This document is a Heterotrophic Plate Count laboratory report for VA Central California Health Care System (HCS), dated May 21, 2025. The report details bacterial testing results for multiple water lines across different rooms and floors of Building 1, with all samples showing bacterial counts less than 10 CFU/mL. The Infection Control Standards for VA Clinics outline specific actions based on bacterial thresholds: lines with over 500 CFU/mL must be taken out of service and shocked, lines with 200-500 CFU/mL should be shocked and remain in service, and lines with under 200 CFU/mL can continue current disinfection protocols. The samples were collected on May 21, 2025, processed on May 22, 2025, and the report was issued on June 2, 2025. The laboratory is ELAP certified in compliance with New York State Department of Health and Florida Administrative Code for environmental and drinking water microbiology testing.

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

VA Central California HCS, MAY 21, 2025 - 1 of 4

ELAP Lab ID: | NELAC Lab ID: | EPA Lab ID:

Travis Horn VA Central California HCS 2615 E Clinton Ave.

Fresno, CA 93703

(o) 559-225-6100 ex5735 travis.horn@va.gov

June 02, 2025

Subject: VA Central California HCS, Q3 FY2025 Heterotrophic Plate Count Results

Dear Mr. Horn, The Laboratory has completed the heterotrophic plate count analysis on samples taken from the VA Central California HCS on May 21, 2025, and delivered to the laboratory on May 22, 2025.

The Infection Control Standards for VA Clinics indicate these actions at the following bacterial thresholds:

1. Detection greater than 500 CFU/mL: Take the line out of service, shock all the lines, and retest to determine treatment efficacy.

2. Detection greater than 200 CFU/mL but less than 500 CFU/mL: Lines may remain in service, but it is recommended that they be shocked again.

3. Detection less than 200 CFU/mL: No additional action -- Continue current disinfection protocols.