These are Final Construction Documents for an Upgrade Fire Alarm System (FM) project at VA Black Hills Healthcare System, Fort Meade, South Dakota, located at 113 Comanche Road. The project number is 568-24-106 with an issue date of March 14, 2025, and Addendum 1 dated April 9, 2026. The design was prepared by Alesia Architecture P.C. (Elkhorn, Nebraska) as the prime architect, with specialized engineering support from Incandescence Life Safety, Inc. (Denver, Colorado), Specialized Engineering Solutions (Omaha, Nebraska), and OCMI, Inc. (North Bethesda, Maryland).
The scope encompasses a comprehensive new fire alarm system serving 26 buildings across the Fort Meade campus, including installation of new Fire Alarm Control Panels (FACPs), addressable smoke and heat detectors, manual pull stations, notification appliances (speakers, strobes, horns), and a networked fire alarm infrastructure with fiber optic interconnection between buildings. The project is phased: Phase 1 installs fire alarm network equipment in Buildings T296, 137, and 148; Phase 2 installs fire alarm systems at protected premises; Phase 2A maintains fire protection in occupied buildings (65, T144, T296) during installation; and Phase 3 demolishes the existing system after the new system is tested and approved. Buildings are classified as fully sprinklered or not fully sprinklered per NFPA standards. The design incorporates emergency voice communication systems in select buildings (53, 88, 89, 90, 46) and maintains general evacuation tone notification in others. All work must comply with NFPA 72 (National Fire Alarm and Signaling Code 2025), NFPA 101 (Life Safety Code 2024), VA Fire Protection Design Manual, and local Authority Having Jurisdiction requirements. The documents include detailed floor plans, fire alarm demolition plans, network diagrams, riser diagrams, and installation details for all 26 buildings, along with specifications for device placement, circuit routing, conduit installation, and coordination with sprinkler system supervision and elevator controls.
View the file
Other files
Show all 25
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
MH
D R Y W E
LL
PROPCOR
WV
WV
R A M P
D N th
S T R E E T
(A S P H A L T)
PARKING LOT
(ASPHALT)
COMANCHE ROAD
(ASPHALT)
CO
WV
PIV
WVWV
C U S
TE
R
A V E
C U S
TE
R
A V E
(A S P H A
LT
CONC.
ASPH.
CONC.
(C O N C
WV
CO
WV
WV
P A R K
IN
G
L O T
(C O N C
C O M P
AC
T O R
R A M P
D N
D N
R A M P
HYD
RAN
T
CO
CONC.
P A R K
IN
G
L O T
(A S P H A L T
P A R K
IN
G
L O T
(C O N C
CO
WV
WV
C O N C
CONC.
PARKING LOT
(ASPHALT)
WV
CO
RENO
ROAD
T H
COMANCHE
ROAD
TERRY
ROAD
D R Y W E
LLMH
CUSTER
STURG
IS
RD.
S E C O N D
S T
R D
TERRY
DR.
CUSTER
M
AC
KE
NZ
IE
T H
SD HW
Y
34/79
COMANCHE
RD.
SHERIDAN
RENO
ROAD
T H
BIK
E
PA
TH
SD H
WY
34/7
SD
H
WY
/7
SHERIDAN
COMANCHE
RD.
CO
MA
NC
HE
RD
TH
TERRY
DR.
T U N N E L
AC
AC
AC
AC
AC
AC
AC AC
ACACAC
x x x x x x x x x x x x x x x x x x x x x x x x x
46 T296
T171
T144
154155
40 CARPENTER / PAINT SHOP
46 LOGISTICS WAREHOUSE
47 FALLOUT SHELTER
48 FACILITY MANAGEMENT WAREHOUSE
50 POST OFFICE
53 BUSINESS OFFICE
65 STUDENT QUARTERS
72 OFFICE
85 DAYCARE CENTER
87 GARAGE
88 CWT WORKSHOP
89 ENGINEERING BUILDING
90 EDUCATION
91 MOTOR POOL
96 VACANT GREENHOUSE
103 COVID STORAGE
120 DAYCARE GARAGE
137 BOILER PLANT
T144 HOPTEL
147 LAUNDRY
148 PATIENT CARE
154 SWITCHGEAR
155 GENERATOR
160 WATER TREATMENT
T171 ENGINEERING / HEAVY EQUIPMENT
T296 FIRE STATION
BUILDING LEGEND
INDUSTRIAL
STORAGE
STORAGE
STORAGE
BUSINESS
BUSINESS
DORMITORY
BUSINESS
DAYCARE
INDUSTRIAL
BUSINESS
BUSINESS, INDUSTRIAL
ASSEMBLY, STORAGE
INDUSTRIAL
STORAGE
STORAGE
STORAGE
INDUSTRIAL
DORMITORY
INDUSTRIAL
HEALTHCARE
INDUSTRIAL
INDUSTRIAL
INDUSTRIAL
INDUSTRIAL
STORAGE, DORMITORY
BUILDING NO. FUNCTIONAL TITLE OCCUPANCY CLASSIFICATION
RICHARD
JOSEPH
ONKEN
A-5125
A
R C H I T E
C
T
S T
A T
E
O F N E B
R A
S K
A
3/14/2025
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED:
BUILDINGS 40, 46, 48, 53, 65, 88, 89, 90, 91, 103, 147,
148, T144, T171, T296
NOT FULLY SPRINKLERED:
BUILDINGS 47, 50, 85, 87, 96, 120, 137, 160
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMP
321 5 6 7 8 9 10
Alesia Architecture P.C.
3705 North 200th Street Elkhorn, Nebraska 68022 Phone: (402) 291-6941
A on e ei gh th in ch o ne f oo t th re e in ch es o ne f oo t
6" on e an d on e ha lf in ch es o ne f oo t on e in ch o ne f oo t
6" 6" th re e qu ar te rs in ch o ne f oo t on e ha lf in ch o ne f oo t th re e ei gh th s in ch o ne f oo t on e qu ar te r in ch o ne f oo t
FINAL CONSTRUCTION
DOCUMENTS
UPGRADE FIRE ALARM
SYSTEM (FM)
568-24-106
FT MEADE, SD
A
B
C
D
E
F
14MAR2025
Incandescence Life Safety, Inc.
3455 Ringsby Ct, Suite 103 Denver, CO 80216 Phone: (720) 722-3010
Specialized Engineering Solutions 10360 Ellison Circle Omaha, NE 68134 Phone: (402) 991-5520
OCMI, Inc.
909 Rose Avenue, Suite 400 North Bethesda, MD 20852
A u to d e s k D o c s /1
-2 -1
A
E U p d a te F ir e
A la rm S y s te m F t M e a d e
/5
-2
-1
.B
.A rc h R
-U p d a te F ir e
A la rm S y s te m F t M e a d e .r v t
/9
/2
:5
:4
P
M
GI001
COVER SHEET
GLG SW
VA BLACK HILLS
HEALTHCARE SYSTEM
U P
G R
A D
E F
IR
E
A
LA
R M
S Y
S T
E M
F
M
F
IN
A
L C
O N
S T
R U
C T
IO
N
D O
C U
M E
N T
S
4M
A R
UPGRADE FIRE ALARM SYSTEM (FM)
113 Comanche Rd, FORT MEADE, SD 57741
SITE MAP
PLAN
NORTH
TRUE
NORTH
Mark Revisions: Date:
1 ADDENDUM 1 09APR26
RICHARD
JOSEPH
ONKEN
A-5125
A
R C H I T E
C
T
S T
A T
E
O F N E B
R A
S K
A
3/14/2025
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED:
BUILDINGS 40, 46, 48, 53, 65, 88, 89, 90, 91, 103, 147,
148, T144, T171, T296
NOT FULLY SPRINKLERED:
BUILDINGS 47, 50, 85, 87, 96, 120, 137, 160
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMP
321 5 6 7 8 9 10
Alesia Architecture P.C.
3705 North 200th Street Elkhorn, Nebraska 68022 Phone: (402) 291-6941
A on e ei gh th in ch o ne f oo t th re e in ch es o ne f oo t
6" on e an d on e ha lf in ch es o ne f oo t on e in ch o ne f oo t
6" 6" th re e qu ar te rs in ch o ne f oo t on e ha lf in ch o ne f oo t th re e ei gh th s in ch o ne f oo t on e qu ar te r in ch o ne f oo t
FINAL CONSTRUCTION
DOCUMENTS
UPGRADE FIRE ALARM
SYSTEM (FM)
568-24-106
FT MEADE, SD
A
B
C
D
E
F
14MAR2025
Incandescence Life Safety, Inc.
3455 Ringsby Ct, Suite 103 Denver, CO 80216 Phone: (720) 722-3010
Specialized Engineering Solutions 10360 Ellison Circle Omaha, NE 68134 Phone: (402) 991-5520
OCMI, Inc.
