Addendum 001 Reference Only Drawings.pdf

PDF 8 MB Posted

Attached to
Z2DA-- Proj# 501-22-101 Upgrade Building 80 for COVID-19 VA New Mexico
Solicitation number
36C26224B0012
Issued by

About this file

This document appears to be an Addendum containing reference drawing details for a federal contract opportunity related to a Medical Oxygen Skid. The drawings provide product specifications, part numbers, and dimensional details for different size Medical Oxygen Skids. Key information includes:

The drawings include 8 different models of Medical Oxygen Skids, ranging from 4 to 16 high pressure oxygen bottles. The part numbers, tank pressures, and flow rates are provided for each model. Overall dimensions, weight, and material details are also specified. The drawings include schematic diagrams showing the component layout and piping configuration for the skids. Additional requirements are noted, such as the use of oxygen-cleaned parts, brazing by certified employees, and optional alarm panels.

View the file

Other files

Show all 21

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

FRONT VIEW

TOP VIEW

VIEW A-A

DETAIL A

A A

DETAIL B

SEE SHEET 2

A

D-20810866

APPVREV ECR REVISION DESCRIPTION BY DATE

# DESIGNATES A NOTE REFERENCE.

MAT'L

FINISH P/N

SEE TABLE

APPV'D DATE

JNB 2/2/2015

D-20810866

SEE B.O.M.

F

1/8"

N/A N/A

TABLE 1 - MEDICAL SKID PART NUMBERS AND SET POINTS

PART NUMBER DESCRIPTION RESERVE IN USE PS2 RESERVE LOW PS1 PRIMARY REG-R2 RESERVE REG -R1 TANK PSI

20810864 MEDICAL MB 4 BOTTLE O2 SKID 80 PSIG (PI-4) 1000 PSIG (PI-2) 50 - 55 PSIG (PI-3) 65 PSIG (PI-1) 125 20810865 MEDICAL MB 6 BOTTLE O2 SKID 80 PSIG (PI-4) 1000 PSIG (PI-2) 50 - 55 PSIG (PI-3) 65 PSIG (PI-1) 125 20810866 MEDICAL MB 8 BOTTLE O2 SKID 80 PSIG (PI-4) 1000 PSIG (PI-2) 50 - 55 PSIG (PI-3) 65 PSIG (PI-1) 125 20891908 MEDICAL MB 12 BOTTLE O2 SKID 80 PSIG (PI-4) 1000 PSIG (PI-2) 50 - 55 PSIG (PI-3) 65 PSIG (PI-1) 125 20891909 MEDICAL MB 16 BOTTLE O2 SKID 80 PSIG (PI-4) 1000 PSIG (PI-2) 50 - 55 PSIG (PI-3) 65 PSIG (PI-1) 125 20810867 MEDICAL MB 4 BOTTLE N2 SKID 180 PSIG (PI-4) 1000 PSIG (PI-2) 170 - 175 PSIG (PI-3) 185 PSIG (PI-1) 220 20810868 MEDICAL MB 6 BOTTLE N2 SKID 180 PSIG (PI-4) 1000 PSIG (PI-2) 170 - 175 PSIG (PI-3) 185 PSIG (PI-1) 220 20810869 MEDICAL MB 8 BOTTLE N2 SKID 180 PSIG (PI-4) 1000 PSIG (PI-2) 170 - 175 PSIG (PI-3) 185 PSIG (PI-1) 220 20894778 MEDICAL MB 12 BOTTLE N2 SKID 180 PSIG (PI-4) 1000 PSIG (PI-2) 170 - 175 PSIG (PI-3) 185 PSIG (PI-1) 220 20894774 MEDICAL MB 16 BOTTLE N2 SKID 180 PSIG (PI-4) 1000 PSIG (PI-2) 170 - 175 PSIG (PI-3) 185 PSIG (PI-1) 220 20840682 SKID MMB 8HPBU HYPERBARIC O2 80 PSIG (PI-4) 1000 PSIG (PI-2) 65 PSIG (PI-3) 75 PSIG (PI-1) 125 20987482 SKID MMB 4HPBU HYPERBARIC 02 80PSIG (PI-4) 1000 PSIG (PI-2) 65 PSIG (PI-3) 75 PSIG (PI-1) 125

5/8 3132 1/4

93 5/8

NOTE:

SKID IS DESIGNED FOR CHART

PERMA-CYL SIZES 1000-3000 LITER

SEE CHART SPEC DRAWINGS FOR DETAILS

NOTES:

1. WEIGHT OF SKID; 1,100 LBS

2. ALL PIPING, VALVES, FITTINGS TO BE CLEANED FOR OXYGEN SERVICE

3. ALL BRAZING TO BE COMPLETED ONLY WITH 56% SILVER SOLDER

4. ALL BRAZING TO BE COMPLETED ONLY BAG-7 CERTIFIED EMPLOYEES

5. PIPING MEETS REQUIREMENT OF NFPA55 AND NFPA99

6. NOT DESIGNED TO PICK UP OR MOVE WITH PRODUCT IN TANK

7. OPTIONAL LOCAL ALARM PANEL AVAILABLE (P/N 11896754)

8. ALL DIMENSIONS ARE ±1/2"

9. CARBON STEEL FRAME W/ POWDERCOATED

10. NON-SLIP STRIPS ON FLOOR

11. OVERSIZED METAL GRATING REQUIRED FOR SKIDS WITH 12 OR 16 HIGH PRESSURE BOTTLES

12. OVERSIZED AWNING REQUIRED FOR SKIDS WITH 12 OR 16 HIGH PRESSURE BOTTLES.

100 1/2

81 1/284

102 1/2

A CGT 209298 JNB 10/21/15

B CGT 209381 JNB 3/7/16

C CGT 209489 CGT 9/8/16

D CGT 209588 CKL 1/4/18

6 11

FOR OVERSIZED SKID ONLY

E CGT 210054 RLC 12/18/18

F CGT 210084 RLC 03/12/19

J.Iwanczyk Proprietary

SECTION B-B

SCALE .125

SECTION C-C

SCALE .125

A A

B

B

C

C

DRAWING

NO

D-20852344

CHART, INC.

BALL GROUND, GA 30107

APPVREV ECR REVISION DESCRIPTION BY DATE

THE MATERIALS AND INFORMATION, INCLUDING THE PRINCIPLES

OF DESIGN PRESENTED BY THIS PRINT, IS THE EXCLUSIVE

PROPERTY OF CHART INC., AND IS CONFIDENTIAL

INFORMATION. ACCORDINGLY, THIS INFORMATION IS SUBMITTED

TO YOU WITH THE AGREEMENT THAT IT IS NOT TO BE REPRODUCED,

COPIED, OR LOANED, IN PART OR IN WHOLE, NOR IS THE

INFORMATION TO BE RELAYED TO ANY COMPANY. ACCEPTANCE OF

THIS DRAWING WILL BE CONSTRUED AS AN AGREEMENT TO THE ABOVE.

DESIGNATES A NOTE REFERENCE.

MAT'L

FINISH P/N

20852344

APPV'D DATE

APPLICATION ORIGINAL ECR/ER

DRAWN

BY

CHECKED

BY

PROJ.

ENGR.

JNB 7/31/2015

CGT 10/6/2015

UNLESS OTHERWISE SPECIFIED

DIMENSIONS ARE IN INCHES.

