Attch2_SPEC CT Site Prep_Drawings.pdf
PDF 19 MB Posted
- Attached to
- Y1DA-660-CSI-109 SPEC CT Site Prep Federal contract opportunity
- Solicitation number
- 36C25920Q0432
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| Attch4_PN 660-CSI-109 100PCT Stamped - Specifications.docx | DOCX document | |
| Amendment0001_36C25920Q0432 0001.docx | DOCX document | |
| Attch2_SIGN IN SHEET CT-Sit Prep.pdf | ||
| Attch3_RFIs_SPEC CT Site Prep.pdf | ||
| Attch1_CT Site Prep _Site Visit Doc.pdf | ||
| Attch3_Past Performance Questionnaire.docx | DOCX document | |
| 36C25920Q0432_1_SOLICITATION.docx | DOCX document | |
| Attch1_SPEC CT Site Prep_Specs.pdf | ||
| Attch4_Calculation Worksheet for Self-Performed and Subcontracted Work.docx | DOCX document |
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
T
T
A
V a l d e z
D r i v e
K i s t e s
S t r e e t
K i s t e r e e t
W a h l n
W a y
B a k r e e t
H a l r e e t
B e n n i o
B v d
HP
HP
P a t i e
R
V
L t
V a l d i v e
V a l d i v e
R d
B u t
C e e k
W a h l y
BIKE
RACKS
E
C
U
500 Foothill Drive
M a r i
C p e c c h i i v e
V
A
NA
C
C
E
S
S
IB
LE
V
A
NA
C
C
E
S
S
IB
LE
W a k a y
Sunnyside Avenue (8th South)
D
F o o t h i i v e
H a r e e t
K i s t e r e e t
B a k r e e t
HP
HP
500 Foothill Drive
V
A
N
A
C
C
E
S
S
I
B
L
E
V
A
N
A
C
C
E
S
S
I
B
L
E
AREA OF WORKVICINITY MAP SHEET INDEX
SALT LAKE CITY VETERANS AFFAIRS MEDICAL CENTER
SALT LAKE CITY, UTAH
VAMC PROJECT #: 660-CSI-109
SPEC CT SITE PREP
True
North
02/27/2019 MVP SD
GI001
COVER SHEET
VEG 18.11
660-CSI-109
500 FOOTHILL DRIVE SALT LAKE CITY, UT 84148
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
F i l e
P a t h
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
321 4 5 6 7 8 9 10
Project Director
Issued: Date:
750 W HAMPDEN AVE.
SUITE #300
ENGLEWOOD, CO 80110
(720) 550-6307
WWW.VALHALLAENGINEERING.COM
CONSULTANTS: ARCHITECT/ENGINEERS: STAMP: CONSTRUCTION DOCUMENTS
(Contract Deliverable CD3-100%)
SPEC CT SITE PREP
AREA OF WORK
BUILDING 1
T
O
View Name
1/8" = 1'-0"
SECTION, DETAIL, OR ELEVATION TITLE EXAMPLE
ELEVATION CALLOUT EXAMPLE
DETAIL CALLOUT EXAMPLE
SECTION CALLOUT EXAMPLE
SECTION, DETAIL, OR ELEVATION
SYMBOL IDENTIFIERS
DETAIL NAME
LETTER OR NUMBER DESIGNATOR
DRAWING SEQUENCE NUMBER
INDICATES WHERE TITLE IS
LOCATED
ONE OR TWO CHARACTER
DISCIPLINE DESIGNATOR (MAY
NOT BE PRESENT IF CALLOUT
AND TITLE ARE ON DRAWINGS
WITHIN THE SAME DISCIPLINE)
A
A101
AE101
AE101
AE101
W-3
P2
RB3
DOOR NUMBER TAG
WALL TYPE TAG
WINDOW TYPE TAG
CENTER LINE
WALL FINISH TAG
A
COLUMN BUBBLE
ROOM TAG
WALL COLOR
BASE TYPE /
COLOR
MATCH LINE
DETAIL NUMBER
ON SHEET
SHEET NUMBER
DETAIL NUMBER
ON SHEET
SHEET NUMBER
NEW LINE TYPE.
EXISTING LINE TYPE.
DEMO LINE TYPE.
ROOM NAME
DEMO HATCH TYPE.
FIRE RESISTIVE RATED WALL, 1 HOUR
FIRE RESISTIVE RATED WALL, 2 HOUR
FIRE RESISTIVE RATED WALL, 3 HOUR
FIRE RESISTIVE RATED WALL, 4 HOUR
S
S
S
S
FIRE RATED, SMOKE BARRIER WALL, 1 HOUR
FIRE RATED, SMOKE BARRIER WALL, 1 HOUR
FIRE RATED, SMOKE BARRIER WALL, 1 HOUR
FIRE RATED, SMOKE BARRIER WALL, 1 HOUR
2'-0" 2'-2"
M A
X
MAX.
0' - 10"
2'-6"
M A
X
M I N
M I N
M I N
M A
X
1'-5"
MIN.
M I N
4'-0"
MIN.
19"
MAX.
MIRROR
CLEAR
FLOOR
SPACE
MAX.
0' - 6"
0'-8"
MIN.
1'-5"
MIN.
MIRROR
M A
X
M I N
M I N
0'-6"
MAX.
0'-8"
MIN.
T
O
1'-0"
MAX.
T
O
3'-6"
MIN.
3'-0"
TOILET PAPER
1'-6"
TYP.
1'-0"1'-0"
3'-0"
MIN.
T
O
T
O
(H) ACCESSIBLE TOILET WITH GRAB BAR (I) ACCESSIBLE TOILET WITH GRAB BAR
2'-0" PREFERRED.
1'-6" MIN.
M
I N
PULL SIDE
PUSH SIDE
(D) FRONT APPROACHES - SWING DOORS
M
I N
4'-0" MIN. IF
DOOR HAS
BOTH LATCH
AND CLOSER
MIN.
1' - 0"
* IF DOOR HAS BOTH A
CLOSER AND LATCH
W I D
T H
CLR. LENGTH
IF WIDTH IS 5', CLR. LENGTH IS 3'-0" MIN.
IF WIDTH IS 4'-6", CLR. LENGTH IS 3'-6" MIN.
M I N
4'-6"
MIN.
4'-0" MAX. IF DOOR
HAS BOTH A CLOSER
AND LATCH.
(G) HINGE-SIDE APPROACHES - SWING DOORS
M
I N
2'-0"
MIN.
4'-6" MIN. IF DOOR HAS CLOSER
(K) LATCH-SIDE APPROACHES - SWING DOORS
2'-0"
MIN.
4'-0" MIN. IF
DOOR HAS
BOTH A LATCH
AND CLOSER
(A) CLEAR FLOOR SPACE, PARALLEL APPROACH (B) HIGH AND LOW SIDE REACH
(C) MAXIMUM SIDE REACH
OVER OBSTRUCTIONS
(E) LAVATORY CLEARANCES (F) DRINKING FOUNTAIN SPOUT HEIGHT
AND KNEE CLEARANCES
(J) ROLL-IN SHOWER WITH FOLDING SEAT
M I N
2'-0"
MIN.
3'-0"
MIN.
DRAIN
NAPKIN DISPOSAL
SYMBOLS LEGENDABBREVIATIONS GENERAL NOTES
02/27/2019 MVP SD
GI002
GENERAL INFORMATION
VEG 18.11
660-CSI-109
500 FOOTHILL DRIVE SALT LAKE CITY, UT 84148
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
F i l e
P a t h
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
321 4 5 6 7 8 9 10
Project Director
Issued: Date:
750 W HAMPDEN AVE.
SUITE #300
ENGLEWOOD, CO 80110
(720) 550-6307
WWW.VALHALLAENGINEERING.COM
CONSULTANTS: ARCHITECT/ENGINEERS: STAMP: CONSTRUCTION DOCUMENTS
(Contract Deliverable CD3-100%)
SPEC CT SITE PREP
& AND
@ AT
AB ANCHOR BOLT
ACFL ACCESS FLOOR
ACOUS ACOUSTICAL
AD AREA DRAIN
ADJ ADJUSTABLE
ADJT ADJACENT
ADMIN ADMINISTRATION
AFF ABOVE FINISH FLOOR
AHU AIR HANDLING UNIT
ALT ALTERNATE
ALUM ALUMINUM
AP ACCESS PANEL
APROX APPROXIMATE
ARCH ARCHITECTURAL
AT ACOUSTICAL CEILING TILE
AUTO AUTOMATIC
AWT ACOUSTICAL WALL TREATMENT
BD BOARD
BFE BOTTOM FOOTING ELEVATION
BG BUMPER GUARD
BKT BRACKET
BLDG BUILDING
BM BEAM
BOT BOTTOM
BP BRICK PAVING
BR BRICK
BRG BEARING
BSMT BASEMENT
C CHANNEL
CAB CABINET
CANTL CANTILEVER
CAP CAPACITY
CAT CATEGORY
CCTV CLOSED CIRCUIT TELEVISION
CD COILING DOOR
CG COILING GRILLE
CGD CORNER GUARD
CH COAT HOOK
CJT CONTROL JOINT
CL CENTER LINE
CLS CLASS
CLG CEILING
CLR CLEAR
CM CONSTRUCTION MANAGER
CMU CONCRETE MASONRY UNIT
CO CASED OPENING
COL COLUMN
CONC CONCRETE
CONF CONFERENCE
CONN CONNECT/-ED/-ION
CONST CONSTRUCTION
CONT CONTINUE/CONTINUOUS
CONTR CONTRACTOR
COORD COORDINATE
CORR CORRIDOR
CP CARPET
CPT CARPET MODULE TILE
CR-1 CHAIR RAIL
CR-2 CRASH RAIL
CT CERAMIC TILE
CTR CENTER
CW CURTAIN WALL
CWR COLD WATER
CYL CYLINDER
D DEPTH OR DEEP
DEMO DEMOLITION
DEPR DEPRESSION
DBL DOUBLE
DF DRINKING FOUNTAIN
DIA DIAMETER
DIAG DIAGONAL
DIFF DIFFUSER
DIM DIMENSION
DISP DISPENSER
DIST DISTRIBUTION
DIV DIVISION
DN DOWN
DP DATA PROCESSING
DR DOOR
DS DOWNSPOUT
DWG DRAWING
ELC ELECTRICAL CABINET
EC EPOXY COATING
EF EXHAUST FAN
EFTR EXISTING FINISH TO REMAIN
EJT EXPANSION JOINT
EL ELEVATION
ELEC ELECTRICAL
EMERG EMERGENCY
EO ELECTRICAL OUTLET
EPDM ETHYLENE PROPYLENE DIENE
MONOMER
EQ EQUAL
EQUIP EQUIPMENT
EWC ELECTRIC WATER COOLER
EXH EXHAUST HOOD
EXIST EXISTING
EXP EXPANSION
EXT EXTERIOR
EXT-P EXTERIOR PAINT
EXT-ST EXTERIOR STAIN
FA FIRE ALARM
FAP FIRE ALARM PANEL
FB FIRE BLANKET
FD FLOOR DRAIN
FDN FOUNDATION
FDV FIRE DEPARTMENT VALVE
FE FIRE EXTINGUISHER
FEC FIRE EXTINGUISHER CABINET
FGS FOAM GASKET SEAL
FH FIRE HOSE
FHV FIRE HOSE VALVE
FIN FINISH
FIXT FIXTURE
FLR FLOOR
FL FLOW LINE
FP FIRE PROOFING
H HIGH
HB HOSE BIB
HD HAND DRYER
HDCP HANDICAP
HDR HEADER
HDW HARDWARE
HM HOLLOW METAL
HORIZ HORIZONTAL
HPT HIGH POINT
HR HANDRAIL
HT HEIGHT
HTR HEATER
HVAC HEATING, VENTILATING,
AIR CONDITIONING
HW HOT WATER
HWD HARDWOOD
IC INTERCOM
ID INSIDE DIAMETER
IN INCH
INSUL INSULATION
INT INTERIOR
ISO ISOLATION
JAN JANITOR
JB JUNCTION BOX
JST JOIST
JT JOINT
KO KNOCK OUT
L LAVATORY
LB POUND
LCD LINEAR CEILING DIFFUSER
LF LINE FIGURED
LIN LINEAR
LKR LOCKER
LLH LONG LEG HORIZONTAL
LLV LONG LEG VERTICAL
LMC LINEAR METAL CEILING
LOC LOCATION OR LOCATE
LPT LOW POINT
LS LAWN SPRINKLING
LT LIGHT
LTG LIGHTING
LVR LOUVER
LWC LINEAR WOOD CEILING
MAT MATERIAL
MAX MAXIMUM
MBD MARKER BOARD
MC MEDICINE CABINET
MCU MODULAR COOLING UNIT
MECH MECHANICAL
MEMB MEMBRANE
MET METAL
MRF MANUFACTURER
MH MANHOLE
MIL MILLIMETER
MN MINIMUM
MR MIRROR
MISC MISCELLANEOUS
MO MASONRY OPENING
MONO MONOLITHIC
MPU MULTI- PURPOSE UNIT
MTD MOUNTED
MTL METAL
MTR MOTOR
MULL MULLION
PNL PANEL
PR PAIR
PRELIM PRELIMINARY
PRES PLASTIC RESIN
PRESS PRESSURE
PRIM PRIMARY
PROJ PROJECTION
PRV POWER ROOF VENTILATOR
PTC PAPER TOWEL CABINET
PTR PRINTER
PVC POLYVINYL CHLORIDE
R RADIUS
RI RISER
RA RETURN AIR
RB RESILIENT BASE/RUBBER BASE
RD ROOF DRAIN
REC RECESSED
REF REFERENCE
REFR REFRIGERATOR
REG REGISTER
REIN REINFORCE/-ED/-ING
REM REMOVE
REQD REQUIRED
RET RETAINING
REVS REVERSE
REV REVISE
RF RESILIENT FLOOR
RFI REQUEST FOR INFORMATION
RH ROOF HATCH
RM ROOM
RO ROUGH OPENING
RS ROUGH SLAB
RSF RESILIENT SHEET FLOOR
RWC RAIN WATER CONDUCTOR
SI SINK
SCHED SCHEDULE
SD SHOWER DRAIN
SDR SMOKE DAMPER
SDISP SOAP DISPENSER
STF STORE FRONT
SF SQUARE FOOT
SH SHOWER
SHT SHEET
SHTG SHEATHING
SIM SIMILAR
SM SURFACE MOUNTED
SNC SANITARY NAPKIN CABINET
SND SANITARY NAPKIN DISPOSER
SP STANDPIPE
SPEC SPECIFICATIONS
SPR SINGLE PLY ROOF
SQ SQUARE
SQ YD SQUARE YARD
SR SERVICE RECEPTOR
SS SERVICE SINK
SST STAINLESS STEEL
STR STREET
ST STONE TILE
STC SOUND TRANSMISSION
STD STANDARD
STL STEEL
STOR STORAGE
STRUC STRUCTURAL
T TOP
TAN TANGENT
TCAB TOWEL CABINET
TDR TRENCH DRAIN
TEL TELEPHONE
TEMP TEMPERATURE
TER TERRAZZO
TG TONGUE & GROVE
THRES THRESHOLD
TOIL TOILET
TPH TOILET PAPER HOLDER
TR TREAD
TRANSF TRANSFORMER
TS TUBE SECTION
TV TELEVISION
TYP TYPICAL
U URINAL
UCT UNDERCUT
UCR UNDERCOUNTER
UFD UNDER FLOOR DUCT
UG UNDERGROUND
UH UNIT HEATER
UNFIN UNFINISHED
UNO UNLESS NOTED OTHERWISE
US UTILITY SHELF
UTIL UTILITY
VIF VERIFY IN FIELD
VC VALVE CABINET
VCT VINYL COMPOSITION TILE
VENT VENTILATION
VERT VERTICAL
VEST VESTIBULE
VR VAPOR RETARDER
VTR VENT THROUGH ROOF
WCV WALL COVERING
W WIDTH/WIDE
WF WIDE FLANGE
W/ WITH
W/O WITHOUT
WC WATER CLOSET
WD WOOD
WDW WINDOW
WG WALL GUARD
WH WALL HYDRANT
WHCH WHEELCHAIR
WHTR WATER HEATER
WPL WALL PANEL
WP WATERPROOF
WR WASTE RECEPTACLE
WS WEATHERSTRIP
WSCT WAINSCOT
WSF WELDED SEAM-RESILIENT
SHEET FLOORING
WDT WINDOW TREATMENT
WT WEIGHT
WW WOOD WINDOW
WWF WELD WIRE FABRIC
NA NOT APPLICABLE
NC NURSE CALL
NIC NOT IN CONTRACT
NO NUMBER
NOM NOMINAL
NRC NOISE REDUCTION COEFFICIENT
NT NOTE
NTS NOT TO SCALE
OC ON CENTER
OD OUTSIDE DIAMETER
OFF OFFICE
OH OVERHEAD
OP OPERABLE PARTITION
OPER OPERATOR
OPNG OPENING
OPP OPPOSITE
OFD OVERFLOW ROOF DRAIN
FRMG FRAMING
FSTOP FIRE STOPPING
FT FOOT/FEET
FTG FOOTING
FURR FURRING
GA GAUGE
GAL GALLONS
GALV GALVANIZED
GB GRAB BAR
GBM GRADE BEAM
GC GENERAL CONTRACTOR
GENL GENERAL
GENR GENERATOR
GL GLASS
GR GRADE
GRT GROUT
GWB GYPSUM WALLBOARD
GYP GYPSUM
P PAINT
PART PARTITION
PB PUSH BUTTON
PC PRECAST CONCRETE
PCD PAPER CUP DISPENSER
PED PEDESTAL
PLT PLATE
PROP PROPERTY LINE
PLAM PLASTIC LAMINATE
PLBG PLUMBING
PLS PLASTER
PLW PLYWOOD
ACCESSIBILITY GUIDELINES
CODE DATA
COR CONTRACTING OFFICER'S
REPRESENTATIVE
1. ALL CONTRACTORS AND THEIR SUPERVISORY PERSONNEL MUST REVIEW THE GENERAL AND
SUPPLEMENTARY CONDITIONS TO THE CONTRACT.
2. ALL WORK MUST CONFORM WITH APPLICABLE BUILDING CODES, REGULATIONS AND ORDINANCES.
3. CONTRACTOR MUST OBTAIN ALL REQUIRED BUILDING AND OCCUPANCY PERMITS.
4. CONTRACTOR MUST BECOME FULLY ACQUAINTED WITH CONDITIONS RELATED TO THE WORK.
5. CONTRACTOR MUST BE SOLELY RESPONSIBLE FOR THE MEANS, METHODS AND SEQUENCES OF
CONSTRUCTION AND THE SAFETY OF ALL CONSTRUCTION PERSONNEL AND VISITORS.
6. DRAWINGS CONTAINED IN THIS SET MUST NOT BE REPRODUCED FOR SHOP DRAWINGS. COPIES OF THESE DRAWINGS SUBMITTED AS SHOP DRAWINGS WILL BE REJECTED AND RETURNED TO THE CONTRACTOR.
7. EACH INSTALLER MUST EXAMINE SUBSTRATE AND/OR CONDITIONS UNDER WHICH THE WORK WILL BE INSTALLED AND REPORT TO THE CONTRACTOR IN WRITING ANY CONDITIONS DETRIMENTAL TO THE PROPER AND TIMELY EXECUTION OF THAT INSTALLERS WORK. DO NOT PROCEED UNTIL UNSATISFACTORY CONDITIONS ARE CORRECTED. COMMENCING WITH INSTALLATION WILL CONSTITUTE ACCEPTANCE OF THE SUBSTRATE
AND/OR CONDITIONS.