909 Rose Avenue, Suite 400 North Bethesda, MD 20852
A u to d e s k D o c s /1
-2 -1
A
E U p d a te F ir e
A la rm S y s te m F t M e a d e
/5
-2
-1
.B
.A rc h R
-U p d a te F ir e
A la rm S y s te m F t M e a d e .r v t
/9
/2
:5
:4
P
M
GI002
INDEX OF DRAWINGS
GLG SW
Index of Drawings
GENERAL INFORMATION
GI001 COVER SHEET
GI002 INDEX OF DRAWINGS
LIFE SAFETY
GI101 LIFE SAFETY PLAN
PHASING
GC101 PHASING PLAN
ARCHITECTURAL
AG001 ARCHITECTURAL ABBREVIATIONS, LEGENDS AND NOTES
40-AE101 BLDG. 40 - FIRST FLOOR PLAN AND REFLECTED CEILING PLAN
46-AE100 BLDG. 46 - BASEMENT FLOOR PLAN AND REFLECTED CEILING PLAN
46-AE101 BLDG. 46 - FIRST FLOOR PLAN AND REFLECTED CEILING PLAN
46-AE102 BLDG. 46 - ATTIC FLOOR - FLOOR PLAN AND REFLECTED CEILING PLAN
47-AE101 BLDG. 47 - FIRST FLOOR PLAN AND REFLECTED CEILING PLAN
48-AE100 BLDG. 48 - BASEMENT FLOOR PLAN AND REFLECTED CEILING PLAN
48-AE101 BLDG. 48 - FIRST FLOOR PLAN AND REFLECTED CEILING PLAN
50-AE101 BLDG. 50 - BASEMENT & FIRST FLOOR PLAN AND REFLECTED CEILING PLAN
53-AE100 BLDG. 53 - BASEMENT FLOOR PLAN AND REFLECTED CEILING PLAN
53-AE101 BLDG. 53 - FIRST FLOOR PLAN AND REFLECTED CEILING PLAN
53-AE102 BLDG. 53 - SECOND FLOOR PLAN AND REFLECTED CEILING PLAN
53-AE103 BLDG. 53 - ATTIC FLOOR PLAN AND REFLECTED CEILING PLAN
65-AE100 BLDG. 65 - BASEMENT FLOOR PLAN AND REFLECTED CEILING PLAN
65-AE101 BLDG. 65 - FIRST FLOOR PLAN AND REFLECTED CEILING PLAN
65-AE102 BLDG. 65 - SECOND FLOOR PLAN AND REFLECTED CEILING PLAN
85-AE101 BLDGS. 72, 85 & 120 - FIRST FLOOR PLAN AND REFLECTED CEILING PLAN
88-AE101 BLDGS. 87 & 88 - FIRST FLOOR PLAN AND REFLECTED CEILING PLAN
88-AE102 BLDG. 88 - SECOND FLOOR PLAN AND REFLECTED CEILING PLAN
89-AE101 BLDG. 89 - FIRST FLOOR PLAN AND REFLECTED CEILING PLAN
89-AE102 BLDG. 89 - SECOND FLOOR PLAN AND REFLECTED CEILING PLAN
90-AE101 BLDG. 90 - FIRST FLOOR PLAN AND REFLECTED CEILING PLAN
90-AE102 BLDG. 90 - SECOND FLOOR PLAN AND REFLECTED CEILING PLAN
91-AE101 BLDG. 91 - FIRST FLOOR PLAN AND REFLECTED CEILING PLAN
96-AE101 BLDGS. 96 AND 103 - FIRST FLOOR PLAN AND REFLECTED CEILING PLAN
137-AE101 BLDG. 137 - FIRST FLOOR PLAN AND REFLECTED CEILING PLAN
147-AE100 BLDG. 147 - BASEMENT FLOOR PLAN AND REFLECTED CEILING PLAN
147-AE101 BLDG. 147 - FIRST FLOOR PLAN AND REFLECTED CEILING PLAN
148-AE101 BLDG. 148 - FIRST FLOOR PLAN AND REFLECTED CEILING PLAN
154-AE101 BLDGS. 154, 155 & T171 - FLOOR PLAN AND REFLECTED CEILING PLAN
T144-AE101 BLDGS. T144 & 160 - FIRST FLOOR PLAN AND REFLECTED CEILING PLAN
T296-AE101 BLDG. T296 - FIRST FLOOR PLAN AND REFLECTED CEILING PLAN
ELECTRICAL
E000 ELECTRICAL SYMBOLS AND ABBREVIATIONS
40-E101 BLDG. 40 - CARPENTER-PAINT SHOP FIRST FLOOR - POWER PLAN
46-E100 BLDG. 46 - BASEMENT & FIRST FLOOR - POWER PLAN
47-E101 BLDG. 47 - FIRST FLOOR - POWER PLAN
48-E100 BLDG. 48 - BASEMENT & FIRST FLOOR - POWER PLAN
50-E101 BLDG. 50 - BASEMENT & FIRST FLOOR - POWER PLAN
53-E100 BLDG. 53 - BASEMENT & FIRST FLOOR - POWER PLAN
65-E100 BLDG. 65 - BASEMENT & FIRST FLOOR - POWER PLAN
85-E101 BLDGS. 72, 85 AND 120 - FIRST FLOOR - POWER PLAN
88-E101 BLDG. 87 & 88 - FIRST FLOOR - POWER PLAN
89-E101 BLDG. 89 - FIRST FLOOR - POWER PLAN
90-E101 BLDG. 90 - FIRST FLOOR - POWER PLAN
91-E101 BLDG. 91 - FIRST FLOOR - POWER PLAN
96-E101 BLDGS. 96 AND 103 - FIRST FLOOR - POWER PLAN
137-E101 BLDG. 137 - FIRST FLOOR AND SECOND FLOOR - POWER PLAN
147-E101 BLDG. 147 - FIRST FLOOR - POWER PLAN
154-E101 BLDG. T171 - FIRST FLOOR - POWER PLAN
T144-E101 BLDGS. T144 AND 160 - FIRST FLOOR - POWER PLAN
T296-E101 BLDG. T296 - FIRST FLOOR - POWER PLAN
FIRE ALARM
FA001 FIRE ALARM GENERAL NOTES
FA002 FIRE ALARM NETWORK DIAGRAM
FA003 FIRE ALARM CAMPUS INTERCONNECTION PLAN
40-FA101 BUILDING 40 - FIRE ALARM DEMOLITION PLAN
46-FA101 BUILDING 46 - FIRE ALARM DEMOLITION PLAN
48-FA101 BUILDING 48 - FIRE ALARM DEMOLITION PLAN
50-FA101 BUILDING 50 - FIRE ALARM DEMOLITION PLAN
53-FA101 BUILDING 53 - FIRE ALARM DEMOLITION PLAN
53-FA102 BUILDING 53 - FIRE ALARM DEMOLITION PLAN
65-FA102 BUILDING 65 - FIRE ALARM DEMOLITION PLAN
85-FA101 BUILDING 85 & 120 - FIRE ALARM DEMOLITION PLAN
88-FA101 BUILDING 88 - FIRE ALARM DEMOLITION PLAN
89-FA101 BUILDING 89 - FIRE ALARM DEMOLITION PLAN
90-FA101 BUILDING 90 - FIRE ALARM DEMOLITION PLAN
91-FA101 BUILDING 91 - FIRE ALARM DEMOLITION PLAN
137-FA101 BUILDING 137 - FIRE ALARM DEMOLITION PLAN
147-FA101 BUILDING 147 - FIRE ALARM DEMOLITION PLAN
T144-FA101 BUILDING T144 - FIRE ALARM DEMOLITION PLAN
T171-FA101 BUILDING T171 & 87 - FIRE ALARM DEMOLITION PLAN
T296-FA101 BUILDING T296 - FIRE ALARM DEMOLITION PLAN
40-FA201 BUILDING 40 - FIRE ALARM PLAN
46-FA201 BUILDING 46 - FIRE ALARM PLAN
46-FA202 BUILDING 46 - FIRE ALARM PLAN
48-FA201 BUILDING 48 & 47 - FIRE ALARM PLAN
50-FA201 BUILDING 50 - FIRE ALARM PLAN
53-FA201 BUILDING 53 - FIRE ALARM PLAN
53-FA202 BUILDING 53 - FIRE ALARM PLAN
65-FA201 BUILDING 65 - FIRE ALARM PLAN
85-FA201 BUILDING 72, 85, & 120 - FIRE ALARM PLAN
88-FA201 BUILDING 88 - FIRE ALARM PLAN
89-FA201 BUILDING 89 - FIRE ALARM PLAN
90-FA201 BUILDING 90 - FIRE ALARM PLAN
91-FA201 BUILDING 91 - FIRE ALARM PLAN
96-FA201 BUILDING 96 - FIRE ALARM PLAN
103-FA201 BUILDING 103 - FIRE ALARM PLAN
137-FA201 BUILDING 137 - FIRE ALARM PLAN
147-FA201 BUILDING 147 - FIRE ALARM PLAN
148-FA201 BUILDING 148 - FIRE ALARM PLAN
154 - FA201 BUILDING 154 & 155 FIRE ALARM PLAN
160-FA201 BUILDING 160 - FIRE ALARM PLAN
T144-FA201 BUILDING T144 - FIRE ALARM PLAN
T171-FA201 BUILDING T171 & 87 - FIRE ALARM PLAN
T296-FA201 BUILDING T296 - FIRE ALARM PLAN
FA501 FIRE ALARM DETAILS
Mark Revisions: Date:
1 ADDENDUM 1 09APR26
S
S S
S S
S S
S
SSSSSSS
S S
FACP FF
c dAIM
AIM
AIM
WKST
SMOKE PARTITION
SYMBOL
LIFE SAFETY WALL LEGEND
DESCRIPTION
1-HOUR FIRE BARRIER
2-HOUR FIRE BARRIER
1-HOUR FIRE / SMOKE
BARRIER
2-HOUR FIRE / SMOKE
BARRIER
30-MINUTE FIRE / SMOKE
BARRIER
S
S
S
S
S
S
S
S
S
S
S
S
S
S
S
SUITESTE STE STE STE STE
HAZARDOUS AREAHZ HZ HZ HZ HZ
HEALTHCARE CORRIDOR
CORRIDOR
AC101
POLICE
A111
A111A
ARMORY
A110
OFFICE /
CAMERA
ROOM
A112
OFFICE
A111B
A111C
OFFICE
A111D
A109
EXIST. FACP
CORRIDOR
CC1-148
Room A113
RESTROOM
A112A
RESTROOM
A112A2
HOUSEKEEPINGFIBER ENTRY AREA
IT ROOM
ATC102
ICRA
LEVEL II
EXIST. FACP
FIBER ENTRY AREA
ICRA
LEVEL II
40 1 CARPENTER'S SHOP
46 BASEMENT OFFICE SUPPLY STORAGE
46 1 LOGISTICS OFFICE SPACE AND NON-STERILE LOADING DOCK
46 2 NON-STERILE STORAGE
47 1 SPILL KIT SUPPLIES
48 ALL FACILITIES STORAGE/POLICE TRAINING
50 BASEMENT MECHANICAL/SAFETY STORAGE
50 1 SAFETY OFFICE
50 1 POST OFFICE
53 BASEMENT STORAGE/MECHANICAL/CONFERENCE ROOM
53 1 & 2 LOBBY
53 1 CITC
53 2 HRM/FINANCE
53 ATTIC MECHANICAL
65 BASEMENT STORAGE
65 1 & 2 RESIDENT QUARTERS
85 1 DAYCARE
87 1 GARAGE
88 1 CWT OFFICE AREA
88 1 CWT OPEN AREA
88 1 BILL/MICK
88 2 STORAGE
89 1 SHOP
89 1 OFFICE
89 2 STORAGE/MECHANICAL
90 1 EDUCATION
90 2 STORAGE/MECHANICAL
91 1 GARAGE
96 1 STORAGE
103 1 LOGISTICS STORAGE
120 1 DAYCARE
137 1 & 2 BOILER PLANT
T144 1 HOPTEL
147 1 & 2 LAUNDRY
148 1 PATIENT CARE
154 1 SWITCH GEAR
155 1 GENERATOR
160 1 WATER TREATMENT PLANT
T171 1 GARAGE
T171 1 OFFICE AREA
T296 1 FIRE STATION
BUILDING ICRA LEGEND
BUILDING NO. FLOOR USE TYPE OF WORK TYPE OF PEOPLE/AREA ICRA LEVEL
C C C C C C C C C C C C C B C C C B C C C C C C C C C C B B B C C C B B B B B C C
LOW
LOW
LOW
LOW
LOW
LOW
LOW
LOW
LOW
LOW
LOW
LOW
LOW
LOW
LOW
LOW
LOW
LOW
LOW
LOW
LOW
LOW
LOW
LOW
LOW
LOW
LOW
LOW
LOW
MEDIUM
LOW
LOW
HIGH
HIGH
MEDIUM
LOW
LOW
LOW
LOW
LOW
LOW
II
II
II
II
II
II
II
II
II
II
II
II
II
II
II
II
II
II
II
II
II
II
II
II
II
II
II
II
I
III
II
II
III
III
II
II
II
II
II
II
II
RICHARD
JOSEPH
ONKEN
A-5125
A
R C H I T E
C
T
S T
A T
E
O F N E B
R A
S K
A
3/14/2025
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED:
BUILDINGS 40, 46, 48, 53, 65, 88, 89, 90, 91, 103, 147,
148, T144, T171, T296
NOT FULLY SPRINKLERED:
BUILDINGS 47, 50, 85, 87, 96, 120, 137, 160
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMP
321 5 6 7 8 9 10
Alesia Architecture P.C.
