Attachment 2.1 668-24-108 Drawings.pdf

PDF 4 MB Posted

Attached to
Repair Sanitary Waste Piping at the Mann-Grandstaff VA Medical Center
Solicitation number
36C26027R0021
Issued by

About this file

This document is a set of 100% construction documents for a federal repair project at Mann-Grandstaff VA Medical Center in Spokane, Washington. The project (No. 668-24-108) involves repair of sanitary waste piping in Building 1, a nine-story healthcare facility operated by the U.S. Department of Veterans Affairs under VISN 20. The construction documents include life safety drawings for all floors (basement through ninth floor/penthouse), general notes and abbreviations, plumbing and electrical plans, ICRA (Infection Control Risk Assessment) floor plans, hazardous materials identification, and a phased construction schedule totaling 195 calendar days across seven phases.

The project requires strict compliance with applicable building codes (International Building Code 2021), life safety standards (NFPA 101 2024), plumbing codes (International Plumbing Code 2024), and electrical codes (NEC 2023). Work must be scheduled outside VA Medical Center operating hours (6 AM to 6 PM within construction areas), with material hauling restricted to before 8 AM or after 5 PM. The project includes traditional asbestos abatement (approximately 300 linear feet of pipe insulation removal) and lead-based paint removal and disposal (approximately 720 square feet). ICRA Level III containment is required with negative pressurization, HEPA filtration, and daily monitoring. The contractor is responsible for all demolition, new piping installation, testing, water purification, finish painting, and final closeout, with emphasis on protecting existing building systems and maintaining facility operations throughout construction.

View the file

Other files

Show all 14

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

COVER SHEET

GI000

SABBVG

PROJECT SITE MAPPROJECT LOCATION MAP

MANN-GRANDSTAFF VA

4815 NORTH ASSEMBLY ST. SPOKANE WA, 99205

PROJECT #668-24-108

REPAIR SANITARY WASTE PIPING BLDG 1

DRAWING INDEX

U.S. Department of Veterans Affairs

WASHINGTON - VISN 20

GENERAL

GI000 COVER SHEET

GI001 GENERAL NOTES, SYMBOLS, AND ABBREVIATIONS

GI100 LIFE SAFETY DRAWING BASEMENT LEVEL

GI110 LIFE SAFETY DRAWING FIRST FLOOR

GI120 LIFE SAFETY DRAWING SECOND FLOOR

GI130 LIFE SAFETY DRAWING THIRD FLOOR

GI140 LIFE SAFETY DRAWING FOURTH FLOOR

GI150 LIFE SAFETY DRAWING FIFTH FLOOR

GI160 LIFE SAFETY DRAWING SIXTH FLOOR

GI170 LIFE SAFETY DRAWING SEVENTH FLOOR

GI180 LIFE SAFETY DRAWING EIGHTH FLOOR

GI190 LIFE SAFETY DRAWING NINTH FLOOR

GC100 ICRA FLOOR PLAN

GC101 PHASING PLAN

HA100 HAZARDOUS MATERIALS

ARCHITECTURAL

AE100 FLOOR PLAN

AE200 BASEMENT LEVEL ELEVATION

AE201 FIRST FLOOR ELEVATION

AE202 SECOND FLOOR ELEVATION

AE203 THIRD FLOOR ELEVATION

AE204 FOURTH FLOOR ELEVATION

AE205 FIFTH FLOOR ELEVATION

AE206 SIXTH FLOOR ELEVATION

AE207 SEVENTH FLOOR ELEVATION

AE208 EIGHTH FLOOR ELEVATION

AE209 NINTH FLOOR ELEVATION

AE400 DETAILS

AE401 APPLIED WALL DETAILS

AE402 EXISTING WALL DETAILS (ADD ALTERNATIVE ONLY)

PLUMBING

P-001 PLUMBING LEGEND, GENERAL NOTES AND ABBREVIATIONS

PD200 PLUMBING DEMO PLAN – DRINKING WATER

PD201 PLUMBING DEMO PLAN – SANITARY, VENT, AND ROOF LEADER

PP200 PLUMBING PLAN – DRINKING WATER

PP201 PLUMBING PLAN – SANITARY, VENT, AND ROOF LEADER

PP400 STACK 25 RISER DIAGRAM AND SCHEDULE

PP401 PLUMBING DETAILS

ELECTRICAL

EG001 ELECTRICAL LEGEND AND GENERAL NOTES

E-100 FLOOR PLANS - ELECTRICAL

SPOKANE

WORK

AREA

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

MANN-GRANDSTAFF

VA MEDICAL

CENTER

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

Project Director

Revisions: Date:

100% CONSTRUCTION

DOCUMENTS

NOT FOR CONSTRUCTION

REPAIR SANITARY WASTE

PIPING

668-24-108

20-JUN-2025

MANN-GRANDSTAFF VA MEDICAL CENTER

(502) 890-2210 * WESTPOINTENGINEERS.COM

1941 BISHOP LANE, STE. 400 * LOUISVILLE, KY 40218

4815 N ASSEMBLY ST., SPOKANE, WA 99205

NOT F

OR

CONSTRUCTIO

N

TYPICAL TOILET TYPICAL TOILET

SURFACE MOUNTED

PAPER TOWEL

DISPENSER

RECESSED PAPER

TOWEL DISPENSER

AND WASTE

RECEPTACLE

SEMI-RECESSED PAPER

TOWEL DISPENSER AND

WASTE RECEPTACLE

SURFACE MOUNTED SOAP

DISPENSER

SURFACE MOUNTED

CHANNEL FRAME MIRROR

SURFACE MOUNTED HAND

DRYER

ROBE HOOK

SURFACE MOUNTED

BABY CHANGING

STATION

TOILET PAPER

DISPENSER

TWIN JUMBO ROLL

SURFACE MOUNTED

FEMININE NAPKIN DISPOSAL

RECESSED FEMININE NAPKIN

DISPOSAL

RECESSED SEAT COVER

DISPENSER

POSTURE MIRROR

RECESSED FIRE

EXTINGUISHER CABINET SHARPS CONTAINER

SHARPS CONTAINER

WITH GLOVE BOX CLOCK WATER

BOTTLE STATION

DRINKING

FOUNTAINS

CONTRACT LIMIT LINE

ELEVATION INDICATOR

CENTER LINE INDICATOR

EXISTING TO REMAIN LINE

HIDDEN FEATURES LINE

BREAK, ROUND (USER DEFINES SIZE)

BREAK, STRAIGHT (SEE SECTION INDICATORS,

BUILDING, WITH BREAK STANDARDS)

DETAIL INDICATOR

DIMENSION LINE

DRAWING BLOCK TITLE, TYPICAL

ELEVATION INDICATOR

ELEVATION INDICATOR, INTERIOR, MULTIPLE VIEW

ELEVATION INDICATOR, INTERIOR, SINGLE VIEW

PHOTOGRAPH INDICATOR

CENTER LINE

FURNITURE, FIXTURE, & EQUIPMENT INDICATOR

GRAPHIC SCALE, 18"=1'-0"

ROOM NAME AND NUMBER

COLUMN GRID

NORTH ARROW

BUILDING SECTION INDICATOR

SYMBOLSABBREVIATIONS

NOTE:

MATCHLINE

DETAIL NUMBER

SHEET WHERE DRAWN

DOOR INDICATOR

WALL TYPE ( SEE SHEET AE500 )

WINDOW TYPE

THE CONTRACTOR IS TO SCHEDULE SELECT WORK AS AN AFTER-VAMC HOURS PROJECT AS WELL AS WEEKENDS OR HOLIDAYS; THIS INCLUDES THE CONSTRUCTION OF CORRIDOR BARRIERS AND ANY SYSTEM SHUTDOWN WORK. WORK WITHIN THE DESIGNATED CONSTRUCTION AREA WILL BE COMPLETED BETWEEN 6 AM AND 6 PM. HAULING OF MATERIALS TO AND FROM THE SITE TO TAKE PLACE BEFORE 8 AM OR AFTER 5 PM.

GENERAL INFORMATION

1. THE CONTRACTOR IS RESPONSIBLE FOR VERIFYING ALL FIELD CONDITIONS BEFORE CONSTRUCTION STARTS AND SHALL NOTIFY THE COR OF ANY DISCREPANCIES.

2. THE CONTRACTOR SHALL REVIEW THE CONTRACT DOCUMENTS FOR CONFLICTS. WHERE CONFLICTS EXIST WITHIN THE DRAWINGS, WORK SHALL NOT PROCEED UNTIL THE COR IS NOTIFIED AND DIRECTION IS GIVEN.

3. WHERE INCIDENTAL WORK IS REQUIRED TO ACCOMPLISH WORK SHOWN ON THE DRAWINGS, THIS WORK IS IMPLIED AND SHALL BE INCLUDED AS PART OF THE BASE BID.

4. BEFORE ANY WORK COMMENCES IN AN AREA, THE CONTRACTOR SHALL NOTIFY THE COR OF HIS INTENTION TO WORK IN THE AREA AND SHALL SCHEDULE A WALK-THROUGH WITH THE COR TO DETERMINE EXISTING CONDITIONS, PREPARE AN ACTIVITY HAZARD ANALYSIS AND SUBMIT A PLAN TO COMPLETE THE WORK TO THE COR FOR APPROVAL. THE AREAS OF WORK SHALL BE RETURNED TO THEIR ORIGINAL STATE BEFORE

REQUESTING FINAL APPROVAL OF THE WORK FROM THE COR.

5. AFTER CONSTRUCTION COMPLETION, THE CONTRACTOR SHALL CLEAN ALL SURFACES OF CONSTRUCTION DEBRIS. SURFACES SHALL BE WIPED CLEAN OF DUST, INCLUDING FIXTURES, WINDOWS AND WINDOW SILLS, DOOR FRAMES, ETC. THE CONTRACTOR SHALL CLEAN USING VAMC-APPROVED PRODUCTS.

6. CONTRACTOR IS RESPONSIBLE FOR CONFORMING TO ALL BUILDING CODES AND SHALL NOT KNOWINGLY EXECUTE WORK WHICH IS NOT IN CONFORMANCE.

7. CONTRACTOR TO INSPECT ALL WALLS FOR FUNCTION. NOTIFY THE COR OF ANY CONDITIONS THAT WILL PREVENT THE CONTRACTOR TO ACHIEVE A COMPLETE PROJECT.

