This document provides details on a federal contract opportunity to expand the emergency department at Lake Nona VA Medical Center. The solicitation number is 36C77622B0023_1 for the project titled "Expand Emergency Department Minor Construction Lake Nona." The opportunity type is a solicitation issued by the Department of Veterans Affairs Technology Acquisition Center located in Austin, Texas. The solicitation seeks construction services to expand the emergency department at the Lake Nona VA Medical Center in Orlando, Florida. Interested contractors should respond with pricing and qualifications by the specified response date. The award date listed is for September 2022, with work to be completed within one year.
View the file
Other files
Show all 35
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
11.
12.
13.
14.
15.
16.
17.
18.
19.
20.
21.
22.
23.
24.
25.
26.
27.
28.
29.
30.
31.
32.
33.
PLUMBING GENERAL NOTES
ALL PLUMBING WORK SHALL BE IN ACCORDANCE WITH 2021 VA PLUMBING DESIGN MANUAL, 2020 7TH
EDITION FLORIDA BUILDING CODE - PLUMBING, AND VA FACILITY STANDARDS.
LOCATE VALVES IN ACCESSIBLE AREAS AND PROVIDE ACCESS PANELS WHERE NECESSARY. (12"X12"
MIN.)
COORDINATE ACTUAL LOCATIONS OF MECHANICAL FLOOR DRAINS WITH FINAL EQUIPMENT
LOCATIONS ON SHOP DRAWINGS.
VENT PIPING SHOWN IS ONLY FOR DIAGRAMMATIC PURPOSES. COORDINATE VTRS WITH HVAC AIR
INTAKES AND MAINTAIN A MINIMUM 25 FT CLEARANCE FROM AIR INTAKES.
PROVIDE BACKWATER VALVES FOR CONDENSATE PIPING CONNECTIONS TO STORM SEWER.
PROVIDE PIPE MARKER FOR ALL PIPING ABOVE THE CEILING SPACES IN ACCORDANCE WITH
SPECIFICATIONS AND FACILITY STANDARDS.
LABEL VALVES ABOVE CEILINGS AND IN CONCEALED SPACES AT CEILING TILE WITH METAL CEILING TACKS INDICATING VALVE # AND TYPE OF WATER. (i.e.; BLUE= COLD WATER, LETTERING CW
VLV1-001).
PROVIDE AND INSTALL WATER HAMMER ARRESTORS ON ALL HW AND CW SUPPLY PIPING WITH QUICK
CLOSING VALVES IN ACCORDANCE WITH PDI-WH201 STANDARDS. AIR CHAMBERS ARE NOT
ACCEPTABLE SUBSTITUTIONS.
PROVIDE THERMAL INSULATION FOR HOT WATER AND HOT WATER RETURN PIPING IN ACCORDANCE WITH THE ENERGY EFFICIENCY CODE FOR BUILDING CONSTRUCTION AND PER SPECIFICATIONS.
PROVIDE CLEANOUTS AT THE BASE OF EACH SANITARY STACK, ALONG HORIZONTAL RUNS SPACED AT 100'-0" INTERVALS AND AT HORIZONTAL CHANGE OF DIRECTION > THAN 45° IN ACCORDANCE WITH
FLORIDA BUILDING CODE - PLUMBING. SIZE CLEANOUTS TO MATCH THE PIPING SERVED.
FIRE CAULK AND SLEEVE PENETRATIONS THROUGH FIRE RATED ASSEMBLIES. REFER TO LIFE
SAFETY PLANS FOR RATED ASSEMBLY LOCATIONS. REFER TO ARCHITECTURAL SHEETS FOR
DETAILS AND UL ASSEMBLY NUMBERS.
REFER TO ARCHITECTURAL SHEETS FOR FIXTURE MOUNTING HEIGHTS.
COORDINATE PIPING ELEVATIONS IN SHOP DRAWINGS WITH HVAC, FIRE PROTECTION,
TELECOMMUNICATION, ELECTRICAL AND STRUCTURAL TRADES TO ENSURE PROPER SERVICE
CLEARANCES AND PENETRATIONS, PRIOR TO INSTALLATION.
SLOPE SANITARY PIPING 2-1/2" OR LESS AT 1/4" PER FOOT. SLOPE SANITARY PIPING 3" AND LARGER
AT 1/8" PER FOOT TO ENSURE MINIMUM VELOCITY OF 2 FT/S.
VALVES AND FITTINGS SHALL BE THE SAME SIZE AS THE PIPING WHERE LOCATED UNLESS
NOTED OTHERWISE.
PROVIDE ALL NECESSARY SUPPORTING DEVICES FOR FIXTURES PER MANUFACTURER INSTALLTAION
INSTRUCTIONS.
FLOOR DRAINS NOT RECEIVING CONTINUOUS DISCHARGE SHALL BE PROVIDED WITH TRAP PRIMER
CONNECTIONS. PROVIDE DEEP SEAL P-TRAPS ON ALL FLOOR DRAINS.
ROUGH-IN WASTE AND WATER SUPPLIES FOR FIXTURES AND PERFORM FINAL CONNECTIONS AS
REQUIRED PER OWNER RECOMMENDATIONS AND MANUFACTURER INSTALLATION INSTRUCTIONS.
ROUGH-IN WATER CLOSET FLUSH VALVES SO THAT THE FLUSH VALVE HANDLE IS TO THE WIDE SIDE
OF THE ROOM.
COMPLY WITH THE AMERICANS WITH DISABILITIES ACT (ADA) ACCESSIBILITY GUIDELINES FOR
BUILDINGS AND FACILITIES.
DISINFECT DOMESTIC WATER PIPING BY EITHER OF TWO WAYS: FILL SYSTEM WITH 50PPM CHLORINE SOLUTION AND STAND FOR 24 HOURS OR 200PPM CHLORINE SOLUTION AND STAND FOR 3 HOURS.
ALL AUTOMATIC CONTROL PROTECTIVE OR SIGNAL DEVICES REQUIRED FOR THE OPERATION
SPECIFIED, SHALL BE PROVIDED WITH ANY CONTROL WIRING AND INSTALLED PER MANUFACTURER
INSTALLATION REQUIREMENTS.
SANITARY AND VENT PIPING SHALL BE SERVICE WEIGHT NO-HUB CAST IRON PIPE.
ALL HOT, COLD AND HOT WATER RETURN PIPE SHALL BE TYPE 'L' COPPER PIPE.
PROVIDE INDIRECT WASTE WITH AN AIR GAP MINIMUM 2 PIPE DIAMETERS OF THE DRAIN SERVED
FROM INDIVIDUAL FIXTURES, DEVICES, APPLIANCES AND APPARATUS.
DISSIMILAR PIPE CONNECTIONS SHALL BE PROVIDED WITH DIELECTRIC UNIONS.
LOWEST PORTION OF HOT WATER AND HOT WATER RECIRCULATION DISTRIBUTION BRANCH PIPING SHALL BE SLOPED BACK TO A MEANS OF DRAINING SYSTEM AND ALLOW FOR FACILITY THERMAL
FLUSHING REQUIREMENTS.
HOT WATER AND HOT WATER RECIRCULATION PIPING SHALL BE ROUTED UP TO SENSOR FAUCETS AND MIXING VALVES IN ACCORDANCE WITH SECTION 404.5 OF THE 2020 FLORIDA BUILDING CODE, ENERGY CONSERVATION.
COORDINATE PENETRATIONS THRU EXITING SLAB AND DISHING OF SLAB FOR NEW FLOOR DRAINS
WITH STRUCTURAL ENGINEER PRIOR TO CONSTRUCTION.
PROVIDE LOCKABLE BALL VALVES ON BOTH COLD AND HOT WATER SUPPLY TO THERMOSTATIC
MIXING VALVES SERVING EMERGENCY FIXTURES (I.E. EYE WASH, EYE WASH DRENCH SHOWER).
PROVIDE LOCKABLE BALL VALVES ON ALL MEDICAL GAS PIPING. LABEL VALVES WITH THE ROOMS
SERVED
SHOP DRAWINGS SHALL BE FULLY COORDINATED PRIOR TO SUBMITTAL.
HOT WATER RECIRCULATION BRANCHES SHALL BE PROVIDED WIH BALANCING VALVES. REFER TO
THE FLOOR PLANS FOR FLOW RATES.
