36C26319B0009-004.pdf
PDF 2 MB Posted
- Solicitation number
- 36C26319B0009
About this file
36C26319B0009 S02_Drawings.pdf
View the file
Other files
| File | Type | Posted |
|---|---|---|
| 36C26319C0174-000.docx | DOCX document | |
| 36C26319B0009-A00004001.pdf | ||
| 36C26319B0009-A00004000.docx | DOCX document | |
| 36C26319B0009-A00003001.pdf | ||
| 36C26319B0009-A00003000.docx | DOCX document | |
| 36C26319B0009-A00002000.docx | DOCX document | |
| 36C26319B0009-A00002001.pdf | ||
| 36C26319B0009-006.docx | DOCX document | |
| 36C26319B0009-005.docx | DOCX document | |
| 36C26319B0009-A00001000.docx | DOCX document | |
| 36C26319B0009-002.pdf | ||
| 36C26319B0009-001.docx | DOCX document | |
| 36C26319B0009-003.pdf | ||
| 36C26319B0009-000.docx | DOCX document |
Show all 14
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
F i l e
P a t h
CONSTRUCTION
DOCUMENTS
Robert Venner
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
POC: Bob Ryckman
Mechanical, Electrical, Plumbing:
4940 N 118th Street Omaha, NE 68164 Phone: (402) 491-4144
Grand Island, Nebraska
Project Director
Revisions: Date: POC: Ron Feuerbach
Architectural:
3705 N 200th Street Omaha, NE 68022 Phone: (402) 291-6941
Calvin L. Hinz Architects, P.C.
Install Air Cooled Chiller -Grand Island 636A4-18-113
APRIL 2, 2019
4/2/19 CS
DATE:APRIL 2, 2019
CONSTRUCTION DOCUMENTS
PROJECT NO.: 18333
Drawing Index
SP1SITE PLAN
NEBRASKA, WESTERN IOWA HEALTH CARE SYSTEM
AIR COOLED CHILLER ADDITION
2201 N BROADWELL AVE
GRAND ISLAND, NE 68803
M1FLOOR PLAN - MECHANICAL
M2MECHANICAL DETAILS AND SCHEDULES
E1FLOOR PLAN - ELECTRICAL
COVER SHEET
CSCOVER SHEET
AutoCAD SHX Text E-5195
AutoCAD SHX Text
FEUERBACH
AutoCAD SHX Text
RONALD
TR
AN
SF
OR
ME
R
TR
AN
SF
OR
ME
R
CHILLER
SCREEN WALL
MANUFACTURERS
RECOMMENDED
SERVICE
CLEARANCES
EXISTING MANHOLE
EXISTING CHILLER PLANT
EXISTING MANHOLE
NEW AIR COOLED
CHILLER
CH-4
CONCRETE PAD
SEE DETAIL 3 ON SHEET M2
6 #6 REBARS VERT. WITH
#4 REBARS 12" O.C. HORIZ.
LOUVERED SCREEN WALL POST
N
T S
SCREEN WALL FOOTING DETAIL
NO SCALE
SP-1
CONCRETE BASE
ROUND POURED18"
ANCHOR BOLTS FURNISHED
WITH POLE
3/4" CHAMFER
POST CONNECTION TO PIER
BY SCREEN WALL SUPPLIER
96 ' TALL LOUVERED SCREEN FENCING
3/8" EXPANSION JOINT
WITH SEALANT
FLOOR ELEVATION = 1866.5'
ENCLOSURE PAD
ELEVATION = 1866.5'
PROVIDE SCREENWALL POSTS AS
REQUIRED BY MANUFACTURER
SEE DETAIL 1 ON SHEET SP-1
SEE SPECIFICATION SECTION 323140
QUANTITY AS REQUIRED BY MANUFACTURER
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
F i t h
CONSTRUCTION
DOCUMENTS
Robert Venner
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
POC: Bob Ryckman
Mechanical, Electrical, Plumbing:
4940 N 118th Street Omaha, NE 68164 Phone: (402) 491-4144
Grand Island, Nebraska
Project Director
Revisions: Date: POC: Ron Feuerbach
Architectural:
3705 N 200th Street Omaha, NE 68022 Phone: (402) 291-6941
Calvin L. Hinz Architects, P.C.
