36C78619B0007-A0003000.docx
DOCX document 801 KB Posted
- Solicitation number
- 36C78619B0007
About this file
36C78619B0007 A0003 36C78619B0007 A0003.docx
View the file
Other files
| File | Type | Posted |
|---|---|---|
| 36C78619C0085-000.docx | DOCX document | |
| 36C78619B0007-A0006000.docx | DOCX document | |
| 36C78619B0007-A0006001.pdf | ||
| 36C78619B0007-A0006002.pdf | ||
| 36C78619B0007-A0005000.docx | DOCX document | |
| 36C78619B0007-A0004003.pdf | ||
| 36C78619B0007-A0004002.pdf | ||
| 36C78619B0007-A0004001.pdf | ||
| 36C78619B0007-A0004000.docx | DOCX document | |
| 36C78619B0007-A0003001.pdf | ||
| 36C78619B0007-A0002000.docx | DOCX document | |
| 36C78619B0007-A0001000.docx | DOCX document | |
| 36C78619B0007-009.pdf | ||
| 36C78619B0007-007.docx | DOCX document | |
| 36C78619B0007-010.pdf | ||
| 36C78619B0007-011.pdf | ||
| 36C78619B0007-008.pdf | ||
| 36C78619B0007-000.docx | DOCX document |
Show all 18
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
5. PROJECT NUMBER (if applicable)
CODE
7. ADMINISTERED BY
2. AMENDMENT/MODIFICATION NUMBER
CODE
6. ISSUED BY
8. NAME AND ADDRESS OF CONTRACTOR
4. REQUISITION/PURCHASE REQ. NUMBER
3. EFFECTIVE DATE
9A. AMENDMENT OF SOLICITATION NUMBER
9B. DATED
PAGE OF PAGES
10A. MODIFICATION
OF CONTRACT/ORDER NUMBER
10B. DATED
BPA NO.
1. CONTRACT ID CODE
FACILITY CODE
CODE
Offers must acknowledge receipt of this amendment prior to the hour and date specified in the solicitation or as amended, by one of the following methods:
The above numbered solicitation is amended as set forth in Item 14. The hour and date specified for receipt of Offers
E. IMPORTANT:
is extended,
(a) By completing Items 8 and 15, and returning __________ copies of the amendment; (b) By acknowledging receipt of this amendment on each copy of the offer submitted; or (c) By separate letter or electronic communication which includes a reference to the solicitation and amendment numbers. FAILURE OF YOUR
ACKNOWLEDGMENT TO BE RECEIVED AT
THE PLACE DESIGNATED FOR THE RECEIPT OF OFFERS PRIOR TO THE HOUR AND DATE SPECIFIED MAY is not extended.
12. ACCOUNTING AND APPROPRIATION DATA
(REV. 11/2016)
is required to sign this document and return ___________ copies to the issuing office is not, A. THIS CHANGE ORDER IS ISSUED PURSUANT TO:
Specify authority) THE CHANGES SET FORTH IN ITEM 14 ARE MADE IN THE CONTRACT ORDER NO. IN ITEM 10A.
15C. DATE SIGNED
B. THE ABOVE NUMBERED CONTRACT/ORDER IS MODIFIED TO REFLECT THE ADM
INISTRATIVE CHANGES
SET FORTH IN ITEM 14, PURSUANT TO THE AUTHORITY OF FAR 43.103(b).
RESULT IN REJECTION OF YOUR OFFER. If by virtue of this amendment you desire to change an offer already submitted, such change may be made by letter or electronic communication, provided each letter or electronic communication makes reference to the solicitation and this amendment, and is received prior to the opening hour and d ate specified.
C. THIS SUPPLEMENTAL AGREEMENT IS ENTERED INTO PURSUANT TO AUTHORITY OF:
D. OTHER
Contractor
16C. DATE SIGNED
14. DESCRIPTION OF AMENDMENT/MODIFICATION
16B. UNITED STATES OF AMERICA
Except as provided herein, all terms and conditions of the document referenced in Item 9A or 10A, as heretofore changed, remains unchanged and in full force and effect.