8. DO NOT SCALE DRAWINGS: FOLLOW WRITTEN DIMENSIONS AND NOTES. CONTACT COR FOR CLARIFICATIONS, IF REQUIRED.
9. DIMENSIONS SHOWN ON THE FLOOR PLAN ARE TO THE FACE OF GYP. BOARD/ WALL (FOG), FACE OF MASONRY (FOM), FACE OF CONCRETE WALLS (FOC) AND COLUMN GRID LINES, UNLESS OTHERWISE NOTED OR
INDICATED.
10. NOTE: WALL THICKNESSES ARE NOMINAL DIMENSIONS, NOT ACTUAL DIMENSIONS. ALL STUD WALL
THICKNESSES ARE 5 INCHES, UNLESS DIMENSIONED OTHERWISE.
11. ALL MASONRY WALL THICKNESSES ARE 8 INCHES, UNLESS DIMENSIONED OTHERWISE NOTED.
12. "TYPICAL", AS USED IN THESE DOCUMENTS, MEANS THAT THE CONDITION OR DIMENSION IS REPRESENTATIVE
OF, OR THE SAME, FOR SIMILAR CONDITIONS THROUGHOUT.
13. IF THERE IS A DISCREPANCY BETWEEN SMALL SCALE AND LARGE SCALE DRAWINGS, (PLAN, SECTION, & DETAIL DRAWINGS, ETC.), CONTACT COR FOR CLARIFICATION. FOR BIDDING PURPOSES: THE MOST EXPENSIVE AND/OR STRICTEST REQUIREMENTS MUST GOVERN. FOR CLARIFICATIONS DURING CONSTRUCTION, THE MOST
EXPENSIVE AND/OR STRICTEST REQUIREMENTS, AS INDICATED BY THE COR, MUST GOVERN.
14. IF THERE ARE ANY DISCREPANCIES BETWEEN THE DRAWINGS AND SPECIFICATIONS, CONTACT COR FOR CLARIFICATION. FOR BIDDING PURPOSES: THE MOST EXPENSIVE AND/OR STRICTEST REQUIREMENTS MUST GOVERN. FOR CLARIFICATIONS DURING CONSTRUCTION: THE MOST EXPENSIVE AND/OR STRICTEST
REQUIREMENTS, AS INDICATED BY THE COR, MUST GOVERN.
15. ANY DISCREPANCIES BETWEEN THE DRAWINGS AND ACTUAL CONDITIONS MUST BE REPORTED TO THE COR IN
WRITING FOR RESOLUTION, PRIOR TO PROCEEDING WITH THE WORK.
16. ANY AND ALL DISCREPANCIES MUST BE REPORTED TO THE COR IN WRITING FOR RESOLUTION, PRIOR TO PROCEEDING WITH THE WORK. IN THESE INSTANCES, NO CHANGE ORDERS OR EXTENSIONS OF TIME WILL BE ALLOWED OR ACCEPTED FOR PROCEEDING WITH THE WORK WITHOUT THE COR'S WRITTEN DIRECTION AND APPROVAL. ALSO, CONTRACTOR MUST REPAIR AND/OR REPLACE ANY UNAUTHORIZED WORK, AS INDICATED
BY THE COR, AT NO ADDITIONAL COST TO THE OWNER.
17. ALL DISSIMILAR METAL MATERIALS MUST BE ISOLATED WITH AN APPROVED NONMETAL ISOLATION MATERIAL.
18. OPEN EXTERIOR JOINTS AROUND WINDOW AND DOOR FRAMES, BETWEEN WALLS AND FOUNDATIONS, BETWEEN WALL PANELS AND AT PENETRATIONS OF UTILITIES THROUGH THE BUILDING ENVELOPE, ETC, MUST BE SEALED, CAULKED, FLASHED OR WEATHER-STRIPPED AS REQUIRED FOR COMPATIBILITY WITH ADJACENT MATERIALS
AND TO ELIMINATE AIR LEAKAGE AND WATER ENTRY.
19. PROVIDE SEALANT AND/OR CAULKING BETWEEN DISSIMILAR ADJOINING INTERIOR MATERIALS. (I.E. WINDOW
SILLS TO GYP. BD., ACT CEILINGS TO MASONRY WALLS, ETC.)
20. DOOR OPENINGS NOT LOCATED BY DIMENSION MUST BE CENTERED IN WALL SHOWN OR LOCATED 2 INCHES FROM FINISH WALL TO FINISH JAMB, ALWAYS ALLOWING A MINIMUM OF 18" FROM THE PULL SIDE OF THE DOOR
TO THE INTERSECTING WALL.
21. CONTRACTOR MUST VERIFY THE LOCATIONS OF ALL EXISTING UNDERGROUND UTILITIES AND THEIR SERVICE
CONNECTIONS WITH THE PROPER UTILITY COMPANY.
22. THE CONTRACTOR IS RESPONSIBLE TO COORDINATE FINAL SIZE AND DEPTH OF THE ELEVATOR PIT, SHAFT, RAIL SUPPORT, HOIST SUPPORT, OVERRUN AND MISC. ELEVATOR REQUIREMENTS WITH THE SELECTED
ELEVATOR MANUFACTURER/ SUPPLIER.
23. CONTRACTOR MUST COORDINATE SIZE, LOCATIONS AND NUMBER OF ALL ROOF OPENINGS AND ROOF ACCESSORIES WITH ALL OTHER TRADES. REFER TO THE CORURAL, STRUCTURAL, PLUMBING, MECHANICAL AND
ELECTRICAL DRAWINGS.
24. LOCATIONS AND SIZES OF ALL CONCRETE MECHANICAL AND ELECTRICAL PADS MUST BE COORDINATED BY THE MECHANICAL AND ELECTRICAL CONTRACTORS, WITH THE SELECTED EQUIPMENT MANUFACTURER/SUPPLIER
AND ARE TO BE APPROVED BY THE COR PRIOR TO PROCEEDING WITH THE WORK.
25. EXCEPT AT FIRE-RATED PARTITIONS, ALL WALL AND COLUMN GYPSUM BOARD FACING MUST BE HELD AT 5/8
INCH BELOW STRUCTURE, UNLESS DETAILED OR NOTED OTHERWISE.
26. AT ALL TELECOMMUNICATION ROOMS: PROVIDE 3/4" X 8'-0" HIGH FIRE-RETARDANT-TREATED WOOD SHEATHING OR PROVIDE PLYWOOD OVER NON-COMBUSTIBLE SHEATHING, BOTTOM TO BE LOCATED AT 4" A.F.F. VERIFY
LENGTHS AND LOCATIONS WITH ELECTRICAL DRAWINGS.
27. GLASS DOORS, ADJACENT PANELS AND ALL GLAZED OPENINGS WITHIN 1'-6" OF THE FLOOR, AND WITHIN A 24-INCH ARC OF EITHER VERTICAL EDGE OF A DOOR, ETC., MUST BE SAFETY GLAZING AS APPROVED FOR
IMPACT BY APPLICABLE BUILDING CODES, AND MUST BE LABELED AS SUCH.
28. ALL CEILING HEIGHTS AS SHOWN ON PLANS AND DETAILS ARE FROM SLAB OR TILE FLOOR (FINISHED FLOOR) TO
FINISH CEILING.
29. PROVIDE INDEPENDENT FRAMING AND ATTACHMENTS TO THE STRUCTURE, ADEQUATE TO SUPPORT THE CEILING SYSTEM, LIGHT FIXTURES, DUCTS, DIFFUSERS, SPRINKLER PIPING AND BUS DUCTS.
30. ALL CLOSETS AND ALCOVES WITHOUT A SPACE IDENTIFICATION NUMBER MUST HAVE THE SAME FINISHES AS
ADJOINING SPACES.
31. CONTRACTOR TO INSTALL WOOD BLOCKING AND PLYWOOD AS REQUIRED FOR THE MOUNTING OF ALL TOILET ACCESSORIES, MILLWORK/ CASEWORK, AV EQUIPMENT, MEP ITEMS AND RADIOLOGY EQUIPMENT, ETC.
32. RE: SPECIFICATIONS FOR ALL REQUIRED TESTING AND INSPECTIONS.
33. ANY/ ALL PROPRIETARY PRODUCTS DESCRIBED AND/OR DRAWN IN THE DOCUMENTS (BUT NOT SPECIFIED) ARE TO MEET THE MANUFACTURER'S STANDARD CRITERIA WHICH IS NOT LIMITED TO THE FOLLOWING:
PERFORMANCE REQUIREMENTS, QUALITY ASSURANCE REQUIREMENTS, APPLICABLE CODES AND INDUSTRY STANDARDS, FABRICATION, ASSEMBLY, HANDLING, DELIVERY, STORAGE, INSTALLATION, OPERATION, ADJUSTMENTS, ETC. PROVIDE THE MANUFACTURER'S STANDARD WARRANTY AND STANDARD FINISH WARRANTY. PROVIDE PRODUCT DATA, SHOP DRAWINGS, SAMPLES AND MAINTENANCE DATA AS REQUIRED.
REFER TO DIVISION 01 SPEC. SECTIONS WHICH ALSO APPLY, SUCH AS SUBSTITUTION PROCEDURES, SUBMITTAL PROCEDURES, QUALITY REQUIREMENTS, REFERENCES, EXECUTION AND CLOSEOUT PROCEDURES.
NOTE: ANY SUBSTITUTIONS MUST MEET THE DESIGN INTENT, AS WELL AS THE CRITERIA DESCRIBED ABOVE.
