36C26118R0541 P09 -- Attachment Temperature Controls.pdf

View the file

Other files

File Type Posted
36C26119C0052-000.docx DOCX document
36C26118R0541_0013.docx DOCX document
S05-AMENDMENT_0013,_Question-Answers_for_RFI.pdf PDF
36C26118R0541-0012000.docx DOCX document
36C26118R0541-0012001.pdf PDF
36C26118R0541-0011000.docx DOCX document
36C26118R0541-0010000.docx DOCX document
36C26118R0541-0009000.docx DOCX document
36C26118R0541-0009002.pdf PDF
36C26118R0541-0009001.pdf PDF
36C26118R0541-0008000.docx DOCX document
36C26118R0541-0008001.pdf PDF
36C26118R0541-0007001.pdf PDF
36C26118R0541-0007000.docx DOCX document
36C26118R0541-0006000.docx DOCX document
36C26118R0541-0006001.pdf PDF
36C26118R0541-0006002.pdf PDF
36C26118R0541-0005000.docx DOCX document
36C26118R0541-0005001.pdf PDF
36C26118R0541-0004001.pdf PDF
36C26118R0541-0004000.docx DOCX document
36C26118R0541-0003000.docx DOCX document
36C26118R0541-0003001.pdf PDF
36C26118R0541-0002000.docx DOCX document
36C26118R0541-0002001.pdf PDF
36C26118R0541-0001000.docx DOCX document
36C26118R0541-015.pdf PDF
36C26118R0541-006.pdf PDF
36C26118R0541-009.pdf PDF
36C26118R0541-007.pdf PDF
36C26118R0541-005.pdf PDF
36C26118R0541-004.docx DOCX document
36C26118R0541-012.pdf PDF
36C26118R0541-016.pdf PDF
36C26118R0541-014.pdf PDF
36C26118R0541-010.pdf PDF
36C26118R0541-011.pdf PDF
36C26118R0541-013.pdf PDF
36C26118R0541-003.docx DOCX document
36C26118R0541-000.docx DOCX document
36C26118R0541-002.docx DOCX document
36C26118R0541-001.docx DOCX document
Show all 42

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

JAN 8, 2010

C A

L

IF

O R

N

IA

E

V

IR

O N

M E

N T

A L

S Y

S T

E M

S

V A

H O

S P

IT

A

L

P H

A R

M A

C Y

U P

G R

A D

E

T H

IS

D

O C

U M

E

T

O

N T

A

IN

P R

O P

R

IE

T A

F O

R M

A T

IO

N

W H

IC

H

A

L L

N O

T B

P R

O D

U C

E D

T

R A

N S

F E

R R

E D

H

E R

D O

C U

M E

N T

S

D

IS

C L

O S

E D

H

E R

S U

S E

D F

M

N

U F

A C

T U

R

IN

G

Y O

T H

E R

P U

R P

O

W

IT

H O

U T

P R

IO

IT

T E

N P

E R

M

IS

S

O M

R S

D /T

O T

N

T R

O L

S h e e t T it le

P ro je c t:

C o n tr a c to r:

R E

N O

N

V

Sheet:

Job #:

Designed By:

Drawing By:

Date:

812928

DLW

DLW

R e v is io n s

R e v D a te

C h a n g e

/1

/1

C o m m e rc e

D ri v e

R o s e v ill e C

A

-7

-5

-7

-5

F a x

A U

B U

R N

C

A

(5

-3

Approved By: DLW

-0

-1

A d d e d V

A V

C o n tr o lle rs /F rz S ta t

M is c e lla n e o u s R e v is io n s

1 2

TABLE OF CONTENTS

SHEET

INDEX & LAN Architechture

AHU-P1 Temperature Control Panel Details

AHU-P1, EF-P1, & EF-P2 Control Details

CAV-P1 & P2 Control Details & Sequence Of Operations

TITLE

IN

D

E X

L

A N

A rc h it e c h tu re

VA Hospital

Pharmacy Upgrade

1000 Locus St

Reno, NV

Total Control is a factory authorized Johnson Controls Metasys Specialist.

Total Control assures through Training, Project Management, Application Engineering, On-site Start-up Assistance and over 45 years of Metasys experience, the operational conformance and satisfaction of each and every installed system.

