Attachment 4 - VFR2627601A-1.03 Aug 2026.USP Testing.Appendix.pdf

PDF 2 MB Posted

Attached to
VACCHCS Pharmacy Certification
Solicitation number
36C26127Q0099
Issued by

About this file

This document is a Testing and Certification Appendix containing comprehensive laboratory and field testing results for pharmaceutical facility cleanroom certification at VA Fresno (2615 East Clinton Avenue, Fresno, CA 93703), dated August 3, 2026, under Service Order NC-VFR2627601A-1. The testing was conducted by Technical Safety Services (TSS) and covers certification of two Baker EG4252 Clean Bench units (Serial Numbers 86796 and 86809) installed in the InPatient Pharmacy IV Room, along with environmental sampling of Building 1 Sterile Compounding areas.

The certification package includes Unidirectional Flow Device Certification Reports for both units, demonstrating compliance with USP <797>, CETA CAG-003, and IEST-RP-CC002.4 standards. Both units achieved "Unit Certified" status with outflow velocities of 98-99 FPM (within 80-100 FPM specification), zero HEPA filter leakage, and aerosol concentrations of 21 µg/l (within 10-100 µg/l range). Airborne Nonviable Particle Count testing confirmed ISO-5 classification for both units with zero particle counts ≥0.5 µm. Airflow Visualization Studies confirmed unidirectional flow patterns without reflux in both benches. Additionally, comprehensive viable and non-viable environmental sampling was performed across ISO-5, ISO-7, and ISO-8 classified areas, with microbial analysis showing acceptable results per USP <797> and CETA CAG-009 standards. The Ante Room (ISO-8) and IV Room (ISO-7) passed pressurization testing with directional airflow from cleaner to less clean spaces. All NIST-traceable calibration equipment used maintains current calibration through 2026-2027, and retest certification is scheduled for February 2027.

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Unidirectional Flow Device Certification Report

4225 Executive Square, Suite 370

La Jolla, CA 92037

(800) 877-7742

Cert.: DV2683104856 Facility: VA Fresno ID: 300002 Cust ID: 6640-21882

SO: NC-VFR2627601A-1 Addr: 2615 East Clinton Avenue Make: BAKER

Contact: Travis Horn Fresno, CA 93703 Model: EG4252

Phone: (559) 225-6100 Ext.5735 2615 SN: 86796Bld:

Email: Travis.Horn@va.gov InPatient pharmacy IV room Class: NA Type: Clean BenchRm:

Test Standard(s): USP <797>, CETA CAG-003, IEST-RP-CC002.4, USP <797> 2023

Results

Inspected Min Max Measured Results

Outflow Velocity (FPM) 80 100 98 Pass

%RSD NA 15 4 Pass

Supply Delta Pressure ("W.C.) NA NA NA NA

Duct Pressure ("W.C.) NA NA NA NA

Backstreaming Test NA NA Pass Pass

Induction Leak Test NA NA

Fluorescent Lighting (FC)

Ultraviolet Lighting (μW/cm²) NA

NANA

NA

NANA

NA NA

NANoise Level (dBA) NA NA NA

NAVibration (in. RMS) NA NA NA

NAElectrical Current Leakage Test (mA) NA NA NA

NAElectrical Ground Resistance Test (Ohms) NA NA NA

NAElectrical Polarity NA NA NA

NAElectrical GCFI NA NA NA supply Min Max Measured Results

HEPA As Found Max Point Leak (%) 0.000 0.010 0.000 Pass

HEPA As Left Max Point Leak (%) 0.000 0.010 NA NA

Patch (%) 0 3 Pre:0.15/New:0.00/Tot:0.15 Pass

Aerosol Concentration (ug/l) 10 100 21 Pass

Comments:

**** Unit Certified **** The following NIST-Traceable equipment were used to perform this test:

Equipment ID Manufacturer Model Serial No. Cal. Due Date

005672 TSI 9535 T95351923010 05/2027

009016 TEC PH-4 4132 11/2026

012839 TEC AG-E3 4952 10/2026

Report Date: 08/2026 www.techsafety.com

This record was electronically signed by:Retest Date: 02/2027 eData: v8.0.2.2 Daniel Velazquez 08/03/2026 01:50 PM

Print Version: Service Manager v8.0.3.0 Field Service Technician

Print Date: 08/2026 Page: 1/2 I certify that this record is a true and accurate representation of work performed.FIO: For Information Only NA: Not Applicable

Project: NC-VFR2627601A-1 Test Date: 03 Aug 2026

Testing & Certification Appendix

Ver. 20 Aug 2026

La Jolla, CA 92037

(800) 877-7742

Cert.: DV2683104856 Facility: VA Fresno ID: 300002 Cust ID: 6640-21882

SO: NC-VFR2627601A-1 Addr: 2615 East Clinton Avenue Make: BAKER

Contact: Travis Horn Fresno, CA 93703 Model: EG4252

Phone: (559) 225-6100 Ext.5735 2615 SN: 86796Bld:

Email: Travis.Horn@va.gov InPatient pharmacy IV room Class: NA Type: Clean BenchRm:

supply

Velocity (FPM) Dimension: Width: 46.00" Height: 28.00" Average Velocity (FPM) 98

Area (ft²): 8.94

Readings: Volume (CFM): 876

104 100 96 99

102 97 92 96

102 99 93 97

Report Date: 08/2026 www.techsafety.com

This record was electronically signed by:Retest Date: 02/2027 eData: v8.0.2.2 Daniel Velazquez 08/03/2026 01:50 PM

Print Version: Service Manager v8.0.3.0 Field Service Technician

Print Date: 08/2026 Page: 2/2 I certify that this record is a true and accurate representation of work performed.FIO: For Information Only NA: Not Applicable

Project: NC-VFR2627601A-1 Test Date: 03 Aug 2026

Testing & Certification Appendix

La Jolla, CA 92037

(800) 877-7742

Cert. No.: DV2683104735 Svc. Order: NC-VFR2627601A-1 Make: BAKER

Facility: VA Fresno Building: 2615 Model: EG4252

Address: 2615 East Clinton Avenue Room: InPatient pharmacy IV room Unit Type: Clean Bench

Fresno, CA 93703 Contact: Travis Horn SN: 86796

Airborne Nonviable Particle Count Test Report Clean Zone: 86796 Status: Operational/Dynamic Cust ID: 6640-21882 Duration: 1.0 Min(s).

Report Date: 08/2026 Class: ISO-5 Area: 8.94 ft² Flow Rate: 75.0 LPM

Retest Date: 02/2027 Occupants: 1 Total Sample Vol.: 75.0 L

Testing is performed to satisfy ISO 14644-1:2015

Pass PPCM (um) ≥ 0.5

Loc Count 1 Count 2 Count 3 Average Result

1) 0 NA NA 0 Pass

T. C° % rH

25.0 55

Class Limit: 3,520 25.0 55

Sample Volume Test: Pass

Class Limit Location Test: Pass

Airborne Nonviable Particle Count Diagram:

www.techsafety.com

This record was electronically signed by:

Page: 1/2 web: www.techsafety.com Daniel Velazquez 8/3/2026 10:48:03 AM eData v8.0.2.2

Field Service Technician Print Version: Service Manager v8.0.3.0

I certify that this record is a true and accurate representation of work performed.Print Date: 08/20/2026

Project: NC-VFR2627601A-1 Test Date: 03 Aug 2026

Testing & Certification Appendix

(800) 877-7742

Cert. No.: DV2683104735 Svc. Order: NC-VFR2627601A-1 Make: BAKER

Facility: VA Fresno Building: 2615 Model: EG4252

Address: 2615 East Clinton Avenue Room: InPatient pharmacy IV room Unit Type: Clean Bench

Fresno, CA 93703 Contact: Travis Horn SN: 86796

The following NIST-Traceable equipment were used to perform this test:

Equipment ID Manufacturer Model Serial # Calibration Due

013812 Govee H5075 EQ13812 10/2026

009464 Climet CI-750t 057234 11/2026 www.techsafety.com

This record was electronically signed by:

Page: 2/2 web: www.techsafety.com Daniel Velazquez 8/3/2026 10:48:03 AM eData v8.0.2.2

Field Service Technician Print Version: Service Manager v8.0.3.0

I certify that this record is a true and accurate representation of work performed.Print Date: 08/20/2026

Project: NC-VFR2627601A-1 Test Date: 03 Aug 2026

Testing & Certification Appendix

Airflow Visualization Study

La Jolla, CA 92037

(800) 877-7742

Cert.: DV2683104530 Facility: VA Fresno ID: 300002 Cust ID: 6640-21882

SO: NC-VFR2627601A-1 Addr: 2615 East Clinton Avenue Make: BAKER

Contact: Travis Horn Fresno, CA 93703 Model: EG4252

Phone: (559) 225-6100 Ext.5735 2615 SN: 86796Bld:

Email: Travis.Horn@va.gov InPatient pharmacy IV room Class: NA Type: Clean BenchRm:

Service Type: Airflow Visualization Study

Comments: (Dynamic) Tracer moves in a unidirectional manner without reflux. Actions of the personnel do not affect the general trajectory of tracer.

