Bid RFI 3 - CS1.5.2- UTILITY PLAN (ADD #1).pdf
PDF 1 MB Posted
- Solicitation number
- 36C26123R0107
About this file
This document is an addendum to a bid request for information related to a federal contract opportunity to renovate a food nutrition kitchen for the Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 21. The addendum provides responses to contractor questions about relocating tanks to avoid utilities conflicts, manhole specifications, temporary power sources and locations, point of connection elevations, offsetting storm drain pipes, installing drain pipes underneath existing ductwork, subdrain layouts and connections to drainage systems. It refers contractors to as-built drawings for details on water, sanitary sewer, storm drainage and gas systems. The solicitation seeks bids for contract number 36C26123R0107 to renovate a 640-square foot food nutrition kitchen for the Veterans Affairs facility.
View the file
Other files
Show all 14
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
ADDENDUM #11
RFI-242R Relocate tank to miss utilities
RFI-214R MH#12 is to be a drop MHRFI-0421R Temporary power source to lift station 54
RFI-0509R Temporary power to lift station 54 to be located in Mech Rm m-0.4 in new addition basement
RFI-0509.1R Temp power panel location
RFI-0551R POC elevation
RFI-524.2R Offset in SD 15" RCP to MH
RFI-0620R Install 15 RCP underneath (E) electrical ductbank, remove SDMH-41 to allow adjustments for elevations
RFI-0421.1R Temp power use panel NH16B (in ME-1) with
(N) 70A/3P breaker
RFI 620.1: Layout confirmation
RFI-1058: The existing subdrain at B100 needs to be plumbed to the storm drainage system: either re-plumbed to its pre-project condition or plumbed to Lift Station
54. Any new sub-drain to deleted work assoiciated with the now deleted tunnel can be deleted.
RFI-1415: No exceptions taken to using materials as called out by Spec Section 334716.17 (bioretention and swales) and approved Submittal
334716.03 LRSU Subdrainage System.
RFI-1484: See 52/LP7.2.0 for subdrain construction detail sjajob Text Box Refer to Submiital 331000.01.01C for Water, Sanitary Sewer, Storm Drainage, Gas- As-Builts
File details come from the government source that posted it. Updated .