P13 Passenger Hydraulic Cat 1 and 5 12-3-2024.pdf
PDF 139 KB Posted
- Attached to
- J035--ELEVATOR MAINTENANCE, INSPECTION, & REPAIR SERVICE VA SIERRA NEVADA HEALTH CARE SYSTEM
- Solicitation number
- 36C26126Q1078
About this file
This is an Elevator/Dumbwaiter Periodic Inspection Report for a hydraulic passenger elevator located at VA Sierra NV Health Care Systems, 975 Kirman Ave, Reno, NV 89502. The inspection was conducted on December 3, 2024, by QEI-certified inspector Houssam Zammam (Certificate #6212) and reported to Terry Barton at phone number 775-784-3936.
The elevator is a hydraulic unit (Elevator ID P13) manufactured by TAC 32 with a capacity of 4,000 pounds, operating at 150 feet per minute. The equipment is maintained by Koch Elevator. Operating specifications include a full load working pressure of 500 PSI and relief valve pressure of 600 PSI, with an overspeed valve tripping speed of 210 FPM. The inspection covered all major elevator systems including machine room access and maintenance, pit conditions, hoistway and car components, and safety systems. Hydraulic tests for both Category One and Category Five were completed on 12/03/2024. The majority of inspected items received "OK" status, including machine room door and lighting, pit access and maintenance, limit switches, guide rails, hoistway door interlocks, car enclosure and ventilation, door safety systems, and emergency features. Several items were marked "NA" (not applicable), including flexible hose connections, governor-related components, brakes, and driving machines, indicating these elements are not present or applicable to this particular hydraulic elevator model.
View the file
Other files
Show all 19
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
ELEVATOR/DUMBWAITER PERIODIC INSPECTION REPORT
NAME OF BUILDING: ______VA Medical Center; VA SIERRA NV HEALTH CARE SYSTEMS ADDRESS: ____ 975 Kirman Ave, Reno, NV 89502________________________________________________________ REPORT TO: __________Terry Barton__________________________ INSPECTION DATE: _ Dec. 3, 2024_______ ____
PHONE NUMBER: 775 784 3936.
SERIAL NO. #:
Electric ______ Hydraulic __X____ Passenger ______ Freight ______ Dumbwaiter ______ Lift ______ Material Lift
INSPECTOR I.D NO. ___QEI_Certificate # 6212______________
INSPECTOR SIGNATURE___Houssam Zammam___ ______ EQUIPMENT MAINTENANCE CO: __Koch Elevator________
EQUIPMENT MNFTR: _____TAC 32________________
Capacity: 4000 LBS FPM: 150 Elevator ID P13, FLWP : 500 PSI , RL V P: 600 PSI. Overspeed Valve tripping speed 210 FPM
Comment Access to Machine Room [30] OK Machine Room Door [32] OK Lighting [36] OK Location of Keys [600] OK M.R. Maintenance (not clean, storage) [619,602] OK Maintenance of Firefighters’ Service [649] OK Machine Room Electrical [39] NA Hydraulic Test (Category One) [676] 12/03/2024
Electric Test (Category One) Cat 1 [672] NA Hydraulic Test (Category Five) Cat 5 [673] 12/03/2024
Other equipment Test [608,683,684,685,686,687,691,692] OK
Flexible Hose Connections [632] NA
Governor Sealed / Data Plate [120,122] NA Governor Switch [155] NA
Brakes [169] NA
Driving Machines and Sheaves [147] NA Equipment Guarding [46] OK
PIT
Access to Pit [11] OK Light and Switch [12] OK Pit Stop Switch [15] OK Pit Maintenance (not clean, water or oil) [617,618] OK Limit Switch(s)-Bottom (normal, final, hydro) [148,149,240] OK Platen Head Attachment [221] NA
Counterweight Runby [19] NA
Counterweight Guard [17] NA Governor Tension Sheave [119] NA Car/Counterweight Safeties [116] NA
OTHER OF SERVICE [659]
https://www1.thecomplianceengine.com/premise/show/836703
ELEVATOR/DUMBWAITER PERIODIC INSPECTION REPORT
HOISTWAY/ TOP OR CAR Comment Hoistway Access Switches [74] OK
Hoistway Door Unlocking Devices [73] OK
Lighting [106] OK Stop Switch (161) OK
Inspection Station [151] OK
Limit Switch(s)- Top (normal, final, hydro) [148,149,204] OK
Hoistway Electrical [39] OK Cartop/ Car Electrical [164] OK
Hoistway Maintenance [617] OK
Cartop Maintenance [621] OK Hoistway Door Interlock [70] OK
Door Panel Clearance (horizontal, vertical) [53,63] OK
Door Bottom Guides [57] OK
Hoistway Door Safety Retainers [58] OK Horizontal Hoistway Door Gap [56] OK
Guide Rails, Rail Brackets, Fastenings [144] OK
Guiding Members-Car [109] OK Traveling Cables [716,717] OK
Emergency Exit [85] OK
Anti-Creep [245] OK Car Top Date (electric, hydro) [114,217] OK
Pull Straps [66] NA
Hoistway Door Combination Mech. Lock&Contact [71] OK
Vertical Hoistway Door Gap [64] OK Selector Switch-Rope/Tape/Chain [157] NA
Safety Switch [155] OK
Suspension & Compensating Ropes [669] NA Governor Rope & Governor rope data plate [668, 121] NA
Suspension Rope Data [130] NA
Guiding Members-Counterweight [137] OK
CAR
Car Stop Switch (freight, pass alarm) [156,163,176] OK Alarm Bell (w/ alarm on standby power) [175] OK
Tow-Way Conversation [177] OK
Capacity Plate [113] 4000 Lbs.
Car Light (W/Protection) [102,107] OK
Car Interior Secure [84] OK
Car Enclosure [83] OK
Car Ventilation [94] OK Fire Service Instruction [187] OK
Car Door/Gate Contact [99] OK
Electric Eyes/Infrared Curtain [81] OK
Safety Edge [81] OK
Door Pressure [80] OK
Door Time [79] OK
Car Door Restrictor [72] NA
Auxiliary Lighting [105] OK
Operating Device Symbols [174] OK
File details come from the government source that posted it. Updated .