Attachment 08-283100 - Fire Alarm and Detection Systems.pdf
PDF 181 KB Posted
- Attached to
- Y1DA--460-22-700 | Construct EHRM Infras Upgrades | Wilmington, DE Federal contract opportunity
- Solicitation number
- 36C77625B0044_1
About this file
This document is a technical specification section for fire alarm and detection systems at the Wilmington VA Medical Center, part of the EHRM Infrastructure Upgrades project (Project No. 460-22-700). The specification provides detailed requirements for a comprehensive fire alarm system, including control panels, detection devices, notification appliances, and installation guidelines. Key technical specifications include:
The system will utilize a Honeywell-Notifier analog-addressable fire alarm platform with microprocessor-controlled intelligent reporting capabilities. It requires a Campus Ethernet IP Network with Resilient Ethernet Protocol, independent building fire alarm/voice communication systems, and full command and control from a campus command center. The installation must comply with multiple NFPA standards, including NFPA 72, and include specific features such as synchronized visual alarms, fire alarm temporal audible notification, emergency voice communication, and integration with building systems like HVAC, lighting controls, and access control. The specification mandates extensive testing, including sound pressure level measurements and voice alarm communication system intelligibility testing, with detailed requirements for measurement procedures and reporting.
View the file
Other files for this federal contract opportunity
Show all 22
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Wilmington VA Medical Center EHRM Infrastructure Upgrades
Project No. 460-22-700 June 30, 2025
Fire Alarm and Detection Systems 28 31 00 - 1
SECTION 28 31 00
FIRE ALARM AND DETECTION SYSTEMS
PART 1 - GENERAL
1.1 SECTION INCLUDES
A. Fire alarm and detection systems.
1.2 RELATED WORK
A. Section 26 05 53 - Electrical Identification: Refer to electrical identification for color and identification labeling requirements.
1.3 QUALITY ASSURANCE
A. Manufacturer: Company specializing in smoke detection and fire alarm systems with ten years' experience.
B. Installer: A factory-authorized Electrical or Security Contractor licensed with the State and local jurisdiction with five years' experience in the design, installation, and maintenance of fire alarm systems by that manufacturer.
C. Qualifications: The person managing/overseeing the preparation of shop drawings and the system installation/programming/testing shall be trained and certified by the system manufacturer and shall be Fire Alarm Certified by NICET, minimum Level 2. This person's name and certification number shall appear on the start-up and testing reports.
1.4 REFERENCES
A. ASME A17.1 - Safety Code for Elevators and Escalators.
B. NFPA 20 - Standard for Centrifugal Fire Pumps.
C. NFPA 70 - National Electrical Code (NEC).
D. NFPA 72 - National Fire Alarm and Signaling Code.
E. NFPA 101 - Life Safety Code.
F. UL 2017 - General Purpose Signaling Devices and Systems.
G. UL 217 / 268 - Standard for Smoke Alarms / Smoke Detectors for Fire Alarm Systems.
H. UL 2572 - Control and Communication Units for Mass Notification Systems.
I. 2015 Fire Code.
28 31 00 - 2
1.5 EXTRA MATERIALS
A. Furnish extra materials that match products installed and that are packaged with protective covering for storage and identified with labels describing contents.
1. Provide quantity equal to 2 percent (2%) of amount of each type installed, but no less than two (2) units of each type.
a. Smoke and heat detectors, manual pull stations, duct smoke detectors, monitor modules, control modules and relays.
b. Notification Appliances: Speakers, speaker strobes, and strobes.
2. Keys: The installing contractor shall collect all equipment spare keys provided with each lockable or resettable device/cabinet minimum of two (2) sets each and shall turn over to the Owner upon completion.
3. All spare parts shall be housed in metal cabinet labeled "Fire Alarm Spare Parts."
1.6 DELIVERY, STORAGE, AND HANDLING
A. Deliver products to site under provisions of Section 26 05 00.
B. Store and protect products under provisions of Section 26 05 00.
1.7 REGULATORY REQUIREMENTS
A. System: UL or FM Global listed.
B. Conform to requirements of NFPA 101.
C. Conform to requirements of Americans with Disabilities Act (ADA).
D. Conform to UL 864 Fire Alarm, UL 1076 Security, UL2017 General Signaling, and UL 2572 Mass Notification Communications.
1.8 SYSTEM DESCRIPTION
A. Performance Statement: This specification section and the accompanying fire alarm specific design documents describe the minimum material quality, required features, and operational requirements of the system. These documents do not convey every wire that must be installed and every equipment connection that must be made. Based on the equipment described and the performance required of the system, as presented in these documents, the Vendor and the Contractor are solely responsible for determining all wiring, programming and miscellaneous equipment required for a complete and operational system.
28 31 00 - 3
B. This section of the specifications includes the furnishing, installation and connection of the microprocessor controlled, intelligent reporting, fire alarm equipment required to form a complete coordinated system that is ready for operation. It shall include, but is not limited to, alarm initiating devices, control panels, auxiliary control devices, annunciators, power supplies, and wiring as indicated on the drawings and specified herein.
C. Extending the Existing Fire Alarm System: Provide all items, components, devices, hardware, software, programming, expansion components, conduit, wiring etc. needed to extend the existing fire alarm system. This includes, but is not limited to, additional power supplies, initiating devices and circuits, signaling devices and circuits, monitoring devices and circuits, auxiliary control and related devices such as, door holders and their control, smoke damper control, fan shutdown, etc. The existing fire alarm system shall be extended such that the existing fire alarm system's functionality, integrity and annunciation shall be equivalent to pre-construction conditions, unless noted otherwise.
The functionality and integrity shall be maintained during construction. The entire system shall be able to be completely reset from any single reset location point. The entire system shall be annunciated at any annunciation location.
