This document is a set of architectural bid documents for the Fort Bliss National Cemetery Expansion project located at 5200 Fred Wilson Avenue, El Paso, Texas. The drawings cover demolition plans, floor plans, exterior elevations, roof plans, interior details, and schedules for three buildings: Building 2101 (Admin Building), Building 3003 (Maintenance Building), and Building 3004 (PIC/Restroom Building).
The demolition scope includes removal of existing partitions, floor finishes, ceiling systems, roofing assemblies, doors, windows, mechanical and electrical equipment, wall finishes, and exterior elements including clay tile roofing, stucco, gutters, and downspouts. The contractor must coordinate all demolition work with the owner and preserve existing structural support members, protect non-removal items, and patch all disturbed areas to match adjacent finishes. Key construction requirements include installing new partitions with fire ratings up to two hours, new floor and wall finishes, roofing with tapered mission style clay tiles, stucco exterior finishes, new doors and frames (hollow metal and aluminum), new mechanical systems, and plumbing fixtures. The project specifies extensive finishes including paint systems, resilient base, static dissipative flooring, and solid surface countertops. The documents identify specific salvage requirements including 300-400 clay roof tiles to be stored on pallets and relocated to cemetery property, existing handrails to be refinished and reinstalled, and various mechanical and electrical components to be removed and relocated. The owner reserves the right of first refusal on all salvaged items. Construction must comply with fire-rated assembly requirements, accessible design standards, and coordinate across all trades including structural, mechanical, electrical, plumbing, and technology systems.
View the file
Other files
Show all 13
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
DEMOLITION GENERAL NOTES
1. CONTRACTOR MUST COORDINATE ALL DEMOLITION WORK, PHASING AND SEQUENCING WITH THE
OWNER. ANY INFORMATION REGARDING SEQUENCING PROVIDED IN THESE DOCUMENTS IS FOR
ARCHITECT - OWNER PLANNING PURPOSES ONLY, UNLESS NOTED OTHERWISE.
2. CONTRACTOR MUST BE RESPONSIBLE FOR COORDINATING WITH ALL TRADES FOR THE
DEMOLITION WORK REQUIRED FOR THIS PROJECT.
3. WHERE PARTITIONS ARE INDICATED TO BE REMOVED, REMOVE PARTITION ALONG WITH ALL
ITEMS CONTAINED WITHIN, INCLUDING DOORS, FRAMES, HARDWARE, SIDELIGHTS, WINDOWS,
MECHANICAL AND ELECTRICAL EQUIPMENT, ETC. TO STRUCTURE ABOVE, UNLESS NOTED
OTHERWISE.
4. WHERE FLOOR FINISH IS INDICATED TO BE DEMOLISHED, REMOVE FINISH TO FLOOR SLAB AS
REQUIRED AND PREPARE SLAB SURFACE FOR SCHEDULED FINISHES WITHIN AREA TO BE
REMODELED, UNLESS NOTED OTHERWISE. REMOVE CARPET TILE UP TO THE FACE OF THE NEW TE
ROOM WALLS. PROTECT CARPET FOR REINSTALLATION AS NECESSARY. SEE FINISH SCHEDULE
FOR EXISTING FLOOR FINISHES TO REMAIN UNDISTURBED.
5. WHERE CEILING IS INDICATED TO BE DEMOLISHED, REMOVE CEILING SUSPENSION SYSTEM
ALONG WITH ALL ASSOCIATED MECHANICAL AND ELECTRICAL ITEMS, UNLESS NOTED OTHERWISE.
SEE MECHANICAL AND ELECTRICAL DRAWINGS FOR EXTENT OF CONDUIT, PIPING AND DUCTWORK DEMOLITION WITHIN AREA TO BE REMODELED. CUT CEILING GRID AND CEILING TILES ONLY TO ALLOW FOR THE CONSTRUCTION OF THE TE ROOM WALLS. WHERE CEILING IS INDICATED TO BE
DEMOLISHED, MODIFY CEILING GRID AND CUT CEILING TILES AS NECESSARY TO ENSURE
ORIGINAL FINISHED CEILING LAYOUT IS MAINTAINED. REINSTALL WALL MOLDING IN ALIGNMENT WITH EXISTING WALL MOLDING, MITER CUT OUTSIDE CORNER, AND PROVIDE STABILIZER CLIPS AS
NECESSARY. REPLACE ALL CEILING TILES DAMAGED OR SOILED DURING THE COURSE OF
CONSTRUCTION WITH NEW TILES TO MATCH EXISTING.
6. WHERE INDICATED, REMOVE ALL WALL/PARTITION EXISTING FINISHES AND PREPARE THE
SURFACES FOR SCHEDULED FINISHES, SEE FINISH SCHEDULE FOR FINISHES.
7. ALL DISTURBED AREAS, WALLS, PARTITIONS, FLOORS, ETC, DAMAGED BY DEMOLITION WORK
MUST BE PATCHED TO MATCH ADJACENT AREA.
8. OWNER RESERVES THE RIGHT OF FIRST REFUSAL OF ALL SALVAGED ITEMS SUCH AS: DOORS, LIGHT FIXTURES, PLUMBING FIXTURES ETC.
9. SALVAGED ITEMS SCHEDULED FOR REUSE MUST BE CLEANED, RESTORED AND/OR REFINISHED
TO LIKE NEW CONDITION, UNLESS NOTED OTHERWISE.
10. DO NOT REMOVE ANY EXISTING STRUCTURAL SUPPORT MEMBERS SUCH AS COLUMNS, BEAMS, JOISTS, LOAD-BEARING PARTITIONS ETC, UNTIL ADEQUATE PERMANENT OR TEMPORARY
SUPPORT IS IN PLACE. ALL EXISTING STRUCTURAL MEMBERS MUST BE ADEQUATELY PROTECTED, COORDINATE WITH STRUCTURAL ENGINEER.
11. SEE STRUCTURAL, MECHANICAL AND ELECTRICAL DRAWINGS FOR RELATED DEMOLITION AND
PREP WORK.
12. WALL AND CEILING MOUNTED ITEMS SHOWN DASHED, SUCH AS WALL CABINETS, SHELVING, CUBICLE CURTAIN TRACKS, PROJECTION SCREENS ETC, MUST BE REMOVED, UNLESS NOTED
OTHERWISE.
13. WITHIN ALL EXISTING ROOMS/SPACES RECEIVING SCHEDULED FLOOR, OR WALL, OR CEILING
FINISHES, REMOVE ALL EXISTING FLOOR, OR WALL, OR CEILING FINISHES DOWN TO THE
SUBSTRATE. INCLUDE THE REMOVAL OF ALL ITEMS LOCATED WITHIN THE EXISTING FINISH
REMOVALS UNO PATCH AND PREP ALL SUBSTRATES TO RECEIVE SCHEDULED FINISHES. FOR
ADDITIONAL INFORMATION, SEE KEYNOTED ITEMS, FINISH PLANS AND/OR SCHEDULES,
STRUCTURAL, MECHANICAL AND ELECTRICAL.
14. SALVAGE CLAY ROOFING TILE: SALVAGE 300-400 OF THE BEST CONDITIONED ROOF TILES AND PLACE ON LEVEL PALLETS. DISPOSE OF ALL OTHER REMOVED CLAY TILE. PALLETS MAY BE NEW OR REUSED FROM THE ORIGINAL TILE DELIVERY. TIGHTLY SECURE TILE ON PALLETS AND COVER WITH A PROTECTIVE WATERPROOF COVERING THAT IS ADEQUATELY VENTILATED. STACK TILE IN
AN ORGANIZED, STABLE MANNER TO PREVENT SHIFTING AND SLIDING WHILE IN STORAGE.
PROVIDE SPACE BETWEEN EACH TILE TO ALLOW AIR FLOW AND VENTILATION. RELOCATE BOTH
PALLETS TO STORAGE LOCATION(S) ON CEMETERY PROPERTY, WHERE DIRECTED BY THE VA.
15. THE CONTRACTOR SHALL PRESERVE AND PROTECT ALL STRUCTURES, EQUIPMENT, AND
VEGETATION (SUCH AS TREES, SHRUBS, AND GRASS) ON OR ADJACENT TO THE WORK SITE,
WHICH ARE NOT TO BE REMOVED AND WHICH DO NOT UNREASONABLY INTERFERE WITH THE
WORK REQUIRED UNDER THIS CONTRACT. REFER TO GENERAL REQUIREMENTS SPECIFICATION
SECTION 010002.
DEMOLITION PLAN SYMBOLS
EXISTING WALL TO
REMAIN
WALL OR
PARTITION TO BE
REMOVED
EXISTING DOOR
AND FRAME TO
REMAIN
KEY NOTE
A
GRIDLINE
NOTE: NOT ALL SYMBOLS MAY BE USED ON EACH PLAN
EXISTING DOOR
AND FRAME TO BE
DEMOLISHED
DASHED LINE
INDICATES ITEM TO
BE REMOVED (UNO)
DE10
REMOVE ALL
STUCCO FROM WALL
AND ENTRANCE
CANOPY IN IT'S
ENTIRETY.
AREA OF DEMO
NIC
EXISTING
ADMIN
STAFF
EXISTING
STORAGE
EXISTING
PROGRAM
SPECIALIST
EXISTING
UNISEX
TOILET
EXISTING
RECEPTION
EXISTING
CONFERENCE
EXISTING
CORRIDOR
EXISTING
OPERATIONS
EXISTING
DIRECTOR
EXISTING
ALCOVE
EXISTING
MENS
EXISTING
STAIR
EXISTING
BREAKROOM
DP4
DP6
2101-
AD201
2101-
AD201
2101-
AD201
2101-
AD201
DP13
DP12
DP12 DP12
DP12
DP12
DP12DP12
DN
DN
EX CONC RAMP
SLOPE DOWN
EX CONC RAMP
SLOPE DOWN
DP10
EXISTING
ADMIN
OFFICER
DP9
DP8
+/- 9'-0 5/8" +/- 6'-0" +/- 18'-3 1/2" +/- 9'-6 1/2" +/- 9'-4"
DP8
DP8
3'
-0
5'
-2
7'-0" DEMO
DP2
DP9
DP7
DP15
D N
DP2
DP2
DP5
DP3
5'-2" DEMO
E X
C O
N C
S T
A
IR
5' -3
/4
D
E M
O
DP14
E X
B U
LL
E
TI
N
B O
A R
DDP16
DP17
DEMOLITION PLAN KEYED NOTES
NOTE: NOT ALL KEYED NOTES MAY BE USED ON EACH PLAN
DP1 DEMO CHAIN LINK GATE AND ASSOCIATED FASTENERS
DP2 GREY DASHED LINE DENOTES EDGE OF ROOF OVERHANG ABOVE
DP3
DEMO GYPSUM BD/PLASTER FINISH DOWN TO STUD FRAMING FOR
ENTIRETY OF PARTITION, ON SIDE OF PARTITION WHICH WILL SERVE NEW
'TE ROOM'
DP4
CAREFULLY REMOVE DRINKING FOUNTAIN AND SALVAGE FOR RELOCATION
IN THE PIC BUILDING, BUILDING 3004 - SEE PLUMBING
DP5
REMOVE EXISTING FLOOR, WALL AND ACT CEILING FINISHES IN HATCHED
AREA
DP6
DEMO EXISTING WALL CABINETS, BASE CABINETS, COUNTERTOP AND SINK
- SEE PLUMBING
DP7
REMOVE AND SALVAGE AWNING POSTS AS NECESSARY TO COMPLETE
STUCCO SCOPE OF WORK
DP8
REMOVE AND SALVAGE ALL EXISTING HAND RAILS AT STAIR AND RAMP
FOR REFINISHING AND REINSTALLATION AFTER STUCCO WORK IS
COMPLETE. SEE FLOOR PLAN FOR REFINISHING OF THESE ELEMENTS.