8. CONTRACTOR TO PROTECT ALL PORTIONS OF THE EXISTING BUILDING TO REMAIN DURING DEMOLITION/ CONSTRUCTION. THE CONTRACTOR IS RESPONSIBLE FOR ANY/ALL DAMAGES DURING THE WORK.

9. CONTRACTOR SHALL MAINTAIN ALL EXISTING ACCESS PANELS AND PROVIDE NEW ACCESS PANELS AS REQUIRED IN AREAS OF RENOVATION AND NEW CONSTRUCTION.

10. CONTRACTOR TO REMOVE ALL UNUSED SCREWS, CLIPS, AND FASTENERS. HOLES WILL BE PATCHED AND PREPPED.

11. ALL DIMENSIONS ARE TO FINISH FACE OF WALL UNLESS OTHERWISE NOTED.

12. PAINTING: SAND EXISTING SURFACES, REMOVE ANY DEFECTS, PRIME AND PAINT FROM CEILING TO THE NEAREST INSIDE/OUTSIDE CORNERS. UNLESS NOTED OTHERWISE.

13. ALL SEALANTS SHALL BE DRY TOOLED. SUPPLY AND UTILIZE A TEST AREA, COORDINATED WITH THE COR, FOR FINISH PRODUCT REFERENCE.

14. THE CONSTRUCTION AREAS WILL BE TURNED OVER TO THE CONTRACTOR FOR THE LIFE OF THE SCHEDULED / PHASED SITE WORK.

15. CONTRACTOR TO PROTECT ALL EXISTING UTILITIES.

16. COORDINATE WITH THE COR ON CONTRACTOR PARKING LOCATION.

17. THE CONTRACTOR IS RESPONSIBLE FOR PROTECTING SIDEWALKS, PAVEMENT, AND CURBS. REPLACE COMPLETE SECTIONS WITH NEW IF DAMAGED.

18. THIS PROJECT IS A BUY AMERICA ACT PROJECT.

A

A

PATIENT

ROOM

AE209

AE209

AE209

B

GC100

AE209

A

AE202

TITLE

1/4" = 1'-0"

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

MANN-GRANDSTAFF

VA MEDICAL

CENTER

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

Project Director

Revisions: Date:

100% CONSTRUCTION

DOCUMENTS

NOT FOR CONSTRUCTION

REPAIR SANITARY WASTE

PIPING

668-24-108

20-JUN-2025

MANN-GRANDSTAFF VA MEDICAL CENTER

(502) 890-2210 * WESTPOINTENGINEERS.COM

1941 BISHOP LANE, STE. 400 * LOUISVILLE, KY 40218

4815 N ASSEMBLY ST., SPOKANE, WA 99205

ABBREVIATIONS AND SYMBOLS

GI001

SABBVG

NOT F

OR

C O A010

A007D

AOO7C

C002A

A009

A008 C001

C003A

C002

A006C

A006

A007

C002C

C003

A009A A002B

A002A

A002

D

D D

C O

C O

C O

C O

C O

C O

C O

C O

C O

D D D

D

D

D

C O

O O

D

BUILDING CODE AND GUIDELINES

A. APPLICABLE CODES:

ALL WORK SHALL CONFIRM TO ALL APPLICABLE CODES, STANDARDS AND GOVERNING AUTHORITIES:

INCLUDING BUT NOT LIMITED TO:

BUILDING: INTERNATIONAL BUILDING CODE, 2021 EDITION

LIFE SAFETY: NFPA 101 LIFE SAFETY CODE, 2024 EDITION

MECHANICAL: INTERNATIONAL MECHANICAL CODE, 2024 EDITION

NFPA 90A

PLUMBING: INTERNATIONAL PLUMBING CODE, 2024 EDITION

FIRE PREVENTION: NFPA NATIONAL FIRE CODES WITH THE EXCEPTION

OF NFPA 5000 AND NFPA 900, CURRENT ED.

ELECTRICAL: NATIONAL ELECTRICAL CODE (NEC), 2023 EDITION

ACCESSIBILITY: ABAAS INCLUDING VA SUPPLEMENT. BARRIER FREE

DESIGN

VA PUBLICATIONS: VA DIRECTIVES, DESIGN MANUALS, AND OTHER

GUIDANCE ON THE TECHNICAL INFORMATION

LIBRARY (TIL)

B. OCCUPANCY USE: NFPA 101 2024: CHAPTER 19 EXISTING

HEALTHCARE OCCUPANCIES

IBC: INSTITUTIONAL I-2

C. CONSTRUCTION TYPE: NFPA 101: TYPE II (222)

IBC: TYPE 2B (PROTECTED)

BASEMENT - CONTRACTOR / EMERGENCY EGRESS PLAN

NTS

KEY PLAN: GROUND FLOOR

A

GI004

B

AE100

B

GC100

HEPA

EXHAUST

HEPA

EXHAUST

H

EP

A

EX

H

AU

ST

H

EP

A

EX

H

AU

ST

LIFE SAFETY PLAN LEGEND

NOTE: ALL SYMBOLS MAY NOT BE USED

FIRE EXTINGUISHER CABINET / FIRE EXTINGUISHER

HORIZONTAL EXIT

EXIT SIGN

EGRESS PATH (COMMON PATH)

RATED WALL ASSEMBLY TYPES

RATE WALL ASSEMBLY LEGEND

NOTE:

ALL SYMBOLS MAY NOT BE USED EXISTING RATED WALLS SHOWN AS HALF-TONE

FIRE RESISTIVE RATED, 1 HOUR

FIRE RESISTIVE RATED, 2 HOUR

FIRE-RATED, SMOKE PARTITION, 1 HOUR

FIRE-RATED, SMOKE PARTITION, 2 HOUR

NON-RATED PARTITION

NON-RATED, SUITE, (SMOKE RESISTIVE)

EMERGENCY BATTERY WALL PACK LIGHT

SUITE DESIGNATIONS (EXISTING)

1. SECURITY CAMERAS LINE OF SIGHT WILL BE BLOCKED WHILE CONSTRUCTION WALLS ARE IN PLACE.

VA WILL ADJUST CAMERAS IF NEEDED.

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

MANN-GRANDSTAFF

VA MEDICAL

CENTER

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

Project Director

Revisions: Date:

100% CONSTRUCTION

DOCUMENTS

NOT FOR CONSTRUCTION

REPAIR SANITARY WASTE

PIPING

668-24-108

20-JUN-2025

MANN-GRANDSTAFF VA MEDICAL CENTER

(502) 890-2210 * WESTPOINTENGINEERS.COM

1941 BISHOP LANE, STE. 400 * LOUISVILLE, KY 40218

4815 N ASSEMBLY ST., SPOKANE, WA 99205

LIFE SAFETY DRAWING BASEMENT

LEVEL

GI100

SABBVG

NOT F

OR

C O

A105

A106 A108

A107 A110 A111

A112

C100

A114A113

A104

C102

A100

A119A

A119

A101

A121

A122A123

A12

A12

A120 A118A A118 A117 A116 A115

C116

C118

C120

C105 C107

C109

C111 C113 C115

C117

C104

C106 C108 C110 C112

A102

A121A

UP

BUILDING CODE AND GUIDELINES

A. APPLICABLE CODES:

ALL WORK SHALL CONFIRM TO ALL APPLICABLE CODES, STANDARDS AND GOVERNING AUTHORITIES:

INCLUDING BUT NOT LIMITED TO:

BUILDING: INTERNATIONAL BUILDING CODE, 2021 EDITION

LIFE SAFETY: NFPA 101 LIFE SAFETY CODE, 2024 EDITION

MECHANICAL: INTERNATIONAL MECHANICAL CODE, 2024 EDITION

NFPA 90A

PLUMBING: INTERNATIONAL PLUMBING CODE, 2024 EDITION

FIRE PREVENTION: NFPA NATIONAL FIRE CODES WITH THE EXCEPTION

OF NFPA 5000 AND NFPA 900, CURRENT ED.

ELECTRICAL: NATIONAL ELECTRICAL CODE (NEC), 2023 EDITION

ACCESSIBILITY: ABAAS INCLUDING VA SUPPLEMENT. BARRIER FREE

DESIGN

VA PUBLICATIONS: VA DIRECTIVES, DESIGN MANUALS, AND OTHER

GUIDANCE ON THE TECHNICAL INFORMATION

LIBRARY (TIL)

B. OCCUPANCY USE: NFPA 101 2024: CHAPTER 19 EXISTING

HEALTHCARE OCCUPANCIES

IBC: INSTITUTIONAL I-2

C. CONSTRUCTION TYPE: NFPA 101: TYPE II (222)

IBC: TYPE 2B (PROTECTED)

FIRST FLOOR - CONTRACTOR / EMERGENCY EGRESS PLAN

NTS

KEY PLAN: GROUND FLOOR

A

GI005

AE100

LIFE SAFETY PLAN LEGEND

NOTE: ALL SYMBOLS MAY NOT BE USED

FIRE EXTINGUISHER CABINET / FIRE EXTINGUISHER

HORIZONTAL EXIT

EXIT SIGN

EGRESS PATH (COMMON PATH)

RATED WALL ASSEMBLY TYPES

RATE WALL ASSEMBLY LEGEND

NOTE:

ALL SYMBOLS MAY NOT BE USED EXISTING RATED WALLS SHOWN AS HALF-TONE

FIRE RESISTIVE RATED, 1 HOUR

FIRE RESISTIVE RATED, 2 HOUR

FIRE-RATED, SMOKE PARITION, 1 HOUR

FIRE-RATED, SMOKE PARTITON, 2 HOUR

NON-RATED PARTITION

NON-RATED, SUITE, (SMOKE RESISTIVE)

EMERGENCY BATTERY WALL PACK LIGHT

SUITE DESIGNATIONS (EXISTING)

UP

GC100

1. SECURITY CAMERAS LINE OF SIGHT WILL BE BLOCKED WHILE CONSTRUCTION WALLS ARE IN PLACE.

VA WILL ADJUST CAMERAS IF NEEDED.