A
B
SIM
A
DESCRIPTIONSYMBOL
110° HOT WATER PIPINGHW
HOT WATER RETURN PIPINGHWR
STO STORM OVERFLOW (SECONDARY)
ST STORM (PRIMARY)
SANITARY PIPINGS
V VENT PIPING
GATE VALVE
PRESSURE GAUGE
THERMOMETER
CHECK VALVE
BALL VALVE
CIRCULATING PUMP
PIPE END CAP
PIPE TURNING DOWN
PIPE TURNING UP
PIPE TURNING DOWN (TEE)
NATURAL GAS PIPING
LIGHT LINEWORK INDICATES EXISTING PIPING
OR EQUIPMENT
CLEANOUTS
CW COLD WATER PIPING
PLUMBING LEGEND
SECTION SYMBOL:
A = IDENTIFYING LETTER
B = SHEET WHERE SECTION IS SHOWN
SIM =
(ONLY NOTED IF IT APPLIES)
GENERAL LEGEND
PLUMBING RISER DESIGNATION:
A = RISER IDENTIFYING SYSTEM TYPE
1 =
SYMBOL
DESCRIPTION
REVISION CLOUD AND
REVISION NUMBER
KEYED REFERENCE
NOTE OR SHEET NOTE
22-1
A TITLE SYMBOL ON SHEET WHERE SHOWN
A = IDENTIFYING NUMBER/LETTER
CD CONDENSATE PIPING
CIRCUIT SETTER VALVE
OR
PDI-"?" WATER HAMMER ARRESTER & SIZE
THERMOSTATIC MIXING VALVE
HB-? OR WHY-? HOSE BIBB / WALL HYDRANT
FLOW ARROW
P-TRAP
ROLL DOWN
PIPING TEE
POINT OF CONNECTION
NOT ALL SYMBOLS USED
NOT ALL SYMBOLS USED
G
RISER IDENTIFYING SYSTEM NUMBER
PRESSURE REGULATING VALVE
BUTTERFLY VALVE
SIMILAR
MEDICAL AIR PIPINGMA
OXYGEN PIPINGO2
MEDICAL VACUUM PIPINGMV
NITROGEN PIPINGN
NITROUS OXIDE PIPINGN2O
POINT OF DEMOLITION
PIPING ABBREVIATIONS
A/E ARCHITECT / ENGINEER
AD AREA DRAIN/ACCESS DOOR
AFF ABOVE FINISH FLOOR
AFG ABOVE FINISH GRADE
AG AIR GAP
AP ACCESS PANEL
AS AUTOMATIC SPRINKLER
ASD ADJUSTABLE SPEED DRIVES
ASD AUTOMATIC SPRINKLER DRAIN
ASHRAE AMERICAN SOCIETY OF HEATING,
REFRIGERATION, AIR CONDITIONING
ENGINEERS
ASME AMERICAN SOCIETY OF MECHANICAL
ENGINEERS
ASPE AMERICAN SOCIETY OF PLUMBING
ENGINEERS
ASR AUTOMATIC SPRINKLER RISER
AV ACID VENT
AW ACID WASTE
BFP REDUCED PRESSURE BACKFLOW
PREVENTER
BHP BREAK HORSEPOWER
BSP BLACK STEEL PIPE
BT BATHTUB
BTU BRITISH THERMAL UNIT
BTUH BRITISH THERMAL UNIT PER HOUR
C CELSIUS
CA COMPRESSED AIR
CGA COMPRESSED GAS ASSOCIATION
CFM CUBIC FEET PER MINUTE
CI CAST IRON
CO CLEANOUT
CO2 CARBON DIOXIDE
CS CLINICAL SINK
CV CONTROL VALVE
DCW DOMESTIC COLD WATER
DFU DRAINAGE FIXTURE UNITS
DHW DOMESTIC HOT WATER
DHWR DOMESTIC HOT WATER RETURN
DHWS DOMESTIC HOT WATER SUPPLY
DI DEIONIZED WATER
DN DOWN
DOE DEPARTMENT OF ENERGY
DS DOWNSPOUT
DW DISHWASHER
DWG DRAWING
DWH DOMESTIC WATER HEATER
DWR DRINKING WATER RETURN
DWS DRINKING WATER SUPPLY
DWV DRAIN WASTE VENT
EL ELEVATION
EMCS ENERGY MONOSERRAT
AND CENTRAL SYSTEM
EPA ENVIROMENTAL PROTECTION
AGENCY
EPACT ENERGY POLICY ACT
ESC ESCUTCHEON
ESH EMERGENCY SHOWER
ET EXPANSION TANK
EWH ELECTRIC WATER HEATER
EWS EYE WASH STATION
EWS/SH EYE WASH/DRENCH SHOWER
E EXISTING
F FAHRENHEIT
FCO FLOOR CLEANOUT
FCW FILTERED COLD WATER
FD FLOOR DRAIN
FDC FIRE DEPARTMENT
(HOSE) CONNECTION
FM FLOW METER
FOP FUEL OIL PUMP
FOR FUEL OIL RETURN
FOS FUEL OIL SUPPLY
FOV FUEL OIL VENT
FS FLOOR SINK
FS FLOW SWITCH
FT/S FEET PER SECOND
FU FIXTURE UNITS
GAL GALLON
GCO GRADE CLEANOUTS
GPD GALLONS PER DAY
GPH GALLONS PER HOUR
GPM GALLONS PER MINUTE
GPR GAS PRESSURE REGULATOR
GRS GAS REGULATOR STATION
GT GREASE TRAP
GVTR GAS VENT THROUGH ROOF
GWH GAS FIRED WATER HEATER
H&CW HOT AND COLD WATER
HB HOSE BIBB
HD HUB DRAIN
HEX HEAT EXCHANGER
HP HORSEPOWER
HS HAND SINK
HST HOT WATER STORAGE TANK
(DOMESTIC)
HWB HOT WATER BOILER
HWCP HOT WATER CIRCULATING PUMP
HWP HOT WATER PUMP
HYD HYDRANT
ID INSIDE DIAMETER
IE INVERT ELEVATION
ICW INDUSTRIAL COLD WATER
IHW INDUSTRIAL HOT WATER
INV INVERT
IPC INTERNATIONAL PLUMBING CODE
IRW IRRIGATION WATER
IW INDIRECT WASTE
IWH INSTANTANEOUS WATER HEATER
IWR INDUSTRIAL WATER RETURN
IWS INDUSTRIAL WATER SUPPLY
KW KILOWATT
KWH KILOWATT-HOUR
L/S LITER PER SECOND
LA LABORATORY AIR
LAV LAVATORY
LBS/HR POUNDS PER HOUR
LCW LABORATORY COLD WATER
LHW LABORATORY HOT WATER
LNG LIQUID NATURAL GAS
LOX LIQUID OXYGEN
LV LABORATORY VACUUM
LW LOW WATER
M METER
MA MEDICAL AIR
MAV MANUAL AIR VENT
MBH 1000 BTUH
MED MEDICAL
MER MECHANICAL EQUIPMENT
ROOM
MH MANHOLE
MOU MEMORANDUM OF
UNDERSTADING
MSB MOP SERVICE BASIN
MV MEDICAL VACUUM
N2 NITROGEN
N20 NITROUS OXIDE
NC NORMALLY CLOSED
NG NATURAL GAS
NIC NOT IN CONTRACT
NO NORMALLY OPEN
NOM. NOMINAL
NPW NON POTABLE WATER
NTS NOT TO SCALE
O2 OXYGEN
OC ON CENTER
OD OUTSIDE DIAMETER
OFD OVERFLOW DRAIN
OR OPERATING ROOM
OVFL OVERFLOW
PA PASCAL
PD PRESSURE DROP OR DIFFERENCE
PDI PLUMBING AND DRAINAGE
INSTITUTE
PG PRESSURE GAGE
PP PLUMBING PUMP
PPM PARTS PER MILLION
PRS PRESSURE REDUCING STATION
PRV PRESSURE REDUCING VALVE
PSI POUNDS PER SQUARE INCH
PSIA POUNDS PER SQUARE INCH
ATMOSPHERE
PSIG POUNDS PER SQUARE INCH
GAGE
PTRV PRESSURE TEMPERATURE RELIEF
VALVE
PW POTABLE WATER
RD ROOF DRAIN
RDL ROOF DRAIN LEADER
RL ROOF LEADER
RP RECIRCULATION PUMP
RO REVERSE OSMOSIS WATER
RWL RAIN WATER LEADER
SAN SANITARY SEWER
SMACNA SHEET METAL AND AIR
CONDITIONING CONTRACTORS
NATIONAL ASSOCIATION
SCFM STANDARD CUBIC FOOT/MINUTE
SCW SOFTENED COLD WATER
SDMH STORM DRAIN MANHOLE
SMH SANITARY MANHOLE
SP SUMP PUMP
SPR SPRINKLER LINE
SQFT/SF SQUARE FEET
SS STAINLESS STEEL
ST STORAGE TANK
SW STORM WATER
TCV TEMPERATURE CONTROL
VALVE
TD TEMPERATURE DIFFERENCE
TD TRENCH DRAIN
TDH TOTAL DYNAMIC HEAD
TEMP TEMPERATURE
TMV THERMOSTATIC MIXING VALVE
TP TRAP PRIMER
TSTAT THERMOSTAT
TWR TEMPERED WATER RETURN
TWS TEMPERED WATER SUPPLY
TYP TYPICAL
U/G UNDER GROUND
V VENT
VAC VACUUM
VB VACUUM BREAKER
VCO VACUUM CLEANER OUTLET
VP VACUUM PUMP
VS VENT STACK
VSD VARIABLE SPEED DRIVE
VTR VENT THROUGH ROOF
W WASTE
WC WATER CLOSET
WCO WALL CLEANOUT
WG WATER GAGE
WH WALL HYDRANT
WH WATER HEATER
WHA WATER HAMMER ARRESTER
WL WATER LINE
WM WATER METER
WPD WATER PRESSURE DROP
WS WASTE STACK
WSFU WATER SUPPLY FIXTURE UNITS
YCO YARD CLEANOUT
YH YARD HYDRANT
ABBR. DESCRIPTION ABBR. DESCRIPTION ABBR. DESCRIPTION ABBR. DESCRIPTION ABBR. DESCRIPTION
MEDICAL AIR PIPING (EXISTING)MA (E)
OXYGEN PIPING (EXISTING)O2 (E)
MEDICAL VACUUM PIPING (EXISTING)MV (E)
WASTE ANESTHETIC GAS DISPOSALWAGD
SANITARY PIPING BELOW SLABS
ST STORM (PRIMARY) UNDERSLAB
P R
O F
E S
S
I O NA L E NG
I N
E E
R
L I CENSE
F L O R I DA
STATE
No. 84275
SIVAD.JELYK
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
CONSTRUCTION
DOCUMENTS
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10 www.abovegroupinc.com COA/CA Lic. No. 31120
305 East Dr., Suite H, Melbourne, Florida 32904
PH: 321.345.9026
FULLY SPRINKLERED
B
IM
O rla nd o V
A L ak e
N on a E
D E xp an si on
/0
L ak e N on a
E R
E xp an si on D iv
1, 2, R
.r vt 8/
/2
:0
1:
P M
P-001
PLUMBING LEGENDS, SYMBOLS,
& GENERAL NOTES
EXPAND EMERGENCY
DEPARTMENT AT LAKE NONA
Orlando, Florida
675-901
08/13/2021 KJD JJAKyle J. Davis, P.E.
FL License #84275
Kevin Glover - COR
SHEET LIST
Sheet Number Sheet Name
P-001 PLUMBING LEGENDS, SYMBOLS, & GENERAL NOTES
PS111 PLUMBING GRAVITY OVERALL PLAN
PS121 PLUMBING GRAVITY PLAN - LEVEL 1 ROOF
PP111 PLUMBING PRESSURE OVERALL PLAN
PP121 PLUMBING PRESSURE PLAN - LEVEL 1 INTERSTITIAL
PG111 PLUMBING MED GAS OVERALL PLAN
PG121 PLUMBING MED GAS PLAN - LEVEL 1 INTERSTITIAL
P-401 PLUMBING ENLARGED PLANS
P-501 PLUMBING DETAILS
P-601 PLUMBING GRAVITY ISOMETRICS
P-602 PLUMBING PRESSURE ISOMETRICS
P-603 PLUMBING MED GAS ISOMETRICS
P-801 PLUMBING SCHEDULES
Revisions Date
4.2
3.2 2.2
A.2
1.2
A.6
34.5
34.2
4.8
3.8 2.8 1.4
34.4
35.45.0
3" V UP TO
4" VTR
4" WCO
4" S
8" S (E)
15" ST (E)
3" S
4" FD-C
P-516
P-420
P-201
P-103
P-420
P-103
P-103
Check-In
109 Check-In
Triage
Nurse First/ Reception
Front End Triage
Triage
Vestibule
Waiting
Electric
Women's Toilet
Men's Toilet
Triage
4" ST
6" STO
6" ST
6" ST
6" STO
6" STO DN TO
DOWNSPOUT. REFER
TO DETAIL 6/P-501 6" ST DN
REFER TO CIVIL PLANS FOR
CONTINUATION. COORDINATE
INVERT AND OFFSET PIPE AFTER
BACKWATER VALVE AS NEEDED.