3705 North 200th Street Elkhorn, Nebraska 68022 Phone: (402) 291-6941
A on e ei gh th in ch o ne f oo t th re e in ch es o ne f oo t
6" on e an d on e ha lf in ch es o ne f oo t on e in ch o ne f oo t
6" 6" th re e qu ar te rs in ch o ne f oo t on e ha lf in ch o ne f oo t th re e ei gh th s in ch o ne f oo t on e qu ar te r in ch o ne f oo t
FINAL CONSTRUCTION
DOCUMENTS
UPGRADE FIRE ALARM
SYSTEM (FM)
568-24-106
FT MEADE, SD
A
B
C
D
E
F
14MAR2025
Incandescence Life Safety, Inc.
3455 Ringsby Ct, Suite 103 Denver, CO 80216 Phone: (720) 722-3010
Specialized Engineering Solutions 10360 Ellison Circle Omaha, NE 68134 Phone: (402) 991-5520
OCMI, Inc.
909 Rose Avenue, Suite 400 North Bethesda, MD 20852
A u to d e s k D o c s /1
-2 -1
A
E U p d a te F ir e
A la rm S y s te m F t M e a d e
/5
-2
-1
.B
.A rc h R
-U p d a te F ir e
A la rm S y s te m F t M e a d e .r v t
/9
/2
:5
:4
P
M
GI101
LIFE SAFETY PLAN
GLG SW
LIFE SAFETY NOTES
1. EXISTING FIRE-RATED WALL - VERIFY RATING.
2 REFER TO FA SHEETS FOR CODE SUMMARY.
1/8" = 1'-0"1
BLDG. 148 - FIRST FLOOR LIFE SAFETY PLAN
APPLICABLE CODES & STANDARDS
Code/Standard Code/Standard Name Code/Standard Year
U.S. DEPARTMENT OF VETERANS AFFAIRS
VAFPDM FIRE PROTECTION DESIGN MANUAL 9TH EDITION, NOV 2023
VAPSDM PHSYICAL SECURITY DESIGN MANUAL FOR VA MISSION CRITICAL FACILITIES OCT 2020, REV MAY 2024
NATIONAL FIRE PROTECTION ASSOCIATION
NFPA 1 FIRE CODE 2024
NFPA 13 STANDARD FOR THE INSTALLATION OF SPRINKLER SYSTEMS 2025
NFPA 99 HEALTH CARE FACILITIES CODE 2021
NFPA 90A STANDARD FOR THE INSTALLATION OF AIR-CONDITIONING AND VENTILATION SYSTEMS 2024
NFPA 70 NATIONAL ELECTRICAL CODE 2023
NFPA 72 NATIONAL FIRE ALARM AND SIGNALING CODE 2025
NFPA 101 LIFE SAFETY CODE 2024
NFPA 220 STANDARD ON TYPES OF BUILDING CONSTRUCTION 2024
NFPA 110 STANDARD FOR EMERGENCY AND STANDBY POWER SYSTEMS 2022
INTERNATIONAL CODE COUNCIL
IBC INTERNATIONAL BUILDING CODE 2024
AMERICAN SOCIETY OF MECHANICAL ENGINEERS
ASME A17.1 SAFETY CODE FOR ELEVATORS AND ESCALATORS 2022
Mark Revisions: Date:
MH
D R Y W E
LL
PROPCOR
WV
WV
R A M P
D N th
S T R E E T
(A S P H A L T)
PARKING LOT
(ASPHALT)
COMANCHE ROAD
(ASPHALT)
CO
WV
PIV
WVWV
C U S
TE
R
A V E
C U S
TE
R
A V E
(A S P H A
LT
CONC.
ASPH.
CONC.
(C O N C
WV
CO
WV
WV
P A R K
IN
G
L O T
(C O N C
C O M P
AC
T O R
R A M P
D N
D N
R A M P
HYD
RAN
T
CO
CONC.
P A R K
IN
G
L O T
(A S P H A L T
P A R K
IN
G
L O T
(C O N C
CO
WV
WV
C O N C
CONC.
PARKING LOT
(ASPHALT)
WV
CO
RENO
ROAD
T H
COMANCHE
ROAD
TERRY
ROAD
D R Y W E
LLMH
CUSTER
STURG
IS
RD.
S E C O N D
S T
R D
TERRY
DR.
CUSTER
M
AC
KE
NZ
IE
T H
SD HW
Y
34/79
COMANCHE
RD.
SHERIDAN
RENO
ROAD
T H
BIK
E
PA
TH
SD H
WY
34/7
SD
H
WY
/7
SHERIDAN
COMANCHE
RD.
CO
MA
NC
HE
RD
TH
TERRY
DR.
T U N N E L
AC
AC
AC
AC
AC
AC
AC AC
ACACAC
x x x x x x x x x x x x x x x x x x x x x x x x x
46 T296
T171
T144
155 154
BUILDING T296 IS IN BOTH
PHASE 1 AND PHASE 2A
40 CARPENTER / PAINT SHOP
46 LOGISTICS WAREHOUSE
47 FALLOUT SHELTER
48 FACILITY MANAGEMENT WAREHOUSE
50 POST OFFICE
53 BUSINESS OFFICE
65 STUDENT QUARTERS
72 OFFICE
85 DAYCARE CENTER
87 GARAGE
88 CWT WORKSHOP
89 ENGINEERING BUILDING
90 EDUCATION
91 MOTOR POOL
96 VACANT GREENHOUSE
103 COVID STORAGE
120 DAYCARE GARAGE
137 BOILER PLANT
T144 HOPTEL
147 LAUNDRY
148 PATIENT CARE
154 SWITCHGEAR
155 GENERATOR
160 WATER TREATMENT
T171 ENGINEERING / HEAVY EQUIPMENT
T296 FIRE STATION
BUILDING LEGEND
INDUSTRIAL
STORAGE
STORAGE
STORAGE
BUSINESS
BUSINESS
DORMITORY
BUSINESS
DAYCARE
INDUSTRIAL
BUSINESS
BUSINESS, INDUSTRIAL
ASSEMBLY, STORAGE
INDUSTRIAL
STORAGE
STORAGE
STORAGE
INDUSTRIAL
DORMITORY
INDUSTRIAL
HEALTHCARE
INDUSTRIAL
INDUSTRIAL
INDUSTRIAL
INDUSTRIAL
STORAGE, DORMITORY
BUILDING NO. FUNCTIONAL TITLE OCCUPANCY CLASSIFICATION
PHASE 1: FIRE ALARM NETWORK EQUIP. IN BUILDINGS T296, 137, AND 148 TO BE
INSTALLED AND BROUGHT ONLINE TO MONITOR PROTECTED PREMISE CONTROL
PANEL.
PHASE 2: INSTALL FIRE ALARM SYSTEM AT THE PROTECTED PREMISE. REFER TO SHEET
FA001 FOR FIRE ALARM WORK PANEL SCHEDULE.
PHASE 2A: BUILDINGS 65, T144 and T296 WILL BE OCCUPIED THROUGHOUT THE
INSTALLATION OF THE NEW SYSTEM. MAINTAIN THE EQUIVALENT LEVELS OF FIRE
PROTECTION OVER THE DURATION OF THE PROJECT. PROVIDE ADVANCED
NOTIFICATION TO THE COR WHEN SYSTEMS ARE DOWN.
PHASE 3: PRIOR TO DEMOLITION OF THE EXISTING SYSTEM, THE NEW SYSTEM SHALL
BE TESTED AND APPROVED BY THE COR. ONCE NEW SYSTEM IS MONITORED BY THE
FIRE ALARM NETWORK DEMOLITION CAN PROCEED.
RICHARD
JOSEPH
ONKEN
A-5125
A
R C H I T E
C
T
S T
A T
E
O F N E B
R A
S K
A
3/14/2025
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED:
BUILDINGS 40, 46, 48, 53, 65, 88, 89, 90, 91, 103, 147,
148, T144, T171, T296
NOT FULLY SPRINKLERED:
BUILDINGS 47, 50, 85, 87, 96, 120, 137, 160
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMP
321 5 6 7 8 9 10
Alesia Architecture P.C.
3705 North 200th Street Elkhorn, Nebraska 68022 Phone: (402) 291-6941
A on e ei gh th in ch o ne f oo t th re e in ch es o ne f oo t
6" on e an d on e ha lf in ch es o ne f oo t on e in ch o ne f oo t
6" 6" th re e qu ar te rs in ch o ne f oo t on e ha lf in ch o ne f oo t th re e ei gh th s in ch o ne f oo t on e qu ar te r in ch o ne f oo t
FINAL CONSTRUCTION
DOCUMENTS
UPGRADE FIRE ALARM
SYSTEM (FM)
568-24-106
FT MEADE, SD
A
B
C
D
E
F
14MAR2025
Incandescence Life Safety, Inc.
3455 Ringsby Ct, Suite 103 Denver, CO 80216 Phone: (720) 722-3010
Specialized Engineering Solutions 10360 Ellison Circle Omaha, NE 68134 Phone: (402) 991-5520
OCMI, Inc.
909 Rose Avenue, Suite 400 North Bethesda, MD 20852
A u to d e s k D o c s /1
-2 -1
A
E U p d a te F ir e
A la rm S y s te m F t M e a d e
/5
-2
-1
.B
.A rc h R
-U p d a te F ir e
A la rm S y s te m F t M e a d e .r v t
/9
/2
:5
:4
P
M
GC101
PHASING PLAN
GLG SW
SITE MAP - PHASING PLAN
PLAN
NORTH
TRUE
NORTH
PLAN
NORTH
TRUE
NORTH
PHASING LEGEND
GENERAL PHASING NOTES
1. TYPICAL VA OPERATIONAL HOURS ARE 0700 - 1630 MOUNTAIN STANDARD TIME,
MONDAY - FRIDAY, UNLESS OTHERWISE NOTED.
2. SEE FIRE PROTECTION AND ELECTRICAL NOTES ON EACH OF THOSE RESPECTIVE
DISCIPLINES FLOOR PLANS AND GENERAL NOTES.
