Exhibit AA - Specification Bulletin 662A-31.pdf

PDF 2 MB Posted

Attached to
Giese Road Substation Feeder 24 Backfeed
Solicitation number
375074GMK
Issued by

About this file

This document is a specification bulletin for S&C Manual PMH Pad-Mounted Gear for outdoor distribution at 14.4 kV and 25 kV voltage levels. The specification provides comprehensive technical details for manual pad-mounted gear with multiple model configurations (PMH-3 through PMH-19), including switch and fuse components, ratings, and optional features. Key technical specifications include 600-ampere external handle-operated Mini-Rupter Switches for three-pole live switching, 200-ampere hookstick-operated S&C Power Fuses with Uni-Rupter Interrupters for single-pole live switching, and enclosures meeting ANSI C57.12.28 standards. The gear offers various fuse types including SML-20, SML-4Z, and Fault Fiter Electronic Power Fuses, with options for different voltage ratings, ampere ranges, and specialized features like key interlocks, surge arresters, base spacers, and different finish colors. The document includes detailed dimensional drawings, connection diagrams, and comprehensive tables detailing product specifications, components, and ordering information for different models and configurations.

View the file

Other files

File Type Posted
Amendment 03 to RFP NO. 375074GMKLB.pdf PDF
Amendment 02 to RFP NO. 375074GMKLB.pdf PDF
Exhibit Y - Image_0299.jpg JPG image
Exhibit Z - 75-150PV-VAULT-WIN.pdf PDF
Amendment 01 to RFP NO. 375074GMK.pdf PDF
Exhibit X - Instructions for Access-Request-form-for-Business-Visitors.pdf PDF
1.0 RFP Instructions to Offerors_Giese Road Substation Feeder 24 Backfeed FINAL.pdf PDF
Exhbit A - SOW_Feeder_24_backup_rework - rev 3.pdf PDF
Exhibit G - 16100 - Ductbank.pdf PDF
Exhibit J - 16450 - GROUNDING AND BONDING v2.pdf PDF
Exhibit M - 2025 Construction Insurance Requirements.pdf PDF
Exhibit O - Fermilab Subcontractor Injury and Illness Data Questionnaire.pdf PDF
Exhibit R - PUR-466_Proposal Certifications_r5_10.14.25.pdf PDF
Exhibit U - FL-40 - Performance Bond.pdf PDF
Exhibit C - 010010_General_Requirements_3_2025_FFDG_.pdf PDF
Exhibit F-014100_Quality_Requirements_-_March_2025.pdf PDF
Exhibit T - FL-42 (Rev 1.25) - Payment Bond.pdf PDF
1.0 RFP Instructions to Offerors_Giese Road Substation Feeder 24 Backfeed.pdf PDF
Exhibit B - Drawings - Giese Road Substation Feeder 24 Backfeed.pdf PDF
Exhibit D - 013100_ESH_Requirements_04-2025_FFDG (1).pdf PDF
Exhibit L - FFDG General Terms and Conditions for Construction.pdf PDF
Exhibit V - WDIL20250011 Heavy and Highway.pdf PDF
Exhibit W - Sample Subcontract.pdf PDF
Exhibit E - 013300_Submittals_FermiForward (3).pdf PDF
Exhibit H - 16121 - Medium Voltage Cable v2.pdf PDF
Exhibit I - 16125 - 15KV Cable Installation v2.pdf PDF
Exhibit K - 16950 - Testing Electrical Systems r1.pdf PDF
Exhibit N - SF1413-23a.pdf PDF
Exhibit P -Price Proposal Form 20251205.pdf PDF
Exhibit Q - SARC_Subcontractor Annual RepsCerts Rev 7.pdf PDF
Exhibit S - Bond Bid FL-41.pdf PDF
Show all 31

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

S&C Manual PMH Pad-Mounted Gear Outdoor Distribution (14.4 kV and 25 kV)

Specifications

September 9, 2024 © S&C Electric Company 2001–2024, all rights reserved Specification Bulletin 662A-31

Conditions of Sale STANDARD: The seller’s standard conditions of sale set forth in Price Sheet 150 apply, except as modified in the “Warranty Qualifications” section on page 3.

SPECIAL TO THIS PRODUCT:

INCLUSIONS: S&C Manual PMH Pad-Mounted Gear features directly operable accessible components.

Switches and fuses are clearly visible. Manual PMH models contain 600‑ampere external handle-operated Mini-Rupter® Switches for three-pole live switching of three-phase source circuits and 200‑ampere hookstick-operated S&C Power Fuses with Uni-Rupter® Interrupters for single-pole live switching of single-phase or three-phase load circuits. (These models offer a choice of S&C Type SML-20 and SML-4Z Power Fuses or Fault Fiter® Electronic Power Fuses. Fault Fiter Electronic Power Fuse mountings also accommodate a variety of single-barrel current-limiting fuses listed in Table 1 of S&C Information Bulletin 660-50.)

Enclosures meet the requirements of ANSI C57.12.28 (enclosure integrity). They are of free-standing, self-supporting construction—not for bolting directly to transformers—with provisions for cable entrance and exit through the bottom. Access to medium voltage is controlled by the Penta-Latch® Mechanism, which provides automatic door latching and permits padlocking only when the door is securely latched. The door can be opened only with a pentahead socket wrench or tool.

The enclosure roof is undercoated with an insulating “no-drip” compound. A resilient closed-cell gasket on the enclosure bottom flange protects the finish from being scratched during installation and isolates it from the alka linity of a concrete foundation. Enclosures are protected from corrosion by S&C’s olive green Ultradur® II Outdoor Finish.

A dual-purpose front barrier of fiberglass-reinforced polyester is provided for each switch and fuse. Where the National Electric Safety Code (ANSI Standard C2) applies, these barriers meet the requirements of Section 381G.

When the switch or fuse is in the Open position, this barrier can be inserted into the open gap to guard against inadvertent contact with live parts. Interphase and end barriers of the same material are provided with each switch and each set of fuses where required to achieve published BIL ratings. Additional barriers of fiberglass-reinforced polyester separate front and rear compartments and isolate the tie bus (where furnished).

Full-length steel barriers separate adjoining compart-ments (where applicable).

These PMH models are provided with a Grappler™ Handling Tool, if applicable; an instruction manual holder; and storage racks in the fuse-compartment doors for spare S&C Fuse Units or Refill Units and for the Grappler tool (storage for Fault Fiter Electronic Power Fuses or current-limiting fuses cannot be provided in these racks). A folding switch-operating handle, secured inside the switch-operating-hub pocket, is provided for each Mini-Rupter Switch. Terminal pads can accommo date a variety of cable-terminating devices for cable sizes through 1000 kc mil for switch and bus terminals, 4/0 maximum for fuse terminals. Each switch, fuse, and bus terminal is provided with a ground stud as is each ground pad.

All terminal pads can accommodate a variety of cable-terminating devices for cable sizes through 1000 kc mil for switch terminals, 4/0 maximum for fuse terminals. The cable-terminating devices must be equipped either with an offset spade-type compression terminal for bolting directly to the terminal pad or with a rod-type compression terminal for attachment to a connector of the type shown in Table 17 on page 20.

For applications where additional height is desired

2 S&C Specification Bulletin 662A-31 .

for increased elevation of ungrounded parts above the mounting pad and to facilitate cable pulling and installa-tion of cable-terminating devices, particularly where no cable pit is used, base spacers are available as listed in Table 4 on page 9.

While the interior of S&C Pad-Mounted Gear is protected from direct exposure to the elements, it is inherently designed for an outdoor environment and requires selection and application of cable-terminating devices accordingly. Terminations must incorpo-rate adequate leakage distance between the exposed conductor and the stress-relief cone across a surface of nontracking material (or a surface rendered nontracking by properly taping with a suitable material).

