ATT 09 - 251216---619-21-106---VA-Montgomery---FINAL-STRUCTURAL.pdf
PDF 3 MB Posted
- Attached to
- Y1DA--Construction | 619-21-106 | EHRM Infrastructure Upgrades - Montgomery (VA-27-00002289)
- Solicitation number
- 36C77626R0112
About this file
This document is a complete set of 100% Construction Documents (Structural Drawings) for the EHRM Infrastructure Upgrades project at the Central Alabama Veterans Health Care System (CAVHS) West Campus in Montgomery, Alabama (Project #619-21-106).
The project involves improvements, reconfigurations, expansions, and renovations of existing spaces across eleven buildings (01, 04, 05, 06, 07, 08, 12, 13, 14, 40, and 99) to create new telecommunication rooms and construct a new data center. The structural drawings provide comprehensive design documentation prepared by SPEES Design Build (Architect/Engineer of Record) with WSP providing structural and civil engineering services. Key structural elements include cast-in-place concrete foundations with spread footings and slab-on-grade construction, 12-inch fully-grouted concrete masonry unit (CMU) walls with reinforcing steel, structural steel roof framing with W-beam members and 3-inch 18-gauge steel roof deck, and non-bearing cold-formed steel stud framing for interior partitions. The design incorporates seismic force-resisting systems utilizing bearing wall systems with special reinforced masonry shear walls (Response Modification Factor R=5). Design parameters include 124 mph wind speeds, 5 PSF ground snow load, and blast load requirements per VA Physical Security & Resiliency Design Manual. Special inspection and testing requirements per IBC Section 1704 are mandated for foundation, masonry, and structural steel work. The 407-page drawing set includes foundation plans, roof plans, wall elevations, typical concrete and masonry details, structural steel connection details, mechanical anchorage details for equipment, and standard penetration details for existing structure coordination.
View the file
Other files
Show all 17
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
ARCHITECTURAL
SPEES DESIGN BUILD
23830 PACIFIC HIGHWAY S. SUITE 300
KENT, WA 98032
PHONE: (206) 590-2118
DESIGN TEAM
CIVIL
ELECTRICAL/OIT
SPEES DESIGN BUILD
MECHANICAL
SPEES DESIGN BUILD
23830 PACIFIC HIGHWAY S. SUITE 300
KENT, WA 98032
PHONE: (206) 590-2118
23830 PACIFIC HIGHWAY S. SUITE 300
KENT, WA 98032
PHONE: (206) 590-2118
RCDD
WSP
211 N BROADWAY, #2800
ST. LOUIS, MO, 63102
PHONE: (615) 571-8922
STRUCTURAL
WSP
211 N BROADWAY, #2800
ST. LOUIS, MO, 63102
PHONE: (615) 571-8922
WSP
211 N BROADWAY, #2800
ST. LOUIS, MO, 63102
PHONE: (615) 571-8922
PROJECT INFORMATION
STATE:
COUNTY:
JURISDICTION:
OWNER:
CODE ANALYSIS
PROJECT DESCRIPTION
THE PROPOSED DESIGN SHALL IMPROVE,
RECONFIGURE, EXPAND, AND RENOVATE
EXISTING SPACES FOR NEW
TELECOMMUNICATION ROOMS, AND THE
CONSTRUCTION OF NEW DATA CENTER.
APPLICABLE BUILDINGS:
01, 04, 05, 06, 07, 08, 12, 13, 14, 40, 99 (DATA CENTER)
ICRA CLASS REQUIREMENTS
REQUIREMENTS DEPENDANT ON
EACH INDIVIDUAL ROOM LOCATION.
ALABAMA
MONTGOMERY
MONTGOMERY
GOV, VETERANS AFFAIRS
BUILDING TYPE
BUILDING 01 - MEDICAL
BUILDING 04 - MEDICAL
BUILDING 05 - NON-MEDICAL
BUILDING 06 - NON-MEDICAL
BUILDING 07 - NON-MEDICAL
BUILDING 08 - NON-MEDICAL
BUILDING 12 - NON-MEDICAL
BUILDING 13 - NON-MEDICAL
BUILDING 14 - NON-MEDICAL
BUILDING 40 - MEDICAL
BUILDING 99 - NON-MEDICAL
SIGNATURE LINE
COR
BUILDINGS WITHIN THE SCOPE OF THIS PROJECT
CENTRAL ALABAMA VETERANS HEALTH CARE SYSTEM (CAVHS) WEST CAMPUS - MONTGOMERY, AL
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of
Construction and Facilities
Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT/DISCIPLINE
321 4 5 6 7 8 9 10
ENGINEERING DISCIPLINE:
SPEES DESIGN BUILD
23830 PACIFIC HIGHWAY S. SUITE 300
KENT, WA 98032
/1 /2
:5
:2 a m
B
IM
/6
-2
-1 a
V A
M o n tg o m e ry
E H
R M
/V A
M Y
G
E N
S H
E E
T S
S
D B
.r v t
G-001
COVER SHEET
JG/JS JS
100% CONSTRUCTION
DOCUMENTS
10/24/2025
619-21-106EHRM INFRASTRUCTURE
UPGRADES - MONTGOMERY
VA AL - CENTRAL ALABAMA (WEST CAMPUS)
215 PERRY HILL ROAD, MONTGOMERY, AL 36109
EHRM INFRASTRUCTURE UPGRADES - MONTGOMERY
CENTRAL ALABAMA VETERANS HEALTH CARE SYSTEM (CAVHS) WEST CAMPUS
215 PERRY HILL ROAD MONTGOMERY, AL 36109-3798
PROJECT #: 619-21-106
NOT TO SCALE
LOCATION MAP
TRUE
NORTH
1" = 160'-0"
VICINITY PLAN
PROJECT
NORTH
CENTRAL ALABAMA VETERANS HEALTH CARE SYSTEM (CAVHS)
- MONTGOMERY, AL
Revisions: Date:
JG/JS
DRAWING INDEX
PAGE # SHEET # SHEET NAME
GENERAL
1 OF 407 G-001 COVER SHEET
2 OF 407 G-002 DRAWING INDEX
CIVIL
3 OF 407 C-001 CIVIL SHEET INDEX AND GENERAL NOTES
4 OF 407 C-002 GENERAL NOTES AND LEGEND
5 OF 407 CD200 MCR BUILDING DEMOLITION PLAN
6 OF 407 CS100 OVERALL CIVIL SITE PLAN
7 OF 407 CS200 MCR BUILDING SITE PLAN
8 OF 407 CS201 MCR BUILDING HORIZONTAL CONTROL PLAN
9 OF 407 CG100 OVERALL EROSION CONTROL PLAN
10 OF 407 CG101 EROSION CONTROL GENERAL NOTES AND DETAILS
11 OF 407 CG200 MCR BUILDING EROSION CONTROL PLAN
12 OF 407 CG201 MCR BUILDING GRADING AND DRAINAGE PLAN
13 OF 407 CG202 MCR BUILDING STORMWATER BMP PLAN
14 OF 407 CU200 MCR BUILDING UTILITY PLAN
15 OF 407 CU250 CIVIL UTILITY CONSTRUCTION DETAILS
16 OF 407 CU300 OVERALL FIBER OPTIC OUTSIDE PLANT UTILITY PLAN
17 OF 407 CU301 FIBER OPTIC OUTSIDE PLANT UTILITY PLAN
18 OF 407 CU302 FIBER OPTIC OUTSIDE PLANT UTILITY PLAN
19 OF 407 CU303 FIBER OPTIC OUTSIDE PLANT UTILITY PLAN
20 OF 407 CU304 FIBER OPTIC OUTSIDE PLANT UTILITY PLAN
21 OF 407 CU500 COMMUNICATION DUCTBANK DETAILS
22 OF 407 CU501 COMMUNICATION TRENCHING DETAILS
23 OF 407 CU502 BUILDING CONNECTION DETAILS
STRUCTURAL
24 OF 407 S-001 STRUCTURAL GENERAL NOTES
25 OF 407 S-002 STRUCTURAL GENERAL NOTES
26 OF 407 S-003 ABRREVIATIONS AND SYMBOLS
27 OF 407 S-101 FOUNDATION PLAN
28 OF 407 S-111 ROOF PLAN
29 OF 407 S-201 STRUCTURAL WALL ELEVATIONS
30 OF 407 S-202 STRUCTURAL WALL ELEVATIONS
31 OF 407 S-501 TYPICAL CONCRETE DETAILS
32 OF 407 S-502 CONCRETE FOUNDATION DETAILS
33 OF 407 S-511 TYPICAL STRUCTURAL STEEL DETAILS
34 OF 407 S-512 TYPICAL STRUCTURAL STEEL DETAILS
35 OF 407 S-531 TYPICAL CMU WALL DETAILS
36 OF 407 S-532 TYPICAL CMU WALL DETAILS
37 OF 407 S-541 MECHANICAL ANCHORAGE DETAILS
38 OF 407 S-542 TYPICAL DETAILS-CABINET TO CFS FRAMED WALL
39 OF 407 S-543 TYPICAL DETAILS-CABINET TO WOOD FRAMED WALL
40 OF 407 S-544 TYPICAL DETAILS-CABINET TO CONCRETE AND CMU WALL
41 OF 407 S-545 TYPICAL PENETRATIONS IN EXISTING STRUCTURE
ENVIRONMENTAL
42 OF 407 001HA100 BLDG 01 - LVL 00G - ABATEMENT DRAWINGS
43 OF 407 001HA101 BLDG 01 - LVL 01 - ABATEMENT DRAWINGS
44 OF 407 001HA102 BLDG 01 - LVL 02 - ABATEMENT DRAWINGS
45 OF 407 001HA103 BLDG 01 - LVL 03 - ABATEMENT DRAWINGS
46 OF 407 001HA104 BLDG 01 - LVL 04 - ABATEMENT DRAWINGS
47 OF 407 001HA105 BLDG 01 - LVL 05 - ABATEMENT DRAWINGS
48 OF 407 004HA100 BLDG 04 - LVL 00 - ABATEMENT DRAWINGS
49 OF 407 004HA101 BLDG 04 - LVL 01 - ABATEMENT DRAWINGS
50 OF 407 005HA100 BLDG 05 - LVL 01 - ABATEMENT DRAWINGS
51 OF 407 006HA100 BLDG 06 - LVL 01 - ABATEMENT DRAWINGS