34. ALL EXTERIOR EXPOSED STEEL MUST BE PAINTED.
Q1
P1
Q1
P1
Plan
North
DEMO OF EXISTING SCANNER BY OTHERS.
DEMO SINK. REFER TO PLUMBING SHEETS FOR MORE INFO.
DEMO OF CONTROL EQUIPMENT BY OTHERS.
DEMO EXISTING RESILIENT SHEET FLOORING TO LIMITS SHOWN AND PREP SUB FLOOR FOR NEW
FLOORING.
DEMO EXISTING CASEWORK.
REMOVE EXISTING LINEN STORAGE UNIT AND RETURN TO MEDICAL CENTER.
DEMO EXISTING FLOOR MOUNTED FAN COIL UNIT. REFER TO MECHANICAL DRAWING FOR MORE
INFORMATION.
TEMPORARY INFECTION CONTROL BARRIER. WALL TYPE TO BE 3-5/8" METAL STUDS AT 16" O.C.
WITH ONE LAYER GYPSUM WALL BOARD ON EACH SIDE. TAPE AND MUD ONLY. PATCH, REPAIR
AND REPAINT EXISTING WALLS AFTER REMOVAL OF TEMPORARY WALL.
KEY NOTES:
SCALE: 1/4" = 1'-0"
1' 2' 4' 8' 16'0
DEMOLITION FLOOR PLAN
02/27/2019 MVP SD
AD101
DEMOLITION FLOOR PLAN
1E11A
TOILET
(STAFF)
1E09B
X-RAY B
1E07
DRAW STATION
1E09
TECH STATION
1E05
READING ROOM
1E08
X-RAY
1E10
X-RAY
1E13
X-RAY
1E15
LAB/OFFICE
1E00A
CORRIDOR
1EA
STAIR LEVEL
1EAA
ELECTRICAL
1EAD
AUX. SYSTEMS
1EAC
TEL/DATA
1EAB
ENTRY (UTILITIES)
1E16
LAB/OFFICE
1E14
LAB/OFFICE
1E12
LOUNGE
(NUCMED)
1E06
LAB
(NUCMED)
VEG 18.11
660-CSI-109
500 FOOTHILL DRIVE SALT LAKE CITY, UT 84148
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
F i l e
P a t h
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
321 4 5 6 7 8 9 10
Project Director
Issued: Date:
750 W HAMPDEN AVE.
SUITE #300
ENGLEWOOD, CO 80110
(720) 550-6307
WWW.VALHALLAENGINEERING.COM
CONSULTANTS: ARCHITECT/ENGINEERS: STAMP: CONSTRUCTION DOCUMENTS
(Contract Deliverable CD3-100%)
SPEC CT SITE PREP
3534A33A
True
North
KEY PLAN
EXISTING 2x4 FIXTURES TO REMAIN. PROTECT FROM DAMAGE AT ALL TIMES.
EXISTING CEILING GRID AND TILES TO REMAIN. PROTECT FROM DAMAGE AT ALL TIMES.
EXISTING MED GASES TO REMAIN. PROTECT FROM DAMAGE AT ALL TIMES.
EXISTING 2x4 FIXTURES TO BE RELOCATED. REMOVE AND REPLACE PER NEW REFLECTED
CEILING PLAN ON SHEET A-201. SEE ELECTRICAL AND LIGHTING PLAN FOR ADDITIONAL
INFORMATION.
EXISTING 2x2 CEILING TILE TO BE REMOVED AND REPLACED PER NEW REFLECTED CEILING PLAN.
PROTECT FROM DAMAGE AT ALL TIMES.
MODIFY EXISTING CEILING GRID AS REQUIRED FOR NEW LIGHTING CONFIGURATION.
KEY NOTES:
SCALE: 1/4" = 1'-0"
1' 2' 4' 8' 16'0
DEMOLITION REFLECTED CEILING PLAN
02/27/2019 MVP SD
AD201
DEMOLITION REFLECTED CEILING
PLAN
VEG 18.11
660-CSI-109
500 FOOTHILL DRIVE SALT LAKE CITY, UT 84148
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
F i l e
P a t h
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
321 4 5 6 7 8 9 10
Project Director
Issued: Date:
750 W HAMPDEN AVE.
SUITE #300
ENGLEWOOD, CO 80110
(720) 550-6307
WWW.VALHALLAENGINEERING.COM
CONSULTANTS: ARCHITECT/ENGINEERS: STAMP: CONSTRUCTION DOCUMENTS
(Contract Deliverable CD3-100%)
SPEC CT SITE PREP
True
North
1E11A
TOILET
(STAFF)
1E09B
X-RAY B
1E07
DRAW STATION
1E09
TECH STATION
1E05
READING ROOM
1E08
X-RAY
1E10
X-RAY
KEY PLAN
1E13
X-RAY
1E15
LAB/OFFICE
1E00A
CORRIDOR
1EA
STAIR LEVEL
1EAA
ELECTRICAL
1EAD
AUX. SYSTEMS
1EAC
TEL/DATA
1EAB
ENTRY (UTILITIES)
1E16
LAB/OFFICE
1E14
LAB/OFFICE
1E12
LOUNGE
(NUCMED)
1E06
LAB
(NUCMED)
34A 3533A
Plan
North
Q1
P1
A-101
A-101
Plan
North
NEW DROP-IN SINK. REFER TO PLUMBING FOR MORE INFORMATION.
LINE OF CEILING MOUNTED CURTAIN TRACK. CURTAIN BY VA.
TEMPORARY INFECTION CONTROL BARRIER. WALL TYPE TO BE 3-5/8" METAL STUDS AT 16" O.C.
WITH ONE LAYER GYPSUM WALL BOARD ON EACH SIDE. EXTEND WALL UP TO EXISTING CEILING.
TAPE AND MUD ONLY. PATCH, REPAIR AND REPAINT EXISTING WALLS AFTER REMOVAL OF
TEMPORARY WALL.
NEW SOLID SURFACE COUNTER TOP AND P-LAM BASE CABINETS. SEE DETAIL 2/A-101 FOR
ELEVATION. PROVIDE ONE 12" DIA. CUTOUT AND ONE 8" DIA. CUTOUT. PROVIDE STAINLESS
STEEL TRASH RING FOR EACH HOLE. HOLES TO BE CENTERED ON CABINET DOORS BELOW.
NEW CT SCANNER BY OTHERS.
PATCH AND REPAIR EXISTING GYPSUM WALL BOARD AS REQUIRED FROM MILLWORK DEMO. FINISH
FLUSH AND SMOOTH WITH ADJACENT WALL. REPAINT PER FLOOR AND WALL FINISH PLAN ON
SHEET A-301. PROVIDE NEW WALL BASE TO MATCH EXISTING.
SEAL EXISTING DOOR PER REQUIREMENTS OF SPECIFICATION SECTION 01 35 26 "SAFETY
REQUIREMENTS."
PATIENT LIFT AND TRACK ABOVE BY OTHERS.
PROVIDE CLASS 2 INFECTION CONTROL BARRIER.
KEY NOTES:
SCALE: 1/4" = 1'-0"
1' 2' 4' 8' 16'0
FLOOR PLAN
02/27/2019 MVP SD
A-101
FLOOR PLAN
VEG 18.11
660-CSI-109
500 FOOTHILL DRIVE SALT LAKE CITY, UT 84148
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
F i l e
P a t h
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
321 4 5 6 7 8 9 10
Project Director
Issued: Date:
750 W HAMPDEN AVE.
SUITE #300
ENGLEWOOD, CO 80110
(720) 550-6307
WWW.VALHALLAENGINEERING.COM
CONSULTANTS: ARCHITECT/ENGINEERS: STAMP: CONSTRUCTION DOCUMENTS
(Contract Deliverable CD3-100%)
SPEC CT SITE PREP
True
North
1E11A
TOILET
(STAFF)
1E09B
X-RAY B
1E07
DRAW STATION
1E09
TECH STATION
1E05
READING ROOM
1E08
X-RAY
1E10
X-RAY
KEY PLAN
1E13
X-RAY
1E15
LAB/OFFICE
1E00A
CORRIDOR
1EA
STAIR LEVEL
1EAA
ELECTRICAL
1EAD
AUX. SYSTEMS
1EAC
TEL/DATA
1EAB
ENTRY (UTILITIES)
1E16
LAB/OFFICE
1E12
LOUNGE
(NUCMED)
1E06
LAB
(NUCMED)
34A 35
DROP-IN SINK. SEE PLUMBING DRAWINGS
FOR MORE INFORMATION. 4" SOLID SURFACE BACKSPLASH
SOLD SURFACE COUNTER TOP
4" WIRE PULL (TYPICAL).
HIGH PRESSURE PLASTIC LAMINATE (TYPICAL)
4" TOE KICK
SCALE: 3/4" = 1'-0"
SCALE: 3/4" = 1'-0"
MILLWORK ELEVATION
FINISHED FLOOR
SOAP DISPENSER
PAPER TOWEL DISPENSER
2'-
4"
5"
7'-6"
CASEWORK SECTION
2x BLOCKING
AS REQUIRED
LINE OF EXISTING
WALL
SE
E
DE
TA
IL
2/A
-1
4"
2' 1"
CABINET LOCKS
FINISHED END PANELFINISHED END PANEL
LINE OF WALL BEYOND
W30 W30 W30
3"
PREFAB POLYSTYREIVE
TOE KICK MOULDING
Plan
North
EXISTING 2x2 CEILING TILE AND GRID TO REMAIN. PROTECT FROM DAMAGE AT ALL TIMES. REPLACE
ANY DAMAGED TILES IN KIND.
NEW CEILING MOUNTED CURTAIN TRACK.
NEW SUSPENDED PATIENT LIFT SYSTEM BY OTHERS.
EXISTING LIGHTING TO REMAIN. SEE ELECTRICAL DRAWINGS FOR MORE INFORMATION. PROTECT
FROM DAMAGE AT ALL TIMES.