T C

P -A

H U

P

L o c a te d i n

A H

U -P

AHU-P1

ADDR: XX

CAT 5 CABLE

Existing Delta

System Controller

Existing Delta PC

EXISTING ETHERNET

S

/T P

B U

S

M S

/T P

B U

S

LAN Architecture2

EOL

M S

/T P

B U

S M

S /T

P B

U S

1 Existing Delta Field Controllers

SHEET NOTES

M S

/T P

B U

S

IOM-1

ADDR: 4

IOM-2

ADDR: 5

IOM-3

ADDR: 6

S A

B U

S S

A B

U S

S A

B U

S

Table of Contents1

1 1

CAV-P1

ADD: 0x

MS/TP BUS

M S

/T P

B U

S

MS/TP BUS

CAV-P2

ADD: 0x

M S

/T P

B U

ADDRESSES TO BE DETERMINED1

A

L

IF

O R

V

IR

O N

M E

N T

S T

E M

S

V A

H O

S P

IT

A

L

P H

A R

M A

C Y

U P

G R

A D

E

T H

IS

D

O C

U M

E

N T

A

O P

R

IE

T A

O

R M

A T

IO

N

W H

A

L L

N O

T

P R

O D

U C

E D

T

R A

N S

F E

R R

E D

H

E R

D O

C U

M E

N T

S

D

IS

C L

O S

E D

H

E R

S U

S E

D F

N

U F

A C

T U

R

IN

G

Y O

T H

E R

P U

R P

O

H O

U T

P R

IT

T E

N P

E R

M

IS

S

O M

R S

D /T

O T

N

T R

O L

S h e e t T it le

P ro je c t:

C o n tr a c to r:

R E

N O

N

V

Sheet:

Job #:

Designed By:

Drawing By:

Date:

812928

DLW

DLW

R e v is io n s

R e v D a te

C h a n g e

/1

/1

C o m m e rc e

D ri v e

R o s e v ill e C

A

-7

-5

-7

-5

F a x

A U

B U

R N

C

A

(5

-3

Approved By: DLW

-0

-1

A d d e d V

A V

C o n tr o lle rs /F rz S ta t

M is c e lla n e o u s R e v is io n s

1 2

A H

U -P

T e m p e ra tu re C o n tr o l P a n e l D e ta il s

PANEL CONTINUED

ON

FC ADDRESS

(SEE SCHEDULE)

