This CFD analysis report details simulations performed to analyze cooling requirements for an infrastructure upgrade project at the Sheridan VA Medical Center data center in Sheridan, Wyoming. Iterative simulations were run adjusting the supply airflow and temperature from a computer room air conditioner unit to achieve an average data rack inlet air temperature of 72 to 80.6 degrees Fahrenheit, with a minimum of 20 degrees temperature difference between supply and return air, as required by VA infrastructure standards. The simulations showed the data rack inlet air temperatures would range from 69 to 76 degrees Fahrenheit with a supply air flow rate of 6,500 cubic feet per minute and supply air temperature of 68 degrees Fahrenheit.

The related federal contract opportunity is a solicitation from the Department of Veterans Affairs Technology Acquisition Center in Austin for infrastructure upgrades construction work at the Sheridan VA Medical Center data center in Sheridan, Wyoming.

View the file

Other files

File Type Posted
Addendum 1 2.14.24.pdf PDF
Technical Questions Tracking Spreadsheet - Sheridan IU Construction 2.20.24.pdf PDF
36C77623B0073 0007.docx DOCX document
36C77623B0073 Amendment 0006.docx DOCX document
Technical Questions Tracking Spreadsheet - Sheridan IU Construction.pdf PDF
Addendum 1.pdf PDF
36C77623B0073 Amendment 0005.docx DOCX document
VHA PCRA 31May2023-Final 700 PA 03JAN24.pdf PDF
36C77623B0073 0004.docx DOCX document
VHA PCRA 31May2023-Final 700 NPA 03JAN24.pdf PDF
Sign In Sheet - 1.11.24.pdf PDF
Wage Determination - Sheridan 1.12.24.pdf PDF
36C77623B0073 0003.docx DOCX document
04 M4.00thruE1-05-2.pdf PDF
07 E1-64-1thruE1-71N-2.pdf PDF
08 E1-71N-3thruE3.pdf PDF
36C77623B0073 Amendment 0002.docx DOCX document
04 M4.00thruE1-05-2.pdf PDF
10 TY-001thruTY-G-1.pdf PDF
08 E1-71N-3thruE3.pdf PDF
36C77623B0073 Amendment 0001.docx DOCX document
09 E4thruTY-000.pdf PDF
Notice for Price Schedule - 12-20-2023.docx DOCX document
07 E1-64-1thruE1-71N-2.pdf PDF
06 E1-11thruE1-61.pdf PDF
SCHEDULE Sheridan 12-20-2023.docx DOCX document
05 E1-06-1thruE1-09-3 (2).pdf PDF
36C77623B0073_1 12.19.23.docx DOCX document
Wage Determination - Sheridan 11.23.pdf PDF
Spec Combined Volume 1.pdf PDF
Limitations on Subcontracting - Construction.docx DOCX document
36C77623B0073_1.docx DOCX document
01 G0-00thruCU114.pdf PDF
Site Visit Instructions.docx DOCX document
Spec Combined Volume 2 Revised 10 2 2023.pdf PDF
02 DT100thruA1-32.pdf PDF
HAZMAT_1.pdf PDF
Sheridan EHRM Finish Board.pdf PDF
03 A1-35thruM1.G.pdf PDF
Show all 39

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

EHRM Infrastructure Upgrades –

Data Center at the Sheridan VA Medical Center, Sheridan, WY

100% SUBMITTAL

CFD Analysis Report

V A P R O J E C T NO. : 259 – 1 6 – D – 0 2 1 7

July 18, 2023

1.0 CFD Modeling

CFD modelling was performed with the new computer room air conditioner (CRAC-1). The backup data center AHU-8B is to be set to the same output parameters (CFM and supply air temperature).

AHU-8B was not included in the CFD model due to the fact it serves the same raised floor plenum and utilizes the same ceiling returns. The results of the CFD model would be the same with either unit running. The data rack layout, air curtain baffles, floor supply tiles and ceiling return grilles were modeled as shown in the plan documents. The results shown below were achieved with a supply air flowrate of 6500cfm and a supply air temperature of 68°F. Iterative simulations were performed adjusting cooling unit airflow and supply air temperature to achieve an average data rack inlet temperature of 72-80.6°F and a minimum of 20° ∆T between supply and return airflow (per the VA Infrastructure Standard for Telecommunications Spaces (ISTS) v4.0 June 1, 2023).

Shown below are the simulation parameters of the cooling unit.

The data rack inlet temperature results are shown in the heatmap below. The average data rack inlet air temperatures range from 69°F to 76°F.

File details come from the government source that posted it. Updated .