TEMPORARY INFECTION CONTROL BARRIER. WALL TYPE TO BE 3-5/8" METAL STUDS AT 16" O.C.
WITH ONE LAYER GYPSUM WALL BOARD ON EACH SIDE. TAPE AND MUD ONLY. PATCH, REPAIR
AND REPAINT EXISTING WALLS AFTER REMOVAL OF TEMPORARY WALL.
EXISTING RELOCATED 2x4 LIGHT FIXTURES. MODIFY EXIST ING CEILING GRID AS REQUIRED TO RELOCATE LIGHT FIXTURE. REFER TO ELECTRICAL AND LIGHTING PLANS FOR MORE INFORMATION.
EXISTING RELOCATED 2x2 CEILING TILE.
NEW 2x4 LIGHT FIXTURE. MODIFY EXISTING CEILING GRID AS REQUIRED TO RELOCATE LIGHT
FIXTURE.
KEY NOTES:
SCALE: 1/4" = 1'-0"
1' 2' 4' 8' 16'0
REFLECTED CEILING FLOOR PLAN
02/27/2019 MVP SD
A-201
REFLECTED CEILING PLAN
True
North
VEG 18.11
660-CSI-109
500 FOOTHILL DRIVE SALT LAKE CITY, UT 84148
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
F i l e
P a t h
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
321 4 5 6 7 8 9 10
Project Director
Issued: Date:
750 W HAMPDEN AVE.
SUITE #300
ENGLEWOOD, CO 80110
(720) 550-6307
WWW.VALHALLAENGINEERING.COM
CONSULTANTS: ARCHITECT/ENGINEERS: STAMP: CONSTRUCTION DOCUMENTS
(Contract Deliverable CD3-100%)
SPEC CT SITE PREP
1E11A
TOILET
(STAFF)
1E09B
X-RAY B
1E07
DRAW STATION
1E09
TECH STATION
1E05
READING ROOM
1E08
X-RAY
1E10
X-RAY
KEY PLAN
1E13
X-RAY
1E15
LAB/OFFICE
1E00A
CORRIDOR 1EA
STAIR LEVEL
1EAD
AUX. SYSTEMS
1EAC
TEL/DATA
1EAB
ENTRY (UTILITIES)
1E16
LAB/OFFICE
1E14
LAB/OFFICE
1E12
LOUNGE
(NUCMED)
1E06
LAB
(NUCMED)
1EAA
ELECTRICAL
33A 3534A
Plan
North
NEW RESILIENT VINYL SHEET FLOORING. COLOR AND PATTERN TO MATCH EXISTING ACCENT
FLOORING IN ROOM #1E09A.
REPAIR EXISTING VINYL FLOORING WELDS THROUGHOUT ROOM THAT ARE FAILING. VERIFY
LOCATIONS WITH CONTRACTING OFFICER'S REPRESENTATIVE PRIOR TO WORK.
EXISTING SHEET VINYL FLOORING TO REMAIN. PROTECT FROM DAMAGE AT ALL TIMES.
PAINT ALL EXISTING WALLS WITH NEW PAINT. COLOR TO BE COORDINATED WITH VA INTERIOR
STAFF AND COR.
PROVIDE NEW RESILIENT VINYL SHEET FLOORING WITH INTEGRAL COVE BASE AT AREA OF
MILLWORK DEMO. FLOORING AND BASE TO MATCH EXISTING.
EAST WALL TO BE AN ACCENT PAITNED WALL. COLOR TO BE COORDINATED WITH VA INTERIOR
STAFF AND COR.
STAINLESS STEEL MOUNTING PLATE BY OTHERS.
KEY NOTES:
SCALE: 1/4" = 1'-0"
1' 2' 4' 8' 16'0
FLOOR AND WALL FINISH PLAN
02/27/2019 MVP SD
A-301
FLOOR AND WALL FINISH PLAN
VEG 18.11
660-CSI-109
500 FOOTHILL DRIVE SALT LAKE CITY, UT 84148
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
F i l e
P a t h
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
321 4 5 6 7 8 9 10
Project Director
Issued: Date:
750 W HAMPDEN AVE.
SUITE #300
ENGLEWOOD, CO 80110
(720) 550-6307
WWW.VALHALLAENGINEERING.COM
CONSULTANTS: ARCHITECT/ENGINEERS: STAMP: CONSTRUCTION DOCUMENTS
(Contract Deliverable CD3-100%)
SPEC CT SITE PREP
True
North
1E11A
TOILET
(STAFF)
1E09B
X-RAY B
1E07
DRAW STATION
1E09
TECH STATION
1E05
READING ROOM
1E08
X-RAY
1E10
X-RAY
+/- 12'-4" (V.I.F.)
- 7
V.
I.F .)2'-0" (V.I.F.)
KEY PLAN
1E13
X-RAY
1E15
LAB/OFFICE
1E00A
CORRIDOR 1EA
STAIR LEVEL
1EAD
AUX. SYSTEMS
1EAC
TEL/DATA
1EAB
ENTRY (UTILITIES)
1E16
LAB/OFFICE
1E14
LAB/OFFICE
1E12
LOUNGE
(NUCMED)
1E06
LAB
(NUCMED)
1EAA
ELECTRICAL
1E09A
X-RAY B
33A 3534A
'-1
1"
+/- 8"
6'-1"
2'- 0"
1'- 6"
3534a33a 3534a33a
P1
Q1
P1
DD02/27/2019
A. CONTRACTOR SHALL FIELD VERIFY AND PROVIDE ROUTING REQUIRED TO OFFSET AROUND
EXISTING FIELD CONDITIONS AND NEW WORK.
A. EXISTING CONDITIONS ARE SHOWN FOR GENERAL LOCATION ONLY. CONTRACTOR SHALL FIELD
VERIFY ACTUAL LOCATION AND ARRANGEMENT.
NEW P-528 SINK. CONNECT TO EXISTING UTILITIES. BASIS OF DESIGN: ELKAY SS 19-1/2" X 19" X 10-1/8" SINK WITH 3 X 1-1/2" DIAMETER FAUCET HOLES ON 4", WRIST BLADE HANDLES, AND
GOOSENECK FAUCET PER SPECIFICATIONS.
GENERAL NOTES:
GENERAL NOTES - DEMOLITION:
KEY NOTES:
MR
PLUMBING PLANS
P-101
VEG 18.11
660-CSI-109
500 FOOTHILL DRIVE SALT LAKE CITY, UT 84148
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
F i l e
P a t h
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
321 4 5 6 7 8 9 10
Project Director
Issued: Date:
750 W HAMPDEN AVE.
SUITE #300
ENGLEWOOD, CO 80110
(720) 550-6307
WWW.VALHALLAENGINEERING.COM
CONSULTANTS: ARCHITECT/ENGINEERS: STAMP: CONSTRUCTION DOCUMENTS
(Contract Deliverable CD3-100%)
SPEC CT SITE PREP
Plan
North
SCALE: 1/4" = 1'-0"
1' 2' 4' 8' 16'0
PLUMBING PLAN
1E11A
TOILET
(STAFF)
1E09B
X-RAY B
1E07
DRAW STATION
1E09
TECH STATION
1E05
READING ROOM
1E08
X-RAY
1E10
X-RAY
Plan
North
1E11A
TOILET
(STAFF)
1E09B
X-RAY B
1E07
DRAW STATION
1E09
TECH STATION
1E05
READING ROOM
1E08
X-RAY
1E10
X-RAY
Plan
North
SCALE: 1/4" = 1'-0"
1' 2' 4' 8' 16'0
PLUMBING DEMO PLAN
DEMO WALL-MOUNTED SINK. UTILITIES TO REMAIN FOR FUTURE SINK CONNECTION.