52 OF 407 007HA100 BLDG 07 - LVL 01 - ABATEMENT DRAWINGS
53 OF 407 008HA100 BLDG 08 - LVL 01 - ABATEMENT DRAWINGS
54 OF 407 012HA100 BLDG 12 - LVL 01 - ABATEMENT DRAWINGS
55 OF 407 013HA100 BLDG 13 - LVL 1 - ABATEMENT DRAWINGS
56 OF 407 014HA100 BLDG 14 - LVL 00 - ABATEMENT DRAWINGS
57 OF 407 040HA100 BLDG 40 - LVL 00 - ABATEMENT DRAWINGS
ARCHITECTURAL
58 OF 407 A-001 ARCHITECTURAL SYMBOLS & ABBREVIATIONS
59 OF 407 AS101 ICRA DETAILS
60 OF 407 AS102 ICRA STANDARDS
61 OF 407 01AS100B BLDG 01 -LVL 00B -PHASING PLAN
62 OF 407 01A-100G BLDG 01 -LVL 00G -ARCHITECTURAL PLAN
63 OF 407 01AS100G BLDG 01 -LVL 00G -PHASING PLAN
64 OF 407 01A-400Ga BLDG 01 -LVL 00G -DEMO, FLOOR PLANS & RCPS
65 OF 407 01A-400Gb BLDG 01 -LVL 00G -DEMO, FLOOR PLANS & RCPS
66 OF 407 01A-101 BLDG 01 -LVL 01 -ARCHITECTURAL PLAN
67 OF 407 01AS101 BLDG 01 -LVL 01 -PHASING PLAN
68 OF 407 01A-401a BLDG 01 -LVL 01 -DEMO, FLOOR PLANS & RCPS
69 OF 407 01A-401b BLDG 01 -LVL 01 -DEMO, FLOOR PLANS & RCPS
70 OF 407 01A-102 BLDG 01 -LVL 02 -ARCHITECTURAL PLAN
71 OF 407 01AS102 BLDG 01 -LVL 02 -PHASING PLAN
72 OF 407 01A-402a BLDG 01 -LVL 02 -DEMO, FLOOR PLANS & RCPS
73 OF 407 01A-402b BLDG 01 -LVL 02 -DEMO, FLOOR PLANS & RCPS
74 OF 407 01A-103 BLDG 01 -LVL 03 -ARCHITECTURAL PLAN
75 OF 407 01AS103 BLDG 01 -LVL 03 -PHASING PLAN
76 OF 407 01A-403a BLDG 01 -LVL 03 -DEMO, FLOOR PLANS & RCPS
77 OF 407 01A-403b BLDG 01 -LVL 03 -DEMO, FLOOR PLANS & RCPS
78 OF 407 01A-104 BLDG 01 -LVL 04 -ARCHITECTURAL PLAN
79 OF 407 01AS104 BLDG 01 -LVL 04 -PHASING PLAN
80 OF 407 01A-404a BLDG 01 -LVL 04 -DEMO, FLOOR PLANS & RCPS
81 OF 407 01A-404b BLDG 01 -LVL 04 -DEMO, FLOOR PLANS & RCPS
82 OF 407 01A-105 BLDG 01 -LVL 05 -ARCHITECTURAL PLAN
83 OF 407 01AS105 BLDG 01 -LVL 05 -PHASING PLAN
84 OF 407 01A-405 BLDG 01 -LVL 05 -DEMO, FLOOR PLANS & RCPS
85 OF 407 01AS106 BLDG 01 -LVL 06 -PHASING PLAN
86 OF 407 04A-100 BLDG 04 -LVL 00 -ARCHITECTURAL PLAN
87 OF 407 04AS100 BLDG 04 -LVL 00 -PHASING PLAN
88 OF 407 04A-400a BLDG 04 -LVL 00 -DEMO, FLOOR PLAN & RCP
89 OF 407 04A-400b BLDG 04 -LVL 00 -DEMO, FLOOR PLAN & RCP
90 OF 407 04A-101 BLDG 04 -LVL 01 -ARCHITECTURAL PLAN
91 OF 407 04AS101 BLDG 04 -LVL 01 -PHASING PLAN
92 OF 407 04A-401 BLDG 04 -LVL 01 -DEMO, FLOOR PLANS & RCPS
93 OF 407 05A-101 BLDG 05 -LVL 01 -ARCHITECTURAL PLAN
94 OF 407 05AS101 BLDG 05 -LVL 01 -PHASING PLAN
95 OF 407 05A-401 BLDG 05 -LVL 01 -DEMO, FLOOR PLANS & RCPS
96 OF 407 06AS100 BLDG 06 -LVL 00 -PHASING PLAN
97 OF 407 06A-101 BLDG 06 -LVL 01 -ARCHITECTURAL PLAN
98 OF 407 06AS101 BLDG 06 -LVL 01 -PHASING PLAN
99 OF 407 06A-401 BLDG 06 -LVL 01 -DEMO, FLOOR PLANS AND RCPS
100 OF 407 06AS102 BLDG 06 -LVL 02 -PHASING PLAN
101 OF 407 07AS100 BLDG 07 -LVL 00 -PHASING PLAN
102 OF 407 07A-101 BLDG 07 -LVL 01-ARCHITECTURAL PLAN
103 OF 407 07AS101 BLDG 07 -LVL 01 -PHASING PLAN
104 OF 407 07A-401 BLDG 07 -LVL 01 -DEMO, FLOOR PLANS & RCPS
105 OF 407 07AS102 BLDG 07 -LVL 02 -PHASING PLAN
106 OF 407 08AS100 BLDG 08 -LVL 00 -PHASING PLAN
107 OF 407 08A-101 BLDG 08 -LVL 01 -ARCHITECTURAL PLAN
108 OF 407 08AS101 BLDG 08 -LVL 01 -PHASING PLAN
109 OF 407 08A-401 BLDG 08 -LVL 01 -DEMO, FLOOR PLANS & RCPS
110 OF 407 08AS102 BLDG 08 -LVL 02 -PHASING PLAN
111 OF 407 12A-101 BLDG 12 -LVL 01 -ARCHITECTURAL PLAN
112 OF 407 12AS101 BLDG 12 -LVL 01 -PHASING PLAN
113 OF 407 12A-401 BLDG 12 -LVL 01 -DEMO, FLOOR PLANS & RCPS
114 OF 407 13A-101 BLDG 13 -LVL 1 -ARCHITECTURAL PLAN
115 OF 407 13AS101 BLDG 13 -LVL 01 -PHASING PLAN
116 OF 407 13A-401 BLDG 13 -LVL 01 -DEMO, FLOOR PLANS & RCPS
117 OF 407 14AS100 BLDG 14 -LVL 00 -PHASING PLAN
118 OF 407 14A-101 BLDG 14 -LVL 01 -ARCHITECTURAL PLAN
119 OF 407 14AS101 BLDG 14 -LVL 01 -PHASING PLAN
120 OF 407 14A-401 BLDG 14 -LVL 01 -DEMO, FLOOR PLANS & RCPS
121 OF 407 40A-100 BLDG 40 -LVL 00 -ARCHITECTURAL PLAN
122 OF 407 40AS100 BLDG 40 -LVL 00 -PHASING PLAN
123 OF 407 40A-400 BLDG 40 -LVL 00 -DEMO, FLOOR PLANS & RCPS
124 OF 407 A-101 BLDG 99 -FLOOR PLAN
125 OF 407 A-102 BLDG 99 -FIRE LIFE SAFETY PLAN
126 OF 407 A-103 BLDG 99 -ROOF PLAN
127 OF 407 A-104 BLDG 99 -RCP
128 OF 407 A-605 BLDG 99 -EXTERIOR DETAILS
129 OF 407 A-606 BLDG 99 -INTERIOR DETAILS AND ELEVATIONS AND EQUIPMENT SCHEDULE
130 OF 407 AE201 BLDG 99 -ELEVATIONS
131 OF 407 AE202 BLDG 99 -ELEVATIONS
132 OF 407 AE301 BLDG 99 -BUILDING SECTIONS
133 OF 407 AE401 BLDG 99 -WALL SECTIONS
134 OF 407 A-601 ROOM FINISH SCHEDULE
135 OF 407 A-602 DOOR DETAILS
136 OF 407 A-603 DETAILS
137 OF 407 A-604 DETAILS
138 OF 407 AE421 ELEVATIONS, TYPICAL DETAILS & TR WALL PLAN VIEW
139 OF 407 AW001 SIGNAGE MESSAGE SCHEDULE
140 OF 407 AW002 SIGNAGE LOCATION PLAN & DETAILS
FIRE PROTECTION
141 OF 407 FX001 FIRE PROTECTION GENERAL NOTES, ABBREVIATION & LEGENDS
142 OF 407 099-FX101 BUILDING -099 -LEVEL -01 -FIRE PROTECTION PLAN
143 OF 407 FX501 FIRE PROTECTION DETAILS & SCHEDULE
PLUMBING
144 OF 407 P-001 PLUMBING GENERAL NOTES
145 OF 407 P-002 PLUMBING GENERAL NOTES, ABBREVIATIONS & LEGENDS
146 OF 407 099-P-101 BUILDING -099 -FOUNDATION -PLUMBING PLAN
147 OF 407 099-P-102 BUILDING -099 -LEVEL -01 -PLUMBING PLAN
148 OF 407 099-P-103 BUILDING -099 -ROOF -PLUMBING PLAN
149 OF 407 P-501 PLUMBING DETAILS
MECHANICAL
150 OF 407 M-001 MECHANICAL GENERAL NOTES
151 OF 407 M-002 MECHANICAL ABBREVIATION & LEGENDS
152 OF 407 001-M-101 BUILDING -001 -LEVEL -00 -MECHANICAL OVERALL PLAN
153 OF 407 001-M-102 BUILDING -001 -LEVEL -01 -MECHANICAL OVERALL PLAN
154 OF 407 001-M-103 BUILDING -001 -LEVEL -02 -MECHANICAL OVERALL PLAN
155 OF 407 001-M-104 BUILDING -001 -LEVEL -03 -MECHANICAL OVERALL PLAN
156 OF 407 001-M-105 BUILDING -001 -LEVEL -04 -MECHANICAL OVERALL PLAN
157 OF 407 001-M-106 BUILDING -001 -LEVEL -05 -MECHANICAL OVERALL PLAN
158 OF 407 001-M-107 BUILDING -001 -LEVEL -06 -MECHANICAL OVERALL PLAN
159 OF 407 001-M-108 BUILDING -001 -LEVEL -07 -MECHANICAL OVERALL PLAN
160 OF 407 001-M-401 BUILDING -001 -LEVEL -00 -DEMOLITION, FLOOR PLANS & RCPS
161 OF 407 001-M-402 BUILDING -001 -LEVEL -00 -DEMOLITION, FLOOR PLANS & RCPS
162 OF 407 001-M-403 BUILDING -001 -LEVEL -00 -PARTIAL FLOOR PLAN
163 OF 407 001-M-404 BUILDING -001 -LEVEL -01 -DEMOLITION, FLOOR PLANS & RCPS
164 OF 407 001-M-405 BUILDING -001 -LEVEL -01 -DEMOLITION, FLOOR PLANS & RCPS
165 OF 407 001-M-406 BUILDING -001 -LEVEL -02 -DEMOLITION, FLOOR PLANS & RCPS
166 OF 407 001-M-407 BUILDING -001 -LEVEL -02 -DEMOLITION, FLOOR PLANS & RCPS
167 OF 407 001-M-408 BUILDING -001 -LEVEL -03 -DEMOLITION, FLOOR PLANS & RCPS
168 OF 407 001-M-409 BUILDING -001 -LEVEL -03 -DEMOLITION, FLOOR PLANS & RCPS
169 OF 407 001-M-410 BUILDING -001 -LEVEL -04 -DEMOLITION, FLOOR PLANS & RCPS
170 OF 407 001-M-411 BUILDING -001 -LEVEL -04 -DEMOLITION, FLOOR PLANS & RCPS
171 OF 407 001-M-412 BUILDING -001 -LEVEL -05 -DEMOLITION, FLOOR PLANS & RCPS
172 OF 407 001-M-413 BUILDING -001 -LEVEL -06 -FLOOR PLAN
173 OF 407 001-M-414 BUILDING -001 -LEVEL -07 -ROOF PLAN
174 OF 407 004-M-101 BUILDING -004 -LEVEL -00 -OVERALL PLAN
175 OF 407 004-M-102 BUILDING -004 -LEVEL -01 -OVERALL PLAN
176 OF 407 004-M-401 BUILDING -004 -LEVEL -00 -DEMOLITION & FLOOR PLANS
