Amendment 0003 Attachment 07 - Drawings 0123027_FP.pdf
PDF 963 KB Posted
- Solicitation number
- 36C77625B0029
About this file
These are fire protection design drawings for a VA warehouse project in Butler, VA, detailing a comprehensive fire suppression system for a new 17,470 square foot storage facility. The drawings specify a fully automatic wet sprinkler system designed in accordance with NFPA 13 2022 Edition, with Early Suppression Fast-Response (ESFR) sprinklers for rack storage of plastic and rubber commodities. A new electrically-operated horizontal split case fire pump will be installed with a jockey pump, flow meter bypass, city bypass, test header connection, and fire pump controller, sized to provide 1,500 GPM at 90 PSI with an anticipated demand of 71 PSI and 1,332 GPM.
The fire protection system will cover multiple hazard classifications including light hazard, ordinary hazard group 1 and 2, and extra hazard group 1 areas, with sprinkler heads strategically placed to provide comprehensive coverage. The system includes multiple fire sprinkler zones, a fire department connection (FDC), underground fire mains, and will comply with numerous NFPA standards including NFPA 13, 14, 20, 24, 25, and others. The design also incorporates specific requirements for rack storage protection, sprinkler head placement, and integration with the fire alarm system, ensuring a robust and code-compliant fire protection solution for the VA warehouse facility.
View the file
Other files
Show all 27
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
FIRE PROTECTION LEGEND
NOTE: SOME ABBREVIATIONS AND SYMBOLS SHOWN ON THIS LEGEND MAY NOT PERTAIN TO THIS PROJECT
GENERAL LEGEND
SYMBOL DESCRIPTION
FIRE DEPARTMENT CONNECTION
FS FLOW SWITCH
TS TAMPER SWITCH
HOSE HOSE LINE CABINET
A
B
SIM
FP
SECTION SYMBOL:
A = IDENTIFYING LETTER
B = SHEET WHERE SECTION IS SHOWN
SIM = SIMILAR
(ONLY NOTED IF IT APPLIES)
FIRE PROTECTION RISER DESIGNATION:
A = RISER IDENTIFYING SYSTEM TYPE
1 =
REVISION CLOUD AND REVISION NUMBER.
REVISION DESCRIPTION SHOWN IN ITALICS.
A
TITLE SYMBOL ON SHEET WHERE SHOWN
A = IDENTIFYING NUMBER/LETTER
RISER IDENTIFYING SYSTEM NUMBER
SYMBOL DESCRIPTION
FIRE PROTECTION ABBREVIATIONS
AS ABOVE SLAB
AFF ABOVE FINISHED FLOOR
ANSI AMERICAN NATIONAL STANDARDS INSTITUTE
ASTM AMERICAN STANDARDS TESTING MATERIALS
BFP BACKFLOW PREVENTER
BLDG BUILDING
BOR BOTTON OF RISER
BS BELOW SLAB
CAP CAPACITY
CONN CONNECTION
CONT CONTINUOUS
COR CONTRACTING OFFICER'S REPRESENTATIVE
CV CHECK VALVE
DIA DIAMETER
DN DOWN
DP DRY PENDENT
DS DRY SIDE WALL
DWG DRAWING
ELEV ELEVATION
ESFR EARLY SUPPRESSION FAST-RESPONSE
ºF DEGREES FAHRENHEIT
FDC FIRE DEPARTMENT CONNECTION
FDV FIRE DEPARTMENT VALVE
FM FACTORY MUTUAL
FP FIRE PROTECTION
FP FIRE PUMP
FS FLOW SWITCH
FT FEET
GA GAUGE
GAL GALLON(S)
GALV GALVANIZED
GPM GALLONS PER MINUTE
HD HEAD
HP HORSEPOWER
HR HOUR
HYD HYDRANT
HZ HERTZ
IE INVERT ELEVATION
ID INTERNAL DIAMETER
IN INCHES
IPS INTERNATIONAL PIPE STANDARD
ABBR. DESCRIPTION ABBR. DESCRIPTION
JP JOCKEY PUMP
KW KILOWATT
MAX MAXIMUM
MFR MANUFACTURER
MIN MINIMUM
NA NOT APPLICABLE
NC NORMALLY CLOSED
NFPA NATIONAL FIRE PROTECTION ASSOCIATION
NTS NOT TO SCALE
OD OUTSIDE DIAMETER
OS&Y OUTSIDE SCREW AND YOLK
P PUMP
PH PHASE
PIV POST INDICATING VALVE
POC POINT OF CONNECTION
PSI POUNDS PER SQUARE INCH
PS PRESSURE SWITCH
QR QUICK RESPONSE
RM ROOM
RPM REVOLUTIONS PER MINUTE
SF SQUARE FEET
SPEC SPECIFICATIONS
SR STANDARD RESPONSE
STD STANDARD
TEMP TEMPERATURE
TDH TOTAL DYNAMIC HEAD
TOR TOP OF RISER
TS TAMPER SWITCH
TYP TYPICAL
U/G UNDERGROUND
UL UNDERWRITER'S LABORATORY
UNO UNLESS NOTED OTHERWISE
V VOLTS
VA U.S. DEPARTMENT OF VETERANS AFFAIRS
VIV VALVE IN VERTICAL
VLV VALVE
VOL VOLUME
W/ WITH
SHEET NOTE CALLOUT1
FIRE PROTECTION COMPLIANCE NOTES FIRE PROTECTION GENERAL NOTES
BUILDING DESIGN:
THE PROJECT CONSISTS OF A COMPLETE FIRE PROTECTION DESIGN FOR THE NEW VISN
4 WAREHOUSE. THE WAREHOUSE WILL CONSIST OF ABOVE 17,470 SQFT. THE BUILDING
WILL BE CLASSIFIED AS AN NFPA 101 STORAGE OCCUPANCY.
SCOPE OF WORK:
PROVIDE A FULLY AUTOMATIC WET SPRINKLER SYSTEM IN ACCORDANCE WITH NFPA 13
2022 EDITION. PROTECTION FOR RACK STORAGE OF PLASTIC AND RUBBER
COMMODITIES SHALL COMPLY WITH NFPA 13 CHAPTERS 14, 20, AND 23 FOR EARLY
SUPPRESSION FAST-RESPONSE (ESFR) SPRINKLERS. RACK STORAGE SHALL BE
DESIGNED FOR CLASS I THROUGH CLASS IV AND EXPOSED NONEXPANDED GROUP 'A'
PLASTICS WITH 12 FEET HIGH, SINGLE-ROW AND DOUBLE-ROW OPEN RACKS (50% FREE
AREA) UP TO A 25 FEET BUILDING HEIGHT. REFER TO RACKING PLANS FOR ADDITIONAL
INFORMATION. ALL OTHER SPRINKLER HEADS SHALL BE QUICK RESPONSE TYPE AND
INSTALLED IN CENTER OF CEILING TILES. SPRINKLER CONTRACTOR SHALL USE FLOW
DATA WHEN PERFORMING HYDRAULIC CALCULATIONS.
A NEW FIRE PUMP SHALL BE PROVIDED TO SERVE THE WAREHOUSE. THE NEW FIRE
PUMP SHALL BE ELECTRICALLY OPERATED HORIZONTAL SPLIT CASE PUMP DESIGN AND
INCLUDE A JOCKEY PUMP, A FLOW METER BYPASS, A CITY BYPASS, A TEST HEADER
CONNECTION, A FIRE PUMP CONTROLLER, AND A JOCKEY PUMP CONTROLLER. THE FIRE
PUMP CONTROL PANEL SHALL HAVE A TRANSFER SWITCH. THE CONTRACTOR SHALL
CONNECT THE FIRE MAIN INLET TO THE SUCTION SIDE OF THE PUMP, THE PUMP
DISCHARGE SHALL BE ROUTED TO THE ALARM RISER LOCATION, AND THE TEST HEADER
TO THE BUILDING EXTERIOR TEST HEADER LOCATION. CONTRACTOR SHALL COORDINATE
ALL ELECTRICAL CONNECTIONS REQUIRED. FIRE PUMP SIZE SHALL BE CONFIRMED BY
FIRE SPRINKLER CONTRACTOR DURING PRODUCTION OF SHOP DRAWINGS AND
HYDRAULIC CALCULATIONS. ANTICIPATED DEMAND IS 71 PSI AND 1,332 GPM, PUMP SHALL
BE SIZED FOR 1,500 GPM AT 90 PSI. CONTRACTOR TO CONFIRM FIRE PUMP SIZE WITH
PRODUCTION OF HYDRAULIC CALCULATIONS.
FIRE PROTECTION SPRINKLER CONTRACTOR SHALL COORDINATE THE DESIGN AND
INSTALLATION OF THE FIRE PROTECTION SPRINKLER SYSTEM AND DELIVER A
COMPLETE, FULLY FUNCTIONAL, AND TESTED FIRE PROTECTION SYSTEM THAT MEETS
THE REQUIREMENTS OF THE FIRE PROTECTION DRAWINGS, FIRE PROTECTION
SPECIFICATIONS, LISTED CODES AND STANDARDS, AND THE REQUIREMENTS OF THE
VA. THE FIRE PROTECTION SPRINKLER CONTRACTOR SHALL PROVIDE AND INSTALL
NEW MATERIALS THAT ARE BOTH UL LISTED AND FM APPROVED AS REQUIRED BY THE
FIRE PROTECTION DRAWINGS AND THE FIRE PROTECTION SPECIFICATIONS. THE FIRE
PROTECTION SPRINKLER CONTRACTOR SHALL INTEGRATE THE NEW FIRE SPRINKLER
SYSTEM WITH THE NEW FIRE ALARM SYSTEM.
