4-26KP07 Bingham HS Football Field Sports Upgrade - Drawings.pdf
PDF 13 MB Posted
- Solicitation number
- 26KP07
- Issued by
- Salt Lake County, Utah
About this file
This document set comprises construction drawings and specifications for a stadium lighting and audio-visual system upgrade project at Bingham High School in South Jordan, Utah, prepared for the Jordan School District. The project encompasses electrical, mechanical, and audio-visual system installations, including new pole-mounted lighting fixtures with controllers, ductless split-system HVAC units for the press box, and a comprehensive sound reinforcement system. The scope of work includes demolition of existing stadium lighting fixtures and equipment, installation of new LED lighting on poles positioned at the 20-yard line, heating and cooling equipment upgrades, and audio-visual infrastructure including microphone systems, amplifiers, speakers, and network equipment. The construction documents indicate a project number of 250864, dated February 19, 2026, with Resolut Group serving as the electrical and design consultant and licensed engineer Brian Hicks and Spencer W. Howell as professional engineers on the project.
The technical specifications detail extensive coordination requirements among multiple trades, including electrical, mechanical, and audio-visual contractors. Electrical work includes providing new circuit breakers rated at 20-30 amperes for lighting controllers, installing 240-volt single-phase circuits for the HVAC split systems, and establishing dedicated power for audio-visual equipment racks. Mechanical work specifies Mitsubishi ductless split systems rated at 18,000-22,000 BTU/hour cooling capacity with condensate pump provisions and heat trace on exposed condensate piping. Audio-visual systems include stadium sound amplification with dual wireless microphone receivers, mixing consoles, multiple speaker arrays located on poles and bleachers, and network infrastructure with UTP and STP cabling. The documents require contractors to coordinate with manufacturers prior to installation, verify existing site conditions before bidding, perform selective demolition while protecting existing equipment not included in the scope, and provide complete documentation including updated panel schedules and equipment labeling upon project completion.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
HICKS
BRIAN
No. 7709037-2202
G
IN
E E R
ONA
O F
ES
SI
R
UT
AH
TE OF
S T A
P
L EN
P ro je c t
N
PROJECT NO:
DRAWN BY:
CHK'D BY:
DATE:
T H
IS
P
R
IN
T
IS
IN
C
O L
O R
T h is d ra w in g i s t h e c o p y ri g h te d p ro p e rt y o f R e s o lu t G ro u p
U n a u th o ri z e d d u p lic a ti o n p u b lic a ti o n o r d is tr ib u ti o n i s s tr ic tl y p ro h ib it e d
U s e o f th is d ra w in g i s a t th e u s e r' s o w n r is k a n d
R e s o lu t G ro u p d is c la im s a n y l ia b il it y f o r d a m a g e s o r lo s s e s a ri s in g f ro m i ts u s e
A
BCDEFGHIJKLMN
ABCDEFGHIJKLMN
FEBRUARY 19, 2026
SITE ADDRESS
DRAWING INDEXVICINITY MAPCONSULTANTS
ELECTRICAL:
RESOLUT GROUP
181 E 5600 S,Suite 200 Murray, UT 84107 Phone:(801) 530-3148
SOUTH JORDAN, UTAH
BINGHAM HIGH SCHOOL FOOTBALL FIELD
2/19/2026
Bingham High School Football Field Sports Upgrade
/1
/2
:4 :0
P
M A u to d e s k D o c s /2
J
S D
B in g h a m
H S
F o o tb a ll
F ie ld S p o rt s /2
J S
D B in g h a m
H S
F o o tb a ll
F ie ld S p o rt s U p g ra d e
E L E
C v
.r v t
2/19/26
250864
BR
RESOLUT
TITLE SHEET
E1
J O
R D
A N
S C
H O
O L
D
IS
T R
IC
T
W S o u th J o rd a n
P k w y S o u th J o rd a n
U T
F O
O T
B A
L L F
IE
L D
L
IG
H T
IN
G
/S O
U N
D U
P G
R A
D E
JO
R
D A
N S
C H
O O
L D
IS
T
R
IC
T
JORDAN SCHOOL DISTRICT
2160 W South Jordan Pkwy South Jordan, UT 84095
ELECTRICAL SHEET LIST
E1 TITLE SHEET
E1.1 SYMBOLS, SCHEDULES, NOTES AND DIAGRAMS
E1.2 ELECTRICAL DEMOLITION PLAN
E2 ELECTRICAL PLAN
E3 ELECTRICAL DIAGRAMS
E4 ELECTRICAL PANEL SCHEDULES
TA1 AUDIOVISUAL NOTES, LEGENDS, & SCHEDULES
TA2 BINGHAM HILLS HIGH SCHOOL SOUND PLAN
TA4 AUDIOVISUAL DIAGRAMS
REVISIONS
MARK DATE DESCRIPTION
M
S
S
M
CO2
CO
H2
HZG
NO2
O2
HS
H
T
TC
TH
TS
KEYNOTE SYMBOL
CONTINUATION SYMBOL
SHEET NUMBER WHERE DETAIL IS PLACED
DETAIL NUMBER ON SHEET
PLAN REVISION NUMBER
GENERAL PLAN SYMBOLS
ROOM NAME / NUMBER
POINT WHERE NEW CONNECTS TO EXISTING
AREA BEING DEMOLISHED
AREA NOT IN CONTRACT
* NOTE *
ALL OF GENERAL NOTES ON THIS SHEET ARE TO BE APPLIED TO ALL OTHER DRAWINGS IN THIS SET.THE
SYMBOLS AND ABBREVIATIONS SHOWN ON THIS SHEET MAY OR MAY NOT BE USED IN THIS SET OF
DRAWINGS.
GRILLE, REGISTER, DIFFUSERS
AIRFLOW
CATALOG THROW PERFORMANCE
NECK SIZE / MODULE SIZE
EXISTING DUCT TO REMAIN
OVAL DUCT SIZE (WIDTH / HEIGHT)
SQ. DUCT SIZE (WIDTH X HEIGHT)
HVAC SYMBOLS
RECT. SUPPLY DUCT RISE / DROP
MECHANICAL EQUIPMENT
ROUND DUCT SIZE (DIAMETER)
DUCT TO BE DEMOLISHED
EQUIPMENT BY OTHERS
(REFER TO OTHER
DISCIPLINES)
EXISTING TO REMAIN
EQUIPMENT
Ø ROUND
ABV ABOVE
AC AIR CONDITIONING
AD AREA DRAIN
ADD ADDENDUM
AFF ABOVE FINISHED FLOOR
AFUE ANNUAL FUEL UTILIZATION EFFICIENCY
ALT ALTERNATE
AP ACCESS PANEL
ARCH ARCHITECT/ARCHITECTURAL
BFF BELOW FINISHED FLOOR
BLW BELOW
BTU BRITISH THERMAL UNITS
BTUH BRITISH THERMAL UNITS PER HOUR
CAP CAPACITY
CB CATCH BASIN
CFM CUBIC FEET PER MINUTE
CLG CEILING
CO CLEAN OUT
CW COLD WATER
D DEGREE
DB DRY BULB
DIA DIAMETER
DN DOWN
DW DISTILLED WATER
EA EACH
EAT ENTERING AIR TEMPERATURE
ELEC ELECTRICAL
EQUIP EQUIPMENT
EWC ELECTRIC WATER COOLER
EWT ENTERING WATER TEMPERATURE
E/A EXHAUST AIR
EXIST EXISTING
F DEGREES FAHRENHEIT
FCO FLOOR CLEAN OUT
FD FLOOR DRAIN
FDC FIRE DEPARTMENT CONNECTION
FL FLOOR
FO FUEL OIL
FOV FUEL OIL VENT
FOR FUEL OIL RETURN
FOS FUEL OIL SUPPLY
FPM FEET PER MINUTE
FS FLOOR SINK
FT FOOT/FEET
FTR FIN TUBE RADIATION
GAL GALLON
GF GAS-FIRED
GC GENERAL CONTRACTOR
GPM GALLONS PER MINUTE
GW GREASE WASTE
HB HOSE BIB
HP HORSE POWER
HTG HEATING
HTR HEATER
HW HOT WATER
HYD HYDRANT
ID INDIRECT
IN INCH
INV INVERT
LB POUND
LB/HR POUNDS PER HOUR
LAT LEAVING AIR TEMPERATURE
LP LOW PRESSURE
LPG LIQUEFIED PETROLEUM GAS
LVR LOUVER
LWT LEAVING WATER TEMPERATURE
M/A MIXED AIR
MAX MAXIMUM
MBH ONE THOUSAND BTU PER HOUR
MCF ONE THOUSAND CUBIC FEET
MD MOTORIZED DAMPER
MECH MECHANICAL
MFR MANUFACTURER
MIN MINIMUM
MISC MISCELLANEOUS
MTR MOTOR
MU/A MAKE-UP/AIR
NC NOISE CRITERIA
NC NORMALLY CLOSED
NIC NOT IN CONTRACT
NO NUMBER
NO NORMALLY OPEN
NTS NOT TO SCALE
O OXYGEN
O/A OUTSIDE AIR
ORD OVERFLOW ROOF DRAIN
PD PRESSURE DROP
PIV POST INDICATOR VALVE
PLBG PLUMBING
PRESS PRESSURE
PRV PRESSURE REDUCING VALVE
PSI POUNDS PER SQUARE INCH
PSIG POUNDS PER SQUARE INCH GAUGE
PWR POWER
R DUCT RISER
R/A RETURN AIR
RCP RADIANT CEILING PANEL
RD ROOF DRAIN
REC RECESSED
RED REDUCER
RH RELATIVE HUMIDITY
RL/A RELIEF AIR
RM ROOM
RPM REVOLUTIONS PER MINUTE
RW RAIN WATER
SF SQUARE FOOT
S/A SUPPLY AIR
SAN SANITARY
SF SQUARE FOOT
SD SMOKE DAMPER
SM SURFACE MOUNT
SP STANDPIPE
SP STATIC PRESSURE
STM STEAM
T THERMOSTAT
TD TEMPERATURE DROP
TDR TRENCH DRAIN
TEMP TEMPERATURE
TYP TYPICAL
UG UNDERGROUND
VAC VACUUM
V VENT
VAV VARIABLE AIR VOLUME
VENT VENTILATION
VTR VENT THROUGH ROOF
W WASTE
WB WET BULB
WCO WALL CLEAN OUT
WH WALL HYDRANT
ABBREVIATIONS
TYPE (SEE SCHEDULE)
MAX NC RATING
DESIGN AIRFLOW RATE
DESIGN WATER FLOW
OPERATING WEIGHT
HEATING CAPACITY
