This document is a specification bulletin for S&C Manual PMH Pad-Mounted Gear for outdoor distribution at 14.4 kV and 25 kV voltage levels. The specification provides comprehensive technical details for manual pad-mounted gear with multiple model configurations (PMH-3 through PMH-19), including switch and fuse components, ratings, and optional features. Key technical specifications include 600-ampere external handle-operated Mini-Rupter Switches for three-pole live switching, 200-ampere hookstick-operated S&C Power Fuses with Uni-Rupter Interrupters for single-pole live switching, and enclosures meeting ANSI C57.12.28 standards. The gear offers various fuse types including SML-20, SML-4Z, and Fault Fiter Electronic Power Fuses, with options for different voltage ratings, ampere ranges, and specialized features like key interlocks, surge arresters, base spacers, and different finish colors. The document includes detailed dimensional drawings, connection diagrams, and comprehensive tables detailing product specifications, components, and ordering information for different models and configurations.
View the file
Other files
Show all 31
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
S&C Manual PMH Pad-Mounted Gear Outdoor Distribution (14.4 kV and 25 kV)
Specifications
September 9, 2024 © S&C Electric Company 2001–2024, all rights reserved Specification Bulletin 662A-31
Conditions of Sale STANDARD: The seller’s standard conditions of sale set forth in Price Sheet 150 apply, except as modified in the “Warranty Qualifications” section on page 3.
SPECIAL TO THIS PRODUCT:
INCLUSIONS: S&C Manual PMH Pad-Mounted Gear features directly operable accessible components.
Switches and fuses are clearly visible. Manual PMH models contain 600‑ampere external handle-operated Mini-Rupter® Switches for three-pole live switching of three-phase source circuits and 200‑ampere hookstick-operated S&C Power Fuses with Uni-Rupter® Interrupters for single-pole live switching of single-phase or three-phase load circuits. (These models offer a choice of S&C Type SML-20 and SML-4Z Power Fuses or Fault Fiter® Electronic Power Fuses. Fault Fiter Electronic Power Fuse mountings also accommodate a variety of single-barrel current-limiting fuses listed in Table 1 of S&C Information Bulletin 660-50.)
Enclosures meet the requirements of ANSI C57.12.28 (enclosure integrity). They are of free-standing, self-supporting construction—not for bolting directly to transformers—with provisions for cable entrance and exit through the bottom. Access to medium voltage is controlled by the Penta-Latch® Mechanism, which provides automatic door latching and permits padlocking only when the door is securely latched. The door can be opened only with a pentahead socket wrench or tool.
The enclosure roof is undercoated with an insulating “no-drip” compound. A resilient closed-cell gasket on the enclosure bottom flange protects the finish from being scratched during installation and isolates it from the alka linity of a concrete foundation. Enclosures are protected from corrosion by S&C’s olive green Ultradur® II Outdoor Finish.
A dual-purpose front barrier of fiberglass-reinforced polyester is provided for each switch and fuse. Where the National Electric Safety Code (ANSI Standard C2) applies, these barriers meet the requirements of Section 381G.
When the switch or fuse is in the Open position, this barrier can be inserted into the open gap to guard against inadvertent contact with live parts. Interphase and end barriers of the same material are provided with each switch and each set of fuses where required to achieve published BIL ratings. Additional barriers of fiberglass-reinforced polyester separate front and rear compartments and isolate the tie bus (where furnished).
Full-length steel barriers separate adjoining compart-ments (where applicable).
These PMH models are provided with a Grappler™ Handling Tool, if applicable; an instruction manual holder; and storage racks in the fuse-compartment doors for spare S&C Fuse Units or Refill Units and for the Grappler tool (storage for Fault Fiter Electronic Power Fuses or current-limiting fuses cannot be provided in these racks). A folding switch-operating handle, secured inside the switch-operating-hub pocket, is provided for each Mini-Rupter Switch. Terminal pads can accommo date a variety of cable-terminating devices for cable sizes through 1000 kc mil for switch and bus terminals, 4/0 maximum for fuse terminals. Each switch, fuse, and bus terminal is provided with a ground stud as is each ground pad.
All terminal pads can accommodate a variety of cable-terminating devices for cable sizes through 1000 kc mil for switch terminals, 4/0 maximum for fuse terminals. The cable-terminating devices must be equipped either with an offset spade-type compression terminal for bolting directly to the terminal pad or with a rod-type compression terminal for attachment to a connector of the type shown in Table 17 on page 20.
For applications where additional height is desired
2 S&C Specification Bulletin 662A-31 .
for increased elevation of ungrounded parts above the mounting pad and to facilitate cable pulling and installa-tion of cable-terminating devices, particularly where no cable pit is used, base spacers are available as listed in Table 4 on page 9.
While the interior of S&C Pad-Mounted Gear is protected from direct exposure to the elements, it is inherently designed for an outdoor environment and requires selection and application of cable-terminating devices accordingly. Terminations must incorpo-rate adequate leakage distance between the exposed conductor and the stress-relief cone across a surface of nontracking material (or a surface rendered nontracking by properly taping with a suitable material).
Furthermore, to maintain the rated BIL, the following minimum clearances are required: 6 inches (152 mm) at
14.4 kV and 71/2 inches (191 mm) at 25 kV from energized parts to electrical ground; 1 inch (25 mm) at 14.4 kV and 21/4 inches (57 mm) at 25 kV from energized parts to fiber-glass-reinforced polyester barriers; 1/2‑inch (13 mm) at
14.4 kV and 11/4 inches (32 mm) at 25 kV from terminator skirts to fiberglass-reinforced polyester barriers.
EXCLUSIONS: Three-phase units listed in Table 3 on pages 6 through 8 do not include the items listed in Table 4 on page 9 through 13, nor do they include the connector, fuse components, switch blades, or acces-sories listed in Table 5, Table 6, and Table 7 on page 14, or Table 14, Table 15 and Table 17 on page 20.
SPECIFICATION DEVIATIONS: Features or modifica tions other than those listed in Table 4 on page 9 cannot be accommodated. Specifically, the following modifications or additions are not available except in custom-design gear or other standard models of S&C gear:
● Relocation of components (switches and fuses)
● Inclusion, in fuse compartments, of surge arresters or porcelain cable-terminating devices
● Separable insulated 200- or 600‑ampere connectors
● Intermediate- or station-class surge arresters
● Mechanical interlocks
Certain minor departures from the optional features can be accommodated. For example, the user may use mounting provisions for different porcelain cable terminators in a switch compartment and bus compart-ment. Such deviations can be accommodated by a “minor modification.” Contact the nearest S&C Sales Office for availability.
APPLICATION NOTES: For application information and a guide to the selection of appropriate ampere ratings and speeds of S&C SML Power Fuses, and types and TCC curve parameters of control modules for Fault Fiter Elec-tronic Power Fuses, contact the nearest S&C Sales Office.
Switching with a Uni-Rupter Interrupter Manual PMH Pad-Mounted Gear features fuses with Uni-Rupter Interrupters for single-pole live switching of single-phase or three-phase load circuits on distribution systems rated 14.4 kV or 25 kV.
Complete ratings and capabilities of S&C Power Fuses with Uni-Rupter Interrupters as applied in manual PMH Pad-Mounted Gear are shown in Table 1 on page 5. The Uni-Rupter Interrupter is also capable of carrying and interrupting load currents up to and including the emergency peak-load capabilities of the associated SML power fuses. In addition to the load-drop-ping capabilities shown, the Uni-Rupter Interrupter is capable of interrupting transformer magnetizing currents associated with the applicable loads as well as line-charging and cable-charging currents typical for distribution systems of these voltage ratings.