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

MANN-GRANDSTAFF

VA MEDICAL

CENTER

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

Project Director

Revisions: Date:

100% CONSTRUCTION

DOCUMENTS

NOT FOR CONSTRUCTION

REPAIR SANITARY WASTE

PIPING

668-24-108

20-JUN-2025

MANN-GRANDSTAFF VA MEDICAL CENTER

(502) 890-2210 * WESTPOINTENGINEERS.COM

1941 BISHOP LANE, STE. 400 * LOUISVILLE, KY 40218

4815 N ASSEMBLY ST., SPOKANE, WA 99205

LIFE SAFETY DRAWING FIRST FLOOR

GI110

SABBVG

NOT F

OR

A213 A212

A208

1208A

A206

A209

A205

A214

A209A

A200 A216A A216 A215

C201

C217

C219

C221

C223

C222

C218

C203

C205 C209

C207 C211 C213

A201

C200 C202

C202A

C204 C206

C208

C O

C O

D

BUILDING CODE AND GUIDELINES

A. APPLICABLE CODES:

ALL WORK SHALL CONFIRM TO ALL APPLICABLE CODES, STANDARDS AND GOVERNING AUTHORITIES:

INCLUDING BUT NOT LIMITED TO:

BUILDING: INTERNATIONAL BUILDING CODE, 2021 EDITION

LIFE SAFETY: NFPA 101 LIFE SAFETY CODE, 2024 EDITION

MECHANICAL: INTERNATIONAL MECHANICAL CODE, 2024 EDITION

NFPA 90A

PLUMBING: INTERNATIONAL PLUMBING CODE, 2024 EDITION

FIRE PREVENTION: NFPA NATIONAL FIRE CODES WITH THE EXCEPTION

OF NFPA 5000 AND NFPA 900, CURRENT ED.

ELECTRICAL: NATIONAL ELECTRICAL CODE (NEC), 2023 EDITION

ACCESSIBILITY: ABAAS INCLUDING VA SUPPLEMENT. BARRIER FREE

DESIGN

VA PUBLICATIONS: VA DIRECTIVES, DESIGN MANUALS, AND OTHER

GUIDANCE ON THE TECHNICAL INFORMATION

LIBRARY (TIL)

B. OCCUPANCY USE: NFPA 101 2024: CHAPTER 19 EXISTING

HEALTHCARE OCCUPANCIES

IBC: INSTITUTIONAL I-2

C. CONSTRUCTION TYPE: NFPA 101: TYPE II (222)

IBC: TYPE 2B (PROTECTED)

SECOND FLOOR - CONTRACTOR / EMERGENCY EGRESS PLAN

NTS

KEY PLAN: SECOND FLOOR

A

GI006

STAIR CLOSED

AE100

UP DN

GC100

LIFE SAFETY PLAN LEGEND

NOTE: ALL SYMBOLS MAY NOT BE USED

FIRE EXTINGUISHER CABINET / FIRE EXTINGUISHER

HORIZONTAL EXIT

EXIT SIGN

EGRESS PATH (COMMON PATH)

RATED WALL ASSEMBLY TYPES

RATE WALL ASSEMBLY LEGEND

NOTE:

ALL SYMBOLS MAY NOT BE USED EXISTING RATED WALLS SHOWN AS HALF-TONE

FIRE RESISTIVE RATED, 1 HOUR

FIRE RESISTIVE RATED, 2 HOUR

FIRE-RATED, SMOKE PARTITION, 1 HOUR

FIRE-RATED, SMOKE PARTITION, 2 HOUR

NON-RATED PARTITION

NON-RATED, SUITE, (SMOKE RESISTIVE)

EMERGENCY BATTERY WALL PACK LIGHT

SUITE DESIGNATIONS (EXISTING)

1. SECURITY CAMERAS LINE OF SIGHT WILL BE BLOCKED WHILE CONSTRUCTION WALLS ARE IN PLACE.

VA WILL ADJUST CAMERAS IF NEEDED.

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

MANN-GRANDSTAFF

VA MEDICAL

CENTER

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

Project Director

Revisions: Date:

100% CONSTRUCTION

DOCUMENTS

NOT FOR CONSTRUCTION

REPAIR SANITARY WASTE

PIPING

668-24-108

20-JUN-2025

MANN-GRANDSTAFF VA MEDICAL CENTER

(502) 890-2210 * WESTPOINTENGINEERS.COM

1941 BISHOP LANE, STE. 400 * LOUISVILLE, KY 40218

4815 N ASSEMBLY ST., SPOKANE, WA 99205

LIFE SAFETY DRAWING SECOND FLOOR

GI120

SABBVG

NOT F

OR

C O

C O

D

C O

D

D

D

D

A313B

A313

A312A

A312 A313A

A314

A313D

A315

A316 C300 C302A

A313C

C302B C304

C306 C310 C312

C325C319

C308

C317 C321 C323 C327

C315

C313C307A

C307C305C303C301A300 A301A302

A311

C309

BUILDING CODE AND GUIDELINES

A. APPLICABLE CODES:

ALL WORK SHALL CONFIRM TO ALL APPLICABLE CODES, STANDARDS AND GOVERNING AUTHORITIES:

INCLUDING BUT NOT LIMITED TO:

BUILDING: INTERNATIONAL BUILDING CODE, 2021 EDITION

LIFE SAFETY: NFPA 101 LIFE SAFETY CODE, 2024 EDITION

MECHANICAL: INTERNATIONAL MECHANICAL CODE, 2024 EDITION

NFPA 90A

PLUMBING: INTERNATIONAL PLUMBING CODE, 2024 EDITION

FIRE PREVENTION: NFPA NATIONAL FIRE CODES WITH THE EXCEPTION

OF NFPA 5000 AND NFPA 900, CURRENT ED.

ELECTRICAL: NATIONAL ELECTRICAL CODE (NEC), 2023 EDITION

ACCESSIBILITY: ABAAS INCLUDING VA SUPPLEMENT. BARRIER FREE

DESIGN

VA PUBLICATIONS: VA DIRECTIVES, DESIGN MANUALS, AND OTHER

GUIDANCE ON THE TECHNICAL INFORMATION

LIBRARY (TIL)

B. OCCUPANCY USE: NFPA 101 2024: CHAPTER 19 EXISTING

HEALTHCARE OCCUPANCIES

IBC: INSTITUTIONAL I-2

C. CONSTRUCTION TYPE: NFPA 101: TYPE II (222)

IBC: TYPE 2B (PROTECTED)

THIRD FLOOR - CONTRACTOR / EMERGENCY EGRESS PLAN

NTS

KEY PLAN: FOURTH FLOOR

A

GI007

STAIR CLOSED

AE100

UP DN

GC100

LIFE SAFETY PLAN LEGEND

NOTE: ALL SYMBOLS MAY NOT BE USED

FIRE EXTINGUISHER CABINET / FIRE EXTINGUISHER

HORIZONTAL EXIT

EXIT SIGN

EGRESS PATH (COMMON PATH)

RATED WALL ASSEMBLY TYPES

RATE WALL ASSEMBLY LEGEND

NOTE:

ALL SYMBOLS MAY NOT BE USED EXISTING RATED WALLS SHOWN AS HALF-TONE

FIRE RESISTIVE RATED, 1 HOUR

FIRE RESISTIVE RATED, 2 HOUR

FIRE-RATED, SMOKE PARTITION, 1 HOUR

FIRE-RATED, SMOKE PARTITION, 2 HOUR

NON-RATED PARTITION

NON-RATED, SUITE, (SMOKE RESISTIVE)

EMERGENCY BATTERY WALL PACK LIGHT

SUITE DESIGNATIONS (EXISTING)

1. SECURITY CAMERAS LINE OF SIGHT WILL BE BLOCKED WHILE CONSTRUCTION WALLS ARE IN PLACE.

VA WILL ADJUST CAMERAS IF NEEDED.

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

MANN-GRANDSTAFF

VA MEDICAL

CENTER

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

Project Director

Revisions: Date:

100% CONSTRUCTION

DOCUMENTS

NOT FOR CONSTRUCTION

REPAIR SANITARY WASTE

PIPING

668-24-108

20-JUN-2025

MANN-GRANDSTAFF VA MEDICAL CENTER

(502) 890-2210 * WESTPOINTENGINEERS.COM

1941 BISHOP LANE, STE. 400 * LOUISVILLE, KY 40218

4815 N ASSEMBLY ST., SPOKANE, WA 99205

LIFE SAFETY DRAWING THIRD FLOOR

GI130

SABBVG

NOT F

OR

C402C400 C404

C407C405C401 C403

A417

A418

A413

BUILDING CODE AND GUIDELINES

A. APPLICABLE CODES:

ALL WORK SHALL CONFIRM TO ALL APPLICABLE CODES, STANDARDS AND GOVERNING AUTHORITIES:

INCLUDING BUT NOT LIMITED TO:

BUILDING: INTERNATIONAL BUILDING CODE, 2021 EDITION

LIFE SAFETY: NFPA 101 LIFE SAFETY CODE, 2024 EDITION

MECHANICAL: INTERNATIONAL MECHANICAL CODE, 2024 EDITION

NFPA 90A

PLUMBING: INTERNATIONAL PLUMBING CODE, 2024 EDITION

FIRE PREVENTION: NFPA NATIONAL FIRE CODES WITH THE EXCEPTION

OF NFPA 5000 AND NFPA 900, CURRENT ED.

ELECTRICAL: NATIONAL ELECTRICAL CODE (NEC), 2023 EDITION

ACCESSIBILITY: ABAAS INCLUDING VA SUPPLEMENT. BARRIER FREE

DESIGN

VA PUBLICATIONS: VA DIRECTIVES, DESIGN MANUALS, AND OTHER

GUIDANCE ON THE TECHNICAL INFORMATION

LIBRARY (TIL)

B. OCCUPANCY USE: NFPA 101 2024: CHAPTER 19 EXISTING

HEALTHCARE OCCUPANCIES

IBC: INSTITUTIONAL I-2

C. CONSTRUCTION TYPE: NFPA 101: TYPE II (222)

IBC: TYPE 2B (PROTECTED)

A

GI007

STAIR CLOSED

FOURTH FLOOR - CONTRACTOR / EMERGENCY EGRESS PLAN

NTS

KEY PLAN: FOURTH FLOOR

AE100

UP DN

GC100

LIFE SAFETY PLAN LEGEND

NOTE: ALL SYMBOLS MAY NOT BE USED

FIRE EXTINGUISHER CABINET / FIRE EXTINGUISHER

HORIZONTAL EXIT

EXIT SIGN

EGRESS PATH (COMMON PATH)

RATED WALL ASSEMBLY TYPES

RATE WALL ASSEMBLY LEGEND

NOTE:

ALL SYMBOLS MAY NOT BE USED EXISTING RATED WALLS SHOWN AS HALF-TONE

FIRE RESISTIVE RATED, 1 HOUR

FIRE RESISTIVE RATED, 2 HOUR

FIRE-RATED, SMOKE PARTITION, 1 HOUR

FIRE-RATED, SMOKE PARTITION, 2 HOUR

NON-RATED PARTITION

NON-RATED, SUITE, (SMOKE RESISTIVE)

EMERGENCY BATTERY WALL PACK LIGHT

SUITE DESIGNATIONS (EXISTING)

1. SECURITY CAMERAS LINE OF SIGHT WILL BE BLOCKED WHILE CONSTRUCTION WALLS ARE IN PLACE.

VA WILL ADJUST CAMERAS IF NEEDED.