TOLERANCES:

FRACTIONS ±

ANGLES ± °

2 PLACE DECIMAL ±

3 PLACE DECIMAL ±

USED ON

SPEC DWG PERMA-CYL

3000HP PSTR FLEX FILL

TITLE:

DRAWING

NO.

SCALE:

DO NOT

SCALE

DRAWING

SHEET:

REV:

D-20852344

N/A 1 of 1

208999

SEE B.O.M.

C

1/2

N/A

N/A

GASEOUS EQUIVALENT: SCF AT 1 ATM & 70º F / Nm³ AT 1 ATM & 0ºC

GAS DELIVERY RATE **

PALLET BASE GALVANIZED

TYPE 304 STAINLESS STEEL

3,800 lbs / 1,724 kg

82,239 SCF / 2,161 Nm³

2,707 LITERS / 715 GALLONS

2,911 LITERS / 769 GALLONS

ASME SEC. VIII. DIV 1

1 % PER DAY NITROGEN

.62 % PER DAY OXYGEN

.62 % PER DAY ARGON

3000 HP FLEX FILL

1,350 SCF/H / 35.4 Nm³/h

250 PSI / 17.2 BAR

CODE

NET VOLUME

ARGON

NITROGEN

OXYGEN

NITROGEN

MATERIAL

NORMAL EVAPORATION RATE

TARE WEIGHT WITH LAB BASE

GROSS VOLUME

RELIEF SETTING MAWP

ITEM

DESIGN SPECIFICATION

80,425 SCF / 2,115 Nm³

66,592 SCF / 1,750 Nm³

OXYGEN

ARGON

PARTS LIST

1,350 SCF/H / 35.4 Nm³/h

1,350 SCF/H / 35.4 Nm³/h

DESCRIPTION

REGULATOR 1/4 FPT @ 140PSI

RV BRS 1/4MPT 550PSI

CYL-TEL GEN 5 0-200"H2O

VALVE CHECK BRS 1/2FPTX1/2FPT

RPD ASSY INLINE 1/2MPT 375PSI

MANUFACTURER P/N

011-0258

PRV9432T550

209105981

GENERANTCV-503B-T-5

12790-0140

REGO

76-603-57

BS&B

REGO

REGO

REGO

WORCESTER

CMM250A

T9454

REGO

APOLLO

REGO

REGO

PRV19434TP250 REGO

PRV9432T550 REGO

Chart

REGOT9454

T9454

VALVE SHUTOFF BRZ 1/2FPT SHORT

VALVE BALL BRS 1/2FPT

VALVE NEEDLE BRS 1/4MPT(ANGLE)

VALVE BALL DIV SS 1/2NPT

VALVE BRS SH 3/8FPTX3/8 SCH 10

VALVE SHUTOFF BRZ 1/2FPT SHORT

1 1712202

1812702

*R-1

RV-1

11051090

11501177

10907239

11905956

11773885

V-4

V-8

10502848

1V-9

V-11

V-1

V-13

V-12

V-10

V-7

RV-5

RV-4

V-2

10502848

*LI-1

PI-1

*R-2

*BD-1

MANUFACTURER

CV-1

11671281

PART NO.ITEM

QTY

RV-3

*RV-2 2

VALVE SHUTOFF 1/4FPT

RV BRS 1/4MPT 550PSI

RV BRS 1/4MPT 550PSI

RV BRS 1/4MPT 550PSI

11905999

10502848 VALVE SHUTOFF BRZ 1/2FPT SHORT

REGOT9452

REGOT9464DA

CN4416PMSE

PRV9432T550

PRV9432T550

CASH-ACME

20683719 VALVE 4-WAY BRS 1/8FPT B-43YTF2-WL8 SWAGELOK

WIKA52721099

DIFF PG 4.5" 0-100" H2O VITON (O2, N2)

DIFF PG 4.5" 0-150" H2O VITON (AR)

WIKA

20923162

20909588 52721125

1812702

1812702

1812702

11488574 RV BRS 1/2MPT 250PSI

20885664

REGULATOR 1/4 FPT @ 325PSI 12790-0325

CASH-ACME

20599868 RV BRS 1/2MPT 350PSI PRV19434TP250 REGO

11526569 RPD ASSY INLINE 1/2MPT 525PSI 011-0258 BS&B

20827654 PG 2-1/2" 0-600PSI/BAR 1/8MPT 52553914

WIKA

350 PSI / 24.1 BAR

500 PSI / 34.4 BAR

10502848 VALVE SHUTOFF BRZ 1/2FPT SHORT T9454

VM-1

REGO

MVE54

20820974 TOP & BTM FILL MANIFOLD

SCHEMATIC

TANK PRESSURE BUILD INLET ISO VALVE

TANK PRESSURE BUILD OUTLET ISO VALVE

TANK GAUGE ISOLATION VALVE

TANK PB INLET

TANK BOTTOM FILL & LIQUID USE

TANK TOP FILL

V-2

RV-5

RV-4

RV-3

RV-2

LI-1

RV-1

R-2

V-1

R-1

PV-1

PBV-1

CV-1

BD-1

TANK FILL ASSEMBLY RELIEF VALVE

TANK PRIMARY RELIEF VALVE

TANK PB INLET RELIEF VALVE

V-11

V-9

R-2

PI-1

LI-1

RV-3

A

B

C

D

E

F

G

H

J

K

L

RV-2

L

PBV-1

PV-1

TANK PB OUTLET

V-10

TANK FULL TRYCOCK / VENT VALVE

TANK GAS USE OUT

TANK PB OUTLET RELIEF VALVE

TANK ECON INLET RELIEF VALVE

TANK ECONOMIZER

TANK GAS USE IN

TANK ECONOMIZER INLET ISO VALVE

TANK GAS USE VALVE

PIPING

V-7

RV-2

V-7

RV-4

V-12

F

RV-5

G

D

J

H

V-8

BD-1

TANK DUAL RELIEF

TANK LIQUID PHASE

TANK VAPOR PHASE

K

V-4

V-1

BD-1

CV-1

TANK PB REGULATOR

TANK ECONOMIZER REGULATOR

TANK PROCESS VAPORIZER COIL

PI-1

TANK LIQUID LEVEL GAUGE

TANK FILL CHECK VALVE

TANK SECONDARY RELIEF DEVICE BURST DISC

TANK PRESSURE GAUGE 0-600 PSI

TANK PRESSURE BUILDING VAPORIZER COIL

NOMENCLATURE

TANK LIQUID WITHDRAWAL VALVE

TANK SAFETY LINE PURGE VALVE

TANK FULL TRYCOCK / VENT VALVE

TANK SAFETY 3-WAY DIVERTER VALVE

TANK ECONOMIZER VALVE

V-13

V-11

V-12

V-10

V-9

V-8

V-7

V-4

A

CB E

V-13

V-2

R-1

BTM FILL

TOP FILL

VENT/DRAIN

RV-1

VM-1

VM-1

TOP & BOTTOM FILL MANIFOLD W/DRAIN

E

C

O

N

S

A

F

E

T

Y

V

E

N

T

B

O

T

T

O

M

I L

L

T

O

P

I L

L

G

A

S

U

S

E

P

B

TOP VIEW

FRONT VIEW

75 1/2

(2 PLCS)

60 1/2

(2 PLCS)

56 1/2

(2 PLCS)

44 5/16

51 1/2

(2 PLCS)

120 5/8

RV-4

V-13

RV-3

V-7

BD-1

RV-2

V-8

RV-2

BD-1

V-7

R-2

V-10

R-1

RV-5

V-2

V-9

V-4

CV-1

VM-1

RV-1

V-1

PI-1

LI-1

V-12

V-11

NOTE:

* - PART NUMBERS ARE DEPENDENT ON THE PLUMBING OPTION KIT CHOSEN FOR THE VESSEL.