NOMINAL COOLING CAPACITY
EXISTING RELOCATED
EQUIPMENT
AC AIR CONDITIONING UNIT
ACCU AIR COOLING CONDENSING UNIT
AHU AIR HANDLING UNIT
AS AIR SEPARATOR
B BOILER
CH CHILLER
CT COOLING TOWER
CUH CABINET UNIT HEATER
CHWP CHILLED WATER PUMP
DBP DOMESTIC WATER BOOSTER PUMP
DC DUCT MOUNTED COIL
DCP DOMESTIC WATER CIRCULATING PUMP
EF EXHAUST FAN
EDC ELECTRIC DUCT COIL
ET EXPANSION TANK
EWH ELECTRIC WATER HEATER
FCU FAN COIL UNIT
FP FIRE PUMP
GI GREASE INTERCEPTOR
GRV GRAVITY ROOF VENTILATOR
HWP HEATING WATER PUMP
HRU HEAT RECOVERY UNIT
PRV POWER ROOF VENTILATOR
RE RETURN/EXHAUST FAN
RTU ROOFTOP UNIT
SP SUMP PUMP
UH UNIT HEATER
WH WATER HEATER
EQUIPMENT ABBREVIATIONS
DAMPER TYPES
ROUND SUPPLY DUCT RISE / DROP
RECT. RETURN DUCT RISE / DROP
ROUND RETURN DUCT RISE / DROP
RECT. EXHAUST DUCT RISE / DROP
ROUND EXHAUST DUCT RISE / DROP
BOTTOM OF EQUIPMENT HEIGHT
NECK SIZE
AIRFLOW
AIRFLOW
MOUNTING ELEVATION (CENTERLINE)
NOMINAL DUCT SIZE
AIRFLOW
NECK SIZE/ SLOT(S)/ ACTIVE LENGTH
AIRFLOW
MOUNTING ELEVATION (CENTERLINE)
NOMINAL DUCT SIZE
AIRFLOW
NECK SIZE / MODULE SIZE
MAX NC RATING
TYPE COUNT FOR SPACE
UNIT IDENTITY
GAS SUPPLY INPUT RATE
THROW PATTERN
SIDEWALL SUPPLY
GRILLE
ROUND CEILING
DIFFUSER
SQUARE CEILING
DIFFUSER
SIDEWALL RETURN
GRILLE
CEILING RETURN
POINT WHERE EXISTING IS TO BE DEMOLISHED
24"x12"
24"/12" FO
18"Ø
(E)AHU-2
RTU-1
10.0 ton
RTU-1
180000 Btu/h
180 CFH
3.7 GPM
VAV 1-2
(R)AHU-3
FLUE
C/A
SA
SA
VA
OA
TA
RA
RLA
EA
GEA
LH
(E)
EF-XX
500 CFM
AC-1
AFF:7'-0"
6"Ø
CD11 100
TYP. X 4
10"Ø/24x24 H6/9/1729
CD3 500
8"Ø/2s/4'-0"L
LD8 200
18"x10"
SG1 500
AFF:9'-0"
16"x16"
RG1 800
AFF:9'-0"
12"x12"/24x24
RG2 500
ET-1
379 lb
Room
LINEAR DIFFUSER
SUPPLY AIR - LOW PRESSURE
SUPPLY AIR - MEDIUM PRESSURE
VENTILATION AIR
OUTDOOR AIR
RETURN AIR
TRANSFER AIR
RELIEF AIR
GENERAL EXHAUST AIR
GREASE EXHAUST DUCT
LABORATORY HOOD
FLUE GAS VENT
COMBUSTION AIR
MANUAL DAMPER
MOTORIZED (ATC) DAMPER
BACKDRAFT DAMPER
SMOKE DAMPER
FIRE DAMPER
COMB. FIRE/ SMOKE DAMPER
MECHANICAL PIPING SYMBOLS
EXISTING PIPE TO REMAIN
PIPE TO BE DEMOLISHED
ABOVE GROUND PIPING
NOMINAL PIPE SIZE
BELOW GROUND PIPING
PIPE SLOPE (WHEN APPLICABLE)
MECHANICAL DEVICES
VALVE TYPES
PIPE RISE / DROP
2"
1/8" / 12" SLOPE
(E)
CHWR
CHWS
GCHWR
GCHWS
CD
CWR
CWS
GHWR
GHWS
GWR
GWS
HWR
HWS
NER
NES
G
LP
RL
RS
RD
LPS
LPCR
PC
HPS
HPCR
CHILLED-WATER RETURN
CHILLED-WATER SUPPLY
GLYCOL CHILLED-WATER RETURN
GLYCOL CHILLED-WATER SUPPLY
CONDENSATE DRAIN
CONDENSER-WATER RETURN
CONDENSER-WATER SUPPLY
GLYCOL HEAING-WATER RETURN
GLYCOL HEATING-WATER SUPPLY
GROUND LOOP-WATER RETURN
GROUND LOOP-WATER SUPPLY
HOT-WATER RETURN
HOT-WATER SUPPLY
NET ENERGY LOOP RETURN
NET ENERGY LOOP SUPPLY
NATURAL GAS
LIQUID PROPANE
REFRIGERANT LIQUID
REFRIGERANT GAS
REFRIGERANT DISCHARGE
LOW PRESSURE STEAM
CONDENSATE RETURN (LOW PRESSURE)
PUMPED CONDENSATE
HIGH PRESSURE STEAM
CONDENSATE RETURN (HIGH PRESSURE)
SHUTOFF
BAL
BFV
CHECK
CHECK
CIRC
GATE
GLOBE
LOCK
PRV
QUICK
STRAIN
M-CNTRL
3-WAY CNTRL
GAS-CNTRL
PLUG
GAS COCK
REG
BALL VALVE
BALANCING VALVE
BUTTERFLY VALVE
CHECK VALVE
ALTERNATE CHECK VALVE
CIRCUIT SETTER
GATE VALVE
GLOBE VALVE
LOCKED SHIELD VALVE
PRESSURE REDUCING VALVE
QUICK OPENING VALVE
FLUID STRAINER
ELEC. CONTROL VALVE
3-WAY ELEC. VALVE
EMERGENCY GAS SHUTOFF
PLUG VALVE
GAS SHUTOFF COCK
GAS REGULATOR
AHU-1 UNIT IDENTITY
TEMPERATURE SENSOR
TEMP/ HUMIDITY SENSOR
TEMP/ CO2 SENSOR
THERMOSTAT
HUMIDISTAT
HUMIDITY SENSOR
CARBON DIOXIDE DETECTOR
CARBON MONOXIDE DETECTOR
HYDROGEN GAS DETECTOR
HAZARDOUS GAS DETECTOR
NITROGEN DIOXIDE DETECTOR
OXYGEN GAS DETECTOR
HVAC GENERAL NOTES
1 COORDINATE EXACT MOUNTING LOCATION OF ALL THERMOSTATS WITH LATEST REVISION OF
ARCHITECTURAL ELEVATION AND FURNISHINGS PLANS, TYPICAL.
2 THE MECHANICAL CONTRACTOR SHALL PROVIDE FIRE, SMOKE OR COMBINATION FIRE/SMOKE
DAMPERS AT ALL LOCATIONS SHOWN ON THE CONTRACT DOCUMENTS AND AS REQUIRED TO MEET
THE INTEGRITY OF ALL SMOKE AND FIRE PARTITIONS. THE CONTRACTOR SHALL REFER TO THE LATEST ARCHITECTURAL LIFE SAFETY PLANS FOR ALL FIRE AND SMOKE PARTITION LOCATIONS.
DAMPERS ARE TO BE PROVIDED WITH SHUTOFF/TEST SWITCH AT EACH LOCATION.
3 INSTALL ALL TERMINAL BOXES IN EASILY ACCESSIBLE AND SERVICEABLE LOCATIONS, MEETING ALL
MANUFACTURERS REQUIRED CLEARANCES ON EACH SIDE, SEE DETAILS, TYPICAL.
4 THE MECHANICAL CONTRACTOR SHALL PROVIDE CEILING MOUNTED ACCESS DOORS FOR ALL FIRE, SMOKE AND COMBINATION FIRE/SMOKE DAMPERS INSTALLED ABOVE INACCESSIBLE CEILING.
FIELD VERIFY EXACT INSTALLATION LOCATIONS PRIOR TO COMMENCING WORK AND COORDINATE
INSTALLATIONS WITH LATEST ARCHITECTURAL REFLECTED CEILING PLANS.
5 PROVIDE ACCESS DOORS TO ACCESS VAV BOX CONTROLS ABOVE HARD CEILINGS. PROVIDE
MINIMUM 24" X 24".
6 THE CONTRACTOR SHALL INFORM THE DESIGNER OF ANY PROPOSED DEVIATIONS FROM THE
CONTRACT DOCUMENTS.
7 PROVIDE ACCESS TO ALL TEMPERATURE CONTROLS ABOVE CEILING. LOCATE IN ACCESSIBLE
LOCATION. WHERE THERE ARE HARD CEILINGS, THE CONTRACTOR SHALL PROVIDE 24" X 24"
ACCESS DOOR.
8 SUPPLY AND RETURN PIPING TO COILS ARE THE SAME SIZE.
9 CONTRACTOR SHALL LOCATE TEMPERATURE SENSORS AT 4'-0" AFF, A MINIMUM OF 8" FROM LIGHT
SWITCH, UNLESS OTHERWISE NOTED ON THE ARCHITECT'S ELEVATIONS. COORDINATE EXACT
LOCATIONS WITH ARCHITECT.
10 CONDENSATE DRAINS SHALL BE SUPPLIED FOR ALL COOLING EQUIPMENT. CONTRACTOR SHALL
ENSURE PROPER INSTALLATION AND DRAINAGE AS REQUIRED BY FEDERAL, STATE, AND LOCAL
CODES. CONDENSATE PIPING SHALL BE TYPE "L" COPPER UNLESS OTHERWISE NOTED IN THE
SPECIFICATIONS.
11 PROVIDE A 6" HOUSEKEEPING PAD FOR EACH PIECE OF MECHANICAL EQUIPMENT THAT IS FLOOR
MOUNTED. COORDINATE SIZES WITH MECHANICAL EQUIPMENT SELECTED.
12 ALL SUPPLY, RETURN, AND EXHAUST DUCTWORK SHALL BE RATED FOR PRESSURE CLASS OF 2"
W.G. UNLESS NOTED OTHERWISE ON THE PLANS OR IN THE SPECIFICATIONS.
13 THIS CONTRACTOR SHALL BE REQUIRED TO REPLACE FILTERS ON HVAC EQUIPMENT AFTER ALL
DUST PRODUCING CONSTRUCTION HAS BEEN COMPLETED AND PRIOR TO THE FINAL PUNCH.
PROJECT REQUIREMENTS
1 THE PROJECT GENERAL NOTES APPLY TO ALL
2 REMOVE ALL UNUSED PIPING, DUCTWORK, EQUIPMENT, AND ACCESSORIES.
3 THE MECHANICAL CONTRACTOR SHALL BE RESPONSIBLE FOR FIELD VERIFYING ALL EXISTING CONDITIONS FOR PLUMBING AND MECHANICAL SYSTEMS WITHIN THE SCOPE OF WORK SPACE AND WITHIN CLOSE PROXIMITY TO THE SCOPE OF WORK SPACE. THE CONTRACTOR WILL FIELD VERIFY AS MUCH AS IS REASONABLE BEFORE THE FINAL BID. AFTER THE FINAL BID THE CONTRACTOR WILL
NOTIFY THE OWNER, ARCHITECT, AND MECHANICAL DESIGN ENGINEER IMMEDIATELY UPON
DISCOVERY OF EXISTING CONDITIONS THAT MAY AFFECT THE DESIGN.
4 THE MECHANICAL CONTRACTOR SHALL PERFORM SERVICE AND REPAIR ON THE EXISTING
EQUIPMENT AND ITS ACCESSORIES AS FOLLOWS: CLEAN ALL COILS, REPLACE THE FILTERS AND
BELTS, INSPECT, REPAIR, OR REPLACE THE ECONOMIZERS, DRIVERS AND FAN BEARINGS,
MOTORS, CONTROL COMPONENTS, VALVES, AND ANY OTHER ITEM NECESSARY FOR A COMPLETE
AND PROPER OPERATING SYSTEM. THIS CONTRACTOR SHALL ALSO VISIT THE SITE, PRIOR TO
FINAL BIDDING, AND VERIFY ALL EXISTING SITE CONDITIONS. PROVIDE ALL MATERIAL AND
COMPONENTS AS NEEDED TO BRING THE UNITS TO FULL COMPLIANCE OF THE OWNER’S CRITERIA
AND LOCAL AUTHORITY HAVING JURISDICTION.
5 WHERE FLOOR DRAINS OCCUR WITH THE LIMITS OF CONSTRUCTION, PREVENT CONSTRUCTION
DEBRIS FROM ENTERING DRAIN BODY BY SEALING DRAIN OPENING PRIOR TO START OF WORK.
UNSEAL DRAINS AT COMPLETION OF CONSTRUCTION.