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

MANN-GRANDSTAFF

VA MEDICAL

CENTER

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

Project Director

Revisions: Date:

100% CONSTRUCTION

DOCUMENTS

NOT FOR CONSTRUCTION

REPAIR SANITARY WASTE

PIPING

668-24-108

20-JUN-2025

MANN-GRANDSTAFF VA MEDICAL CENTER

(502) 890-2210 * WESTPOINTENGINEERS.COM

1941 BISHOP LANE, STE. 400 * LOUISVILLE, KY 40218

4815 N ASSEMBLY ST., SPOKANE, WA 99205

LIFE SAFETY DRAWING FOURTH FLOOR

GI140

SABBVG

NOT F

OR

C502 C500

C507C505C501 C503

A511

A512

A510

BUILDING CODE AND GUIDELINES

A. APPLICABLE CODES:

ALL WORK SHALL CONFIRM TO ALL APPLICABLE CODES, STANDARDS AND GOVERNING AUTHORITIES:

INCLUDING BUT NOT LIMITED TO:

BUILDING: INTERNATIONAL BUILDING CODE, 2021 EDITION

LIFE SAFETY: NFPA 101 LIFE SAFETY CODE, 2024 EDITION

MECHANICAL: INTERNATIONAL MECHANICAL CODE, 2024 EDITION

NFPA 90A

PLUMBING: INTERNATIONAL PLUMBING CODE, 2024 EDITION

FIRE PREVENTION: NFPA NATIONAL FIRE CODES WITH THE EXCEPTION

OF NFPA 5000 AND NFPA 900, CURRENT ED.

ELECTRICAL: NATIONAL ELECTRICAL CODE (NEC), 2023 EDITION

ACCESSIBILITY: ABAAS INCLUDING VA SUPPLEMENT. BARRIER FREE

DESIGN

VA PUBLICATIONS: VA DIRECTIVES, DESIGN MANUALS, AND OTHER

GUIDANCE ON THE TECHNICAL INFORMATION

LIBRARY (TIL)

B. OCCUPANCY USE: NFPA 101 2024: CHAPTER 19 EXISTING

HEALTHCARE OCCUPANCIES

IBC: INSTITUTIONAL I-2

C. CONSTRUCTION TYPE: NFPA 101: TYPE II (222)

IBC: TYPE 2B (PROTECTED)

A

GI008

STAIR CLOSED

FIFTH FLOOR - CONTRACTOR / EMERGENCY EGRESS PLAN

NTS

KEY PLAN: FIFTH FLOOR

AE100

UP DN

GC100

LIFE SAFETY PLAN LEGEND

NOTE: ALL SYMBOLS MAY NOT BE USED

FIRE EXTINGUISHER CABINET / FIRE EXTINGUISHER

HORIZONTAL EXIT

EXIT SIGN

EGRESS PATH (COMMON PATH)

RATED WALL ASSEMBLY TYPES

RATE WALL ASSEMBLY LEGEND

NOTE:

ALL SYMBOLS MAY NOT BE USED EXISTING RATED WALLS SHOWN AS HALF-TONE

FIRE RESISTIVE RATED, 1 HOUR

FIRE RESISTIVE RATED, 2 HOUR

FIRE-RATED, SMOKE PARTITION, 1 HOUR

FIRE-RATED, SMOKE PARTITION, 2 HOUR

NON-RATED PARTITION

NON-RATED, SUITE, (SMOKE RESISTIVE)

EMERGENCY BATTERY WALL PACK LIGHT

SUITE DESIGNATIONS (EXISTING)

1. SECURITY CAMERAS LINE OF SIGHT WILL BE BLOCKED WHILE CONSTRUCTION WALLS ARE IN PLACE.

VA WILL ADJUST CAMERAS IF NEEDED.

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

MANN-GRANDSTAFF

VA MEDICAL

CENTER

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

Project Director

Revisions: Date:

100% CONSTRUCTION

DOCUMENTS

NOT FOR CONSTRUCTION

REPAIR SANITARY WASTE

PIPING

668-24-108

20-JUN-2025

MANN-GRANDSTAFF VA MEDICAL CENTER

(502) 890-2210 * WESTPOINTENGINEERS.COM

1941 BISHOP LANE, STE. 400 * LOUISVILLE, KY 40218

4815 N ASSEMBLY ST., SPOKANE, WA 99205

LIFE SAFETY DRAWING FIFTH FLOOR

GI150

SABBVG

NOT F

OR

C600 C602

C607C605C601 C603

A614

A616

A613

A615

A617

BUILDING CODE AND GUIDELINES

A. APPLICABLE CODES:

ALL WORK SHALL CONFIRM TO ALL APPLICABLE CODES, STANDARDS AND GOVERNING AUTHORITIES:

INCLUDING BUT NOT LIMITED TO:

BUILDING: INTERNATIONAL BUILDING CODE, 2021 EDITION

LIFE SAFETY: NFPA 101 LIFE SAFETY CODE, 2024 EDITION

MECHANICAL: INTERNATIONAL MECHANICAL CODE, 2024 EDITION

NFPA 90A

PLUMBING: INTERNATIONAL PLUMBING CODE, 2024 EDITION

FIRE PREVENTION: NFPA NATIONAL FIRE CODES WITH THE EXCEPTION

OF NFPA 5000 AND NFPA 900, CURRENT ED.

ELECTRICAL: NATIONAL ELECTRICAL CODE (NEC), 2023 EDITION

ACCESSIBILITY: ABAAS INCLUDING VA SUPPLEMENT. BARRIER FREE

DESIGN

VA PUBLICATIONS: VA DIRECTIVES, DESIGN MANUALS, AND OTHER

GUIDANCE ON THE TECHNICAL INFORMATION

LIBRARY (TIL)

B. OCCUPANCY USE: NFPA 101 2024: CHAPTER 19 EXISTING

HEALTHCARE OCCUPANCIES

IBC: INSTITUTIONAL I-2

C. CONSTRUCTION TYPE: NFPA 101: TYPE II (222)

IBC: TYPE 2B (PROTECTED)

A

GI009

STAIR CLOSED

SIXTH FLOOR - CONTRACTOR / EMERGENCY EGRESS PLAN

NTS

KEY PLAN: SIXTH FLOOR

AE100

UP DN

GC100

LIFE SAFETY PLAN LEGEND

NOTE: ALL SYMBOLS MAY NOT BE USED

FIRE EXTINGUISHER CABINET / FIRE EXTINGUISHER

HORIZONTAL EXIT

EXIT SIGN

EGRESS PATH (COMMON PATH)

RATED WALL ASSEMBLY TYPES

RATE WALL ASSEMBLY LEGEND

NOTE:

ALL SYMBOLS MAY NOT BE USED EXISTING RATED WALLS SHOWN AS HALF-TONE

FIRE RESISTIVE RATED, 1 HOUR

FIRE RESISTIVE RATED, 2 HOUR

FIRE-RATED, SMOKE PARTITION, 1 HOUR

FIRE-RATED, SMOKE PARTITION, 2 HOUR

NON-RATED PARTITION

NON-RATED, SUITE, (SMOKE RESISTIVE)

EMERGENCY BATTERY WALL PACK LIGHT

SUITE DESIGNATIONS (EXISTING)

1. SECURITY CAMERAS LINE OF SIGHT WILL BE BLOCKED WHILE CONSTRUCTION WALLS ARE IN PLACE.

VA WILL ADJUST CAMERAS IF NEEDED.

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

MANN-GRANDSTAFF

VA MEDICAL

CENTER

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

Project Director

Revisions: Date:

100% CONSTRUCTION

DOCUMENTS

NOT FOR CONSTRUCTION

REPAIR SANITARY WASTE

PIPING

668-24-108

20-JUN-2025

MANN-GRANDSTAFF VA MEDICAL CENTER

(502) 890-2210 * WESTPOINTENGINEERS.COM

1941 BISHOP LANE, STE. 400 * LOUISVILLE, KY 40218

4815 N ASSEMBLY ST., SPOKANE, WA 99205

LIFE SAFETY DRAWING SIXTH FLOOR

GI160

SABBVG

NOT F

OR

C702C700

C707C705C701 C703

A711

A712

A710

A713

BUILDING CODE AND GUIDELINES

A. APPLICABLE CODES:

ALL WORK SHALL CONFIRM TO ALL APPLICABLE CODES, STANDARDS AND GOVERNING AUTHORITIES:

INCLUDING BUT NOT LIMITED TO:

BUILDING: INTERNATIONAL BUILDING CODE, 2021 EDITION

LIFE SAFETY: NFPA 101 LIFE SAFETY CODE, 2024 EDITION

MECHANICAL: INTERNATIONAL MECHANICAL CODE, 2024 EDITION

NFPA 90A

PLUMBING: INTERNATIONAL PLUMBING CODE, 2024 EDITION

FIRE PREVENTION: NFPA NATIONAL FIRE CODES WITH THE EXCEPTION

OF NFPA 5000 AND NFPA 900, CURRENT ED.