Doc. Title Doc. # Doc. Version Completed Date Originally Retained By

Diagram NA NA 08/03/2026 Daniel Velazquez www.techsafety.com

Report Date: 08/03/2026

This record was electronically signed by:Retest Date: NA eData v8.0.2.2 Daniel Velazquez 08/03/2026 10:46 AM

Print Version: Service Manager v8.0.3.0 Field Service Technician

Print Date: 08/20/2026 Page: 1/2 I certify that this record is a true and accurate representation of work performed.FIO: For Information Only NA: Not Applicable

Project: NC-VFR2627601A-1 Test Date: 03 Aug 2026

Testing & Certification Appendix

La Jolla, CA 92037

(800) 877-7742

Cert.: DV2683104530 Facility: VA Fresno ID: 300002 Cust ID: 6640-21882

SO: NC-VFR2627601A-1 Addr: 2615 East Clinton Avenue Make: BAKER

Contact: Travis Horn Fresno, CA 93703 Model: EG4252

Phone: (559) 225-6100 Ext.5735 2615 SN: 86796Bld:

Email: Travis.Horn@va.gov InPatient pharmacy IV room Class: NA Type: Clean BenchRm:

www.techsafety.com

Report Date: 08/03/2026

This record was electronically signed by:Retest Date: NA eData v8.0.2.2 Daniel Velazquez 08/03/2026 10:46 AM

Print Version: Service Manager v8.0.3.0 Field Service Technician

Print Date: 08/20/2026 Page: 2/2 I certify that this record is a true and accurate representation of work performed.FIO: For Information Only NA: Not Applicable

Project: NC-VFR2627601A-1 Test Date: 03 Aug 2026

Testing & Certification Appendix

La Jolla, CA 92037

(800) 877-7742

Cert.: DV268310498 Facility: VA Fresno ID: 300003 Cust ID: 6640-21883

SO: NC-VFR2627601A-1 Addr: 2615 East Clinton Avenue Make: BAKER

Contact: Travis Horn Fresno, CA 93703 Model: EG4252

Phone: (559) 225-6100 Ext.5735 2615 SN: 86809Bld:

Email: Travis.Horn@va.gov Inpatient Pharmacy IV room Class: NA Type: Clean BenchRm:

Test Standard(s): CETA CAG-003, IEST-RP-CC002.4, USP <797> 2023

Results

Inspected Min Max Measured Results

Outflow Velocity (FPM) 80 100 99 Pass

%RSD NA 15 4 Pass

Supply Delta Pressure ("W.C.) NA NA NA NA

Duct Pressure ("W.C.) NA NA NA NA

Backstreaming Test NA NA Pass Pass

Induction Leak Test NA NA

Fluorescent Lighting (FC)

Ultraviolet Lighting (μW/cm²) NA

NANA

NA

NANA

NA NA

NANoise Level (dBA) NA NA NA

NAVibration (in. RMS) NA NA NA

NAElectrical Current Leakage Test (mA) NA NA NA

NAElectrical Ground Resistance Test (Ohms) NA NA NA

NAElectrical Polarity NA NA NA

NAElectrical GCFI NA NA NA supply Min Max Measured Results

HEPA As Found Max Point Leak (%) 0.000 0.010 0.000 Pass

HEPA As Left Max Point Leak (%) 0.000 0.010 NA NA

Patch (%) 0 3 Pre:0.00/New:0.00/Tot:0.00 Pass

Aerosol Concentration (ug/l) 10 100 21 Pass

Comments:

**** Unit Certified **** The following NIST-Traceable equipment were used to perform this test:

Equipment ID Manufacturer Model Serial No. Cal. Due Date

005672 TSI 9535 T95351923010 05/2027

009016 TEC PH-4 4132 11/2026

012839 TEC AG-E3 4952 10/2026

Report Date: 08/2026 www.techsafety.com

This record was electronically signed by:Retest Date: 02/2027 eData: v8.0.2.2 Daniel Velazquez 08/03/2026 01:56 PM

Print Version: Service Manager v8.0.3.0 Field Service Technician

Print Date: 08/2026 Page: 1/2 I certify that this record is a true and accurate representation of work performed.FIO: For Information Only NA: Not Applicable

Project: NC-VFR2627601A-1 Test Date: 03 Aug 2026

Testing & Certification Appendix

La Jolla, CA 92037

(800) 877-7742

Cert.: DV268310498 Facility: VA Fresno ID: 300003 Cust ID: 6640-21883

SO: NC-VFR2627601A-1 Addr: 2615 East Clinton Avenue Make: BAKER

Contact: Travis Horn Fresno, CA 93703 Model: EG4252

Phone: (559) 225-6100 Ext.5735 2615 SN: 86809Bld:

Email: Travis.Horn@va.gov Inpatient Pharmacy IV room Class: NA Type: Clean BenchRm:

Velocity (FPM) Dimension: Width: 46.00" Height: 28.00" Average Velocity (FPM) 99

Area (ft²): 8.94

Readings: Volume (CFM): 885

92 105 96 98

102 94 97 101

103 95 96 104

Report Date: 08/2026 www.techsafety.com

This record was electronically signed by:Retest Date: 02/2027 eData: v8.0.2.2 Daniel Velazquez 08/03/2026 01:56 PM

Print Version: Service Manager v8.0.3.0 Field Service Technician

Print Date: 08/2026 Page: 2/2 I certify that this record is a true and accurate representation of work performed.FIO: For Information Only NA: Not Applicable

Project: NC-VFR2627601A-1 Test Date: 03 Aug 2026

Testing & Certification Appendix

(800) 877-7742

Cert. No.: DV2683104810 Svc. Order: NC-VFR2627601A-1 Make: BAKER

Facility: VA Fresno Building: 2615 Model: EG4252

Address: 2615 East Clinton Avenue Room: Inpatient Pharmacy IV room Unit Type: Clean Bench

Fresno, CA 93703 Contact: Travis Horn SN: 86809

Airborne Nonviable Particle Count Test Report Clean Zone: 86809 Status: Operational/Dynamic Cust ID: 6640-21883 Duration: 1.0 Min(s).

Report Date: 08/2026 Class: ISO-5 Area: 8.94 ft² Flow Rate: 75.0 LPM

Retest Date: 02/2027 Occupants: 1 Total Sample Vol.: 75.0 L

Testing is performed to satisfy ISO 14644-1:2015

Pass PPCM (um) ≥ 0.5

Loc Count 1 Count 2 Count 3 Average Result

1) 0 NA NA 0 Pass

T. C° % rH

24.9 54

Class Limit: 3,520 24.9 54

Sample Volume Test: Pass

Class Limit Location Test: Pass

Airborne Nonviable Particle Count Diagram:

www.techsafety.com

This record was electronically signed by:

Page: 1/2 web: www.techsafety.com Daniel Velazquez 8/3/2026 10:48:41 AM eData v8.0.2.2

Field Service Technician Print Version: Service Manager v8.0.3.0

I certify that this record is a true and accurate representation of work performed.Print Date: 08/20/2026

Project: NC-VFR2627601A-1 Test Date: 03 Aug 2026

Testing & Certification Appendix

(800) 877-7742

Cert. No.: DV2683104810 Svc. Order: NC-VFR2627601A-1 Make: BAKER

Facility: VA Fresno Building: 2615 Model: EG4252

Address: 2615 East Clinton Avenue Room: Inpatient Pharmacy IV room Unit Type: Clean Bench

Fresno, CA 93703 Contact: Travis Horn SN: 86809

The following NIST-Traceable equipment were used to perform this test:

Equipment ID Manufacturer Model Serial # Calibration Due

013812 Govee H5075 EQ13812 10/2026

009464 Climet CI-750t 057234 11/2026 www.techsafety.com

This record was electronically signed by:

Page: 2/2 web: www.techsafety.com Daniel Velazquez 8/3/2026 10:48:41 AM eData v8.0.2.2

Field Service Technician Print Version: Service Manager v8.0.3.0

I certify that this record is a true and accurate representation of work performed.Print Date: 08/20/2026

Project: NC-VFR2627601A-1 Test Date: 03 Aug 2026

Testing & Certification Appendix

La Jolla, CA 92037

(800) 877-7742

Cert.: DV268310476 Facility: VA Fresno ID: 300003 Cust ID: 6640-21883

SO: NC-VFR2627601A-1 Addr: 2615 East Clinton Avenue Make: BAKER

Contact: Travis Horn Fresno, CA 93703 Model: EG4252

Phone: (559) 225-6100 Ext.5735 2615 SN: 86809Bld:

Email: Travis.Horn@va.gov Inpatient Pharmacy IV room Class: NA Type: Clean BenchRm:

Service Type: Airflow Visualization Study

Comments: (Dynamic) Tracer moves in a unidirectional manner without reflux. Actions of the personnel do not affect the general trajectory of tracer.