6 COORDINATE INSTALLATION OF PIPING, DUCTWORK, CONDUIT, LIGHTS, CABLE TRAY, STRUCTURE, EQUIPMENT, CEILINGS, ARCHITECTURAL COMPONENTS, AND ANYTHING ELSE PERTAINING TO THE
PROJECT TO PREVENT CONFLICTS.
7 THE CONTRACTOR SHALL BE FAMILIAR WITH ALL THE CONDITIONS BOTH EXISTING AND THOSE ILLUSTRATED BY THESE DOCUMENTS AND THOSE OF OTHER DISCIPLINES, INCLUDING, BUT NOT LIMITED TO ARCHITECTURAL, CIVIL, ELECTRICAL, VENTILATION, PLUMBING, AND OTHER SYSTEMS
INVOLVED ON THIS PROJECT.
8 FINAL PRODUCT SHALL BE A COMPLETE AND FUNCTIONING SYSTEM, AND SHALL CONFORM TO ALL
REQUIREMENTS OF APPLICABLE FEDERAL, STATE, AND LOCAL CODES, INCLUDING BUT NOT
LIMITED TO THE INTERNATIONAL BUILDING CODE, INTERNATIONAL MECHANICAL CODE, AND
INTERNATIONAL PLUMBING CODE.
9 LOCATE EQUIPMENT REQUIRING ACCESS 2'-0" MAXIMUM ABOVE CEILING.
10 COORDINATE INSTALLATION OF DUCTWORK, PIPING AND MECHANICAL EQUIPMENT WITH NEC
CLEARANCES INCLUDING THE SPACE ABOVE ELECTRICAL PANELS, TRANSFORMERS AND OTHER
ELECTRICAL EQUIPMENT. NO PIPING OR DUCTWORK TO RUN OVER ELECTRICAL PANELS, VFD'S OR MCC'S. PROTECT EQUIPMENT WITH A 42" DEEP ZONE IN FRONT OF PANELS, VFD'S AND MCC'S.
PROVIDE PANS IF REQUIRED UNDER PIPING.
11 PROVIDE SLEEVES AND/OR OPENINGS TO RUN PIPES AND DUCTS THROUGH FOUNDATIONS,
FLOORS, WALLS, AND ROOF.
12 TRANSITION PIPING AND DUCTWORK SIZES TO MATCH THE SIZE OF EQUIPMENT CONNECTION.
13 ALL PIPE AND DUCT SIZES SHOWN SHALL BE CONTINUED IN THE DIRECTION OF FLOW UNTIL
ANOTHER SIZE IS SHOWN.
14 FOR DETAILS, EQUIPMENT CONNECTIONS, AND PIPE SIZES NOT SHOWN ON THE SEGMENTS, REFER
TO DETAILS, SCHEDULES, AND SPECIFICATIONS.
15 INSTALL ALL EQUIPMENT IN ACCORDANCE WITH THE RESPECTIVE MANUFACTURER'S WRITTEN
INSTALLATION INSTRUCTIONS, AT A LEVEL OF WORKMANSHIP CONSISTENT WITH THE
SPECIFICATIONS.
17 INSTALL EXPOSED PIPING AND DUCTWORK AS HIGH AS PRACTICAL IN ROOMS WITHOUT CEILINGS.
18 LOCATIONS OF PIPING, DUCTWORK AND EQUIPMENT, AS INDICATED ON THE DRAWING, ARE
APPROXIMATE AND SUBJECT TO MINOR ADJUSTMENTS IN THE FIELD, INCLUDING, BUT NOT LIMITED
TO, OFFSETS AND TRANSITIONS. NEW DUCTWORK, PIPING AND EQUIPMENT SHALL BE
COORDINATED WITH STRUCTURE, LIGHTS, REFLECTED CEILING PLANS, CABLE TRAY, ELECTRICAL CONDUIT, PLUMBING, MECHANICAL AND FIRE PROTECTION PIPING, MEDICAL GASES, ALL OTHER
TRADES AND ALL OTHER EXISTING CONDITIONS TO AVOID INTERFERENCE IN THE FIELD..
19 MECHANICAL CONTRACTOR SHALL ENSURE THAT ALL EQUIPMENT IS PROVIDED AND INSTALLED
WITH CLEARANCES PER MANUFACTURERS RECOMMENDATIONS. THE CONTRACTOR SHALL
MAINTAIN PROPER SERVICE SPACE FOR COIL PULLS, BAS DEVICES, MAINTENANCE ACCESS, ETC.
19 THE CONTRACTOR SHALL INFORM THE DESIGNER OF ANY PROPOSED DEVIATIONS FROM THE
CONTRACT DOCUMENTS.
20 IF CONTRACTOR ENCOUNTERS MATERIAL WHICH MAY CONTAIN ASBESTOS, IMMEDIATELY STOP
WORK IN THIS AREA AND NOTIFY THE OWNER.
21 DETAILS REFERENCE ALL SHEETS.
22 INSTALL ALL PIPING AND DUCTWORK WITHOUT FORCING OR SPRINGING.
23 LOCATE VALVING, ACCESSORIES, AND EQUIPMENT IN ACCESSIBLE LOCATIONS. WHERE LOCATED ABOVE HARD CEILING PROVIDE AN ACCESS DOOR IN CEILING. MINIMUM ACCESS DOOR SIZE OF 24"
X 24". COORDINATE EXACT LOCATION AND STYLE WITH ARCHITECT. EQUIPMENT SHALL BE
LOCATED IN THE CEILING CAVITY SO IT CAN BE SAFELY SERVICED FROM SOMEONE STANDING ON A
LADDER PLACED BELOW THE CEILING ACCESS.
24 WHERE VALVING, ACCESSORIES, OR EQUIPMENT IS LOCATED IN A WALL, PROVIDE AN
APPROPRIATELY SIZED ACCESS DOOR. COORDINATE ACCESS DOOR SIZE, LOCATION, AND STYLE
WITH ARCHITECT.
25 CONTRACTOR TO PROVIDE VALVE IDENTIFICATION AND LOCATION ON ALL CEILING TILES WHERE
VALVES ARE LOCATED.
L I C
E N
S E
D
PROFESS IONA
L
E N
G I N
E E
R
No. 4775391-2202
S
T A
T E O F U
TA
H
SPENCER W.
HOWELL
PROJECT NO:
CHK'D BY:
DATE:
T H
IS
P
R
IN
T
IS
IN
C
O L
O R
A
BCDEFGHIJKLMN
ABCDEFGHIJKLMN
02/19/2026
DRAWN BY:
/1
/2
:4 :0
P
M A u to d e s k D o c s /2
J
S D
B in g h a m
H S
F o o tb a ll
F ie ld S p o rt s /2
J S
D B in g h a m
H S
F o o tb a ll
F ie ld S p o rt s U p g ra d e
E L E
C v
.r v t
2/19/26
250864
SK
MJ
MECHANICAL
SYMBOLS,
LEGENDS AND
ABBREVIATIONS
M001
J O
R D
A N
S C
H O
O L
D
IS
T R
IC
T
W S o u th J o rd a n
P k w y S o u th J o rd a n
U T
F O
O T
B A
L L F
IE
L D
L
IG
H T
IN
G
/S O
U N
D U
P G
R A
D E
JO
R
D A
N S
C H
O O
L D
IS
T
R
IC
T
REVISIONS
Title Sheet Revision
1 1
X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X
SSI-1 SSI-22
2 4
CP-1
CP-2
T T
SSO-1 SSO-2
OUTDOOR
CONDENSING
UNIT
RL
RS
R L
R S
INDOOR UNIT
FACTORY ROOF STAND
PROVIDE CURB
FOR PIPE
ROUTING, SEAL
WATER TIGHT.
CONDENSATE PUMP
CEILING
LOCATE UNIT MINIMUM 3-
INCHES BELOW CEILING.
L I C
E N
S E
D
PROFESS IONA
L
E N
G I N
E E
R
No. 4775391-2202
S
T A
T E O F U
TA
H
SPENCER W.
HOWELL
PROJECT NO:
CHK'D BY:
DATE:
T H
IS
P
R
IN
T
IS
IN
C
O L
O R
A
BCDEFGHIJKLMN
ABCDEFGHIJKLMN
02/19/2026
DRAWN BY:
/1
/2
:4 :0
P
M A u to d e s k D o c s /2
J
S D
B in g h a m
H S
F o o tb a ll
F ie ld S p o rt s /2
J S
D B in g h a m
H S
F o o tb a ll
F ie ld S p o rt s U p g ra d e
E L E
C v
.r v t
2/19/26
250864
SK
MJ
MECHANICAL
PLANS
M101
J O
R D
A N
S C
H O
O L
D
IS
T R
IC
T
W S o u th J o rd a n
P k w y S o u th J o rd a n
U T
F O
O T
B A
L L F
IE
L D
L
IG
H T
IN
G
/S O
U N
D U
P G
R A
D E
JO
R
D A
N S
C H
O O
L D
IS
T
R
IC
T
1/2" = 1'-0"
PRESS BOX MECHANICAL DEMOLITION PLAN
1/2" = 1'-0"
PRESS BOX MECHANICAL PLAN
1/2" = 1'-0"
PRESS BOX MECHANICAL ROOF PLAN
0 2' 4'1'
0 2' 4'1'
0 2' 4'1'
KEYNOTES
1 REMOVE BASEBOARD HEATER AND ALL ASSOCIATED CONTROLS.
2 COORDINATE FINAL UNIT LOCATION AND ELEVATION WITH SITE CONDITIONS
3 ROUTE CONDENSATE UP THRU PRESS BOX ROOF AND OVER TO WALL TO GO TO HIGH ROOF,
TERMINATE WITH INSECT SCREEN. COORDINATE FINAL PIPE ROUTING WITH SITE CONDITIONS
4 ROUTE REFRIGERANT PIPING TO/FROM THE REAR OF THE INDOOR UNIT. COORDINATE WITH SITE
CONDITIONS.
5 LOCATE REMOTE CONTROL 48"-60" ABOVE FINISHED FLOOR, COORDINATE EXACT PLACEMENT
WITH OWNER.
6 PROVIDE HEAT TRACE ON CONDENSATE PIPING ABOVE ROOF. PROVIDE CHROMALOX SRF HEATING
CABLE OR EQUIVALENT. FIELD VERIFY LENGTHS AND COORDINATE WITH ELECTRICAL.