Install Air Cooled Chiller -Grand Island 636A4-18-113
APRIL 2, 2019
4/2/19 SP1
SITE PLAN
1" = 10'-0"
N
AutoCAD SHX Text
6 SPACES
AutoCAD SHX Text
7 SPACES
AutoCAD SHX Text
27 SPACES
AutoCAD SHX Text
22 SPACES
AutoCAD SHX Text
BOLLARD SEE - 5F (TYP)
AutoCAD SHX Text
CONCRETE PAD
AutoCAD SHX Text
LINE OF COOLING TOWER PLATFORM ABOVE
AutoCAD SHX Text E-5195
AutoCAD SHX Text
FEUERBACH
ELECTRICAL
ROOM
CHILLER
PLANT
CORRIDOR
METER ROOM
VFD-1 VFD-2 VFD-3
6" CWR
ISOLATION VALVE
EVP
REFRIGERANT
PIPING
CHILLER SUPPORT FOOTING SEE
EXISTING CWS
EXISTING CWS
DROP PIPE DOWN TO 12"
ABOVE GRADE AND SUPPORT
FROM WALL EVERY 6'-0"
SLEEVE FOR PIPING. SEAL
WEATHER TIGHT
STRAINER
SUPPORT EVAPORATOR
FROM STRUCTURE
SEE DETIAL
M2
28'-0"
CHECK VALVE
MOTORIZED 2-WAY VALVE
6" CWS
CHILLER SCREEN WALL
CH-4
SEE DETAIL
M2
FOR CHILLER PIPING DETAIL
M2
ISOLATION VALVE
(TYPICAL)
EXISTING CHILLED WATER
PIPING SERVING CHILLERS
SEE DETIAL
M2
MANUFACTURER RECOMMENDED
SERVICE CLEARANCES
1'-4" WIDE x 4'-0" DEEP
FOOTING, ALL SIDES OF
CHILLER PAD
40' - 6"
5" THICK CONCRETE SLAB
TO LIMITS OF SCREEN WALL
5" THICK CONCRETE SLAB
TO LIMITS OF SCREEN WALL
M2
MECHANICAL GENERAL NOTES
MECHANICAL FLAG NOTES
1. DO NOT ROUTE DUCTWORK, PIPING OR LOCATE EQUIPMENT ABOVE ELECTRICAL PANELS. MAINTAIN ALL
CODE REQUIRED CLEARANCES.
3. FIELD VERIFY ALL EXISTING CONDITIONS PRIOR TO NEW WORK. MECHANICAL CONTRACTOR SHALL BE
RESPONSIBLE FOR ADJUSTING PIPING AS NECESSARY TO AVOID CONFLICTS WITH EXISTING
STRUCTURE .
2. ALL ITEMS SHOWN LIGHT OR INDICATED ON PLAN AS (E) ARE EXISTING.
ALL ITEMS SHOWN DARK ARE NEW. NOT ALL MECHANICAL ITEMS ARE SHOWN.
INSTALL VFD IN ACCESSIBLE LOCATION. MAINTAIN 36" CLEARANCE IN FRONT OF
VFD. COORDINATE POWER WIRING WITH ELECTRICAL CONTRACTOR.
CONNECT NEW PIPE TO EXISTING. VERIFY SIZE AND LOCATION OF EXISTING.
MAINTAIN MANUFACTURER'S REQUIRED CLEARANCES.
