36C78619R0052-007.pdf
PDF 1 MB Posted
- Solicitation number
- 36C78619R0052
About this file
36C78619R0052 802-MM19-02 - Shelter Structural.pdf
View the file
Other files
| File | Type | Posted |
|---|---|---|
| 36C78619C0097-000.docx | DOCX document | |
| 36C78619R0052-A0004000.docx | DOCX document | |
| 36C78619R0052-A0003000.docx | DOCX document | |
| 36C78619R0052-A0003001.pdf | ||
| 36C78619R0052-A0002000.docx | DOCX document | |
| 36C78619R0052-A0001000.docx | DOCX document | |
| 36C78619R0052-004.pdf | ||
| 36C78619R0052-001.docx | DOCX document | |
| 36C78619R0052-006.pdf | ||
| 36C78619R0052-008.pdf | ||
| 36C78619R0052-003.pdf | ||
| 36C78619R0052-002.pdf | ||
| 36C78619R0052-005.pdf | ||
| 36C78619R0052-009.pdf | ||
| 36C78619R0052-010.pdf | ||
| 36C78619R0052-000.docx | DOCX document |
Show all 16
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
TOP OF
TYPICAL DETAIL
SCALE: 3/4"=1'-0"
SECTION ELEVATION
PARTIAL PLAN CALLOUT
ELEVATION REF
GRID BUBBLE
NORTH ARROW
REVISION
CLOUD &
TRIANGLE
NOTEDETAIL
NUMBER
PLAN AND SECTION TITLE
S-200
OH
S-100
SIM
S-300
SIM
SLAB ON GRADE
ELEV. 0'-0"
REV
SHEET
NUMBER
NOTEDETAIL
NUMBER
SHEET
NUMBER
DETAIL
NUMBER
SHEET
NUMBER
NOTE
ASTM AMERICAN SOCIETY FOR TESTING AND MATERIALS
ADDL ADDITIONAL
ARCH ARCHITECTURAL
B BOTTOM BARS
BLDG BUILDING
BOT BOTTOM
BTW BETWEEN
CL CENTERLINE
CLR CLEAR
CONC CONCRETE
CONT CONTINUOUS
DET DETAIL
DIM DIMENSION
DWG DRAWING
EL ELEVATION
EXIST EXISTING
FDN FOUNDATION
FF FINISHED FLOOR
FTG FOOTING
GALV GALVANIZED
GC GENERAL CONTRACTOR
GEN GENERAL
HDG HOT-DIP GALVANIZED
MANUF MANUFACTURER
MAX MAXIMUM
MIN MINIMUM
MISC MISCELLANEOUS
OC ON CENTER
PROJ PROJECT
REINF REINFORCED
SIM SIMILAR
SPEC SPECIFICATION
SQ SQUARE
SS STAINLESS STEEL
STD STANDARD
STIFF STIFFENER
STL STEEL
STRUCT STRUCTURAL
SW SHORT WAYS
SYM SYMMETRICAL
TOF TOP OF FOOTING
TOW TOP OF WALL
TYP TYPICAL
UNO UNLESS NOTED OTHERWISE
STRUCTURAL LINE TYPES
STRUCTURAL WALL TYPES
STRUCTURAL PATTERNS
CONCRETE
CRUSHED STONE
WOOD TRUSS,
DELEGATED DESIGN
CONCRETE
CONTINUOUS
HIDDEN LINE,
FOUNDATION,
SLAB OUTLINE
ROOF OUTLINE
STONEWORK
Location: Baltimore National Cemetery
5501 Frederick Ave., Catonsville, Baltimore County, MD 21228
Issue Date
S T
A M
P
Project Number
Building Number
Drawing Number
Project Title
Checked Drawn
Drawing Title
Approved:
U.S. Department of Veterans Affairs
Phase
ARCHITECT OF RECORDCONSULTANTS
Project Director
Revisions: Date:
Office of Construction and Facilities Management
VA FORM 08 - 6231
F ile
P a th
/1
/2
:3
:0
P
M
100% CONSTRUCTION DOCUMENTS
March 25, 2019
NOT SUPPRESSED
C
ARCHITURA CORPORATION
9880 Westpoint Drive, Suite #400
Indianapolis, IN 46256-3384
PH: (317) 348-1000
POC: Michael Conly, AIA, NCARB, President
802-MM18-05
Committal Shelter
03.25.2019 o n e e ig h th in c h o n e fo o t
F o n e q u a rt e r in c h o n e fo o t
Design Services for Committal Service Shelter ImprovementsCivil/ Structural/ Electrical Engineer:
KCI Technologies, Inc.
1352 Marrows Road, Suite 100
Newark, Delaware 19711
PH: 302.731.9176
POC: Tom deLorimier th re e e ig h th s in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e in c h o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t th re e in c h e s o n e fo o t
D
E
F
E
D
C
B
B
A
A
2 3 4 5 6 7 8 9 10
1 2 3 4 5 6 7 8 9 10
8 9
C
D
E
F
B
A
BALTIMORE NATIONAL CEMETERY
Landscape Architect:
Pashek+MTR, Ltd.
619 E. Ohio St.
Pittsburgh, PA 15212
PH:412-321-6362
POC: Kara Roggenkamp
PROFESSIONAL CERTIFICATION:
I HEREBY CERTIFY THAT THESE DOCUMENTS
WERE PREPARED OR APPROVED BY ME, AND THAT
I AM A DULY LICENSED PROFESSIONAL ENGINEER
UNDER THE LAWS OF THE STATE OF MARYLAND.
LICENSE NO: 40953 EXP. DATE: 07-21-2019
S-001
NAMARL
GENERAL STRUCTURAL NOTES,
SYMBOLS, AND ISOMETRIC
BUILDING CODES:
A. THE 2015 INTERNATIONAL BUILDING CODE (IBC) AND ALL SUBSEQUENT SUPPLEMENTS.
B. GOVERNING LOCAL BUILDING CODES AND AMENDMENTS.
DESIGN LOADS:
A. IN ADDITION TO SELF WEIGHT, THE BUILDING IS DESIGNED FOR THE FOLLOWING FLOOR
AND ROOF LIVE LOADS:
LIVE LOAD (PSF) SUPERIMPOSED DEAD LOAD (PSF)
• ROOF: 20 PSF 10 PSF
• REDUCED ROOF: 12 PSF --
B. SNOW LOAD DESIGN CRITERIA:
• GROUND SNOW LOAD ( Pg ): 25.0 PSF
• FLAT ROOF SNOW LOAD ( Pf ): 18.9 PSF
• SLOPED ROOF SNOW LOAD ( Ps ): 8.59 PSF
• EXPOSURE FACTOR ( Ce ): 0.90
• IMPORTANCE FACTOR ( Is ): 1.00
• THERMAL FACTOR ( Ct ): 1.20
• SNOW DRIFTS: N/A
C. WIND LOAD DESIGN CRITERIA:
• ULTIMATE DESIGN WIND SPEED ( Vult ): 115 MPH
• NOMINAL DESIGN WIND SPEED ( Vasd ): 89.1 MPH
• RISK CATEGORY: II
• WIND EXPOSURE: B
INTERNAL PRESSURE COEFFICIENT ( GCpi ): 0.85
D. SEISMIC LOAD DESIGN CRITERIA:
• RISK CATEGORY: II
• IMPORTANCE FACTOR ( Ie ): 1.00
• MAPPED SPECTRAL RESPONSE ACCELERATORS:
i. Ss = 0.128
ii. S1 = 0.051
• SITE CLASS: D (ASSUMED)
• DESIGN SPECTRAL RESPONSE ACCELERATORS:
i. SDS = 0.136
ii. SD1 = 0.082
• SEISMIC DESIGN CATEGORY: B
• SEISMIC RESPONSE COEFFICIENT ( Cs ): 0.045
• RESPONSE MODIFICATION FACTOR ( R ): 3.0
• SEISMIC RESISTING SYSTEM: ORDINARY REINFORCED CONCRETE
MOMENT FRAME
E. THE CONTRACTOR SHALL NOT STORE ANY CONSTRUCTION MATERIALS OR
UNDERTAKE ANY CONSTRUCTION OPERATION WHICH WILL EXCEED THE DESIGN LIVE
LOADINGS NOTED.
F. THE STABILITY OF THE STRUCTURE IS DEPENDENT UPON THE DIAPHRAGM ACTION OF
THE FLOORS AND ROOF. THE CONTRACTOR IS COMPLETELY RESPONSIBLE FOR THE
METHOD OF CONSTRUCTION AND SHALL PROVIDE ALL TEMPORARY BRACING AND
SHORING REQUIRED TO MAINTAIN THE STABILITY OF THE STRUCTURE AND TO
SUPPORT CONSTRUCTION LOADS DURING CONSTRUCTION, INCLUDING SOILS ON
WALLS FROM BACKFILLING PRIOR TO PLACING SLABS ON GRADE. DESIGN OF ALL
BRACING IS THE CONTRACTORS RESPONSIBILITY.
G. ALL EXTERIOR CEILINGS AND SOFFITS SHALL BE DESIGNED FOR THE LOADS INDICATED
OR SPECIFIED BY THE BUILDING CODE.
SPREAD FOOTING FOUNDATIONS:
A. REFER TO "CAST IN PLACE CONCRETE" FOR APPLICABLE CODES AND STANDARDS.
B. REFER TO PROJECT GEOTECHNICAL REPORT BY JOHN D HYNES & ASSOCIATES, INC.
AND DATED OCTOBER 3, 2018 FOR SITE PREPARATION AND RECOMMENDATIONS::
a. MINIMUM DEPTH TO BOTTOM OF EXTERIOR FOOTINGS FOR FROST PROTECTION
= 30 INCHES BELOW GRADE
b. NET ALLOWABLE BEARING CAPACITY = 2500 PSF
C. THE ALLOWABLE SOIL BEARING PRESSURE SHALL BE FIELD VERIFIED BY A
REGISTERED GEOTECHNICAL ENGINEER AND APPROVED PRIOR TO PLACING
FOUNDATIONS. SHOULD THE ACTUAL SOIL BEARING PRESSURE BE LESS THAN 2000
PSF, THE CONTRACTOR SHALL IMMEDIATELY NOTIFY THE ENGINEER.
D. ALL EXCAVATION AND BACKFILLING OPERATIONS WITHIN THE BUILDING FOOTPRINT,
INCLUDING ALL COMPACTION TESTS AND INSPECTIONS, SHALL BE DONE UNDER THE
DIRECTION AND SUPERVISION OF A REGISTERED GEOTECHNICAL ENGINEER.
E. ALL EXISTING SOIL CONTAINING GRAVEL, CONSTRUCTION OR DEMOLITION DEBRIS,
ORGANIC SUBSTANCES, OR OTHER FOREIGN OBJECTS SHALL BE REMOVED FROM THE
REGION WITHIN THE FOOTPRINT OF THE STRUCTURE.
CAST IN PLACE CONCRETE:
A. CODES AND STANDARDS:
a. ACI 301 “SPECIFICATIONS FOR STRUCTURAL CONCRETE FOR BUILDINGS”
b. ACI 318 “BUILDING CODE REQUIREMENTS FOR REINFORCED CONCRETE”
c. ACI 117 "SPECIFICATIONS FOR TOLERANCES FOR CONCRETE CONSTRUCTION
AND MATERIALS"
d. ACI 305 "RECOMMENDED PRACTICE FOR HOT WEATHER CONCRETING"
e. ACI 306 "RECOMMENDED PRACTICE FOR COLD WEATHER CONCRETING"
f. ACI 347 "RECOMMENDED PRACTICE FOR CONCRETE FORM WORK"
g. ACI 315 "DETAILS AND DETAILING OF CONCRETE REINFORCEMENT”
h. CRSI "MANUAL OF STANDARD PRACTICE"
B. REINFORCING MATERIALS:
a. STEEL REINFORCEMENT: ASTM A 615, GRADE 60, DEFORMED
b. PLAIN-STEEL WELDED WIRE REINFORCEMENT: ASTM A 185
C. CONCRETE MATERIALS:
1. PORTLAND CEMENT: ASTM C 150, TYPE I/II
2. FLY ASH: ASTM C 618, CLASS F
3. GROUND GRANULATED BLAST FURNACE SLAG: ASTM C 989, GRADE 120
GENERAL STRUCTURAL NOTES
4. NORMAL WEIGHT AGGREGATES: ASTM C 33
• MAXIMUM COARSE AGGREGATE SIZE: 1 INCH NOMINAL
• FINE AGGREGATE SHALL BE FREE OF MATERIAL WITH DELETERIOUS
REACTIVITY TO ALKALI IN CEMENT.
5. LIGHT WEIGHT AGGREGATES: ASTM C 330, 1 INCH NOMINAL
MAXIMUM AGGREGATE SIZE
6. WATER: ASTM C 94, POTABLE
D. ADMIXTURES:
1. AIR ENTRAINMENT: ASTM C 260
2. WATER-REDUCER: ASTM C 494
3. SILICA FUME: ASTM C 1240
4. NO ADMIXTURES CONTAINING CALCIUM CHLORIDE SHALL BE PERMITTED.
E. CONCRETE MIXTURES:
1. FLY ASH, POZZOLAN, GROUND GRANULATED BLAST FURNACE SLAG, AND SILICA
FUME MAY BE USED AS NEEDED TO REDUCE THE TOTAL AMOUNT OF PORTLAND
CEMENT WHICH WOULD OTHERWISE BE USED BY NOT MORE THAN 40 PERCENT.