The duty-cycle fault-closing capabilities shown for S&C Power Fuses with Uni-Rupter Interrupters repre sent the fault-closing capabilities of the fuse with the Uni-Rupter Interrupter when the fuse is closed with a purposeful thrust without hesitation. Following the specified number of such closings (two or three), the Uni-Rupter Interrupter will remain operable and able to carry and interrupt rated current.
. S&C Specification Bulletin 662A-31 3
A Note on Single-Pole Switching In single-pole switching of ungrounded-primary three-phase transformers or banks (or a single-phase transformer connected line to line), circuit connec-tions or parameters may, in some cases, produce excessive overvoltages. In particular, for the following applications above 22 kV, single-pole switching by any means—including the Uni-Rupter Interrupter—should be performed only under the conditions stated in italics
● Switching unloaded or lightly loaded delta-con-nected or ungrounded-primary wye-wye connected three-phase transformers or banks (or line-to-line connected single-phase transformers), rated 150 kVA or less three-phase, or 50 kVA or less single-phase— or of any kVA rating when combined with unloaded cables or lines—where maximum system operating voltage exceeds 22 kV (Single-pole switching should be performed only if each phase is carrying 5% load or more, or if the transformer or bank is tempo-rarily grounded at the primary neutral during switching.)
● Switching loaded or unloaded ungrounded-primary wye-delta connected three-phase transformers or banks—alone or combined with unloaded cables or lines—where maximum system operating voltage exceeds 22 kV (Single-pole switching should be performed only if each phase is carrying 5% load or more and if the lighting-load phase is always switched open first (or switched closed last), or if the transformer or bank is temporarily grounded at the primary neutral during switching.)
Recommended Voltage Ratings of Current‑Limiting Fuses for Use in S&C Pad‑Mounted Gear In general, current-limiting fuses should have a maximum voltage rating equal to, but not greater than 140% of, the system line-to-line voltage because for most applications, the fuses can be exposed to full system line-to-line voltage in clearing faults. Although there may be economic or space-saving incentives for using current-limiting fuses with voltage ratings “appro-priate for system line-to-ground voltage” (i.e., fuses with a voltage rating lower than line-to-line voltage but greater than or equal to maximum system line-to-ground voltage), S&C can recommend such use only in any of the following applications:
● Protection of single-phase transformers serving single-phase loads
● Protection of three-phase lateral circuits fed by a single-conductor shielded cable (provided each transformer on that lateral is individually fused so the current-limiting fuse serving the lateral will not be required to clear secondary faults)
● Protection of single-phase lateral circuits fed by a single-conductor shielded cable where the load is line-to-ground connected
Switching with a Mini-Rupter Switch Manual PMH Pad-Mounted Gear features Mini-Rupter Switches for three-pole live switching of three-phase circuits.
Complete ratings for Mini-Rupter Switches as applied in manual PMH Pad-Mounted Gear are shown in Table 2 on page 5. In addition to the load-dropping ratings shown, a Mini-Rupter Switch is capable of interrupting transformer magnetizing currents associated with the applicable loads as well as line-charging and cable-charging currents typical for distribution systems of these voltage ratings.
For applications on systems rated higher than 7.2 kV and involving load current with high harmonic content (such as rectifier load currents), refer to the nearest S&C Sales Office. The two-time duty-cycle fault-closing ratings shown for Mini-Rupter Switches define the ability to close the Mini-Rupter Switch twice against a three-phase fault with asymmetrical current in at least one phase equal to the rated value, with the switch remaining operable and able to carry and interrupt rated current.
WARRANTY QUALIFICATIONS: The standard warranty contained in the seller’s standard conditions of sale (as set forth in Price Sheet 150) does not apply to manual PMH Pad-Mounted Gear where fuse units, fuse unit end-fittings, holders, refill units, or switch blades of other than S&C manufacture are used in conjunction with S&C SML Mountings. Nor does it apply to manual PMH Pad-Mounted Gear where other than Fault Fiter Electronic Power Fuses, S&C Switch Blades, or the current-limiting fuses listed in Table 1 of S&C Informa-tion Bulletin 660-50 are used in conjunction with Fault Fiter Electronic Power Fuse mountings and S&C Holders designed therefor, or when current-limiting fuses are applied other than as set forth in the “Recommended Voltage Ratings of Current-Limiting Fuses for Use in S&C Pad-Mounted Gear” section.
4 S&C Specification Bulletin 662A-31 .
How to Order Complete the following steps for a typical order of manual PMH Pad-Mounted Gear:
Step 1. Select the three-phase pad-mounted gear.
(a) Obtain the catalog number of the desired unit from Table 3 on pages 6 through 8.
Catalog Number:
(b) Add suffix designations (to the catalog number above) to indicate the optional features desired, selected from Table 4 on pages 9 through 13.
Suffix: –
(c) Obtain the catalog number of the connector, accessories, and touch-up kit components from Table 15, Table 16, and Table 17 on page 20.
Catalog Number: –
Step 2. Select the fuse components and switch blades
(a) For SML-20 Power Fuses: Obtain the catalog number of the end-fittings and the fuse units from Table 5 on page 14, taking care to match the voltage rating of the end fittings to the fuse units.
Catalog Number:
(b) For SML-4Z Power Fuses: Obtain the catalog number of the holder and refill units from Table 6 on page 14, taking care to match the voltage rating of the holder to the refill units.
Catalog Number:
(c) For Fault Fiter Electronic Power
Fuses: Obtain the catalog number for the holders, the interrupting modules, and the control modules from Table 7 on page 14, taking care to match the voltage rating of the holders, interrupting modules, and the control modules.
Catalog Number:
(d) For switch blades: Obtain the catalog number for the switch blades from Table 14 on page 20.
Catalog Number:
Example: The catalog number of a 14.4‑kV manual Model PMH-9 with SML-20 Mountings, optional cable guides for switches and fuses, and 10‑kV metal-oxide surge arresters at all switch terminals is:.
Catalog Number:
5 5 1 5 2 R 4 – M 2 M 3 N 7
. S&C Specification Bulletin 662A-31 5
Table 1. Ratings and Capabilities for S&C Power Fuses With Uni-Rupter Interrupters
Fuse Type
Voltage, kV Current, Amperes, RMS
Nom. Max BIL Max Interr. (Sym.)
Live Switching
Load Splitting (Parallel or Loop
Switching) Load Dropping
Duty-Cycle Fault-Closing
RMS, Sym.
SML-20
14.4 17 95 200E or 200K 14 000 200 200 14 000 ●
25 27 125 200E or 200K 12 500 200 200 12 500■
SML-4Z
14.4 17 95 200E 12 500 200 200 12 500●
25 27 125 200E 12 500▲ 200 200 12 500■
Fault Fiter fuse
14.4 17 95 200 14 000 200 200 14 000●
25 29 125 200 12 500 200 200 12 500■
| ● | Three-time duty-cycle fault-closing capability |
| ■ | Two-time duty-cycle fault-closing capability |
▲ Applicable to solidly ground-neutral systems only, with fuses connected by single-conductor, concentric-neutral-type cable to a trans-former or transformers. Rating is 9,400 amperes, RMS, symmetrical for all other applications.
Table 2. Ratings for Mini-Rupter Switches
Voltage, kV Current, Amperes
Nom. Max BIL Cont.
Live Switching Three-Time Duty-Cycle Fault-Closing Short-Circuit
Load-Splitting (Parallel or Loop
Switching)
Load Dropping
Peak RMS, Sym.
Peak
Withstand, Peak
One-Second Short Time Withstand, RMS, Sym.