4" ST & STO
UP TO RD
105 GPM
6" ST & STO
UP TO RD
159 GPM
15" ST (E)
4" S (E)
4" S (E)
P-420
P-420
FCO
4" 2-WAY ECO
4" FD-C
P-516
P-516
P-516
2" WCO
2" V UP TO
3" VTR
2" S2" S
4" S
4" S
4" S
4" S
2" S
2" S
4" S
4" S
2" S
2" S
2" S
4" S
4" S
4" S 2" V
2" V
3" V
3" V
2" V
2" V
INV. ELEV.
-3.50'
REFER TO CIVIL PLANS
FOR CONTINUATION
1 1/2" V
1 1/2" V
1 1/2" V
264 GPM
264 GPM
2" V
2" ST
2" ST
2" ST
PROVIDE BACKWATER VALVE
PROVIDE BACKWATER VALVE
REFER TO CIVIL PLANS FOR
CONTINUATION. COORDINATE
INVERT AND OFFSET PIPE AFTER
BACKWATER VALVE AS NEEDED.
2" ST STUBBED UP THROUGH CONCRETE
PAD FOR CONNECTION TO GUTTER
DOWNSPOUT. COORDINATE EXACT
LOCATION WITH ARCHITECTURAL PLANS
2" S
P R
O F
E S
S
I O NA L E NG
I N
E E
R
L I CENSE
F L O R I DA
STATE
No. 84275
SIVAD.JELYK
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
CONSTRUCTION
DOCUMENTS
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10 www.abovegroupinc.com COA/CA Lic. No. 31120
305 East Dr., Suite H, Melbourne, Florida 32904
PH: 321.345.9026
FULLY SPRINKLERED
A1 A2
A3
B2 B1
C1
D1 D2 D3
E1 E2 E3
KEY PLAN
NTS
A4
E4
B
IM
O rla nd o V
A L ak e
N on a E
D E xp an si on
/0
L ak e N on a
E R
E xp an si on D iv
1, 2, R
.r vt 8/
/2
:0
2:
P M
PS111
PLUMBING GRAVITY OVERALL
PLAN
EXPAND EMERGENCY
DEPARTMENT AT LAKE NONA
Orlando, Florida
675-901
08/13/2021 KJD JJAKyle J. Davis, P.E.
FL License #84275
Kevin Glover - COR
DRAWING NOTES:
1. REFER TO P-400 FOR ENLARGED PLANS.
2. SLOPE ALL VENT PIPING BACK TO SANITARY MAIN.
0 2' 4' 8' 12'
1/4" = 1'-0"
N
1/4" = 1'-0"PS111
1 PLUMBING - OVERALL GRAVITY PLAN EXPANSION
CODED NOTES:
2" SAN DN, 1 1/2" V UP. 1 1/2" SAN TO SINK/LAV
4" SAN DN, 2" V UP. 4" SAN TO WC
3" SAN DN, 2" V UP. 3" SAN TO UR
4" SAN DN, 2" V UP
A.2
1.2
34.5
34.2
3.8 2.8 1.4
34.4
35.4
4" RD
2241.5 SQFT
105 GPM
4" VTR
3" VTR
6" RD
3397.0 SQFT
159 GPM
P R
O F
E S
S
I O NA L E NG
I N
E E
R
L I CENSE
F L O R I DA
STATE
No. 84275
SIVAD.JELYK
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
CONSTRUCTION
DOCUMENTS
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10 www.abovegroupinc.com COA/CA Lic. No. 31120
305 East Dr., Suite H, Melbourne, Florida 32904
PH: 321.345.9026
FULLY SPRINKLERED
A1 A2
A3
B2 B1
C1
D1 D2 D3
E1 E2 E3
KEY PLAN
NTS
A4
E4
B
IM
O rla nd o V
A L ak e
N on a E
D E xp an si on
/0
L ak e N on a
E R
E xp an si on D iv
1, 2, R
.r vt 8/
/2
:0
2:
P M
PS121
PLUMBING GRAVITY PLAN -
LEVEL 1 ROOF
EXPAND EMERGENCY
DEPARTMENT AT LAKE NONA
Orlando, Florida
675-901
08/13/2021 KJD JJAKyle J. Davis, P.E.
FL License #84275
Kevin Glover - COR
0 2' 4' 8' 12'
1/4" = 1'-0"
N
1/4" = 1'-0"PS121
1 PLUMBING - EXPANSION ROOF GRAVITY PLAN EXPANSION
6.2 5.2 4.2
C.2
A.2
D.2
B.2
1.2
C
B
C.6
A.6
34.5 34.2
5.8 4.8
3.8 2.8 1.4
3435 34.4
A.01
35.4
D.3
5.0
J.14
P-516
3/4" HWR
3/4" HWR UP
2" CW UP
1 1/4" HW UP
3/4" HW
3/4" HWR
2" CW
1/2" CW
3/4" HW
P-401
P-401
1 1/2" CW
3/4" HWR
3/4" HW
P-516
P-516
3/4" CW
3/4" HWR
3/4" HW
2 5
2" CW 1 1/4" HW
3/4" HWR
1/2" HWR
3/4" HWR
1/2" HWR
P-516
Shower
1A702b
Sterile Supply Room
1A701 Seclusion Room
1A703
Exam/ Treatment
1A705 Exam/ Treatment
1A707 Exam/ Treatment
1A711
Exam/ Treatment
1A715
Exam/ Treatment
1A109d
Exam/ Treatment
1A109b
Exam/ Treatment
1A109a
Patient Tlt
1A704
Patient Tlt
1A105
Exam/ Treatment
1A109c
Patient Tlt
1A714
Patient Tlt
1A115
Elec
1A702d
Staff Tlt
1A608
Life Support Unit
1A112
Meds
1A409
Bathroom
1A607a
Ent Exam/ Treatment
1A118
Physician
1F505
Staff Lockers
1A607
Gyn Exam/ Treatment
1A122
Comm
1A702c
Exam/ Treatment
1A101
Gyn Exam/ Treatment
1A120
Vestibule
1A702
Operations
1B303a
Holding
1B303b
Vestibule
1B303
Elec
1F802
Central Workstation
1F716b
Satallite Workstation
1F716c
Fire Command
1B505
Armory Workrm
1B303c
Decon
1A702a Exam/ Treatment
1A709
Exam/ Treatment
1A933
Men's Toilet
Corridor
1AC01
Corridor
1AC07
Corridor
C02
Triage
Front End Triage
Check-In
110 Electric
Check-In
Nurse First/ Reception
Waiting
Triage
Triage
Women's Toilet
Vestibule
Triage Sub-Waiting
105A
Roof Access exterior
EXT
Isolation
1A717
Isolation
1A721
Ante Rm
1A719
Office
1A801
Triage
1A718
Triage
1B204
Triage
1B202
Physician
1F507
Results Waiting
1A124
Procedure Check In
1B205
Procedure Check In
1B203
Phone
1A501
Waiting
1A121
Mas Workrm
1B201
Comm
1B201b
Ed Tlt Male
1A502
Ed Tlt Female
1A504
Nurse First
1A121a Elec
1B201a
Triage
1A119 Office
1A803 exterior
EXT
1/2" CW
3/4" HWR
3/4" HWR
3/4" HW
1/2" CW
PROVIDE DROP FITTING
ISOLATION VALVE (TYP)
2 5
P R
O F
E S
S
I O NA L E NG
I N
E E
R
L I CENSE
F L O R I DA
STATE
No. 84275
SIVAD.JELYK
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
CONSTRUCTION
DOCUMENTS
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10 www.abovegroupinc.com COA/CA Lic. No. 31120
305 East Dr., Suite H, Melbourne, Florida 32904
PH: 321.345.9026
FULLY SPRINKLERED
A1 A2
A3
B2 B1
C1
D1 D2 D3
E1 E2 E3
KEY PLAN
NTS
A4
E4
B
IM
O rla nd o V
A L ak e
N on a E
D E xp an si on
/0
L ak e N on a
E R
E xp an si on D iv
1, 2, R
.r vt 8/
/2
:0
1:
P M
PP111
PLUMBING PRESSURE OVERALL
PLAN
EXPAND EMERGENCY
DEPARTMENT AT LAKE NONA
Orlando, Florida
675-901
08/13/2021 KJD JJAKyle J. Davis, P.E.
FL License #84275
Kevin Glover - COR
DRAWING NOTES:
1. REFER TO P-400 SERIES FOR ENLARGED PLANS.
CODED NOTES:
HWR BALANCING VALVE SET AT 2.75 GPM.
3/4" HW TO BECOME 3/4" HWR AFTER 1/2" TAP TO LAVATORY, THEN ROUTED UP. 1/2" HW TO TMV-1.
LOCK BALL VALVE IN THE CLOSED POSITION. PIPING CAPPED FOR FUTURE RENOVATION.
1/2" CW FROM TRAP PRIMER. REFER TO P-401 FOR CONTINUATION.
1/2" CW ROUTED DOWN TO SINK. 1/2" CW TO TMV-1 AND TO SINK.
HWR BALANCING VALVE SET AT 3.0 GPM.
0 4' 8' 16' 24'
1/8" = 1'-0"
N
1/8" = 1'-0"PP111
1 PLUMBING - OVERALL PRESSURE PLAN EXPANSION
U
3.2 2.2
C.2
A.2
D.2
B.2
1.2
C
B
C.6
A.6
34.5 34.2
5.8 4.8
3.8 2.8 1.4
3435 34.4
A.01
35.4
D.3
5.0
J.14
6" CW (E)
2" HWR (E)
4" HW (E)
3" HW (E)
1" HWR (E)
4" CW (E)
4" CW (E)
1 1/4" HWR (E)
3" HW (E)
3" CW (E)
2" HW (E)
2" HW (E)
2 1/2" CW (E)
2" HW (E)
2 1/2" CW (E)
1" HW (E)
2" CW (E)
2" CW (E)
1" HW (E)
3/4" HWR DN
2" CW
1 1/4" HW
1 1/4" HW &
2" CW DN
ISOLATION VALVE (TYP)
P R
O F
E S
S
I O NA L E NG
I N
E E
R
L I CENSE
F L O R I DA
STATE
No. 84275
SIVAD.JELYK
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
CONSTRUCTION
DOCUMENTS
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10 www.abovegroupinc.com COA/CA Lic. No. 31120
305 East Dr., Suite H, Melbourne, Florida 32904
PH: 321.345.9026
FULLY SPRINKLERED
A1 A2
A3
B2 B1
C1
D1 D2 D3
E1 E2 E3
KEY PLAN
NTS
A4
E4
B
IM
O rla nd o V
A L ak e
N on a E
D E xp an si on
/0
L ak e N on a
E R
E xp an si on D iv
1, 2, R
.r vt 8/
/2
:0
1:
P M
PP121
PLUMBING PRESSURE PLAN -
LEVEL 1 INTERSTITIAL
EXPAND EMERGENCY
DEPARTMENT AT LAKE NONA
Orlando, Florida
675-901
08/13/2021 KJD JJAKyle J. Davis, P.E.
