEN GRAVITY OR PRESSURE SEWER PIPES AND WATER PIPES. THE MINIMUM HORIZONTAL SEPARATION CAN BE REDUCED TO 3 FEET FOR VACUUM TYPE SEWERS OR FOR GRAVITY SEWERS WHERE THE TOP OF THE SEWER PIPE IS AT LEAST 6 INCHES BELOW THE BOTTOM OF THE WATER PIPE. WHEN THE ABOVE SPECIFIED HORIZONTAL DISTANCE CRITERIA CANNOT BE MET DUE TO AN EXISTING UNDERGROUND FACILITY
CONFLICT, SMALLER SEPARATIONS ARE ALLOWED IF ONE OF THE FOLLOWING IS MET:
A) THE SEWER PIPES ARE DESIGNED AND CONSTRUCTED EQUAL TO THE WATER PIPE AND PRESSURE TESTED
AT 150 PSI.
B) THE SEWER IS ENCASED IN A WATERTIGHT CARRIER PIPE OR CONCRETE.
C) THE TOP OF THE SEWER IS AT LEAST 18 INCHES BELOW THE BOTTOM OF THE WATER PIPE.
2. A VERTICAL DISTANCE OF AT LEAST 12 INCHES (OUTSIDE TO OUTSIDE) SHALL BE MAINTAINED BETWEEN ANY WATER AND SEWER MAINS WITH SEWER PIPES PREFERABLY CROSSING UNDER WATER MAINS. THE MINIMUM VERTICAL SEPARATION CAN BE REDUCED TO 6 INCHES FOR VACUUM TYPE SEWERS OR FOR GRAVITY SEWERS WHERE THE SEWER PIPE IS BELOW THE WATER MAIN. THE CROSSING SHALL BE ARRANGED SO THAT ALL WATER MAIN JOINTS ARE AT LEAST 6 FEET FROM ALL JOINTS IN GRAVITY AND PRESSURE SEWER PIPES. THIS DISTANCE CAN BE REDUCED TO 3 FEET FOR VACUUM TYPE SEWERS. WHEN THE ABOVE SPECIFIED VERTICAL DISTANCE CRITERIA CANNOT BE MET DUE TO AN EXISTING UNDERGROUND FACILITY CONFLICT, SMALLER
SEPARATIONS ARE ALLOWED IF ONE OF THE FOLLOWING IS MET:
A) THE SEWER PIPES ARE DESIGNED AND CONSTRUCTED EQUAL TO THE WATER PIPE AND PRESSURE TESTED
AT 150 PSI.
B) THE SEWER IS ENCASED IN A WATERTIGHT CARRIER PIPE OR CONCRETE.
3. AIR RELEASE VALVES SHALL BE PROVIDED AT HIGH POINTS OF NEW FORCE MAIN SANITARY SEWERS.
4. GRAVITY SANITARY SEWERS CONSTRUCTED WITHIN A PUBLIC WELLFIELD PROTECTION AREA SHALL BE C-900 PVC OR DUCTILE IRON PIPE. THE MAXIMUM ALLOWABLE EXFILTRATION RATE OF GRAVITY SANITARY SEWERS
CONSTRUCTED IN A PUBLIC WELLFIELD PROTECTION AREA SHALL BE:
A) RESIDENTIAL LAND USES. FIFTY (50) GALLONS PER INCH PIPE DIAMETER PER MILE PER DAY, BASED ON A MINIMUM TWO (2) HOUR TEST HAVING A MINIMUM OF TWO (2) FEET OF POSITIVE HEAD ABOVE THE CROWN OF
THE PIPE.
B) NON-RESIDENTIAL LAND USES. TWENTY (20) GALLONS PER INCH PIPE DIAMETER PER MILE PER DAY, BASED ON A MINIMUM TWO (2) HOUR TEST HAVING A MINIMUM OF TWO (2) FEET OF POSITIVE HEAD ABOVE THE CROWN
OF THE PIPE.
C) ANY OBSERVED LEAKS OR ANY OBVIOUSLY DEFECTIVE JOINTS OR PIPES SHALL BE REPLACED EVEN WHEN
THE TOTAL LEAKAGE IS BELOW THAT ALLOWED.
5. THE MAXIMUM ALLOWABLE EXFILTRATION RATE OF GRAVITY SANITARY SEWERS CONSTRUCTED OUTSIDE A PUBLIC WELLFIELD PROTECTION AREA SHALL BE ONE HUNDRED (100) GALLONS PER INCH PIPE DIAMETER PER MILE PER DAY, BASED ON A MINIMUM TWO (2) HOUR TEST HAVING A MINIMUM OF TWO (2) FEET OF POSITIVE HEAD ABOVE THE CROWN OF THE PIPE. ANY OBSERVED LEAKS OR ANY OBVIOUSLY DEFECTIVE JOINTS OR
PIPES SHALL BE REPLACED EVEN WHEN THE TOTAL LEAKAGE IS BELOW THAT ALLOWED.
6. FORCEMAIN SANITARY SEWERS CONSTRUCTED WITHIN A PUBLIC WELLFIELD PROTECTION AREA SHALL BE
DUCTILE IRON, C-900 PVC, HDPE OR REINFORCED CONCRETE PRESSURE SEWER PIPES.
7. THE MAXIMUM ALLOWABLE EXFILTRATION/LEAKAGE RATE OF FORCEMAIN SANITARY SEWERS SHALL BE:
A) DUCTILE IRON, C-900 PVC, HDPE AND PVC PIPE. THE ALLOWABLE LEAKAGE RATE SPECIFIED IN AMERICAN WATER WORKS ASSOCIATION STANDARD (AWWAS) C600-82 AT A TEST PRESSURE OF 100 PSI FOR A DURATION
OF NOT LESS THAN TWO (2) HOURS.
B) REINFORCED CONCRETE PRESSURE PIPE. HALF (1/2) THE ALLOWABLE LEAKAGE RATE SPECIFIED IN AWWA C600-82 AT A TEST PRESSURE OF 100 PSI FOR A DURATION OF NOT LESS THAN TWO (2) HOURS.
C) ANY OBSERVED LEAKS OR ANY OBVIOUSLY DEFECTIVE JOINTS OR PIPES SHALL BE REPLACED EVEN WHEN
THE TOTAL LEAKAGE IS BELOW THAT ALLOWED.
8. THE CONTRACTOR SHALL VERIFY NATURE, DEPTH, AND CHARACTER OF EXISTING UNDERGROUND UTILITIES
PRIOR TO START OF CONSTRUCTION.
9. IN NO CASE SHALL A CONTRACTOR INSTALL UTILITY PIPES, CONDUITS, CABLES, ETC. IN THE SAME TRENCH
ABOVE AN EXISTING WATER OR SEWER PIPE EXCEPT WHERE THEY CROSS.
10. IF ANY AREA OF THE WORK SITE IS FOUND TO CONTAIN BURIED SOLID WASTE AND/OR GROUND OR GROUND
WATER CONTAMINATION, THE FOLLOWING SHALL APPLY:
A) ALL WORK IN THE AREA SHALL FOLLOW ALL APPLICABLE SAFETY REQUIREMENTS (E.G., OSHA, ETC.) AND
NOTIFICATION MUST BE PROVIDED TO THE APPROPRIATE AGENCIES.
B) IMMEDIATELY NOTIFY THE ENVIRONMENTAL MONITORING AND RESTORATION DIVISION (EMRD). THE EMRD
CAN BE CONTACTED AT (305) 372-6700.
C) IF CONTAMINATED SOILS AND/OR BURIED SOLID WASTE MATERIAL IS EXCAVATED DURING CONSTRUCTION, THEN THEY REQUIRE PROPER HANDLING AND DISPOSAL IN ACCORDANCE WITH THE LOCAL, STATE AND FEDERAL REGULATIONS. BE ADVISED THAT THE LANDFILL OWNER/OPERATOR IS THE FINAL AUTHORITY ON DISPOSAL AND MAY HAVE REQUIREMENTS BEYOND THOSE PROVIDED BY HEREIN. IF DISPOSAL WITHIN A MIAMI-DADE COUNTY OWNED LANDFILL (CLASS I LANDFILL) IS APPROPRIATE AND SELECTED, PLEASE CONTACT THE MIAMI-DADE COUNTY DEPARTMENT OF SOLID WASTE MANAGEMENT AT (305) 594-6666 FOR INFORMATION.
D) THE REUSE OF CONTAMINATED SOILS THAT ARE NOT RETURNED TO THE ORIGINAL EXCAVATION REQUIRES PRIOR APPROVAL OF A SOIL MANAGEMENT PLAN FROM THE ENVIRONMENTAL MONITORING AND RESTORATION
DIVISION. THE EMRD CAN BE CONTACTED AT (305) 372-6700.
11. PUMPS MUST COMPLY WITH THE NATIONAL ELECTRICAL CODE (NEC) REQUIREMENTS FOR CLASS I, GROUP D, DIVISION 1 LOCATIONS (EXPLOSION PROOF).
12. HE CONTRACTOR IS ADVISED THAT A TREE REMOVAL/RELOCATION PERMIT MAY BE REQUIRED PRIOR TO THE REMOVAL AND/OR RELOCATION OF TREE RESOURCES. PRIOR TO REMOVING OR RELOCATING ANY TREES, THE CONTRACTOR SHALL NOTIFY THE TREE AND FOREST RESOURCES SECTION OF DERM AT (305) 372-6574 OR VIA E-MAIL AT: TFRS@MIAMIDADE.GOV, OR CONTACT THE MUNICIPALITY WITH TREE ORDINANCE JURISDICTION TO OBTAIN ANY REQUIRED PERMITS. THOSE TREES NOT INTERFERING WITH THE CONSTRUCTION SHALL BE PROTECTED IN PLACE IN ACCORDANCE WITH THE PROVISIONS OF SECTION 24-49.5 OF THE MIAMI-DADE CODE.