FC+

FC-

REF

IN1

IC1

IN2

IC2

RJ

UI IN1 Duct Static

UI IN2

UI IN3

BI IN7 EF VFD Status

HOT

COM

Disch Airflow

Exhaust Airflow

UI IN6 SF VFD Fault

UI IN4 Spare

BI IN8 EF VFD Fault

V A

C F

C B

U S

SHLD

SA+

SA-

COM

RJ

S A

B U

S

PWR

+15V

+15V

IN3

IC3

IN4

IC4

+15V

IN6

IC6

U N

IV

E

R S

A L

IN

P

U T

S

IN7

IC7

IN8

IC8

B

IN

A R

Y

IN

P U

T S

BO OUT1 SF VFD Enable

BO OUT2 EF VFD Enable

O1

OC1

O2

OC2

B

IN

A R

Y O

U T

P U

T S

O3

OC3

BO OUT3 Bypass Damper

CO OUT4 OA Damper Cmd

CO OUT5 EA Damper Cmd

O4

OC4

O5

OC5

C O

N F

IG

U

R A

B L

E O

U T

P U

T S

O6

OC6

CO OUT6 Spare

CO OUT7 Spare

AO OUT8 SF VFD Speed

AO OUT9 EF VFD Speed

O7

OC7

O8

OC8

O9

OC9

A N

A L

O G

O U

T P

U T

S

INT

EXT

SOURCE 24VAC

INT

EXT

SOURCE 24VAC

INT

EXT

SOURCE 24VAC

SETUP: 24VAC Maintained

SETUP: 24VAC Maintained

SETUP: 24VAC Maintained

SETUP: 24VAC Maintained

SETUP: 0-10V

SETUP: 0-10V

UI IN5 SF VFD Status IN5

IC5

7 8 R1

5 3 R1-1

FEC

7 8 R2

7 8 R3

7 8 R4

7 8 R5

Supply Fan VFD Run Command

Dry Contact

5 3 R2-1

5 3 R3-1

5 3 R4-1

5 3 R5-1

ON

SA BUS ADDRESS

IN1

IC1

IN2

UI IN1 PreFilter DP

UI IN3

BI IN7 OA Damper Status

HOT

COM

Filter DP

EA Filter DP

UI IN6 Exhaust Air Temp

UI IN4 Disch Temp

BI IN8 EA Damper Status

V A

C

SA+

SA-

COM

RJ

S A

B U

S

PWR

+15V

+15V

IN3

IC3

IN4

IC4

IN6

IC6

U N

IV

E

R S

A L

IN

P

U T

S

IN7

IC7

IN8

IC8

B

IN

A R

Y

IN

P U

T S

AO OUT8 Heating Valve

AO OUT9 Cooling Valve

O8

OC8

O9

OC9

A N

A L

O G

O U

T P

U T

S

SETUP: 0-10Vdc

SETUP: 0-10Vdc

SETUP: 0-10V

SETUP: 0-10V

UI IN5 Outdoor Temp IN5

IC5

IOM

ON

EOL

ON

EOL

TO NEXT

DEVICE

FROM PREVIOUS

DEVICE

E n d o f L in e o n ly

”O N

” fo r b o th d e v ic e s

A t e n d s o f b u s d a is y c h a in

LOCAL DISPLAY

XF1H

XF1H

XF1H

Air Handler and Exhaust Fan Detail

SETUP: 0-10VDC

SETUP: 0-10VDC

SETUP: Nickel 1K RTD

SETUP: 0-10VDC

120L

120N

GND GND

CB

120VAC

XF

REF

SHD

FC-

FC+

SETUP: Dry Contact Maintained

SETUP: Dry Contact Maintained

SETUP: 0-10Vdc

SETUP: Nickel 1K RTD

SETUP: Nickel 1K RTD

PANEL CONTINUED

ON

SA BUS ADDRESS

IN1

IC1

UI IN1 EF-P2 Duct Static

UI IN3

BI IN7 EF-P1 Fan Status

HOT

COM

Zone 1 Humid

Zone 2 Humid

UI IN6 EF-P2 Dmpr Status

UI IN4 Zone 3 Humid

BI IN8 EF-P2 Fan Status

V A

C

SA+

SA-

COM

RJ

S A

B U

S

PWR

+15V

+15V

IN3

IC3

IN4

IC4

+15V

IN6

IC6

U N

IV

E

R S

A L

IN

P

U T

S

IN7

IC7

IN8

IC8

B

IN

A R

Y

IN

P U

T S

BO OUT1 EF-P1 Command

BO OUT2 EF-P2 VFD Enable

O1

OC1

O2

OC2

B

IN

A R

Y O

U T

P U

T S

O3

OC3

BO OUT3 EF-P2 DamperCmd

CO OUT4 Spare