14.4 17.5 95 600 600 600 36 400 14 000 36 400 14 000
25 29 125 600 600 600 32 500 12 500 32 500 12 500
6 S&C Specification Bulletin 662A-31 .
Table 3. Three-Phase Units (Including mountings with Uni-Rupter Interrupters—less fuse components①)
Model Connection Diagram②
Fuse Type
Ratings③
Catalog Number
Net Wt., Lbs.
Page Refer-ence for
Dimen-sional Infor-mation kV Amperes, RMS Short-Circuit
Nom. Max BIL
Fuse with Uni-Rupter Interrupter
Mini-Rupter Switch Amperes, RMS, Sym.
MVA
3-Phase Sym. at Rated
VoltageMax Load
Dropping Cont.
Load Dropping
PMH-3 —
14.4 17 95 — — 600 600 14 000 350 55232R3 650
25 29 125 — — 600 600 12 500 540 55233R3 950
PMH-4●
SML-20
14.4 17 95 200E■ 200 — — 14 000 350 55102R3 525
25 27 125 200E■ 200 — — 12 500 540 55103R3 675
SML-4Z
14.4 17 95 200E 200 — — 12 500 310 55302R3 525
25 27 125 200E 200 — — 12 500▲ 540▲ 55303R3 675
Fault Fiter
Fuse④
14.4 17 95 200 200 — — 14 000 350 55502R3 525
25 29 125 200 200 — — 12 500 540 55503R3 675
PMH-5◆
SML-20
14.4 17 95 200E■ 200 600 600 14 000 350 55112R3 825
25 27 125 200E■ 200 600 600 12 500 540 55113R3 1150
SML-4Z
14.4 17 95 200E 200 600 600 12 500 310 55312R3 825
25 27 125 200E 200 600 600 12 500▲ 540▲ 55313R3 1150
Fault Fiter
Fuse④
14.4 17 95 200 200 600 600 14 000 350 55512R3 825
25 29 125 200 200 600 600 12 500 540 55513R3 1150
PMH-6◆
SML-20
14.4 17 95 200E■ 200 600 600 14 000 350 55122R4 1475
25 27 125 200E■ 200 600 600 12 500 540 55123R3 1975
SML-4Z
14.4 17 95 200E 200 600 600 12 500 310 55322R4 1475
25 27 125 200E 200 600 600 12 500▲ 540▲ 55323R3 1975
Fault Fiter
Fuse④
14.4 17 95 200 200 600 600 14 000 350 55522R4 1475
25 29 125 200 200 600 600 12 500 540 55523R3 1975
① Fuse components are to be ordered separately. Refer to Table 5, Table 6 and Table 7 on page 14,Table 8 on page 15, Table 9 on page 16,Table 10 on page 17, Table 11 and Table 12 on page 18, and Table 13 on page 19.
| ② | Compartment numbers appear in corners of each diagram. |
| ③ | The short-circuit ratings expressed in amperes, RMS, asymmet- |
rical are 1.6 times the symmetrical values listed. Fault-closing and/or momentary ratings of switches and bus, and fault-closing capabilities and interrupting ratings of fuses, equal or exceed these values. For complete live-switching (as well as momentary and one-second) ratings for Mini-Rupter Switches and complete live-switching capabilities of Uni-Rupter Interrupters as applied in manual PMH Pad-Mounted Gear, refer to the “Application Notes” section on page 2.
④ These models also accommodate selected current-limiting fuses in S&C Holders; refer to Table 1 of S&C Information Bulletin 660-50.
Maximum voltage and maximum ampere ratings as listed in that table apply when current-limiting fuses are used. Consult appropriate current-limiting fuse manufacturer for complete fuse ratings.
| ● | Available only when ultimate user is an electric utility. |
| ■ | SMU-20 Fuse Units are available in ratings through 200K amperes |
as well as 200E amperes.
▲ Applicable to solidly grounded-neutral systems only, with fuses connected by single-conductor, concentric-neutral-type cable to a transformer or transformers. Rating is 9400 amperes, RMS, symmetrical (405 MVA) for all other applications.
◆ Key interlocks (catalog number suffix “-C3” or “-C4”) are required for ultimate users other than electric utilities.
TABLE CONTINUED ▶
. S&C Specification Bulletin 662A-31 7
Table 3. Three-Phase Units (Including mountings with Uni-Rupter Interrupters—less fuse components①)— Continued
Model Connection Diagram②
Fuse Type
Ratings③
Catalog Number
Net Wt., Lbs.
Page Refer-ence for Dimen-sional
Informa-tion kV Amperes, RMS Short-Circuit
Nom. Max BIL
Fuse with Uni-Rupter Interrupter
Mini-Rupter Switch Amperes, RMS, Sym.
MVA
3-Phase Sym. at Rated
VoltageMax Load
Dropping Cont.
Load Dropping
PMH-7◆
SML-20
14.4 17 95 200E■ 200 600 600 14 000 350 55132R4 1400
25 27 125 200E■ 200 600 600 12 500 540 55133R3 1875
SML-4Z
14.4 17 95 200E 200 600 600 12 500 310 55332R4 1400
25 27 125 200E 200 600 600 12 500▲ 540▲ 55333R3 1875
Fault Fiter
Fuse④
14.4 17 95 200 200 600 600 14 000 350 55532R4 1400
25 29 125 200 200 600 600 12 500 540 55533R3 1875
PMH-8●
SML-20
14.4 17 95 200E■ 200 600 600 14 000 350 55142R4 1350
25 27 125 200E■ 200 600 600 12 500 540 55143R3 1900
SML-4Z
14.4 17 95 200E 200 600 600 12 500 310 55342R4 1350
25 27 125 200E 200 600 600 12 500▲ 540▲ 55343R3 1900
Fault Fiter
Fuse④
14.4 17 95 200 200 600 600 14 000 350 55542R4 1350
25 29 125 200 200 600 600 12 500 540 55543R3 1900
PMH-9◆
SML-20
14.4 17 95 200E■ 200 600 600 14 000 350 55152R4 1550
25 27 125 200E■ 200 600 600 12 500 540 55153R3 2050
SML-4Z
14.4 17 95 200E 200 600 600 12 500 310 55352R4 1550
25 27 125 200E 200 600 600 12 500▲ 540▲ 55353R3 2050
Fault Fiter
Fuse④
14.4 17 95 200 200 600 600 14 000 350 55552R4 1550
25 29 125 200 200 600 600 12 500 540 55553R3 2050
PMH-10 —
14.4 17 95 — — 600 600 14 000 350 55242R4 1725
25 29 125 — — 600 600 12 500 540 55243R3 2275
① Fuse components are to be ordered separately. Refer to Table 5, Table 6 on page 14 and Table 7 on page 14,Table 8 on page 15, Table 9 on page 16,Table 10 on page 17, Table 11 and Table 12 on page 18, and Table 13 on page 19.
| ② | Compartment numbers appear in corners of each diagram. |
| ③ | The short-circuit ratings expressed in amperes, RMS, asymmet- |
rical are 1.6 times the symmetrical values listed. Fault-closing and/or momentary ratings of switches and bus, and fault-closing capabilities and interrupting ratings of fuses, equal or exceed these values. For complete live-switching (as well as momentary and one-second) ratings for Mini-Rupter Switches and complete live-switching capabilities of Uni-Rupter Interrupters as applied in manual PMH Pad-Mounted Gear, refer to the “Application Notes” section on page 2.
④ These models also accommodate selected current-limiting fuses in S&C Holders; refer to Table 1 in S&C Information Bulletin 660-50.