13. PLEASE NOTE THAT THE DEMOLITION, REMOVAL, AND/OR DISTURBANCE OF EXISTING UNDERGROUND UTILITIES THAT CONTAIN ASBESTOS CEMENT PIPES (ACP) ARE SUBJECT TO THE PROVISIONS OF 40 CFR-61 SUBPART M. THEREFORE, PURSUANT TO THE PROVISIONS OF 40 CFR-61-145, A NOTICE OF DEMOLITION OR ASBESTOS RENOVATION FORM MUST BE FILED WITH THE AIR QUALITY MANAGEMENT DIVISION (AQMD) OF DERM, AT LEAST TEN (10) WORKING DAYS PRIOR TO STARTING OF ANY WORK. NOTE THAT THE BACKFILLING AND BURIAL OF CRUSHED ACP WOULD CAUSE THESE LOCATIONS TO BE CONSIDERED ACTIVE DISPOSAL SITES AND SUBJECT TO 40 CFR-61.154, AND 40 CFR-61.151 A YEAR AFTER PROJECT COMPLETION. EXISTING STANDARD OPERATING PROCEDURES, AS WELL AS APPLICABLE FEDERAL, STATE AND LOCAL REGULATORY CRITERIA, MUST BE FOLLOWED AND IMPLEMENTED TO MINIMIZE ANY POTENTIAL RELEASE OF FUGITIVE EMISSIONS, ESPECIALLY DURING PROJECT CONSTRUCTION ACTIVITIES. THE AQMD CAN BE CONTACTED VIA
EMAIL AT ASBESTOS@MIAMIDADE.GOV OR 305-372-6925.
DERM NOTES FOR WATER AND SEWER INSTALLATIONS:
VARIESMTE MATCH TO EXISTING VA
X X X X X X X X
X X
X X
X X
X
XXXX
X X
X X
X X
X
X X X
O H
E O
H E
O H
E O
H E
O H
E O
H E
O H
E O
H E
X
X
X X X X X X X X
X X
X X
X X
X
XXXX
X X
X X
X X
X
X X X
O H
E O
H E
O H
E O
H E
O H
E O
H E
O H
E O
H E
X
X
DESIGNED
DRAWN
CHECKED
PROJ. ENGR.
DATENo. ISSUED FOR BY
CAD REFERENCE:
ENGINEERS PROJECT:
CLIENTS PROJECT:
CONTRACT:
41055-081
REF. No.
DRAWING:
SHEET:
DATE:
OF
P.E.
DRAWING.
THE SCALE BAR
SHOWN BELOW
MEASURES ONE
INCH LONG ON
THE ORIGINAL
CITY OF HOMESTEAD
HAZEN AND SAWYER
999 PONCE de LEON BLVD, SUITE 1150
CORAL GABLES, FLORIDA 33134
LICENSE No.: 2771 BI
D S
ET
CHRISTOPHER L. KISH
55480
PUMP STATION 22 UPGRADES
JULY 2025
41055-081
1"=10'-0"
10 0 10'
C.L.K.
A.G.J.
C-01J.O.H.
41055-081-C-01.DWG
C.L.K. PS 22 EXISTING BYPASS SYSTEM AND DEMOLITION PLANS
SCALE: 1/8" = 1'-0"
EXISTING SITE PLAN AND BYPASS SYSTEM
EX
IS
T.
P
EXIST. P
L
EX
IS
T.
P L
L
2" WATER
SERVICE
EXIST. MH (2) RIM EL.
7.40
SOUTH INV. EL. (-)5.69
EAST INV. EL. (-)-5.71
EXIST. MH (1)
RIM EL. 7.40
NORTH INV. EL. (-)5.58
WEST INV. EL. (-)5.56
EXIST. CHAIN
LINK SECURITY
FENCE
EXIST. 18" VCP
(TYP.)
EXIST. 21" VCP
(TYP.)
EXIST. 8" VCP
(TYP.)
EXIST. 8" VCP
(TYP.)
TELEMETRY
ANTENNA AND
FOUNDATION
E.O.P.
E.O.P.
20" PVC
RESOD AREAS
DAMAGED BY
CONSTRUCTION
E MOWRY DRIVE
SW 320TH STREET
RESOD AREAS
DAMAGED BY
CONSTRUCTION
ROWROW
8" SUCTION
PIPE (TYP.)
EXIST. 12" CHECK AND
PLUG VALVES (TYP.)
EXIST. P
EXIST. 8" LINED VCP
GRAVITY MAIN
FROM TRAILER
PARK
L
EXIST. CHAIN
LINK SECURITY
FENCE
EXIST. CHAIN LINK
SECURITY FENCE
EXIST. 8' DIA. WET
WELL CONVERTED TO
MH (0)
RIM EL. 7.40
NORTH INV. EL. (-)3.36
SOUTH INV. EL. (-)5.51
EAST INV. EL. (-)5.53
EXIST. SERVICE FEED
EXIST. 6"
DISCHARGE
PIPE (TYP.)
16" DISCHARGE PIPING
EXIST.
72"x72"PAD AND
TRANSFORMER
EXIST. RTU
EXIST.
CONTROL PANEL
30A
EXIST. 200A TEMP. SERVICE
DISCONNECT
REMOVE EXIST.
DISCONNECT AND
GUTTER MOUNTED ON
UNISTRUT RACK (TYP.)
REMOVE EXIST.
RACK WITH GUTTER
100A
EXIST. 6"X12" REDUCER (TYP.)
EL
EC
TR
IC
PU
M
P N o.
KW
D
IE
SE
L G
EN
ER
AT
O
R
EL
EC
TR
IC
PU
M
P N o.
EL
EC
TR
IC
PU
M
P N o.
4'-0" 4'-0"
3'-6"
9' -1
0"
8' -8
6"X8"
REDUCER
(TYP.)
EXIST. 21" GM
VCP WITH LINER
REMOVE EXIST.
BYPASS GENERATOR.
EXIST. SECURITY
FENCE/GATE ON SOUTH
SIDE OF SITE
LEGAL DESCRIPTION:
A PORTION OF EAST MOWRY DRIVE WEST OF SOUTHWEST 167TH AVENUE AND EAST OF
NORTH HOMESTEAD BOULEVARD
TOGETHER WITH
A PORTION OF SOUTHEAST 6TH AVENUE NORTH OF SOUTHWEST 328TH STREET AND
SOUTH OF EAST MOWRY STREET:
SAID LANDS LYING AND BEING IN THE CITY OF HOMESTEAD, MIAMI-DADE COUNTY, FLORIDA.
NOTES:
1. ELEVATIONS ARE BASED ON NATIONAL GEODETIC VERTICAL DATUM OF 1929.
MIAMI-DADE COUNTY BENCHMARK #R-751, ELEVATION: 7.51 FEET.
2. THIS SITE LIES IN SECTION 18, TOWNSHIP 57 SOUTH, RANGE 39 EAST, MIAMI-DADE
COUNTY, FLORIDA.
3. THE HORIZONTAL POSITIONAL ACCURACY OF WELL DEFINED IMPROVEMENTS ON THIS
SURVEY IS ±0.2'. THE VERTICAL ACCURACY OF ELEVATIONS OF WELL DEFINED
IMPROVEMENTS ON THIS SURVEY IS ±0.1'.
4. THIS SURVEY WAS PREPARED WITHOUT BENEFIT OF A COMMITMENT FOR TITLE
INSURANCE. ONLY PLATTED OR KNOWN EASEMENTS ARE DEPICTED HEREON.
5. ALL RECORDED DOCUMENTS ARE PER MIAMI-DADE COUNTY PUBLIC RECORDS.
BY-PASS PUMPING SYSTEM:
1. AN OPERATIONAL BYPASS SYSTEM IS CURRENTLY IN PLACE AT THE SITE AND HAS
BEEN MAINTAINED BY THE CITY. THE SYSTEM CONSISTS OF THREE (3) ELECTRICALLY
POWERED 60 HP BYPASS PUMPS, WHICH ARE SUPPLIED BY AN ON-SITE ELECTRICAL
TRANSFORMER. IN THE EVENT OF A POWER OUTAGE, THE SYSTEM IS SUPPORTED BY
AN AUTOMATIC TRANSFER SWITCH AND A 150 KW DIESEL GENERATOR. THE SYSTEM
IS INTEGRATED WITH THE CITY’S TELEMETRY NETWORK, ALLOWING REMOTE
MONITORING OF KEY OPERATIONAL PARAMETERS.
2. UPON MOBILIZATION, THE CONTRACTOR SHALL ASSUME FULL RESPONSIBILITY FOR
THE OPERATION AND MAINTENANCE OF THE EXISTING BYPASS SYSTEM FOR THE
DURATION OF THE PROJECT. BEFORE ANY CONSTRUCTION ACTIVITY MAY BEGIN, THE
CONTRACTOR IS REQUIRED TO SUCCESSFULLY OPERATE AND MAINTAIN THE BYPASS
SYSTEM FOR A MINIMUM OF 72 CONTINUOUS HOURS. CONSTRUCTION AND
DEMOLITION ACTIVITIES MAY ONLY COMMENCE ONCE THE CITY HAS VERIFIED THE
CONTRACTOR’S COMPETENCY AND IS SATISFIED WITH THE OPERATION OF THE
SYSTEM.
3. THE CONTRACTOR SHALL PERFORM ALL NECESSARY MAINTENANCE TASKS
ASSOCIATED WITH THE BYPASS SYSTEM, INCLUDING BUT NOT LIMITED TO: CLEANING
THE BYPASS SYSTEM WET WELL, DE-RAGGING PUMPS IN THE EVENT OF CLOGGING,
ENSURING PUMPS REMAIN IN PROPER WORKING CONDITION TO PREVENT FAILURE,
CONDUCTING MONTHLY TESTING OF THE ON-SITE GENERATOR TO CONFIRM
READINESS, SUPPLYING ALL NECESSARY DIESEL FUEL TO MAINTAIN GENERATOR
FUNCTIONALITY.
4. THE CONTRACTOR SHALL COORDINATE WITH THE CITY ON A MONTHLY BASIS TO
COLLECT AND REPORT POWER CONSUMPTION DATA, WHICH WILL BE SUBMITTED TO
DERM. ACCURATE REPORTING IS CRITICAL TO ENSURE THE BYPASS SYSTEM
REMAINS IN COMPLIANCE WITH THE 10-HOUR RUNTIME LIMITATION. NONCOMPLIANCE
COULD RESULT IN THE FACILITY BEING PLACED UNDER MORATORIUM.