NOT TO SCALE
4 WALL MOUNTED DUCTLESS SPLIT SYSTEM DETAIL
4. PROVIDE WITH HANGING BRACKETS FOR WALL MOUNT.
3. 3/8" O.D. BARBED DISCHARGE ADAPTER WITH BUILT-IN CHECK VALVE
2. AUTOMATIC START AND STOP OPERATION
1. 1 GALLON COLLECTION TANK
CP-2 VCMA VCL-24ULS 25 24 1/18 115/1/60 2.5 148 1,2,3,4
CP-1 VCMA VCL-24ULS 25 24 1/18 115/1/60 2.5 148 1,2,3,4
ID MANUFACTURER MODEL NUMBER (GPH) (FT) (HP) VOLT/PH/HZ AMPS WATTS NOTES
RATE HEAD SIZE
FLOW MAX MOTOR
FLUID ELECTRICAL
CONDENSATE PUMP SCHEDULE
9. PROVIDE LINE-HIDE LINE SET COVER SYSTEM.
8. PROVIDE WITH BACNET INTERFACE.
7. PROVIDE WITH DISCONNECT AT OUTDOOR UNIT.
6. INDOOR UNIT IS TO BE POWERED FROM OUTDOOR UNIT.
5. PROVIDE WITH HAIL GUARDS.
4. WIRELESS REMOTE CONTROLLER. PROVIDE WALL MOUNTED HOLDER.
3. PROVIDE FACTORY WIND BAFFLE AND LOW AMBIENT HEAD CONTROLLER TO ALLOW COOLING OPERATION DOWN TO 0 DEG. F. D.B.
2. PROVIDE FACTORY MOUNTED STAND FOR CONDENSING UNIT.
1. CONDENSING UNIT TO BE SIZE MATCHED TO INDOOR UNIT AND TO BE BY SAME MANUFACTURER AS INDOOR UNIT.
SSI-2 / SSO-2 MITSUBISHI 18,000 22,000 PKA-AK18NL 320-425 36 X 12 X 10 1.0 240/1/60 PUZ-AH18NL 32 X 25 X 12 100 11 28 240/1/60 R454B 1/4 1/2 1-9
SSI-1 / SSO-1 MITSUBISHI 18,000 22,000 PKA-AK18NL 320-425 36 X 12 X 10 1.0 240/1/60 PUZ-AH18NL 32 X 25 X 12 100 11 28 240/1/60 R454B 1/4 1/2 1-9
(BTU/H) (BTU/H) MODEL NUMBER RANGE W" x D" x H" (MCA) VOLTS/PH/HZ. MODEL NUMBER W" x H" x D" (LBS.) (MCA) MOCP VOLTS/PH/HZ. TYPE LIQUID GAS
CAPACITY CAPACITY @ 47°F CFM DIMENSIONS AMPS DIMENSIONS WEIGHT AMPS
COOLING HEATING
ID MANUFACTURER
NOMINAL NOMINAL
INDOOR UNIT OUTDOOR UNIT REFRIGERANT
NOTES
CR
D
EV EV
DO
M
TV
J
P#
FB PT
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X X
X W
A P
W A
P X
X
J
P#
VFD
F
TC
D##
WS
#-a
LC
#-a
XX
POWER SYMBOLS LEGEND
SYMBOL DEVICE/FIXTURE DESCRIPTION MOUNTING NOTES
S
WALL MOUNTED RECEPTACLE
SWITCHED RECEPTACLE
EMERGENCY RECEPTACLE
GROUND FAULT RECEPTACLE
RECEPTACLE MODIFIERS:
##": HEIGHT AFF OC
WP: WEATHERPROOF IN-USE
COVER
T: TAMPER-PROOF
U: RECEPTACLE WITH USB OUTLET
G: GROUND FAULT
18"
18"
D Q SP
18"
18"
RECEPTACLE (SPECIFIC HEIGHT)
ISOLATED GROUND RECEPTACLE
7,26, SP W/CAP
GENERAL NOTE
B
18"
SWITCH MODIFIERS:
K: KEYED
T: TIMER
M: MANUAL STARTER THERMAL
OVERLOAD SWITCH
EMERGENCY POWER OFF PUSH BUTTON
DOOR OPENER PUSH PLATE
ELECTRICAL POWER METER
FUSED DISCONNECT SWITCH
TOMBSTONE RECEPTACLE*
CORD REEL, DEVICE VARIES
CORD DROP, DEVICE VARIES
MULTI-OUTLET ASSEMBLY
FILLED SQUARES INDICATE 120V OUTLET
OPEN SQUARES INDICATE WITH USB
SINGLE / DUAL PORT ELECTRICAL VEHICLE
CHARGER
POWER POLE
NON-FUSED DISCONNECT SWITCH
MAGNETIC STARTER
MAGNETIC STARTER WITH FUSED DISCONNECT
POWER RELAY
PUSHBUTTON
VARIABLE FREQUENCY DRIVE
SURGE PROTECTION DEVICE
TRANSFORMER:
SEE SINGLE-LINE DIAGRAM FOR DESCRIPTION &
REQUIREMENTS.
TX
7, 25
GENERAL LEGEND
SYMBOL DESCRIPTION NOTES
SOLID ARCHED LINES INDICATE UNSWITCHED
POWER CIRCUITING
DASHED ARCHED LINES INDICATE SWITCHED
POWER CIRCUITING
ONE CIRCUIT, HOME RUN TO PANEL
SYMBOL DEVICE/FIXTURE DESCRIPTION MOUNTING NOTES
4" CONCRETE
BASE
MAIN DISTRIBUTION PANEL 6'-6" TO TOP 8
FLUSH PANELBOARD 6'-6" TO TOP 8
SURFACE PANELBOARD 6'-6" TO TOP 8
TWO CIRCUITS, HOME RUN TO PANEL -
THREE CIRCUITS, HOME RUN TO PANEL -
CONDUIT RUN CONCEALED IN FLOOR OR GROUND -
CONDUIT RUN CONCEALED IN WALL OR CEILING -
CONDUIT UP -
CONDUIT DOWN -
CONDUIT STUB LOCATION CAP CONDUIT
CONDUIT / CIRCUIT CONTINUATION -
GROUND BUS BAR
CABLE TRAY
SOLID BOTTOM
LADDER
BASKET
MOUNTING
AS NOTED
8+18"
EQUIPMENT CEILING RACK
EQUIPMENT CABINET/RACK
EQUIPMENT 2-POST CABINET/RACK
TELEPHONE DEMARCATION BOARD +18" 25
AS NOTED 18, 25
SEE SPEC.
AS NOTED 18, 25
SEE SPEC.
CEILING
EXISTING --
DEMO --
TEMPORARY --
NEW --
CONDUIT
OHP: OVERHEAD POWER SERVICE
UGP: UNDERGROUND POWER
SERVICE
UGF: UNDERGROUND FIBER
SERVICE
TEL: TELEPHONE SERVICE
POWER DISTRIBUTION EQUIPMENT SYMBOLS
CONTROLLED RECEPTACLE 7+18" OR AS
NOTED
SPD PROTECTED RECEPTACLE 7+18" OR AS
NOTED
TIME CLOCK +60" -
NOT IN CONTRACT --
MAGNETIC STARTER WITH BREAKER DISCONNECT
MOTOR
CEILING MOUNTED RECEPTACLE CEILING
TV BACKBOX FLAT PANEL
HEIGHT +12"
NOTES:
1. HATCHED FILL INDICATES DISTRIBUTION PANEL OR
SWITCHBOARD.
2. SOLID FILL INDICATES BRANCH PANEL OR LOAD CENTER.
3. DASHED BOX INDICATES CODE-REQUIRED CLEARANCE
(WIDTH & DEPTH).
4. DOOR INDICATES FRONT OF RECESSED PANEL.
H P
1A
LP
1A
M D
P
SB1
POWER TAGS LEGEND
JUNCTION BOX
x
JUNCTION BOX
D1 (DEFAULT)
M1/2 = D1 M3/4 =D2
CONDUIT CABLE TYPE CONDUIT SIZING GUIDE
(1) 3/4" C.
(1) 1" C.
(1) 1" C.
(1) MA/LA
(1) S##
(2) S##
MA / LA TYPE CABLE
(18) CABLES PER 3/4" C.
(23) CABLES PER 1" C.
(77) CABLES PER 1-1/2" C.
S## TYPE CABLE
(3-10) CABLES PER 1" C.
(7-18) CABLES PER 1-1/2" C.
CABLE GROUP
D2 (DEFAULT)
MD = D1
MT = D1
(1) 1" C. (1) UTP (8) CABLES PER 1" C.
(20) CABLES PER 1-1/2" C.
D1
D2
(1) 1" C. (1) UTP 5
ROUGH-IN PER
BACK BOX SCH.
SCH AS NOTED
(1) MA
(2) UTP
(1) MA
AS NOTED
D1 (DEFAULT) (1) 1-1/2" C. (1) VGA + (2) LA
(1) HD + (2) LA
(1) VGA + (1) HD
+ (2) LA
VGA (1-4) CABLES PER 1-1/2" C.
HD (1-3) CABLES PER 2" C.
D3
D3
D1
D2
D1
D1
D2
D1
(1) 1" C.
(1) STP
(1) UTP
(1) UTP
(1) STP
(1) STP
(1) STP
(1) STP
(1) STP
(1) STP
IN MILLWORK,
UNDER FURNITURE,
OR AS NOTED
D1 (DEFAULT) (1) 1" C.
(#) UTP
(#) STP
D2 (DEFAULT) (1) 1-1/2" C. (2) UTP + (2) LA
+ (2) S16
AS NOTED5
D1 (DEFAULT) (1) 3/4" C. AS NOTED
AS NOTED5
D1
D4
(1) 1" C.
(2) LA
(2) LA
(18) CABLES PER 3/4" C.
(23) CABLES PER 1" C.
(77) CABLES PER 1-1/2" C.
D1 (DEFAULT) (1) 1" C. AS NOTED (7) CABLES PER 1" C.
(12) CABLES PER 1-1/2" C.
D1 (DEFAULT) (1) 1" C. (1) CT OR
(1) BUS
(7) CABLES PER 1" C.
(12) CABLES PER 1-1/4" C.
D2 (DEFAULT)
D1
NO BACK BOX
PER SCH
PER SCH
(1) 1" C.
(1) S##
(2) S##
(1) UTP
(1) UTP/BUS
5 (DEFAULT)
NA AS NOTED
PER SCH (1) 1" C. (1) S##
PER SIGNAL
FLOW
TV BACK BOX (2) 1-1/2" C. AS NOTED AS NOTED
(2) A1 (DEFAULT)
(1) FOR POWER
(1) 1" C. (1) UTP
(1) CT
(4) CABLES PER 1" C.
(9) CABLES PER 1-1/2" C.
D1 (DEFAULT) (1) 1" C. AS NOTED AS NOTED5
AS NOTED
PER SCH
D1
AS NOTED IN
SCH
(1) 3/4" 5
D1 (DEFAULT) (1) 1" C. (1) UTP 5
D1 OR D2 (1) 1-1/2" C. AS NOTED AS NOTEDAS NOTED
(6) CABLES PER 1" C.
(16) CABLES PER 1-1/2" C.
(4) CABLES PER 1" C.
(9) CABLES PER 1-1/2" C.
(1) 1" C. (1) STP
(1) UTP
(1) UTP
(1) STP
(1) STP
(1) STP
(1) STP
(1) STP
(4) CABLES PER 1" C.
(9) CABLES PER 1-1/2" C.
(4) CABLES PER 1" C.
(9) CABLES PER 1-1/2" C.
S## TYPE CABLE
(3-10) CABLES PER 1" C.
(7-18) CABLES PER 1-1/2" C.
UTP TYPE CABLE
(4) CABLES PER 1" C.
(9) CABLES PER 1-1/2" C.
(1) 1-1/2" C. AS NOTED
(3-10) CABLES PER 1" C.
(7-18) CABLES PER 1-1/2" C.
AS NOTEDAS NOTED
(4) CABLES PER 1" C.
(9) CABLES PER 1-1/2" C.
D1 (DEFAULT) (1) 1-1/2" C. (1) UTP
(1) STP
AS NOTED5
B1 (DEFAULT) (1) 1" C. (1) S##
PER SIGNAL
FLOW
4 (3-10) CABLES PER 1" C.
(7-18) CABLES PER 1-1/2" C.