** - OPTIONAL 3,500 SCF/H (92 Mn

h) FLOW KIT AVAILABLE

DATA PLATE

5 3/8

A CGT 209500

UPDATE PARTS LIST, SCHEM, DIMS

RLB 07/11/17

B CGT 210007 CHANGED R-1 REGULATORS LAD 12/14/18

21267966

21267965 REGULATOR 1/2 NPT SET @ 300PSI

REGULATOR 1/2 NPT SET @ 125PSI PB504-125

PB504-300 REGO

REGO

C JE 211090

ADDED TABLE, CHANGED V-4 DATA

ZMB 4/8/2021

Pad Dimensions and Reinforcing:

A

Fence

(Area Must be Secure)

6"

5’-0"5’-0"

A Typical

Concrete:

Reinforcing:

Soil Bearing Capacity:

4000 PSI @ 28 Days.

ASTM A615 Grade 60

2000 PSF (minimum)

Pad Specifications

Tank Pad:

Note 1

5’-0" Opening Recommended.

Tank Pad Shall be Level and

3" Above Grade

450L 5’-8"

6’-9"

7’-7"

Model Height

Weight

Empty

Weight

Full N Tank Diameter

Width

4’-0"

2’-6"

3’-6"

Net Cap.

Liters

1000L

1500L

3200 4500

4800 6700

APPROXIMATE TANK DIMENSIONS & CAPACITIES

FOR PERMA-CYL MICROBULK SYSTEMS

Weights do not include lab base option (base option:265 lbs.)

TANK PAD

10’-0" x 10’-0" x 8" Thick

House Line

Location of Gate and Orientation of Equipment to Suit Site

MB1

#5 at 12" On Center Each Way

Depending upon exposure, this installation meets the standards set in National Fire

Protection Association booklet #55 and O.S.H.A. regulation 1910.104.

Pad Design Parameters: (Based Upon The International Building Code - 2012)

Soil Type D, Ultimate Wind Speed 180 mph, Risk Category 2, Exposure D

Seismic: 0.2 Sec. Spectral Response Acceleration of 306% gravity

MBP1- Pad Installation Procedure

MBP2- Standard Bollard Detail

MBE1- Tank Anchoring Procedure

3" Bottom Clearance

Weight

Full Ar

Weight

Full CO

(IBC OCCUPANCY CATEGORY 1 OR 2)

National Standard

For Industrial Use

Rolling Or Sliding Gate May Be Preferred.

Location Determined By Customer Based on Site Conditions to Protect Installation.

Bollards - See Drawing MBP2

10’-0"

Work This Drawing With 2015 Versions of Airgas National Microbulk Standard Drawings:

4/9/15

Tank Microbulk

Note 1

CONCRETE PAD INSTALLATION DETAILS

FOR PERMA-CYL MICROBULK SYSTEMS WITH

NITROGEN, ARGON, and CO

MODELS 450L, 1000L and 1500L

Tank Pad For Microbulk Systems

Date

CONFIDENTIAL NOTICE

Issued By

This document and the designs, specifications and engineering information disclosed hereon are the proprietary property of the Airgas company providing it and are not to be disseminated or reproduced without the prior express written consent of such Airgas company. This proprietary document is being sent in confidence and only for consideration of the matter hereon.

In accepting the loan of this document, recipient agrees to keep it and the matter disclosed hereon in confidence and shall not use or permit their use in any way detrimental to any Airgas companies.

The Airgas companies accept no responsibility for the use of this document by any recipient, this document is only for illustrative purposes. Date

C 2015 Airgas

S

A

F H

O

P F

SIO

S

E68652

T

T E O

O

I

R O

ES

NAL ENG

IN

E E

RR

E

G I T E

R

E D

DAVID

K.

CREMERS

Finish Grade

SECTION A-A

4" Compacted Crushed Stone

Tank Pad

6’-0" Chain Link Fence w/ 3 Strands of Barbed Wire

#5 at 12" On Center Each Way

Microbulk Tank Must Be Set On

Pad Before Fence Is Installed.

Firm Subgrade

For Pad Installation Procedure

See Drawing MBP1

3" Bottom Clearance

MB2

Depending upon exposure, this installation meets the standards set in National Fire

Protection Association booklet #55 and O.S.H.A. regulation 1910.104.

Pad Design Parameters: (Based Upon The International Building Code - 2012)

Soil Type D, Ultimate Wind Speed 180 mph, Risk Category 2, Exposure D

Seismic: 0.2 Sec. Spectral Response Acceleration of 306% gravity

National Standard

For Industrial Use 4/9/15

Location of Gate and Orientation of Equipment to Suit Site

(IBC OCCUPANCY CATEGORY 1 OR 2)

450L 5’-8"

6’-9"

7’-7"

Model Height

Weight

Empty

Tank Diameter

Width

4’-0"

2’-6"

3’-6"

Net Cap.

Liters

1000L

1500L

APPROXIMATE TANK DIMENSIONS & CAPACITIES

FOR PERMA-CYL MICROBULK SYSTEMS

Weights do not include lab base option (base option:265 lbs.)

Pad Dimensions and Reinforcing:

Concrete:

Reinforcing:

Soil Bearing Capacity:

4000 PSI @ 28 Days.

ASTM A615 Grade 60

2000 PSF (minimum)

Pad Specifications

Tank Pad: 10’-0" x 10’-0" x 8" Thick

#5 at 12" On Center Each Way

MBP1- Pad Installation Procedure

MBP2- Standard Bollard Detail

MBE1- Tank Anchoring Procedure

3" Bottom Clearance

Work This Drawing With 2015 Versions of Airgas National Microbulk Standard Drawings:

Weight

Full O

Transport Pad: 12’-0" x 12’-0" x 6" thick

#4 at 12" On Center Each Way

Centered In Slab

A

6"

5’-0"5’-0"

A Typical

Note 1

Tank Pad Shall be Level and

3" Above Grade

TANK PAD

House Line

Bollards

10’-0"

6’-0"6’-0"

12’-0"

Shall Be Clean and Level At Driveway Grade

Transport Pad (for oxygen service only)

Fence

(Area Must be Secure)

5’-0" Opening Recommended.

Rolling Or Sliding Gate May Be Preferred.

Location Determined By Customer Based on Site Conditions to Protect Installation.

- See Drawing MBP2

Tank Microbulk

Note 1

Microbulk Tank

CONCRETE PAD INSTALLATION DETAILS

FOR PERMA-CYL MICROBULK SYSTEMS WITH OXYGEN

MODELS 450L, 1000L and 1500L

For Joint Specifications

See Standard Drawing MBP1

Tank Pad For Microbulk Oxygen Systems

Date

CONFIDENTIAL NOTICE

Issued By

This document and the designs, specifications and engineering information disclosed hereon are the proprietary property of the Airgas company providing it and are not to be disseminated or reproduced without the prior express written consent of such Airgas company. This proprietary document is being sent in confidence and only for consideration of the matter hereon.

