This document is a comprehensive product specification and submittal package for a Liebert eXM Uninterruptible Power Supply (UPS) system with associated equipment and services for VA Medical EHRM Infrastructure Upgrades.

The project involves procurement of two (2) Liebert eXM 150 kVA/150 kW UPS units (Model 51SA150HAA00SCV) configured for 480VAC input and 208/120VAC output through step-down transformation. Key system components include: two external battery cabinets with East Penn HR5000 batteries (36 jars each, 4,620 lbs. each); a maintenance bypass cabinet with three-breaker configuration; an 880mm distribution cabinet with 600A, 84-position panelboard and six 60A and 70A breakers; and a spill containment system (EnviroGuard HAWK 44"x168" with 60 mil liner). The UPS operates with transformer-free architecture, 65kAIC rating, unity power factor support, and energy optimization mode. Battery backup provides 22 minutes at full load (beginning of life) and 16 minutes (end of life at 125% load). The system includes Intellislot Unity Card communications (SNMP, HTTP, BACnet, Modbus), a Liebert IntelliSlot Relay Card for remote alarm monitoring, and optional remote status panel (Pythia CS0-RSP-UPS).

Startup services include 24x7 availability with 2-3 week advance notice to Vertiv (816-246-2065). Factory burn-in testing (8 hours with data logging every 30 minutes), one day of site acceptance testing with load bank, and four hours of on-site customer training are included as standard startup services. The equipment is Buy American Act compliant with FOB Destination terms. Documentation provided includes detailed electrical schematics, wiring diagrams, equipment outline drawings with center of gravity specifications, technical specifications, control wiring diagrams, maintenance bypass cabinet circuit breaker schedules, and efficiency curves. The project specifies specs sections 26 33 53 and 26 26 00, with Ace Electric as the designated purchaser and Data Center Systems, Inc. as the submittal provider (DCSI Job #401599, dated December 22, 2022).

View the file

Other files

File Type Posted
S06 - Amend 0007 - Att 01 - Abstract of Bids - 07152026 - MCR Update - MN.pdf PDF
S06 - Amend 0007 - 36C77626B0017 - 07152026 - MCR Update - MN.pdf PDF
S06 - Amend 0006 - 36C77626B0017 - 07012026 - MCR Update - MN.pdf PDF
S06 - Amend 0006 - Att 04 - Statement of Changes - Add 01 - MCR Update - Minneapolis.pdf PDF
S06 - Amend 0006 - RFIs - 07012026 - MCR Update - Minneapolis.pdf PDF
S06 - Amend 0006 - Att 03 - DWGs - 06122026 - MCR Update - Minneapolis.pdf PDF
S06 - Amend 0006 - Att 02 - Specs - 01302026 - MCR Update - Minneapolis.pdf PDF
S06 - Amend 0005 - 36C77626B0017 - 06232026 - MCR Update - MN.pdf PDF
S06 - Amend 0004 - 36C77626B0017 - 06092026 - MCR Update - MN.pdf PDF
S06 - Amend 0003 - 36C77626B0017 - 05262026 - MCR Update - MN.pdf PDF
S06 - Amend 0002 - 36C77626B0017 - 05122026 - MCR Update - MN.pdf PDF
S06 - Amend 0002 - Site Visit - Attendance Sheet - 05112026 - MCR Update - MN.pdf PDF
S06 - Amend 0002 - Site Visit - Agenda - 05112026 - Final - MCR Update - MN.pdf PDF
36C77626B0017 0001 5.6.2026.docx DOCX document
S06 - Amend 0001- FAR 52.222-90 - MCR Update - Minneapolis.pdf PDF
Att 02 - Spec - Vol 02 - 01302026 - MCR - Minneapolis.pdf PDF
Att 03 - CD Drawings - MCR Mod - Minneapolis.pdf PDF
Att 07 - Wage Rates - DBA - Hennepin - 01022026 - MCR Mod - Minneapolis.pdf PDF
Att 08 - Site Visit Agenda - IFB - MCR Update - Minneapolis.pdf PDF
Sol - 36C77626B0017 - 04212026 - MCR Mod Update - Minneapolis.docx DOCX document
Att 05 - Memo - J and A - Brand Name - Final - MCR Mod - Minneapolis.pdf PDF
Att 01 - Spec - Vol 01 - 03312026 - MCR - Minneapolis.pdf PDF
Att 04 - SOW - Final - MCR Mod - Minneapolis.pdf PDF
Att 06 - Limitations on Subcontracting - MCR Mod - Minneapolis.pdf PDF
Show all 24

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

12140 Nicollet Ave. South * Burnsville, MN 55337 Phone 952-403-9900

Fax 952-403-9920 datacsi.com

Liebert eXM Uninterruptible Power Supply

VA Medical EHRM Infrastructure Upgrades

51SA150HAA00SCV

Two (2) December 22, 2022 401599 Ace Electric

TBD

Job Name Model Quantity Date DCSI Job# Purchaser P.O. # Submitted By Spec Section

Data Center Systems, Inc. – Dave Boehde /ah 26 33 53 & 26 26 00

12140 Nicollet Ave. South * Burnsville, MN 55337 * Phone 952-403-9900 * Fax 952-403-9920 * datacsi.com

ATTENTION:

Startup Procedures

For Vertiv Services to accommodate your start-up scheduling needs, please contact Vertiv by calling

816-246-2065.

You may also call your sales representative with Data Center Systems, Inc. at 952-403-9900.

Please allow 2-3 weeks notice.

~Thank you~ eXM Spec Sheet

Project Name

DCSI Project Number 401599

Model Number

Quantity

Date

Nominal Max

UPS Module Input 480 VAC 189 FLA 208 FLA 300A Recommended Ext. OPD 3 wire or 4 wire Plus Ground

UPS Module Output 208/120 VAC 416 FLA N/A FLA 600A Recommended Ext. OPD 3 wire or 4 wire Plus Ground

UPS Size: 10 kVA / 10 kW 15 kVA / 15 kW 20 kVA / 20 kW

EXM 208V (10-200kVA) 30 kVA / 30 kW 40 kVA / 40 kW 60 kVA / 60 kW

80 kVA / 80 kW 100 kVA / 100 kW

EXM 480V (50-250kVA) 50 kVA / 50 kW 100 kVA / 100 kW 150 kVA / 150 kW

200 kVA / 200 kW 250 kVA / 200 kW

UPS Module Options

Single Input 65kAIC Rating

Dual Input Transformer-Free Architecture

Relay Contact Card (IS-RELAY) Unity Power Factor Rating

Site Scan Interface Card Load Power Factor Support

Energy Optimization Mode

Generator Load Control

Remote Status Panel Local Emergency Power Off (EPO)

Backlit LCD display

Dimensions 24" W x 78.7" H x 39.1" D Weight

150 kW 22 Minutes of Battery Back Up Time "at Full Load" Beginning of Life

150 kW 16 Minutes of Battery Back Up Time "at Full Load" End of Life (125% percent of full rated output load day 1)

VRLA Spill Containment System Included

Mounting Options Right hand side of UPS module Left hand side of UPS module Stand Alone Battery Cabinet

Dimensions: 47.4" W x 78.7" H x 39.1"D Weight 4,620 Lbs.

