36C78619R0083-0003003.pdf
PDF Posted
- Attached to
- FY19 CSD Continental District - Ft Logan - Mini-Minor Project for Admin Bldg Addition Federal contract opportunity
- Solicitation number
- 36C78619R0083
About this file
This document outlines technical specifications for network cabling installations at Department of Veterans Affairs facilities. The National Cemetery Administration is soliciting offers for a 900 square foot building addition and restroom at Fort Logan National Cemetery, including furnishing labor, materials, tools, equipment and supervision to construct according to specifications, drawings, codes and requirements. The acquisition is set aside for Service-Disabled Veteran-Owned Small Businesses. Offerors must be registered in SAM and representations certified at sam.gov. Electronic solicitations will be available at fbo.gov on August 9th with proposals due as specified. Proposals must be submitted through VA's eCMS Vendor Portal at vendorportal.ecms.va.gov.
The first document provides specifications for network cabling at VA facilities, including categories, labeling, testing requirements and points of contact. The second announces a solicitation for a building addition at Fort Logan National Cemetery, with an SDVOSB set-aside, registration requirements, and proposal submission instructions.
36C78619R0083 0003 S06_Amendment-0003_Attach-3_NCA Cabling Spec 2016.pdf
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| 36C78619R0083-0003000.docx | DOCX document | |
| 36C78619R0083-0003002.pdf | ||
| 36C78619R0083-0003001.pdf | ||
| 36C78619R0083-0002000.docx | DOCX document | |
| 36C78619R0083-0001000.docx | DOCX document | |
| 36C78619R0083-0001001.pdf | ||
| 36C78619R0083-0001002.pdf | ||
| 36C78619R0083-001.docx | DOCX document | |
| 36C78619R0083-005.pdf | ||
| 36C78619R0083-007.xlsx | XLSX spreadsheet | |
| 36C78619R0083-004.pdf | ||
| 36C78619R0083-006.pdf | ||
| 36C78619R0083-002.pdf | ||
| 36C78619R0083-003.pdf |
Show all 14
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Department of Veterans Affairs
Enterprise Operations, Quantico ITC 01/14/2016
Department of Veterans Affairs
Office of Information & Technology
Enterprise Operations
Quantico Information Technology Center
Network Cabling Specifications
National Cemetery Administration
January 14, 2016
Quantico Information Technology Center . 5101 Russell Road . Quantico, VA 22134 . v. 703.441.3000 f. 703.441.3068
Table of Contents
1. Networks & Communications Staff Information
2. General
2.1 Codes of Practice
2.2 Documentation
2.3 Network Equipment
2.4 Network Equipment Environment
3. Unshielded Twisted Pair (UTP) Category 6
3.1 Network Configuration Constraints
3.2 Installation Constraints
3.2.1 Installation Standards
3.2.2 General Requirements
3.2.3 Data Outlets
3.2.4 Horizontal Cabling
3.2.5 Network Outlet and Labeling
3.2.6 Cable Installation
3.2.7 Patch Cables
3.3 Inter-Building Cabling
3.3.1 Wiring Maintenance and other Local Buildings
3.3.2 Connecting Maintenance and other Local Buildings with the Admin Building
3.3.3 Radio Frequency Transmission Bridges
3.4 Testing
3.5 Documentation
4. Optical Fiber Cable (Ethernet)
4.1 Fiber Network Configuration Constraints
4.2 Installation Constraints
4.3 Testing
4.4 Documentation
1. Networks & Communication Staff Information
Data cable specifications and installations for local area networks in VA National Cemetery Administration and maintenance buildings. For technical inquiries relating to these standards, contact either the project Contracting Officer or:
Ron F. Reuschling (author) Department of Veterans Affairs Director, Quantico Information Technology Center 5101 Russell Road
Quantico, VA 22134 Email: ron.reuschling@va.gov Voice: 703.441.3098 Cell: 540-846-3034 Fax: 703.441.3068
Kurt R Hashbarger
Chief, Network Engineering Quantico Information Technology Center 5101 Russell Road Quantico, VA 22134 Email: kurt.hashbarger@va.gov Voice: 703-441-3073 Cell: 703-504-8151 Fax: 703-441-3068
QITC Network Engineering NCANetwork@va.gov Voice: 703-441-3000 Fax: 703-441-3068 mailto:ron.reuschling@va.gov mailto:kurt.hashbarger@va.gov mailto:NCANetwork@va.gov
2. General 2.1 Codes of Practice
Adherence to the VA/NCA Network Cable Specifications by cabling installation contractors is a condition of contract. In the event the cabling installation is sub-contracted by the prime contractor, the prime contractor will supply a copy of these specifications to the sub-contractor. This requirement shall cover all levels of sub-contracting.