In accepting the loan of this document, recipient agrees to keep it and the matter disclosed hereon in confidence and shall not use or permit their use in any way detrimental to any Airgas companies.

The Airgas companies accept no responsibility for the use of this document by any recipient, this document is only for illustrative purposes. Date

C 2015 Airgas

S

A

F H

O

P F

SIO

S

E68652

T

T E O

O

I

R O

ES

NAL ENG

IN

E E

RR

E

G I T E

R

E D

DAVID

K.

CREMERS

Finish GradeTransport Pad

Tank Pad

6’-0" Chain Link Fence w/ 3 Strands of Barbed Wire

Microbulk Tank Must Be Set On

Pad Before Fence Is Installed.

#4 at 12" On Center Each Way Centered In Slab

For Pad Installation Procedure

See Drawing MBP1

SECTION A-A

4" Compacted Crushed Stone

Tank Pad

#5 at 12" On Center Each Way

Firm Subgrade

For Pad Installation Procedure

See Drawing MBP1

3" Bottom Clearance robert.scheehl Highlight

MB3

Protection Association booklet #55 and O.S.H.A. regulation 1910.104.

Pad Design Parameters: (Based Upon The International Building Code - 2012)

Soil Type D, Ultimate Wind Speed 180 mph, Risk Category 2, Exposure D

Seismic: 0.2 Sec. Spectral Response Acceleration of 306% gravity

National Standard

For Industrial Use 4/9/15

Pad Dimensions and Reinforcing:

A

Fence

(Area Must be Secure)

6"

6’-0"6’-0"

A Typical

Tank Pad:

Note 1

Note 1

5’-0" Opening Recommended.

Tank Pad Shall be Level and

3" Above Grade

Model Height

Weight

Empty

Weight

Full N Tank Diameter

Width

Net Cap.

Liters

APPROXIMATE TANK DIMENSIONS & CAPACITIES

FOR PERMA-CYL MICROBULK SYSTEMS

Weights do not include lab base option (base option:265 lbs.)*

TANK PAD

House Line

Location of Gate and Orientation of Equipment to Suit Site

#5 at 12" On Center Each Way

3" Bottom Clearance

Weight

Full Ar

Weight

Full CO

(IBC OCCUPANCY CATEGORY 1 OR 2)

Rolling Or Sliding Gate May Be Preferred.

12’-0"

2000L

3000L 10’-2"

9’-9" 4’-0"

4’-11" 2707

1945 2600

* 11,700

Location Determined By Customer Based on Site Conditions to Protect Installation.

Bollards - See Drawing MBP2

Microbulk Tank

12’-0" x 12’-0" x 10" Thick

CONCRETE PAD INSTALLATION DETAILS

FOR PERMA-CYL MICROBULK SYSTEMS WITH

NITROGEN, ARGON, and CO

MODELS 2000L and 3000L

Tank Pad For Microbulk Systems

Concrete:

Reinforcing:

Soil Bearing Capacity:

4000 PSI @ 28 Days.

ASTM A615 Grade 60

2000 PSF (minimum)

Pad Specifications

MBP1- Pad Installation Procedure

MBP2- Standard Bollard Detail

MBE1- Tank Anchoring Procedure

Work This Drawing With 2015 Versions of Airgas National Microbulk Standard Drawings:

Date

CONFIDENTIAL NOTICE

Issued By

This document and the designs, specifications and engineering information disclosed hereon are the proprietary property of the Airgas company providing it and are not to be disseminated or reproduced without the prior express written consent of such Airgas company. This proprietary document is being sent in confidence and only for consideration of the matter hereon.

In accepting the loan of this document, recipient agrees to keep it and the matter disclosed hereon in confidence and shall not use or permit their use in any way detrimental to any Airgas companies.

The Airgas companies accept no responsibility for the use of this document by any recipient, this document is only for illustrative purposes. Date

C 2015 Airgas

S

A

F H

O

P F

SIO

S

E68652

T

T E O

O

I

R O

ES

NAL ENG

IN

E E

RR

E

G I T E

R

E D

DAVID

K.

CREMERS

Finish Grade

SECTION A-A

4" Compacted Crushed Stone

Tank Pad

6’-0" Chain Link Fence w/ 3 Strands of Barbed Wire

#5 at 12" On Center Each Way

Microbulk Tank Must Be Set On

Pad Before Fence Is Installed.

Firm Subgrade

For Pad Installation Procedure

See Drawing MBP1

3" Bottom Clearance

MB4

Protection Association booklet #55 and O.S.H.A. regulation 1910.104.

Pad Design Parameters: (Based Upon The International Building Code - 2012)

Soil Type D, Ultimate Wind Speed 180 mph, Risk Category 2, Exposure D

Seismic: 0.2 Sec. Spectral Response Acceleration of 306% gravity

National Standard

For Industrial Use 4/9/15

Location of Gate and Orientation of Equipment to Suit Site

(IBC OCCUPANCY CATEGORY 1 OR 2)

Pad Dimensions and Reinforcing:

Concrete:

Reinforcing:

Soil Bearing Capacity:

4000 PSI @ 28 Days.

ASTM A615 Grade 60

2000 PSF (minimum)

Pad Specifications

Tank Pad:

#5 at 12" On Center Each Way

MBP1- Pad Installation Procedure

MBP2- Standard Bollard Detail

MBE1- Tank Anchoring Procedure

3" Bottom Clearance

Work This Drawing With 2015 Versions of Airgas National Microbulk Standard Drawings:

Transport Pad: 12’-0" x 12’-0" x 6" thick

#4 at 12" On Center Each Way

Centered In Slab

A

TANK PAD

6’-0"6’-0"

12’-0"

Shall Be Clean and Level At Driveway Grade

Transport Pad (for oxygen service only)

Model Height

Weight

Empty

Tank Diameter

Width

Net Cap.

Liters

APPROXIMATE TANK DIMENSIONS & CAPACITIES

FOR PERMA-CYL MICROBULK SYSTEMS

Weights do not include lab base option (base option:265 lbs.)*

2000L

3000L 10’-2"

9’-9" 4’-0"

4’-11" 2707

1945 2600

CONCRETE PAD INSTALLATION DETAILS

FOR PERMA-CYL MICROBULK SYSTEMS WITH OXYGEN

MODELS 2000L and 3000L

Weight

Full 0

10,200

6"

6’-0"6’-0"

A Typical

Note 1

Tank Pad Shall be Level and

3" Above Grade

House Line

12’-0"

Microbulk Tank

Fence

(Area Must be Secure)

Note 1

Bollards

5’-0" Opening Recommended.

Rolling Or Sliding Gate May Be Preferred.

Location Determined By Customer Based on Site Conditions to Protect Installation.

- See Drawing MBP2 12’-0" x 12’-0" x 10" Thick

For Joint Specifications

See Standard Drawing MBP1

Tank Pad For Microbulk Oxygen SystemsTank Pad For Microbulk Oxygen Systems

Date

CONFIDENTIAL NOTICE

Issued By

This document and the designs, specifications and engineering information disclosed hereon are the proprietary property of the Airgas company providing it and are not to be disseminated or reproduced without the prior express written consent of such Airgas company. This proprietary document is being sent in confidence and only for consideration of the matter hereon.