CO OUT5 Spare

O4

OC4

O5

OC5

C O

N F

IG

U

R A

B L

E O

U T

P U

T S

O6

OC6

CO OUT6 Spare

CO OUT7 Spare

AO OUT8 EF-P2 VFD Speed

AO OUT9 AHU-P1 Humidifier

O7

OC7

O8

OC8

O9

OC9

A N

A L

O G

O U

T P

U T

S

INT

EXT

SOURCE 24VAC

INT

EXT

SOURCE 24VAC

INT

EXT

SOURCE 24VAC

SETUP: 0-10Vdc

SETUP: 0-10Vdc

SETUP: 0-10VDC

SETUP: 0-10Vdc

SETUP: 0-10Vdc

SETUP: 24VAC Maintained

SETUP: 24VAC Maintained

SETUP: 0-10V

SETUP: 0-10V

UI IN5 Spare IN5

IC5

ON

EOL

SETUP: 0-10Vdc

SETUP: 0-10Vdc

SETUP: 4-20mA or 0-10Vdc

Dry Contact

Dry Contact

Dry Contact

Dry Contact

Dry Contact

Dry Contact

SETUP: Nickel 1K RTD

XF

X F

X F

Discharge Airflow Meter

0-10VDC = 0-????cfm

SIG

COM

PWR

Exhaust Airflow Meter

0-10VDC = 0-????cfm

PWR

SIG

COM

Supply Fan VFD Status

Dry Contact

Supply Fan VFD Fault

Dry Contact

Exhaust Fan VFD Status

Dry Contact

Exhaust Fan VFD Fault

Dry Contact

X F

X F

Exhaust Fan VFD Run Command

Dry Contact

Outdoor Damper Command

24VAC Open / Spring Return Close

Exhaust Damper Command

24VAC Open / Spring Return Close

Bypass Damper Command

24VAC = Bypass

Spring Return = Heat Recovery

24VAC

COM

Supply Fan VFD Speed Command

0-10VDC = 0-100%

Exhaust Fan VFD Speed Command

0-10VDC = 0-100%

X F

X F

X F

X F

X F

X F

S A

B

S A

B

S A

B

X F

X F

Duct Static Pressure

0-10VDC = 0-2.5" w.c.

PWR

SIG

COM

XF1H

X F

X F

PreFilter Differential Pressure

0-10VDC = 0-2.5" w.c.

PWR

SIG

COM

Final Filter Differential Pressure

0-10VDC = 0-2.5" w.c.

SIG

COM

PWR

Exhaust Filter Differential Pressure

0-10VDC = 0-2.5" w.c.

PWR

SIG

COM

Discharge Air Temperature

Nickel 1k

Outdoor Air Temperature

Nickel 1k

Exhaust Air Temperature

Nickel 1k

Outdoor Damper Status

Dry Contact

Exhaust Damper Status

Dry Contact

COM

COM

24VAC

24VAC

PreHeat Coil Steam Valve

2-10VDC = 0-100% Heating

Cooling Coil ChW Valve

2-10VDC = 0-100% Cooling

XF2H

COM

SIG

PWR

COM

SIG

PWR

X F

X F

ON

SA BUS ADDRESS

IN1

IC1

UI IN1 Spare

UI IN3

BI IN7 Spare

HOT

COM

Spare

Spare

UI IN6 Spare

UI IN4 Spare

BI IN8 Spare

V A

C

SA+

SA-

COM

RJ

S A

B U

S

PWR

+15V

+15V

IN3

IC3

IN4

IC4

IN6

IC6

U N

IV

E

R S

A L

IN

P

U T

S

IN7

IC7

IN8

IC8

B

IN

A R

Y

IN

P U

T S

AO OUT8 Spare

AO OUT9 Spare

O8

OC8

O9

OC9

A N

A L

O G

O U

T P

U T

S

SETUP: Nickel 1K RTD

SETUP: Nickel 1K RTD

SETUP: 0-10V

SETUP: 0-10V

UI IN5 Spare IN5

IC5

IOM

ON

EOL

SETUP: Nickel 1K RTD

SETUP: Nickel 1K RTD

SETUP: Ohms

Dry Contact

Dry Contact

SETUP: Ohms

S A

B

S A

B

X F

X F

XF2H

X F

X F

IOM

S A

B

X F

X F

X F

X F

EF-P2 Duct Static Pressure

0-10VDC = 0-2.5" w.c.