Furthermore, to maintain the rated BIL, the following minimum clearances are required: 6 inches (152 mm) at

14.4 kV and 71/2 inches (191 mm) at 25 kV from energized parts to electrical ground; 1 inch (25 mm) at 14.4 kV and 21/4 inches (57 mm) at 25 kV from energized parts to fiber-glass-reinforced polyester barriers; 1/2‑inch (13 mm) at

14.4 kV and 11/4 inches (32 mm) at 25 kV from terminator skirts to fiberglass-reinforced polyester barriers.

EXCLUSIONS: Three-phase units listed in Table 3 on pages 6 through 8 do not include the items listed in Table 4 on page 9 through 13, nor do they include the connector, fuse components, switch blades, or acces-sories listed in Table 5, Table 6, and Table 7 on page 14, or Table 14, Table 15 and Table 17 on page 20.

SPECIFICATION DEVIATIONS: Features or modifica tions other than those listed in Table 4 on page 9 cannot be accommodated. Specifically, the following modifications or additions are not available except in custom-design gear or other standard models of S&C gear:

● Relocation of components (switches and fuses)

● Inclusion, in fuse compartments, of surge arresters or porcelain cable-terminating devices

● Separable insulated 200- or 600‑ampere connectors

● Intermediate- or station-class surge arresters

● Mechanical interlocks

Certain minor departures from the optional features can be accommodated. For example, the user may use mounting provisions for different porcelain cable terminators in a switch compartment and bus compart-ment. Such deviations can be accommodated by a “minor modification.” Contact the nearest S&C Sales Office for availability.

APPLICATION NOTES: For application information and a guide to the selection of appropriate ampere ratings and speeds of S&C SML Power Fuses, and types and TCC curve parameters of control modules for Fault Fiter Elec-tronic Power Fuses, contact the nearest S&C Sales Office.

Switching with a Uni-Rupter Interrupter Manual PMH Pad-Mounted Gear features fuses with Uni-Rupter Interrupters for single-pole live switching of single-phase or three-phase load circuits on distribution systems rated 14.4 kV or 25 kV.

Complete ratings and capabilities of S&C Power Fuses with Uni-Rupter Interrupters as applied in manual PMH Pad-Mounted Gear are shown in Table 1 on page 5. The Uni-Rupter Interrupter is also capable of carrying and interrupting load currents up to and including the emergency peak-load capabilities of the associated SML power fuses. In addition to the load-drop-ping capabilities shown, the Uni-Rupter Interrupter is capable of interrupting transformer magnetizing currents associated with the applicable loads as well as line-charging and cable-charging currents typical for distribution systems of these voltage ratings.

The duty-cycle fault-closing capabilities shown for S&C Power Fuses with Uni-Rupter Interrupters repre sent the fault-closing capabilities of the fuse with the Uni-Rupter Interrupter when the fuse is closed with a purposeful thrust without hesitation. Following the specified number of such closings (two or three), the Uni-Rupter Interrupter will remain operable and able to carry and interrupt rated current.

. S&C Specification Bulletin 662A-31 3

A Note on Single-Pole Switching In single-pole switching of ungrounded-primary three-phase transformers or banks (or a single-phase transformer connected line to line), circuit connec-tions or parameters may, in some cases, produce excessive overvoltages. In particular, for the following applications above 22 kV, single-pole switching by any means—including the Uni-Rupter Interrupter—should be performed only under the conditions stated in italics

● Switching unloaded or lightly loaded delta-con-nected or ungrounded-primary wye-wye connected three-phase transformers or banks (or line-to-line connected single-phase transformers), rated 150 kVA or less three-phase, or 50 kVA or less single-phase— or of any kVA rating when combined with unloaded cables or lines—where maximum system operating voltage exceeds 22 kV (Single-pole switching should be performed only if each phase is carrying 5% load or more, or if the transformer or bank is tempo-rarily grounded at the primary neutral during switching.)

● Switching loaded or unloaded ungrounded-primary wye-delta connected three-phase transformers or banks—alone or combined with unloaded cables or lines—where maximum system operating voltage exceeds 22 kV (Single-pole switching should be performed only if each phase is carrying 5% load or more and if the lighting-load phase is always switched open first (or switched closed last), or if the transformer or bank is temporarily grounded at the primary neutral during switching.)

Recommended Voltage Ratings of Current‑Limiting Fuses for Use in S&C Pad‑Mounted Gear In general, current-limiting fuses should have a maximum voltage rating equal to, but not greater than 140% of, the system line-to-line voltage because for most applications, the fuses can be exposed to full system line-to-line voltage in clearing faults. Although there may be economic or space-saving incentives for using current-limiting fuses with voltage ratings “appro-priate for system line-to-ground voltage” (i.e., fuses with a voltage rating lower than line-to-line voltage but greater than or equal to maximum system line-to-ground voltage), S&C can recommend such use only in any of the following applications:

● Protection of single-phase transformers serving single-phase loads

● Protection of three-phase lateral circuits fed by a single-conductor shielded cable (provided each transformer on that lateral is individually fused so the current-limiting fuse serving the lateral will not be required to clear secondary faults)

● Protection of single-phase lateral circuits fed by a single-conductor shielded cable where the load is line-to-ground connected

Switching with a Mini-Rupter Switch Manual PMH Pad-Mounted Gear features Mini-Rupter Switches for three-pole live switching of three-phase circuits.

Complete ratings for Mini-Rupter Switches as applied in manual PMH Pad-Mounted Gear are shown in Table 2 on page 5. In addition to the load-dropping ratings shown, a Mini-Rupter Switch is capable of interrupting transformer magnetizing currents associated with the applicable loads as well as line-charging and cable-charging currents typical for distribution systems of these voltage ratings.

For applications on systems rated higher than 7.2 kV and involving load current with high harmonic content (such as rectifier load currents), refer to the nearest S&C Sales Office. The two-time duty-cycle fault-closing ratings shown for Mini-Rupter Switches define the ability to close the Mini-Rupter Switch twice against a three-phase fault with asymmetrical current in at least one phase equal to the rated value, with the switch remaining operable and able to carry and interrupt rated current.

WARRANTY QUALIFICATIONS: The standard warranty contained in the seller’s standard conditions of sale (as set forth in Price Sheet 150) does not apply to manual PMH Pad-Mounted Gear where fuse units, fuse unit end-fittings, holders, refill units, or switch blades of other than S&C manufacture are used in conjunction with S&C SML Mountings. Nor does it apply to manual PMH Pad-Mounted Gear where other than Fault Fiter Electronic Power Fuses, S&C Switch Blades, or the current-limiting fuses listed in Table 1 of S&C Informa-tion Bulletin 660-50 are used in conjunction with Fault Fiter Electronic Power Fuse mountings and S&C Holders designed therefor, or when current-limiting fuses are applied other than as set forth in the “Recommended Voltage Ratings of Current-Limiting Fuses for Use in S&C Pad-Mounted Gear” section.

4 S&C Specification Bulletin 662A-31 .

How to Order Complete the following steps for a typical order of manual PMH Pad-Mounted Gear:

Step 1. Select the three-phase pad-mounted gear.

(a) Obtain the catalog number of the desired unit from Table 3 on pages 6 through 8.

Catalog Number:

(b) Add suffix designations (to the catalog number above) to indicate the optional features desired, selected from Table 4 on pages 9 through 13.

Suffix: –

(c) Obtain the catalog number of the connector, accessories, and touch-up kit components from Table 15, Table 16, and Table 17 on page 20.

Catalog Number: –

Step 2. Select the fuse components and switch blades

(a) For SML-20 Power Fuses: Obtain the catalog number of the end-fittings and the fuse units from Table 5 on page 14, taking care to match the voltage rating of the end fittings to the fuse units.

Catalog Number:

(b) For SML-4Z Power Fuses: Obtain the catalog number of the holder and refill units from Table 6 on page 14, taking care to match the voltage rating of the holder to the refill units.