ELECTRICAL: NATIONAL ELECTRICAL CODE (NEC), 2023 EDITION

ACCESSIBILITY: ABAAS INCLUDING VA SUPPLEMENT. BARRIER FREE

DESIGN

VA PUBLICATIONS: VA DIRECTIVES, DESIGN MANUALS, AND OTHER

GUIDANCE ON THE TECHNICAL INFORMATION

LIBRARY (TIL)

B. OCCUPANCY USE: NFPA 101 2024: CHAPTER 19 EXISTING

HEALTHCARE OCCUPANCIES

IBC: INSTITUTIONAL I-2

C. CONSTRUCTION TYPE: NFPA 101: TYPE II (222)

IBC: TYPE 2B (PROTECTED)

A

GI009

STAIR CLOSED

SEVENTH FLOOR - CONTRACTOR / EMERGENCY EGRESS PLAN

NTS

KEY PLAN: SEVENTH FLOOR

AE100

UP DN

GC100

LIFE SAFETY PLAN LEGEND

NOTE: ALL SYMBOLS MAY NOT BE USED

FIRE EXTINGUISHER CABINET / FIRE EXTINGUISHER

HORIZONTAL EXIT

EXIT SIGN

EGRESS PATH (COMMON PATH)

RATED WALL ASSEMBLY TYPES

RATE WALL ASSEMBLY LEGEND

NOTE:

ALL SYMBOLS MAY NOT BE USED EXISTING RATED WALLS SHOWN AS HALF-TONE

FIRE RESISTIVE RATED, 1 HOUR

FIRE RESISTIVE RATED, 2 HOUR

FIRE-RATED, SMOKE PARTITION, 1 HOUR

FIRE-RATED, SMOKE PARTITION, 2 HOUR

NON-RATED PARTITION

NON-RATED, SUITE, (SMOKE RESISTIVE)

EMERGENCY BATTERY WALL PACK LIGHT

SUITE DESIGNATIONS (EXISTING)

1. SECURITY CAMERAS LINE OF SIGHT WILL BE BLOCKED WHILE CONSTRUCTION WALLS ARE IN PLACE.

VA WILL ADJUST CAMERAS IF NEEDED.

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

MANN-GRANDSTAFF

VA MEDICAL

CENTER

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

Project Director

Revisions: Date:

100% CONSTRUCTION

DOCUMENTS

NOT FOR CONSTRUCTION

REPAIR SANITARY WASTE

PIPING

668-24-108

20-JUN-2025

MANN-GRANDSTAFF VA MEDICAL CENTER

(502) 890-2210 * WESTPOINTENGINEERS.COM

1941 BISHOP LANE, STE. 400 * LOUISVILLE, KY 40218

4815 N ASSEMBLY ST., SPOKANE, WA 99205

LIFE SAFETY DRAWING SEVENTH

FLOOR

GI170

SABBVG

NOT F

OR

A802

A807A805

A801

A803

A800B B803

A800A

A804

BUILDING CODE AND GUIDELINES

A. APPLICABLE CODES:

ALL WORK SHALL CONFIRM TO ALL APPLICABLE CODES, STANDARDS AND GOVERNING AUTHORITIES:

INCLUDING BUT NOT LIMITED TO:

BUILDING: INTERNATIONAL BUILDING CODE, 2021 EDITION

LIFE SAFETY: NFPA 101 LIFE SAFETY CODE, 2024 EDITION

MECHANICAL: INTERNATIONAL MECHANICAL CODE, 2024 EDITION

NFPA 90A

PLUMBING: INTERNATIONAL PLUMBING CODE, 2024 EDITION

FIRE PREVENTION: NFPA NATIONAL FIRE CODES WITH THE EXCEPTION

OF NFPA 5000 AND NFPA 900, CURRENT ED.

ELECTRICAL: NATIONAL ELECTRICAL CODE (NEC), 2023 EDITION

ACCESSIBILITY: ABAAS INCLUDING VA SUPPLEMENT. BARRIER FREE

DESIGN

VA PUBLICATIONS: VA DIRECTIVES, DESIGN MANUALS, AND OTHER

GUIDANCE ON THE TECHNICAL INFORMATION

LIBRARY (TIL)

B. OCCUPANCY USE: NFPA 101 2024: CHAPTER 19 EXISTING

HEALTHCARE OCCUPANCIES

IBC: INSTITUTIONAL I-2

C. CONSTRUCTION TYPE: NFPA 101: TYPE II (222)

IBC: TYPE 2B (PROTECTED)

A

GI009

STAIR CLOSED

EIGHTH FLOOR - CONTRACTOR / EMERGENCY EGRESS PLAN

NTS

KEY PLAN: EIGHTH FLOOR

AE100

UP DN

GC100

LIFE SAFETY PLAN LEGEND

NOTE: ALL SYMBOLS MAY NOT BE USED

FIRE EXTINGUISHER CABINET / FIRE EXTINGUISHER

HORIZONTAL EXIT

EXIT SIGN

EGRESS PATH (COMMON PATH)

RATED WALL ASSEMBLY TYPES

RATE WALL ASSEMBLY LEGEND

NOTE:

ALL SYMBOLS MAY NOT BE USED EXISTING RATED WALLS SHOWN AS HALF-TONE

FIRE RESISTIVE RATED, 1 HOUR

FIRE RESISTIVE RATED, 2 HOUR

FIRE-RATED, SMOKE PARTITION, 1 HOUR

FIRE-RATED, SMOKE PARTITION, 2 HOUR

NON-RATED PARTITION

NON-RATED, SUITE, (SMOKE RESISTIVE)

EMERGENCY BATTERY WALL PACK LIGHT

SUITE DESIGNATIONS (EXISTING)

1. SECURITY CAMERAS LINE OF SIGHT WILL BE BLOCKED WHILE CONSTRUCTION WALLS ARE IN PLACE.

VA WILL ADJUST CAMERAS IF NEEDED.

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

MANN-GRANDSTAFF

VA MEDICAL

CENTER

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

Project Director

Revisions: Date:

100% CONSTRUCTION

DOCUMENTS

NOT FOR CONSTRUCTION

REPAIR SANITARY WASTE

PIPING

668-24-108

20-JUN-2025

MANN-GRANDSTAFF VA MEDICAL CENTER

(502) 890-2210 * WESTPOINTENGINEERS.COM

1941 BISHOP LANE, STE. 400 * LOUISVILLE, KY 40218

4815 N ASSEMBLY ST., SPOKANE, WA 99205

LIFE SAFETY DRAWING EIGHTH FLOOR

GI180

SABBVG

NOT F

OR

1. SECURITY CAMERAS LINE OF SIGHT WILL BE BLOCKED WHILE CONSTRUCTION WALLS ARE IN PLACE.

VA WILL ADJUST CAMERAS IF NEEDED.

BUILDING CODE AND GUIDELINES

A. APPLICABLE CODES:

ALL WORK SHALL CONFIRM TO ALL APPLICABLE CODES, STANDARDS AND GOVERNING AUTHORITIES:

INCLUDING BUT NOT LIMITED TO:

BUILDING: INTERNATIONAL BUILDING CODE, 2021 EDITION

LIFE SAFETY: NFPA 101 LIFE SAFETY CODE, 2024 EDITION

MECHANICAL: INTERNATIONAL MECHANICAL CODE, 2024 EDITION

NFPA 90A

PLUMBING: INTERNATIONAL PLUMBING CODE, 2024 EDITION

FIRE PREVENTION: NFPA NATIONAL FIRE CODES WITH THE EXCEPTION

OF NFPA 5000 AND NFPA 900, CURRENT ED.

ELECTRICAL: NATIONAL ELECTRICAL CODE (NEC), 2023 EDITION

ACCESSIBILITY: ABAAS INCLUDING VA SUPPLEMENT. BARRIER FREE

DESIGN

VA PUBLICATIONS: VA DIRECTIVES, DESIGN MANUALS, AND OTHER

GUIDANCE ON THE TECHNICAL INFORMATION

LIBRARY (TIL)

B. OCCUPANCY USE: NFPA 101 2024: CHAPTER 19 EXISTING

HEALTHCARE OCCUPANCIES

IBC: INSTITUTIONAL I-2

C. CONSTRUCTION TYPE: NFPA 101: TYPE II (222)

IBC: TYPE 2B (PROTECTED)

A

GI009

PENTHOUSE - CONTRACTOR / EMERGENCY EGRESS PLAN

NTS

KEY PLAN: PENTHOUSE

AE100

DNDN

LIFE SAFETY PLAN LEGEND

NOTE: ALL SYMBOLS MAY NOT BE USED

FIRE EXTINGUISHER CABINET / FIRE EXTINGUISHER

HORIZONTAL EXIT

EXIT SIGN

EGRESS PATH (COMMON PATH)

RATED WALL ASSEMBLY TYPES

RATE WALL ASSEMBLY LEGEND

NOTE:

ALL SYMBOLS MAY NOT BE USED EXISTING RATED WALLS SHOWN AS HALF-TONE

FIRE RESISTIVE RATED, 1 HOUR

FIRE RESISTIVE RATED, 2 HOUR

FIRE-RATED, SMOKE PARTITION, 1 HOUR

FIRE-RATED, SMOKE PARTITION, 2 HOUR

NON-RATED PARTITION

NON-RATED, SUITE, (SMOKE RESISTIVE)

EMERGENCY BATTERY WALL PACK LIGHT

SUITE DESIGNATIONS (EXISTING)

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

MANN-GRANDSTAFF

VA MEDICAL

CENTER

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

Project Director

Revisions: Date:

100% CONSTRUCTION

DOCUMENTS

NOT FOR CONSTRUCTION

REPAIR SANITARY WASTE

PIPING

668-24-108

20-JUN-2025

MANN-GRANDSTAFF VA MEDICAL CENTER

(502) 890-2210 * WESTPOINTENGINEERS.COM

1941 BISHOP LANE, STE. 400 * LOUISVILLE, KY 40218

4815 N ASSEMBLY ST., SPOKANE, WA 99205

LIFE SAFETY DRAWING NINTH FLOOR

GI190

SABBVG

NOT F

OR

C O A010

A007D

C002A

D

D D

C O

A105

A106 A108

A213 A214

A209A

C O

C O

C O

C300 C302A

C402 C404

C502 C500

C702C700 A802 C600 C602

A615

A617

GC100

7 SEVENTH FLOOR PLAN

1/4" - 1'-0" GC100

8 EIGHTH FLOOR PLAN

1/4" - 1'-0"

GC100

5 FIFTH FLOOR PLAN

1/4" - 1'-0"GC100

4 FOURTH FLOOR PLAN

1/4" - 1'-0"GC100

3 THIRD FLOOR PLAN

1/4" - 1'-0"

GC100

B BASEMENT FLOOR PLAN

1/4" - 1'-0" GC100

1 FIRST FLOOR PLAN

1/4" - 1'-0" GC100

2 SECOND FLOOR PLAN

1/4" - 1'-0"

GC100

6 SIXTH FLOOR

1/4" - 1'-0"

1/4" SINTRA RED

3/8" WHITE LINE

WHITE LETTERING

CUSTOM TEMPORARY SIGNAGE

1/4" SINTRA YELLOW

3/8" BLACK LINE

BLACK LETTERING

INSTALL ON DOOR AND ON TEMPORARY

DOOR PANEL TO CONSTRUCTION AREA.