Maintenance Bypass Cabinet Number of Switching Devices: Two (2) Devices (MBB, MIB) Three (3) Devices (BIB, MBB, MIB)

Model #51MBH33AA0R1S03 Breaker Trip Rating: 300A Key Interlock

Mounting Options: Right hand side of UPS module Left hand side of UPS module

Dimensions Weight:

UPS output Distribution Cabinet Type: K20 Output Transformer One (1) 600A, 84P Panelboard

Per panel schedule 1383-70E-701 Two (2) 10kA, 3 Pole 30a Breakers, shipped loose

Model #51X150HCAMEASHV Six (6) 10kA, 3 Pole 60A Breakers, shipped loose

Six (6) 10kA, 3 Pole 70A Breakers, shipped loose

Two (2) 10kA, 3 Pole 80A Breakers, shipped loose

Dimensions 35" W x 78.7" H x 39.1" D 2,538 Lbs.

LGS Services Preferred Service 1 PM 2 PM's 3 PM's 4 PM's

Essential Service 1 PM 2 PM's 3 PM's 4 PM's

Basic Service 0 PM's

PM Only 7 x 24 1 PM 2 PM's 3 PM's 4 PM's

PM Only 5 x 8 1 PM 2 PM's 3 PM's 4 PM's

Start-up Services Start-up 7 x 24 (Customers designated time)

One (1) Day of Site Accetance Testing with Load Bank

Four (4) Hours of On-Site Customer Training

Eight (8) Hour Factory Burn-In Testing with Data Logging Every 30 Minutes

Buy American Act Compliant

FOB Destination

Remarks:

THREE-PHASE UPS

VA Medical - EHRM Infrastructure Upgrades

51SA150HAA00SCV

Two (2)

December 22, 2022

Standard FeaturesOptional Features

*Start up Services - Please contact Liebert Global Services @ 816-246-2065. (Please allow 2 - 3 weeks notice.)

Weight

12.1" W x 78.7" H x 39.1" D 288 Lbs.

936 Lbs.

Intellislot Unity Card, for communication via SNMP, HTTP, Bacnet, or Modbus, IS-

UNITY-DP

Two (2) External Battery Cabinets with East

Penn 31FR5000 Batteries

Model #51BPHWAD2L10SCA

Document generated 22 December 2022 11:37 AM (EST).

NOTES

1. NOMINAL INPUT CURRENT (CONSIDERED CONTINUOUS) IS

BASED ON FULL RATED OUTPUT LOAD. MAXIMUM

CURRENT INCLUDES NOMINAL INPUT CURRENT AND

MAXIMUM BATTERY RECHARGE CURRENT (CONSIDERED

NONCONTINUOUS). CONTINUOUS AND NONCONTINUOUS

CURRENT ARE DEFINED IN NEC 100. RECOMMENDED

OVERCURRENT PROTECTION IS BASED ON 80% RATED

DEVICES. * THE RECOMMENDED OVERCURRENT

PROTECTION REPRESENTS 125% OF NOMINAL FULL LOAD

CURRENT (CONTINUOUS) PER NEC 215.

2. MAXIMUM INPUT CURRENT IS CONTROLLED BY THE

CURRENT LIMIT SETTING.

3. RECOMMENDED AC INPUT EXTERNAL OVERCURRENT

PROTECTION IS BASED ON 80% RATED DEVICES AND

MAXIMUM INPUT CURRENT LIMIT SETTING.

4. RECOMMENDED AC OUTPUT EXTERNAL OVERCURRENT

PROTECTION IS BASED ON 80% RATED DEVICES AND FULL

RATED OUTPUT CURRENT.

5. NOMINAL BATTERY VOLTAGE IS SHOWN AT 2.0 VOLTS /

CELL.

6. INPUT POWER FACTOR OF 0.99 IS USED FOR THE

CALCULATIONS.

TITLE

DATE (LATEST REV.)

REVISION

DRAWN BY:

DESIGNED BY:

APPROVED BY:

SHEET NO.

ECN NO.

REF DWG.

DWG. NO.

TM

1050 DEARBORN DR

P.O. BOX 29186

COLUMBUS, OH 43229

EXM48001

LIEBERT 480VAC EXM

SINGLE INPUT

D. HUDSON

D. HUDSON

J. SHIPMAN

06/04/2018

50-250kVA, 60Hz, 480VAC IN, 480VAC OUT

TECHNICAL INFORMATION

THIS CHART IS FOR UPS WEIGHTS ONLY. FOR MBC OR BDC

WEIGHTS REFER TO SUBMITTAL EXM18014 OR EXM18015.

Document generated 22 December 2022 11:37 AM (EST).

AC Output listed is for UPS module only at 480V. The complete system will include an output step down transformer cabinet and a 600A 120/208V 84P distribution panel

TITLE

DATE (LATEST REV.)

REVISION

DRAWN BY:

DESIGNED BY:

APPROVED BY:

SHEET NO.

ECN NO.

REF DWG.

DWG. NO.

TM

1050 DEARBORN DR

P.O. BOX 29186

COLUMBUS, OH 43229

EXM43032

880mm DISTRIBUTION CABINET, LIEBERT 480VAC EXM

MAINTENANCE BYPASS CABINET (300mm) WITH

D. McLAURIN

D. McLAURIN

K. STACY

8/3/2017

150kVA - 200kVA UPS TO BATTERY CABINET (1200mm) AND

LINE-UP DETAIL

NOTES

1. ALL DIMENSIONS ARE IN inches [mm].

2. 24" [610mm] MINIMUM CLEARANCE ABOVE UNIT AIR

EXHAUST. 36" [914mm] FRONT ACCESS REQUIRED FOR

SERVICE.

3. KEEP CABINET WITHIN 15 DEGREES OF VERTICAL.

4. UPS - BOTTOM CABLE ENTRY THROUGH REMOVABLE PLATES.

MBC - TOP AND BOTTOM CABLE ENTRY AVAILABLE THROUGH

REMOVABLE PLATES. REMOVE, PUNCH TO SUIT CONDUIT

SIZE AND REPLACE.

5. UNIT BOTTOM IS STRUCTURALLY ADEQUATE FOR FORKLIFT

HANDLING.

6. CONTROL WIRING AND POWER WIRING MUST BE RUN IN

SEPARATE CONDUITS.

7. ALL WIRING MUST BE IN ACCORDANCE WITH NATIONAL

AND LOCAL ELECTRICAL CODES.

8. ALL BATTERY CABINETS MUST BE POSITIONED ON THE LEFT

SIDE OF UPS.