177 OF 407 004-M-402 BUILDING -004 -LEVEL -00 -DEMOLITION & RCPS
178 OF 407 004-M-403 BUILDING -004 -LEVEL -00 -FLOOR PLAN
179 OF 407 004-M-404 BUILDING -004 -LEVEL -01 -DEMOLITION, FLOOR PLANS & RCPS
180 OF 407 005-M-101 BUILDING -005 -LEVEL -01 -OVERALL PLAN
181 OF 407 005-M-401 BUILDING -005 -LEVEL -01 -DEMOLITION & FLOOR PLANS
182 OF 407 006-M-101 BUILDING -006 -LEVEL -01 -OVERALL PLAN
183 OF 407 006-M-401 BUILDING -006 -LEVEL -01 -DEMOLITION, FLOOR PLANS & RCPS
184 OF 407 007-M-101 BUILDING -007 -LEVEL -01 -OVERALL PLAN
185 OF 407 007-M-401 BUILDING -007 -LEVEL -01 -DEMOLITION, FLOOR PLANS & RCPS
186 OF 407 008-M-101 BUILDING -008 -LEVEL -01 -OVERALL PLAN
187 OF 407 008-M-401 BUILDING -008 -LEVEL -01 -DEMOLITION & FLOOR PLANS
188 OF 407 012-M-101 BUILDING -012 -LEVEL -01 -OVERALL PLAN
189 OF 407 012-M-401 BUILDING -012 -LEVEL -01 -DEMOLITION, FLOOR PLANS & RCPS
190 OF 407 013-M-101 BUILDING -013 -LEVEL -01 -OVERALL PLAN
191 OF 407 013-M-401 BUILDING -013 -LEVEL -01 -DEMOLITION, FLOOR PLANS & RCPS
192 OF 407 040-M-101 BUILDING -040 -LEVEL -00 -OVERALL PLAN
193 OF 407 040-M-401 BUILDING -040 -LEVEL -00 -DEMOLITION, FLOOR PLANS & RCPS
194 OF 407 099-MH101 BUILDING -099 -LEVEL -01 -HVAC DUCT PLAN
195 OF 407 099-MH102 BUILDING -099 -LEVEL -01 -HVAC RCP
196 OF 407 099-MH103 BUILDING -099 -ROOF -HVAC PLAN
197 OF 407 099-MP101 BUILDING -099 -LEVEL -01 -HVAC PIPING PLAN
198 OF 407 099-M-301 DATA CENTER -SECTION VIEW
199 OF 407 099-M-302 DATA CENTER -SECTION VIEW
200 OF 407 099-M-303 GENERATOR BUILDING -SECTION VIEW
201 OF 407 M-501 MECHANICAL DETAILS I
202 OF 407 M-502 MECHANICAL DETAILS II
203 OF 407 M-601 MECHANICAL SCHEDULES I
204 OF 407 M-602 MECHANICAL SCHEDULES II
205 OF 407 M-603 MECHANICAL SCHEDULES II
206 OF 407 M-701 MECHANICAL CONTROLS I
207 OF 407 M-702 MECHANICAL CONTROLS II
208 OF 407 M-703 MECHANICAL CONTROLS III
209 OF 407 M-704 MECHANICAL CONTROLS IV
210 OF 407 M-705 MECHANICAL CONTROLS V
211 OF 407 M-706 MECHANICAL CONTROLS VI
212 OF 407 M-800 DATA CENTER - PRESSURE MAP PLAN
ELECTRICAL
213 OF 407 EG001 ABBREVIATIONS, GENERAL NOTES
214 OF 407 EG002 ELECTRICAL LEGENDS
215 OF 407 ES001 ELECTRICAL FACILITY SITE PLAN
216 OF 407 ES002 ENLARGED SITE -ELECTRICAL PLAN -EXISTING
217 OF 407 ES003 ENLARGED SITE -ELECTRICAL PLAN -REVISED
218 OF 407 01EP100 BLDG 01 -LEVEL 00 -ELECTRICAL PLAN
219 OF 407 01EP101 BLDG 01 -LEVEL 01 -ELECTRICAL PLAN
220 OF 407 01EP102 BLDG 01 -LEVEL 02 -ELECTRICAL PLAN
221 OF 407 01EP103 BLDG 01 -LEVEL 03 -ELECTRICAL PLAN
222 OF 407 01EP104 BLDG 01 -LEVEL 04 -ELECTRICAL PLAN
223 OF 407 01EP106 BLDG 01 -LEVEL 06 -ELECTRICAL PLAN
224 OF 407 01EP107 BLDG 01 -LEVEL 07-ELECTRICAL PLAN
225 OF 407 04EP100 BLDG 04 -LEVEL 00 -ELECTRICAL PLAN
226 OF 407 05EP101 BLDG 05 -LEVEL 01 -ELECTRICAL PLAN
227 OF 407 06EP100 BLDG 06 -LEVEL 00 -ELECTRICAL PLAN
228 OF 407 07EP100 BLDG 07 -LEVEL -00 -ELECTRICAL PLAN
229 OF 407 07EP101 BLDG 07 -LEVEL -01 -ELECTRICAL PLAN
230 OF 407 08EP100 BLDG 08 -LEVEL -00 -ELECTRICAL PLAN
231 OF 407 12EP100 BLDG 12 -LEVEL 00 -ELECTRICAL PLAN
232 OF 407 13EP100 BLDG 13 -LEVEL 00 -ELECTRICAL PLAN
233 OF 407 14EP100 BLDG 14 -LEVEL 00 -ELECTRICAL PLAN
234 OF 407 40EP100 BLDG 40 -LEVEL 00 -ELECTRICAL PLAN
235 OF 407 99EL101 DATA CENTER -LIGHTING PLAN
236 OF 407 99EP101 DATA CENTER -POWER PLAN
237 OF 407 99EP102 DATA CENTER -POWER PLAN -MECHANICAL EQUIPMENT
238 OF 407 99EP103 DATA CENTER -POWER PLAN -RECEPTACLE
239 OF 407 99EG101 DATA CENTER -GROUNDING PLAN
240 OF 407 99EG102 DATA CENTER -GROUNDING PLAN -LIGHTNING PROTECTION
241 OF 407 99EF101 DATA CENTER -FIRE ALARM SYSTEM PLAN
242 OF 407 99EP201 DATA CENTER -EXTERIOR ELEVATION PLANS
243 OF 407 99EP202 DATA CENTER -EXTERIOR ELEVATION PLANS
244 OF 407 01EP400a BLDG 01 -LEVEL -00 -ENLARGED ELECTRICAL PLANS
245 OF 407 01EP400b BLDG 01 -LEVEL -00 -ENLARGED ELECTRICAL PLANS
246 OF 407 01EP400c BLDG 01 -LEVEL -00 -ENLARGED ELECTRICAL PLANS
247 OF 407 01EP400d BLDG 01 -LEVEL -00 -ENLARGED ELECTRICAL PLANS
248 OF 407 01EP400e BLDG 01 -LEVEL -00 -ENLARGED ELECTRICAL PLANS
249 OF 407 01EP401a BLDG 01 -LEVEL -01 -ENLARGED ELECTRICAL PLANS
250 OF 407 01EP401b BLDG 01 -LEVEL -01 -ENLARGED ELECTRICAL PLANS
251 OF 407 01EP402a BLDG 01 -LEVEL -02 -ENLARGED ELECTRICAL PLANS
252 OF 407 01EP402b BLDG 01 -LEVEL -02 -ENLARGED ELECTRICAL PLANS
253 OF 407 01EP403a BLDG 01 -LEVEL -03 -ENLARGED ELECTRICAL PLANS
254 OF 407 01EP403b BLDG 01 -LEVEL -03 -ENLARGED ELECTRICAL PLANS
255 OF 407 01EP404a BLDG 01 -LEVEL -04 -ENLARGED ELECTRICAL PLANS
256 OF 407 01EP404b BLDG 01 -LEVEL -04 -ENLARGED ELECTRICAL PLANS
257 OF 407 01EP405 BLDG 01 -LEVEL -05 -ENLARGED ELECTRICAL PLANS
258 OF 407 04EP400a BLDG 04 -LEVEL 00 -ENLARGED ELECTRICAL PLANS
259 OF 407 04EP400b BLDG 04 -LEVEL 00 -ENLARGED ELECTRICAL PLANS
260 OF 407 04EP400c BLDG 04 -LEVEL 00 -ENLARGED ELECTRICAL PLANS
261 OF 407 04EP401 BLDG 04 -LEVEL 01 -ENLARGED ELECTRICAL PLANS
262 OF 407 05EP401 BLDG 05 -LEVEL 01 -ENLARGED ELECTRICAL PLANS
263 OF 407 06EP401 BLDG 06 -LEVEL 01 -ENLARGED ELECTRICAL PLANS
264 OF 407 07EP401 BLDG 07 -LEVEL 01 -ENLARGED ELECTRICAL PLANS
265 OF 407 08EP401 BLDG 08 -LEVEL -01 -ENLARGED ELECTRICAL PLANS
266 OF 407 12EP400 BLDG 12 -LEVEL 00 -ENLARGED ELECTRICAL PLANS
267 OF 407 13EP400 BLDG 13 -LEVEL 00 -ENLARGED ELECTRICAL PLANS
268 OF 407 14EP401 BLDG 14 -LVL 01 -ENLARGED ELECTRICAL PLAN
269 OF 407 40EP400 BLDG 40 -LEVEL 00 -ENLARGED ELECTRICAL PLANS
270 OF 407 EP501 ELECTRICAL DETAILS
271 OF 407 EP502 ELECTRICAL DETAILS
272 OF 407 EP503 ELECTRICAL DETAILS
273 OF 407 EP504 ELECTRICAL DETAILS
274 OF 407 EP505 ELECTRICAL DETAILS
275 OF 407 EP506 ELECTRICAL DETAILS
276 OF 407 EP507 ELECTRICAL DETAILS
277 OF 407 EP508 ELECTRICAL DETAILS
278 OF 407 EP509 ELECTRICAL DETAILS
279 OF 407 EP510 ELECTRICAL DETAILS
280 OF 407 EP511 ELECTRICAL DETAILS
281 OF 407 EP512 ELECTRICAL DETAILS
282 OF 407 EF601 FIRE ALARM SYSTEMS RISER DIAGRAM AND MATRICES
283 OF 407 EG601 TELECOMMUNICATIONS BONDING RISER DIAGRAM
284 OF 407 00EP601 MEDIUM VOLTAGE -ONE-LINE DIAGRAM -EXISTING
285 OF 407 00EP611 MEDIUM VOLTAGE -ONE-LINE DIAGRAM -REVISED
286 OF 407 01EP601 BLDG 01 -ONE-LINE DIAGRAM -PART 1 OF 2 -EXISTING
287 OF 407 01EP602 BLDG 01 -ONE-LINE DIAGRAM -PART 2 OF 2 -EXISTING
288 OF 407 01EP611 BLDG 01 -ONE-LINE DIAGRAM -PART 1 OF 2 -REVISED
289 OF 407 01EP612 BLDG 01 -ONE-LINE DIAGRAM -PART 2 OF 2 -REVISED
290 OF 407 04EP601 BLDG 04 -ONE-LINE DIAGRAM -EXISTING
291 OF 407 04EP611 BLDG 04 -ONE-LINE DIAGRAM -REVISED
292 OF 407 05EP601 BLDG 05 -ONE-LINE DIAGRAM
293 OF 407 06EP601 BLDG 06 -ONE-LINE DIAGRAMS
294 OF 407 07EP601 BLDG 07 -ONE-LINE DIAGRAMS
295 OF 407 08EP601 BLDG 08 -ONE-LINE DIAGRAM
296 OF 407 12EP601 BLDG 12 -ONE-LINE DIAGRAMS
297 OF 407 13EP601 BLDG 13 -ONE-LINE DIAGRAM -EXISTING
298 OF 407 13EP611 BLDG 13 -ONE-LINE DIAGRAM -REVISED
299 OF 407 14EP601 BLDG 14 -ONE-LINE DIAGRAMS
300 OF 407 40EP601 BLDG 40 -ONE-LINE DIAGRAMS
301 OF 407 99EP601 DATA CENTER -ONE-LINE DIAGRAM
302 OF 407 EP701 ELECTRICAL SCHEDULES
303 OF 407 01EP701 ELECTRICAL SCHEDULES