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
F i t h
CONSTRUCTION
DOCUMENTS
Robert Venner
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
POC: Bob Ryckman
Mechanical, Electrical, Plumbing:
4940 N 118th Street Omaha, NE 68164 Phone: (402) 491-4144
Grand Island, Nebraska
Project Director
Revisions: Date: POC: Ron Feuerbach
Architectural:
3705 N 200th Street Omaha, NE 68022 Phone: (402) 291-6941
Calvin L. Hinz Architects, P.C.
Install Air Cooled Chiller -Grand Island 636A4-18-113
APRIL 2, 2019
4/2/19
FLOOR PLAN - MECHANICAL
1/4" = 1'-0"
M1
N
FLOOR PLAN - MECHANICAL
AutoCAD SHX Text
DN
AutoCAD SHX Text 1 1/4"
AutoCAD SHX Text
AIR
AutoCAD SHX Text
SEP.
AutoCAD SHX Text
DHW
AutoCAD SHX Text 1 1/4"
AutoCAD SHX Text
AV
AutoCAD SHX Text
PH
AutoCAD SHX Text
IA
AutoCAD SHX Text
IA
AutoCAD SHX Text E-5195
AutoCAD SHX Text
FEUERBACH
AIR COOLED CHILLER SCHEDULE
REMARKS
ELECTRICAL
REMARKS
MAXIMUM FUSE SIZE (AMPS)
PHASE
VOLTS
GENERAL
WATER
MODEL NUMBER
MAXIMUM WEIGHT (LBS.)
MAXIMUM SIZE (LxWxH) (IN.)
WATER FLOW (GPM)
ENTERING WATER TEMPERATURE (ºF)
CONFIGURATION
SERVES
MANUFACTURER
PLAN TAG
CHILLED
-SORS
COMPRES-
LEAVING WATER TEMPERATURE (ºF)
PRESSURE DROP (FEET)
HP (EACH)
TYPE
QUANTITY
MIN. STEPS UNLOADING
ACCESSORIES
ANCE DATA
PERFORM-
MAXIMUM DPLV
MINIMUM EER
MAXIMUM APLV
NOMINAL TONNAGE
REFRIGERANT
MINIMUM CIRCUIT AMPACITY
CH-4
DAIKIN
AGZ241E
EVP
AIR COOLED
328 x 88 x 99
R410A
(1)
54.0
44.0
10.1
SCROLL
10.24
16.43
525.5
(2) (3) (4)
REMARKS
ELECTRICAL
VARIABLE FREQUENCY DRIVE SCHEDULE
GENERAL
REMARKS
VOLTAGE
CONNECTED MOTOR HP
MOTOR TYPE
PHASE
MAX. DRIVE OUTPUT CURRENT (AMPS)
SERVES
LOCATION
MARK
VFD-1
P-1
SEE PLANS
14.5
ODP
1. VARIABLE FREQUENCY DRIVES SHALL BE SUITABLE FOR HVAC APPLICATIONS. DRIVE SHALL HAVE
STANDARD FEATURES PLUS FOLLOWING: DISCONNECT, EMI, RFI FILTERS, INPUT AC LINE REACTORS AND
AUTOMATIC RESET UPON LOSS OF POWER. SEE SPECIFICATION SECTION 230960 "VARIABLE FREQUENCY
DRIVES".
2. VARIABLE FREQUENCY DRIVE SHALL BE FURNISHED BY THE MECHANICAL CONTROL CONTRACTOR AND
INSTALLED BY THE ELECTRICAL CONTRACTOR.
3. PROVIDE DRIVES WITH BUILT-IN COMMUNICATION TO ALLOW FOR INDICATED SEQUENCE OF OPERATION.
COORDINATE WITH TEMPERATURE CONTROL CONTRACTOR.
BELOW
SEE
6" CONCRETE SLAB WITH #4 AT 12" ON CENTER EACH WAY
S L A
B
T
O
E
X T
E N
D
T
O
L I M
I T
S
O
F
S C
R E
E N
W
A L L
16"x48" TRENCH FOOTINGS (TYPICAL ALL SIDES)
6" CONCRETE SLAB ELEVATION 1865.00'
#4 AT 12" ON CENTER EACH WAY
1'-4" 1'-4"
PAD TO EXTEND TO DIMENSIONS
OF CHILLER BASE EACH DIRECTION.
