Attachment D25 - Physical Security Design Manual for Life Safety PG-18-3 Noise Transmission Control.pdf

PDF 258 KB Posted

Attached to
Q201--Escondido CBOC RFP
Solicitation number
36C26220R0128
Issued by

View the file

Other files

File Type Posted
Attachment D21 - Section F Lease -Escondido - updated Square Footage .pdf PDF
Attachment D23 - VA Handbook 0730.pdf PDF
36C26220R0128 0007 - QandA and RFP Updates.pdf PDF
36C26220R0128 0007_1.docx DOCX document
Attachment 22 - Davis-Bascon Wage Determination.pdf PDF
Attachment D24 - Physical Security Design Manual for Life Safety Protected Facilities.pdf PDF
36C26220R0128 0006.pdf PDF
36C26220R0128 0006_1.docx DOCX document
36C26220R0128 0005_1.docx DOCX document
36C26220R0128 0005.pdf PDF
36C26220R0128 0004_1.docx DOCX document
36C26220R0128 0004 - QandA and PWS Update and Attachments.pdf PDF
36C26220R0128 0003.pdf PDF
36C26220R0128 0003_1.docx DOCX document
36C26220R0128 0002.pdf PDF
36C26220R0128 0002_1.docx DOCX document
36C26220R0128 0001.pdf PDF
36C26220R0128 0001_1.docx DOCX document
Attachment D2 - Price Work Sheet.pdf PDF
Attachment D20 - Mental Health No Show Policy.pdf PDF
Attachment D10 -Patients_ Rights Responsibilities and Conduct HSP 003-04.pdf PDF
Attachment D19 - Home Telehealth Manual.pdf PDF
Attachment D18 - Connected Care Telehealth Manual.pdf PDF
Attachment D9 - Wage Determination.pdf PDF
Attachment D5 - Contractor Security Requirements (Handbook 6500.6).pdf PDF
Attachment D3 - Past Performance Questionnaire.pdf PDF
36C26220R0128_2.docx DOCX document
Attachment D21 - Section F Lease -Escondido.docx DOCX document
Attachment D7 - Rules of Behavior.pdf PDF
Attachment D13 - VHA Directive 2011-012 - Medication Reconciliation.pdf PDF
Attachment D6 - Immigration and Nationality Act of 1952 Certification.pdf PDF
Attachment D17 - Anticoagulation Therapy.pdf PDF
S02 - RFP - 36C26220R0128 - ESCONDIDO CBOC.pdf PDF
Attachment D11 - Ancillary Testing Policy HSP 05-01.pdf PDF
Attachment D16 - HCS Policy 114-01 Attachment I.pdf PDF
Attachment D14 - Memorandum 11-99 Communicating Test Results.pdf PDF
Attachment D15 - MCM 00-18 Patient and Nursing Home Resident Rights and Responsibilities.pdf PDF
Attachment D4 - Conflict of Interest.pdf PDF
Attachment D1- Quality Assurance Surveillance Plan.pdf PDF
Attachment D12 - Pathology and Laboratory Medicine Service Procedures.pdf PDF
Attachment D8 - Proper Use of Email and Other Messaging Services.pdf PDF
Show all 41

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

PG 18-3 – DESIGN AND CONSTRUCTION PROCEDURES April 2004

NOISE TRANSMISSION CONTROL 11-1

TOPIC 11 – NOISE TRANSMISSION CONTROL

1. GENERAL: Where rooms do not contribute to or are not affected by sound transmission from an adjacent space, conventional construction is satisfactory.

2. PARTITION-CEILING-DOOR-DUCT SYSTEM ACOUSTIC DESIGN

a. Acoustical Isolation. Design the sound resistant enclosures of the following spaces to suppress generated noise and provide a satisfactory degree of acoustical isolation for adjacent occupied spaces. Achieve a minimum Sound Transmission Class (STC) rating of 45.

NOTE: When the VA Hospital Building System (VAHBS) is used, achieve the required rating using construction such as a double layer of 16 mm (5/8 in.) gypsum board (GB) on both sides of 100 mm (4 in.) nominal metal studs and 64 mm (2 1/2 in.) sound attenuation blankets between the studs. These should extend above conventional lay-in ceilings to the underside of walk-on deck/platforms.

(1) A/C and other mechanical equipment rooms.

(2) Manual arts therapy shops.

(3) Auditoriums.

(4) Multipurpose rooms.

(5) Mental Health and Behavioral Sciences Service i.e. group therapy rooms.

(6) Emergency generator rooms.

(7) Kitchen & Dishwashing spaces.

NOTE: Alternatively, provide a gypsum board ceiling or gypsum board lay-in panels both with a 65 mm (2 1/2 in.) sound attenuation blanket for non-VAHBS type of construction where ducts, pipes, etc., make it impractical to extend sound partitions to slabs or deck above. Where gypsum board ceilings with attenuation blankets are used, the double GB partitions and sound attenuation blanket should extend 100 mm (4 in.) above the ceiling. Studs should continue to the floor above. Give special attention to details shown on the construction documents to prevent possible flanking paths for noise transmission.

b. Speech Privacy. Design the sound resistant enclosures of the following spaces to assure speech privacy and achieve an STC rating of 40 (45 for space marked with an asterisk).

PG 18-3 – DESIGN AND CONSTRUCTION PROCEDURES April 2004

NOISE TRANSMISSION CONTROL 11-2

(1) Conference rooms.

(2) Consultation offices.

(3) Examination and Treatment Rooms.

(4) Individual Offices in Mental Health and Behavioral Sciences Service.

(5) Audiology and Speech Pathology Areas.

(6) Medical Media Production Services* (Recording Areas).

NOTE: Partition and ceiling construction should be similar to Paragraph 1.a., except that for spaces requiring an STC value of 40, use only a single layer of gypsum board on both sides.

c. Sound Dampening. Provide sound damping in libraries, chapels, quiet rooms, telephone operator's room, and similar areas by finish materials shown for these areas in Program Guide PG-18-14, "Room Finishes, Door, & Hardware Schedule".

NOTE: Where an area generating unusual noise or vibration is located adjacent to occupied spaces, the A/E should obtain the services of a professional acoustical consultant to design the sound suppression measures required to produce a comfortable working environment in the adjacent spaces.

d. Door Types. Use door types 19 and 20 with mechanical seal at entrances to spaces where noise suppression or speech privacy is a requirement. See VA Standard Detail Nos. 08100- 1.DWG and 08100-2.DWG.

NOTE: Duct system sound attenuation and room noise criteria are shown in the heating, ventilating, and air-conditioning (HVAC) design manual.

3. MECHANICAL AND ELECTRICAL ITEMS: Properly locate, detail, and caulk or insulate penetrations of the sound resistant enclosure by electrical boxes, light fixtures, air conditioning or ventilating ducts and grills, and other mechanical and electrical components to suppress generated noise or provide speech privacy for the spaces listed in paragraph 2.a. and 2.b.

Evaluate equipment and mechanical rooms for noise problems and provide recommendations during the design phase as to additional sound attenuation required. In the analysis, list the possible flanking paths for noise transmission and the methods recommended to prevent this leakage through the enclosure.

4. EXTERIOR ENCLOSURES: In the design of exterior building walls and fenestrations at sites near airports, freeways, or heavy city traffic, give consideration for the control of noise transmission from external sources.