15A. NAME AND TITLE OF SIGNER
16A. NAME AND TITLE OF CONTRACTING OFFICER
15B. CONTRACTOR/OFFEROR
STANDARD FORM 3
PREVIOUS EDITION NOT USABLE
Prescribed by GSA - FAR (48 CFR) 53.243 (Type or print) (Type or print) (Organized by UCF section headings, including solicitation/contract subject matter where feasible.)
(Number, street, county, State and ZIP Code) (If other than Item 6) (Specify type of modification and authority) (such as changes in paying office, appropriation date, etc.)
(If required)
(SEE ITEM 11)
(SEE ITEM 13)
(X)
CHECK
ONE
13. THIS ITEM APPLIES ONLY TO
MODIFICATIONS OF CONTRACTS/ORDERS,
IT MODIFIES THE CONTRACT/ORDER NO. AS DESCRIBED IN ITEM 14.
11. THIS ITEM ONLY APPLIES TO AMENDMENTS OF SOLICITATIONS
AMENDMENT OF SOLICITATION/MODIFICATION OF CONTRACT
(Signature of person authorized to sign) (Signature of Contracting Officer) A0003 04-13-2019
860IC3027
36C786 Department of Veterans Affairs National Cemetery Administration Contracting Services 75 Barrett Heights Road, Suite 309 Stafford VA 22556 43C1 Department of Veterans Affairs NCA Contracting Service 75 Barrett Heights Rd. Suite 309 Stafford VA 22556 To all Offerors/Bidders
36C78619B0007 04-13-2019 A0001 X X X
X Memphis National Cemetery | 36C78619B0007 | Renovate Site and Buildings to Correct FCA Deficiencies
1.) The attached questions from prospective bidders and government responses are attached.
1A.) QUESTION: "The “XBA” type fi xtures description manufacturer and model as shown on attached sheet ES 7.01 (highlighted text)".
2.) Please see the Government's Answer, in Attachment Format o n Continuation Page.
**ALL TERM AND CONDITIONS OF THE SPECIFICATIONS REMAIN THE SAME**
Sheryl Palacio-Davis Contracting Officer
CONTINUATION PAGE
See attached document: ES 7.01.
image1.emf
ES 7.01.pdf
Pl ot
D at e:
o n e e ig h th in c h o n e fo o t 1 th re e in c h e s o n e fo t e a n d o n e h a lf in c h e s o n e fo e in c h o n e fo re e q u a rt e rs in c h o n e fo e h a lf in c h o n e fo re e e ig h th s in c h o n e fo n e q u a rt e r in c h o n e fo
VA FORM 08-6231
F
E
D
C
B
A
1 2 3 4 5 6 87 9
97 8654321 10
Project Title
Location
Date Checked Drawn
Project Number
Drawing Reference Number
Drawing Number
Office of Construction and Facilities Management
Drawing Title
Approved: Director, Design and Construction Services
REVISIONS DATE
CONSULTANTS: LAND. ARCH/CIVIL ENG.:
SECURITY ARCHITECTURE/STRUC-MECH-ELEC-PLMG ENG
901 K STREET NW SUITE 400
WASHINGTON, DC 20001
202.842.2100 www.smithgroupjjr.com
201 DEPOT STREET
ANN ARBOR, MI 48104
734.662.4457 www.smithgroupjjr.com 2013/05/31 2013/05/31
MEMPHIS, TENNESSEE
MEMPHIS NATIONAL CEMETERY -
PIC/ADMIN AND MAINT BLDGS, SHELTER
AND SITE IMPROVEMENTS
860CM3017A
5/
/2
1:
:2
PM
ES 7.01
LIGHTING FIXTURE SCHEDULE
SL
KEYED NOTES
SHEET NOTES
LIGHTING FIXTURE SCHEDULE
TYPE DESCRIPTION MANUFACTURER MODEL LOAD LAMP BALLAST VOLTAGE MOUNTING COMMENTS
AA RECESSED COMPACT FLUORESCENT DOWNLIGHT WITH 4"
APERTURE, SEMI-SPECULAR, DIMMING BALLAST
GOTHAM AFV-32TRT-4AR-1
20-ADEZ
32 VA 32W CFL 5% DIMMING 120 V RECESSED DIM THRU PHOTOSENSOR CONTROL
SYSTEM AND TIE TO PHOTOSENSOR
INSTALLED IN LINEAR FLUORESCENT
PENDANT
AB RECESSED WET LOCATION COMPACT FLUORESCENT
DOWNLIGHT WITH LENS AND 4" APERTURE, SPECULAR
CLEAR CONE, ELECTRONIC BALLAST
KURT VERSEN WP920 32 VA 32W CFL ELECTRONIC 120 V RECESSED
FA SURFACE-MOUNTED LINEAR FLUORESCENT ASYMMETRIC
COVE UPLIGHT, DIMMING BALLAST
ELLIPTIPAR F306-A132-S-00-T-
32 VA (1) 32W T8 5% DIMMING 120 V COVE DIM THRU PHOTOSENSOR CONTROL
SYSTEM
FB LINEAR FLUORESCENT 8' PENDANT WITH UPLIGHT AND
DOWNLIGHT WITH STAGGERED LAMPING AND CONTINUOUS
FROSTED ACRYLIC LENS, ALUMINUM FINISH, 2 CIRCUITS,
DIMMING BALLAST, *INTEGRAL OCCUPANCY SENSOR AND
PHOTOSENSOR
AXIS BEAM 4
BB-F-8-T8-1S-1-AP
-120-D-2-CA*-DOS
150 VA (6) 25W T8 5% DIMMING 120 V PENDANT SUSPEND AT 9' TO BOTTOM OF FIXTURE; DIM
THRU PHOTOSENSOR CONTROL SYSTEM;
*PROVIDE "DOS" SENSOR OPTION; DOS
SENSOR TO BE LOCATED AT FIXTURE
INDICATED ON PLANS; *COORDINATE
MOUNTING WITH CEILING USED
FC LINEAR FLUORESCENT 4' PENDANT WITH ASYMMETRIC
DOWNLIGHT, ALUMINUM FINISH, DIMMING BALLAST
BBD-A-A-4-T8-1-0-
AP-120-D-1*
32 VA (1) 32W T8 5% DIMMING 120 V PENDANT SUSPEND AT 9' TO BOTTOM OF FIXTURE;
*COORDINATE MOUNTING WITH CEILING
USED
FD SURFACE MOUNTED LINEAR FLUORESCENT ASYMMETRIC
WALL WASHER, ALUMINUM FINISH, DIMMING BALLAST
BBS-A-4-T8-1-AP-1
20-D-1-*
32 VA (1) 32W T8 5% DIMMING 120 V SURFACE WALL WASHING OVER CREDENZA,
TYPE USED
FE UNDERCABINET LED TASK LIGHT 28" LENGTH, SATIN
ALUMINUM FINISH, INTEGRAL BALLAST, 120V
ALKCO LINCS100-L28-120-
SA-*
9 VA LED INTEGRAL
DRIVER
120 V UNDERCABINET MANUAL ALL ON/OFF WITH VACANCY
SENSOR, *HARDWIRE FIXTURES SO THAT
ALL WIRING AND CONDUIT IS CONCEALED
FF RECESSED LINEAR FLUORESCENT 2'X2' LENSED TROFFER,