• MAXIMUM SUBSTITUTION OF FLY ASH SHALL BE 20 PERCENT.
• MAXIMUM SUBSTITUTION OF SILICA FUME SHALL BE 10 PERCENT.
F. PROPORTION NORMAL WEIGHT CONCRETE MIXES AS FOLLOWS:
28 DAY WATER-CEMENT SLUMP AIR
LOCATION STRENGTH (f'c) RATIO LIMIT CONTENT
FOUNDATIONS 4000 PSI 0.50 4" ± 1" 6.0% ± 1.5%
COLUMNS 4000 PSI 0.50 4" ± 1" 6.0% ± 1.5%
AND WALLS
G. ALL CONCRETE MIX DESIGNS, INCLUDING CEMENT CONTENT, WATER CEMENT RATIO,
FINE AND COARSE AGGREGATE CONTENT AND ALL ADMIXTURES, SHALL BE REVIEWED BY
ENGINEER PRIOR TO PLACING FIRST CONCRETE.
H. ALL CONCRETE SHALL BE SAMPLED AND TESTED BY THE TESTING AGENCY. THE
CONTRACTOR SHALL NOTIFY THE TESTING AGENCY 48 HOURS PRIOR TO THE PLACING
OF ANY CONCRETE.
J. THE CONCRETE STRUCTURE SHALL NOT SUPPORT THE DESIGN LIVE LOAD FOR A MINIMUM
OF 28 DAYS AND ALL SHORING AND RESHORING REQUIRED TO SUPPORT THE
CONCRETE STRUCTURE DURING CONSTRUCTION SHALL BE DESIGNED AND PROVIDED BY
THE CONTRACTOR. SHOP DRAWINGS, SIGNED AND SEALED BY A REGISTERED
ENGINEER IN THE STATE OF MARYLAND, SHALL BE SUBMITTED FOR REVIEW. SHOP
DRAWINGS SHALL INDICATE THE TYPE, EXTENT, SIZE, AND LOCATION OF ALL SHORING
AND RESHORING AS WELL AS THE SEQUENCE OF CONSTRUCTION.
K. MINIMUM COVER FOR ALL REINFORCING SHALL BE AS FOLLOWS UNLESS OTHERWISE
INDICATED:
FOUNDATIONS 3 INCHES
COLUMNS 2 INCHES
WALLS 2 INCHES
L. THE GENERAL CONTRACTOR SHALL SUBMIT PLANS SHOWING ALL PENETRATIONS THROUGH
THE FRAMED CONCRETE SLABS. THE OPENINGS SHALL BE ACCURATELY SHALL BE
ACCURATELY LOCATED AND DIMENSIONED.
M. CONTRACTOR SHALL REFER TO ARCHITECTURAL DRAWINGS FOR CONCRETE FINISHES.
N. NON-METALLIC, SHRINKAGE RESISTANT GROUT: ASTM C 1107 WITH MINIMUM
COMPRESSIVE STRENGTH OF 5000 PSI AT 28 DAYS.
DELEGATED DESIGN:
A. WOOD TRUSSES ARE DELEGATED DESIGN AND ARE INDICATED ON THE DRAWINGS WITH
NOTES AND HATCHING. SEE “WOOD TRUSS, DELEGATED DESIGN” HATCH IN THE
STRUCTURAL LEGEND.
B. THE RIDGE BEAM IS INCLUDED IN THE DELEGATED DESIGN AND SHALL BE A SPF NO. 1 4X12
AT MINIMUM. RIDGE BEAM-TO-TRUSS CONNECTION SHALL BE DESIGNED BY THE TRUSS
MANUFACTURER.
C. THE TRUSS OUTRIGGERS ARE DELEGATED DESIGN. SEE THE ARCHITECTURAL DRAWINGS
FOR MORE INFORMATION.
D. IT IS THE RESPONSIBILITY OF THE TRUSS MANUFACTURER TO DESIGN THE LATERAL FORCE
RESISTING SYSTEM. THE LATERAL FORCE RESISTING SYSTEM IS TO BE DESIGNED IN
ACCORDANCE WITH THE LOCAL BUILDING CODES AND MINIMUM DESIGN PARAMETERS
STATED IN THE GENERAL NOTES.
E. THE ROOF STRUCTURE SYSTEM INDICATED ON THE DRAWINGS IS FOR REFERENCE ONLY
AND SHALL NOT BE CONSIDERED FINAL DESIGN.
F. TRUSS LOADING DIAGRAMS ARE PROVIDED ON DETAIL 6/S-102. TRUSSES SHALL BE
DESIGNED TO WORK WITH THE CONNECTIONS SPECIFIED IN THIS DRAWING PACKAGE. IF
THE END REACTIONS OF THE TRUSSES EXCEED THE MAXIMUM LOADS ALLOWED BY THE
CONNECTIONS, IT SHALL BE THE RESPONSIBILITY OF THE TRUSS MANUFACTURER TO
PROPOSE NEW CONNECTIONS AND TO PROVIDED SIGNED AND SEALED CALCULATIONS.
G. TRUSSES SHALL BE SPACED AT A 2 FOOT MAXIMUM. TRUSS MANUFACTURER IS
RESPONSIBLE FOR CONFIRMING THAT THEIR DESIGNATED SPACING ALLOWS ROOM FOR THE
CONNECTIONS SPECIFIED IN THIS DRAWING PACKAGE.
H. FOR SUBMITTAL INFORMATION, SEE WOOD FRAMING NOTES ON THIS SHEET.
J. THE DELEGATED DESIGN ELEMENTS DESCRIBED HEREIN ARE TO BE SUBMITTED TO THE
ENGINEER OF RECORD FOR APPROVAL PRIOR TO FINAL ACCEPTANCE OF DESIGN AND
FABRICATION. IF THE PROVIDED DESIGN BY OTHERS DOES NOT MEET THE REQUIREMENTS
PRESENTED ON THIS DRAWING, THE ENGINEER OF RECORD MAY REFUSE THE SUBMITTAL.