Maximum voltage and maximum ampere ratings as listed in that table apply when current-limiting fuses are used. Consult appropriate current-limiting fuse manufacturer for complete fuse ratings.
| ● | Available only when ultimate user is an electric utility. |
| ■ | SMU-20 Fuse Units are available in ratings through 200K amperes |
as well as 200E amperes.
▲ Applicable to solidly grounded-neutral systems only, with fuses connected by single-conductor, concentric-neutral-type cable to a transformer or transformers. Rating is 9400 amperes, RMS, symmetrical (405 MVA) for all other applications.
◆ Key interlocks (catalog number suffix “-C3” or “-C4”) are required for
8 S&C Specification Bulletin 662A-31 .
Table 3. Three-Phase Units (Including mountings with Uni-Rupter Interrupters—less fuse components①)— Continued
Model Connection Diagram②
Fuse Type
Ratings③
Catalog Number
Net Wt., Lbs.
Page Refer-ence for Dimen-sional
Informa-tion kV Amperes, RMS Short-Circuit
Nom. Max BIL
Fuse with Uni-Rupter Interrupter
Mini-Rupter Switch Amperes, RMS, Sym.
MVA
3-Phase Sym. at Rated
VoltageMax Load
Dropping Cont.
Load Dropping
PMH-11◆
SML-20
14.4 17 95 200E■ 200 600 600 14 000 350 55162R4 1625
25 27 125 200E■ 200 600 600 12 500 540 55163R3 2175
SML-4Z
14.4 17 95 200E 200 600 600 12 500 310 55362R4 1625
25 27 125 200E 200 600 600 12 500▲ 540▲ 55363R3 2175
Fault Fiter
Fuse④
14.4 17 95 200 200 600 600 14 000 350 55562R4 1625
25 29 125 200 200 600 600 12 500 540 55563R3 2175
PMH-12◆
SML-20
14.4 17 95 200E■ 200 600 600 14 000 350 55172R4 1450
25 27 125 200E■ 200 600 600 12 500 540 55173R3 1950
SML-4Z
14.4 17 95 200E 200 600 600 12 500 310 55372R4 1450
25 27 125 200E 200 600 600 12 500▲ 540▲ 55373R3 1950
Fault Fiter
Fuse④
14.4 17 95 200 200 600 600 14 000 350 55572R4 1450
25 29 125 200 200 600 600 12 500 540 55573R3 1950
PMH-13 —
14.4 17 95 — — 600 600 14 000 350 55252R4 1525
25 29 125 — — 600 600 12 500 540 55253R3 2125
PMH-19◆
SML-20 14.4 17 95 200E■ 200 600 600 14 000 350 55212R4 1625
32SML-4Z 14.4 17 95 200E 200 600 600 12 500 310 55412R4 1625
Fault Fiter
Fuse④
14.4 17 95 200 200 600 600 14 000 350 55612R4 1625
① Fuse components are to be ordered separately. Refer to Table 5, Table 6 and Table 7 on page 14,Table 8 on page 15, Table 9 on page 16,Table 10 on page 17, Table 11 and Table 12 on page 18, and Table 13 on page 19.
| ② | Compartment numbers appear in corners of each diagram. |
| ③ | The short-circuit ratings expressed in amperes, RMS, asymmet- |
rical are 1.6 times the symmetrical values listed. Fault-closing and/or momentary ratings of switches and bus, and fault-closing capabilities and interrupting ratings of fuses, equal or exceed these values. For complete live-switching (as well as momentary and one-second) ratings for Mini-Rupter Switches and complete live-switching capabilities of Uni-Rupter Interrupters as applied in manual PMH Pad-Mounted Gear, refer to the “Application Notes” section on page 2.
④ These models also accommodate selected current-limiting fuses in S&C Holders; refer to Table 1 of S&C Information Bulletin 660-50.
Maximum voltage and maximum ampere ratings as listed in that table apply when current-limiting fuses are used. Consult appropriate current-limiting fuse manufacturer for complete fuse ratings.
| ● | Available only when ultimate user is an electric utility. |
| ■ | SMU-20 Fuse Units are available in ratings through 200K amperes |
as well as 200E amperes.
▲ Applicable to solidly grounded-neutral systems only, with fuses connected by single-conductor, concentric-neutral-type cable to a transformer or transformers. Rating is 9400 amperes, RMS, symmetrical (405 MVA) for all other applications.
◆ Key interlocks (catalog number suffix “-C3” or “-C4”) are required for
. S&C Specification Bulletin 662A-31 9
Table 4. Optional Features
Item Suffix to be Added to Pad-Mounted Gear
Catalog Number Applicable to Models
Light gray outdoor Ultradur II Outdoor Finish instead of olive green -A2 All models
Equipment green Ultradur II Outdoor Finish (Toronto standard) instead of olive green -A3 All models
Seafoam green Ultradur II Outdoor Finish instead of olive green -A4 All models
Special color Ultradur II Outdoor Finish instead of olive green -A5 All models
Stainless steel enclosure①
With olive green outdoor Ultradur II Outdoor Finish -A10 All models
With light gray outdoor Ultradur II Outdoor Finish -A12 All models
With special color outdoor Ultradur II Outdoor Finish -A15 All models
Hexhead actuator for use in lieu of pentahead actuator on all Penta-Latch Mechanisms
For use except when catalog number suffix “-F2” is specified -B1●■ All models
For use when catalog number suffix “‑F2” is also specified -B2▲■ All models except PMH-4
Copper bus② and copper switch terminals, fuse connector adapters, and bus terminals -B5 All models
Reinforced bus Used with standard aluminum bus -B6 15‑kV models of PMH-6, -7, -8, -9, -10, -11, 12, -13Used with optional copper bus -B7
Key interlocks to prevent paralleling of switches in compartments 1 and 2③ -C1 PMH-6, -9, -10, -11, -13, -19
Key interlocks to prevent opening fuse-compartment doors unless all switches (series tap switch only in PMH-19) are locked open③ -C3◆ PMH-5, -6, -7, -9, -11, -12, -19
Key interlocks. Combines functions of options “-C1” and “-C3” listed above③ -C4◆ PMH-6, -9, -11, -19
Fuse Storage feature for three spare fuse assemblies per compartment④
Located in compartment 1 -E1 PMH-5, -6, -7, -8, -9, -11, -19
Located in compartment 2 -E2 PMH-6, -7, -9, -11, -12, -19
Located in compartments 1 and 2 -E3 PMH-6, -7, -9, -11, -19
TABLE CONTINUED ▶
① When this optional feature is specified, the entire exterior of the enclosure is fabricated from 11-gauge Type 304 stainless steel. When specifying optional hexhead actuators, provisions for fault indicators with viewing windows in doors, or base spacer, specify the correct suffix for use in gear with a stainless steel enclosure.
| ② | Copper bus measures 1/4‑inch (6 mm) by 2 inches (51mm). |
| ③ | When specifying, please furnish name of ultimate user, station, and |
location of gear.
④ Fuse assemblies (fuse holders or fuse units with end fittings) are not included. For units equipped with Fault Fiter Electronic Power Fuse mountings, two spare Fault Fiter fuse interrupting modules, one spare
Fault Fiter Electronic Power Fuse holder, or one spare current-limiting fuse holder can be accommodated in each compartment.
● Specify catalog number suffix “-B11” for gear with stainless steel enclosure.
| ■ | Not available if UL listing (catalog number suffix “-X”) is specified. |
| ▲ | Specify catalog number suffix “-B12” for gear with stainless steel |
enclosure.
◆ Must be specified if end user is not an electric utility and/or if Canadian Standards Association listing (catalog number suffix “-Z”) is specified.