304 OF 407 01EP702 ELECTRICAL SCHEDULES
305 OF 407 01EP703 ELECTRICAL SCHEDULES
306 OF 407 01EP704 ELECTRICAL SCHEDULES
307 OF 407 01EP705 ELECTRICAL SCHEDULES
308 OF 407 01EP706 ELECTRICAL SCHEDULES
309 OF 407 04EP701 ELECTRICAL SCHEDULES
310 OF 407 05EP701 ELECTRICAL SCHEDULES
311 OF 407 06EP701 ELECTRICAL SCHEDULES
312 OF 407 07EP701 ELECTRICAL SCHEDULES
313 OF 407 08EP701 ELECTRICAL SCHEDULES
314 OF 407 12EP701 ELECTRICAL SCHEDULES
315 OF 407 13EP701 ELECTRICAL SCHEDULES
316 OF 407 14EP701 ELECTRICAL SCHEDULES
317 OF 407 40EP701 ELECTRICAL SCHEDULES
318 OF 407 99EP701 ELECTRICAL SCHEDULES
319 OF 407 99EP702 ELECTRICAL SCHEDULES
TELECOM
320 OF 407 TNG001 ABBREVIATIONS, AND SHEET INDEX
321 OF 407 TNG002 GENERAL NOTES
322 OF 407 TNG003 TELECOMMUNICATIONS LEGEND
323 OF 407 01TN1000 BLDG 01 -LEVEL 000 -TELECOMMUNICATIONS PLAN
324 OF 407 01TN100 BLDG 01 -LEVEL 00 -TELECOMMUNICATIONS PLAN
325 OF 407 01TN101 BLDG 01 -LEVEL 01 -TELECOMMUNICATIONS PLAN
326 OF 407 01TN102 BLDG 01 -LEVEL 02 -TELECOMMUNICATIONS PLAN
327 OF 407 01TN103 BLDG 01 -LEVEL 03 -TELECOMMUNICATIONS PLAN
328 OF 407 01TN104 BLDG 01 -LEVEL 04 -TELECOMMUNICATIONS PLAN
329 OF 407 01TN105 BLDG 01 -LEVEL 05 -TELECOMMUNICATIONS PLAN
330 OF 407 01TN106 BLDG 01 -LEVEL 06 -TELECOMMUNICATIONS PLAN
331 OF 407 04TN100 BLDG 04 -LEVEL 00 -TELECOMMUNICATIONS PLAN
332 OF 407 04TN101 BLDG 04 -LEVEL 01 -TELECOMMUNICATIONS PLAN
333 OF 407 05TN101 BLDG 05 -LEVEL 01 -TELECOMMUNICATIONS PLAN
334 OF 407 06TN100 BLDG 06 -LEVEL 00 -TELECOMMUNICATIONS PLAN
335 OF 407 06TN101 BLDG 06 -LEVEL 01 -TELECOMMUNICATIONS PLAN
336 OF 407 06TN102 BLDG 06 -LEVEL 02 -TELECOMMUNICATIONS PLAN
337 OF 407 07TN100 BLDG 07 -LEVEL -00 -TELECOMMUNICATIONS PLAN
338 OF 407 07TN101 BLDG 07 -LEVEL -01 -TELECOMMUNICATIONS PLANS
339 OF 407 07TN102 BLDG 07 -LEVEL -02 -TELECOMMUNICATIONS PLAN
340 OF 407 08TN100 BLDG 08 -LEVEL -00 -TELECOMMUNICATIONS PLAN
341 OF 407 08TN101 BLDG 08 -LEVEL -01 -TELECOMMUNICATIONS PLAN
342 OF 407 08TN102 BLDG 08 -LEVEL -02 -TELECOMMUNICATIONS PLAN
343 OF 407 12TN100 BLDG 12 -LEVEL 00 -TELECOMMUNICATIONS PLAN
344 OF 407 13TN100 BLDG 13 -LEVEL 00 -TELECOMMUNICATIONS PLAN
345 OF 407 14TN100 BLDG 14 -LEVEL 00 -TELECOMMUNICATIONS PLAN
346 OF 407 14TN101 BLDG 14 -LEVEL 01 -TELECOMMUNICATIONS PLAN
347 OF 407 40TN100 BLDG 40 -LEVEL 00 -TELECOMMUNICATIONS PLAN
348 OF 407 99TN101 DATA CENTER -TELECOMMUNICATIONS PLAN
349 OF 407 99TN102 DATA CENTER -HORIZONTAL DISTRIBUTION OVERHEAD PLAN
350 OF 407 99TN103 DATA CENTER -FIBER BACKBONE OVERHEAD PLAN
351 OF 407 01TN400a BLDG 01 -LEVEL 00 -ENLARGED TELECOMMUNICATIONS PLANS
352 OF 407 01TN400b BLDG 01 -LEVEL 00 -ENLARGED TELECOMMUNICATIONS PLANS
353 OF 407 01TN400c BLDG 01 -LEVEL 00 -ENLARGED TELECOMMUNICATIONS PLANS
354 OF 407 01TN400d BLDG 01 -LEVEL 00 -ENLARGED TELECOMMUNICATIONS PLANS
355 OF 407 01TN400e BLDG 01 -LEVEL 00 -ENLARGED TELECOMMUNICATIONS PLANS
356 OF 407 01TN401a BLDG 01 -LEVEL 01 -ENLARGED TELECOMMUNICATIONS PLANS
357 OF 407 01TN401b BLDG 01 -LEVEL 01 -ENLARGED TELECOMMUNICATIONS PLANS
358 OF 407 01TN401c BLDG 01 -LEVEL 01 -ENLARGED TELECOMMUNICATIONS PLANS
359 OF 407 01TN401d BLDG 01 -LEVEL 01 -ENLARGED TELECOMMUNICATIONS PLANS
360 OF 407 01TN401e BLDG 01 -LEVEL 01 -ENLARGED TELECOMMUNICATIONS PLANS
361 OF 407 01TN401f BLDG 01 -LEVEL 01 -ENLARGED TELECOMMUNICATIONS PLANS
362 OF 407 01TN402a BLDG 01 -LEVEL 02 -ENLARGED TELECOMMUNICATIONS PLANS
363 OF 407 01TN402b BLDG 01 -LEVEL 02 -ENLARGED TELECOMMUNICATIONS PLANS
364 OF 407 01TN402c BLDG 01 -LEVEL 02 -ENLARGED TELECOMMUNICATIONS PLANS
365 OF 407 01TN402d BLDG 01 -LEVEL 02 -ENLARGED TELECOMMUNICATIONS PLANS
366 OF 407 01TN402e BLDG 01 -LEVEL 02 -ENLARGED TELECOMMUNICATIONS PLANS
367 OF 407 01TN402f BLDG 01 -LEVEL 02 -ENLARGED TELECOMMUNICATIONS PLANS
368 OF 407 01TN403a BLDG 01 -LEVEL 03 -ENLARGED TELECOMMUNICATIONS PLANS
369 OF 407 01TN403b BLDG 01 -LEVEL 03 -ENLARGED TELECOMMUNICATIONS PLANS
370 OF 407 01TN403c BLDG 01 -LEVEL 03 -ENLARGED TELECOMMUNICATIONS PLANS
371 OF 407 01TN403d BLDG 01 -LEVEL 03 -ENLARGED TELECOMMUNICATIONS PLANS
372 OF 407 01TN403e BLDG 01 -LEVEL 03 -ENLARGED TELECOMMUNICATIONS PLANS
373 OF 407 01TN404a BLDG 01 -LEVEL 04 -ENLARGED TELECOMMUNICATIONS PLANS
374 OF 407 01TN404b BLDG 01 -LEVEL 04 -ENLARGED TELECOMMUNICATIONS PLANS
375 OF 407 01TN404c BLDG 01 -LEVEL 04 -ENLARGED TELECOMMUNICATIONS PLANS
376 OF 407 01TN404d BLDG 01 -LEVEL 04 -ENLARGED TELECOMMUNICATIONS PLANS
377 OF 407 01TN404e BLDG 01 -LEVEL 04 -ENLARGED TELECOMMUNICATIONS PLANS
378 OF 407 01TN405a BLDG 01 -LEVEL 05 -ENLARGED TELECOMMUNICATIONS PLANS
379 OF 407 01TN405b BLDG 01 -LEVEL 05 -ENLARGED TELECOMMUNICATIONS PLANS
380 OF 407 04TN400a BLDG 04 -LEVEL 00 -ENLARGED TELECOMMUNICATIONS PLANS
381 OF 407 04TN400b BLDG 04 -LEVEL 00 -ENLARGED TELECOMMUNICATIONS PLANS
382 OF 407 04TN400c BLDG 04 -LEVEL 00 -ENLARGED TELECOMMUNICATIONS PLANS
383 OF 407 04TN401a BLDG 04 -LEVEL 01 -ENLARGED TELECOMMUNICATIONS PLANS
384 OF 407 04TN401b BLDG 04 -LEVEL 01 -ENLARGED TELECOMMUNICATIONS PLANS
385 OF 407 05TN401 BLDG 05 -LEVEL 01 -ENLARGED TELECOMMUNICATIONS PLANS
386 OF 407 06TN401 BLDG 06 -LEVEL 01 -ENLARGED TELECOMMUNICATIONS PLANS
387 OF 407 07TN401a BLDG 07 -LEVEL -01 -ENLARGED TELECOMMUNICATIONS PLANS
388 OF 407 07TN401b BLDG 07 -LEVEL -01 -ENLARGED TELECOMMUNICATIONS PLANS
389 OF 407 08TN401a BLDG 08 -LEVEL -01 -ENLARGED TELECOMMUNICATIONS PLANS
390 OF 407 08TN401b BLDG 08 -LEVEL -01 -ENLARGED TELECOMMUNICATIONS PLANS
391 OF 407 08TN402 BLDG 08 -LEVEL -02 -ENLARGED TELECOMMUNICATIONS PLANS
392 OF 407 12TN400 BLDG 12 -LEVEL 00 -ENLARGED TELECOMMUNICATIONS PLANS
393 OF 407 13TN400a BLDG 13 -LEVEL 0 -ENLARGED TELECOMMUNICATIONS PLANS
394 OF 407 13TN400b BLDG 13 -LEVEL 00 -ENLARGED TELECOMMUNICATIONS PLANS
395 OF 407 14TN401a BLDG 14 -LEVEL 01 -ENLARGED TELECOMMUNICATIONS PLANS
396 OF 407 14TN401b BLDG 14 -LEVEL 01 -ENLARGED TELECOMMUNICATIONS PLANS
397 OF 407 40TN400a BLDG 40 -LEVEL 00 -ENLARGED TELECOMMUNICATIONS PLANS
398 OF 407 40TN400b BLDG 40 -LEVEL 00 -ENLARGED TELECOMMUNICATIONS PLANS
399 OF 407 TN501 TELECOMMUNICATIONS DETAILS
400 OF 407 TN502 TELECOMMUNICATIONS DETAILS
401 OF 407 TN503 TELECOMMUNICATIONS DETAILS
402 OF 407 TN504 TELECOMMUNICATIONS DETAILS
403 OF 407 TN505 TELECOMMUNICATIONS DETAILS
404 OF 407 TN506 TELECOMMUNICATIONS DETAILS
405 OF 407 TN601 SITE FIBER RISER DIAGRAM -CORE A
406 OF 407 TN602 SITE FIBER RISER DIAGRAM -CORE B
407 OF 407 TN701 TELECOMMUNICATIONS SCHEDULE
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of
Construction and Facilities
Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT/DISCIPLINE
321 4 5 6 7 8 9 10
ENGINEERING DISCIPLINE:
SPEES DESIGN BUILD
23830 PACIFIC HIGHWAY S. SUITE 300
KENT, WA 98032
/3 /2
:1
:1
P M
B
IM
/6
-2
-1 a V
A M o n tg o m e ry E
H R
M /V
A M
Y G
E N
S H
E E
T S
S
D B
.r v t
G-002
DRAWING INDEX
JG/JS JS
100% CONSTRUCTION
DOCUMENTS
10/24/2025
619-21-106EHRM INFRASTRUCTURE
UPGRADES - MONTGOMERY
VA AL - CENTRAL ALABAMA (WEST CAMPUS)
215 PERRY HILL ROAD, MONTGOMERY, AL 36109
Revisions: Date:
WSP USA Inc.