Doc. Title Doc. # Doc. Version Completed Date Originally Retained By

Diagram NA NA 08/03/2026 Daniel Velazquez www.techsafety.com

Report Date: 08/03/2026

This record was electronically signed by:Retest Date: NA eData v8.0.2.2 Daniel Velazquez 08/03/2026 10:47 AM

Print Version: Service Manager v8.0.3.0 Field Service Technician

Print Date: 08/20/2026 Page: 1/2 I certify that this record is a true and accurate representation of work performed.FIO: For Information Only NA: Not Applicable

Project: NC-VFR2627601A-1 Test Date: 03 Aug 2026

Testing & Certification Appendix

La Jolla, CA 92037

(800) 877-7742

Cert.: DV268310476 Facility: VA Fresno ID: 300003 Cust ID: 6640-21883

SO: NC-VFR2627601A-1 Addr: 2615 East Clinton Avenue Make: BAKER

Contact: Travis Horn Fresno, CA 93703 Model: EG4252

Phone: (559) 225-6100 Ext.5735 2615 SN: 86809Bld:

Email: Travis.Horn@va.gov Inpatient Pharmacy IV room Class: NA Type: Clean BenchRm:

www.techsafety.com

Report Date: 08/03/2026

This record was electronically signed by:Retest Date: NA eData v8.0.2.2 Daniel Velazquez 08/03/2026 10:47 AM

Print Version: Service Manager v8.0.3.0 Field Service Technician

Print Date: 08/20/2026 Page: 2/2 I certify that this record is a true and accurate representation of work performed.FIO: For Information Only NA: Not Applicable

Project: NC-VFR2627601A-1 Test Date: 03 Aug 2026

Testing & Certification Appendix

Viable Sample Report

La Jolla, CA 92037

800.877.7742

Cert.: DV268310656 Facility: VA Fresno ID: 20998566 Cust ID: NA

SO: NC-VFR2627601A-1 Addr: 2615 East Clinton Avenue Make: NA

Contact: Travis Horn Fresno, CA 93703 Model: NA

Phone: (559) 225-6100 Ext.5735 Bld: 1 SN: **Semi Annual** Building 1 Sterile Compounding

Email: Travis.Horn@va.gov Rm: Building 1 Sterile Compoundin Class: NA Type: Environmental Sampling

Area Status: Operational/Dynamic

Occupants: TSS: 1 Client: 1

14 - Active Air Samples

Sample ID Location Type

Sample Size Media Lot # Exp. Date

A-01 ISO-5 1000 Liters TSA Settling Plate 681632P 08/2026

A-02 ISO-5 1000 Liters TSA Settling Plate 681632P 08/2026

A-03 ISO-5 1000 Liters TSA Settling Plate 681632P 08/2026

A-04 ISO-5 1000 Liters TSA Settling Plate 681632P 08/2026

A-06 ISO-7 1000 Liters TSA Settling Plate 681632P 08/2026

A-07 ISO-7 1000 Liters TSA Settling Plate 681632P 08/2026

A-08 ISO-7 1000 Liters TSA Settling Plate 681632P 08/2026

A-10 ISO-8 1000 Liters TSA Settling Plate 681632P 08/2026

A-11 ISO-8 1000 Liters TSA Settling Plate 681632P 08/2026

A-12 ISO-8 1000 Liters TSA Settling Plate 681632P 08/2026

A-13 ISO-8 1000 Liters TSA Settling Plate 681632P 08/2026

A-18 CNC 1000 Liters TSA Settling Plate 681632P 08/2026

A-19 CNC 1000 Liters TSA Settling Plate 681632P 08/2026

Control NA NA TSA Settling Plate 681632P 08/2026

14 - Surface Samples

Sample ID Location Type

Sample Size Media Lot # Exp. Date

Control NA NA TSA Contact Plate 684400P 10/2026

S-01 ISO-5 1 Plate TSA Contact Plate 684400P 10/2026

S-02 ISO-5 1 Plate TSA Contact Plate 684400P 10/2026

S-03 ISO-5 1 Plate TSA Contact Plate 684400P 10/2026

S-04 ISO-5 1 Plate TSA Contact Plate 684400P 10/2026

S-06 ISO-7 1 Plate TSA Contact Plate 684400P 10/2026

S-07 ISO-7 1 Plate TSA Contact Plate 684400P 10/2026

S-08 ISO-7 1 Plate TSA Contact Plate 684400P 10/2026

S-10 ISO-8 1 Plate TSA Contact Plate 684400P 10/2026

S-11 ISO-8 1 Plate TSA Contact Plate 684400P 10/2026

S-12 ISO-8 1 Plate TSA Contact Plate 684400P 10/2026

S-13 ISO-8 1 Plate TSA Contact Plate 684400P 10/2026 www.techsafety.com

08/2026Sample Date: This record was electronically signed by:

Daniel Velazquez 08/03/2026 10:42 AM eData: v 8.0.2.2

Field Service Technician Print Version: Service Manager v8.0.3.0

I certify that this record is a true and accurate representation of work performed.

Print Date: 08/2026 Page: 1/4

Project: NC-VFR2627601A-1 Test Date: 03 Aug 2026

Testing & Certification Appendix

La Jolla, CA 92037

800.877.7742

Cert.: DV268310656 Facility: VA Fresno ID: 20998566 Cust ID: NA

SO: NC-VFR2627601A-1 Addr: 2615 East Clinton Avenue Make: NA

Contact: Travis Horn Fresno, CA 93703 Model: NA

Phone: (559) 225-6100 Ext.5735 Bld: 1 SN: **Semi Annual** Building 1 Sterile Compounding

Email: Travis.Horn@va.gov Rm: Building 1 Sterile Compoundin Class: NA Type: Environmental Sampling

14 - Surface Samples

Sample ID Location Type

Sample Size Media Lot # Exp. Date

S-18 CNC 1 Plate TSA Contact Plate 684400P 10/2026

S-19 CNC 1 Plate TSA Contact Plate 684400P 10/2026

Remarks: NA www.techsafety.com

08/2026Sample Date: This record was electronically signed by:

Daniel Velazquez 08/03/2026 10:42 AM eData: v 8.0.2.2

Field Service Technician Print Version: Service Manager v8.0.3.0

I certify that this record is a true and accurate representation of work performed.

Print Date: 08/2026 Page: 2/4

Project: NC-VFR2627601A-1 Test Date: 03 Aug 2026

Testing & Certification Appendix

La Jolla, CA 92037

800.877.7742

Cert.: DV268310656 Facility: VA Fresno ID: 20998566 Cust ID: NA

SO: NC-VFR2627601A-1 Addr: 2615 East Clinton Avenue Make: NA

Contact: Travis Horn Fresno, CA 93703 Model: NA

Phone: (559) 225-6100 Ext.5735 Bld: 1 SN: **Semi Annual** Building 1 Sterile Compounding

Email: Travis.Horn@va.gov Rm: Building 1 Sterile Compoundin Class: NA Type: Environmental Sampling www.techsafety.com

08/2026Sample Date: This record was electronically signed by:

Daniel Velazquez 08/03/2026 10:42 AM eData: v 8.0.2.2

Field Service Technician Print Version: Service Manager v8.0.3.0

I certify that this record is a true and accurate representation of work performed.

