Attachment 2.1 668-24-108 Drawings.pdf
PDF 4 MB Posted
- Solicitation number
- 36C26027R0021
About this file
This document is a set of 100% construction documents for a federal repair project at Mann-Grandstaff VA Medical Center in Spokane, Washington. The project (No. 668-24-108) involves repair of sanitary waste piping in Building 1, a nine-story healthcare facility operated by the U.S. Department of Veterans Affairs under VISN 20. The construction documents include life safety drawings for all floors (basement through ninth floor/penthouse), general notes and abbreviations, plumbing and electrical plans, ICRA (Infection Control Risk Assessment) floor plans, hazardous materials identification, and a phased construction schedule totaling 195 calendar days across seven phases.
The project requires strict compliance with applicable building codes (International Building Code 2021), life safety standards (NFPA 101 2024), plumbing codes (International Plumbing Code 2024), and electrical codes (NEC 2023). Work must be scheduled outside VA Medical Center operating hours (6 AM to 6 PM within construction areas), with material hauling restricted to before 8 AM or after 5 PM. The project includes traditional asbestos abatement (approximately 300 linear feet of pipe insulation removal) and lead-based paint removal and disposal (approximately 720 square feet). ICRA Level III containment is required with negative pressurization, HEPA filtration, and daily monitoring. The contractor is responsible for all demolition, new piping installation, testing, water purification, finish painting, and final closeout, with emphasis on protecting existing building systems and maintaining facility operations throughout construction.
View the file
Other files
Show all 14
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
COVER SHEET
GI000
SABBVG
PROJECT SITE MAPPROJECT LOCATION MAP
MANN-GRANDSTAFF VA
4815 NORTH ASSEMBLY ST. SPOKANE WA, 99205
PROJECT #668-24-108
REPAIR SANITARY WASTE PIPING BLDG 1
DRAWING INDEX
U.S. Department of Veterans Affairs
WASHINGTON - VISN 20
GENERAL
GI000 COVER SHEET
GI001 GENERAL NOTES, SYMBOLS, AND ABBREVIATIONS
GI100 LIFE SAFETY DRAWING BASEMENT LEVEL
GI110 LIFE SAFETY DRAWING FIRST FLOOR
GI120 LIFE SAFETY DRAWING SECOND FLOOR
GI130 LIFE SAFETY DRAWING THIRD FLOOR
GI140 LIFE SAFETY DRAWING FOURTH FLOOR
GI150 LIFE SAFETY DRAWING FIFTH FLOOR
GI160 LIFE SAFETY DRAWING SIXTH FLOOR
GI170 LIFE SAFETY DRAWING SEVENTH FLOOR
GI180 LIFE SAFETY DRAWING EIGHTH FLOOR
GI190 LIFE SAFETY DRAWING NINTH FLOOR
GC100 ICRA FLOOR PLAN
GC101 PHASING PLAN
HA100 HAZARDOUS MATERIALS
ARCHITECTURAL
AE100 FLOOR PLAN
AE200 BASEMENT LEVEL ELEVATION
AE201 FIRST FLOOR ELEVATION
AE202 SECOND FLOOR ELEVATION
AE203 THIRD FLOOR ELEVATION
AE204 FOURTH FLOOR ELEVATION
AE205 FIFTH FLOOR ELEVATION
AE206 SIXTH FLOOR ELEVATION
AE207 SEVENTH FLOOR ELEVATION
AE208 EIGHTH FLOOR ELEVATION
AE209 NINTH FLOOR ELEVATION
AE400 DETAILS
AE401 APPLIED WALL DETAILS
AE402 EXISTING WALL DETAILS (ADD ALTERNATIVE ONLY)
PLUMBING
P-001 PLUMBING LEGEND, GENERAL NOTES AND ABBREVIATIONS
PD200 PLUMBING DEMO PLAN – DRINKING WATER
PD201 PLUMBING DEMO PLAN – SANITARY, VENT, AND ROOF LEADER
PP200 PLUMBING PLAN – DRINKING WATER
PP201 PLUMBING PLAN – SANITARY, VENT, AND ROOF LEADER
PP400 STACK 25 RISER DIAGRAM AND SCHEDULE
PP401 PLUMBING DETAILS
ELECTRICAL
EG001 ELECTRICAL LEGEND AND GENERAL NOTES
E-100 FLOOR PLANS - ELECTRICAL
SPOKANE
WORK
AREA
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
MANN-GRANDSTAFF
VA MEDICAL
CENTER
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
Project Director
Revisions: Date:
100% CONSTRUCTION
DOCUMENTS
NOT FOR CONSTRUCTION
REPAIR SANITARY WASTE
PIPING
668-24-108
20-JUN-2025
MANN-GRANDSTAFF VA MEDICAL CENTER
(502) 890-2210 * WESTPOINTENGINEERS.COM
1941 BISHOP LANE, STE. 400 * LOUISVILLE, KY 40218
4815 N ASSEMBLY ST., SPOKANE, WA 99205
NOT F
OR
CONSTRUCTIO
N
TYPICAL TOILET TYPICAL TOILET
SURFACE MOUNTED
PAPER TOWEL
DISPENSER
RECESSED PAPER
TOWEL DISPENSER
AND WASTE
RECEPTACLE
SEMI-RECESSED PAPER
TOWEL DISPENSER AND
WASTE RECEPTACLE
SURFACE MOUNTED SOAP
DISPENSER
SURFACE MOUNTED
CHANNEL FRAME MIRROR
SURFACE MOUNTED HAND
DRYER
ROBE HOOK
SURFACE MOUNTED
BABY CHANGING
STATION
TOILET PAPER
DISPENSER
TWIN JUMBO ROLL
SURFACE MOUNTED
FEMININE NAPKIN DISPOSAL
RECESSED FEMININE NAPKIN
DISPOSAL
RECESSED SEAT COVER
DISPENSER
POSTURE MIRROR
RECESSED FIRE
EXTINGUISHER CABINET SHARPS CONTAINER
SHARPS CONTAINER
WITH GLOVE BOX CLOCK WATER
BOTTLE STATION
DRINKING
FOUNTAINS
CONTRACT LIMIT LINE
ELEVATION INDICATOR
CENTER LINE INDICATOR
EXISTING TO REMAIN LINE
HIDDEN FEATURES LINE
BREAK, ROUND (USER DEFINES SIZE)
BREAK, STRAIGHT (SEE SECTION INDICATORS,
BUILDING, WITH BREAK STANDARDS)
DETAIL INDICATOR
DIMENSION LINE
DRAWING BLOCK TITLE, TYPICAL
ELEVATION INDICATOR
ELEVATION INDICATOR, INTERIOR, MULTIPLE VIEW
ELEVATION INDICATOR, INTERIOR, SINGLE VIEW
PHOTOGRAPH INDICATOR
CENTER LINE
FURNITURE, FIXTURE, & EQUIPMENT INDICATOR
GRAPHIC SCALE, 18"=1'-0"
ROOM NAME AND NUMBER
COLUMN GRID
NORTH ARROW
BUILDING SECTION INDICATOR
SYMBOLSABBREVIATIONS
NOTE:
MATCHLINE
DETAIL NUMBER
SHEET WHERE DRAWN
DOOR INDICATOR
WALL TYPE ( SEE SHEET AE500 )
WINDOW TYPE
THE CONTRACTOR IS TO SCHEDULE SELECT WORK AS AN AFTER-VAMC HOURS PROJECT AS WELL AS WEEKENDS OR HOLIDAYS; THIS INCLUDES THE CONSTRUCTION OF CORRIDOR BARRIERS AND ANY SYSTEM SHUTDOWN WORK. WORK WITHIN THE DESIGNATED CONSTRUCTION AREA WILL BE COMPLETED BETWEEN 6 AM AND 6 PM. HAULING OF MATERIALS TO AND FROM THE SITE TO TAKE PLACE BEFORE 8 AM OR AFTER 5 PM.
GENERAL INFORMATION
1. THE CONTRACTOR IS RESPONSIBLE FOR VERIFYING ALL FIELD CONDITIONS BEFORE CONSTRUCTION STARTS AND SHALL NOTIFY THE COR OF ANY DISCREPANCIES.
2. THE CONTRACTOR SHALL REVIEW THE CONTRACT DOCUMENTS FOR CONFLICTS. WHERE CONFLICTS EXIST WITHIN THE DRAWINGS, WORK SHALL NOT PROCEED UNTIL THE COR IS NOTIFIED AND DIRECTION IS GIVEN.
3. WHERE INCIDENTAL WORK IS REQUIRED TO ACCOMPLISH WORK SHOWN ON THE DRAWINGS, THIS WORK IS IMPLIED AND SHALL BE INCLUDED AS PART OF THE BASE BID.
4. BEFORE ANY WORK COMMENCES IN AN AREA, THE CONTRACTOR SHALL NOTIFY THE COR OF HIS INTENTION TO WORK IN THE AREA AND SHALL SCHEDULE A WALK-THROUGH WITH THE COR TO DETERMINE EXISTING CONDITIONS, PREPARE AN ACTIVITY HAZARD ANALYSIS AND SUBMIT A PLAN TO COMPLETE THE WORK TO THE COR FOR APPROVAL. THE AREAS OF WORK SHALL BE RETURNED TO THEIR ORIGINAL STATE BEFORE
REQUESTING FINAL APPROVAL OF THE WORK FROM THE COR.
5. AFTER CONSTRUCTION COMPLETION, THE CONTRACTOR SHALL CLEAN ALL SURFACES OF CONSTRUCTION DEBRIS. SURFACES SHALL BE WIPED CLEAN OF DUST, INCLUDING FIXTURES, WINDOWS AND WINDOW SILLS, DOOR FRAMES, ETC. THE CONTRACTOR SHALL CLEAN USING VAMC-APPROVED PRODUCTS.
6. CONTRACTOR IS RESPONSIBLE FOR CONFORMING TO ALL BUILDING CODES AND SHALL NOT KNOWINGLY EXECUTE WORK WHICH IS NOT IN CONFORMANCE.
7. CONTRACTOR TO INSPECT ALL WALLS FOR FUNCTION. NOTIFY THE COR OF ANY CONDITIONS THAT WILL PREVENT THE CONTRACTOR TO ACHIEVE A COMPLETE PROJECT.