D. Extending the Existing SIMPLEX Fire Alarm System: The existing control panel shall remain and shall be operational throughout construction. The system shall only be disabled to make new connections and to modify the programming. A fire watch shall be provided for all areas affected during outages. All system outages must be scheduled with the Owner at least one week prior. Individual devices may be disabled as needed based on construction activities to reduce the potential for false alarms, but all devices must be operational when the Contractor is not physically on site. New initiating devices may be connected to the existing signaling line circuits where capacity is available.
Provide additional signaling line circuits as needed based on existing and new device quantity, including replacement of existing panel components. Provide new notification circuits to serve the new devices, including all necessary power supplies, amplifiers, batteries, and 120-volt input circuits. All new devices shall be programmed to provide the same sequence of operation as the existing devices of the same type, unless noted otherwise.
E. Fire Alarm System: NFPA 72; Automatic and manual fire alarm system, non-coded, analog-addressable with automatic sensitivity control of certain detectors, multiplexed signal transmission.
F. Campus Ethernet IP Network: A complete fire alarm and mass notification Ethernet network shall be provided. The network shall be Class X, Resilient Ethernet Protocol (REP) 100BaseTX / 100 Mbps that shall be able to operate with any single break and self-restoring network communications. Each building shall contain an independent building fire alarm / voice communications system, with full command and control from the campus command center. In no case shall read only network annunciation be acceptable as the only networking function.
28 31 00 - 4
G. In-Building Network: A complete fire alarm system network shall be provided. Provide quantity of control panels as indicated on the drawings. The network shall be a Style 7 token ring, peer-to-peer network. The network shall be characterized by simultaneous or sequential transmission, or both, and reception of multiple signals on a signaling line circuit or communication channel. The distributed intelligent characteristic of the network shall provide for all nodes independently making pertinent system decisions with no need for a central controller. Each node shall be capable of independent operation should loss of network communications occur. In no case shall read-only network annunciation be acceptable as the only networking function.
H. Voice Communication: The facility shall have an emergency voice alarm communication system. The digitized recorded voice message shall notify occupants that a fire condition has been reported. Emergency manual voice override shall be provided.
I. System Supervision: Provide electrically supervised system, with supervised Signal Line Circuit (SLC) and Notification Appliance Circuit (NAC). Occurrence of single ground or open condition in initiating or signaling circuit places circuit in TROUBLE mode.
Component or power supply failure places system in TROUBLE mode.
J. Alarm Reset: Key-accessible RESET function resets alarm system out of ALARM if alarm initiating circuits have cleared.
K. Lamp Test: Manual LAMP TEST function causes alarm indication at each zone at fire alarm control panel and at annunciator panels.
L. Drawings: Only device layouts and some equipment have been shown on the contract drawings. Wiring and additional equipment to make a complete and functioning system has not been shown but shall be submitted on the shop drawings.
1.9 PROJECT RECORD DOCUMENTS
A. Submit documents under the provisions of Section 26 05 00.
B. Include location of end-of-line devices.
C. Provide a CAD drawing of each area of the building (minimum scale of 1/16" = 1'-0") showing each device on the project and its address. The devices shall be shown in their installed location and shall be labeled with the same nomenclature as is used in the fire alarm panel programming.
D. Submit test results of sound pressure level (dBA) and intelligibility (STI) with the rooms tested designated on the floor plan. Notification devices shall have the tap wattage designated.
28 31 00 - 5
1.10 OPERATION AND MAINTENANCE DATA
A. Submit data under provisions of Section 26 05 00.
B. Include operating instructions, and maintenance and repair procedures.
C. Include results of testing of all devices and functions.
D. Include manufacturer's representative's letter stating that system is operational.
E. Include the CAD floor plan drawings.
F. Include shop drawings as reviewed by the Architect/Engineer and the local Authority Having Jurisdiction.
1.11 WARRANTY
A. Provide one (1) year warranty on all materials and labor from Date of Substantial Completion.
B. Warranty requirements shall include furnishing and installing all software upgrades issued by the manufacturer during the one (1) year warranty period.
1.12 ANNUAL INSPECTION/TESTING AND SERVICE CONTRACT
A. Provide cost to furnish service, inspect, and test all devices of the fire alarm system per the requirement of NFPA for one (1) year, starting one year after the Date of Substantial Completion. Submit written reports of inspection testing per NFPA 72, Chapter 14.
B. Provide an alternate cost for a complete inspection/testing and service/maintenance contract for the fire alarm system for one (1) year two (2) years, starting one year after the Date of Substantial Completion. Submit sample contract terms and conditions for review with shop drawings.
C. The Owner may enter into a contract directly with the vendor after shop drawing submittals. This specification is not a contract between the Owner and the vendor to perform these services.
28 31 00 - 6
PART 2 - PRODUCTS
2.1 MANUFACTURERS
A. Honeywell – Notifier
2.2 EXISTING: FIRE ALARM CONTROL PANEL (FACP)
A. Control Panel: Modular, power-limited electronic design. Provide wall-mounted enclosure as shown on plans. Enclosure shall be minimum 0.060 steel with provisions for electrical conduit connections into the sides and top. The door shall provide a key lock and shall include a glass or other transparent opening for viewing of all indicators.
B. Central Processing Unit:
1. The central processing unit (CPU) shall communicate with the monitor and control all other modules in the panel. Removal, disconnection or failure of any control panel module shall be detected and reported to the CPU.
2. The CPU shall execute all control-by-event programs for specific action to be taken if a designated situation is detected in the system. A real-time system clock for time annotations on the display and printer shall be included.
3. All power for the unit shall be supervised and supplied by the FAP.
C. Display:
1. The board shall provide all controls and indicators used by the system operator and may also be used to program all control panel parameters.
