ATT 02 - 619-21-106_VA-Montgomery_SPECS_updated 080526.pdf
PDF 12 MB Posted
- Attached to
- Y1DA--Construction | 619-21-106 | EHRM Infrastructure Upgrades - Montgomery (VA-27-00002289)
- Solicitation number
- 36C77626R0112
About this file
This is a comprehensive specification document for construction services related to EHRM Infrastructure Upgrades at Montgomery VA Medical Center in Montgomery, Alabama (Project 619-21-106). The project encompasses significant infrastructure modernization across multiple buildings (1, 4, 5, 6, 7, 8, 12, 13, 14, 40) and campus-wide systems, including electrical panel upgrades with normal and emergency power provisions, HVAC reconfiguration and expansion, data center replacement with new construction, communication infrastructure upgrades (Cat 6A cabling, data outlets, patch panels), fiber optic backbone installation campus-wide, physical security upgrades, site civil work, and comprehensive hazardous material abatement (asbestos, lead-based paint removal).
The contract is structured into eight primary work items: General Requirements and Management; General Construction including selective demolition; Electrical Work; Mechanical Work; Telecommunications Work; Structural Work; Site and Civil Work; and Environmental Remediation. The specification mandates strict security protocols including badge access requirements, document control procedures, vehicle authorization protocols, and employee screening. Critical operational requirements include maintaining 24/7 medical center operations with construction phased to minimize disruption, with specific ICRA (Infection Control Risk Assessment) classifications determining work hours—Class II and III areas requiring normal business hours with 21-28 days advance notice, and Class IV areas (Buildings 1 and 40) permitting work on maximum one room at a time during normal business hours. The contractor must provide detailed phasing plans addressing infrastructure cutover procedures, maintain existing utility services continuously, conduct pre-construction surveys documenting existing conditions, provide as-built drawings, implement comprehensive warranty management with 4 and 9-month inspections, and coordinate all activities with the VA Contracting Officer's Representative throughout the project duration.
View the file
Other files
Show all 17
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
24 OCTOBER 2025
EHRM
INFRASTRUCTURE
UPGRADES
PROJECT #: 619-21-106
MONTGOMERY VA MEDICAL CENTER –
MONTGOMERY, ALABAMA
SPECIFICATIONS
DIV 00-33
100% SUBMITTAL
CONSTRUCTION DOCUMENTS 2
EHRM INFRASTRUCTURE UPGRADES PROJECT #: 619-21-106
MONTGOMERY VA MEDICAL CENTER – MONTGOMERY, AL PUB. DATE: 2022-07
TABLE OF CONTENTS 00 01 10 - 01
DEPARTMENT OF VETERANS AFFAIRS
VHA MASTER SPECIFICATIONS
TABLE OF CONTENTS
Section 00 01 10
SECTION NO. DIVISION AND SECTION TITLES DATE
DIVISION 00 - SPECIAL SECTIONS
00 01 07 Seals Page 00 01 15 List of Drawing Sheets 05-20
DIVISION 01 - GENERAL REQUIREMENTS
01 00 00 General Requirements 11-21 01 32 16.15 Project Schedules (Small Projects – Design/Bid/Build 01-24 01 33 23 Shop Drawings, Product Data, and Samples 11-23 01 35 26 Safety Requirements 05-24 01 42 19 Reference Standards 11-20 01 45 00 Quality Control 02-21 01 45 29 Testing Laboratory Services 11-18 01 45 35 Special Inspections 06-21 01 57 19 Temporary Environmental Controls 01-21 01 74 19 Construction Waste Management 04-22 01 81 13 Sustainable Construction Requirements 10-17 01 91 00 General Commissioning Requirements 04-22
DIVISION 02 – EXISTING CONDITIONS
02 41 19 Selective Demolition 08-17 02 65 00 Above Ground Storage Tank Removal 01-21 02 82 13.19 Asbestos Floor Tile and Mastic Abatement 01-21 02 83 33.13 Lead-Based Paint Removal and Disposal 01-21
DIVISION 03 – CONCRETE
03 30 00 Cast-in-Place Concrete 01-21
DIVISION 04 – MASONRY
04 05 13 Masonry Mortaring 10-17 04 05 16 Masonry Grouting 01-21 04 20 00 Unit Masonry 08-17
TABLE OF CONTENTS 00 01 10 - 02
SECTION NO. DIVISION AND SECTION TITLES DATE
DIVISION 05 – METALS
05 12 00 Structural Steel Framing 11-18 05 31 00 Steel Decking 01-21
DIVISION 06 – WOOD, PLASTICS AND COMPOSITES
06 10 00 Rough Carpentry 10-17
DIVISION 07 - THERMAL AND MOISTURE PROTECTION
07 21 13 Thermal Insulation 01-21 07 22 00 Roof and Deck Insulation 01-21 07 27 27 Fluid-Applied Membrane Air Barrier, Vapor Retarding 01-21 07 54 23 Thermoplastic Polyolefin (TPO) Roofing 01-21 07 60 00 Flashing and Sheet Metal 01-21 07 72 00 Roof Accessories 01-21 07 81 00 Sprayed Applied Fireproofing 07-23 07 84 00 Firestopping 01-21 07 92 00 Joint Sealants 04-22
DIVISION 08 - OPENINGS
08 11 13 Hollow Metal Doors and Frames 01-21 08 14 00 Interior Wood Doors 01-21 08 17 10 Integrated Door Assemblies 01-21 08 34 53 Security Doors and Frames 01-21 08 71 00 Door Hardware 03-24 08 90 00 Louvers and Vents 01-21
DIVISION 09 – FINISHES
09 05 16 Subsurface Preparation for Floor Finishes 01-21 09 06 00 Schedule for Finishes 01-21 09 22 16 Non-Structural Metal Framing 06-18 09 29 00 Gypsum Board 04-20 09 65 13 Resilient Base and Accessories 01-21 09 65 19 Resilient Tile Flooring 05-18 09 66 00 Static Dissipative Sealer for Concrete Substrates 01-21 09 91 00 Painting 01-21
DIVISION 10 – SPECIALTIES
TABLE OF CONTENTS 00 01 10 - 03
SECTION NO. DIVISION AND SECTION TITLES DATE
10 14 00 Signage 01-21 10 26 00 Wall and Door Protection 01-21 10 44 13 Fire Extinguisher Cabinets 08-18
DIVISION 13 - SPECIAL CONSTRUCTION
13 05 41 Seismic Restraint Requirements for Non-Structural Components 01-21
DIVISION 21- FIRE SUPPRESSION
21 13 13 Wet-Pipe Sprinkler Systems 06-15 21 22 00 Clean Agent Fire Suppression Systems 05-15