Print Date: 08/2026 Page: 3/4

Project: NC-VFR2627601A-1 Test Date: 03 Aug 2026

Testing & Certification Appendix

La Jolla, CA 92037

800.877.7742

Cert.: DV268310656 Facility: VA Fresno ID: 20998566 Cust ID: NA

SO: NC-VFR2627601A-1 Addr: 2615 East Clinton Avenue Make: NA

Contact: Travis Horn Fresno, CA 93703 Model: NA

Phone: (559) 225-6100 Ext.5735 Bld: 1 SN: **Semi Annual** Building 1 Sterile Compounding

Email: Travis.Horn@va.gov Rm: Building 1 Sterile Compoundin Class: NA Type: Environmental Sampling

The following NIST-Traceable equipment were used to collect these viable samples:

Equipment ID Manufacturer Model Serial # Calibration Due

012632 AP BUCK B30120 C103665 10/24/2026

012638 AP BUCK B30120 C103671 10/24/2026

www.techsafety.com

08/2026Sample Date: This record was electronically signed by:

Daniel Velazquez 08/03/2026 10:42 AM eData: v 8.0.2.2

Field Service Technician Print Version: Service Manager v8.0.3.0

I certify that this record is a true and accurate representation of work performed.

Print Date: 08/2026 Page: 4/4

Project: NC-VFR2627601A-1 Test Date: 03 Aug 2026

Testing & Certification Appendix

(800) 877-7742

Test Report

General Information:

Project Site: VA Fresno

2615 East Clinton Avenue

Fresno, CA 93703

Room: Hazardous Storage Room

Test Report ID: DV2683104922

Project ID: NC-VFR2627601A-1

Project Contact: Travis Horn

VFR01 | VA Fresno

(559) 225-6100

Travis.Horn@va.gov

Project Lead Tech: Daniel Velazquez

823 Kifer Rd

Sunnyvale, CA 94086 tel: (800) 877-7742 fax: (510) 845-5595

Project Description: AL T3 Semi-Annual, VA Fresno-Pharmacy Certification Bld 1, AUG 2026

Technician Remarks: NA

Test Standards: TSS SOP 05.06.01.00, USP <800> www.techsafety.com

Report Date: 08/03/2026

This record was electronically signed by:Retest Date: 02/2027 eData: v 8.0.2.2

Daniel Velazquez 08/03/2026 02:20 PM Print Version: Service Manager v8.0.3.0

Field Service TechnicianPrint Date: 08/20/2026 Page: 1/5 I certify that this record is a true and accurate representation of work performed.FIO: For Information Only NA: Not Applicable

Project: NC-VFR2627601A-1 Test Date: 03 Aug 2026

Testing & Certification Appendix

(800) 877-7742

Client: VA Fresno Test Date(s): 08/2026 Room: Hazardous Storage Room

Proj. ID: NC-VFR2627601A-1 Technician: Daniel Velazquez Report ID: DV2683104922

Room Description:

Building: 1

Room: Hazardous Storage Room

Room Size:

Area (ft²): 75.78 Volume (ft³): 594

Area (m²): 7.04 Volume (m³): 17

Room Design:

NA

Results

Inspected Min Max Measured Results

Airflow Volume (CFM) NA NA 211 FIO

Grand Mean (FPM) NA NA NA NA

Airflow Uniformity (%RSD) NA NA NA NA

Average Velocities (FPM) * * * FIO

Individual Unit Uniformity (%RSD) * * * NA

Leak Test (%) * * * NA

Patch (% of Filter Area) * * * NA

Room Air Exchange Rate (AC/H) 12 NA 21 Pass

Airborne Nonviable Particle Count * * * NA

Differential Pressure * * * Pass

* Footnote – Results are aggregate of all units tested; individual unit criterion noted in the following pages.

www.techsafety.com

Report Date: 08/03/2026

This record was electronically signed by:Retest Date: 02/2027 eData: v 8.0.2.2

Daniel Velazquez 08/03/2026 02:20 PM Print Version: Service Manager v8.0.3.0

Field Service TechnicianPrint Date: 08/20/2026 Page: 2/5 I certify that this record is a true and accurate representation of work performed.FIO: For Information Only NA: Not Applicable

Project: NC-VFR2627601A-1 Test Date: 03 Aug 2026

Testing & Certification Appendix

(800) 877-7742

Client: VA Fresno Test Date(s): 08/2026 Room: Hazardous Storage Room

Proj. ID: NC-VFR2627601A-1 Technician: Daniel Velazquez Report ID: DV2683104922

TAF AIRFLOW MEASUREMENTS: Hazardous Storage Room

Filter ID Individual Measurements Lower Limit

Upper Limit

Avg Vel (fpm)

Area (ft²)

Kv Avg Vol (cfm)

%RSD

Limit

%RSD ΔP Result

Cert. ID: EE848EA2-9D6C-44F8-9F20-B49B0125B790

NA NA 53 4.00 1.00 211 NA NA NA FIOExhaust (CFM) 211 comments: NA www.techsafety.com

Report Date: 08/03/2026

This record was electronically signed by:Retest Date: 02/2027 eData: v 8.0.2.2

Daniel Velazquez 08/03/2026 02:20 PM Print Version: Service Manager v8.0.3.0

Field Service TechnicianPrint Date: 08/20/2026 Page: 3/5 I certify that this record is a true and accurate representation of work performed.FIO: For Information Only NA: Not Applicable

Project: NC-VFR2627601A-1 Test Date: 03 Aug 2026

Testing & Certification Appendix

(800) 877-7742

Client: VA Fresno Test Date(s): 08/2026 Room: Hazardous Storage Room

Proj. ID: NC-VFR2627601A-1 Technician: Daniel Velazquez Report ID: DV2683104922

Pressurization Data

Zone (+) Zone (-) Actual ΔP ("wc)

Min ΔP ("wc)

Max ΔP ("wc)

Directional Airflow

Door Gauge Readings ("wc) Meets CriteriaClosed ("wc) Open ("wc)

Ambient Room Hazardous Storage Room

0.011 0.0001 NA Pass 0.011 0.000 Yes comments: NA www.techsafety.com

Report Date: 08/03/2026

This record was electronically signed by:Retest Date: 02/2027 eData: v 8.0.2.2

Daniel Velazquez 08/03/2026 02:20 PM Print Version: Service Manager v8.0.3.0

Field Service TechnicianPrint Date: 08/20/2026 Page: 4/5 I certify that this record is a true and accurate representation of work performed.FIO: For Information Only NA: Not Applicable

Project: NC-VFR2627601A-1 Test Date: 03 Aug 2026

Testing & Certification Appendix

(800) 877-7742

Client: VA Fresno Test Date(s): 08/2026 Room: Hazardous Storage Room

Proj. ID: NC-VFR2627601A-1 Technician: Daniel Velazquez Report ID: DV2683104922

The following NIST-Traceable equipment were used to perform this test:

Equipment ID Manufacturer Model Serial # Calibration Due

006337 Evergreen Telemetry S-PVF-1 1900817C 10/2026

009747 Evergreen Telemetry Wrist Reporter WR-401 2C03501 08/2026

009752 Evergreen Telemetry Three Pounder 2200368B 08/2026 www.techsafety.com

Report Date: 08/03/2026

This record was electronically signed by:Retest Date: 02/2027 eData: v 8.0.2.2

Daniel Velazquez 08/03/2026 02:20 PM Print Version: Service Manager v8.0.3.0

Field Service TechnicianPrint Date: 08/20/2026 Page: 5/5 I certify that this record is a true and accurate representation of work performed.FIO: For Information Only NA: Not Applicable

Project: NC-VFR2627601A-1 Test Date: 03 Aug 2026

Testing & Certification Appendix

(800) 877-7742

Test Report

General Information:

Project Site: VA Fresno

2615 East Clinton Avenue

Fresno, CA 93703

Room: Ante Room

Test Report ID: DV2683104251

Project ID: NC-VFR2627601A-1

Project Contact: Travis Horn

VFR01 | VA Fresno

(559) 225-6100

Travis.Horn@va.gov

Project Lead Tech: Daniel Velazquez

823 Kifer Rd

Sunnyvale, CA 94086 tel: (800) 877-7742 fax: (510) 845-5595

Project Description: AL T3 Semi-Annual, VA Fresno-Pharmacy Certification Bld 1, AUG 2026

Technician Remarks: NA

Test Standards: TSS SOP 05.06.01.00, CETA CAG-003, IEST-RP-CC006, USP <797> 2023 www.techsafety.com

Report Date: 08/03/2026

This record was electronically signed by:Retest Date: 02/2027 eData: v 8.0.2.2

Daniel Velazquez 08/03/2026 02:15 PM Print Version: Service Manager v8.0.3.0

Field Service TechnicianPrint Date: 08/20/2026 Page: 1/9 I certify that this record is a true and accurate representation of work performed.FIO: For Information Only NA: Not Applicable