Catalog Number:

(c) For Fault Fiter Electronic Power

Fuses: Obtain the catalog number for the holders, the interrupting modules, and the control modules from Table 7 on page 14, taking care to match the voltage rating of the holders, interrupting modules, and the control modules.

Catalog Number:

(d) For switch blades: Obtain the catalog number for the switch blades from Table 14 on page 20.

Catalog Number:

Example: The catalog number of a 14.4‑kV manual Model PMH-9 with SML-20 Mountings, optional cable guides for switches and fuses, and 10‑kV metal-oxide surge arresters at all switch terminals is:.

Catalog Number:

5 5 1 5 2 R 4 – M 2 M 3 N 7

. S&C Specification Bulletin 662A-31 5

Table 1. Ratings and Capabilities for S&C Power Fuses With Uni-Rupter Interrupters

Fuse Type

Voltage, kV Current, Amperes, RMS

Nom. Max BIL Max Interr. (Sym.)

Live Switching

Load Splitting (Parallel or Loop

Switching) Load Dropping

Duty-Cycle Fault-Closing

RMS, Sym.

SML-20

14.4 17 95 200E or 200K 14 000 200 200 14 000 ●

25 27 125 200E or 200K 12 500 200 200 12 500■

SML-4Z

14.4 17 95 200E 12 500 200 200 12 500●

25 27 125 200E 12 500▲ 200 200 12 500■

Fault Fiter fuse

14.4 17 95 200 14 000 200 200 14 000●

25 29 125 200 12 500 200 200 12 500■

●Three-time duty-cycle fault-closing capability
■Two-time duty-cycle fault-closing capability

▲ Applicable to solidly ground-neutral systems only, with fuses connected by single-conductor, concentric-neutral-type cable to a trans-former or transformers. Rating is 9,400 amperes, RMS, symmetrical for all other applications.

Table 2. Ratings for Mini-Rupter Switches

Voltage, kV Current, Amperes

Nom. Max BIL Cont.

Live Switching Three-Time Duty-Cycle Fault-Closing Short-Circuit

Load-Splitting (Parallel or Loop

Switching)

Load Dropping

Peak RMS, Sym.

Peak

Withstand, Peak

One-Second Short Time Withstand, RMS, Sym.

14.4 17.5 95 600 600 600 36 400 14 000 36 400 14 000

25 29 125 600 600 600 32 500 12 500 32 500 12 500

6 S&C Specification Bulletin 662A-31 .

Table 3. Three-Phase Units (Including mountings with Uni-Rupter Interrupters—less fuse components①)

Model Connection Diagram②

Fuse Type

Ratings③

Catalog Number

Net Wt., Lbs.

Page Refer-ence for

Dimen-sional Infor-mation kV Amperes, RMS Short-Circuit

Nom. Max BIL

Fuse with Uni-Rupter Interrupter

Mini-Rupter Switch Amperes, RMS, Sym.

MVA

3-Phase Sym. at Rated

VoltageMax Load

Dropping Cont.

Load Dropping

PMH-3 —

14.4 17 95 — — 600 600 14 000 350 55232R3 650

25 29 125 — — 600 600 12 500 540 55233R3 950

PMH-4●

SML-20

14.4 17 95 200E■ 200 — — 14 000 350 55102R3 525

25 27 125 200E■ 200 — — 12 500 540 55103R3 675

SML-4Z

14.4 17 95 200E 200 — — 12 500 310 55302R3 525

25 27 125 200E 200 — — 12 500▲ 540▲ 55303R3 675

Fault Fiter

Fuse④

14.4 17 95 200 200 — — 14 000 350 55502R3 525

25 29 125 200 200 — — 12 500 540 55503R3 675

PMH-5◆

SML-20

14.4 17 95 200E■ 200 600 600 14 000 350 55112R3 825

25 27 125 200E■ 200 600 600 12 500 540 55113R3 1150

SML-4Z

14.4 17 95 200E 200 600 600 12 500 310 55312R3 825

25 27 125 200E 200 600 600 12 500▲ 540▲ 55313R3 1150

Fault Fiter

Fuse④

14.4 17 95 200 200 600 600 14 000 350 55512R3 825

25 29 125 200 200 600 600 12 500 540 55513R3 1150

PMH-6◆

SML-20

14.4 17 95 200E■ 200 600 600 14 000 350 55122R4 1475

25 27 125 200E■ 200 600 600 12 500 540 55123R3 1975

SML-4Z

14.4 17 95 200E 200 600 600 12 500 310 55322R4 1475

25 27 125 200E 200 600 600 12 500▲ 540▲ 55323R3 1975

Fault Fiter

Fuse④

14.4 17 95 200 200 600 600 14 000 350 55522R4 1475

25 29 125 200 200 600 600 12 500 540 55523R3 1975

① Fuse components are to be ordered separately. Refer to Table 5, Table 6 and Table 7 on page 14,Table 8 on page 15, Table 9 on page 16,Table 10 on page 17, Table 11 and Table 12 on page 18, and Table 13 on page 19.

②Compartment numbers appear in corners of each diagram.
③The short-circuit ratings expressed in amperes, RMS, asymmet-

rical are 1.6 times the symmetrical values listed. Fault-closing and/or momentary ratings of switches and bus, and fault-closing capabilities and interrupting ratings of fuses, equal or exceed these values. For complete live-switching (as well as momentary and one-second) ratings for Mini-Rupter Switches and complete live-switching capabilities of Uni-Rupter Interrupters as applied in manual PMH Pad-Mounted Gear, refer to the “Application Notes” section on page 2.

④ These models also accommodate selected current-limiting fuses in S&C Holders; refer to Table 1 of S&C Information Bulletin 660-50.

Maximum voltage and maximum ampere ratings as listed in that table apply when current-limiting fuses are used. Consult appropriate current-limiting fuse manufacturer for complete fuse ratings.

●Available only when ultimate user is an electric utility.
■SMU-20 Fuse Units are available in ratings through 200K amperes

as well as 200E amperes.

▲ Applicable to solidly grounded-neutral systems only, with fuses connected by single-conductor, concentric-neutral-type cable to a transformer or transformers. Rating is 9400 amperes, RMS, symmetrical (405 MVA) for all other applications.

◆ Key interlocks (catalog number suffix “-C3” or “-C4”) are required for ultimate users other than electric utilities.

TABLE CONTINUED ▶

. S&C Specification Bulletin 662A-31 7

Table 3. Three-Phase Units (Including mountings with Uni-Rupter Interrupters—less fuse components①)— Continued

Model Connection Diagram②

Fuse Type

Ratings③

Catalog Number

Net Wt., Lbs.

Page Refer-ence for Dimen-sional

Informa-tion kV Amperes, RMS Short-Circuit

Nom. Max BIL

Fuse with Uni-Rupter Interrupter

Mini-Rupter Switch Amperes, RMS, Sym.

MVA

3-Phase Sym. at Rated

VoltageMax Load

Dropping Cont.

Load Dropping

PMH-7◆

SML-20

14.4 17 95 200E■ 200 600 600 14 000 350 55132R4 1400

25 27 125 200E■ 200 600 600 12 500 540 55133R3 1875

SML-4Z

14.4 17 95 200E 200 600 600 12 500 310 55332R4 1400

25 27 125 200E 200 600 600 12 500▲ 540▲ 55333R3 1875

Fault Fiter

Fuse④

14.4 17 95 200 200 600 600 14 000 350 55532R4 1400

25 29 125 200 200 600 600 12 500 540 55533R3 1875

PMH-8●

SML-20

14.4 17 95 200E■ 200 600 600 14 000 350 55142R4 1350

25 27 125 200E■ 200 600 600 12 500 540 55143R3 1900

SML-4Z

14.4 17 95 200E 200 600 600 12 500 310 55342R4 1350

25 27 125 200E 200 600 600 12 500▲ 540▲ 55343R3 1900

Fault Fiter

Fuse④

14.4 17 95 200 200 600 600 14 000 350 55542R4 1350

25 29 125 200 200 600 600 12 500 540 55543R3 1900

PMH-9◆

SML-20

14.4 17 95 200E■ 200 600 600 14 000 350 55152R4 1550

25 27 125 200E■ 200 600 600 12 500 540 55153R3 2050

SML-4Z

14.4 17 95 200E 200 600 600 12 500 310 55352R4 1550

25 27 125 200E 200 600 600 12 500▲ 540▲ 55353R3 2050

Fault Fiter

Fuse④

14.4 17 95 200 200 600 600 14 000 350 55552R4 1550

25 29 125 200 200 600 600 12 500 540 55553R3 2050

PMH-10 —

14.4 17 95 — — 600 600 14 000 350 55242R4 1725

25 29 125 — — 600 600 12 500 540 55243R3 2275

① Fuse components are to be ordered separately. Refer to Table 5, Table 6 on page 14 and Table 7 on page 14,Table 8 on page 15, Table 9 on page 16,Table 10 on page 17, Table 11 and Table 12 on page 18, and Table 13 on page 19.