2. The board shall provide an alphanumeric array for display of custom alphanumeric labels for all addressable points. It shall also provide indicators for AC Power, System Alarm, System Trouble, Display Trouble and Signal Silence.
3. Displayed descriptions of addressable points shall include actual room names/numbers selected by the Owner. This information shall be obtained prior to programming. Room names/numbers shown on floor plans shall not be used.
4. The board shall provide a touch key-pad with control capability to command all system functions and entry of any alphanumeric information. Twenty different passwords with four levels of security shall be supported to prevent unauthorized manual control or programming.
D. Memory: The CPU and display interface board shall be augmented by non-volatile field programmable memory. EPROM memory will also be allowed provided the memory is burned in with minimum expansion capability equal to the total system capacity of the panel. Memory shall not be lost upon primary and secondary power failure.
28 31 00 - 7
E. Serial Interface Board: The board shall provide interfaces to a printer, LCD display and other monitoring devices through RS-232 connections. The minimum operational distance between the board and the peripheral devices shall be 500 feet. Up to three (3) RS-232 outputs shall be supported.
F. Power Supply:
1. Input power shall be 120 VAC, 60 Hertz. Output power shall be as noted on the device specifications and drawings. Each component of the fire alarm system requiring 120 VAC input power shall be served from a dedicated emergency branch circuit. Provide two #12 conductors and one #12 ground in 3/4" conduit to a dedicated 20A/1P circuit breaker with a red handle and a manufacturer's standard handle lock-on device. Identify/label breaker and branch circuit in accordance with NFPA requirements and Specification Section 26 05 53.
2. Adequate to supply 125% of all control panel and peripheral power needs as well as 125% of power required for all external audio-visual devices. The power supply may be increased as needed by adding additional modular expansion power supplies. Over-current protections shall be provided on all power outputs.
3. All power supplies shall be designed and installed to meet UL and NFPA requirements for power-limited operation on all external initiating and indicating circuits.
4. The power supply shall provide integral charger for use with internal batteries.
Battery capacity shall be sufficient for operation of the entire system for 24 hours in a non-alarm state followed by alarm mode for 15 minutes, plus 25% spare capacity for future devices.
G. Surge Protection:
1. All fire alarm control panels, NAC panels, etc. shall be provided with a surge protection device (SPD). The SPD shall be UL listed to Standard 1449 Rev 3. The unit should be clearly labeled in accordance with Identification Section 26 05 53.
The SPD shall have thermal fuses to protect against fire in short circuit conditions.
The unit shall provide visual indication that the unit is protecting and functioning.
2. Any communications or signaling circuits associated with the fire alarm system, which leave or enter a facility, shall be provided with a surge protection device.
The devices shall be as recommended by the fire alarm system manufacturer.
28 31 00 - 8
2.3 SIGNALING LINE CIRCUIT DEVICES
A. Combination Devices: Subscripts identify combination type devices when applicable.
Contractor shall provide the combination device or provide multiple device(s) to meet the functionality when the manufacturer does not offer the required functionality with a single device.
B. Signal Line Device(s):
1. Subscripts: Subscripts are used to define the device type, installation, and identify the device with a specific sequence of operation.
a. Device type as follows:
1) W = Weather Proof
2) WG = Wire guard is required
3) Candela Ratings:
a) ## = 15 Candela, 30 Candela; 75 Candela; 110 Candela; 177 Candela Shall be field adjustable.
b) CD = NICET select Candela rating as required to provide full coverage of the space, or per plans.
b. Sequence of operation as follows:
1) A = Atrium
2) CA = Clean Agent System
3) CR = Computer Room
4) E = Elevator Recall
5) D = HVAC Control
6) DH = Door Hold Release
7) DIPS = Dual Interlock Pre-Action System
8) FD = Fire Door Release
9) MP = Medical Procedure Room
10) S = Sleeping / Patient Room
11) SW = Stairwell
C. FA-120; Smoke Detectors:
1. Subscripts are used to define the device type, installation, and identify the device with a specific sequence of operation.
a. Device types as follows:
1) Blank = Photoelectric
2) AT = Attic (located in)
3) BR = Beam Receiver
4) BT = Beam Transmitter
5) CO = Combination Smoke / Carbon Monoxide
28 31 00 - 9
6) COH = Combination Smoke / Carbon Monoxide / Heat
7) COS = Combination Smoke / Carbon Monoxide / Strobe
8) H = Combination Smoke / Heat Detectors
9) ION = Ionization Type
10) ID = In-Duct Detector
11) SA = Stand Alone with Sounder
12) SB = Sounder Base
13) SV = Stand Alone with Sounder and 177 Candela Strobe
2. (BLANK) Analog Photoelectric Type Sensor: Shall use the photoelectric principle to measure smoke density and send data to the control panel representing the analog level of smoke density measured.
3. (BR) and (BT) Projected Beam Type Detectors: This device shall utilize photoelectric analog smoke sensor technology. Provide with transmitter and associated receiver. Microprocessor-based detector shall provide a minimum of eight sensitivity levels, temperature and dirt compensation, and automatic gain control. Sensor to contain beam alignment adjustments and receiver calibration.
a. Detector shall connect directly to an SLC loop or shall be provided with multiple monitor modules, as required, to connect to the SLC loop and for monitoring alarm and trouble output contacts. The detector shall be provided complete with all mounting hardware provided and installed where indicated on the drawings.
b. Dual alarm and power indicators shall be provided that flash under normal conditions and remain continuous under alarm or trouble conditions. Remote indicator terminals shall be provided.
c. Provide with remote indicator panel providing LED indications of alarm and trouble.