DP9
EXISTING PARTIAL HEIGHT STUCCO WALL W/ CONCRETE CAP (CAP NOT
SHOWN FOR CLARITY). REMOVE STUCCO SYSTEM FROM WALL IN IT'S
ENTIRETY IN PREPARATION FOR NEW
DP10
EXISTING FLOOR DRAIN TO REMAIN. PROTECT FROM CONSTRUCTION
DEBRIS DURING CONSTRUCTION
DP11
REMOVE AND DISPOSE OF EXISTING TELECOMMUNICATIONS CABINET.SEE
FIRST FLOOR PLANS FOR LOCATION OF NEW TELECOMMUNICATIONS
ENCLOSURE (TE) ROOM
DP12
REMOVE AND DISPOSE OF EXISTING DOWNSPOUT, BRACKETS AND
FASTENERS
DP13 REMOVE AND RELOCATE EXISTING PAPER SHREDDER
DP14
REMOVE AND RELOCATE OR DISPOSE OF THE EXISTING 8'X4' GLASS
ENCASED BULLETIN BOARD WITHIN THE FACILITY AS DIRECTED BY THE VA
COR.
DP15
EXISTING VENT PIPE TO REMAIN. IF NECESSARY FOR STUCCO
REPLACEMENT, REMOVE AND SALVAGE FOR REINSTALLATION AFTER
STUCCO WORK IS COMPLETE - SEE PLUMBING
DP16
REMOVE AND SALVAGE EXISTING TRIM BOTH SIDES OF DOOR AS
NECESSARY TO INSTALL NEW DOOR AND FRAME. IF TRIM IS DAMAGED
DURING DEMOLITION, PROVIDE NEW TRIM TO MATCH EXISTING
DP17 DEMO EXISTING TRIM BOTH SIDES OF DOOR
1/4" = 1'-0"
FIRST LEVEL DEMOLITION PLAN
I hereby certify that this plan, specification or report was prepared by me or under my direct supervision and that I am a duly Licensed Architect under the laws of the State of Minnesota.
Name:
Date:
License number:
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
BID DOCUMENTS
NOT SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
DESIGNER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
BID DOCUMENTS
IRRIGATION:
AQUA ENGINEERING
300 BOARDWALK DRIVE
UNIT 4B
FORT COLLINS,CO 80525
970.372.6104
JD LEONARD
GEOTECHNICAL:
TERRACON
6460 HILLER STREET
SUITE A
EL PASO, TX 79925
915.778.5233
IVAN AVELAR
COST ESTIMATING:
OCMI
2100 NORTH GREENVILLE AVENUE
SUITE 1150
RICHARDSON, TX 75082
469.431.0571
RAYMOND BODO
FIRE / L0W VOLTAGE / SECURITY:
IMEG
623 26TH AVENUE
ROCK ISLAND, IL 61201
309.781.3770
MATT SNYDER / PETE MCGHEE
CHRISTINA MCDANIEL
06/15/2026
52909
C U s e rs \P u b lic \D o c u m e n ts
\R e v it P ro je c ts
\1
-A D
M
IN
-A -R c m c d a n ie l@ a e
-m n
.c o m .r v t
/1
/2
:5
:2
P
M
2101- AD111
ADMIN BLDG - FIRST LEVEL DEMOLITION PLAN FT BLISS NATIONAL CEMETERY
EXPANSION
5200 FRED WILSON AVENUE, EL PASO,TEXAS
886CM3026
JUNE 15, 2026 CM RG
18528
0 4' 8'2'
Revisions: Date: 83 of 155
BASE BID
FIRST LEVEL
100'-0"
DE1
DE2
DE7
DE2DE4
DE1
DE2
DE5
DE10DE11 TYPTYP
DE13
DE5
FIRST LEVEL
100'-0"
DE1
DE2
DE4
DE2
DE1
DE5
DE6
DE2
DE9
TYP
DE14DE14
T .O
. R
ID
G E
C A
P
8'
-0
(E X
IS
T
IN
G
DE15
DE5
DE8
FIRST LEVEL
100'-0"
DE1
DE5
DE2
DE7
DE1
DE2
DE2
DE4 DE6 DE6
DE2
DE8
DE9
DE8
3' -6
TYP
DE14
DE14
DE13
DE15 BEYOND
DE5
FIRST LEVEL
100'-0"
DE1
DE5
DE2
DE2
DE4
DE2
DE6
DE7 FOREGROUND
DE9
DE9
DE10DE10
DE10
DE11
TYP
TYP
DE13
DE14
DE14
DE14
1'
-6
E X
IS
T
IN
G
DE5
WALLS BEYOND SHOWN
GRAY TONED
DEMOLITION ELEVATION KEYED NOTES
NOTE: NOT ALL KEYED NOTES MAY BE USED ON EACH ELEVATION
DE1
REMOVE ALL EXISTING CLAY TILE ROOFING ASSEMBLY, ASSOCIATED
UNDERLAYMENT, ROOF FLASHINGS, EAVE CLOSERS AND TREATED WOOD
BLOCKING, EXCEPT WHERE NOTED OTHERWISE. EXISTING WOOD SHEATHING
TO REMAIN, SALVAGE A PORTION OF THE REMOVED TILES FOLLOWING THE
DIRECTION PROVIDED IN THE DEMOLITION GENERAL NOTES
DE2 DEMO EXISTING GUTTER AND DOWNSPOUT SYSTEM IN ITS ENTIRETY
DE3 NOT USED
DE4 REMOVE AND SALVAGE EXISTING SPLASH BLOCK DURING DEMOLITION, TYP
DE5
REMOVE ALL EXISTING STUCCO FINISH AND METAL FLASHING ON CHIMNEY IN
PREPARATION FOR NEW
DE6
REMOVE AND SALVAGE ALL EXISTING HANDRAILS AT STAIR AND RAMP FOR
REFINISHING AND REINSTALLATION AFTER STUCCO WORK IS COMPLETE. SEE
FLOOR PLAN FOR REFINISHING OF THESE ELEMENTS.
DE7
REMOVE AND SALVAGE AWNING, BRACKETS, FASTENERS AND POSTS AND
SALVAGE FOR REINSTALLATION AFTER STUCCO WORK IS COMPLETE. ANY
COMPONENTS OF THE AWNING ASSEMBLY DAMAGED DURING CONSTRUCTION,
INCLUDING FABRIC, BRACKETS, FASTENERS OR POSTS, ARE TO BE REPLACED
IN-KIND OR BETTER THAN THE EXISTING.
DE8 EXISTING PRECAST CONCRETE CAP TO REMAIN
DE9
REMOVE ALL STUCCO FROM WALL AND ENTRANCE CANOPY IN IT'S ENTIRETY -
SEE DEMOLITION PLAN
DE10
EXISTING MECH AND ELEC SYSTEMS IN THIS AREA. IF NECESSARY FOR
STUCCO REPLACEMENT, REMOVE AND SALVAGE FOR REINSTALLATION AFTER
STUCCO WORK IS COMPLETE. PROVIDE AND COORDINATE ALL DISCONNECTS
WITH THE VA - SEE ELECTRICAL
DE11 EXISTING CRAWLSPACE VENT TO REMAIN
DE12 NOT USED
DE13 REMOVE AND DISPOSE LIGHT FIXTURE - SEE ELECTRICAL
DE14 EXISTING VENT PIPE TO REMAIN.
DE15
REMOVE AND SALVAGE EXISTING SIGN FOR REINSTALLATION ONCE STUCCO
WORK IS COMPLETE
DEMOLITION ELEV SYMBOLS
KEY NOTE
NOTE: NOT ALL SYMBOLS MAY BE USED ON EACH PLAN
DASHED LINE
INDICATES ITEM TO
BE REMOVED (UNO)
DE10
AREA OF
STUCCO
REMOVAL
AREA OF TOTAL STUCCO REMOVAL AND REPLACEMENT
SOUTH ELEVATION
(INCLUDING WALLS, SILLS, RAMP AND STAIR
PARTIAL HEIGHT WALLS, ENTRANCE CANOPY)
WEST ELEVATION
(2) CHIMNEYS 148 SF
148 SF
148 SF
I hereby certify that this plan, specification or report was prepared by me or under my direct supervision and that I am a duly Licensed Architect under the laws of the State of Minnesota.
Name:
Date:
License number:
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
BID DOCUMENTS
NOT SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
DESIGNER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
BID DOCUMENTS
IRRIGATION:
AQUA ENGINEERING
300 BOARDWALK DRIVE
UNIT 4B
FORT COLLINS,CO 80525
970.372.6104
JD LEONARD
GEOTECHNICAL:
TERRACON
6460 HILLER STREET
SUITE A
EL PASO, TX 79925
915.778.5233
IVAN AVELAR
COST ESTIMATING:
OCMI
2100 NORTH GREENVILLE AVENUE
SUITE 1150
RICHARDSON, TX 75082
469.431.0571
RAYMOND BODO
FIRE / L0W VOLTAGE / SECURITY:
IMEG
623 26TH AVENUE
ROCK ISLAND, IL 61201
309.781.3770
MATT SNYDER / PETE MCGHEE
CHRISTINA MCDANIEL
06/15/2026
52909
C U s e rs \P u b lic \D o c u m e n ts
\R e v it P ro je c ts
\1
-A D
M
IN
-A -R c m c d a n ie l@ a e
-m n
.c o m .r v t
/1
/2
:5
:2
P
M
2101- AD201
ADMIN BLDG - DEMOLITION EXTERIOR
ELEVATIONS
FT BLISS NATIONAL CEMETERY
EXPANSION
5200 FRED WILSON AVENUE, EL PASO,TEXAS
886CM3026
JUNE 15, 2026 CM RG
18528
1/4" = 1'-0"
EXTERIOR DEMOLITION ELEVATION - NORTH
1/4" = 1'-0"
EXTERIOR DEMOLITION ELEVATION - EAST
1/4" = 1'-0"
EXTERIOR DEMOLITION ELEVATION - SOUTH
1/4" = 1'-0"
EXTERIOR DEMOLTION ELEVATION - WEST
0 4' 8'2' 0 4' 8'2'
0 4' 8'2'0 4' 8'2'
Revisions: Date: 84 of 155
EXISTING
RECORDS
STORAGE
EXISTING
STORAGE/ELEC/OIT
FL5
FL6
UNEXCAVATED
FL13 FL14
UP
FL18
FL19
SHELF
S H
E
LF
WH
FL8
FL15
FLOOR PLAN KEYED NOTES
NOTE: NOT ALL KEYED NOTES MAY BE USED ON EACH PLAN
FL1
4'-0"W x 8'-0"H X 3/4" AC GRADE FIRE RATED PLYWOOD. CUT PANELS AS
NECESSARY TO FIT ROOM. 2 COATS OF FIRE RESISTANT PAINT ALL SIDES
AND TOP WITH COAT OF HIGH GLOSS WHITE. MOUNT BOTTOM OF
PLYWOOD 1'-0" AFF
FL2 WALL - MOUNT TELECOM ENCLOSURE, SEE TECHNOLOGY
FL3 SECURITY PANEL - SEE TECHNOLOGY
FL4
FULLY RECESSED 1HR FIRE RATED FIRE ESTINGUISHER CABINET FOR NEW
CO2 EXTINGUISHERS. SEE SIMILAR DETAIL 4/2101- AE601 FOR MORE
INFORMATION.