S: SIMPLEX D: DUPLEX
Q: FOURPLEX SP: SPECIAL PURPOSE
FLOOR BOX / POKE-THRU
- SEE SCHEDULE FOR TYPE INFORMATION
AS NOTED
AUDIOVISUAL SYMBOLS LEGEND
SYMBOL DEVICE/FIXTURE DESCRIPTION
RECEPTACLE
HEIGHT /
FLOOR BOX /
CEILING
OR AS NOTED
ANALOG AUDIO WALL PLATE
M#: MICROPHONE XLR-F, #
INDICATES QTY M1/M2 = D1 J-BOX,
M3/M4 = D2 J-BOX
AX: AUXILIARY INPUT, 3.5MM/RCA
CONNECTION, WALL PLATE
T: XLR MALE CONNECTION
TS: 1/4 TS CONNECTION
NL1: SPEAKER LEVEL SPEAKON
OUTPUT 1 CONNECTION,
CABLE PER SIGNAL FLOW
NL2: SPEAKER LEVEL, SPEAKON
OUTPUT 2 CONNECTION,
CABLE PER SIGNAL FLOW
MOUNTING COMMENTS
W F C W: WALL F: FLOOR BOX C: CEILING
RECEPTACLE
HEIGHT /
FLOOR BOX
OR AS
NOTED
DIGITAL AUDIO WALL PLATE
MD: DUAL MICROPHONE XLR-F/1/4"
INPUT AUDIO TRANSCEIVER
MT: DUAL MICROPHONE XLR-F INPUT
AUDIO TRANSCEIVER
M2D: MICROPHONE (2) XLR-F INPUT
& (2) XLR-M OUTPUT UTP AUDIO
TRANSCEIVER
M4D: MICROPHONE (4) XLR-F INPUT
UTP AUDIO TRANSCEIVER
MXT: DUAL MICROPHONE XLR-F &
AUXILIARY 3.5 INPUT WITH 3.5MM
OUTPUT UTP AUDIO TRANSCEIVER
7, 25
SWITCH
HEIGHT OR
AS NOTED
DIGITAL BLUETOOTH WALL PLATE
BT: BLUETOOTH AUDIO RECEIVER
BXT: BLUETOOTH & AUXILIARY
3.5MM INPUT/OUTPUT AUDIO
TRANSCEIVER
7, 25
SWITCH
HEIGHT /
CEILING
OR AS NOTED
MICROPHONE DEVICES
MB: TABLE TOP BOUNDARY
MICROPHONE
MC#: MICROPHONE CEILING ARRAY
# = IDENTIFIES TYPE
MW: WALL MOUNTED MICROPHONE
7, 25
RECEPTACLE
HEIGHT /
FLOOR BOX /
CEILING
OR AS NOTED
PASSIVE VIDEO WALL PLATE
VG: RGBHV VIDEO VGA INPUT W/
3.5MM AUDIO
HD: HIGH DEFINITION HDMI INPUT
HV: HIGH DEFINITION HDMI INPUT
& RGBHV VIDEO VGA INPUT
W/3.5MM AUDIO
ACTIVE VIDEO TRANSCEIVER, TRANSMITTER, OR
RECEIVER WALL PLATE
EN#: AVoIP NETWORK ENCODER
DC#: AVoIP NETWORK DECODER
TxH: HDBaseT TRANSMITTER, HIGH
DEFINITION HDMI INPUT
TxD: HDBaseT TRANSMITTER, HIGH
DEFINITION HDMI & RGBHV
VGA INPUT W/3.5MM AUDIO
RxH: HDBaseT RECEIVER, HIGH
DEFINITION HDMI OUTPUT
US#: USB EXTENSION INPUT/
OUTPUT # = IDENTIFIES TYPE
CHD: HDBaseT TRANSMITTER, DUAL
HIGH DEFINITION HDMI INPUT
HDU: HDBaseT TRANSMITTER, HIGH
DEFINITION HDMI INPUT W/3.5MM
AUDIO & USB INPUT/OUTPUT
7, 25
ACTIVE VIDEO TRANSCEIVER, TRANSMITTER, OR
RECEIVER SURFACE MOUNTED DEVICE
EN#: AVoIP NETWORK ENCODER
DC#: AVoIP NETWORK DECODER
Tx: HDBaseT TRANSMITTER, HIGH
HDMI INPUT
Rx: HDBaseT RECEIVER, HIGH
DEFINITION HDMI OUTPUT
TxM: HDBaseT TRANSMITTER
MULTIPLE INPUT SWITCHER,
OR AS NOTED.
US#: USB EXTENSION INPUT/
OUTPUT # = IDENTIFIES TYPE
HDU: HDBaseT TRANSMITTER, HIGH
DEFINITION HDMI INPUT W/3.5M
AUDIO & USB INPUT/OUTPUT
7, 25
CATEGORY CONNECTION, WALL PLATE
AV#: 8P8C FEMALE CONNECTOR
# INDICATES QTY
TxT: SHIELDED 8P8C FEMALE
CONNECTOR REFER TO SIGNAL
FLOW FOR CONNECTION QTY
SUBSCRIPT INDICATES POINT TO
POINT CONNECTION. REFER TO
SIGNAL FLOW
7, 25
AS NOTEDCLASSROOM SOUND AMPLIFICATION/AMPLIFIER
CSA: CLASSROOM SOUND AMP
7, 5
SWITCH
HEIGHT OR
AS NOTED
2-WAY INTERCOMMUNICATION STATION WITH 1/2
BUTTON
CAL: CALL SWITCH
7, 24
SWITCH
HEIGHT OR
AS NOTED
PERFORMANCE VENUE WALL PLATE
CI: CREWCOM HEADSET INPUT, 4-XLR-F
CIS: CREWCOM TALK BACK WALL
STATION
+108" OR
AS NOTED
ANTENNA EMITTER / RECEIVER
ALS: ASSISTIVE LISTENING SYSTEM
RF ANTENNA OR IR EMITTER
AT: WIRELESS MICROPHONE
RECEIVING ANTENNA
+96" / CEILING
OR AS NOTED
INFRARED PARTITION SENSOR
IR: PARTITION SENSOR
7, 25
SWITCH
HEIGHT OR
AS NOTED
USER INTERFACE DEVICE
V: VOLUME CONTROL, STEREO
OR MONO
SV: COLUMN CONTROL WITH
SOURCE SELECTOR
TP#: TOUCH PANEL
TT#: TABLE TOP TOUCH PANEL
RS#: ROOM SCHEDULING TOUCH
PANEL OR SIGN
KP#: KEYPAD, REFER TO SCH FOR
ROUGH-IN, # IDENTIFIES TYPE
7, 25
7, 23, 25
7, 23, 25
7, 23, 25
7, 24
FURNITURE /
MILLWORK
TABLE / FURNITURE BOX
TB#: TABLE BOX, # IDENTIFIES TYPE
AS NOTED
LOUDSPEAKER
REFER TO LEGEND & SCH FOR TYPE,
FLOOR BOX LOUDSPEAKER IS IN-GROUND /
LANDSCAPE LOUDSPEAKER
AS NOTEDFLAT PANEL DISPLAY
D##: DISPLAY TYPE, # IDENTIFIES TYPE
AS NOTEDPROJECTOR SCREEN
SC#: PROJECTOR SCREEN, # IDENTIFIES
TYPE
UNDER FLAT
PANEL
SOUND BAR
SB#: SOUND BAR, # IDENTIFIES TYPE
19, 23
VIDEO PROJECTOR,
P#: PROJECTOR, # IDENTIFIES TYPE
AS NOTED /
SWITCH
HEIGHT
CUSTOM JUNCTION BOX, REFER TO BACK BOX SCH,
C##: CUSTOM BACK BOX, #
IDENTIFIES TYPE
SSW: PROJECTOR SCREEN
CONTROLLER
+36" OR AS
NOTED
AV CONFERENCING / BROADCAST CAMERA 19
AS NOTEDGROMMET PASS THROUGH PLATE
GP#: # IDENTIFIES QTY OF GANGS
AS NOTED 7
RECEPTACLE
HEIGHT /
FLOOR BOX /
CEILING
OR AS NOTED
RECEPTACLE
HEIGHT /
FLOOR BOX /
CEILING
OR AS NOTED
RECEPTACLE
HEIGHT /
FLOOR BOX /
CEILING
OR AS NOTED
DATA NETWORK SYMBOLS LEGEND
SYMBOL DEVICE/FIXTURE DESCRIPTION MOUNTING NOTES
DATA OUTLET (SINGLE CABLE) 18" WALL/
FLOOR/CEILING
DATA OUTLET (TWO CABLES) 18" WALL/
FLOOR/CEILING
DATA OUTLET (THREE CABLES) 18" WALL/
FLOOR/CEILING
SERIES-X COAXIAL CABLE OUTLET
DISTRIBUTED ANTENNA SYSTEM (DAS)
PUBLIC SAFETY AND/OR
CELLULAR/COMMERCIAL
ANT: ANTENNA
BDA: BI-DIRECTIONAL AMPLIFIER
SPL: SPLITTER
VIA: VIA
108" WALL,
CEILING,
ABOVE
CEILING, OR AS
NOTED
WIRELESS ACCESS POINT* 96" WALL/
CEILING
W F C W: WALL F: FLOOR C: CEILING
GROUND ROD
GROUND ROD WITH TEST WELL
LIGHTNING PROTECTION AIR TERMINAL
LIGHTNING PROTECTION CONDUCTOR SPLICE
STATIC GROUND RECEPTACLE
GROUNDING AND LIGHTNING PROTECTION SYMBOLS
SYMBOL DEVICE/FIXTURE DESCRIPTION MOUNTING NOTES
AS NOTED -
AS NOTED -
AS NOTED -
AS NOTED -
AS NOTED -
AS NOTEDLOUDSPEAKER
REFER TO LEGEND & SCH FOR TYPE
7 (CLG)
18" WALL/
FLOOR/CEILING
EQUIPMENT SYSTEM PANELS
ACS: ACCESS CONTROL PANEL
IDS: INTRUSION DETECTION PANEL
PSP: POWER SUPPLY PANEL
RP#: LIGHTING PANEL
DAS: DISTRIBUTED ANTENNA SYSTEM
ERCCS: FIRST RESPONDERS RADIO SYSTEM
CATV: CABLE TV CONTENT EQUIPMENT
7, 13
CEILING
CEILING
+46" 7, REFER TO
SPEC
+46" 7
+46" 7
8, 9
8, 9, 10, 11
8, 9, 10, 11
8, 9, 10, 11
+72"
+60"
+60"
+60"
+60"
AS NOTED
+46"
18, 25
SEE SPEC.
7, 22
7, 25
7, 25
7, 25
7, 25
7, 25
EXIT SIGNAGE
SHADING & ARROWS INDICATE FACES &
DIRECTIONAL CHEVRONS
WALL-MOUNTED FIXTURES, TYPICAL
(VARIOUS SYMBOLS)
LINEAR, CEILING MOUNTED LIGHT FIXTURE
(VARIOUS DIMENSIONS, DOTS INDICATE PENDANT
MOUNT)
RECESSED DOWNLIGHT FIXTURE
CHEVRON INDICATES WALL WASH
DIRECTIONAL LIGHT, TRACK OR FLOOD LIGHT
LINEAR LIGHT, TAPE LIGHT
LIGHTING FIXTURE SYMBOLS LEGEND
NOTE:
1. SWITCH IDS ARE UNIQUE PER SPACE.
2. A SWITCH WITHOUT A TAGGED ID CONTROLS ALL LIGHTING FIXTURES WITHIN A SPACE.
3. ID TAGS MAY BE USED ON CONTROL DEVICES OTHER THAN SWITCHES, SUCH AS OCCUPANCY
SENSORS OR CONTACTORS.
4. ABSENCE OF A SWITCH DESIGNATION ON A LIGHTING FIXTURE INDICATES FIXTURE IS
CONTROLLED BY THE ONLY SWITCH IN THE SPACE.