FL License #84275
Kevin Glover - COR
DRAWING NOTES:
1. FLOOR PLAN IS SHOWN FOR REFERENCE ONLY.
0 4' 8' 16' 24'
1/8" = 1'-0"
N
1/8" = 1'-0"PP121
1 PLUMBING - LEVEL 1 INTERSTITIAL PRESSURE PLAN EXPANSION
CODED NOTES:
CONNECT NEW 3/4" HWR TO (E)1 1/4" HWR IN THE INTERSTITIAL SPACE. COORDINATE SHUTDOWN
WITH OWNER PRIOR TO CONSTRUCTION.
CONNECT NEW 2" CW & 1 1/4" HW TO (E)2 1/2" CW AND 2" HW IN THE INTERSTITIAL SPACE.
COORDINATE SHUTDOWN WITH OWNER PRIOR TO CONSTRUCTION.
1.2
A.6
34.5 34.23.8 2.8 1.4
35 34.4
35.4
ZVB-1
1/2" MA
Check-In
Check-In
Triage
Nurse First/ Reception
Front End Triage
Triage
Vestibule
Waiting
Electric
Women's Toilet
Men's Toilet
Triage
MGO-1
MGO-2
MGO-3
MGO-1
MGO-2
MGO-3
MGO-1
MGO-2
MGO-3
MGO-1
MGO-2
MGO-3
3/4" O2
1/2" O2
1/2" O2
1" MV
3/4" MV
3/4" MV
3/4" MA
1/2" MA
1/2" MA
1/2" O2
3/4" MV
MGO-1
MGO-2
MGO-3
1/2" O2
1/2" MA
3/4" MV
3/4" MV
1/2" MA
1/2" O2
(TYP ALL
ROOMS)
P R
O F
E S
S
I O NA L E NG
I N
E E
R
L I CENSE
F L O R I DA
STATE
No. 84275
SIVAD.JELYK
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
CONSTRUCTION
DOCUMENTS
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10 www.abovegroupinc.com COA/CA Lic. No. 31120
305 East Dr., Suite H, Melbourne, Florida 32904
PH: 321.345.9026
FULLY SPRINKLERED
A1 A2
A3
B2 B1
C1
D1 D2 D3
E1 E2 E3
KEY PLAN
NTS
A4
E4
B
IM
O rla nd o V
A L ak e
N on a E
D E xp an si on
/0
L ak e N on a
E R
E xp an si on D iv
1, 2, R
.r vt 8/
/2
:0
1:
P M
PG111
PLUMBING MED GAS OVERALL
PLAN
EXPAND EMERGENCY
DEPARTMENT AT LAKE NONA
Orlando, Florida
675-901
08/13/2021 KJD JJAKyle J. Davis, P.E.
FL License #84275
Kevin Glover - COR
CODED NOTES:
1/2" O2, 1/2" MA, 3/4" MV DN TO OUTLETS
3/4" O2, 3/4" MA, 1 1/2" MV UP. 3/4" O2, 3/4" MA, 1" MV TO ZVB
PRESSURE SWITCH. WIRE BACK TO LOCAL ALARM
LOCAL MED GAS ZONE ALARM PANEL. WIRE BACK TO MASTER ALARM PANEL
0 2' 4' 8' 12'
1/4" = 1'-0"
N
1/4" = 1'-0"PG111
1 PLUMBING - OVERALL MED GAS PLAN EXPANSION
U
3.2 2.2
C.2
A.2
D.2
B.2
1.2
C
B
C.6
A.6
34.5 34.2
5.8 4.8
3.8 2.8 1.4
3435 34.4
A.01
35.4
D.3
5.0
J.14
4" MV(E)
1 1/4" MA(E)
2" O2(E)
1 1/2" MV
3/4" MA
3/4" O2
1 1/2" MV
3/4" MA
3/4" O2
Shower
1A702b Sterile Supply Room
1A701 Seclusion Room
1A703
Exam/ Treatment
1A705 Exam/ Treatment
1A707 Exam/ Treatment
1A711
Exam/ Treatment
1A715
Exam/ Treatment
1A109d
Exam/ Treatment
1A109b
Exam/ Treatment
1A109a
Patient Tlt
1A704
Patient Tlt
1A105
Exam/ Treatment
1A109c
Patient Tlt
1A714
Patient Tlt
1A115
Elec
1A702d
Staff Tlt
1A608
Life Support Unit
1A112
Meds
1A409
Bathroom
1A607a
Ent Exam/ Treatment
1A118
Physician
1F505
Staff Lockers
1A607
Gyn Exam/ Treatment
1A122
Comm
1A702c
Exam/ Treatment
1A101
Gyn Exam/ Treatment
1A120
Vestibule
1A702
Operations
1B303a
Holding
1B303b
Vestibule
1B303
Elevator
1BE01
Elevator
1BE02
Elec
1F802
Central Workstation
1F716b
Satallite Workstation
1F716c
Fire Command
1B505
Armory Workrm
1B303c
Decon
1A702a Exam/ Treatment
1A709
Exam/ Treatment
1A933
Men's Toilet
Corridor
1AC01
Corridor
1AC07
Corridor
C02
Triage
Front End Triage
Check-In
110 Electric
Check-In
Nurse First/ Reception
Waiting
Triage
Triage
Women's Toilet
Vestibule
Triage Sub-Waiting
105A
Roof Access exterior
EXT
Isolation
1A717
Isolation
1A721
Ante Rm
1A719
Office
1A801
Triage
1A718
Triage
1B204
Triage
1B202
Physician
1F507
Results Waiting
1A124
Procedure Check In
1B205
Procedure Check In
1B203
Phone
1A501
Waiting
1A121
Mas Workrm
1B201
Comm
1B201b
Ed Tlt Male
1A502
Ed Tlt Female
1A504
Nurse First
1A121a Elec
1B201a
Triage
1A119 Office
1A803 exterior
EXT
3/4" O2
1 1/2" MV
3/4" MA
ISOLATION
VALVES (TYP)
P R
O F
E S
S
I O NA L E NG
I N
E E
R
L I CENSE
F L O R I DA
STATE
No. 84275
SIVAD.JELYK
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
CONSTRUCTION
DOCUMENTS
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10 www.abovegroupinc.com COA/CA Lic. No. 31120
305 East Dr., Suite H, Melbourne, Florida 32904
PH: 321.345.9026
FULLY SPRINKLERED
A1 A2
A3
B2 B1
C1
D1 D2 D3
E1 E2 E3
KEY PLAN
NTS
A4
E4
B
IM
O rla nd o V
A L ak e
N on a E
D E xp an si on
/0
L ak e N on a
E R
E xp an si on D iv
1, 2, R
.r vt 8/
/2
:0
1:
P M
PG121
PLUMBING MED GAS PLAN -
LEVEL 1 INTERSTITIAL
EXPAND EMERGENCY
DEPARTMENT AT LAKE NONA
Orlando, Florida
675-901
08/13/2021 KJD JJAKyle J. Davis, P.E.
FL License #84275
Kevin Glover - COR
DRAWING NOTES:
1. FLOOR PLAN IS SHOWN FOR REFERENCE ONLY.
2. COORDINATE MED GAS SHUT-DOWN WITH OWNER PRIOR TO ANY CONSTRUCTION.
CODED NOTES:
3/4" O2, 3/4" MA, 1 1/2" MV DN
LOCKABLE VALVES IN THE OPEN POSITION
(E)1/2" O2, 1/2" MA, 1 1/2" MV DN
CAP PIPING FOR FUTURE CONNECTION AND LOCKABLE BALL VALVES IN THE CLOSED POSITION
0 4' 8' 16' 24'
1/8" = 1'-0"
N
1/8" = 1'-0"PG121
1 PLUMBING - LEVEL 1 INTERSTITIAL MED GAS PLAN EXPANSION
Women's Toilet
P-420
P-420
P-103
P-103
1 1/4" CW
1 1/4" CW
1 1/2" CW
3/4" HWR
3/4" HW
1/2" CW
1/2" CW
FD-C
1/2" CW
A.2
3.8
Men's Toilet
Roof Access
P-103
P-201
P-420
1 1/2" CW
3/4" HWR
3/4" HW
P-420
TP-1 7
FD-C
1/2" CW U/G
1 1/4" CW
P R
O F
E S
S
I O NA L E NG
I N
E E
R
L I CENSE
F L O R I DA
STATE
No. 84275
SIVAD.JELYK
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
CONSTRUCTION
DOCUMENTS
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10 www.abovegroupinc.com COA/CA Lic. No. 31120
305 East Dr., Suite H, Melbourne, Florida 32904
PH: 321.345.9026
FULLY SPRINKLERED
A1 A2
A3
B2 B1
C1
D1 D2 D3
E1 E2 E3
KEY PLAN
NTS
A4
E4
B
IM
O rla nd o V
A L ak e
N on a E
D E xp an si on
/0
L ak e N on a
E R
E xp an si on D iv
1, 2, R
.r vt 8/
/2
:0
1:
P M
P-401
PLUMBING ENLARGED PLANS EXPAND EMERGENCY
DEPARTMENT AT LAKE NONA
Orlando, Florida
675-901
08/13/2021 KJD JJAKyle J. Davis, P.E.
FL License #84275
Kevin Glover - COR
1/2" = 1'-0"1 PLUMBING ENLARGED PRESSURE PLAN EXPANSION -RM 106
1/2" = 1'-0"2 PLUMBING ENLARGED PRESSURE PLAN EXPANSION - RM 100 & 107
0 1' 2' 4' 6'
1/2" = 1'-0"
CODED NOTES:
REFER TO PP111 FOR CONTINUATION.
3/4" HW DOWN TO RUN IN WALL HORIZONTALLY. TAP OFF WITH 1/2" HW TO EACH LAVATORY. 1/2" HW
TO TMV-1.
3/4" HW TO BECOME 3/4" HWR AFTER 1/2" TAP TO LAVATORY, THEN ROUTED UP. 1/2" HW TO TMV-1.
3/4" CW ROUTED DOWN TO URINAL.
1-1/4" CW ROUTED DOWN TO WATER CLOSET.
1/2" CW ROUTED DOWN TO LAVATORY. 1/2" CW TO TMV-1 AND TO LAVATORY.
3/4" CW ROUTED DOWN TO TRAP PRIMER.
1/2" CW FROM TRAP PRIMER, DOWN BELOW GRADE, AND ROUTED TO FLOOR DRAIN.