10 S&C Specification Bulletin 662A-31 .
Table 4. Optional Features—Continued
Item Suffix to be Added to Pad-Mounted Gear
Catalog Number Applicable to Models
Mounting provisions for a fault indicator in each switch compartment (except series tap switch in PMH-19)⑤
Without viewing window in door -F1 All models except PMH-4
With viewing window in door -F2▼□ All models except PMH-4
Inner barrier panels—a panel inside the enclosure door for each compartment, secured by recessed pentahead bolt(s)⑥⑦ -G7□ All models
Copper ground stud for each switch, fuse, or bus terminal and ground pad⑧
In fuse compartments⑨ -H2 All models except PMH-3, -10, -13
In switch and bus compartments -J2 All models except PMH-4
TABLE CONTINUED ▶
⑤ Accommodates three-phase indicator with single-phase sensors.
⑥ Where the National Electrical Safety Code (ANSI Standard C2) applies, this optional feature may be included to meet the requirements of Section 381G.
| ⑦ | Meets RUS’s requirements for “dead-front.” |
| ⑧ | Diameters of copper ground studs are as follows: |
| ⑨ | Including bus-compartment terminals in Model PMH-4. |
| ▼ | Specify catalog number suffix “-F12” for gear with stainless steel |
enclosure.
□ Not available if Canadian Standards Association listing (catalog number suffix “-Z”) is specified.
TABLE CONTINUED ▶
Ground Stud Switch Fuse Bus Terminal Ground Pad
Diameter, in inches (mm) 1/2 (13) 7/16 (11) 7/16 (11) 7/16 (11)
. S&C Specification Bulletin 662A-31 11
Table 4. Optional Features—Continued
Item Suffix to be Added to Pad-Mounted Gear
Catalog Number Applicable to Models
Base spacer, compartmented to match enclosure, increases cable-termination height
Carbon steel
6 inches (152 mm) -K1 All models
12 inches (305 mm) -K2 All models
18 inches (457 mm) -K3 All models
24 inches (610 mm) -K4 All models
Stainless steel
6 inches (152 mm) -K11 All models
12 inches (305 mm) -K12 All models
18 inches (457 mm) -K13 All models
24 inches (610 mm) -K14 All models
Base spacer, noncompartmented, increases cable-termination height
Carbon steel
6 inches (152 mm) -K7 All models
12 inches (305 mm) -K8 All models
18 inches (457 mm) -K9 All models
24 inches (610 mm) -K10 All models
Stainless steel
6 inches (152 mm) -K17 All models
12 inches (305 mm) -K18 All models
18 inches (457 mm) -K19 All models
24 inches (610 mm) -K20 All models
12 S&C Specification Bulletin 662A-31 .
Table 4. Optional Features—Continued
Item Suffix to be Added to Pad-Mounted Gear
Catalog Number Applicable to Models
International crating⑩ -L71 All models
Switch- and bus-terminal adapters—for connection of two cables (through 750 kc mil) per terminal⑪⑫
-M1 All models
Cable guides, one at each terminal⑪⑬
In switch and bus compartments.
For conductor sizes No. 2 through 1000 kc mil
-M2 All models
In fuse compartments. For conductor sizes No. 2 through 4/0 -M3
PMH-4, -5, -6, -11, -19
PMH-7, -8, -9
PMH-12
Polymer-housed metal-oxide surge arresters⑭, base-mounted, at switch termi-nals and bus terminals in compartments 1 and 2 (removed for shipment)
9 kV -N6△ All models
10 kV -N7△ All models
12 kV -N8 All models
15 kV -N9 All models
18 kV -N10◇ All models except PMH-19
Metal-oxide surge arresters,⑬ base-mounted, at switch terminals and bus terminals in compartments 1 and 2 (removed for shipment)
3 kV -N11▽ All models
6 kV -N12▽ All models
TABLE CONTINUED ▶
⑩ Wood products used in the packaging are either hardwood or certified by the wood supplier as being “heat treated (kiln dried) to a core temperature of 133°F (56°C) for a minimum of 30 minutes.”
⑪ When catalog number suffix “-M1” or “-M2” is specified, cable-termination options (catalog number suffix “-U2” and “-U3”) cannot be accommodated. In addition, when catalog number suffix “-M1” and “-M2” are both specified, only one cable guide is provided at each switch terminal.
⑫ Space limitations prevent use of these adapters where surge arresters are to be installed
⑬ These devices extend below the base of the unit. Provide a cable pit or specify a base spacer that provides a 12‑inch (305 mm) or greater increase in cable-termination height.
| ⑭ | Surge arresters are base-mounted only (without isolators). |
| △ | Not applicable to 25‑kV models. |
| ◇ | Not applicable to 14.4‑kV models. |
| ▽ | A supplemental label is provided for catalog number suffixes “-N11” |
and “-N12” indicating the voltage rating of the surge arresters furnished.
. S&C Specification Bulletin 662A-31 13
Table 4. Optional Features—Continued
Item Suffix to be Added to Pad-Mounted Gear
Catalog Number Applicable to Models
Mounting provisions for base-mounted surge arresters⑮, at switch terminals and bus terminals in compartments 1 and 2
9 kV, 10 kV, or 9/10 kV -P1△ All models
12 kV -P3 All models
15 kV -P4 All models
18 kV -P5◇ All models except PMH-19
Mounting provisions for porcelain cable terminators for single-conductor UD cable, at all cable-connected switch terminals and bus terminals
G&W PSC for No. 6 through 2/0◐, or G&W PAT for No. 4 through 250 kc mil copper or aluminum cable
-U2 All models
G&W PAT for 3/0 through 750 kc mil copper or 500 kc mil aluminum cable◐ -U3 All models
UL listing. Includes “UL listed” symbol on ratings label and nameplate -X◧◭ All 14.4 kV models
Canadian Standards Association listing. Includes viewing window with tamper-resistant cover in switch compartment door(s), and hazard-alerting labels and nameplate per CSA specification
-Z◀◁◑◧
PMH-3, -5, -7, -12
PMH-6, -9
PMH-11, -13, -19
PMH-10
⑮ These provisions accommodate Ohio Brass Type PDV (metal oxide), McGraw-Edison Type AZL19C (metal oxide), General Electric Tranquell® (metal oxide), or McGraw-Edison Type ES (silicon carbide) distribu-tion-class surge arresters. Surge arresters must be base-mounted only (without isolators).
◐ These devices extend below the base of the unit. Provide a cable pit or specify a base spacer.
| △ | Not applicable to 25‑kV models. |
| ◇ | Not applicable to 14.4‑kV models. |
| ◧ | UL listing (catalog number suffix“-X”) cannot be furnished if |
Canadian Standards Association listing (catalog number suffix “-Z”) is specified and vice versa.
◭ Not available if hexhead actuator for use in lieu of pentahead actuator on all Penta-Latch Mechanisms (catalog number suffix “-B1,” “-B2,” “-B11,” or “-B12”) is specified.
◀ Key interlocks (catalog number suffix “-C3” or “-C4”) must be speci-fied on gear with fuse compartment(s).
◁ Not available if mounting provisions for fault indicator with viewing window in switch compartment door(s) (catalog number suffix “-F2” or “-F12”) is specified.
◑ Not available if inner barrier panels (catalog number suffix “-G7) is specified.
14 S&C Specification Bulletin 662A-31 .
Table 5. SML-20 Power Fuse Components
Fuse-Unit End Fittings
Item Catalog Number
End-fittings (including silencer), for use with SMU-20 Fuse Units 3097
SMU-20® Fuse Units①
14.4 kV Nominal, 17 kV Max 25 kV Nominal, 27 kV Max
For a complete listing of available ampere ratings, speeds, and catalog numbers, refer to Table 8 on page 15 and Table 9 on page 16.