5. THE BYPASS SYSTEM MUST BE MONITORED CONTINUOUSLY—24 HOURS PER DAY, 7
DAYS PER WEEK—WITHOUT EXCEPTION. ANY FAILURE OF THE SYSTEM DUE TO
CONTRACTOR NEGLIGENCE WILL NOT BE TOLERATED. THE CONTRACTOR WILL BE
HELD FULLY LIABLE FOR ANY RESULTING CONSEQUENCES, INCLUDING CLEANUP
COSTS, PROPERTY DAMAGE, AND ANY FINES IMPOSED BY REGULATORY AGENCIES.
6. ALL BYPASS SYSTEM EQUIPMENT INCLUDING PUMPS, ELECTRICAL AND CONTROL
EQUIPMENT, AND THE GENERATOR REMAINS THE PROPERTY OF THE CITY OF
HOMESTEAD. FOLLOWING THE COMPLETION OF CONSTRUCTION AND SUCCESSFUL
7-DAY OPERATION OF THE NEW PUMP STATION, THE CONTRACTOR SHALL CAREFULLY
DISMANTLE THE EXISTING BYPASS SYSTEM. ALL COMPONENTS MUST BE HANDLED
WITH CARE, AND THE CONTRACTOR IS RESPONSIBLE FOR DELIVERING THE
DISMANTLED EQUIPMENT TO A DESIGNATED CITY FACILITY. THIS INCLUDES
PROVIDING ALL LABOR, EQUIPMENT, AND MATERIALS NECESSARY FOR PROPER
LOADING, SECURE TRANSPORT, AND UNLOADING OF THE SYSTEM.
7. IT IS ANTICIPATED THAT BYPASS PUMPING WILL BE REQUIRED DURING THE
INSTALLATION OF THE PROPOSED GRAVITY MAIN. PRIOR TO COMMENCING
CONSTRUCTION OF THE 30-INCH GRAVITY MAIN SEGMENT, THE CONTRACTOR SHALL
SUBMIT A DETAILED WRITTEN PLAN OUTLINING THE PROPOSED BYPASS METHOD AND
SEQUENCE OF OPERATIONS. THE CONTRACTOR SHALL BE FULLY RESPONSIBLE FOR
PROVIDING BYPASS PUMPING TO ACCOMMODATE THE DESIGN FLOW WHILE THE
PUMP STATION IS OUT OF SERVICE. THE BYPASS SYSTEM MUST BE CONTINUOUSLY
MANNED AND MONITORED 24 HOURS PER DAY, 7 DAYS PER WEEK, FOR THE
DURATION OF THE BYPASS OPERATION. GIVEN THAT THE WORK IS TO OCCUR WITHIN
A RESIDENTIAL AREA, THE CONTRACTOR IS REQUIRED TO SELECT AND UTILIZE
EQUIPMENT DESIGNED TO MINIMIZE NOISE LEVELS AND LIMIT DISRUPTION TO THE
SURROUNDING COMMUNITY.
8. SIMILAR TO THE EXISTING BYPASS SYSTEM THE CONTRACTOR WILL OPERATE AND
MAINTAIN THROUGHOUT THE CONSTRUCTION PROCESS AND STATION TESTING
PERIOD, ANY TEMPORARY BYPASS SYSTEM REQUIRED FOR THE GRAVITY MAIN
INSTALLATION SHALL BE SOLELY OPERATED, MAINTAINED, AND CONTINUOUSLY
MONITORED BY THE CONTRACTOR 24 HOURS PER DAY, 7 DAYS PER WEEK. THE
CONTRACTOR SHALL BE FULLY RESPONSIBLE FOR ADDRESSING ANY FAILURES OF
THE TEMPORARY BYPASS SYSTEM RESULTING FROM NEGLIGENCE. THIS INCLUDES
IMMEDIATE CORRECTIVE ACTION, CLEANUP, REPAIR OF ANY PROPERTY DAMAGE,
AND PAYMENT OF ANY REGULATORY FINES THAT MAY BE IMPOSED. ONCE THE
TEMPORARY BYPASS SYSTEM IS NO LONGER NEEDED, IT SHALL BE FULLY
DISMANTLED AND REMOVED FROM THE SITE. THE CONTRACTOR IS ALSO
RESPONSIBLE FOR REPAIRING ANY STRUCTURES IMPACTED BY THE TEMPORARY
SYSTEM AND PERFORMING ALL NECESSARY SITE RESTORATION TO RETURN THE
AREA TO ITS ORIGINAL CONDITION.
SCALE: 1/8" = 1'-0"
EXISTING SITE PLAN DEMOLITION
EX
IS
T.
P
EXIST. P
L
EX
IS
T.
P L
L
REMOVE EXIST.
DRIVEWAY
EXIST. MH (2) RIM EL.
7.40
SOUTH INV. EL. (-)5.69
EAST INV. EL. (-)-5.71
EXIST. MH (1)
RIM EL. 7.40
NORTH INV. EL. (-)5.58
WEST INV. EL. (-)5.56
EXIST. 18" VCP
(TYP.)
EXIST. 21" VCP
(TYP.)
EXIST. 8" VCP
(TYP.)
EXIST. 8" VCP
(TYP.)
REMOVE
TELEMETRY
ANTENNA AND
FOUNDATION
E.O.P.
E.O.P.
20" PVC
RESOD AREAS
DAMAGED BY
CONSTRUCTION
E MOWRY DRIVE
SW 320TH STREET
RESOD AREAS
DAMAGED BY
CONSTRUCTION
ROWROW
REMOVE EXIST.
8" SUCTION
PIPE (TYP.)
REMOVE EXIST. 12" CHECK
AND PLUG VALVES (TYP.)
EXIST. P
EXIST. 8" LINED VCP
GRAVITY MAIN
FROM TRAILER
PARK
L
EXIST. CHAIN LINK
SECURITY FENCE
EXIST. 8' DIA. WET
WELL CONVERTED TO
MH (0)
RIM EL. 7.40
NORTH INV. EL. (-)3.36
SOUTH INV. EL. (-)5.51
EAST INV. EL. (-)5.53
REMOVE EXIST.
EXIST. SERVICE FEED
REMOVE EXIST.
6" DISCHARGE
PIPE (TYP.)
16" DISCHARGE PIPING
REMOVE EXIST. RTU
REMOVE EXIST.
CONTROL PANEL
30A
REMOVE EXIST. 200A TEMP.
SERVICE DISCONNECT
REMOVE EXIST.
DISCONNECTS AND
GUTTER MOUNTED ON
UNISTRUT RACK (TYP.)
REMOVE EXIST.
RACK WITH GUTTER
100A
REMOVE EXIST. 6"X12"
REDUCER (TYP.)
REMOVE EXIST. BAR
SCREEN FROM MH (0)
EL
EC
TR
IC
PU
M
P N o.
KW
D
IE
SE
L G
EN
ER
AT
O
R
EL
EC
TR
IC
PU
M
P N o.
EL
EC
TR
IC
PU
M
P N o.
4'-0" 4'-0"
3'-6"
9' -1
0"
8' -8
REMOVE EXIST.
21" GM VCP
WITH LINER
REMOVE EXIST.
BYPASS GENERATOR.
REMOVE EXIST. SECURITY
FENCE/GATE ON SOUTH
SIDE OF SITE AS
REQUIRED
REMOVE EXIST.
6"X8" REDUCER
(TYP.)
SEAL BYPASS PUMP
WALL PENTRATIONS
W/ NON-SHRINK
GROUT (TYP.)
EXIST. CHAIN LINK
SECURITY FENCE
EXIST. CHAIN LINK
SECURITY FENCE
REMOVE/
RELOCATE EXIST.
72"x72"PAD AND
TRANSFORMER
EL. 5.89
EL. 5.92
EL. 5.82
EL. 6.32
EL. 5.62
EL. 6.20
EL. 5.89
EL. 5.92
EL. 5.82
EL. 6.32
EL. 5.62
EL. 6.20
EXIST. MH-A
SANITARY MANHOLE
RIM ELEVATION:5.95'
INVERT ELEVATION:-5.60'(E)
INVERT ELEVATION:-2.30'(W)
INVERT ELEVATION:-5.60'(N)
EXIST. MH-A
SANITARY MANHOLE
RIM ELEVATION:5.95'
INVERT ELEVATION:-5.60'(E)
INVERT ELEVATION:-2.30'(W)
INVERT ELEVATION:-5.60'(N)
REMOVE EXIST.
BYPASS PUMPS
EXIST.
EXIST.
X X X X X X X
X X
X X
X X
XX
X
X X
X X
X
5.79'
6.03'
6.39'
5.54'
5.91'
6.05'
6.85'
5.9'5.
9'
7.64'
X X X X X X X
X X X X X X X
X X X X X X X X
X X
X X
X X
XX
X
X X
X X
X
SCALE: 1/8" = 1'-0"
PROPOSED YARD PIPING PLAN
DESIGNED
DRAWN
CHECKED
PROJ. ENGR.
DATENo. ISSUED FOR BY
CAD REFERENCE:
ENGINEERS PROJECT:
CLIENTS PROJECT:
CONTRACT:
41055-081
REF. No.
DRAWING:
SHEET:
DATE:
OF
P.E.
DRAWING.
THE SCALE BAR
SHOWN BELOW
MEASURES ONE
INCH LONG ON
THE ORIGINAL
CITY OF HOMESTEAD
HAZEN AND SAWYER
999 PONCE de LEON BLVD, SUITE 1150
CORAL GABLES, FLORIDA 33134
LICENSE No.: 2771 BI
D S
ET
CHRISTOPHER L. KISH
55480
PUMP STATION 22 UPGRADES
JULY 2025
41055-081
8'02468
1/8"=1'-0"
C.L.K.
A.G.J.
C-02J.O.H.
41055-081-C-02.DWG
C.L.K.
PS 22 PROPOSED YARD PIPING AND SITE PLAN
SCALE: 1/8" = 1'-0"
PROPOSED SITE PLAN
EXISTING
PROPOSED
CONCRETE
DRIVEWAY
1. LOCATIONS OF EXIST. UNDERGROUND PIPELINES AND UTILITIES WERE
OBTAINED FROM AVAILABLE RECORDS. NEITHER THE CITY (OWNER) NOR
ENGINEER OF RECORD (EOR) ASSUMES ANY RESPONSIBILITY FOR
PIPELINES OR UTILITIES NOT SHOWN OR NOT LOCATED WHERE SHOWN.