8. CONTRACTOR TO PROTECT ALL PORTIONS OF THE EXISTING BUILDING TO REMAIN DURING DEMOLITION/ CONSTRUCTION. THE CONTRACTOR IS RESPONSIBLE FOR ANY/ALL DAMAGES DURING THE WORK.
9. CONTRACTOR SHALL MAINTAIN ALL EXISTING ACCESS PANELS AND PROVIDE NEW ACCESS PANELS AS REQUIRED IN AREAS OF RENOVATION AND NEW CONSTRUCTION.
10. CONTRACTOR TO REMOVE ALL UNUSED SCREWS, CLIPS, AND FASTENERS. HOLES WILL BE PATCHED AND PREPPED.
11. ALL DIMENSIONS ARE TO FINISH FACE OF WALL UNLESS OTHERWISE NOTED.
12. PAINTING: SAND EXISTING SURFACES, REMOVE ANY DEFECTS, PRIME AND PAINT FROM CEILING TO THE NEAREST INSIDE/OUTSIDE CORNERS. UNLESS NOTED OTHERWISE.
13. ALL SEALANTS SHALL BE DRY TOOLED. SUPPLY AND UTILIZE A TEST AREA, COORDINATED WITH THE COR, FOR FINISH PRODUCT REFERENCE.
14. THE CONSTRUCTION AREAS WILL BE TURNED OVER TO THE CONTRACTOR FOR THE LIFE OF THE SCHEDULED / PHASED SITE WORK.
15. CONTRACTOR TO PROTECT ALL EXISTING UTILITIES.
16. COORDINATE WITH THE COR ON CONTRACTOR PARKING LOCATION.
17. THE CONTRACTOR IS RESPONSIBLE FOR PROTECTING SIDEWALKS, PAVEMENT, AND CURBS. REPLACE COMPLETE SECTIONS WITH NEW IF DAMAGED.
18. THIS PROJECT IS A BUY AMERICA ACT PROJECT.
A
A
PATIENT
ROOM
AE209
AE209
AE209
B
GC100
AE209
A
AE202
TITLE
1/4" = 1'-0"
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
MANN-GRANDSTAFF
VA MEDICAL
CENTER
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
Project Director
Revisions: Date:
100% CONSTRUCTION
DOCUMENTS
NOT FOR CONSTRUCTION
REPAIR SANITARY WASTE
PIPING
668-24-108
20-JUN-2025
MANN-GRANDSTAFF VA MEDICAL CENTER
(502) 890-2210 * WESTPOINTENGINEERS.COM
1941 BISHOP LANE, STE. 400 * LOUISVILLE, KY 40218
4815 N ASSEMBLY ST., SPOKANE, WA 99205
ABBREVIATIONS AND SYMBOLS
GI001
SABBVG
NOT F
OR
C O A010
A007D
AOO7C
C002A
A009
A008 C001
C003A
C002
A006C
A006
A007
C002C
C003
A009A A002B
A002A
A002
D
D D
C O
C O
C O
C O
C O
C O
C O
C O
C O
D D D
D
D
D
C O
O O
D
BUILDING CODE AND GUIDELINES
A. APPLICABLE CODES:
ALL WORK SHALL CONFIRM TO ALL APPLICABLE CODES, STANDARDS AND GOVERNING AUTHORITIES:
INCLUDING BUT NOT LIMITED TO:
BUILDING: INTERNATIONAL BUILDING CODE, 2021 EDITION
LIFE SAFETY: NFPA 101 LIFE SAFETY CODE, 2024 EDITION
MECHANICAL: INTERNATIONAL MECHANICAL CODE, 2024 EDITION
NFPA 90A
PLUMBING: INTERNATIONAL PLUMBING CODE, 2024 EDITION
FIRE PREVENTION: NFPA NATIONAL FIRE CODES WITH THE EXCEPTION
OF NFPA 5000 AND NFPA 900, CURRENT ED.
ELECTRICAL: NATIONAL ELECTRICAL CODE (NEC), 2023 EDITION
ACCESSIBILITY: ABAAS INCLUDING VA SUPPLEMENT. BARRIER FREE
DESIGN
VA PUBLICATIONS: VA DIRECTIVES, DESIGN MANUALS, AND OTHER
GUIDANCE ON THE TECHNICAL INFORMATION
LIBRARY (TIL)
B. OCCUPANCY USE: NFPA 101 2024: CHAPTER 19 EXISTING
HEALTHCARE OCCUPANCIES
IBC: INSTITUTIONAL I-2
C. CONSTRUCTION TYPE: NFPA 101: TYPE II (222)
IBC: TYPE 2B (PROTECTED)
BASEMENT - CONTRACTOR / EMERGENCY EGRESS PLAN
NTS
KEY PLAN: GROUND FLOOR
A
GI004
B
AE100
B
GC100
HEPA
EXHAUST
HEPA
EXHAUST
H
EP
A
EX
H
AU
ST
H
EP
A
EX
H
AU
ST
LIFE SAFETY PLAN LEGEND
NOTE: ALL SYMBOLS MAY NOT BE USED
FIRE EXTINGUISHER CABINET / FIRE EXTINGUISHER
HORIZONTAL EXIT
EXIT SIGN
EGRESS PATH (COMMON PATH)
RATED WALL ASSEMBLY TYPES
RATE WALL ASSEMBLY LEGEND
NOTE:
ALL SYMBOLS MAY NOT BE USED EXISTING RATED WALLS SHOWN AS HALF-TONE
FIRE RESISTIVE RATED, 1 HOUR
FIRE RESISTIVE RATED, 2 HOUR
FIRE-RATED, SMOKE PARTITION, 1 HOUR
FIRE-RATED, SMOKE PARTITION, 2 HOUR
NON-RATED PARTITION
NON-RATED, SUITE, (SMOKE RESISTIVE)
EMERGENCY BATTERY WALL PACK LIGHT
SUITE DESIGNATIONS (EXISTING)
1. SECURITY CAMERAS LINE OF SIGHT WILL BE BLOCKED WHILE CONSTRUCTION WALLS ARE IN PLACE.
VA WILL ADJUST CAMERAS IF NEEDED.
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
MANN-GRANDSTAFF
VA MEDICAL
CENTER
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
Project Director
Revisions: Date:
100% CONSTRUCTION
DOCUMENTS
NOT FOR CONSTRUCTION
REPAIR SANITARY WASTE
PIPING
668-24-108
20-JUN-2025
MANN-GRANDSTAFF VA MEDICAL CENTER
(502) 890-2210 * WESTPOINTENGINEERS.COM
1941 BISHOP LANE, STE. 400 * LOUISVILLE, KY 40218
4815 N ASSEMBLY ST., SPOKANE, WA 99205
LIFE SAFETY DRAWING BASEMENT
LEVEL
GI100
SABBVG
NOT F
OR
C O
A105
A106 A108
A107 A110 A111
A112
C100
A114A113
A104
C102
A100
A119A
A119
A101
A121
A122A123
A12
A12
A120 A118A A118 A117 A116 A115
C116
C118
C120
C105 C107
C109
C111 C113 C115
C117
C104
C106 C108 C110 C112
A102
A121A
UP
BUILDING CODE AND GUIDELINES
A. APPLICABLE CODES:
ALL WORK SHALL CONFIRM TO ALL APPLICABLE CODES, STANDARDS AND GOVERNING AUTHORITIES:
INCLUDING BUT NOT LIMITED TO:
BUILDING: INTERNATIONAL BUILDING CODE, 2021 EDITION
LIFE SAFETY: NFPA 101 LIFE SAFETY CODE, 2024 EDITION
MECHANICAL: INTERNATIONAL MECHANICAL CODE, 2024 EDITION
NFPA 90A
PLUMBING: INTERNATIONAL PLUMBING CODE, 2024 EDITION
FIRE PREVENTION: NFPA NATIONAL FIRE CODES WITH THE EXCEPTION
OF NFPA 5000 AND NFPA 900, CURRENT ED.
ELECTRICAL: NATIONAL ELECTRICAL CODE (NEC), 2023 EDITION
ACCESSIBILITY: ABAAS INCLUDING VA SUPPLEMENT. BARRIER FREE
DESIGN
VA PUBLICATIONS: VA DIRECTIVES, DESIGN MANUALS, AND OTHER
GUIDANCE ON THE TECHNICAL INFORMATION
LIBRARY (TIL)
B. OCCUPANCY USE: NFPA 101 2024: CHAPTER 19 EXISTING
HEALTHCARE OCCUPANCIES
IBC: INSTITUTIONAL I-2
C. CONSTRUCTION TYPE: NFPA 101: TYPE II (222)
IBC: TYPE 2B (PROTECTED)
FIRST FLOOR - CONTRACTOR / EMERGENCY EGRESS PLAN
NTS
KEY PLAN: GROUND FLOOR
A
GI005
AE100
LIFE SAFETY PLAN LEGEND
NOTE: ALL SYMBOLS MAY NOT BE USED
FIRE EXTINGUISHER CABINET / FIRE EXTINGUISHER
HORIZONTAL EXIT
EXIT SIGN
EGRESS PATH (COMMON PATH)
RATED WALL ASSEMBLY TYPES
RATE WALL ASSEMBLY LEGEND
NOTE:
ALL SYMBOLS MAY NOT BE USED EXISTING RATED WALLS SHOWN AS HALF-TONE
FIRE RESISTIVE RATED, 1 HOUR
FIRE RESISTIVE RATED, 2 HOUR
FIRE-RATED, SMOKE PARITION, 1 HOUR
FIRE-RATED, SMOKE PARTITON, 2 HOUR
NON-RATED PARTITION
NON-RATED, SUITE, (SMOKE RESISTIVE)
EMERGENCY BATTERY WALL PACK LIGHT
SUITE DESIGNATIONS (EXISTING)
UP
GC100
1. SECURITY CAMERAS LINE OF SIGHT WILL BE BLOCKED WHILE CONSTRUCTION WALLS ARE IN PLACE.
VA WILL ADJUST CAMERAS IF NEEDED.