UPS MBC

TOTAL WIDTH WITH

ADDITIONAL BATTERY CABINETS

NO. OF

BATT. CABINETS

TOTAL WIDTH

164.7" [4188mm]

211.8" [5378mm]

258.9" [6578mm]

BATTERY

CABINET #1

DISTRIBUTION

CABINET

117.6" [2988mm]

34.6" [880mm]

11.8" [300mm]

23.6" [600mm]47.1" [1196mm]

REF. DWG.

CHK BY

DRAWN BY

SHEET NO.

ECN NO.

DATE REV. #

FILE NAME:

DWG. NO.

LIEBERT 480VAC EXM

50kVA - 200kVA UPS

OUTLINE DRAWING

ORDER NO.

I:\appl-DLW\Ohio Appl\AE Submittals - Standard\eXM dwg\480V\B) Outline Dwg\EXM42001A-03.dwg

EXM42001A

4/6/18

B. SANBORN

J. SHIPMAN

DRAWN BY

SHEET NO.

ECN NO.

DATE REV. #

FILE NAME:

DWG. NO.LIEBERT 480VAC EXM

50kVA - 200kVA UPS

MAIN COMPONENTS LAYOUT

OUTLINE DRAWINGS

ORDER NO.

I:\appl-DLW\Ohio Appl\AE Submittals - Standard\eXM dwg\480V\B) Outline Dwg\EXM42001B-03.dwg

EXM42001B

4/6/18

B. SANBORN

J. SHIPMAN

FRONT VIEW

WITH DOOR OPENED

RIGHT SIDE VIEW

WITH DOOR OPENED

(AND SIDE PANEL REMOVED)

DETAIL A

DRAWN BY

SHEET NO.

ECN NO.

DATE REV. #

FILE NAME:

DWG. NO.

LIEBERT 480VAC EXM

BATTERY CABINET (1200mm)

OUTLINE DRAWING

ORDER NO.

I:\appl\Ohio Appl\AE Submittals - Standard\eXM dwg\480V\B) Outline Dwg\EXM42004A-04.dwg

EXM42004A

4/6/18

B. SANBORN

J. SHIPMAN

NOTES:

1. ALL DIMENSIONS ARE IN inches [mm].

2. 24" [610mm] MINIMUM CLEARANCE ABOVE UNIT FOR AIR EXHAUST.

36" [914mm] FRONT ACCESS REQUIRED FOR SERVICE.

3. KEEP CABINET WITHIN 15 DEGREES OF VERTICAL.

4. TOP AND BOTTOM CABLE ENTRY AVAILABLE THROUGH REMOVABLE

ACCESS PLATES. REMOVE, PUNCH TO SUIT CONDUIT SIZE AND REPLACE.

5. CONTROL WIRING AND POWER WIRING MUST BE RUN IN SEPARATE

CONDUITS.

6. COPPER CABLES ONLY ARE RECOMMENDED.

7. ALL WIRING IS TO BE IN ACCORDANCE WITH NATIONAL AND LOCAL

ELECTRICAL CODES.

8. OVERALL DIMENSIONS ARE SHOWN WITH SIDE PANELS.

FRONT

CENTER GRAVITY

LEVELING FEET

Z

39.1" [993mm]

DOOR CLOSED

78.7"

[2000mm]

BATTERY

AND TRAY

RIGHT SIDE VIEWFRONT VIEW

(WITHOUT COVERS)

ALBER BDSUI

(OPTIONAL)

BATTERY

BREAKER

47.4" 1204mm]

OVERALL

Y

47.1" [1196mm]

CABLE ENTRY

AREA

15.8" [401mm] x

10.4" [264mm]

ALBER SERVICE

PLATES

19.3" [490mm] x

14.0" [356mm]

CABLE ENTRY

AREA

12.6" [320mm] x

12.1" [310mm]

CABLE ENTRY

AREA

9.3" [236mm] x

14.2" [361mm]

34.3"

[871mm]

12.7"

[326mm]

BRKT.

CENTERS

12.7"

[326mm]

BRKT.

CENTERS

6.2"

[157mm]

6.9" [175mm]

OUTSIDE FRAME

16.8" [419mm]

OUTSIDE FRAME

BOTTOM VIEW

(VIEWED FROM FLOOR)

TOP VIEW

MAX DOOR SWING 120°

X

CENTER OF GRAVITY TABLE (mm)

X Y Z

20.0" (510) 35.6" (905) 19.8" (504)

DRAWN BY

SHEET NO.

ECN NO.

DATE

REV. #

FILE NAME:

DWG. NO.LIEBERT 480VAC EXM

BATTERY CABINET (1200mm)

MAIN COMPONENTS LAYOUT

OUTLINE DRAWING

ORDER NO.

I:\appl\Ohio Appl\AE Submittals - Standard\eXM dwg\B) Outline Dwg\EXM42004B-04.dwg

EXM42004B

4/6/18

B. SANBORN

REVISION

DRAWN BY:

DESIGNED BY:

APPROVED BY:

SHEET NO.

ECN NO.

REF DWG.

DWG. NO.

TM

1050 DEARBORN DR

P.O. BOX 29186

COLUMBUS, OH 43229

EXM48003

LIEBERT 480VAC EXM

B. SANBORN

B. SANBORN

N. M.

08/27/2020

BATTERY CABINETS

TECHNICAL INFORMATION

NOTES

1. 250kVA eXM UPS REQUIRES A MINIMUM OF TWO

CABINETS.

From To

TB1-6 X9J22-1 Black +12V_BCB_DRV 18G

TB1-7 X9J22-3 Brown BCB_STATE 18G

TB1-8 X9J22-5 White GND_Dry 18G

TB1-9 X9J22-7 Green BCB_ONLINE 18G

TB1-10 X9J22-11 Black GND_Dry 18G

TB1-11 X9J22-13 White TEMP_BAT 18G

TB1-12 X9J22-15 Red +12V_A 18G

Terminal Designation Color

Cable Group #3 - From UPS to Battery Cabinet #1 or MBD

Signal Name Recommended Wire

From To

TB1-1 TB1-1 Black Shunt Trip 18G

TB1-2 TB1-2 White Shunt Trip 18G

TB1-3 TB1-3 Green Aux Contact 18G

TB1-4 TB1-5 Red Aux Contact 18G

Cable Group #4 - From Battery Cabinet to Battery Cabinet

Terminal Designation Color Signal Name Recommended Wire

Protecting Mission-Critical Facilities and Personnel Since 1993.SM

5534 Olive street • Montclair, CA 91763 • 800.206.9884 • Fax 909.624.1772 • www.EnviroGuard.com EnviroGuard is an ISO 9001-2015 Certified Manufacturer of UL Listed and UL Recognized products

SP_SC_HAWK

HAWK™ SYSTEM

Liner-Based for Cabinets, VRLA & NiCd Battery Applications

Features

• Fast and easy installation

• Non-metallic components

• Minimal �oor preparation necessary

• Corrosive-resistant liner with Class 1 �re rating (NFPA 101)

• Can be con�gured to �t most applications

• Optional �oor anchors for easy installation on computer �oors

• Quick-slip barrier walls for easy battery access

• Spill containment for stationary lead-acid battery systems

• Available in gray

• UL Listed

Part Number

HAWK - WW-LLL

(i.e. HAWK 30-120) WW=Width in inches, LLL=Length in inches

Regulations In Compliance With

• NFPA

• International Fire Code (IFC)

• OSHA

• Underwriters Laboratories (UL)

Specifications

• 4” x 1/2” Polypropylene Barriers

• Standard 60 mil Polymeric Liner

• Optional 80 mil Polymeric Liner

• System includes 12"x12" Neutralization and Absorption Pads (VRLAPADs)

• KOH VRLAPADs substituted for NiCd

Battery Applications

Battery Room Aisle Mat

Compliance Package

Reommended Products

Part Number: HAWK-WW-LLL

200709A

Spill Containment Drawing

Quote Number: E

Project Information Project Name: Spill for Cabinets Date Created: 12/28/2022 Construction: New Construction Est. Product Weight: 208.08 lbs.