②Compartment numbers appear in corners of each diagram.
③The short-circuit ratings expressed in amperes, RMS, asymmet-

rical are 1.6 times the symmetrical values listed. Fault-closing and/or momentary ratings of switches and bus, and fault-closing capabilities and interrupting ratings of fuses, equal or exceed these values. For complete live-switching (as well as momentary and one-second) ratings for Mini-Rupter Switches and complete live-switching capabilities of Uni-Rupter Interrupters as applied in manual PMH Pad-Mounted Gear, refer to the “Application Notes” section on page 2.

④ These models also accommodate selected current-limiting fuses in S&C Holders; refer to Table 1 in S&C Information Bulletin 660-50.

Maximum voltage and maximum ampere ratings as listed in that table apply when current-limiting fuses are used. Consult appropriate current-limiting fuse manufacturer for complete fuse ratings.

●Available only when ultimate user is an electric utility.
■SMU-20 Fuse Units are available in ratings through 200K amperes

as well as 200E amperes.

▲ Applicable to solidly grounded-neutral systems only, with fuses connected by single-conductor, concentric-neutral-type cable to a transformer or transformers. Rating is 9400 amperes, RMS, symmetrical (405 MVA) for all other applications.

◆ Key interlocks (catalog number suffix “-C3” or “-C4”) are required for

8 S&C Specification Bulletin 662A-31 .

Table 3. Three-Phase Units (Including mountings with Uni-Rupter Interrupters—less fuse components①)— Continued

Model Connection Diagram②

Fuse Type

Ratings③

Catalog Number

Net Wt., Lbs.

Page Refer-ence for Dimen-sional

Informa-tion kV Amperes, RMS Short-Circuit

Nom. Max BIL

Fuse with Uni-Rupter Interrupter

Mini-Rupter Switch Amperes, RMS, Sym.

MVA

3-Phase Sym. at Rated

VoltageMax Load

Dropping Cont.

Load Dropping

PMH-11◆

SML-20

14.4 17 95 200E■ 200 600 600 14 000 350 55162R4 1625

25 27 125 200E■ 200 600 600 12 500 540 55163R3 2175

SML-4Z

14.4 17 95 200E 200 600 600 12 500 310 55362R4 1625

25 27 125 200E 200 600 600 12 500▲ 540▲ 55363R3 2175

Fault Fiter

Fuse④

14.4 17 95 200 200 600 600 14 000 350 55562R4 1625

25 29 125 200 200 600 600 12 500 540 55563R3 2175

PMH-12◆

SML-20

14.4 17 95 200E■ 200 600 600 14 000 350 55172R4 1450

25 27 125 200E■ 200 600 600 12 500 540 55173R3 1950

SML-4Z

14.4 17 95 200E 200 600 600 12 500 310 55372R4 1450

25 27 125 200E 200 600 600 12 500▲ 540▲ 55373R3 1950

Fault Fiter

Fuse④

14.4 17 95 200 200 600 600 14 000 350 55572R4 1450

25 29 125 200 200 600 600 12 500 540 55573R3 1950

PMH-13 —

14.4 17 95 — — 600 600 14 000 350 55252R4 1525

25 29 125 — — 600 600 12 500 540 55253R3 2125

PMH-19◆

SML-20 14.4 17 95 200E■ 200 600 600 14 000 350 55212R4 1625

32SML-4Z 14.4 17 95 200E 200 600 600 12 500 310 55412R4 1625

Fault Fiter

Fuse④

14.4 17 95 200 200 600 600 14 000 350 55612R4 1625

① Fuse components are to be ordered separately. Refer to Table 5, Table 6 and Table 7 on page 14,Table 8 on page 15, Table 9 on page 16,Table 10 on page 17, Table 11 and Table 12 on page 18, and Table 13 on page 19.

②Compartment numbers appear in corners of each diagram.
③The short-circuit ratings expressed in amperes, RMS, asymmet-

rical are 1.6 times the symmetrical values listed. Fault-closing and/or momentary ratings of switches and bus, and fault-closing capabilities and interrupting ratings of fuses, equal or exceed these values. For complete live-switching (as well as momentary and one-second) ratings for Mini-Rupter Switches and complete live-switching capabilities of Uni-Rupter Interrupters as applied in manual PMH Pad-Mounted Gear, refer to the “Application Notes” section on page 2.

④ These models also accommodate selected current-limiting fuses in S&C Holders; refer to Table 1 of S&C Information Bulletin 660-50.

Maximum voltage and maximum ampere ratings as listed in that table apply when current-limiting fuses are used. Consult appropriate current-limiting fuse manufacturer for complete fuse ratings.

●Available only when ultimate user is an electric utility.
■SMU-20 Fuse Units are available in ratings through 200K amperes

as well as 200E amperes.

▲ Applicable to solidly grounded-neutral systems only, with fuses connected by single-conductor, concentric-neutral-type cable to a transformer or transformers. Rating is 9400 amperes, RMS, symmetrical (405 MVA) for all other applications.

◆ Key interlocks (catalog number suffix “-C3” or “-C4”) are required for

. S&C Specification Bulletin 662A-31 9

Table 4. Optional Features

Item Suffix to be Added to Pad-Mounted Gear

Catalog Number Applicable to Models

Light gray outdoor Ultradur II Outdoor Finish instead of olive green -A2 All models

Equipment green Ultradur II Outdoor Finish (Toronto standard) instead of olive green -A3 All models

Seafoam green Ultradur II Outdoor Finish instead of olive green -A4 All models

Special color Ultradur II Outdoor Finish instead of olive green -A5 All models

Stainless steel enclosure①

With olive green outdoor Ultradur II Outdoor Finish -A10 All models

With light gray outdoor Ultradur II Outdoor Finish -A12 All models

With special color outdoor Ultradur II Outdoor Finish -A15 All models

Hexhead actuator for use in lieu of pentahead actuator on all Penta-Latch Mechanisms

For use except when catalog number suffix “-F2” is specified -B1●■ All models

For use when catalog number suffix “‑F2” is also specified -B2▲■ All models except PMH-4

Copper bus② and copper switch terminals, fuse connector adapters, and bus terminals -B5 All models

Reinforced bus Used with standard aluminum bus -B6 15‑kV models of PMH-6, -7, -8, -9, -10, -11, 12, -13Used with optional copper bus -B7

Key interlocks to prevent paralleling of switches in compartments 1 and 2③ -C1 PMH-6, -9, -10, -11, -13, -19

Key interlocks to prevent opening fuse-compartment doors unless all switches (series tap switch only in PMH-19) are locked open③ -C3◆ PMH-5, -6, -7, -9, -11, -12, -19

Key interlocks. Combines functions of options “-C1” and “-C3” listed above③ -C4◆ PMH-6, -9, -11, -19

Fuse Storage feature for three spare fuse assemblies per compartment④

Located in compartment 1 -E1 PMH-5, -6, -7, -8, -9, -11, -19

Located in compartment 2 -E2 PMH-6, -7, -9, -11, -12, -19

Located in compartments 1 and 2 -E3 PMH-6, -7, -9, -11, -19

TABLE CONTINUED ▶

① When this optional feature is specified, the entire exterior of the enclosure is fabricated from 11-gauge Type 304 stainless steel. When specifying optional hexhead actuators, provisions for fault indicators with viewing windows in doors, or base spacer, specify the correct suffix for use in gear with a stainless steel enclosure.