4. (CO) Combination Smoke / Carbon Monoxide:
a. Multi-criteria sensor for photoelectrical smoke sensing and carbon monoxide (CO) detection. Carbon monoxide electrolytic sensing module shall provide toxic gas sensing to UL2034 and UL2075 standards.
b. The combined photoelectric smoke detection CO module shall have separate sensors that adjust the detection profile in response to the input from the sensors.
c. The combined photoelectric smoke detection / CO module shall have selectable modes of operation for OSHA compliant toxic gas sensing, enhanced fire sensing, and nuisance alarm reduction mode.
d. The detector shall use only one address on the SLC.
e. CO sensor cartridge element shall be field replaceable.
28 31 00 - 10
5. (IN) In-Duct Smoke Detectors:
a. Analog Photoelectric Type Sensor: Shall use the photoelectric principle to measure smoke density and send data to the control panel representing the analog level of smoke density measured.
b. Analog Ionization Type Sensor: Shall use the dual chamber ionization principle to measure smoke density and send data to the control panel representing the analog level of smoke density measured.
c. Low Flow Type: Listed for use in duct with 0-2000 feet per minute velocity.
d. Each smoke detector shall connect directly to an SLC loop.
e. Each detector shall be mounted, where shown on the drawings, on a twist-lock base with all mounting hardware provided to match the duct application. Provide a two-piece head/base design.
f. Each detector shall have a manual switching means to set the internal identifying code (address) of that detector, which the control panel shall use to identify its address with the type of sensor connected.
g. Provide a remote LED indicator device (FA-240/241), mounted in ceiling directly below detector with a single-gang faceplate labeled: Duct Smoke Detector.
6. (SA) Stand Alone with Horn:
a. 120 VAC with 9V battery backup (batteries supplied by Contractor), photoelectric type, integral test switch, Form A/Form C contacts, 90 dB piezo solid-state horn, low/missing battery alarm, pulsing LED sensing chamber, insect screen, LED condition indicator, UL 217 listed.
b. Approved Manufacturers:
1) Gentex 9120 Series
2) System Sensor
3) Fenwall
4) Gamewell
5) Kidde
7. (SB) Analog Photoelectric Type Sensor with Sounder Base
8. (SV) Stand Alone with Sounder and 177 Candela Strobe:
a. 120 VAC with 9V battery backup (batteries supplied by Contractor), photoelectric type, integral 177 Candela strobe, integral test switch, Form A/Form C contacts, 90 dB piezo solid-state horn, low/missing battery alarm, pulsing LED sensing chamber, insect screen, LED condition indicator, UL 217 listed.
b. Approved Manufacturers:
1) Gentex 9120 Series
2) System Sensor
3) Fenwall
4) Gamewell
5) Kidde
28 31 00 - 11
9. Each smoke detector shall connect directly to an SLC loop, unless listed as stand alone.
10. Each detector shall be mounted, where shown on the drawings, on a twist-lock base with all mounting hardware provided. Provide a two-piece head/base design.
11. Each detector shall have a manual switching means to set the internal identifying code (address) of that detector, which the control panel shall use to identify its address with the type of sensor connected.
12. Dual alarm and power indicators shall be provided that flash under normal conditions and remain continuous under alarm or trouble conditions. Remote indicator terminals shall be provided. Provide a remote LED indicator device if detector is not visible from a floor standing position.
13. A test means shall be provided to simulate an alarm condition.
14. Where operation is noted as required below 32°F and/or above 120°F, a conventional device shall be installed with a unique monitor module located in the nearest available location with maintained temperatures between 32°F and 120°F.
15. Audible Sounder Detector Base for Sleeping Room Applications:
a. The audible base shall sound an alarm in the local room in UL2017 operation and UL484 for general evacuation. The unit shall be programmable by the main control panel for the duration of operation.
b. The audible sounder base shall sound Temporal 3 (fire) or Temporal 4 (CO alarm) and be at 75 dB at 10 feet.
D. FA-130; Manual Pull Stations:
1. Manual pull station, addressable, single action with plastic breakrod, reset key lock, semi-flush mount, red high abuse plastic or cast metal construction with white lettering. Provided with all necessary mounting hardware. Use surface mount only on precast concrete or structure.
2. Manual stations shall connect directly to an SLC loop. Stations shall provide address setting means using rotary decimal or DIP switches.
3. Where operation is noted as required below 32°F and/or above 120°F, a conventional device shall be installed with a unique monitor module located in the nearest available location, with maintained temperatures between 32°F and 120°F.
E. FA-160; Monitor Modules:
1. Subscripts are used to define the device type, installation, and identify the device with a specific sequence of operation.
a. Device types as follows:
1) Blank = Refer to Plans
2) KB = Knox Box Monitor
28 31 00 - 12
2. Monitor Module shall connect directly to an SLC loop and receive power from a separate 24 VDC circuit. It shall interface initiating devices with the control panel using Style D or Style B circuits. Contractor Option: Use an interface module (2-wire operation) for Style B circuits connected to normally-open dry contacts, such as a flow switch.
3. The module shall be mounted in an enclosure located in an accessible service location as near as possible to the device(s) being monitored, or where shown on the drawings. All mounting hardware shall be provided.
4. The module shall supply the required power to operate the monitored device(s).
5. The module shall provide address setting means using rotary decimal or DIP switches.
F. FA-161; Addressable Control Module:
1. Subscripts are used to define the device type, installation, and identify the device with a specific sequence of operation.
a. Device types as follows:
1) Blank = Refer to Plans
2) DH = Door Hold Open
3) PD = Hold Open Override
2. Relay that represents an addressable control point used primarily for the control of auxiliary devices as indicated on the drawings. Contractor to provide additional child relay(s), as required, rated for the electrical load being controlled (Contractor to match voltage, amps, etc.).
