This technical specification outlines translucent fiberglass sandwich panel systems required for an expansion of the emergency department at the Lake Nona VA Medical Center in Orlando, Florida. The specification requires insulated, translucent sandwich panels made of fiberglass face sheets bonded to an aluminum I-beam grid core. Panels must be 2-3/4 inches thick with a U-factor of 0.53 and visible light transmittance of 37%. The system must meet various structural and wind load requirements and achieve a Class A roof rating. It also describes aluminum clamptite installation systems and calls for factory finishes on exposed aluminum. The related federal contract opportunity is for the expansion of the emergency department minor construction project at Lake Nona under solicitation number 36C77622B0023_1 issued by the Department of Veterans Affairs Technology Acquisition Center in Austin, Texas.
View the file
Other files
Show all 35
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
675-901 TRANSLUCENT FIBERGLASS SANDWICH PANEL CANOPY SYSTEM
Expand Emergency Department at Lake Nona VAMC Orlando, FL
08 45 23 - 1
SECTION 08 45 23
TRANSLUCENT FIBERGLASS SANDWICH PANEL CANOPY SYSTEM
PART 1 - GENERAL
1.1 SUMMARY
A. Section includes the insulated, translucent sandwich panel system and accessories as shown and specified. Work includes providing and installing:
1. Flat insulated, translucent sandwich panels
2. Aluminum clamptite installation system
3. Aluminum flashing attached to Skyroofs
B. Related Sections:
1. Section 07 92 00, JOINT SEALANTS
1.2 SUBMITTALS
A. Submit manufacturer’s product data. Include construction details, material descriptions, profiles, and finishes of components.
B. Submit shop drawings. Include plans, elevations, and details.
C. Submit manufacturer’s color charts showing the full range of colors available for factory finished exposed aluminum.
1. When requested, submit samples for each exposed finish required, in same thickness and material indicated for the work and in size indicated below.
a. Sandwich panels: 14” x 28” units
b. Factory finished aluminum: 5” long sections
D. Submit Installer Certificate, signed by installer, certifying compliance with project qualification requirements.
E. Submit product reports from a qualified independent testing agency indicating each type and class of panel system complies with the project performance requirements, based on comprehensive testing of current products. Previously completed reports will be acceptable if for current manufacturer and indicative of products used on this project.
1. Reports required (if applicable) are:
a. Flame Spread and Smoke Developed (UL 723) – Submit UL Card
b. Burn Extent (ASTM D 635)
c. Color Difference (ASTM D 2244)
d. Impact Strength (UL 972)
e. Bond Tensile Strength (ASTM C 297 after aging by ASTM D 1037)
f. Bond Shear Strength (ASTM D 1002)
g. Beam Bending Strength (ASTM E 72)
08 45 23 - 2
h. Insulation U-Factor (NFRC 100)
i. NFRC System U-Factor Certification (NFRC 700)
j. NFRC Visible Light Transmittance (NFRC 202)
k. Solar Heat Gain Coefficient (NFRC or Calculations)
l. Fire Penetration of Exterior Wall Assemblies Using a Direct Flame Impingement
Exposure (ASTM E2707)
m. Fall Through Resistance (ASTM E 661)
n. Class A Roof Covering Burning Brand (UL 790)
o. UL Listed Class A Roof System (UL 790) (Optional) – Submit UL Card
1.3 CLOSEOUT SUBMITTALS
A. Provide field maintenance manual to include in project maintenance manuals.
1.4 QUALITY ASSURANCE
A. Manufacturer’s Qualifications:
1. Material and products shall be manufactured by a company continuously and regularly employed in the manufacture of specified materials for a period of at least ten consecutive years and which can show evidence of those materials being satisfactorily used on at least six projects of similar size, scope, and location. At least three of the projects shall have been in successful use for ten years or longer.
2. Panel system must be listed by an ANSI accredited Evaluation Service, which requires quality control inspections and fire, structural, and water infiltration testing of sandwich panel systems by an accredited agency.
3. Quality control inspections shall be conducted at least once each year and shall include manufacturing facilities, sandwich panel components, and production sandwich panels for conformance with AC177 “Translucent Fiberglass Reinforced Plastic (FRP) Faced Panel Wall, Roof and Skylight Systems” as issued by the ICC-ES.