FL5 EXISTING MECHANICAL CHASE
FL6 EXISTING CAST-IN-PLACE CONCRETE FOUNDATION WALL
FL7 S-1 COUNTERTOP
FL8
MOUNT CARD READER TO ADJACENT WALL AND PROVIDE ALL
CONNECTIONS FOR FUNCTIONING ACCESS CONTROLLED DOOR.
CREDENTIAL MAY BE INSTALLED ON DOOR PANEL AT CONTRACTOR'S
OPTION.
FL9
1-HR FIRE RATED HORIZONTAL SHAFT PARTITION FULL EXTENT OF ROOM.
BOTTOM OF GYPSUM BOARD FINISH AT 8'-6" AFF.
FL10
EXISTING FLUE REINSTALL ONCE STUCCO AND PAINT WORK IS COMPLETE
IF REMOVED TO COMPLETE REFINISHING WORK
FL11 EXISTING CONCRETE RAMP, LANDINGS AND STAIR TO REMAIN
FL12
CIP CONCRETE EQUIPMENT PADS, COORDINATE EXACT LOCATION WITH
THE VA DURING SHOP DRAWING REVIEW – SEE CIVIL AND MECHANICAL
FL13 EXISTING FIRE EXTINGUISHER
FL14
WIRE MESH HINGED DOOR 3'-0" X 6'-10". (CUSTOM DOOR SIZE MAY BE
REQUIRED TO FIT EXISTING CONSTRUCTION AT NO ADDITIONAL COST TO
THE VA), HARDWARE SET HW-G1. EXISTING CLNG HT IS 7'-0"; HOWEVER,
SPACE NEEDS TO BE MADE ABOVE DOOR TO AVOID HITTING CEILING
MOUNTED CONDUIT. FIELD VERIFY SPACE AVAILABLE FOR FULLY
FUNCTIONAL ACCESS CONTROLLED DOOR OPENING PRIOR TO
SUBMITTING SHOP AND ERECTION DRAWINGS.
FL15
PATCH WALLS AND STAIR WITH FINISH TO MATCH EXISTING WHERE
EXISTING DOOR WAS DEMOLISHED.
FL16 RELOCATED EXISTING PAPER SHREDDER
FL17
PROVIDE NEW 3" METAL DOWNSPOUT, SCALLOPED PROFILE TO MATCH
EXISTING
FL18 EXISTING CRAWL SPACE ACCESS DOOR
FL19
EXISTING ELEC AND BUILDING SYSTEM PANELS - SEE ELECTRICAL,
TECHNOLOGY
FL20
SECURE KEY STORAGE CABINET WITH CREDENTIAL READER CAPABILITY -
SEE TECHNOLOGY, COORDINATE FINAL LOCATION WITH CEMETERY
DIRECTOR
FL21 REINSTALL AWNING POSTS REMOVED DURING DEMOLITION
FL22
PRIOR TO REINSTALLATION, SAND/STRIP PAINT FROM THE HAND AND
STAIR RAILS AND ASSOCIATED HARDWARE ON SITE. REMOVE RUST WITH A
RUST NEUTRALIZER BEFORE PRIMING. APPLY PRIMER, INTERMEDIATE AND
TOP PAINT COATS TO HANDRAILS AND ASSOCIATED HARDWARE (P-9).
FL23 DASHED LINE DENOTES EDGE OF ROOF OVERHANG ABOVE
GENERAL NOTES
1. THE ARCHITECTURAL DRAWINGS SHOW PRINCIPAL AREAS AND LIMITS OF
CONSTRUCTION WHERE WORK MUST BE ACCOMPLISHED UNDER THIS CONTRACT.
INCIDENTAL WORK MAY BE NECESSARY IN AREAS NOT SHOWN ON ARCHITECTURAL
DRAWINGS DUE TO CHANGES AFFECTING ELECTRICAL, MECHANICAL, PLUMBING AND
OTHER SYSTEMS. THIS INCIDENTAL WORK MUST BE PART OF THIS CONTRACT.
INSPECT THESE AREAS TO ASCERTAIN WORK REQUIRED AND PERFORM THE WORK IN
ACCORDANCE OF CONTRACT REQUIREMENTS.
2. DO NOT SCALE DRAWINGS. NOTIFY ARCHITECT IMMEDIATELY OF ANY DISCREPANCIES.
3. PATCH OPENINGS CUT THOUGH RATED CONSTRUCTION WITH MATERIALS
COMPATIBLE WITH EXISTING ASSEMBLY TO RESTORE INTEGRITY OF THE RATING.
RESTORE FINISHES OF DISTURBED AREAS TO LIKE NEW CONDITION.
4. GENERAL CONTRACTOR TO CHECK MECHANICAL DRAWINGS FOR EXISTING PIPES AND
DUCTS FURRED IN WALLS. VERIFY SIZE AND LOCATION WITH MECHANICAL
CONTRACTOR PRIOR TO PROCEEDING WITH REMODELING.
5. DIMENSIONS OF EQUIPMENT ARE THOSE OF THE BASIS-OF-DESIGN EQUIPMENT.
VERIFY DIMENSIONS OF ACTUAL EQUIPMENT BEING PROVIDED TO COORDINATE SPACE
REQUIREMENTS.
6. VERIFY DIMENSIONS OF MECHANICAL OR ELECTRICAL EQUIPMENT PRIOR TO
FABRICATING SUPPORTS FOR THE EQUIPMENT.
7. PATCH AREAS DISTURBED OR MODIFIED BY THIS WORK WITH MATERIALS TO MATCH
EXISTING ADJACENT SURFACES OR SCHEDULED FINISHES AND TO A LIKE NEW
CONDITION.
8. PROVIDE ACCESS PANELS WHERE INDICATED ON DRAWINGS AND WHERE DESCRIBED
IN SPECIFICATIONS SECTION 08 31 13. COORDINATE LOCATIONS AND SIZES REQUIRED
(24" X 24" MINIMUM) WITH MECHANICAL, PLUMBING, ELECTRICAL AND TECHNOLOGY
SUBCONTRACTORS.
9. ABBREVIATIONS AND SYMBOLS OF ARCHITECTURAL, STRUCTURAL, MECHANICAL, AND
ELECTRICAL MAY VARY BY DISCIPLINE. SEE RESPECTIVE DISCIPLINE SECTIONS AND/OR
DRAWINGS FOR DEFINITIONS.
10. AT MECHANICAL AND ELECTRICAL EQUIPMENT ROOMS, PROVIDE 3/4" FIRE
RETARDANT TREATED (FRT) PLYWOOD SURFACE OF SCHEDULED PARTITION FOR
SURFACE MOUNTED FIXTURES AND EQUIPMENT, UNLESS NOTED OTHERWISE. DO NOT
PAINT OVER FRT LABEL.
11. DEFINITIONS OF COMMON TERMS.
• FURNISH: TO SUPPLY AND DELIVER TO THE SITE, READY FOR INSTALLATION
• INSTALL: TO PLACE INTO POSITION SERVICE OR USE
• PROVIDE: TO FURNISH AND INSTALL
12. SEE TECHNOLOGY FOR MORE INFORMATION ABOUT CREDENTIAL READERS (CR)s.
13. THE CONTRACTOR SHALL PRESERVE AND PROTECT ALL STRUCTURES, EQUIPMENT,
AND VEGETATION (SUCH AS TREES, SHRUBS, AND GRASS) ON OR ADJACENT TO THE
WORK SITE, WHICH ARE NOT TO BE REMOVED AND WHICH DO NOT UNREASONABLY
INTERFERE WITH THE WORK REQUIRED UNDER THIS CONTRACT. REFER TO GENERAL
REQUIREMENTS SPECIFICATION SECTION 010002.
FLOOR PLAN SYMBOLS
EXISTING WALL TO
REMAIN
WALL
EXISTING DOOR
AND FRAME TO
REMAIN
DOOR
INTERIOR
BORROWED LITE
101B
101A
8'-0"
DIMENSION LINE
8'-0" EXTENDED
DIMENSION LINE
AE2111A
INTERIOR
ELEVATION
INDICATOR TAG
2B
XXXX-
AE2O1
EXTERIOR
ELEVATION
INDICATOR TAG
1A
203 EQUIPMENT TAG
100 FLOOR SPOT
ELEVATIONWALL TAG
OFFICE
ROOM NAME AND
NUMBER
DETAIL REFERENCE
TAG
EXTERIOR SECTION
REFERENCE TAG
INTERIOR SECTION
REFERENCE TAG
KEY NOTE
A GRIDLINE
REVISION TAG
PR01
REVISION CLOUD
NOTE: NOT ALL SYMBOLS MAY BE USED ON EACH PLAN
FP10
B3
CURTAIN WALL TAG
OR WINDOW TAGCW1 W3OR
LIMITS OF
CONSTRUCTION
XXXX-
AE2O1
1A
XXXX-
AE2O1
1A
XXXX-
AE2O1
1A
INSTALL 7/8" THICK 3-
COAT DIRECT APPLIED
STUCCO ON WALL IN
IT'S ENTIRETY, IN
ADDITION TO ALL
STUCCO ON
ENTRANCE OVERHANG
AND COLUMNS
NIC
AREA IN
DESIGNATED FOR
TECHNOLOGY
ENCLOSURE
MATERIAL LEGEND
EXISTING
NOTE: NOT ALL SYMBOLS MAY BE USED ON EACH PLAN
BRICK
BRICK
CONCRETE
GYPSUM BOARD
GRAVEL / FILL
PLYWOOD
EARTH
PLAN & SECTION SECTION
ELEVATION
NEW CONSTRUCTION
CMU
RIGID INSULATION
SPRAY FOAM
STONE WOOD - HORIZONTAL
WOOD - VERTICALFIRE PROOFING
CMU
CONCRETE
METAL
MORTAR NET
SOLID SURFACE
BATT INSULATION
EXISTING STUCCO
STUCCO
I hereby certify that this plan, specification or report was prepared by me or under my direct supervision and that I am a duly Licensed Architect under the laws of the State of Minnesota.