CHARACTERISTICS OF THE WATER SUPPLY TO BE USED:
A CURRENT HYDRANT FLOW TEST SHALL BE PERFORMED AND VERIFIED WITHIN THE LAST
12 MONTHS PRIOR TO PRODUCTION OF LAYOUT DOCUMENTS.
FLOW TEST DATA:
65 PSI STATIC; 42 PSI RESIDUAL; 1,000 GPM FLOWING; FLOW TEST RESULTS WAS
PERFORMED ON FIRE HYDRANT #H27 ON 'A' STREET BY KEVIN KELSO ON 11/08/2023.
BACKFLOW PREVENTION AND METERING SPECIFICATIONS:
THE BACKFLOW PREVENTION DEVICE ASSEMBLY AND METERING EQUIPMENT WILL MEET
THE REQUIREMENTS OF THE LOCAL WATER PURVEYOR. ALL NEW INTERIOR FIRE
PROTECTION EQUIPMENT SHALL BE UL LISTED AND FM APPROVED.
QUALITY AND PERFORMANCE SPECIFICATIONS OF ALL INTERIOR FIRE PROTECTION
COMPONENTS:
ALL NEW INTERIOR FIRE PROTECTION EQUIPMENT EQUIPMENT SHALL BE UL LISTED OR
FM APPROVED.
SPRINKLERS SHALL BE FM APPROVED.
VALVING AND ALARM REQUIREMENTS TO MINIMIZE POTENTIAL FOR IMPAIRMENTS AND
UNRECOGNIZED FLOW OF WATER:
THE FIRE SPRINKLER RISER FOR THIS BUILDING AND ALL CONTROL VALVE, POST
INDICATOR AND BACKFLOW PREVENTER WILL BE EQUIPPED WITH A WATER FLOW
SWITCH AND PRESSURE SWITCH ON PREACTION VALVE, WITH A LOCAL ALARM BELL AND
FIRE ALARM PANEL.
FIRE FLOW ANALYSIS:
CONSTRUCTION: TYPE II (000)
BUILDING AREA: 17,500 SQFT
TABLE 18.4.4.2.1 MINIMUM FLOW REQUIREMENTS: 2,750 GPM @ 20 PSI FOR 2 HOURS
REDUCTIONS ALLOWED PER 18.4.4.3: YES
MINIMUM FLOW REQUIREMENTS REDUCED: 1,000 GPM @ 20 PSI FOR 2 HOURS
SPRINKLER FLOW DEMAND (TO BE CONFIRMED BY HYDRAULIX CALCULATIONS): 1,332 GPM
@ 71 PSI
WATER SUPPLY SUFFICUENT: YES
ACCEPTANCE TEST CRITERIA:
FIRE SPRINKLER SYSTEM SHALL BE DESIGNED PER NFPA 13, 2022 EDITION AND SHALL
COMPLY WITH THE LOCAL FIRE MARSHAL AND THE VA. THE ACCEPTANCE TESTING OF
THE FIRE SPRINKLER SYSTEM AND IT'S COMPONENTS SHALL CONSIST OF ALL
APPLICABLE ITEMS SHOWN ON THESE TWO FORMS, NFPA 13, 2022 EDITION, ANNEX A
(FIG. A.29.1) CONTRACTOR'S MATERIAL AND TEST CERTIFICATE FOR ABOVE GROUND
PIPING. SEE NFPA 13, 2022 EDITION CHAPTER 29 FOR SYSTEM ACCEPTANCE AND NFPA
25, 2020 INSPECTION TESTING AND MAINTENANCE.
1. NFPA 13 2022 CHAPTER 29, SYSTEM ACCEPTANCE
A. 29.1 APPROVAL OF SPRINKLER SYSTEM
B. 29.2 ACCEPTANCE REQUIREMENTS
C. 29.3 INSTRUCTIONS
D. 29.4 HYDRAULIC DESIGN INFORMATION SIGNS
APPLICABLE NFPA AND VA STANDARDS TO BE APPLIED:
1. VA FIRE PROTECTION DESIGN MANUAL - NINTH EDITION
2. INTERNATIONAL BUILDING CODE (IBC) 2024 EDITION
3. NFPA 1 FIRE CODE 2024 EDITION
4. NFPA 13 STANDARD FOR THE INSTALLATION OF SPRINKLER SYSTEMS 2022 EDITION
5. NFPA 14 STANDARD FOR THE INSTALLATION OF STANDPIPE AND HOSE SYSTEMS
2024 EDITION
6. NFPA 20 STANDARD FOR THE INSTALLATION OF STATIONARY PUMPS FOR FIRE
PROTECTION 2022 EDITION
7. NFPA 22 STANDARD FOR WATER TANKS FOR PRIVATE FIRE PROTECTION 2023
EDITION
8. NFPA 24 STANDARD FOR THE INSTALLATION OF PRIVATE FIRE SERVICE MAINS AND
THEIR APPURTENANCES 2022 EDITION
9. NFPA 25 INSPECTION, TESTING AND MAINTENANCE OF WATER BASED FIRE
PROTECTION SYSTEM 2023 EDITION
10. NFPA 37 STANDARD FOR THE INSTALLATION OF STATIONARY COMBUSTION
ENGINES AND GAS TURBINES 2024 EDITION
11. NFPA 72 NATIONAL FIRE ALARM AND SIGNALING CODE 2022 EDITION
12. NFPA 101 LIFE SAFETY CODE 2024 EDITION
13. NFPA 110 STANDARD FOR EMERGENCY AND STANDBY POWER SYSTEMS 2022
EDITION
14. NFPA 170 FIRE SAFETY SYMBOLS 2024 EDITION
CLASSIFICATION OF HAZARD OCCUPANCY FOR EACH ROOM OR AREA:
LIGHT HAZARD:
SPACES WITH LOW QUANTITY AND COMBUSTIBILITY OF CONTENTS
I.E. OFFICES, EXAM ROOMS, CORRIDORS, MEETING ROOMS, BREAK ROOMS,
AND RESTROOMS.
ORDINARY HAZARD GROUP 1:
SPACES WITH MODERATE QUANTITY AND LOW COMBUSTIBILITY OF CONTENTS
I.E. LABORATORIES, MECHANICAL ROOMS, ELECTRICAL ROOMS, JANITOR
CLOSETS, CLEAN AND SOILED UTILITY ROOMS, AND AUTOPSY.
ORDINARY HAZARD GROUP 2:
SPACES WITH MODERATE TO HIGH QUANTITY AND COMBUSTIBILITY OF CONTENTS
I.E. NITROGEN STORAGE, MODERATE QUANTITY AND MODERATE
COMBUSTIBILITY STORAGE (UP TO 12 FT IN HEIGHT),CLEAN AND SOILED LINEN
ROOMS, AND LAUNDRY.
EXTRA HAZARD GROUP 1:
SPACES WITH HIGH QUANTITY AND COMBUSTIBILITY OF CONTENTS
I.E. SPACES WHERE DUST, LINT, OR OTHER MATERIALS ARE PRESENT THAT
WILL CONTRIBUTE A RAPIDLY DEVELOPING FIRE.
CLASS I THROUGH CLASS IV AND EXPOSED NONEXPANDED GROUP 'A' PLASTICS
STORAGE:
SPACES WITH HIGH QUANTITY AND COMBUSTIBILITY OF CONTENTS BEING STORED
IN RACK SYSTEMS
I.E. SPACES WHERE DUST, LINT, OR OTHER MATERIALS ARE PRESENT THAT
WILL CONTRIBUTE A RAPIDLY DEVELOPING FIRE.
DESIGN APPROACH:
SPRINKLER SYSTEM TO EXTEND INTO ALL AREAS IN ACCORDANCE WITH NFPA 13 LIGHT
HAZARD OR AS NOTED. LISTED AND APPROVED SIDEWALL (5.60 K-FACTOR) AND
PENDENT (5.60 K-FACTOR) SPRINKLER HEADS TO BE PROVIDED. UPRIGHT (5.60 K-
FACTOR) HEADS TO BE PROVIDED WHERE NOTED ON DRAWINGS.
1. FIRE PROTECTION SYSTEM SHALL COMPLY WITH NFPA 13 AND VA FIRE PROTECTION MANUAL FOR INSTALLATION OF SPRINKLER SYSTEMS. INSPECTION, TESTING, AND MAINTENANCE SHALL COMPLY TO NFPA 25. IN ADDITION, INSTALLATION AND INSPECTION, TESTING, AND MAINTENANCE SHALL COMPLY WITH THE PROJECT SPECIFICATIONS AND ALL APPLICABLE STATE, LOCAL CODES & VA
REQUIREMENTS.
2. FINAL INSPECTION AND APPROVAL SHALL BE BY THE VA.
3. SPRINKLER SHOP DRAWINGS AND MATERIAL SUBMITTALS SHALL BE SUBMITTED TO THE VA COR AND VA OFFICE OFFIRE
PROTECTION ENGINEERING AND SHALL BE APPROVED PRIOR TO ANY INSTALLATION.