②Copper bus measures 1/4‑inch (6 mm) by 2 inches (51mm).
③When specifying, please furnish name of ultimate user, station, and

location of gear.

④ Fuse assemblies (fuse holders or fuse units with end fittings) are not included. For units equipped with Fault Fiter Electronic Power Fuse mountings, two spare Fault Fiter fuse interrupting modules, one spare

Fault Fiter Electronic Power Fuse holder, or one spare current-limiting fuse holder can be accommodated in each compartment.

● Specify catalog number suffix “-B11” for gear with stainless steel enclosure.

■Not available if UL listing (catalog number suffix “-X”) is specified.
▲Specify catalog number suffix “-B12” for gear with stainless steel

enclosure.

◆ Must be specified if end user is not an electric utility and/or if Canadian Standards Association listing (catalog number suffix “-Z”) is specified.

10 S&C Specification Bulletin 662A-31 .

Table 4. Optional Features—Continued

Item Suffix to be Added to Pad-Mounted Gear

Catalog Number Applicable to Models

Mounting provisions for a fault indicator in each switch compartment (except series tap switch in PMH-19)⑤

Without viewing window in door -F1 All models except PMH-4

With viewing window in door -F2▼□ All models except PMH-4

Inner barrier panels—a panel inside the enclosure door for each compartment, secured by recessed pentahead bolt(s)⑥⑦ -G7□ All models

Copper ground stud for each switch, fuse, or bus terminal and ground pad⑧

In fuse compartments⑨ -H2 All models except PMH-3, -10, -13

In switch and bus compartments -J2 All models except PMH-4

TABLE CONTINUED ▶

⑤ Accommodates three-phase indicator with single-phase sensors.

⑥ Where the National Electrical Safety Code (ANSI Standard C2) applies, this optional feature may be included to meet the requirements of Section 381G.

⑦Meets RUS’s requirements for “dead-front.”
⑧Diameters of copper ground studs are as follows:
⑨Including bus-compartment terminals in Model PMH-4.
▼Specify catalog number suffix “-F12” for gear with stainless steel

enclosure.

□ Not available if Canadian Standards Association listing (catalog number suffix “-Z”) is specified.

TABLE CONTINUED ▶

Ground Stud Switch Fuse Bus Terminal Ground Pad

Diameter, in inches (mm) 1/2 (13) 7/16 (11) 7/16 (11) 7/16 (11)

. S&C Specification Bulletin 662A-31 11

Table 4. Optional Features—Continued

Item Suffix to be Added to Pad-Mounted Gear

Catalog Number Applicable to Models

Base spacer, compartmented to match enclosure, increases cable-termination height

Carbon steel

6 inches (152 mm) -K1 All models

12 inches (305 mm) -K2 All models

18 inches (457 mm) -K3 All models

24 inches (610 mm) -K4 All models

Stainless steel

6 inches (152 mm) -K11 All models

12 inches (305 mm) -K12 All models

18 inches (457 mm) -K13 All models

24 inches (610 mm) -K14 All models

Base spacer, noncompartmented, increases cable-termination height

Carbon steel

6 inches (152 mm) -K7 All models

12 inches (305 mm) -K8 All models

18 inches (457 mm) -K9 All models

24 inches (610 mm) -K10 All models

Stainless steel

6 inches (152 mm) -K17 All models

12 inches (305 mm) -K18 All models

18 inches (457 mm) -K19 All models

24 inches (610 mm) -K20 All models

12 S&C Specification Bulletin 662A-31 .

Table 4. Optional Features—Continued

Item Suffix to be Added to Pad-Mounted Gear

Catalog Number Applicable to Models

International crating⑩ -L71 All models

Switch- and bus-terminal adapters—for connection of two cables (through 750 kc mil) per terminal⑪⑫

-M1 All models

Cable guides, one at each terminal⑪⑬

In switch and bus compartments.

For conductor sizes No. 2 through 1000 kc mil

-M2 All models

In fuse compartments. For conductor sizes No. 2 through 4/0 -M3

PMH-4, -5, -6, -11, -19

PMH-7, -8, -9

PMH-12

Polymer-housed metal-oxide surge arresters⑭, base-mounted, at switch termi-nals and bus terminals in compartments 1 and 2 (removed for shipment)

9 kV -N6△ All models

10 kV -N7△ All models

12 kV -N8 All models

15 kV -N9 All models

18 kV -N10◇ All models except PMH-19

Metal-oxide surge arresters,⑬ base-mounted, at switch terminals and bus terminals in compartments 1 and 2 (removed for shipment)

3 kV -N11▽ All models

6 kV -N12▽ All models

TABLE CONTINUED ▶

⑩ Wood products used in the packaging are either hardwood or certified by the wood supplier as being “heat treated (kiln dried) to a core temperature of 133°F (56°C) for a minimum of 30 minutes.”

⑪ When catalog number suffix “-M1” or “-M2” is specified, cable-termination options (catalog number suffix “-U2” and “-U3”) cannot be accommodated. In addition, when catalog number suffix “-M1” and “-M2” are both specified, only one cable guide is provided at each switch terminal.

⑫ Space limitations prevent use of these adapters where surge arresters are to be installed

⑬ These devices extend below the base of the unit. Provide a cable pit or specify a base spacer that provides a 12‑inch (305 mm) or greater increase in cable-termination height.

⑭Surge arresters are base-mounted only (without isolators).
△Not applicable to 25‑kV models.
◇Not applicable to 14.4‑kV models.
▽A supplemental label is provided for catalog number suffixes “-N11”

and “-N12” indicating the voltage rating of the surge arresters furnished.

. S&C Specification Bulletin 662A-31 13

Table 4. Optional Features—Continued

Item Suffix to be Added to Pad-Mounted Gear

Catalog Number Applicable to Models

Mounting provisions for base-mounted surge arresters⑮, at switch terminals and bus terminals in compartments 1 and 2

9 kV, 10 kV, or 9/10 kV -P1△ All models

12 kV -P3 All models

15 kV -P4 All models

18 kV -P5◇ All models except PMH-19

Mounting provisions for porcelain cable terminators for single-conductor UD cable, at all cable-connected switch terminals and bus terminals

G&W PSC for No. 6 through 2/0◐, or G&W PAT for No. 4 through 250 kc mil copper or aluminum cable

-U2 All models

G&W PAT for 3/0 through 750 kc mil copper or 500 kc mil aluminum cable◐ -U3 All models

UL listing. Includes “UL listed” symbol on ratings label and nameplate -X◧◭ All 14.4 kV models

Canadian Standards Association listing. Includes viewing window with tamper-resistant cover in switch compartment door(s), and hazard-alerting labels and nameplate per CSA specification

-Z◀◁◑◧

PMH-3, -5, -7, -12

PMH-6, -9

PMH-11, -13, -19

PMH-10

⑮ These provisions accommodate Ohio Brass Type PDV (metal oxide), McGraw-Edison Type AZL19C (metal oxide), General Electric Tranquell® (metal oxide), or McGraw-Edison Type ES (silicon carbide) distribu-tion-class surge arresters. Surge arresters must be base-mounted only (without isolators).

◐ These devices extend below the base of the unit. Provide a cable pit or specify a base spacer.

△Not applicable to 25‑kV models.
◇Not applicable to 14.4‑kV models.
◧UL listing (catalog number suffix“-X”) cannot be furnished if

Canadian Standards Association listing (catalog number suffix “-Z”) is specified and vice versa.