3. Relay shall connect directly to an SLC loop and receive power from a separate 24 VDC circuit.
4. The relay shall be mounted in an enclosure located in an accessible service location as near as possible to the device(s) being controlled, unless otherwise shown on the drawings. All mounting hardware shall be provided.
5. The relay shall supply 24 VDC power to the device(s) being controlled, unless otherwise indicated on the drawings.
28 31 00 - 13
2.4 NOTIFICATION APPLIANCE DEVICES
A. Combination Devices: Subscripts identify combination type devices when applicable.
Contractor shall provide the combination device or provide multiple device(s) to meet the functionality when the manufacturer does not offer the required functionality with a single device.
B. Notification Appliance Device(s):
1. Subscripts: Subscripts are used to define the device type, installation, and identify the device with a specific sequence of operation.
a. Device types as follows:
1) W = Weather Proof
2) WG = Wire guard is required
3) Candela Ratings:
a) ## = 15 Candela; 30 Candela; 75 Candela; 110 Candela; 177 Candela
b) CD = NICET designer shall select Candela rating as required to provide full coverage of the space.
b. Sequence of operation as follows:
1) S = Sleeping / Patient Room
C. Notification Device(s):
1. Wall Mounted: Red housing with white, White housing with red lettering or pictogram.
2. Ceiling Mounted: Red housing with white, White housing with red lettering or pictogram.
D. FA-200; Visual Alarm Devices:
1. Wall or ceiling mounted, refer to plans.
2. High intensity (Candela rating as scheduled on the drawings) xenon strobe or equivalent under a lens. Candela rating shall be visible from exterior of the device.
3. The maximum pulse duration shall be 0.2 seconds with a maximum duty cycle of
40%. The flash rate shall be 1 Hz. Where more than two strobes are visible from any one location, the fire alarm visual devices shall be synchronized.
4. Device, housing, and backbox shall be UL listed for fire alarm/emergency applications.
28 31 00 - 14
5. (W) Weatherproof Visual Notification Device: High intensity strobe, square housing, 75 Candela rating, suitable for wet locations. Provide with weatherproof back box.
a. Mounting: Semi-flush wall.
b. Conduit shall not be exposed.
E. FA-211; Combination Audio Chime and Visual Alarm Device:
1. Wall or ceiling mounted, refer to plans.
2. Combine audio and visual components into a single device. Refer to the corresponding paragraphs above for requirements of each component.
3. (W) Weatherproof Audio/Visual Notification Device: Electronic horn with high intensity strobe, square housing, 75 Candela, suitable for wet locations. Provide with weatherproof back box.
a. Mounting: Semi-flush wall.
b. Conduit shall not be exposed.
F. FA-220; Audio (Speaker) Alarm Devices:
1. Wall or ceiling mounted, refer to plans.
2. Sound rating shall be dependent on the tap (wattage) setting. Tap settings shall be available in 3 dBA increments. A minimum of four (4) tap settings should be available to allow field adjustment of the sound output across a minimum range of 78 to 87 dBA, 400Hz to 4KHz (6 dBA cutoff) frequency range. Speakers shall operate on a 25-volt or 70-volt RMS system, unless otherwise noted on drawings.
3. Speakers shall clearly reproduce a signal consisting of a live or prerecorded human voice and with voice intelligibility.
4. Speaker, housing, and backbox shall be UL listed for fire alarm/emergency applications.
5. Wall Mounted: Speaker, square housing, flush or semi-flush mounted.
6. Ceiling Mounted: 4" speaker, round housing, flush mounted (provide tile bridge where applicable).
G. FA-221; Combination Audio (Voice) and Visual Alarm Device:
1. Wall or ceiling mounted, refer to plans.
2. Combine speaker and visual components into a single device. Refer to the corresponding paragraphs above for requirements of each component.
3. (W) Weatherproof Voice/Visual Notification Device: Speaker with high intensity 75
Candela rated strobe. 25-volt or 70-volt VRMS with a minimum of four (4) tap settings which shall allow field adjustment of the sound output across a minimum range of 78 to 87 dBA (UL 1480), 400 Hz to 4 KHz (6dBA cutoff) frequency range.
a. Mounting: Semi-flush wall.
b. Conduit shall not be exposed.
28 31 00 - 15
H. FA-232; Emergency Visual Alarm Device:
1. Wall or ceiling mounted, refer to plans.
2. High intensity xenon strobe or equivalent shall have a clear lens for fire alarm annunciation strobe and an amber lens for the alert strobe. Candela rating shall be visible from exterior of the device.
3. The maximum pulse duration shall be 0.2 seconds with a maximum duty cycle of 40%. The flash rate shall be 1 Hz. Where more than two strobes are visible from any one location, the fire alarm visual devices shall be synchronized.
4. Device, housing, and backbox shall be UL listed for fire alarm/emergency applications.
5. (W) Weatherproof Visual Notification Device: High intensity strobe, square housing, 75 Candela rating, suitable for wet locations. Provide with weatherproof back box.
a. Mounting: Semi-flush wall.
b. Conduit shall not be exposed.
2.5 WIRING
A. Fire alarm wiring/cabling shall be furnished and installed by the Contractor in accordance with the manufacturer's recommendations and pursuant to National Fire Codes. Cabling shall be UL listed and labeled as complying with the Electrical Code for power-limited fire alarm signal service.
B. Fire Alarm Cable:
1. Manufacturers:
a. Comtran Corp.
b. Helix/HiTemp Cables, Inc.
c. Rockbestos-Suprenant Cable Corp.
d. West Penn Wire/CDT.
e. Radix.