Mark Revisions: Date:
FACP F
TS
TS
TS
PS
PS
AIM
AIM
AIM
AIM
AIM
FADC
FACP F
TS
TS
TS
PS
PS
AIM
AIM
AIM
AIM
AIM
FADC
C
75 cd
C
75 cd
P
GARAGE
OFFICE
RESTROOM
101A
LOBBY
GARAGE
OFFICE
RESTROOM
101A
LOBBY
AFF12' - 6"
AFF7' - 9"
AFF7' - 9"
AFF7' - 9"
EXISTING GYPSUM WALL BOARD / PLASTER CEILING
EXISTING CAR SIDING T & G WOOD CEILING
EXISTING 1'-0" x 1'-0" STAPLED CEILING TILE
EXISTING 2'-0" x 2'-0" METAL TILE CEILING
REFLECTED CEILING LEGEND
NEW GYPSUM WALL BOARD / PLASTER CEILING
NEW CAR SIDING T & G WOOD CEILING
NEW 1'-0" x 1'-0" STAPLED CEILING TILE
NEW 2'-0" x 2'-0" METAL TILE CEILING
EXISTING NEW CONSTRUCTION
EXISTING SUSPENDED ACOUSTICAL CEILING TILE NEW SUSPENDED ACOUSTICAL CEILING TILE
HARD CEILING TYPES - ALL CEILING DEVICES AND CONDUIT SURFACE MOUNTED:
FINISHED SPACE:
CONCEALED CONDUIT. WHERE CONDUIT CANNOT BE CONCEALED,
SURFACE MOUNT AND PAINT TO MATCH EXISTING PER SPECIFICATION
SECTION 28 31 00 FIRE DETECTION AND ALARM.
UNFINISHED SPACE:
CONDUIT SURFACE MOUNTED AND PAINTED RED
RICHARD
JOSEPH
ONKEN
A-5125
A
R C H I T E
C
T
S T
A T
E
O F N E B
R A
S K
A
3/14/2025
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED:
BUILDINGS 40, 46, 48, 53, 65, 88, 89, 90, 91, 103, 147,
148, T144, T171, T296
NOT FULLY SPRINKLERED:
BUILDINGS 47, 50, 85, 87, 96, 120, 137, 160
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMP
321 5 6 7 8 9 10
Alesia Architecture P.C.
3705 North 200th Street Elkhorn, Nebraska 68022 Phone: (402) 291-6941
A on e ei gh th in ch o ne f oo t th re e in ch es o ne f oo t
6" on e an d on e ha lf in ch es o ne f oo t on e in ch o ne f oo t
6" 6" th re e qu ar te rs in ch o ne f oo t on e ha lf in ch o ne f oo t th re e ei gh th s in ch o ne f oo t on e qu ar te r in ch o ne f oo t
FINAL CONSTRUCTION
DOCUMENTS
UPGRADE FIRE ALARM
SYSTEM (FM)
568-24-106
FT MEADE, SD
A
B
C
D
E
F
14MAR2025
Incandescence Life Safety, Inc.
3455 Ringsby Ct, Suite 103 Denver, CO 80216 Phone: (720) 722-3010
Specialized Engineering Solutions 10360 Ellison Circle Omaha, NE 68134 Phone: (402) 991-5520
OCMI, Inc.
909 Rose Avenue, Suite 400 North Bethesda, MD 20852
A u to d e s k D o c s /1
-2 -1
A
E U p d a te F ir e
A la rm S y s te m F t M e a d e
/5
-2
-1
.B
.A rc h R
-U p d a te F ir e
A la rm S y s te m F t M e a d e .r v t
/9
/2
:5
:2
P
M
154-AE101
BLDGS. 154, 155 & T171 - FLOOR PLAN
AND REFLECTED CEILING PLAN
GLG SW
1/8" = 1'-0"1
BLDG. T171 - FIRST FLOOR PLAN
08' 8' 16'4'
SCALE: 1/8" = 1'-0"
154 155 & T171
1/8" = 1'-0"4
BLDG. T171 - FIRST FLOOR REFLECTED CEILING PLAN
N TRUE
NORTH
BUILDING 154: SWITCHGEAR
INDUSTRIAL OCCUPANCY
BUILDING 155: GENERATOR
INDUSTRIAL OCCUPANCY
BUILDING T171: ENGINEERING / HEAVY EQUIPMENT
INDUSTRIAL OCCUPANCY
GENERAL NOTES
1 ALL NEW CONSTRUCTION IS INDICATED BOLD OR FULL TONE.
2 ALL METAL STUD AND GYPSUM WALLBOARD PARTITIONS ARE DIMENSIONED TO
FACE OF STUD AND TO COLUMN GRID UNLESS OTHERWISE NOTED.
3 WHEN WALL PARTITIONS OF DIFFERENT FIRE RATING INTERSECT, THE HIGHEST
RATED PARTITION TAKES PRECEDENT. MAINTAIN RATING BEHIND FACP
INSTALLATION LOCATIONS.
4 CONTRACTOR SHALL FIELD VERIFY EXISTING CONDITIONS PRIOR TO WORK.
5 ALL EXISTING TO REMAIN CEILING AND WALL GRILLES, DIFFUSERS AND LIGHTS,
ETC. TYPICAL IN WORK AREAS TO BE CLEANED AFTER WORK IS FINISHED.
6 CONTRACTOR SHALL REPAIR WALL PENETRATIONS AND DAMAGE THAT OCCUR
DURING THE WORK.
7 SEE SHEET AG001 FOR GENERAL ARCHITECTURAL NOTES AND GENERAL
INTERIOR FINISH NOTES.
8 SEE FA100 SERIES SHEETS FOR FIRE ALARM DEMOLITION PLANS.
CONSTRUCTION PROJECT TYPE PATIENT RISK GROUP ICRA LEVEL
B LOW II
ICRA CLASSIFICATION:
CONSTRUCTION PROJECT TYPE PATIENT RISK GROUP ICRA LEVEL
B LOW II
CONSTRUCTION PROJECT TYPE PATIENT RISK GROUP ICRA LEVEL
B LOW II (GARAGE)
C LOW II (OFFICE)
REMOVED FROM SCOPE REMOVED FROM SCOPE
REMOVED FROM SCOPEREMOVED FROM SCOPE
Mark Revisions: Date:
1. PROVIDE A COMPLETE FIRE ALARM AND OCCUPANT NOTIFICATION SYSTEM
WITH ALL NECESSARY EQUIPMENT, APPURTENANCES, AND CONTROLS,
COMPLETELY COORDINATED WITH ALL DISCIPLINES. ALL WORK SHALL BE
PERFORMED IN ACCORDANCE THE AUTHORITY HAVING JURISDICTION (AHJ)
REQUIREMENTS, AND THESE CONTRACT DOCUMENTS (INCLUDING, BUT
NOT LIMITED TO NFPA 70, NFPA 72, NFPA 90A, AND THE VAFPDM).
2. ALL COMPONENTS AND ASSEMBLIES SHALL BE U.L. LISTED OR FM
APPROVED FOR THEIR INTENDED APPLICATION.
3. THESE DRAWINGS ARE DIAGRAMMATIC IN NATURE AND ARE INTENDED TO
CONVEY OVERALL SYSTEM ARRANGEMENT AS IT PERTAINS TO THIS SCOPE
OF WORK. THE CONTRACTOR SHALL BE RESPONSIBLE FOR FURNISHING
AND INSTALLING A COMPLETE FIRE ALARM SYSTEM AS INDICATED IN THE
DESIGN DOCUMENTS AND THE REFERENCED STANDARDS AND
DETERMINING SPEAKER WATTAGE (IF APPLICABLE). THE CONTRACTOR
SHALL BE RESPONSIBLE FOR THE FINAL SELECTION AND PLACEMENT OF
NOTIFICATION APPLIANCES, INCLUDING DETERMINATION OF CANDELA
RATING AND SPEAKER WATTAGE REQUIREMENTS.
4. ADDITIONAL DEVICES AND PARTS BEYOND WHAT IS SHOWN ON THESE
PLANS MAY BE REQUIRED; CONTRACTOR SHALL HAVE THE DISCRETION TO
ALTER DEVICE LOCATIONS AND COUNTS.
5. COORDINATE ALL WORK WITH ARCHITECTURAL, MECHANICAL, AND
ELECTRICAL TRADES. PROVIDE ALL OFFSETS TO AVOID INTERFERENCE
WITH EQUIPMENT, PIPING, DUCTWORK, LIGHTS, CONDUIT, OR STRUCTURAL
MEMBERS.
6. ALL FIRE ALARM CABLES AND WIRING SHALL BE INSTALLED WITHIN METAL
RACEWAYS. ALL RACEWAYS SHALL BE CONCEALED WITHIN FINISHED
AREAS. RACEWAYS SHALL BE PARALLEL OR PERPENDICULAR TO BUILDING
STRUCTURAL ELEMENTS. JUNCTION BOXES SHALL BE PROVIDED AND ALL
CONDUCTORS SHALL BE IDENTIFIED AT EACH JUNCTION BOX, PULL BOX,
ETC. WITH APPROPRIATE INFORMATION (E.G. PANEL NUMBER, CIRCUIT
NUMBER, ETC.).
7. SMOKE DETECTORS SHALL BE LOCATED PER NFPA 72 AND
MANUFACTURERS REQUIREMENTS. LOCATIONS SHOWN ARE
DIAGRAMMATIC. DETECTORS SHALL NOT BE PLACED WITHIN 3'-0" OF ANY
CEILING MOUNTED HVAC SUPPLY AIR DEVICE, WITHIN 4" OF WALL AND
WHEN WALL MOUNTED SHALL BE LOCATED BETWEEN 4" AND 12" FROM
CEILING PLANE.
8. NEW DEVICES THAT ARE INSTALLED BUT NOT YET IN SERVICE SHALL BE
TAGGED "NOT IN SERVICE" UNTIL ACCEPTANCE OF THE NEW FIRE ALARM
SYSTEM.
FIRE ALARM GENERAL NOTES FIRE ALARM SYMBOL LEGEND
FIRE ALARM CONTROL PANELFACP
NOTIFICATION APPLIANCE CIRCUIT EXTENDER
POWER PANEL
NAC
FIRE ALARM SYSTEM ANNUNCIATOR PANELANN
CLEAR STROBE NOTIFICATION APPLIANCE
SPEAKER NOTIFICATION APPLIANCE
COMBINATION SPEAKER/CLEAR STROBE APPLIANCE
WATER FLOW DETECTOR/SWITCHWF
VALVE SUPERVISORY TAMPER SWITCHTS
ADDRESSABLE MANUAL PULL STATIONF
ADDRESSABLE INPUT MODULE
AIM
ADDRESSABLE PHOTOELECTRIC SMOKE
DETECTOR
ADDRESSABLE PHOTOELECTRIC DUCT SMOKE
DETECTOR
ADDRESSABLE CONTROL MODULE RELAY
CM
FIRE ALARM NETWORK WORKSTATIONWKSN
WP WEATHER PROOF
REMOTE TEST SWITCH
ABBREVIATIONS
P
PHOTOELECTRIC SMOKE DETECTOR WITH LOW
FREQUENCY SOUNDER BASESB
C
C S
COMPONENT PHASE LEGEND
NEW COMPONENT
C
COMPONENT TO BE DEMOLISHED
C
EXISTING COMPONENT TO REMAIN
C
NET NETWORK APPLIANCE
F G
EXTERIOR MECHANICAL GONG
HORN NOTIFICATION APPLIANCE
C CEILING MOUNTED DEVICE
COMBINATION HORN/CLEAR STROBE APPLIANCE
FIRE ALARM BATTERY CABINETBATT
END OF LINE POWER SUPERVISION RELAYPWR
FIRE ALARM DOCUMENT CABINETFADC
CABON MONOXIDE DETECTOR
CO
1. ALL ELECTRICAL ITEMS INSTALLED IN WALLS, FLOORS, OR CEILINGS TO BE DEMOLISHED SHALL BE REMOVED IN THEIR ENTIRETY UNLESS OTHERWISE NOTED OR REQUIRED BY OTHER CONDITIONS IN
THESE DOCUMENTS. SEE DRAWINGS OF ALL OTHER TRADES FOR EXTENT OF DEMOLITION WORK.