Any variations to the issued job specification shall be referred for approval to the Contracting Officer Technical Representative (COTR). VA Quantico Information Technology Center (ITC) also must approve these variations.
Contractors shall install all cable and cabling products with a proven track record for data network cabling installations. Such installations shall also meet all requirements as set out in this specification.
Un-terminated "future capacity" cables are not permitted. All installed cables shall be terminated at each end and documentation, labeling and (where applicable) test results provided. This applies to all permanently installed cable types.
2.2 Documentation
At least two copies of documents describing the data cable installation shall be provided. A copy to be supplied to:
1. Director, VA National Cemetery for which the work is being performed.
2. COTR for approval by VA Quantico ITC
2.3 Network Equipment
VA Quantico ITC must approve the installation or removal of network hardware equipment. Non- VA/NCA staff shall carry out such work only with prior approval from the VA Quantico ITC.
2.4 Network Equipment Environment
Punch down area(s) (location of the data communication rack(s)) will be determined by the building Architect/Engineer and the Quantico ITC.
Contractor shall supply 100BaseT, Category 6 certified rack-mounted modular RJ45 punch down block/panel (24/48 ports) for jacks meeting the ANSI/EIA/TIA 568- B Category 6 standards.
Contractor will supply 1 9”W x 84”H steel data communication lockable rack with three (3) rack mounted cantilever shelves (19”W x 18”D). or a 19” X 18”D X 25 1/4” wall mounted lockable IT cabinet with Vent fans if the IT closet does not have a lockable door.
Contractor will supply a heavy-duty power strip (minimum 5 outlets) with surge suppression.
Each jack on the punch down block/panel will correspond with the jack at the wall device faceplate.
Where network equipment is to be located in a secure room or large closet, the room or closet shall have a dry powder extinguisher, suitable for electrical fires, provided and installed within the room. Adequate through flow ventilation shall be provided in a manner that does not compromise the security of the closet.
3. Unshielded Twisted Pair (UTP) Category
IEEE 802.3 100BaseT UTP Level 6, 24 AWG plenum rated cable. Insulation - high-speed data grade. Sheath - high temperature UL data grade.
3.1 Network Configuration Constraints
Each segment comprises a four pair Category 6 cable. Pin all 8 conductors.
Maximum link length - 90 meters Maximum channel length - 100 meters Maximum number of stations per segment - 1.
3.2 Installation Constraints
3.2.1 Installation Standards
Cable and connecting hardware will meet or exceed the CAT6 specifications and shall be used throughout, with pairs terminated according to the T568B wiring scheme.
3.2.2 General Requirements
The cabling system shall include all patch panels, horizontal cables, transition blocks, vertical cabling, modular jacks, system cables, patch cables, cable management, and a comprehensive labeling system.
3.2.3 Data Outlets
The following information represents a minimum requirement for the number of UTP outlets that shall be installed in each type of workspace.
If the construction at the location of the data outlet is drywall, provide flush-mounted single-gang outlet boxes with two-port base plates and applicable wall device faceplates (cable to be installed behind drywall).
If the construction at the location of the data outlet is a solid wall, provide surface-mounted single-gang outlet boxes with two-port base plates and applicable wall device faceplates (cable to be installed in plastic wall mold equipped with protective insulator or sleeve).
Where modular furniture is used, the location of the data outlet will be in the baseboard of the furniture, where the networked equipment (computers, printers, etc) will be located.
Provide flush-mounted single gang outlet boxes with two-port base plates and applicable wall device faceplates. If flush-mounted single-gang outlet boxes cannot be used, then modular
Surface mount boxes will be used with two-port inserts. All cable runs in modular furniture will be through furniture wire baseboard ducts/conduit.
3.2.4 Horizontal Cabling
The horizontal wiring shall be a star topology connecting each network outlet jack to a jack on a patch panel rack in a communications enclosure/room.
The cable used shall be 4-pair 100-ohm high performance, 24 AWG solid conductor, and unshielded twisted pair cable, meeting or exceeding the Category 6 specification.