ELECTRONIC BALLAST
COOPER SURE LITE R3-WL-3T8-1C-120
-22-*
51 VA (3) 17W T8 ELECTRONIC 120 V RECESSED PROVIDE INTEGRAL BATTERY PACK FOR
FIXTURES DESIGNATED AS EGRESS LIGHTS,
FG LINEAR FLUORESCENT CHAIN-HUNG INDUSTRIAL STRIP WITH
WIRE CAGE, GLOSS WHITE FINISH
PRUDENTIAL P222-2T8-04'-WG-
YGW-S-SC-120
64 VA (2) 32W T8 ELECTRONIC 120 V PENDANT
FH RECESSED LINEAR FLUORESCENT 2'X2' VOLUMETRIC HIGH
EFFICIENCY TROFFER, VL CENTER OPTIC, WHITE FINISH
AXIS WAVE
WA22-VL-T8-1W-1
20-E-1-*
17 VA (1) 17W T8 ELECTRONIC 120 V RECESSED *COORDINATE MOUNTING WITH CEILING
FI LINEAR FLUORESCENT PENDANT WITH UPLIGHTING AND
STAGGERED DOWNLIGHTING WITH FROSTED ACRLYIC LENS,
AND HALOGEN DOWNLIGHTS EVERY 3FT, DIMMING BALLAST
AND MAGNETIC XFMR, ALUMINUM FINISH, 2 CIRCUITS,
*INTEGRAL OCCUPANCY SENSOR AND PHOTOSENSOR
BB-F-6-T8-2S-1-M
R16#3-AP-120-D-2-
CA*-DOS
321 VA (3) 32W T8 + (3)
25W T8 + (3) 50W
MR16
5% DIMMING +
MAGN XFMR
120 V PENDANT SUSPEND AT 9' TO BOTTOM OF FIXTURE; DIM
FJ RECESSED LINEAR FLUORESCENT 2'X2' LENSED TROFFER,
COOPER SURE LITE R3-WL-2T8-1C-120
-22-*
34 VA (2) 17W T8 ELECTRONIC 120 V RECESSED PROVIDE INTEGRAL BATTERY PACK FOR
FIXTURES DESIGNATED AS EGRESS LIGHTS,
FK LINEAR FLUORESCENT 8' PENDANT WITH DOWNLIGHT WITH
STAGGERED LAMPING AND CONTINUOUS FROSTED ACRYLIC
LENS, ALUMINUM FINISH, DIMMING BALLAST
BBD-F-8-T8-1-0-AP
-120-D-1-CA*
75 VA (3) 25W T8 5% DIMMING 120 V PENDANT SUSPEND AT 9' TO BOTTOM OF FIXTURE; DIM
FL LINEAR FLUORESCENT 8' PENDANT WITH UPLIGHT AND
STAGGERED DOWNLIGHTING WITH STAGGERED LAMPING
AND CONTINUOUS FROSTED ACRYLIC LENS, ALUMINUM
FINISH, 2 CIRCUITS, DIMMING BALLAST, *INTEGRAL
OCCUPANCY SENSOR AND PHOTOSENSOR
BB-F-8-T8-2S-1-AP
-120-D-2-CA*-DOS
225 VA (9) 25W T8 5% DIMMING 120 V PENDANT SUSPEND AT 9' TO BOTTOM OF FIXTURE; DIM
FM LINEAR FLUORESCENT 4' PENDANT WITH DOWNLIGHT WITH
CONTINUOUS FROSTED LENS, ALUMINUM FINISH, DIMMING
BALLAST, *INTEGRAL OCCUPANCY SENSOR AND
PHOTOSENSOR, PROVIDE (1) LIT 90 DEGREE CORNER
BBD-F-4-T8-1-0-AP
-120-D-1-CA*-DOS
32 VA (1) 32W T8 5% DIMMING 120 V PENDANT SUSPEND AT 9' TO BOTTOM OF FIXTURE;
*DIM THRU PHOTOSENSOR CONTROL
SYSTEM; *PROVIDE "DOS" SENSOR OPTION;
DOS SENSOR TO BE LOCATED AT FIXTURE
WA LINEAR FLUORSCENT WALL SCONCE WITH SATIN ACRYLIC
LENS, ADA COMPLIANT DEPTH, ALUMINUM FINISH, DIMMING
BALLAST
AXIS PRIME
PWW-S-4-T8-1-AP-
120-D-1-DS