N
4" x 3" x 4"
WELD TO 5"
EXTRA HEAVY RISER
CLAMP-BOLT TO 4"L
LEG AGAINST WALL
PIPE
"Ø BOLTS
1'-0"
PIPE HANGER (SEE
SPECIFICATIONS 22 05 11)
GALVANIZED SHEETMETAL
PIPE SADDLE W/FLARED ENDS
INSULATED PIPE
PIPE HANGER (SEE
SPECIFICATIONS 22 05 11)
TEST TEE
THREADED
CLEANOUT PLUG
ACCESS COVER AND FRAME
FINISHED WALL SURFACE
2" MINIMUM AIR
GAP (SEE NOTE)
FLOOR DRAIN (FD-B) WITH
INTERNAL BACKWATER VALVE
DRAIN LINE
TO "P" TRAP
FINISHED FLOOR
REMOVABLE GRATE
SUPPORT PIPING
EVERY 4'-0"
INDIRECT WASTE
LINE
NOTE:
THE AIR GAP BETWEEN THE INDIRECT WASTE PIPEAND THE FLOOD LEVEL RIM OF THE WASTE RECEPTOR SHALL BE A
MINIMUM OF TWICE THE EFFECTIVEOPENING OF THE INDIRECT WASTE PIPE.
TWO WAY CLEAR CUT
FITTING
12" DIAMTER x 4" THICK
CONCRETE COLLAR
IN AREAS W/NO SLAB
SCORIATED CLEANOUT COVER
(ZURN - Z-1406)
CLEANOUT PLUG
PAVEMENTGRADE
SECTION
CAST IRON CLEANOUT COLLAR
W/HEAVY DUTY COVER
PAVEMENT
18" SQ x 4" DEEP
CONC. PAD
CLEAN-OUT COVER
IN VEHICULAR
TRAFFIC AREAS
SHALL BE DUCTILE IRON
TWO-WAY
C.O. FTG.
RECESSED ALARM PANEL (AP) WITH
CONTINUOUS DIGITAL DISPLAY OF ALL
MEDICAL GASES AND VACUUM
PROVIDE ZONE
IDENTIFICATION SIGN
120V/1Ø POWER SUPPLY BY ELECTRICAL
CONTRACTOR,COORDINATE EXACT
LOCATION BEFORE CONSTRUCTION
SIGNAL WIRING IN
CONDUIT FROM
PRESSURE SWITCHES
CONDUIT WITH
SIGNAL WIRING FROM
PRESSURE SWITCHES
TO ALARM PANEL
PROVIDE PERMANENT IDENTIFICATION
FOR LOCATION OF SWITCHES LOCATED IN
CEILING SPACE
PROVIDE SUPPORT FOR
PRESSURE/VACUUM SWITCHES SEPARATE
FROM PIPE SUPPORTS
MEDICAL GAS ZONE PIPING DOWN IN
WALL,SEE PLANS FOR EXACT SIZE AND
LOCATION
RECESSED MEDICAL GAS ZONE VALVE BOX (MGV) WITH
SHUT-OFF VALVES, PRESSURE/VACUUM GAUGES AND
REMOVABLE WINDOW WITH PULL RING
CONNECT TO CAPPED PIPE
EXTENSION (TYPICAL)
CONDUIT WITH SIGNAL WIRING FROM
PRESSURE/VACUUM SWITCH TO AREA ALARM PANEL
(AP) BY ELECTRICAL CONTRACTOR, COORDINATE
EXACT LOCATION BEFORE CONSTRUCTION.
PRESSURE/VACUUM
SWITCH (TYPICAL)
PROVIDE UNIVERSAL QUICK-
CONNECT FITTING FOR IN-LINE
PRESSURE/ VACUUM SWITCH
(TYPICAL)
ZURN #Z-199 DOWNSPOUT NOZZLE
STORM DRAIN PIPING, SEE FLOOR
PLANS FOR SIZE AND LOCATIONS
STORAGE ROOM WALL
GARAGE FINISHED FLOOR
18"-36"MAX
SPLASH BLOCK
4' -0
FLOOR DRAIN
P-TRAP
4 TO 30
FLOOR DRAINS
BALL VALVE
3/4" COLD WATER
FINISH FLOOR
1/2" TYPE "K" SOFT SEAMLESS COPPER
WITH NO JOINTS BELOW FLOOR SLAB.
SLOPE AT 1/8" PER FOOT MINIMUM TO
FLOOR DRAIN CONNECTION.
120/1/60 ELECTRICAL
CONNECTION
ELECTRONIC TRAP PRIMING MANIFOLD SUITABLE FOR 4 TO 30
FLOOR DRAINS. COMPLETE WITH CIRCUIT BREAKER, TIMER,
BALL VALVE, SOLENOID VALVE & VACUUM BREAKER
COMPLETLY MOUNTED IN STEEL CABINET ENCLOSURE.
(PRECISION PLUMBING PRODUCTS PT-4 THRU PT-30)
SOLENOID VALVE
24-HOUR TIME CLOCK
WITH TEST AND
OVERRIDE BUTTONS.
VACUUM BREAKER
GALVANIZED STEEL
CABINET
FINISHED FLOOR
FOR FIXTURE HEIGHT
SEE ARCHITECTURAL
DRAWINGS
1" [25mm] STOP
[56mm] 2 1/4"
[69mm] 2 3/4"
[119mm] 4 3/4"
FR
O
M F
LO
O
R
0m m
[8 m m
/8
[4 m m
[2 m m
1/ 2"
[6 3m m
1/
2"
[4 m m
NOTE:
FURNISH 24 VOLT TRANSFORMER
C/L OF FIXTURE
FINISHED WALL
MANUAL OVER-RIDE
BUTTON
SENSOR
ELECTRICAL BOXES
OR CATCH BASIN
TO STORM DRAIN
CAST IRON BACKWATER VALVE
W/PVC FLAPPER AND O-RING
SEAL EQUAL TO ZURN-Z-1090
GRADE
10" DIAMETER CAST IRON COVER
MARKED 'BACKWATER VALVE',
EQUAL TO BROOKS 3-RT SERIES
PRECAST CONCRETE BODY
PROVIDE EXTENSIONS AS
REQUIRED
UNDERGROUND
CONDESATE DRAIN
PIPING, SEE PLAN FOR SIZE
FAUCET
LAVATORY
SUPPLY ANGLE
STOP (TYP)
NOTES:
1. ALL PIPING BETWEEN WATER HEATER AND
FAUCET SHALL BE A MINIMUM OF 1/2".
2. IF MOUNTED UNDER ADA LAVATORY,
PROVIDE INSULATION ON H/C LINES.
TEMPERED WATER
SET 105°F MAX
1/2" CW SUPPLY
1/2" HW SUPPLY
3/4" HW SUPPLY IN WALL
1/2" CW SUPPLY
IN WALL
AFTER CONNECTION TO
SINK, 3/4" HW TURNS TO
3/4" HWR
3/4" HWR SUPPLY IN WALL
TMV-1, REFER
TO SCHEDULE
FAUCET
LAVATORY
SUPPLY ANGLE
STOP (TYP)
NOTES:
1. ALL PIPING BETWEEN WATER HEATER AND
FAUCET SHALL BE A MINIMUM OF 1/2".
2. IF MOUNTED UNDER ADA LAVATORY,
PROVIDE INSULATION ON H/C LINES.
TMV-1, REFER
TO SCHEDULE
TEMPERED WATER
SET 105°F MAX
1/2" CW SUPPLY
1/2" HW SUPPLY
3/4" HW SUPPLY IN WALL
3/4" CW SUPPLY
IN WALL
AFTER LAST
CONNECTION TO LAV, 3/4"
HW TURNS TO 3/4" HWR
3/4" HWR SUPPLY IN WALL
P R
O F
E S
S
I O NA L E NG
I N
E E
R
L I CENSE
F L O R I DA
STATE
No. 84275
SIVAD.JELYK
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
CONSTRUCTION
DOCUMENTS
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10 www.abovegroupinc.com COA/CA Lic. No. 31120
305 East Dr., Suite H, Melbourne, Florida 32904
PH: 321.345.9026
FULLY SPRINKLERED
B
IM
O rla nd o V
A L ak e
N on a E
D E xp an si on
/0
L ak e N on a
E R
E xp an si on D iv
1, 2, R
.r vt 8/
/2
:0
1:
P M
P-501
PLUMBING DETAILS EXPAND EMERGENCY
DEPARTMENT AT LAKE NONA
Orlando, Florida
675-901
08/13/2021 KJD JJAKyle J. Davis, P.E.
FL License #84275
Kevin Glover - COR
N.T.S.
PIPE ANCHOR TO VERTICAL DETAIL1
N.T.S.
INSULATED PIPE HANGER3
N.T.S.
WALL CLEANOUT2
N.T.S.
CONDENSATE DRAIN - INSULATED4
N.T.S.
EXTERIOR CLEAN OUT (TWO WAY) DETAIL5
N.T.S.
MEDICAL GAS ZONE VALVE / ALARM PANEL DETAIL7
N.T.S.
OVERFLOW NOZZLE DETAIL6N.T.S.
ELECTRONIC TRAP PRIMER9
N.T.S.
WATER CLOSET - SENSOR OPERATED DETAIL8
N.T.S.
BACKWATER VALVE10
N.T.S.
TMV UNDER SINK11
12" = 1'-0"12 TMV UNDER MULTIPLE LAVS
8" S (E)
4" S
4" S
4" S
3" S
WCO
WCO
2-WAY ECO
FCO
P-103 P-103
P-103
P-201
P-420 P-420
P-420 P-420
6" RD
159 GPM
4" RD
105 GPM
VTR
VTR
FD-C
FD-C
4" S
4" S
2" S
2" V2" V1 1/2" V
1 1/2" V1 1/2" V
2" V
2" V
2" S 2" S
2" S 2" S
4" S
4" S
4" S
2" S
2" S 2" S
2" S
STO DOWNSPOUT NOZZLE
TO SPLASH BLOCK
6" STO
6" STO
6" STO
4" ST
6" ST
6" ST
1 1/2" V
1 1/2" V
1 1/2" V
1 1/2" V
1 1/2" V
2" S
2" V 2" V
2" V
1 1/2" V 1 1/2" V
2" V
3" V
1 1/2" V
264 GPM
264 GPM
2" V
P-516 P-516
P-516
P-516
8" S (E)
BACKWATER VALVE
BACKWATER VALVE
2" ST 2" ST
2" ST
2" ST STUBBED UP THROUGH CONCRETE
PAD FOR CONNECTION TO GUTTER
DOWNSPOUT. COORDINATE EXACT
LOCATION WITH ARCHITECTURAL PLANS
P R
O F
E S
S
I O NA L E NG
I N
E E
R
L I CENSE
F L O R I DA
STATE
No. 84275
SIVAD.JELYK
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
CONSTRUCTION
DOCUMENTS
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10 www.abovegroupinc.com COA/CA Lic. No. 31120
305 East Dr., Suite H, Melbourne, Florida 32904
PH: 321.345.9026
FULLY SPRINKLERED
B
IM
O rla nd o V
A L ak e
N on a E
D E xp an si on
/0
L ak e N on a
E R
E xp an si on D iv
1, 2, R
.r vt 8/
/2
:0
1:
P M
P-601
PLUMBING GRAVITY
ISOMETRICS
EXPAND EMERGENCY
DEPARTMENT AT LAKE NONA
Orlando, Florida
675-901
08/13/2021 KJD AJZKyle J. Davis, P.E.