K. BOTTOM CHORD DEFLECTION SHALL NOT EXCEED L/360 OR 1 INCH, WHICHEVER IS STRICTER.
L. TOP CHORD MEMBERS SHALL BE 2X8.
WOOD FRAMING
A. CODES AND STANDARDS:
a. “NATIONAL DESIGN SPECIFICATIONS” PUBLISHED BY THE NATIONAL FOREST
PRODUCTS ASSOCIATION.
b. NIST'S VOLUNTARY PRODUCT STANDARD DOC PS 20 "AMERICAN SOFTWOOD LUMBER
STANDARD"
c. NIST'S VOLUNTARY PRODUCT STANDARD DOC PS 2 "PERFORMANCE STANDARD FOR
WOOD BASED STRUCTURAL PANELS"
d. TRUSS PLATE INSTITUTE’S “DESIGN SPECIFICATIONS FOR LIGHT METAL PLATE
CONNECTED WOOD TRUSSES”
e. AMERICAN WOOD PRESERVER'S ASSOCIATION (APWA) STANDARD
B. MATERIALS (UNADJUSTED VALUES FOR 12" DEPTH):
a. DIMENSION LUMBER NO. 1 SPRUCE-PINE-FIR:
Fb : Fv : Fc(perp) : Fc(parallel): Ft : E :
875 PSI 135 PSI 335 PSI 1050 PSI 400 PSI 1200 KSI
b. PRESERVATIVE TREATMENT BY PRESSURE PROCESS (P.T.) LUMBER: AWPA U1
• INTERIOR CONSTRUCTION NOT IN CONTACT WITH GROUND: USE CATEGORY
UC2
• EXTERIOR CONSTRUCTION NOT IN CONTACT WITH GROUND: USE CATEGORY
UC3B
• ALL CONSTRUCTION IN CONTACT WITH GROUND: USE CATEGORY UC4A
c. ROOF SHEATHING: EXTERIOR, STRUCTURAL I PLYWOOD OR OSB SHEATHING, FOR
SPANS SHOWN ON DRAWINGS
C. SUBMITTALS:
a. SHOP DRAWINGS AND DESIGN CALCULATIONS FOR ALL WOOD TRUSSES INCLUDING
MEMBER LAYOUT, WOOD SPECIES AND GRADE, MEMBER SIZES, TRUSS BEARING
CONNECTION DETAILS, CAPACITY OF CONNECTOR PLATES AND THE SIZE AND
LOCATION OF ALL REQUIRED BRIDGING, SIGNED AND SEALED BY A REGISTERED
PROFESSIONAL ENGINEER.
b. WOOD PRESERVATIVE TREATMENT DATA, INCLUDING CERTIFICATION BY TREATING
PLANT THAT MATERIALS COMPLY WITH REQUIREMENTS.
c. MATERIAL CERTIFICATES FOR LUMBER SPECIFIED TO COMPLY WITH MINIMUM
ALLOWABLE UNIT STRESSES.
d. TECHNICAL DATA FOR FASTENERS, INCLUDING GAUGE, FINISH, AND STRUCTURAL
LOAD CAPACITY.
D. FASTENERS
a. WOOD FRAMING CONNECTIONS REQUIRING STEEL FASTENERS AND HANGERS SHALL
BE HOT-DIP GALVANIZED. ALL CONNECTIONS SHALL DEVELOP THE LOAD CAPACITY
OF BASIS OF DESIGN PRODUCTS INDICATED.
b. NAILING OF ALL WOOD FRAMING SHALL MEET THE MINIMUM RECOMMENDED
REQUIREMENTS PROVIDED IN THE FASTENING SCHEDULE OF THE IBC BUILDING
CODE.
E. INSTALLATION:
a. ALL WOOD MEMBERS BEARING DIRECTLY ON CONCRETE SHALL HAVE A
PRESERVATIVE PRESSURE TREATMENT.
• PROVIDE A MINIMUM 3" BEARING LENGTH OF ALL WOOD MEMBERS BEARING
ON MASONRY OR CONCRETE.
b. THE CONTRACTOR SHALL CUT OR NOTCH THE WOOD FRAMING ONLY AS SHOWN ON
THE CONTRACT DRAWINGS OR MANUFACTURER SPECIFICATIONS FOR ENGINEERED
WOOD PRODUCTS.
WELDING
A. CODES AND STANDARDS:
a. AISC “STEEL CONSTRUCTION MANUAL”, 14TH EDITION.
b. AISC 303 "CODE OF STANDARD PRACTICE FOR BUILDINGS AND BRIDGES"
c. AISC 360 "SPECIFICATION FOR STRUCTURAL STEEL BUILDINGS"
d. AWS D1.1 "STRUCTURAL WELDING CODE"
B. SUBMITTALS:
a. SHOP DRAWINGS INDICATING THE SIZES, EXTENT, AND LOCATION OF ALL
CONNECTIONS.
C. MATERIALS:
a. GALVANIZE: HOT-DIP ZINC COATING, ASTM A 123
D. CONNECTIONS:
a. WELDED CONNECTIONS: E70XX ELECTRODES
E. INSPECTIONS BY INDEPENDENT INSPECTION AGENCY:
a. WELDED CONNECTIONS: VISUAL INSPECTION, TESTING AND INSPECTION PER
AWS D1.1
b. VERIFY, WITH ERECTOR PRESENT, ELEVATIONS OF CONCRETE AND MASONRY
BEARING SURFACES AND LOCATIONS OF ANCHOR BOLTS AND OTHER EMBEDDED
ITEMS.
F. INSTALLATION
a. ALL SHOP AND FIELD WELDS SHALL BE PERFORMED BY CERTIFIED WELDERS.
b. WELDS SHALL DEVELOP THE FULL STRENGTH OF MATERIALS BEING WELDED UNLESS
OTHERWISE INDICATED.
MISCELLANEOUS:
A. THE CONTRACTOR SHALL LOCATE ALL UTILITIES IN THE AREA OF CONSTRUCTION AND
PREVENT DAMAGE TO THEM. SHOULD DAMAGE OCCUR TO ANY UTILITIES, THE CONTRACTOR
IS REQUIRED TO REPAIR THE DAMAGE TO THE SATISFACTION OF THE OWNER AT HIS OWN
EXPENSE.
B. SHOP DRAWINGS FOR ALL STRUCTURAL ELEMENTS SHOWN ON THE CONTRACT
DOCUMENTS MUST BE SUBMITTED BY THE CONTRACTOR OR OWNER FOR REVIEW BY THE
ENGINEER. IF THE CONTRACTOR OR OWNER FAILS TO SUBMIT THE SHOP DRAWINGS, THE
ENGINEER WILL NOT BE RESPONSIBLE FOR STRUCTURAL CERTIFICATION AND DESIGN OF
THE PROJECT. THE SHOP DRAWINGS SHALL INDICATE ANY DEVIATIONS OR OMISSIONS
FROM THE CONTRACT DOCUMENTS. THE GENERAL CONTRACTOR SHALL REVIEW ALL SHOP
DRAWINGS PRIOR TO SUBMISSION AND MAKE ALL CORRECTIONS DEEMED NECESSARY.
C. THE CONTRACTOR SHALL REVIEW THE ARCHITECTURAL, CIVIL, MECHANICAL AND
ELECTRICAL DRAWINGS FOR LOCATION AND DIMENSION OF CHASES, INSERTS, OPENINGS,
SLEEVES, DEPRESSIONS AND OTHER PROJECT REQUIREMENTS WHICH IMPACT THE
STRUCTURAL COMPONENTS.