4. CUTTING OF STRUCTURAL AND/OR ARCHITECTURAL MEMBERS TO BE DONE ONLY WITH THE WRITTEN APPROVAL OF THE COR
AND/OR STRUCTURAL ENGINEER.
5. FITTINGS REQUIRED FOR PROPER INSTALLATION, COORDINATION WITH OTHER EXISTING TRADES, AND/OR TO MAINTAIN PROPER
CLEARANCES SHALL BE PROVIDED. VERIFY STRUCTURAL, MECHANICAL, ELECTRICAL INSTALLATIONS AND AVOID AN/ALL
OBSTRUCTIONS OR INTERFERENCES WITH FIRE PROTECTION PIPE ROUTING.
6. CONTRACTOR SHALL VERIFY ARCHITECTURAL REFLECTED CEILING PLANS AND ELECTRICAL LIGHTING, CEILING CONFIGURATIONS
AND HEIGHTS IN EACH AREA.
7. FIRE STOP ALL PENETRATIONS OF SMOKE/FIRE WALLS, CEILINGS, FLOORS, ROOFS, ETC., FLASH AND COUNTERFLASH ROOF
PENETRATIONS.
8. PROVIDE ACCESS PANELS TO ALL VALVES ABOVE NON-ACCESSIBLE CEILINGS AND CHASES.
9. SPRINKLER HEADS ARE TO BE COORDINATED WITH ALL LOCATIONS OF DIFFUSERS, SPEAKERS, LIGHTING FIXTURES, CEILING
SYSTEMS AND STRUCTURAL SYSTEM.
10. INDICATE CENTER TO CENTER DIMENSIONS AND/OR PIPE CUT LENGTHS AND NOMINAL PIPE DIAMETERS ON ALL PIPING. INDICATE
PIPE TYPE, SCHEDULE OF WALL THICKNESS AND METHOD OF JOINING ON SHOP DRAWING.
11. PROVIDE STOCK OF SPARE SPRINKLERS IN ACCORDANCE WITH NFPA 13 SECTION 16.2.7.
12. PROVIDE DETAIL AND INDICATE TYPE OF HANGERS TO BE INSTALLED FOR SPRINKLER PIPING. METHODS OF HANGING PIPES, HEADERS AND BRANCHES SHALL BE IN ACCORDANCE WITH NFPA 13. ALL HANGERS ON 4" PIPE AND LARGER SHALL BE CLEVIS-TYPE HANGERS. HANGERS SHALL NOT INTERFERE WITH ANY OTHER TRADE. POWDER DRIVEN STUDS SHALL NOT BE USED.
13. ALL GROOVED & SCREWED FITTINGS SHALL BE UL/FM APPROVED AND SUBMITTED TO THE ENGINEER OF RECORD FOR APPROVAL PRIOR TO ANY INSTALLATION. THE ENGINEER OF RECORD RESERVES THE RIGHT TO DISAPPROVE ANY FITTING. ALL SCREWED PIPING SHALL BE SCHEDULE 40 BLACK STEEL PIPE IN ACCORDANCE WITH SPECIFICATIONS ASTM A120 AND SHALL BE JOINED BY SCREWED JOINTS IN ACCORDANCE WITH SPECIFICATION ANSI B2.1. ALL GROOVED PIPING 2-1/2" OR LARGER SHALL BE SCHEDULE 10
BLACK STEEL.
14. WELD-O-LETS SHALL BE TWO SIZES SMALLER THAN CROSS MAIN, NO LENGTH OF CROSS MAIN SHALL BE GREATER THAN 10'-0". ALL
SPRINKLER PIPING & FITTINGS SHALL BE INSTALLED ABSOLUTELY RUST-FREE.
15. AUTOMATIC SPRINKLER TEMPERATURE RATINGS OF FUSIBLE ELEMENTS TO BE IN ACCORDANCE WITH NFPA 13 SECTION 7.2.4.
16. PIPE SHALL BE REAMED AND CLEANED BEFORE ASSEMBLY, AND AFTER ASSEMBLY THE ENTIRE PIPING SYSTEM SHALL BE FLUSHED
CLEAN.
17. PROVIDE SPRINKLERS ABOVE AND BELOW EXPOSED DUCTWORK WIDER THAN 4 FEET.
18. PROVIDE HAZARD COVERAGE FOR THE FUNCTIONS FOR EACH AREA.
19. INDICATE THE TOTAL SQUARE FOOT AREA PROTECTED BY SYSTEM(S).
20. INDICATE THE NUMBER OF SPRINKLERS ON EACH RISER.
21. ALL PENDENT SPRINKLERS SHALL BE CENTER OF TILE, UNLESS MAXIMUM DISTANCES FROM WALLS OR BETWEEN HEADS IS
EXCEEDED OR UNLESS SHOWN DIFFERENTLY ON DRAWINGS. IF NOT POSSIBLE ALL SPRINKLER HEADS MOUNTED IN CEILING SHALL BE LOCATED A MINIMUM OF 4" AWAY FROM ANY WALLS, CEILING GRID MEMBERS, CEILING HEIGHT CHANGES OR ANY OTHER
VERTICAL INTERSECTING STRUCTURAL SURFACE.
22. FIRE PROTECTION CONTRACTOR SHALL ASSIST IN PREPARATION OF COORDINATION DRAWINGS FOR ALL LEVELS WHICH INDICATE ALL THE ENGINEERING DISCIPLINES & FIRE PROTECTION PIPING. THESE DRAWINGS SHALL BE PREPARED & APPROVED BY THE
ENGINEER OF RECORD PRIOR TO ANY INSTALLATION.
23. FIRE SPRINKLER PIPING SHALL NOT TRAVEL OVER THE TOPS OF ELECTRICAL PANELBOARDS OR ELECTRICAL EQUIPMENT.
24. PROVIDE TEFLON COATING FOR ALL SPRINKLERS IN ANY CORROSIVE AREA.
25. ALL EXPOSED PIPING SHALL BE SHALL BE PAINTED RED AND CLEARLY LABELED.
26. ALL MATERIALS, WHERE APPLICABLE, SHALL BE U.L. LISTED AND/OR FACTORY MUTUAL APPROVED FOR USE IN AUTOMATIC
SPRINKLER SYSTEMS. ALL NEW PIPING SHALL BE HYDROSTATICALLY TESTED FOR TWO HOURS IN ACCORDANCE WITH NFPA 13.
MINIMUM HYDROSTATIC TEST PRESSURE SHALL BE 200 PSI.
27. FLEXIBLE SPRINKLER CONNECTIONS SHALL ONLY BE PERMITTED UPON VA APPROVAL. IF FLEXIBLE SPRINKLER CONNECTIONS ARE PERMITTED AND USED, HYDRAULIC CALCULATIONS MUST BE PERFORMED AND SUBMITTED TO THE ENGINEER OF RECORD.
28. ALL VALVES FOR FIRE SERVICE SHALL BE LISTED BY THE UNDERWRITER'S LABORATORIES, INC. AND THE FACTORY MUTUAL LABORATORIES. VALVES SHALL BE FACTORY MARKED "UL" OR "FM", AND RATED FOR 175 WORKING PRESSURE.
29. ELECTRICALLY SUPERVISED VALVES SHALL BE PROVIDED WHERE REQUIRED IN NFPA 13. TYPE AND EXACT LOCATION AND PURCHASE/INSTALLATION OF FLOW AND SUPERVISORY SWITCHES SHALL BE BY THE SPRINKLER CONTRACTOR. ELECTRICAL CONTRACTOR TO PROVIDE ADDITIONAL CIRCUITS, WIRING, SWITCHES, CONDUIT OR JUNCTION BOXES REQUIRED.
30. SPRINKLER COVERAGE SHALL COMPLY WITH NFPA 13. SPRINKLER LOCATIONS WITH RESPECT TO OBSTRUCTIONS SHALL COMPLY WITH NFPA 13-2022, CHAPTER 9, OR THE APPROPRIATE CHAPTER BASED ON SPRINKLER TYPE.
31. IMMEDIATELY NOTIFY THE ARCHITECT/ENGINEER OF ANY DISCREPANCIES FOUND BETWEEN THESE PLANS, OTHER ENGINEERING PLANS, THE ARCHITECTURAL PLANS AND/OR FIELD CONDITIONS PRIOR TO FINAL BID PRICE OR FINAL PERMITTING.
32. IN CASE OF DISPUTE OR DOUBT AS TO INTENT OF DRAWINGS OR SPECIFICATIONS, OBTAIN ARCHITECT/ENGINEER'S WRITTEN
DECISION BEFORE PROCEEDING WITH BID OR WORK INVOLVED.
33. DRAWINGS ARE DIAGRAMMATIC AND INDICATE GENERAL ARRANGEMENT OF SYSTEMS. PROVIDE COMPONENTS INDICATED IN
DETAILS AND RISER DIAGRAMS WHETHER OR NOT INDICATED ON PLANS AND VICE VERSA.