In accepting the loan of this document, recipient agrees to keep it and the matter disclosed hereon in confidence and shall not use or permit their use in any way detrimental to any Airgas companies.

The Airgas companies accept no responsibility for the use of this document by any recipient, this document is only for illustrative purposes. Date

C 2015 Airgas

S

A

F H

O

P F

SIO

S

E68652

T

T E O

O

I

R O

ES

NAL ENG

IN

E E

RR

E

G I T E

R

E D

DAVID

K.

CREMERS

Finish GradeTransport Pad

Tank Pad

6’-0" Chain Link Fence w/ 3 Strands of Barbed Wire

Microbulk Tank Must Be Set On

Pad Before Fence Is Installed.

#4 at 12" On Center Each Way Centered In Slab

For Pad Installation Procedure

See Drawing MBP1

SECTION A-A

4" Compacted Crushed Stone

Tank Pad

#5 at 12" On Center Each Way

Firm Subgrade

For Pad Installation Procedure

See Drawing MBP1

3" Bottom Clearance robert.scheehl Highlight

Protection Association booklet #55 and O.S.H.A. regulation 1910.104.

Pad Design Parameters: (Based Upon The International Building Code - 2012)

Soil Type D, Ultimate Wind Speed 200 mph, Risk Category 4, Exposure D

Seismic: 0.2 Sec. Spectral Response Acceleration of 230% gravity

4/9/15 MBHC1

Tank Pad For Microbulk Oxygen Systems

National Standard

For Healthcare Facility Use

450L 5’-8"

6’-9"

7’-7"

Model Height

Weight

Empty

Tank Diameter

Width

4’-0"

2’-6"

3’-6"

Net Cap.

Liters

1000L

1500L

APPROXIMATE TANK DIMENSIONS & CAPACITIES

FOR PERMA-CYL MICROBULK SYSTEMS

Weights do not include lab base option (base option:265 lbs.)

Weight

Full O

(IBC OCCUPANCY CATEGORY 4)

CONCRETE PAD INSTALLATION DETAILS FOR

PERMA-CYL MICROBULK HEALTHCARE SYSTEMS WITH OXYGEN

MODELS 450L, 1000L and 1500L

Location of Gate and Orientation of Equipment to Suit Site

Pad Dimensions and Reinforcing:

Concrete:

Reinforcing:

Soil Bearing Capacity:

4000 PSI @ 28 Days.

ASTM A615 Grade 60

2000 PSF (minimum)

Pad Specifications

Tank Pad: 12’-0" x 12’-0" x 8" Thick

#5 at 12" On Center Each Way

MBP1- Pad Installation Procedure

MBP2- Standard Bollard Detail

MBE1- Tank Anchoring Procedure

3" Bottom Clearance

Work This Drawing With 2015 Versions of Airgas National Microbulk Standard Drawings:

Transport Pad: 12’-0" x 12’-0" x 6" thick

#4 at 12" On Center Each Way

Centered In Slab

A

TANK PAD

6’-0"6’-0"

12’-0"

Shall Be Clean and Level At Driveway Grade

Transport Pad (for oxygen service only)

6"

6’-0"6’-0"

A

Typical

Note 1

Tank Pad Shall be Level and

3" Above Grade

12’-0"

Note 1

Bollards

Fence

(Area Must be Secure)

5’-0" Opening Recommended.

Rolling Or Sliding Gate May Be Preferred.

Location Determined By Customer Based on Site Conditions to Protect Installation.

- See Drawing MBP2

For Joint Specifications

See Standard Drawing MBP1

Tank Microbulk

Alarm Conduit

Electrical Conduit

House Line

Regulation

Stand

6 Cylinder

Reserve Manifold

Date

CONFIDENTIAL NOTICE

Issued By

This document and the designs, specifications and engineering information disclosed hereon are the proprietary property of the Airgas company providing it and are not to be disseminated or reproduced without the prior express written consent of such Airgas company. This proprietary document is being sent in confidence and only for consideration of the matter hereon.

In accepting the loan of this document, recipient agrees to keep it and the matter disclosed hereon in confidence and shall not use or permit their use in any way detrimental to any Airgas companies.

The Airgas companies accept no responsibility for the use of this document by any recipient, this document is only for illustrative purposes. Date

C 2015 Airgas

S

A

F H

O

P F

SIO

S

E68652

T

T E O

O

I

R O

ES

NAL ENG

IN

E E

RR

E

G I T E

R

E D

DAVID

K.

CREMERS

Finish GradeTransport Pad

Tank Pad

6’-0" Chain Link Fence w/ 3 Strands of Barbed Wire

Microbulk Tank Must Be Set On

Pad Before Fence Is Installed.

#4 at 12" On Center Each Way Centered In Slab

For Pad Installation Procedure

See Drawing MBP1

SECTION A-A

4" Compacted Crushed Stone

Tank Pad

#5 at 12" On Center Each Way

Firm Subgrade

For Pad Installation Procedure

See Drawing MBP1

3" Bottom Clearance

MBHC24/9/15

Protection Association booklet #55 and O.S.H.A. regulation 1910.104.

Pad Design Parameters: (Based Upon The International Building Code - 2012)

Soil Type D, Ultimate Wind Speed 200 mph, Risk Category 4, Exposure D

Seismic: 0.2 Sec. Spectral Response Acceleration of 230% gravity

Tank Pad For Microbulk Oxygen Systems

National Standard

For Healthcare Facility Use

(IBC OCCUPANCY CATEGORY 4)

Model Height

Weight

Empty

Tank Diameter

Width

Net Cap.

Liters

APPROXIMATE TANK DIMENSIONS & CAPACITIES

FOR PERMA-CYL MICROBULK SYSTEMS

Weights do not include lab base option (base option:265 lbs.)*

2000L

3000L 10’-2"

9’-9" 4’-0"

4’-11" 2707

1945 2600

Weight

Full 0

10,200

CONCRETE PAD INSTALLATION DETAILS FOR

PERMA-CYL MICROBULK HEALTHCARE SYSTEMS WITH OXYGEN

MODELS 2000L and 3000L

Location of Gate and Orientation of Equipment to Suit Site

Pad Dimensions and Reinforcing:

Concrete:

Reinforcing:

Soil Bearing Capacity:

4000 PSI @ 28 Days.

ASTM A615 Grade 60

2000 PSF (minimum)

Pad Specifications

Tank Pad:

#5 at 12" On Center Each Way

MBP1- Pad Installation Procedure

MBP2- Standard Bollard Detail

MBE1- Tank Anchoring Procedure

3" Bottom Clearance

Work This Drawing With 2015 Versions of Airgas National Microbulk Standard Drawings:

Transport Pad: 12’-0" x 12’-0" x 6" thick

#4 at 12" On Center Each Way

Centered In Slab

15’-0" x 12’-0" x 10" Thick

A

TANK PAD

12’-0"

Shall Be Clean and Level At Driveway Grade

Transport Pad (for oxygen service only)

6’-0"6’-0"

A

Note 1

12’-0"

Microbulk Tank

Note 1

Bollards

Fence

(Area Must be Secure)

5’-0" Opening Recommended.