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
MANN-GRANDSTAFF
VA MEDICAL
CENTER
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
Project Director
Revisions: Date:
100% CONSTRUCTION
DOCUMENTS
NOT FOR CONSTRUCTION
REPAIR SANITARY WASTE
PIPING
668-24-108
20-JUN-2025
MANN-GRANDSTAFF VA MEDICAL CENTER
(502) 890-2210 * WESTPOINTENGINEERS.COM
1941 BISHOP LANE, STE. 400 * LOUISVILLE, KY 40218
4815 N ASSEMBLY ST., SPOKANE, WA 99205
LIFE SAFETY DRAWING FIRST FLOOR
GI110
SABBVG
NOT F
OR
A213 A212
A208
1208A
A206
A209
A205
A214
A209A
A200 A216A A216 A215
C201
C217
C219
C221
C223
C222
C218
C203
C205 C209
C207 C211 C213
A201
C200 C202
C202A
C204 C206
C208
C O
C O
D
BUILDING CODE AND GUIDELINES
A. APPLICABLE CODES:
ALL WORK SHALL CONFIRM TO ALL APPLICABLE CODES, STANDARDS AND GOVERNING AUTHORITIES:
INCLUDING BUT NOT LIMITED TO:
BUILDING: INTERNATIONAL BUILDING CODE, 2021 EDITION
LIFE SAFETY: NFPA 101 LIFE SAFETY CODE, 2024 EDITION
MECHANICAL: INTERNATIONAL MECHANICAL CODE, 2024 EDITION
NFPA 90A
PLUMBING: INTERNATIONAL PLUMBING CODE, 2024 EDITION
FIRE PREVENTION: NFPA NATIONAL FIRE CODES WITH THE EXCEPTION
OF NFPA 5000 AND NFPA 900, CURRENT ED.
ELECTRICAL: NATIONAL ELECTRICAL CODE (NEC), 2023 EDITION
ACCESSIBILITY: ABAAS INCLUDING VA SUPPLEMENT. BARRIER FREE
DESIGN
VA PUBLICATIONS: VA DIRECTIVES, DESIGN MANUALS, AND OTHER
GUIDANCE ON THE TECHNICAL INFORMATION
LIBRARY (TIL)
B. OCCUPANCY USE: NFPA 101 2024: CHAPTER 19 EXISTING
HEALTHCARE OCCUPANCIES
IBC: INSTITUTIONAL I-2
C. CONSTRUCTION TYPE: NFPA 101: TYPE II (222)
IBC: TYPE 2B (PROTECTED)
SECOND FLOOR - CONTRACTOR / EMERGENCY EGRESS PLAN
NTS
KEY PLAN: SECOND FLOOR
A
GI006
STAIR CLOSED
AE100
UP DN
GC100
LIFE SAFETY PLAN LEGEND
NOTE: ALL SYMBOLS MAY NOT BE USED
FIRE EXTINGUISHER CABINET / FIRE EXTINGUISHER
HORIZONTAL EXIT
EXIT SIGN
EGRESS PATH (COMMON PATH)
RATED WALL ASSEMBLY TYPES
RATE WALL ASSEMBLY LEGEND
NOTE:
ALL SYMBOLS MAY NOT BE USED EXISTING RATED WALLS SHOWN AS HALF-TONE
FIRE RESISTIVE RATED, 1 HOUR
FIRE RESISTIVE RATED, 2 HOUR
FIRE-RATED, SMOKE PARTITION, 1 HOUR
FIRE-RATED, SMOKE PARTITION, 2 HOUR
NON-RATED PARTITION
NON-RATED, SUITE, (SMOKE RESISTIVE)
EMERGENCY BATTERY WALL PACK LIGHT
SUITE DESIGNATIONS (EXISTING)
1. SECURITY CAMERAS LINE OF SIGHT WILL BE BLOCKED WHILE CONSTRUCTION WALLS ARE IN PLACE.
VA WILL ADJUST CAMERAS IF NEEDED.
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
MANN-GRANDSTAFF
VA MEDICAL
CENTER
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
Project Director
Revisions: Date:
100% CONSTRUCTION
DOCUMENTS
NOT FOR CONSTRUCTION
REPAIR SANITARY WASTE
PIPING
668-24-108
20-JUN-2025
MANN-GRANDSTAFF VA MEDICAL CENTER
(502) 890-2210 * WESTPOINTENGINEERS.COM
1941 BISHOP LANE, STE. 400 * LOUISVILLE, KY 40218
4815 N ASSEMBLY ST., SPOKANE, WA 99205
LIFE SAFETY DRAWING SECOND FLOOR
GI120
SABBVG
NOT F
OR
C O
C O
D
C O
D
D
D
D
A313B
A313
A312A
A312 A313A
A314
A313D
A315
A316 C300 C302A
A313C
C302B C304
C306 C310 C312
C325C319
C308
C317 C321 C323 C327
C315
C313C307A
C307C305C303C301A300 A301A302
A311
C309
BUILDING CODE AND GUIDELINES
A. APPLICABLE CODES:
ALL WORK SHALL CONFIRM TO ALL APPLICABLE CODES, STANDARDS AND GOVERNING AUTHORITIES:
INCLUDING BUT NOT LIMITED TO:
BUILDING: INTERNATIONAL BUILDING CODE, 2021 EDITION
LIFE SAFETY: NFPA 101 LIFE SAFETY CODE, 2024 EDITION
MECHANICAL: INTERNATIONAL MECHANICAL CODE, 2024 EDITION
NFPA 90A
PLUMBING: INTERNATIONAL PLUMBING CODE, 2024 EDITION
FIRE PREVENTION: NFPA NATIONAL FIRE CODES WITH THE EXCEPTION
OF NFPA 5000 AND NFPA 900, CURRENT ED.
ELECTRICAL: NATIONAL ELECTRICAL CODE (NEC), 2023 EDITION
ACCESSIBILITY: ABAAS INCLUDING VA SUPPLEMENT. BARRIER FREE
DESIGN
VA PUBLICATIONS: VA DIRECTIVES, DESIGN MANUALS, AND OTHER
GUIDANCE ON THE TECHNICAL INFORMATION
LIBRARY (TIL)
B. OCCUPANCY USE: NFPA 101 2024: CHAPTER 19 EXISTING
HEALTHCARE OCCUPANCIES
IBC: INSTITUTIONAL I-2
C. CONSTRUCTION TYPE: NFPA 101: TYPE II (222)
IBC: TYPE 2B (PROTECTED)
THIRD FLOOR - CONTRACTOR / EMERGENCY EGRESS PLAN
NTS
KEY PLAN: FOURTH FLOOR
A
GI007
STAIR CLOSED
AE100
UP DN
GC100
LIFE SAFETY PLAN LEGEND
NOTE: ALL SYMBOLS MAY NOT BE USED
FIRE EXTINGUISHER CABINET / FIRE EXTINGUISHER
HORIZONTAL EXIT
EXIT SIGN
EGRESS PATH (COMMON PATH)
RATED WALL ASSEMBLY TYPES
RATE WALL ASSEMBLY LEGEND
NOTE:
ALL SYMBOLS MAY NOT BE USED EXISTING RATED WALLS SHOWN AS HALF-TONE
FIRE RESISTIVE RATED, 1 HOUR
FIRE RESISTIVE RATED, 2 HOUR
FIRE-RATED, SMOKE PARTITION, 1 HOUR
FIRE-RATED, SMOKE PARTITION, 2 HOUR
NON-RATED PARTITION
NON-RATED, SUITE, (SMOKE RESISTIVE)
EMERGENCY BATTERY WALL PACK LIGHT
SUITE DESIGNATIONS (EXISTING)
1. SECURITY CAMERAS LINE OF SIGHT WILL BE BLOCKED WHILE CONSTRUCTION WALLS ARE IN PLACE.
VA WILL ADJUST CAMERAS IF NEEDED.
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
MANN-GRANDSTAFF
VA MEDICAL
CENTER
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
Project Director
Revisions: Date:
100% CONSTRUCTION
DOCUMENTS
NOT FOR CONSTRUCTION
REPAIR SANITARY WASTE
PIPING
668-24-108
20-JUN-2025
MANN-GRANDSTAFF VA MEDICAL CENTER
(502) 890-2210 * WESTPOINTENGINEERS.COM
1941 BISHOP LANE, STE. 400 * LOUISVILLE, KY 40218
4815 N ASSEMBLY ST., SPOKANE, WA 99205
LIFE SAFETY DRAWING THIRD FLOOR
GI130
SABBVG
NOT F
OR
C402C400 C404
C407C405C401 C403
A417
A418
A413
BUILDING CODE AND GUIDELINES
A. APPLICABLE CODES:
ALL WORK SHALL CONFIRM TO ALL APPLICABLE CODES, STANDARDS AND GOVERNING AUTHORITIES:
INCLUDING BUT NOT LIMITED TO:
BUILDING: INTERNATIONAL BUILDING CODE, 2021 EDITION
LIFE SAFETY: NFPA 101 LIFE SAFETY CODE, 2024 EDITION
MECHANICAL: INTERNATIONAL MECHANICAL CODE, 2024 EDITION
NFPA 90A
PLUMBING: INTERNATIONAL PLUMBING CODE, 2024 EDITION
FIRE PREVENTION: NFPA NATIONAL FIRE CODES WITH THE EXCEPTION
OF NFPA 5000 AND NFPA 900, CURRENT ED.
ELECTRICAL: NATIONAL ELECTRICAL CODE (NEC), 2023 EDITION
ACCESSIBILITY: ABAAS INCLUDING VA SUPPLEMENT. BARRIER FREE
DESIGN
VA PUBLICATIONS: VA DIRECTIVES, DESIGN MANUALS, AND OTHER
GUIDANCE ON THE TECHNICAL INFORMATION
LIBRARY (TIL)
B. OCCUPANCY USE: NFPA 101 2024: CHAPTER 19 EXISTING
HEALTHCARE OCCUPANCIES
IBC: INSTITUTIONAL I-2
C. CONSTRUCTION TYPE: NFPA 101: TYPE II (222)
IBC: TYPE 2B (PROTECTED)
A
GI007
STAIR CLOSED
FOURTH FLOOR - CONTRACTOR / EMERGENCY EGRESS PLAN
NTS
KEY PLAN: FOURTH FLOOR
AE100
UP DN
GC100
LIFE SAFETY PLAN LEGEND
NOTE: ALL SYMBOLS MAY NOT BE USED
FIRE EXTINGUISHER CABINET / FIRE EXTINGUISHER
HORIZONTAL EXIT
EXIT SIGN
EGRESS PATH (COMMON PATH)
RATED WALL ASSEMBLY TYPES
RATE WALL ASSEMBLY LEGEND
NOTE:
ALL SYMBOLS MAY NOT BE USED EXISTING RATED WALLS SHOWN AS HALF-TONE
FIRE RESISTIVE RATED, 1 HOUR
FIRE RESISTIVE RATED, 2 HOUR
FIRE-RATED, SMOKE PARTITION, 1 HOUR
FIRE-RATED, SMOKE PARTITION, 2 HOUR
NON-RATED PARTITION
NON-RATED, SUITE, (SMOKE RESISTIVE)
EMERGENCY BATTERY WALL PACK LIGHT
SUITE DESIGNATIONS (EXISTING)
1. SECURITY CAMERAS LINE OF SIGHT WILL BE BLOCKED WHILE CONSTRUCTION WALLS ARE IN PLACE.
VA WILL ADJUST CAMERAS IF NEEDED.