Name:
Date:
License number:
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
BID DOCUMENTS
NOT SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
DESIGNER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
BID DOCUMENTS
IRRIGATION:
AQUA ENGINEERING
300 BOARDWALK DRIVE
UNIT 4B
FORT COLLINS,CO 80525
970.372.6104
JD LEONARD
GEOTECHNICAL:
TERRACON
6460 HILLER STREET
SUITE A
EL PASO, TX 79925
915.778.5233
IVAN AVELAR
COST ESTIMATING:
OCMI
2100 NORTH GREENVILLE AVENUE
SUITE 1150
RICHARDSON, TX 75082
469.431.0571
RAYMOND BODO
FIRE / L0W VOLTAGE / SECURITY:
IMEG
623 26TH AVENUE
ROCK ISLAND, IL 61201
309.781.3770
MATT SNYDER / PETE MCGHEE
CHRISTINA MCDANIEL
06/15/2026
52909
C U s e rs \P u b lic \D o c u m e n ts
\R e v it P ro je c ts
\1
-A D
M
IN
-A -R c m c d a n ie l@ a e
-m n
.c o m .r v t
/1
/2
:5
:2
P
M
2101- AE101
ADMIN BLDG - BASEMENT FLOOR PLAN FT BLISS NATIONAL CEMETERY
EXPANSION
5200 FRED WILSON AVENUE, EL PASO,TEXAS
886CM3026
JUNE 15, 2026 CM RG
18528
1/4" = 1'-0"
BASEMENT FLOOR PLAN
0 4' 8'2'
Revisions: Date: 85 of 155
DN
2101-
AE201
2101-
AE201
2101-
AE201
2101-
AE201
EXISTING
ADMIN
OFFICER
EXISTING
UNISEX
TOILET
EXISTING
PROGRAM
SPECIALIST
EXISTING
DIRECTOR
EXISTING
ALCOVE
EXISTING
MENS
EXISTING
ADMIN
STAFF
EXISTING
CONFERENCE
EXISTING
RECEPTION
EXISTING
OPERATIONS
EXISTING
CORRIDOR
EXISTING
BREAKROOM
EXISTING
STAIR
EXISTING
STORAGE
TE
7'-0"
FL1
FL2
FL3
ALIGN
FL7
FL16
FL5
FL17
FL17
FL17
FL17
FL17
FL17
FL17
FL20
DN
DN
FL22
FL23
FL23
FL11
5'-2"
1'-5 1/2"
FL21
2101-
AE601
XN3
B3b
1' -0
FL4
CL
DN
FL10
G3c
G3c
FL9
EX REF EX COUNTERTOP
E X
B U
LL
E
TI
N
B O
A R
D
TYP
EX CONC RAMP
SLOPE DOWN
EX CONC RAMP
SLOPE DOWN
D N
E X
C O
N C
S T
A
IR
(E X
IS
T
IN
G
V
IF
'-3
/4
ALIGN
2101-
AE550
FINISH
PLAN
1' -3
2' -1
0.
0.
FL8
FL8
FL8
1'-3"
FL12
2101-
AE111
AT CEILING
ABOVE
AT CEILING
ABOVE
2101-
AE111
FLOOR PLAN KEYED NOTES
NOTE: NOT ALL KEYED NOTES MAY BE USED ON EACH PLAN
FL1
4'-0"W x 8'-0"H X 3/4" AC GRADE FIRE RATED PLYWOOD. CUT PANELS AS
NECESSARY TO FIT ROOM. 2 COATS OF FIRE RESISTANT PAINT ALL SIDES
AND TOP WITH COAT OF HIGH GLOSS WHITE. MOUNT BOTTOM OF
PLYWOOD 1'-0" AFF
FL2 WALL - MOUNT TELECOM ENCLOSURE, SEE TECHNOLOGY
FL3 SECURITY PANEL - SEE TECHNOLOGY
FL4
FULLY RECESSED 1HR FIRE RATED FIRE ESTINGUISHER CABINET FOR NEW
CO2 EXTINGUISHERS. SEE SIMILAR DETAIL 4/2101- AE601 FOR MORE
INFORMATION.
FL5 EXISTING MECHANICAL CHASE
FL6 EXISTING CAST-IN-PLACE CONCRETE FOUNDATION WALL
FL7 S-1 COUNTERTOP
FL8
MOUNT CARD READER TO ADJACENT WALL AND PROVIDE ALL
CONNECTIONS FOR FUNCTIONING ACCESS CONTROLLED DOOR.
CREDENTIAL MAY BE INSTALLED ON DOOR PANEL AT CONTRACTOR'S
OPTION.
FL9
1-HR FIRE RATED HORIZONTAL SHAFT PARTITION FULL EXTENT OF ROOM.
BOTTOM OF GYPSUM BOARD FINISH AT 8'-6" AFF.
FL10
EXISTING FLUE REINSTALL ONCE STUCCO AND PAINT WORK IS COMPLETE
IF REMOVED TO COMPLETE REFINISHING WORK
FL11 EXISTING CONCRETE RAMP, LANDINGS AND STAIR TO REMAIN
FL12
CIP CONCRETE EQUIPMENT PADS, COORDINATE EXACT LOCATION WITH
THE VA DURING SHOP DRAWING REVIEW – SEE CIVIL AND MECHANICAL
FL13 EXISTING FIRE EXTINGUISHER
FL14
WIRE MESH HINGED DOOR 3'-0" X 6'-10". (CUSTOM DOOR SIZE MAY BE
REQUIRED TO FIT EXISTING CONSTRUCTION AT NO ADDITIONAL COST TO
THE VA), HARDWARE SET HW-G1. EXISTING CLNG HT IS 7'-0"; HOWEVER,
SPACE NEEDS TO BE MADE ABOVE DOOR TO AVOID HITTING CEILING
MOUNTED CONDUIT. FIELD VERIFY SPACE AVAILABLE FOR FULLY
FUNCTIONAL ACCESS CONTROLLED DOOR OPENING PRIOR TO
SUBMITTING SHOP AND ERECTION DRAWINGS.
FL15
PATCH WALLS AND STAIR WITH FINISH TO MATCH EXISTING WHERE
EXISTING DOOR WAS DEMOLISHED.
FL16 RELOCATED EXISTING PAPER SHREDDER
FL17
PROVIDE NEW 3" METAL DOWNSPOUT, SCALLOPED PROFILE TO MATCH
EXISTING
FL18 EXISTING CRAWL SPACE ACCESS DOOR
FL19
EXISTING ELEC AND BUILDING SYSTEM PANELS - SEE ELECTRICAL,
TECHNOLOGY
FL20
SECURE KEY STORAGE CABINET WITH CREDENTIAL READER CAPABILITY -
SEE TECHNOLOGY, COORDINATE FINAL LOCATION WITH CEMETERY
DIRECTOR
FL21 REINSTALL AWNING POSTS REMOVED DURING DEMOLITION
FL22
PRIOR TO REINSTALLATION, SAND/STRIP PAINT FROM THE HAND AND
STAIR RAILS AND ASSOCIATED HARDWARE ON SITE. REMOVE RUST WITH A
RUST NEUTRALIZER BEFORE PRIMING. APPLY PRIMER, INTERMEDIATE AND
TOP PAINT COATS TO HANDRAILS AND ASSOCIATED HARDWARE (P-9).
FL23 DASHED LINE DENOTES EDGE OF ROOF OVERHANG ABOVE
GENERAL NOTES
1. THE ARCHITECTURAL DRAWINGS SHOW PRINCIPAL AREAS AND LIMITS OF
CONSTRUCTION WHERE WORK MUST BE ACCOMPLISHED UNDER THIS CONTRACT.
INCIDENTAL WORK MAY BE NECESSARY IN AREAS NOT SHOWN ON ARCHITECTURAL
DRAWINGS DUE TO CHANGES AFFECTING ELECTRICAL, MECHANICAL, PLUMBING AND
OTHER SYSTEMS. THIS INCIDENTAL WORK MUST BE PART OF THIS CONTRACT.
INSPECT THESE AREAS TO ASCERTAIN WORK REQUIRED AND PERFORM THE WORK IN
ACCORDANCE OF CONTRACT REQUIREMENTS.
2. DO NOT SCALE DRAWINGS. NOTIFY ARCHITECT IMMEDIATELY OF ANY DISCREPANCIES.
3. PATCH OPENINGS CUT THOUGH RATED CONSTRUCTION WITH MATERIALS
COMPATIBLE WITH EXISTING ASSEMBLY TO RESTORE INTEGRITY OF THE RATING.
RESTORE FINISHES OF DISTURBED AREAS TO LIKE NEW CONDITION.
4. GENERAL CONTRACTOR TO CHECK MECHANICAL DRAWINGS FOR EXISTING PIPES AND
DUCTS FURRED IN WALLS. VERIFY SIZE AND LOCATION WITH MECHANICAL
CONTRACTOR PRIOR TO PROCEEDING WITH REMODELING.
5. DIMENSIONS OF EQUIPMENT ARE THOSE OF THE BASIS-OF-DESIGN EQUIPMENT.
VERIFY DIMENSIONS OF ACTUAL EQUIPMENT BEING PROVIDED TO COORDINATE SPACE
REQUIREMENTS.
6. VERIFY DIMENSIONS OF MECHANICAL OR ELECTRICAL EQUIPMENT PRIOR TO
FABRICATING SUPPORTS FOR THE EQUIPMENT.
7. PATCH AREAS DISTURBED OR MODIFIED BY THIS WORK WITH MATERIALS TO MATCH
EXISTING ADJACENT SURFACES OR SCHEDULED FINISHES AND TO A LIKE NEW
CONDITION.
8. PROVIDE ACCESS PANELS WHERE INDICATED ON DRAWINGS AND WHERE DESCRIBED
IN SPECIFICATIONS SECTION 08 31 13. COORDINATE LOCATIONS AND SIZES REQUIRED
(24" X 24" MINIMUM) WITH MECHANICAL, PLUMBING, ELECTRICAL AND TECHNOLOGY
SUBCONTRACTORS.
9. ABBREVIATIONS AND SYMBOLS OF ARCHITECTURAL, STRUCTURAL, MECHANICAL, AND
ELECTRICAL MAY VARY BY DISCIPLINE. SEE RESPECTIVE DISCIPLINE SECTIONS AND/OR
DRAWINGS FOR DEFINITIONS.
10. AT MECHANICAL AND ELECTRICAL EQUIPMENT ROOMS, PROVIDE 3/4" FIRE
RETARDANT TREATED (FRT) PLYWOOD SURFACE OF SCHEDULED PARTITION FOR
SURFACE MOUNTED FIXTURES AND EQUIPMENT, UNLESS NOTED OTHERWISE. DO NOT
PAINT OVER FRT LABEL.