CONTRACTOR SHALL FIELD VERIFY THE LOCATIONS AND ELEVATIONS OF
ALL EXISTING PIPELINES AND UTILITIES BEFORE COMMENCING
CONSTRUCTION WORK. CONTRACTOR SHALL PROVIDE THE OWNER WITH
RECORD INFORMATION ON ALL FIELD VERIFICATIONS MEASUREMENTS AS
SPECIFIED.
2. THE CONTRACTOR SHALL TAKE ALL PRECAUTIONARY MEASURES TO
PROTECT EXISTING PIPELINES OR UTILITIES WHETHER SHOWN OR NOT.
3. THE CONTRACTOR SHALL NOTIFY THE ENGINEER / CITY IN ADVANCE OF
MAKING ANY CONNECTION TO AN ACTIVE PIPELINE OR UTILITY SYSTEM.
4. ALL NEW PIPING AND FITTINGS SHALL BE DUCTILE IRON UNLESS
OTHERWISE SPECIFIED. ALL BURIED IRON PIPE AND FITTINGS SHALL BE
RESTRAINED (LOCKED) MECH. JOINTS AS NOTED.
5. ALL ELEVATIONS REFER TO NORTH AMERICAN VERTICAL DATUM OF 1929
(NAVD 1929), UNLESS OTHERWISE SPECIFIED.
6. THE CONTRACTOR IS RESPONSIBLE FOR DISPOSING OF UNSUITABLE
MATERIAL IN A PROPER MANNER IN COMPLIANCE WITH ALL APPLICABLE
LAWS.
7. THE CONTRACTOR SHALL TAKE ALL PRECAUTIONARY MEASURES
NECESSARY TO PROTECT EXISTING EQUIPMENT REMAINING IN PLACE
FROM DAMAGE. ANY IMPROVEMENTS DAMAGED BY THE CONTRACTOR'S
OPERATIONS SHALL BE EXPEDITIOUSLY REPAIRED OR RECONSTRUCTED
TO CITY / ENGINEER'S SATISFACTION AT THE CONTRACTOR'S EXPENSE
WITHOUT ADDITIONAL COMPENSATION.
8. THE CONTRACTOR SHALL BE RESPONSIBLE FOR TRAFFIC CONTROL
DURING CONSTRUCTION AND FOR ANY NECESSARY TEMPORARY TRAFFIC
DIVERSIONS DURING CONSTRUCTION. A MOT SHALL BE SUBMITTED TO
ENTITIES HAVING JURISDICTION OVER THE R.O.W./ ROADWAY ALONG
WHICH WORK IS OCCURRING, PRIOR TO CONSTRUCTION. MOT SHALL BE
PREPARED BY CERTIFIED SPECIALIST AND MUST BE APPROVED PRIOR TO
CONSTRUCTION COMMENCING.
9. ANY EXISTING SODDED AREAS, FENCING, SIDEWALK OR ROAD PAVEMENT /
MARKINGS DISTURBED DURING CONSTRUCTION SHALL BE RESTORED TO
EQUAL OR BETTER CONDITION.
10. ALL FASTENERS AND MISCELLANEOUS HARDWARE SHALL BE 316
STAINLESS STEEL AS DETAILED IN THE SPECS.
11. CONTRACTOR SHALL MAINTAIN PROPER ACCESS TO SITE AT ALL TIMES
DURING CONSTRUCTION.
12. CONTRACTOR SHALL SUPPLY INSTALL AND REMOVE TEMPORARY FENCING
AS REQUIRED TO SECURE SITE FROM UNAUTHORIZED ACCESS AT ALL
TIMES.
13. CONTRACTOR SHALL VISIT SITE PRIOR TO CONSTRUCTION TO EXAMINE
EXISTING FOLIAGE TO DETERMINE IF TRIMMING OR TREE REMOVAL WILL
BE NECESSARY AND ACCOUNT FOR THIS WORK IF NECESSARY IN THE BID.
14. IF CATCH BASINS OR ASSOCIATED STORM WATER SYSTEMS WITHIN THE
VICINITY OF THE STATION WILL BE IMPACTED BY CONSTRUCTION
ACTIVITIES, THE CONTRACTOR SHALL EMPLOY SILT BARRIERS AS
REQUIRED.
15. ANY CONFLICTS WITH PROPOSED WORK SHALL BE REPORTED
IMMEDIATELY TO THE ENGINEER FOR DIRECTION CONCERNING PIPELINE/
EQUIPMENT LOCATION ADJUSTMENTS OR OBSTACLE RELOCATION.
16. THE CONTRACTOR SHALL BE RESPONSIBLE FOR ALL COORDINATION WITH
HOMESTEAD ELECTRIC DURING THE DURATION OF THE PROJECT.
17. ALL AREAS TO BE SODDED UNLESS OTHERWISE INDICATED.
(**) OWNER FURNISHED EQUIPMENT (OFE)
GENERAL NOTES:
SCALE: 1/8" = 1'-0"
PROPOSED SITE CROSS SECTION A-A
8"
36'-6"
8'-0"1'-6"TRANSITION TO EXISTING OVER 1'-0"
70'-3"
50'-0"
MTE EL. 5.40
EL. 7.40 E.O.S. EL. 7.40 CONC. DRIVEWAY
EL. 7.40
R /W
EXIST. CHAIN LINK
SECURITY FENCE
DRIVEWAY EL. 5.95
EDGE OF PAVEMENT
10% (MAX) SLOPE
1' -6
57 STONE
L
EX
IS
T.
P
EL. 7.40
19'-9"
T.O.S. EL. 8.00
RAISE RIM TO EL. 7.40
1'-0"
C E. MOWRY DRIVEL
COMPOSITE FENCE
W/ROLLER GATE
EX
IS
T.
P
EXIST. P
EXIST. 8" LINED VCP
GRAVITY MAIN
FROM TRAILER
PARK
VALVE
VAULT
L
EX
IS
T.
P L
L
ELECTRICAL CONDUITS.
REFER TO ELECTRICAL
DWG. FOR SIZE AND
WIRES (TYP.)
2" WATER
SERVICE
30" C900 PVC
GRAVITY PIPING
EXIST. 30" C900 PVC
GRAVITY PIPING
BOLLARD
(TYP.)
EXIST MH (2) RIM EL. 7.40
SOUTH INV. EL. (-)5.69
EAST INV. EL. (-)-5.71
E.O.S.
EXIST. MH (1)
RIM EL. 7.40
NORTH INV. EL. (-)5.58
WEST INV. EL. (-)5.56
FLOW
METER
VAULT
WET WELL
BOLLARD
(TYP.)
16" DIP (TYP.)
12" DIP (TYP.)
EXIST. CHAIN
LINK SECURITY
FENCE
EXIST. CHAIN LINK
SECURITY FENCE
EXIST. CHAIN
LINK SECURITY
FENCE
EXIST. 18" VCP
(TYP.)
EXIST. 8" VCP
(TYP.)
EXIST. 8" VCP
(TYP.)
TELEMETRY
ANTENNA AND
FOUNDATION(**) OFE
125 KW GENERATOR W/ MIN.
550 GAL. BELLY TANK
E.O.P.
E.O.P.
E.O.S.
E.O.S.
2" PVC DRAIN
PIPE
6" PVC VENT PIPE
2" PVC
DRAIN PIPE
EXIST. 8' DIA. WET
WELL CONVERTED TO
MH (0)
RIM EL. 7.40
NORTH INV. EL. (-)3.36
SOUTH INV. EL. (-)5.51
EAST INV. EL. (-)5.53
20" PVC
6" EMERGENCY
PUMP OUT
RESOD AREAS
DAMAGED BY
CONSTRUCTION
E MOWRY DRIVE
SW 320TH STREET
RESOD AREAS
DAMAGED BY
CONSTRUCTION
ROWROW
ALUM. FENCE AND
ROLLER GATE
EXIST. 30" C900
PVC STUBOUT 5' ±
CORE DRILL EXIST. MH TO
ACCOMODATE 30" C900 PVC
30" RMJ SLEEVE
30" C900 PVC
GRAVITY PIPING
CORE DRILL EXIST.
MH TO ACCOMODATE
30" C900 PVC EXIST. MH-A
SANITARY MANHOLE
RIM ELEVATION:5.95'
INVERT ELEVATION:-5.60'(E)
INVERT ELEVATION:-2.30'(W)
INVERT ELEVATION:-5.60'(N)
TELEMETRY ANTENNA
AND FOUNDATION
6" ACTIVATED CARBON VENT
COVER. POLOYLOK, OR EQUAL
VALVE ID
MARKER (TYP.)
SECURITY FENCE
BOLLARD
(TYP.)
CONCRETE
ELECTRICAL SLAB
ELECTRICAL RACK
AND SUPPORT
STRUCTURE
CONCRETE
GENERATOR SLAB
(**)OFE
125 KW GENERATOR W/ MIN.
550 GAL. BELLY TANK
EX
IS
T.
P L L
EXIST. PL
E.O.S.
E.O.P.
E.O.S.
EXIST.MH (1)
5' DIA. PRECAST MH
RIM EL. 7.40
NORTH INV. EL. (-)5.58
EAST INV. EL. (-)5.56
WATER
METER
E.O.S.
FLOW
METER
VAULT
WET WELL
EXIST. CHAIN
LINK SECURITY
FENCE
EXIST. CHAIN LINK
SECURITY FENCE
EXIST. CHAIN LINK
SECURITY FENCE
EXIST. MH (2) RIM EL. 7.40
SOUTH INV. EL. (-)5.69
EAST INV. EL. (-)-5.71
EXIST. 8' DIA. WET
WELL CONVERTED TO
MH (0)
RIM EL. 7.40
NORTH INV. EL. (-)3.36
SOUTH INV. EL. (-)5.51
EAST INV. EL. (-)5.53
RESOD AREAS
DAMAGED BY
CONSTRUCTION
RESOD AREAS
DAMAGED BY
CONSTRUCTION
E MOWRY DRIVE
SW 320TH STREET
VALVE ID
MARKER
(TYP.)