PWR

SIG

COM

XF1H

XF1H

Zone 1 Humidity Transmitter

0-10VDC = 0-100% RH

SIG

COM

PWR

Zone 2 Humidity Transmitter

0-10VDC = 0-100% RH

PWR

SIG

COM

XF1H

Zone 3 Humidity Transmitter

0-10VDC = 0-100% RH

SIG

COM

PWR

Exhaust Damper Status

Dry Contact

Exhaust Fan EF-P1 Status

Dry Contact

Exhaust Fan EF-P2 VFD Status

Dry Contact

7 8 R6

5 3 R6-1

Exhaust Fan EF-P1 Start/Stop

Dry Contact

X F

X F

X F

X F

7 8 R7

7 8 R8

5 3 R7-1

Exhaust Fan EF-P2 VFD Run Command

Dry Contact

5 3 R8-1

Exhaust Fan EF-P2 Damper Command

24VAC Open / Spring Return Close

Supply Fan VFD Speed Command

0-10VDC = 0-100%

AHU-P1 Steam Humidifier Valve

2-10VDC = 0-100% Full Humidfier Output

XF2H

COM

SIG

PWR

TAG QTY DESCRIPTION

FEC 1 JC MS-FEU2620-0 Controller, MS/TP BACnet, 17 Point w/ Display

IOM 3 JC MS-IOU4710-0 Expansion Module, MS/TP BACnet, 17 Point

R1-R8 8 VE VMD2 Relay, 2P2T, 24VAC w/ Hand

8 VE VMD2-C 2 Pole Relay Subase

XF-1, 2 3 LEC LE15550 75VA 408/24VAC Transformer

XF-1, 2 2 LEC LE16550 50VA 408/120/24VAC Transformer

CB-1 1 2A Circuit Breaker

CB-2 1 3A Circuit Breaker

ENC 1 HAM EN4SD20206GY Enclosure w/ Backplate

PANEL COMPONENTS

PART NUMBER

A CB

A

X F

X F

1Spare Points

1Spare Points

A

L

IF

O R

V

IR

O N

M E

N T

S T

E M

S

V A

H O

S P

IT

A

L

P H

A R

M A

C Y

U P

G R

A D

E

T H

IS

D

O C

U M

E

N T

A

O P

R

IE

T A

O

R M

A T

IO

N

W H

A

L L

N O

T

P R

O D

U C

E D

T

R A

N S

F E

R R

E D

H

E R

D O

C U

M E

N T

S

D

IS

C L

O S

E D

H

E R

S U

S E

D F

N

U F

A C

T U

R

IN

G

Y O

T H

E R

P U

R P

O

H O

U T

P R

IT

T E

N P

E R

M

IS

S

O M

R S

D /T

O T

N

T R

O L

S h e e t T it le

P ro je c t:

C o n tr a c to r:

R E

N O

N

V

Sheet:

Job #:

Designed By:

Drawing By:

Date:

812928

DLW

DLW

R e v is io n s

R e v D a te

C h a n g e

/1

/1

C o m m e rc e

D ri v e

R o s e v ill e C

A

-7

-5

-7

-5

F a x

A U

B U

R N

C

A

(5

-3

Approved By: DLW

-0

-1

A d d e d V

A V

C o n tr o lle rs /F rz S ta t

M is c e lla n e o u s R e v is io n s

1 2

A H

U -P

E

F -P

E F

-P

C o n tr o l D e ta il s

Air Handler Flow Schematic (AHU-P1)

EXHAUST FAN

RAEA

OA

HEAT

PIPE

C

C DUCT STATIC

¼ “ Pneumatic Tubing

A T

U S

E N

A B

L E

I C S

P E

E D

U

L T

XF2H

SUPPLY FAN

A T

U S

E N

A B

L E

9 1

I C

S P

E E

D

F A

U

FILTER

NC

XF2H

HUMIDIFIER

2-10VDC

By Air Handler Manufacturer

V-3

XF2HO +

Reference

O +

X F

H

SA

L N

V

N SD-1

O +

NC

NO

O+

L N

V

N SD-2

NC

CAV-P1 (TYP of CAV-P2)