D. THE CONTRACTOR SHALL CHECK AND VERIFY ALL DIMENSIONS SHOWN ON THE CONTRACT
DRAWINGS BEFORE PROCEEDING WITH CONSTRUCTION.
E. HE CONTRACTOR SHALL NOT SUBMIT REPRODUCTIONS OF THE STRUCTURAL CONTRACT
DOCUMENTS AS SHOP DRAWINGS.
F. SCALES SHOWN ON THE STRUCTURAL CONTRACT DRAWINGS ARE FOR GENERAL
INFORMATION ONLY. DIMENSIONAL INFORMATION SHALL NOT BE OBTAINED BY SCALING THE
DRAWINGS.
G. ELEVATION 100'-0" ON THE STRUCTURAL DRAWINGS IS EQUIVALENT TO 356'-6" ON THE CIVIL
AND LANDSCAPING DRAWINGS.
GENERAL AND ANNOTATIVE SYMBOLS: ABBREVIATIONS
BALTIMORE CEMETERY
COMMITTAL SERVICE SHELTER
SHEETS
S-001 - GENERAL STRUCTURAL NOTES, SYMBOLS, AND ISOMETRIC
S-100 - FOUNDATION PLAN AND ROOF COLUMN LAYOUT PLAN VIEWS
S-101 - ROOF FRAMING PLAN VIEW AND SECTION VIEWS
S-102 - STRUCTURAL DETAILS
S-103 - STRUCTURAL DETAILS
STRUCTURAL LEGEND
A
B
C
D
3' - 1 5/8" 3' - 1 5/8"
7' - 10"
S-101
S-101
F-1
EL. 97'-6"
F-1
EL. 97'-6"
F-3
EL. 97'-6"
F-1
EL. 97'-6"
F-1
EL. 95'-6"
F-2
EL. 95'-6"
F-3 SIMEL. 95'-6"
F-1EL. 95'-6"
F-1EL. 97'-6"
F-2 SIMEL. 97'-6"
W-1
EL. 97'-6"
PLAN NOTES:
1. ALL FOOTING ELEVATIONS ARE MARKED ON PLAN THUS: F-X. ELEVATION INDICATES TOP OF FOOTING.
2. ALL FOOTINGS ARE CENTERED ABOUT THE COLUMN LINES U.N.O.
/8
W-2
EL. 95'-6"
EDGE OF SLAB, REFER TO LANDSCAPE
ARCHITECTURE DRAWINGS FOR DETAILING
8' - 8 7/8" 7' - 0" 8' - 8 7/8"
EXISTING STORM
DRAIN, REFER TO
CIVIL DRAWINGS
FOR LOCATION
1 2 3 4 6 7 8 9 10
A
B
C
D
2' - 6 1/8" 2' - 6 1/8" 2' - 6 1/8"
1' - 4 1/8"
10' - 0"
1' - 4 1/8"
2' - 6 1/8" 2' - 6 1/8" 2' - 6 1/8"
/8
/8
/2
3' - 6 5/8"
7' - 0"
3' - 6 5/8"
/8
8" THICK WALL,
ISOLATE FROM
SLAB
S-101
S-101 0' - 8 1/2"
0' - 8 1/2"
1' - 4 3/8" 1' - 4 3/8"
EDGE OF SLAB, REFER TO LANDSCAPE
ARCHITECTURE DRAWINGS FOR DETAILING
1 1
ISOLATE COLUMNS FROM SLAB, TYP
BIER
/8
6' - 0"
S-102
S-102
PLAN NOTES:
1. SEE ARCHITECTURAL DRAWINGS FOR STONE VENEER INFORMATION.
2. MASONRY VENEER SHALL BE ANCHORED TO CONCRETE WITH ADJUSTABLE ANCHORS.
3. PROVIED 1 ANCHOR FOR EACH 2.67 FT2 OF WALL AREA WITH A MAXIMUM VERTICAL SPACING OF 32" AND A MAXIMUM HORIZONTAL SPACING OF 25".
4. MORTAR BED JOINT THICKNESS SHALL BE AT LEAST TWICE THE THICKNESS OF THE EMBEDDED ANCHOR.
5. REFER TO L-102 FOR TOP OF SLAB ELEVATION.
S-102
S-102
S-102
SIM
S-102
SIM
Location: Baltimore National Cemetery
5501 Frederick Ave., Catonsville, Baltimore County, MD 21228
Issue Date
S T
A M
P
Project Number
Building Number
Drawing Number
Project Title
Checked Drawn
Drawing Title
Approved:
U.S. Department of Veterans Affairs
Phase
ARCHITECT OF RECORDCONSULTANTS
Project Director
Revisions: Date:
Office of Construction and Facilities Management
VA FORM 08 - 6231
F ile
P a th
/1
/2
:3
:0
P
M
100% CONSTRUCTION DOCUMENTS
March 25, 2019
NOT SUPPRESSED
C
ARCHITURA CORPORATION
9880 Westpoint Drive, Suite #400
Indianapolis, IN 46256-3384
PH: (317) 348-1000
POC: Michael Conly, AIA, NCARB, President
802-MM18-05
Committal Shelter
03.25.2019 o n e e ig h th in c h o n e fo o t
F o n e q u a rt e r in c h o n e fo o t
Design Services for Committal Service Shelter ImprovementsCivil/ Structural/ Electrical Engineer:
KCI Technologies, Inc.
1352 Marrows Road, Suite 100
Newark, Delaware 19711
PH: 302.731.9176
POC: Tom deLorimier th re e e ig h th s in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e in c h o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t th re e in c h e s o n e fo o t
D
E
F
E
D
C
B
B
A
A
2 3 4 5 6 7 8 9 10
1 2 3 4 5 6 7 8 9 10
8 9
C
D
E
F
B
A
BALTIMORE NATIONAL CEMETERY
Landscape Architect:
Pashek+MTR, Ltd.
619 E. Ohio St.
Pittsburgh, PA 15212
PH:412-321-6362
POC: Kara Roggenkamp
PROFESSIONAL CERTIFICATION:
I HEREBY CERTIFY THAT THESE DOCUMENTS
WERE PREPARED OR APPROVED BY ME, AND THAT
I AM A DULY LICENSED PROFESSIONAL ENGINEER
UNDER THE LAWS OF THE STATE OF MARYLAND.