EMERGENCY PUMP OUT
ROW ROW
.0
77'-1"
14'-5" 3'-8" 13'-9" 33'-2"12'-0"
'-3
9' -1
1" 8'
-8
EXIST. PAVEMENT
EXIST. PAVEMENT
EXIST. PAVEMENT
ROLLER GATE
REFER TO SHEET C-03
FOR PAVEMENT
RESTORATION DETAILS
EXIST. MH-A
SANITARY MANHOLE
RIM ELEVATION:5.95'
INVERT ELEVATION:-5.60'(E)
INVERT ELEVATION:-2.30'(W)
INVERT ELEVATION:-5.60'(N)
ASPHALT
DRIVEWAY
APPROACH
M
TE
M
TE
EL
. 5
.4
MTE
EL. 5.40
EL. 7.40
EL
. 7
.4
EL. 7.40
EL. 7.40
4.4:1
EL. 5.40
T.O.S. EL. 8.00
T.O.S. EL. 8.00
T.O.S.
EL. 8.00
4:
4:
4:
±4 :1
±4 :1
4:
4:
4:
4.4:1
4.4:1
4.4:1
4.4:1
4.4:1
4.4:1
4.4:1
EL
. 5
.4
EL
. 7
.4
T.O.S.
EL. 7.50
T.O.S.
EL. 7.50
T.O.S.
EL. 7.50
2.7:1
2.7:1
2.7:1
2.7:1
2.7:1
2.7:1
2.7:1
2.7:1
57 STONE
EL
. 5
.4
VA:1
VA:1
VA:1 VA:1
VA:1
M
TE M
TE
MTE
EL. 6.68
EL. 6.40
EL. 6.40
EL. 6.68
MTE
EL. 6.68
EL. 7.40EL. 7.40 EL. 7.40
4:
4:
4:
4:
EX
IS
T.
P
10'-2" 11'-5" 7'-8" 11'-5" 6'-8" 18'-0" 12'-2"
VA
R
IE
S
7' -7
2'
-1 0"
'-1
1"
'-2
'-1
1"
14'-2"9'-4"4'-0"14'-0"27'-5"
RELOCATE EXIST. CITY OF HOMESTEAD
ELEC. TRANSFORMER AND PAD
BACKFLOW
PREVENTER
CONC.
DRIVEWAY
AREA BETWEEN SLAB
AND SLOPE 57 STONE
AREA BETWEEN SLAB
AND SLOPE 57 STONE
8'-9"
12'-1"
AREA BETWEEN SLAB
AND SLOPE 57 STONE
8" THK. CONC. SLAB
8" LIMEROCK BASE (LBR 100)
COMPACTED TO 98% DENSITY
PER AASHTO T180 (TYP.)
REWORK 12" SUBGRADE (LBR 40)
COMPACTED TO 98% DENSITY
PER AASHTO T180 (TYP.)
RELOCATE EXIST. CITY
OF HOMESTEAD ELEC.
TRANSFORMER AND PAD
16" RMJ
PLUG
VALVE
LIGHT
LIGHT
LIGHT
ALUM. FENCE AND
ROLLER GATE
X
X X
X X
XX
X
X X
X X
X
X X X X X X X
DESIGNED
DRAWN
CHECKED
PROJ. ENGR.
DATENo. ISSUED FOR BY
CAD REFERENCE:
ENGINEERS PROJECT:
CLIENTS PROJECT:
CONTRACT:
41055-081
REF. No.
DRAWING:
SHEET:
DATE:
OF
P.E.
DRAWING.
THE SCALE BAR
SHOWN BELOW
MEASURES ONE
INCH LONG ON
THE ORIGINAL
CITY OF HOMESTEAD
HAZEN AND SAWYER
999 PONCE de LEON BLVD, SUITE 1150
CORAL GABLES, FLORIDA 33134
LICENSE No.: 2771 BI
D S
ET
CHRISTOPHER L. KISH
55480
PUMP STATION 22 UPGRADES
JULY 2025
41055-081
C.L.K.
A.G.J.
C-03J.O.H.
41055-081-C-03.DWG
C.L.K.
PAVEMENT RESTORATION
SCALE: 1/8" = 1'-0"
PROPOSED SITE PLAN
TELEMETRY ANTENNA
AND FOUNDATION
VALVE ID
MARKER (TYP.)
SECURITY FENCE
CONCRETE
ELECTRICAL SLAB
ELECTRICAL RACK AND
SUPPORT STRUCTURE
CONCRETE
GENERATOR SLAB 125 KW GENERATOR
W/ MIN. 550 GAL.
BELLY TANK
EX
IS
T.
P L
EX
IS
T.
P L
EXIST. PL
E.O.S.
E.O.P.
E.O.S.
EXIST.MH (1)
5' DIA. PRECAST MH
RIM EL. 7.40
NORTH INV. EL. (-)5.58
EAST INV. EL. (-)5.56
WATER
METER
E.O.S.
FLOW
METER
VAULT
WET WELL
EXIST. CHAIN
LINK SECURITY
FENCE
EXIST. CHAIN LINK
SECURITY FENCE
EXIST. CHAIN LINK
SECURITY FENCE
EXIST. MH (2) RIM EL. 7.40
SOUTH INV. EL. (-)5.69
EAST INV. EL. (-)-5.71
EXIST. 8' DIA. WET
WELL CONVERTED TO
MH (0)
RIM EL. 7.40
NORTH INV. EL. (-)3.36
SOUTH INV. EL. (-)5.51
EAST INV. EL. (-)5.53
RESOD AREAS
DAMAGED BY
CONSTRUCTION
RESOD AREAS
DAMAGED BY
CONSTRUCTION
E MOWRY DRIVE
SW 320TH STREET
EMERGENCY
PUMP OUT
ROW ROW
.0
77'-1"
14'-5" 3'-8" 13'-9" 33'-2"12'-0"
9'-4"4'-0"14'-0"27'-5" 14'-1"
12'-1"
25'-5"4'-9"6'-8"11'-5"7'-8"11'-5"10'-2"
BACKFLOW
PREVENTER
4' -1
1"
'-6
'-3
'-0
8' -1
0"
9' -1
1" 8'
-8
'-7
'-1 1"
'-2
'-1 1"
'-5
2' -1
0" 7'
-7
R12'-0" R12
'-0
R12'-0"
EXIST. PAVEMENT
EXIST. PAVEMENT
EXIST. PAVEMENT
EXIST. MH-A
SANITARY MANHOLE
RIM ELEVATION:5.95'
INVERT ELEVATION:-5.60'(E)
INVERT ELEVATION:-2.30'(W)
INVERT ELEVATION:-5.60'(N)
ASPHLAT
DRIVEWAY
APPROACH
8'02468
1/8"=1'-0"
CONC.
DRIVEWAY
ALONG A NEAT, STRAIGHT LINE
EXISTING PAVEMENT SHALL BE SAW CUT
COMPACTED BACKFILL
TACK COAT ALL
SURFACES & EDGES
2" ASPHALTIC CONCRETE, MIN.
REFER TO SPECIFICATIONS
FOR BASE RESTORATION
SECTION A-A & B-B
PIPE
MIN.
12"
VARIES
MIN.
12"
EXISTING BASE
EXISTING PAVEMENT
8"
C OF ROADWAY
PLAN
CONSTRUCT NEW PAVEMENT
TRENCH
BB
PAVEMENT
EDGE OF
TRENCH
12"
MAX.
M
IN
SECTION A-A
CONSTRUCT NEW PAVEMENT
A A
TRENCH
PLAN
PAVEMENT
EDGE OF
L
C OF ROADWAYL
PAVEMENT RESTORATION TYPE "A"
PAVEMENT RESTORATION TYPE "B"
LEGEND
TYPE A
TYPE B
NOTES:
1. ASPHALTIC CONCRETE THICKNESS & TYPE TO BE THE SAME AS ADJACENT ROADWAY.
2. REFER TO MDWASD TYPE II PAVEMENT RESTORATION DETAIL A1.2 AND TYPE V PAVEMENT
RESTORATION DETAIL A.1.1
3. STRIPING SHALL BE REPLACED AS REQUIRED PER FDOT REQUIREMENTS TO RESTORE ROADWAY TO
ORIGINAL CONDITIONS OR BETTER.
4. SPECIAL ATTENTION AND CARE WILL BE PAID TO ALL DRIVEWAYS THAT ARE ALONG THE FORCE MAIN
ROUTE. ANY DAMAGE BY THE CONTRACTOR DUE TO CONSTRUCTION ACTIVITIES WILL REQUIRED
REPLACEMENT OF THE ENTIRE APPROACH TO ORIGINAL CONDITION AT NO COST TO THE OWNER.
5. CONTRACTOR SHALL ASSUME THAT WORK ON THE FDOT SHALL BE CONDUCTED AT NIGHT. PROPER EQUIPMENT SHALL BE MOBILIZED TO COMPLETE PIPE INSTALLATION AND ROADWAY RESTORATION
AT NIGHT.
6. PAVEMENT MARKINGS SHOULD BE RESTORED BY FDOT DESIGN STANDARDS (LATEST EDITION)
FULL ROAD WIDTH RESTORATION
12"
MIN. MIN.
12"
EXISTING BASE
REFER TO SPECIFICATIONS
FOR BASE RESTORATION
(UNLESS NOTED)
PIPE
12"
MAX.
COMPACTED
BACKFILL
TACK COAT
ALL SURFACES
& EDGES
EXISTING
PAVEMENT
MILL AND OVERLAY
1" ASPHALTIC CONC.
2"1"
24'-0"
MIN, "2 THK.
ASPHALT OVER
TRENCH
RELOCATE EXIST.
HOMESTEAD ELEC.
TRANSFORMER AND
PAD
E.O.S.
AREA BETWEEN SLAB
AND SLOPE 57 STONE
AREA BETWEEN SLAB
AND SLOPE 57 STONE
AREA BETWEEN SLAB
AND SLOPE 57 STONE
CONCRETE DRIVEWAY
LIGHT
LIGHT
LIGHT
ALUM. FENCE AND
ROLLER GATE
CHECKED
PROJ. ENGR.
DATENo. ISSUED FOR BY
CAD REFERENCE:
ENGINEERS PROJECT:
CLIENTS PROJECT:
CONTRACT:
41055-081
REF. No.