11. DEFINITIONS OF COMMON TERMS.
• FURNISH: TO SUPPLY AND DELIVER TO THE SITE, READY FOR INSTALLATION
• INSTALL: TO PLACE INTO POSITION SERVICE OR USE
• PROVIDE: TO FURNISH AND INSTALL
12. SEE TECHNOLOGY FOR MORE INFORMATION ABOUT CREDENTIAL READERS (CR)s.
13. THE CONTRACTOR SHALL PRESERVE AND PROTECT ALL STRUCTURES, EQUIPMENT,
AND VEGETATION (SUCH AS TREES, SHRUBS, AND GRASS) ON OR ADJACENT TO THE
WORK SITE, WHICH ARE NOT TO BE REMOVED AND WHICH DO NOT UNREASONABLY
INTERFERE WITH THE WORK REQUIRED UNDER THIS CONTRACT. REFER TO GENERAL
REQUIREMENTS SPECIFICATION SECTION 010002.
FLOOR PLAN SYMBOLS
EXISTING WALL TO
REMAIN
WALL
EXISTING DOOR
AND FRAME TO
REMAIN
DOOR
INTERIOR
BORROWED LITE
101B
101A
8'-0"
DIMENSION LINE
8'-0" EXTENDED
DIMENSION LINE
AE2111A
INTERIOR
ELEVATION
INDICATOR TAG
2B
XXXX-
AE2O1
EXTERIOR
ELEVATION
INDICATOR TAG
1A
203 EQUIPMENT TAG
100 FLOOR SPOT
ELEVATIONWALL TAG
OFFICE
ROOM NAME AND
NUMBER
DETAIL REFERENCE
TAG
EXTERIOR SECTION
REFERENCE TAG
INTERIOR SECTION
REFERENCE TAG
KEY NOTE
A GRIDLINE
REVISION TAG
PR01
REVISION CLOUD
NOTE: NOT ALL SYMBOLS MAY BE USED ON EACH PLAN
FP10
B3
CURTAIN WALL TAG
OR WINDOW TAGCW1 W3OR
LIMITS OF
CONSTRUCTION
XXXX-
AE2O1
1A
XXXX-
AE2O1
1A
XXXX-
AE2O1
1A
INSTALL 7/8" THICK 3-
COAT DIRECT APPLIED
STUCCO ON WALL IN
IT'S ENTIRETY, IN
ADDITION TO ALL
STUCCO ON
ENTRANCE OVERHANG
AND COLUMNS
NIC
AREA IN
DESIGNATED FOR
TECHNOLOGY
ENCLOSURE
MATERIAL LEGEND
EXISTING
NOTE: NOT ALL SYMBOLS MAY BE USED ON EACH PLAN
BRICK
BRICK
CONCRETE
GYPSUM BOARD
GRAVEL / FILL
PLYWOOD
EARTH
PLAN & SECTION SECTION
ELEVATION
NEW CONSTRUCTION
CMU
RIGID INSULATION
SPRAY FOAM
STONE WOOD - HORIZONTAL
WOOD - VERTICALFIRE PROOFING
CMU
CONCRETE
METAL
MORTAR NET
SOLID SURFACE
BATT INSULATION
EXISTING STUCCO
STUCCO
EXISTING CEILING FINISH
109'-1"
5-1/2″ 20 GA METAL JOIST W/ 1 5/8" LEGS,
FASTENED W/ #12 TEK SCREWS @ BOTH
TOP AND BOTTOM OF BOTH SIDES OF
BUTT JOINT
(3) LAYERS 5/8" GYP BD
BO ROOM CEILING FINISH
108'-4"
20 GA MIN CONTINUOUS METAL TRACK
UL DESIGN 1504
1 HR FIRE RATING
B3b
MODIFY EXISTING ACT AS
NECESSARY FOR NEW PARTITION
CONSTRUCTION, TYPICAL AT ALL
NEW PARTITIONS
5-1/2″ 18 GA METAL STUD CEILING
JOISTS @ 1'- 4" OC MAX
EXISTING CEILING FINISH
109'-1"
BO ROOM CEILING FINISH
108'-4"
5-1/2″ 20 GA METAL TRACK W/ 1 5/8" LEGS, FASTENED W/
#12 TEK SCREWS @ BOTH TOP AND BOTTOM OF BOTH
SIDES OF BUTT JOINT
(3) LAYERS 5/8" GYP BD
20 GA MIN CONTINUOUS METAL TRACK
3/4" FIRE RATED PLYWOOD
4" WIDE (20 GA) GALV STEEL STRAP @ CENTER OF
JOISTS SPANNING THIS ROOM, FASTENED WITH #12
TEK SCREW @ EACH JOIST
5-1/2″ 18 GA METAL STUD CEILING JOISTS @ 1'- 4" OC MAX
UL DESIGN 1504
1 HR FIRE RATING
B3b
MODIFY EXISTING ACT AS
NECESSARY FOR NEW PARTITION
CONSTRUCTION, TYPICAL AT ALL
NEW PARTITIONS
CL
JOIST/
STRAP
I hereby certify that this plan, specification or report was prepared by me or under my direct supervision and that I am a duly Licensed Architect under the laws of the State of Minnesota.
Name:
Date:
License number:
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
BID DOCUMENTS
NOT SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
DESIGNER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
BID DOCUMENTS
IRRIGATION:
AQUA ENGINEERING
300 BOARDWALK DRIVE
UNIT 4B
FORT COLLINS,CO 80525
970.372.6104
JD LEONARD
GEOTECHNICAL:
TERRACON
6460 HILLER STREET
SUITE A
EL PASO, TX 79925
915.778.5233
IVAN AVELAR
COST ESTIMATING:
OCMI
2100 NORTH GREENVILLE AVENUE
SUITE 1150
RICHARDSON, TX 75082
469.431.0571
RAYMOND BODO
FIRE / L0W VOLTAGE / SECURITY:
IMEG
623 26TH AVENUE
ROCK ISLAND, IL 61201
309.781.3770
MATT SNYDER / PETE MCGHEE
CHRISTINA MCDANIEL
06/15/2026
52909
C U s e rs \P u b lic \D o c u m e n ts
\R e v it P ro je c ts
\1
-A D
M
IN
-A -R c m c d a n ie l@ a e
-m n
.c o m .r v t
/1
/2
:5
:3
P
M
2101- AE111
ADMIN BLDG - FIRST LEVEL FLOOR PLAN FT BLISS NATIONAL CEMETERY
EXPANSION
5200 FRED WILSON AVENUE, EL PASO,TEXAS
886CM3026
JUNE 15, 2026 CM RG
18528
0 4' 8'2'
1/4" = 1'-0"1
FIRST LEVEL FLOOR PLAN
1 1/2" = 1'-0"
1 HR FIRE RATED CEILING MEMBRANE DETAIL
1 1/2" = 1'-0"
1 HR FIRE RATED CEILING MEMBRANE DETAIL
Revisions: Date: 86 of 155
S
LO
P E
:1
D
O W
N
S
LO
P E
:1
D
O W
N
RO1 RO2
RO2
RO1
RO1
RO2
RO1
RO2
RO7
RO6
RO6
RO5
RO2
RO1
RO4RO5
RO8
RO10
RO10
S
LO
P E
3:
D O
W N
S
LO
P E
2:
D O
W N
S
LO
P E
:1
D
O W
N
RO11
RO11
RO2
SLOPE 4:12 DOWN
2101-
AE501
2101-
AE501
2101-
AE501
TYP
TYP
TYP
RO8
RO3
RO3
2101-
AE501
2101-
AE501
RO9
2101-
AE501
2101-
AE501
SIM
2101-
AE501
2101-
AE501
SIM
DR1
DR1
DR2 DR5
DR6
DR6
DR5
DR2
DR2
DR2
DR2
DR4
S
LO
P E
:1
D
O W
N
S
LO
P E
:1
D
O W
N
DR2
DR7
SLOPE 4:12 DOWN
S
LO
P E
3:
D O
W N
S
LO
P E
2:
D O
W N
S
LO
P E
:1
D
O W
N
DR3
DR8
DR3
DEMOLITION GENERAL NOTES
1. CONTRACTOR MUST COORDINATE ALL DEMOLITION WORK, PHASING AND SEQUENCING WITH THE
OWNER. ANY INFORMATION REGARDING SEQUENCING PROVIDED IN THESE DOCUMENTS IS FOR
ARCHITECT - OWNER PLANNING PURPOSES ONLY, UNLESS NOTED OTHERWISE.
2. CONTRACTOR MUST BE RESPONSIBLE FOR COORDINATING WITH ALL TRADES FOR THE
DEMOLITION WORK REQUIRED FOR THIS PROJECT.
3. WHERE PARTITIONS ARE INDICATED TO BE REMOVED, REMOVE PARTITION ALONG WITH ALL
ITEMS CONTAINED WITHIN, INCLUDING DOORS, FRAMES, HARDWARE, SIDELIGHTS, WINDOWS,
MECHANICAL AND ELECTRICAL EQUIPMENT, ETC. TO STRUCTURE ABOVE, UNLESS NOTED
OTHERWISE.
4. WHERE FLOOR FINISH IS INDICATED TO BE DEMOLISHED, REMOVE FINISH TO FLOOR SLAB AS
REQUIRED AND PREPARE SLAB SURFACE FOR SCHEDULED FINISHES WITHIN AREA TO BE
REMODELED, UNLESS NOTED OTHERWISE. REMOVE CARPET TILE UP TO THE FACE OF THE NEW TE
ROOM WALLS. PROTECT CARPET FOR REINSTALLATION AS NECESSARY. SEE FINISH SCHEDULE
FOR EXISTING FLOOR FINISHES TO REMAIN UNDISTURBED.
5. WHERE CEILING IS INDICATED TO BE DEMOLISHED, REMOVE CEILING SUSPENSION SYSTEM
ALONG WITH ALL ASSOCIATED MECHANICAL AND ELECTRICAL ITEMS, UNLESS NOTED OTHERWISE.
SEE MECHANICAL AND ELECTRICAL DRAWINGS FOR EXTENT OF CONDUIT, PIPING AND DUCTWORK DEMOLITION WITHIN AREA TO BE REMODELED. CUT CEILING GRID AND CEILING TILES ONLY TO ALLOW FOR THE CONSTRUCTION OF THE TE ROOM WALLS. WHERE CEILING IS INDICATED TO BE
DEMOLISHED, MODIFY CEILING GRID AND CUT CEILING TILES AS NECESSARY TO ENSURE
ORIGINAL FINISHED CEILING LAYOUT IS MAINTAINED. REINSTALL WALL MOLDING IN ALIGNMENT WITH EXISTING WALL MOLDING, MITER CUT OUTSIDE CORNER, AND PROVIDE STABILIZER CLIPS AS
NECESSARY. REPLACE ALL CEILING TILES DAMAGED OR SOILED DURING THE COURSE OF
CONSTRUCTION WITH NEW TILES TO MATCH EXISTING.
6. WHERE INDICATED, REMOVE ALL WALL/PARTITION EXISTING FINISHES AND PREPARE THE
SURFACES FOR SCHEDULED FINISHES, SEE FINISH SCHEDULE FOR FINISHES.
7. ALL DISTURBED AREAS, WALLS, PARTITIONS, FLOORS, ETC, DAMAGED BY DEMOLITION WORK
MUST BE PATCHED TO MATCH ADJACENT AREA.