LICENSE NO: 40953 EXP. DATE: 07-21-2019
S-100
NAMARL
FOUNDATION PLAN AND ROOF
COLUMN LAYOUT PLAN VIEWS
FOUNDATION SCHEDULE
TYPE LENGTH WIDTH THICKNESS
TRANVERSE
BARS
LONGITUDINAL
BARS
F-1 3' - 0" 3' - 0" 1' - 0" (4)-#6 BARS T&B (4)-#6 BARS T&B
F-2 4' - 0" 4' - 0" 1' - 0" (5)-#6 BARS T&B (5)-#6 BARS T&B
F-3 4' - 6" 4' - 6" 1' - 0" (6)-#6 BARS T&B (6)-#6 BARS T&B
W-1 7' - 10" 2' - 6" 1' - 0" #4@12" T&B (4)-#4 BARS T&B
W-2 7' - 0" 3' - 0" 1' - 0" #6@12" T&B (4)-#6 BARS T&B
COLUMN SCHEDULE
TYPE
SIZE
LONG.
REINF. TIES
1 1'-0" x 1'-0" (4)-#6 BARS (3)-#4 TIES WITHIN TOP 6", THEN SPACED AT 12"
2 SEE DETAIL 7/S-101 (4)-#6 BARS (3)-#4 TIES WITHIN TOP 6", THEN SPACED AT 12"
3 SEE DETAIL 8/S-101 (4)-#6 BARS (3)-#4 TIES WITHIN TOP 6", THEN SPACED AT 12"
3/8" = 1'-0"
FOUNDATION PLAN
3/8" = 1'-0"
SLAB AND COLUMN LAYOUT PLAN
S-101
S-101
S L O
P E
S L O
P E
SLOPESLOPE
PLAN NOTES:
1. SEE ARCHITECTURAL DRAWINGS FOR ROOF SLOPE.
2. PLYWOOD PIECES SHALL BE CONNECTED TO EACH OTHER BY A SIMPSON STRONG TIE PSCL 3/4 HDG WITH 2 CLIPS PER SPAN.
/8
16' - 0 5/8" 16' - 0 5/8"
7' - 7 1/2" 7' - 7 1/2"
15' - 3"
32' - 1 1/8"
6X12 PERIMETER
WOOD BEAM, TYP
OUTRIGGER BEAM TO BE
DESIGNED BY OTHERS
RIDGE BEAM TO BE
DESIGNED BY OTHERS
FOR THE 4 END
TRUSSES (2 ON EACH
END OF THE BUILDING),
THE BEARING PLATES
SHALL BE ON THE INSIDE
OF THE CONFIGURATION
(TYP., 4 PLACES)
6X12 PERIMETER
WOOD BEAM, TYP
W O
O D
T R
U S
S S
P A
C E
D
M
A X
D
E S
IG
N
E D
B Y
O T
H E
R S
TOP OF SLAB
100' - 0"
TRUSS BEARING
109' - 0"
PEAK OF TRUSS
AT PLAN NORTH
117' - 0 1/2"
PEAK OF TRUSS
AT PLAN SOUTH
125' - 7"
ABCD
SLOPE, SEE
ARCH. DRAWINGS
ROOFING, SEE
ARCHITECTURAL
DRAWINGS
PERIMETER
WOOD BEAM,
SEE PLAN
CONCRETE COLUMN BEYOND
CONCRETE
COLUMN, SEE
SCHEDULE
CRUSHED STONE, SEE LANDSCAPE
ARCHITECTURAL DRAWINGS FOR DETAILS
SLAB, SEE
LANDSCAPE
ARCHITECTURAL
DRAWINGS FOR
DETAILS
TRUSS CONFIGURATION, TO BE
DESIGNED BY OTHERS
S-102
OUTRIGGER BEAMS TO
BE DESIGNED BY OTHERS
S-102
S-102
RIDGE BEAM TO BE
DESIGNED BY OTHERS
STONE VENEER, SEE
ARCHITECTURAL DRAWINGS
FOR DETAILS
CONCRETE WALL
CONCRETE PAVEMENT, SEE
LANDSCAPE ARCHITECTURAL
DRAWINGS FOR DETAILS
S-103
P L A
N
S E
E F
O U
N D
A T
IO
N
NOTE:
1. TOP OF SLAB = 100'-0" (CONTROL/DATUM OF 100'-00" IS EQUAL TO 356'-6" PER USGS AS SHOWN ON CIVIL AND LANDSCAPING PLANS.
SLAB, SEE LANDSCAPE
ARCHITECTURAL DRAWINGS
FOR DETAILS
TRUSS CONFIGURATION, TO
BE DESIGNED BY OTHERS
CEILING, SEE
ARCHITECTURAL DRAWINGS
SLOPE, SEE
ARCH. DRAWING
PERIMETER WOOD BEAM, SEE PLAN
ROOFING, SEE
ARCHITECTURAL
DRAWINGS
P L A
N
S E
E F
O U
N D
A T
IO
N
CONCRETE COLUMN, SEE
ROOF FRAMING PLAN
STONE VENEER, SEE ARCHITECTURAL
DRAWINGS FOR DETAILS
CONCRETE PAVEMENT, SEE LANDSCAPE
ARCHITECTURAL DRAWINGS FOR DETAILS
CRUSHED STONE, SEE LANDSCAPE
ARCHITECTURAL DRAWINGS FOR DETAILS
TOP OF SLAB
100' - 0"
TRUSS BEARING
109' - 0"
S-102
S-102
O F
C O
L L
A R
T
IE
T
O U
N D
E R
S
ID
E
RIDGE BEAM, TO BE
DESIGNED BY OTHERS
Location: Baltimore National Cemetery
5501 Frederick Ave., Catonsville, Baltimore County, MD 21228
Issue Date
S T
A M
P
Project Number
Building Number
Drawing Number
Project Title
Checked Drawn
Drawing Title
Approved:
U.S. Department of Veterans Affairs
Phase
ARCHITECT OF RECORDCONSULTANTS
Project Director
Revisions: Date:
Office of Construction and Facilities Management
VA FORM 08 - 6231
F ile
P a th
/1
/2
:3
:0
P
M
100% CONSTRUCTION DOCUMENTS
March 25, 2019
NOT SUPPRESSED
C
ARCHITURA CORPORATION
9880 Westpoint Drive, Suite #400
Indianapolis, IN 46256-3384
PH: (317) 348-1000
POC: Michael Conly, AIA, NCARB, President
802-MM18-05
Committal Shelter
03.25.2019 o n e e ig h th in c h o n e fo o t
F o n e q u a rt e r in c h o n e fo o t
Design Services for Committal Service Shelter ImprovementsCivil/ Structural/ Electrical Engineer:
KCI Technologies, Inc.
1352 Marrows Road, Suite 100
Newark, Delaware 19711
PH: 302.731.9176
POC: Tom deLorimier th re e e ig h th s in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e in c h o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t th re e in c h e s o n e fo o t
D
E
F
E
D
C
B
B
A
A
2 3 4 5 6 7 8 9 10
1 2 3 4 5 6 7 8 9 10
8 9
C
D
E
F
B
A
BALTIMORE NATIONAL CEMETERY
Landscape Architect:
Pashek+MTR, Ltd.