DRAWING:
SHEET:
DATE:
OF
P.E.
DRAWING.
THE SCALE BAR
SHOWN BELOW
MEASURES ONE
INCH LONG ON
THE ORIGINAL
CITY OF HOMESTEAD
HAZEN AND SAWYER
999 PONCE de LEON BLVD, SUITE 1150
CORAL GABLES, FLORIDA 33134
LICENSE No.: 2771 BI
D S
ET
CHRISTOPHER L. KISH
55480
PUMP STATION 22 UPGRADES
JULY 2025
41055-081
MAXIMUM TRENCH WIDTH
BA
C
KF
IL
L
PI
PE
E M
BE
D
M
EN
T
BE
D
ID
N
G
PIPE
6" M
IN
M
IN
1' -6
IN
IT
IA
L M
IN
6"
C
AR
EF
U
LL
Y
PL
AC
E
MAX.MAX.
PIPE O.D. PLUS 24 INCHES
12" 12"
VA
R
IE
S
MATERIAL 2" MAXIMUM SIZE. SEE NOTE 5
FO
R
G R
AD
AT
IO
N
SE
E
TA
BL
E N o.
C
LA
SS
II
M
AT
ER
IA
L
AN
D C
O M
PA
C
T
FOUNDATION OF SELECT BACKFILL
BOTTOM OF EXISTING ROADWAY
BASE OR GROUND
DETAIL 3
TYPICAL TRENCH CONSTRUCTION
NTS -
M.J. GATE VALVE
CONCRETE FOOTING
(L-3") x 16"x 8"L-3"
L
1 #3 CONTINUOUS
8"X 8" CONC. AROUND
2" SQUARE NUT
FINISH GRADE
PIPE
VA
R
IE
S
6" DI RISER PIPE
(LENGTH AS
REQUIRED)
PROVIDE EXTENSION
AS REQUIRED
DETAIL 2
VALVE BOX DETAIL
NTS -
NOTES:
1. FOR EXCAVATION AND BACKFILL AROUND MANHOLES, APPURTENANCES, OR IN
WATER, REFER TO PROVISIONS WITHIN THE SPECIFICATIONS.
2. CLASS II MATERIALS ARE WELL GRADED COURSE SANDS AND GRAVEL. SEE TABLE 2
FOR REQUIREMENTS.
3. WHERE REQUIRED, SHEETING AND SHORING SHALL BE IN ACCORDANCE WITH THE
SPECIFICATIONS
4. UNSUITABLE SOILS ARE DEFINED IN THE SPECIFICATIONS AND SHALL INCLUDE FINE
SANDS BELOW THE WATER TABLE.
5. EXTEND EXCAVATION AT LEAST 2 FEET DEEPER FOR FOUNDATIONUNLESS SUITABLE
MATERIAL IS FOUND AT A LESSER DEPTH. GREATER DEPTHS MAY BE REQUIRED FOR
EXTREMELY POOR CONDITIONS.
SUITABLE BACKFILL PLACED AND
COMPACTED TO AT LEAST 98% OF
MAXIMUM DENSITY, 9" LIFTS, PER
AASHTO SPEC. NO. T-180.
SELECT BACKFILL PLACED AND
TO AT LEAST 98% OF MAXIMUM
DENSITY, 2", MAX. SIZE, 6" LIFTS,
PER AASHTO SPEC. NO. T-180
TABLE No.2
SIEVE SIZE PERCENT PASSING
BU WEIGHT
3/4 100
3/8 85-100
#8 40-60
#30 5-30
#100 0-2
USF 6715 WATER VALVE BOX
A A
CONTRACTOR'S RESPONSIBILITY
EROSION AND SEDIMENTATION CONTROLS ARE PERFORMANCE
BASED CRITERIA. IF THE BMPS PROVIDED DO NOT PREVENT SOILS
FROM LEAVING A CONSTRUCTION SITE, THEN THE CONTRACTOR
IS REQUIRED TO EMPLOY ADDITIONAL PROCEDURES TO PROVIDE
CLEAN RUNOFF FROM A SITE.
NOTES:
1. DROP INLET SEDIMENT BARRIERS ARE TO BE
USED FOR SMALL, NEARLY LEVEL DRAINAGE
AREAS. (LESS THAN 5%).
2. USE 2"X4" WOOD OR EQUIVALENT METAL
STAKES.
(3' MIN. LENGTH).
3. INSTALL 2"X4" WOOD TOP FRAME TO INSURE
STABILITY.
4. THE TOP OF THE FRAME (PONDING HEIGHT)
MUST BE WELL BELOW THE GROUND
ELEVATION DOWNSLOPE TO PREVENT RUNOFF
FROM BYPASSING THE INLET.
A TEMPORARY DIKE MAY BE NECESSARY ON
THE DOWNSLOPE SIDE OF THE STRUCTURE.
5. MIRAFI OR APPROVED EROSION CONTROL
FABRIC SHALL BE WRAPPED AROUND GRATE.
6. THE METHOD SHALL NOT APPLY TO INLETS
RECEIVING CONCENTRATED FLOWS, SUCH AS
IN STREET OR HIGHWAY MEDIANS.
7. STAKED INLET PROTECTION NOT ACCEPTABLE
FOR STRUCTURES THAT ARE LOCATED WITHIN
A PAVED APRON (SEDIMENT BAGS AND/OR
FILTER FABRIC BENEATH THE INLET GRATE ARE
ACCEPTABLE SOLUTIONS).
8. STAKED INLET PROTECTION ACCEPTABLE ONLY
FOR STRUCTURES THAT ARE NOT LOCATED
WITHIN A PAVED APRON BUT WOULD REQUIRE
4" BURIAL CONSISTENT WITH TYPICAL SILT
FENCE INSTALLATION (SEDIMENT BAGS AND/OR
FILTER FABRIC BENEATH THE INLET GRATE ARE
ACCEPTABLE ALTERNATIVES).
FLOW
LESS THAN
5% SLOPE
TE
M
PO
R
AR
Y
D
IK
E
IF
N
EE
D
ED
ATTACH FILTER
FABRIC SECURELY TO
2"X4" WOOD FRAME,
OVERLAPPING FABRIC
TO NEXT STAKE
TOP FRAME NECESSARY
FOR STABILITY
2"X4" WOOD FRAME
4 SIDES OF DROP INLET
PONDING HEIGHT
DROP INLET
STAKE
FABRIC
2" X 4" WOOD
FRAME
1'-6"
MAX.
GATHER EXCESS
FABRIC AT
CORNERS
FABRIC
MANHOLE
CURB OPENING
WITHOUT GRATE
CURB FILTER
AGGREGATE
POUCH
OVERFLOW
GAP
NOTES:
1. INSTALL CURB FILTERS AT ALL INLETS WITHOUT GRATES TO KEEP SILT, SEDIMENT AND
CONSTRUCTION DEBRIS OUT OF THE STORM SYSTEM
2. THE CURB FILTER SHALL BE DANDY CURB AS MANUFACTURED BY DANDY PRODUCTS
INC., OR EQUAL. SUBMIT SHOP A SHOP DRAWING FOR THE CURB FILTERS.
3. THE CURB FILTER SHALL FORM OF A CYLINDRICAL TUBE PLACED IN FRONT OF AND
EXTENDING BEYOND THE INLET OPENING ON BOTH SIDES.
4. THE CURB FILTER SHALL HAVE A POUCH ON THE STREET SIDE OF THE UNIT FOR STONE
AGGREGATE TO HOLD THE FILTER IN PLACE.
5. THE CURB FILTER SHALL BE CONSTRUCTED OF A HIGH VISIBILITY ORANGE
MONOFILAMENT FABRIC.
6. FILL POUCH WITH FDOT #57 STONE AGGREGATE TO A LEVEL (AT LEAST HALF-FULL) THAT
WILL KEEP UNIT IN PLACE DURING A RAIN EVENT AND CREATE A SEAL BETWEEN THE
CURB FILTER AND THE SURFACE OF THE STREET.
7. CENTER THE UNIT AGAINST CURB OR MEDIAN INLET OPENING SO THAT THE CURB SIDE
OF THE UNIT CREATES A SEAL WITH THE CURB OR MEDIAN BARRIER AND INLET
STRUCTURE. THERE WILL BE APPROXIMATELY TWELVE (12) INCHES OF THE INLET
PROTECTION UNIT OVERHANGING ON EACH SIDE OF THE OPENING.
8. THE CONTRACTOR SHALL REMOVE ALL ACCUMULATED SEDIMENT AND DEBRIS FROM
SURFACE AND VICINITY OF UNIT AFTER EACH RAIN EVENT.
9. SHOULD THE CONTRACTOR FAIL TO IMPLEMENT STORM DRAINAGE PROTECTION
REQUIREMENTS, OR IF THE METHODS FAIL, THE CONTRACTOR SHALL AT NO ADDITIONAL
CHARGE TO THE CITY CLEAN/ VACUUMS THE STORM DRAINAGE SYSTEM AS NECESSARY
TO REMOVE SEDIMENT/ DEBRIS AS REQUIRED.
NOTES:
1. A SPILLWAY SHALL BE DESIGNATED FOR EACH
DIRECTION OF APPROACHING FLOW AS SHOWN.
THE SPILLWAY SHALL BE LOCATED TO ALLOW
THE MAXIMUM AMOUNT OF STORMWATER TO
POOL WITHOUT FLOODING AREAS UP GRADE OF
THE INLET.
2. FOR INLETS THAT ARE NOT ADJACENT TO
CURBS, PLACE GRAVEL BAGS ONE BAG HIGH
AROUND THE ENTIRETY OF THE INLET TO
ACCOMMODATE FLOW FROM ALL DIRECTIONS.
3. BAG MATERIAL: BAGS SHALL BE WOVEN
POLYPROPYLENE, POLYETHYLENE OR
POLYAMIDE FABRIC, MINIMUM UNIT WEIGHT
FOUR OUNCES PER SQUARE YARD, MULLEN
BURST STRENGTH EXCEEDING 300 PSI IN
CONFORMANCE WITH THE REQUIREMENTS IN
ASTM D3786, AND ULTRAVIOLET STABILITY
EXCEEDING 70% IN CONFORMANCE WITH THE
REQUIREMENTS IN ASTM D4355.