① These fuse units are usable in SM-20, SMD-20, SML-20, and SME-20 Mountings.
Table 6. SML-4Z Power Fuse Components
Holders
Item
Rating
Catalog NumberkV Amperes, MaxNom. Max
Holder (including silencer), for use with SM-4 Refill Units
14.4 17 200E 92352
25 27 200E 92353
SM-4® Refill Units①
14.4 kV Nominal, 17 kV Max 25 kV Nominal, 27 kV Max
For a complete listing of available ampere ratings, speeds, and catalog numbers, refer to Table 10 on page 17.
① These fuse units are usable in SM-4, SM-4Z, SML-4Z, and SME-4Z Mountings.
Table 7. Fault Fiter Electronic Power Fuse Components
Holders
Item
Rating
Catalog NumberkV Amperes, Cont.Nom. Max
Holder, for use with Fault Fiter Electronic Power Fuses
13.8 17 400 99412R1
25 29 200 99413R1
Interrupting Modules①
Item
Rating
Catalog NumberkV Amperes, Cont.Nom. Max
Interrupting module, for use with Fault Fiter Electronic Power Fuses
13.8 17 600 802600R2
25 29 600 803600R2
Control Modules①
For a complete listing of available types, TCC curve parameters, and catalog numbers, refer to Table 11 and Table 12 on page 18, and Table 13 on page 19.
① Interrupting modules and control modules rated 600 amperes contin-uous are also applicable for use in mountings rated 200 or 400 amperes continuous.
. S&C Specification Bulletin 662A-31 15
Table 8. SMU-20® Fuse Units (For use in SM-20 or SML-20 Mountings)①
14.4 kV Nominal, 17 kV Max
“K” Ratings “E” Ratings
Rating, Amperes
Catalog Number Rating, Amperes Catalog Number
Speed S&C “K”
TCC 165-2
Speed
S&C Std.
TCC 115-2
1 702001
Speed S&C Std.
TCC 153-2
S&C Slow
TCC 119-2
S&C Very Slow
TCC 176-2
3K 702003
6K 702006 5E 612005
8K 702008 7E 612007
10K 702010 10E 612010
12K 702012 13E 612013
15K 702015 15E 612015 712015
20K 702020 20E 612020 712020
25K 702025 25E 612025 712025
30K 702030 30E 612030 712030
40K 702040 40E 612040 712040
50K 702050 50E 612050 712050 602050
65K 702065 65E 612065 712065 602065
80K 702080 80E 612080 712080 602080
100K 702100 100E 612100 712100 602100
140K 702140 125E 612125 712125 602125
200K 702200 150E 612150 712150 602150
175E 612175 712175 602175
200E 612200 712200 602200
① These fuse units are equally suitable for use in SMD-20 Outdoor Distribution Mountings and for use with SME-20 Fuse Unit End-Fit-tings listed in S&C Specification Bulletin 665-31, “S&C Manual PME Pad-Mounted Gear” and in S&C Specification Bulletin 666-31, “S&C Remote Supervisory PME Pad-Mounted Gear.”
16 S&C Specification Bulletin 662A-31 .
Table 9. SMU-20® Fuse Units (For use in SM-20 or SML-20 Mountings)①
25 kV Nominal, 27 kV Max②
“K” Ratings “E” Ratings
Rating, Amperes
Catalog Number Rating, Amperes Catalog Number
Speed S&C “K”
TCC 165-2
Speed
S&C Std.
TCC 115-2
1 703001
Speed S&C Std.
TCC 153-2
S&C Slow
TCC 119-2
S&C Very Slow
TCC 176-2
3K 703003
6K 703006 5E 613005
8K 703008 7E 613007
10K 703010 10E 613010
12K 703012 13E 613013
15K 703015 15E 613015 713015
20K 703020 20E 613020 713020
25K 703025 25E 613025 713025
30K 703030 30E 613030 713030
40K 703040 40E 613040 713040
50K 703050 50E 613050 713050 603050
65K 703065 65E 613065 713065 603065
80K 703080 80E 613080 713080 603080
100K 703100 100E 613100 713100 603100
140K 703140 125E 613125 713125 603125
200K 703200 150E 613150 713150 603150
175E 613175 713175 603175
200E 613200 713200 603200
① These fuse units are equally suitable for use in SMD-20 Outdoor Distribution Mountings and for use with SME-20 Fuse Unit End-Fit-tings listed in S&C Specification Bulletin 665-31, “S&C Manual PME Pad-Mounted Gear” and in S&C Specification Bulletin 666-31, “S&C Remote Supervisory PME Pad-Mounted Gear.”
② Also suitable for protection of single-phase-to-neutral circuits (lines or transformers) on 20/34.5 GrY-kV systems.
. S&C Specification Bulletin 662A-31 17
Table 10. SM-4® Refill Units (For use in SM-4 and SML-4 Holders)①
Rating, Amperes
14.4 kV Nominal, 17 kV Max② 25 kV Nominal, 27 kV Max
Catalog Number Catalog Number
Speed S&C Std.
TCC 115-4
S&C Std.
TCC 115-4
1 122001R4 123001R4
2 122002R4 123002R4
Speed S&C Std.
TCC 153-4
S&C Slow
TCC 119-4
S&C Coord.
TCC 179-4
S&C Std.
TCC 153-4
S&C Slow
TCC 119-4
3E 122005R4 123005R4
5E 122007R4 123007R4
7E 122010R4 123010R4
10E 122015R4 123015R4
13E 122020R4 123020R4
15E 122025R4 252025R4 123025R4 253025R4
20E 122030R4 252030R4 123030R4 253030R4
25E 122040R4 252040R4 123040R4 253040R4
30E 122050R4 252050R4 123050R4 253050R4
40E 122060R4 252060R4 123060R4 253060R4
50E 122075R4 252075R4 123075R4 253075R4
65E 122100R4 252100R4 123100R4 253100R4
80E 122125R4 252125R4 123125R4 253125R4
100E 122150R4 252150R4 123150R4 253150R4
125E 122200R4 252200R4 123200R4 253200R4
150E 122250R4 252250R4 123250R4 253250R4
175E 122275R4 252275R4 123275R4 253275R4
200E 122300R4 252300R4 123300R4 253300R4
210E 382210R4●
① These refill units are also suitable for use with SME-4Z Holders listed in S&C Specification Bulletin 665-31, “S&C Manual PME Pad-Mounted Gear” and in S&C Specification Bulletin 666-31, “S&C Remote Supervi-sory PME Pad-Mounted Gear.”
② Rated 14.4 kV nominal, for use in SM-4 Holders rated 14.4 kV when applied in listed mountings rated 13.8 kV or in discontinued mountings rated 14.4 kV.
● This S&C Coordinating Speed refill unit should be applied where the maximum continuous load current does not exceed 200 amperes and where all fault currents below 1000 amperes will be cleared by another fuse.
18 S&C Specification Bulletin 662A-31 .
Table 11. Fault Fiter Fuse Control Modules—Underground Subloop① Type (TCC No. 422-7)
Continuous Current, Amperes, Max②
TCC Curve Parameters
Catalog NumberMinimum Pickup, Amperes, RMS
Short-Time Pickup, Amperes, RMS
Short-Time Delay Band
Instantaneous Pickup, Amperes, RMS
400 1300 2 3000 7020-C40P130S2T3
500 1300 1 3000 7020-C50P130S1T3
① This control module is applicable for protection of 15‑kV and 25‑kV class underground distribution subloops having the following parameters: maximum available fault current—14,000 amperes, RMS, symmetrical at 15 kV, 12,500 amperes, RMS, symmetrical at 25 kV;
maximum rated transformer kVA connected for residential circuits— 1200 kVA single-phase, 3600 kVA three-phase at 15 kV, 2400 kVA single-phase, 7200 kVA three-phase at 25 kV; with no capacitor banks or current-limiting fuses on the load side of the Fault Fiter fuse. If the maximum rated transformer kVA connected is greater than the values listed above, or if the application involves protection of circuits serving industrial, commercial, or institutional loads, contact the nearest S&C Sales Office.