LETTERS SIZE 2"

32" TALL FREE STANDING SIGNS.

SUPPLY 2, TWO OR FOUR SIDED FLOOR

SIGNS. MAINTAIN WATCH PERSON

UNTIL FLOOR IS DRY.

1/4" SINTRA WHITE

3/8" BLACK LINE

BLACK LETTERING

16X16 INCH SIGN INSTALLED ON DOOR

LEAVING CONSTRUCTION AREA.

LETTERS SIZE 2"

LEVEL I

1. PERFORM WORK ACTIVITY IN A MANNER THAT DOES NOT CREATE DUST.

2. IMMEDIATELY REPLACE ANY CEILING TILE, CLOSE ACCESS PANELS, ETC., UPON COMPLETION OF WORK.

3. ANY MATERIALS AND EQUIPMENT BEING BROUGHT INTO THE FACILITY MUST BE FREE OF

CONTAMINANTS AND LOOSE MATERIAL.

LEVEL II - PLUS ALL OF CONTROL LEVEL I

1. PROVIDE ACTIVE MEANS TO CONTROL AIRBORNE DUST FROM DISPERSING INTO OCCUPIED AREAS AND/OR WATER MIST SURFACE TO CONTROL

DUST (E.G., MOBILE DUST CONTAINMENT CART OR SOME OTHER SYSTEM).

2. ENSURE WORKER CLOTHING IS CLEAN AND FREE OF VISIBLE DUST BEFORE LEAVING THE WORK AREA. REMOVE OR ISOLATE AIR DIFFUSERS (SUPPLY AND RETURN) TO PROTECT THE HVAC SYSTEM FROM DUST AND REDUCE AIR TURBULENCE. REBALANCE SYSTEM TO ADDRESS DIFFUSER

ISOLATION.

3. WHEN THE WORK INVOLVES OR IMPACTS POTABLE WATER SYSTEMS INCLUDING STAGNATION DUE TO REDUCED USAGE, THE PIPING SHALL BE

FLUSHED TWICE A WEEK OR ISOLATED FROM THE MAIN SYSTEM.

4. SEAL DOORS TO PREVENT DUST MIGRATION.

5. CONTAIN ALL TRASH AND DEBRIS IN THE WORK AREA. PERFORM DAILY CLEANING AND DISPOSAL OF TRASH (COVERED) FROM WORK AREA USING

AN IDENTIFIED EXIT ROUTE.

6. ANY EQUIPMENT, TOOLS, OR MATERIALS REMOVED FROM THE WORK AREA MUST BE IN SEALED CONTAINERS AND/OR CLEANED OF DUST AND

DEBRIS PRIOR TO REMOVAL FROM THE AREA.

7. NONPOROUS/SMOOTH AND CLEANABLE CONTAINERS (WITH A HARD LID) MUST BE USED TO TRANSPORT TRASH AND DEBRIS FROM THE

CONSTRUCTION AREAS. THESE CONTAINERS MUST BE DAMP-WIPED CLEANED AND FREE OF VISIBLE DUST/DEBRIS BEFORE LEAVING THE

CONTAINED WORK AREA.

8. INSTALL A STICKY (DUST COLLECTION) MAT AT ENTRANCE OF CONTAINED WORK AREA BASED ON FACILITY POLICY. STICKY MATS MUST BE

CHANGED ROUTINELY AND WHEN VISIBLY SOILED.

9. MAINTAIN CLEAN SURROUNDINGS WHEN AREA IS NOT CONTAINED BY DAMP MOPPING OR HEPA VACUUMING SURFACES AT LEAST DAILY.

LEVEL III ALL CONTROL MEASURES IN LEVELS I AND II AND THE FOLLOWING:

1. ENSURE AVAILABILITY OF EQUIPMENT FOR CLEANING HANDS.

2. CONSTRUCT AND COMPLETE CRITICAL BARRIERS MEETING NFPA 241 REQUIREMENTS. BARRIERS MUST EXTEND TO THE CEILING OR IF CEILING TILE

IS REMOVED, TO THE DECK ABOVE. SOLID WALL BARRIERS MUST EXTEND TO 8'-0"+/- FACTORY LABELED FIRE RATED PLASTIC MAY BE USED IN

CLEAR STORY AREA ABOVE 8'-0" +/- FACTORY LABELED FIRE RATED TAPE MUST BE USED

3. ALL (PLASTIC OR HARD) BARRIER CONSTRUCTION ACTIVITIES MUST BE COMPLETED IN A MANNER THAT PREVENTS DUST RELEASE. PLASTIC BARRIERS MUST BE EFFECTIVELY AFFIXED TO FLOOR AND CEILING (OR FLOOR/ROOF DECK ABOVE) AND SECURE FROM MOVEMENT OR DAMAGE.

4. SEAL ALL PENETRATIONS IN CONTAINMENT BARRIERS, INCLUDING FLOORS AND CEILING, USING APPROVED MATERIALS (UL SCHEDULE FIRESTOP IF

APPLICABLE FOR BARRIER TYPE).

5. MAINTAIN .01 INCHES /WATER GAUGE NEGATIVE PRESSURIZATION OF THE ENTIRE WORKSPACE BY USE OF HEPA EXHAUST AIR SYSTEMS DIRECTED OUTDOORS (UNLESS A WORK SPECIFIC WAIVER IS APPROVED BY VHA’S OFFICE OF HEALTHCARE ENGINEERING); THIS MUST BE MAINTAINED CONTINUOUSLY 24/7 FOR THE DURATION OF THE PROJECT. EXHAUST DISCHARGED DIRECTLY TO THE OUTDOORS THAT IS 25 FEET OR GREATER FROM ENTRANCES, AIR INTAKES AND WINDOWS IS NOT REQUIRED TO BE HEPA-FILTERED. EXHAUSTING DISCHARGED AIR INTO SHARED OR RECIRCULATING HVAC SYSTEMS, OR OTHER SHARED EXHAUST SYSTEMS (E.G., BATHROOM EXHAUST) IS PROHIBITED.

6. INSTALL A DIFFERENTIAL PRESSURE SENSING DEVICE (DIGITAL MONITORING) ON EXTERIOR OF WORK CONTAINMENT TO CONTINUALLY MONITOR AND DOCUMENT NEGATIVE PRESSURIZATION. THE “BALL IN THE WALL” OR SIMILAR APPARATUS ARE NOT ACCEPTABLE.

LEVEL OF PRECAUTIONS CONTROL MEASURES - III

THE CONTRACTOR SHALL COMPLY WITH ALL CONTROL MEASURES

ALL

CONTRACTOR

PROVIDED FIRE

EXTINGUISHER

ON STANDS

HEPA AIR

SCRUBBER

CONNECT TO

EXHAUST DUCT

1 HOUR HARD WALL

CONTAINMENT

STAIR CLOSEDSTAIR CLOSED

STAIR CLOSED STAIR CLOSED STAIR CLOSED

STAIR CLOSED

WALK OFF MAT

EXHAUST THROUGH WINDOW EXHAUST THROUGH WINDOW

EXHAUST THROUGH WINDOW

EXHAUST THROUGH WINDOWEXHAUST THROUGH WINDOW

EXHAUST THROUGH WINDOW

EXHAUST THROUGH WINDOW

ELECTRONIC MONITOR

GAUGE NEGATIVE

PRESSURIZATION.

BALL IN WALL NOT PERMIT.

ELECTRONIC MONITOR

GAUGE NEGATIVE

PRESSURIZATION.

BALL IN WALL NOT PERMIT.

ELECTRONIC MONITOR

GAUGE NEGATIVE

PRESSURIZATION.

BALL IN WALL NOT PERMIT.

ELECTRONIC MONITOR

GAUGE NEGATIVE

PRESSURIZATION.

BALL IN WALL NOT PERMIT.

ELECTRONIC MONITOR

GAUGE NEGATIVE

PRESSURIZATION.

BALL IN WALL NOT PERMIT.

ELECTRONIC MONITOR

GAUGE NEGATIVE

PRESSURIZATION.

BALL IN WALL NOT PERMIT.

ELECTRONIC MONITOR

GAUGE NEGATIVE

PRESSURIZATION.

BALL IN WALL NOT PERMIT.

ELECTRONIC MONITOR

GAUGE NEGATIVE

PRESSURIZATION.

BALL IN WALL NOT PERMIT.

ELECTRONIC MONITOR

GAUGE NEGATIVE

PRESSURIZATION.

BALL IN WALL NOT PERMIT.

AE400

AE400

AE400

AE400

AE400

AE400

AE400

AE400

AE400

STAIR CLOSED

SD SD

SD

SD

SD

SD

SD

SD SD

SD CONSTRUCTION

PROVIDED TEMPORARY

SMOKE AND HEAT

DETECTOR.

CODED NOTES

A. WORK WITHIN THE CONTAINED CONSTRUCTION AREA SHALL BE ICRA LEVEL III.

B. WORK WITHIN THE MECHANICAL ROOM IS ICRA LEVEL I.

C. CONTRACTOR TO SUBMIT A FULL ICRA PLAN ALONG WITH ANY ACTIVITY HAZARD ANALYSIS TO THE COR FOR APPROVAL. THE PROVIDED

SUGGESTION ON THIS SHEET ARE MINIMAL AND SHOULD ONLY BE USED TO GUIDE THE CONTRACTOR IN A FULL ICRA SUBMITTAL.

D. THE WALLS, FANS, DOORS, AND OVERALL EQUIPMENT DEPICTED ON THIS DRAWING IS A GENERAL LOCATION AND SHALL BE MOVED TO

ACCOMMODATE THE CONTRACTOR AND OWNERS COORDINATED BUILDING PLAN.