B. Installer’s Qualifications: Installation shall be by an experienced installer, which has been in the business of installing Kalwall panel systems for at least two consecutive years and can show evidence of satisfactory completion of projects of similar size, scope, and type.
1.5 PERFORMANCE REQUIREMENTS
A. The manufacturer shall be responsible for the configuration and fabrication of the complete panel system.
1. When requested, include span analysis data.
2. Standard panel system shall have less than 0.01 cfm/ft² air leakage by ASTM E 283 at
6.24 PSF (50 mph) and no water penetration by ASTM E 331 at 15 PSF; and structural testing by ASTM E 330.
3. Structural Loads. Provide Canopy system capable of handling the following loads:
a. Live Load (PSF): 20 PSF
b. Snow Load (PSF): 24 PSF
c. Drift Load (PSF): 76 PSF
d. Wind Load (PSF): meet requirements of Risk Category IV wind speeds
08 45 23 - 3
B. Deflection Limits:
1. Canopy: Limited to L/60 of clear span for each assembly component.
C. Thermal Movements: Allow for thermal movements from ambient- and surface-temperature changes. Base calculations on surface temperatures of materials due to both solar heat gain and nighttime-sky heat loss.
1. Temperature Change (Range): 110 deg F (43 deg C), ambient; 150 deg F (66 deg C), material surfaces.
1.6 DELIVERY, STORAGE AND HANDLING
A. Deliver panel system, components, and materials in manufacturer’s standard protective packaging.
B. Store panels on the long edge; several inches above the ground, blocked and under cover in accordance with manufacturer’s storage and handling instructions.
1.7 WARRANTY
A. Provide manufacturer's and installer's written warranties agreeing to repair or replace panel system work, which fails in material or workmanship, within one year from the date of delivery.
Failure of material or workmanship shall include deterioration of finish on metal in excess of normal weathering; and defects in accessories; insulated, translucent sandwich panels; and other components of the work.
PART 2 - PRODUCTS
2.1 MANUFACTURER
A. The basis for this specification is for products manufactured by Kalwall Corporation. Other manufacturers may bid this project subject to compliance with the performance requirements of this specification and submission of evidence thereof. Listing other manufacturers’ names in this specification does not constitute approval of their products or relieve them of compliance with all the performance requirements contained herein.
2.2 PANEL COMPONENTS
A. Face Sheets:
1. Translucent faces: Manufactured from glass fiber reinforced thermoset resins, formulated specifically for architectural use.
a. Thermoplastic (e.g. polycarbonate, acrylic) faces are not acceptable.
b. Face sheets shall not deform, deflect, or drip when subjected to fire or flame.
2. Interior face sheets:
a. Flame spread: Underwriters Laboratories (UL) listed, which requires periodic unannounced retesting, with flame spread rating no greater than 25 or less for
08 45 23 - 4 canopies and smoke developed no greater than 450 when tested in accordance with UL 723.
b. Burn extent by ASTM D 635 shall be no greater than 1”.
3. Exterior face sheets:
a. Color stability: Full thickness of the exterior face sheet shall not change color more than 3 CIE Units DELTA E by ASTM D 2244 after 3 years outdoor South Florida weathering at 5° facing south as measured on a white sample, with and without a protective film or coating to ensure long-term color stability. Color stability shall be unaffected by abrasion or scratching.
b. Strength: Exterior face sheet shall be uniform in strength, impenetrable by hand held pencil and repel an impact minimum of 70 ft. lbs. without fracture or tear when impacted by a 3-1/4” diameter, 5 lb. free-falling ball per UL 972.
c. Erosion Protection: Integral, embedded-glass erosion barrier.
4. Appearance:
a. Exterior face sheet: Smooth, 0.070” thick and Crystal in color.
b. Interior face sheet: Smooth, 0.070” thick and White in color.
c. Face sheets shall not vary more than ± 10% in thickness and be uniform in color.
B. Grid Core:
1. Aluminum I-beam grid core shall be of 6063-T6 or 6005-T5 alloy and temper with provisions for mechanical interlocking of muntin-mullion and perimeter. Width of I-beam shall be no less than 7/16”.
C. Laminate Adhesive:
1. Heat and pressure resin type adhesive engineered for structural sandwich panel use, with minimum 25-years field use. Adhesive shall pass testing requirements specified by the International Code Council “Acceptance Criteria for Sandwich Panel Adhesives".