32 VA (1) 32W T8 5% DIMMING 120 V WALL MOUNT VERTICALLY ON WALL, 5' TO
CENTER; DIM THRU PHOTOSENSOR
CONTROL SYSTEM
WB2 LINEAR FLUORESCENT WET LOCATIOM WALL SCONCE WITH
IMPACT RESISTANT MATTE PEARLESCENT ACRYLIC LENS
AND TAMPER-PROOF HARDWARE, COOL SATIN ALUMINUM
FINISH, ELECTRONIC BALLAST
KENALL MILLENIUM
FREESCALE
FS524R-0-MPA-CS
-17-1-120
17 VA (1) 17W T8 ELECTRONIC 120 V WALL
WB4 LINEAR FLUORESCENT WET LOCATIOM WALL SCONCE WITH
IMPACT RESISTANT MATTE PEARLESCENT ACRYLIC LENS
AND TAMPER-PROOF HARDWARE, COOL SATIN ALUMINUM
FINISH, ELECTRONIC BALLAST
KENALL MILLENIUM
FREESCALE
FS548R-0-MPA-CS
-32-1-120
32 VA 32W T8 ELECTRONIC 120 V WALL
WC WALL-MOUNTED LINEAR FLUORESCENT UPLIGHT,
NEORAY AL-COVE
74IW-1-T5HO-4-12
0-EB-SI
54 VA (1) 54W T5HO ELECTRONIC 120 V WALL SWITCH THRU RELAY PANEL CONTROL
SYSTEM
WD LINEAR FLUORESCENT STAGGERED STRIP WITH
TELECOPING ENDS, GLOSS WHITE FINISH, ELECTRONIC
PRUDENTIAL PT8W-SS-TEL-STD
-1T8-04'-YGW-SC-
64 VA 32W T8 ELECTRONIC 120 V COVE WALL MOUNT IN CEILING COVE; PROVIDE
COMBINATION OF STAGGERED STRIPS TO
FILL LENGTH OF COVE; SEE ARCH
MOUNTING DETAILS
X1 CEILING-MOUNTED GREEN LED EDGE-LIT EXIT SIGN WITH
FLUSH CEILING FLANGE AND RECESSED HOUSING,
BRUSHED ALUMINUM FINISH, MIRRORED FACE
SURE LITES ES SERIES 4 VA LED INTEGRAL
DRIVER
120 V CEILING PROVIDE INTEGRAL BATTERY PACK FOR
EXIT SIGNS LOCATED IN MAINTENANCE
BUILDING; PROVIDE NUMBER OF FACES AND
ARROWS AS SHOWN IN PLANS
XBA GRADE-MOUNTED ADJUSTABLE METAL HALIDE LANDSCAPE
LIGHT, WET LOCATION RATED, BRONZE FINISH, IN-GRADE
REMOTE BALLAST ENCLOSURE
BK LIGHTING EV-58-BZP-9-B
(FIXTURE) +
HP2RM-H35M-120
(REMOTE
BALLAST)
35 VA (1) 35W PAR20
MH 20DEG SPOT
REMOTE
MAGNETIC
120 V GRADE FLAG UPLIGHTING
XFA SURFACE-MOUNTED LINEAR FLUORESCENT WET LOCATION
DOWNLIGHT WITH FROSTED LENS, ALUMINUM FINISH,
AXIS WET BEAM
WBS-F-4-T8-2-AP-
120-E-1-SC
64 VA (2) 32W T8 ELECTRONIC 120 V SURFACE EXTERIOR LIGHTING OVER WORK AREAS
XPA POLE-MOUNTED COMPACT FLUORESCENT AREA LIGHT WITH
TYPE 4 DISTRIBUTION, FULL CUTOFF, GRAPHIC METALLIC
INVUE AES-42-CF-120-4S
-GM
42 VA (1) 42W CFL ELECTRONIC 120 V POLE
XWA WALL-MOUNTED COMPACT FLUORESCENT WET LOCATION
WALL SCONCE WITH SOLID FACE, DOWNLIGHT
DISTRIBUTION, GRAPHIC METALLIC FINISH, ELECTRONIC
INVUE ENC-42-CF-120-EB
-CFM-GM
42 VA (1) 42W CFL ELECTRONIC 120 V WALL INSTALL FIXTURE IN DOWNLIGHT
ORIENTATION
Bid Documents 6/2/17 slappano
Rectangle
Text Box
NIC
vacoKazemih
Polygon