E. REMOVE THE STAIRWELL FIRE RATED DOOR. CONSTRUCT A NEW TWO HOUR RATED BARRIER WALL AT THE DOOR LOCATION. INSTALL A RATED

FIRE DAMPER AND A RATED ACCESS DOOR.

F. INSTALL 25MIL HEAVY DUTY FIRE RETARDANT ANTI SKID FLOOR PROTECTION.

G. PROVIDE ONE EXTINGUISHER MOUNTED ON A STAND ON EACH FLOOR STAIR LANDING AS WELL AS IN EACH CONSTRUCTION AREA.

H. PROVIDE STICKY FLOOR MATS AT EACH EGRESS AREA FROM THE CONSTRUCTION AREA.

I. INSTALL ONE SMOKE DETECTOR IN EACH CONSTRUCTION AREA THESE SHALL NOTIFY SECURITY WHEN IN ALARM.

J. REMOVE, MODIFY AND REINSTALL WINDOWS USING A WINDOW MANUFACTURE APPROVED PROCESS. PROVIDE A LETTER FROM THE WINDOW

MANUFACTURE THAT ALL STAIR WINDOWS REMAIN IN COMPLIANCE WITH THERE WARRANTY.

K. HEPA AIR SCRUBBERS TO BE CLEANED AS NEEDED WITH DAILY REPORTS SHOWING RUN TIME, FILTER LIFE AND ESTIMATED FILTER CHANGE DATES.

ALL FILTERS FOLLOWING ABATEMENT SHALL BE REPLACED BY THE ABATEMENT COMPANY.

L. DIGITAL NEGATIVE AIR MONITORING SHALL MAINTAIN AN HOURLY AVERAGE AS DEFINED IN THE SPECIFICATION. PRODUCE THIS REPORT DAILY TO

THE COR OR APPROVED CLOUD BASED MANAGEMENT SYSTEM. BASIS OF DESIGN IS PROCORE.

M. REVIEW ALL CEILING TILES ARE IN PLACE AT THE END OF EACH SHIFT AND ANY CEILING OR WALL PENETRATIONS ARE SEALED TO A U.L. APPROVED

WALL OR CEILING METHOD.

N. REVIEW ALL HARDWALL ENCLOSURES ARE MAINTAINED AND FUNCTIONAL.

O. "NEW" DENOTES THE ADDITION OF A BOTTLE FILL STATION.

P. "EXISTING" DENOTES THE REMOVAL OF AN EXISTING DRINKING FOUNTAIN.

EXHAUST OUT

WINDOW IN

ROOM

A002

SEE GI100 FOR

ROUTING

NEW

EXISTING

NEW

NEW NEW

EXISTING

NEW NEW

EXISTING

GENERAL NOTES

1. REMOVE AND REINSTALL DOOR. INFILL THE DOOR FRAME WITH A 2 HOUR RATED WALL WITH A SIZED FIRE DAMPER PERMITTING AIR TO BE PULLED

FROM THE CONSTRUCTION AREA AND EXHAUSTED OUT THE STAIR WINDOWS.

2. INSTALL FIRE RESISTANT FLOOR COVERING COMPLIANT WITH ASTM C1028-96; NFPA 701-04.

3. REMOVE WINDOW, INSTALL EXHAUST DUCT AND REINSTALL WINDOW MAINTAINING THE MANUFACTURER'S WARRANTY.

4. SECURITY CAMERAS LINE OF SIGHT WILL BE BLOCKED WHILE CONSTRUCTION WALLS ARE IN PLACE. VA WILL ADJUST CAMERAS IF NEEDED.

2 2 2

3 3 3

RELOCATE PULL STATION

AND EMERGENCY LIGHTING

TO SOLID WALL CONTAINMENT .

REINSTALL UPON COMPLETION.

RELOCATE

EMERGENCY

EGRESS LIGHTING

RIGHT HAND SIDE

OF DOOR

RELOCATE EXISTING FIRE PULL

STATION TO EXTERIOR OF

TEMPORARY SOLID WALL

CONSTRUCTION BARRIER.

REINSTALL NEW COR APPROVED

LOCATION UPON COMPLETION.

REMOVE AND RELOCATE

EXISTING EXIT LIGHT TO NEW

COR APPROVED LOCATION.

REMOVE AND RELOCATE

EXISTING FIRE PULL STATION

TO NEW COR APPROVED

LOCATION WITHIN 60" OF

EGRESS DOOR. CONTRACTOR

SHALL TEMPORARILY MOUNT TO

CONSTRUCTION BARRIER.

REMOVE AND RELOCATE

EXISTING FIRE PULL STATION

TO NEW COR APPROVED

LOCATION WITHIN 60" OF

EGRESS DOOR. CONTRACTOR

SHALL TEMPORARILY MOUNT TO

CONSTRUCTION BARRIER.

4 4

4 4

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

MANN-GRANDSTAFF

VA MEDICAL

CENTER

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

Project Director

Revisions: Date:

100% CONSTRUCTION

DOCUMENTS

NOT FOR CONSTRUCTION

REPAIR SANITARY WASTE

PIPING

668-24-108

20-JUN-2025

MANN-GRANDSTAFF VA MEDICAL CENTER

(502) 890-2210 * WESTPOINTENGINEERS.COM

1941 BISHOP LANE, STE. 400 * LOUISVILLE, KY 40218

4815 N ASSEMBLY ST., SPOKANE, WA 99205

ICRA FLOOR PLAN

GC100

SABBVG

EXHAUST THROUGH

STAIRWELL OUT 2ND

FLOOR STAIRWELL

WINDOW. SEE DETAIL

2/GC100 AND GI100.

STAIR CLOSED

SD

NOT F

OR

C O A010

A007D

C002A

A009

A008 C001

C002

D

D D

O

C O

C

C O

A105

A106 A108

A113

UP

3"- ROOF

LEADER

1" -DRINKING WATER COLD

2" - SANITARY

1 1/2" - VENT

6" - FIRE

A213 A212

A214

A209A

A216A A216

C O

C O

3"- ROOF

LEADER

1" -DRINKING WATER COLD

2" - SANITARY

1 1/2" - VENT

6" - FIRE

C O

C O

C O C O

A315

A316 C300 C302A

C302B

C307C305C303C301

3"- ROOF

LEADER

1" -DRINKING WATER COLD

2" - SANITARY

1 1/2" - VENT

6" - FIRE

C402C400 C404

C407C405C401 C403

A417

A418

3"- ROOF LEADER

1" -DRINKING WATER COLD

2" - SANITARY

1 1/2" - VENT

6" - FIRE

C502 C500

C507C505C501 C503

A512

3"- ROOF LEADER

1" -DRINKING WATER COLD

2" - SANITARY

1 1/2" - VENT

6" - FIRE

C702C700

C707C705C701 C703

A712

A713

3"- ROOF LEADER

1" -DRINKING WATER COLD

2" - SANITARY

1 1/2" - VENT

6" - FIRE A802

A807A805 A803

A800A

3"- ROOF LEADER

1" -DRINKING WATER COLD

2" - SANITARY

1 1/2" - VENT

6" - FIRE

ROOF

ELEVATOR

MACHINE

ROOM

EXT. 4"- SANITARY/VENT

EXT. 2"- SANITARY

EXT. 3"- ELECTRICAL

PANEL 9N1

REMOVE 3PHASE

WELDER BREAKER

AND INSTALL NEW

POWER TO

EQUIPMENT

C600 C602

C607C605C601 C603

A616

A615

A617

3"- ROOF LEADER

1" -DRINKING WATER COLD

2" - SANITARY

1 1/2" - VENT

6" - FIRE

GC101

7 SEVENTH FLOOR PLAN

1/4" - 1'-0" GC101

8 EIGHTH FLOOR PLAN

1/4" - 1'-0"

GC101

10 NINTH FLOOR

1/4" - 1'-0"

GC101

5 FIFTH FLOOR PLAN

1/4" - 1'-0"GC101

4 FOURTH FLOOR PLAN

1/4" - 1'-0"GC101

3 THIRD FLOOR PLAN

1/4" - 1'-0"

GC101

B BASEMENT FLOOR PLAN

1/8" - 1'-0" GC101

1 FIRST FLOOR PLAN

1/4" - 1'-0" GC101

2 SECOND FLOOR PLAN

1/4" - 1'-0"

GC101

6 SIXTH FLOOR

1/4" - 1'-0"

EXISTING

WINDOW

PHASING PLAN - 195 TOTAL DAYS

ALL DAYS ARE CALENDAR DAYS

PHASE 1 30 DAYS (VA TO PROVIDE DIRECTION

SUBMITTALS / PROJECT SETUP

PHASE 2 60 DAYS DEMOLITION / ABATEMENT RETAIN

ACCESS FROM THE 7TH FLOOR TO

THE 9TH FLOOR AT ALL TIMES.

REMAINDER OF STAIR WELL ONE

WILL BE CLOSED.

PHASE 3 30 DAYS NEW PIPING INSTALLATION AND

ELECTRICAL INSTALLATION FROM

9TH FLOOR AND BELOW.

PHASE 4 15 DAYS INSTALLING BOTTLE FILL STATIONS

CORRIDOR PAINTING TO TAKE

PLACE AND CONTAINMENT AREAS

CAN BE REMOVED.