34. WHERE A DISCREPANCY OR CONFLICT IS FOUND BETWEEN ONE DRAWING AND ANOTHER, OR BETWEEN A DRAWING AND APPLICABLE SPECIFICATIONS, NOTIFY THE COR IMMEDIATELY IN WRITTEN FORM. IN GENERAL, THE MOST STRINGENT REQUIREMENT SHALL GOVERN UNLESS THE DISCREPANCY CONFLICTS WITH APPLICABLE CODES OR VA'S DESIGN STANDARDS, WHEREIN THE
CODE OR VA'S DESIGN STANDARDS SHALL GOVERN.
LIGHT HAZARD:
SYSTEM TYPE: WET PIPE AUTOMATIC SPRINKLER SYSTEM, USING STEEL SUPPLY PIPING TO
NEW QUICK RESPONSE, PENDENT OR UPRIGHT HEADS. AREAS SUBJECT TO FREEZING
SHALL USE DRY BARREL TYPE SPRINKLERS.
K-FACTOR: 5.6 (EXTENDED COVERAGE SPRINKLER HEADS ARE ACCEPTABLE).
DENSITY: 0.10 GPM/SQ.FT.
AREA OF OPERATION: 900 SQ FT MIN AND 1500 SQ FT MAX (DESIGN AREA REDUCTION MAY
ONLY BE USED IF CEILING HEIGHT AND AREA CLASSIFICATION PERMITS PER NFPA 13 2022
EDITION.
HEAD TEMPERATURE RATING: 155 °F
SPACING: 225 SQ. FT. MAX. PER SPRINKLER HEAD OR BY MANUFACTURER LITERATURE.
HOSE ALLOWANCE: 100 GPM
ORDINARY HAZARD GROUP 1:
SYSTEM TYPE: WET PIPE AUTOMATIC SPRINKLER SYSTEM, USING STEEL SUPPLY PIPING TO
NEW QUICK RESPONSE, PENDENT OR UPRIGHT HEADS.
K-FACTOR: 5.6, 8.0, 11.2, OR 14.0 (EXTENDED COVERAGE SPRINKLER HEADS ARE
ACCEPTABLE).
DENSITY: 0.15 GPM/SQ.FT.
AREA OF OPERATION: 900 SQ FT MIN AND 1500 SQ FT MAX (DESIGN AREA REDUCTION MAY
ONLY BE USED IF CEILING HEIGHT AND AREA CLASSIFICATION PERMITS PER NFPA 13 2022
EDITION.
HEAD TEMPERATURE RATING: 155 °F
SPACING: 130 SQ. FT. MAX. PER SPRINKLER HEAD OR BY MANUFACTURER LITERATURE.
HOSE ALLOWANCE: 250 GPM
ORDINARY HAZARD GROUP 2:
SYSTEM TYPE: WET PIPE AUTOMATIC SPRINKLER SYSTEM, USING STEEL SUPPLY PIPING TO
NEW QUICK RESPONSE, OR STANDARD SPRAY UPRIGHT, SEMI-RECESSED PENDENT, OR
SIDEWALL HEADS.
K-FACTOR: 5.6, 8.0, 11.2, OR 14.0 (EXTENDED COVERAGE SPRINKLER HEADS ARE
ACCEPTABLE).
DENSITY: 0.20 GPM/SQ.FT.
AREA OF OPERATION: 900 SQ FT MIN AND 1500 SQ FT MAX (DESIGN AREA REDUCTION MAY
ONLY BE USED IF CEILING HEIGHT AND AREA CLASSIFICATION PERMITS PER NFPA 13 2022
EDITION).
HEAD TEMPERATURE RATING: 155°F
SPACING: 130 SQ. FT. MAX. PER SPRINKLER HEAD OR BY MFR LITERATURE.
HOSE ALLOWANCE: 250 GPM
EXTRA HAZARD GROUP 1:
SYSTEM TYPE: WET PIPE AUTOMATIC SPRINKLER SYSTEM, USING STEEL SUPPLY PIPING TO
NEW QUICK RESPONSE, OR STANDARD SPRAY UPRIGHT, SEMI-RECESSED PENDENT, OR
SIDEWALL HEADS.
K-FACTOR: 8.0 OR LARGER.
DENSITY: 0.30 GPM/SQ.FT.
AREA OF OPERATION: 2,500 SQ FT MIN
HEAD TEMPERATURE RATING: 250°F
SPACING: 100 SQ. FT. MAX. PER SPRINKLER HEAD OR BY MFR LITERATURE.
HOSE ALLOWANCE: 500 GPM
CLASS I THROUGH CLASS IV AND EXPOSED NONEXPANDED GROUP 'A' PLASTICS STORAGE:
SYSTEM TYPE: WET PIPE AUTOMATIC SPRINKLER SYSTEM, USING STEEL SUPPLY
PIPING TO ESFR PENDENT/UPRIGHT HEADS. REFER TO TABLE 23.3.1 OF NFPA 13.
SPRINKLERS SHALL BE INSTALLED IN THE PENDENT ORIENTATION.
K-FACTOR: 14.0 OR LARGER.
MIN. PRESSURE: 50 PSI (FOR K14 SPRINKLERS)
DESIGN AREA: 12 SPRINKLERS, WITH 4 SPRINKLERS ON EACH OF THREE BRANCH LINES
IN-RACK SPRINKLERS REQUIRED: NO
HEAD TEMPERATURE RATING: 155 DEGREES F
SPACING: 64 SQ. FT. MIN TO 100 SQ. FT. MAX. AREA COVERAGE PER SPRINKLER HEAD, 8FT
TO 12 FT SPACING PER SPRINKLER HEAD OR BY MFR LITERATURE.
REV DESCR
FLOW METER
PRESSURE GAUGE WITH SHUTOFF
ELBOW, TURNED DOWN
INLINE PUMP
CAP
ELBOW, 90° ELBOW, TURNED UP
TEE, OUTLET DOWN
FM
ELBOW, 45°
TEE, OUTLET UP
45° PIPE RISE (R)/DROP (D)
PIPE ANCHORS
CONCENTRIC REDUCER
ECCENTRIC REDUCER
R R
FLANGES
FLOW DIRECTION
UNION
THERMOMETER
FLEX CONNECTION (DOUBLE SPHERE
FOR PIPES 6" AND LARGER; SINGLE
SPHERE FOR PIPES 4" AND SMALLER
TEST PLUG (PRESSURE/TEMPERATURE)
MANUAL VENT
PRESSURE SWITCH
AUTOMATIC AIR VENT
HOSE CONNECTION
TEE, SIDE CONNECTION
BUTTERFLY VALVE
PRESSURE REGULATING VALVE
CHECK VALVE
GATE VALVE
BALL VALVE
STRAINER WITH BALL VALVE AND
HOSE CONNECTION
FM U/G FIRE MAIN PIPING (UNDERGROUND)
FM FIRE MAIN PIPING
OS&Y VALVE
FLOW SWITCH
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10 www.abovegroupinc.com COA/CA Lic. No. 31120
FULLY SPRINKLERED305 East Dr., Suite H, Melbourne, Florida 32904
PH: 321.345.9026
A u to d e s k D o c s
/0
V A
M C
B u tl e r
V
IS
N
W a re h o u s e
/0
V A
B u tl e r_ V
IS
N
W a re h o u s e
R
M
E P
F P
F A
T .r v t
/2
/2
:5
:1
A
M
FP001
FIRE PROTECTION LEGENDS &
SYMBOLS
CONSTRUCT A WAREHOUSE
FOR VISN 4 WESTERN
MARKET DISTRIBUTION
BUTLER, VA
529-314
06/02/2025 JMC AJZ
BID DOCUMENTS
ALLEN LANTZ III, P.E.
PA License #PE091315
SHEET LIST
SHEET NUMBER SHEET NAME
FP001 FIRE PROTECTION LEGENDS & SYMBOLS
FP100 FIRE PROTECTION SITE PLAN
FP111 HAZARD CLASSIFICATION PLAN - FIRE PROTECTION - NEW WORK
FP112 PIPING FLOOR PLAN - FIRE PROTECTION - NEW WORK
FP401 FIRE PUMP SCHEDULES, SCHEMATICS, & SECTIONS
FP501 FIRE PROTECTION DETAILS
Revisions Date
1 Addendum #1 07/22/2025
POST INDICATOR VALVE A MINIMUM OF 21'-0" FROM
BUILDING, ACCORDING TO NFPA 24 6.2.9(1)(a).
COORDINATE FINAL LOCATION WITH CIVIL CONTRACTOR
AND FINAL BUILDING HEIGHT.
(6) 2-1/2" HOSE CONNECTION FREE STANDING FIRE PUMP TEST
HEADER LOCATED OUTSIDE OF FIRE PUMP ROOM THAT WILL
ALLOW WATER TO NOT BE DISCHARGED TO A LOCATION THAT
WILL NOT CREATE A NUISANCE, ACCORDING TO NFPA 20 4.22.1.5.
COORDINATE FINAL LOCATION WITH CIVIL CONTRACTOR.
6" FM TO 4" STORZ FDC. FDC TO BE A MAXIMUM OF 100' - 0" AWAY FROM
NEAREST FIRE HYDRANT, ACCORDING TO NFPA 14 9.9.5.4 AND A MAXIMUM
OF 50' - 0" AWAY FROM THE NEAREST POINT OF FIRE DEPARTMENT
APPARATUS ACCESS, ACCORDING TO NFPA 14 10.7.2.4. COORDINATE FINAL
LOCATION WITH CIVIL CONTRACTOR AND FIRE DEPARTMENT AHJ. REFER
TO DETAIL 8 ON SHEET FP501 FOR BOLLARDS AND SIGNAGE DETAILS.