Description: 2 UPS systems, each will have 2 battery cabinets each containing (36) jars of East Penn

HR5000 batteries

Order Instructions:

5534 Olive St., Montclair, CA. 91763 Phone: 800-206-9884 Fax: 909-624-1772

REVISION

DRAWN BY:

DESIGNED BY:

APPROVED BY:

SHEET NO.

ECN NO.

REF DWG.

DWG. NO.

TM

1050 DEARBORN DR

P.O. BOX 29186

COLUMBUS, OH 43229

EXM48004

LIEBERT 480VAC EXM

D. McLAURIN

D. McLAURIN

K. STACY

8/9/2017

MAINTENANCE BYPASS CABINETS (MBC)

TECHNICAL INFORMATION

REVISION

DRAWN BY:

DESIGNED BY:

APPROVED BY:

SHEET NO.

ECN NO.

REF DWG.

DWG. NO.

TM

1050 DEARBORN DR

P.O. BOX 29186

COLUMBUS, OH 43229

EXM44015

LIEBERT 480VAC EXM

UPS TO MAINTENANCE BYPASS CABINET (MBC)

G. HOGE

G. HOGE

J. SHIPMAN

11/29/2017

CABLE GROUP #10

CONTROL WIRING

DRAWN BY

SHEET NO.

ECN NO.

DATE REV. #

FILE NAME:

DWG. NO.

LIEBERT 480VAC EXM

MAINTENANCE BYPASS CABINET (300mm)

BASE DETAIL

ORDER NO.

I:\appl\Ohio Appl\AE Submittals - Standard\eXM dwg\480V\I) Seismic & Base Details\EXM49005-01.dwg

EXM49005

1/31/18

J. SHIPMAN

NOTES

1. ALL DIMENSIONS ARE IN INCHES [mm].

2. UNIT BOTTOM IS STRUCTURALLY ADEQUATE FOR

FORKLIFT HANDLING.

BOTTOM VIEW

TITLE

DATE (LATEST REV.)

REVISION

DRAWN BY:

DESIGNED BY:

APPROVED BY:

SHEET NO.

ECN NO.

REF DWG.

DWG. NO.

TM

1050 DEARBORN DR

P.O. BOX 29186

COLUMBUS, OH 43229

EXM49009

LIEBERT 480VAC EXM

J. WARNER

J. WARNER

J. SHIPMAN

01/04/2018

DISTRIBUTION CABINET (880mm)

BASE DETAIL

26.0" [660mm]

31.5" [799mm]

35.0" [888mm] m m m m m m

FRONT

REVISION

DRAWN BY:

DESIGNED BY:

APPROVED BY:

SHEET NO.

ECN NO.

REF DWG.

DWG. NO.

TM

1050 DEARBORN DR

P.O. BOX 29186

COLUMBUS, OH 43229

EXM47007

LIEBERT 480VAC EXM

B. SANBORN

B. SANBORN

J. SHIPMAN

12/06/2018

150 kVA

UPS EFFICIENCY

NOTES

1. NO LOAD POWER LOSS: 1.28 kW

ECO MODE

NORMAL MODE

Pythia Technologies 740.363.2272 sales@pythiatech.com 1

Status Panel (pn: CS0-RSP-UPS)

Description:

The UPS Remote Status Panel is used to remotely monitor up to (6) UPS alarms via dry-contacts. The CS0-RSP-UPS is wall mounted and can be located up to 500 feet from the monitored dry-contact. The panel uses LED’s to visually display the monitored point input status along with a siren to alert users to alarm and new alarm conditions. An

Acknowledge button allows user to silence alarms and provides a lamp test function when held for 10 seconds.

Additional standard features:

Echo Option: Provides (6 total) output contacts to mimic input alarm states for notifications to other systems.

Network Option: Modbus/TCP or BACnet/IP or SNMP

Technical Specification

Assembly Overview

• Wall mounted enclosure

• Dims: 16” (H) x 12” (W) x 4” (D) @ 12lbs

• Visual indication with audible alarm.

• Requires 120VAC power

• NEMA 1 Enclosure for indoor use

• UL508A Listed

• Powder coated

• On UPS • On Bypass • UPS Fault

• On Battery • Low Battery • Summary Alarm

• Summary Alarm dry-contact output • Modbus 485 communications

Pythia Technologies 740.363.2272 sales@pythiatech.com 2

Dimensions

Pythia Technologies 740.363.2272 sales@pythiatech.com 3

A sse m b ly

(S h o w n w ith o u t o p tio n s in sta lle d

Pythia Technologies 740.363.2272 sales@pythiatech.com 4

A sse m b ly

(S h o w n w ith E c h o a n d M o d b u s/T

C P o p tio n s in sta lle d

Pythia Technologies 740.363.2272 sales@pythiatech.com 5

E x a m p le

W irin g

175 S. Sandusky Street, Suite 321 Delaware OH 43015 Tel. 740.363.2272 sales@pythiatech.net

© 2022 Pythia Technologies, Inc.

All rights reserved throughout the world.

Specification may change at anytime without notice. Document #: SPEC_CS0-RSP-UPS_003_1122

Key Features:

Wall mounted panel to remotely monitor UPS conditions from 500 feet away

Alarm siren with acknowledge button and lamp test function

Modbus RTU RS485 communications standard. Options for Modbus/TCP or BACnet/IP or SNMP

Summary Alarm contact output. Option for 5 additional to mimic alarm inputs

NEMA1, UL508A Listed, powder coated panel

SPECIFICATIONS

Standard Communications Modbus RTU

Inputs 6

Input Type Dry-contact only / zero voltage relays or contacts / Normally Open / Closed

Input Dry-Contact distance 500ft verified w/ 22awg cabling Belden 8747 (6-pair), Belden 8761 (1-pair) or equal

Output Contact (Summary Alarm) 1 Standard, 5 additional with Echo option

Output Contact Rating Contact closure 24VAC @ 1.0A max

Dimensions 16” x 14” x 4.75”

Weight Panel / Shipping 12.0 / 20lbs

Input Power 120/240 VAC @ 1.5A maximum

Communications Standard Modbus/RTU RS485 2-wire Slave ID: 02 @ 9600 baud, N,8,1 data rate . Baud rate and slave