DIVISION 22 – PLUMBING
22 05 11 Common Work Results for Plumbing 01-23 22 07 11 Plumbing Insulation 09-15 22 11 00 Facility Water Distribution 05-21 22 13 00 Facility Sanitary and Vent Piping 09-20 22 14 00 Facility Storm Drainage 09-15 22 40 00 Plumbing Fixtures 09-15
DIVISION 23 – HEATING, VENTILATING, AND AIR CONDITIONING (HVAC)
23 05 11 Common Work Results for HVAC 09-23 23 05 12 General Motor Requirements for HVAC and Steam Generation Equipment 03-23 23 05 41 Noise and Vibration Control for HVAC Piping and Equipment 03-23 23 05 93 Testing, Adjusting, and Balancing for HVAC 03-23 23 07 11 HVAC Insulation 02-20 23 08 00 Commissioning of HVAC Systems 03-23 23 09 23 Direct-Digital Control System for HVAC 03-23 23 23 00 Refrigerant Piping 03-24 23 31 00 HVAC Ducts and Casings 02-20 23 34 00 HVAC Fans 03-23 23 37 00 Air Outlets and Inlets 03-23 23 50 11 Boiler Plant Mechanical Equipment 03-22 23 72 00 Air-to-Air Energy Recovery Equipment 03-20 23 81 23 Computer-Room Air-Conditioners 03-20 23 81 43 Air-Source Unitary Heat Pumps 03-23 23 82 16 Air Coils 03-20 23 84 00 Humidity Control Equipment 03-20
DIVISION 26 – ELECTRICAL
TABLE OF CONTENTS 00 01 10 - 04
SECTION NO. DIVISION AND SECTION TITLES DATE
26 05 11 Requirements for Electrical Installations 11-22 26 05 13 Medium-Voltage Cables 11-22 26 05 19 Low-Voltage Electrical Power Conductors and Cables 11-22 26 05 26 Grounding and Bonding for Electrical Systems 11-22 26 05 33 Raceway and Boxes for Electrical Systems 11-22 26 05 41 Underground Electrical Construction 11-22 26 05 73 Overcurrent Protective Device Coordination Study 11-22 26 08 00 Commissioning of Electrical Systems 11-16 26 09 23 Lighting Controls 11-22 26 12 19 Pad-Mounted, Liquid-Filled, Medium-Voltage Transformers 11-22 26 22 00 Low-Voltage Transformers 11-22 26 23 00 Low-Voltage Switchgear 01-17 26 24 13 Distribution Switchboards 11-22 26 24 16 Panelboards 11-22 26 25 11 Busways 11-22 26 27 26 Wiring Devices 11-22 26 29 11 Motor Controllers 11-22 26 29 21 Enclosed Switches and Circuit Breakers 11-22 26 32 13 Engine Generators 11-22 26 33 53 Static Uninterruptible Power Supply 11-22 26 36 23 Automatic Transfer Switches 11-22 26 41 00 Facility Lightning Protection 11-22 26 43 13 Surge Protective Devices 11-22 26 51 00 Interior Lighting 03-24 26 56 00 Exterior Lighting 11-22
DIVISION 27 – COMMUNICATIONS
27 05 26 Grounding and Bonding for Communications Systems 11-22 27 05 33i Raceways and Boxes for Communications Systems 11-22 27 05 36i Cable Trays for Communications Systems 11-22 27 05 53i Identification for Communications Systems 11-22 27 10 00i Structured Cabling 11-22 27 11 16i Communications Cabinets Tacks Frames and Enclosures 11-22 27 11 19i Communications Termination Blocks and Patch Panels 11-22 27 11 26 Communications Rack-Mounted Power Protection & Power Strips 11-22 27 13 13 Communications Copper Backbone Cabling 11-22 27 13 13.13i Communications Copper Cable Splicing and Terminations 11-22 27 13 23 Communications Optical Fiber Backbone Cabling 06-15 27 13 23.13i Communications Optical Fiber Splicing and Terminations 11-22 27 15 13i Communications Copper Horizontal Cabling 05-24 27 16 19i Communications Patch Cords Station Cords and Cross Connects 11-22
TABLE OF CONTENTS 00 01 10 - 05
SECTION NO. DIVISION AND SECTION TITLES DATE
DIVISION 28 – ELECTRONIC SAFETY AND SECURITY
28 05 00 Common Work Results for Electronic Safety and Security 04-18 28 05 13 Conductors and Cables for Electronic Safety and Security 10-18 28 05 26 Grounding and Bonding for Electronic Safety and Security 09-11 28 05 28.33 Conduit and Backbone for Electronic Safety and Security 09-11 28 08 00 Commissioning of Electronic Safety and Security Systems 11-16 28 13 00 Physical Access Control System 10-11 28 13 53 Security Access Detection 09-11 28 23 00 Video Surveillance 09-11 28 31 00 Fire Detection and Alarm 10-11
DIVISION 31 – EARTHWORK
31 20 11 Earthwork (Short Form) 10-12
DIVISION 32 – EXTERIOR IMPROVEMENTS
32 05 23 Cement and Concrete for Exterior Improvements 08-16 32 12 16 Asphalt Paving 09-15 32 17 23 Pavement Markings 08-16
DIVISION 33 – UTILITIES
33 10 00 Water Utilities 03-17 33 30 00 Sanitary Sewer Utilities 06-13 33 40 00 Storm Sewer Utilities 12-17
MONTGOMERY VA MEDICAL CENTER – MONTGOMERY, AL
SEALS PAGE 00 01 07 - 01
SECTION 00 01 07
SEALS PAGE
CERTIFICATION
The technical material and data contained in these Contract Documents were prepared under the supervision and direction of the undersigned, whose seal, as a licensed professional to practice as such, is affixed below.
James M. King, Registered Architect Division 0, 1, 4 & 6-10
Michael Hubbard, P.E.
Mechanical Engineer Division 22-23
L. Ryan Litzko, P.E.
Electrical Engineer Division 26
Mark Morgan, PE
CIH
Division 02
MONTGOMERY VA MEDICAL CENTER – MONTGOMERY, AL
SEALS PAGE 00 01 07 - 02
Dante Valdez, S.E.
Structural Engineering Division 5, 13
Peter Bailey, P.E.
Civil Engineering Division 3, 31-33
Greg Kimble, PE Fire Protection Engineer Division 21, 27-28 (Fire alarm)
Kris Good
RCDD
Division 27-28 (No Fire alarm)
MONTGOMERY VA MEDICAL CENTER – MONTGOMERY, AL PUB. DATE: 2020-05
LIST OF DRAWING SHEETS 00 01 15 - 01
SECTION 00 01 15
LIST OF DRAWING SHEETS
The drawings listed below accompanying this specification form a part of the contract.
1 OF 410 G-001 COVER SHEET
2 OF 410 G-002 DRAWING INDEX
3 OF 410 C-001 CIVIL SHEET INDEX AND GENERAL NOTES
4 OF 410 C-002 GENERAL NOTES AND LEGEND
5 OF 410 CD200 MCR BUILDING DEMOLITION PLAN
6 OF 410 CS100 OVERALL CIVIL SITE PLAN
7 OF 410 CS200 MCR BUILDING SITE PLAN
8 OF 410 CS201 MCR BUILDING HORIZONTAL CONTROL PLAN
9 OF 410 CG100 OVERALL EROSION CONTROL PLAN