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
MANN-GRANDSTAFF
VA MEDICAL
CENTER
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
Project Director
Revisions: Date:
100% CONSTRUCTION
DOCUMENTS
NOT FOR CONSTRUCTION
REPAIR SANITARY WASTE
PIPING
668-24-108
20-JUN-2025
MANN-GRANDSTAFF VA MEDICAL CENTER
(502) 890-2210 * WESTPOINTENGINEERS.COM
1941 BISHOP LANE, STE. 400 * LOUISVILLE, KY 40218
4815 N ASSEMBLY ST., SPOKANE, WA 99205
LIFE SAFETY DRAWING FOURTH FLOOR
GI140
SABBVG
NOT F
OR
C502 C500
C507C505C501 C503
A511
A512
A510
BUILDING CODE AND GUIDELINES
A. APPLICABLE CODES:
ALL WORK SHALL CONFIRM TO ALL APPLICABLE CODES, STANDARDS AND GOVERNING AUTHORITIES:
INCLUDING BUT NOT LIMITED TO:
BUILDING: INTERNATIONAL BUILDING CODE, 2021 EDITION
LIFE SAFETY: NFPA 101 LIFE SAFETY CODE, 2024 EDITION
MECHANICAL: INTERNATIONAL MECHANICAL CODE, 2024 EDITION
NFPA 90A
PLUMBING: INTERNATIONAL PLUMBING CODE, 2024 EDITION
FIRE PREVENTION: NFPA NATIONAL FIRE CODES WITH THE EXCEPTION
OF NFPA 5000 AND NFPA 900, CURRENT ED.
ELECTRICAL: NATIONAL ELECTRICAL CODE (NEC), 2023 EDITION
ACCESSIBILITY: ABAAS INCLUDING VA SUPPLEMENT. BARRIER FREE
DESIGN
VA PUBLICATIONS: VA DIRECTIVES, DESIGN MANUALS, AND OTHER
GUIDANCE ON THE TECHNICAL INFORMATION
LIBRARY (TIL)
B. OCCUPANCY USE: NFPA 101 2024: CHAPTER 19 EXISTING
HEALTHCARE OCCUPANCIES
IBC: INSTITUTIONAL I-2
C. CONSTRUCTION TYPE: NFPA 101: TYPE II (222)
IBC: TYPE 2B (PROTECTED)
A
GI008
STAIR CLOSED
FIFTH FLOOR - CONTRACTOR / EMERGENCY EGRESS PLAN
NTS
KEY PLAN: FIFTH FLOOR
AE100
UP DN
GC100
LIFE SAFETY PLAN LEGEND
NOTE: ALL SYMBOLS MAY NOT BE USED
FIRE EXTINGUISHER CABINET / FIRE EXTINGUISHER
HORIZONTAL EXIT
EXIT SIGN
EGRESS PATH (COMMON PATH)
RATED WALL ASSEMBLY TYPES
RATE WALL ASSEMBLY LEGEND
NOTE:
ALL SYMBOLS MAY NOT BE USED EXISTING RATED WALLS SHOWN AS HALF-TONE
FIRE RESISTIVE RATED, 1 HOUR
FIRE RESISTIVE RATED, 2 HOUR
FIRE-RATED, SMOKE PARTITION, 1 HOUR
FIRE-RATED, SMOKE PARTITION, 2 HOUR
NON-RATED PARTITION
NON-RATED, SUITE, (SMOKE RESISTIVE)
EMERGENCY BATTERY WALL PACK LIGHT
SUITE DESIGNATIONS (EXISTING)
1. SECURITY CAMERAS LINE OF SIGHT WILL BE BLOCKED WHILE CONSTRUCTION WALLS ARE IN PLACE.
VA WILL ADJUST CAMERAS IF NEEDED.
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
MANN-GRANDSTAFF
VA MEDICAL
CENTER
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
Project Director
Revisions: Date:
100% CONSTRUCTION
DOCUMENTS
NOT FOR CONSTRUCTION
REPAIR SANITARY WASTE
PIPING
668-24-108
20-JUN-2025
MANN-GRANDSTAFF VA MEDICAL CENTER
(502) 890-2210 * WESTPOINTENGINEERS.COM
1941 BISHOP LANE, STE. 400 * LOUISVILLE, KY 40218
4815 N ASSEMBLY ST., SPOKANE, WA 99205
LIFE SAFETY DRAWING FIFTH FLOOR
GI150
SABBVG
NOT F
OR
C600 C602
C607C605C601 C603
A614
A616
A613
A615
A617
BUILDING CODE AND GUIDELINES
A. APPLICABLE CODES:
ALL WORK SHALL CONFIRM TO ALL APPLICABLE CODES, STANDARDS AND GOVERNING AUTHORITIES:
INCLUDING BUT NOT LIMITED TO:
BUILDING: INTERNATIONAL BUILDING CODE, 2021 EDITION
LIFE SAFETY: NFPA 101 LIFE SAFETY CODE, 2024 EDITION
MECHANICAL: INTERNATIONAL MECHANICAL CODE, 2024 EDITION
NFPA 90A
PLUMBING: INTERNATIONAL PLUMBING CODE, 2024 EDITION
FIRE PREVENTION: NFPA NATIONAL FIRE CODES WITH THE EXCEPTION
OF NFPA 5000 AND NFPA 900, CURRENT ED.
ELECTRICAL: NATIONAL ELECTRICAL CODE (NEC), 2023 EDITION
ACCESSIBILITY: ABAAS INCLUDING VA SUPPLEMENT. BARRIER FREE
DESIGN
VA PUBLICATIONS: VA DIRECTIVES, DESIGN MANUALS, AND OTHER
GUIDANCE ON THE TECHNICAL INFORMATION
LIBRARY (TIL)
B. OCCUPANCY USE: NFPA 101 2024: CHAPTER 19 EXISTING
HEALTHCARE OCCUPANCIES
IBC: INSTITUTIONAL I-2
C. CONSTRUCTION TYPE: NFPA 101: TYPE II (222)
IBC: TYPE 2B (PROTECTED)
A
GI009
STAIR CLOSED
SIXTH FLOOR - CONTRACTOR / EMERGENCY EGRESS PLAN
NTS
KEY PLAN: SIXTH FLOOR
AE100
UP DN
GC100
LIFE SAFETY PLAN LEGEND
NOTE: ALL SYMBOLS MAY NOT BE USED
FIRE EXTINGUISHER CABINET / FIRE EXTINGUISHER
HORIZONTAL EXIT
EXIT SIGN
EGRESS PATH (COMMON PATH)
RATED WALL ASSEMBLY TYPES
RATE WALL ASSEMBLY LEGEND
NOTE:
ALL SYMBOLS MAY NOT BE USED EXISTING RATED WALLS SHOWN AS HALF-TONE
FIRE RESISTIVE RATED, 1 HOUR
FIRE RESISTIVE RATED, 2 HOUR
FIRE-RATED, SMOKE PARTITION, 1 HOUR
FIRE-RATED, SMOKE PARTITION, 2 HOUR
NON-RATED PARTITION
NON-RATED, SUITE, (SMOKE RESISTIVE)
EMERGENCY BATTERY WALL PACK LIGHT
SUITE DESIGNATIONS (EXISTING)
1. SECURITY CAMERAS LINE OF SIGHT WILL BE BLOCKED WHILE CONSTRUCTION WALLS ARE IN PLACE.
VA WILL ADJUST CAMERAS IF NEEDED.
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
MANN-GRANDSTAFF
VA MEDICAL
CENTER
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
Project Director
Revisions: Date:
100% CONSTRUCTION
DOCUMENTS
NOT FOR CONSTRUCTION
REPAIR SANITARY WASTE
PIPING
668-24-108
20-JUN-2025
MANN-GRANDSTAFF VA MEDICAL CENTER
(502) 890-2210 * WESTPOINTENGINEERS.COM
1941 BISHOP LANE, STE. 400 * LOUISVILLE, KY 40218
4815 N ASSEMBLY ST., SPOKANE, WA 99205
LIFE SAFETY DRAWING SIXTH FLOOR
GI160
SABBVG
NOT F
OR
C702C700
C707C705C701 C703
A711
A712
A710
A713
BUILDING CODE AND GUIDELINES
A. APPLICABLE CODES:
ALL WORK SHALL CONFIRM TO ALL APPLICABLE CODES, STANDARDS AND GOVERNING AUTHORITIES:
INCLUDING BUT NOT LIMITED TO:
BUILDING: INTERNATIONAL BUILDING CODE, 2021 EDITION
LIFE SAFETY: NFPA 101 LIFE SAFETY CODE, 2024 EDITION
MECHANICAL: INTERNATIONAL MECHANICAL CODE, 2024 EDITION
NFPA 90A
PLUMBING: INTERNATIONAL PLUMBING CODE, 2024 EDITION
FIRE PREVENTION: NFPA NATIONAL FIRE CODES WITH THE EXCEPTION
OF NFPA 5000 AND NFPA 900, CURRENT ED.