619 E. Ohio St.
Pittsburgh, PA 15212
PH:412-321-6362
POC: Kara Roggenkamp
PROFESSIONAL CERTIFICATION:
I HEREBY CERTIFY THAT THESE DOCUMENTS
WERE PREPARED OR APPROVED BY ME, AND THAT
I AM A DULY LICENSED PROFESSIONAL ENGINEER
UNDER THE LAWS OF THE STATE OF MARYLAND.
LICENSE NO: 40953 EXP. DATE: 07-21-2019
S-101
NAMARL
ROOF FRAMING PLAN VIEW AND
SECTION VIEWS
3/8" = 1'-0"
ROOF FRAMING PLAN
1/4" = 1'-0"
EAST SECTION VIEW
1/4" = 1'-0"
SOUTH SECTION VIEW
MINIMUM FASTENER SCHEDULE
APPLICATION NAIL
EDGE
SPA.
TYP. SPA.
3/4" THICK PLYWOOD 8d COMMON 6" 12"
TOP OF SLAB
100' - 0"
T.O.F.
97' - 6"
#4@12" O.C. BOTH
SIDES, BOTH WAYS
T A
L L
W A
L L
CONCRETE ORNAMENT WALL
F O
O T
IN
G
S C
H E
D U
L E
R E
F E
R T
O
C L R
C
L R
E M
B
H O
O K
SCHEDULE
REFER TO FOOTING
8" HOOK
1/2" ISOLATION JOINT
TYP.
2" CLR.,
NOTES:
1. SEE ARCHITECTURAL DRAWINGS FOR CAP ANCHORAGE LOCATIONS.
2. SEE ARCHITECTURAL DRAWINGS FOR LIMESTONE CAP DIMENSIONS.
3. FORM DIMENSIONS UNDER LIMESTONE CAP ARE TYP. ON ALL SIDES.
4. SEE ARCHITECTURAL DRAWINGS FOR LIMESTONE CAP ATTACHMENT REBAR SPACING.
5. INSTALL REBAR INTO LIMESTONE CAP, THEN POST-INSTALL REBAR INTO CONCRETE.
LIMESTONE CAP
TOP OF SLAB
100' - 0"
S-102
REFER TO FOOTING SCHEDULE
C L R
C
L R
TYP.
2" CLR.,
1/2" ISOLATION JOINT
TIES, SEE COLUMN SCHEDULE
S C
H E
D U
L E
R E
F E
R T
O F
O O
T
IN
G
E M
B
H O
O K
11" HOOK
P L A
N
S E
E F
O U
N D
A T
IO
N
REFER TO COLUMN SCHEDULE
FOR REINFORCEMENT CALLOUTS
TYP.
2" CLR.,
COLUMN SCHEDULE
REFER TO
C O
L U
M N
S C
H E
D U
L E
R E
F E
R T
O
TIES SHALL ABIDE BY ACI
318-14 CHAPTER 25.7.2
REFER TO ARCH FOR AIR
GAP AND STONE FACADE
TOP OF SLAB
100' - 0"
B
IE
R H
E
IG
H T
E M
B
H O
O K
6" HOOK
#6@12" MAX
SPACING, BOTH
SIDES, BOTH WAYS
LIMESTONE CAP
REFER TO FOOTING SCHEDULE
S C
H E
D U
L E
R E
F E
R T
O F
O O
T
IN
G
1/2" ISOLATION
JOINT
TYP.
2" CLR.,
C L R
C
L R
NOTES:
1. SEE ARCHITECTURAL DRAWINGS FOR CAP ANCHORAGE LOCATIONS.
2. SEE ARCHITECTURAL DRAWINGS FOR LIMESTONE CAP DIMENSIONS.
3. FORM DIMENSIONS UNDER LIMESTONE CAP ARE TYP. ON ALL SIDES.
4. SEE ARCHITECTURAL DRAWINGS FOR LIMESTONE CAP ATTACHMENT REBAR SPACING.
5. INSTALL REBAR INTO LIMESTONE CAP, THEN POST-INSTALL REBAR INTO CONCRETE.
T.O.F. 2 95' - 6"
TRUSS BEARING
109' - 0"
6X12 PERIMETER WOOD BEAM
4X10 WOOD
BEARING PLATE
WOOD TRUSS, BY OTHERS
1" THICK PLYWOOD SHEATHING,
SEE FASTENER SCHEDULE FOR
CONNECTION TO WOOD TRUSS
COLUMN, SEE SCHEDULE
FOR SIZE AND DETAIL FOR
REINFORCEMENT
SIMPSON STRONG TIE EPB66
HDG ELEVATED POST BASE
(3
T
IE
S
W
IT
H
IN
/2
NOTES:
1. TRUSS MANUFACTURER SHALL PROVIDE A CALCULATION SHOWING THAT THE 1/4" FILLET WELD IS ACCEPTABLE.
2. TRUSS MANUFACTURER SHALL DESIGN TRUSS TO BEARING PLATE CONNECTION.
CC04 HDG COLUMN CAP,
CCOB CONFIGURATION
1/4"
1/4"
TYP
TO CL OF COLUMN CAP
3 1/2" CL OF PERIMETER BEAM
CONNECTION DESIGN BY
TRUSS MANUFACTURER
1/4"
1/4"
TYP
CC06 HDG COLUMN CAP,
CCOB CONFIGURATION
RLL = 25 PLF
SL = 20 PLF
W L
+3
P
LF
/-3
PLF
WL = +10 PSF/-10 PSF
W L = +30 P
LF/-25 PLF
WL = +10 PSF/-5 PSF
NOTES:
1. POSITIVE LOADS ARE TOWARDS THE TRUSS.
2. ALL LOADS ARE UNFACTORED.
3. AREA LOADS ARE TO BE APPLIED TO END TRUSSES ONLY.
4. LOADS ARE CALCULATED FOR 2' SPACING.
D L
P
LF
D L = 30 P
LF
RLL = 25 PLF
SL = 20 PLF
W L
+3
P
LF
/-1
PLF
W
L = +30 P
LF/-10 PLFD
L
P
LF
D L = 30 P
LF
MAX LOADS MIN LOADS
A
' - 4
/8
1' - 5 1/4"
/8
1' - 1 3/8"
MIN
2" CLR.,
TIES SHALL ABIDE
BY ACI 318-14
CHAPTER 25.7.2
REFER TO ARCH
FOR AIR GAP AND
STONE FACADE
REFER TO COLUMN
SCHEDULE FOR
REINFORCEMENT
CALLOUTS
4.