ID access via Modbus write function

Options: Echo = 6 total contact closures mimicking input states

Network = Modbus/TCP or BACnet/IP or SNMP

Certifications NEMA1 enclosure indoor use only, UL508A Enclosed Industrial Control Panel

Other Specifications none

Part Numbers

CS0-RSP-UPS-x-xxxx (No Options)

CS0-RSP-UPS-E-xxxx (Echo Option) Total of (6) dry-contact outputs

CS0-RSP-UPS-x-MTCP (Network Comms Options) MTCP = Modbus/TCP, BAC0 = BACnet/IP, SNMP = SNMP

Liebert® IntelliSlot™ Relay Card Product Specification/Installation Guide

590-1802-501A/ SL-23212_REV1_12-20 1

Liebert® IntelliSlotTM Relay CardLiebert® IntelliSlotTM Relay Card The Liebert IntelliSlot Relay Card (IS-RELAY) provides contact closures for remote monitoring of alarm conditions in your Liebert unit. The card is easy to install and integrates with other relay contact monitoring systems.

This advanced power management device is designed to function in units with a Liebert IntelliSlot port.

The Liebert IntelliSlot Relay Card is rated for 24VAC/VDC at 1A.

COMPATIBILITY with Liebert Equipment

IntelliSlot Web Card Part Number Compatible with:

Liebert® IntelliSlot™ Relay Card IS-RELAY

Liebert® EPM Liebert® GXE2 Liebert® NX

Liebert® EXM Liebert® GXT3 Liebert® NXC

Liebert® EXM2 Liebert® GXT4 Liebert® NXR

Liebert® APM Liebert® GXT5 Liebert® PSI5

Liebert® APS Liebert® ITA2 Vertiv™ Edge

Liebert® EXS Liebert® Nfinity™

2 590-1802-501A/ SL-23212_REV1_12-20

Product Specification/Installation Guide

Jumper Settings The card has five jumpers, P3 through P7. Each jumper connects two pins. By default, all five jumpers have shunts installed. The two pins are shunted together to provide the functions (see PIN CONFIGURATION table on the previous page), allowing relay commons to be tied together.

NOTE: The jumpers should be removed if any external voltage source may be connected to the relay.

Removing the shunt from any two pins breaks the connection between the relay commons so they are not tied together.

Jumper P6

Jumper P5

Jumper P4

Jumper P3

Jumper P7

Pin Function Operation

1 Common - Low Battery —

2 Low Battery Closed if low battery point occurs

3 Low Battery Closed if battery is OK

4 Common - UPS Fault —

5 UPS Fault Closed if UPS fault occurs

6 UPS Fault Closed if no UPS failure

7 Common - On Battery —

8 On Battery Closed if on battery power (utility failure)

9 On Battery Closed if not on battery power (utility OK)

10 Signal Ground Use for UPS Any-Mode Shutdown

11 Signal Ground Use for UPS Any-Mode Shutdown

12 UPS Any-Mode Shutdown Turn UPS Off when shorted to Pin 10 or 11

13 Summary Alarm Closed if no alarm conditions are present

14 Summary Alarm Closed if summary alarm occurs

15 Common - Summary Alarm —

16 On UPS Closed if on UPS (inverter) power

17 On Bypass Closed if on bypass

18 Common - On Bypass —

PIN CONFIGURATION

These pin functions represent common pin assignments for the supported units listed above.

Jumper Relay

P6 On Battery

P5 UPS Fault

P4 Low Battery

P3 On Bypass

P7 Summary Alarm

590-1802-501A/ SL-23212_REV1_12-20 3

Product Specification/Installation Guide

DIMENSIONS

SPECIFICATIONS

Power Requirements DC Inputs 7 - 12VDC

Power Consumptions: 2.0W maximum

Dimensions, W x D x H 2.87 in. x 5.19 in. x 1.46 in. (73mm x 131.8mm x 37.2 mm)

Weight (assembled) Net: 6 oz (0.2 kg)

Shipping: 0.8 lb (0.4 kg)

Ambient Operating Environ-ment

32 to 131 (0 to 55); 10% to 90% RH (non-condensing)

Ambient Storage Temperature –4°F to 140°F (–20°C to 60°C)

Terminal Blocks Two 9-Pin Connectors Relay Contact Points

Wire Type: 24 AWG-16 AWG 0.24in. - 0.28 in. (6mm-7 mm) Wire Strip Length

5.19” (131.8 mm)

2.36” (60 mm)

1.46” (37.2 mm)

2.87” (73 mm)

Front face Board

To contact Vertiv Technical Support: visit www.Vertiv.com © 2020 Vertiv Group Corp. All rights reserved. Vertiv™ and the Vertiv logo are trademarks or registered trademarks of Vertiv Group Corp. All other names and logos referred to are trade names, trademarks or registered trademarks of their respective owners. While every precaution has been taken to ensure accuracy and completeness here, Vertiv Group Corp. assumes no responsibility, and disclaims all liability, for damages resulting from use of this information or for any errors or omissions. Specifications, rebates and other promotional offers are subject to change at Vertiv’s sole discretion upon notice.

4 590-1802-501A/ SL-23212_REV1_12-20

590-1307-501C/SL-52646_REV11_6-17

LIEBERT® INTELLISLOT™

UNITY PLATFORM CARDS

Product Specification/Installation Guide

The Liebert IntelliSlot Unity Platform brings SNMP, BACnet IP, BACnet MSTP, Modbus TCP, Modbus RTU, YDN23 and Web management capability to many models of Vertiv’s power and cooling equipment. The cards employ Ethernet and RS-485 networks to monitor and manage a wide range of operating parameters, alarms and notifications. The card also supports communication for LIFE™ Services by VERTIV.

ADDITIONAL FEATURES

• SNMPv1, SNMPv2c and SNMPv3 with MIB-II support

• HTTP/HTTPS 1.1

• BootP

• DHCP per RFC2131/2132

• Remote firmware updates via a Web browser

• IPv6 support for HTTP/HTTPS, DHCPv6, e-mail, SMS, SNMP v1/v2c/ v3 and Modbus TCP

• Liebert SN Environmental Sensor Support (Web, SNMP, SMS and SMTP): Temperature, Humidity, Door Closure, Contact Closure and Leak Detection: Liebert SN-2D, Liebert SN-3C, Liebert SN-L, Liebert SN-T, Liebert SN-TH, Liebert SN-Z01, Liebert SN-Z02 and Liebert SN-Z03

IntelliSlot Unity cards are a form, fit, and function replacement for several Liebert IntelliSlot Web and 485 cards.

