S02A - RFQ 3677626Q0240 - FPLS Report Template - Attachment A3.pdf

PDF 165 KB Posted

Attached to
R425--VHA Fire Protection and Life Safety Services BPA
Solicitation number
36C77626Q0240
Issued by

About this file

This is a Fire Protection and Life Safety Project Design Review Report from the U.S. Department of Veterans Affairs for the VA Anytown Healthcare System.

The report documents a Schematic Design (SD) level review at 35% completion for the "Renovate Primary Care" project (VA Project Number 101-26-101). The review was conducted by ZYX Fire Protection Design on January 15, 2026, following a submittal date of January 10, 2026. The review identified one mandatory requirement regarding fire barrier ratings for newly constructed perimeter walls. Drawing A-301 was flagged because the submitted drawings did not indicate partition types or fire barrier ratings. The mandatory requirement specified that newly constructed perimeter walls for the two departments (Eye Clinic and Primary Care) must be rated as 1-hour minimum fire barriers in accordance with NFPA 101-2024, Section 8.3.1.1, which is applicable to suite construction. The design team's resolution confirmed that perimeter partitions surrounding the two main areas will be constructed to one-hour rating as required. The report includes certification sections for both the Life Safety Agent and the VA Project Manager to sign upon final resolution and acceptance of all review comments, indicating compliance with VA's adopted codes, standards, and applicable fire protection and life safety policies under the BPA task order framework.

View the file

Other files

Show all 17

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

U.S. DEPARTMENT OF VETERANS AFFAIRS

FIRE PROTECTION AND LIFE SAFETY PROJECT DESIGN REVIEW REPORT

Review by:

Firm:

First MI. Last, P.E.

ZYX Fire Protection Design Phone: (123) 456-7890

Ext 1234 Date: Jan 15, 2026 VA Project Manager: First MI. Last, Credential

Facility: VA Anytown HCS Project Title: Renovate Primary Care Submittal: Schematic Design (SD) / 35%

VA Project Number:

Submittal Date:

101-26-101 Jan 10, 2026

ITEM

NO.:

DRAWING NO. /

SPEC SECTION /

DOC TITLE

COMMENTS

(*Indicates Advisory Comments)

(** Indicates Mandatory Requirements)

REFERENCE

CODE OR STD

(* With Year of Ed.)

RESOLUTION

(Provided by VA or A/E)

1. A-301 ** The drawings provided do not indicate partition types (fire barrier ratings). Ensure that newly constructed perimeter walls for the two departments are 1-hour rated (minimum).

NFPA 101-2024,

8.3.1.1

Perimeter partitions surrounding the two main areas (Eye Clinic and Primary Care) will be one-hour rated as required for suite construction.

2.

3.

4.

5.

6.

7.

8.

9.

10.

11.

12.

13.

14.

15.

16.

17.

18.

19.

20.

U.S. DEPARTMENT OF VETERANS AFFAIRS

FIRE PROTECTION AND LIFE SAFETY PROJECT DESIGN REVIEW REPORT

Review Certifications (Upon final resolution and acceptance of all review comments, print this report to PDF, sign and add to the project record)

Life Safety Agent Certification: I have completed the third-party fire protection and life safety review for the subject project and submittal phase in accordance with the VA’s requirements. I certify that I have reviewed the comment resolutions and determined they appear to meet VA’s adopted codes and standards for fire protection and life safety, as well as comply with applicable VA fire protection and life safety policies.

First MI. Last, PE ZYX Fire Protection Design

Date: Mon XX, YEAR

VA Project Manager Certification: I certify that I have reviewed the Life Safety Agent’s work and determined it meets the requirements of the subject project, VA fire protection and life safety policies and the BPA task order.

First MI. Last, Credential VA Anytown HCS

Date: Mon XX, YEAR

File details come from the government source that posted it. Updated .