28 31 00 - 16
PART 3 - EXECUTION
3.1 SEQUENCES OF FIRE ALARM OPERATION
A. General:
1. Refer to the Fire Alarm Operation Matrix on the drawings for basic requirements and system operation.
2. The GUI/graphic annunciator shall display audible and visual alarms. The device activated shall be immediately displayed on a CAD floor plan at approximately 1/8" scale. Visual indication shall further indicate the device by utilizing an easily recognized color change of the symbol. The use of flashing symbols is encouraged.
3. All system output programs assigned via control-by-event equations to be activated by the particular point in alarm shall be executed, and the associated system outputs (alarm notification appliances and/or relays) shall be activated.
B. Panel/Annunciator Alarm, Trouble, Supervisory Indication:
1. Appropriate system Alarm, Trouble, or Supervisory LED shall flash at the control panel, transponder, and annunciator locations.
2. A local signal in the control panel and the color graphics PC shall sound.
3. The LCD display shall indicate all information associated with the condition, including the name of the item, type of device and its location within the protected premises.
4. Printing and history storage equipment shall log the information associated with the fire alarm control panel (FAP) condition, along with the time and date.
5. Transmit the appropriate signal (supervisory, trouble, alarm) to the central station via the digital communicator.
6. Transmit the appropriate signal (supervisory, trouble, alarm) to the building automation system via addressable relays tied to contact monitors on the system.
C. Audible Alarms Sequence:
1. Audible alarms throughout the building shall sound.
2. Audible alarms within the floor or fire/smoke compartment where the emergency signal originated and in adjacent areas shall sound.
3. Separate voice announcements shall be played in different fire compartments depending on proximity to the device that initiated the alarm. Refer to the requirements above for the Voice Command Center programming.
D. Visual Alarms Sequence:
1. Visual alarms throughout the building shall flash.
2. Visual alarms within the floor or fire/smoke compartment where the emergency signal originated and in adjacent areas shall flash.
28 31 00 - 17
E. Fire Protection Electric Sprinkler Bell Sequence:
1. The fire alarm shall utilize an addressable relay to energize the electric sprinkler bell upon activation of the flow switch.
F. Computer Room System Sequence:
G. HVAC System Sequence:
H. Smoke Damper Control Sequence:
1. The fire alarm system shall utilize an addressable relay to open the power connection to smoke or fire/smoke dampers and allow them to close. Coordinate other requirements with damper installer.
2. Where a damper is in a main air duct, where closure of that single damper will entirely block airflow in the duct system, the smoke damper sequence shall also initiate the AHU and mechanical fan shutdown sequence for the affected unit.
3. The AHU and mechanical fan shutdown sequence shall be initiated only when ALL the dampers associated with that unit or mechanical fan are closed. Otherwise, the AHU or mechanical fan shall continue to serve other areas.
4. Smoke and fire/smoke dampers located in branch ductwork shall be closed individually or in groups, as identified on the plans.
5. All smoke and fire/smoke dampers shall be closed throughout the building.
I. AHU and Mechanical Fan Shutdown Sequence:
1. The fire alarm system shall utilize addressable relays to de-energize all AHU motor controllers and mechanical fans. Coordinate other requirements with HVAC installer.
2. The fire alarm system shall directly shut down the AHU or mechanical fan through the local HVAC control device (i.e., variable frequency drive or motor starter).
3. Where a facility has more than one AHU or mechanical fan, each shall be shutdown individually based on input from initiation devices in the area served by the unit or designated for each air distribution system.
4. All AHUs and mechanical fans shall be shutdown simultaneously throughout the building.
J. Lighting Control Override Sequence: Coordinate requirements between the fire alarm and lighting control system.
1. The fire alarm shall use addressable output relay(s) to remotely override the local lighting control sequences of operation for egress, emergency, and life safety designated lighting. Coordinate the location and quantity of addressable output relays required with the lighting control shop drawings. Addressable fire alarm relays will be required, but not limited to, at the following locations:
a. Centralized, architectural, and theatrical lighting control panels.
b. Branch circuit lighting control zones, relays, automatic load control relays
(ACLR), branch circuit emergency lighting transfer switches (BCELTS).
28 31 00 - 18
K. Access Control Override Sequence:
1. The fire alarm shall use addressable output relay(s) to signal the access control panel.
2. Refer to the access control specifications for requirement upon fire alarm signal.
The fire alarm shall initiate an override of delayed egress doors.
3.2 INSTALLATION
A. Install system in accordance with manufacturer's instructions and referenced codes.
B. Fire Alarm Control Panel:
1. Install the control panel where shown on the drawings.
2. All expansion compartments, if required, shall be located at the control panel.
3. Install the voice command center and fire command center in the location as indicated on the drawings. This location should be primary fire department "attack" location. Coordinate with the local fire department prior to submitting shop drawings.
4. The fire alarm voice prerecorded messages shall be verified by the Contractor, as approved by the Owner, prior to the shop drawing submittal process.
C. Devices:
1. General:
a. All ceiling-mounted devices shall be located where shown on the reflected ceiling and floor plans. If not shown on the reflected ceiling or reflected floor drawings, the devices shall be installed in the relative locations shown on the floor drawings in a neat and uniform pattern.
b. All devices shall be coordinated with luminaires, diffusers, sprinkler heads, piping and other obstructions to maintain a neat and operable installation.
Mounting locations and spacing shall not exceed the requirements of NFPA 72.
c. Where the devices are to be installed in a grid type ceiling system, the detectors shall be centered in the ceiling tile.
d. The location of all fire alarm devices shall be coordinated with other devices mounted in the proximity. Where a conflict arises with other items or with architectural elements that will not allow the device to be mounted at the location or height shown, the Contractor shall notify the Architect/Engineer to coordinate a different acceptable location adjust location of device so that new location meets all requirements in NFPA 72 and all applicable building codes.