ELECTRICAL ITEMS SHALL INCLUDE POWER, LIGHTING, AND SPECIAL SYSTEMS. REFER ALL QUESTIONS OF APPLICABILITY TO THE A/E PRIOR TO BID FOR CLARIFICATION; OTHERWISE, FIELD DECISIONS BY
THE A/E SHALL BE BINDING.
2. IT IS NOTED THAT THESE DRAWINGS DEPICT THE GENERAL INTENT OF THE SCOPE OF THE DEMOLITION WORK AND THAT NOT ALL ITEMS OF ELECTRICAL DEMOLITION ARE NECESSARILY SHOWN. PLEASE SEE THE ELECTRICAL SHEETS FOR THE SCOPE OF ELECTRICAL DEMOLITION. THE CONTRACTOR SHALL BE REQUIRED TO FIELD VERIFY THE SCOPE OF THE DEMOLITION WORK PRIOR TO BID. REFER ALL
QUESTIONS TO THE A/E PRIOR TO BID FOR CLARIFICATION.
3. PHASING OF ELECTRICAL DEMOLITION SHALL FOLLOW THAT OF THE GENERAL CONTRACTOR.
COORDINATE REMOVAL OF ELECTRICAL WORK WITH OTHER CONSTRUCTION ACTIVITIES AND THE
REQUIREMENTS OF THE OWNER.
4. THE OWNER SHALL HAVE SALVAGE RIGHTS TO ANY ITEMS THAT ARE TO BE DEMOLISHED. ITEMS SUCH
AS SPEAKERS AND PANELS AND OTHER ITEMS THAT THE OWNER WISHES TO SALVAGE SHALL BE
CAREFULLY REMOVED AND STORED IN A LOCATION AS DIRECTED BY THE OWNER. ALL OTHER ITEMS OF DEMOLITION SHALL BECOME THE PROPERTY OF THE CONTRACTOR AND SHALL BE REMOVED FROM
THE SITE.
5. FIELD VERIFY THAT ALL FIRE ALARM CONDUCTORS AND RACEWAYS ORIGINATING WITHIN THE WORK
AREA DO NOT SERVE AREAS OUTSIDE THE SCOPE OF WORK. WHERE DEMOLITION WORK WILL
INTERRUPT CIRCUIT CONTINUITY TO OTHER AREAS OF THE FACILITY THAT ARE TO REMAIN IN OPERATION, RACEWAYS AND WIRING SHALL BE INSTALLED TO MAINTAIN THOSE AREAS IN COMPLETE OPERATION. PROVIDE TEMPORARY CONNECTIONS AS REQUIRED. COORDINATE ANY INTERRUPTIONS
WITH THE OWNER AT LEAST TWO WEEKS PRIOR AND ACCOMMODATE THE OWNER'S NEEDS AS
REQUIRED.
6. ELECTRICAL CIRCUITS THAT ARE TO BE REMOVED SHALL BE REMOVED IN THEIR ENTIRETY.
CONDUCTORS SHALL BE REMOVED FROM THE ITEM TO BE DEMOLISHED TO THE SOURCE
OVERCURRENT DEVICE. RACEWAYS WHICH ARE INSTALLED IN OR BELOW FLOORS OR WITHIN WALLS
MAY BE ABANDONED, BUT ALL OVERHEAD OR EXPOSED RACEWAYS SHALL BE REMOVED. EXPOSED
RACEWAYS TO BE ABANDONED SHALL BE REMOVED AND SHALL BE CUT OR CHISELED AT LEAST 2"
INTO THE WALL OR FLOOR AND THE OPENING GROUTED SMOOTH.
7. WHERE EXISTING DEVICE OR JUNCTION BOXES MUST REMAIN IN EXISTING WALLS OR CEILINGS (SUCH AS FOR CIRCUITS THAT MUST BE MAINTAINED TO OTHER AREAS), THEN THEY SHALL BE FITTED WITH
BLANK COVER PLATES.
8. WHERE DISTRIBUTION OR BRANCH CIRCUIT EQUIPMENT (PANELBOARDS, SWITCHBOARDS, ETC.) IS TO BE REMOVED, THEN ALL CIRCUITS WHICH FEED ITEMS TO REMAIN SHALL BE RECONNECTED TO NEW
DISTRIBUTION OR BRANCH CIRCUIT EQUIPMENT. REFER ALL QUESTIONS TO THE A/E FOR
CLARIFICATION.
9. IF HAZARDOUS MATERIALS (I.E. ASBESTOS, PCB's, ETC.) ARE ENCOUNTERED AT ANY TIME DURING
CONSTRUCTION IN THE WORK AREA, STOP WORK IMMEDIATELY AND CONTACT THE A/E OR THE
OWNER.
FIRE ALARM DEMOLITION NOTES
1. THE FIRE ALARM SYSTEM PHASING, TESTING, AND CUTOVER PLANS MUST BE APPROVED BY THE
CONTRACTING OFFICER REPRESENTATIVE PRIOR TO ANY FIRE ALARM SYSTEM OUTAGE.
2. ALL FIRE SUPPRESSION AND FIRE ALARM SYSTEMS ARE MAINTAINED BY GOVERNMENT FIRE PROTECTION
MAINTENANCE CONTRACTORS AND ONLY THESE CONTRACTORS CAN PERFORM THE SHUTDOWN AND
RESTARTING OF SAID SYSTEMS. CONSTRUCTION GENERAL CONTRACTOR IS TO NEGOTIATE WITH, AND PAY DIRECTLY SAID GOVERNMENT FIRE PROTECTION MAINTENANCE CONTRACTORS. GOVERNMENT WILL
NOT REIMBURSE.
3. A FIRE WATCH, AT CONTRACTOR'S COST, WILL BE CONDUCTED CONTINUOUSLY THROUGHOUT THE DURATION OF THE OUTAGE IN ALL AREAS AFFECTED BY THE OUTAGE. FINDINGS/COMMENTS WILL BE
DOCUMENTED HOURLY ON WATCH FORMS PROVIDED BY THE GOVERNMENT. DOCUMENTATION OF
FINDINGS WILL BE MADE AVAILABLE TO THE GOVERNMENT OFFICIALS UPON THEIR REQUEST. IN THE
EVENT OF ANY FIRE/SMOKE EMERGENCIES DISCOVERED DURING THE FIRE WATCH, EMERGENCY
NOTIFICATION WILL BE CONDUCTED IN ACCORDANCE WITH PROCEDURES OUTLINED BY THE
GOVERNMENT.
4. OUTAGE TIME DURATIONS WILL NOT BE PERMITTED TO SPAN THE ENTIRE DURATION OF THE PROJECT.
OVERNIGHT OUTAGES WILL NOT BE PERMITTED UNLESS WORK IS BEING DONE DURING THAT TIME PERIOD AND THE FIRE ALARM SYSTEM IS PUT BACK INTO SERVICE WITHIN AN HOUR FROM COMPLETION OF WORK. OUTAGES SHALL BE LIMITED TO 8 HOURS INCLUDING TIME FOR DRAINING AND REFILLING.
5. FIRE ALARM SYSTEMS ARE NOT PERMITTED TO HAVE AN OUTAGE FOR MORE THAN AN HOUR BEFORE STARTING WORK. THE FIRE ALARM AND SPRINKLER SYSTEM SHALL BE RESTORED WITHIN AN HOUR OF COMPLETION OF WORK. THE CONTRACTOR CANNOT LEAVE THE CONSTRUCTION SITE UNPROTECTED.
THE SPRINKLER SYSTEM SHALL BE PROPERLY CHARGED AND OPERATIONAL WITHIN AN HOUR OF
COMPLETION OF WORK. REMOVED CEILING TILES SHALL BE REPLACED AFTER EVERY SHIFT.
6. FIRE SPRINKLER SUPERVISION FOR FLOW AND TAMPER SHALL BE CONTINUOUS THROUGH THE PROJECT.
CUTOVER OF THE FIRE SPRINKLER SYSTEM FLOW AND TAMPER DEVICES SHALL NOT BE CONDUCTED UNTIL THE NEW FIRE ALARM SYSTEM IS OTHERWISE TESTED, ACCEPTED AND REPORTING TO THE
PROTECTED PREMISES.
FIRE ALARM SYSTEM OUTAGE NOTES:
WIRE SCHEDULE
SIGNALING LINE CIRCUIT (SLC)
VISUAL NOTIFCATION APPLIANCE CIRCUIT (NAC)
AUXILIARY POWER
INITIATING DEVICE CIRCUIT
NETWORK DATA & POWER
WIRE DESCRIPTION
*WIRING SPECIFCATIONS ARE GENERAL AND MANUFACTURE'S WIRING RECONMENDATIONS MUST BE FOLLOWED.
**ALL UNDERGROUND WIRING SHALL BE RATED FOR UNDERGROUND APPLICATIONS.
† REFERENCE THE NOTIFICATION CHARATERISTICS (THIS SHEET) TO DETERMINE WIRE REQUREMENTS FROM BUILDING TO BUILDING.
TYPE SYMBOL
A
B
C
E
D
AUDIBLE NOTIFCATION APPLIANCE CIRCUIT (NAC)†
F
LIFE SAFETY NOTES:
SMOKE PARTITION
SYMBOL
FOR FIRE ALARM SYSTEM, SEE FIRE ALARM DRAWINGS.
ALL FIRE RATED PARTITIONS SHALL EXTEND FROM FLOOR SLAB TO
THE UNDERSIDE OF THE DECK ABOVE. THE SPACE ADJACENT TO
THE DECK AND OTHER SURFACES, AND THE SPACES AROUND
PENETRATING ITEMS SHALL BE FIRESTOPPED.
LIFE SAFETY SYMBOLS:
DESCRIPTION
1-HOUR FIRE BARRIER
2-HOUR FIRE BARRIER
SMOKE BARRIER
1-HOUR SMOKE BARRIER
2-HOUR SMOKE BARRIER
30-MINUTE SMOKE BARRIER
S S
S
S
S
S
S
S
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED:
BUILDINGS 40, 46, 48, 53, 65, 88, 89, 90, 91, 103, 147,
148, T144, T171, T296
NOT FULLY SPRINKLERED:
BUILDINGS 47, 50, 85, 87, 96, 120, 137, 160
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMP
321 5 6 7 8 9 10
Alesia Architecture P.C.