8. OWNER RESERVES THE RIGHT OF FIRST REFUSAL OF ALL SALVAGED ITEMS SUCH AS: DOORS, LIGHT FIXTURES, PLUMBING FIXTURES ETC.
9. SALVAGED ITEMS SCHEDULED FOR REUSE MUST BE CLEANED, RESTORED AND/OR REFINISHED
TO LIKE NEW CONDITION, UNLESS NOTED OTHERWISE.
10. DO NOT REMOVE ANY EXISTING STRUCTURAL SUPPORT MEMBERS SUCH AS COLUMNS, BEAMS, JOISTS, LOAD-BEARING PARTITIONS ETC, UNTIL ADEQUATE PERMANENT OR TEMPORARY
SUPPORT IS IN PLACE. ALL EXISTING STRUCTURAL MEMBERS MUST BE ADEQUATELY PROTECTED, COORDINATE WITH STRUCTURAL ENGINEER.
11. SEE STRUCTURAL, MECHANICAL AND ELECTRICAL DRAWINGS FOR RELATED DEMOLITION AND
PREP WORK.
12. WALL AND CEILING MOUNTED ITEMS SHOWN DASHED, SUCH AS WALL CABINETS, SHELVING, CUBICLE CURTAIN TRACKS, PROJECTION SCREENS ETC, MUST BE REMOVED, UNLESS NOTED
OTHERWISE.
13. WITHIN ALL EXISTING ROOMS/SPACES RECEIVING SCHEDULED FLOOR, OR WALL, OR CEILING
FINISHES, REMOVE ALL EXISTING FLOOR, OR WALL, OR CEILING FINISHES DOWN TO THE
SUBSTRATE. INCLUDE THE REMOVAL OF ALL ITEMS LOCATED WITHIN THE EXISTING FINISH
REMOVALS UNO PATCH AND PREP ALL SUBSTRATES TO RECEIVE SCHEDULED FINISHES. FOR
ADDITIONAL INFORMATION, SEE KEYNOTED ITEMS, FINISH PLANS AND/OR SCHEDULES,
STRUCTURAL, MECHANICAL AND ELECTRICAL.
14. SALVAGE CLAY ROOFING TILE: SALVAGE 300-400 OF THE BEST CONDITIONED ROOF TILES AND PLACE ON LEVEL PALLETS. DISPOSE OF ALL OTHER REMOVED CLAY TILE. PALLETS MAY BE NEW OR REUSED FROM THE ORIGINAL TILE DELIVERY. TIGHTLY SECURE TILE ON PALLETS AND COVER WITH A PROTECTIVE WATERPROOF COVERING THAT IS ADEQUATELY VENTILATED. STACK TILE IN
AN ORGANIZED, STABLE MANNER TO PREVENT SHIFTING AND SLIDING WHILE IN STORAGE.
PROVIDE SPACE BETWEEN EACH TILE TO ALLOW AIR FLOW AND VENTILATION. RELOCATE BOTH
PALLETS TO STORAGE LOCATION(S) ON CEMETERY PROPERTY, WHERE DIRECTED BY THE VA.
15. THE CONTRACTOR SHALL PRESERVE AND PROTECT ALL STRUCTURES, EQUIPMENT, AND
VEGETATION (SUCH AS TREES, SHRUBS, AND GRASS) ON OR ADJACENT TO THE WORK SITE,
WHICH ARE NOT TO BE REMOVED AND WHICH DO NOT UNREASONABLY INTERFERE WITH THE
WORK REQUIRED UNDER THIS CONTRACT. REFER TO GENERAL REQUIREMENTS SPECIFICATION
SECTION 010002.
ROOF PLAN KEYED NOTES - BUILDING 2101
NOTE: NOT ALL KEYED NOTES MAY BE USED ON EACH PLAN
RO1
INSTALL TAPERED MISSION STYLE CLAY ROOF TILES (2,700 SF) AND
ASSOCIATED ACCESORIES
RO2 5" ROUND METAL GUTTER, IN-KIND WITH EXISTING, TYP
RO3 CRICKET SEE -
RO4
REINSTALL ELECTRICAL COMPONENTS REMOVED DURING DEMOLITION
ONCE CHIMNEY REPAIRS ARE COMPLETE
RO5
NEW 3-COAT DIRECT APPLIED STUCCO FINISH AND METAL FLASHING, ALL
SIDES OF EXISTING CHIMNEY
RO6 EXISTING ROOF PENETRATION. SEE
RO7
REINSTALL FABRIC AWNING ASSEMBLY SALVAGED DURING DEMOLITION.
REPLACE W/ NEW SS BRACKETS AND FASTENERS IF DAMAGED DURING
CONSTRUCTION
RO8 CLAY TILE EAVE CLOSURE AT ALL EAVES, TYP
RO9 RAKE TILES AT ALL ROOF RAKES, TYP
RO10 RIDGE TILE W/ RIDGE END TILES AT ALL ENDS, TYP
RO11
POINT OF ROOF SLOPE CHANGE. ROOF SLOPES SHOWN ARE EXISTING
AND APPROXIMATE. MATCH EXISTING ROOF SLOPE FOR NEW WORK
/6 2101- AE501
/7 2101- AE501
GENERAL NOTES
1. THE ARCHITECTURAL DRAWINGS SHOW PRINCIPAL AREAS AND LIMITS OF
CONSTRUCTION WHERE WORK MUST BE ACCOMPLISHED UNDER THIS CONTRACT.
INCIDENTAL WORK MAY BE NECESSARY IN AREAS NOT SHOWN ON ARCHITECTURAL
DRAWINGS DUE TO CHANGES AFFECTING ELECTRICAL, MECHANICAL, PLUMBING AND
OTHER SYSTEMS. THIS INCIDENTAL WORK MUST BE PART OF THIS CONTRACT.
INSPECT THESE AREAS TO ASCERTAIN WORK REQUIRED AND PERFORM THE WORK IN
ACCORDANCE OF CONTRACT REQUIREMENTS.
2. DO NOT SCALE DRAWINGS. NOTIFY ARCHITECT IMMEDIATELY OF ANY DISCREPANCIES.
3. PATCH OPENINGS CUT THOUGH RATED CONSTRUCTION WITH MATERIALS
COMPATIBLE WITH EXISTING ASSEMBLY TO RESTORE INTEGRITY OF THE RATING.
RESTORE FINISHES OF DISTURBED AREAS TO LIKE NEW CONDITION.
4. GENERAL CONTRACTOR TO CHECK MECHANICAL DRAWINGS FOR EXISTING PIPES AND
DUCTS FURRED IN WALLS. VERIFY SIZE AND LOCATION WITH MECHANICAL
CONTRACTOR PRIOR TO PROCEEDING WITH REMODELING.
5. DIMENSIONS OF EQUIPMENT ARE THOSE OF THE BASIS-OF-DESIGN EQUIPMENT.
VERIFY DIMENSIONS OF ACTUAL EQUIPMENT BEING PROVIDED TO COORDINATE SPACE
REQUIREMENTS.
6. VERIFY DIMENSIONS OF MECHANICAL OR ELECTRICAL EQUIPMENT PRIOR TO
FABRICATING SUPPORTS FOR THE EQUIPMENT.
7. PATCH AREAS DISTURBED OR MODIFIED BY THIS WORK WITH MATERIALS TO MATCH
EXISTING ADJACENT SURFACES OR SCHEDULED FINISHES AND TO A LIKE NEW
CONDITION.
8. PROVIDE ACCESS PANELS WHERE INDICATED ON DRAWINGS AND WHERE DESCRIBED
IN SPECIFICATIONS SECTION 08 31 13. COORDINATE LOCATIONS AND SIZES REQUIRED
(24" X 24" MINIMUM) WITH MECHANICAL, PLUMBING, ELECTRICAL AND TECHNOLOGY
SUBCONTRACTORS.
9. ABBREVIATIONS AND SYMBOLS OF ARCHITECTURAL, STRUCTURAL, MECHANICAL, AND
ELECTRICAL MAY VARY BY DISCIPLINE. SEE RESPECTIVE DISCIPLINE SECTIONS AND/OR
DRAWINGS FOR DEFINITIONS.
10. AT MECHANICAL AND ELECTRICAL EQUIPMENT ROOMS, PROVIDE 3/4" FIRE
RETARDANT TREATED (FRT) PLYWOOD SURFACE OF SCHEDULED PARTITION FOR
SURFACE MOUNTED FIXTURES AND EQUIPMENT, UNLESS NOTED OTHERWISE. DO NOT
PAINT OVER FRT LABEL.
11. DEFINITIONS OF COMMON TERMS.
• FURNISH: TO SUPPLY AND DELIVER TO THE SITE, READY FOR INSTALLATION
• INSTALL: TO PLACE INTO POSITION SERVICE OR USE
• PROVIDE: TO FURNISH AND INSTALL
12. SEE TECHNOLOGY FOR MORE INFORMATION ABOUT CREDENTIAL READERS (CR)s.
13. THE CONTRACTOR SHALL PRESERVE AND PROTECT ALL STRUCTURES, EQUIPMENT,
AND VEGETATION (SUCH AS TREES, SHRUBS, AND GRASS) ON OR ADJACENT TO THE
WORK SITE, WHICH ARE NOT TO BE REMOVED AND WHICH DO NOT UNREASONABLY
INTERFERE WITH THE WORK REQUIRED UNDER THIS CONTRACT. REFER TO GENERAL
REQUIREMENTS SPECIFICATION SECTION 010002.
DEMOLITION ROOF PLAN KEYED NOTES
NOTE: NOT ALL KEYED NOTES MAY BE USED ON EACH PLAN
DR1
REMOVE ALL EXISTING CLAY TILE ROOFING ASSEMBLY, ASSOCIATED
UNDERLAYMENT, ROOF FLASHINGS, EAVE CLOSERS AND TREATED WOOD
BLOCKING, EXCEPT WHERE NOTED OTHERWISE. EXISTING WOOD
SHEATHING TO REMAIN. SALVAGE A PORTION OF THE REMOVED TILES
FOLLOWING THE DIRECTION PROVIDED IN THE DEMOLITION GENERAL
NOTES, ROOF 2,593 SF
DR2 DEMO EXISTING GUTTER AND DOWNSPOUT SYSTEM IN ITS ENTIRETY
DR3 EXISTING CHIMNEY TO REMAIN
DR4
REMOVE AND SALVAGE EXISTING ELECTRICAL COMPONENTS ATTACHED
TO CHIMNEY FOR REINSTALLATION AFTER CHIMNEY REPAIRS ARE
COMPLETE
DR5
REMOVE ALL EXISTING STUCCO FINISH AND METAL FLASHING ON CHIMNEY
IN PREPARATION FOR NEW
DR6 EXISTING ROOF PENETRATION TO REMAIN
DR7
REMOVE AND SALVAGE AWNING,BRACKETS, FASTENERS AND POSTS FOR
REINSTALLATION AFTER STUCCO REPAIR IS COMPLETE
DR8
POINT OF ROOF SLOPE CHANGE. ROOF SLOPES SHOWN ARE EXISTING AND
APPROXIMATE. MATCH EXISTING ROOF SLOPE FOR NEW WORK
DEMOLITION PLAN SYMBOLS
EXISTING WALL TO
REMAIN
WALL OR
PARTITION TO BE
REMOVED
EXISTING DOOR
AND FRAME TO
REMAIN
KEY NOTE
A
GRIDLINE
NOTE: NOT ALL SYMBOLS MAY BE USED ON EACH PLAN
EXISTING DOOR
AND FRAME TO BE
DEMOLISHED
DASHED LINE
INDICATES ITEM TO
BE REMOVED (UNO)
DE10
REMOVE ALL
STUCCO FROM WALL
AND ENTRANCE
CANOPY IN IT'S
ENTIRETY.