FL License #84275
Kevin Glover - COR
N.T.S.
PLUMBING GRAVITY RISER DIAGRAM1
DRAWING NOTES:
1. FOR REFERENCE ONLY. REFER TO FLOOR PLANS FOR MORE INFORMATION.
2. SLOPE ALL VENT PIPING BACK TO SANITARY MAIN.
6" CW (E)
2" HWR (E)
4" HW (E)
3" HW (E)
1" HWR (E)
4" CW (E)
4" CW (E)
1 1/4" HWR (E)
3" HW (E)
3/4" HWR
3/4" HWR
3/4" HWR
3/4" HWR
3" CW (E)
2" HW (E)
2" HW (E)
2 1/2" CW (E)
2 1/2" CW (E)
2" HW (E)
2" CW
1 1/4" HW
3/4" CW
3/4" HW
3/4" HWR
1 1/2" CW
1 1/2" CW
3/4" HW
3/4" HW
TP-1
2" CW
3/4" HW
P-103
P-103
P-103
P-201
BALANCING VALVE
BALANCING VALVE
BALANCING VALVE
BALANCING VALVE
CAP PIPING FOR FUTURE
CONNECTION AND LOCK
BALL VALVES IN THE
CLOSED POSITION
CAP PIPING FOR FUTURE
CONNECTION AND LOCK
BALL VALVES IN THE
CLOSED POSITION
CAP PIPING FOR FUTURE
CONNECTION AND LOCK
BALL VALVES IN THE
CLOSED POSITION
CAP PIPING FOR FUTURE
CONNECTION AND LOCK
BALL VALVES IN THE
CLOSED POSITION
(2) P-420
P-420
P-420
P-516
P-516
P-516
P-516
P R
O F
E S
S
I O NA L E NG
I N
E E
R
L I CENSE
F L O R I DA
STATE
No. 84275
SIVAD.JELYK
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
CONSTRUCTION
DOCUMENTS
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10 www.abovegroupinc.com COA/CA Lic. No. 31120
305 East Dr., Suite H, Melbourne, Florida 32904
PH: 321.345.9026
FULLY SPRINKLERED
B
IM
O rla nd o V
A L ak e
N on a E
D E xp an si on
/0
L ak e N on a
E R
E xp an si on D iv
1, 2, R
.r vt 8/
/2
:0
1:
P M
P-602
PLUMBING PRESSURE
ISOMETRICS
EXPAND EMERGENCY
DEPARTMENT AT LAKE NONA
Orlando, Florida
675-901
08/13/2021 KJD AJZKyle J. Davis, P.E.
FL License #84275
Kevin Glover - COR
DRAWING NOTES:
1. FOR REFERENCE ONLY. REFER TO FLOOR PLANS FOR MORE INFORMATION
N.T.S.
PLUMBING PRESSURE RISER DIAGRAM1
CODED NOTES:
PROVIDE TMV-1 UNDER SINK/LAV. 1/2" CW & HW TO TMV. 1/2" TEMPERED WATER & 1/2" CW TO
FIXTURE.
PRESSURE SWITCHES
CAP PIPING FOR FUTURE
CONNECTION AND LOCK
BALL VALVES IN THE
CLOSED POSITION
LOCK BALL VALVES IN
THE OPEN POSITION
ZVB-1
LOCAL ALARM
MGO-1
MGO-2
MGO-3
MGO-1
MGO-2
MGO-3
MGO-1
MGO-2
MGO-3
MGO-1
MGO-2
MGO-3
MGO-1
MGO-2
MGO-3
1/2" O2
1/2" MA
3/4" MV
1/2" O2
1/2" MA
3/4" MV
1/2" O2
1/2" MA
3/4" MV
3/4" O2
3/4" MA
1" MV
3/4" MV
1/2" MA
1/2" O2
(TYP ALL ROOMS)
1 1/2" MV
3/4" MA
3/4" O2
3/4" O2
3/4" MA
1 1/2" MV
3/4" O2
3/4" MA
1 1/2" MV
1 1/2" MV(E)
3/4" MA(E)
3/4" O2(E)
1 1/2" MV(E)
1/2" MA(E)
1/2" O2(E)
1 1/2" MV(E)
3/4" MA(E)
3/4" O2(E)
4" MV(E)
1 1/4" MA(E)
2" O2(E)
1 1/2" O2(E)
1 1/4" MA(E)
3" MV(E)
P R
O F
E S
S
I O NA L E NG
I N
E E
R
L I CENSE
F L O R I DA
STATE
No. 84275
SIVAD.JELYK
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
CONSTRUCTION
DOCUMENTS
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10 www.abovegroupinc.com COA/CA Lic. No. 31120
305 East Dr., Suite H, Melbourne, Florida 32904
PH: 321.345.9026
FULLY SPRINKLERED
B
IM
O rla nd o V
A L ak e
N on a E
D E xp an si on
/0
L ak e N on a
E R
E xp an si on D iv
1, 2, R
.r vt 8/
/2
:0
1:
P M
P-603
PLUMBING MED GAS
ISOMETRICS
EXPAND EMERGENCY
DEPARTMENT AT LAKE NONA
Orlando, Florida
675-901
08/13/2021 KJD AJZKyle J. Davis, P.E.
FL License #84275
Kevin Glover - COR
DRAWING NOTES:
1. FOR REFERENCE ONLY. REFER TO FLOOR PLANS FOR MORE INFORMATION
N.T.S.
PLUMBING MED GAS RISER DIAGRAM1
P R
O F
E S
S
I O NA L E NG
I N
E E
R
L I CENSE
F L O R I DA
STATE
No. 84275
SIVAD.JELYK
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
CONSTRUCTION
DOCUMENTS
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10 www.abovegroupinc.com COA/CA Lic. No. 31120
305 East Dr., Suite H, Melbourne, Florida 32904
PH: 321.345.9026
FULLY SPRINKLERED
B
IM
O rla nd o V
A L ak e
N on a E
D E xp an si on
/0
L ak e N on a
E R
E xp an si on D iv
1, 2, R
.r vt 8/
/2
:0
1:
P M
P-801
PLUMBING SCHEDULES EXPAND EMERGENCY
DEPARTMENT AT LAKE NONA
Orlando, Florida
675-901
08/13/2021 KJD JJAKyle J. Davis, P.E.
FL License #84275
Kevin Glover - COR
PLUMBING MEDICAL GAS OUTLET
MARK
BASIS OF DESIGN
MANUFACTURER
BASIS OF DESIGN MODEL
NO. DESCRIPTION MOUNTING SERVICE
MGO-1 AMIC0 O-DISWAL-U-OXY MEDICAL GAS OUTLET WALL MEDICAL OXYGEN
MGO-2 AMIC0 O-DISWAL-U-AIR MEDICAL GAS OUTLET WALL MEDICAL AIR
MGO-3 AMIC0 O-DISWAL-U-VAC MEDICAL GAS OUTLET WALL MEDICAL VACUUM
PLUMBING FIXTURE SCHEDULE
MARK FIXTURE WASTE PIPE (INCHES)
VENT PIPE
(INCHES)
COLD WATER
(INCHES)
HOT WATER
(INCHES)
WASTE FIXTURE
UNITS
WATER FIXTURE
UNITS
WRIST BLADE
HANDLES
ELECTRIC
SENSOR
P-103 WATER CLOSET 4 2 1-1/4 - 4 10 - YES
P-201 URINAL 2 1-1/2 3/4 - 2 3 - YES
P-420 LAVATORY 1-1/2 1-1/2 1/2 1/2 1 2 NO YES
P-516 SINK 1-1/2 1-1/2 1/2 1/2 3 2 YES NO
FD-C FLOOR DRAIN REFER TO FLOOR PLAN - - - 2 - - -
PLUMBING MEDICAL GAS VALVE BOX
MARK
BASIS OF DESIGN
MANUFACTURER
BASIS OF DESIGN
MODEL NO. DESCRIPTION MOUNTING SERVICES LOCATION
ZVB-1 AMICO AVU-2O2A3V ZONE VALVE BOX WALL MA, O2, & MV TRIAGE
ELECTRONIC TRAP PRIMER SCHEDULE
MARK BASIS OF DESIGN MANUFACTURER
BASIS OF DESIGN
MODEL NUMBER CW INLET CW OUTLET SIZE
MAX DRAINS
SERVED DIMENSIONS (W" x H" x D") V/PH/HZ
TP-1 PRECISION PLUMBING PRODUCTS PT-4 3/4" 1/2" 4 14" x 16" x 3-3/8" 120/1/60
NOTES:
1. REFER TO SPECIFICATIONS FOR ADDITIONAL INFORMATION.
NOTES:
1. REFER TO SPECIFICATIONS FOR MORE INFORMATION.
2. PROVIDE WITH INTEDRAL DISCONNECT.
THERMOSTATIC MIXING VALVE SCHEDULE
MARK
BASIS OF DESIGN
MANUFACTURER
BASIS OF DESIGN
MODEL NO. OUTLET/TEMPERATURE INLET/OUTLET SIZE MIN. FLOW RATE LOCATION
TMV-1 WATTS LFUSG-B 105°F 1/2" / 1/2" 0.25 GPM SINKS/LAVS
NOTES:
1. THERMOSTATIC MIXING VALVE SHALL BE PIPED PER MANUFACTURER RECOMMENDATIONS.
2. PROVIDE WITH INLET AND OUTLET SHUT-OFF VALVES.
DUCTWORK SYMBOLS
SYMBOL DESCRIPTION
HVAC ABBREVIATIONS
ABBR. DESCRIPTION ABBR. DESCRIPTION
A/E ARCHITECT / ENGINEER
AF AFTER FILTER
AFF ABOVE FINISHED FLOOR
AFMD AIR FLOW MEASURING DEVICE
AHU AIR-HANDLING UNIT
AMP AMPERAGE
APD AIR PRESSURE DROP
ARI AIR CONDITIONING AND REFRIGERATION INSTITUTE
AS AIR SEPARATOR
ASME AMERICAN SOCIETY OF MECHANICAL ENGINEERS
B BOILER
BDD BACKDRAFT DAMPER
BFP BACKFLOW PREVENTER
BHP BRAKE HORSEPOWER
BTU BRITISH THERMAL UNIT
BTUH BRITISH THERMAL UNIT PER HOUR
CC COOLING COIL
CD CONDENSATE
CFM CUBIC FEET PER MINUTE
CHW CHILLER WATER
CHWR CHILLED WATER RETURN
CHWS CHILLED WATER SUPPLY
CO CLEANOUT
COP COEFFICIENT OF PERFORMANCE
CV CONSTANT VOLUME
D DAMPER - AUTOMATIC
DB DECIBELS
DB DRY-BULB TEMPERATURE
DDC DIRECT DIGITAL CONTROLS
DEG DEGREE
DN DOWN
LAT LEAVING AIR TEMPERATURE
LBS/HR POUNDS PER HOUR
LF LINEAR FOOT (FEET)
LPR LOW PRESSURE RETURN (STEAM CONDENSATE)
LPRC LOW PRESSURE STEAM RETURN (CLEAN)
LVG LEAVING
LWT LEAVING WATER TEMPERATURE
MA MIXED AIR
MAT MIXED AIR TEMPERATURE
MBH 1000 BTUH
MCA MINIMUM BRANCH CIRCUIT AMPACITY
MERV MINIMUM EFFICIENCY REPORTING VALUE
MIN MINIMUM
MPR MEDIUM PRESSURE RETURN (STEAM CONDENSATE)
MPS MEDIUM PRESSURE STEAM
MVD MANUAL VOLUME DAMPER
NC NOISE CRITERIA
NC NORMALLY CLOSED
NO NORMALLY OPEN
NPLV NON-STANDARD PART LOAD VALUE
NPSH NET POSITIVE SUCTION HEAD
NTS NOT TO SCALE
OA OUTSIDE AIR
P PUMP
PD PRESSURE DROP
PF PRE-FILTER
PHC PREHEAT COIL
PSI POUNDS PER SQUARE INCH
PSIA POUNDS PER SQUARE INCH – ABSOLUTE
PSIG POUNDS PER SQUARE INCH – GAGE
RA RETURN AIR
RH RELATIVE HUMIDITY
LIMIT OF DEMOLITION
DN
DN
UP
UP
SUPPLY DUCT (UP &
DOWN)
EXHAUST DUCT (UP &
DOWN)
ROUND AND SQUARE 4-WAY
CEILING DIFFUSERS
SUPPLY TOP REGISTER OR GRILLE
(WALL TYPE)
EXHAUST OR RETURN CEILING
REGISTER OR GRILLE
EXHAUST OR RETURN BOTTOM REGISTER
OR GRILLE (WALL TYPE)
EXHAUST OR RETURN REGISTER OR TOP
GRILLE (WALL TYPE)
VANED ELBOW & AIR SPLIT TYPE DUCT
TAKE-OFF
CONNECT NEW DUCT TO EXISTING
DUCT
DNUP
RETURN DUCT (UP &
DOWN)
SQUARE 3-WAY CEILING
DIFFUSERS
SQUARE 2-WAY CEILING
DIFFUSERS
SQUARE 1-WAY CEILING
DIFFUSERS
FC
10x8
FLEXIBLE CONNECTION,
EQUIPMENT, VIBRATION, OR SEISMIC
VANED ELBOW (SHORT RADIUS)
STANDARD RADIUS ELBOW (LONG
RADIUS)
NEW DUCT (INSIDE DIMENSIONS: WIDTH x DEPTH)
EXISTING DUCT TO
REMAIN
FIRE DAMPER
FD
VD
FLEXIBLE DUCTWORK
(INSULATED)
MANUAL VOLUME DAMPER
EXISTING DUCT TO BE
REMOVED
SUPPLY
RETURN45°
STANDARD BRANCH SUPPLY
OR RETURN, NO SPLITTER(45° TAP)
45°
CONTROLS SYMBOLS
SMOKE DAMPER
SD
T ROOM THERMOSTAT/TRANSMITTER - WALL MOUNT
AIR TERMINAL SYMBOLS
TERMINAL UNIT WITH REHEAT
COIL
DRAWING SYMBOLS
BASIC MATERIALS
EXISTING TO BE REMOVED (HEAVY, DASHED LINE)
EXISTING TO REMAIN (THIN, HALFTONED LINE)
NEW (HEAVY, SOLID LINE)
2-AHU-3-1
26-TU-I-I
VIEW NUMBER
DRAWING NUMBER WHERE SHOWN
SECTION LETTER
TYPICAL UNIT NUMBER; AHU NO. 1, LOCATED ON LEVEL 3, LOCATED IN BLDG. 2
BUILDING NO. WHERE EQUIPMENT IS LOCATED.
AHU NUMBER
EQUIPMENT ABBREVIATION. AN "(E)" SHOWN IN FRONT OF EQUIPMENT TAGS NOTIFIES
THAT EQUIPMENT IS EXISTING
ITEM NUMBER (TERMINAL UNIT NO. 1)
ITEM (TERMINAL UNIT SHOWN)
SERVED BY AIR HANDLER UNIT NO. 1
BUILDING NO. WHERE EQUIPMENT IS LOCATED
H4
H7
A
SHEET NUMBER
H ROOM HUMIDITY SENSOR - WALL MOUNT
ABBR. DESCRIPTION
(E) EXISTING
EA EXHAUST AIR
EAT ENTERING AIR TEMPERATURE
ECC ENGINEERING CONTROL CENTER
EF EXHAUST FAN
ENT ENTERING
ESP EXTERNAL STATIC PRESSURE
ET EXPANSION TANK
EWT ENTERING WATER TEMPERATURE
F FAHRENHEIT
FC FLEXIBLE CONNECTION
FCU FAN COIL UNIT
FD FIRE DAMPER
FF FINAL FILTER
FPM FEET PER MINUTE
FPS FEET PER SECOND
FS FLOW SWITCH
FSD COMBINATION FIRE SMOKE DAMPER
GPM GALLONS PER MINUTE
HC HEATING COIL
HD HEAD
HOA HAND/OFF/AUTOMATIC
HP HEAT PUMP
HP HORSEPOWER
HPDT HIGH PRESSURE DRIP TRAP
HPR HIGH PRESSURE RETURN (STEAM CONDENSATE)
HPS HIGH PRESSURE SUPPLY (STEAM)
HWHC HEATING HOT WATER COIL
HHWR HEATING HOT WATER RETURN
HHWS HEATING HOT WATER SUPPLY
HE HEAT EXCHANGER
HZ HERTZ
I/O INPUT/OUTPUT
IN INCHES
IN WC INCH WATER COLUMN
IPLV INTEGRATED PART LOAD VALUE
ABBR. DESCRIPTION
SAT SUPPLY AIR TEMPERATURE
SD SMOKE DETECTOR
SD SMOKE DAMPER
SEN SENSIBLE HEAT
SP STATIC PRESSURE
SPS STATIC PRESSURE SENSOR
SQ FT SQUARE FOOT (FEET)
SS STAINLESS-STEEL
TAB TESTING, ADJUSTING, BALANCE
TSP TOTAL STATIC PRESSURE
TSTAT THERMOSTAT
TU TERMINAL UNIT
TYP TYPICAL
UL UNDERWRITERS LABORATORY
VAV VARIABLE AIR VOLUME
VD VOLUME DAMPER (MANUAL OPPOSED BLADE)
VFD VARIABLE FREQUENCY DRIVE
SYMBOL DESCRIPTION
SYMBOL DESCRIPTION
1. CONNECTION TO EQUIPMENT SHALL BE VERIFIED WITH MANUFACTURER'S CERTIFIED DRAWINGS.
TRANSITIONS TO ALL EQUIPMENT SHALL BE VERIFIED AND PROVIDED FOR EQUIPMENT FURNISHED.
2. DIMENSIONS SHALL BE FIELD-VERIFIED AND COORDINATED PRIOR TO PROCUREMENT OR
FABRICATION. COORDINATE THE WORK WITH OTHER TRADES INVOLVED. FIELD MODIFICATIONS SUCH
AS OFFSETS IN PIPING OR DUCTWORK (INCLUDING DIVIDED DUCTWORK) NEEDED DUE TO
OBSTRUCTIONS OR INTERFERENCES SHALL BE PROVIDED AT NO ADDITIONAL COST.
3. DUCT CONSTRUCTION SHALL BE IN ACCORDANCE WITH THE LATEST EDITION OF THE SMACNA HVAC
DUCT CONSTRUCTION STANDARD.
4. INSTALL ALL FIRE DAMPERS, SMOKE DAMPERS AND COMBINATION FIRE/SMOKE DAMPERS IN
ACCORDANCE WITH MANUFACTURE'S INSTALLATION DIRECTIONS. PROVIDE ACCESS DOORS TO
ALLOW COMPLETE INSPECTION AND MAINTENANCE OF ALL DEVICES.
5. CONTRACTOR SHALL PROVIDE LIST BY ROOM NUMBER LOCATION FOR NEW FIRE DAMPERS, SMOKE
DAMPERS AND COMBINATION FIRE/SMOKE DAMPERS.
6. CONTRACTOR PROVIDE PHOTOS SHOWING NEW FIRE DAMPERS, SMOKE DAMPERS AND
COMBINATION FIRE/SMOKE DAMPERS IN OPEN AND CLOSED POSITION.
7. PROVIDE 1.5R ELBOWS IN DUCTWORK AS INDICATED. IF 1.5R ELBOWS DO NOT FIT, PROVIDE 1.0R ELBOWS. IF 1.0R ELBOWS DO NOT FIT, PROVIDE 90 DEGREE RECTANGULAR DUCT ELBOWS WITH
TURNING VANES.
8. DUCT SIZES AND ALL OPENINGS THROUGH BUILDING CONSTRUCTION SHALL SUIT EQUIPMENT
FURNISHED.
9. LOCATE THERMOSTATS, TEMPERATURE SENSORS, HUMIDISTATS, AND HUMIDITY SENSORS AT 48"
ABOVE FINISHED FLOOR UNLESS NOTED OTHERWISE. COORDINATE LOCATIONS WITH OTHER
EQUIPMENT, FURNITURE, AND DOOR SWINGS.
10. ALL EQUIPMENT, DUCTWORK, ETC., SHALL BE SUPPORTED AS DETAILED AND/OR SPECIFIED. PROVIDE
ADDITIONAL SUPPORTS AS REQUIRED TO PROVIDE A VIBRATION-FREE, RIGID INSTALLATION.
11. ALL DUCT SIZES SHOWN ARE INSIDE CLEAR DIMENSIONS.
12. DAMPERS AND INSIDES OF DUCTS VISIBLE THROUGH GRILLES, REGISTERS AND DIFFUSERS SHALL BE
PAINTED FLAT BLACK.
13. REFER TO TYPICAL DETAILS FOR PIPING AND INSTALLATION OF EQUIPMENT.
14. TRAPPED CONDENSATE DRAINS FROM ALL MECHANICAL EQUIPMENT SHALL BE PROVIDED FOR
PROPER DRAINAGE TO SUIT EQUIPMENT FURNISHED.