PHASE 5 15 DAYS TESTING AND WATER PURIFICATION

PHASE 6 15 DAYS FINISH PAINT IS APPLIED AND FINAL

CLEANUP

PHASE 7 30 DAYS EDUCATION AND CLOSEOUT

EXISTING

WINDOW

EXISTING

WINDOW

EXISTING

WINDOW

EXISTING

WINDOW

EXISTING

WINDOW

EXISTING

WINDOW

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

MANN-GRANDSTAFF

VA MEDICAL

CENTER

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

Project Director

Revisions: Date:

100% CONSTRUCTION

DOCUMENTS

NOT FOR CONSTRUCTION

REPAIR SANITARY WASTE

PIPING

668-24-108

20-JUN-2025

MANN-GRANDSTAFF VA MEDICAL CENTER

(502) 890-2210 * WESTPOINTENGINEERS.COM

1941 BISHOP LANE, STE. 400 * LOUISVILLE, KY 40218

4815 N ASSEMBLY ST., SPOKANE, WA 99205

PHASING

GC101

SABBVG

NOT F

OR

O

C O A010

C002A

A009

A008 C001

4"

D D C O

6" 1"

2-1/2" 1"

1" 1"

MEDICAL

VACUUM

3"- ROOF LEADER

1" -DRINKING WATER COLD

2" - SANITARY

1 1/2" - VENT

6" - FIRE

A106 A108

A113

3"- ROOF

LEADER

1" -DRINKING WATER COLD

2" - SANITARY

1 1/2" - VENT

6" - FIRE

A213 A214

A209A

WV O

S

V

T T

3"- ROOF

LEADER

1" -DRINKING WATER COLD

2" - SANITARY

1 1/2" - VENT

6" - FIRE

C O

C O C

O

C300 C302A

C302B

V W O

3"- ROOF

LEADER

1" -DRINKING WATER COLD

2" - SANITARY

1 1/2" - VENT

6" - FIRE

C402 C404

3"- ROOF LEADER

1" -DRINKING WATER COLD

2" - SANITARY

1 1/2" - VENT

6" - FIRE

C502 C500

3"- ROOF LEADER

1" -DRINKING WATER COLD

2" - SANITARY

1 1/2" - VENT

6" - FIRE

C702C700

3"- ROOF LEADER

1" -DRINKING WATER COLD

2" - SANITARY

1 1/2" - VENT

6" - FIRE A802

3"- ROOF LEADER

1" -DRINKING WATER COLD

2" - SANITARY

1 1/2" - VENT

6" - FIRE

EXT. 4"- SANITARY/VENT

EXT. 2"- SANITARY

EXT. 3"- ELECTRICAL

PANEL 9N1

REMOVE 3PHASE

WELDER BREAKER

AND INSTALL NEW

POWER TO

EQUIPMENTC600 C602

A615

A617

3"- ROOF LEADER

1" -DRINKING WATER COLD

2" - SANITARY

1 1/2" - VENT

6" - FIRE

HA100

7 SEVENTH FLOOR PLAN

1/4" - 1'-0" HA100

8 EIGHTH FLOOR PLAN

1/4" - 1'-0" HA100

9 NINTH FLOOR PLAN

1/4" - 1'-0"

HA100

5 FIFTH FLOOR PLAN

1/4" - 1'-0"HA100

4 FOURTH FLOOR PLAN

1/4" - 1'-0"HA100

3 THIRD FLOOR PLAN

1/4" - 1'-0"

HA100

B BASEMENT FLOOR PLAN

1/4" - 1'-0" HA100

1 FIRST FLOOR PLAN

1/4" - 1'-0" HA100

2 SECOND FLOOR PLAN

1/4" - 1'-0"

HA100

6 SIXTH FLOOR

1/4" - 1'-0"

PLAN NOTES

GENERAL NOTES

1. INDICATES AREAS OF ASBESTOS-CONTAINING PIPE INSULATION, CLEAN ALL CHASE CEILING, WALL, AND FLOOR CAVITIES CLEANING AND

ENCAPSULATION ALL SURFACES.

2. ON EACH FLOOR / DECK PENETRATION REMOVE SURROUNDING CONCRETE / SCRATCH-COAT CEMENT PLASTER TO ALLOW REMOVAL OF

ASBESTOS FLOOR OR DECK PENETRATIONS.

3. CLEAN ALL CEILINGS, WALLS AND FLOORS AND SPRAY A WHITE ENCAPSULATING ASBESTOS BINDING COMPOUND ON ALL CHASE CEILINGS, WALLS AND FLOOR AREAS.

4.INSULATION CONTAINING ACM. ROOF LEADER IS CORK REMOVE AS WELL. SEE PLUMBING DRAWINGS FOR ADDITIONAL DETAIL.

5.EXISTING PLASTER CONTAINS A PAINT COAT CONTAINING LEAD BASED PAINT ABOVE THE ACTION LEVEL. ABATE LEAD PAINT FROM WALL PRIOR TO DEMOLITION WORK. PROVIDE A FEDERAL APPROVED ABATEMENT PLAN APPROVED 30 DAYS BEFORE DEMOLITION IS TO START. PEEL AWAY 1

IS AN APPROVED STRIPPER OR APPROVED EQUAL.

1 1

1 1 1

GENERAL DESCRIPTION:

A. ON THE BASEMENT LEVEL REMOVE ONE WYTHE CLAY WALL BRICK TO EXPOSE THE WATER AND CORK COVERED PLUMBING LINES.

REMOVE ALL ACM MATERIALS STOPPING AT THE EXTENT OF THE WALL DEMOLITION. IN TWO LOCATIONS WORK ABOVE THE WALL INDICATED ON THE DRAWINGS WILL REQUIRE REMOVAL OF CORK AND INSULATED LINES WITHIN SIX FEET OF THE CHASE, TERMINATING AT VALVES OR AS THE PIPE EXTEND INTO THE FLOOR, CEILING OR WALLS. SEE PHOTOGRAPHS ON THE PLAN SET FOR

ADDITIONAL INFORMATION ALSO SEE THE PLUMBING DEMOLITION PLANS.

B. ON THE 2ND TO 8TH FLOOR EXPOSE THE CHASE AREA PER THE APPROVED DEMOLITION SUBMITTAL. REMOVE ALL LOSE MATERIALS FROM THE FLOOR AREA, EACH CHASE HAS FIBROUS INSULATED AND OR A CORK INSULATION ABATE / REMOVE ALL EXISTING INSULATION FROM THE CHASE AREA. CLEAN ALL WALLS AS WELL AS THE CONCRETE DECK OF ACM AND COAT WITH A (WHITE) ASBESTOS BINDING COMPOUND ON ALL REMAINING CHASE FLOOR, CEILING AND WALL SURFACES.

C. AT EACH FLOOR PENETRATION EXPAND THE EXISTING CEMENT SCRATCH COAT AND CONCRETE TO ALLOW FOR FIRE SLEEVES ALL WHILE INSURING ALL ASBESTOS MATERIALS ARE REMOVED FROM THESE PIPES FLOOR AND DECK PASS THROUGH.

D. SEE PLUMBING DESIGN FOR NEW INSULATION REQUIREMENTS.

E. THE CONTRACTOR SHALL TAKE SAMPLES OF EACH PAINT TO BE DISTURBED OR REMOVED ON EACH FLOOR. THE CONTRACTOR SHALL REMOVE / MANAGE ALL LEAD BASED PAINT ON DOOR FRAMES, DOORS AND PLASTER WALLS. FOLLOW A LOCAL, STATE AND FEDERAL APPROVED LEAD ABATEMENT / MANAGEMENT PLAN APPROVED 30 DAYS BEFORE WORK IS TO BEGIN.

F. NOTED: "ROOF LEADER" HAS A CORK INSULATION. REMOVE AND INSTALL NEW INSULATION.

G. NOTED: "DRINKING WATER COLD" ABATE INSULATION AND INSTALL NEW INSULATION PER THE PLUMBING DESIGN.

2 2 2

2 2

3 3

3 3

3 3 3

LEAD ABATEMENT (LBP)

SEE SPECIFICATIONS 02 83 33.13 LEAD-BASED PAINT REMOVAL AND DISPOSAL

REMOVE / MANAGE 720 + / - SQUARE FEET OF LEAD- CONTAINING PAINT. REMOVE / MANAGE ALL LEAD PAINT FROM EACH FLOORS: DOORS, FRAMES, WALLS, AND PIPES STARTING IN THE BASEMENT AND ENDING ON THE NINTH FLOOR. THIS PROJECT IS NOT A FULL ABATEMENT PROJECT FOR LEAD PAINT. 100% REMOVAL IS REQUIRED FOR CUTTING THROUGH THE LEAD PAINT AREAS. ALL OTHER AREAS CAN REMAIN

AFTER WALL PREPARATION AND ENCAPSULATION BEFORE APPLYING NEW FINISHES.

CLEAN AND ENCAPSULATE ALL EXPOSED LEAD BASE PAINT PRIOR TO PRIMER AND FINISH COATS OF PAINT. FOLLOW THE CONTRACTORS

APPROVED LEAD BASED PAINT MANAGEMENT PLAN.

SOME ORIGINALLY LEAD BASED PAINTED PLASTER WALLS ARE BEHIND NEWER DRYWALL OR THE ORIGINAL FINISH HAS BEEN RECOATED.

THE CONTRACTOR IS TO ASSUME ALL ORIGINAL PLASTER, DOORS AND FRAMES CONTAIN LEAD PAINT ABOVE THE ACTION LEVEL.

AE200

AE200

AE207

5 5

5 5 5

ASBESTOS ABATEMENT (ACM)

SEE SPECIFICATIONS 02 82 11 TRADITIONAL ASBESTOS ABATEMENT

REMOVE AND DISPOSE OF 300 + / - LINEAL FEET OF ASBESTOS - CONTAINING PIPE INSULATION. REMOVE ALL ACM FROM EACH FLOORS

CHASE STARTING IN THE BASEMENT AND ENDING ON THE EIGHTH FLOOR.

CLEAN AND ENCAPSULATE ALL INNER CHASE CEILINGS, WALLS AND FLOOR USING AN ASBESTOS BINDING COMPOUND STARTING ON THE

FIRST FLOOR AND ENDING ON THE EIGHTH FLOOR.

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

MANN-GRANDSTAFF

VA MEDICAL

CENTER

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

Project Director

Revisions: Date:

100% CONSTRUCTION

DOCUMENTS

NOT FOR CONSTRUCTION

REPAIR SANITARY WASTE

PIPING

668-24-108

20-JUN-2025

MANN-GRANDSTAFF VA MEDICAL CENTER

(502) 890-2210 * WESTPOINTENGINEERS.COM

1941 BISHOP LANE, STE. 400 * LOUISVILLE, KY 40218

4815 N ASSEMBLY ST., SPOKANE, WA 99205

HAZARDOUS MATERIALS

HA100

SABBVG

NOT F

OR

GI130
GI130
GI140
GI140
GI150
GI150
GI160
GI160
GI170
GI170
668-24-108_100CD_DRAWINGS_Part1.pdf
GI000
GI000
GI001
GI001
GI100
GI100
GI110
GI110
GI120
GI120
668-24-108_100CD_DRAWINGS_Part3.pdf
GI180
GI180
GI190
GI190
GC100
GC100

File details come from the government source that posted it. Updated .