◭ Not available if hexhead actuator for use in lieu of pentahead actuator on all Penta-Latch Mechanisms (catalog number suffix “-B1,” “-B2,” “-B11,” or “-B12”) is specified.

◀ Key interlocks (catalog number suffix “-C3” or “-C4”) must be speci-fied on gear with fuse compartment(s).

◁ Not available if mounting provisions for fault indicator with viewing window in switch compartment door(s) (catalog number suffix “-F2” or “-F12”) is specified.

◑ Not available if inner barrier panels (catalog number suffix “-G7) is specified.

14 S&C Specification Bulletin 662A-31 .

Table 5. SML-20 Power Fuse Components

Fuse-Unit End Fittings

Item Catalog Number

End-fittings (including silencer), for use with SMU-20 Fuse Units 3097

SMU-20® Fuse Units①

14.4 kV Nominal, 17 kV Max 25 kV Nominal, 27 kV Max

For a complete listing of available ampere ratings, speeds, and catalog numbers, refer to Table 8 on page 15 and Table 9 on page 16.

① These fuse units are usable in SM-20, SMD-20, SML-20, and SME-20 Mountings.

Table 6. SML-4Z Power Fuse Components

Holders

Item

Rating

Catalog NumberkV Amperes, MaxNom. Max

Holder (including silencer), for use with SM-4 Refill Units

14.4 17 200E 92352

25 27 200E 92353

SM-4® Refill Units①

14.4 kV Nominal, 17 kV Max 25 kV Nominal, 27 kV Max

For a complete listing of available ampere ratings, speeds, and catalog numbers, refer to Table 10 on page 17.

① These fuse units are usable in SM-4, SM-4Z, SML-4Z, and SME-4Z Mountings.

Table 7. Fault Fiter Electronic Power Fuse Components

Holders

Item

Rating

Catalog NumberkV Amperes, Cont.Nom. Max

Holder, for use with Fault Fiter Electronic Power Fuses

13.8 17 400 99412R1

25 29 200 99413R1

Interrupting Modules①

Item

Rating

Catalog NumberkV Amperes, Cont.Nom. Max

Interrupting module, for use with Fault Fiter Electronic Power Fuses

13.8 17 600 802600R2

25 29 600 803600R2

Control Modules①

For a complete listing of available types, TCC curve parameters, and catalog numbers, refer to Table 11 and Table 12 on page 18, and Table 13 on page 19.

① Interrupting modules and control modules rated 600 amperes contin-uous are also applicable for use in mountings rated 200 or 400 amperes continuous.

. S&C Specification Bulletin 662A-31 15

Table 8. SMU-20® Fuse Units (For use in SM-20 or SML-20 Mountings)①

14.4 kV Nominal, 17 kV Max

“K” Ratings “E” Ratings

Rating, Amperes

Catalog Number Rating, Amperes Catalog Number

Speed S&C “K”

TCC 165-2

Speed

S&C Std.

TCC 115-2

1 702001

Speed S&C Std.

TCC 153-2

S&C Slow

TCC 119-2

S&C Very Slow

TCC 176-2

3K 702003

6K 702006 5E 612005

8K 702008 7E 612007

10K 702010 10E 612010

12K 702012 13E 612013

15K 702015 15E 612015 712015

20K 702020 20E 612020 712020

25K 702025 25E 612025 712025

30K 702030 30E 612030 712030

40K 702040 40E 612040 712040

50K 702050 50E 612050 712050 602050

65K 702065 65E 612065 712065 602065

80K 702080 80E 612080 712080 602080

100K 702100 100E 612100 712100 602100

140K 702140 125E 612125 712125 602125

200K 702200 150E 612150 712150 602150

175E 612175 712175 602175

200E 612200 712200 602200

① These fuse units are equally suitable for use in SMD-20 Outdoor Distribution Mountings and for use with SME-20 Fuse Unit End-Fit-tings listed in S&C Specification Bulletin 665-31, “S&C Manual PME Pad-Mounted Gear” and in S&C Specification Bulletin 666-31, “S&C Remote Supervisory PME Pad-Mounted Gear.”

16 S&C Specification Bulletin 662A-31 .

Table 9. SMU-20® Fuse Units (For use in SM-20 or SML-20 Mountings)①

25 kV Nominal, 27 kV Max②

“K” Ratings “E” Ratings

Rating, Amperes

Catalog Number Rating, Amperes Catalog Number

Speed S&C “K”

TCC 165-2

Speed

S&C Std.

TCC 115-2

1 703001

Speed S&C Std.

TCC 153-2

S&C Slow

TCC 119-2

S&C Very Slow

TCC 176-2

3K 703003

6K 703006 5E 613005

8K 703008 7E 613007

10K 703010 10E 613010

12K 703012 13E 613013

15K 703015 15E 613015 713015

20K 703020 20E 613020 713020

25K 703025 25E 613025 713025

30K 703030 30E 613030 713030

40K 703040 40E 613040 713040

50K 703050 50E 613050 713050 603050

65K 703065 65E 613065 713065 603065

80K 703080 80E 613080 713080 603080

100K 703100 100E 613100 713100 603100

140K 703140 125E 613125 713125 603125

200K 703200 150E 613150 713150 603150

175E 613175 713175 603175

200E 613200 713200 603200

① These fuse units are equally suitable for use in SMD-20 Outdoor Distribution Mountings and for use with SME-20 Fuse Unit End-Fit-tings listed in S&C Specification Bulletin 665-31, “S&C Manual PME Pad-Mounted Gear” and in S&C Specification Bulletin 666-31, “S&C Remote Supervisory PME Pad-Mounted Gear.”

② Also suitable for protection of single-phase-to-neutral circuits (lines or transformers) on 20/34.5 GrY-kV systems.

. S&C Specification Bulletin 662A-31 17

Table 10. SM-4® Refill Units (For use in SM-4 and SML-4 Holders)①

Rating, Amperes

14.4 kV Nominal, 17 kV Max② 25 kV Nominal, 27 kV Max

Catalog Number Catalog Number

Speed S&C Std.

TCC 115-4

S&C Std.

TCC 115-4

1 122001R4 123001R4

2 122002R4 123002R4

Speed S&C Std.

TCC 153-4

S&C Slow

TCC 119-4

S&C Coord.

TCC 179-4

S&C Std.

TCC 153-4

S&C Slow

TCC 119-4

3E 122005R4 123005R4

5E 122007R4 123007R4

7E 122010R4 123010R4

10E 122015R4 123015R4

13E 122020R4 123020R4

15E 122025R4 252025R4 123025R4 253025R4

20E 122030R4 252030R4 123030R4 253030R4

25E 122040R4 252040R4 123040R4 253040R4

30E 122050R4 252050R4 123050R4 253050R4

40E 122060R4 252060R4 123060R4 253060R4

50E 122075R4 252075R4 123075R4 253075R4

65E 122100R4 252100R4 123100R4 253100R4

80E 122125R4 252125R4 123125R4 253125R4

100E 122150R4 252150R4 123150R4 253150R4

125E 122200R4 252200R4 123200R4 253200R4

150E 122250R4 252250R4 123250R4 253250R4

175E 122275R4 252275R4 123275R4 253275R4

200E 122300R4 252300R4 123300R4 253300R4

210E 382210R4●

① These refill units are also suitable for use with SME-4Z Holders listed in S&C Specification Bulletin 665-31, “S&C Manual PME Pad-Mounted Gear” and in S&C Specification Bulletin 666-31, “S&C Remote Supervi-sory PME Pad-Mounted Gear.”

② Rated 14.4 kV nominal, for use in SM-4 Holders rated 14.4 kV when applied in listed mountings rated 13.8 kV or in discontinued mountings rated 14.4 kV.

● This S&C Coordinating Speed refill unit should be applied where the maximum continuous load current does not exceed 200 amperes and where all fault currents below 1000 amperes will be cleared by another fuse.