3705 North 200th Street Elkhorn, Nebraska 68022 Phone: (402) 291-6941
A on e ei gh th in ch o ne f oo t th re e in ch es o ne f oo t
6" on e an d on e ha lf in ch es o ne f oo t on e in ch o ne f oo t
6" 6" th re e qu ar te rs in ch o ne f oo t on e ha lf in ch o ne f oo t th re e ei gh th s in ch o ne f oo t on e qu ar te r in ch o ne f oo t
FINAL CONSTRUCTION
DOCUMENTS
UPGRADE FIRE ALARM
SYSTEM (FM)
568-24-106
FT MEADE, SD
A
B
C
D
E
F
14MAR2025
Incandescence Life Safety, Inc.
3455 Ringsby Ct, Suite 103 Denver, CO 80216 Phone: (720) 722-3010
Specialized Engineering Solutions 10360 Ellison Circle Omaha, NE 68134 Phone: (402) 991-5520
OCMI, Inc.
909 Rose Avenue, Suite 400 North Bethesda, MD 20852
A u to d e s k D o c s
/1
-2
-1
A
E U p d a te
F ir e
A la rm S y s te m F t M e a d e /5
-2
-1
V
A F t M e a d e F
P L
S R
.r v t
/9
/2
:1
:5
P
M
FA001
FIRE ALARM GENERAL NOTES
TGD GMP
FIRE ALARM WORK PANEL SCHEDULE
BUILDING
NUMBER BUILDING NAME FIRE ALARM WORK DESCRIPTION NOTIFICATION CHARACTERISTIC
40 CARPENTER / PAINT SHOP NEW FIRE ALARM SYSTEM GENERAL EVACUATION (TONE)
46 LOGISTICS WAREHOUSE NEW FIRE ALARM SYSTEM GENERAL EVACUATION (VOICE)
47 FALLOUT SHELTER NEW FIRE ALARM DEVICES - EXTENDED SLC FROM BUILDING 48 GENERAL EVACUATION (TONE)
48 FACILITY MANAGEMENT WAREHOUSE NEW FIRE ALARM SYSTEM GENERAL EVACUATION (TONE)
50 POST OFFICE NEW FIRE ALARM SYSTEM GENERAL EVACUATION (TONE)
53 BUSINESS OFFICE NEW FIRE ALARM SYSTEM GENERAL EVACUATION (VOICE)
65 STUDENT QUARTERS NEW FIRE ALARM SYSTEM GENERAL EVACUATION (TONE)
72 OFFICE MONITOR EXISTING FIRE ALARM SYSTEM - EXTENDED FROM BUILDING 85 N/A
85 DAY CARE NEW FIRE ALARM SYSTEM GENERAL EVACUATION (TONE)
87 GARAGE NEW FIRE ALARM SYSTEM GENERAL EVACUATION (TONE)
88 CWT WORKSHOP NEW FIRE ALARM SYSTEM GENERAL EVACUATION (VOICE)
89 ENGINEERING NEW FIRE ALARM SYSTEM GENERAL EVACUATION (VOICE)
90 EDUCATION NEW FIRE ALARM SYSTEM GENERAL EVACUATION (VOICE)
91 MOTOR POOL NEW FIRE ALARM SYSTEM GENERAL EVACUATION (TONE)
96 GREENHOUSE NETWORK EXISTING PANEL INTO NEW NETWORK N/A
103 COVID STORAGE NETWORK EXISTING PANEL INTO NEW NETWORK N/A
120 DAY CARE GARGE NEW FIRE ALARM DEVICES - EXTENDED SLC FROM BUILDING 85 GENERAL EVACUATION (TONE)
137 BOILER PLANT NEW FIRE ALARM SYSTEM & NETWORK MONITORING WORKSTATION GENERAL EVACUATION (TONE)
147 LAUNDRY NEW FIRE ALARM SYSTEM GENERAL EVACUATION (VOICE)
148 MAIN MEDICAL CLINIC REDUNDANT CPU FOR EXISTING SYSTEM & NEW NETWORK MONITORING WORKSTATION MAINTAIN STAFF RESPONSE
154 SWITCHGEAR NEW FIRE ALARM SYSTEM GENERAL EVACUATION (TONE)
155 GENERATOR NEW FIRE ALARM SYSTEM GENERAL EVACUATION (TONE)
160 TREATMENT PLANT NEW FIRE ALARM SYSTEM GENERAL EVACUATION (TONE)
T144 HOPTEL NEW FIRE ALARM SYSTEM GENERAL EVACUATION (TONE)
T171 ENGINEERING / HEAVY EQUIPMENT NEW FIRE ALARM SYSTEM GENERAL EVACUATION (TONE)
T296 FIRE DEPARTMENT NEW NETWORK MONITORING WORKSTATION FOR FIRE ALARM SYSTEM N/A
T296 FIRE DEPARTMENT NEW FIRE ALARM SYSTEM GENERAL EVACUATION (TONE)
Mark Revisions: Date:
04/09/26
SSS
SS S
S
S S S S S S
FACP
NODE #
BLDG 103
FIRE ALARM
CONTROL
PANEL
FACP
NODE #
BLDG 65
FIRE ALARM
CONTROL
PANEL
FACP
NODE #
BLDG 96
FIRE ALARM
CONTROL
PANEL
FACP
NODE #
BLDG 147
FIRE ALARM
CONTROL
PANEL
FACP
NODE #
BLDG 137
FIRE ALARM
CONTROL
PANEL
FACP
NODE #
BLDG 148
FIRE ALARM
CONTROL
PANEL
FACP
NODE #
BLDG 53
FIRE ALARM
CONTROL
PANEL
FACP
NODE #
BLDG 50
FIRE ALARM
CONTROL
PANEL
FACP
NODE #
BLDG 48
FIRE ALARM
CONTROL
PANEL
FACP
NODE #
BLDG 90
FIRE ALARM
CONTROL
PANEL
FACP
NODE #
BLDG T144
FIRE ALARM
CONTROL
PANEL
FACP
NODE #
BLDG T296
FIRE ALARM
CONTROL
PANEL
FACP
NODE #
BLDG 89
FIRE ALARM
CONTROL
PANEL
FACP
NODE #
BLDG T171
FIRE ALARM
CONTROL
PANEL
FACP
NODE #
BLDG 87
FIRE ALARM
CONTROL
PANEL
FACP
NODE #
BLDG 154
FIRE ALARM
CONTROL
PANEL
FACP
NODE #
BLDG 155
FIRE ALARM
CONTROL
PANEL
FACP
NODE #
BLDG 88
FIRE ALARM
CONTROL
PANEL
FACP
NODE #
BLDG 40
FIRE ALARM
CONTROL
PANEL
FACP
NODE #
BLDG 91
FIRE ALARM
CONTROL
PANEL
FACP
NODE #
BLDG 46
FIRE ALARM
CONTROL
PANEL
FACP
NODE #
BLDG 85
FIRE ALARM
CONTROL
PANEL
FACP
NODE #
BLDG 160
FIRE ALARM
CONTROL
PANEL
BLDG. 55
PASS THROUGH
@ PATCH PANEL
BLDG. 120
ADDRESSABLE FIRE
ALARM DEVICES &
NOTIFICATION
APPLIANCES ON SLC &
NAC FED FROM BLDG. 85
FACP
BLDG. 72
ADDRESSABLE FIRE
ALARM DEVICES &
NOTIFICATION
APPLIANCES ON SLC &
NAC FED FROM BLDG. 85
FACP
BLDG. 47
ADDRESSABLE FIRE
ALARM DEVICES &
NOTIFICATION
APPLIANCES ON SLC &
NAC FED FROM BLDG. 48
FACP
BLDG. 96
EXISTING
ADDRESSABLE FIRE
ALARM DEVICES &
NOTIFICATION
APPLIANCES TO
REMAIN.
NEW FIRE ALARM
FACP NODE TO
MONITOR EXISTING
SIMPLEX PANEL
FOR ALARM,
SUPERVISORY &
TROUBLE
CONDITIONS
BLDG. 103
EXISTING
ADDRESSABLE FIRE
ALARM DEVICES &
NOTIFICATION
APPLIANCES TO
REMAIN.
NEW FIRE ALARM
FACP NODE TO
MONITOR EXISTING
SIMPLEX PANEL
FOR ALARM,
SUPERVISORY &
TROUBLE
CONDITIONS
BLDG. 148
EXISTING
ADDRESSABLE FIRE
ALARM DEVICES &
NOTIFICATION
APPLIANCES TO
REMAIN.
NEW FIRE ALARM
FACP NODE TO
MONITOR EXISTING
SIMPLEX PANEL
FOR ALARM,
SUPERVISORY &
TROUBLE
CONDITIONS
INSTALL NEW
REDUNDANT CPU IN
EXISTING SIMPLEX
FIRE ALARM
CONTROL PANEL
MONITORING
STATION
(NODE #)
MONITORING
STATION
(NODE #)
MONITORING
STATION
(NODE #)
FF
FF
F F
F
F F
F
F F
F F
FFFF
F F
F F
F
F
F
F
F
F
F
FFFFF
F
F
F
F F F
F
FF F
F
EMH 21
EMH 17EMH 8
SMH 4EMH 3 SMH 5
EMH 2
MH20A MH10A MH11A MH11B MH12B MH12A
1. THE NEW FIRE ALARM NETWORK MASTER CONTROL WILL BE LOCATED AT T296.
2. NETWORK MONITORING IN BUILDINGS T296, 137, AND 148 FOR THIS PROJECT MUST BE
CONNECTED PRIOR TO BRINGING ON ADDITIONAL FIRE ALARM SYSTEMS.
3. COORDINATE GENERAL PHASING OF FIRE ALARM WORK WITH ARCHITECTURAL PLANS.
FIRE ALARM NETWORK INTERCONNECTION NOTES
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED:
BUILDINGS 40, 46, 48, 53, 65, 88, 89, 90, 91, 103, 147,
148, T144, T171, T296
NOT FULLY SPRINKLERED:
BUILDINGS 47, 50, 85, 87, 96, 120, 137, 160
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMP
321 5 6 7 8 9 10
Alesia Architecture P.C.
3705 North 200th Street Elkhorn, Nebraska 68022 Phone: (402) 291-6941
A on e ei gh th in ch o ne f oo t th re e in ch es o ne f oo t
6" on e an d on e ha lf in ch es o ne f oo t on e in ch o ne f oo t
6" 6" th re e qu ar te rs in ch o ne f oo t on e ha lf in ch o ne f oo t th re e ei gh th s in ch o ne f oo t on e qu ar te r in ch o ne f oo t
FINAL CONSTRUCTION
DOCUMENTS
UPGRADE FIRE ALARM
SYSTEM (FM)
568-24-106
FT MEADE, SD
A
B
C
D
E
F
14MAR2025
Incandescence Life Safety, Inc.
3455 Ringsby Ct, Suite 103 Denver, CO 80216 Phone: (720) 722-3010
Specialized Engineering Solutions 10360 Ellison Circle Omaha, NE 68134 Phone: (402) 991-5520
OCMI, Inc.