28 31 00 - 19
2. Per the requirements of NFPA, detector heads shall not be installed until after the final construction cleaning unless required by the local Authority Having Jurisdiction (AHJ). If detector heads must be installed prior to final cleaning (for partial occupancy, to monitor finished areas or as otherwise required by the AHJ), they shall not be installed until after the fire alarm panel is installed, with wires terminated, ready for operation. Any detector head installed prior to the final construction cleaning shall be removed and cleaned prior to closeout.
3. Protection of Fire Alarm System:
a. A smoke detector shall be installed within the vicinity of the main fire alarm panel and every NAC extender panel per NFPA 72. A heat detector may be substituted when a smoke detector is not appropriate for the environment of installation.
4. Analog Smoke and Heat Detectors:
a. In elevator shafts and elevator equipment rooms, provide a heat detector for elevator shutdown within 2' of every sprinkler head. Coordinate with fire protection contractor.
5. Duct-type Analog Smoke Detectors:
a. Duct-type analog smoke detectors shall be installed on the duct where shown on the drawings and details. The sampling tubes shall be installed in the respective duct at the approximate location where shown on the electrical drawings to meet the operation requirements of the system.
b. All detectors shall be accessible.
c. Duct-type detectors shall be installed according to the manufacturer's instructions.
6. In-Duct Analog Smoke Detectors:
a. In-duct analog smoke detectors shall be installed in the duct where shown on the drawings and details. The devices shall be installed in the respective duct at the approximate location where shown on the electrical drawings to meet the operation requirements of the system.
b. All detectors shall be accessible.
7. Heat Detector, Linear Wire Type:
a. Install detection wire within 20 inches of the underside of building roof, floor, or as recommended by the manufacturer.
b. The protected area shall not exceed 4,000 square feet per zone. Provide a separate zone for areas divided by fire/smoke rated walls.
8. Manual Pull Stations:
a. Stations shall be located where shown and at the height noted on the drawings.
28 31 00 - 20
9. Addressable Relays and Monitor Modules:
a. Modules shall be located as near to the respective monitor or control devices as possible, unless otherwise indicated on the drawings.
b. All modules shall be mounted in or on a junction box in an accessible location.
c. Where not visible from a floor standing position, a remote indicator shall be installed to allow inspection of the device status from a local floor standing location.
10. SLC Loop Isolation Modules:
a. Isolation modules shall be installed to limit the number of addressable devices that are incapacitated by a circuit fault.
b. Install all Isolation Modules within the fire alarm control panel, unless otherwise indicated on the drawings. Refer to the fire alarm riser diagram for requirements. Refer to the floor plans for areas served by separate isolation modules.
11. Notification Appliance Devices:
a. Devices shall be located where shown on the drawings.
b. Wall-mounted audio, visual and audio/visual alarm devices shall be mounted as denoted on the drawings.
c. Where ceiling mounted visual alarm devices or combination audio/visual alarm devices are shown where the ceiling is greater than 30'-0" high, they shall be stem mounted so that the entire unit is below 30'-0". This does not apply to audio-only alarm devices.
D. Wiring:
1. Fire alarm wiring/cabling shall be provided by the Contractor in accordance with the manufacturer's recommendations and pursuant to National Fire Codes.
2. Wiring shall be installed in conduit. Refer to Identification Section 26 05 13 for color and identification requirements.
3. Wiring shall be installed in conduit from device to above accessible ceilings.
Exposed plenum-rated cable (FPLP) shall be used above accessible ceilings supported every 4 feet or run in cable trays (if applicable) maintaining a minimum of 5-inches clearance from all lighting ballasts. Fire alarm cabling shall not be installed in the same bridle rings or cable trays designated for the cabling of other systems.
4. All junction boxes with SLC and NAC circuits shall be identified on cover. Refer to Identification Section 26 05 13 for color and identification requirements.
28 31 00 - 21
5. Partial evacuation or relocation of occupants is the standard operating procedure for this facility in the event of an alarm. Therefore, all notification appliance circuits (NAC), including circuits serving NAC extender panels and other network communication circuits, must be installed and protected in accordance with the "circuit survivability" requirements described in NFPA 72. Contractor shall maintain the following:
a. NACs serving separate evacuation signaling zones shall be routed separately such that they are no less than 4 feet apart when run horizontally and 1 foot apart when run vertically. They may come simultaneously only within 10 feet of the control panel.
b. NACs passing through other evacuation signaling zone(s) shall be installed in conduit and routed through the 2-hour fire-rated chase(s) or enclosure(s) identified on the drawings.
c. NACs passing through other evacuation signaling zone(s) shall be Electrical Code classified CIC cable (Fire Alarm Circuit Integrity) installed in conduit.
Provide CIC cable meeting UL requirements for 2-hour listing.
1) The CIC cable system shall be installed in a conduit system meeting all requirements of its UL-listed installation system (conduit, boxes, connectors, etc.).
6. Fire Alarm Power Branch Circuits: Building wiring as specified in Section 26 05 13.
7. Notification Appliance Circuits shall provide the features listed below. These requirements may require separate circuits for visual and audible devices.
a. Fire alarm temporal audible notification for all audio appliances.
b. Synchronization of all visual devices where two or more devices are visible from the same location.
c. Ability to silence audible alarm while maintaining visual device operation.
d. Emergency communication alert and textual visible appliance notification.
8. Notification Appliance Circuits shall not span floors.
9. Signal line circuits connecting devices shall not span floors or[ 2-hour smoke compartments].
10. Signal line circuits connecting devices shall be provided with an isolation module at each floor separation or as otherwise shown on the drawings.