2. Minimum tensile strength of 750 PSI when the panel assembly is tested by ASTM C 297 after two exposures to six cycles each of the aging conditions prescribed by ASTM D 1037.
3. Minimum shear strength of the panel adhesive by ASTM D 1002 after exposure to four separate conditions:
a. 50% Relative Humidity at 68° F: 540 PSI
b. 182° F: 100 PSI
c. Accelerated Aging by ASTM D 1037 at room temperature: 800 PSI
d. Accelerated Aging by ASTM D 1037 at 182° F: 250 PSI
2.3 PANEL CONSTRUCTION
A. Provide sandwich panels of flat fiberglass reinforced translucent face sheets laminated to a grid core of mechanically interlocking I-beams. The adhesive bonding line shall be straight, cover the entire width of the I-beam and have a neat, sharp edge.
1. Thickness: 2-3/4 inches
2. Grid Core Insulation: Fill panel cores with air
3. Panel U-factor by NFRC certified laboratory: 2-3/4” aluminum grid: 0.53
4. Visible Light Transmittance (VLT): 37%
5. Solar heat gain coefficient 0.52
6. Grid pattern as viewed: Nominal size 12” x 24”; pattern Shogi
08 45 23 - 5
B. Standard panels shall deflect no more than 1.9” at 30 PSF in 10’-0” span without a supporting frame by ASTM E 72.
C. Panels shall meet the conditions of acceptance according to ASTM E2707 Fire Penetration of Exterior Wall Assemblies Using a Direct Flame Impingement Exposure:
1. Absence of flame penetration through the wall assembly at any time.
2. Absence of evidence of glowing combustion on the interior surface of the assembly at the end of the 60-min observation period.
3. Absence of evidence of flame, glow, and smoke if the test is terminated prior to the completion of the 60-min observation period.
D. Canopy System:
1. Canopy system shall pass Class A Roof Burning Brand Test by UL 790.
2. Canopy system shall be UL listed as a Class A Roof by UL 790, which requires periodic unannounced factory inspections and retesting by Underwriters Laboratories.
E. Canopy System shall meet the fall through requirements of OSHA 1910.21 as demonstrated by testing in accordance with ASTM E 661, thereby not requiring supplemental screens or railings.
2.4 ALUMINUM CLAMPTITE INSTALLATION SYSTEM
A. Aluminum clamptite installation system Canopy:
1. Extruded aluminum 6063-T6 and 6063-T5 alloy and temper clamp-tite screw type closure system.
2. Curved alumiumum clamptite installation system may be roll formed.
3. Canopy perimeter aluminum clampite installation system at curbs shall be factory sealed to panels.
B. Sealing tape: Manufacturer's standard, pre-applied to aluminum clamptite installation system at the factory under controlled conditions.
C. Fasteners: 300 series stainless steel screws for aluminum clamptite installation system, excluding final fasteners to the building.
D. Finish:
1. Manufacturer's factory applied finish, which meets the performance requirements of AAMA 2604. Color to be selected by architect from manufacturer's standards.
PART 3 - EXECUTION
3.1 EXAMINATION
A. Installer shall examine substrates, supporting structure, and installation conditions.
B. Do not proceed with panel installation until unsatisfactory conditions have been corrected.
08 45 23 - 6
3.2 PREPARATION
A. Metal Protection:
1. Where aluminum will contact dissimilar metals, protect against galvanic action by painting contact surfaces with primer or by applying sealant or tape recommended by sealant manufacturer for this purpose.
2. Where aluminum will contact concrete, masonry, or pressure treated wood, protect against corrosion by painting contact surfaces with bituminous paint or method recommended by sealant manufacturer.
3.3 INSTALLATION
A. Install the panel system in accordance with the manufacturer's fabrication drawings and suggested installation instructions.
1. Anchor component parts securely in place by permanent mechanical attachment system.
2. Accommodate thermal and mechanical movements.
3. Seal aluminum clamptite installation system as shown on the manufacturer’s fabrication drawings and suggested installation instructions.
B. Install joint sealants at perimeter joints and within the panel system in accordance with manufacturers fabrication drawings and suggested installation instructions.
3.5 CLEANING
A. Clean the panel system, interior and exterior, immediately after installation.
B. Refer to manufacturer's written recommendations.
- - - END OF SECTION - - -