② Control modules rated 600 amperes continuous are also applicable for use in mountings rated 200 amperes or 400 amperes continuous.
Table 12. Fault Fiter Fuse Control Modules—Inverse Curve Type (TCC No. 410-7)
Continuous Current, Amperes, Max①
Minimum Pickup, Amperes, RMS
Catalog Number
400 814040
500 814050
600 814060
700 814070
800 814080
1000 814100
1250 814125
1500 814150
① Control modules rated 600 amperes continuous are also applicable for use in mountings rated 200 amperes or 400 amperes continuous.
. S&C Specification Bulletin 662A-31 19
Table 13. Fault Fiter Fuse Control Modules—Time-Delayed Compound-Curve Type (TCC No. 421-7)
Continuous Current, Amperes, Max①
TCC Curve Parameters
Catalog NumberMinimum Pickup, Amperes, RMS
Short-Time Delay Band
High-Current Pickup, Amperes, RMS
High-Current Delay Band
Time Delay, ms
3000 8 7010-C40S1T3D8
6000 8 7010-C40S1T6D8
3000 8 7010-C40S2T3D8
6000 8 7010-C40S2T6D8
3000 8 7010-C40S3T3D8
6000 8 7010-C40S3T6D8
3000 8 7010-C40S4T3D8
6000 8 7010-C40S4T6D8
3000 8 7010-C60S1T3D8
6000 8 7010-C60S1T6D8
3000 8 7010-C60S2T3D8
6000 8 7010-C60S2T6D8
3000 8 7010-C60S3T3D8
6000 8 7010-C60S3T6D8
3000 8 7010-C60S4T3D8
6000 8 7010-C60S4T6D8
3000 8 7010-C80S1T3D8
6000 8 7010-C80S1T6D8
3000 8 7010-C80S2T3D8
6000 8 7010-C80S2T6D8
3000 8 7010-C80S3T3D8
6000 8 7010-C80S3T6D8
3000 8 7010-C80S4T3D8
6000 8 7010-C80S4T6D8
3000 8 7010-C110S1T3D8
6000 8 7010-C110S1T6D8
3000 8 7010-C110S2T3D8
6000 8 7010-C110S2T6D8
3000 8 7010-C110S3T3D8
6000 8 7010-C110S3T6D8
3000 8 7010-C110S4T3D8
6000 8 7010-C110S4T6D8
① Control modules rated 600 amperes continuous are also applicable for use in mountings rated 200 amperes or 400 amperes continuous.
20 S&C Specification Bulletin 662A-31 .
Table 14. Switch Blades①
Item
Rating
Catalog NumberkV Amperes, Cont.
Nom. Max
Switch blade, for use in lieu of SMU-20 Fuse Unit in SML-20 Mounting
14.4 17 200 5432
25 27 200 5433
Switch blade, for use in lieu of SML-4Z Holder in SML-4 Mounting
14.4 17 200 5442
25 27 200 5443
Switch blade, for use in lieu of Fault Fiter fuse holder in Fault Fiter fuse mounting
14.4 17 400 3222
25 29 200 3223R1
① When switch blades are used in lieu of fuses, the Uni-Rupter Interrupter associated with these switches can carry and interrupt load currents up to and including the emergency peak-load capabilities of the SML power fuses, or up to 400 amperes at 14.4 kV and 200 amperes at 25 kV for Fault Fiter Electronic Power Fuses. Furthermore, the switches with a Uni-Rupter Interrupter have fault-closing ratings equal to those of S&C Power Fuses with Uni-Rupter Interrupters (refer to the “Application Notes” section on page 2). The momentary and one-second ratings of the switches equal the short-circuit ratings of the pad-mounted gear.
Table 15. Accessories
Item Catalog Number
Grounding jumpers, set of three, with eye-type clamps for installa-tion with a standard shotgun clamp stick 3‑foot (914‑mm) cable length 4210
Shotgun clamp sticks for use with separable connectors and voltage testers
771/2 inches (1969 mm) 9933-150
1011/2 inches (2578‑mm) 9933-151
Storage bag, heavy canvas
For grounding jumpers 9933-149
For shotgun clamp stick 78 inches (1981 mm) 9933-152
102 inches (2591 mm) 9933-153
Voltage tester with audio and visual signals, includes voltage tester, batteries, adapter for shotgun clamp sticks, and storage case① 9931-072
Pentahead socket, for 1/2‑inch drive 9931-074
① For ultimate users other than electric utilities, also specify a shotgun clamp stick of the appropriate length.
Table 16. Touch-Up Kit Components—Aerosol Coatings in 12-Ounce Cans
Item Catalog Number
S&C Light Gray Outdoor Finish 9999-080
S&C Olive Green (Munsell 7GY3.29/1.5) Outdoor Finish 9999-058
S&C Red-Oxide Primer 9999-061
Table 17. Connector
Illustration Description Accommodating Connector Catalog Number
Bronze body, tin-plated, two galvanized steel bolts, two Belleville washers
No. 2 solid through 500 kc mil stranded copper or aluminum 4745
. S&C Specification Bulletin 662A-31 21 kV, Nominal A1● A2● B C D E1 E2 F G1 G2 G3 H M W
14.4 97/8
(251) 111/8
(283) 51/8
(130)
(432) 403/4
(1035) 127/8
(327) 71/2
(191) 373/4
(959)
(152) 93/4
(248) 93/4
(248)
(1118)
(864) 347/8
(886)
25 141/8 (359)
151/4
(387) 71/8
(181) 421/2
(1080) 593/4
(1518) 133/4
(349) 95/8
(244) 563/4
(1441) 71/2
(191)
(254) 121/2
(318)
(1397) 421/2
(1080)
(1092)
● When catalog number suffix “-M1,” “-U2,” or “-U3” is specified, cable-termination locations will be slightly affected. Consult the nearest S&C Sales Office for details.
Model PMH-3
14.4 kV and 25 kV Nominal
1½ (38)
2¾ (70)
2¾ (70)
(152)
1½ (38)
Dimensions in inches (mm)
FOUR 5/8 (16) DIA. ANCHOR
BOLTS—BY USER
1½ (38) MIN.
M (103° DOOR OPENINGS)
ANCHOR BRACKET–BY S&C
APPROXIMATE
CABLE TERMINATION
LOCATIONS
GASKET
CONCRETE PAD
ENCLOSURE
ANCHOR BOLt DetAIL
ANCHOR BOLt pLAN CONNeCtION DIAGRAM
FRONt VIeW
W
H
SIDe VIeW
W
F
C
B
G2
G1 G1 e2 e1
A2
A1
G3
F
D
22 S&C Specification Bulletin 662A-31 .
Model PMH-4
14.4 kV and 25 kV Nominal kV, Nominal
A1 A2● B C D E F G1 G2 H J K M W
14.4
(178) 111/8
(283) 51/8
(130) 271/2
(699) 403/4
(1035) 77/8
(200) 373/4
(959) 93/4
(248) 93/4
(248)
(1118) 101/2
(267) 93/4
(248)
(864) 347/8
(886)
111/4
(286) 151/4
(387) 71/8
(181) 421/2
(1080) 593/4
(1518) 95/8
(244) 563/4
(1441)
(254) 121/2
(318)
(1397) 111/2
(292) 121/2
(318) 421/2
(1080)
(1092)
● When catalog number suffix “-M1,” “-U2,” or “-U3” is specified, cable-termination locations will be slightly affected. Consult the nearest S&C Sales Office for details.