10 OF 410 CG101 EROSION CONTROL GENERAL NOTES AND DETAILS
11 OF 410 CG200 MCR BUILDING EROSION CONTROL PLAN
12 OF 410 CG201 MCR BUILDING GRADING AND DRAINAGE PLAN
13 OF 410 CG202 MCR BUILDING STORMWATER BMP PLAN
14 OF 410 CU200 MCR BUILDING UTILITY PLAN
15 OF 410 CU250 CIVIL UTILITY CONSTRUCTION DETAILS
16 OF 410 CU300 OVERALL FIBER OPTIC OUTSIDE PLANT UTILITY PLAN
17 OF 410 CU301 FIBER OPTIC OUTSIDE PLANT UTILITY PLAN
18 OF 410 CU302 FIBER OPTIC OUTSIDE PLANT UTILITY PLAN
19 OF 410 CU303 FIBER OPTIC OUTSIDE PLANT UTILITY PLAN
20 OF 410 CU304 FIBER OPTIC OUTSIDE PLANT UTILITY PLAN
21 OF 410 CU500 COMMUNICATION DUCTBANK DETAILS
22 OF 410 CU501 COMMUNICATION TRENCHING DETAILS
23 OF 410 CU502 BUILDING CONNECTION DETAILS
24 OF 410 S-001 STRUCTURAL GENERAL NOTES
25 OF 410 S-002 STRUCTURAL GENERAL NOTES
26 OF 410 S-003 ABRREVIATIONS AND SYMBOLS
27 OF 410 S-101 FOUNDATION PLAN
28 OF 410 S-111 ROOF PLAN
29 OF 410 S-201 STRUCTURAL WALL ELEVATIONS
30 OF 410 S-202 STRUCTURAL WALL ELEVATIONS
31 OF 410 S-501 TYPICAL CONCRETE DETAILS
32 OF 410 S-502 CONCRETE FOUNDATION DETAILS
33 OF 410 S-511 TYPICAL STRUCTURAL STEEL DETAILS
34 OF 410 S-512 TYPICAL STRUCTURAL STEEL DETAILS
35 OF 410 S-531 TYPICAL CMU WALL DETAILS
36 OF 410 S-532 TYPICAL CMU WALL DETAILS
00 01 15 -
LIST OF DRAWING SHEETS 00 01 15 - 02
37 OF 410 S-541 MECHANICAL ANCHORAGE DETAILS
38 OF 410 S-542 TYPICAL DETAILS-CABINET TO CFS FRAMED WALL
39 OF 410 S-543 TYPICAL DETAILS-CABINET TO WOOD FRAMED WALL
40 OF 410 S-544 TYPICAL DETAILS-CABINET TO CONCRETE AND CMU WALL
41 OF 410 S-545 TYPICAL PENETRATIONS IN EXISTING STRUCTURE
42 OF 410 001HA100 BLDG 01 - LVL 00G - ABATEMENT DRAWINGS
43 OF 410 001HA101 BLDG 01 - LVL 01 - ABATEMENT DRAWINGS
44 OF 410 001HA102 BLDG 01 - LVL 02 - ABATEMENT DRAWINGS
45 OF 410 001HA103 BLDG 01 - LVL 03 - ABATEMENT DRAWINGS
46 OF 410 001HA104 BLDG 01 - LVL 04 - ABATEMENT DRAWINGS
47 OF 410 001HA105 BLDG 01 - LVL 05 - ABATEMENT DRAWINGS
48 OF 410 004HA100 BLDG 04 - LVL 00 - ABATEMENT DRAWINGS
49 OF 410 004HA101 BLDG 04 - LVL 01 - ABATEMENT DRAWINGS
50 OF 410 005HA100 BLDG 05 - LVL 01 - ABATEMENT DRAWINGS
51 OF 410 006HA100 BLDG 06 - LVL 01 - ABATEMENT DRAWINGS
52 OF 410 007HA100 BLDG 07 - LVL 01 - ABATEMENT DRAWINGS
53 OF 410 008HA100 BLDG 08 - LVL 01 - ABATEMENT DRAWINGS
54 OF 410 012HA100 BLDG 12 - LVL 01 - ABATEMENT DRAWINGS
55 OF 410 013HA100 BLDG 13 - LVL 01 - ABATEMENT DRAWINGS
56 OF 410 014HA100 BLDG 14 - LVL 00 - ABATEMENT DRAWINGS
57 OF 410 040HA100 BLDG 40 - LVL 00 - ABATEMENT DRAWINGS
58 OF 410 A-001 ARCHITECTURAL SYMBOLS & ABBREVIATIONS
59 OF 410 AS101 ICRA DETAILS
60 OF 410 AS102 ICRA STANDARDS
61 OF 410 01AS100B BLDG 01 -LVL 00B -PHASING PLAN
62 OF 410 01A-100G BLDG 01 -LVL 00G -ARCHITECTURAL PLAN
63 OF 410 01AS100G BLDG 01 -LVL 00G -PHASING PLAN
64 OF 410 01A-400Ga BLDG 01 -LVL 00G -DEMO, FLOOR PLANS & RCPS 65 OF 410 01A-400Gb BLDG 01 -LVL 00G -DEMO, FLOOR PLANS & RCPS
66 OF 410 01A-101 BLDG 01 -LVL 01 -ARCHITECTURAL PLAN
67 OF 410 01AS101 BLDG 01 -LVL 01 -PHASING PLAN
68 OF 410 01A-401a BLDG 01 -LVL 01 -DEMO, FLOOR PLANS & RCPS 69 OF 410 01A-401b BLDG 01 -LVL 01 -DEMO, FLOOR PLANS & RCPS
70 OF 410 01A-102 BLDG 01 -LVL 02 -ARCHITECTURAL PLAN
71 OF 410 01AS102 BLDG 01 -LVL 02 -PHASING PLAN
72 OF 410 01A-402a BLDG 01 -LVL 02 -DEMO, FLOOR PLANS & RCPS 73 OF 410 01A-402b BLDG 01 -LVL 02 -DEMO, FLOOR PLANS & RCPS
74 OF 410 01A-103 BLDG 01 -LVL 03 -ARCHITECTURAL PLAN
75 OF 410 01AS103 BLDG 01 -LVL 03 -PHASING PLAN
76 OF 410 01A-403a BLDG 01 -LVL 03 -DEMO, FLOOR PLANS & RCPS 77 OF 410 01A-403b BLDG 01 -LVL 03 -DEMO, FLOOR PLANS & RCPS
LIST OF DRAWING SHEETS 00 01 15 - 03
78 OF 410 01A-104 BLDG 01 -LVL 04 -ARCHITECTURAL PLAN
79 OF 410 01AS104 BLDG 01 -LVL 04 -PHASING PLAN
80 OF 410 01A-404a BLDG 01 -LVL 04 -DEMO, FLOOR PLANS & RCPS 81 OF 410 01A-404b BLDG 01 -LVL 04 -DEMO, FLOOR PLANS & RCPS
82 OF 410 01A-105 BLDG 01 -LVL 05 -ARCHITECTURAL PLAN
83 OF 410 01AS105 BLDG 01 -LVL 05 -PHASING PLAN
84 OF 410 01A-405 BLDG 01 -LVL 05 -DEMO, FLOOR PLANS & RCPS
85 OF 410 01AS106 BLDG 01 -LVL 06 -PHASING PLAN
86 OF 410 04A-100 BLDG 04 -LVL 00 -ARCHITECTURAL PLAN
87 OF 410 04AS100 BLDG 04 -LVL 00 -PHASING PLAN
88 OF 410 04A-400a BLDG 04 -LVL 00 -DEMO, FLOOR PLAN & RCP 89 OF 410 04A-400b BLDG 04 -LVL 00 -DEMO, FLOOR PLAN & RCP
90 OF 410 04A-101 BLDG 04 -LVL 01 -ARCHITECTURAL PLAN
91 OF 410 04AS101 BLDG 04 -LVL 01 -PHASING PLAN
92 OF 410 04A-401 BLDG 04 -LVL 01 -DEMO, FLOOR PLANS & RCPS
93 OF 410 05A-101 BLDG 05 -LVL 01 -ARCHITECTURAL PLAN
94 OF 410 05AS101 BLDG 05 -LVL 01 -PHASING PLAN
95 OF 410 05A-401 BLDG 05 -LVL 01 -DEMO, FLOOR PLANS & RCPS
96 OF 410 06AS100 BLDG 06 -LVL 00 -PHASING PLAN
97 OF 410 06A-101 BLDG 06 -LVL 01 -ARCHITECTURAL PLAN
98 OF 410 06AS101 BLDG 06 -LVL 01 -PHASING PLAN
99 OF 410 06A-401 BLDG 06 -LVL 01 -DEMO, FLOOR PLANS AND RCPS
100 OF 410 06AS102 BLDG 06 -LVL 02 -PHASING PLAN
101 OF 410 07AS100 BLDG 07 -LVL 00 -PHASING PLAN
102 OF 410 07A-101 BLDG 07 -LVL 01-ARCHITECTURAL PLAN
103 OF 410 07AS101 BLDG 07 -LVL 01 -PHASING PLAN
104 OF 410 07A-401 BLDG 07 -LVL 01 -DEMO, FLOOR PLANS & RCPS
105 OF 410 07AS102 BLDG 07 -LVL 02 -PHASING PLAN
106 OF 410 08AS100 BLDG 08 -LVL 00 -PHASING PLAN
107 OF 410 FX001 FIRE PROTECTION GENERAL NOTES, ABBREVIATION & LEGENDS
108 OF 410 099-FX101 BUILDING -099 -LEVEL -01 -FIRE PROTECTION PLAN
109 OF 410 FX501 FIRE PROTECTION DETAILS & SCHEDULE
110 OF 410 08A-101 BLDG 08 -LVL 01 -ARCHITECTURAL PLAN
111 OF 410 08AS101 BLDG 08 -LVL 01 -PHASING PLAN
112 OF 410 08A-401 BLDG 08 -LVL 01 -DEMO, FLOOR PLANS & RCPS
113 OF 410 08AS102 BLDG 08 -LVL 02 -PHASING PLAN
114 OF 410 12A-101 BLDG 12 -LVL 01 -ARCHITECTURAL PLAN