Highlight
2016-0812 95 Review_Memphis NC
Sheets and Views
X1.01 COVER SHEET
X1.02 INDEX SHEET
B1.01 SURVEY - OVERALL
B1.02 SURVEY - ENTRANCE & MEMPHIS DRIVE SOUTHWEST
B1.03 SURVEY - ADMIN & MAINTENANCE
B1.04 SURVEY - MEMPHIS DRIVE WEST
B1.05 SURVEY - MEMPHIS DRIVE NORTH
B1.06 SURVEY - MEMPHIS DRIVE EAST
B1.07 SURVEY - MEMPHIS DRIVE SOUTH
B1.08 SURVEY - MORGAN DRIVE WEST
B1.09 SURVEY - SHILOH CIRCLE
B1.10 SURVEY - MORGAN DRIVE EAST
B1.11 SURVEY - COMMITTAL SHELTER SITE
B1.12 SURVEY - STORM SEWERS
D1.01 DEMOLITION - OVERALL
D1.02 DEMOLITION - ADMIN + MAINTENANCE AREA
D1.03 DEMOLITION - FRONT ENTRY
D1.04 DEMOLITION - DETAILS
C1.01 LAYOUT - OVERALL
C1.02 LAYOUT - ADMIN + MAINTENANCE AREA
C1.03 LAYOUT - FRONT ENTRY
C1.04 LAYOUT - ENTRY + MEMPHIS DRIVE
C1.05 LAYOUT - MEMPHIS DRIVE
C1.06 LAYOUT - MORGAN DRIVE
C1.07 LAYOUT - SHILOH CIRCLE
C1.10 TYPICAL PAVEMENT SECTIONS
C1.11 PAVEMENT DETAILS
C1.12 SITE DETAILS
C1.13 SITE FURNISHINGS
C1.14 ASSEMBLY AREA DETAILS
C2.01 GRADING + UTILITIES - OVERALL
C2.02 GRADING + UTILITIES - ADMIN + MAINTENANCE AREA
C2.03 GRADING + UTILITIES - FRONT ENTRY
C2.04 GRADING + UTILITIES - ENTRY + MEMPHIS DRIVE
C2.05 GRADING + UTILITIES - MEMPHIS DRIVE
C2.06 GRADING + UTILITIES - MORGAN DRIVE
C2.07 GRADING + UTILITIES - SHILOH CIRCLE
C2.10 UTILITY DETAILS
C2.11 ROAD PROFILES
C2.12 ROAD PROFILES
C2.13 ROAD PROFILES
C2.14 ROAD PROFILES
C2.15 STORM SEWER PROFILES
C2.16 STORM SEWER PROFILES
C2.17 STORM SEWER PROFILES
L3.01 LANDSCAPE - OVERALL
L3.02 LANDSCAPE - ADMIN + MAINTENANCE AREA
L3.03 LANDSCAPE - FRONT ENTRY
L3.10 LANDSCAPE DETAILS
2016-0812 Rescope - ARCH 1
042_AD 1-01 - PARTIAL DEMOLITION PLANS
044_AS 0-01 - BUILDING CODE SUMMARY
045_ AS 0-02 - ARCHITECTURAL ABBREVIATIONS AND SYMBOLS
046_AS 0-03 - TYPICAL TOILET ROOM MOUNTING HEIGHTS AND STALL CONFIGURATION DIAGRAMS
047_AS 0-04 - TYPICAL MOUNTING HEIGHTS AND DIMENSIONING CONVENTIONS
048_AS 0-05 - TYPICAL RULES FOR MOUNTING HEIGHTS AND LOCATIONS
049_AS 0-06 - TYPICAL REFLECTED CEILING PLAN LOCATIONS AND CONFIGURATIONS
050_AS 0-07 - ISONOMETRIC VIEWS
051_AS 1-00 - PIC AND MAINTENANCE BUILDING - LAYOUT PLANS
053_AS 1-11 - STORAGE FLOOR AND ROOF PLAN
054_AS 1-21 - MAINTENANCE BUILDING FLOOR AND ROOF PLAN
055_AS 2-01 - PUBLIC INFORMATION CENTER - EXTERIOR ELEVATIONS
056_AS 2-11 - STORAGE AND MAINTENANCE BUILDING EXTERIOR ELEVATIONS
057_ AS 3-01 - PIC-ADMIN, MAINTENANCE, AND STORAGE REFLECTED CEILING PLANS