5. AN "x" IN PLACE OF THE SWITCH DESIGNATION INDICATES UNSWITCHED.
a
SYMBOL DEVICE/FIXTURE DESCRIPTION MOUNTING NOTES
CEILING
CEILING
AS NOTED
AS NOTED
WALL/CEILING
WALL/CEILING
1, 2
1, 2
1, 3, 5, 12
1, 3, 5, 12
EMERGENCY EGRESS LIGHT FIXTURE CEILING 1, 2, 4
CRITICAL EGRESS LIGHT FIXTURE CEILING 1, 2, 4
CIRCULAR, CEILING MOUNTED LIGHT FIXTURE
CENTER DOT INDICATES PENDANT
CEILING 1, 2, 4
EMERGENCY LIGHTING UNIT, INTEGRAL BATTERY WALL/CEILING 1
CW W: WALL C: CEILING
LIGHTING TAGS LEGEND
EXIT SIGNAGE WITH AUXILIARY HEAD
SHADING & ARROWS INDICATE FACES &
DIRECTIONAL CHEVRONS
AS NOTED
AREA LIGHT POLE & FIXTURE
POST-TOP LIGHT POLE & FIXTURE
BOLLARD LIGHT
ARROWS INDICATE DIRECTION
SWITCH
SWITCH MODIFIERS:
3: 3-WAY
4: 4-WAY
K: KEYED
D: DIMMING
T: TIMER
P: SWITCH W/ PILOT LIGHT
CONCRETE
BASE
CONCRETE
BASE
CONCRETE
BASE
LIGHTING CONTROL SYMBOLS
SYMBOL DEVICE/FIXTURE DESCRIPTION MOUNTING NOTES
46"
1, 14
REFER TO DIA
1, 14
REFER TO DIA
1, 14
REFER TO DIA
6, 7
STEP LIGHT FIXTURE AS NOTED 1
IN-GRADE LIGHT FIXTURE AS NOTED 1
MOMENTARY CONTACT SWITCH 46" 6, 7
LOW VOLTAGE WALL STATION
(SUBSCRIPT INDICATES CONFIGURATION)
46" 6, 7
CEILING FAN CEILING -
LIGHTING CONTACTOR
LIGHTING CONTROL TOUCH SCREEN
WALL
46"
SENSORS/SWITCHES:
PC: PHOTO-ELECTRIC CONTROL
OS: OCCUPANCY SENSOR SWITCH
DL: DAYLIGHT HARVESTING SENSOR
AS NOTED 6, 7, 28
6,7
SWITCH PACKS:
AP: AUXILIARY PACK
PP: POWER PACK
ABOVE
CEILING
6, 28
CONTROL:
RC: DIGITAL ROOM CONTROLLER
(SUBSCRIPT = NUMBER OF RELAYS)
EP: EMERGENCY LIGHTING CONTROL
UNIT
ABOVE
CEILING
REFER TO DIA
AND SPEC
CW W: WALL C: CEILING
A a
FIXTURE ID (UPPERCASE UNDERLINED LETTER)
PANEL ID (NUMBERS & UPPERCASE LETTERS) - CIRCUIT NUMBER
RELAY ID (UPPERCASE LETTERS)
FIXTURE CONTROL ZONE ID (LOWERCASE LETTER)
#: INDICATES SWITCH TYPE
LOWERCASE LETTER: INDICATES SWITCH ID
HICKS
BRIAN
No. 7709037-2202
G
IN
E E R
ONA
O F
E
SS
I
R
UT
AH
TE OF
S T A
P
L EN
PROJECT NO:
DRAWN BY:
CHK'D BY:
DATE:
T H
IS
P
R
IN
T
IS
IN
C
O L
O R
A
BCDEFGHIJKLMN
ABCDEFGHIJKLMN
S A
L T
L A
K E
T .G
E O
R G
E
02/19/26
CONSTRUCTION DOCUMENTS
/1
/2
:4 :0
P
M A u to d e s k D o c s /2
J
S D
B in g h a m
H S
F o o tb a ll
F ie ld S p o rt s /2
J S
D B in g h a m
H S
F o o tb a ll
F ie ld S p o rt s U p g ra d e
E L E
C v
.r v t
2/19/26
250864
BR
RESOLUT
SYMBOLS,
SCHEDULES,
NOTES AND
DIAGRAMS
E1.1
J O
R D
A N
S C
H O
O L
D
IS
T R
IC
T
W S o u th J o rd a n
P k w y S o u th J o rd a n
U T
F O
O T
B A
L L F
IE
L D
L
IG
H T
IN
G
/S O
U N
D U
P G
R A
D E
JO
R
D A
N S
C H
O O
L D
IS
T
R
IC
T
GENERAL NOTES
1. CONSULT ARCHITECTURAL REFLECTED CEILING PLANS FOR EXACT LOCATION OF ALL LIGHTING FIXTURES.
2. VERIFY ALL EQUIPMENT DIMENSIONS AND LOCATIONS BEFORE BEGINNING ROUGH IN. CONSULT ALL APPLICABLE CONTRACT DRAWINGS AND SHOP DRAWINGS TO INSURE NEC CODE CLEARANCES REQUIRED
AROUND ALL ELECTRICAL EQUIPMENT.
3. CONTRACTOR SHALL VERIFY ALL ELECTRICAL LOADS (VOLTAGE, PHASE, CONNECTION REQUIREMENTS, ETC) OF ALL EQUIPMENT FURNISHED UNDER ALL DIVISIONS, INCLUDING ALL EXISTING EQUIPMENT TO BE RE-USED.
REVIEW ALL SHOP DRAWINGS AND EXISTING EQUIPMENT BEFORE BEGINNING ROUGH-IN.
4. SEE SECTION 265100 (16510) OF THE SPECIFICATION FOR REQUIRED COORDINATION MEETINGS WITH
MECHANICAL AND CEILING CONTRACTORS.
5. SEE APPLICABLE SHOP DRAWINGS FOR ROUGH IN LOCATION OF ALL EQUIPMENT, WIRING DEVICES, ETC.
WHERE APPLICABLE MOUNT ALL WIRING DEVICES ABOVE BACK SPLASH EXCEPT THOSE SERVING UNDER
COUNTER EQUIPMENT.
6. SEE SPECIFICATION FOR ENERGY SAVING LAMP AND BALLAST REQUIREMENTS.
7. FINISHES OF ALL LIGHT FIXTURES SHALL BE AS SELECTED BY ARCHITECT.
8. THE ELECTRICAL CONTRACTOR SHALL NOTIFY AND COOPERATE WITH THE MECHANICAL CONTRACTOR SUCH THAT NO PIPING, DUCTS, OR EQUIPMENT FOREIGN TO THE OPERATION OF THE ELECTRICAL EQUIPMENT SHALL BE PERMITTED TO BE INSTALLED IN, ENTER OR PASS THRU ELECTRICAL ROOMS OR SPACES, OR ABOVE OR
BELOW ELECTRICAL EQUIPMENT IN OTHER AREAS.
9. ELECTRICAL BOXES SHALL NOT BE LOCATED IN MASONRY COLUMNS IN BRICK WALLS OR IN GROUTED CELLS
ADJACENT TO OPENINGS. COORDINATE LOCATION OF BOXES WITH MASONRY CONTRACTOR.
10. ALL PENETRATIONS OF FIRE RATED FLOORS, WALLS, AND CEILINGS SHALL BE SEALED WITH APPROVED
MATERIAL TO MAINTAIN FIRE RATING OF SURFACE PENETRATED.
11. CONTRACTOR SHALL VERIFY FURNITURE LAYOUT PRIOR TO ANY FLOORBOX OR POKE-THRU INSTALLATION.
COORDINATE EXACT LOCATION OF FLOOR BOX OR POKE-THRU WITH OWNER AND FURNITURE PROVIDER PRIOR
TO ROUGH-IN.
12. CIRCUITS EXTENDING OVER 70' FOR 120 VOLT AND 115' FOR 277 VOLT 20 AMP CIRCUITS SHALL BE RUN WITH
CONDUCTORS PER TABLE BELOW.
A. THESE ARE BASED ON MAXIMUM LENGTH OF CIRCUIT.
B. PERFORM VOLTAGE DROP CALCULATIONS AND PROVIDE CONDUCTOR SIZE TO KEEP
BRANCH CIRCUIT VOLTAGE DROP LESS THAN 3% WITH A 15 AMP LOAD.
C. CONTRACTOR SHALL ENSURE THAT THE INSTALLATION OF EACH BRANCH CIRCUIT STAYS
WITHIN 3% VOLTAGE DROP FOR A 15 AMP LOAD. IF NECESSARY,CONTRACTOR SHALL
INCREASE WIRE AND CONDUIT SIZE TO MEET THE STANDARD AT NO ADDITIONAL COST TO
OWNER.
MAXIMUM LENGTH
20 AMP MINIMUM BRANCH CIRCUIT CONDUCTOR SIZING
BRANCH CIRCUIT VOLTAGE
CONDUCTOR LENGTH (FT) 120 VOLT 277 VOLT
<70 MIN. #12 AWG
70 - 115
115 - 170
170 - 270
271 - 380
>380
MIN. #12 AWG
MIN. #10 AWG MIN. #12 AWG
MIN. #8 AWG MIN. #10 AWG
MIN. #6 AWG MIN. #8 AWG
NOTE B MIN. #8 AWG
NOTE B NOTE B
ABBREV. DESCRIPTION ABBREV. DESCRIPTION
ABBREVIATIONS INDEX
# NUMBER
AC ALTERNATING CURRENT
A.F.F. ABOVE FINISH FLOOR
AIC AMPS INTERRUPTING CAPACITY
AM AMPS METER
AMP AMPERE
ANN ANNUNCIATOR
ATS AUTOMATIC TRANSFER SWITCH
AUX AUXILIARY
AWG AMERICAN WIRE GAUGE
BC BARE COPPER
BFG BELOW FINISH GRADE
C CONDUIT
CAB CABINET
CATB COMMUNITY ANTENNA TELEVISION
CATV CABLE TELEVISION
CKT CIRCUIT
CLG CEILING
CNTR CONTRACTOR
C.O. CONDUIT ONLY
CRT COMPUTER TERMINAL
CT CURRENT TRANSFORMER
CU COPPER
C/W COMPLETE WITH
DB DECIBEL
DC DIRECT CURRENT
DWG DRAWING
(E) EXISTING
EC EMPTY CONDUIT
EG EMERGENCY GENERATOR
EMT ELECTRICAL METALLIC TUBING
EX EXPLOSION PROOF
FACP FIRE ALARM CONTROL PANEL
FC FOOT CANDLE
FT FOOT
GFI GROUND FAULT INTERRUPTER
GND GROUND
GRC GALVANIZED RIGID CONDUIT
HP HORSE POWER
HZ HERTZ
IG ISOLATED GROUND
IMC INTERMEDIATE METALLIC CONDUIT
IN INCH
J-BOX JUNCTION BOX
KV KILOVOLT
KVA KILOVOLT AMPERES
KVAR KILOVARS
KW KILOWATT
LRA LOCKED ROTOR AMPS
LTG LIGHTING
MNF MANUFACTURER
MAX MAXIMUM
MB MAIN BUS
MCC MOTOR CONTROL CENTER
MCM 1000 CIRCULAR MILLS
MH MANHOLE
MIC MICROPHONE
MIN MINIMUM
MTG MOUNTING
MTR MOTOR
N/A NOT APPLICABLE
NC NORMALLY CLOSED
NEC NATIONAL ELECTRICAL CODE
NEMA NATIONAL ELECT. MANUFAC. ASSOC.
IFC INTERNATIONAL FIRE CODE
NFPA NATIONAL FIRE PROTECTION ASSOC.
N.I.C. NOT IN CONTRACT
NO NORMALLY OPENED
NTS NOT TO SCALE
OS & Y OUTSIDE SCREW & YOKE
PB PUSHBUTTON
PF POWER FACTOR
PFR PHASE FAILURE RELAY
PNL PANEL
PT POTENTIAL TRANSFORMER
PVC POLYVINYL CHLORIDE CONDUIT
(R) RELOCATE
RECEP RECEPTACLE
REQ REQUIREMENT
RLA RATED LOAD AMPS
RMS ROOT MEAN SQUARE
SE SERVICE ENTRANCE
SPEC SPECIFICATIONS
SPKR SPEAKER
SS SELECTOR SWITCH
SW SWITCH
SWBD SWITCHBOARD
SWGR SWITCHGEAR
TTB TELEPHONE TERMINAL BOARD
TTC TELEPHONE TERMINAL CABINET
TV TELEVISION
TYP TYPICAL
UG UNDERGROUND
RMP ROCKY MOUNTAIN POWER
UPS UNINTERRUPTED POWER SUPPLY
V VOLT (KV-KILOVOLT)
VA/R VOLT-AMPS/REACTIVE
VM VOLT METER
W WATTS
W/ WITH
WH WATTHOUR METER
W/O WITHOUT
WP WEATHERPROOF
XFMR TRANSFORMER
XFMR SW TRANSFER SWITCH
XP EXPLOSION PROOF
1P SINGLE-PHASE
2P TWO-POLE
3P THREE-POLE
4P FOUR-POLE
∅ PHASE
DEMOLITION NOTES
1. COORDINATE ALL NEW ELECTRICAL EQUIPMENT REQUIREMENTS AND MAKE CONNECTION TO EXISTING
SYSTEMS. THIS INCLUDES LIGHTING, POWER, SIGNAL, RACEWAY AND OTHER SYSTEMS INCLUDED UNDER
DIVISION 26 (16).
