36E77619R0038-009.pdf
PDF 352 KB Posted
- Solicitation number
- 36E77619R0038
About this file
36E77619R0038 Attachment 4 - NFS Refrig Freezers Controls ICRA Preliminary.pdf
View the file
Other files
| File | Type | Posted |
|---|---|---|
| 36E77619R0038-005.pdf | ||
| 36E77619R0038-007.docx | DOCX document | |
| 36E77619R0038-003.pdf | ||
| 36E77619R0038-012.pdf | ||
| 36E77619R0038-001.docx | DOCX document | |
| 36E77619R0038-010.pdf | ||
| 36E77619R0038-008.zip | ZIP file | |
| 36E77619R0038-004.pdf | ||
| 36E77619R0038-013.docx | DOCX document | |
| 36E77619R0038-002.pdf | ||
| 36E77619R0038-006.docx | DOCX document | |
| 36E77619R0038-011.pdf | ||
| 36E77619R0038-000.docx | DOCX document |
Show all 13
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Overton Brooks VAMC Infection Prevention & Control Construction Risk Assessment (ICRA)
*A preliminary ICRA is required for contracting purposes only; do not post during construction. The FINAL ICRA must be posted at the construction site.
Project: NFS Refrig, Freezers & Controls 667-18-115 Preliminary Assessment* by: Vickie L. Moore Date: 1/25/19 FINAL ICRA Determined and Processed by: ______________________________Final Date: ________________
STEP ONE: CIRCLE the Type of Construction Project based on scope and expected activity (Type A-D)
TYPE
A
Inspection and Non-Invasive Activities. Includes, but is not limited to:
removal of ceiling tiles for visual inspection only, e.g., limited to 1 tile per 50 square feet painting (but not sanding) wallcovering, electrical trim work, minor plumbing, activities which do not generate dust or require cutting of walls or access to ceilings other than for visual inspection.
TYPE
B
Small scale, short duration activities which create minimal dust Includes, but is not limited to:
installation of telephone and computer cabling access to chase spaces cutting of walls or ceiling where dust migration can be controlled.
TYPE
C
Work generates a moderate/high level of dust or requires demolition/removal of any fixed building components or assemblies Includes, but is not limited to:
sanding of walls for painting or wall covering removal of floorcoverings, ceiling tiles and casework new wall construction minor duct work or electrical work above ceilings major cabling activities any activity which cannot be completed within a single work shift.
TYPE
D
Major demolition and construction projects Includes, but is not limited to:
activities which require consecutive work shifts requires heavy demolition, removal of a complete cabling system, or excavation new construction.
STEP TWO: CIRCLE the affected Patient Risk Groups. If more than one risk group will be affected, select the higher risk group.
Low Risk Medium Risk High Risk Highest Risk
Office areas Kitchen storage area Public access, hallways, elevator Lobby
Non-clinical vacated engineering space
Cardiology Echocardiography Endoscopy Nuclear Medicine Physical Therapy Radiology/MRI Respiratory
Therapy Kitchen – food preparation area
BN16, 9A, 10
Step Down Unit Emergency Room Laboratories (specimen) Medical Units Outpatient Surgery Pharmacy Post Anesthesia Care Unit Surgical Units Minor Procedure Rooms Sterile Supply storage/distribution
Immunocompromised patient care areas
Cardiac Cath Lab Sterile Processing Service Preparation Area Decontamination Area
Intensive Care Unit Negative pressure isolation rooms Oncology Operating rooms
STEP THREE: Using the IC Matrix CIRCLE the Class of Precautions as determined by Construction Type and Patient Risk Construction Project Type
Patient Risk Group TYPE A TYPE B TYPE C TYPE D
IC
M at ri x LOW Risk Group I II II III/IV
MEDIUM Risk Group I II III IV
HIGH Risk Group I II III/IV IV
HIGHEST Risk Group II III/IV III/IV IV
Preliminary ICRA Approved Final ICRA Approved 1/25/2019
X Vickie L. Moore Vickie L. Moore MA, CIC, VHA-CM Infection Prevention Program Manager Signed by: VICKIE L. MOORE 193380
X Vickie L. Moore MA, CIC, VHA-CM Infection Prevention Program Manager
Overton Brooks VAMC Infection Control Precautions for Class III Projects
Based on the Infection Control Risk Assessment of this construction/remodel project, the following activities are required.
Project: NFS Refrigerator, Freezer & Control #667-18-115 for BN10 Dry Storage ONLY
During Construction Project: Upon Completion of Project:
C la ss
II
I
1. Complete all critical barriers i.e. sheetrock, plywood, plastic, to seal area from non-work area before construction begins. Construct the BN10 barrier with no entrance to the site.
2. Keep doors to the project area closed.
3. Block off and seal air vents if the HVAC system is removed or isolated.
4. Place dust mat at entrance and exit of work area
5. Remove or Isolate HVAC system in area where work is being done if required to prevent contamination of adjacent areas.
6. Maintain negative air pressure within work site with filtration and pressure monitoring. Utilize HEPA equipped air filtration units if air is recirculated within the building.
7. Construction Waste/Debris
a. Transport in tightly covered container,
b. Containers without tight fitting solid lids must have covering taped in place BEFORE transport outside the project area,
c. Outside of containers must be cleaned when visibly soiled, and
d. When removing construction debris, utilize only the designated construction route.
8. Minimize construction worker traffic within the facility.
9. Provide appropriate secure temperature controlled storage for refrigerated/frozen food and pharmaceutical storage.
10. Provide for safe protected transport of pharmaceuticals and bulk refrigerated and frozen food from storage area to production areas.
1. Wipe work surfaces with cleaner/disinfectant.
2. Contain construction waste before transport in tightly covered containers.
3. Periodically clean outside of construction waste transport container.
4. Do not remove barriers from work area until completed project is inspected by Engineering Service, Infection Prevention and the area is thoroughly cleaned.
5. Remove barrier materials carefully to minimize spreading of dirt and debris associated with construction.
6. Wet mop area with cleaner/disinfectant.
7. Upon completion, restore HVAC system where work was performed.
Maintain control measures until ALL Work is completed. Exceptions must be approved by Infection Prevention on a case by case basis.
Preliminary Final
X Vickie L. Moore Vickie L. Moore MA, CIC, VHA-CM Infection Prevention Program Manager Signed by: VICKIE L. MOORE 193380
X Vickie L. Moore MA, CIC, VHA-CM Infection Prevention Program Manager
| STEP ONE: CIRCLE the Type of Construction Project based on scope and expected activity (Type A-D) |
| STEP THREE: Using the IC Matrix CIRCLE the Class of Precautions as determined by Construction Type and Patient Risk |
| TYPE A |
| TYPE D |
| TYPE C |
| TYPE B |
File details come from the government source that posted it.