11. No wiring other than that directly associated with fire alarm detection, alarm or auxiliary fire protection functions shall be in fire alarm conduits. Wiring splices shall be avoided to the extent possible, and if needed, they shall be made only in junction boxes, and enclosed by plastic wire nut type connectors. Transposing or changing color coding of wires shall not be permitted. All conductors in conduit containing more than one wire shall be labeled on each end, in all junction boxes, and at each device with "E-Z Markers" or equivalent. Conductors in cabinets shall be carefully formed and harnessed so that each drops off directly opposite to its terminal. Cabinet terminals shall be numbered and coded, and no unterminated conductors are permitted in cabinets or control panels. All controls, function switches, etc. shall be clearly labeled on all equipment panels.
28 31 00 - 22
E. Fire Alarm Cabling Color Code: Provide circuit conductors with insulation color coding as follows or using colored tape at each conductor termination and in each junction box.
1. Power Branch Circuit Conductors: In accordance with Section 26 05 53.
2. Signaling Line Circuit: Overall red jacket with black and red conductors.
3. DC Power Supply Circuit: Overall red jacket with violet and brown conductors.
4. Notification Appliance Circuit: Overall red jacket with blue and white conductors.
5. Door Release Circuit: Gray conductors.
6. Central Station Trip Circuit: Orange conductors.
7. Central Station Fire Alarm Loop: Black and white conductors.
F. Devices surface mounted in finished areas shall be mounted on surface backboxes furnished by fire alarm equipment supplier. Backboxes shall be painted to match device, shall be the same shape and size as the device shall not have visible knockouts.
G. Make conduit and wiring connections to door release devices, sprinkler flow and pressure switches, sprinkler valve monitor switches, fire suppression system control panels, duct analog smoke detectors and all other system devices shown or noted on the Contract Documents or required in the manufacturer's product data and shop drawings.
3.3 FIELD QUALITY CONTROL
A. Field inspection and testing will be performed under provisions of Section 26 05 00.
B. Test in accordance with NFPA 72, Chapter 14 and local fire department requirements.
Submit documentation with O & M manuals in accordance with Section 14.6 of the Code.
C. Contractor shall test and adjust the fire alarm system as follows:
1. Speaker taps shall be adjusted to the lowest tap setting which achieves a sound level higher than or equal to the greatest of the following:
a. 70dBA.
b. 15 dBA above ambient levels as indicated in NFPA 72 Table A.18.4.3.
c. 15 dBA above measured ambient. 5 dBA above the maximum measured sound level with duration of more than 60 seconds.
d. As specified on the drawings.
2. Sound level measurement procedure shall meet the following requirements:
a. All measurements shall use the 'A' weighted, dBA, sound measurement scale.
b. All measurements shall be taken after furnishings, wall coverings and floor coverings are in place.
c. All measurements shall be taken after fixed equipment (HVAC units, etc.)
producing ambient noise is installed and is in operation.
d. Final ambient sound measurements shall be taken during occupancy and the units shall be re-adjusted at that time, if necessary.
28 31 00 - 23
e. All sound level measurements shall be taken at a height of 5' above the finished floor level.
f. Measurements shall be taken in every unique room. If there are multiple rooms, which have the identical dimensions and function, 10%, or a minimum of two (2) rooms shall be tested. The results from the rooms tested shall be averaged and the remaining rooms may be adjusted per the average.
g. Measurements shall be taken on a 20' x 20' grid and the results for all points taken shall be averaged. If the room is smaller than 20' x 20' a minimum of two measurements are required.
h. Measurements shall be taken halfway between speakers or halfway between a speaker and the wall. No measurements shall be taken at the extreme edges of the room, nor directly under speakers.
D. Additionally, test the voice alarm communication system intelligibility per IEC 60849:
1. The following acoustically distinguishable spaces shall be tested: All unique rooms shall be tested.
2. Utilize equipment designed to test per IEC 60849 per the equipment manufacturer's instructions. This equipment includes a signal generator, which is input to the fire alarm system and a portable measurement device. This equipment is available from Simplex Grinnell or Gold Line.
3. Testing equipment that can simulate 'crowd babble' shall be used in rooms with occupancy of greater than 200.
4. Wide-area notification intelligibility shall be tested in acoustically distinguishable spaces and areas as designated by the Owner.
5. When testing for intelligibility, the quantity and location of the measurement points shall be the same as the points used for measurement of dBA level.
6. Provide a room by room report, showing the average dBA level and STI for each room tested, the number and location of. The report shall be presented to the Architect/Engineer in an Excel .xls file.
3.4 MANUFACTURER'S FIELD SERVICES
A. Provide manufacturer's field services under provisions of Section 26 05 00.
B. Include services of the manufacturer's software programmer to write initial custom-user program (for Color Graphics Annunciation System).
C. Include services of certified technician to supervise installation, adjustments, final connections, and system testing.
D. Note that room numbers depicted on the architectural/engineering drawings will not necessarily reflect the actual room (signage) numbers that the Owner selects.
Contractor and fire alarm manufacturer shall coordinate the actual room numbers as the Owner directs to identify each device. This list shall be a part of the floor plan record drawing to be turned in at the project closeout.
28 31 00 - 24
E. Include the services to train up to three of the Owner's staff in operation, maintenance, and programming of the fire alarm system at the manufacturer's factory. Airfare and lodging expenses for the Owner's staff will be by the Owner.
F. System Occupancy Adjustments: When requested by Owner within 12 months of date of Substantial Completion, provide on-site system adjustments to suit actual occupied conditions. For this purpose, provide up to two (2) site visits, four (4) hours each visit, outside normal occupancy hours.
3.5…
This is the start of the file's text. The full file is on GovTribe.
File details come from the government source that posted it. Updated .