3" CLEAR
3" CLEAR
#4 AT 12" ON CENTER WITH 2'-0" LEGS
(TYPICAL ALL SIDES)
TRENCH FOOTING WITH
2-#5 TOP AND BOTTOM AND
#4 TIES AT 48" ON CENTER
(TYPICAL ALL SIDES)
1" CLEAR
6" VOID FORM
NEW CONCRETE PAD FOOTING TO BE INSTALLED ADJACENT
TO EXISTING BUILDING WALL FOOTING. FIELD VERIFY EXACT
SIZE, LOCATION, AND DEPTH OF EXISTING FOOTING.
CHILLER PAD SECTION
NO SCALE
M2
PIPING DETAIL FOR BRAZED PLATE HEAT EXCHANGER (EVP)
NO SCALE
M2
MECHANICAL SYMBOLS
SYMBOLSYMBOL DESCRIPTION
TYPICAL PIPING
DESCRIPTION
ELBOW DN / ELBOW UP
PIPE TEE / PIPE ELBOW
DTD
GATE VALVE
ISOLATION VALVE (BALL OR BUTTERFLY)
BALANCING VALVE
GLOBE VALVE
PRESSURE/TEMPERATURE TEST PORT
UNION
STRAINER WITH BLOWDOWN
CHECK VALVE (ARROW INDICATES FLOW)
AUTOMATIC CONTROL VALVE TWO-WAY / THREE WAY
PRESSURE REGULATING VALVE (PRV)
PRESSURE GAUGE
THERMOMETER
P.T.T.
CHILLED WATER SUPPLY PIPING
HOT WATER RETURN PIPING
CONDENSER WATER RETURN PIPING
CHILLED WATER RETURN PIPING
CONDENSER WATER SUPPLY PIPING
HOT WATER SUPPLY PIPING
HYDRONIC HVAC PIPING
HWS
HWR
CWR
CWS
CR
CS
COIL CONDENSATE DRAIN (SLOPE TO DRAIN)CD
AIR VENT
GWR
GWS
HPLR
HPLS
GLYCOL WATER RETURN PIPING
GLYCOL WATER SUPPLY PIPING
HEAT PUMP LOOP RETURN PIPING
HEAT PUMP LOOP PIPING SUPPLY PIPING
SOLENOID VALVE
THERMOSTATIC EXPANSION VALVE (TXV)
SIGHT GLASS
REFIGERATION PIPING
REFRIGERANT HOT GAS DISCHARGE LINE
REFRIGERANT SUCTION LINE
REFIGERANT LIQUID LINE
RS
RL
RD
INLET
OUTLET
AIR VENT
DRAIN
FLOW SWITCH
FLEXIBLE CONNECTION
FLEXIBLE CONNECTION
EVAPORATOR
(EVP)