DEMOLITION KEY NOTES:
True
KEY PLAN
02/27/2019 DD MR
M-001
MECHANICAL ABBREVIATIONS AND
GENERAL NOTES
HVAC GENERAL NOTES
MECHANICAL ABBREVIATIONS
SR SUPPLY AIR REGISTER
SS STAINLESS STEEL
SSHX STEAM TO STEAM HEAT EXCHANGER
SSR SOLID SEPARATOR
ST STEAM TRAP
SUH STEAM UNIT HEATER
SV STEAM PRESSURE REDUCING VALVE
SVS STEAM VENT SILENCER
SWHX STEAM TO WATER HEAT EXCHANGER
T&PCV TEMPERATURE AND PRESSURE CONTROL
VALVE
TAB TESTING, ADJUSTING, AND BALANCING
TD TEMPERATURE DIFFERENCE
TDH TOTAL DYNAMIC HEAD
TDS TOTAL DISSOLVED SOLIDS
TG TRANSFER GRILLE
TP TRAP
TR TOP REGISTER
TSP TOTAL STATIC PRESSURE
TSTAT THERMOSTAT
TU TERMINAL UNIT
TWU THRU-WALL UNIT
UC UNDERCUT
UC UNIT COOLER
UH UNIT HEATER
UL UNDERWRITER'S LABORATORY
URV UPBLAST UNIT VENTILATOR
V VALVE
VAF VANE-AXIAL FAN
VAV VARIABLE AIR VOLUME
VD VOLUME DAMPER (MANUAL OPPOSED BLADE)
VFD VARIABLE FREQUENCY DRIVE
VHA VETERANS HEALTH ADMINISTRATION
VI VIBRATION ISOLATOR
VIV VARIABLE INLET VANES
VP VACUUM PUMP
VPS VARIABLE PRIMARY SYSTEM
VR VACUUM (STEAM CONDENSATE) RETURN
VSD VARIABLE SPEED DRIVE
VUH VERTICAL UNIT HEATER
W WASTE
WAG WASTE ANESTHESIA GAS
WB WET BULB
WC WATER COOLED
WCCH WATER COOLED CHILLER
WCCU WATER COOLED CONDENSING UNIT
WCPU WATER COOLED HEAT PUMPS
WEF WATER COOLED PACKAGED UNIT
WF WATER FILTER
WFCV WATER FLOW CONTROL VALVE
WFM WATER FLOWMETER
WFMD WATER FLOW MEASURING DEVICE
WG WATER GAGE
WPD WATER SIDE PRESSURE DROP
YR YEAR
OFM OIL FLOWMETER
OR OPERATING ROOM
P PUMP
PA PASCAL
PC PUMPED CONDENSATE
PCF POUNDS PER CUBIC FOOT
PD PRESSURE DROP
PEF PROPELLER TYPE EXHAUST FAN
PF PRE-FILTER
PG PRESSURE GAUGE
PGW PROPYLENE GLYCOL-WATER SOLUTION
PHC PREHEAT COIL
PPM PARTS PER MILLION
PRS PRESSURE REGULATING VALVE STATION
PRV PRESSURE REGULATING VALVE
PSI POUNDS PER SQUARE INCH
PSIA POUNDS PER SQUARE INCH, ABSOLUTE
PSIG POUNDS PER SQUARE INCH, GAGE
PSS PRIMARY SECONDARY SYSTEM
PSV PRESSURE SAFETY VALVE
PTAC PACKAGED TERMINAL AIR CONDITIONER
R/E RETURN OR EXHAUST
RA RETURN AIR
RAD REFRIGERANT AIR DRYER
RAF RADIO FREQUENCY
RAHX ROTARY AIR HEAT EXCHANGER
RAT RETURN AIR TEMPERATURE
RCCH REMOTE CONDENSER CHILLER
RCU RECIPROCATING CHILLER UNIT
RD REFRIGERANT DISCHARGE
RDS ROOM DATA SHEETS
REA RELIEF AIR
RF RETURN FAN
RG RETURN GRILLE
RH RELATIVE HUMIDITY
RHC REHEAT COIL
RHG REFRIGERANT HOT GAS
RL REFRIGERANT LIQUID LINE
RLA RUN LOAD AMPERE
RO REVERSE OSMOSIS
RPM REVOLUTIONS PER MINUTE
RR RETURN REGISTER
RS REFRIGERANT SUCTION
RTU ROOFTOP UNIT
RV RELIEF VALVE
SA SUPPLY AIR
SAD SOUND ATTENUATING DEVICE
SAT SUPPLY AIR TEMPERATURE
SC SHADING COEFFICIENT
SCFM SPINAL CODE INJURY
SCR SILICON CONTROLLED RECTIFIER
SD SMOKE DETECTOR
SD SUPPLY AIR DIFFUSER
SD-1 SCHEMATIC DESIGN SUBMISSION 1
SD-2 SCHEMATIC DESIGN SUBMISSION 2
SDPR SMOKE DAMPER
SDR SMOKE DAMPER (RETURN)
SDS SMOKE DAMPER (SUPPLY)
SEN SENSIBLE HEAT
SF SUPPLY FAN
SG SUPPLY AIR GRILLE
SH STEAM HUMIDIFIER
SHC STEAM HEATING COIL
SI SQUARE INCHES
SP STATIC PRESSURE
SP GR SPECIFIC GRAVITY
SPD SUPPLY PROCESS AND DISTRIBUTION
SPRV STEAM PRESSURE REDUCING VALVE
SPS STATIC PRESSURE SENSOR
SQ FT SQUARE FOOT
IRH INFRARED HEATER
IS INSECT SCREEN
IU INDUCTION UNIT
IV INLET VANES
KG KILOGRAM
KG/H KILOGRAMS PER HOUR
KPA KILOPASCAL
KW KILOWATT
KWH KILOWATT HOURS
L LITER
L/H LITERS PER HOUR
L/M LITERS PER MINUTE
L/S LITERS PER SECOND
LAT LEAVING AIR TEMPERATURE
LB/H POUND PER HOUR
LF LINEAR FOOT (FEET)
LGT LEAVING GLYCOL TEMPERATURE
LH LATENT HEAT
LLHX LIQUID TO LIQUID HEAT EXCHANGER
LPG LIQUID PROPANE GAS
LPR LOW PRESSURE RETURN (STEAM
CONDENSATE)
LPRC LOW PRESSURE STEAM RETURN (CLEAN)
LPS LOW PRESSURE STEAM
LPSC LOW PRESSURE STEAM (CLEAN)
LSD LINEAR SLOT DIFFUSER
LTCP LOCAL TEMPERATURE CONTROL PANEL
LVG LEAVING
LVR LOUVER
LWT LEAVING WATER TEMPERATURE
M METER
M/S METERS PER SECOND
MA MIXED AIR
MAT MIXED AIR TEMPERATURE
MAU MAKE-UP AIR UNIT
MAV MANUAL AIR VENT
MAX MAXIMUM
MB MIXING BOX
MBH 1000 BTUH
MCA MINIMUM BRANCH CIRCUIT AMPACITY
MER MECHANICAL EQUIPMENT ROOM
MERV MINIMUM EFFICIENCY REPORTING VALUE
MH MANHOLE
MHP MOTOR HORSEPOWER
MIN MINIMUM
MM MILLIMETER
MOV MOTOR OPERATED VALVE
MPR MEDIUM PRESSURE RETURN (STEAM
CONDENSATE)
MPS MEDIUM PRESSURE STEAM
MRI MAGNETIC RESONANCE IMAGING UNIT
MTD MEAN TEMPERATURE DIFFERENCE
MVD MANUAL VOLUME DAMPER
MZ MULTI-ZONE
NA NOT APPLICABLE
NC NOISE CRITERIA
NC NORMALLY CLOSED
NG NATURAL GAS
NGFM NATURAL GAS FLOW METER
NO NORMALLY OPEN
NOAA NATIONAL OCEANIC & ATMOSPHERIC
ADMINISTRATION
NOM NOMINAL
NPLV NON-STANDARD PART LOAD VALUE
NPSH NET POSITIVE SUCTION HEAD
NTS NOT TO SCALE
OA OUTSIDE AIR
OAG OUTSIDE AIR GRILLE
OAI OUTSIDE AIR INTAKE
OD OUTER DIAMETER
FF FINAL FILTER
FHX FLUE GAS/FEEDWATER HEAT EXCHANGER
FM FLOW METER
FOHX FUEL OIL HEAT EXCHANGER
FOP FUEL OIL PUMP
FOT FUEL OIL TANK
FPM FEET PER MINUTE
FPS FEET PER SECOND
FPTU FAN POWERED TERMINAL UNIT
FR FLOOR REGISTER
FRP FIBER REINFORCED POLYESTER
FS FLOW SWITCH
FSTAT FREEZESTAT
FT FEET
FT-LB FOOT-POUND
FTR FINNED TUBE RADIATION
FV FACE VELOCITY
GA GAUGE
GAL GALLONS
GH GRAVITY HOOD
GPD GALLONS PER DAY
GPH GALLONS PER HOUR
GPM GALLONS PER MINUTE
GPR GAS PRESSURE REGULATOR
GS GALVANIZED STEEL
H HUMIDIFIER
H&CW HOT & COLD WATER
HAC HOUSEKEEPING AID CLOSET
HB HOSE BIBB
HC HEATING COIL
HD HEAD
HD HOOD
HOA HAND/OFF/AUTOMATIC
HP HEAT PUMP
HP HORSEPOWER
HPDT HIGH PRESSURE DRIP TRAP
HPR HIGH PRESSURE RETURN (STEAM
CONDENSATE)
HPS HIGH PRESSURE SUPPLY (STEAM)
HRC HEAT RECOVERY COIL
HRD HEAT RECOVERY DEVICE
HRP HYDRONIC RADIANT (CEILING) PANEL
HRW HEAT RECOVERY WHEEL
HSTAT HUMIDISTAT
HTM HUMIDIFIER TERMINAL
HUM HUMIDIFIER UNIT MOUNTED
HVD HOISTWAY VENT DAMPER
HVU HEATING AND VENTILATING UNIT
HW HOT WATER
HWC HOT WATER COIL
HWHC HOT WATER HEATING COIL
HWP HEATING WATER PUMP
HWR HEATING WATER RETURN
HWS HEATING WATER SUPPLY
HWUH HOT WATER UNIT HEATER
HX HEAT EXCHANGER
HZ HERTZ
I/O INPUT/OUTPUT
IAQ INDOOR AIR QUALITY
IBT INVERTED BUCKET TRAP
ICF IN-LINE CENTRIFUGAL FAN
ICU INTENSIVE CARE UNIT
ID INSIDE DIAMETER
IFB INTEGRAL FACE AND BYPASS
IN INCHES
IN HG INCHES OF MERCURY
IN WC INCHES OF WATER COLUMN
IN WG INCHES OF WATER, GAUGE