058_AS 4-01 - BUILDING SECTIONS
062_AS 4-34 - MAINTENANCE AND STORAGE BUILDING - WALL SECTIONS
064_AS 4-52 - INTERIOR ELEVATIONS
066_AS 4-54 - LOCKER ROOMS - ENLARGED PLAN AND ELEVATIONS
070_AS 5-04 - ENLARGED SECTION DETAILS
071_AS 5-11 - PLAN DETAILS
073_AS 5-13 - PLAN DETAILS
075_ AS 5-22 - CASEWORK DETAILS
076_AS 9-01 - FINISH AND MATERIAL SCHEDULE
077_AS 9-02 - PARTITION TYPES AND DETAILS
078_AS 9-03 - PARTITION DETAILS
079_AS 9-11 - PAVING PLAN
080_AS 9-31 - DOOR TYPES AND SCHEDULE
081_AS 9-32 - WINDOW TYPES
082_AS 9-41 - INTERIOR SIGNAGE
STRUCTURAL COMBINED
ES 0-01-ELECTRICAL ABBREVIATIONS AND SYMBOLS
ES 0-02 - ELECTRICAL SCHEDULES
ES 1-01 - ELECTRICAL SITE PLAN
ES 2-01 - POWER PLAN
ES 3-01 - ELECTRICAL LIGHTING PLAN
ES 4-01 - FIRE ALARM PLAN
ES 5-01 - ELECTRICAL RISER DIAGRAM
ES 5-02 - TELECOM DETAILS
ES 6-01 - ELECTRICAL DETAILS
ES 7-01 - LIGHTING FIXTURE SCHEDULE
ES 8-01 - ELECTRICAL PANELBOARD SCHEDULES
MH0-01 - MECHANICAL ABBREVIATIONS AND SYMBOLS
MHD2-01 - MAINTENANCE OFFICE DEMOLITION PLAN
MH 2-02 MAINTENANCE OFFICE AND SHED HVAC PLAN
MH 3-01 - MECHANICAL PIPING PLAN
MH 6-01 - DETAILS
MH 7-01 - MECHANICAL SCHEDULES
MH 8-01 - MECHANICAL CONTROLS LEGEND
MH 8-02 - MECHANICAL CONTROLS
PL 0-01 - PLUMBING ABBREVIATIONS AND GENERAL NOTES
PLD2-01 - PLUMBING DEMOLITION PLAN - MAINTENANCE BLDG
PL 2-02 - PLUMBING FLOOR AND ROOF PLAN - STORAGE BLDG
PL 2-03 - PLUMBING FLOOR AND ROOF PLAN - MAINTENANCE BLDG
PL 5-01 - PLUMBING RISER DIAGRAMS
PL 7-01 - PLUMBING SCHEDULES
SC 0.01
SC 0.01.dwg
SC0.1
SC 1.01
SC 1.01.dwg
SC 1.02
SC 1.02.dwg
SC 1.03
SC 1.03.dwg
SC 1.04
SC 1.04.dwg
SC 5.01
SC 5.01.dwg
SC 5.02
SC 5.02.dwg
SC 6.01
SC 6.01.dwg
2016-0825 Rescope - MECH.pdf
MH 2-02 MAINTENANCE OFFICE AND SHED HVAC PLAN
MH 3-01 - MECHANICAL PIPING PLAN
MH 6-01 - DETAILS
MH 7-01 - MECHANICAL SCHEDULES
MH 8-01 - MECHANICAL CONTROLS LEGEND
MH 8-02 - MECHANICAL CONTROLS
MH0-01 - MECHANICAL ABBREVIATIONS AND SYMBOLS
MHD2-01 - MAINTENANCE OFFICE DEMOLITION PLAN
2016-0825 Rescope - PLUMB.pdf
PL 0-01 - PLUMBING ABBREVIATIONS AND GENERAL NOTES
PLD2-01 - PLUMBING DEMOLITION PLAN - MAINTENANCE BLDG
PL 2-02 - PLUMBING FLOOR AND ROOF PLAN - STORAGE BLDG
PL 2-03 - PLUMBING FLOOR AND ROOF PLAN - MAINTENANCE BLDG
PL 5-01 - PLUMBING RISER DIAGRAMS
PL 7-01 - PLUMBING SCHEDULES
File details come from the government source that posted it.