36C26119B0026-092.docx

DOCX document 27 KB Posted

Attached to
VAPAHCS - Correct Facility Deficiencies Menlo Park Division & Mountain View Center
Solicitation number
36C26119B0026
Issued by

About this file

36C26119B0026 P09 - Specification 224000 - Plumbing Fixture.docx

View the file

Other files

File Type Posted
36C26119B0026-0002003.xlsx XLSX spreadsheet
36C26119B0026-0002002.dwg DWG drawing
36C26119B0026-0002001.dwg DWG drawing
36C26119B0026-0002000.docx DOCX document
36C26119B0026-0001000.docx DOCX document
36C26119B0026-089.docx DOCX document
36C26119B0026-069.pdf PDF
36C26119B0026-084.docx DOCX document
36C26119B0026-076.docx DOCX document
36C26119B0026-085.docx DOCX document
36C26119B0026-064.docx DOCX document
36C26119B0026-072.pdf PDF
36C26119B0026-066.pdf PDF
36C26119B0026-082.docx DOCX document
36C26119B0026-077.docx DOCX document
36C26119B0026-090.docx DOCX document
36C26119B0026-071.pdf PDF
36C26119B0026-078.pdf PDF
36C26119B0026-081.docx DOCX document
36C26119B0026-073.pdf PDF
36C26119B0026-093.docx DOCX document
36C26119B0026-070.pdf PDF
36C26119B0026-079.doc DOC document
36C26119B0026-065.pdf PDF
36C26119B0026-067.pdf PDF
36C26119B0026-074.docx DOCX document
36C26119B0026-075.doc DOC document
36C26119B0026-087.docx DOCX document
36C26119B0026-088.docx DOCX document
36C26119B0026-068.pdf PDF
36C26119B0026-080.pdf PDF
36C26119B0026-063.docx DOCX document
36C26119B0026-083.docx DOCX document
36C26119B0026-091.docx DOCX document
36C26119B0026-086.docx DOCX document
36C26119B0026-000.docx DOCX document
Show all 36

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

09-01-15

SECTION 22 40 00

PLUMBING FIXTURES

Correct Building Deficiencies Project Number: 640-19-112M

PART 1 - GENERAL

1.1 DESCRIPTION

A. Plumbing fixtures, associated trim and fittings necessary to make a complete installation from wall or floor connections to rough piping, and certain accessories.

B. A complete listing of all acronyms and abbreviations are included in Section 22 05 11, COMMON WORK RESULTS FOR PLUMBING.

1.2 RELATED WORK

A.Section 01 00 00, GENERAL REQUIREMENTS.
B.Section 01 33 23, SHOP DRAWINGS, PRODUCT DATA, AND SAMPLES.
C.Section 01 81 13, SUSTAINABLE CONSTRUCTION REQUIREMENTS.
D.Section 01 91 00, GENERAL COMMISSIONING REQUIREMENTS.
E.Section 07 92 00, JOINT SEALANTS: Sealing between fixtures and other finish surfaces.
H.Section 22 05 11, COMMON WORK RESULTS FOR PLUMBING.
I.Section 22 08 00, COMMISSIONING OF PLUMBING SYSTEMS: Requirements for commissioning, systems readiness checklist, and training.

1.3 APPLICABLE PUBLICATIONS

A. The publications listed below form a part of this specification to the extent referenced. The publications are referenced in the text by the basic designation only.

B.The American Society of Mechanical Engineers (ASME):
A112.6.1M-1997 (R2012)Supports for Off-the-Floor Plumbing Fixtures for Public Use
A112.19.1-2013Enameled Cast Iron and Enameled Steel Plumbing Fixtures
A112.19.2-2013Ceramic Plumbing Fixtures
A112.19.3-2008Stainless Steel Plumbing Fixtures
C.American Society for Testing and Materials (ASTM):
A276-2013aStandard Specification for Stainless Steel Bars and Shapes
B584-2008Standard Specification for Copper Alloy Sand Castings for General Applications
D.CSA Group:
B45.4-2008 (R2013)Stainless Steel Plumbing Fixtures
E.National Association of Architectural Metal Manufacturers (NAAMM):
AMP 500-2006Metal Finishes Manual
F.American Society of Sanitary Engineering (ASSE):
1016-2011Automatic Compensating Valves for Individual Showers and Tub/Shower Combinations
G.NSF International (NSF):
14-2013Plastics Piping System Components and Related Materials
61-2013Drinking Water System Components – Health Effects
372-2011Drinking Water System Components – Lead Content
H.American with Disabilities Act (A.D.A)
I.International Code Council (ICC):
IPC-2015International Plumbing Code

1.4 SUBMITTALS

A. Submittals, including number of required copies, shall be submitted in accordance with Section 01 33 23, SHOP DRAWINGS, PRODUCT DATA, AND SAMPLES.

B. Information and material submitted under this section shall be marked “SUBMITTED UNDER SECTION 22 40 00, PLUMBING FIXTURES”, with applicable paragraph identification. Shall be made in U.S.A. – American Brand

C. Manufacturer's Literature and Data including: Full item description and optional features and accessories. Include dimensions, weights, materials, applications, standard compliance, model numbers, size, connections, and capacity.

D. Operating Instructions: Comply with requirements in Section 01 00 00, GENERAL REQUIREMENTS.

PART 2 - PRODUCTS

2.1 MATERIALS

A. Material or equipment containing a weighted average of greater than 0.25 percent lead is prohibited in any potable water system intended for human consumption, and shall be certified in accordance with NSF 61 or NSF 372. Endpoint devices used to dispense water for drinking shall meet the requirements of NSF 61.

B. Plastic pipe, fittings, and solvent cement shall meet NSF 14 and shall be NSF listed for the service intended.

2.2 SINKS AND LAUNDRY TUBS

A. Dimensions for sinks and laundry tubs are specified, length by width (distance from wall) and depth.

B. (P-501) Service Sink (Regular, ASME A112.19.1) service sink, class 1, single bowl, acid resistant enameled cast iron, approximately 610 mm by 508 mm (24 inches by 20 inches) with a 229 to 305 mm (9 to 12 inches) raised back without faucet holes. Equip sink with CRS rim guard, and mounted on trap standard. Set sinks rim 711 mm (28 inches) above finished floor.

1. Faucet: Part B, Type II, solid brass construction, 9.5 L/m (2.5 gpm) combination faucet with replaceable Monel seat, removable replacement unit containing all parts subject to wear, integral check/stops, mounted on wall above sink. Spout shall have a pail hook, 19 mm (3/4 inch) hose coupling threads, vacuum breaker, and top or bottom brace to wall. Four-arm handles on faucets shall be cast, formed, or drop forged copper alloy. Escutcheons shall be either forged copper alloy or CRS. Exposed metal parts, including exposed part under valve handle when in open position, shall have a smooth bright finish.

2. Drain: Grid.

3. Trap: Trap standard, painted outside and enameled inside with acid-resistant enamel, drain through adjoining wall.

PART 3 - EXECUTION

3.1 INSTALLATION

A. Fixture Setting: Opening between fixture and floor and wall finish shall be sealed as specified under Section 07 92 00, JOINT SEALANTS. Bio-based materials shall be utilized when possible.

3.2 CLEANING

A. At completion of all work, fixtures, exposed materials and equipment shall be thoroughly cleaned.

3.3 DEMONSTRATION AND TRAINING

A. Provide services of manufacturer’s technical representative for 1 hour to instruct VA Personnel in operation and maintenance of the sink, American Brand Name, including all OEM and manuals that came with the sink system and all rough in piping – Made In U.S.A

- - - E N D - - - 22 40 00 - 1