Rolling Or Sliding Gate May Be Preferred.

Location Determined By Customer Based on Site Conditions to Protect Installation.

- See Drawing MBP2

For Joint Specifications

See Standard Drawing MBP1

6"

Typical

Tank Pad Shall be Level and

3" Above Grade

6 Cylinder

Reserve ManifoldRegulation

Stand

Alarm Conduit

Electrical Conduit

House Line

Date

CONFIDENTIAL NOTICE

Issued By

This document and the designs, specifications and engineering information disclosed hereon are the proprietary property of the Airgas company providing it and are not to be disseminated or reproduced without the prior express written consent of such Airgas company. This proprietary document is being sent in confidence and only for consideration of the matter hereon.

In accepting the loan of this document, recipient agrees to keep it and the matter disclosed hereon in confidence and shall not use or permit their use in any way detrimental to any Airgas companies.

The Airgas companies accept no responsibility for the use of this document by any recipient, this document is only for illustrative purposes. Date

C 2015 Airgas

S

A

F H

O

P F

SIO

S

E68652

T

T E O

O

I

R O

ES

NAL ENG

IN

E E

RR

E

G I T E

R

E D

DAVID

K.

CREMERS

Finish GradeTransport Pad

Tank Pad

6’-0" Chain Link Fence w/ 3 Strands of Barbed Wire

Microbulk Tank Must Be Set On

Pad Before Fence Is Installed.

#4 at 12" On Center Each Way Centered In Slab

For Pad Installation Procedure

See Drawing MBP1

SECTION A-A

4" Compacted Crushed Stone

Tank Pad

#5 at 12" On Center Each Way

Firm Subgrade

For Pad Installation Procedure

See Drawing MBP1

3" Bottom Clearance

REV DATE DWN CHK APVD DATE

JOB NO.

COMPUTER FILE

DRAWN BY

CHECKED BY

APPRD. / D.A.

DATE REV NO.

DWG NO.

an Air Liquide company

CONFIDENTIAL NOTICE

THIS DOCUMENT AND THE DESIGNS, SPECIFICATIONS AND ENGINEERING INFORMATION DISCLOSED

HEREON ARE THE PROPERTY OF AIRGAS, AN AIR LIQUIDE COMPANY, AND ARE NOT TO BE

DISSEMINATED OR REPRODUCED WITHOUT EXPRESS WRITTEN CONSENT OF AIRGAS, AN AIR LIQUIDE

COMPANY. THIS PROPRIETARY DOCUMENT IS BEING SENT IN CONFIDENCE AND ONLY FOR

CONSIDERATION OF THE MATTERS HEREON. IN ACCEPTING THE LOAN OF THIS DOCUMENT, RECIPIENT

AGREES TO KEEP IT AND THE MATTERS DISCLOSED HEREON I CONFIDENCE AND SHALL NOT USE

THEM NOR PERMIT THEIR USE IN ANY WAY DETRIMENTAL TO AIRGAS, AN AIR LIQUIDE COMPANY.

REV DATE DWN CHK APVD

S.M. HAW ASSOC.

T. MIRABELLA

C. LAFLIN

12-04-2020

Diameter

Slope Top For Drainage Concrete Fill

Grade

Slope For Drainage

3,000 PSI

Concrete Foundation

Schedule 40 Standard Wt. Pipe 4" Dia. x 5'-6" Lg.

12" Diameter 16" Lap 2-#5 Reinforcing Rings

Existing Paving or

Transport Pad

Crushed Stone 4" Compacted

Firm Subgrade

Grade FinishSee Typical Joint Detail

Typical Section Through Pads

Reinforcing

Clearance

Tank Pad

1'-4"

FOR CONSTRUCTION

C 2020 Airgas, an Air Liquide Company

Standard Bollard, Fence, and Joint Details

STF-DET-01

Standard Bollard Detail

Apply Per Manufacturers Recommendations.

Color to be Safety Yellow (206327).

VOC Alkyd Enamel

Finish Coat: RUST-OLEUM Industrial Choice 340

VOC Alkyd Enamel Primer.

Primer: RUST-OLEUM Industrial Choice 340 to Remove Rust and Scale

Clean Surface Per SSPC- SP3

Bollard Pipe Paint Specification

(Prevent Gates From Opening Fully).

Interfere with Any Access Gates

Location of Bollards Should Not

Maximum Distance Between Bollards is 4'-0" C/C.

On All Sides Exposed To Vehicle Traffic

Upon Site Conditions To Protect Installation

By Customer And Airgas Based

Bollard Locations To Be Verified

Bollard Design Per International Fire Code Section 312

1 "2

2"

(Level)

"3

"3 4x

Typical All Around or Tooled Edge Chamfer

Polyfoam Board"1

1 "2

Other Sealants Not Permitted Chem Seal CS 2727 Sealant

(818) 890-1401 www.flamemaster.com By The Flamemaster Corporation

Board is Prohibited Use of Asphalt Impregnated

For Oxygen Service

Argon Service For Nitrogen or

"Ceramar" www.wrmeadows.com

3" Clear

Bottom Reinforcing Typical

Typical

Top Reinforcing

1 "21 Clear Driveway Grade

Level and At Off-Load Pad

See Typical Joint Detail

High Performance Polyurethane Sealant

For Oxygen Service

For Nitrogen or Argon Service

Chem Seal CS 2727 Sealant

Sikaflex 1a or Other Approved Polyurethane Sealant High Performance

C/J

Typical Control Joint

Shown Thus On Plan

Typical Control Joint

1 "21 Deep Saw Cut Fill With Sealant

High Performance Polyurethane Sealant

For Oxygen Service

For Nitrogen or Argon Service

Chem Seal CS 2727 Sealant

For Crack Control

Reinforcing

3" Break

Fill With Sealant and Backer Rod

3" Deep Saw Cut

Pad Isolation Construction Joint

For Equipment Isolation

For Equipment Isolation

Construction Joint Continuous Pad

12-04-20

12-04-20

1/2 "

3.

2.

1.

T

DC

Typical Fence Detail

N.T.S.

Airgas Standard Reference Drawings:

STE-GEN-001 "Standard Grounding Guidelines for Bulk Systems"

3.

2.

1.

Bollard Locations

Typ. Sliding Gate - Plan

N.T.S.

SLIDING FILL GATE

36"

36"

36"

ENCASEMENT

12" DIA. CONC.

PIPE" SCH40 GALV.2

END OR CORNER POST,

OR SURFACE MATERIAL

TOP OF FINISH GRADE

" O.D.2

BRACE RAIL

END

RAIL

GALVANIZED BARB WIRE

(3) STRANDS - 4 POINT

6'

6'

11'

(TYPICAL)

O.D.2

BRACE RAIL

36"

36"

36" 36"

10'10'

7 GAUGE

WIRES

TENSION

TIES

WIRE

GALVANIZED BARB WIRE

(3) STRANDS - 4 POINT

PIPE" SCH40 GALV.2

END OR CORNER POST,

POST

LINE OR SURFACE MATERIAL

TOP OF FINISH GRADE

Typ. Sliding Gate - Elevation

N.T.S.

42"

8' MAX

32"

21"

STEEL

2"X2" STRUCTURAL

21"

4" TOEBOARD

HANDRAIL

See OSHA Standard 1910.23

Typ. Railing Detail

N.T.S.