1201 Pacific Ave, Suite 550 Tacoma WA, 98402
TEL: (206) 431-2300
FAX: (206) 431-2250
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
ENGINEERING DISCIPLINE:
SPEES DESIGN BUILD
23830 PACIFIC HIGHWAY S. SUITE 203
KENT, WA 98032
/1 /2
:1
:5
P M
B
IM
/6
-2
-1 a V
A M o n tg o m e ry E
H R
M /V
A M
Y
D A
T A
C E
N T
E R
S
T R
.r v t
S-001
STRUCTURAL GENERAL NOTES
BUILDING #99
NRT JKM
100% CONSTRUCTION
DOCUMENTS
10/24/2025
619-21-106EHRM INFRASTRUCTURE
UPGRADES - MONTGOMERY
VA AL - CENTRAL ALABAMA (WEST CAMPUS)
215 PERRY HILL ROAD, MONTGOMERY, AL 36109
SNOW LOAD
SNOW LOAD IMPORTANCE FACTOR, Is
GROUND SNOW LOAD, Pg
SNOW LOAD ON FLAT ROOFS, Pf
EXPOSURE CATEGORY
SNOW LOAD EXPOSURE FACTOR, Ce
THERMAL FACTOR, Ct
1.2
5 PSF
3.8 PSF
FULLY EXPOSED
0.90
1.0
VALUEDESIGN PARAMETER
WIND LOAD
BASIC WIND SPEED (3-SEC GUST), V
WIND EXPOSURE CATEGORY
ENCLOSURE CLASSIFICATION
INTERNAL PRESSURE COEFFICIENT
124 MPH
B
ENCLOSED
±0.18
VALUEDESIGN PARAMETER
SEISMIC IMPORTANCE FACTOR, Ie
SITE LOCATION
SOIL SITE CLASS
MAPPED SPECTRAL ACCELERATION
DESIGN SPECTRAL ACCELERATION
SEISMIC DESIGN CATEGORY
1.5
38.3841745° N -82.5165789° E
C
0.155 0.069
0.134 0.069
C
VALUEDESIGN PARAMETER
SEISMIC LOAD
LATITUDE
LONGITUDE
SHORT PERIOD, Ss
1-SECOND PERIOD, S1
SHORT PERIOD, Sds 1-SECOND PERIOD, Sd1
PRINCIPLE BUILDING AXES (NTS)
LONG AXIS
T R
A N
S A
X
IS
SEISMIC FORCE RESISTING SYSTEM
RESPONSE MODIFICATION FACTOR, R
OVERSTRENGTH FACTOR, Ω0
DEFLECTION AMPLIFICATION FACTOR, Cd
SEISMIC WEIGHT, W
SEISMIC RESPONSE COEFF., Cs
DESIGN BASE SHEAR, V
ANALYSIS PROCEDURE
SEISMIC SYSTEM DESIGN
A1 - BEARING WALL
SYSTEM: SPC REINF
MASONARY SHEAR WALLS
2.0 3.5
656.2 KIPS
0.035
23 KIPS
BOTH
DIRECTION
EQUIVALENT LATERAL
FORCE ANALYSIS
1. GROUND PREPARATION FOR THE SITE MUST BE IN ACCORDANCE WITH THE FINAL GEOTECHNICAL REPORT LISTED.
2. THE CONTRACTOR MUST BE FAMILIAR WITH SUBSURFACE CONDITIONS AND RELEVANT ASPECTS OF THIS REPORT BEFORE COMMENCING EXCAVATION. THE CONTRACTOR MUST RETAIN A GEOTECHNICAL ENGINEER FOR INSPECTIONS, TO VERIFY CONDITIONS, OR TO PERFORM ADDITIONAL EXPLORATION, AS
NECESSARY.
3. LOCATIONS OF SUBSURFACE SITE CONDITIONS, INCLUDING BURIED UTILITIES OR OBSTRUCTIONS AND OTHER FEATURES KNOWN TO THE DESIGN TEAM ARE IDENTIFIED IN DRAWINGS. VERIFY THE EXTENT AND LOCATIONS OF SITE UTILITIES AND OBSTRUCTIONS. REPORT ANY DISCREPANCY ENCOUNTERED AS
SOON AS THEY ARE KNOWN TO THE CONTRACTING OFFICER.
4. FOOTING DESIGN IS BASED ON THE FOLLOWING ALLOWABLE SOIL PROPERTIES:
5. EXTERIOR FOOTINGS MUST BEAR AT OR BELOW MINIMUM BEARING DEPTH. UNLESS NOTED OTHERWISE, MINIMUM BEARING DEPTH IS 24-INCHES BELOW THE
ADJACENT FINISHED GRADE.
6. FOOTINGS MUST BEAR ON ENGINEERED STRUCTURAL FILL OR COMPETENT NON-EXPANSIVE NATIVE SOILS. PLACE STRUCTURAL FILL MATERIAL IN UNIFORM LAYERS COMPACTED TO 95% OF MAXIMUM DRY DENSITY PER ASTM D1557. A QUALIFIED TEST LABORATORY OR AN EXPERIENCED, QUALIFIED GEOTECHNICAL
ENGINEER MUST BE RETAINED TO MONITOR SOIL COMPACTION.
7. SPECIAL INSPECTION MUST BE PERFORMED DURING SITE EXCAVATION TO CONFIRM THAT EXISTING CONDITIONS COMPLY WITH CONDITIONS IN THE
GEOTECHNICAL REPORT.
8. EXCAVATIONS MUST BE DEWATERED TO ALLOW FOR CASTING FOUNDATION CONCRETE IN DRY CONDITIONS.
9. USE FORMWORK TO CAST CONCRETE, SOIL FORMING CONCRETE WORK IS PROHIBITED.
10. USE A 15 MIL MIN VAPOR RETARDER AND A 4 INCH COMPACTED DRAINAGE LAYER BELOW SLABS-ON-GRADE, UNLESS NOTED OTHERWISE OR PER SPECIFIC
REQUIREMENTS OF THE GEOTECHNICAL REPORT.
FOUNDATIONS
REPORT TITLE
PREPARED BY
PROJECT NUMBER
DATED
GEOTECHNICAL REPORT
VAMC MAIN COMPUTER ROOM MONTGOMERY, AL
BUILDING AND EARTH GEOTECHNICAL, INC
MG240011
15 FEBRUARY 2024
SOIL PROPERTY LOAD CASE VALUE
BEARING CAPACITY:
MODULUS OF SUBGRADE REACTION
COEFFICIENT OF FRICTION AT STRENGTH
FROST DEPTH
SUSTAINED
TRANSIENT (INCL. W ,E,OR BLAST)
2,500 PSF
3325 PSF
120 PCI
0.40
24"
1. DEFERRED COMPONENT SUBMITTALS ARE INTENDED TO BE VENDOR DESIGNED AND HAVE NOT BEEN DESIGNED BY THE ARCHITECT/ENGINEER OF RECORD. THE COMPONENT DESIGNER IS RESPONSIBLE FOR CODE CONFORMANCE AND NECESSARY CONNECTIONS NOT CALLED OUT ON
ARCHITECTURAL OR STRUCTURAL DRAWINGS.
2. DEFERRED SUBMITTALS INCLUDING CALCULATIONS MUST BE STAMPED AND SIGNED BY A REGISTERED PROFESSIONAL ENGINEER. DEFERRED SUBMITTALS MUST FIRST BE SUBMITTED TO THE ENGINEER OF RECORD FOR A CURSORY REVIEW FOR LOADS IMPOSED ON THE BASIC STRUCTURE.
3. A SUBMITTAL MAY THEN BE MADE BY THE CONTRACTOR TO THE CONTRACTING OFFICER’S REPRESENTATIVE TO SUBMIT TO THE AUTHORITY HAVING
JURISDICTION FOR REVIEW AND APPROVAL.