Dimensions in inches (mm)
ANCHOR BRACKET–BY S&C
GASKET
CONCRETE PAD
ENCLOSURE
ANCHOR BOLt DetAIL
1½ (38)
1½ (38)
1½ (38) MIN.
2¾ (70)
2¾ (70)
FOUR 5/8 (16) DIA. ANCHOR
BOLTS—BY USER
M (103° DOOR OPENINGS)
APPROXIMATE
CABLE TERMINATION
LOCATIONS
ANCHOR BOLt pLAN CONNeCtION DIAGRAM
FRONt VIeW SIDe VIeW
H
F D
W
B e
W
C
KK
G1
J
A1
A2
G2
. S&C Specification Bulletin 662A-31 23 kV, Nominal A1● A2 B C D E F G H J K M W
14.4 97/8
(251)
(178) 51/8
(130)
(787) 543/4
(1391) 127/8
(327) 513/4
(1314)
(152)
(1118) 47/8
(124) 93/4
(248)
(864) 347/8
(886)
141/8
(359) 111/4
(286) 71/8
(181)
(1295) 681/4
(1734) 133/4
(349) 651/4
(1657) 71/2
(191)
(1397) 65/8
(168) 121/2
(318) 421/2
(1080)
(1092)
● When catalog number suffix “-M1,” “-U2,” or “-U3” is specified, cable-termination locations will be slightly affected. Consult the nearest S&C Sales Office for details.
Model PMH-5
14.4 kV and 25 kV Nominal
Dimensions in inches (mm)
ANCHOR BRACKET–BY S&C
GASKET
CONCRETE PAD
ENCLOSURE
ANCHOR BOLt DetAIL
(152)
FRONt VIeW SIDe VIeW
ANCHOR BOLt pLAN CONNeCtION DIAGRAM
M (103° DOOR OPENINGS)
APPROXIMATE
CABLE TERMINATION
LOCATIONS
1½ (38)
1½ (38)
1½ (38) MIN.
FOUR 5/8 (16) DIA. ANCHOR
BOLTS—BY USER
2¾ (70)
2¾ (70)
W
H
G e
G
A1
A2
C
B
KK
W
J
24 S&C Specification Bulletin 662A-31 .
kV, Nominal A1● A2 B C D E F G H J K L M W
14.4 97/8
(251)
(178) 51/8
(130)
(1016) 633/4
(1619) 127/8
(327) 603/4
(1543)
(152)
(1118) 43/4
(121) 93/4
(248) 143/4
(375)
(864)
(1702)
141/8
(359) 111/4
(286) 71/8
(181) 621/2
(1588) 793/4
(2026) 133/4
(349) 763/4
(1949) 71/2
(191)
(1397)
(152) 121/2
(318) 161/2
(419) 411/2
(1054)
(2083)
● When catalog number suffix “-M1,” “-U2,” or “-U3” is specified, cable-termination locations will be slightly affected. Consult the nearest S&C Sales Office for details.
Model PMH-6
14.4 kV and 25 kV Nominal
Dimensions in inches (mm)
ANCHOR BRACKET–BY S&C
SIDe VIeW
D
FW
W
H
(152)
(152)
1½ (38)
1½ (38)
M (103° DOOR OPENINGS)
2¾ (70)
2¾ (70)
1½ (38) MIN.
FOUR 5/8 (16) DIA. ANCHOR
BOLTS—BY USER
FRONt VIeW
GASKET
CONCRETE PAD
ENCLOSURE
ANCHOR BOLt DetAIL
CONNeCtION DIAGRAM
ANCHOR BOLt pLAN
APPROXIMATE
CABLE TERMINATION
LOCATIONS
C
B e
GG GG
e
F
J K L
A1
A2
. S&C Specification Bulletin 662A-31 25
Model PMH-7
14.4 kV and 25 kV Nominal kV, Nominal A1● A2 B C D E F G H J K L M W
14.4 97/8
(251)
(178) 51/8
(130)
(1016) 633/4
(1619) 127/8
(327) 603/4
(1543)
(152)
(1118) 43/4
(121) 93/4
(248) 143/4
(375)
(864)
(1702)
141/8
(359) 111/4
(286) 71/8
(181) 621/2
(1588) 793/4
(2026) 133/4
(349) 763/4
(1949) 71/2
(191)
(1397)
(152) 121/2
(318) 161/2
(419) 411/2
(1054)
(2083)
● When catalog number suffix “-M1,” “-U2,” or “-U3” is specified, cable-termination locations will be slightly affected. Consult the nearest S&C Sales Office for details.
Dimensions in inches (mm)
ANCHOR BRACKET–BY S&C
SIDe VIeW
(152)
M (103° DOOR OPENINGS)
1½ (38) MIN.
FOUR 5/8 (16) DIA. ANCHOR
BOLTS—BY USER
FRONt VIeW
GASKET
CONCRETE PAD
ENCLOSURE
ANCHOR BOLt DetAIL
CONNeCtION DIAGRAM
ANCHOR BOLt pLAN
J J
B
K KL
W
L
W
H
2¾ (70)
APPROXIMATE CABLE
TERMINATION LOCATIONS
2¾ (70)
1½ (38)
1½ (38)
A2
F e
GG
26 S&C Specification Bulletin 662A-31 .
kV, Nominal A1● A2 A3● B C D E1 E2 F G1 G2 H J K L M W
14.4 97/8
(251)
(178)
(483) 51/8
(130)
(1016) 633/4
(1619) 127/8
(327) 83/4
(222) 603/4
(1543)
(152) 91/4
(235)
(1118) 43/4
(121) 93/4
(248) 143/4
(375)
(864)
(1702)
141/8
(359) 111/4
(286) 183/4
(476) 71/8
(181) 621/2
(1588) 793/4
(2026) 133/4
(349) 81/16
(205) 763/4
(1949) 71/2
(191) 121/2
(318)
(1397)
(152) 121/2
(318) 161/2
(419) 411/2
(1054)
(2083)
● When catalog number suffix “-M1,” “-U2,” or “-U3” is specified, cable-termination locations will be slightly affected. Consult the nearest S&C Sales Office for details.
Model PMH-8
14.4 kV and 25 kV Nominal
Dimensions in inches (mm)
1½ (38)
1½ (38)
B
JJ KK
W
W F D
L L
2¾ (70)
2¾ (70)
A2
A3 A1 e1
G1G2 G1G2 e2
M (103° DOOR OPENINGS)
ANCHOR BOLt pLAN
CONNeCtION DIAGRAM
SIDe VIeWFRONt VIeW
ANCHOR BRACKET–BY S&C
GASKET
CONCRETE PAD
ENCLOSURE
ANCHOR BOLt DetAIL
1½ (38) MIN.
FOUR 5/8 (16) DIA. ANCHOR
BOLTS—BY USER
APPROXIMATE CABLE
TERMINATION LOCATIONS
H
F
(152)
C
. S&C Specification Bulletin 662A-31 27 kV, Nominal A1● A2 B C D E F G H J K L M W
14.4 97/8
(251)
(178) 51/8
(130)
(1016) 633/4
(1619) 127/8
(327) 603/4
(1543)
(152)
(1118) 43/4
(121) 93/4
(248) 143/4
(375)
(864…