ROD

TRUSS

" MIN.8

SCH40 GALV. PIPE

"2

GATE FRAME 1

8" DIA. CONC.

ENCASEMENT

ENCASEMENT

12" DIA. CONC.

TRUSS ROD

" MIN.8

END

RAIL

DIAMOND MESH

WOVEN WITH A 2"X2"

#9 GAUGE GALV. WIRE

CHAIN LINK FABRIC

SCH40 GALV. PIPE

LINE POST 2"

TM CL

Airgas Standard Reference Drawings:

FOR CONSTRUCTION

STF-DET-01 - Pad, Bollard, and Fence Installation Details STF-DET-02 - Pad and Anchoring Installation Notes

A

STF-DET-02

See Drawing Procedure For Pad Installation

Tank MicroBulk

See Table - This Drawing Specifications For Tank Anchoring

12.

11.

10.

9.

8.

7.

6.

5.

4.

3.

2.

1.

12'-0"

X

Ground

(Min. Height 8'-0") Lighting (1 Place)

Stand Regulation

See Drawing STF-DET-01 Area Must Be Secure w/ 3 Strands Of Barbed Wire.

6'-0" Chain Link Fence

Y

PLAN - TANK PAD

For Nitrogen, Oxygen, Argon or CO2 MicroBulk Tanks

ELEVATION

Tank Pad

3" Above Grade

Shall be Level and

12-04-20

12-04-20 0

Industrial LIN - LOX - LAR-CO2

MicroBulk VJ Vessels

C 2020 Airgas, an Air Liquide Company

Standard Foundation Reference tation of equipment.

Off-Load Pad, and orien-on location of gates, Airgas shall be consulted

GENERAL NOTES

STF-MB-003

A

By a Registered Professional Engineer.

Table. Larger Pads Must Have The Reinforcing Reviewed Direction Without Changing The Reinforcing Shown In the Concrete Pad Dimensions Can Be Increased By 2'-0" In Each

Association Booklet #55 And O.S.H.A. Regulation 1910.104.

Separation Requirements Defined In National Fire Protection Depending Upon Exposure, This Installation Shall Meet The

Design Seismic: Per Table.

Design Wind Velocity: Per Table.

Design For Risk Category II.

IBC 2018/ASCE7-16 and IBC 2015/ASCE7-10.

Design Loads are Based Upon the More Stringent of

Design Soil Capacity 2000 psf Minimum.

ASTM A615 Grade 60.

All Reinforcing Bars Shall Conform To

4000 Psi @ 28 Days.

Concrete Compressive Strength Shall Be

With The Latest Editions Of ACI-301, ACI-302 And ACI-318.

All Concrete Construction Shall Be In Accordance

Filled With Suitable Material & Compacted.

Any Soft Spots Shall Be Excavated, New Concrete, The Subgrade Shall Be Compacted.

Prior To Installing Granular Base & Pouring

Upon Between Site Owner and Aigas.

Exact Site Location And Orientation Shall Be Agreed

Verify All Dimensions And Conditions In Field.

Reference Building Line

STM-MB-001 "MicroBulk Vessel Decal Placement" STE-GEN-001 "Standard Grounding Guidelines for Bulk Systems" STA-GEN-006 "Courtyard Guidelines" STA-CO2-001 "Distance Exposure - Bulk Carbon Dioxide STA-GEN-004 "Distance Exposure - Liquid Oxygen" STA-GEN-003 "Distance Exposure - Cryogenic Systems" Turning Radius" STA-GEN-007 "MicroBulk Systems Delivery Guidelines and

Off-Load Pad

At Driveway Grade

Shall be Level and

Service Only)

(For Oxygen

Detail and Application STF-DET-01 for See Airgas Drawing Bollards

TM

See Drawing STF-DET-01 Area Must Be Secure w/ 3 Strands Of Barbed Wire.

6'-0" Chain Link Fence

Typ.

Double Gate 5'-0" Wide

Shown For Reference 3000L Tank an Air Liquide company

M a x

1'-6"

Typ.

N .T

.S

Centered In Slab

Bottom Reinforcing See Table

Firm Subgrade

3" Bottom Clearance

Each Way #4 at 12" O.C.

And Reinforcing See Table For Pad Size

Tank Pad

Crushed Stone 4" Compacted

SECTION A-A

Off-Load Pad

12'-0" x 12'-0" x 6" Thick

Not Shown on This Section See Drawing STF-DET-01 for Information

T

6"

DC CL

REV DATE DWN CHK APVD DATE

JOB NO.

COMPUTER FILE

DRAWN BY

CHECKED BY

APPRD. / D.A.

DATE REV NO.

DWG NO.

an Air Liquide company

CONFIDENTIAL NOTICE

THIS DOCUMENT AND THE DESIGNS, SPECIFICATIONS AND ENGINEERING INFORMATION DISCLOSED

HEREON ARE THE PROPERTY OF AIRGAS, AN AIR LIQUIDE COMPANY, AND ARE NOT TO BE

DISSEMINATED OR REPRODUCED WITHOUT EXPRESS WRITTEN CONSENT OF AIRGAS, AN AIR LIQUIDE

COMPANY. THIS PROPRIETARY DOCUMENT IS BEING SENT IN CONFIDENCE AND ONLY FOR

CONSIDERATION OF THE MATTERS HEREON. IN ACCEPTING THE LOAN OF THIS DOCUMENT, RECIPIENT

AGREES TO KEEP IT AND THE MATTERS DISCLOSED HEREON I CONFIDENCE AND SHALL NOT USE

THEM NOR PERMIT THEIR USE IN ANY WAY DETRIMENTAL TO AIRGAS, AN AIR LIQUIDE COMPANY.

REV DATE DWN CHK APVD

S.M. HAW ASSOC.

T. MIRABELLA

C. LAFLIN

12-04-2020

DETAIL B

DETAIL C

C

APPVREV ECR REVISION DESCRIPTION BY DATE

# DESIGNATES A NOTE REFERENCE.

MAT'L

FINISH P/N

SEE TABLE

APPV'D DATE

JNB 2/2/2015

APOLLO 1/2" 3-WAY DIVERTER VALVE

RESERVE IN USE PRESS SWITCH ALARM

RESERVE LOW PRESS SWITCH ALARM

PT-1

PS-2

OXYGEN PIGTAILS

WESTERN B-52 CGA 540 1/2"