3.2.5 Network Outlet and Labeling
Each network outlet faceplate shall incorporate one or more modular, universal RJ45 IDC jack sockets meeting or exceeding the Category 6 specification. Label each jack at this wall device faceplate to correspond with the label on the patch panel jack (D1, D2, etc.). All numbering should be readily visible.
3.2.6 Cable Installation
The cable interconnecting a network outlet to the patch panel shall be one continuous length with no intermediate joins, splices or taps.
Cable termination onto a horizontal distribution panel or patch panel shall be undertaken in a manner that permits additional cables to be terminated without unduly disturbing previously installed cables.
Each data outlet / device location will have two (2) cable runs that will terminate in the punch down block/panel at the punch down area.
No more than 24 cables shall be cable tied in a bunch.
A 2-meter loop of cable shall be left within or on the approach to each communications room/enclosure to facilitate re-termination of the cable in the future, should this be required.
Such cable slack shall be coiled and supported in a neat and practical manner.
A 0.5-meter loop of cable shall be left in the trunking on the approach to each network outlet to facilitate re-termination of the cable in the future, should this be required.
The amount of untwisting in a pair as a result of termination to connecting hardware shall be no greater than 13mm, and less than this if possible.
Cable bend radii shall be no less than eight times the cable diameter or as specified by the cable manufacturer; whichever is the greater.
Precautions shall be observed to eliminate cable stress caused by tension in suspended cable runs and tightly strapped bundles.
Cable bundles shall not rub on, or be unduly compressed against any building infrastructure, building equipment, cable tray, equipment racking, or other cable support.
Cable bundles shall not obstruct the installation and removal of equipment in equipment racks.
Where UTP cables are run parallel with electrical cables the following minimum separation rules shall be observed:
Circuit rating Unshielded power/data Shielded power/data
< 1 KVA 300mm 25mm
> 1 < 2 KVA 450mm 50mm
> 2 < 5 KVA 600mm 150mm
5 KVA 1500mm 300mm
Where UTP cables are run in the proximity of electrical motors or transformers the minimum separation shall be 1 meter.
In situations where the above minimum distances cannot be applied due to a lack of available space, data cables shall be enclosed in rigid and/or flexible steel conduit. Conduit shall be bonded to a protective ground at one point in the installation. No steel cabling enclosure medium shall be installed without having continuity to a protective ground.
3.2.7 Patch Cables
The cable to be used for copper patch shall be 4 pair 100-ohm high performance, stranded conductor, unshielded twisted pair cable, meeting or exceeding the Category 6 specifications.
The cable to be used for fiber patch shall be of the same type (multi-mode or single mode – see specifications in section 4 below) of what is used to connect the buildings.
Each patch lead shall be terminated in RJ45 connectors (male) meeting or exceeding the Category 6 specification.
Contractor will supply one (1) 4’ category 6 patch cable with RJ45 connectors (male) for every cable run installed into the patch panel. This will allow connectivity between the patch panel and VA supplied switch.
Contractor will supply one (1) 25’ category 6 patch cable with RJ45 connectors (male) for every cable run terminated at the user/device work location. This will allow connectivity from the networked device (computer, printer, etc) to the wall jack.
The Quantico ITC will supply the multi-mode or single-mode fiber patch cables with SC or ST connectors. This will allow connectivity from the demarcation point of the fiber to the switch. Ensure the demarcation point of the fiber is within 10’ from the patch panel.
3.3 Inter-Building Cabling
3.3.1 Wiring Maintenance or other local buildings:
If local network connectivity for Maintenance or other local buildings is required, follow all specifications as stated in this document.
3.3.2 Connecting Maintenance or other local buildings with the Administration Building:
If the distance between the punch down area in the Administration Building to the punch down area in the Maintenance Building does not exceed 100m or 328’ (maximum length of the cable run), then 100BaseT UTP Level 6 24AWG plenum 4 pair cable may be used. Two cables will be required and must be installed in conduit that will connect the two buildings.
If the distance to the punch down area in the Maintenance Building exceeds 100m / 328’ but is no more than 2km / 1.24 miles (maximum length of the cable run), then use a multimode fiber 6 strand 62.5x125 microns cable (see Section 4). Cable should be routed as shown on the contract drawing.
If the distance to the maintenance building exceeds 2km / 1.24 miles but is no more than 5km / 3.10 miles, then single-mode fiber 6 strand 8x125 microns is recommended (see Section 4).