18 S&C Specification Bulletin 662A-31 .

Table 11. Fault Fiter Fuse Control Modules—Underground Subloop① Type (TCC No. 422-7)

Continuous Current, Amperes, Max②

TCC Curve Parameters

Catalog NumberMinimum Pickup, Amperes, RMS

Short-Time Pickup, Amperes, RMS

Short-Time Delay Band

Instantaneous Pickup, Amperes, RMS

400 1300 2 3000 7020-C40P130S2T3

500 1300 1 3000 7020-C50P130S1T3

① This control module is applicable for protection of 15‑kV and 25‑kV class underground distribution subloops having the following parameters: maximum available fault current—14,000 amperes, RMS, symmetrical at 15 kV, 12,500 amperes, RMS, symmetrical at 25 kV;

maximum rated transformer kVA connected for residential circuits— 1200 kVA single-phase, 3600 kVA three-phase at 15 kV, 2400 kVA single-phase, 7200 kVA three-phase at 25 kV; with no capacitor banks or current-limiting fuses on the load side of the Fault Fiter fuse. If the maximum rated transformer kVA connected is greater than the values listed above, or if the application involves protection of circuits serving industrial, commercial, or institutional loads, contact the nearest S&C Sales Office.

② Control modules rated 600 amperes continuous are also applicable for use in mountings rated 200 amperes or 400 amperes continuous.

Table 12. Fault Fiter Fuse Control Modules—Inverse Curve Type (TCC No. 410-7)

Continuous Current, Amperes, Max①

Minimum Pickup, Amperes, RMS

Catalog Number

400 814040

500 814050

600 814060

700 814070

800 814080

1000 814100

1250 814125

1500 814150

① Control modules rated 600 amperes continuous are also applicable for use in mountings rated 200 amperes or 400 amperes continuous.

. S&C Specification Bulletin 662A-31 19

Table 13. Fault Fiter Fuse Control Modules—Time-Delayed Compound-Curve Type (TCC No. 421-7)

Continuous Current, Amperes, Max①

TCC Curve Parameters

Catalog NumberMinimum Pickup, Amperes, RMS

Short-Time Delay Band

High-Current Pickup, Amperes, RMS

High-Current Delay Band

Time Delay, ms

3000 8 7010-C40S1T3D8

6000 8 7010-C40S1T6D8

3000 8 7010-C40S2T3D8

6000 8 7010-C40S2T6D8

3000 8 7010-C40S3T3D8

6000 8 7010-C40S3T6D8

3000 8 7010-C40S4T3D8

6000 8 7010-C40S4T6D8

3000 8 7010-C60S1T3D8

6000 8 7010-C60S1T6D8

3000 8 7010-C60S2T3D8

6000 8 7010-C60S2T6D8

3000 8 7010-C60S3T3D8

6000 8 7010-C60S3T6D8

3000 8 7010-C60S4T3D8

6000 8 7010-C60S4T6D8

3000 8 7010-C80S1T3D8

6000 8 7010-C80S1T6D8

3000 8 7010-C80S2T3D8

6000 8 7010-C80S2T6D8

3000 8 7010-C80S3T3D8

6000 8 7010-C80S3T6D8

3000 8 7010-C80S4T3D8

6000 8 7010-C80S4T6D8

3000 8 7010-C110S1T3D8

6000 8 7010-C110S1T6D8

3000 8 7010-C110S2T3D8

6000 8 7010-C110S2T6D8

3000 8 7010-C110S3T3D8

6000 8 7010-C110S3T6D8

3000 8 7010-C110S4T3D8

6000 8 7010-C110S4T6D8

① Control modules rated 600 amperes continuous are also applicable for use in mountings rated 200 amperes or 400 amperes continuous.

20 S&C Specification Bulletin 662A-31 .

Table 14. Switch Blades①

Item

Rating

Catalog NumberkV Amperes, Cont.

Nom. Max

Switch blade, for use in lieu of SMU-20 Fuse Unit in SML-20 Mounting

14.4 17 200 5432

25 27 200 5433

Switch blade, for use in lieu of SML-4Z Holder in SML-4 Mounting

14.4 17 200 5442

25 27 200 5443

Switch blade, for use in lieu of Fault Fiter fuse holder in Fault Fiter fuse mounting

14.4 17 400 3222

25 29 200 3223R1

① When switch blades are used in lieu of fuses, the Uni-Rupter Interrupter associated with these switches can carry and interrupt load currents up to and including the emergency peak-load capabilities of the SML power fuses, or up to 400 amperes at 14.4 kV and 200 amperes at 25 kV for Fault Fiter Electronic Power Fuses. Furthermore, the switches with a Uni-Rupter Interrupter have fault-closing ratings equal to those of S&C Power Fuses with Uni-Rupter Interrupters (refer to the “Application Notes” section on page 2). The momentary and one-second ratings of the switches equal the short-circuit ratings of the pad-mounted gear.

Table 15. Accessories

Item Catalog Number

Grounding jumpers, set of three, with eye-type clamps for installa-tion with a standard shotgun clamp stick 3‑foot (914‑mm) cable length 4210

Shotgun clamp sticks for use with separable connectors and voltage testers

771/2 inches (1969 mm) 9933-150

1011/2 inches (2578‑mm) 9933-151

Storage bag, heavy canvas

For grounding jumpers 9933-149

For shotgun clamp stick 78 inches (1981 mm) 9933-152

102 inches (2591 mm) 9933-153

Voltage tester with audio and visual signals, includes voltage tester, batteries, adapter for shotgun clamp sticks, and storage case① 9931-072

Pentahead socket, for 1/2‑inch drive 9931-074

① For ultimate users other than electric utilities, also specify a shotgun clamp stick of the appropriate length.

Table 16. Touch-Up Kit Components—Aerosol Coatings in 12-Ounce Cans

Item Catalog Number

S&C Light Gray Outdoor Finish 9999-080

S&C Olive Green (Munsell 7GY3.29/1.5) Outdoor Finish 9999-058

S&C Red-Oxide Primer 9999-061

Table 17. Connector

Illustration Description Accommodating Connector Catalog Number

Bronze body, tin-plated, two galvanized steel bolts, two Belleville washers

No. 2 solid through 500 kc mil stranded copper or aluminum 4745

. S&C Specification Bulletin 662A-31 21 kV, Nominal A1● A2● B C D E1 E2 F G1 G2 G3 H M W

14.4 97/8

(251) 111/8

(283) 51/8

(130)

(432) 403/4

(1035) 127/8

(327) 71/2

(191) 373/4

(959)

(152) 93/4

(248) 93/4

(248)

(1118)

(864) 347/8

(886)

25 141/8 (359)

151/4

(387) 71/8

(181) 421/2

(1080) 593/4

(1518) 133/4

(349) 95/8

(244) 563/4

(1441) 71/2

(191)

(254) 121/2

(318)

(1397) 421/2

(1080)

(1092)

● When catalog number suffix “-M1,” “-U2,” or “-U3” is specified, cable-termination locations will be slightly affected. Consult the nearest S&C Sales Office for details.

Model PMH-3

14.4 kV and 25 kV Nominal

1½ (38)

2¾ (70)

2¾ (70)

(152)

1½ (38)

Dimensions in inches (mm)

FOUR 5/8 (16) DIA. ANCHOR

BOLTS—BY USER

1½ (38) MIN.