909 Rose Avenue, Suite 400 North Bethesda, MD 20852
A u to d e s k D o c s
/1
-2
-1
A
E U p d a te
F ir e
A la rm S y s te m F t M e a d e /5
-2
-1
V
A F t M e a d e F
P L
S R
.r v t
/9
/2
:1
:5
P
M
FA002
FIRE ALARM NETWORK DIAGRAM
TGD GMP
1/8" = 1'-0"3
VA FORT MEADE NEW FIRE ALARM NETWORK DIAGRAM
REMOVED FROM
SCOPE OF WORK
Mark Revisions: Date:
E E
E
S
S
S
E
E
SE
E
SSSS S S S
S
S
S
E
S
CONC.CONC.
EMH
PARKING LOT
(ASPHALT)
C O M P A C T O R
R
AM
P
D N
SMH
S
E th
S T
R E
E T
COMANCHE ROAD
C U
S T
E R
A V
E
C U
S T
E R
A V
E
RENO ROAD
T
H
COMANCHE ROAD
TERRY ROAD
CUSTER
STURGIS RD.
S E
C O
N D
S
T
R
D
TERRY DR.
CUSTER
M
AC
KEN
ZIE
T
H
COMANCHE RD.
SHERIDAN
RENO ROAD
T
H
COMANCHE RD.
SD HWY 34/79
SD H
W
Y 34/79
SHERIDAN
COMANCHE RD.
T
H
TERRY DR.
SMH 4 EMH 8
EMH 2
EMH 2A
EMH 35
EMH 36
EMH 34
EMH 3
EMH 3A
EMH 4B
EMH 20ASMH 6A
SMH 5A
EMH 17AEMH 12B
EMH 11B
EMH 11A
EMH 18 EMH 19 EMH 20A
EMH 21A
EMH 22
EMH 23
EMH 23A
EMH 10A
10 9
360 362 150
4&5
B
A
T -2
109108
B L D
B L D
B L D
B L D
T171
T296
T144
FIR
E S
TATIO
N
NATL GUARD
NATL GUARDNATL GUARD
x x x x x x x x x x x x x x x x x x
E E
E E
E E
E E
E
E
E x x x x x x x x x x x x x x x x x x
1. REFER TO SHEET FA001 FOR FIRE ALARM GENERAL NOTES.
2. THIS SHEET IS DIAGRAMMATIC IN NATURE AND IS INTENDED TO DEMONSTRATE SITE
WIDE INTERCONNECTION OF THE FIRE ALARM SYSTEM.
3. SHADED BUILDINGS INDICATE LOCATIONS FOR NEW FIRE ALARM NETWORK NODE AND
WILL REQUIRE FIRE ALARM NETWORK FIBER OPTIC CABLE.
4. FIBER OPTIC CABLES ARE TO BE MULTIMODE CABLES WITH [ST] CONNECTOR
TERMINATIONS. UNDERGROUND RUNS SHALL BE RATED FOR WET LOCATIONS AND
RUNS THROUGH BUILDINGS SHALL BE PLENUM RATED.
5. SINGLE MODE CABLE TYPE MAY BE USED WITH MULTI MODE CONVERTERS WHERE
LONGER RUNS ARE REQUIRED. ALL REQUIRED FIBER CONVERTERS WILL BE
PROVIDED BY THE FIRE ALARM CONTRACTOR.
6. FIRE ALARM NETWORK SHALL BE RUN IN CLASS X CONFIGURATION IN ACCORDANCE
WITH PROJECT SPECIFICATIONS AND VA REQUIREMENTS.
FIRE ALARM INTERCONNECTION GENERAL NOTES:
FIRE ALARM FIBER OPTIC CABLE LEGEND:
NEW FIBER OPTIC CABLE IN EXISTING UNDERGROUND SIGNAL DUCT
NEW FIBER OPTIC CABLE IN EXISTING UNDERGROUND FIRE ALARM DUCT
NEW FIBER OPTIC CABLE RUN IN EXISTING BUILDING RACEWAY
1. APPROXIMATE PATH OF EXISTING FIRE ALARM FIBER ROUTE. PULL NEW FIRE
ALARM NETWORK FIBER OPTIC CABLE THROUGH EXISTING PATHWAYS.
2. APPROXIMATE PATH OF EXISTING BASE SIGNAL FIBER ROUTE. PULL NEW FIRE
ALARM NETWORK FIBER OPTIC CABLE THROUGH EXISTING PATHWAYS.
3. EXISTING FIRE ALARM NETWORK FIBER OPTIC CABLE INSTALLED IN LATE 2024.
VERIFY SPARE FIBER STRANDS AND USE EXISTING CABLE FOR NEW FIRE
ALARM NETWORK COMMUNICATIONS IF POSSIBLE.
4. EXISTING FIBER PATH CONTINUES TO BUILDING 160. VERIFY SPARE FIBER
STRANDS AND USE EXISTING CABLE FOR NEW FIRE ALARM NETWORK
COMMUNICATIONS. PROVIDE ST CONNECTORS AT FIBER TERMINATION AS
DETAILED IN SPECIFICATION SECTION 280513.
5. RUN NEW FIRE ALARM FIBER THROUGH BUILDING USING EXISTING FIRE ALARM
FIBER PATH.
FIRE ALARM KEYNOTES X
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED:
BUILDINGS 40, 46, 48, 53, 65, 88, 89, 90, 91, 103, 147,
148, T144, T171, T296
NOT FULLY SPRINKLERED:
BUILDINGS 47, 50, 85, 87, 96, 120, 137, 160
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMP
321 5 6 7 8 9 10
Alesia Architecture P.C.
3705 North 200th Street Elkhorn, Nebraska 68022 Phone: (402) 291-6941
A on e ei gh th in ch o ne f oo t th re e in ch es o ne f oo t
6" on e an d on e ha lf in ch es o ne f oo t on e in ch o ne f oo t
6" 6" th re e qu ar te rs in ch o ne f oo t on e ha lf in ch o ne f oo t th re e ei gh th s in ch o ne f oo t on e qu ar te r in ch o ne f oo t
FINAL CONSTRUCTION
DOCUMENTS
UPGRADE FIRE ALARM
SYSTEM (FM)
568-24-106
FT MEADE, SD
A
B
C
D
E
F
14MAR2025
Incandescence Life Safety, Inc.
3455 Ringsby Ct, Suite 103 Denver, CO 80216 Phone: (720) 722-3010
Specialized Engineering Solutions 10360 Ellison Circle Omaha, NE 68134 Phone: (402) 991-5520
OCMI, Inc.
909 Rose Avenue, Suite 400 North Bethesda, MD 20852
A u to d e s k D o c s
/1
-2
-1
A
E U p d a te
F ir e
A la rm S y s te m F t M e a d e /5
-2
-1
V
A F t M e a d e F
P L
S R
.r v t
/9
/2
:1
:5
P
M
FA003
FIRE ALARM CAMPUS
INTERCONNECTION PLAN
TGD GMP
1" = 160'-0"1
FIRE ALARM INTERCONNECTION SITE PLAN
PLAN
NORTH
TRUE
NORTH
1" = 160'-0"2
FIRE ALARM INTERCONNECTION SITE B160
Mark Revisions: Date:
DN
UP
F A
C P
TS AIM
W P
C
30 cdC
15 cd
C
15 cd
F
F
F
C
15 cd
C
15 cd
C
75 cd
C
15 cd
C
30 cd
C
30 cd c d c d
C
15 cd c d
P
15 cd 15 cd 15 cd
15 cd
15 cd
30 cd
15 cd c d c d
C
15 cd
F A
D C
C
15 cd
TS
TS
TS
TS
PS
PS
C
75 cd
F
AIM
AIM
AIM
AIM
AIM
AIM
F c d
C
15 cd
C
15 cd
C
15 cd
C
30 cd
C
30 cd
C
30 cd
OFFICE
OFFICE
OFFICE
OFFICE
OFFICE
104 OFFICE
OFFICE
CORRIDOR
C102
LOBBY
C101
STAIR
ST1
VESTIBULE
C100
OFFICE
OFFICE
114F
OFFICE
114E
OFFICE
114D
CORRIDOR
COPY ROOM
OFFICE
114A
OFFICE
114B
OFFICE
114C
WOMEN'S
RESTROOM
MEN'S
RESTROOM
BREAK ROOM
OFFICE
CUBICLES
OFFICES
OFFICE
CONFERENCE
ROOM
STORAGE
113A
PORCH
P1
CORRIDOR
C103
ELEC. CLOSET
107A
NO
EXIT
NO
EXIT
1. REFER TO SHEET FA001 FOR FIRE ALARM GENERAL NOTES.
FIRE ALARM GENERAL NOTES
TELEPHONE/ IT
CLOSET
TCB1
WORKOUT AREA
B105
STORAGE
HCB1
MECH. ROOM
B105A
ELEC. CLOSET
ECB1
RESTROOM
B104
CONFERENCE
ROOM
B100 -
B101
STORAGE
B102
STORAGE
B100A
UNUSED SPACE
B100A1
STORAGE
B103
STORAGE
B103A
STORAGE
B103B
CORRIDOR
CB100
STAIR
ST3
STORAGE STORAGE STORAGE
1. PROVIDE MONITOR MODULE AND TVSS SURGE SUPPRESSOR FOR POST
INDICATOR VALVE TAMPER SWITCH.
2. FIELD LOCATE NEW WEATHER RESISTANT HORN/STROBE ABOVE FIRE
DEPARTMENT CONNECTION, CLEAR OF VISIBLE OBSTRUCTIONS.
3. SURFACE MOUNT DEVICE CENTERED IN DECORATIVE METAL CEILING PANEL.
PAINT CONDUIT TO MATCH CEILING.
FIRE ALARM KEYNOTES X
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED:
BUILDINGS 40, 46, 48, 53, 65, 88, 89, 90, 91, 103, 147,
148, T144, T171, T296
NOT FULLY SPRINKLERED:
BUILDINGS 47, 50, 85, 87, 96, 120, 137, 160
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMP
321 5 6 7 8 9 10
Alesia Architecture P.C.
3705 North 200th Street Elkhorn, Nebraska 68022 Phone: (402) 291-6941
A on e ei gh th in ch o ne f oo t th re e in ch es o ne f oo t
6" on e an d on e ha lf in ch es o ne f oo t on e in ch o ne f oo t
6" 6" th re e qu ar te rs in ch o ne f oo t on e ha lf in ch o ne f oo t th re e ei gh th s in ch o ne f oo t on e qu ar te r in ch o ne f oo t
FINAL CONSTRUCTION
DOCUMENTS
UPGRADE FIRE ALARM
SYSTEM (FM)
568-24-106
FT MEADE, SD
A
B
C
D
E
F
14MAR2025
Incandescence Life Safety, Inc.
3455 Ringsby Ct, Suite 103 Denver, CO 80216 Phone: (720) 722-3010
Specialized Engineering Solutions 10360 Ellison Circle Omaha, NE 68134 Phone: (402) 991-5520
OCMI, Inc.