ZONE REHEATS MOVED TO NEXT DRAWING

EF-P1

RAEA

M

S

C

NO

POWER

L1 N

2 3 EF-P1

4 3

AIRFLOW STATION

0-10VDC

AIRFLOW STATION

4-20MA/0-10VDC

S1

S2

S1

S2

TAG QTY DESCRIPTION

TE 4 3 JCI TE-6311P-1 Temp Sensor, Duct Mount, 8" Ni-1k

HE 3 VER HWX3XSX Wall Mount Space Humidity Sensor

DP 4 VER PXULX05S Differential Pressure Trasmitter

7 A345 Static Pressure Tip

7 A302 Static Pressure Tip Mount

DM 3 BEL AF24-S US Spring Return 2 Pos Damper Motor

LL-1 1 JCI A11A-1C Manual Reset Low Limit T-Stat

V 0 BY OTHERS

SF VFD 0 BY OTHERS

EF VFD 0 BY OTHERS

SD 0 BY OTHERS

AFMS-1 (By Others) 1 JCI ASTNN22x20 Air Flow Measuring Station, 0-10VDC

AFMS-2 (By Others) 1 JCI ASTNN16x20 Air Flow Measuring Station, 0-10VDC

FIELD COMPONENTS

PART NUMBER

TE

TE

TE

DP

DP

DP

DP

DM

DM

DM

V-1V-2

TAG QTY DESCRIPTION

CS-1 1 FUN RIBXKTF Current Switch, Solid Core, Non-Adjustable

FIELD COMPONENTS

PART NUMBER

CS

1 EXHAUST FAN

EA

A T

U S

E N

A B

L E

I C S

P E

E D

DUCT STATIC

¼ “ Pneumatic Tubing

O +

Reference

DP

NC1

S1

S2

DM

4 EF-P2

-74

O73

HE

XF1H

-76

O75

HE

-78

O77

HE

TAG QTY DESCRIPTION

DM 1 BEL AF24-S US Spring Return 2 pos Damper Actuator

DP 1 VER PXULX05S Pressure Transducer

1 A345 Static Pressure Tip

1 A302 Static Pressure Tip Mount

VFD 0 BY OTHERS

FIELD COMPONENTS

PART NUMBER

X F

H

X F

H

X F

H

X F

H

X F

H

X F

H

XF1H

XF1H

Humidity Transmitter

Located in IV Admixture 1D106

Humidity Transmitter

Located in Ante-Room 1D107

Humidity Transmitter

Located in Clean Room 1D107A

LL

R Y

AFMS-1

AFMS-2

SEE SEQUENCE OF OFERATIONS ON NEXT DRAWING

A

L

IF

O R

V

IR

O N

M E

N T

S T

E M

S

V A

H O

S P

IT

A

L

P H

A R

M A

C Y

U P

G R

A D

E

T H

IS

D

O C

U M

E

N T

A

O P

R

IE

T A

O

R M

A T

IO

N

W H

A

L L

N O

T

P R

O D

U C

E D

T

R A

N S

F E

R R

E D

H

E R

D O

C U

M E

N T

S

D

IS

C L

O S

E D

H

E R

S U

S E

D F

N

U F

A C

T U

R

IN

G

Y O

T H

E R

P U

R P

O

H O

U T

P R

IT

T E

N P

E R

M

IS

S

O M

R S

D /T

O T

N

T R

O L

S h e e t T it le

P ro je c t:

C o n tr a c to r:

R E

N O

N

V

Sheet:

Job #:

Designed By:

Drawing By:

Date:

812928

DLW

DLW

R e v is io n s

R e v D a te

C h a n g e

/1

/1

C o m m e rc e

D ri v e

R o s e v ill e C

A

-7

-5

-7

-5

F a x

A U

B U

R N

C

A

(5

-3

Approved By: DLW

-0

-1

A d d e d V

A V

C o n tr o lle rs /F rz S ta t

M is c e lla n e o u s R e v is io n s

1 2

C A

V -P

P

C o n tr o l D e ta il s

S e q u e n c e O f O p e ra ti o n s

CAV-P1 VAV Control Detail (TYP of CAV-P2)1

SA

RED

LO

HI

HOT

COM

OCOM5

XF

L

N 120V 1Ø

ICOM

IN

OUT4

OCOM4

SA PWR

SA COM

SA -

SA +

SA BUS (22ga, 2 twisted pair)

S A

B U

S

IN

P U

T C

O N

IG

U

T P

U T

S

VAV

FC COM

FC -

FC +

FC SHLD

F C

B U

S

FC BUS

FC BUS

FC BUS

FROM PREVIOUS DEVICE

FC BUS

TO NEXT DEVICE

SA COM

SA -

SA +

SA PWR

TE

CLR

V A

C

RJ

SA

H

C

A AB

HWR

HWS

N.O.

FLOW

STATION

HI LO

VAV BOX

OCOM4

OUT4

24VAC HOT

TO HWV

ACTUATOR

V

FROM VAV CONTROLLER

TAG QTY DESCRIPTION

VAV-1 2 JC MS-VMA1620-0 VAV Controller w/ Integral Damper Actuator

XF-1 2 VER X050CAA 120/24VAC, 50VA Transformer w/ Internal Circuit Brkr

TE-1 2 JC TE-6311P-1 Temp Sensor, Duct Mount, 8" Ni-1k

TE-2 2 JC TE-67NT Temp Sensor w/ Warm/Cool Adj, Wall

TE-2 2 JC NS-BTP7002-0 Network Sensor Zone Temp, Wall Mt. W/C Adj, & PB

V-1 1 BEL B214+TR24-SR CAV-P1 Valve & Proportional Actuator (2-10VDC)

V-2 1 BEL B218+TR24-SR CAV-P2 Valve & Proportional Actuator (2-10VDC)