Project: NC-VFR2627601A-1 Test Date: 03 Aug 2026

Testing & Certification Appendix

(800) 877-7742

Client: VA Fresno Test Date(s): 08/2026 Room: Ante Room

Proj. ID: NC-VFR2627601A-1 Technician: Daniel Velazquez Report ID: DV2683104251

Room Description:

Building: 2615

Room: Ante Room

Room Size:

Area (ft²): 142.36 Volume (ft³): 1,365

Area (m²): 13.23 Volume (m³): 39

Room Design:

ISO-8

Results

Inspected Min Max Measured Results

Airflow Volume (CFM) NA NA 478 FIO

Grand Mean (FPM) NA NA NA NA

Airflow Uniformity (%RSD) NA NA NA NA

Average Velocities (FPM) * * * Pass

Individual Unit Uniformity (%RSD) * * * NA

Leak Test (%) * * * Pass

Patch (% of Filter Area) * * * Pass

Room Air Exchange Rate (AC/H) 15 NA 21 Pass

PEC Air Exchange Rate (AC/H) NA NA 48 FIO

Room Air Exchange Rate + PEC (AC/H) 20 NA 69 Pass

Airborne Nonviable Particle Count * * * Pass

Differential Pressure * * * Pass

* Footnote – Results are aggregate of all units tested; individual unit criterion noted in the following pages.

www.techsafety.com

Report Date: 08/03/2026

This record was electronically signed by:Retest Date: 02/2027 eData: v 8.0.2.2

Daniel Velazquez 08/03/2026 02:15 PM Print Version: Service Manager v8.0.3.0

Field Service TechnicianPrint Date: 08/20/2026 Page: 2/9 I certify that this record is a true and accurate representation of work performed.FIO: For Information Only NA: Not Applicable

Project: NC-VFR2627601A-1 Test Date: 03 Aug 2026

Testing & Certification Appendix

(800) 877-7742

Client: VA Fresno Test Date(s): 08/2026 Room: Ante Room

Proj. ID: NC-VFR2627601A-1 Technician: Daniel Velazquez Report ID: DV2683104251

TAF AIRFLOW MEASUREMENTS: Ante Room

Filter ID Individual Measurements Lower Limit

Upper Limit

Avg Vel (fpm)

Area (ft²)

Kv Avg Vol (cfm)

%RSD

Limit

%RSD ΔP Result

Cert. ID: 84C894DE-5BF3-4426-A3DA-B49B0123ECB9

0 1,000 94 5.10 1.00 478 NA NA NA PassTAF-1 (CFM) 478 comments: NA www.techsafety.com

Report Date: 08/03/2026

This record was electronically signed by:Retest Date: 02/2027 eData: v 8.0.2.2

Daniel Velazquez 08/03/2026 02:15 PM Print Version: Service Manager v8.0.3.0

Field Service TechnicianPrint Date: 08/20/2026 Page: 3/9 I certify that this record is a true and accurate representation of work performed.FIO: For Information Only NA: Not Applicable

Project: NC-VFR2627601A-1 Test Date: 03 Aug 2026

Testing & Certification Appendix

(800) 877-7742

Client: VA Fresno Test Date(s): 08/2026 Room: Ante Room

Proj. ID: NC-VFR2627601A-1 Technician: Daniel Velazquez Report ID: DV2683104251

TAF INSTALLATION LEAK TEST RESULTS: Ante Room

PAO (μg/l)% Patched AreaFilter ID

Initial Final

Leakage Diagram (Magnitude, Location, and Dimension)

% Leak Conc. Result

Conc.Max Min Max Initial Final Max

TAF-1 No Diagram 0.00 0.00 3.00 26 10 100 0.000 NA 0.010 Pass comments: NA www.techsafety.com

Report Date: 08/03/2026

This record was electronically signed by:Retest Date: 02/2027 eData: v 8.0.2.2

Daniel Velazquez 08/03/2026 02:15 PM Print Version: Service Manager v8.0.3.0

Field Service TechnicianPrint Date: 08/20/2026 Page: 4/9 I certify that this record is a true and accurate representation of work performed.FIO: For Information Only NA: Not Applicable

Project: NC-VFR2627601A-1 Test Date: 03 Aug 2026

Testing & Certification Appendix

(800) 877-7742

Client: VA Fresno Test Date(s): 08/2026 Room: Ante Room

Proj. ID: NC-VFR2627601A-1 Technician: Daniel Velazquez Report ID: DV2683104251

Pressurization Data

Zone (+) Zone (-) Actual ΔP ("wc)

Min ΔP ("wc)

Max ΔP ("wc)

Directional Airflow

Door Gauge Readings ("wc) Meets CriteriaClosed ("wc) Open ("wc)

Ante Room Ambient Room 0.073 0.020 NA Pass 0.091 0.000 Yes comments: NA www.techsafety.com

Report Date: 08/03/2026

This record was electronically signed by:Retest Date: 02/2027 eData: v 8.0.2.2

Daniel Velazquez 08/03/2026 02:15 PM Print Version: Service Manager v8.0.3.0

Field Service TechnicianPrint Date: 08/20/2026 Page: 5/9 I certify that this record is a true and accurate representation of work performed.FIO: For Information Only NA: Not Applicable

Project: NC-VFR2627601A-1 Test Date: 03 Aug 2026

Testing & Certification Appendix

(800) 877-7742

Client: VA Fresno Test Date(s): 08/2026 Room: Ante Room

Proj. ID: NC-VFR2627601A-1 Technician: Daniel Velazquez Report ID: DV2683104251

Airborne Nonviable Particle Count Test Report Clean Zone: Ante Room Status: Operational/Dynamic Cust ID: NA Duration: 1.0 Min(s).

Report Date: 08/2026 Class: ISO-8 Area: 142.36 ft² Flow Rate: 75.0 LPM

Retest Date: 02/2027 Occupants: 1 Total Sample Vol.: 75.0 L

Testing is performed to satisfy ISO 14644-1:2015

Pass PPCM (um) ≥ 0.5

Loc Count 1 Count 2 Count 3 Average Result

1) 3146 NA NA 3146 Pass

2) 1826 NA NA 1826 Pass

3) 2706 NA NA 2706 Pass

4) 4653 NA NA 4653 Pass

5) 3813 NA NA 3813 Pass

6) 2840 NA NA 2840 Pass

T. C° % rH

22.1 55

22.4 54

22.5 56

22.5 56

22.4 55

22.4 55

Class Limit: 3,520,000 22.4 55

Sample Volume Test: Pass

Class Limit Location Test: Pass www.techsafety.com

Report Date: 08/03/2026

This record was electronically signed by:Retest Date: 02/2027 eData: v 8.0.2.2

Daniel Velazquez 08/03/2026 02:15 PM Print Version: Service Manager v8.0.3.0

Field Service TechnicianPrint Date: 08/20/2026 Page: 6/9 I certify that this record is a true and accurate representation of work performed.FIO: For Information Only NA: Not Applicable

Project: NC-VFR2627601A-1 Test Date: 03 Aug 2026

Testing & Certification Appendix

(800) 877-7742

Client: VA Fresno Test Date(s): 08/2026 Room: Ante Room

Proj. ID: NC-VFR2627601A-1 Technician: Daniel Velazquez Report ID: DV2683104251

Airborne Nonviable Particle Count Test Report Clean Zone: Ante Room Status: Operational/Dynamic Cust ID: NA Duration: 1.0 Min(s).