AREA OF DEMO
NIC
I hereby certify that this plan, specification or report was prepared by me or under my direct supervision and that I am a duly Licensed Architect under the laws of the State of Minnesota.
Name:
Date:
License number:
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
BID DOCUMENTS
NOT SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
DESIGNER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
BID DOCUMENTS
IRRIGATION:
AQUA ENGINEERING
300 BOARDWALK DRIVE
UNIT 4B
FORT COLLINS,CO 80525
970.372.6104
JD LEONARD
GEOTECHNICAL:
TERRACON
6460 HILLER STREET
SUITE A
EL PASO, TX 79925
915.778.5233
IVAN AVELAR
COST ESTIMATING:
OCMI
2100 NORTH GREENVILLE AVENUE
SUITE 1150
RICHARDSON, TX 75082
469.431.0571
RAYMOND BODO
FIRE / L0W VOLTAGE / SECURITY:
IMEG
623 26TH AVENUE
ROCK ISLAND, IL 61201
309.781.3770
MATT SNYDER / PETE MCGHEE
CHRISTINA MCDANIEL
06/15/2026
52909
C U s e rs \P u b lic \D o c u m e n ts
\R e v it P ro je c ts
\1
-A D
M
IN
-A -R c m c d a n ie l@ a e
-m n
.c o m .r v t
/1
/2
:5
:3
P
M
2101- AE191
ADMIN BLDG - DEMOLITION ROOF PLAN AND
ROOF PLAN
FT BLISS NATIONAL CEMETERY
EXPANSION
5200 FRED WILSON AVENUE, EL PASO,TEXAS
886CM3026
JUNE 15, 2026 CM RG
18528
1/4" = 1'-0"
ROOF PLAN
0 4' 8'2' 1/4" = 1'-0"
DEMOLITION ROOF PLAN
0 4' 8'2'
Revisions: Date: 87 of 155
FIRST LEVEL
100'-0"
EL1
EL5
EL2
EL4EL5EL5
EL2
EL5
EL7
EL1
EL5
EL8 EL3
TYP AT ALL
DOWNSPOUTS
EL14EL12
0'
-0
E X
IS
T
IN
G
REPLACEMENT
STUCCO
EL8
EL10
EL18
EL15
4"
8"
8"
EL1
EL2
EL5
EL4
EL2
EL5
EL2
EL5
EL2
EL1
EL8
EL6
'-2
'-0
EL9
EL10
EL11
EL3
TYP AT ALL
DOWNSPOUTS
0'
-0
E X
IS
T
IN
G
STUCCO REPLACEMENT
EL16
EL812
+/- 2
EL15
EL15
8"
FIRST LEVEL
100'-0"
EL8
EL2
EL1
EL2
EL5
EL7
EL4
EL5 EL6 EL6
EL5
EL2
EL1
'-2
EL9
EL9
EL10 EL10 EL10
EL3
EL11
'-2
TYP AT ALL
DOWNSPOUTS
O V
E R
A
LL
B U
IL
D
IN
G
D
IM
E N
S
IO
N
0'
-0
E
X
IS
T
IN
G
EL13EL13
STUCCO REPLACEMENT
EL8
EL17
EL2
1'-3"
EL16 ON WALL BEYOND
EL15
8"
8"
FIRST LEVEL
100'-0"
EL1
EL8
EL2
EL2EL4
EL5
EL2
EL5
EL7 FOREGROUND
EL10
EL11
EL3
EL3
EL2
EL12
EL12TYP AT ALL
DOWNSPOUTS
EL12
EL13EL14 EL14
1'
-6
E
X
IS
T
IN
G
STUCCO REPLACEMENT
EL8
EL10
EL10
EL6
EL15
EL15
8"
ELEVATION KEYED NOTES
NOTE: NOT ALL KEYED NOTES MAY BE USED ON EACH ELEVATION
EL1
PROVIDE TAPERED MISSION STYLE CLAY ROOF TILES AND ASSOCIATED
ACCESORIES
EL2 5" ROUND METAL GUTTER, IN-KIND WITH EXISTING, TYP
EL3
PROVIDE METAL PIPE FLASHING AT ALL EXISTING PIPE ROOF
PENETRATIONS
EL4 REINSTALL EXISTING SPLASHBLOCKS REMOVED DURING DEMOLTION
EL5 3" ROUND METAL DOWNSPOUT, TYP
EL6
REINSTALL ALL EXISTING HANDRAILS AND BRACKETS SALVAGED DURING
DEMOLITION IN SAME LOCATION AS EXISTING AFTER REFINISHING
EL7 REINSTALL FABRIC AWNING ASSEMBLY SALVAGED DURING DEMOLITION
EL8
NEW 3-COAT DIRECT APPLIED STUCCO FINISH (TOTAL STUCCO = 2,500 SF),
CRICKET, AND METAL FLASHING, ALL SIDES OF EXISTING CHIMNEY
EL9 EXISTING PRECAST CONCRETE CAP TO REMAIN
EL10
INSTALL 7/8" THICK 3-COAT DIRECT APPLIED STUCCO ON WALL AND
ENTRANCE CANOPY IN IT'S ENTIRETY, SEE FLOOR PLAN
EL11
EXISTING PIPE, REINSTALL ONCE STUCCO AND PAINT WORK IS COMPLETE
IF REMOVED TO COMPLETE REFINISHING WORK
EL12
EXISTING MECH AND ELEC SYSTEMS IN THIS AREA, REINSTALL ONCE
STUCCO AND PAINT WORK IS COMPLETE IF REMOVED TO COMPLETE
REFINISHING WORK
EL13
LIGHT FIXTURE, INSTALL IN SAME LOCATION AS DEMOLISHED EXISTING
FIXTURE - SEE ELECTRICAL
EL14 EXISTING CRAWLSPACE VENT TO REMAIN
EL15
METAL SURFACE-MOUNTED COUNTERFLASHING MECHANICALLY
ANCHORED TO CHIMNEY FACE W/ TERMINATION BAR AND BASE FLASHING
BELOW
EL16 REINSTALL SIGN AS DIRECTED BY THE VA COR
EL17
CREDENTIAL READER MOUNT WITH CENTERLINE AT 3'-0" ABOVE FINISHED
FLOOR - SEE TECHNOLOGY
EL18
CIP CONCRETE EQUIPMENT PADS, COORDINATE EXACT LOCATION WITH
THE VA DURING SHOP DRAWING REVIEW – SEE CIVIL AND MECHANICAL
MATERIAL LEGEND
EXISTING
NOTE: NOT ALL SYMBOLS MAY BE USED ON EACH PLAN
BRICK
BRICK
CONCRETE
GYPSUM BOARD
GRAVEL / FILL
PLYWOOD
EARTH
PLAN & SECTION SECTION
ELEVATION
NEW CONSTRUCTION
CMU
RIGID INSULATION
SPRAY FOAM
STONE WOOD - HORIZONTAL
WOOD - VERTICALFIRE PROOFING
CMU
CONCRETE
METAL
MORTAR NET
SOLID SURFACE
BATT INSULATION
EXISTING STUCCO
STUCCO
I hereby certify that this plan, specification or report was prepared by me or under my direct supervision and that I am a duly Licensed Architect under the laws of the State of Minnesota.
Name:
Date:
License number:
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
BID DOCUMENTS
NOT SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
DESIGNER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
BID DOCUMENTS
IRRIGATION:
AQUA ENGINEERING
300 BOARDWALK DRIVE
UNIT 4B
FORT COLLINS,CO 80525
970.372.6104
JD LEONARD
GEOTECHNICAL:
TERRACON
6460 HILLER STREET
SUITE A
EL PASO, TX 79925
915.778.5233
IVAN AVELAR
COST ESTIMATING:
OCMI
2100 NORTH GREENVILLE AVENUE
SUITE 1150
RICHARDSON, TX 75082
469.431.0571
RAYMOND BODO
FIRE / L0W VOLTAGE / SECURITY:
IMEG
623 26TH AVENUE
ROCK ISLAND, IL 61201
309.781.3770
MATT SNYDER / PETE MCGHEE
CHRISTINA MCDANIEL
06/15/2026
52909
C U s e rs \P u b lic \D o c u m e n ts
\R e v it P ro je c ts
\1
-A D
M
IN
-A -R c m c d a n ie l@ a e
-m n
.c o m .r v t
/1
/2
:5
:3
P
M
2101- AE201
ADMIN BLDG - EXTERIOR ELEVATIONS FT BLISS NATIONAL CEMETERY
EXPANSION
5200 FRED WILSON AVENUE, EL PASO,TEXAS
886CM3026
JUNE 15, 2026 CM RG
18528
1/4" = 1'-0"
EXTERIOR ELEVATION - NORTH
1/4" = 1'-0"
EXTERIOR ELEVATION - EAST
1/4" = 1'-0"3
EXTERIOR ELEVATION - SOUTH
1/4" = 1'-0"4
EXTERIOR ELEVATION - WEST
0 4' 8'2' 0 4' 8'2'
0 4' 8'2'0 4' 8'2'
Revisions: Date: 88 of 155
5" ROUND METAL GUTTER, IN-KIND WITH
EXISTING, TYP
TAPERED MISSION STYLE CLAY ROOF TILES, TYP
PT WOOD BATTEN
CLAY TILE EAVE CLOSURE
EXISTING WALL CONSTRUCTION VARIES
EXISTING EXPOSED WOOD OUTLOOKERS
EXISTING PLYWOOD SHEATHING
(2) LAYERS ROOF UNDERLAYMENT
CONTINUOUS OVER ENTIRE ROOF
ROOF SLOPE VARIES - SEE ROOF PLAN
DRIP EDGE FLASHING EXTENDED INTO GUTTER,
METAL TO MATCH GUTTER
EXISTING OUTLOOKER
ROLLED RAKE
(2) LAYERS ROOF
UNDERLAYMENT CONTINUOUS
OVER ENTIRE ROOF - TURN
DOWN TOP LAYER MIN 2" AT
RAKE EDGE
MORTAR
PT WOOD NAILER BOARDS AS
REQUIRED
EXISTING 3/4" PLYWOOD
REQUIRED FASTENERS
TAPERED MISSION
STYLE CLAY TILE
ASSEMBLY
NEW/EXISTING STUCCO
FINISH - SEE ELEVATIONS
EXISTING WALL
TOP FIXTURE
ROOF UNDERLAYMENT
CLAY TILE
EXISTING PLYWOOD SHEATHING
CIRCULAR COVER RIDGE
EXISTING RIDGE STRINGER
ROOF CEMENT OR SEALANT
18" ROOF UNDERLAYMENT
REQUIRED FASTENERS
HEADLAP (TYP)
3"MIN
TOP FIXTURE
(2) LAYERS ROOF UNDERLAYMENT TURN UP TOP
LAYER MIN 8" ABOVE ROOF DECK
CLAY TILE
EXISTING ROOF CONSTRUCTION
3-COAT DIRECT APPLIED STUCCO
FINISH AND PERMEABLE AIR
BARRIER APPLIED TO ENTIRE
CHIMNEY - SEE ELEVATIONS
SEALANT
SST COUNTER FLASHING
SST APRON FLASHING EXTENDING UP
WALL 4" AND 4" ACROSS TILES
REQUIRED FASTENERS
CONTINUOUS TERMINATION BAR,
FASTENERS AS REQUIRED BY MFR
8" M
IN
4"
(2) LAYERS ROOF UNDERLAYMENT
CONTINUOUS OVER ENTIRE ROOF -
TURN UP TOP LAYER MIN 6" ABOVE
WOOD BLOCKING
PT WOOD NAILER BOARDS AS
REQUIRED
EXISTING 3/4"
PLYWOOD
REQUIRED FASTENERS
TAPERED MISSION STYLE
CLAY TILE ASSEMBLY
EXISTING FINISH - SEE
ELEVATIONS
2X6 PT WOOD BLOCKING
TERMINATION BAR
SST FLASHING, SPAN ENTIRE TOP OF
SIDE WALL, HEM END
EXISTING CONSTRUCTION
EXISTING WALL
SST PAN FLASHING 6" MIN
F
LA
S H
IN
G
6"
CASING BEAD WITH
WEEPS
6"
EXISTING MEMBRANE
AIR BARRIER
REMOVE 6" OF EXISTING STUCCO
SYSTEM TO ALLOW FOR OVERLAP OF
UNDERLAYMENT AND FLASHING
3-COAT DIRECT APPLIED
STUCCO FINISH
AT SIM - CHIMNEY PROVIDE 3-COAT
DIRECT APPLIED STUCCO FINISH AND
PERMEABLE AIR BARRIER APPLIED TO
ENTIRE CHIMNEY
8"
3"
END FIXTURE
ROOF UNDERLAYMENT
EXTEND UP WALL MIN 6"
EXISTING ROOF CONSTRUCTION
3-COAT DIRECT APPLIED STUCCO FINISH
SEALANT
COUNTER FLASHING
CRICKET FLASHING
CLAY TILE
CRICKET
4"
MEMBRANE AIR BARRIER
EXISTING
CHIMNEY
TERMINATION
BAR
8" M
IN
ROOF
UNDERLAYMENT
BELOW
FLEXIBLE
COPPER SHEET SECONDARY
FLASHING. BEND AS
REQUIRED TO CONFORM
TO TILE SHAPE.