COMPATABILITY with Liebert Equipment

IntellSlot Card Compatible with

IS-UNITY-DP

IS-UNITY-SNMP

IS-UNITY-LIFE

Alber BDSU-50™

Liebert APM™

Liebert APS™

Liebert Challenger

3000™

Liebert CRV™

Liebert CW™

Liebert DCL™

Liebert DCP™

Liebert Deluxe System/3™

Liebert DS™

Liebert DSE™

Liebert EPM™

Liebert EXC™

Liebert eXL™

Liebert EXL™ S1

Liebert eXM™

Liebert FDC™

Liebert FPC™

Liebert GXT3™

Liebert GXT4™

Liebert HPC™

Liebert HPC-S/M/R/W/Generic™

Liebert HPM™

Liebert NX™ 225-600 kVA

Liebert NXC™

Liebert NXL™ *

Liebert NXR™

Liebert PCW™/PDX™

Liebert PeX™ *

Liebert PPC™

Liebert RDC™

Liebert RX™

Liebert XDC™

Liebert XDP™

Liebert XDP-Cray™

* YDN23 supported only for Liebert PeX and Liebert NXL.

VertivCo.com | Vertiv Headquarters, 1050 Dearborn Drive, Columbus, OH, 43085, USA © 2017 Vertiv Co. All rights reserved. Vertiv and the Vertiv logo are trademarks or registered trademarks of Vertiv Co. All other names and logos referred to are trade names, trademarks or registered trademarks of their respective owners. While every precaution has been taken to ensure accuracy and completeness herein, Vertiv Co. assumes no responsibility, and disclaims all liability, for damages resulting from use of this information or for any errors or omissions. Specifications are subject to change without notice.

590-1307-501C/SL-52646_REV11_6-17

LIEBERT® INTELLISLOT™ UNITY PLATFORM CARDS

Product Specification/Installation Guide

COMPATABILITY with Communication Protocols

Liebert IntelliSlot Card

Life Services Support

Communication Protocol

HTTP

HTTPS

Velocity Protocol

Email SMS SNMP v1, v2c, v3

BACnet IP BACnet MSTP

Modbus TCP Modbus RTU

YDN23*

IS-UNITY-DP

IS-UNITY-SNMP — — —

IS-UNITY-LIFE — — — —

* YDN23 supported only for Liebert PeX and Liebert NXL.

DIMENSIONS

SPECIFICATIONS

Power Requirements DC Inputs 7 to 12 VDC

Power Consumptions: 3.6 W maximum

Dimensions, W x D x H 2.97 x 5.2 x 1.45 in. (75.5 x 15 x 37 mm)

Weight (assembled) Net: 7 oz (0.2 kg)

Shipping: 1.3 lb (0.6 kg)

Ambient Operating Environment 32 to 104°F (0 to 40°C); 10% to 90% RH (non-condensing)

Ambient Storage Temperature –4 to 140°F (–20 to 60°C)

Communication Ports Ethernet Communication RJ-45 (LIFE™ Services requires a network connection to the Internet)

RJ-45 (RJ-45 to 2-position terminal-block adapter)

WIRING

10/100 Mb/s Ethernet connector Standard Category 5E Cable 328 ft. (100m)

RJ-45 - One-Wire Connector Liebert® Integrated One-Wire Sensor Cable or 2m Cat 5E to Modular 1-Wire

65.6 ft. (20m)

1/2” (11 mm)4-3/4” (121 mm)

2-3/8” (60.3 mm)

1-1/2” (38 mm)

3” (76 mm)

Front face

Board

SCOPE OF WORK

UNINTERRUPTIBLE POWER SYSTEMS

EXM UPS ONLY

STARTUP (24X7) SERVICE

SERVICE SUMMARY

Feature Detail

On-Site Service One site trip within the 48 contiguous states after the system has been installed and cabling terminated. Visit to be scheduled at the customer's convenience (excluding national holidays).

LIFE

Includes LIFE Services activation and service for the duration of warranty period (supported products ONLY).

Validates Warranty Vertiv startup validates the warranty.

VERTIV PROPRIETARY SERVICE TOOLS AND SOFTWARE

Vertiv Customer Engineers (CEs) are the only authorized, factory- trained and OEM-supported service providers for Vertiv equipment with access to Vertiv’s proprietary service tools and software to ensure optimal equipment performance.

l Using proprietary software PPvis™, Paramset™, and WinSVT™ CEs apply Vertiv’s knowledge base to diagnose, configure and optimize your Vertiv equipment.

l Vertiv is the only authorized source for critical proprietary firmware updates providing your equipment the latest version of operational firmware to ensure equipment is running at optimal performance and efficiency levels.

l Vertiv exclusively enables:

l Access to OEM engineering support and product enhancements.

l Optimized methods of procedure for efficient service supported by proprietary documentation.

l Improved MTBR and MTTR.

l Root cause forensic analysis.

l Continual improvements with tested and certified updates for software and hardware improvements throughout the equipment’s lifecycle.

l CEs to be equipped with proprietary service documentation that provides access to the latest method of procedures and event data to return equipment online in the most efficient manner possible.

l Benchmarking against the entire service population to identify service trends and provide solutions rapidly or before they occur, reducing or eliminating customer events and outages.

l Vertiv Services CEs are trained in NFPA and OSHA best practices, and all processes and procedures strictly comply with NFPA 70A and 70E industry standards.

SERVICE PERFORMED

Startup Service

1. Perform a complete visual inspection of the equipment, checking for broken, damaged, or stressed components.

2. Check air filters for cleanliness. (if applicable)

3. Check all nuts, bolts, screws, and connectors for tightness.

. Scope of Work | EXM All Startup 24x7 © 2019 Vertiv Co. All rights reserved.

Rev: 05/15/2019 Page 1 of 3 .

4. Clean any foreign material and dust from equipment.

5. Verify that the system is installed correctly.

6. Perform an operational test of the system including unit transfer and battery discharge.

7. Ensure that input, output, and DC voltages are within tolerance.

8. Verify operation of installed options.

9. Calibrate UPS meters and ensure all UPS metering is within UPS specification.

10. Verify proper operation with customer load, if available.

11. Verify proper operation with generator, if available.

12. Review equipment installation and conduct Operational Tour (i.e. train customer on unit operation during Start Up visit).

Additional visits, if required by customer, will be billable.

13. LIFE Services activation.

14. Site Acceptance Test of the LIFE™ Service to validate performance and event recognition

LIFE Services includes:

1. 24x7 continuous remote monitoring of events and parametric data from UPS.

2. Quarterly event and data analysis report that identifies recent trends and changes to recorded data that may impact performance or availability of the managed equipment. This report will be emailed to the customer’s primary contact.

3. Contacting the customer by phone on critical events or conditions that may impact availability. Please note critical events are predefined by Vertiv Service for the managed equipment.

4. Dispatch field service engineer if required and if managed equipment is under maintenance contract with Vertiv.

5. Technical phone support (8x5 Monday-Friday, excluding national holidays) for the LIFE™ Services, events/alarm(s), processes, communication issues, and report clarification.

6. Full parts, labor, and travel coverage on communication card(s) during the LIFE™ Services contract term.

Site Requirements for LIFE™ Services:

1. Provide a primary site contact person responsible for receiving notification of critical events or conditions, requests for on-site service access, reports, and authorization of service changes.