115 OF 410 12AS101 BLDG 12 -LVL 01 -PHASING PLAN
116 OF 410 12A-401 BLDG 12 -LVL 01 -DEMO, FLOOR PLANS & RCPS
117 OF 410 13A-101 BLDG 13 -LVL 1 -ARCHITECTURAL PLAN
118 OF 410 13AS101 BLDG 13 -LVL 01 -PHASING PLAN
LIST OF DRAWING SHEETS 00 01 15 - 04
119 OF 410 13A-401 BLDG 13 -LVL 01 -DEMO, FLOOR PLANS & RCPS
120 OF 410 14AS100 BLDG 14 -LVL 00 -PHASING PLAN
121 OF 410 14A-101 BLDG 14 -LVL 01 -ARCHITECTURAL PLAN
122 OF 410 14AS101 BLDG 14 -LVL 01 -PHASING PLAN
123 OF 410 14A-401 BLDG 14 -LVL 01 -DEMO, FLOOR PLANS & RCPS
124 OF 410 40A-100 BLDG 40 -LVL 00 -ARCHITECTURAL PLAN
125 OF 410 40AS100 BLDG 40 -LVL 00 -PHASING PLAN
126 OF 410 40A-400 BLDG 40 -LVL 00 -DEMO, FLOOR PLANS & RCPS
127 OF 410 A-101 BLDG 99 -FLOOR PLAN
128 OF 410 A-102 BLDG 99 -FIRE LIFE SAFETY PLAN
129 OF 410 A-103 BLDG 99 -ROOF PLAN
130 OF 410 A-104 BLDG 99 -RCP
131 OF 410 A-605 BLDG 99 -EXTERIOR DETAILS
132 OF 410 A-606 BLDG 99 -INTERIOR DETAILS AND ELEVATIONS AND EQUIPMENT SCHEDULE
133 OF 410 AE201 BLDG 99 -ELEVATIONS
134 OF 410 AE202 BLDG 99 -ELEVATIONS
135 OF 410 AE301 BLDG 99 -BUILDING SECTIONS
136 OF 410 AE401 BLDG 99 -WALL SECTIONS
137 OF 410 A-601 ROOM FINISH SCHEDULE
138 OF 410 A-602 DOOR DETAILS
139 OF 410 A-603 DETAILS
140 OF 410 A-604 DETAILS
141 OF 410 AE421 ELEVATIONS, TYPICAL DETAILS & TR WALL PLAN VIEW
142 OF 410 AW001 SIGNAGE MESSAGE SCHEDULE
143 OF 410 AW002 SIGNAGE LOCATION PLAN & DETAILS
144 OF 410 P-001 PLUMBING GENERAL NOTES
145 OF 410 P-002 PLUMBING GENERAL NOTES, ABBREVIATIONS & LEGENDS
146 OF 410 099-P-101 BUILDING -099 -FOUNDATION -PLUMBING PLAN
147 OF 410 099-P-102 BUILDING -099 -LEVEL -01 -PLUMBING PLAN
148 OF 410 099-P-103 BUILDING -099 -ROOF -PLUMBING PLAN
149 OF 410 P-501 PLUMBING DETAILS
150 OF 410 M-001 MECHANICAL GENERAL NOTES
151 OF 410 M-002 MECHANICAL ABBREVIATION & LEGENDS
152 OF 410 001-M-101 BUILDING -001 -LEVEL -00 -MECHANICAL OVERALL PLAN
153 OF 410 001-M-102 BUILDING -001 -LEVEL -01 -MECHANICAL OVERALL PLAN
154 OF 410 001-M-103 BUILDING -001 -LEVEL -02 -MECHANICAL OVERALL PLAN
155 OF 410 001-M-104 BUILDING -001 -LEVEL -03 -MECHANICAL OVERALL PLAN
156 OF 410 001-M-105 BUILDING -001 -LEVEL -04 -MECHANICAL OVERALL PLAN
157 OF 410 001-M-106 BUILDING -001 -LEVEL -05 -MECHANICAL OVERALL PLAN
158 OF 410 001-M-107 BUILDING -001 -LEVEL -06 -MECHANICAL OVERALL PLAN
159 OF 410 001-M-108 BUILDING -001 -LEVEL -07 -MECHANICAL OVERALL PLAN
LIST OF DRAWING SHEETS 00 01 15 - 05
160 OF 410 001-M-401 BUILDING -001 -LEVEL -00 -DEMOLITION, FLOOR PLANS & RCPS
161 OF 410 001-M-402 BUILDING -001 -LEVEL -00 -DEMOLITION, FLOOR PLANS & RCPS
162 OF 410 001-M-403 BUILDING -001 -LEVEL -00 -PARTIAL FLOOR PLAN
163 OF 410 001-M-404 BUILDING -001 -LEVEL -01 -DEMOLITION, FLOOR PLANS & RCPS
164 OF 410 001-M-405 BUILDING -001 -LEVEL -01 -DEMOLITION, FLOOR PLANS & RCPS
165 OF 410 001-M-406 BUILDING -001 -LEVEL -02 -DEMOLITION, FLOOR PLANS & RCPS
166 OF 410 001-M-407 BUILDING -001 -LEVEL -02 -DEMOLITION, FLOOR PLANS & RCPS
167 OF 410 001-M-408 BUILDING -001 -LEVEL -03 -DEMOLITION, FLOOR PLANS & RCPS
168 OF 410 001-M-409 BUILDING -001 -LEVEL -03 -DEMOLITION, FLOOR PLANS & RCPS
169 OF 410 001-M-410 BUILDING -001 -LEVEL -04 -DEMOLITION, FLOOR PLANS & RCPS
170 OF 410 001-M-411 BUILDING -001 -LEVEL -04 -DEMOLITION, FLOOR PLANS & RCPS
171 OF 410 001-M-412 BUILDING -001 -LEVEL -05 -DEMOLITION, FLOOR PLANS & RCPS
172 OF 410 001-M-413 BUILDING -001 -LEVEL -06 -FLOOR PLAN
173 OF 410 001-M-414 BUILDING -001 -LEVEL -07 -ROOF PLAN
174 OF 410 004-M-101 BUILDING -004 -LEVEL -00 -OVERALL PLAN
175 OF 410 004-M-102 BUILDING -004 -LEVEL -01 -OVERALL PLAN
176 OF 410 004-M-401 BUILDING -004 -LEVEL -00 -DEMOLITION & FLOOR PLANS
177 OF 410 004-M-402 BUILDING -004 -LEVEL -00 -DEMOLITION & RCPS
178 OF 410 004-M-403 BUILDING -004 -LEVEL -00 -FLOOR PLAN
179 OF 410 004-M-404 BUILDING -004 -LEVEL -01 -DEMOLITION, FLOOR PLANS & RCPS
180 OF 410 005-M-101 BUILDING -005 -LEVEL -01 -OVERALL PLAN
181 OF 410 005-M-401 BUILDING -005 -LEVEL -01 -DEMOLITION & FLOOR PLANS
182 OF 410 006-M-101 BUILDING -006 -LEVEL -01 -OVERALL PLAN
183 OF 410 006-M-401 BUILDING -006 -LEVEL -01 -DEMOLITION, FLOOR PLANS & RCPS
184 OF 410 007-M-101 BUILDING -007 -LEVEL -01 -OVERALL PLAN
185 OF 410 007-M-401 BUILDING -007 -LEVEL -01 -DEMOLITION, FLOOR PLANS & RCPS
186 OF 410 008-M-101 BUILDING -008 -LEVEL -01 -OVERALL PLAN
187 OF 410 008-M-401 BUILDING -008 -LEVEL -01 -DEMOLITION & FLOOR PLANS
188 OF 410 012-M-101 BUILDING -012 -LEVEL -01 -OVERALL PLAN
189 OF 410 012-M-401 BUILDING -012 -LEVEL -01 -DEMOLITION, FLOOR PLANS & RCPS
190 OF 410 013-M-101 BUILDING -013 -LEVEL -01 -OVERALL PLAN
191 OF 410 013-M-401 BUILDING -013 -LEVEL -01 -DEMOLITION, FLOOR PLANS & RCPS
192 OF 410 040-M-101 BUILDING -040 -LEVEL -00 -OVERALL PLAN
193 OF 410 040-M-401 BUILDING -040 -LEVEL -00 -DEMOLITION, FLOOR PLANS & RCPS
194 OF 410 099-MH101 BUILDING -099 -LEVEL -01 -HVAC DUCT PLAN
195 OF 410 099-MH102 BUILDING -099 -LEVEL -01 -HVAC RCP
196 OF 410 099-MH103 BUILDING -099 -ROOF -HVAC PLAN
197 OF 410 099-MP101 BUILDING -099 -LEVEL -01 -HVAC PIPING PLAN
198 OF 410 099-M-301 DATA CENTER -SECTION VIEW
199 OF 410 099-M-302 DATA CENTER -SECTION VIEW
200 OF 410 099-M-303 GENERATOR BUILDING -SECTION VIEW
LIST OF DRAWING SHEETS 00 01 15 - 06
201 OF 410 M-501 MECHANICAL DETAILS I
202 OF 410 M-502 MECHANICAL DETAILS II
203 OF 410 M-601 MECHANICAL SCHEDULES I
204 OF 410 M-602 MECHANICAL SCHEDULES II
205 OF 410 M-603 MECHANICAL SCHEDULES II
206 OF 410 M-701 MECHANICAL CONTROLS I
207 OF 410 M-702 MECHANICAL CONTROLS II
208 OF 410 M-703 MECHANICAL CONTROLS III
209 OF 410 M-704 MECHANICAL CONTROLS IV
210 OF 410 M-705 MECHANICAL CONTROLS V
211 OF 410 M-706 MECHANICAL CONTROLS VI