FIELD COMPONENTS

PART NUMBER

OUT5

RA

TE

FROM RA SENSOR

RA

RA Duct from Room 1D106 for CAV-P1

RA Duct from Room 1D107 for CAV-P2

IN IC

O

M

VAV BOX

Sequence of Operations General:

Air Handler Unit (AHU) is automatically enabled by the Start/Stop Program at the DDC Controller. During normal operation, hand-off-auto switches shall be kept in the “Auto” position. In the normal mode, supply and exhaust fans shall run continuously. The supply fan shall be interlocked to run only when the associated exhaust fans are enabled. Anytime the AHU is turned off, AHU smoke dampers in the supply duct/exhaust duct, outside air damper, and general exhaust air damper shall close. All dampers shall be proven open, before fans are allowed to start again. Anytime the supply and exhaust fans are turned off, the associated combination fire/smoke dampers (CSFD) in the AHU duct distribution system, shall close. All dampers shall be proven open before fans start again. Pressure differential transmitters DP-1, DP-2 & DP-4, monitor three separate filter banks respectively, for dirty filter status.

Automatic Shutdown Mode:

Automatic shutdown of the AHU system shall be accomplished by interrupting the power source of the air moving equipment via the Fire alarm contacts at the FACP. If smoke is detected by the supply or exhaust air smoke detectors, the supply fan and exhaust fan shall be disabled, and the outside air damper shall close. AHU supply air and exhaust air smoke dampers shall be closed. Other associated exhaust fans shall continue to operate. SF/EF status’s shall be monitored by the VFD Status Outputs, and the outside air/exhaust air damper positions shall be indicated by end switch inputs, for unit operation condition.

Air Flow & Static Pressure Control-Normal Operation:

Supply air flow and static pressure shall be controlled by the DDC Controller to compensate for filter dust loading and wet/dry cooling coil pressure drop. The DDC Controller shall modulate the supply fan VFD to maintain the duct static pressure setpoint of 1.0” W.C. (adj.), as sensed by DP-3.

Air flow measuring station signals for the supply air and return air (AFMS-1 & AFMS-2 respectively), reset the exhaust fan (VFD) to maintain a constant air flow differential between the supply fan and the exhaust fan equal to the capacity of general exhaust fan (EF-P1) serving the unpacking area.

The same air flow signals shall be used as status indication that each fan is operating. Alarm if no air flow, when fans are programmed to operate.

Analog filter pressure drop transmitter shall alarm at the DDC controller at the filter pressure drop set point (adj.).

Humidification Control:

The Energy Management System (EMS) shall monitor zone relative humidity levels through wall-mounted relative humidity sensors as scheduled on drawing. The average zone relative humidity level shall be calculated by the EMS and used to modulate the steam humidifier control valve (analog output) to maintain a zone relative humidity set point (adj.).

Supply Air Temperature Control:

The facility EMS with supply air temperature input from a supply air sensor in the supply air stream (TE-1) shall control the position of the stream and chilled water coil control valves in sequenced to maintain supply air temperature set point. The facility EMS shall continuously monitor the heating or cooling demand of each zone where an EMS temperature sensor is located and reset the supply air temperature set point to satisfy the zone with the highest cooling demand.

Max. CAV Zone Temperature Difference: Supply Air Set Point:

2 55 1 60 0 to -1.9 65

On a call for cooling, when the outside sir temp is below 72°F (adj.) the cooling coil control valve will be opened to allow increasing amounts of chilled water to the coil to meet the cooling demand.

On a call for heating, the heating control valve will be opened to allow increasing amounts of hot water to the coil to meet the heating demand.

Freeze protection low limit thermostat (LL-1) across the face of the cooling coil shall alarm at DCP if air temperature is 40°F or below.

Heat Recovery Loop Bypass Damper Control (Normal Position “Closed”):

Cooling Mode (Outside Air Temperature):

Above 75°F the “Bypass Damper” shall remain closed.

At 75°F or below the “Bypass Damper” shall remain Closed.

Heating Mode (Outside Air temperature):

Below 50°F the “Bypass Damper” shall remain Closed At 55°F or above the “Bypass Damper” open position shall be determined by the discharge supply air set point.

Sequence Of Operations

VA Hospital Reno Pharmacy_Master Mechanical.vsd
TitleSheet
TCP
AHU
CAV-P1 & P2