ELECTRICAL: NATIONAL ELECTRICAL CODE (NEC), 2023 EDITION
ACCESSIBILITY: ABAAS INCLUDING VA SUPPLEMENT. BARRIER FREE
DESIGN
VA PUBLICATIONS: VA DIRECTIVES, DESIGN MANUALS, AND OTHER
GUIDANCE ON THE TECHNICAL INFORMATION
LIBRARY (TIL)
B. OCCUPANCY USE: NFPA 101 2024: CHAPTER 19 EXISTING
HEALTHCARE OCCUPANCIES
IBC: INSTITUTIONAL I-2
C. CONSTRUCTION TYPE: NFPA 101: TYPE II (222)
IBC: TYPE 2B (PROTECTED)
A
GI009
STAIR CLOSED
SEVENTH FLOOR - CONTRACTOR / EMERGENCY EGRESS PLAN
NTS
KEY PLAN: SEVENTH FLOOR
AE100
UP DN
GC100
LIFE SAFETY PLAN LEGEND
NOTE: ALL SYMBOLS MAY NOT BE USED
FIRE EXTINGUISHER CABINET / FIRE EXTINGUISHER
HORIZONTAL EXIT
EXIT SIGN
EGRESS PATH (COMMON PATH)
RATED WALL ASSEMBLY TYPES
RATE WALL ASSEMBLY LEGEND
NOTE:
ALL SYMBOLS MAY NOT BE USED EXISTING RATED WALLS SHOWN AS HALF-TONE
FIRE RESISTIVE RATED, 1 HOUR
FIRE RESISTIVE RATED, 2 HOUR
FIRE-RATED, SMOKE PARTITION, 1 HOUR
FIRE-RATED, SMOKE PARTITION, 2 HOUR
NON-RATED PARTITION
NON-RATED, SUITE, (SMOKE RESISTIVE)
EMERGENCY BATTERY WALL PACK LIGHT
SUITE DESIGNATIONS (EXISTING)
1. SECURITY CAMERAS LINE OF SIGHT WILL BE BLOCKED WHILE CONSTRUCTION WALLS ARE IN PLACE.
VA WILL ADJUST CAMERAS IF NEEDED.
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
MANN-GRANDSTAFF
VA MEDICAL
CENTER
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
Project Director
Revisions: Date:
100% CONSTRUCTION
DOCUMENTS
NOT FOR CONSTRUCTION
REPAIR SANITARY WASTE
PIPING
668-24-108
20-JUN-2025
MANN-GRANDSTAFF VA MEDICAL CENTER
(502) 890-2210 * WESTPOINTENGINEERS.COM
1941 BISHOP LANE, STE. 400 * LOUISVILLE, KY 40218
4815 N ASSEMBLY ST., SPOKANE, WA 99205
LIFE SAFETY DRAWING SEVENTH
FLOOR
GI170
SABBVG
NOT F
OR
A802
A807A805
A801
A803
A800B B803
A800A
A804
BUILDING CODE AND GUIDELINES
A. APPLICABLE CODES:
ALL WORK SHALL CONFIRM TO ALL APPLICABLE CODES, STANDARDS AND GOVERNING AUTHORITIES:
INCLUDING BUT NOT LIMITED TO:
BUILDING: INTERNATIONAL BUILDING CODE, 2021 EDITION
LIFE SAFETY: NFPA 101 LIFE SAFETY CODE, 2024 EDITION
MECHANICAL: INTERNATIONAL MECHANICAL CODE, 2024 EDITION
NFPA 90A
PLUMBING: INTERNATIONAL PLUMBING CODE, 2024 EDITION
FIRE PREVENTION: NFPA NATIONAL FIRE CODES WITH THE EXCEPTION
OF NFPA 5000 AND NFPA 900, CURRENT ED.
ELECTRICAL: NATIONAL ELECTRICAL CODE (NEC), 2023 EDITION
ACCESSIBILITY: ABAAS INCLUDING VA SUPPLEMENT. BARRIER FREE
DESIGN
VA PUBLICATIONS: VA DIRECTIVES, DESIGN MANUALS, AND OTHER
GUIDANCE ON THE TECHNICAL INFORMATION
LIBRARY (TIL)
B. OCCUPANCY USE: NFPA 101 2024: CHAPTER 19 EXISTING
HEALTHCARE OCCUPANCIES
IBC: INSTITUTIONAL I-2
C. CONSTRUCTION TYPE: NFPA 101: TYPE II (222)
IBC: TYPE 2B (PROTECTED)
A
GI009
STAIR CLOSED
EIGHTH FLOOR - CONTRACTOR / EMERGENCY EGRESS PLAN
NTS
KEY PLAN: EIGHTH FLOOR
AE100
UP DN
GC100
LIFE SAFETY PLAN LEGEND
NOTE: ALL SYMBOLS MAY NOT BE USED
FIRE EXTINGUISHER CABINET / FIRE EXTINGUISHER
HORIZONTAL EXIT
EXIT SIGN
EGRESS PATH (COMMON PATH)
RATED WALL ASSEMBLY TYPES
RATE WALL ASSEMBLY LEGEND
NOTE:
ALL SYMBOLS MAY NOT BE USED EXISTING RATED WALLS SHOWN AS HALF-TONE
FIRE RESISTIVE RATED, 1 HOUR
FIRE RESISTIVE RATED, 2 HOUR
FIRE-RATED, SMOKE PARTITION, 1 HOUR
FIRE-RATED, SMOKE PARTITION, 2 HOUR
NON-RATED PARTITION
NON-RATED, SUITE, (SMOKE RESISTIVE)
EMERGENCY BATTERY WALL PACK LIGHT
SUITE DESIGNATIONS (EXISTING)
1. SECURITY CAMERAS LINE OF SIGHT WILL BE BLOCKED WHILE CONSTRUCTION WALLS ARE IN PLACE.
VA WILL ADJUST CAMERAS IF NEEDED.
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
MANN-GRANDSTAFF
VA MEDICAL
CENTER
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
Project Director
Revisions: Date:
100% CONSTRUCTION
DOCUMENTS
NOT FOR CONSTRUCTION
REPAIR SANITARY WASTE
PIPING
668-24-108
20-JUN-2025
MANN-GRANDSTAFF VA MEDICAL CENTER
(502) 890-2210 * WESTPOINTENGINEERS.COM
1941 BISHOP LANE, STE. 400 * LOUISVILLE, KY 40218
4815 N ASSEMBLY ST., SPOKANE, WA 99205
LIFE SAFETY DRAWING EIGHTH FLOOR
GI180
SABBVG
NOT F
OR
1. SECURITY CAMERAS LINE OF SIGHT WILL BE BLOCKED WHILE CONSTRUCTION WALLS ARE IN PLACE.
VA WILL ADJUST CAMERAS IF NEEDED.
BUILDING CODE AND GUIDELINES
A. APPLICABLE CODES:
ALL WORK SHALL CONFIRM TO ALL APPLICABLE CODES, STANDARDS AND GOVERNING AUTHORITIES:
INCLUDING BUT NOT LIMITED TO:
BUILDING: INTERNATIONAL BUILDING CODE, 2021 EDITION
LIFE SAFETY: NFPA 101 LIFE SAFETY CODE, 2024 EDITION
MECHANICAL: INTERNATIONAL MECHANICAL CODE, 2024 EDITION
NFPA 90A
PLUMBING: INTERNATIONAL PLUMBING CODE, 2024 EDITION
FIRE PREVENTION: NFPA NATIONAL FIRE CODES WITH THE EXCEPTION
OF NFPA 5000 AND NFPA 900, CURRENT ED.
ELECTRICAL: NATIONAL ELECTRICAL CODE (NEC), 2023 EDITION
ACCESSIBILITY: ABAAS INCLUDING VA SUPPLEMENT. BARRIER FREE
DESIGN
VA PUBLICATIONS: VA DIRECTIVES, DESIGN MANUALS, AND OTHER
GUIDANCE ON THE TECHNICAL INFORMATION
LIBRARY (TIL)
B. OCCUPANCY USE: NFPA 101 2024: CHAPTER 19 EXISTING
HEALTHCARE OCCUPANCIES
IBC: INSTITUTIONAL I-2
C. CONSTRUCTION TYPE: NFPA 101: TYPE II (222)
IBC: TYPE 2B (PROTECTED)
A
GI009
PENTHOUSE - CONTRACTOR / EMERGENCY EGRESS PLAN
NTS
KEY PLAN: PENTHOUSE
AE100
DNDN
LIFE SAFETY PLAN LEGEND
NOTE: ALL SYMBOLS MAY NOT BE USED
FIRE EXTINGUISHER CABINET / FIRE EXTINGUISHER
HORIZONTAL EXIT
EXIT SIGN
EGRESS PATH (COMMON PATH)
RATED WALL ASSEMBLY TYPES
RATE WALL ASSEMBLY LEGEND
NOTE:
ALL SYMBOLS MAY NOT BE USED EXISTING RATED WALLS SHOWN AS HALF-TONE
FIRE RESISTIVE RATED, 1 HOUR
FIRE RESISTIVE RATED, 2 HOUR
FIRE-RATED, SMOKE PARTITION, 1 HOUR
FIRE-RATED, SMOKE PARTITION, 2 HOUR
NON-RATED PARTITION
NON-RATED, SUITE, (SMOKE RESISTIVE)
EMERGENCY BATTERY WALL PACK LIGHT
SUITE DESIGNATIONS (EXISTING)
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
MANN-GRANDSTAFF
VA MEDICAL
CENTER
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
Project Director
Revisions: Date:
100% CONSTRUCTION
DOCUMENTS
NOT FOR CONSTRUCTION
REPAIR SANITARY WASTE
PIPING
668-24-108
20-JUN-2025
MANN-GRANDSTAFF VA MEDICAL CENTER
(502) 890-2210 * WESTPOINTENGINEERS.COM
1941 BISHOP LANE, STE. 400 * LOUISVILLE, KY 40218
4815 N ASSEMBLY ST., SPOKANE, WA 99205
LIFE SAFETY DRAWING NINTH FLOOR
GI190
SABBVG
NOT F
OR
C O A010
A007D
C002A
D
D D
C O
A105
A106 A108
A213 A214
A209A
C O
C O
C O
C300 C302A
C402 C404
C502 C500
C702C700 A802 C600 C602
A615
A617
GC100
7 SEVENTH FLOOR PLAN
1/4" - 1'-0" GC100
8 EIGHTH FLOOR PLAN
1/4" - 1'-0"
GC100
5 FIFTH FLOOR PLAN
1/4" - 1'-0"GC100
4 FOURTH FLOOR PLAN
1/4" - 1'-0"GC100
3 THIRD FLOOR PLAN
1/4" - 1'-0"
GC100
B BASEMENT FLOOR PLAN
1/4" - 1'-0" GC100
1 FIRST FLOOR PLAN
1/4" - 1'-0" GC100
2 SECOND FLOOR PLAN
1/4" - 1'-0"
GC100
6 SIXTH FLOOR
1/4" - 1'-0"
1/4" SINTRA RED
3/8" WHITE LINE
WHITE LETTERING
CUSTOM TEMPORARY SIGNAGE
1/4" SINTRA YELLOW
3/8" BLACK LINE
BLACK LETTERING
INSTALL ON DOOR AND ON TEMPORARY
DOOR PANEL TO CONSTRUCTION AREA.