STANDARD GALVANIZED STEEL
BASE FLASHING WITH FELT
UNDERLAYMENT UNDER AND
OVER TOP HALF AND LACED INTO
FELT UNDERLAYMENT BELOW
CAULKING ON
TOP EDGE
LAP TOP ROW OF CLAY
TILE OVER FLEXIBLE
COPPER SHEET
SECONDARY
FLASHING. BEND AS
REQUIRED TO CONFORM
TO TILE SHAPE.
EXISTING PIPE
TAPERED MISSION STYLE CLAY
ROOF TILES
1 1/2" = 1'-0"
SECTION DETAIL AT ROOF RAKE EDGE
1 1/2" = 1'-0"
SECTION DETAIL AT RAFTER END
I hereby certify that this plan, specification or report was prepared by me or under my direct supervision and that I am a duly Licensed Architect under the laws of the State of Minnesota.
Name:
Date:
License number:
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
BID DOCUMENTS
NOT SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
DESIGNER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
BID DOCUMENTS
IRRIGATION:
AQUA ENGINEERING
300 BOARDWALK DRIVE
UNIT 4B
FORT COLLINS,CO 80525
970.372.6104
JD LEONARD
GEOTECHNICAL:
TERRACON
6460 HILLER STREET
SUITE A
EL PASO, TX 79925
915.778.5233
IVAN AVELAR
COST ESTIMATING:
OCMI
2100 NORTH GREENVILLE AVENUE
SUITE 1150
RICHARDSON, TX 75082
469.431.0571
RAYMOND BODO
FIRE / L0W VOLTAGE / SECURITY:
IMEG
623 26TH AVENUE
ROCK ISLAND, IL 61201
309.781.3770
MATT SNYDER / PETE MCGHEE
CHRISTINA MCDANIEL
06/15/2026
52909
C U s e rs \P u b lic \D o c u m e n ts
\R e v it P ro je c ts
\1
-A D
M
IN
-A -R c m c d a n ie l@ a e
-m n
.c o m .r v t
/1
/2
:5
:3
P
M
2101- AE501
ADMIN BLDG - EXTERIOR DETAILS FT BLISS NATIONAL CEMETERY
EXPANSION
5200 FRED WILSON AVENUE, EL PASO,TEXAS
886CM3026
JUNE 15, 2026 CM JT/RG
18528
3" = 1'-0"
SECTION DETAIL AT ROOF RIDGE AT CLAY TILE
3" = 1'-0"
SECTION DETAIL AT CLAY TILE ROOF AND HEAD WALL OR CHIMNEY DOWNSLOPE
3" = 1'-0"
SECTION DETAIL AT CLAY TILE ROOF AT SIDE WALL AND CHIMNEY SIDE SLOPE
3" = 1'-0"
SECTION DETAIL AT CRICKET AT CHIMINEY
3" = 1'-0"
DETAIL - VENT FLASHING
Revisions: Date: 89 of 155
2' -1
0"
S-1 COUNTERTOP
W/ INTEGRAL BACK
AND SIDE SPLASH
PLAM-1 CASEWORK
WITH FILLER PANELS
AS REQUIRED, TYP.
33"
27"33"
27"
2101-
AE550
2101-
AE550
2101-
AE550
EXISTING GYP
BD SOFFIT, P-1
P-1
RB-1
SST LAY-IN SINK WITH
GOOSENECK FAUCET AND
FILTERED WATER DISPENSER
SPIGOT - SEE PLUMB.
2' -0
E X
IS
T
IN
G
E O
EXISTING
DUPLEX
BOTTOM OF
SOFFIT
S E
E E
LE
V
A T
IO
N
S
ADJUSTABLE SHELVES, SEE INTERIOR
ELEVATIONS FOR QTY
EXISTING PARTITION
EXISTING GYP BD SOFFIT
E X
IS
T
IN
G
F A
S C
IA
H
E
IG
H T
FILLER CUT TO FIT TO MATCH
CABINET FACE
1"
1"
EXISTING CEILING
10 1/2" CLEAR
6"
ADJUSTABLE SHELF
DRAWER UNIT
3"
4"
S E
E E
LE
LV
A T
IO
N
S
2'-1" UNO
BASE AS SCHEDULED
SEALANT AT WALLS
INTEGRAL SIDE &
BACK SPLASH, TYP
1/4" RADIUS EDGE AT ALL
OUTSIDE EDGES
SOLID SURFACE COUNTERTOP
1X3 NOMINAL HARDWOOD OR
PLYWOOD FRAME AND WEB
SUPPORT(S)
FACE OF CABINET
1/
2"
U N
O
4"
USE EXISTING WALL
BRACING FOR WALL
AND BASE
CABINETS. PROVIDE
ADDITIONAL WALL
BRACING/BACKING
AS NECESSARY TO
SUPPORT NEW
CABINETS
1"
8" 3"
9"
2' -3
S E
E E
LE
V
A T
IO
N
LAY-IN STAINLESS STEEL
SINK - SEE PLUMBING
CLEAR WHEEL
CHAIR CLEARANCE
PROVIDE REMOVABLE 3/4" THICK
PLAM FASCIA PANEL. CONTINUOUS,
FULL LENGTH OF VANITY
1"
1' -1
/4
2'-1"UNO
1'-7"
8"
1/
2"
1. REFER TO PROJECT MATERIAL SCHEDULE ON THIS SHEET AND PROJECT
SPECIFICATIONS FOR SPECIFIC PRODUCT SELECTION REQUIREMENTS
2. MANUFACTURER'S TRADE NAMES AND NUMBERS USED IN MATERIAL SCHEDULES
ARE ONLY TO IDENTIFY COLORS, FINISHES, TEXTURES AND PATTERNS. PRODUCTS
OF OTHER MANUFACTURERS CONSISTENT WITH THE COLORS, FINISHES, TEXTURES,
PATTERNS AND, AT MINIMUM, MEETS THE TECHNICAL SPECIFICATIONS WILL BE
REVIEWED IN ACCORDANCE WITH SPECIFICATION SECTION 01 33 23 SHOP
DRAWINGS, PRODUCT DATA, AND SAMPLES
3. FIELD FINISH VENTS, GRILLES, ACCESS PANELS, PLUG STRIP, BASEBOARD
RADIATION ENCLOSURES, ELECTRICAL PANEL BOARDS (IN FINISHED SPACES) TO
MATCH SURFACE ON WHICH THEY OCCUR UNLESS OTHERWISE INDICATED.
EXCEPTION: ITEMS WITH FACTORY WHITE FINISH, OCCURRING ON WHITE ACT OR
WHITE GYPSUM BOARD CEILING MUST NOT BE PAINTED. STAINLESS STEEL ITEMS
MUST NOT BE PAINTED
4. FIELD VERIFY ALL NEW CONDITIONS. NOTIFY ARCHITECT OF ANY DISCREPANCIES
PRIOR TO INSTALLATION
5. PROVIDE SEALANT AT JOINT BETWEEN COUNTER TOP, BACK OR SIDE SPLASH AND
WALLS
6. PROVIDE CLEAR SILICONE SEALANT AT THE BASE OF DOOR FRAME TO RESILIENT
AND CT FLOORING, TYP. SEE PLANS AND ROOM FINISH SCHEDULE FOR FLOOR FINISH
LOCATIONS
7. WOOD DOORS AND HOLLOW METAL FRAMES TO BE PAINTED P-2, UNLESS NOTED
OTHERWISE IN THE OPENING SCHEDULE
8. WOOD: PRE-FINISHED TO MATCH BUILDING STANDARD, REFER TO SPECIFICATION
9. CEILING HEIGHTS AND MATERIALS/FINISHES CALLED OUT IN ROOM FINISH
SCHEDULE ARE FOR ENTIRE CEILING OR MAJORITY OF THAT ROOM, UNLESS
OTHERWISE INDICATED. SEE REFLECTED CEILING PLAN FOR CHANGES IN CEILING
MATERIAL AND CEILING HEIGHT. PAINT ALL SURFACES OF SOFFIT SAME COLOR AS
INDICATED
10. COLOR SELECTIONS ARE BASED ON USE OF PRODUCTS INDICATED IN THE
PROJECT MATERIAL SCHEDULE.