M (103° DOOR OPENINGS)

ANCHOR BRACKET–BY S&C

APPROXIMATE

CABLE TERMINATION

LOCATIONS

GASKET

CONCRETE PAD

ENCLOSURE

ANCHOR BOLt DetAIL

ANCHOR BOLt pLAN CONNeCtION DIAGRAM

FRONt VIeW

W

H

SIDe VIeW

W

F

C

B

G2

G1 G1 e2 e1

A2

A1

G3

F

D

22 S&C Specification Bulletin 662A-31 .

Model PMH-4

14.4 kV and 25 kV Nominal kV, Nominal

A1 A2● B C D E F G1 G2 H J K M W

14.4

(178) 111/8

(283) 51/8

(130) 271/2

(699) 403/4

(1035) 77/8

(200) 373/4

(959) 93/4

(248) 93/4

(248)

(1118) 101/2

(267) 93/4

(248)

(864) 347/8

(886)

111/4

(286) 151/4

(387) 71/8

(181) 421/2

(1080) 593/4

(1518) 95/8

(244) 563/4

(1441)

(254) 121/2

(318)

(1397) 111/2

(292) 121/2

(318) 421/2

(1080)

(1092)

● When catalog number suffix “-M1,” “-U2,” or “-U3” is specified, cable-termination locations will be slightly affected. Consult the nearest S&C Sales Office for details.

Dimensions in inches (mm)

ANCHOR BRACKET–BY S&C

GASKET

CONCRETE PAD

ENCLOSURE

ANCHOR BOLt DetAIL

1½ (38)

1½ (38)

1½ (38) MIN.

2¾ (70)

2¾ (70)

FOUR 5/8 (16) DIA. ANCHOR

BOLTS—BY USER

M (103° DOOR OPENINGS)

APPROXIMATE

CABLE TERMINATION

LOCATIONS

ANCHOR BOLt pLAN CONNeCtION DIAGRAM

FRONt VIeW SIDe VIeW

H

F D

W

B e

W

C

KK

G1

J

A1

A2

G2

. S&C Specification Bulletin 662A-31 23 kV, Nominal A1● A2 B C D E F G H J K M W

14.4 97/8

(251)

(178) 51/8

(130)

(787) 543/4

(1391) 127/8

(327) 513/4

(1314)

(152)

(1118) 47/8

(124) 93/4

(248)

(864) 347/8

(886)

141/8

(359) 111/4

(286) 71/8

(181)

(1295) 681/4

(1734) 133/4

(349) 651/4

(1657) 71/2

(191)

(1397) 65/8

(168) 121/2

(318) 421/2

(1080)

(1092)

● When catalog number suffix “-M1,” “-U2,” or “-U3” is specified, cable-termination locations will be slightly affected. Consult the nearest S&C Sales Office for details.

Model PMH-5

14.4 kV and 25 kV Nominal

Dimensions in inches (mm)

ANCHOR BRACKET–BY S&C

GASKET

CONCRETE PAD

ENCLOSURE

ANCHOR BOLt DetAIL

(152)

FRONt VIeW SIDe VIeW

ANCHOR BOLt pLAN CONNeCtION DIAGRAM

M (103° DOOR OPENINGS)

APPROXIMATE

CABLE TERMINATION

LOCATIONS

1½ (38)

1½ (38)

1½ (38) MIN.

FOUR 5/8 (16) DIA. ANCHOR

BOLTS—BY USER

2¾ (70)

2¾ (70)

W

H

G e

G

A1

A2

C

B

KK

W

J

24 S&C Specification Bulletin 662A-31 .

kV, Nominal A1● A2 B C D E F G H J K L M W

14.4 97/8

(251)

(178) 51/8

(130)

(1016) 633/4

(1619) 127/8

(327) 603/4

(1543)

(152)

(1118) 43/4

(121) 93/4

(248) 143/4

(375)

(864)

(1702)

141/8

(359) 111/4

(286) 71/8

(181) 621/2

(1588) 793/4

(2026) 133/4

(349) 763/4

(1949) 71/2

(191)

(1397)

(152) 121/2

(318) 161/2

(419) 411/2

(1054)

(2083)

● When catalog number suffix “-M1,” “-U2,” or “-U3” is specified, cable-termination locations will be slightly affected. Consult the nearest S&C Sales Office for details.

Model PMH-6

14.4 kV and 25 kV Nominal

Dimensions in inches (mm)

ANCHOR BRACKET–BY S&C

SIDe VIeW

D

FW

W

H

(152)

(152)

1½ (38)

1½ (38)

M (103° DOOR OPENINGS)

2¾ (70)

2¾ (70)

1½ (38) MIN.

FOUR 5/8 (16) DIA. ANCHOR

BOLTS—BY USER

FRONt VIeW

GASKET

CONCRETE PAD

ENCLOSURE

ANCHOR BOLt DetAIL

CONNeCtION DIAGRAM

ANCHOR BOLt pLAN

APPROXIMATE

CABLE TERMINATION

LOCATIONS

C

B e

GG GG

e

F

J K L

A1

A2

. S&C Specification Bulletin 662A-31 25

Model PMH-7

14.4 kV and 25 kV Nominal kV, Nominal A1● A2 B C D E F G H J K L M W

14.4 97/8

(251)

(178) 51/8

(130)

(1016) 633/4

(1619) 127/8

(327) 603/4

(1543)

(152)

(1118) 43/4

(121) 93/4

(248) 143/4

(375)

(864)

(1702)

141/8

(359) 111/4

(286) 71/8

(181) 621/2

(1588) 793/4

(2026) 133/4

(349) 763/4

(1949) 71/2

(191)

(1397)

(152) 121/2

(318) 161/2

(419) 411/2

(1054)

(2083)

● When catalog number suffix “-M1,” “-U2,” or “-U3” is specified, cable-termination locations will be slightly affected. Consult the nearest S&C Sales Office for details.

Dimensions in inches (mm)

ANCHOR BRACKET–BY S&C

SIDe VIeW

(152)

M (103° DOOR OPENINGS)

1½ (38) MIN.

FOUR 5/8 (16) DIA. ANCHOR

BOLTS—BY USER

FRONt VIeW

GASKET

CONCRETE PAD

ENCLOSURE

ANCHOR BOLt DetAIL

CONNeCtION DIAGRAM

ANCHOR BOLt pLAN

J J

B

K KL

W

L

W

H

2¾ (70)

APPROXIMATE CABLE

TERMINATION LOCATIONS

2¾ (70)

1½ (38)

1½ (38)

A2

F e

GG

26 S&C Specification Bulletin 662A-31 .

kV, Nominal A1● A2 A3● B C D E1 E2 F G1 G2 H J K L M W

14.4 97/8

(251)

(178)

(483) 51/8

(130)

(1016) 633/4

(1619) 127/8

(327) 83/4

(222) 603/4

(1543)

(152) 91/4

(235)

(1118) 43/4

(121) 93/4

(248) 143/4

(375)

(864)

(1702)

141/8

(359) 111/4

(286) 183/4

(476) 71/8

(181) 621/2

(1588) 793/4

(2026) 133/4

(349) 81/16

(205) 763/4

(1949) 71/2

(191) 121/2

(318)

(1397)

(152) 121/2

(318) 161/2

(419) 411/2

(1054)

(2083)

● When catalog number suffix “-M1,” “-U2,” or “-U3” is specified, cable-termination locations will be slightly affected. Consult the nearest S&C Sales Office for details.

Model PMH-8

14.4 kV and 25 kV Nominal

Dimensions in inches (mm)

1½ (38)

1½ (38)

B

JJ KK

W

W F D

L L

2¾ (70)

2¾ (70)

A2

A3 A1 e1

G1G2 G1G2 e2

M (103° DOOR OPENINGS)

ANCHOR BOLt pLAN

CONNeCtION DIAGRAM

SIDe VIeWFRONt VIeW

ANCHOR BRACKET–BY S&C

GASKET

CONCRETE PAD

ENCLOSURE

ANCHOR BOLt DetAIL

1½ (38) MIN.

FOUR 5/8 (16) DIA. ANCHOR

BOLTS—BY USER

APPROXIMATE CABLE

TERMINATION LOCATIONS

H

F

(152)

C

. S&C Specification Bulletin 662A-31 27 kV, Nominal A1● A2 B C D E F G H J K L M W

14.4 97/8

(251)

(178) 51/8

(130)

(1016) 633/4

(1619) 127/8

(327) 603/4

(1543)

(152)

(1118) 43/4

(121) 93/4

(248) 143/4

(375)

(864…