909 Rose Avenue, Suite 400 North Bethesda, MD 20852
A u to d e s k D o c s
/1
-2
-1
A
E U p d a te
F ir e
A la rm S y s te m F t M e a d e /5
-2
-1
V
A F t M e a d e F
P L
S R
.r v t
/9
/2
:1
:5
P
M
53-FA201
BUILDING 53 - FIRE ALARM PLAN
TGD GMP
1/8" = 1'-0"2
B53 FIRE ALARM PLAN - FIRST FLOOR
PLAN
NORTH
TRUE
NORTH
1/8" = 1'-0"1
B53 FIRE ALARM PLAN - BASEMENT
08' 8' 16'4'
SCALE: 1/8" = 1'-0"
BUILDING 53 - CODE SUMMARY
REHABILITATION WORK:
EXTENSIVE MODIFICATION (NFPA 101 §43.5.2)
OCCUPANCY CLASSIFICATION:
PER VAFPDM OCCUPANCY CLASSIFICATION DETERMINED IN ACCORDANCE WITH
NFPA 101
BASEMENT: STORAGE (CHAPTER 42)
FIRST FLOOR: NEW BUSINESS (CHAPTER 38) & STORAGE (NFPA 101 CHAPTER 42)
SECOND FLOOR: NEW BUSINESS (CHAPTER 38)
ATTIC: INDUSTRIAL (NFPA 101 CHAPTER 40)
OCCUPANCY SEPARATION:
MIXED OCCUPANCY
CONSTRUCTION TYPE:
TYPE V-B (IBC CHAPTER 6) - NOT AFFECTED BY THIS SCOPE OF WORK
SEPARATION REQUIREMENTS:
FLOORS SEPARATING STORIES SHALL BE CONSTRUCTED AS SMOKE BARRIERS
IN ACCORDANCE WITH NFPA 101 §8.6.1.THROUGH PENETRATIONS MUST
RESTRICT THE PASSAGE OF SMOKE.
MEANS OF EGRESS:
NOT AFFECTED BY THIS SCOPE OF WORK
FIRE SUPPRESSION:
FULLY SPRINKLER PROTECTED (NOT AFFECTED BY THIS SCOPE OF WORK)
FIRE ALARM:
NEW FIRE ALARM SYSTEM (USER ELECTED)
THIS BUILDING WILL UTILIZE AN EMERGENCY VOICE COMMUNICATION SYSTEM.
SURFACE MOUNTED DEVICES WITH EXPOSED CONDUIT EXCEPT IN CONFERENCE B100 WHERE CONDUIT SHOULD BE CONCEALED IF POSSIBLE AND
PAINTED TO MATCH EXISTING SURFACE IF EXPOSED
IN AREAS WITH DECORATIVE METAL TILE CEILING, CONDUIT SHOULD BE SURFACE MOUNTED AND PAINTED TO MATCH SURFACE WITH DEVICE CENTERED IN THE TILE. IN ALL OTHER AREAS, CONDUIT SHOULD BE CONCEALED AND DEVICES FLUSH MOUNTED
Mark Revisions: Date:
c d
C
30 cd
F
C
30 cd
C
15 cd
C
15 cd
F
C
15 cd
C
30 cd
C
15 cd
C
15 cd
15 cd
15 cd
C
15 cd
C
15 cd
F
15 cd
C
15 cd
C
15 cd
C
15 cd
C
15 cd
C
15 cd
C
15 cd
CM
CMCM
F
75 cd c d
OFFICE
CUBICLES
OFFICE
201AOFFICE
OFFICE
STORAGE
OFFICE
OFFICE
206 OFFICE
OFFICE
WOMEN'S
RESTROOM
MEN'S
RESTROOM
BREAK ROOM
211OFFICE
OFFICE
OFFICE
OFFICE
OFFICE
OFFICE
CORRIDOR
C203
CORRIDOR
C200
STAIR
ST2
OFFICE
CUBICLES
OFFICE
200A
OFFICE
200B
OFFICE
200C
CORRIDOR
C202
CORRIDOR
C201
ELEC. CLOSET
209A
1. REFER TO SHEET FA001 FOR FIRE ALARM GENERAL NOTES.
FIRE ALARM GENERAL NOTES
ATTIC
MECH. ROOM
MECH. ROOM
ATTIC
MECH. ROOM
FIRE ALARM CONTROL
PANEL(FACP)
LOBBY (C101) WITH
VOICE COMMAND & AMP.
BATTERIES
FIRST FLOOR SIGNALING
LINE CIRCUIT (SLC) -TYPICAL
UNDERGROUND FIRE ALARM
NETWORK IN FROM PREVIOUS NODE
UNDERGROUND FIRE ALARM NETWORK
OUT TO NEXT NODE
(X1) (X5)
(X6)
FIRST FLOOR
SECOND FLOOR
AIM
F P
BASEMENT
(X2)
F
BASEMENT SIGNALING
LINE CIRCUIT (SLC) -
TYPICAL
BASEMENT
NOTIFICATION CIRCUIT
(NAC) - PUBLIC MODE
(X3)
F
SECOND FLOOR SIGNALING
LINE CIRCUIT (SLC) -TYPICAL
120 VAC
FDC
FS
EXTERIOR
HORN/STROBE AT FDC
WP
C
(X11)
FIRST FLOOR
NOTIFICATION CIRCUIT
(NAC) - PUBLIC MODE
(X10)
C
SECOND FLOOR
NOTIFICATION CIRCUIT
(NAC) - PUBLIC MODE
EOL
C
EOL
(X5)
(X7)
EOL
EOL
(X1)
(X7)
(X1)
AIM
(X1)
EOL
EOL
(X1)(X2)
ATTIC
(X2) (X1)
F
ATTIC SIGNALING LINE
CIRCUIT (SLC) -TYPICAL
(X3)
CM
(X3)
(X1)
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED:
BUILDINGS 40, 46, 48, 53, 65, 88, 89, 90, 91, 103, 147,
148, T144, T171, T296
NOT FULLY SPRINKLERED:
BUILDINGS 47, 50, 85, 87, 96, 120, 137, 160
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMP
321 5 6 7 8 9 10
Alesia Architecture P.C.
3705 North 200th Street Elkhorn, Nebraska 68022 Phone: (402) 291-6941
A on e ei gh th in ch o ne f oo t th re e in ch es o ne f oo t
6" on e an d on e ha lf in ch es o ne f oo t on e in ch o ne f oo t
6" 6" th re e qu ar te rs in ch o ne f oo t on e ha lf in ch o ne f oo t th re e ei gh th s in ch o ne f oo t on e qu ar te r in ch o ne f oo t
FINAL CONSTRUCTION
DOCUMENTS
UPGRADE FIRE ALARM
SYSTEM (FM)
568-24-106
FT MEADE, SD
A
B
C
D
E
F
14MAR2025
Incandescence Life Safety, Inc.
3455 Ringsby Ct, Suite 103 Denver, CO 80216 Phone: (720) 722-3010
Specialized Engineering Solutions 10360 Ellison Circle Omaha, NE 68134 Phone: (402) 991-5520
OCMI, Inc.
909 Rose Avenue, Suite 400 North Bethesda, MD 20852
A u to d e s k D o c s
/1
-2
-1
A
E U p d a te
F ir e
A la rm S y s te m F t M e a d e /5
-2
-1
V
A F t M e a d e F
P L
S R
.r v t
/9
/2
:1
:5
P
M
53-FA202
BUILDING 53 - FIRE ALARM PLAN
TGD GMP
1/8" = 1'-0"1
B53 FIRE ALARM PLAN - SECOND FLOOR
PLAN
NORTH
TRUE
NORTH
1/8" = 1'-0"2
B53 FIRE ALARM PLAN - ATTIC
08' 8' 16'4'
SCALE: 1/8" = 1'-0"
1/2" = 1'-0"3
FIRE ALARM RISER DIAGRAM - BUILDING 53
THIS BUILDING WILL UTILIZE AN EMERGENCY VOICE COMMUNICATION SYSTEM.
IN AREAS WITH A.C.T., CONDUIT SHOULD BE CONCEALED AND DEVICES FLUSH MOUNTED
RED SURFACE MOUNT CONDUIT AND DEVICES IN THIS UNFINISHED SPACE
NOT TO SCALE
Mark Revisions: Date:
1 ADDENDUM 1 09APR26
04/09/26
VHAFTMSeideT Polygon
VHAFTMSeideT Text Box (X12)
VHAFTMSeideT Text Box (X16)
VHAFTMSeideT Polygon
FACP
F
F
F
F
F P
SB
SB
SB
SB
SB
SB
15 cd15 cd
15 cd
15 cd
15 cd
15 cd
SB
SB
WP
15 cd
30 cd
30 cd
AIM
FADC
PS
PS
F
F
C M
C
30 cd
C
30 cd
C
75 cd
15 cd
AIM
AIM
15 cd
CO
15 cd15 cd15 c d
15 cd
15 cd
SB
SB
SB
SB
15 cd c d
SB SB SB
SB SB SB
SB
SB
SB
SB
SB
F
F
F
F
PORCH
P1
CORRIDOR
C101
DAYROOM /
KITCHEN
KITCHEN / LIVING
AREA
BEDROOM #6
100A
BATHROOM
100A1
BEDROOM #3
102A
CLOSET
100A2
STAIR
ST1A
VESTIBULE
C100
VESTIBULE
BEDROOM #7
BATHROOM
STAIR
ST1C
RECEPTION
CLOSET
106A
PORCH / MUD
ROOM
105A
BEDROOM #8
CLEAN LINEN
107A
BEDROOM #4
HALLWAY
DAYROOM
CLOSET
109A
VESTIBULE
C102
CORRIDOR
C102A
STAIR
ST2A
BATHROOM
110A2
BEDROOM #5
110A
KITCHEN / LIVING
AREA
CORRIDOR
C100A
VESTIBULE
C101
CLOSET
103A
1. REFER TO SHEET FA001 FOR FIRE ALARM GENERAL NOTES.
FIRE ALARM GENERAL NOTES
STORAGE
B106C
STORAGE /
WORKSHOP
B106
STAIR
STBB
B101A
STORAGE
B103
STORAGE
B102
CRAWL SPACE
B102A
MECHANICAL
ROOM
B101
STORAGE
B107
LAUNDRY
B100
STAIR
STBA
STAIR
STBC
STORAGE
PORCH
P2
KITCHEN / LIVING
AREA
BEDROOM #9
200B
CLOSET
200B2
BATHROOM
200B3
CORRIDOR
C200
KITCHEN / LIVING
AREA
BEDROOM #13
KITCHEN / LIVING
AREA
BEDROOM #11
211B
CORRIDOR
C201
BEDROOM #10
201B
BATHROOM
201B2CLOSET
201B1
CLOSET
211B2
CORRIDOR
C202
BATHROOM
211B3
BATHROOM
212BCLOSET
212B2
KITC…
This is the start of the file's text. The full file is on GovTribe.