4. THE LIST OF ITEMS FOR DEFERRED SUBMITTALS INCLUDES THE FOLLOWING ITEMS:
A. SEISMIC RESTRAINT FOR NON-STRUCTURAL COMPONENTS
5. SUBMITTAL MUST INCLUDE:
A. CALCULATIONS
B. A DIAGRAM SHOWING LOAD MAGNITUDES AND LOCATIONS, SEPARATED INTO DEAD, AND SEISMIC COMPONENTS - THAT ARE APPLIED TO THE
PRIMARY STRUCTURE.
DEFERRED SUBMITTALS
1. REFERENCES:
A. ACI 301-20 SPECIFICATIONS FOR CONCRETE CONSTRUCTION
B. ACI SP-66-04 ACI DETAILING MANUAL
C. ACI 315R-18 DETAILS AND DETAILING CONCRETE CONSTRUCTION
D. AWS D1.4 2018 STRUCTURAL WELDING CODE – REINFORCING STEEL
2. STEEL REINFORCEMENT MUST CONFORM TO:
3. PROVIDE BAR SUPPORTS AND SPACERS PER ACI 315 UNLESS NOTED OTHERWISE. DEFORMED BAR REINFORCEMENT AND INSERTS MUST BE SECURED IN- PLACE PRIOR TO PLACING CONCRETE. DO NOT PLACE REBAR MATS DIRECTLY AGAINST SOIL; REBAR MATS ADJACENT TO SOIL OR OVER MUD SLABS MUST BE
SUPPORTED BY CHAIRS, DO NOT LIFT INTO PLACE DURING POURING.
4. UNLESS INDICATED OTHERWISE, REINFORCEMENT BARS ARE CONTINUOUS AND MUST BE LAP SPLICED OR COUPLED WITH MECHANICAL CONNECTORS. LAP
LENGTH NOTES:
A. SEE DEVELOPMENT AND LAP SPLICE LENGTH SCHEDULES FOR REINFORCEMENT DETAILS.
B. LAP SPLICE LENGTH MUST BE USED FOR THE LARGER BAR SIZE WHEN BAR SIZE TRANSITIONS AT LAP.
C. OVERLAP WELDED WIRE LAYER REINFORCEMENT A LENGTH OF 1.5X WIRE DEVELOPMENT LENGTH OR ONE CROSSWIRE SPACING PLUS 2 INCHES, WHICHEVER IS LARGER.
D. MECHANICAL CONNECTORS MUST HAVE A MINIMUM CAPACITY OF 1.25 X YIELD STRENGTH OF THE BAR.
E. MECHANICAL CONNECTORS IN MEMBERS DESIGNATED AS PART OF THE SEISMIC-FORCE-RESISTING SYSTEM MUST HAVE A MINIMUM CAPACITY
EQUAL TO THE TENSILE STRENGTH OF THE BAR.
5. TYPE 1 MECHANICAL CONNECTORS MUST DEVELOP 125% OF THE YIELD STRENGTH (Fy) OF THE STRONGER OF THE TWO BAR BEING SPLICED. TYPE 2 MECHANICAL CONNECTORS MUST DEVELOP THE FULL TENSILE STRENGTH OF THE STRONGER OF THE TWO BARS BEING SPLICED. WHERE MECHANICAL CONNECTORS ARE USED IN LIEU OF LAP SPLICES, PROVIDE TYPE 2 MECHANICAL CONNECTORS EXCEPT WHERE TYPE 1 ARE PERMITTED AS INDICATED.
6. HEADED DEFORMED BARS (TERMINATORS) MUST BE INTEGRALLY FORMED OR THREADED DEVICES MEETING THE REQUIREMENTS OF ACI 318, SECTION 25.4.4.1.
7. UNLESS NOTED OTHERWISE ON THE DRAWINGS:
A. DEFORMED BAR COVER MUST CONFORM TO SPECIFIED CONCRETE COVER REQUIREMENTS OF ACI 318.
B. REINFORCEMENT MUST BE CONTINUOUS THROUGH CONSTRUCTION JOINTS
C. APPROVAL FROM SER REQUIRED BEFORE WELDING NON-ASTM A706 Gr. 60 REINFORCEMENT
D. APPROVAL FROM SER REQUIRED BEFORE FIELD BENDING REINFORCEMENT PARTIALLY EMBEDDED CONCRETE
E. MATCH DOWELS TO THE LARGER OF MULTIPLE BAR SIZES
8. DOWELS MUST BE SECURED WITH A RIGID TEMPLATE TO ENSURE SPLICE IS LOCATED INSIDE THE CONFINED REGION (REGION ENCLOSED BY SHEAR OR
HORIZONTAL REINFORCEMENT) OF CROSS-SECTION.
REINFORCING STEEL
CONDITION STANDARD AND GRADE MIN YIELD (KSI)
TYPICAL DEFORMED BAR
WELDABLE DEFORMED BAR,
ASTM A615 GR 60
ASTM A706 GR 60
1. REFERENCES:
A. TMS 402-16 BUILDING CODE REQUIREMENTS FOR MASONRY STRUCTURES
B. TMS 602-16 SPECIFICATIONS FOR MASONRY STRUCTURES
2. PROVIDE INSPECTION LEVEL C FOR RC IV FOR QUALITY ASSURANCE AND SPECIAL INSPECTION AND TESTING PER TMS 602
3. CONCRETE MASONRY ASSEMBLY MUST ACHIEVE A COMPRESSIVE STRENGTH AND COMPONENT MATERIAL STRENGTH DETERMINED PER ARTICLE 1.4 B OF
TMS 602. COMPRESSIVE STRENGTH MUST BE VERIFIED BEFORE CONSTRUCTION
4. PROVIDE CONCRETE MASONRY UNIT (CMU) COMPONENT MATERIAL STRENGTHS AS FOLLOWING. CONCRETE MASONRY ASSEMBLY MUST ACHIEVE THE
COMPRESSIVE STRENGTH SHOWN AS DETERMINED PER ARTICLE 1.4B OF TMS 602.
5. COLD AND HOT WEATHER CONSTRUCTION MUST BE IN ACCORDANCE WITH ARTICLE 1.8C AND ARTICLE 1.8D RESPECTIVELY OF TMS 602.
6. LAY UP MASONRY UNITS IN RUNNING BOND, UNLESS NOTED OTHERWISE. MORTAR JOINTS MUST NOT EXCEED A THICKNESS OF 5/8 INCH.
7. PROVIDE BOND BEAM UNITS AT LAYERS WITH HORIZONTAL REINFORCEMENT, EXCEPT WHERE LINTEL SECTIONS ARE REQUIRED.
8. CONTINUOUS REINFORCING STEEL MUST BE LAP SPLICED IN ACCORDANCE WITH THE DEVELOPMENT AND LAP SPLICE LENGTHS FOR MASONRY PER THE
DRAWINGS.
9. MECHANICAL SPLICES, WHERE NOTED ON DRAWINGS, MUST BE TAPERED THREADED OR UPSET THREADED BAR COUPLERS CERTIFIED TO DEVELOP 125% OF THE YIELD STRENGTH (Fy) OF THE BAR. HEADED REINFORCEMENTS BARS (TERMINATORS) MUST BE INTEGRALLY FORMED OR THREADED DEVICES PER ACI 318, SECTION 25.4.4.1, AND CAPABLE OF DEVELOPING THE FULL YIELD STRENGTH OF THE BAR..
10. PROVIDE VERTICAL BARS FULL HEIGHT AT WALL CORNERS, AND EACH SIDE OF DOORS, WINDOWS, AND OTHER OPENINGS. PROVIDE HORIZONTAL REINFORCEMENT ABOVE DOOR OPENINGS, ABOVE AND BELOW WINDOWS AND AT OTHER OPENINGS. EXTEND REINFORCEMENT AT LEAST ONE DEVELOPMENT LENGTH OF THE BAR BEYOND EACH SIDE OF OPENING UNLESS NOTED OTHERWISE. PROVIDE CONTINUOUS HORIZONTAL REINFORCEMENT AT
CORNERS.
11. PROVIDE FINE GROUT OR COARSE GROUT BASED ON MINIMUM GROUT SPACE REQUIREMENTS OF TABLE 7 OF TMS 602.
12. GROUTING HEIGHTS GREATER THAN 5’-4” IS ONLY PERMITTED BY APPROVAL OF THE CONTRACTING OFFICER BEFORE CONSTRUCTION, SUBMIT REQUEST A MINIMUM OF TEN (10) DAYS PRIOR TO PROCEEDING WITH SITE MOBILIZATION. HIGH-LIFT GROUTING MUST BE IN ACCORDANCE WITH ARTICLE 3.5 OF TMS 602
AND SUBMITTAL MUST INCLUDE:
A. EXPECTED LIFT HEIGHTS AND PROCESS. LIFT MUST NOT EXCEED ONE STORY LEVEL, OR 12’-8” MAXIMUM, WHICHEVER IS LESSER.
B. QUALIFICATIONS OF UNIT AND GROUTING CREWS HAVING A MINIMUM OF FIVE (5) YEARS OF EXPERIENCE WITH SIMILAR HIGH-LIFT GROUTING WORK.
LIST THREE PROJECTS WITH CONTACT INFORMATION OF A REFERENCE FOR EACH.
C. OTHER ITEMS DEEMED IMPORTANT BY THE CONTRACTOR.
13. SPACE CONTROL JOINTS AT A MAXIMUM OF 25 FEET O.C., THREE TIMES THE WALL HEIGHT, WHICHEVER IS LESSER WHEN NOT INDICATED ON THE DRAWINGS.
WHEN INDICATED PER DRAWINGS, CONTROL JOINTS LOCATED BY DIMENSIONS SHOWN TAKE PRECEDENCE.
14. REFER TO THE ARCHITECTURAL DRAWINGS FOR THE ROUGH OPENING DIMENSION AND LOCATIONS OF WINDOWS AND DOORS. COORDINATE WITH ARCHITECTURAL DRAWINGS FOR THE LOCATION, EXTENT, AND ORIENTATION OF CMU BLOCKS WITH REGARD TO COLOR AND FINISH.
15. OPENINGS FOR DUCTS AND PIPES PENETRATING MASONRY WALLS MUST BE COORDINATED PER CONTRACT DOCUMENTS. PROVIDE ADDITIONAL
REINFORCEMENT AROUND PENETRATIONS THROUGH WALLS AS SHOWN.
MASONRY
ITEM STANDARD, GRADE, AND NOTES MIN STRENGTH (PSI)
ASSEMBLY COMPRESSIVE STRENGTH, f'm
CMU BLOCK (MIN. NET AREA COMPRESSIVE
28-DAY STRENGTH)
MORTAR
GROUT
STEEL REINFORCEMENT
ASTM C90, TYPE 1 (MOISTURE
CONTROLLED), MEDIUM WEIGHT
ASTM C270, TYPE S. MASONRY CEMENT
MORTAR PROHIBITED.
GROUT SLUMP AT TIME OF GROUTING MUST
BE 8 TO 11 INCHES. WATER-REDUCING
ADMIXTURES MAY BE ADDED TO ACHIEVE
PERMITTED SLUMP.
