P8 Passenger Hydraulic Cat 1 and 5 12-2-2024.pdf
PDF 124 KB Posted
- Attached to
- J035--ELEVATOR MAINTENANCE, INSPECTION, & REPAIR SERVICE VA SIERRA NEVADA HEALTH CARE SYSTEM
- Solicitation number
- 36C26126Q1078
About this file
This is an Elevator/Dumbwaiter Periodic Inspection Report for a hydraulic passenger elevator located at the VA Medical Center; VA Sierra NV Health Care Systems, 975 Kirman Ave, Reno, NV 89502. The inspection was conducted on December 2, 2024, by inspector Houssam Zammam (QEI Certificate #6212) and reported to Terry Barton at phone number 775-784-3936. The elevator is a Schindler 330A model with a capacity of 2,100 lbs, operating at 100 feet per minute with a rated load valve pressure of 280 PSI and overspeed tripping speed of 127 FPM at 100 PSI. The equipment maintenance provider is Koch Elevator.
The inspection report comprehensively documents the condition of all major elevator components across multiple categories including machine room, pit, hoistway/top or car, and car systems. Virtually all inspected items received "OK" status, indicating compliance with applicable safety standards. Notable inspections performed include Hydraulic Test (Category One) dated 12/02/2024 and Cat 5 Test (Category Five) dated 12/03/2024. Several components were marked "NA" (not applicable), including electric test components, flexible hose connections, governor sealed/data plate, driving machines and sheaves, counterweight-related components, pull straps, selector switch, suspension and compensating ropes, governor rope data, suspension rope data, car door restrictor, and various rope-related items. All critical safety features including brakes, limit switches, door interlocks, electrical systems, emergency exits, and alarm systems were verified as operational.
View the file
Other files
Show all 19
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
ELEVATOR/DUMBWAITER PERIODIC INSPECTION REPORT
NAME OF BUILDING: ______VA Medical Center; VA SIERRA NV HEALTH CARE SYSTEMS ADDRESS: ____ 975 Kirman Ave, Reno, NV 89502________________________________________________________ REPORT TO: __________Terry Barton__________________________ INSPECTION DATE: _ Dec. 2, 2024_______ ____
PHONE NUMBER: 775 784 3936.
SERIAL NO. #:
Electric ______ Hydraulic __X____ Passenger ______ Freight ______ Dumbwaiter ______ Lift ______ Material Lift
INSPECTOR I.D NO. ___QEI_Certificate # 6212______________
INSPECTOR SIGNATURE___Houssam Zammam___ ______ EQUIPMENT MAINTENANCE CO: __Koch Elevator________ EQUIPMENT MNFTR: _____Schindler_330A________________ Capacity:2100 LBS FPM: 100 Elevator ID P8, FLWP : 280 PSI , RL V P: 4 Overspeed tripping speed 127 FPM00 PSI Comment Access to Machine Room [30] OK Machine Room Door [32] OK Lighting [36] OK Location of Keys [600] OK M.R. Maintenance (not clean, storage) [619,602] OK Maintenance of Firefighters’ Service [649] OK Machine Room Electrical [39] NA Hydraulic Test (Category One) [676] 12/02/2024 Electric Test (Category One) Cat 1 [672] NA Cat 5 Test (Category Five) Cat 5 [673] 12/03/2024 Other equipment Test [608,683,684,685,686,687,691,692] OK Flexible Hose Connections [632] NA Governor Sealed / Data Plate [120,122] NA Governor Switch [155] NA Brakes [169] OK Driving Machines and Sheaves [147] NA Equipment Guarding [46] OK
PIT
Access to Pit [11] OK Light and Switch [12] OK Pit Stop Switch [15] OK Pit Maintenance (not clean, water or oil) [617,618] OK Limit Switch(s)-Bottom (normal, final, hydro) [148,149,240] OK Platen Head Attachment [221] NA Counterweight Runby [19] NA Counterweight Guard [17] NA Governor Tension Sheave [119] NA Car/Counterweight Safeties [116] NA
OTHER OF SERVICE [659]
https://www1.thecomplianceengine.com/premise/show/836703
ELEVATOR/DUMBWAITER PERIODIC INSPECTION REPORT
HOISTWAY/ TOP OR CAR Comment Hoistway Access Switches [74] OK Hoistway Door Unlocking Devices [73] OK Lighting [106] OK Stop Switch (161) OK Inspection Station [151] OK Limit Switch(s)- Top (normal, final, hydro) [148,149,204] OK Hoistway Electrical [39] OK Cartop/ Car Electrical [164] OK Hoistway Maintenance [617] OK Cartop Maintenance [621] OK Hoistway Door Interlock [70] OK Door Panel Clearance (horizontal, vertical) [53,63] OK Door Bottom Guides [57] OK Hoistway Door Safety Retainers [58] OK Horizontal Hoistway Door Gap [56] OK Guide Rails, Rail Brackets, Fastenings [144] OK Guiding Members-Car [109] OK Traveling Cables [716,717] OK Emergency Exit [85] OK Anti-Creep [245] OK Car Top Date (electric, hydro) [114,217] OK Pull Straps [66] NA Hoistway Door Combination Mech. Lock&Contact [71] OK Vertical Hoistway Door Gap [64] OK Selector Switch-Rope/Tape/Chain [157] NA Safety Switch [155] OK Suspension & Compensating Ropes [669] NA Governor Rope & Governor rope data plate [668, 121] NA Suspension Rope Data [130] NA Guiding Members-Counterweight [137] OK
CAR
Car Stop Switch (freight, pass alarm) [156,163,176] OK Alarm Bell (w/ alarm on standby power) [175] OK Tow-Way Conversation [177] OK Capacity Plate [113] 2100 Lbs.
Car Light (W/Protection) [102,107] OK Car Interior Secure [84] OK Car Enclosure [83] OK Car Ventilation [94] OK Fire Service Instruction [187] OK Car Door/Gate Contact [99] OK Electric Eyes/Infrared Curtain [81] OK Safety Edge [81] OK Door Pressure [80] OK Door Time [79] OK Car Door Restrictor [72] NA Auxiliary Lighting [105] OK Operating Device Symbols [174] OK
File details come from the government source that posted it. Updated .