2. Provide alternative site contact if applicable for receiving notification of critical events or conditions and also requests for on-site access.

3. Provide a valid e-mail address to ensure receipt of quarterly event and data analysis report.

4. A primary site network contact person shall be provided for assigning IP addresses and installation of network drops.

5. Connectivity to the local area network for each UPS module (network drop).

6. Availability of network port : TCP port 80

ASSUMPTIONS AND CLARIFICATIONS

Any customer site visit is limited to eight (8) hours per visit. Any time beyond forty (40) hours/wk or eight (8) hrs/day or additional Startup visits will be billed separately.

Parts coverage is in accordance with Product Warranty.

Expenses incurred due to delays that are beyond the control of Vertiv may be billed at cost.

CUSTOMER RESPONSIBILITIES

In order to provide timely, accurate and thorough execution of the services described herein, Vertiv requests the following:

. Scope of Work | EXM All Startup 24x7

Rev: 05/15/2019 Page 2 of 3 .

l Point of Contact: Provide an authorized point of contact(s), specific for the scope of work, for scheduling and coordination purposes.

l Scheduling: Make dates available for scheduling service. All visits must be requested 10 business days in advance of need by contacting the Vertiv Customer Resolution Center at 1-800-543-2378.

l Site Access: Prior to time of scheduled work, provide site access including any customer required escort, security clearance, safety training and badging for Vertiv service personnel.

l Equipment Access: Convenient access to the equipment covered by the Scope of Work. Prior to scheduled time of work, notify Vertiv service personnel of any special requirements for equipment access including lifts, ladders, etc.

l Shutdown: Service may require shutdown of load to ensure electrical connection integrity.

l Notification: If for any reason the work cannot be performed during scheduled time, notify Vertiv service personnel 24-hours prior to scheduled event.

TERMS AND CONDITIONS

Subject to all Terms & Conditions as noted in the Vertiv Terms & Conditions or the terms of a Master Agreement between the parties, if any, shall apply.

. Scope of Work | EXM All Startup 24x7

Rev: 05/15/2019 Page 3 of 3 .

EXM UPS ONLY

SITE ACCEPTANCE TESTING PACKAGE 24X7 WITH LOAD BANK

SERVICE SUMMARY

Feature Detail

On-Site Service Includes Standard Site Acceptance Testing of the system at the customer's convenience (excluding national holidays), within 150 miles of a Vertiv Services' Service Center.

Service Professional Performed by Vertiv factory-trained and authorized technician equipped with Vertiv Proprietary tools and software. Vertiv CEs and Vertiv Partners are the only approved OEM service providers for Vertiv products.

VERTIV PROPRIETARY SERVICE TOOLS AND SOFTWARE

Vertiv Customer Engineers (CEs) are the only authorized, factory- trained and OEM-supported service providers for Vertiv equipment with access to Vertiv’s proprietary service tools and software to ensure optimal equipment performance.

l Using proprietary software PPvis™, Paramset™, and WinSVT™ CEs apply Vertiv’s knowledge base to diagnose, configure and optimize your Vertiv equipment.

l Vertiv is the only authorized source for critical proprietary firmware updates providing your equipment the latest version of operational firmware to ensure equipment is running at optimal performance and efficiency levels.

l Vertiv exclusively enables:

l Access to OEM engineering support and product enhancements.

l Optimized methods of procedure for efficient service supported by proprietary documentation.

l Improved MTBR and MTTR.

l Root cause forensic analysis.

l Continual improvements with tested and certified updates for software and hardware improvements throughout the equipment’s lifecycle.

l CEs to be equipped with proprietary service documentation that provides access to the latest method of procedures and event data to return equipment online in the most efficient manner possible.

l Benchmarking against the entire service population to identify service trends and provide solutions rapidly or before they occur, reducing or eliminating customer events and outages.

l Vertiv Service CEs are trained in NFPA and OSHA best practices, and all processes and procedures strictly comply with NFPA 70A and 70E industry standards.

SERVICE PERFORMED

UPS Standard Site Acceptance Testing

1. Site Acceptance Testing performed after start-up is completed.

2. Testing to be performed per the Standard, published Vertiv Site Acceptance Testing procedures, including:

l Demonstrate alarms & functions (reference sample Test Report).

l Load testing (using resistive load bank) at 0%, 50%, and 100% load.

. Scope of Work | EXM All SAT with Load Bank

Rev: 11/07/2019 Page 1 of 2 .

l Record system parameters during load testing, including all voltages & currents, and power.

l Determine Voltage Regulation and Voltage Unbalance percentages.

l Transient testing using a power monitor (Astromed or equivalent), including load steps, UPS transfers, and UPS failure simulation.

l Battery Capacity Testing, recording total battery string DC voltage and current at 1-minute intervals until end of discharge.

l 4-Hour system burn-in, recording voltage and current parameters at 30-minute intervals.

l Options demonstration (as applicable).

l Final report provided for customer records.

3. Resistive load bank provided by Vertiv Services. Up to 200ft. of temporary cabling provided with the exception of suitcase style load banks for smaller systems, 100kW maximum, which are designed to be placed near the UPS.). Contact Vertiv Services if cable lengths longer than 200ft. will be required.

4. Test equipment provided by Vertiv Services, including oscilloscopes, digital multi-meters, ac and dc current clamps, power analyzer (Dranetz/BMI or equivalent), Power Monitor (AstroMed or equivalent), and handheld infrared scanning (Raytek ST2 or equivalent).

ASSUMPTIONS AND CLARIFICATIONS

Load-Fault testing, or destructive testing, is not performed as part of the Standard UPS Site Acceptance Testing. This type of testing should be arranged at the Vertiv factory before shipment.

Special site testing, beyond the standard published procedures, must be approved by Vertiv Services prior to the testing dates.

Temporary storage of the load bank, while on site and not in use, to be provided by the customer.

CUSTOMER RESPONSIBILITIES

In order to provide timely, accurate and thorough execution of the services described herein, Vertiv requests the following:

l Point of Contact: Provide an authorized point of contact(s), specific for the scope of work, for scheduling and coordination purposes.

l Scheduling: Make dates available for scheduling service. All visits must be requested 10 business days in advance of need by contacting the Vertiv Customer Resolution Center at 1-800-543-2378.

l Site Access: Prior to time of scheduled work, provide site access including any customer required escort, security clearance, safety training and badging for Vertiv service personnel.

l Equipment Access: Convenient access to the equipment covered by the Scope of Work. Prior to scheduled time of work, notify Vertiv service personnel of any special requirements for equipment access including lifts, ladders, etc.

l Shutdown: Service may require shutdown of load to ensure electrical connection integrity.

l Notification: If for any reason the work cannot be performed during scheduled time, notify Vertiv service personnel 24-hours prior to scheduled event.

TERMS AND CONDITIONS

Subject to all Terms & Conditions as noted in the Vertiv Terms & Conditions or the terms of a Master Agreement between the parties, if any, shall apply.