212 OF 410 M-800 DATA CENTER - PRESSURE MAP PLAN
213 OF 410 EG002 ELECTRICAL LEGENDS
214 OF 410 99EF101 DATA CENTER -FIRE ALARM SYSTEM PLAN
215 OF 410 EF601 FIRE ALARM SYSTEMS RISER DIAGRAM AND MATRICES
216 OF 410 EG001 ABBREVIATIONS, GENERAL NOTES
217 OF 410 EG002 ELECTRICAL LEGENDS
218 OF 410 ES001 ELECTRICAL FACILITY SITE PLAN
219 OF 410 ES002 ENLARGED SITE -ELECTRICAL PLAN -EXISTING
220 OF 410 ES003 ENLARGED SITE -ELECTRICAL PLAN -REVISED
221 OF 410 01EP100 BLDG 01 -LEVEL 00 -ELECTRICAL PLAN
222 OF 410 01EP101 BLDG 01 -LEVEL 01 -ELECTRICAL PLAN
223 OF 410 01EP102 BLDG 01 -LEVEL 02 -ELECTRICAL PLAN
224 OF 410 01EP103 BLDG 01 -LEVEL 03 -ELECTRICAL PLAN
225 OF 410 01EP104 BLDG 01 -LEVEL 04 -ELECTRICAL PLAN
226 OF 410 01EP106 BLDG 01 -LEVEL 06 -ELECTRICAL PLAN
227 OF 410 01EP107 BLDG 01 -LEVEL 07-ELECTRICAL PLAN
228 OF 410 04EP100 BLDG 04 -LEVEL 00 -ELECTRICAL PLAN
229 OF 410 05EP101 BLDG 05 -LEVEL 01 -ELECTRICAL PLAN
230 OF 410 06EP100 BLDG 06 -LEVEL 00 -ELECTRICAL PLAN
231 OF 410 07EP100 BLDG 07 -LEVEL -00 -ELECTRICAL PLAN
232 OF 410 07EP101 BLDG 07 -LEVEL -01 -ELECTRICAL PLAN
233 OF 410 08EP100 BLDG 08 -LEVEL -00 -ELECTRICAL PLAN
234 OF 410 12EP100 BLDG 12 -LEVEL 00 -ELECTRICAL PLAN
235 OF 410 13EP100 BLDG 13 -LEVEL 00 -ELECTRICAL PLAN
236 OF 410 14EP100 BLDG 14 -LEVEL 00 -ELECTRICAL PLAN
237 OF 410 40EP100 BLDG 40 -LEVEL 00 -ELECTRICAL PLAN
238 OF 410 99EL101 DATA CENTER -LIGHTING PLAN
239 OF 410 99EP101 DATA CENTER -POWER PLAN
240 OF 410 99EP102 DATA CENTER -POWER PLAN -MECHANICAL EQUIPMENT
241 OF 410 99EP103 DATA CENTER -POWER PLAN -RECEPTACLE
LIST OF DRAWING SHEETS 00 01 15 - 07
242 OF 410 99EG101 DATA CENTER -GROUNDING PLAN
243 OF 410 99EG102 DATA CENTER -GROUNDING PLAN -LIGHTNING PROTECTION
244 OF 410 99EF101 DATA CENTER -FIRE ALARM SYSTEM PLAN
245 OF 410 99EP201 DATA CENTER -EXTERIOR ELEVATION PLANS
246 OF 410 99EP202 DATA CENTER -EXTERIOR ELEVATION PLANS
247 OF 410 01EP400a BLDG 01 -LEVEL -00 -ENLARGED ELECTRICAL PLANS 248 OF 410 01EP400b BLDG 01 -LEVEL -00 -ENLARGED ELECTRICAL PLANS 249 OF 410 01EP400c BLDG 01 -LEVEL -00 -ENLARGED ELECTRICAL PLANS 250 OF 410 01EP400d BLDG 01 -LEVEL -00 -ENLARGED ELECTRICAL PLANS 251 OF 410 01EP400e BLDG 01 -LEVEL -00 -ENLARGED ELECTRICAL PLANS 252 OF 410 01EP401a BLDG 01 -LEVEL -01 -ENLARGED ELECTRICAL PLANS 253 OF 410 01EP401b BLDG 01 -LEVEL -01 -ENLARGED ELECTRICAL PLANS 254 OF 410 01EP402a BLDG 01 -LEVEL -02 -ENLARGED ELECTRICAL PLANS 255 OF 410 01EP402b BLDG 01 -LEVEL -02 -ENLARGED ELECTRICAL PLANS 256 OF 410 01EP403a BLDG 01 -LEVEL -03 -ENLARGED ELECTRICAL PLANS 257 OF 410 01EP403b BLDG 01 -LEVEL -03 -ENLARGED ELECTRICAL PLANS 258 OF 410 01EP404a BLDG 01 -LEVEL -04 -ENLARGED ELECTRICAL PLANS 259 OF 410 01EP404b BLDG 01 -LEVEL -04 -ENLARGED ELECTRICAL PLANS
260 OF 410 01EP405 BLDG 01 -LEVEL -05 -ENLARGED ELECTRICAL PLANS
261 OF 410 04EP400a BLDG 04 -LEVEL 00 -ENLARGED ELECTRICAL PLANS 262 OF 410 04EP400b BLDG 04 -LEVEL 00 -ENLARGED ELECTRICAL PLANS 263 OF 410 04EP400c BLDG 04 -LEVEL 00 -ENLARGED ELECTRICAL PLANS
264 OF 410 04EP401 BLDG 04 -LEVEL 01 -ENLARGED ELECTRICAL PLANS
265 OF 410 05EP401 BLDG 05 -LEVEL 01 -ENLARGED ELECTRICAL PLANS
266 OF 410 06EP401 BLDG 06 -LEVEL 01 -ENLARGED ELECTRICAL PLANS
267 OF 410 07EP401 BLDG 07 -LEVEL 01 -ENLARGED ELECTRICAL PLANS
268 OF 410 08EP401 BLDG 08 -LEVEL -01 -ENLARGED ELECTRICAL PLANS
269 OF 410 12EP400 BLDG 12 -LEVEL 00 -ENLARGED ELECTRICAL PLANS
270 OF 410 13EP400 BLDG 13 -LEVEL 00 -ENLARGED ELECTRICAL PLANS
271 OF 410 14EP401 BLDG 14 -LVL 01 -ENLARGED ELECTRICAL PLAN
272 OF 410 40EP400 BLDG 40 -LEVEL 00 -ENLARGED ELECTRICAL PLANS
273 OF 410 EP501 ELECTRICAL DETAILS
274 OF 410 EP502 ELECTRICAL DETAILS
275 OF 410 EP503 ELECTRICAL DETAILS
276 OF 410 EP504 ELECTRICAL DETAILS
277 OF 410 EP505 ELECTRICAL DETAILS
278 OF 410 EP506 ELECTRICAL DETAILS
279 OF 410 EP507 ELECTRICAL DETAILS
280 OF 410 EP508 ELECTRICAL DETAILS
281 OF 410 EP509 ELECTRICAL DETAILS
282 OF 410 EP510 ELECTRICAL DETAILS
LIST OF DRAWING SHEETS 00 01 15 - 08
283 OF 410 EP511 ELECTRICAL DETAILS
284 OF 410 EP512 ELECTRICAL DETAILS
285 OF 410 EF601 FIRE ALARM SYSTEMS RISER DIAGRAM AND MATRICES
286 OF 410 EG601 TELECOMMUNICATIONS BONDING RISER DIAGRAM
287 OF 410 00EP601 MEDIUM VOLTAGE -ONE-LINE DIAGRAM -EXISTING
288 OF 410 00EP611 MEDIUM VOLTAGE -ONE-LINE DIAGRAM -REVISED
289 OF 410 01EP601 BLDG 01 -ONE-LINE DIAGRAM -PART 1 OF 2 -EXISTING
290 OF 410 01EP602 BLDG 01 -ONE-LINE DIAGRAM -PART 2 OF 2 -EXISTING
291 OF 410 01EP611 BLDG 01 -ONE-LINE DIAGRAM -PART 1 OF 2 -REVISED
292 OF 410 01EP612 BLDG 01 -ONE-LINE DIAGRAM -PART 2 OF 2 -REVISED
293 OF 410 04EP601 BLDG 04 -ONE-LINE DIAGRAM -EXISTING
294 OF 410 04EP611 BLDG 04 -ONE-LINE DIAGRAM -REVISED
295 OF 410 05EP601 BLDG 05 -ONE-LINE DIAGRAM
296 OF 410 06EP601 BLDG 06 -ONE-LINE DIAGRAMS
297 OF 410 07EP601 BLDG 07 -ONE-LINE DIAGRAMS
298 OF 410 08EP601 BLDG 08 -ONE-LINE DIAGRAM
299 OF 410 12EP601 BLDG 12 -ONE-LINE DIAGRAMS
300 OF 410 13EP601 BLDG 13 -ONE-LINE DIAGRAM -EXISTING
301 OF 410 13EP611 BLDG 13 -ONE-LINE DIAGRAM -REVISED
302 OF 410 14EP601 BLDG 14 -ONE-LINE DIAGRAMS
303 OF 410 40EP601 BLDG 40 -ONE-LINE DIAGRAMS
304 OF 410 99EP601 DATA CENTER -ONE-LINE DIAGRAM
305 OF 410 EP701 ELECTRICAL SCHEDULES
306 OF 410 01EP701 ELECTRICAL SCHEDULES
307 OF 410 01EP702 ELECTRICAL SCHEDULES
308 OF 410 01EP703 ELECTRICAL SCHEDULES
309 OF 410 01EP704 ELECTRICAL SCHEDULES
310 OF 410 01EP705 ELECTRICAL SCHEDULES
311 OF 410 01EP706 ELECTRICAL SCHEDULES
312 OF 410 04EP701 ELECTRICAL SCHEDULES
313 OF 410 05EP701 ELECTRICAL SCHEDULES
314 OF 410 06EP701 ELECTRICAL SCHEDULES
315 OF 410 07EP701 ELECTRICAL SCHEDULES
316 OF 410 08EP701 ELECTRICAL SCHEDULES
317 OF 410 12EP701 ELECTRICAL SCHEDULES