UNITED BRASS 1/2" SWING CHECK VALVE

REGO 1/2 NPT 350 PSIG

REGO 1/2 NPT 75 PSIG ASME

VICTOR 1/4 NPT

REGO 1/2" 40-110 PSI MEDICAL REGULATOR

VICTOR HIGH PRESSURE REGULATOR SR450D

VICTOR 1/4 NPT

HIGH PRESSURE SUPPLY REGULATOR

PT4540 OXYGEN PIGTAILS - SUPERIOR

UNITED ELECTRIC 80-1700 PSI PRESS SWITCH

UNITED ELECTRIC 15-300 PSI PRESS SWITCH

1/4 NPT (4"DIAL) - WIKA

1/4 NPT (4"DIAL) - WIKA

PRESSURE GAUGE 0-4000 PSI

PRESSURE GAUGE 0-400 PSI

PRESSURE GAUGE 0-200 PSI

TITAN 1/2" W/100 MESH SS

APOLLO 1/2" 3-WAY DIVERTER VALVE

APOLLO 1/2" BALL VALVE W/UNION END

REGO 1/4 NPT 350 PSIGTHERMAL RELIEF VALVE FOR R-2

PRESSURE GAUGE 0-200 PSI

NOMENCLATURE

SS-XSS4-1 EXCESS FLOW VALVE - SWAGELOK

REGO 1/2" 9560CA MASTER VALVE

APOLLO 1/2" BALL VALVE W/UNION END HIGH PRESS SUPPLY REG ISO VALVE

HIGH PRESS SUPPLY ISO VALVE

MANUFACTURER

MAIN GAS OUTLET SAFETY 3-WAY VALVE

0-200 PSI PRESSURE GAUGE ISO VALVE APOLLO 1/4" BALL VALVE W/ 1/8 PURGE PORT

MAIN GAS SUPPLY REGULATOR

VALVE OUTLET ADAPTER W/ CHECK VALVE

EXCESS FLOW VALVE FOR PS-2

MAIN GAS INLET SAFETY 3-WAY VALVE

0-400 PSI PRESSURE GAUGE ISO VALVEV-8

V-7

TANK INLET CHECK VALVECV-2

V-9

CV-1

SS-XSS4-1 EXCESS FLOW VALVE - SWAGELOK

APOLLO 1/4" BALL VALVE W/ 1/8 PURGE PORT

MAIN GAS LINE INLET STRAINER

MAIN GAS OUTLET RELIEF VALVE ASME

R-1 S-1

RV-3 A&B

RV-2 A&B

MAIN GAS INLET RELIEF VALVE RV-1 A&B

DESCRIPTION

V-2

ITEM

V-1

R-2 A&B

PI-2

PI-1

PS-1

PI-4

PI-3

V-4 V-3

GAS SUPPLY REGULATOR ISO VALVE

V-6

V-5 A-D

EXCESS FLOW VALVE FOR PS-1

V-10 BRASS BLEED VALVE SUPERIOR 3000PSI 1/4"x1/4" BRASS VALVE

NOMENCLATURE (PARTS TO SUBSTITUTE FOR NITROGEN SKID)

DESCRIPTIONITEM MANUFACTURER

CV-1 VALVE OUTLET ADAPTER W/ CHECK VALVE WESTERN B-52 CGA 540 1/2"

RV-3 A&B MAIN GAS OUTLET RELIEF VALVE ASME REGO 1/2 NPT 275 PSIG ASME

R-2 A&B MAIN GAS SUPPLY REGULATOR REGO 1/2" 100-200 PSIG MEDICAL

PI-1 PRESSURE GAUGE 0-400 PSIG VICTOR 1/4 NPT

PI-3 PRESSURE GAUGE 0-400 PSIG VICTOR 1/4 NPT (4"DIAL) - WIKA

PT-1 NITROGEN PIGTAILS PT4580 NITROGEN PIGTAILS - SUPERIOR

V-11 PS-2 ISOLATION VALVE W/PORT EXHAUST SWAGELOK SS-42GVS4

CV-3 HIGH PRESS INLET CHECK VALVE APOLLO 1/2" 400WOG SPRING LOADED

PI-5 PRESSURE GAUGE 0-400 PSI 1/4 NPT (2"DIAL) - WIKA

PARTS TO SUBSTITUE FOR HYPERBARIC O2

ITEM DESCRIPTION MANUFACTURER

RV-3B BACK PRESSURE REGULATOR REGO ECL-140 SET 75 PSIG

RV-3A MAIN GAS OUTLET RELIEF VALVE ASME REGO 1/2" NPT 90PSIG

M MUFFLER IN BP REGULATOR PARKER LEGRIS COMECTIC P/N 0670-00-13

RV-4 HP REGULATOR RELIEF VALVE REGO NPT 1/4" 350PSIG

R-1CV-3

V-2

RV-1B

PI-1 PI-2

R-2B

V-5DV-5C

S-1

RV-2B

V-4

RV-1A

R-2A

V-3

RV-3B

V-5BV-5A

RV-2AV-8 RV-3AV-7

PS-2

PI-4 PI-3

MEDICAL MANIFOLD PIPING

PI-5

CV-1 CV-1CV-1 CV-1 CV-1

HIGH PRESSURE RESERVE

CV-2

CV-1

PIG-TAILS WESTERN P-63 CGA540 (PT-1)

FROM TANK GAS USE VALVE

V-10

CV-1CV-1

V-9

V-6

PS-1

TO FACILITY SOURCE VALVE

B4

NO

R5

C

Y

NC

C

NC

14 R

13 B

NO

Y

LOW LEVEL SWITCH ON TANK

- TERMINAL IN ELECTRICAL

IN JUNCTION BOX

NC

9 R

B8

NOC

Y 2

V-1

RESERVE IN USE

RESERVE LOW

V-11

RV-4

PI-4 PI-3

V-8

V-5A R-2A

V-7

V-5C

R-2B

V-5D

V-5BPS-2 PS-1

SEE

DETAIL C

RV-1A

V-4

RV-1B CV-3

V-2

PI-1 PI-2

R-1 V-1

V-6

RV-3A

CV-2

S-1

V-3

V-9

V-10PI-5

V-11 RV-2A

RV-2B

RV-4

C C C C

NONONONO

NCNCNCNC

G G G G

NCNCNCNC

NONONONO

C C C C

SPAR

E

LIQ

U

ID

LEVEL

R

ESER

VE IN

U

SE

R

ESER

VE LO

W

ALARM WIRES TO

FACILITY

TO HP MANIFOLD

TO GAS USE VALVE

ON LIQUID STORAGE TANK

TO FACILITY SOURCE VALVE

SEE PAGE 1, TABLE 1 FOR OTHER CONFIGURATIONS

RV-3B

APPVREV ECR REVISION DESCRIPTION BY DATE

# DESIGNATES A NOTE REFERENCE.

MAT'L

FINISH P/N

SEE TABLE

APPV'D DATE

JNB 2/2/2015

GAS USE

TO

P FILL

BO

TT

O M

F

IL

L

VENT

ECON OUT

SAFETY/ECON IN PB OUT

H

L

R E S E R V E

B O T T L E S

DIM A

102 1/2

81 1/2

100 1/2

56 1/2

45 3/8 52 3/8

3 7/8

PART NUMBER SPEC DRAWING MODEL DIM A (in.) WEIGHT W/FRAME (lbs.)

20814390 20852345 PERMA-CYL 1000HP FF 83 2600

20814391 20852342 PERMA-CYL 1500HP FF 83 2850

20814392 20852343 PERMA-CYL 2000HP FF 92 3300

20814394 20852344 PERMA-CYL 3000HP FF 92 3600

20755351 20852345 PERMA-CYL 1000VHP FF 120 3700

20755352 20852342 PERMA-CYL 1500VHP FF 121 4050

20793147 20852341 PERMA-CYL 2000VHP FF 123 4400

20793148 20852350 PERMA-CYL 3000VHP FF 124 5350

6 1/2

TYP2 3/4 TYP

13611

711 1/2

FOR OVERSIZED

SKIDS ONLY

File details come from the government source that posted it. Updated .