ASTM A615, GR 60
ASTM A706, GR 60 (WHERE WELDED)
2,000
2,000
1,800
2,000
60 KSI YIELD
1. REFERENCES:
A. ACI 301-20 SPECIFICATIONS FOR CONCRETE CONSTRUCTION
B. ACI 315R-18 DETAILS AND DETAILING CONCRETE CONSTRUCTION
C. ACI 318-19 BUILDING CODE REQUIREMENTS FOR STRUCTURAL CONCRETE
D. ACI 347-14 GUIDE TO FORMWORK FOR CONCRETE
1. CONCRETE WORK MUST CONFORM TO ACI 301. FORMWORK MUST CONFORM TO ACI 347.
2. MINIMUM CONCRETE PROPERTIES AT 28-DAYS PER THE FOLLOWING TABLE.
3. FLEXURAL STRENGTH FOR SLAB-ON-GRADE CONCRETE 650 PSI AT 90 DAYS
4.
5. CONCRETE EXPOSED TO THE ENVIRONMENT MUST HAVE 6% +/- 1% AIR ENTRAINMENT BY VOLUME PER ASTM C260.
6. PROVIDE A MUD SLAB (MINIMUM 2 INCHES OF CONCRETE, LEVELED AT THE TOP SURFACE) UNDER SLABS AND FOOTINGS AT WET OR MUDDY GROUND SURFACES WHICH ARE UNSUITABLE FOR SUPPORTING REBAR CHAIRS, CONSTRUCTION WORKERS AND EQUIPMENT. PROVIDE WATERPROOF MEMBRANE TO
TOP OF MUD SLAB AS REQUIRED.
7. HORIZONTAL CONSTRUCTION JOINTS IN SPREAD FOOTINGS, STRIP FOOTINGS, PILE CAPS, BEAMS AND SLABS ARE PROHIBITED UNLESS SHOWN ON THE
DRAWINGS OR APPROVED BY THE SER.
8. THE EXTENT OF CONCRETE PLACEMENTS MUST BE LIMITED AS FOLLOWS, UNLESS NOTED OTHERWISE:
A. STRIP FOOTINGS AND WALLS: 60 FT (UNLESS INTERMEDIATE CONTROL JOINTS ARE PROVIDED)
B. SLABS-ON GROUND: 30 FT MAXIMUM LENGTH AND 900 SQ FT MAXIMUM AREA (UNLESS INTERMEDIATE CONTROL JOINTS ARE PROVIDED)
9. BEFORE CASTING THE SECOND SIDE OF A CONSTRUCTION JOINT, ROUGHEN SURFACE OF CONCRETE ELEMENTS AT CONSTRUCTION JOINTS TO A MINIMUM AMPLITUDE OF 1/4 INCH, UNLESS NOTED OTHERWISE. CLEAN AND APPLY BONDING AGENT TO THE HARDENED CONCRETE SURFACE RECEIVING FRESH
CONCRETE.
10. SECTIONS AND DETAILS MAY NOT SHOW ALL REQUIRED DEFORMED BAR REINFORCEMENT FOR CLARITY. ADDITIONAL REINFORCEMENT MAY BE DESCRIBED
IN PLANS, SCHEDULES, NOTES, OR OTHER DETAILS, AS APPLICABLE.
11. COORDINATE FLOOR FINISHES, SLAB SLOPES & DEPRESSIONS, FLOOR DRAINS, CURBS, CONCRETE PADS, AND OTHER CONCRETE FEATURES IDENTIFIED IN
THE CONTRACT DOCUMENTS.
12. THE STRUCTURAL DRAWINGS DO NOT NECESSARILY SHOW ALL ITEMS EMBEDDED IN THE CONCRETE. COORDINATE AND PROVIDED EMBEDDED ITEMS AS SHOWN IN THE CONTRACT DOCUMENTS AND AS REQUIRED BY THE EQUIPMENT MANUFACTURERS, AS NEEDED.
13. NON-STRUCTURAL STEEL MEMBERS EMBEDDED IN CONCRETE MUST BE HOT-DIP GALVANIZED OR PAINTED. DAMAGED COATINGS OF EMBEDDED ITEMS MUST
BE REPAIRED PRIOR TO CASTING CONCRETE.
14. PENETRATIONS THROUGH CONCRETE WALLS OR SLABS MUST CONFORM TO STANDARD DETAIL DRAWINGS.
15. PROVIDE 3/4" CHAMFER ON EXPOSED CONCRETE EDGES UNLESS NOTED OTHERWISE.
CAST IN PLACE CONCRETE
LOCATION MIN 28-DAY COMPRESSIVE
STRENGTH
(PSI)
FREEZING
& THAWING
FOUNDATIONS
SLAB-ON-GROUND (EXTERIOR)
SLAB-ON-GROUND (INTERIOR)
4,500
4,500
4,000
S1
S1
S0
SULFATE WATER
CONTACT
ACI 318, CH. 19 EXPOSURE CATEGORIES
CORROSION
PROTECTION
F2
F2
F0
W1
W2
W0
C1
C2
C0
MAX
WATER/CEMENT
RATIO
0.45
0.45
0.50
CEMENT
TYPE
II
II
I OR II
NOMINAL MAX
AGGREGATE
SIZE
1"
1"
1 1/2"
VERTICAL
LATERAL
STORY DRIFT
L/600
L/180
TOTAL: DL + LL
ELEMENT
1. DEFLECTION LIMITS OF MATERIAL STANDARDS ALSO APPLY.
2. SPAN LENGTH (L) AND WALL HEIGHT (H) ARE MEASURED IN INCHES FROM THE CENTERLINES OF SUPPORTS. THE LENGTH OF CANTILEVERED ELEMENTS
MUST BE FACTORED BY 2.
DEFLECTION LIMITS
VENEER LINTELS
ROOFS (NOT SUPPORTING PLASTER
OR STUCCO CEILINGS)
WALLS WITH BRITTLE FINISHES
(EXCL. VENEER)
WALLS WITH FLEXIBLE FINISHES
WIND
SEISMIC
DEFLECTION LIMITS FOR LOAD CASE
LL OR SL OR WL
L/600
L/240
H/600
H/180
H/500 (ELASTIC)
0.007 H (INELASTIC)
1. CONFLICTS BETWEEN THE DRAWINGS AND SPECIFICATIONS MUST BE BROUGHT TO THE ATTENTION OF THE CONTRACTING OFFICER AND STRUCTURAL ENGINEER OF RECORD (SER) IN WRITTEN FORM AND RESOLVED BEFORE PROCEEDING WITH AFFECTED WORK.
2. STRUCTURAL DRAWINGS REPRESENT THE COMPLETED STRUCTURE. THE CONTRACTOR IS RESPONSIBLE FOR THE MEANS AND METHODS NECESSARY TO COMPLETE THE WORK, FOR JOB SITE SAFETY AND FOR COORDINATING WITH OTHER DISCIPLINES AS REQUIRED.
3. THE CONTRACTOR IS RESPONSIBLE FOR THE ERECTION PROCEDURE AND SEQUENCING TO ENSURE STABILITY OF THE STRUCTURE DURING CONSTRUCTION. PROVIDE SHORING, BRACING, AND FALSEWORK AS NEEDED TO PROTECT THE STRUCTURE THROUGHOUT CONSTRUCTION.
4. ERECTION AIDS FOR FACILITATING CONSTRUCTION NOT SHOWN IN THESE DRAWINGS MUST BE REMOVED AND ELEMENTS RESTORED TO ITS ORIGINAL
DESIGN INTENT SHOWN PER THESE DRAWINGS.
5. STRUCTURAL DRAWINGS SHOW GENERAL AND TYPICAL DETAILS OF CONSTRUCTION. WHERE SPECIFIC CONDITIONS ARE NOT SHOWN, DETAILS OF
SIMILAR TYPE AND CHARACTER MAY BE USED BUT REQUIRE APPROVAL FROM THE SER.
6. TYPICAL DETAILS MAY NOT BE REFERENCED FROM THE PLANS BUT APPLY FOR THE CONDITIONS AS DESCRIBED BY THE DETAIL.
7. CONTRACTOR-INITIATED CHANGES REQUIRE APPROVAL FROM THE SER.
8. FOR A CONTRACTOR REQUESTED DESIGN REVISION, THE PROPOSED ALTERNATIVE MUST BE SUBMITTED TO THE CONTRACTING OFFICER FOR REVIEW AND APPROVAL BY THE SER. THE SUBMITTAL MUST INCLUDE DRAWINGS, STRUCTURAL DETAILS AND RELATED CALCULATIONS, STAMPED AND SIGNED BY A PROFESSIONAL ENGINEER LICENSED TO PRACTICE IN THE JURISDICTION OF THE PROJECT LOCATION. CALCULATIONS MUST DEMONSTRATE COMPLIANCE WITH THE CODES AND DESIGN REQUIREMENTS LISTED PER THESE DRAWINGS; AND THAT THE ALTERNATIVE DESIGN DOES NOT ADVERSELY
AFFECT THE STRUCTURE SHOWN IN THESE DRAWINGS.
9. CONTRACTOR MUST COORDINATE THESE DRAWINGS WITH THE DRAWINGS OF THE OTHER DISCIPLINES AND SPECIFICATIONS FOR ADDITIONAL INFORMATION NOT SHOWN ON THE STRUCTURAL DRAWINGS. EXAMPLES INCLUDE EMBEDDED ANCHORS, SLEEVES AND INSERTS, MISCELLANEOUS ATTACHMENT DETAILS, FLOOR FINISHES, DOOR THRESHOLDS, SLOPES TO DRAINS, OPENINGS IN STRUCTURAL ELEMENTS, ETC.
10. VERIFY DIMENSIONS AND DETAILS PRIOR TO FABRICATION AND CONSTRUCTION. THIS INCLUDES COORDINATING THE SIZE AND LOCATION OF OPENINGS THROUGH STRUCTURAL ELEMENTS WITH THE RESPECTIVE SUBCONTRACTOR, AS WELL AS COORDINATING INSERTS AND ATTACHMENTS FOR USE BY
OTHER TRADES.
11. NO PIPES OR DUCTS MAY BE PLACED IN STRUCTURAL MEMBERS UNLESS DETAILED BY THE STRUCTURAL PLANS OR APPROVED BY THE SER.
12. DIMENSIONS MUST NOT BE SCALED FROM THE DRAWINGS.
13. PROVIDE SUBMITTALS AND (FABRICATION, AND ERECTION, ETC.) SHOP DRAWINGS FOR THE WORK SHOWN IN THESE DRAWINGS TO THE CONTRACTING OFFICE FOR APPROVAL FROM THE SER. WORK MUST NOT PROCEED WITHOUT REVIEW AND APPROVAL BY THE SER.
14. SUBMIT A DETAILED PLAN OF THE CONSTRUCTION INCLUDING A DESCRIPTION OF DEMOLITION, CONSTRUCTION METHODS, ERECTION SEQUENCING, METHODS OF STABILIZING THE STRUCTURE, SHORING LAYOUT, ELEMENT SIZES, CONNECTIONS AND ACCESSORIES WITH SUPPORTING CALCULATIONS STAMPED AND SIGNED BY A REGISTERED PROFESSIONAL ENGINEER, TO THE CONTRACTING OFFICER FOR REVIEW AND APPROVAL PRIOR TO BEGINNING
WORK.