.0
7°
IN RELATION TO GRIDLINE14.93° COLUMN SKEW
D
' - 1
/8
' - 4
/8
1' - 0"
REFER TO COLUMN
SCHEDULE FOR
REINFORCEMENT
CALLOUTS
TIES SHALL ABIDE BY ACI
318-14 CHAPTER 25.7.2
REFER TO ARCH FOR AIR
GAP AND STONE FACADE
MIN
2" CLR.,
1' - 0 3/8"75 .0
7°
104.93°
IN RELATION TO GRIDLINE14.93° COLUMN SKEW
T Y
P
/2
3/4" TYP.
P R
O J
E M
B
POST INSTALL
#6 REBAR
NON-SHRINK
STRUCTURAL GROUT
T Y
P
/2
3/4" TYP
P R
O J
E M
B
POST-INSTALL
#6 REBAR
NON-SHRINK
STRUCTURAL
GROUT
Location: Baltimore National Cemetery
5501 Frederick Ave., Catonsville, Baltimore County, MD 21228
Issue Date
S T
A M
P
Project Number
Building Number
Drawing Number
Project Title
Checked Drawn
Drawing Title
Approved:
U.S. Department of Veterans Affairs
Phase
ARCHITECT OF RECORDCONSULTANTS
Project Director
Revisions: Date:
Office of Construction and Facilities Management
VA FORM 08 - 6231
F ile
P a th
/1
/2
:3
:0
P
M
100% CONSTRUCTION DOCUMENTS
March 25, 2019
NOT SUPPRESSED
C
ARCHITURA CORPORATION
9880 Westpoint Drive, Suite #400
Indianapolis, IN 46256-3384
PH: (317) 348-1000
POC: Michael Conly, AIA, NCARB, President
802-MM18-05
Committal Shelter
03.25.2019 o n e e ig h th in c h o n e fo o t
F o n e q u a rt e r in c h o n e fo o t
Design Services for Committal Service Shelter ImprovementsCivil/ Structural/ Electrical Engineer:
KCI Technologies, Inc.
1352 Marrows Road, Suite 100
Newark, Delaware 19711
PH: 302.731.9176
POC: Tom deLorimier th re e e ig h th s in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e in c h o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t th re e in c h e s o n e fo o t
D
E
F
E
D
C
B
B
A
A
2 3 4 5 6 7 8 9 10
1 2 3 4 5 6 7 8 9 10
8 9
C
D
E
F
B
A
BALTIMORE NATIONAL CEMETERY
Landscape Architect:
Pashek+MTR, Ltd.
619 E. Ohio St.
Pittsburgh, PA 15212
PH:412-321-6362
POC: Kara Roggenkamp
PROFESSIONAL CERTIFICATION:
I HEREBY CERTIFY THAT THESE DOCUMENTS
WERE PREPARED OR APPROVED BY ME, AND THAT
I AM A DULY LICENSED PROFESSIONAL ENGINEER
UNDER THE LAWS OF THE STATE OF MARYLAND.
LICENSE NO: 40953 EXP. DATE: 07-21-2019
S-102
NAMARL
STRUCTURAL DETAILS
3/4" = 1'-0"
WALL SECTION
3/4" = 1'-0"
COLUMN FOUNDATION SECTION
3/4" = 1'-0"
COLUMN SECTION
3/4" = 1'-0"
BIER SECTION
1 1/2" = 1'-0"
TRUSS TO WOOD BEAM CONNECTION
DETAIL
NTS
TRUSS LOADING DIAGRAMS
1 1/2" = 1'-0"
COLUMN #3 DETAIL
1 1/2" = 1'-0"
COLUMN #2 DETAIL
TRUSS BEARING
109' - 0"
A
TRUSSTRUSS
SIMPSON STRONG TIE
EPB66 HDG ELEVATED
POST BASE
1/4"
1/4"
TYP
(2) CC06 HDG COLUMN CAP,
CCOB CONFIGURATION
6X12 PERIMETER WOOD BEAM
6X12 PERIMETER WOOD BEAM
NOTES:
1. TRUSS-TO-BEARING PLATE AND BEARING PLATE-TO-PERIMETER BEAM
CONNECTIONS NOT SHOWN FOR CLARITY.
Location: Baltimore National Cemetery
5501 Frederick Ave., Catonsville, Baltimore County, MD 21228
Issue Date
S T
A M
P
Project Number
Building Number
Drawing Number
Project Title
Checked Drawn
Drawing Title
Approved:
U.S. Department of Veterans Affairs
Phase
ARCHITECT OF RECORDCONSULTANTS
Project Director
Revisions: Date:
Office of Construction and Facilities Management
VA FORM 08 - 6231
F ile
P a th
/1
/2
:3
:0
P
M
100% CONSTRUCTION DOCUMENTS
March 25, 2019
NOT SUPPRESSED
C
ARCHITURA CORPORATION
9880 Westpoint Drive, Suite #400
Indianapolis, IN 46256-3384
PH: (317) 348-1000
POC: Michael Conly, AIA, NCARB, President
802-MM18-05
Committal Shelter
03.25.2019 o n e e ig h th in c h o n e fo o t
F o n e q u a rt e r in c h o n e fo o t
Design Services for Committal Service Shelter ImprovementsCivil/ Structural/ Electrical Engineer:
KCI Technologies, Inc.
1352 Marrows Road, Suite 100
Newark, Delaware 19711
PH: 302.731.9176
POC: Tom deLorimier th re e e ig h th s in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e in c h o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t th re e in c h e s o n e fo o t
D
E
F
E
D
C
B
B
A
A
2 3 4 5 6 7 8 9 10
1 2 3 4 5 6 7 8 9 10
8 9
C
D
E
F
B
A
BALTIMORE NATIONAL CEMETERY
Landscape Architect:
Pashek+MTR, Ltd.
619 E. Ohio St.
Pittsburgh, PA 15212
PH:412-321-6362
POC: Kara Roggenkamp
PROFESSIONAL CERTIFICATION:
I HEREBY CERTIFY THAT THESE DOCUMENTS
WERE PREPARED OR APPROVED BY ME, AND THAT
I AM A DULY LICENSED PROFESSIONAL ENGINEER
UNDER THE LAWS OF THE STATE OF MARYLAND.
LICENSE NO: 40953 EXP. DATE: 07-21-2019
S-103
NAMARL
STRUCTURAL DETAILS
1 1/2" = 1'-0"
PERIMETER BEAM TO PERIMETER
BEAM CONNECTION AT COLUMN LINE A
| Sheets |
| S-001 - GENERAL STRUCTURAL NOTES, SYMBOLS, AND ISOMETRIC |
| S-100 - FOUNDATION PLAN AND ROOF COLUMN LAYOUT PLAN VIEWS |
| S-101 - ROOF FRAMING PLAN VIEW AND SECTION VIEWS |
| S-102 - STRUCTURAL DETAILS |
| S-103 - STRUCTURAL DETAILS |