. Scope of Work | EXM All SAT with Load Bank

Rev: 11/07/2019 Page 2 of 2 .

ALL 3-PHASE MODELS

BURN-IN TESTING 8-HOUR 24X7

SERVICE SUMMARY

Feature Detail

On-Site Service Includes Burn-in Testing of the system, to meet the specification requirements, at the customer's convenience (excluding national holidays), within 150 miles of a Vertiv Services' Service Center.

Service Professional Performed by Vertiv factory-trained and authorized technician equipped with Vertiv Proprietary tools and software. Vertiv CEs and Vertiv Partners are the only approved OEM service providers for Vertiv products.

VERTIV PROPRIETARY SERVICE TOOLS AND SOFTWARE

Vertiv Customer Engineers (CEs) are the only authorized, factory- trained and OEM-supported service providers for Vertiv equipment with access to Vertiv’s proprietary service tools and software to ensure optimal equipment performance.

l Using proprietary software PPvis™, Paramset™, and WinSVT™ CEs apply Vertiv’s knowledge base to diagnose, configure and optimize your Vertiv equipment.

l Vertiv is the only authorized source for critical proprietary firmware updates providing your equipment the latest version of operational firmware to ensure equipment is running at optimal performance and efficiency levels.

l Vertiv exclusively enables:

l Access to OEM engineering support and product enhancements.

l Optimized methods of procedure for efficient service supported by proprietary documentation.

l Improved MTBR and MTTR.

l Root cause forensic analysis.

l Continual improvements with tested and certified updates for software and hardware improvements throughout the equipment’s lifecycle.

l CEs to be equipped with proprietary service documentation that provides access to the latest method of procedures and event data to return equipment online in the most efficient manner possible.

l Benchmarking against the entire service population to identify service trends and provide solutions rapidly or before they occur, reducing or eliminating customer events and outages.

l Vertiv Service CEs are trained in NFPA and OSHA best practices, and all processes and procedures strictly comply with NFPA 70A and 70E industry standards.

SERVICE PERFORMED

Burn-in Testing 8-Hour

1. Burn-in Testing performed after start-up is completed

2. Testing may be performed in conjunction with other Site Acceptance Testing on the same system.

. Scope of Work | Burn-in Testing 8-Hour 24x7 © 2019 Vertiv Co. All rights reserved.

Rev: 09/12/2019 Page 1 of 2 .

8 hour burn-in test will be performed at factory prior to shipment per project specification

3. Testing to be performed per accepted procedures, including:

l Full load (kW) test of the system (at 100% redundant or non-redundant load depending upon system configuration).

l Record voltage and current parameters at 30-minute intervals for the duration of the test.

l Perform regular infrared scans of the system components during the test (using a handheld Raytek ST2 or equivalent).

l Final report provided for customer records.

4. Test equipment provided by Vertiv Services, including digital multi-meters, ac current clamps, and handheld infrared scanning (Raytek ST2 or equivalent).

ASSUMPTIONS AND CLARIFICATIONS

Additional time required, for delays or circumstances beyond Vertiv control, may be billable to the customer. The customer will NOT be responsible for charges due to additional testing or re-testing requirements as a result of any warranty related repairs.

Reference the Vertiv Services Bill of Materials, and other Scopes of Work as applicable, for summaries of additional items included with this burn-in testing.

Resistive load bank may be provided by Vertiv Services, or by others. See Bill of Materials for clarification.

Load bank connection to system or switchgear is to be provided by others, typically the electrical contractor.

Infrared thermal imaging of the system, during burn-in testing, may be provided by Vertiv Services, or by others, as a separate service.

See Bill of Materials for clarification.

Any customer site visit is limited to eight (8) hours per visit. Any time beyond forty (40) hours/wk or eight (8) hrs/day or additional Startup visits will be billed separately.

CUSTOMER RESPONSIBILITIES

In order to provide timely, accurate and thorough execution of the services described herein, Vertiv requests the following:

l Point of Contact: Provide an authorized point of contact(s), specific for the scope of work, for scheduling and coordination purposes.

l Scheduling: Make dates available for scheduling service. All visits must be requested 10 business days in advance of need by contacting the Vertiv Customer Resolution Center at 1-800-543-2378.

l Site Access: Prior to time of scheduled work, provide site access including any customer required escort, security clearance, safety training and badging for Vertiv service personnel.

l Equipment Access: Convenient access to the equipment covered by the Scope of Work. Prior to scheduled time of work, notify Vertiv service personnel of any special requirements for equipment access including lifts, ladders, etc.

l Shutdown: Service may require shutdown of load to ensure electrical connection integrity.

l Notification: If for any reason the work cannot be performed during scheduled time, notify Vertiv service personnel 24-hours prior to scheduled event.

TERMS AND CONDITIONS

Subject to all Terms & Conditions as noted in the Vertiv Terms & Conditions or the terms of a Master Agreement between the parties, if any, shall apply.

. Scope of Work | Burn-in Testing 8-Hour 24x7

Rev: 09/12/2019 Page 2 of 2 .

ALL 3-PHASE MODELS

BASIC ON-SITE TRAINING BY CUSTOMER ENGINEER 24X7

SERVICE SUMMARY

Feature Detail

On-site Service Includes basic operational training of the system, after start-up is completed, at the customer's convenience (excluding national holidays), within 150 miles of a Vertiv's Service Center.

Online Portal Includes access to Vertiv Customer Services Network Online Internet portal.

Instructor Performed by Vertiv factory trained and authorized technician. Vertiv is the OEM service provider for Liebert products.

SERVICE PERFORMED

Basic On Site Training by Customer Engineer

1. Basic operational training provided after start-up is completed.

2. Operational training intended to familiarize the customer and their representatives with the equipment, display and menu tree navigation, alarm interpretation and actions, basic user maintenance, etc.

3. Training generally follows the Operation & Maintenance manual for the equipment provided.

4. No system or board level schematics of the equipment are provided as part of this training. Site electrical single-line diagrams are to be referenced as necessary for the training.

l Options demonstration (as applicable).

l Final report provided for customer records.

ASSUMPTIONS AND CLARIFICATIONS

Reference the Vertiv Services Bill of Materials for the number of labor days allotted to Basic On Site Training on this system.

Additional time required, for delays or circumstances beyond Vertiv control, may be billable to the customer.

No load banks or special test equipment are required to perform this basic level on site training as provided by the Customer Engineer.

Videotaping is not provided with this training or allowed by the customer. Vertiv Services does not allow videotaping of system training, inspection, testing, or troubleshooting activities.

Any customer site visit is limited to eight (8) hours per visit. Any time beyond forty (40) hours/wk or eight (8) hrs/day or additional Startup visits will be billed separately.

TERMS AND CONDITIONS

Subject to all Terms & Conditions as noted in the Vertiv Terms & Conditions or the terms of a Master Agreement between the parties, if any, shall apply.

. Scope of Work | Basic On Site Training CE 24x7 © 2017 Vertiv Co. All rights reserved.

Rev: 12/22/2018 Page 1 of 1 .