LETTERS SIZE 2"
32" TALL FREE STANDING SIGNS.
SUPPLY 2, TWO OR FOUR SIDED FLOOR
SIGNS. MAINTAIN WATCH PERSON
UNTIL FLOOR IS DRY.
1/4" SINTRA WHITE
3/8" BLACK LINE
BLACK LETTERING
16X16 INCH SIGN INSTALLED ON DOOR
LEAVING CONSTRUCTION AREA.
LETTERS SIZE 2"
LEVEL I
1. PERFORM WORK ACTIVITY IN A MANNER THAT DOES NOT CREATE DUST.
2. IMMEDIATELY REPLACE ANY CEILING TILE, CLOSE ACCESS PANELS, ETC., UPON COMPLETION OF WORK.
3. ANY MATERIALS AND EQUIPMENT BEING BROUGHT INTO THE FACILITY MUST BE FREE OF
CONTAMINANTS AND LOOSE MATERIAL.
LEVEL II - PLUS ALL OF CONTROL LEVEL I
1. PROVIDE ACTIVE MEANS TO CONTROL AIRBORNE DUST FROM DISPERSING INTO OCCUPIED AREAS AND/OR WATER MIST SURFACE TO CONTROL
DUST (E.G., MOBILE DUST CONTAINMENT CART OR SOME OTHER SYSTEM).
2. ENSURE WORKER CLOTHING IS CLEAN AND FREE OF VISIBLE DUST BEFORE LEAVING THE WORK AREA. REMOVE OR ISOLATE AIR DIFFUSERS (SUPPLY AND RETURN) TO PROTECT THE HVAC SYSTEM FROM DUST AND REDUCE AIR TURBULENCE. REBALANCE SYSTEM TO ADDRESS DIFFUSER
ISOLATION.
3. WHEN THE WORK INVOLVES OR IMPACTS POTABLE WATER SYSTEMS INCLUDING STAGNATION DUE TO REDUCED USAGE, THE PIPING SHALL BE
FLUSHED TWICE A WEEK OR ISOLATED FROM THE MAIN SYSTEM.
4. SEAL DOORS TO PREVENT DUST MIGRATION.
5. CONTAIN ALL TRASH AND DEBRIS IN THE WORK AREA. PERFORM DAILY CLEANING AND DISPOSAL OF TRASH (COVERED) FROM WORK AREA USING
AN IDENTIFIED EXIT ROUTE.
6. ANY EQUIPMENT, TOOLS, OR MATERIALS REMOVED FROM THE WORK AREA MUST BE IN SEALED CONTAINERS AND/OR CLEANED OF DUST AND
DEBRIS PRIOR TO REMOVAL FROM THE AREA.
7. NONPOROUS/SMOOTH AND CLEANABLE CONTAINERS (WITH A HARD LID) MUST BE USED TO TRANSPORT TRASH AND DEBRIS FROM THE
CONSTRUCTION AREAS. THESE CONTAINERS MUST BE DAMP-WIPED CLEANED AND FREE OF VISIBLE DUST/DEBRIS BEFORE LEAVING THE
CONTAINED WORK AREA.
8. INSTALL A STICKY (DUST COLLECTION) MAT AT ENTRANCE OF CONTAINED WORK AREA BASED ON FACILITY POLICY. STICKY MATS MUST BE
CHANGED ROUTINELY AND WHEN VISIBLY SOILED.
9. MAINTAIN CLEAN SURROUNDINGS WHEN AREA IS NOT CONTAINED BY DAMP MOPPING OR HEPA VACUUMING SURFACES AT LEAST DAILY.
LEVEL III ALL CONTROL MEASURES IN LEVELS I AND II AND THE FOLLOWING:
1. ENSURE AVAILABILITY OF EQUIPMENT FOR CLEANING HANDS.
2. CONSTRUCT AND COMPLETE CRITICAL BARRIERS MEETING NFPA 241 REQUIREMENTS. BARRIERS MUST EXTEND TO THE CEILING OR IF CEILING TILE
IS REMOVED, TO THE DECK ABOVE. SOLID WALL BARRIERS MUST EXTEND TO 8'-0"+/- FACTORY LABELED FIRE RATED PLASTIC MAY BE USED IN
CLEAR STORY AREA ABOVE 8'-0" +/- FACTORY LABELED FIRE RATED TAPE MUST BE USED
3. ALL (PLASTIC OR HARD) BARRIER CONSTRUCTION ACTIVITIES MUST BE COMPLETED IN A MANNER THAT PREVENTS DUST RELEASE. PLASTIC BARRIERS MUST BE EFFECTIVELY AFFIXED TO FLOOR AND CEILING (OR FLOOR/ROOF DECK ABOVE) AND SECURE FROM MOVEMENT OR DAMAGE.
4. SEAL ALL PENETRATIONS IN CONTAINMENT BARRIERS, INCLUDING FLOORS AND CEILING, USING APPROVED MATERIALS (UL SCHEDULE FIRESTOP IF
APPLICABLE FOR BARRIER TYPE).
5. MAINTAIN .01 INCHES /WATER GAUGE NEGATIVE PRESSURIZATION OF THE ENTIRE WORKSPACE BY USE OF HEPA EXHAUST AIR SYSTEMS DIRECTED OUTDOORS (UNLESS A WORK SPECIFIC WAIVER IS APPROVED BY VHA’S OFFICE OF HEALTHCARE ENGINEERING); THIS MUST BE MAINTAINED CONTINUOUSLY 24/7 FOR THE DURATION OF THE PROJECT. EXHAUST DISCHARGED DIRECTLY TO THE OUTDOORS THAT IS 25 FEET OR GREATER FROM ENTRANCES, AIR INTAKES AND WINDOWS IS NOT REQUIRED TO BE HEPA-FILTERED. EXHAUSTING DISCHARGED AIR INTO SHARED OR RECIRCULATING HVAC SYSTEMS, OR OTHER SHARED EXHAUST SYSTEMS (E.G., BATHROOM EXHAUST) IS PROHIBITED.
6. INSTALL A DIFFERENTIAL PRESSURE SENSING DEVICE (DIGITAL MONITORING) ON EXTERIOR OF WORK CONTAINMENT TO CONTINUALLY MONITOR AND DOCUMENT NEGATIVE PRESSURIZATION. THE “BALL IN THE WALL” OR SIMILAR APPARATUS ARE NOT ACCEPTABLE.
LEVEL OF PRECAUTIONS CONTROL MEASURES - III
THE CONTRACTOR SHALL COMPLY WITH ALL CONTROL MEASURES
ALL
CONTRACTOR
PROVIDED FIRE
EXTINGUISHER
ON STANDS
HEPA AIR
SCRUBBER
CONNECT TO
EXHAUST DUCT
1 HOUR HARD WALL
CONTAINMENT
STAIR CLOSEDSTAIR CLOSED
STAIR CLOSED STAIR CLOSED STAIR CLOSED
STAIR CLOSED
WALK OFF MAT
EXHAUST THROUGH WINDOW EXHAUST THROUGH WINDOW
EXHAUST THROUGH WINDOW
EXHAUST THROUGH WINDOWEXHAUST THROUGH WINDOW
EXHAUST THROUGH WINDOW
EXHAUST THROUGH WINDOW
ELECTRONIC MONITOR
GAUGE NEGATIVE
PRESSURIZATION.
BALL IN WALL NOT PERMIT.
ELECTRONIC MONITOR
GAUGE NEGATIVE
PRESSURIZATION.
BALL IN WALL NOT PERMIT.
ELECTRONIC MONITOR
GAUGE NEGATIVE
PRESSURIZATION.
BALL IN WALL NOT PERMIT.
ELECTRONIC MONITOR
GAUGE NEGATIVE
PRESSURIZATION.
BALL IN WALL NOT PERMIT.
ELECTRONIC MONITOR
GAUGE NEGATIVE
PRESSURIZATION.
BALL IN WALL NOT PERMIT.
ELECTRONIC MONITOR
GAUGE NEGATIVE
PRESSURIZATION.
BALL IN WALL NOT PERMIT.
ELECTRONIC MONITOR
GAUGE NEGATIVE
PRESSURIZATION.
BALL IN WALL NOT PERMIT.
ELECTRONIC MONITOR
GAUGE NEGATIVE
PRESSURIZATION.
BALL IN WALL NOT PERMIT.
ELECTRONIC MONITOR
GAUGE NEGATIVE
PRESSURIZATION.
BALL IN WALL NOT PERMIT.
AE400
AE400
AE400
AE400
AE400
AE400
AE400
AE400
AE400
STAIR CLOSED
SD SD
SD
SD
SD
SD
SD
SD SD
SD CONSTRUCTION
PROVIDED TEMPORARY
SMOKE AND HEAT
DETECTOR.
CODED NOTES
A. WORK WITHIN THE CONTAINED CONSTRUCTION AREA SHALL BE ICRA LEVEL III.
B. WORK WITHIN THE MECHANICAL ROOM IS ICRA LEVEL I.
C. CONTRACTOR TO SUBMIT A FULL ICRA PLAN ALONG WITH ANY ACTIVITY HAZARD ANALYSIS TO THE COR FOR APPROVAL. THE PROVIDED
SUGGESTION ON THIS SHEET ARE MINIMAL AND SHOULD ONLY BE USED TO GUIDE THE CONTRACTOR IN A FULL ICRA SUBMITTAL.
D. THE WALLS, FANS, DOORS, AND OVERALL EQUIPMENT DEPICTED ON THIS DRAWING IS A GENERAL LOCATION AND SHALL BE MOVED TO
ACCOMMODATE THE CONTRACTOR AND OWNERS COORDINATED BUILDING PLAN.
E. REMOVE THE STAIRWELL FIRE RATED DOOR. CONSTRUCT A NEW TWO HOUR RATED BARRIER WALL AT THE DOOR LOCATION. INSTALL A RATED
FIRE DAMPER AND A RATED ACCESS DOOR.