4. BAG SIZE: EACH GRAVEL-FILLED BAG SHALL BE
18-INCHES X 12-INCHES X 3-INCHES AND HAVE A
MASS OF APPROXIMATELY 33 LBS. ALTERNATIVE
BAG SIZES SHALL BE CONSIDERED BASED ON
LOCALLY AVAILABLE MATERIALS.
5. FILL MATERIAL: GRAVEL SHALL BE PEA GRAVEL
3/8 INCHES IN DIAMETER AND SHALL BE CLEAN
AND FREE OF CLAY BALLS, ORGANIC MATTER,
OR OTHER DELETERIOUS MATERIALS.
NOTES:
1. LAY ONE BLOCK ON EACH SIDE OF THE STRUCTURE ON
ITS SIDE FOR DEWATERING. FOUNDATION SHALL BE 2
INCHES MINIMUM BELOW REST OF INLET AND BLOCKS
SHALL BE PLACED AGAINST INLET SUPPORT.
2. HARDWARE CLOTH OR 1/2" WIRE MESH SHALL BE
PLACED OVER BLOCK OPENINGS TO SUPPORT STONE.
3. USE CLEAN STONE OR GRAVEL 1/2 - 3/4 INCH IN
DIAMETER PLACED 2 INCHES BELOW THE TOP OF THE
BLOCK ON A 2:1 SLOPE OR FLATTER.
4. FOR INLETS IN ROADWAYS WITH HEAVY TRAFFIC
CONDITIONS PREFABRICATED FILTER INSERTS MAY BE
USED.
CONCRETE BLOCKWIRE SCREEN FDOT #57 STONE
WIRE SCREEN
2x4 WOOD STUDS
RUNOFF
WATER
W/SEDIMENT
OVERFLOW
FILTERED WATER
CURB INLET
CURB INLET
RUNOFF WATER W/SEDIMENT
FLOW FLOW
CURB INLET
GRAVEL BAGS
2-BAGS HIGH
SPILLWAY
1-BAG
HIGH, TYP
SPILLWAY
1 BAG HIGH
GRAVEL BAGS
2-BAGS HIGH
CURB
INLET
GRATE
DETAIL 1
STORM DRAIN PROTECTION DETAILS
SECTION A-A
NTS
ISOMETRIC VIEW
NTS
DETAIL OF STAKE &
FABRIC ORIENTATION
NTS
PLAN VIEW
NTS
SECTION
NTS
ISOMETRIC
NTS
DETAIL 4
UTILITY CROSSING DETAIL
FITTING TYPE CROSSING
DEFLECTION TYPE CROSSING
MAIN CROSSINGS)
48" MIN. COVER
SEE NOTE BELOW.
CENTER A FULL LENGTH
OF PIPE AT THE POINT
OF CROSSING. (FOR WATER
OF PIPE AT THE POINT
OF CROSSING. (FOR WATER
CENTER A FULL LENGTH
MAIN CROSSINGS)
FITTINGS
RESTRAINED M.J.
COVER
48" MIN.
OBSTRUCTION
NOTES:
1. THE DEFLECTION TYPE CROSSING SHALL BE USED WHEREVER
POSSIBLE
2. JOINT DEFLECTION SHALL BE LIMITED TO 2.50 DEGREES PER JOINT
(MAX.).
3. CLEARANCE SHALL BE 18 INCHES FOR CROSSING WATER MAINS AND
6 INCHES FOR OTHER CROSSINGS. WHEN MAIN IS DUCTILE IRON PIPE
OR AWWA C900 PVC PRESSURE PIPE, MINIMUM VERTICAL
CLEARANCE SHALL BE 6 INCHES.
C.L.K.
A.G.J.
C-04J.O.H.
41055-081-C-04.DWG
C.L.K.
CIVIL DETAILS SHEET 1
CHECKED
PROJ. ENGR.
DATENo. ISSUED FOR BY
CAD REFERENCE:
ENGINEERS PROJECT:
CLIENTS PROJECT:
CONTRACT:
41055-081
REF. No.
DRAWING:
SHEET:
DATE:
OF
P.E.
DRAWING.
THE SCALE BAR
SHOWN BELOW
MEASURES ONE
INCH LONG ON
THE ORIGINAL
CITY OF HOMESTEAD
HAZEN AND SAWYER
999 PONCE de LEON BLVD, SUITE 1150
CORAL GABLES, FLORIDA 33134
LICENSE No.: 2771 BI
D S
ET
CHRISTOPHER L. KISH
55480
PUMP STATION 22 UPGRADES
JULY 2025
41055-081
1/4" BRASS ANCHOR PIN
FOR CONCRETE EMBEDMENT
INSTALLATION
VALVE SIZE
NORMAL OPERATING
POSITION
N.O.=NORMALLY OPEN
N.C.=NORMALLY CLOSED
VALVE TYPE
(SEE CHART BELOW
FOR VALVE TYPE)
OWNERS NAME
TYPE OF USE
DIRECT AND NUMBER
OF TURNS TO OPEN
CCW=COUNTERCLOCKWISE
CW=CLOCKWISE
YEAR VALVE MANUFACTURED
VALVE MANUFACTURER
N.O., CCW-34
XYZ VALVE CO.
24", PV, 2003
VALVE TYPES
NOTES:
SEWER
BV - BALL VALVE
GV - GATE VALVE
BFV - BUTTERFLY VALVE
PV - PLUG VALVE
VALVE INFORMATION TO BE ENGRAVED INTO TOP
SURFACE WITH 1/4" CAPITAL LETTERS.
ENTIRE MARKER TO BE COATED WITH CLEAR EPOXY
TO PREVENT TARNISHING,
MARKERS SHALL BE MANUFACTURED BY WAGCO
MARKERS, OR APPROVED EQUAL.
1.
2.
3.
CITY OF
HOMESTEAD
SEWER
2 #4 BARS CONTINUOUS AND
4 #3 BARS DIAGONAL (2" MIN.
COVER FOR REINFORCING STEEL)
THE WORDS "SEWER" SHALL
BE CAST ON VALVE COVER
24"x24"x8"
THICK CONC. PAD
TYPICAL EACH VALVE BOX
3" DIA. BRONZE DISC ANCHORED
IN CONCRETE PAD STAMP AS REQ'D
3000 P.S.I. CONCRETE MIN.
VALVE BOX AND COVER (TYP.)
CITY OF
HOMESTEAD
XYZ VALVE CO.
24", PV, 1977
WATER N.O.,
CCW-34
DETAIL 6
VALVE IDENTIFICATION MARKER DETAIL
NTS -
C.L.K.
C.L.K.
C-05J.O.H.
41055-081-C-05.DWG
C.L.K.
CIVIL DETAILS SHEET 2
DETAIL 8
30" GM CONNECTION TO MH-A
NTS -
DETAIL 9
30" GM CONNECTION TO MH-0
NTS -
4'-0"
8'-0"
EXIST. MH (A)
4' DIA. PRECAST
RIM EL. 5.95
EAST INV. EL. (-)5.60
WEST INV. EL. (-)2.30
NORTH INV. EL. (-)5.60
LINK SEAL
EXIST.
BALLAST
ROCK (TYP.)
INV. EL. (-)5.60
30" C900 PVC GRAVITY
MAIN TO MH-0
COAT MH W/MICOR
UROFLEX OR EQUAL
REFORM INVERT
FLOW CHANNELS
AS REQUIRED
C-07
CORE DRILL OPENING FOR
30" GM PIPE AND LINK SEAL
EXIST. 8' DIA. WET WELL
CONVERTED TO MH (0)
RIM EL. 7.40
NORTH INV. EL. (-)3.36
SOUTH INV. EL. (-)5.51
EAST INV. EL. (-)5.53
LINK SEAL
EXIST. EPOXY
COATING
EXIST.
BALLAST
ROCK (TYP.)
INV. EL. (-)5.51
30" C900 PVC GRAVITY
MAIN TO MH-A
REFORM INVERT
FLOW CHANNELS
AS REQUIRED
C-07
CORE DRILL OPENING FOR
30" GM PIPE AND LINK SEAL
NOTE:
PATCH/REPAIR INTERIOR COATING AS REQUIRED1.
REPAIR EPOXY
COATING AS
WARRANTED AT
CORE DRILL
EXISTING
DEMOLISH
PROPOSED
(*) REMOVE EXIST. BAR
SCREEN AND RETURN TO CITY
EXIST. EPOXY COATING
INSTALL/ REPAIR
EPOXY COATING AT
PENETRATION AS
REQUIRED REMOVE BYPASS SUCTION
PIPING AND FILL OPENING WITH
NON-SHRINK GROUT (TYP. OF 3)
(*) UPON REMOVAL OF THE BAR SCREEN, ALL
PENETRATION INTO THE MANHOLE FLOOR/
WALLS SHALL BE SEALED W/ NON-SHRINK
GROUT AND COATED W/ EPOXY.
CHECKED
PROJ. ENGR.
DATENo. ISSUED FOR BY
CAD REFERENCE:
ENGINEERS PROJECT:
CLIENTS PROJECT:
CONTRACT:
41055-081
REF. No.
DRAWING:
SHEET:
DATE:
OF
P.E.
DRAWING.
THE SCALE BAR
SHOWN BELOW
MEASURES ONE
INCH LONG ON
THE ORIGINAL
CITY OF HOMESTEAD
HAZEN AND SAWYER
999 PONCE de LEON BLVD, SUITE 1150
CORAL GABLES, FLORIDA 33134
LICENSE No.: 2771 BI
D S
ET
CHRISTOPHER L. KISH
55480
PUMP STATION 22 UPGRADES
JULY 2025
41055-081
C.L.K.
A.G.J.
C-06J.O.H.
41055-081-C-06.DWG
C.L.K.
CIVIL DETAILS SHEET 3
DETAIL
FILL W/CONCRETE AND ROUND
OFF TOP WITH GROUT PLUG
(3)-1" WIDE YELLOW
STRIPES (REFLECTOR)
6" SCH 40 STEEL PIPE GRIND
SMOOTH ALL ROUGH AREAS
AND EDGES
1/2" EXPANSION JOINT
CONCRETE SLAB
PAVEMENT OR
FLOOR SLAB
NOTE:
1. THE MINIMUM WALL THICKNESS OF THE PIPE
SHALL BE 0.188".