318 OF 410 13EP701 ELECTRICAL SCHEDULES
319 OF 410 14EP701 ELECTRICAL SCHEDULES
320 OF 410 40EP701 ELECTRICAL SCHEDULES
321 OF 410 99EP701 ELECTRICAL SCHEDULES
322 OF 410 99EP702 ELECTRICAL SCHEDULES
323 OF 410 TNG001 ABBREVIATIONS, AND SHEET INDEX
LIST OF DRAWING SHEETS 00 01 15 - 09
324 OF 410 TNG002 GENERAL NOTES
325 OF 410 TNG003 TELECOMMUNICATIONS LEGEND
326 OF 410 01TN1000 BLDG 01 -LEVEL 000 -TELECOMMUNICATIONS PLAN
327 OF 410 01TN100 BLDG 01 -LEVEL 00 -TELECOMMUNICATIONS PLAN
328 OF 410 01TN101 BLDG 01 -LEVEL 01 -TELECOMMUNICATIONS PLAN
329 OF 410 01TN102 BLDG 01 -LEVEL 02 -TELECOMMUNICATIONS PLAN
330 OF 410 01TN103 BLDG 01 -LEVEL 03 -TELECOMMUNICATIONS PLAN
331 OF 410 01TN104 BLDG 01 -LEVEL 04 -TELECOMMUNICATIONS PLAN
332 OF 410 01TN105 BLDG 01 -LEVEL 05 -TELECOMMUNICATIONS PLAN
333 OF 410 01TN106 BLDG 01 -LEVEL 06 -TELECOMMUNICATIONS PLAN
334 OF 410 04TN100 BLDG 04 -LEVEL 00 -TELECOMMUNICATIONS PLAN
335 OF 410 04TN101 BLDG 04 -LEVEL 01 -TELECOMMUNICATIONS PLAN
336 OF 410 05TN101 BLDG 05 -LEVEL 01 -TELECOMMUNICATIONS PLAN
337 OF 410 06TN100 BLDG 06 -LEVEL 00 -TELECOMMUNICATIONS PLAN
338 OF 410 06TN101 BLDG 06 -LEVEL 01 -TELECOMMUNICATIONS PLAN
339 OF 410 06TN102 BLDG 06 -LEVEL 02 -TELECOMMUNICATIONS PLAN
340 OF 410 07TN100 BLDG 07 -LEVEL -00 -TELECOMMUNICATIONS PLAN
341 OF 410 07TN101 BLDG 07 -LEVEL -01 -TELECOMMUNICATIONS PLANS
342 OF 410 07TN102 BLDG 07 -LEVEL -02 -TELECOMMUNICATIONS PLAN
343 OF 410 08TN100 BLDG 08 -LEVEL -00 -TELECOMMUNICATIONS PLAN
344 OF 410 08TN101 BLDG 08 -LEVEL -01 -TELECOMMUNICATIONS PLAN
345 OF 410 08TN102 BLDG 08 -LEVEL -02 -TELECOMMUNICATIONS PLAN
346 OF 410 12TN100 BLDG 12 -LEVEL 00 -TELECOMMUNICATIONS PLAN
347 OF 410 13TN100 BLDG 13 -LEVEL 00 -TELECOMMUNICATIONS PLAN
348 OF 410 14TN100 BLDG 14 -LEVEL 00 -TELECOMMUNICATIONS PLAN
349 OF 410 14TN101 BLDG 14 -LEVEL 01 -TELECOMMUNICATIONS PLAN
350 OF 410 40TN100 BLDG 40 -LEVEL 00 -TELECOMMUNICATIONS PLAN
351 OF 410 99TN101 DATA CENTER -TELECOMMUNICATIONS PLAN
352 OF 410 99TN102 DATA CENTER -HORIZONTAL DISTRIBUTION OVERHEAD PLAN
353 OF 410 99TN103 DATA CENTER -FIBER BACKBONE OVERHEAD PLAN
354 OF 410 01TN400a BLDG 01 -LEVEL 00 -ENLARGED TELECOMMUNICATIONS PLANS 355 OF 410 01TN400b BLDG 01 -LEVEL 00 -ENLARGED TELECOMMUNICATIONS PLANS 356 OF 410 01TN400c BLDG 01 -LEVEL 00 -ENLARGED TELECOMMUNICATIONS PLANS 357 OF 410 01TN400d BLDG 01 -LEVEL 00 -ENLARGED TELECOMMUNICATIONS PLANS 358 OF 410 01TN400e BLDG 01 -LEVEL 00 -ENLARGED TELECOMMUNICATIONS PLANS 359 OF 410 01TN401a BLDG 01 -LEVEL 01 -ENLARGED TELECOMMUNICATIONS PLANS 360 OF 410 01TN401b BLDG 01 -LEVEL 01 -ENLARGED TELECOMMUNICATIONS PLANS 361 OF 410 01TN401c BLDG 01 -LEVEL 01 -ENLARGED TELECOMMUNICATIONS PLANS 362 OF 410 01TN401d BLDG 01 -LEVEL 01 -ENLARGED TELECOMMUNICATIONS PLANS 363 OF 410 01TN401e BLDG 01 -LEVEL 01 -ENLARGED TELECOMMUNICATIONS PLANS 364 OF 410 01TN401f BLDG 01 -LEVEL 01 -ENLARGED TELECOMMUNICATIONS PLANS
LIST OF DRAWING SHEETS 00 01 15 - 10
365 OF 410 01TN402a BLDG 01 -LEVEL 02 -ENLARGED TELECOMMUNICATIONS PLANS 366 OF 410 01TN402b BLDG 01 -LEVEL 02 -ENLARGED TELECOMMUNICATIONS PLANS 367 OF 410 01TN402c BLDG 01 -LEVEL 02 -ENLARGED TELECOMMUNICATIONS PLANS 368 OF 410 01TN402d BLDG 01 -LEVEL 02 -ENLARGED TELECOMMUNICATIONS PLANS 369 OF 410 01TN402e BLDG 01 -LEVEL 02 -ENLARGED TELECOMMUNICATIONS PLANS 370 OF 410 01TN402f BLDG 01 -LEVEL 02 -ENLARGED TELECOMMUNICATIONS PLANS 371 OF 410 01TN403a BLDG 01 -LEVEL 03 -ENLARGED TELECOMMUNICATIONS PLANS 372 OF 410 01TN403b BLDG 01 -LEVEL 03 -ENLARGED TELECOMMUNICATIONS PLANS 373 OF 410 01TN403c BLDG 01 -LEVEL 03 -ENLARGED TELECOMMUNICATIONS PLANS 374 OF 410 01TN403d BLDG 01 -LEVEL 03 -ENLARGED TELECOMMUNICATIONS PLANS 375 OF 410 01TN403e BLDG 01 -LEVEL 03 -ENLARGED TELECOMMUNICATIONS PLANS 376 OF 410 01TN404a BLDG 01 -LEVEL 04 -ENLARGED TELECOMMUNICATIONS PLANS 377 OF 410 01TN404b BLDG 01 -LEVEL 04 -ENLARGED TELECOMMUNICATIONS PLANS 378 OF 410 01TN404c BLDG 01 -LEVEL 04 -ENLARGED TELECOMMUNICATIONS PLANS 379 OF 410 01TN404d BLDG 01 -LEVEL 04 -ENLARGED TELECOMMUNICATIONS PLANS 380 OF 410 01TN404e BLDG 01 -LEVEL 04 -ENLARGED TELECOMMUNICATIONS PLANS 381 OF 410 01TN405a BLDG 01 -LEVEL 05 -ENLARGED TELECOMMUNICATIONS PLANS 382 OF 410 01TN405b BLDG 01 -LEVEL 05 -ENLARGED TELECOMMUNICATIONS PLANS 383 OF 410 04TN400a BLDG 04 -LEVEL 00 -ENLARGED TELECOMMUNICATIONS PLANS 384 OF 410 04TN400b BLDG 04 -LEVEL 00 -ENLARGED TELECOMMUNICATIONS PLANS 385 OF 410 04TN400c BLDG 04 -LEVEL 00 -ENLARGED TELECOMMUNICATIONS PLANS 386 OF 410 04TN401a BLDG 04 -LEVEL 01 -ENLARGED TELECOMMUNICATIONS PLANS 387 OF 410 04TN401b BLDG 04 -LEVEL 01 -ENLARGED TELECOMMUNICATIONS PLANS
388 OF 410 05TN401 BLDG 05 -LEVEL 01 -ENLARGED TELECOMMUNICATIONS PLANS
389 OF 410 06TN401 BLDG 06 -LEVEL 01 -ENLARGED TELECOMMUNICATIONS PLANS
390 OF 410 07TN401a BLDG 07 -LEVEL -01 -ENLARGED TELECOMMUNICATIONS PLANS 391 OF 410 07TN401b BLDG 07 -LEVEL -01 -ENLARGED TELECOMMUNICATIONS PLANS 392 OF 410 08TN401a BLDG 08 -LEVEL -01 -ENLARGED TELECOMMUNICATIONS PLANS 393 OF 410 08TN401b BLDG 08 -LEVEL -01 -ENLARGED TELECOMMUNICATIONS PLANS
394 OF 410 08TN402 BLDG 08 -LEVEL -02 -ENLARGED TELECOMMUNICATIONS PLANS
395 OF 410 12TN400 BLDG 12 -LEVEL 00 -ENLARGED TELECOMMUNICATIONS PLANS
396 OF 410 13TN400a BLDG 13 -LEVEL 0 -ENLARGED TELECOMMUNICATIONS PLANS 397 OF 410 13TN400b BLDG 13 -LEVEL 00 -ENLARGED TELECOMMUNICATIONS PLANS 398 OF 410 14TN401a BLDG 14 -LEVEL 01 -ENLARGED TELECOMMUNICATIONS PLANS 399 OF 410 14TN401b BLDG 14 -LEVEL 01 -ENLARGED TELECOMMUNICATIONS PLANS 400 OF 410 40TN400a BLDG 40 -LEVEL 00 -ENLARGED TELECOMMUNICATIONS PLANS 401 OF 410 40TN400b BLDG 40 -LEVEL 00 -ENLARGED TELECOMMUNICATIONS PLANS