Report Date: 08/2026 Class: ISO-8 Area: 142.36 ft² Flow Rate: 75.0 LPM

Retest Date: 02/2027 Occupants: 1 Total Sample Vol.: 75.0 L

Airborne Nonviable Particle Count Diagram:

www.techsafety.com

Report Date: 08/03/2026

This record was electronically signed by:Retest Date: 02/2027 eData: v 8.0.2.2

Daniel Velazquez 08/03/2026 02:15 PM Print Version: Service Manager v8.0.3.0

Field Service TechnicianPrint Date: 08/20/2026 Page: 7/9 I certify that this record is a true and accurate representation of work performed.FIO: For Information Only NA: Not Applicable

Project: NC-VFR2627601A-1 Test Date: 03 Aug 2026

Testing & Certification Appendix

(800) 877-7742

Client: VA Fresno Test Date(s): 08/2026 Room: Ante Room

Proj. ID: NC-VFR2627601A-1 Technician: Daniel Velazquez Report ID: DV2683104251

Cleanroom Diagram:

www.techsafety.com

Report Date: 08/03/2026

This record was electronically signed by:Retest Date: 02/2027 eData: v 8.0.2.2

Daniel Velazquez 08/03/2026 02:15 PM Print Version: Service Manager v8.0.3.0

Field Service TechnicianPrint Date: 08/20/2026 Page: 8/9 I certify that this record is a true and accurate representation of work performed.FIO: For Information Only NA: Not Applicable

Project: NC-VFR2627601A-1 Test Date: 03 Aug 2026

Testing & Certification Appendix

(800) 877-7742

Client: VA Fresno Test Date(s): 08/2026 Room: Ante Room

Proj. ID: NC-VFR2627601A-1 Technician: Daniel Velazquez Report ID: DV2683104251

The following NIST-Traceable equipment were used to perform this test:

Equipment ID Manufacturer Model Serial # Calibration Due

006337 Evergreen Telemetry S-PVF-1 1900817C 10/2026

009016 TEC PH-4 4132 11/2026

009464 Climet CI-750t 057234 11/2026

009747 Evergreen Telemetry Wrist Reporter WR-401 2C03501 08/2026

009752 Evergreen Telemetry Three Pounder 2200368B 08/2026

012839 TEC AG-E3 4952 10/2026

013812 Govee H5075 EQ13812 10/2026 www.techsafety.com

Report Date: 08/03/2026

This record was electronically signed by:Retest Date: 02/2027 eData: v 8.0.2.2

Daniel Velazquez 08/03/2026 02:15 PM Print Version: Service Manager v8.0.3.0

Field Service TechnicianPrint Date: 08/20/2026 Page: 9/9 I certify that this record is a true and accurate representation of work performed.FIO: For Information Only NA: Not Applicable

Project: NC-VFR2627601A-1 Test Date: 03 Aug 2026

Testing & Certification Appendix

(800) 877-7742

Test Report

General Information:

Project Site: VA Fresno

2615 East Clinton Avenue

Fresno, CA 93703

Room: IV Room

Test Report ID: DV2683102910

Project ID: NC-VFR2627601A-1

Project Contact: Travis Horn

VFR01 | VA Fresno

(559) 225-6100

Travis.Horn@va.gov

Project Lead Tech: Daniel Velazquez

823 Kifer Rd

Sunnyvale, CA 94086 tel: (800) 877-7742 fax: (510) 845-5595

Project Description: AL T3 Semi-Annual, VA Fresno-Pharmacy Certification Bld 1, AUG 2026

Technician Remarks: NA

Test Standards: CETA CAG-003, IEST-RP-CC006, USP <797> 2023 www.techsafety.com

Report Date: 08/03/2026

This record was electronically signed by:Retest Date: 02/2027 eData: v 8.0.2.2

Daniel Velazquez 08/03/2026 02:04 PM Print Version: Service Manager v8.0.3.0

Field Service TechnicianPrint Date: 08/20/2026 Page: 1/9 I certify that this record is a true and accurate representation of work performed.FIO: For Information Only NA: Not Applicable

Project: NC-VFR2627601A-1 Test Date: 03 Aug 2026

Testing & Certification Appendix

(800) 877-7742

Client: VA Fresno Test Date(s): 08/2026 Room: IV Room

Proj. ID: NC-VFR2627601A-1 Technician: Daniel Velazquez Report ID: DV2683102910

Room Description:

Building: 2615

Room: IV Room

Room Size:

Area (ft²): 75.00 Volume (ft³): 800

Area (m²): 6.97 Volume (m³): 23

Room Design:

ISO-7

Results

Inspected Min Max Measured Results

Airflow Volume (CFM) NA NA 274 FIO

Grand Mean (FPM) NA NA NA NA

Airflow Uniformity (%RSD) NA NA NA NA

Average Velocities (FPM) * * * Pass

Individual Unit Uniformity (%RSD) * * * NA

Leak Test (%) * * * Pass

Patch (% of Filter Area) * * * Pass

Room Air Exchange Rate (AC/H) 15 NA 21 Pass

PEC Air Exchange Rate (AC/H) NA NA 132 FIO

Room Air Exchange Rate + PEC (AC/H) 30 NA 153 Pass

Airborne Nonviable Particle Count * * * Pass

Differential Pressure * * * Pass

* Footnote – Results are aggregate of all units tested; individual unit criterion noted in the following pages.

www.techsafety.com

Report Date: 08/03/2026

This record was electronically signed by:Retest Date: 02/2027 eData: v 8.0.2.2

Daniel Velazquez 08/03/2026 02:04 PM Print Version: Service Manager v8.0.3.0

Field Service TechnicianPrint Date: 08/20/2026 Page: 2/9 I certify that this record is a true and accurate representation of work performed.FIO: For Information Only NA: Not Applicable

Project: NC-VFR2627601A-1 Test Date: 03 Aug 2026

Testing & Certification Appendix

(800) 877-7742

Client: VA Fresno Test Date(s): 08/2026 Room: IV Room

Proj. ID: NC-VFR2627601A-1 Technician: Daniel Velazquez Report ID: DV2683102910

TAF AIRFLOW MEASUREMENTS: IV Room

Filter ID Individual Measurements Lower Limit

Upper Limit

Avg Vel (fpm)

Area (ft²)

Kv Avg Vol (cfm)

%RSD

Limit

%RSD ΔP Result

Cert. ID: A4136827-BA70-45FB-A72D-B49B01202B41

0 1,000 52 2.34 1.00 121 NA NA NA PassTAF-1 (CFM) 121 comments: NA

Cert. ID: A5F8729D-15D0-433F-8A29-B49B01202B45

0 1,000 65 2.34 1.00 153 NA NA NA PassTAF-2 (CFM) 153 comments: NA www.techsafety.com

Report Date: 08/03/2026

This record was electronically signed by:Retest Date: 02/2027 eData: v 8.0.2.2

Daniel Velazquez 08/03/2026 02:04 PM Print Version: Service Manager v8.0.3.0

Field Service TechnicianPrint Date: 08/20/2026 Page: 3/9 I certify that this record is a true and accurate representation of work performed.FIO: For Information Only NA: Not Applicable

Project: NC-VFR2627601A-1 Test Date: 03 Aug 2026

Testing & Certification Appendix

(800) 877-7742

Client: VA Fresno Test Date(s): 08/2026 Room: IV Room

Proj. ID: NC-VFR2627601A-1 Technician: Daniel Velazquez Report ID: DV2683102910

TAF INSTALLATION LEAK TEST RESULTS: IV Room

PAO (μg/l)% Patched AreaFilter ID

Initial Final

Leakage Diagram (Magnitude, Location, and Dimension)

% Leak Conc. Result

Conc.Max Min Max Initial Final Max

TAF-1 No Diagram 0.00 0.00 3.00 26 10 100 0.000 NA 0.010 Pass comments: NA

TAF-2 No Diagram 0.00 0.00 3.00 26 10 100 0.000 NA 0.010 Pass comments: NA www.techsafety.com

Report Date: 08/03/2026

This record was electronically signed by:Retest Date: 02/2027 eData: v 8.0.2.2

Daniel Velazquez 08/03/2026 02:04 PM Print Version: Service Manager v8.0.3.0

Field Service TechnicianPrint Date: 08/20/2026 Page: 4/9 I certify that this record is a true and accurate representation of work performed.FIO: For Information Only NA: Not Applicable

Project: NC-VFR2627601A-1 Test Date: 03 Aug 2026

Testing & Certification Appendix

(800) 877-7742

Client: VA Fresno Test Date(s): 08/2026 Room: IV Room

Proj. ID: NC-VFR2627601A-1 Technician: Daniel Velazquez Report ID: DV2683102910

Pressurization Data

Zone (+) Zone (-) Actual ΔP ("wc)

Min ΔP ("wc)

Max ΔP ("wc)

Directional Airflow

Door Gauge Readings ("wc) Meets CriteriaClosed ("wc) Open ("wc)

IV Room Ante Room 0.163 0.020 NA Pass 0.170 0.000 Yes comments: NA www.techsafety.com

Report Date: 08/03/2026

This record was electronically signed by:Retest Date: 02/2027 eData: v 8.0.2.2

Daniel Velazquez 08/03/2026 02:04 PM Print Version: Service Manager v8.0.3.0

Field Service TechnicianPrint Date: 08/20/2026 Page: 5/9 I certify that this record is a true and accurate representation of work performed.FIO: For Information Only NA: Not Applicable

Project: NC-VFR2627601A-1 Test Date: 03 Aug 2026

Testing & Certification Appendix

(800) 877-7742

Client: VA Fresno Test Date(s): 08/2026 Room: IV Room

Proj. ID: NC-VFR2627601A-1 Technician: Daniel Velazquez Report ID: DV2683102910

Airborne Nonviable Particle Count Test Report Clean Zone: IV Room Status: Operational/Dynamic Cust ID: NA Duration: 1.0 Min(s).