2. ALL POST SHALL HAVE 2 COATS OF PRIMER
AND 2 COATS OF YELLOW TOP COAT, UNLESS
OTHERWISE NOTED.
3. THE PRIMER COAT SHALL MEET THE
REQUIREMENTS OF FDOT 971-5.
4. ALL CONCRETE SHALL BE FDOT CLASS1.
DETAIL
DETAIL
DETAIL
6"
24"
DIA.
2%2%
MIN, 3,000 PSI
CONCRETE
FOUNDATION AND
WITHIN PIPE
NOTES:
1. MIN. 3" COVER BETWEEN REBAR AND EDGE OF
CONC. SHALL BE MAINTAINED ALL AROUND.
2. CURING COMPOUND SHALL BE APPLIED TO TOP OF
SLAB WHEN CONCRETE IS PLACED.
3. CONTRACTOR SHALL WET/ FLOOD SLAB AFTER
PLACEMENT TO ALLOW FOR PROPER CURING.
DETAIL
57 STONE
MIN. 6" CLASS A 4000 PSI CONC. MIN. EL. 7.40
8" THK. CONC. SLAB
W/ #5 8" O.C. E.W.
EL. VARIES
STRUCTURE
OR BOLLARD
MIN. 1" THK.
EXPANSION JOINT
8" LIMEROCK BASE (LBR 100)
COMPACTED TO 98% DENSITY
PER AASHTO T180 (TYP.)REWORK 12" SUBGRADE (LBR 40)
COMPACTED TO 98% DENSITY
PER AASHTO T180 (TYP.)
8"
57 STONE
MIN. 6" DEEP EL. 7.40
REWORK 12" SUBGRADE (LBR 40)
COMPACTED TO 98% DENSITY
PER AASHTO T180 (TYP.)
6"
DETAIL
VEVOR PREMIUM
WEED BARRIER
OR EQUAL
8" THK. CONC. SLAB
W/ #5 8" O.C. E.W.
CHECKED
PROJ. ENGR.
DATENo. ISSUED FOR BY
CAD REFERENCE:
ENGINEERS PROJECT:
CLIENTS PROJECT:
CONTRACT:
41055-081
REF. No.
DRAWING:
SHEET:
DATE:
OF
P.E.
DRAWING.
THE SCALE BAR
SHOWN BELOW
MEASURES ONE
INCH LONG ON
THE ORIGINAL
CITY OF HOMESTEAD
HAZEN AND SAWYER
999 PONCE de LEON BLVD, SUITE 1150
CORAL GABLES, FLORIDA 33134
LICENSE No.: 2771 BI
D S
ET
CHRISTOPHER L. KISH
55480
PUMP STATION 22 UPGRADES
JULY 2025
41055-081
C.L.K.
A.G.J.
C-07J.O.H.
41055-081-C-07.DWG
C.L.K.
CIVIL DETAILS SHEET 4
DETAIL
MANHOLE SCHEDULE
MANHOLE No. RIM EL.
INVERT ELEVATION
MH DIA. PIPE DIA.
LENGTH AND
SLOPE COMMENTSNORTH SOUTH EAST WEST
TABLE No.1
DETAIL
3 SQx0.1875 (WALL
ALUMINUM POST. TYP.)
2"
2 SQ x 0.1875
ALUM. TUBE
6" GUIDE ROLLERS
2 1/2" Ø MIN
3 SQx0.1875 (WALL)
ALUMINUM TUBE. 3.66" ALUM. PPOST MANUF.
(WALL) ALUMINUM POST. TYP
8"X8"X0.25 ALUM
BASE PLATE
W/(4) 3/8" Ø A.B.
EMBEDMENT=2"
WWF
16"X16"X8"
CONC. PAD 4'
-4
1'-0" DIA.
4"
2"X2"X0.1875 MIN.
4"Ø WHEEL
TRACK ANCHORED
TO FLOOR
6'-0" 6'-0" 6'-0"
8' -0
4' -0
4' -4
ALUM. TOP COVER ALUM. CAP
ALUM. POST
3.66"X3.66"X146.2"
LARGE
COMPOSITE
PANELS
ALUM. BOTTOM
COVER
6'-0" O.C.
ALUM. PANELS
2"X2"X0.1875" MIN.
TRACK ANCHORED
TO CONC. PAD
2"X2"X0.1875" MIN.
4"Ø WHEEL
MAX. 6' O.C.
CONC. PAD 12"X12"X8"
W/(2) #5 CONT.
NOTE:
1. SECURE COMPOSITE PANELS TO GATE. PER
MANUF. REQUIREMENTS.
NOTE:
1. PANELS / POST SHALL BE PROVIDE SINGLE
MANUFACTURE, MONDARIA OR EQUAL.
2. ALUM. UTILITY GREEN PANELS.
3. ALUM. UTILITY GREEN POSTS.
4. CAP COVER AND TOP/BOTTOM COVER COLOR
UTILITY GREEN.
5. ALUM. POST SHALL BE SLOTED TO RECEIVE
PANELS
NOTE:
1. ALUMINUM MEMBERS IN CONTACT WITH
CONCRETE OR MASONRY SHALL BE PROTECTED
AS PER ADMI-2015. (ALUMINUM DESIGN MANUAL
AND SPECIFICATIONS). M-7 THRU M7.3.
DETAIL
4"
GRADE VARIES
1'-0" DIA.
GRADE MTE GRADE MTE
ALUM. TOP COVER ALUM. CAP
T.O.P. EL. 15.40
GRADE EL. 7.40
ROLLER GATE
6'-0" 6'-0"
SCALE: NTS
SOUTH ELEVATION ALUMINUM FENCE
ALUM. BOTTOM
COVER
X X
X X
X X
X X
X X
X X
X X
X X
PUMP STATION NOTES :
NOTES:
(*) DIMENSIONS ARE FROM AS-BUILT
INFORMATION. ACTUAL DIMENSION
MAY VARY.
DESIGNED
DRAWN
CHECKED
PROJ. ENGR.
DATENo. ISSUED FOR BY
CAD REFERENCE:
ENGINEERS PROJECT:
CLIENTS PROJECT:
CONTRACT:
41055-081
REF. No.
DRAWING:
SHEET:
DATE:
OF
P.E.
DRAWING.
THE SCALE BAR
SHOWN BELOW
MEASURES ONE
INCH LONG ON
THE ORIGINAL
CITY OF HOMESTEAD
HAZEN AND SAWYER
999 PONCE de LEON BLVD, SUITE 1150
CORAL GABLES, FLORIDA 33134
LICENSE No.: 2771 BI
D S
ET
CHRISTOPHER L. KISH
55480
PUMP STATION 22 UPGRADES
JULY 2025
41055-081
C.L.K.
A.G.J.
M-01J.O.H.
41055-081-M-01.DWG
C.L.K.
PUMP STATION 22 PLAN
PUMP: SUBMERSIBLE DISCHARGE, INCLUDES 304 SCH 40 S.S. RAILS, WITH S.S.
INTERMEDIATE SUPPORT. PUMP SHALL BE EQUIPPED WITH SEAL FAILURE
SENSORS AND HEAT SENSORS. SET PUMP IN FIELD IN PROPER RELATION TO
COVER, TO INSURE ACCURATE ALIGNMENT OF STAINLESS STEEL GUIDE RAILS.
ANCHOR PUMP DISCHARGE CONNECTION TO SUMP FLOOR WITH APPROPRIATE
EXPANSION SHIELDS.
LEVEL CONTROL FLOATS SHALL EACH BE PROVIDED WITH A MINIMUM OF FORTY
(40) FEET OF ELECTRIC CABLE AND WEIGHTS. SPLICING NOT ALLOWED.
WET WELL, VALVE BOX AND METER BOX ACCESS HATCH COVER SHALL BE A
MINIMUM OF 54"x34", 106"x96" AND 60"X60" RESPECTIVELY , DOOR LEAF SHALL BE
1/4-INCH THICK STEEL DIAMOND PLATE REINFORCED FOR AN AASHTO H-20
WHEEL LOAD. THE FRAME SHALL BE 1/4-INCH THICK STEEL ANGLE WITH 1"x4"
ANCHORS WELDED AT 18 INCHES ON CENTER. THE FLOOR ACCESS DOOR SHALL
BE EQUIPPED WITH A FLUSH STEEL DROP HANDLE THAT DOES NOT PROTUDE
ABOVE THE COVER, AND A 316 STAINLESS STEEL HOLD OPEN ARM WITH RED
VINYL GRIP THAT AUTOMATICALLY LOCKS THE COVER IN THE 90 DEGREE OPEN
POSITION.
PADLOCK FOR ACCESS HATCH COVERS, CONTROL PANELS, AND DISCONNECTS.
ALL WALL PENETRATIONS THROUGH WET WELL, SHALL BE SEALED WITH NON
SHRINK GROUT BY SIKA OR APPROVED EQUAL.
NEW 6" VENT PIPE REQUIRED WITH STAINLESS STEEL INSECT SCREEN.
ENTIRE INTERIOR SURFACE OF VALVE VAULT SHALL BE COATED WITH MICOR
CRM MODIFIED (NON-SKID) BY EPOYTEC INTERNATIONAL. WET WELL SHALL BE
COATED WITH MICOR UROFLEX BY EPOXYTEC INTERNATIONAL.
1. ALL JOINTS BETWEEN EXISTING AND NEW WORK SHALL BE SAW CUT
2. CONTRACTOR SHALL PROVIDE OPENING FOR CONDUITS AND DRAIN PIPE
3. FEMA FLOOD MAP
12086CO727L
ZONE X
4. WET WELL SHALL BE CONSIDERED CLASS 1, DIVISION 1, GROUP D
REFER TO MANHOLE SCHEDULE C-07
(**) OWNER FURNISHED EQUIPMENT (OFE)
(^) DIMENSIONS MAY VARY BASED ON
MANUFACTURER SELECTED
BOLLARD (TYP.)
60"x60" ACCESS ALUM. HATCH
USF & M TYPE H20 W/ RECESSED LOCK
AND S.S. SPRINGS (TYP.)
BACKFLOW
PREVENTER
12…