402 OF 410 TN501 TELECOMMUNICATIONS DETAILS
403 OF 410 TN502 TELECOMMUNICATIONS DETAILS
404 OF 410 TN503 TELECOMMUNICATIONS DETAILS
405 OF 410 TN504 TELECOMMUNICATIONS DETAILS
LIST OF DRAWING SHEETS 00 01 15 - 11
406 OF 410 TN505 TELECOMMUNICATIONS DETAILS
407 OF 410 TN506 TELECOMMUNICATIONS DETAILS
408 OF 410 TN601 SITE FIBER RISER DIAGRAM -CORE A
409 OF 410 TN602 SITE FIBER RISER DIAGRAM -CORE B
410 OF 410 TN701 TELECOMMUNICATIONS SCHEDULE
EHRM INFRASTRUCTURE UPGRADES PROJECT#: 619-21-106
MONTGOMERY VA MEDICAL CENTER – MONTGOMERY, AL PUB. DATE: 2021-11
GENERAL REQUIREMENTS 01 00 00 -1
SECTION 01 00 00
GENERAL REQUIREMENTS
GENERAL
1.1 SAFETY REQUIREMENTS
A. Refer to section 01 35 26, SAFETY REQUIREMENTS for safety and infection control requirements.
1.2 GENERAL INTENTION
A. Contractor shall completely prepare site for building operations, including demolition and removal of existing structures, and furnish labor and materials and perform work for EHRM INFRASTRUCTURE UPGRADES as required by drawings and specifications.
Project scope includes but is not limited to the following infrastructure upgrades:
Electrical (electrical panel upgrade, power [normal, emergency]); Bonding; UPS; Building
Management System interfaces; new and upgrades to existing HVAC; reconfiguration, expansion, and renovation of existing space (demo, new construction, finishes);
replacement of the existing Data Center with a new construction of a general small Data
Center; communication infrastructure (new data outlets, patch panels, upgrades to Cat
6A cable) in buildings as necessary; physical security upgrades; upgrade to fiber infrastructure backbone campus-wide within buildings and between buildings; site civil work / investigation as required; and hazardous material abatement. Project scope includes Buildings 1, 4, 5, 6, 7, 8, 12, 13, 14, 40, and campus site.
B. Visits to the site by Bidders may be made only by appointment with the VA Medical
Center Contracting Officer’s Representative (COR).
C. Offices of Spees Design Build, as Architect-Engineers, will render certain technical services during construction. Such services shall be considered as advisory to the
Government and shall not be construed as expressing or implying a contractual act of the Government without affirmations by Contracting Officer or his duly authorized representative.
GENERAL REQUIREMENTS 01 00 00 -2
D. All employees of general contractor and subcontractors shall comply with VA security management program and obtain permission of the VA police, be identified by project and employer, and restricted from unauthorized access.
1.3 STATEMENT OF BID ITEM(S)
A. ITEM I, EHRM INFRASTRUCTURE UPGRADES: Work includes all general, safety, and management requirements depicted in the contract documents.
B. ITEM II, GENERAL CONSTRUCTION: Work includes general construction, alterations, and selective demolition depicted in the contract documents.
C. ITEM III, ELECTRICAL WORK: Work includes all labor, materials, equipment, and supervision to perform the required electrical construction work on this project as depicted in the contract documents.
D. ITEM IV, MECHANICAL WORK: Work includes all labor, material, equipment, and supervision to perform the required mechanical construction work on this project depicted in the contract documents.
E. ITEM V, TELECOMMUNICATIONS WORK: Work includes all labor, material, equipment, and supervision to perform the required telecommunications construction work on this project depicted in the contract documents.
F. ITEM VI, STRUCTURAL WORK: Work includes all labor, material, equipment, and supervision to perform the required structural construction work on this project depicted in the contract documents.
G. ITEM VII, SITE AND CIVIL WORK: Work includes all labor, material, equipment, and supervision to perform the required site and civil construction work on this project depicted in the contract documents.
H. ITEM VIII, ENVIRONMENTAL WORK: Work includes all labor, material, equipment, and supervision to perform the required environmental remediation work on this project depicted in the contract documents.
1.4 SPECIFICATIONS AND DRAWINGS FOR CONTRACTOR
A. Drawings and contract documents may be obtained from the website where the solicitation is posted. Additional copies will be at Contractor's expense.
GENERAL REQUIREMENTS 01 00 00 -3
1.5 CONSTRUCTION SECURITY REQUIREMENTS
A. Security Plan:
1. Physical security of the construction site and installations will meet requirements depicted in the next paragraph “Security Procedures,” the VA Design Manual
“Physical Security Design Manual for VA Life-Safety Protected Facilities,” and any other applicable VA documentation.
2. The Contractor is responsible for determining the security plan that will define both physical and administrative security procedures. Once approved by the VA, these procedures will remain effective for the entire duration of the project.
3. The General Contractor is responsible for assuring that all subcontractors working on the project and their employees also comply with these regulations.
B. Security Procedures:
1. General Contractor’s employees shall not enter the project site without appropriate badge. They may also be subject to inspection of their personal effects when entering or leaving the project site.
2. Before starting work the General Contractor shall give one week’s notice to the
Contracting Officer so that security escort and/or arrangements can be provided for the employees. This notice is separate from any notices required for utility shutdown described later in this section.
3. No photography of VA premises is allowed without written permission of the
Contracting Officer. Patients and staff are not to be photographed at any time.
4. VA reserves the right to close or shut down the project site and order General
Contractor’s employees off the premises in the event of a national emergency. The
General Contractor may return to the site only with the written approval of the
Contracting Officer.
C. Key Control
1. The General Contractor shall provide duplicate keys and lock combinations to the
Contracting officers representative (COR) for the purpose of security inspections of
GENERAL REQUIREMENTS 01 00 00 -4
every area of project including tool boxes and parked machines and take any emergency action.
2. The General Contractor shall install all permanent cores at completion of the work.
See Section 08 71 00 DOOR HARDWARE and coordinate with the VA COR.
D. Document Control
1. Before starting any work, the General Contractor/Sub Contractors shall submit an electronic security memorandum describing the approach to following goals and maintaining confidentiality of “sensitive information”.
2. The General Contractor is responsible for safekeeping of all drawings, project manual and other project information. This information shall be shared only with those with a specific need to accomplish the project.
3. Certain documents, sketches, videos or photographs and drawings may be marked
“Law Enforcement Sensitive” or “Sensitive Unclassified”. Secure such information in separate containers and limit the access to only those who will need it for the project.
Return the information to the Contracting Officer upon request.
4. These security documents shall not be removed or transmitted from the project site without the written approval of Contracting Officer.
5. All paper waste or electronic media such as CD’s and diskettes shall be shredded and destroyed in a manner acceptable to the VA.
6. Notify Contracting Officer and Site Security Officer immediately when there is a loss or compromise of “sensitive information”.
7. All electronic information shall be stored in specified location following VA standards and procedures using an Engineering Document Management Software (EDMS).
a) Security, access and maintenance of all project drawings, both scanned and electronic shall be performed and tracked through the EDMS system.
b) “Sensitive information” including drawings and other documents may be attached to e-mail provided all VA encryption procedures are followed.
E. Motor Vehicle Restrictions
GENERAL REQUIREMENTS 01 00 00 -5
1. Vehicle authorization request shall be required for any vehicle entering the site and such request shall be submitted 24 hours before the date and time of access. Access shall be restricted to picking up and dropping off materials and supplies.
2. A limited number of permits shall be issued for General Contractor and its employees for parking in designated areas only. Contractor to coordinate with VA
Medical Center Facility Manager.