FUSIBLE PLUG
HGBP
VALVE
SCHRADER
VALVE
FILTER DRIER
SCHRADER
VALVE
INLET
OUTLET
6" CWR
6" CWS
LIQUID
PIPING
SUCTION
PIPING
1. PROVIDE WITH REMOTE BRAZED PLATE EVAPORATOR MODEL AGZ241 (EVP).
2. PROVIDE WITH SINGLE POINT POWER CONNECTION WITH INTEGRAL FACTORY DISCONNECT.
3. PROVIDE WITH BACnet INTERFACE FOR CONNECTION TO BUILDING BAS.
4. PROVIDE FLOW SWITCH FOR EVAPORATOR PIPING CONNECTION.
2 5/8"
1 5/8"
AIR
COOLED
CHILLER
CH-4
EVP
P-1 P-2 P-3
DP
DP
DP
EXISTING
CHILLED WATER
PUMP P-1
EXISTING
CHILLED WATER
PUMP P-2
EXISTING
CHILLED WATER
PUMP P-3
8" CWR
8" CWR
8" CWR
8" CWR8" CWR 10" CWR 10" CWR
10" CWS
8" BYPASS
10" CWS
NEW 6" CWR
NEW 6" CWR
TO SECONDARY CHILLED WATER PUMPS
FROM BUILDING
CHILLED WATER PIPING DETAIL
NO SCALE
M2
FLEX CONNECTION (TYP)
CONNECT NEW TO EXISTING
CONNECT NEW TO EXISTING
(TWO REQUIRED)
(TWO REQUIRED)
ISOLATION VALVE (TYP)
EXPANSION VALVE (TWO REQUIRED)
SITE GLASS
P.T.T. (TYP)
STRAINER
BLOW DOWN VALVE
HOSE END CONNECTION
THERMOMETER (TYP)
ISOLATION VALVE (TYP)
REDUCER (TYP)
EXISTING PRESSURE GAUGE (TYP)
EXISTING DIFFERENTIAL
PRESSURE SENSOR (TYP)
EXISTING ROOF ASSEMBLY
ISOLATION VALVE (TYP)
STRAINER
TWO-POSITION AUTOMATIC VALVE
CHECK VALVE
1/2"
WELDED PIPE CONNECTIONS ARE NOT ALLOWED
BETWEEN STRAINER AND EVAPORATOR.
VFD-2
P-2
SEE PLANS
14.5
ODP
VFD-3
P-3
SEE PLANS
14.5
ODP
TEMPERATURE CONTROL SEQUENCE
A. GENERAL: Temperature control work shall be performed by the building controls contractor
Johnson Controls Inc. Modify the existing DDC system as required to provide the specified sequence of control. Provide all sensors, switches, relays, electrical wiring , panels, and programming etc. required for a complete operating system. Submit shop drawings with temperature control wiring diagram, points list, and sequences of control.
B. Sequence of Control - CH-4:
1. CHILLER CH-4 is an air cooled chiller to be used in shoulder seasons to generate chilled water for building cooling.
2. START UP: When enabled through the DDC system based on operator selection, the chiller iso;ation valve shall open and the designated lead primary chilled water pump shall ramp to the set speed through the pump VFD and run continuously to maintain 530 GPM
(differential pressure of 4.5 psig) through the chiller evaporator. Once flow status has been confirmed (DI point) chiller CH-4 shall be enabled.
3. Chilled Water Temperature Control: Once enabled the chiller leaving water temperature shall be controlled through the internal chiller controls to maintain a leaving water temperature of 45 degrees F.
4. The existing chiller sequences for CH-1, 2 and 3 shall remain as programmed.
C. BAS Shall Generate the Following Alarms:
· Loss of CH-4 status is detected
· Loss of chilled water flow through the evaporator is detected
· Any chiller fault is detected.