If fiber is used to connect multiple buildings, a minimum of 6 strands will be required and must be installed in conduit. All fiber will be terminated within a fiber termination box (at both ends) with SC or ST connectors. All bends will be made with long radius conduit.
Below is a list of hardware that is required if fiber is installed. VA Quantico ITC will supply the Cisco Catalyst Switch for installation by the contractor on an approval basis.
Contact the COTR to arrange delivery.
Multi-mode Cisco Catalyst 2960-8/24/48
Cisco GLC-FE-100FX LC to SC/ST patch cable Multi-mode Fiber 62.5x125 microns SC/ST connectors
Single-mode Cisco Catalyst 2960-8/24/48 Cisco GLC-FE-100LX LC to SC/ST patch cable Single-mode Fiber 8.3x125 microns SC/ST connectors
3.3.3 Radio Frequency Transmission Bridges
Where copper or fiber transmissions are not possible due to distance, obstacles or funding, another option to connect multiple buildings within a facility includes radio frequency transmission bridges. This solution can be cost effective, however, provides limited bandwidth and has special requirements. Several cemeteries are utilizing this RF solution with remote bridges. NCA utilizes the Cisco Aironet encrypted wireless bridge for this transmission design. All wireless installations will be documented and supplied to the Quantico ITC; this includes but is not limited to configurations, passwords, and diagrams.
3.4 Testing
Testing shall be carried out with building electrical services operating (lighting, power, air conditioning plant and lift services where applicable).
Wiring shall be tested to verify the continuity, integrity and polarity of the cable according to the specified pin and pair grouping assignments.
3.5 Documentation
The contractor shall provide installation documentation at the completion of the cabling system installation.
The contractor shall certify that the cabling system meets the UTP cabling system requirements for Category 6 performance levels.
4. Optical Fiber Cable (Ethernet)
Multi-mode Fiber:
Core diameter 62.5 microns Cladding diameter 125 microns Prim. Acryl. Buffer diameter 250 microns Proof test not less than 50kpsi.
Numerical aperture 0.275 Attenuation not greater than 4dB/km @ 850nm.
Bandwidth not less than 160MHz/km @ 850nm.
Termination: All Multi-mode terminations shall be made with SC or ST connectors
Single-mode Fiber Core Diameter 7 - 9 microns Cladding diameter 125 microns Prim. Acryl. Buffer diameter 250 microns
Proof test not less than 50kpsi.
Numerical aperture 0.11 Attenuation not greater than 0.5dB/Km @ 1310nm. not greater than 0.4dB/Km @ 1550nm.
Termination: All Single-mode terminations shall be made with SC or ST connectors
4.1 Fiber Network Configuration Constraints
Maximum Single-mode segment length – 5 km Maximum Multi-mode segment length - 2 km
4.2 Installation Constraints
Minimum bend radius (during installation) - not less than 20 X outside diameter of cable.
Minimum bend radius (as installed) - not less than 10 X outside diameter of cable or the manufacturer’s specification, whichever is the greater.
During installation the pulling force shall not exceed the manufacturer’s specified maximum.
Cable slack shall be provided as follows:
Within pits - 2 meters minimum.
At a termination location - 2 meters minimum.
Within a termination enclosure - 0.5 meter minimum.
All fiber cable terminations are to be SC or ST connectors. When using a wall or rack mount enclosure, a patch cord protector shall be included in the installation.
4.3 Testing
100% Insertion Loss (light source and power meter) testing of all terminated fibers shall be performed in both directions at 850nm for multimode cables and 1310nm for single mode cables.
OTDR tests shall be performed at high wavelength, if the distance is greater than 500m at 131 0nm for multimode cables and greater than 1 000m at 1 550nm for single mode cables.
Optical loss covers the total loss between two corresponding optical ports and must include allowances for losses due to fiber, connectors, passive optical components, splices and any margin for maintenance. This loss shall not exceed 5db.
Copies of all test results are to be provided to the VA Quantico ITC on completion of the project.
4.4 Documentation
Documentation of a cable installation shall comprise the following with copies provided to the cemetery director and the Quantico ITC Network Section (See Contact information at beginning of document):
Cable type Route followed Pit locations (where applicable) Building names Building Cable Diagrams (internal/external) showing locations of each drop or termination point Configurations of equipment.
Table of losses for each core