2. RELOCATE, REWIRE AND/OR RECONNECT EXISTING ELECTRICAL DEVICES AND/OR EQUIPMENT THAT FOR ANY
REASON OBSTRUCTS CONSTRUCTION.
3. CONCEAL ALL RACEWAY AND WIRING IN EXISTING WALLS, CEILINGS, FLOORS, ETC. EXCEPT WHERE THE USE OF
SURFACE METAL RACEWAYS (E.G. WIRE MOLD) IS INDICATED ON DRAWINGS OR IN SPEC.
4. LEAVE ALL EXISTING EQUIPMENT, IN PORTIONS OF THE BUILDING NOT BEING REMODELED, IN WORKING CONDITION. RESTORE ALL INTERRUPTED BRANCH CIRCUITS, FEEDERS, ETC. TO WORKING CONDITION.
5. EXISTING RACEWAYS MAY BE REUSED (IN PLACE) WHERE POSSIBLE, AND WHERE IN COMPLIANCE WITH THE SPECIFICATIONS AND THE INTENT OF THE CONTRACT DOCUMENTS. INSURE INTEGRITY OF EXISTING RACEWAY
BEFORE REUSE.
6. REMOVE ALL RACEWAYS, CONDUCTORS, BOXES, DEVICES, EQUIPMENT, ETC. THAT ARE NOT TO BE REUSED.
7. REMOVE EXISTING LIGHT FIXTURES WHICH ARE NOT TO BE REUSED, PLACE IN CARTON, LABEL APPROPRIATELY, AND RETURN TO OWNER, OR PROPERLY DISPOSE OF FIXTURES THAT THE OWNER CHOOSES NOT TO KEEP.
8. DO NOT PENETRATE STRUCTURAL ELEMENTS OF FLOORS, WALLS, CEILINGS, ROOFS, ETC.
9. DISCONNECT AND RECONNECT ANY/ALL FIXTURES, DEVICES, EQUIPMENT, ETC. REQUIRED FOR PROPER
COMPLETION OF THE WORK.
REVISIONS
MARK DATE DESCRIPTION
SYMBOL LEGEND GENERAL NOTES
1. SOLID BOX AROUND DEVICE INDICATES INSTALLED IN FLOOR. DASHED BOX AROUND DEVICE
INDICATES INSTALLED IN CEILING.
2. WALL DEVICES NOTED WITH A CHEVRON INDICATE TO COORDINATE WITH MILLWORK SHOP
DRAWINGS & ELEVATIONS FOR HEIGHT.
3. TYPICAL SYMBOL SCHEDULE. SOME SYMBOLS MAY NOT BE USED IN THIS SET OF DRAWINGS.
4. REFER TO LUMINAIRE SCHEDULE FOR FIXTURE TYPES, MOUNTING REQUIREMENTS, WATTAGE
& DETAILS.
5. WIRE LIGHT FIXTURE FROM ADJACENT JUNCTION BOX.
6. CONNECT NEAREST UN-SWITCHED HOT CONDUCTOR TO EMERGENCY BALLAST.
7. LIGHT FIXTURES ARE SCALED WITHIN THE DRAWINGS BASED ON ACTUAL DIMENSIONS.
8. REFER TO DRAWINGS FOR DIRECTIONAL ARROWS.
9. SUBSCRIPT INDICATES FIXTURES TO BE CONTROLLED.
10. HEIGHT MEASURED TO CENTER LINE OF THE BOX FROM THE FINISHED FLOOR.
11. HEIGHT MEASURED TO TOP OF THE BOX FROM FINISHED FLOOR.
12. NEMA TYPE 'ND' NON-FUSED UNLESS NOTED 'F' (FUSED). USE HEAVY DUTY (HD) DEVICE FOR
480 VOLT.
13. SIZE TO THE EQUIPMENT BEING CONTROLLED.
14. PROVIDE H.O.A. & S.S. PUSHBUTTONS AS REQUIRED.
15. DOUBLE ARROWS INDICATES A DOUBLE FACE UNIT.
16. FOR WATER COOLER LOCATION, REFER TO DIAGRAM R002. FOR ALL OTHER LOCATIONS,
MOUNT AT +16" TO BOTTOM OF BOX FROM FINISHED FLOOR, OR AS NOTED.
17. ARROWS SHOWN ON DEVICE INDICATE AIMING DIRECTION.
18. COORDINATE WITH DOOR HARDWARE SUPPLIER.
19. MOUNT ON TRACK OF OVERHEAD DOOR, 6" FROM TOP OF DOOR, UNLESS OVERHEAD DOOR IS
A ROLL UP DOOR, THEN MOUNT PER MANUFACTURER'S INSTRUCTIONS.
20. INSTALL DEVICES PER MANUFACTURER'S INSTALLATION INSTRUCTIONS.
21. DASHED LINE INDICATES EQUIPMENT CLEARANCES. ARROW INDICATES FRONT OF RACK.
22. HEIGHT MEASURED TO BOTTOM OF THE DEVICE FROM FINISHED FLOOR.
23. PROVIDE MUD RING &/OR BOX COVER APPROPRIATE FOR DEVICE/FIXTURE SERVED.
24. REFER TO DIAGRAMS, ELEVATIONS, & SCHEDULES FOR CUSTOM ROUGH-IN REQUIREMENTS.
25. ROUGH-IN TO BE HORIZONTAL.
26. REFER TO MANUFACTURER'S RECOMMENDED CABLE REQUIREMENTS FOR EXACT CABLE
REQUIRED.
27. FOLLOW BICSI STANDARDS FOR CABLE ROUTING & DISTANCES.
28. SUBSCRIPT INDICATES NEMA CONFIGURATION.
29. USE A 4" X 4" BOX WITH A MUD RING TO MATCH THE DEVICE & INSTALLATION.
30. USE WITH POWER PACK.
31. PROVIDE UL LISTED DEVICE COMPATIBLE WITH THE FIRE ALARM PANEL/SYSTEM.
32. CAMERA TYPES ARE INDICATED INSIDE THE CAMERA SYMBOL.
J J
IR
WAP
T
T
J
J
JJJJ
JJJ
WAP
T
T
11HLA SECTION 1 (EXISTING)
LIGHTING CABINET (EXISTING)
11HLA SECTION 2 (EXISTING)
'NP' (EXISTING)
E2
E2
D4
D3
E1
D4
E2
D1 D1
D2 D2
D7
BL24(E)
EXISTING FIELD LIGHTING OVERRIDE SWITCHES
D6
(E) DATA CABINET
D11
BL24(E)
(E) DATA CABINET
EXISTING (3) 1" CONDUITS
1 - SPARE
1 - DATA
1 - AV
EXISTING BASEBOARD HEATERS
EXISTING
BASEBOARD
HEATERS
EXISTING BASEBOARD HEATERS
D5
D5
D5
EXISTING TO BE
DEMOLISHED IN NEW
CONSTRUCTION
ALT 1
ALT 1
D8
ALT 1
ALT 1
THERMOSTAT (EXISTING) TO BE RELOCATED
D11 D10
REMOVE CONCRETE ENCASED JUNCTION BOX
REMOVE CONCRETE BASEPAD REMOVAL ALONG CONTROL JOINT
PAD REMOVAL ALONG CONTROL JOINT
REMOVE CONCRETE ENCASED JUNCTION BOX
REMOVE CONCRETE BASE
HICKS
BRIAN
No. 7709037-2202
G
IN
E E R
ONA
O F
E
SS
I
R
UT
AH
TE OF
S T A
P
L EN
PROJECT NO:
DRAWN BY:
CHK'D BY:
DATE:
T H
IS
P
R
IN
T
IS
IN
C
O L
O R
A
BCDEFGHIJKLMN
ABCDEFGHIJKLMN
S A
L T
L A
.G
E O
R G
E
02/19/26
CONSTRUCTION DOCUMENTS
/1
/2
:4 :0
P
M A u to d e s k D o c s /2
J
S D
B in g h a m
H S
F o o tb a ll
F ie ld S p o rt s /2
J S
D B in g h a m
H S
F o o tb a ll
F ie ld S p o rt s U p g ra d e
E L E
C v
.r v t
2/19/26
250864
BR
RESOLUT
ELECTRICAL
DEMOLITION
PLAN
E1.2
J O
R D
A N
S C
H O
O L
D
IS
T R
IC
T
W S o u th J o rd a n
P k w y S o u th J o rd a n
U T
F O
O T
B A
L L F
IE
L D
L
IG
H T
IN
G
/S O
U N
D U
P G
R A
D E
JO
R
D A
N S
C H
O O
L D
IS
T
R
IC
T
SCALE = 1" = 30'-0"
ELECTRICAL DEMOLITION PLAN
KEYNOTES
D1 EXISTING STADIUM LIGHT FIXTURES AND POLE TO BE DEMOLISHED. PULL BACK EXISTING WIRE
AND CONDUIT FROM POLE TO EXISTING CONCRETE ENCASED JUNCTION BOX FOR FUTURE
REUSE.
D2 CONTRACTOR SHALL DEMOLISH EXISTING CONCRETE PAD, CONCRETE ENCASED JUNCTION
BOX, AND CONCRETE POLE BASE. CONCRETE PAD REMOVAL SHALL BE DONE ALONG CONTROL
JOINTS AS HIGHLIGHTED IN IMAGE ABOVE. REMOVE AND REINSTALL PORTIONS OF RAMP AND
BLEACHERS AS REQUIRED TO FACILITATE THE REMOVAL OF THE CONCRETE PAD. PROTECT
EXISTING CONDUIT AND WIRING.
D3 EXISTING LIGHTING CABINET IS TO REMAIN. NO MODIFICATIONS, RELOCATION, OR
REPLACEMENT OF THE EXISTING LIGHTING CABINET IS INCLUDED IN THE SCOPE OF WORK
UNLESS SPECIFICALLY NOTED OTHERWISE. CONTRACTOR SHALL PROTECT EXISTING
EQUIPMENT DURING CONSTRUCTION AND MAINTAIN FULL OPERATIONAL STATUS THROUGHOUT
THE PROJECT DURATION.
D4 EXISTING STADIUM LIGHT FIXTURES TO BE DEMOLISHED. POLE TO REMAIN FOR REUSE.
EXISTING WIRE IS TO BE PULLED BACK AS NEEDED DURING CONSTRUCTION AND PROTECTED
FOR FUTURE REUSE. REFER TO E1.2 FOR NEW REQUIREMENTS.
D5 ALT 1: EXISTING BASEBOARD HEATERS TO BE DEMOLISHED. DISCONNECT AND REMOVE
EXISTING BASEBOARD HEATERS. DISCONNECT AND PULL BACK ALL ASSOCIATED CONDUIT AND
WIRING BACK TO THE SERVING PANEL. REMOVE UNUSED CONDUCTORS. PROVIDE BREAKER
BLANKS AS REQUIRED FOR ALL ABANDONED CIRCUITS AND UPDATE PANEL SCHEDULES TO
REFLECT REVISED LOADS AND CIRCUIT CONFIGURATION. PATCH & REPAIR ALL AFFECTED WALL
FINISHES AS REQUIRED.
D6 EXISTING FIELD LIGHT SWITCHES TO REMAIN.