D. Minimum Points List: Provide the following minimum points for chiller CH-4 as well as additional points required to provide the above sequence of control:
· CH-4 chiller enable (BO)
· CH-4 chiller status (BI)
· Chiller staging (AO)
· Chiller evaporator differential pressure (AI)
· Chiller evaporator water isolation valve (BO)
· Chiller chilled water supply temperature (AI)
· Chiller chilled water return temperature (AI)
· Pumps P-1, P-2, and P-3 speed (AO)
AIR
COOLED
CHILLER
CH-4
EVP-1
P-1 P-2 P-3
DP
DP
DP
EXISTING
CHILLED WATER
PUMP P-1
EXISTING
CHILLED WATER
PUMP P-2
EXISTING
CHILLED WATER
PUMP P-3
8" CWR
8" CWR
8" CWR
8" CWR8" CWR 10" CWR 10"
10" CWS
8" BYPASS
10"
NEW 6" CWR
NEW 6" CWR
TO SECONDARY CHILLED WATER PUMPS
FROM BUILDING
CHILLLER CONTROL SCHEMATIC
NO SCALE
M2
EXISTING PRESSURE GAUGE (TYP)
EXISTING DIFFERENTIAL
PRESSURE SENSOR (TYP)
TWO-POSITION AUTOMATIC VALVE
VFD-1 VFD-2 VFD-3
BI BO BO
NOTE 7
NOTE 8
NOTE 9
AO T
OPAO
AO
AI
AO
AI
AO
AI
NOTE 2
NOTE 3
NOTE 2
NOTE 3
NOTE 2
NOTE 3
NOTE 4
NOTE 5
AO
T
NOTE 6
NOTES:
1. ALL EXISTING CONTROL POINT AND SEQUENCES FOR PUMPS P-1, P-2, AND P-3 TO
REMAIN
2. VFD CONTROL INPUT 0-10 VOLTS
3. VFD FAULT OUTPUT
4. CHILLED WATER RETURN TEMPERATURE OUTPUT
5. EVAPORATOR DIFFERENTIAL PRESSURE OUTPUT
6. CHILLED WATER SUPPLY TEMPERATURE OUTPUT
7. CHILLER ENABLE INPUT
8. CHILLER STATUS OUTPUT
9. CHILLER FAULT OUTPUT
EVAPORATOR SUPPORT DETAIL
NO SCALE
M2
EVAPORATOR
OPERATING
WEIGHT 1000 LBS
EXISTING BAR JOIST (TYP)
SPAN MINIMUM 3 BAR JOISTS
DOUBLE NUT HANGER ROD
" THREADED ROD
3" x 3" x
" ANGLE IRON SUPPORT
DOUBLE NUT HANGER ROD (TYP)
3" x 3" x
" ANGLE IRON SUPPORT
TWO SUPPORTS REQUIRED (FRONT AND BACK)
SLAB TO EXTEND TO LIMITS OF SCREEN
WALL ENCLOSURE 40' - 6"
WELD OR CLAMP L3x3 ANGLES
TO JOIST BOTTOM CHORDS
CHILLER PAD OUTLINE WITHIN SCREENWALL ENCLOSURE
1/2"
PRESSURE GAUGE
NOTE: NEW CHILLED WATR COONECTIONS TO EXISITNG
PIPING MUST BE HOT TAPPED DURING OFF HOURS.
NOTES:
1. MAINTAIN MANUFCATURER
RECOMMENDED CLEARANCES.
SIZE AND INSTALL REFRIGERANT PIPING PER
MANUFACTURER RECOMMENDATIONS.
SIZE AND INSTALL REFRIGERANT PIPING PER
MANUFACTURER RECOMMENDATIONS.
5" THICK CONCRETE SLAB
TO LIMITS OF SCREEN WALL
5" THICK CONCRETE SLAB
TO EXISTING SLAB
PROVIDE FILL AS REQUIRED
#4 BENT BAR AT 18 ON CENTER
2 #4 BAR
ENCLOSURE PAD EDGE SECTION
NO SCALE
M2
SLAB TO EXTEND TO LIMITS OF
SCREEN WALL ENCLOSURE
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
F i t h
CONSTRUCTION
DOCUMENTS
Robert Venner
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
POC: Bob Ryckman
Mechanical, Electrical, Plumbing:
4940 N 118th Street Omaha, NE 68164 Phone: (402) 491-4144
Grand Island, Nebraska
Project Director
Revisions: Date: POC: Ron Feuerbach
Architectural:
3705 N 200th Street Omaha, NE 68022 Phone: (402) 291-6941
Calvin L. Hinz Architects, P.C.
Install Air Cooled Chiller -Grand Island 636A4-18-113
APRIL 2, 2019
4/2/19 M2
MECHANICAL DETAILS
AND SCHEDULES
AutoCAD SHX Text E-5195
AutoCAD SHX Text
FEUERBACH