IN-LB INCH-POUND
IPLV INTEGRATED PART LOAD VALUE
CP CONDENSATE PUMP
CR CEILING REGISTER
CS CONDENSATE STORAGE TANK
CSG CLEAN STEAM GENERATOR
CT COOLING TOWER
CU CONDENSING UNIT
CUH CABINET UNIT HEATER
CV CONSTANT VOLUME
CW COLD WATER (POTABLE)
CWCC CHILLED WATER COOLING COIL
CWP CONDENSER WATER PUMP
CWR CONDENSER WATER RETURN (TO COOLING
TOWER)
CWS CONDENSER WATER SUPPLY (FROM COOLING
TOWER)
D DAMPER - AUTOMATIC
D-1 OUTDOOR AIR DAMPER
D-2 RETURN AIR DAMPER
D-3 RELIEF AIR DAMPER
Db DRY BULB TEMPERATURE dB DECIBEL
DD-1 DESIGN DEVELOPMENT SUBMISSION 1
DD-2 DESIGN DEVELOPMENT SUBMISSION 2
DDC DIRECT DIGITAL CONTROLS
DEG DEGREES
DF DIFFUSER
DIA DIAMETER
DIW DEIONIZED WATER
DP DEW POINT TEMPERATURE
DP DIFFUSER PLATE
DPA DIFFERENTIAL PRESSURE ASSEMBLY
DPS DIFFERENTIAL PRESSURE SENSOR
DX DIRECT EXPANSION
DXCC DIRECT EXPANSION COOLING COIL
EA EXHAUST AIR
EAT ENTERING AIR TEMPERATURE
EC EVAPORATIVE COOLER
ECC ENGINEERING CONTROL CENTER
ECU EVAPORATIVE CONDENSER UNIT
EDH ELECTRIC DUCT HEATER
EER ENERGY EFFICIENCY RATIO
EF EXHAUST FAN
EG EXHAUST GRILLE
EGS EMERGENCY GAS SHUTOFF
EGT ENTERING GLYCOL TEMPERATURE
EH EXHAUST HOOD
EJ EXPANSION JOINT
EMD END OF MAIN DRIP (STEAM)
ENT ENTERING
ER EXHAUST REGISTER
ERC ELECTRIC REHEAT COIL
ERP ELECTRIC RADIANT PANEL
ESP EXTERNAL STATIC PRESSURE
ET EXPANSION TANK
ETO ETHYLENE OXIDE
EUH ELECTRIC UNIT HEATER
EWC EVAPORATIVE WATER COOLER
EWT ENTERING WATER TEMPERATURE
EX. EXISTING
F FAHRENHEIT
F&T FLOAT AND THERMOSTATIC
F/SDPR COMBINATION FIRE SMOKE DAMPER
FA FREE AREA
FC FLEXIBLE CONNECTION
FCU FAN COIL UNIT (4 PIPE)
FCUC FAN COIL UNIT COOLING ONLY
FCUH FAN COIL UNIT HEATING ONLY
FCW FORWARD CURVED WHEEL (FAN)
FD FLOOR DRAIN
FD FIRE DAMPER
A/E ARCHITECT / ENGINEER
AAHX AIR TO AIR HEAT EXCHANGER
AAV AUTOMATIC AIR VENT
AB AIR BLENDER
ACC AIR COOLED CONDENSER
ACCH AIR COOLED CHILLER
ACCU AIR-COOLED CONDENSING UNIT
ACD AUTOMATIC CONTROL DAMPER, MODULATING
ACD-TP AUTOMATIC CONTROL DAMPER, TWO
POSITION
ACFM ACTUAL CUBIC FEET PER MINUTE
ACU AIR CONDITIONING UNIT
AD ACCESS DOOR
AF AFTER FILTER
AFCV AIR FLOW CONTROL VALVE
AFF ABOVE FINISHED FLOOR
AFMD AIR FLOW MEASURING DEVICE
AFW AIR FOIL WHEEL (FAN)
AHU AIR HANDLING UNIT
AMP AMPERE
AP ACCESS PANEL
APD AIR PRESSURE DROP
ARI AIR CONDITIONING AND REFRIGERATION
INSTITUTE
AS AIR SEPARATOR
ASME AMERICAN SOCIETY OF MECHANICAL
ENGINEERS
AW AIR WASHER
AXF AXIAL FLOW
B BOILER
BD BUTTERFLY DAMPER
BDD BACKDRAFT DAMPER
BDR BASE BOARD RADIATOR
BFP BACKFLOW PREVENTER
BFT BOILER PLANT FIRE TUBE
BG BOTTOM GRILLE
BHP BRAKE HORSEPOWER
BHW HOT WATER HEATING BOILER
BHX BOILER BLOWDOWN HEAT EXCHANGER
BIW BACKWARD INCLINED WHEEN (FAN)
BR BONE REGISTER
BSC BIOLOGICAL SAFETY CABINETS
BT BLOWOFF TANK
BTC BLOWOFF TANK CONTROL VALVE
BTU BRITISH THERMAL UNIT
BTUH BRITISH THERMAL UNIT PER HOUR
BWT BOILER PLANT WATER TUBE
C CENTIGRADE (CELSIUS)
CC COOLING COIL
CCD COOLING COIL CONDENSATE DRAIN
CD CEILING DIFFUSER
CD-1 CONSTRUCTION DOCUMENTS (SUBMISSION 1)
CD-2 CONSTRUCTION DOCUMENTS (SUBMISSION 2)
CENT CENTRIFUGAL
CFH CUBIC FEET PER HOUR
CFM CUBIC FEET PER MINUTE
CFP CHEMICAL FEED PUMP
CFT CEILING GRILLE
CG CEILING GRILLE
CH CHILLER
CHP CHILLED WATER PUMP
CHR CHILLED WATER RETURN
CHS CHILLED WATER SUPPLY
CHW CHILLED WATER
CI CAST IRON
CM CARBON MONOXIDE
CM CUBIC METER
CO2 CARBON DIOXIDE
COMP COMPRESSOR UNIT
COP COEFFICIENT OF PERFORMANCE
1. CONTRACTOR SHALL PROVIDE AN INFECTION CONTROL RISK ASSESSMENT BARRIER AROUND
THE PROJECT AREA CONSISTENT WITH THE CONTRACTOR'S PHASING PLAN AS APPROVED BY
THE VA.
BAS BUILDING AUTOMATION SYSTEMS
1. ALL PIPING AND DUCTS IN FINISHED ROOMS OR SPACES SHALL BE CONCEALED IN A
FURRED CHASE OR ABOVE THE HARD SUSPENDED CEILING.
2. THE FIRST FIGURE OF DUCT SIZE INDICATES DIMENSION OF FACE SHOWN OR
INDICATED. DUCT SIZES ARE NET INSIDE DIMENSIONS.
3. ACCESS PANELS IN HARD SUSPENDED CEILINGS ARE REQUIRED FOR ALL VALVES,
TRAPS, DAMPERS, CLEANOUTS, CONTROLS, ETC. ACCESS PANELS SHALL BE
FURNISHED AND INSTALLED UNDER THE ARCHITECTURAL SPECIFICATIONS.
4. TOTAL STATIC PRESSURE NOTED IN THE SCHEDULES INCLUDES DUCT SYSTEM,
TERMINAL UNITS, FILTERS, COILS, ETC.
5. FOR TYPICAL STEAM AND WATER PIPING CONNECTIONS TO EQUIPMENT, SEE
EQUIPMENT DETAILS.
6. DIFFUSER, REGISTER AND GRILLE SIZES SHOWN ON FLOOR PLANS ARE NECK SIZES.
7. WATER PIPE CONNECTIONS TO AIR HEATING AND COOLING COILS SHALL BE MADE
TO PROVIDE COUNTER FLOW BETWEEN WATER AND AIR.
8. WALL TYPE EXHAUST REGISTERS NOTED AS "BR" ON DRAWINGS ARE TO BE
INSTALLED WITH BOTTOM ELEVATION OF REGISTER AT 7" ABOVE FINISHED FLOOR.
9. ALL PRESSURES LISTED ARE GAGE PRESSURE UNLESS NOTED OTHERWISE
10. ALL CONTROL SYSTEM EQUIPMENT SHALL BE COMPATIBLE WITH EXISTING
BUILDING MANAGEMENT SYSTEM CONTROLS. EXTEND EXISTING CONTROL SYSTEM
TO INCLUDE ALL OF THE CONTROLS AND SEQUENCES SHOWN.
11. COORDINATE EXISTING FIRE SPRINKLER HEADS AND LIGHTS WITH DIFFUSERS.
GENERAL NOTES
VEG 18.11
660-CSI-109
500 FOOTHILL DRIVE SALT LAKE CITY, UT 84148
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
F i l e
P a t h
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
321 4 5 6 7 8 9 10
Project Director
Issued: Date:
750 W HAMPDEN AVE.
SUITE #300
ENGLEWOOD, CO 80110
(720) 550-6307
WWW.VALHALLAENGINEERING.COM
CONSULTANTS: ARCHITECT/ENGINEERS: STAMP: CONSTRUCTION DOCUMENTS
(Contract Deliverable CD3-100%)
SPEC CT SITE PREP
CONTROLS SYMBOLS
DRAWING SYMBOLS
DUCTWORK SYMBOLS GENERAL PIPING SYMBOLS HVAC PIPING SYMBOLS
VALVE SYMBOLS TERMINAL UNIT SYMBOLS
AIR TERMINAL SYMBOLS
2'x4' RADIANT CEILING PANEL
2'x2' RADIANT CEILING PANEL
AIR CURTAIN
A
PTAC
A
TWU
THRU WALL AIR CONDITIONING UNIT.
LETTER INDICATES UNIT SIZE.
WINDOW TYPE AIR CONDITIONING UNIT.
LETTER INDICATES UNIT SIZE.
UNIT HEATER (VERTICAL)
UNIT HEATER (HORIZONTAL)
CONVECTOR OR RADIATOR (RECESSED)
FLOOR MOUNTED VERTICAL CABINET FAN
COIL UNIT. LETTER INDICATES UNIT SIZE.
FLOOR MOUNTED VERTICAL RECESSED
FAN COIL UNIT. LETTER INDICATES UNIT
SIZE.
CONVECTOR OR RADIATOR (WALL HUNG)
A
FCU
FCU
A
FLOOR MOUNTED HEAT PUMP. LETTER
INDICATES UNIT SIZE.