15. ACCESS PANELS IN DUCTWORK AND CEILINGS SHALL BE PROVIDED WHERE REQUIRED FOR
OPERATION, BALANCING OR MAINTENANCE OF ALL MECHANICAL EQUIPMENT.
16. ALL DUCTWORK AND PIPING IS SHOWN SCHEMATICALLY. PROVIDE ALL TRANSITIONS, TURNING VANES, ELBOWS, FITTINGS, ETC., TO ALLOW SMOOTH FLOWS. ALL SPLIT DUCT FITTINGS SHALL TRANSITION TO
FULL SIZE OF THE SUM OF BOTH BRANCHES, UPSTREAM OF SPLIT.
17. COORDINATE SIZE REQUIREMENTS OF ALL CONCRETE HOUSEKEEPING PADS UNDER ALL FLOOR-
MOUNTED EQUIPMENT.
18. VERIFY FINISH WITH ARCHITECT PRIOR TO PURCHASING GRILLES, REGISTERS, DIFFUSERS, LOUVERS
AND OTHER AIR DISTRIBUTION DEVICES.
19. PROVIDE FLEXIBLE DUCT CONNECTIONS ON ALL DUCTWORK CONNECTING TO FANS, AIR HANDLING
UNITS, AND FAN COIL UNITS.
20. PROVIDE TRANSITIONS AT DIFFUSER NECKS AS REQUIRED TO MATCH SIZES OF FLEX DUCTS TO BE
CONNECTED.
21. SLEEVE AND SEAL ALL PIPING PENETRATIONS THROUGH BUILDING PARTITIONS.
22. MAINTAIN CLEARANCE OF A MINIMUM OF 6" BETWEEN DUCTWORK, PIPING, EQUIPMENT, ETC., AND ALL FIRE RATED AND FIRE/SMOKE RATED PARTITIONS, TO ALLOW FOR INSPECTIONS OF RATED WALLS.
23. LOCATE ALL OUTSIDE AIR INTAKES A MINIMUM OF 25'-0" CLEAR FROM ALL PLUMBING VENTS. LOWEST
POINT OF EACH OUTSIDE AIR INTAKE ON ROOF SHALL BE A MINIMUM OF 24" ABOVE ROOF.
24. DUCT RUNOUTS TO DIFFUSERS SHALL MATCH THE SIZE OF THE DIFFUSER NECK.
25. THE FIRST FIGURE OF DUCT SIZE INDICATES DIMENSION OF FACE SHOWN OR INDICATED. DUCT SIZES
ARE NET INSIDE DIMENSIONS.
26. REFER TO ARCHITECTURAL REFLECTED CEILING PLANS FOR EXACT LOCATIONS OF CEILING
DIFFUSERS, REGISTERS, AND GRILLES.
27. ALL DDC CONTROL PANELS SHALL BE LOCKABLE.
ZC VALVE OR DAMPER POSITION CONTROLLER
PDS PRESSURE DIFFERENTIAL TRANSMITTER
TT TEMPERATURE TRANSMITTER, AVERAGING ELEMENT
TSL TEMPERATURE SWITCH, LOW (FREEZESTAT)
FS FLOW SWITCH
IT CURRENT TRANSMITTER
MT MOISTURE (HUMIDITY) TRANSMITTER
HS HAND SWITCH (HAND-OFF-AUTO SWITCH)
ECC
VSMC
INTEGRATE CONTROL POINT ON REMOTE GRAPHICS
WORKSTATION AT ENERGY CONTROL CENTER
VARIABLE SPEED MOTOR CONTROLLER
AFMD AIR FLOW MEASURING DEVICE
VALVE SYMBOLS
SYMBOL DESCRIPTION
SD SMOKE DAMPER
MOTOR STARTER
PSH PRESSURE SWITCH HIGH
SPS STATIC PRESSURE SENSOR
SD SMOKE DETECTOR
PC
PRESSURE CONTROLLER. SEE SEQUENCE OF
OPERATION
ECM AIR FLOW MEASURING DEVICE
ZS DAMPER POSITION FEEDBACK TO ECC
TE TEMPERATURE ELEMENT
COMBINATION FIRE/SMOKE DAMPER
STAINLESS STEEL DUCT
FSD
AUTOMATIC CONTROL DAMPER MODULATING
GENERAL EQUIPMENT SYMBOLS
EQUIPMENT WITH CLEARANCE
CLEARANCE
EQUIPMENT
SYMBOL DESCRIPTION
QUICK-COUPLE HOSE CONNECTOR
SIDE CONNECTION
ECCENTRIC REDUCER
BOTTOM CONNECTION, 45° OR 90°
TOP CONNECTION, 45° OR 90°
UNION
RISE OR DROP IN PIPE
CAPPED OUTLET
PRESSURE GAGE
THERMOMETER
FLOW ELEMENT
PIPE UP
PIPE DOWN
REFRIGERANT SIGHT GLASS
TEST PLUG (PRESSURE/TEMPERATURE)
AUTOMATIC AIR VENTAV
MANUAL AIR VENTMV
FE
THERMOSTATIC TRAP SET INCLUDING PIPING ACCESSORIES
SEE DETAIL
VANED ELBOW (PROVIDE ALL SQUARE OR
RECTANGULAR ELBOWS WITH VANES EVEN IF
SYMBOL IS MISSING)
PIPING SYMBOLS
HIGH PRESSURE STEAM CONDENSATE RETURN
HIGH PRESSURE STEAM (60 PSIG AND ABOVE)
HEATING HOT WATER SUPPLY
CONDENSATE PUMP DISCHARGE
LOW PRESSURE STEAM CONDENSATE RETURN
LOW PRESSURE STEAM (15 PSIG AND BELOW)
MEDIUM PRESSURE STEAM CONDENSATE RETURN
MEDIUM PRESSURE STEAM (16 PSIG THRU 59 PSIG)
CHILLED WATER SUPPLY
CHILLED WATER RETURN
HEATING HOT WATER RETURN
HPS
HPR
MPS
MPR
LPS
LPR
PC
HHWS
HHWR
CHWR
CHWS
SYMBOL DESCRIPTION
CONDENSATECD
CONDENSATE CLEANOUTCO
REDUCER OR INCREASER
DIRECTION OF FLOW
LC
M
WATER LEVEL CONTROLLER
FLOW METER
BALL VALVE
CHECK VALVE
ANGLE GLOBE VALVE
BUTTERFLY VALVE
MODULATING CONTROL VALVE
THREE-WAY MODULATING CONTROL VALVE
PRESSURE SAFETY VALVE
WYE STRAINER (WITH BALL VALVE & HOSE CONNECTION)
FLEXIBLE CONNECTION
GLOBE VALVE
HVAC SYMBOL LEGEND
HVAC GENERAL NOTES
CEILING ACCESS HATCH
M
AIRFLOW CONTROL VALVE
ACV GATE VALVE
BUTTERFLY VALVE
PRESSURE REDUCING VALVE
FLEXIBLE CONNECTION
WYE STRAINER (WITH BALL VALVE &
HOSE CONNECTION)
WYE STRAINER (WITH VALVE DRAIN &
QUICK-COUPLE HOSE CONNECTION)
DUCT SMOKE DETECTOR
CALIBRATED BALANCING VALVE
A 200
DEVICE MARK
DEVICE FLOW RATE (CFM)
12X10 SA
DUCT DIMENSION (INCHES)
TYPICAL AIR DISTRIBUTION DEVICE TAG
TYPICAL DUCTWORK TAG
SYSTEM TYPE (SA = SUPPLY AIR , RA = RETURN
AIR, OA = OUTSIDE AIR, EA = EXHAUST AIR,
SS EA = STAINLESS-STEEL EXHAUST)
INVERTED BUCKET TRAP SET INCLUDING PIPING
ACCESSORIES SEE DETAIL LEVEL EQUIPMENT LOCATED ON / LEVEL IT SERVES
P R
O F
E S
S
I O NA L E NG
I N
E E
R
L I CENSE
F L O R I DA
STATE
No. 84275
SIVAD.JELYK
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
CONSTRUCTION
DOCUMENTS
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10 www.abovegroupinc.com COA/CA Lic. No. 31120
305 East Dr., Suite H, Melbourne, Florida 32904
PH: 321.345.9026
FULLY SPRINKLERED
B
IM
O rla nd o V
A L ak e
N on a E
D E xp an si on
/0
L ak e N on a
E R
E xp an si on D iv
1, 2, R
.r vt 8/
/2
3:
:3
P M
M-001
MECHANICAL LEGENDS,
SYMBOLS, & GENERAL NOTES
EXPAND EMERGENCY
DEPARTMENT AT LAKE NONA
Orlando, Florida
675-901
08/13/2021 KJD JJAKyle J. Davis, P.E.
FL License #84275
Kevin Glover - COR
SHEET LIST
Sheet Number Sheet Name
M-001 MECHANICAL LEGENDS, SYMBOLS, & GENERAL NOTES
MD111 MECHANICAL HVAC DEMO PLAN - LEVEL 1
MH111 MECHANICAL HVAC PLAN - LEVEL 1
MH112 MECHANICAL HVAC PLAN - LEVEL 1 ROOF
MP111 MECHANICAL PIPING PLAN - LEVEL 1
MP112 MECHANICAL PIPING PLAN - LEVEL 1 INTERSTITIAL
M-501 MECHANICAL DETAILS
M-502 MECHANICAL DETAILS
M-503 MECHANICAL DETAILS
M-504 MECHANICAL DETAILS
M-701 MECHANICAL CONTROLS
M-801 MECHANICAL SCHEDULES
10x10 SA(E)
1 T
6.2 5.2 4.2 3.2 2.2
C.2
A.2
D.2
B.2
1.2
C
B
C.6
A.6
34.5 34.2
5.8 4.8 3.8 2.8 1.4
35 34.4
A.01
35.4
D.3
5.0
J.14
P R
O F
E S
S
I O NA L E NG
I N
E E
R
L I CENSE
F L O R I DA
STATE
No. 84275
SIVAD.JELYK
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
CONSTRUCTION
DOCUMENTS
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10 www.abovegroupinc.com COA/CA Lic. No. 31120
305 East Dr., Suite H, Melbourne, Florida 32904
PH: 321.345.9026
FULLY SPRINKLERED
A1 A2
A3
B2 B1
C1
D1 D2 D3
E1 E2 E3
KEY PLAN
NTS
A4
E4
B
IM
O rla nd o V
A L ak e
N on a E
D E xp an si on
/0
L ak e N on a
E R
E xp an si on D iv
1, 2, R
.r vt 8/
/2
3:
:4
P M
MD111
MECHANICAL HVAC DEMO PLAN
- LEVEL 1
EXPAN…