8" FM U/G
EX FIRE HYDRANT #23
100' - 0" FROM
FIRE HYDRANT #23
8" FM U/G 6" FM U/G
6" FM U/G
NEW FIRE HYDRANT.
REFER TO CIVIL PLANS
FOR EXACT LOCATION
100' - 0" FROM NEW
FIRE HYDRANT
FIRELANE. REFER
TO CIVIL PLANS FOR
FINAL LOCATION.
BIORETENTION AREA. REFER TO CIVIL
DRAWINGS FOR MORE INFORMATION.
BIORETENTION AREA. REFER TO CIVIL
DRAWINGS FOR MORE INFORMATION.
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10 www.abovegroupinc.com COA/CA Lic. No. 31120
FULLY SPRINKLERED305 East Dr., Suite H, Melbourne, Florida 32904
PH: 321.345.9026
A u to d e s k D o c s
/0
V A
M C
B u tl e r
V
IS
N
W a re h o u s e
/0
V A
B u tl e r_ V
IS
N
W a re h o u s e
R
M
E P
F P
F A
T .r v t
/2
/2
:5
:1
A
M
FP100
FIRE PROTECTION SITE PLAN CONSTRUCT A WAREHOUSE
FOR VISN 4 WESTERN
MARKET DISTRIBUTION
BUTLER, VA
529-314
06/02/2025 JMC AJZ
BID DOCUMENTS
ALLEN LANTZ III, P.E.
PA License #PE091315
DRAWING NOTES:
1. COORDINATE ALL INVERTS WITH CIVIL CONTRACTOR BEFORE INSTALLATION OF ANY PIPING.
2. ALL PIPING SHOWN ON THIS PLAN IS PROVIDED AND INSTALLED BY CIVIL CONTRACTOR. COORDINATE
WITH CIVIL CONTRACTOR FOR FINAL FDC, TEST HEADER, AND PIV LOCATIONS.
3. FDC, TEST HEADER, AND PIV TO BE PROVIDED BY FIRE PROTECTION CONTRACTOR AND INSTALLED BY CIVIL CONTRACTOR. REFER TO SPECIFICATION 21 13 00 AND 21 30 13 FOR MORE INFORMATION ON
FIRE PROTECTION EQUIPMENT. COORDINATE WITH CIVIL CONTRACTOR FOR FINAL FDC, TEST
HEADER, AND PIV LOCATIONS.
1" = 30'-0"1
SITE PLAN - FIRE PROTECTION
N 0 15' 30' 60' 90'
1" = 30'
Revisions Date
HAZARD CLASSIFICATION
LIGHT HAZARD
ORDINARY HAZARD GROUP 1
CLASS I THROUGH CLASS IV
AND EXPOSED NONEXPANDED
GROUP 'A' PLASTICS STORAGE
KEY
EXTRA HAZARD GROUP 1
ORDINARY HAZARD GROUP 2
WAREHOUSE
ELECTRICAL ROOM
GENERATOR ROOM
FIRE PUMP ROOM
OPEN OFFICE AREA
ENTRY
STAFF LOUNGE
M. TLT.
W. TLT.
CORRIDOR
HAC
SUPPLY RM
COPY RM
HOLDING AREA
RECEIVING DOCK
MECHANICAL ROOM
EDBA C
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10 www.abovegroupinc.com COA/CA Lic. No. 31120
FULLY SPRINKLERED305 East Dr., Suite H, Melbourne, Florida 32904
PH: 321.345.9026
A u to d e s k D o c s
/0
V A
M C
B u tl e r
V
IS
N
W a re h o u s e
/0
V A
B u tl e r_ V
IS
N
W a re h o u s e
R
M
E P
F P
F A
T .r v t
/2
/2
:5
:2
A
M
FP111
HAZARD CLASSIFICATION PLAN -
FIRE PROTECTION - NEW WORK
CONSTRUCT A WAREHOUSE
FOR VISN 4 WESTERN
MARKET DISTRIBUTION
BUTLER, VA
529-314
06/02/2025 JMC AJZ
BID DOCUMENTS
ALLEN LANTZ III, P.E.
PA License #PE091315
N 0 4' 8' 16' 24'
1/8" = 1'-0"
1/8" = 1'-0"
FIRST FLOOR HAZARD CLASSIFICATION PLAN
DRAWING NOTES:
1. HOLDING AREA 116 IS CALSSIFIED AS A LIGHT HAZARD OCCUPANCY. HOWEVER, THE SPACE IS NOT SEPERATED FROM WAREHOUSE 114 BY A PHYSICAL BARRIER OR PARTITION CAPABLE OF DELAYNG HEAT FROM A FIRE IN ADJACENT AREA. ACCORDING TO NFPA 13 20.13.1, THE WAREHOUSE HAZARD CLASSIFICATION MUST EXTEND 15 FEET BEYOND IT'S PERIMETER INTO ADJACENT SPACE. HOLDING AREA IS ONLY 16' - 8" WIDE (ONLY 1' - 8" OVER 15 FEET NOT ALLOWING FOR A ROW OF LIGHT HAZARD SPRINKLERS BASED ON SPACING), CLASSIFYING THE ENTIRE AREA AS PART OF THE WAREHOUSE
HAZARD CLASSIFICATION.
REF
F E
C
FE
FE
FE
FE
FE
FE
FE
FE
FE
FE
FE
FE
FE
WAREHOUSE
GENERATOR ROOM
OPEN OFFICE AREA
STAFF LOUNGE
FIRE PUMP ROOM
ENTRY
FIRE SPRINKLER
ZONE 1
14,625 SQ. FT
FIRE SPRINKLER
ZONE 2
2,733 SQ. FT
6" FM
FP401
ELECTRICAL ROOM
MECHANICAL ROOM
W. TLT.
M. TLT.
CORRIDOR
SUPPLY RM
107 HAC
COPY RM
HOLDING AREA
RECEIVING DOCK
EDBA C
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10 www.abovegroupinc.com COA/CA Lic. No. 31120
FULLY SPRINKLERED305 East Dr., Suite H, Melbourne, Florida 32904
PH: 321.345.9026
A u to d e s k D o c s
/0
V A
M C
B u tl e r
V
IS
N
W a re h o u s e
/0
V A
B u tl e r_ V
IS
N
W a re h o u s e
R
M
E P
F P
F A
T .r v t
/2
/2
:5
:2
A
M
FP112
PIPING FLOOR PLAN - FIRE
PROTECTION - NEW WORK
CONSTRUCT A WAREHOUSE
FOR VISN 4 WESTERN
MARKET DISTRIBUTION
BUTLER, VA
529-314
06/02/2025 JMC AJZ
BID DOCUMENTS
ALLEN LANTZ III, P.E.
PA License #PE091315
DRAWING NOTES:
1. COORDINATE SPRINKLER HEIGHT WITH ARCHITECTURAL REFLECTED CEILING PLANS.
2. EXPOSED SPRINKLERS SHALL BE INSTALLED ACCORDING TO NFPA 13.
3. REFER TO FP111 FOR HAZARD CLASSIFICATIONS.
4. DUCTWORK IS WIDER THAN 48" IN MECHANICAL ROOM AND WAREHOUSE. PROVIDE SPRINKLER PROTECTION ABOVE AND BELOW DUCTWORK IN ACCORDANCE WITH NFPA 13. REFER TO MH101 AND
M-401 FOR DUCT LOCATIONS. COORDINATE EXACT LOCATION IN SHOP DRAWINGS BY NOTING
DUCTWORK GREATER THAN 48" LOCATION ON FIRE PROTECTION SHOP DRAWINGS.
N 0 4' 8' 16' 24'
1/8" = 1'-0"
1/8" = 1'-0"
FIRST FLOOR PLAN - FIRE PROTECTION - NEW WORK
CODED NOTES:
PROVIDE ESFR SPRINKLER HEADS WITHIN THIS AREA. FOR RACK STORAGE OF CLASS I THROUGH
CLASS IV AND EXPOSED NONEXPANDED GROUP 'A' PLASTICS.
PROVIDE QUICK RESPONSE SPRINKLER HEADS FOR LIGHT AND ORDINARY HAZARD CLASSIFICATIONS
IN THIS AREA.
9' - 0" WIDE OVERHEAD DOOR. PROVIDE A SAIDEWALL SPRINKLER HEAD UNDER DOOR TRACK FOR
HAZARD CLASSIFICATION SHOWN ON FP111 PER NFPA 13 9.5.5.3.
PROVIDE HIGH TEMPERATURE SPRINKLER HEAD IN THIS AREA.
FE
JOCKEY PUMP CONTROLLER
FIRE SERVICE
TO FDC
JOCKEY PUMP
F
KEY NOTES:
5' -0
M
IN
IM
U M
(T Y
P
IC
A L)
TO HOSE
VALVE TEST
HEADER
BY-PASS
FIRE PUMP CONTROLLER
WITH TRANSFER SWITCH
TO SYSTEM
ELECTRIC
FIRE PUMP
FIRE PUMP PRESSURE SENSING LINE.