Report Date: 08/2026 Class: ISO-7 Area: 75.00 ft² Flow Rate: 75.0 LPM

Retest Date: 02/2027 Occupants: 1 Total Sample Vol.: 75.0 L

Testing is performed to satisfy ISO 14644-1:2015

Pass PPCM (um) ≥ 0.5

Loc Count 1 Count 2 Count 3 Average Result

1) 1080 NA NA 1080 Pass

2) 506 NA NA 506 Pass

3) 546 NA NA 546 Pass

4) 2693 NA NA 2693 Pass

T. C° % rH

24.7 53

24.7 52

24.8 54

24.9 55

Class Limit: 352,000 24.8 53

Sample Volume Test: Pass

Class Limit Location Test: Pass www.techsafety.com

Report Date: 08/03/2026

This record was electronically signed by:Retest Date: 02/2027 eData: v 8.0.2.2

Daniel Velazquez 08/03/2026 02:04 PM Print Version: Service Manager v8.0.3.0

Field Service TechnicianPrint Date: 08/20/2026 Page: 6/9 I certify that this record is a true and accurate representation of work performed.FIO: For Information Only NA: Not Applicable

Project: NC-VFR2627601A-1 Test Date: 03 Aug 2026

Testing & Certification Appendix

(800) 877-7742

Client: VA Fresno Test Date(s): 08/2026 Room: IV Room

Proj. ID: NC-VFR2627601A-1 Technician: Daniel Velazquez Report ID: DV2683102910

Airborne Nonviable Particle Count Test Report Clean Zone: IV Room Status: Operational/Dynamic Cust ID: NA Duration: 1.0 Min(s).

Report Date: 08/2026 Class: ISO-7 Area: 75.00 ft² Flow Rate: 75.0 LPM

Retest Date: 02/2027 Occupants: 1 Total Sample Vol.: 75.0 L

Airborne Nonviable Particle Count Diagram:

www.techsafety.com

Report Date: 08/03/2026

This record was electronically signed by:Retest Date: 02/2027 eData: v 8.0.2.2

Daniel Velazquez 08/03/2026 02:04 PM Print Version: Service Manager v8.0.3.0

Field Service TechnicianPrint Date: 08/20/2026 Page: 7/9 I certify that this record is a true and accurate representation of work performed.FIO: For Information Only NA: Not Applicable

Project: NC-VFR2627601A-1 Test Date: 03 Aug 2026

Testing & Certification Appendix

(800) 877-7742

Client: VA Fresno Test Date(s): 08/2026 Room: IV Room

Proj. ID: NC-VFR2627601A-1 Technician: Daniel Velazquez Report ID: DV2683102910

Cleanroom Diagram:

www.techsafety.com

Report Date: 08/03/2026

This record was electronically signed by:Retest Date: 02/2027 eData: v 8.0.2.2

Daniel Velazquez 08/03/2026 02:04 PM Print Version: Service Manager v8.0.3.0

Field Service TechnicianPrint Date: 08/20/2026 Page: 8/9 I certify that this record is a true and accurate representation of work performed.FIO: For Information Only NA: Not Applicable

Project: NC-VFR2627601A-1 Test Date: 03 Aug 2026

Testing & Certification Appendix

(800) 877-7742

Client: VA Fresno Test Date(s): 08/2026 Room: IV Room

Proj. ID: NC-VFR2627601A-1 Technician: Daniel Velazquez Report ID: DV2683102910

The following NIST-Traceable equipment were used to perform this test:

Equipment ID Manufacturer Model Serial # Calibration Due

006337 Evergreen Telemetry S-PVF-1 1900817C 10/2026

009016 TEC PH-4 4132 11/2026

009464 Climet CI-750t 057234 11/2026

009747 Evergreen Telemetry Wrist Reporter WR-401 2C03501 08/2026

009752 Evergreen Telemetry Three Pounder 2200368B 08/2026

012839 TEC AG-E3 4952 10/2026

013812 Govee H5075 EQ13812 10/2026 www.techsafety.com

Report Date: 08/03/2026

This record was electronically signed by:Retest Date: 02/2027 eData: v 8.0.2.2

Daniel Velazquez 08/03/2026 02:04 PM Print Version: Service Manager v8.0.3.0

Field Service TechnicianPrint Date: 08/20/2026 Page: 9/9 I certify that this record is a true and accurate representation of work performed.FIO: For Information Only NA: Not Applicable

Project: NC-VFR2627601A-1 Test Date: 03 Aug 2026

Testing & Certification Appendix

Single Pass Certification Report

La Jolla, CA 92037

(800) 877-7742

Cert.: DV2683104941 Facility: VA Fresno ID: 348536 Cust ID: NA

SO: NC-VFR2627601A-1 Addr: 2615 East Clinton Avenue Make: OMNITEC DESIGN

Contact: Travis Horn Fresno, CA 93703 Model: 1200

Phone: (559) 225-6100 Ext.5735 2615 SN: 121661Bld:

Email: Travis.Horn@va.gov Ante Room Class: I Type: Single PassRm:

Test Standard(s): MANUFACTURER

Results

Inspected Min Max Measured Results

Average Inflow Velocity (FPM) 0 NA 809 Pass

Minimum Point Reading (FPM) NA NA 699 NA

Airflow Smoke Pattern NA NA Pass Pass

Lighting Flourescent (FC) NA NA NA NA

Lighting Ultraviolet (uW/cm2) NA NA NA NA

Unit Duct Pressure (In.W.C.) NA NA NA NA

Unit Supply Pressure (In.W.C.) NA NA 0.27 FIO

Airflow Monitor NA NA No FIO

Supply Min Max Measured Results

HEPA As Found Max Point Leak (%) 0.000 0.005 0.000 Pass

HEPA As Left Max Point Leak (%) 0.000 0.005 NA NA

Patch (%) 0 3 Pre:0.00/New:0.00/Tot:0.00 Pass

Aerosol Concentration (ug/l) 10 100 17 Pass

Comments:

**** Unit Certified **** The following NIST-Traceable equipment were used to perform this test:

Equipment ID Manufacturer Model Serial No. Cal. Due Date

005672 TSI 9535 T95351923010 05/2027

009016 TEC PH-4 4132 11/2026

012839 TEC AG-E3 4952 10/2026

Inflow (FPM) Dimension (inches): Width: 14.00 Height: 14.00 Average Inflow Velocity(FPM): 809

Area (sq.ft.): 1.36

Readings:

Volume (CFM): 1,100

853 914

699 769

Report Date: 08/2026 www.techsafety.com

This record was electronically signed by:Retest Date: 02/2027 eData: v8.0.2.2 Daniel Velazquez 08/03/2026 02:02 PM

Print Version: Service Manager v8.0.3.0 Field Service Technician

Print Date: 08/2026 Page: 1/1 I certify that this record is a true and accurate representation of work performed.FIO: For Information Only NA: Not Applicable

Project: NC-VFR2627601A-1 Test Date: 03 Aug 2026

Testing & Certification Appendix

823 Kifer Rd Sunnyvale, CA 94086 tel: (800) 877-7742 ISO/IEC 17025:2017 Microbial Analysis Report www.techsafety.com

AT-3296/AT-3296.01

VA Fresno NC-VFR2627601A-1Service Order: Sampled Date: 08/03/2026 Lab Project ID: 2621600029 Received Date: 08/04/2026