F. INSTALL 25MIL HEAVY DUTY FIRE RETARDANT ANTI SKID FLOOR PROTECTION.
G. PROVIDE ONE EXTINGUISHER MOUNTED ON A STAND ON EACH FLOOR STAIR LANDING AS WELL AS IN EACH CONSTRUCTION AREA.
H. PROVIDE STICKY FLOOR MATS AT EACH EGRESS AREA FROM THE CONSTRUCTION AREA.
I. INSTALL ONE SMOKE DETECTOR IN EACH CONSTRUCTION AREA THESE SHALL NOTIFY SECURITY WHEN IN ALARM.
J. REMOVE, MODIFY AND REINSTALL WINDOWS USING A WINDOW MANUFACTURE APPROVED PROCESS. PROVIDE A LETTER FROM THE WINDOW
MANUFACTURE THAT ALL STAIR WINDOWS REMAIN IN COMPLIANCE WITH THERE WARRANTY.
K. HEPA AIR SCRUBBERS TO BE CLEANED AS NEEDED WITH DAILY REPORTS SHOWING RUN TIME, FILTER LIFE AND ESTIMATED FILTER CHANGE DATES.
ALL FILTERS FOLLOWING ABATEMENT SHALL BE REPLACED BY THE ABATEMENT COMPANY.
L. DIGITAL NEGATIVE AIR MONITORING SHALL MAINTAIN AN HOURLY AVERAGE AS DEFINED IN THE SPECIFICATION. PRODUCE THIS REPORT DAILY TO
THE COR OR APPROVED CLOUD BASED MANAGEMENT SYSTEM. BASIS OF DESIGN IS PROCORE.
M. REVIEW ALL CEILING TILES ARE IN PLACE AT THE END OF EACH SHIFT AND ANY CEILING OR WALL PENETRATIONS ARE SEALED TO A U.L. APPROVED
WALL OR CEILING METHOD.
N. REVIEW ALL HARDWALL ENCLOSURES ARE MAINTAINED AND FUNCTIONAL.
O. "NEW" DENOTES THE ADDITION OF A BOTTLE FILL STATION.
P. "EXISTING" DENOTES THE REMOVAL OF AN EXISTING DRINKING FOUNTAIN.
EXHAUST OUT
WINDOW IN
ROOM
A002
SEE GI100 FOR
ROUTING
NEW
EXISTING
NEW
NEW NEW
EXISTING
NEW NEW
EXISTING
GENERAL NOTES
1. REMOVE AND REINSTALL DOOR. INFILL THE DOOR FRAME WITH A 2 HOUR RATED WALL WITH A SIZED FIRE DAMPER PERMITTING AIR TO BE PULLED
FROM THE CONSTRUCTION AREA AND EXHAUSTED OUT THE STAIR WINDOWS.
2. INSTALL FIRE RESISTANT FLOOR COVERING COMPLIANT WITH ASTM C1028-96; NFPA 701-04.
3. REMOVE WINDOW, INSTALL EXHAUST DUCT AND REINSTALL WINDOW MAINTAINING THE MANUFACTURER'S WARRANTY.
4. SECURITY CAMERAS LINE OF SIGHT WILL BE BLOCKED WHILE CONSTRUCTION WALLS ARE IN PLACE. VA WILL ADJUST CAMERAS IF NEEDED.
2 2 2
3 3 3
RELOCATE PULL STATION
AND EMERGENCY LIGHTING
TO SOLID WALL CONTAINMENT .
REINSTALL UPON COMPLETION.
RELOCATE
EMERGENCY
EGRESS LIGHTING
RIGHT HAND SIDE
OF DOOR
RELOCATE EXISTING FIRE PULL
STATION TO EXTERIOR OF
TEMPORARY SOLID WALL
CONSTRUCTION BARRIER.
REINSTALL NEW COR APPROVED
LOCATION UPON COMPLETION.
REMOVE AND RELOCATE
EXISTING EXIT LIGHT TO NEW
COR APPROVED LOCATION.
REMOVE AND RELOCATE
EXISTING FIRE PULL STATION
TO NEW COR APPROVED
LOCATION WITHIN 60" OF
EGRESS DOOR. CONTRACTOR
SHALL TEMPORARILY MOUNT TO
CONSTRUCTION BARRIER.
REMOVE AND RELOCATE
EXISTING FIRE PULL STATION
TO NEW COR APPROVED
LOCATION WITHIN 60" OF
EGRESS DOOR. CONTRACTOR
SHALL TEMPORARILY MOUNT TO
CONSTRUCTION BARRIER.
4 4
4 4
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
MANN-GRANDSTAFF
VA MEDICAL
CENTER
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
Project Director
Revisions: Date:
100% CONSTRUCTION
DOCUMENTS
NOT FOR CONSTRUCTION
REPAIR SANITARY WASTE
PIPING
668-24-108
20-JUN-2025
MANN-GRANDSTAFF VA MEDICAL CENTER
(502) 890-2210 * WESTPOINTENGINEERS.COM
1941 BISHOP LANE, STE. 400 * LOUISVILLE, KY 40218
4815 N ASSEMBLY ST., SPOKANE, WA 99205
ICRA FLOOR PLAN
GC100
SABBVG
EXHAUST THROUGH
STAIRWELL OUT 2ND
FLOOR STAIRWELL
WINDOW. SEE DETAIL
2/GC100 AND GI100.
STAIR CLOSED
SD
NOT F
OR
C O A010
A007D
C002A
A009
A008 C001
C002
D
D D
O
C O
C
C O
A105
A106 A108
A113
UP
3"- ROOF
LEADER
1" -DRINKING WATER COLD
2" - SANITARY
1 1/2" - VENT
6" - FIRE
A213 A212
A214
A209A
A216A A216
C O
C O
3"- ROOF
LEADER
1" -DRINKING WATER COLD
2" - SANITARY
1 1/2" - VENT
6" - FIRE
C O
C O
C O C O
A315
A316 C300 C302A
C302B
C307C305C303C301
3"- ROOF
LEADER
1" -DRINKING WATER COLD
2" - SANITARY
1 1/2" - VENT
6" - FIRE
C402C400 C404
C407C405C401 C403
A417
A418
3"- ROOF LEADER
1" -DRINKING WATER COLD
2" - SANITARY
1 1/2" - VENT
6" - FIRE
C502 C500
C507C505C501 C503
A512
3"- ROOF LEADER
1" -DRINKING WATER COLD
2" - SANITARY
1 1/2" - VENT
6" - FIRE
C702C700
C707C705C701 C703
A712
A713
3"- ROOF LEADER
1" -DRINKING WATER COLD
2" - SANITARY
1 1/2" - VENT
6" - FIRE A802
A807A805 A803
A800A
3"- ROOF LEADER
1" -DRINKING WATER COLD
2" - SANITARY
1 1/2" - VENT
6" - FIRE
ROOF
ELEVATOR
MACHINE
ROOM
EXT. 4"- SANITARY/VENT
EXT. 2"- SANITARY
EXT. 3"- ELECTRICAL
PANEL 9N1
REMOVE 3PHASE
WELDER BREAKER
AND INSTALL NEW
POWER TO
EQUIPMENT
C600 C602
C607C605C601 C603
A616
A615
A617
3"- ROOF LEADER
1" -DRINKING WATER COLD
2" - SANITARY
1 1/2" - VENT
6" - FIRE
GC101
7 SEVENTH FLOOR PLAN
1/4" - 1'-0" GC101
8 EIGHTH FLOOR PLAN
1/4" - 1'-0"
GC101
10 NINTH FLOOR
1/4" - 1'-0"
GC101
5 FIFTH FLOOR PLAN
1/4" - 1'-0"GC101
4 FOURTH FLOOR PLAN
1/4" - 1'-0"GC101
3 THIRD FLOOR PLAN
1/4" - 1'-0"
GC101
B BASEMENT FLOOR PLAN
1/8" - 1'-0" GC101
1 FIRST FLOOR PLAN
1/4" - 1'-0" GC101
2 SECOND FLOOR PLAN
1/4" - 1'-0"
GC101
6 SIXTH FLOOR
1/4" - 1'-0"
EXISTING
WINDOW
PHASING PLAN - 195 TOTAL DAYS
ALL DAYS ARE CALENDAR DAYS
PHASE 1 30 DAYS (VA TO PROVIDE DIRECTION
SUBMITTALS / PROJECT SETUP
PHASE 2 60 DAYS DEMOLITION / ABATEMENT RETAIN
ACCESS FROM THE 7TH FLOOR TO
THE 9TH FLOOR AT ALL TIMES.
REMAINDER OF STAIR WELL ONE
WILL BE CLOSED.
PHASE 3 30 DAYS NEW PIPING INSTALLATION AND
ELECTRICAL INSTALLATION FROM
9TH FLOOR AND BELOW.
PHASE 4 15 DAYS INSTALLING BOTTLE FILL STATIONS
CORRIDOR PAINTING TO TAKE
PLACE AND CONTAINMENT AREAS
CAN BE REMOVED.