15. SHOP DRAWINGS MUST BE SUBMITTED TO THE CONTRACTING OFFICER FOR REVIEW AND APPROVAL PRIOR TO FABRICATION. UNLESS NOTED
OTHERWISE, PROVIDE SHOP DRAWINGS FOR:
a. DEFORMED BAR REINFORCING LAYOUT FOR CONCRETE AND MASONRY,
b. STRUCTURAL AND MISCELLANEOUS STEEL,
c. COLD-FORMED STEEL FRAMING,
d. ROOF METAL DECK
1. BY SUBMITTING FOR ENGINEER’S REVIEW, THE CONTRACTOR CONFIRMS THE ACCURACY OF THE SUBMITTALS FOR DIMENSIONS, QUANTITIES, ELEMENT SIZES, CONSTRUCTION MATERIALS, FIELD MEASUREMENTS AND THAT THE CONTENTS HAVE BEEN REVIEWED FOR MEANS, METHODS, AND OPERATIONS
OF CONSTRUCTION, AND FOR ITS ADHERENCE TO SAFETY PROTOCOLS AT THE SITE.
2. SHOP DRAWING REVIEW DOES NOT RELIEVE THE CONTRACTOR FROM HAVING SOLE RESPONSIBILITY FOR THE ACCURACY OF ELEMENT SIZES, DIMENSIONS AND DETAILS. SUCH REVIEW DOES NOT CONSTITUTE ACCEPTANCE BY THE ENGINEER OF THE CORRECTNESS OR ADEQUACY OF SUCH SUBMITTALS, NOR IS A WARRANTY THAT THE SUBMITTALS SATISFY THE REQUIREMENTS OF THE CONTRACT.
GENERAL CONDITIONS
CODES AND STANDARDS
REFERENCES:
ASCE 7-16 MINIMUM DESIGN LOADS FOR BUILDINGS AND OTHER STRUCTURES
VA STRUCTURAL DESIGN MANUAL PG-18-10 OCTOBER 1ST 2022, REVISED JULY 1, 2023
DESIGN LOADS
DEAD LOADS
SUPERIMPOSED DEAD LOADS
ROOF
WALLS
WALLS
ROOFING MATERIALS
EXTERIOR WALL SKIN
PARTITIONS
40 (LATERAL ONLY)
15 (10 LATERAL)
UNIFORM LOAD
(PSF)
CATEGORYLOCATION
LIVE AND ROOF LIVE LOADS
CORRIDORS
MECHANICAL ROOM
OFFICE
Data Center
ROOF
20 300
CONCRETE LOAD
(LBS)
OCCUPANCY OR USE UNIFORM LOAD
(PSF)
BLAST LOADS
CHARGE WEIGHTS VA PHYSICAL SECURITY TEAM
STANDOFF REQUIREMENTS VA PHYSICAL SECURITY & RESILIENCY DESIGN MANUAL
BLAST LOADING UFC 3-340-02
LEVEL OF PROTECTION VA PHYSICAL SECURITY & RESILIENCY DESIGN MANUAL AND ASCE 59-11
ALL DOOR EXTERIOR DOOR FRAMES AND CONNECTIONS SHALL BE DESIGNED FOR BLAST LOADS
Revisions: Date: 024 OF 410 407
WSP USA Inc.
1201 Pacific Ave, Suite 550 Tacoma WA, 98402
TEL: (206) 431-2300
FAX: (206) 431-2250
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
ENGINEERING DISCIPLINE:
SPEES DESIGN BUILD
23830 PACIFIC HIGHWAY S. SUITE 203
KENT, WA 98032
/1 /2
:1
:5
P M
B
IM
/6
-2
-1 a V
A M o n tg o m e ry E
H R
M /V
A M
Y
D A
T A
C E
N T
E R
S
T R
.r v t
S-002
STRUCTURAL GENERAL NOTES
BUILDING #99
NRT JKM
100% CONSTRUCTION
DOCUMENTS
10/24/2025
619-21-106EHRM INFRASTRUCTURE
UPGRADES - MONTGOMERY
VA - AL CENTRAL ALABAMA (WEST CAMPUS)
215 PERRY HILL ROAD, MONTGOMERY, AL 36109
STRUCTURAL STEEL
WIDE FLANGES (W) AND TEES (WT)
CHANNELS (C & MC) AND ANGLES (L)
PLATE AND FLAT BAR STOCK (PL)
HSS
PIPE
OTHER STEEL
ASTM A992
ASTM A36
ASTM A36 GR 36
ASTM A500 GR C
ASTM A500 GR B
ASTM A53 GR B
ASTM A572
MIN YIELD
(KSI)
SHAPE
1. REFERENCES:
A. AISC 303-22 CODE OF STANDARD PRACTICE FOR STEEL BUILDINGS AND BRIDGES
B. AISC 360-16 SPECIFICATION FOR STRUCTURAL STEEL BUILDINGS
C. AISC RESEARCH COUNCIL ON STRUCTURAL CONNECTIONS (RCSC) SPECIFICATION FOR STRUCTURAL JOINTS USING HIGH-STRENGTH BOLTS 2014
2. STRUCTURAL STEEL WORK MUST BE PERFORMED BY AISC CERTIFIED FABRICATORS & ERECTORS.
3. STEEL CONSTRUCTION AND DESIGN AS PART A DEFERRED DESIGN SUBMITTAL MUST CONFORM TO AISC 360 AND AISC 303.
4. USE STRUCTURAL STEEL SHAPES (AS APPLICABLE PER THE DRAWINGS), WITH CROSS-SECTIONS PER ASTM A6, PER THE FOLLOWING TABLE.
5. PROVIDE PROTECTIVE COATING AT STEEL EXPOSED TO THE ENVIRONMENT AND WEATHER PER ARCHITECTURAL REQUIREMENTS.
6. MACHINE COLUMN ENDS AT SPLICES TO PROVIDE A FLUSH BEARING CONTACT SURFACE, UNLESS NOTED OTHERWISE.
7. EQUALLY SPACE STEEL BEAMS, NOT SPECIFICALLY DIMENSIONED ON PLAN, BETWEEN COLUMN GRID LINES OR THE INDICATED DIMENSIONED POINTS.
8. CAMBER BEAMS AS INDICATED. WHERE CAMBER IS NOT SHOWN, FABRICATE BEAMS WITH INCIDENTAL CAMBER SO THE HIGH SIDE IS PLACED UPWARD, OR
OUTWARD AT WIND GIRTS.
9. CAMBER MUST BE COLD FORMED PER AISC SPECIFICATIONS AND TOLERANCES.
10. USE HIGH STRENGTH (HS) BOLTS PER ASTM F3125, GRADES AS INDICATED IN THE FOLLOWING TABLE, UNLESS NOTED OTHERWISE.
11. SLIP-CRITICAL (SC) BOLTS MUST BE PER THE RCSC SPECIFICATION AND INSPECTED IN ACCORDANCE WITH THE IBC.
12. USE SNUG-TIGHT (ST) BOLTS PER THE RCSC WHEN SLIP-CRITICAL IS NOT IDENTIFIED IN THE DRAWINGS.
13. USE ASTM A449 BOLTS WITH ASTM F563 NUTS AND ASTM F436 HARDENED WASHERS FOR THROUGH BOLTING HSS SHAPES. BOLTS MUST BE SNUG TIGHT ONLY.
PROVIDE JAMB NUT TIGHTENED AGAINST STANDARD NUT TO FASTEN CONNECTOR.
14. DIRECT TENSION INDICATING (DTI) WASHERS, IF USED FOR HIGH STRENGTH BOLTS, MUST NOT BE TIGHTENED TO A FULLY CRUSHED CONDITION. DTI MUST HAVE THE MINIMUM ACCEPTABLE NUMBER OF TAPERED GAGE REJECTIONS BETWEEN LUGS. REJECTION OF GAGE AT EACH LUG LOCATION IS CAUSE FOR
REJECTION OF BOLT INSTALLATION.
15. CONTRACTOR MUST SUBMIT A BOLTING PROCEDURE PLAN TO THE CONTRACTING OFFICER FOR REVIEW AND APPROVAL BY THE SER BEFORE BEGINNING
WORK.
16. BOLT HOLES CUT IN THE FIELD MUST BE DRILLED, NOT BURNED. BOLT HOLES CUT IN THE SHOP MAY BE DRILLED, WATER-JET OR LASER CUT; PLASMA CUTTING
HOLES NOT PERMITTED.
17. LOCATION OF EMBEDDED ELEMENTS MUST BE COORDINATED WITH CONTRACT DOCUMENTS.
18. STEEL COMPONENTS EMBEDDED IN CONCRETE OR MASONRY AT EXTERIOR LOCATIONS, EXPOSED TO EARTH, OR LOCATED IN UNCONDITIONED SPACE, MUST
BE HOT-DIPPED GALVANIZED PER ASTM A123 [OR ASTM A767 FOR REINFORCEMENT].
19. AT INTERIOR CONDITIONS (NOT EXPOSED TO WEATHER) AND COMPONENTS EMBEDDED IN CONCRETE OR MASONRY MUST BE LEFT UNPAINTED.
20. ERECTION AIDS, WHICH ARE THE SOLE RESPONSIBILITY OF THE CONTRACTOR, MUST BE REMOVED AND THE AFFECTED ELEMENTS RESTORED TO ORIGINAL
DESIGN INTENT.
21. NOTIFY CONTRACTING OFFICER OF ANY FABRICATION OR ERECTION ERRORS, OR DEVIATIONS. WRITTEN APPROVAL IS REQUIRED BEFORE FIELD
CORRECTIONS ARE MADE.
STANDARD &
GRADE
RECTANGULAR OR SQUARE
ROUND
BOLT DIAMETER
BOLT ASTM F3125 GRADE
BOLT FINISH/COATING
HEAVY HEX NUT
HARDENED WASHER (CIRCULAR, BEVELED OR
CLIPPED, AS REQ'D)
DIRECT TENSION INDICATING WASHERS
BOLT DIAM. 1-1/2 IN AND SMALLER
BOLT DIAM. UP TO 2-1/2 INCHES
TENSION CONTROLLED BOLTS (USE
MANUFACTURER SUPPLIED NUTS AND WASHERS)
7/8 INCH DIAMETER, UNO
A325, TYPE 1 UNO
ASTM F2329 HDG [ASTM B695, F1136, F2833]
ASTM A563 TYPE DH'
ASTM F436 TYPE 1
ASTM F959
ASTM F2437
F1852 , TYPE 1
TYPICAL HIGH STRENGTH BOLTS STANDARD, GRADE, AND NOTES
ANCHOR RODS
1. ANCHOR RODS MUST BE ASTM F1554 GRADE 55 WITH S-1 (WELDABLE) SUPPLEMENT, UNLESS NOTED OTHERWISE.
2. PROVIDE SMOOTH ANCHOR RODS THREADED ONLY AT EACH END OF THE ANCHOR ROD. BEFORE CASTING CONCRETE, GREASE THE UPPER 2/3 LENGTH OF EACH ANCHOR ROD.