JOCKEY PUMP PRESSURE SENSING LINE.
6" HIGH CONCRETE PAD.
0'-4" HIGH CONCRETE PAD. GROUT BASE.
ECCENTRIC REDUCER WITH PRESSURE GAUGE. INSTALL REDUCER WITH
STRAIGHT SIDE ON TOP.
CONCENTRIC REDUCER WITH PRESSURE GAUGE.
SWING TYPE CHECK VALVE WITH 3/32" ORIFICE IN CLAPPER.
FULL SIZE DRAIN FROM PACKING BOX TO FLOOR DRAIN.
SWING TYPE CHECK VALVE.
WAFER TYPE ANTI-WATER HAMMER CHECK VALVE; 250 PSI RATED.
AUTOMATIC AIR RELEASE VALVE.
OS&Y VALVE WITH TAMPER SWITCH.
BUTTERFLY VALVE WITH TAMPER SWITCH.
BUTTERFLY VALVE (NORMALLY CLOSED) WITH TAMPER SWITCH.
AUTOMATIC BALL DRIP.
FLOW SWITCH.
PRESSURE RELIEF VALVE.
LISTED WATER METERING DEVICE.
FS
M
14131013
FP401
8" FM
1" FM
8" FM
6" FM
8" FM TO FIRE PUMP TEST
HEADER AND SYSTEM OUTLET.
SIZE PIPING PER NFPA 20.
8" FM
8" FM
FIRE PUMP BYPASS
8" FM
8" FM
8" FM
JOCKEY
PUMP
FIRE
PUMP
ALARM CHECK
VALVES
DRAIN PIPING
SIZED PER NFPA 13
8" FM HEADER
FOR RISERS AND
FDC CONNECTION
1 1/4" FM
1/2" FM FIRE
PUMP PRESSURE
SENSING LINE
1/2" FM JOCKEY
PUMP PRESSURE
SENSING LINE
8" FM
CONCRETE PAD WITH
VIBRATION CONTROL
4" FM
FLOW METER LOOP
FP401
4" FM TO
SPRINKLER
ZONE #2
6" FM TO
SPRINKLER
ZONE #1
6" FM TO FDC.
6" FM4" FM
8" FM
6" FM
1 1/4" FM
1 1/4" FM TO JOCKEY PUMP
8" FM TO FIRE PUMP
2" DRAIN TO EXTERIOR SPLASHBLOCK
CC
FP401
FP401
JOCKEY PUMP
CONTROL PANEL
FIRE PUMP CONTROL PANEL
WITH TRANSFER SWITCH
JOCKEY PUMP
FIRE PUMP
FP-1
8" FM U/G
6" FM
4" FM TO
SPRINKLER
ZONE #2
REFER TO FP112 FOR
CONTINUATION OF 6" FM
1/2" FM
1/2" FM
8" FM
6" FM
8" FM
C
4" FM
6" FM U/G
8" FM U/G
(TO REMOTE
TEST HEADER)
(TO REMOTE
STORZ FDC)
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10 www.abovegroupinc.com COA/CA Lic. No. 31120
FULLY SPRINKLERED305 East Dr., Suite H, Melbourne, Florida 32904
PH: 321.345.9026
A u to d e s k D o c s
/0
V A
M C
B u tl e r
V
IS
N
W a re h o u s e
/0
V A
B u tl e r_ V
IS
N
W a re h o u s e
R
M
E P
F P
F A
T .r v t
/2
/2
:5
:2
A
M
FP401
FIRE PUMP SCHEDULES,
SCHEMATICS, & SECTIONS
CONSTRUCT A WAREHOUSE
FOR VISN 4 WESTERN
MARKET DISTRIBUTION
BUTLER, VA
529-314
06/02/2025 JMC AJZ
BID DOCUMENTS
ALLEN LANTZ III, P.E.
PA License #PE091315
FIRE PUMP SCHEDULE
FIRE PUMP
NO. TYPE
FIRE PUMP SPECIFICATIONS JOCKEY PUMP SPECIFICATIONS ELECTRICAL DATA
FIRE PUMP
WEIGHT (LBS)
JOCKEY PUMP
WEIGHT (LBS)
BASIS OF DESIGN
PUMP TYPE
CAPACITY
(GPM)
HEAD
(PSI)
MOTOR
HP
MOTOR
RPM
CAPACITY
(GPM)
HEAD
(PSI)
MOTOR
HP
MOTOR
RPM V PH HZ MANUFACTURER
FIRE PUMP
MODEL NO.
JOCKEY PUMP
MODEL NO.
FP-1 ELECTRIC HORIZONTAL SPLIT CASE 1500 90 75 1800 150 100 15 3600 460 3 60 1600 190 ARMSTRONG HSC 8x6x15NF 4700-VMS-3203
NOTES:
1. FIRE PUMP COMPONENTS TO BE INCLUDED:
A. ELECTRONIC FIRE PUMP AND MOTOR
B. ELECTRIC FIRE PUMP CONTROLLER WITH TRANSFER SWITCH
C. ELECTRONIC JOCKEY PUMP
D. ELECTRIC JOCKEY PUMP CONTROLLER
E. CITY BY-PASS LOOP
F. FIRE PUMP TEST HEADER
2. COORDINATE ELECTRICAL CONNECTION POINTS WITH ELECTRICAL CONTRACTOR. REFER TO ELECTRICAL FOR MORE INFORMATION.
A. CONNECTION #1: 480 VOLT 3 PHASE 60 HZ CONNECTION TO FIRE PUMP CONTROL PANEL.
B. CONNECTION #2: 480 VOLT 3 PHASE 60 HZ CONNECTION TO JOCKEY PUMP CONTROL PANEL.
N.T.S.1
ELECTRIC FIRE PUMP SCHEMATIC
1/2" = 1'-0"
FIRE PUMP SECTION 0 1' 2' 4' 6'
1/2" = 1'-0"1/2" = 1'-0"
FIRE RISERS SECTION
DRAWING NOTES:
1. ALL PIPE SIZES AND PUMP SIZES SHALL BE CONFIRMED BY THE ENGINEER COMPLETING HYDRAULIC
CALCULATIONS.
CODED NOTES:
4" AND 6" WET RISER. REFER TO FIRE SERVICE ENTRANCE DETAIL ON SHEET FP501.
TERMINATE 2" MAIN DRAIN 24" ABOVE GRADE. DISCHARGE TO SPLASH BLOCK.
6" FM TO (2) 2-1/2" 90 DEGREE FREESTANDING FDC. PROVIDE SIGNAGE FOR FDC AS REQUIRED. OFFSET
FOR FDC CONNECTION IS SHOWN FOR WATER ENTRANCE CLARITY.
PIPING TO MATCH CIVIL INVERTS. REFER TO FP100 AND CIVIL DRAWINGS FOR CONTINUATION.
8" FM DN. SPLIT FM INTO (2) 8" CONNECTIONS. (1) 8" FM DN TO FREESTANDING FIRE PUMP TEST HEADER. (1) 8" FM DN TO SYSTEM OUTLET THROUGH A GOOSNECK TO MEET REQUIREMENTS IN VA FIRE PROTECTION DESIGN GUIDE TO HAVE A SECOND OUTLET FOR AN INVERTED U FIRE PUMP PIPING
ARRANGEMENT.
PROVIDE THRUST BLOCK. REFER TO DETAIL 9 ON SHEET FP501.
1/2" = 1'-0"
ENLARGED FIRE PUMP ROOM - FIRE PROTECTION
N
Revisions Date
1. WALL ASSEMBLY--THE 1, 2, 3 OR 4 HR FIRE-RATED GYPSUM
WALLBOARD/STUD WALL ASSEMBLY SHALL BE CONSTRUCTED OF THE
MATERIALS AND IN THE MANNER DESCRIBED IN THE INDIVIDUAL U300 OR
U400 SERIES WALL OR PARTITION DESIGNS IN THE UL FIRE RESISTANCE
DIRECTORY AND SHALL INCLUDE THE FOLLOWING CONSTRUCTION
FEATURES:
A. STUDS--WALL FRAMING MAY CONSIST OF EITHER WOOD STUDS
(MAX 2 H FIRE RATED ASSEMBLIES OR STEEL CHANNEL STUDS.
WOOD STUDS TO CONSIST OF NOM 2 BY 4 IN. LUMBER SPACED 16
IN. OC WITH NOM 2 BY 4 IN. LUMBER END PLATES AND CROSS
BRACES. STEEL STUDS TO BE MIN 3-5/8 IN. WIDE BY 1-3/8 IN. DEEP
CHANNELS SPACED MAX 24 IN. OC.
B. WALLBOARD, GYPSUM *--NOM 1/2 OR 5/8 IN. THICK, 4 FT. WIDE WITH
SQUARE OR TAPERED EDGES. THE GYPSUM WALLBOARD TYPE,
THICKNESS, NUMBER OF LAYERS, FASTENER TYPE AND SHEET
ORIENTATION SHALL BE AS SPECIFIED IN THE INDIVIDUAL U300 OR
U400 SERIES DESIGN IN THE UL FIRE RESISTANCE DIRECTORY. MAX
DIAM OF OPENING IS 13-1/2 IN.