PHASE 5 15 DAYS TESTING AND WATER PURIFICATION
PHASE 6 15 DAYS FINISH PAINT IS APPLIED AND FINAL
CLEANUP
PHASE 7 30 DAYS EDUCATION AND CLOSEOUT
EXISTING
WINDOW
EXISTING
WINDOW
EXISTING
WINDOW
EXISTING
WINDOW
EXISTING
WINDOW
EXISTING
WINDOW
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
MANN-GRANDSTAFF
VA MEDICAL
CENTER
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
Project Director
Revisions: Date:
100% CONSTRUCTION
DOCUMENTS
NOT FOR CONSTRUCTION
REPAIR SANITARY WASTE
PIPING
668-24-108
20-JUN-2025
MANN-GRANDSTAFF VA MEDICAL CENTER
(502) 890-2210 * WESTPOINTENGINEERS.COM
1941 BISHOP LANE, STE. 400 * LOUISVILLE, KY 40218
4815 N ASSEMBLY ST., SPOKANE, WA 99205
PHASING
GC101
SABBVG
NOT F
OR
O
C O A010
C002A
A009
A008 C001
4"
D D C O
6" 1"
2-1/2" 1"
1" 1"
MEDICAL
VACUUM
3"- ROOF LEADER
1" -DRINKING WATER COLD
2" - SANITARY
1 1/2" - VENT
6" - FIRE
A106 A108
A113
3"- ROOF
LEADER
1" -DRINKING WATER COLD
2" - SANITARY
1 1/2" - VENT
6" - FIRE
A213 A214
A209A
WV O
S
V
T T
3"- ROOF
LEADER
1" -DRINKING WATER COLD
2" - SANITARY
1 1/2" - VENT
6" - FIRE
C O
C O C
O
C300 C302A
C302B
V W O
3"- ROOF
LEADER
1" -DRINKING WATER COLD
2" - SANITARY
1 1/2" - VENT
6" - FIRE
C402 C404
3"- ROOF LEADER
1" -DRINKING WATER COLD
2" - SANITARY
1 1/2" - VENT
6" - FIRE
C502 C500
3"- ROOF LEADER
1" -DRINKING WATER COLD
2" - SANITARY
1 1/2" - VENT
6" - FIRE
C702C700
3"- ROOF LEADER
1" -DRINKING WATER COLD
2" - SANITARY
1 1/2" - VENT
6" - FIRE A802
3"- ROOF LEADER
1" -DRINKING WATER COLD
2" - SANITARY
1 1/2" - VENT
6" - FIRE
EXT. 4"- SANITARY/VENT
EXT. 2"- SANITARY
EXT. 3"- ELECTRICAL
PANEL 9N1
REMOVE 3PHASE
WELDER BREAKER
AND INSTALL NEW
POWER TO
EQUIPMENTC600 C602
A615
A617
3"- ROOF LEADER
1" -DRINKING WATER COLD
2" - SANITARY
1 1/2" - VENT
6" - FIRE
HA100
7 SEVENTH FLOOR PLAN
1/4" - 1'-0" HA100
8 EIGHTH FLOOR PLAN
1/4" - 1'-0" HA100
9 NINTH FLOOR PLAN
1/4" - 1'-0"
HA100
5 FIFTH FLOOR PLAN
1/4" - 1'-0"HA100
4 FOURTH FLOOR PLAN
1/4" - 1'-0"HA100
3 THIRD FLOOR PLAN
1/4" - 1'-0"
HA100
B BASEMENT FLOOR PLAN
1/4" - 1'-0" HA100
1 FIRST FLOOR PLAN
1/4" - 1'-0" HA100
2 SECOND FLOOR PLAN
1/4" - 1'-0"
HA100
6 SIXTH FLOOR
1/4" - 1'-0"
PLAN NOTES
GENERAL NOTES
1. INDICATES AREAS OF ASBESTOS-CONTAINING PIPE INSULATION, CLEAN ALL CHASE CEILING, WALL, AND FLOOR CAVITIES CLEANING AND
ENCAPSULATION ALL SURFACES.
2. ON EACH FLOOR / DECK PENETRATION REMOVE SURROUNDING CONCRETE / SCRATCH-COAT CEMENT PLASTER TO ALLOW REMOVAL OF
ASBESTOS FLOOR OR DECK PENETRATIONS.
3. CLEAN ALL CEILINGS, WALLS AND FLOORS AND SPRAY A WHITE ENCAPSULATING ASBESTOS BINDING COMPOUND ON ALL CHASE CEILINGS, WALLS AND FLOOR AREAS.
4.INSULATION CONTAINING ACM. ROOF LEADER IS CORK REMOVE AS WELL. SEE PLUMBING DRAWINGS FOR ADDITIONAL DETAIL.
5.EXISTING PLASTER CONTAINS A PAINT COAT CONTAINING LEAD BASED PAINT ABOVE THE ACTION LEVEL. ABATE LEAD PAINT FROM WALL PRIOR TO DEMOLITION WORK. PROVIDE A FEDERAL APPROVED ABATEMENT PLAN APPROVED 30 DAYS BEFORE DEMOLITION IS TO START. PEEL AWAY 1
IS AN APPROVED STRIPPER OR APPROVED EQUAL.
1 1
1 1 1
GENERAL DESCRIPTION:
A. ON THE BASEMENT LEVEL REMOVE ONE WYTHE CLAY WALL BRICK TO EXPOSE THE WATER AND CORK COVERED PLUMBING LINES.
REMOVE ALL ACM MATERIALS STOPPING AT THE EXTENT OF THE WALL DEMOLITION. IN TWO LOCATIONS WORK ABOVE THE WALL INDICATED ON THE DRAWINGS WILL REQUIRE REMOVAL OF CORK AND INSULATED LINES WITHIN SIX FEET OF THE CHASE, TERMINATING AT VALVES OR AS THE PIPE EXTEND INTO THE FLOOR, CEILING OR WALLS. SEE PHOTOGRAPHS ON THE PLAN SET FOR
ADDITIONAL INFORMATION ALSO SEE THE PLUMBING DEMOLITION PLANS.
B. ON THE 2ND TO 8TH FLOOR EXPOSE THE CHASE AREA PER THE APPROVED DEMOLITION SUBMITTAL. REMOVE ALL LOSE MATERIALS FROM THE FLOOR AREA, EACH CHASE HAS FIBROUS INSULATED AND OR A CORK INSULATION ABATE / REMOVE ALL EXISTING INSULATION FROM THE CHASE AREA. CLEAN ALL WALLS AS WELL AS THE CONCRETE DECK OF ACM AND COAT WITH A (WHITE) ASBESTOS BINDING COMPOUND ON ALL REMAINING CHASE FLOOR, CEILING AND WALL SURFACES.
C. AT EACH FLOOR PENETRATION EXPAND THE EXISTING CEMENT SCRATCH COAT AND CONCRETE TO ALLOW FOR FIRE SLEEVES ALL WHILE INSURING ALL ASBESTOS MATERIALS ARE REMOVED FROM THESE PIPES FLOOR AND DECK PASS THROUGH.
D. SEE PLUMBING DESIGN FOR NEW INSULATION REQUIREMENTS.
E. THE CONTRACTOR SHALL TAKE SAMPLES OF EACH PAINT TO BE DISTURBED OR REMOVED ON EACH FLOOR. THE CONTRACTOR SHALL REMOVE / MANAGE ALL LEAD BASED PAINT ON DOOR FRAMES, DOORS AND PLASTER WALLS. FOLLOW A LOCAL, STATE AND FEDERAL APPROVED LEAD ABATEMENT / MANAGEMENT PLAN APPROVED 30 DAYS BEFORE WORK IS TO BEGIN.
F. NOTED: "ROOF LEADER" HAS A CORK INSULATION. REMOVE AND INSTALL NEW INSULATION.
G. NOTED: "DRINKING WATER COLD" ABATE INSULATION AND INSTALL NEW INSULATION PER THE PLUMBING DESIGN.
2 2 2
2 2
3 3
3 3
3 3 3
LEAD ABATEMENT (LBP)
SEE SPECIFICATIONS 02 83 33.13 LEAD-BASED PAINT REMOVAL AND DISPOSAL
REMOVE / MANAGE 720 + / - SQUARE FEET OF LEAD- CONTAINING PAINT. REMOVE / MANAGE ALL LEAD PAINT FROM EACH FLOORS: DOORS, FRAMES, WALLS, AND PIPES STARTING IN THE BASEMENT AND ENDING ON THE NINTH FLOOR. THIS PROJECT IS NOT A FULL ABATEMENT PROJECT FOR LEAD PAINT. 100% REMOVAL IS REQUIRED FOR CUTTING THROUGH THE LEAD PAINT AREAS. ALL OTHER AREAS CAN REMAIN
AFTER WALL PREPARATION AND ENCAPSULATION BEFORE APPLYING NEW FINISHES.
CLEAN AND ENCAPSULATE ALL EXPOSED LEAD BASE PAINT PRIOR TO PRIMER AND FINISH COATS OF PAINT. FOLLOW THE CONTRACTORS
APPROVED LEAD BASED PAINT MANAGEMENT PLAN.
SOME ORIGINALLY LEAD BASED PAINTED PLASTER WALLS ARE BEHIND NEWER DRYWALL OR THE ORIGINAL FINISH HAS BEEN RECOATED.
THE CONTRACTOR IS TO ASSUME ALL ORIGINAL PLASTER, DOORS AND FRAMES CONTAIN LEAD PAINT ABOVE THE ACTION LEVEL.
AE200
AE200
AE207
5 5
5 5 5
ASBESTOS ABATEMENT (ACM)
SEE SPECIFICATIONS 02 82 11 TRADITIONAL ASBESTOS ABATEMENT
REMOVE AND DISPOSE OF 300 + / - LINEAL FEET OF ASBESTOS - CONTAINING PIPE INSULATION. REMOVE ALL ACM FROM EACH FLOORS
CHASE STARTING IN THE BASEMENT AND ENDING ON THE EIGHTH FLOOR.
CLEAN AND ENCAPSULATE ALL INNER CHASE CEILINGS, WALLS AND FLOOR USING AN ASBESTOS BINDING COMPOUND STARTING ON THE
FIRST FLOOR AND ENDING ON THE EIGHTH FLOOR.
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
MANN-GRANDSTAFF
VA MEDICAL
CENTER
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
Project Director
Revisions: Date:
100% CONSTRUCTION
DOCUMENTS
NOT FOR CONSTRUCTION
REPAIR SANITARY WASTE
PIPING
668-24-108
20-JUN-2025
MANN-GRANDSTAFF VA MEDICAL CENTER
(502) 890-2210 * WESTPOINTENGINEERS.COM
1941 BISHOP LANE, STE. 400 * LOUISVILLE, KY 40218
4815 N ASSEMBLY ST., SPOKANE, WA 99205
HAZARDOUS MATERIALS
HA100
SABBVG
NOT F
OR
| GI130 |
| GI130 |
| GI140 |
| GI140 |
| GI150 |
| GI150 |
| GI160 |
| GI160 |
| GI170 |
| GI170 |
| 668-24-108_100CD_DRAWINGS_Part1.pdf |
| GI000 |
| GI000 |
| GI001 |
| GI001 |
| GI100 |
| GI100 |
| GI110 |
| GI110 |
| GI120 |
| GI120 |
| 668-24-108_100CD_DRAWINGS_Part3.pdf |
| GI180 |
| GI180 |
| GI190 |
| GI190 |
| GC100 |
| GC100 |
File details come from the government source that posted it. Updated .