Clinton Report Date: 08/12/2026 2615 East Clinton Avenue Fresno, CA 93703

Sample Type

ISO

Class

CFU

ResultSample ID Media Result Comments

TSA Settling Plate ISO-5 0 CFU/m^3 No GrowthA-01 Active Air TSA Settling Plate ISO-5 0 CFU/m^3 No GrowthA-02 Active Air TSA Settling Plate ISO-5 0 CFU/m^3 No GrowthA-03 Active Air TSA Settling Plate ISO-5 0 CFU/m^3 No GrowthA-04 Active Air TSA Settling Plate ISO-7 0 CFU/m^3 No GrowthA-06 Active Air TSA Settling Plate ISO-7 0 CFU/m^3 No GrowthA-07 Active Air TSA Settling Plate ISO-7 0 CFU/m^3 No GrowthA-08 Active Air TSA Settling Plate ISO-8 0 CFU/m^3 No GrowthA-10 Active Air TSA Settling Plate ISO-8 0 CFU/m^3 No GrowthA-11 Active Air TSA Settling Plate ISO-8 0 CFU/m^3 No GrowthA-12 Active Air TSA Settling Plate ISO-8 0 CFU/m^3 No GrowthA-13 Active Air TSA Settling Plate CNC 0 CFU/m^3 No GrowthA-18 Active Air TSA Settling Plate CNC 1 CFU/m^3 FIOA-19 Active Air TSA Settling Plate NA 0 CFU/Plate No GrowthControl Active Air

(Control) TSA Contact Plate NA 0 CFU/Plate No GrowthControl Surface TSA Contact Plate ISO-5 0 CFU/Plate No GrowthS-01 Surface TSA Contact Plate ISO-5 0 CFU/Plate No GrowthS-02 Surface TSA Contact Plate ISO-5 0 CFU/Plate No GrowthS-03 Surface TSA Contact Plate ISO-5 0 CFU/Plate No GrowthS-04 Surface TSA Contact Plate ISO-7 0 CFU/Plate No GrowthS-06 Surface TSA Contact Plate ISO-7 0 CFU/Plate No GrowthS-07 Surface TSA Contact Plate ISO-7 0 CFU/Plate No GrowthS-08 Surface TSA Contact Plate ISO-8 0 CFU/Plate No GrowthS-10 Surface TSA Contact Plate ISO-8 0 CFU/Plate No GrowthS-11 Surface TSA Contact Plate ISO-8 0 CFU/Plate No GrowthS-12 Surface TSA Contact Plate ISO-8 2 CFU/Plate AcceptableS-13 Surface TSA Contact Plate CNC 0 CFU/Plate No GrowthS-18 Surface TSA Contact Plate CNC 0 CFU/Plate No GrowthS-19 Surface

Spacer

Project: NC-VFR2627601A-1 Test Date: 03 Aug 2026

Testing & Certification Appendix tel: (800) 877-7742 ISO/IEC 17025:2017 Microbial Analysis Report www.techsafety.com

AT-3296/AT-3296.01

VA Fresno NC-VFR2627601A-1Service Order: Sampled Date: 08/03/2026 Lab Project ID: 2621600029 Received Date: 08/04/2026

Clinton Report Date: 08/12/2026 2615 East Clinton Avenue Fresno, CA 93703

Sample Type

ISO

Class

CFU

ResultSample ID Media Result Comments

No Growth: No growth of microorganisms. Sample in compliance with USP <797> and CETA CAG-009 guidance documents.

Acceptable: Growth of microorganisms. Sample in compliance with USP <797> and CETA CAG-009 guidance documents.

FIO: For Information Only.

TNTC: Too Numerous to Count.

OOC: Out of Compliance. Unacceptable concentrations. Sample not in compliance with USP <797> and CETA CAG-009 guidance documents.

CFU Result: CFU results are reported as CFU/m³ for all Active Air samples, and CFU/plate for all Surface, Fingertip, and Passive

Air samples. TNTC represents a total CFU count that is innumerable. CFU totals are not applicable for Media Fill samples.

TBD: To be determined.

Report Reviewed/Authorized By: Kristi Molina, MLT(ASCP) (Lab Technologist) 08/12/2026 02:04 pm

Spacer

Project: NC-VFR2627601A-1 Test Date: 03 Aug 2026

Testing & Certification Appendix tel: (800) 877-7742 ISO/IEC 17025:2017 www.techsafety.comMicrobial Analysis ReportAT-3296/AT-3296.01

NC-VFR2627601A-1 Sampled Date: 08/03/2026VA Fresno Service Order:

Lab Project ID: 2621600029 Received Date: 08/04/2026

Clinton Report Date: 08/12/2026 2615 East Clinton Avenue Fresno, CA 93703

Sample ID: A-01 Active Air Lab Sample ID: 2621600029-1

Test: USP <797> 2023 Single Media Dual Incubation ID All Growth Plus Pathogenicity ISO Class: ISO-5 Condition of sample upon receipt: Media in good condition Sample Size: 1000 Liters Positive Holes: 380 Alert Limit: NA Positive Hole Corrected Result: 0 CFU/m^3 Action Limit: 1 Final Result: No Growth Media: TSA Settling Plate Lot: 681632P Exp.2026-08-31

Temperature: 30-35 C Start Date: 08/04/2026 10:19 am PDT End Date: 08/06/2026 03:18 pm PDT

Temperature: 20-25 C Start Date: 08/06/2026 03:18 pm PDT End Date: 08/11/2026 02:38 pm PDT

Sample ID: A-02 Active Air Lab Sample ID: 2621600029-2

Test: USP <797> 2023 Single Media Dual Incubation ID All Growth Plus Pathogenicity ISO Class: ISO-5 Condition of sample upon receipt: Media in good condition Sample Size: 1000 Liters Positive Holes: 380 Alert Limit: NA Positive Hole Corrected Result: 0 CFU/m^3 Action Limit: 1 Final Result: No Growth Media: TSA Settling Plate Lot: 681632P Exp.2026-08-31

Temperature: 30-35 C Start Date: 08/04/2026 10:19 am PDT End Date: 08/06/2026 03:18 pm PDT

Temperature: 20-25 C Start Date: 08/06/2026 03:18 pm PDT End Date: 08/11/2026 02:38 pm PDT

Sample ID: A-03 Active Air Lab Sample ID: 2621600029-3

Test: USP <797> 2023 Single Media Dual Incubation ID All Growth Plus Pathogenicity ISO Class: ISO-5 Condition of sample upon receipt: Media in good condition Sample Size: 1000 Liters Positive Holes: 380 Alert Limit: NA Positive Hole Corrected Result: 0 CFU/m^3 Action Limit: 1 Final Result: No Growth Media: TSA Settling Plate Lot: 681632P Exp.2026-08-31

Temperature: 30-35 C Start Date: 08/04/2026 10:19 am PDT End Date: 08/06/2026 03:18 pm PDT

Temperature: 20-25 C Start Date: 08/06/2026 03:19 pm PDT End Date: 08/11/2026 02:38 pm PDT

Spacer

Project: NC-VFR2627601A-1 Test Date: 03 Aug 2026

Testing & Certification Appendix tel: (800) 877-7742 ISO/IEC 17025:2017 www.techsafety.comMicrobial Analysis ReportAT-3296/AT-3296.01

NC-VFR2627601A-1 Sampled Date: 08/03/2026VA Fresno Service Order:

Lab Project ID: 2621600029 Received Date: 08/04/2026

Clinton Report Date: 08/12/2026 2615 East Clinton Avenue Fresno, CA 93703

Sample ID: A-04 Active Air Lab Sample ID: 2621600029-4

Test: USP <797> 2023 Single Media Dual Incubation ID All Growth Plus Pathogenicity ISO Class: ISO-5 Condition of sample upon receipt: Media in good condition Sample Size: 1000 Liters Positive Holes: 380 Alert Limit: NA Positive Hole Corrected Result: 0 CFU/m^3 Action Limit: 1 Final Result: No Growth Media: TSA Settling Plate Lot: 681632P Exp.2026-08-31

Temperature: 30-35 C Start Date: 08/04/2026 10:19 am PDT End Date: 08/06/2026 03:18 pm PDT

Temperature: 20-25 C Start Date: 08/06/2026 03:18 pm PDT End Date: 08/11/2026 02:38 pm PDT

Sample ID: A-06 Active Air Lab Sample ID: 2621600029-5

Test: USP <797> 2023 Single Media Dual Incubation ID All Growth Plus Pathogenicity ISO Class: ISO-7 Condition of sample upon receipt: Media in good condition Sample Size: 1000 Liters Positive Holes: 380 Alert Limit: NA Positive Hole Corrected Result: 0 CFU/m^3 Action Limit: 10 Final Result: No Growth Media: TSA Settling Plate Lot: 681632P Exp.2026-08-31

Temperature: 30-35 C Start Date: 08/04/2026 10:19 am PDT End Date: 08/06/2026 03:18 pm PDT

Tem…

This is the start of the file's text. The full file is on GovTribe.

File details come from the government source that posted it. Updated .