2. PIPE OR CONDUIT--NOM 12 IN. DIAM (OR SMALLER) SCHEDULE 10 (OR
HEAVIER) STEEL PIPE, NOM 12 IN. DIAM (OR SMALLER) SERVICE WEIGHT (OR
HEAVIER) CAST IRON SOIL PIPE, NOM 12 IN. DIAM (OR SMALLER) CLASS 50
(OR HEAVIER) DUCTILE IRON PRESSURE PIPE, NOM 6 IN. DIAM (OR SMALLER)
STEEL CONDUIT, NOM 4 IN. DIAM (OR SMALLER) STEEL ELECTRICAL
METALLIC TUBING, NOM 6 IN. DIAM (OR SMALLER) TYPE L OR (OR
HEAVIER) COPPER TUBING OR NOM 1 IN. DIAM (OR SMALLER) FLEXIBLE
STEEL CONDUIT. WHEN COPPER PIPE IS USED, MAX F RATING OF FIRESTOP
SYSTEM (ITEM 3) IS 2 H. STEEL PIPES OR CONDUITS LARGER THAN NOM 4 IN.
DIAM MAY ONLY BE USED IN WALLS CONSTRUCTED USING STEEL CHANNEL
STUDS. A MAX OF ONE PIPE OR CONDUIT IS PERMITTED IN THE FIRESTOP
SYSTEM. PIPE OR CONDUIT TO BE INSTALLED NEAR CENTER OF STUD
CAVITY WIDTH AND TO BE RIGIDLY SUPPORTED ON BOTH SIDES OF WALL
ASSEMBLY.
3. FILL, VOID OR CAVITY MATERIAL*--CAULK--CAULK FILL MATERIAL INSTALLED
TO COMPLETELY FILL ANNULAR SPACE BETWEEN PIPE OR CONDUIT AND
GYPSUM WALLBOARD AND WITH A MIN 1/4 IN. DIAM BEAD OF CAULK APPLIED
TO PERIMETER OF PIPE OR CONDUIT AT ITS EGRESS FROM THE WALL.
CAULK INSTALLED SYMMETRICALLY ON BOTH SIDES OF WALL ASSEMBLY.
THE HOURLY F RATING OF THE FIRESTOP SYSTEM IS DEPENDENT UPON
THE HOURLY FIRE RATING OF THE WALL ASSEMBLY IN WHICH IT IS
INSTALLED, AS SHOWN IN THE FOLLOWING TABLE. THE HOURLY T RATING
OF THE FIRESTOP SYSTEM IS DEPENDENT UPON THE TYPE OR SIZE OF THE
PIPE OR CONDUIT AND THE HOURLY FIRE RATING OF THE WALL ASSEMBLY
IN WHICH IT IS INSTALLED, AS TABULATED BELOW:
Max pipe or Conduit Diam
In.
+When copper is used, T Rating is 0h.
SECTION A-A
12 3/16 to 3/8
1/4 to 1/2
0 to 1-1/2
1/4 to 1/2
3 to 3/16
3 or 4
1 or 2
1 or 2
3 or 4
1 or 2 0
0+, 1 or 2
3 or 4
Minnesota Mining & Mfg. Co .--Types FB-2000, FB-2000+.
*Bearing the UL Classification Marking
System No. W-L-1001 (Formerly System No. 147)
F Rating--1, 2, 3 and 4 Hr (See Items 2 and 3) T Ratings--0, 1, 2, 3, and 4 Hr (See Items 2 and 3)
L Rating at Ambient--less than 1 CFM/sq ft L Rating At 400 F--less than 1 CFM/sq ft
Annular Space In. F Rating Hr. T Rating Hr.
A
A
1B
1A
A
4A
4 1
SECTION A-A
System No. C-AJ-1044 (formerly system no. 319)
F Rating - 2, 3 and 4 Hr (see items 2A and 4) T Rating - 0 Hr
L Rating At Ambient - 2 CFM/sq ft L Rating At 400 F - less than 1 CFM/sq ft
1. FLOOR OR WALL ASSEMBLY - LIGHTWEIGHT OR NORMAL WEIGHT (100-150PCF) CONCRETE. EXCEPT AS NOTED IN TABLE UNDER ITEM 4, MIN THICKNESS OF SOLID CONCRETE FLOOR OR WALL ASSEMBLY IS 4-1/2". FLOOR MAY ALSO BE CONSTRUCTED OF A MIN. 6" THICK. UL CLASSIFIED HOLLOW CORE PRECAST CONCRETE UNITS*. WHEN FLOOR IS CONSTRUCTED OF HOLLOW CORE PRECAST CONCRETE UNITS, PACKING MATERIAL (ITEM 3) AND CAULK FILL MATERIAL (ITEM 4) TO BE INSTALLED SYMMETRICALLY ON BOTH SIDES OF FLOOR, FLUSH WITH FLOOR SURFACE. WALL ASSEMBLY MAY ALSO BE CONSTRUCTED OF ANY UL CLASSIFIED CONCRETE BLOCKS*. MAX. DIA. OF OPENING IS IN SOLID LIGHTWEIGHT OR NORMAL WEIGHT CONCRETE. FLOOR IS 32" MAX. DIA. OF OPENING IN FLOOR CONSTRUCTED OF
HOLLOW-CORE PRECAST CONCRETE UNITS IS 7".
SEE CONCRETE BLOCKS (CAT) AND PRECAST CONCRETE UNITS (CT) CATEGORIES IN THE FIRE RESISTANCE
DIRECTORY FOR NAMES OF MANUFACTURERS.
1A. STEEL SLEEVE - (OPTIONAL, NOT SHOWN) - MAX. 15" ID (OR SMALLER) SCHEDULE 10 (OR HEAVIER) STEEL SLEEVE CAST OR GROUTED INTO FLOOR OR WALL ASSEMBLY. SLEEVE MAY EXTEND A MAX. OF 2" ABOVE TOP OF FLOOR OR BEYOND EITHER SURFACE OF WALL. MAX. 16" ID (OR SMALLER) MIN. 0.028 WALL THICKNESS (OR HEAVIER) GALVANIZED STEEL SLEEVE CAST OR GROUTED INTO FLOOR OR WALL ASSEMBLY. SLEEVE MAY EXTEND A MAX. OF 1/2" BEYOND
EITHER SURFACE OF FLOOR OR WALL.
2. THROUGH ENTRANTS - ONE METALLIC PIPE, CONDUIT OR TUBING TO BE INSTALLED EITHER CONCENTRIC ALLY OR ECCENTRICALLY WITHIN THE FIRESTOP SYSTEM. MAX. ANNULAR SPACE BETWEEN PIPE, CONDUIT OR TUBING AND EDGE OF THROUGH OPENING OR SLEEVE IS DEPENDENT ON THE PARAMETERS SHOWN IN ITEM 4. MIN. ANNULAR SPACE BETWEEN PIPE OR CONDUIT AND EDGE OF THROUGH OPENING IS 0". (POINT CONTACT). PIPE CONDUIT OR TUBING TO BE RIGIDLY SUPPORTED ON BOTH SIDES OF FLOOR OR WALL ASSEMBLY. THE FOLLOWING TYPES AND SIZES
OF METALLIC PIPES, CONDUITS OR TUBING MAY BE USED
A. STEEL PIPE - NOM. 30" DIA. (OR SMALLER) SCHEDULE 10 (OR HEAVIER) STEEL PIPE
B. IRON PIPE - NOM. 30" DIA. (OR SMALLER) CAST OR DUCTILE IRON PIPE
C. CONDUIT - NOM. 6" DIA. (OR SMALLER) RIGID STEEL CONDUIT
D. CONDUIT - NOM. 4" DIA. (OR SMALLER) STEEL ELECTRICAL METALLIC TUBING
E. COPPER TUBING - NOM. 8" DIA. (OR SMALLER) TYPE L (OR HEAVIER) COPPER TUBE
F. COPPER PIPE - NOM. 6" DIA. (OR SMALLER) REGULAR (OR HEAVIER) COPPER PIPE
3. PACKING MATERIAL - POLYETHYLENE BACKER ROD OR NOM. 1" THICKNESS OF TIGHTLY PACKED MINERAL WOOL BATT OR GLASS FIBER INSULATION FIRMLY PACKED INTO OPENING AS A PERMANENT FORM. PACKING MATERIAL TO BE RECESSED FROM TOP SURFACE OF FLOOR OR FROM BOTH SURFACES OF WALL AS REQUIRED TO
ACCOMMODATE THE REQUIRED THICKNESS OF CAULK FILL MATERIAL (ITEM 4).
4. FILL, VOID OR CAVITY MATERIAL* - CAULK - APPLIED TO FILL THE ANNULAR SPACE FLUSH WITH TOP SURFACE OF FLOOR. IN WALL ASSEMBLIES, REQUIRED CAULK THICKNESS TO BE INSTALLED SYMMETRICALLY ON BOTH SIDES OF WALL, FLUSH WITH WALL SURFACE, AT POINT CONTACT LOCATION BETWEEN PENETRANT AND SLEEVE OR BETWEEN PENETRANT AND CONCRETE, A MIN. 1/4" DIA. BEAD OF CAULK SHALL BE APPLIED AT TOP SURFACE PIPE CONDUIT OR TUBING TO BE RIGIDLY SUPPORTED ON BOTH SIDES OF FLOOR OR WALL OF FLOOR AND AT BOTH SURFACES OF WALL.