D7 ALTERNATE 2: IF A LIGHTING MANUFACTURER OTHER THAN EPHESUS IS UTILIZED, REMOVE
EXISTING LIGHTING CONTACTORS AND REWORK LIGHTING CONTROLS AND POWER
DISTRIBUTION AS SHOWN IN THE APPROVED LIGHTING SHOP DRAWINGS. ALL MODIFICATIONS
SHALL BE COORDINATED WITH THE LIGHTING MANUFACTURER AND SHALL MAINTAIN
COMPLIANCE WITH APPLICABLE CODES AND DESIGN INTENT.
D8 DEMOLISH AND REMOVE FROM THE PROJECT SITE THE EXISTING PANELBOARD “BL24.â€
FIELD VERIFY MAIN BREAKER LOCATION PRIOR TO COMMENCING DEMOLITION. PULL BACK,
SECURE, AND PROTECT EXISTING FEEDER AND BRANCH CIRCUITS ORIGINATING FROM OR
ROUTED TO PANELBOARD “BL24.†CIRCUITS SHALL BE CAREFULLY IDENTIFIED, DISCONNECTED, AND RETRACTED TO A SAFE LOCATION DURING CONSTRUCTION ACTIVITIES.
CONDUCTORS SHALL BE CAPPED, TAGGED, AND PHYSICALLY PROTECTED TO PREVENT
DAMAGE, ENERGIZATION, OR INTERFERENCE WITH OTHER TRADES.
D10 ALT 1: REMOVE EXISTING THERMOSTAT BACK TO ITS COURSE. PATCH AND REPAIR ALL
DAMAGED WALL AND CEILING FINISHES AS NEEDED. ENSURE FINISHES MATCH EXISTING
TEXTURE AND PAINT.
D11 EXISTING THERMOSTAT TO BE RELOCATED. EXTEND EXISTING CABLING AND CONDUIT AS
NEEDED TO NEW LOCATION SHOWN IN SHEET 'E2' FOR NEW LOCATION.
E1 EXISTING DISTRIBUTION PANELS AND FIELD LIGHTING CONTACTORS ARE APPROXIMATE
LOCATIONS IN FIELD HOUSE STORAGE ROOM LOCATED WITHIN THE BUILDING.
E2 EXISTING LIGHT POLE TO REMAIN. PROTECT IN PLACE.
1/4" = 1'-0"
PRESS BOX LIGHTING DEMOLITION PLAN
1/4" = 1'-0"
PRESS BOX POWER DEMOLITION PLAN
J
J
J J
T
T
JJ
F F
J J
JJ
EXISTING (3) 1" CONDUITS
1 - SPARE
1 - DATA
1 - AV
(E) DATA CABINET
EXISTING TELECOM ENCLOSURENEW 240/120V I00A
24 SPACE PANEL
E14
E13
ALT 1
B L2
4-
B L2
4-
B L2
4-
E13
ALT 1
BL24
B L2
4-
B L2
4-
NEW THERMOSTAT LOCATION
WP
WPWP
WP
BL24- 13,15
SSO-1
ALT 1
E12 E12
ALT 1
BL24- 17,19
SSO-2BL24-18 BL24-16
HEAT TRACEHEAT TRACE
WP WP
11HLA SECTION 1 (EXISTING)
MAIN LIGHTING CONTROLLER
11HLA SECTION 2 (EXISTING)
'NP' (EXISTING)
E2
E2
E2
E8 E8
E5
E7 E7
E5
E4 E4
E9
E10
C003
E3
L003
E3
C003
E3
L003
E3
ALT2
TA2
E6
E6
HICKS
BRIAN
No. 7709037-2202
G
IN
E E R
ONA
O F
E
SS
I
R
UT
AH
TE OF
S T A
P
L EN
PROJECT NO:
DRAWN BY:
CHK'D BY:
DATE:
T H
IS
P
R
IN
T
IS
IN
C
O L
O R
A
BCDEFGHIJKLMN
ABCDEFGHIJKLMN
S A
L T
L A
.G
E O
R G
E
02/19/26
CONSTRUCTION DOCUMENTS
/1
/2
:4 :0
P
M A u to d e s k D o c s /2
J
S D
B in g h a m
H S
F o o tb a ll
F ie ld S p o rt s /2
J S
D B in g h a m
H S
F o o tb a ll
F ie ld S p o rt s U p g ra d e
E L E
C v
.r v t
2/19/26
250864
BR
RESOLUT
ELECTRICAL
PLAN
E2
J O
R D
A N
S C
H O
O L
D
IS
T R
IC
T
W S o u th J o rd a n
P k w y S o u th J o rd a n
U T
F O
O T
B A
L L F
IE
L D
L
IG
H T
IN
G
/S O
U N
D U
P G
R A
D E
JO
R
D A
N S
C H
O O
L D
IS
T
R
IC
T
GENERAL NOTES
1. DIVISION 26 SHALL VISIT THE SITE PRIOR TO BIDDING. BIDS SHALL SERVE AS EVIDENCE OF KNOWLEDGE OF EXISTING CONDITIONS. BIDDERS
SHALL EXAMINE THE SITE AND THE COMPLETE SET OF PLANS AND SPECIFICATIONS COVERING THE ENTIRE PROJECT. THEY SHALL BECAME
FULLY CONVERSANT WITH THE TYPE OF GENERAL CONSTRUCTIONS AS WELL AS ALL PERTINENT FACTS AFFECTING THE COST OF CARRYING
OUT THE WORK THEY WILL CONTRACT TO PERFORM. DIVISION 26 SHALL COORDINATE PROJECT PHASING WITH THE GENERAL CONTRACTOR
AND BID PERFORM RESPONSIBILITIES FOR THIS PROJECT TO CONTRACT EXPECTATIONS.
2. DIVISION 26 SHALL CONFIRM EXACT LOCATION OF EXISTING AND NEW EQUIPMENT WITH OWNERS. ROUGH-IN LOCATIONS ARE
DIAGRAMMATICALLY SHOWN ON THE DRAWINGS. EXISTING ELECTRICAL FIXTURES, DEVICES, EQUIPMENT, CIRCUITING AND/OR CONDITIONS
ARE NOT SPECIFIED UNLESS NOTED ON DRAWINGS. FINAL ROUTING OF THE CONDUITS, CIRCUITING, AND CABLING SHALL BE DETERMINED BY
THE CONTRACTOR AND CLOSELY COORDINATED WITH OWNER. ALL EXISTING CONDITIONS MUST BE VERIFIED WITHOUT EXCEPTION.
3. DIVISION 26 SHALL BLUE STAKE THE AREA OF NEW CONSTRUCTION PRIOR TO EXCAVATION FOR FOOTINGS, ETC. IDENTIFY BURIED ELECTRICAL
SYSTEMS (UTILITIES, POWER, COMMUNICATIONS, ETC.) AND COORDINATE LOCATIONS WITH THE GENERAL CONTRACTOR. IF EXISTING
ELECTRICAL SYSTEMS ARE DISTURBED (POWER, AUXILIARY, ETC.) ELECTRICAL CONTRACTOR SHALL MAKE NECESSARY REPAIRS (AS
APPROVED BY DISTRICT REPRESENTATIVE AS PART OF THIS CONTRACT.
4. CONTRACTOR TO CLOSELY COORDINATE ALL NEW AND EXISTING DEVICE LOCATIONS WITH CIVIL DRAWINGS. CONTRACTOR TO VERIFY ALL
FINAL GRADE REQUIREMENTS WITH CIVIL DRAWINGS.
5. COORDINATE DEMOLITION AND PROJECT PHASING REQUIREMENTS WITH THE ENTIRE CONSTRUCTION SET AND GENERAL CONTRACTOR.
PROVIDE SELECT DEMOLITION OF ELECTRICAL APPARATUSES IN AREAS SHOWN FOR DEMOLITION. MAKE DEMOLITION AREAS SAFE AS
REQUIRED. LEAVE ALL EXISTING EQUIPMENT IN PORTIONS OF THE BUILDING, SITE, AND CAMPUS NOT BEING REMODELED AND AREAS NOT YET
DEMOLISHED IN WORKING.
6. DURING DEMOLITION AND NEW CONSTRUCTION, THE CONTINUATION OF BUILDING SYSTEMS MAY BE NECESSARY. TRACE AND IDENTIFY
EXISTING ELECTRICAL SYSTEM (POWER, LIGHTING, FIRE ALARM AND SECURITY) WIRING IN AREAS PRIOR TO DEMOLITION. ELECTRICAL
CONTRACTOR SHALL DISCONNECT ALL NECESSARY EQUIPMENT TO MAKE IT SAFE FOR DEMOLITION. WHERE LIVE CIRCUITS OR FEEDERS PASS
THROUGH A REMODEL AREA, CONTRACTOR SHALL MAINTAIN ELECTRIC CONTINUITY TO AND PROTECT BRANCH CIRCUITS AND/OR FEEDERS
PASSING THROUGH. WHERE FEEDERS AND/OR BRANCH CIRCUITS FEED BOTH LOADS IN A REMODELED AREA AND OUTSIDE OF A REMODELED
AREA, CONTRACTOR SHALL DISCONNECT AND REMOVE PORTIONS OF THE ELECTRICAL BRANCH CIRCUITS AND/OR FEEDERS WITH-IN THE
REMODELED AREA AND RE-WORK BRANCH CIRCUITS AND/OR FEEDERS TO MAINTAIN ELECTRICAL CONTINUITY TO LOADS OUTSIDE OF THE
REMODELED AREA.
7. DEVICES AND EQUIPMENT TO BE DEMOLISHED SHALL BE REMOVED, INCLUDING ALL RELATED CONDUCTORS, RACEWAY, JUNCTION AND
SPLICE BOXES UP TO THE PANELBOARD/SWICTHBOARD. ALL CONDUITS AND BOXES THAT ARE SURFACE MOUNTED AND NO LONGER REQUIRE
ACTIVE CIRCUITS SHALL BE COMPLETELY REMOVED. DEVICES TO BE REMOVED ON DRY WALL OR PLASTER TYPE WALLS THAT ARE TO REMAIN
SHALL HAVE THE WALL SURFACE PATCHED TO MATCH THE EXISTING FINISH. THE CONTRACTOR SHALL IDENTIFY ALL DEMOLISHED AND
ABANDONED BRANCH CIRCUITS. THESE SHALL NE NOTED AS SPARE ON PANELBOARD SCHEDULES. THIS INCLUDES IDENTIFYING EXISTING
ABANDONED AND SPARE CIRCUITS THAT ARE CURRENTLY IDENTIFIED AS USED. THE CONTRACTOR SHALL FURNISH NEW TYPED DIRECTORIES
FOR ALL PANELBOARDS.
8. OWNER HAS THE RIGHT TO RETAIN ALL SALVAGEABLE MATERIAL. ANY MATERIAL THE OWNER CHOOSES NOT TO ACCEPT SHALL BE REMOVED
FROM THE SITE AND DISPOSED OF BY THE CONTRACTOR.
9. CLOSELY COORDINATE ANY REQUIRED POWER SHUTDOWNS WITH GENERAL. HEAD CUSTODIAN, AND OWNER.
10. TRENCHING AND BACKFILL: LOCATE AND PROTECT EXISTING UTILITIES AND OTHER UNDERGROUND WORK IN A MANNER WHICH WILL ENSURE
THAT NO DAMAGE OR SERVICE INTERRUPTIONS WILL RESULT FROM EXCAVATING AND BACKFILLING. PERFORM EXCAVATION IN A MANNER
WHICH PROJECTS WALLS, FOOTINGS, AND OTHER STRUCTURAL MEMBERS FROM BEING DISTURBED OR DAMAGED IN ANY WAY. BURIAL
DEPTHS MUST COMPLY WITH NEC SECTION 300-5 (OR STATE UTAH REQUIREMENTS, WHICHEVER IS MORE STRINGENT), UNLESS NOTED
OTHERWISE. PATCH AND REPAIR ROADS, PARKING AREAS, SIDEWALK, CURB, OTHER…