1.6 OPERATIONS AND STORAGE AREAS (FAR 52.236-10)
A. The Contractor shall confine all operations (including storage of materials) on
Government premises to areas authorized or approved by the Contracting Officer. The
Contractor shall hold and save the Government, its officers and agents, free and harmless from liability of any nature occasioned by the Contractor's performance.
B. Limited amounts of well-organized and unobtrusive materials and tools may be kept in the construction area during construction. The VA Medical Center COR may request items be relocated at any points.
C. Temporary buildings (e.g., storage sheds, shops, offices) and utilities may be erected by the Contractor only with the approval of the Contracting Officer and shall be built with labor and materials furnished by the Contractor without expense to the Government.
The temporary buildings and utilities shall remain the property of the Contractor and shall be removed by the Contractor at its expense upon completion of the work. With the written consent of the Contracting Officer, the buildings and utilities may be abandoned and need not be removed. Possible locations and requirements will be discussed and determined by the COR during the post-bid, pre-construction meeting.
D. The Contractor shall, under regulations prescribed by the Contracting Officer, use only established roadways as authorized by the Contracting Officer. When materials are transported in prosecuting the work, vehicles shall not be loaded beyond the loading capacity recommended by the manufacturer of the vehicle or prescribed by any Federal, State, or local law or regulation. When it is necessary to cross curbs or sidewalks, the
Contractor shall protect them fromdamage. The Contractor shall repair or pay for the repair of any damaged curbs, sidewalks, or roads.
GENERAL REQUIREMENTS 01 00 00 -6
E. Working space and space available for storing materials shall be as determined by the
COR.
F. Workers are subject to the rules of the VA Medical Center that are applicable to their conduct.
G. Execute work in such a manner as to interfere as little as possible with work being done by others. Keep roads clear of construction materials, debris, standing construction equipment and vehicles at all times.
H. Execute work so as to interfere as little as possible with normal functioning of the VA
Medical Center as a whole, including operations of utility services, fire protection systems and any existing equipment, and with work being done by others. Use of equipment and tools that transmit vibrations and noises through the building structure, are not permitted in buildings that are occupied, during construction, jointly by patients or medical personnel, and Contractor's personnel, except as permitted by COR where required by limited working space.
1. Do not store materials and equipment in other than assigned areas.
2. Schedule delivery of materials and equipment to immediate construction working or storage areas within buildings in use by Department of Veterans Affairs in quantities sufficient for not more than two workdays. Provide unobstructed access to Medical
Center areas required to remain in operation.
3. Where access by Medical Center personnel to vacated portions of buildings is not required, storage of Contractor's materials and equipment will be permitted subject to fire and safety requirements.
I. Utilities Services: Where necessary to cut existing pipes, electrical wires, conduits, cables, etc., of utility services, or of fire protection systems or communications systems
(except telephone), they shall be cut and capped at suitable places where shown; or, in absence of such indication, where directed by COR. All such actions shall be coordinated with the COR or Utility Company involved:
1. Whenever it is required that a connection fee be paid to a public utility provider for new permanent service to the construction project, for such items as water, sewer, GENERAL REQUIREMENTS 01 00 00 -7 electricity, gas or steam, payment of such fee shall be the responsibility of the
Government and not the Contractor.
J. Phasing:
1. The Medical Center must maintain its operation 24 hours a day 7 days a week.
Therefore, any interruption in service must be scheduled and coordinated with the
COR to ensure that no lapses in operation occur. It is the CONTRACTOR'S responsibility to develop a work plan and schedule detailing, at a minimum, the procedures to be employed, the equipment and materials to be used, the interim life safety measure to be used during the work, and a schedule defining the duration of the work with milestone subtasks.
a. Normal working hours for this contract will be from 8:00 AM – 4:30 PM (local time), Monday through Friday except for weekends and established Federal
Holidays.
b. Performing on-site work outside normal working hours will require approval from the Contracting Officer (CO) and the Contracting Officer’s Representative (COR).
Requests shall be submitted via email at least 72 hours prior to the requested date and at no additional cost to the Government. Approvals are subject to the availability of on-site staff.
2. To ensure such executions, Contractor shall furnish the COR with a schedule of approximate phasing dates on which the Contractor intends to accomplish work in each specific area of site, building or portion thereof. In addition, Contractor shall notify the COR 21 calendar days in advance of the proposed date of starting work in
ICRA Class I and II work areas, and 28 calendar days in advance of ICRA Class III and
IV work areas, as well as critical infrastructure buildings (i.e. Boiler Plant, Chiller
Plant, etc.). Arrange such phasing dates to ensure accomplishment of this work in successive phases mutually agreeable to the VA Medical Center Director, COR and
Contractor.
3. A/E recommended phasing plans, put together with input from the VA COR and
Epidemiologist, takes into consideration the complexity of the Medical Center
GENERAL REQUIREMENTS 01 00 00 -8
complexity and broad scope of buildings impacted by TR/TE renovations and recabling efforts. Phasing of TR/TE renovations and individual room Cat 6A recabling will be heavily influenced by the ICRA precautions required by the VA, informed by the associated patient risk levels. Critical patient care areas should be considered distinct from non-patient care areas (engineering, admin space, etc.), and the contractor shall regularly consult with the VA on patient care area phasing plans before commencing construction work and upon completion.
4. The following tables outline healthcare and non-healthcare spaces, and recommended phasing constraints:
Non-Healthcare Buildings
Location ICRA Class Construction Hours –
TR/TEs
Construction Hours – Cat 6a Re-cabling
Building 4 II/III Normal business hours Nights / Weekends
Building 5 II/III Normal business hours Nights / Weekends
Building 6 II/III Normal business hours Nights / Weekends
Building 7 II/III Normal business hours Nights / Weekends
Building 8 II/III Normal business hours Nights / Weekends
Building 12 II/III Normal business hours Nights / Weekends
Building 13 II/III Normal business hours Nights / Weekends
Building 14 II/III Normal business hours Nights / Weekends
HEALTHCARE BUILDINGS
Location ICRA Class Construction Hours – TR/TEs Construction Hours – Cat 6a
Re-cabling
GENERAL REQUIREMENTS 01 00 00 -9
II
*Normal business hours, pending VA approval of
Contractor work plan submitted at least 28 calendar days in advance of start of work.
*Class II - Contractor shall present work plan to the VA
COR 21 calendar days in advance of work for VA pre-approval, showing max rooms that may be re-cabled in a phasing area during 1 work shift
III
*Normal business hours, pending VA approval of
Contractor work plan submitted at least 28 calendar days in advance of start of work.
*Contractor shall present work plan at least 28 calendar days in advance of work for VA pre-approval; (3) rooms maximum may be worked on at one time to allow for equipment movement and coordination with VA staff and services. Any variations in room maximum will be on a case-by-case basis and must be approved by the
VA COR in advance of construction activities.
K. Buildings 1, IV
*Normal business hours, pending VA approval of
Contractor work plan submitted at least 28 calendar days in advance of start of work.
*Contractor shall present work plan at least 28 calendar days in advance of work for VA pre-approval; (1) room maximum may be worked on at one time to allow for equipment
GENERAL REQUIREMENTS 01 00 00 -10
movement and coordination with VA staff and services. Any variations in room maximum will be on a case-by-case basis and must be approved by the
VA COR in advance of construction activities.
5. Contractor shall provide work plans to VA for final approval. Contractor shall consider the following constraints in phasing:
a. Contractor shall not commence any planned phase of work without authorization from the COR and an approved outage schedule. It is the Contractor’s responsibility to review any appropriate VA phasing forms with VA COR during
Preconstruction Meeting. All subsequent planned outages will need to be documented and approved by the COR prior to regulated outages.
b. The Government may halt work in patient care areas at no cost if work impedes patient care.
c. The contractor will coordinate with the VA for movement of furniture from new
TR spaces prior to work starting.
d. Any TR work that causes excessive noise and/or vibrations shall be coordinated with the VA COR and shall occur only during nights and/or weekends as approved by VA COR.
e. Contractor is responsible for ensuring continuous network connectivity for patient care spaces. Outages shall not exceed 1 work shift. Cable pulling shall only occur during non-working, non-peak hours, and scheduled weekends as approved by the
VA COR, or as noted otherwise in the above tables.
f. Contractor is responsible for providing a work plan to the VA for approval regarding separation of existing cables and new, and all anticipated demo work.
GENERAL REQUIREMENTS 01 00 00 -11
g. Contractor to ensure all work in current phase is complete and approved by VA before proceeding to next phase.
6. Taking the above into consideration, the A/E recommends the following phased sequence of construction activities:
_______PROPOSED PHASING SEQUENCE
Phase 1 Overview – Campus Infrastructure
*Same-numbered…
This is the start of the file's text. The full file is on GovTribe.
File details come from the government source that posted it. Updated .