THE HOURLY F RATINGS AND THE MIN. REQUIRED CAULK THICKNESS' ARE DEPENDENT UPON A NUMBER OF
PARAMETERS, AS SHOWN IN THE FOLLOWING TABLE:
min. floor or wall nom. pipe tube or conduit thickness, in. dia.., in.
max. annular space, in. thickness, in.
min. caulk f rating, hr.
21/21-3/81/2-122-1/2
22-1/2 1/2-12 3-1/4 1
24-1/2 1/2-6 1-3/8 1/4 (A)
34-1/2 1/2-12 1-1/4 1/2
4-1/2 1/2-20 2 1 3
4-1/2
1/2-6
2 1
34-1/2 1/2-12 3-1/4 1
44-1/2
1/2-20
1-3/8 1 (B)
(A) min. 2" thickness of mineral wool batt insulation required in annular space.
(B) min. 1" thickness of mineral wool batt insulation required in annular space. on both sides of floor or wall assembly. min 1" thickness of caulk to be installed flush with each surface of floor or wall assembly.
minnesota mining and manufacturing co. - cp 25wb+.
*bearing the ul classification marking
CEILING ESCUTCHEON
FINISH
CEILING
SUPPLY LINE
REDUCING
COUPLING
ALL THREAD ROD
PIPE
MODEL 300 WICHLGAN TOP
BEAM CLAMP OR EQUAL
W/LOCK NUT
SWIVEL RING
STEEL I-BEAM OR
BAR JOIST
4" T
O
DEFLECTOR
REDUCER
WALL
OBSTRUCTION
SPRINKLER
BRANCH LINE
IF OFFSET LENGTH
EXCEEDS 2', PROVIDE
PIPE HANGER
DROP NIPPLE
CLOSE NIPPLE
THREADED 90°
ELBOW (TYPICAL)
REDUCER SUSPENDED CEILING
SPRINKLER PER SPECIFICATION
(PENDENT SPRINKLER SHOWN)
6"
PIPE DRAIN TO EXTERIOR AT
APPROXIMATELY 2'-0" ABOVE
GRADE. PROVIDE CONCRETE
SPLASH BLOCK2"
6" FM TO FSZ-1
FINISHED
FLOOR
CHECK VALVE
PIPE TO DRAIN
DRIP RECEIVER
RETARDING
CHAMBER
THREE WAY
ALARM AND
TEST COCK
PIPING CONNECTION
TO WATER MOTOR
GONG
PRESSURE GAUGE (TYP)
MAIN DRAIN
(TYP)
RESTRICTION CHECK
AND BYPASS
CONNECTION
FLOW SWITCH (TYP)
ANGLE VALVE
(TYP)
WET ALARM
CHECK VALVE
GRADE
2" DRAIN
6" x 4" TAG. SPRINKLER
CONTRACTOR TO
IDENTIFY SYSTEM
NUMBER (TYP)
ESCUTCHEON
(TYPICAL)
CONCRETE
SPLASH BLOCK
SEAL WALL PENETRATION
WATER TIGHT (TYP)
O.S.&Y. VALVE
WITH TAMPER
SWITCH (TYP)
CHECK VALVE
6"
4" FM TO FSZ-2
SEAL WALL PENETRATION
WATER TIGHT
6"
2"
4" 6"
6" FM FREESTANDING FDC
8" FP FROM
FIRE PUMP
DISCHARGE
FINISHED
FLOOR
8" FM TO FIRE
PUMP SUCTION
8" FM TO BUILDING
8"8" CAP FIRE RISER
HEADER PIPING
8" DCDA BACKFLOW
PREVENTER WITH CONTROL
VALVES AND TAMPER
SWITCHES.
SUPPORT PIPING AS
NECESSARY WITH
FLOOR PIPE STANDS
FLANGE CONNECTION. PROVIDED BY
FIRE PROTECTION CONTRACTOR AND
INSTALLED BY CIVIL CONTRACTOR.
COORDINATE INSTALLATION
LOCATION WITH CIVIL CONTRACTOR.
TOP OF FLANGE CONNECTION SHALL BE SET AT 18" AFF. COORDINATE
INSTALLATION OF FLANGE WITH CIVIL CONTRACTOR. CIVIL
CONTRACTOR SHALL INSTALL ALL ITEMS UP TO AND INCLUDING
FLANGE. FIRE PROTECTION CONTRACTOR TO COORDINATE
LOCATION OF FLANGE WITH CIVIL CONTRACTOR. CIVIL CONTRACTOR
TO CAP 8" PIPING AT FLANGE FOR CONNECTION BY FIRE PROTECTION
CONTRACTOR. FIRE PROTECTION CONTRACTOR TO REMOVE CAP TO
INSTALL FIRE PROTECTION PIPING AT THE PROVIDED FLANGE.
CONCRETE THRUST BLOCK. CONCRETE
SHALL NOT CONTACT BLOTS OF ENDS
OF MECHANICAL FITTINGS.
THRUST BLOCK
6" TO FIRE PUMP
ROOM
FINISH GRADE
1' -6
CONTRACTOR TO PROVIDE FDC SIGN TO READ "FIRE
DEPARTMENT CONNECTION FOR BUILDING #xxx" CONFIRM
BUILDING NUMBER WITH VA COR. MOUNT PANEL TO
GALZANIZED "U" CHANNEL 3' - 0" BEHIND FDC SO THAT IS
LEGIBLE FROM ROAD. PROVIDE FIRE PUMP TEST
HEADERSIGN TO READ "TEST FOR BUILDING #xxx"
CONFIRM BUILDING NUMBER WITH VA COR. TEST HEADER
SINAGE TO BE INSTALLED IN SAME MANNER OF FDC.
4" STORZ CONNECTION OR FIRE PUMP
TEST HEADER. PROVIDE ALL HOSE
CONNECTIONS WITH KNOX LOCKING CAPS
M
IN
IM
U
M
4' -0
M
IN
IM
U
M
BALL DRIP IN #4
CRUSHED STONE
12" x 12" x 4"
CONCRETE PAD
SECTION VIEW PLAN VIEW
12" x 12" x 4"
CONCRETE PAD
(TYP)
FDC/TEST HEADER
FDC/TEST
HEADER
SINAGE
BOLLARD. REFER TO CONCRETE
BOLLARD DETAIL IN CIVIL
DRAWINGS FOR CONSTRUCTION
AND PAINTING REQUIREMENTS.
(TYP)
3' - 0" CLEARANCE SHALL
BE MAINTAINED AROUND
FDC/TEST HEADER.
FIRE DEPARTMENT ACCESS
TO THIS SIDE OF EQUIPMENT
EARTH
MECHANICAL RESTRAINT JOINTCONCRETE
THRUST BLOCK
MECHANICAL RESTRAINT JOINT
DETAIL "BB"
B B
NOTE:
THRUST BLOCKS SHALL BE POURED AGAINST UNDISTURBED EARTH.
WHERE TRENCH WALLS HAVE BEEN DISTURBED EXCAVATE ALL LOOSE
EARTH AND EXTEND THRUST BLOCK TO UNDISTURBED EARTH.
PROVIDE EITHER A THRUST BLOCK OR RETAINER GLAND AT EACH
TRANSITION.
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10 www.abovegroupinc.com COA/CA Lic. No. 31120
FULLY SPRINKLERED305 East Dr., Suite H, Melbourne, Florida 32904
PH: 321.345.9026
A u to d e s k D o c s
/0
V A
M C
B u tl e r
V
IS
N
W a re h o u s e
/0
V A
B u tl e r_ V
IS
N
W a re h o u s e
R
M
E P
F P
F A
T .r v t
/2
/2
:5
:3
A
M
FP501
FIRE PROTECTION DETAILS CONSTRUCT A WAREHOUSE
FOR VISN 4 WESTERN
MARKET DISTRIBUTION
BUTLER, VA
529-314
06/02/2025 JMC AJZ
BID DOCUMENTS
ALLEN LANTZ III, P.E.
PA License #PE091315
N.T.S.1
WALL - DRYWALL - PIPE - 1/2/3/4 HR
N.T.S.3
WALL/FLR - CONC - PIPE - 2/3/4 HR
N.T.S.4
PENDENT SPRINKLER HEAD DETAIL
N.T.S.6
BOTTOM BEAM CLAMP DETAIL
N.T.S.7
SIDEWALL SPRINKLER HEAD DETAIL
N.T.S.2
RETURN BEND DETAIL
N.T.S.5
FIRE SERVICE AND FIRE RISERS DETAIL
N.T.S.8
FREESTANDING FDC AND TEST HEADER DETAIL
N.T.S.9
THRUST BLOCK DETAIL
| Sheets |
| FP001 - FIRE PROTECTION LEGENDS & SYMBOLS |
| FP100 - FIRE PROTECTION SITE PLAN |
| FP111 - HAZARD CLASSIFICATION PLAN - FIRE PROTECTION - NEW WORK |
| FP112 - PIPING FLOOR PLAN - FIRE PROTECTION - NEW WORK |
| FP401 - FIRE PUMP SCHEDULES, SCHEMATICS, & SECTIONS |
| FP501 - FIRE PROTECTION DETAILS |
File details come from the government source that posted it. Updated .