PTAC
A
GATE VALVE WITH GLOBE-VALVED BYPASS
PLUG VALVE
CONTROL VALVE (CV) - FLOAT-OPERATED
PRESSURE REDUCING VALVE (PRV)
HOSE CONNECTOR
WYE STRAINER WITH VALVED DRAIN AND QUICK-COUPLE
WATER LEVEL CONTROLLER
FLOW METER
LC
M
BALL VALVE
GATE VALVE WITH 3/4" HOSE ADAPTER
CHECK VALVE
ANGLE GLOBE VALVE
BUTTERFLY VALVE
MODULATING CONTROL VALVE
TWO POSITION CONTROL VALVE
THREE-WAY MODULATING CONTROL VALVE
AUTOMATIC BALANCING CONTROL VALVE
PRESSURE SAFETY VALVE
GATE VALVE - THREADED/FLANGED
GLOBE VALVE - THREADED/FLANGED
PRESSURE REGULATING VALVE
THREE-WAY TWO POSITION CONTROL VALVE
WYE STRAINER (WITH BALL VALVE & HOSE CONNECTION)
FLEXIBLE CONNECTION
WATER BALANCE DEVICE
MODULATING CONTROL BUTTERFLY VALVE
CIRCUIT SETTER VALVE
FEEDWATER SAMPLE (FROM DEAERATOR)
BOILER WATER SAMPLE
CONTINUOUS BLOWDOWN
CHEMICAL FEED
BOILER BLOWOFF
TUBE CLEANER WATER SUPPLY
COMPRESSED AIR
OVERFLOW
COLD WATER (CITY WATER)
LIQUEFIED PETROLEUM GAS IGNITER FUEL
NATURAL GAS IGNITER FUEL
NATURAL GAS MAIN FUEL
HOT WATER
SOFTENED WATER
FUEL OIL RETURN
FUEL OIL SUPPLY
RH
SCH
SH
TH
PS
RC
RISER CLAMP (TYPE 42)*
FLOOR-SUPPORTED PIPE STAND
CLEVIS-TYPE HANGER
VARIABLE SPRING-TYPE HANGER (TYPE 51)*
ROLLER-TYPE HANGER
TO TRAPEZE EXCEPT WHERE RH ARE INDICATED)
TRAPEZE HANGER (PROVIDE U-BOLT PIPE ATTACHMENT
SPRING CUSHION-TYPE HANGER (TYPE 48 OR 49)*
WB
CSH
SS
SLIDING SUPPORTS (TYPE 35)*
CONSTANT SUPPORT HANGER (TYPE 54, 55, 56)*
WALL BRACKET (TYPE 31, 32, 33)*
* TYPE NUMBERS REFER TO MANUFACTURER'S STANDARDIZATION SOCIETYSTANDARD PRACTICE SP-58
VACUUM CONDENSATE RETURN
CONDENSATE TRANSFER PUMP SUCTION
CONDENSATE TRANSFER PUMP DISCHARGE
FEEDWATER PUMP DISCHARGE
FEEDWATER PUMP SUCTION
VR
CTPS
CTPD
FWPS
FWPD
CF
FWS
BWS
CBD
BO
TC
A
OFL
HW
SW
CW
FOR
FOS
LPG(I)
G(I)
G
HIGH PRESSURE STEAM CONDENSATE RETURN
HIGH PRESSURE STEAM (60 PSIG AND ABOVE)
HEATING WATER SUPPLY
CONDENSATE PUMP DISCHARGE
LOW PRESSURE STEAM CONDENSATE RETURN
LOW PRESSURE STEAM (15 PSIG AND BELOW)
MEDIUM PRESSURE STEAM CONDENSATE RETURN
MEDIUM PRESSURE STEAM (16 PSIG THRU 59 PSIG)
VENT LINE
SOLAR WATER RETURN
SOLAR WATER SUPPLY
GLYCOL-WATER HEATING RETURN
GLYCOL-WATER HEATING SUPPLY
REFRIGERANT SUCTION
REFRIGERANT HOT GAS
REFRIGERANT LIQUID
CHILLED WATER SUPPLY
CHILLED WATER RETURN
DRAIN LINE
MAKE-UP WATER
CONDENSER WATER RETURN (TO TOWER)
CHILLED GLYCOL-WATER RETURN
CHILLED GLYCOL-WATER SUPPLY
CONDENSER WATER SUPPLY (FROM TOWER)
HEATING WATER RETURN
HPS
HPR
MPS
MPR
LPS
LPR
PC
HWS
HWR
GHS
GHR
V
SWS
SWR
CWR
CHR
GCR
RL
RS
RHG
CWS
CHS
GCS
MW
D
GLYCOL-WATER RUN AROUND SUPPLY
GLYCOL-WATER RUN AROUND RETURNGRR
GRS
X EXISTING PIPE TO BE REMOVED
QUICK-COUPLE HOSE CONNECTOR
ANCHOR
REDUCER OR INCREASER
DIRECTION OF FLOW
SIDE CONNECTION
ECCENTRIC REDUCER
BOTTOM CONNECTION, 45° OR 90°
TOP CONNECTION, 45° OR 90°
DIRECTION OF PIPE PITCH (DOWN)
UNION
RISE OR DROP IN PIPE
CAPPED OUTLET
PRESSURE GAGE
THERMOMETER
FLOW ELEMENT
FLOAT & THERMOSTATIC TRAP SET INCLUDING
PIPING ACCESSORIES SEE DETAIL
INVERTED BUCKET TRAP SET INCLUDING
PIPING ACCESSORIES SEE DETAIL
FE
PIPE UP
PIPE DOWN
REFRIGERANT SIGHT GLASS
TEST PLUG (PRESSURE/TEMPERATURE)
AUTOMATIC AIR VENT
AV
MANUAL AIR VENTMV
THERMOSTATIC TRAP SET INCLUDING
PIPING ACCESSORIES SEE DETAIL
LIMIT OF DEMOLITION
(WALL TYPE)
DN
DN
UP
UP
SUPPLY DUCT (UP & DOWN)
EXHAUST DUCT (UP & DOWN)
ROUND AND SQUARE 4-WAY CEILING DIFFUSERS
SUPPLY TOP REGISTER OR GRILLE (WALL TYPE)
EXHAUST OR RETURN CEILING
REGISTER OR GRILLE
EXHAUST OR RETURN BOTTOM
REGISTER OR GRILLE (WALL TYPE)
EXHAUST OR RETURN REGISTER OR TOP GRILLE
VANED ELBOW & AIR SPLIT TYPE DUCT TAKE-OFF
CONNECT NEW DUCT TO EXISTING DUCT
D
INCLINED RISE, IN DIRECTION OF AIR FLOW
INCLINED DROP, IN DIRECTION OF AIR FLOW
R
DNUP
RETURN DUCT (UP & DOWN)
SQUARE 3-WAY CEILING DIFFUSERS
SQUARE 2-WAY CEILING DIFFUSERS
LINEAR SLOT DIFFUSER
SQUARE 1-WAY CEILING DIFFUSERS
BACK DRAFT DAMPER
BDD
FC
10x8
FLEXIBLE CONNECTION, EQUIPMENT, VIBRATION,
OR SEISMIC
VANED ELBOW (PROVIDE ALL SQUARE OR
RECTANGULAR ELBOWS WITH VANES EVEN IF
SYMBOL IS MISSING)
VANED ELBOW (SHORT RADIUS)
STANDARD RADIUS ELBOW (LONG RADIUS)
NEW DUCT (INSIDE DIMENSIONS: WIDTH x DEPTH)
EXISTING DUCT TO REMAIN
LOUVER (LOUVER SPECIFIED IN ARCHITECTURAL
SECTION.)
FIRE DAMPER
FD
VD
DUCT WITH SOUND LINING
FLEXIBLE DUCTWORK (INSULATED)
MANUAL VOLUME DAMPER
EXISTING DUCT TO BE REMOVED
DUCT MOUNTED COIL (ELECTRIC)
DUCT MOUNTED COIL (HOT WATER OR STEAM
COIL)
SUPPLY
RETURN
45°
STANDARD BRANCH SUPPLY OR RETURN, NO
SPLITTER (45° TAP)
MANUAL SPLITTER DAMPER
45°
N
2 1
POINT OF CHANGE IN DUCT CONSTRUCTION BY
STATIC PRESSURE CLASS. THE NUMBER ASSIGNS
PRESSURE CLASS (IN. OF WATER) WHICH WILL
ACCOMMODATE MAXIMUM OPERATING PRESSURE
IN THE DUCT SUBSECTION. THE SYMBOL CONTINUES
THE ASSIGNMENT UNTIL THE DUCT TERMINATES OR
ANOTHER SYMBOL APPEARS. A "N" SUPERSCRIPT
INDICATES NEGATIVE PRESSURE.
COMBINATION FIRE/SMOKE DAMPER
1/2
STAINLESS STEEL DUCT
F/S DPR
AUTOMATIC CONTROL DAMPER MODULATING
AUTOMATIC CONTROL DAMPER TWO POSITION
FAN POWERED VARIABLE VOLUME
TERMINAL UNIT WITH HEATING COIL.
MB
DOUBLE DUCT MIXING BOX.
TERMINAL UNIT WITH REHEAT COIL
26-SF 3
26-TU-I-I
DETAIL NUMBER
DRAWING NUMBER WHERE SHOWN
SECTION LETTER
TYPICAL UNIT NO.
BUILDING NO. WHERE EQUIPMENT IS LOCATED.
SUPPLY FAN NO. 3 IN BUILDING NO. 26
EQUIPMENT ABBREVIATION (SUPPLY FAN)
ITEM NUMBER (TERMINAL UNIT NO. 1)
ITEM (TERMINAL UNIT SHOWN)
SERVED BY AIR HANDLER UNIT NO. 1
DRAWING NUMBER WHERE DRAWN
BUILDING NO. WHERE EQUIPMENT IS LOCATED
H4
H7
A
T ROOM THERMOSTAT/TRANSMITTER - WALL MOUNT
TT TEMPERATURE TRANSMITTER
M
ROOM HUMIDISTAT (MOISTURE)/TRANSMITTER - WALL
MOUNT
MT MOISTURE (HUMIDITY) TRANSMITTER
PT PRESSURE TRANSMITTER
TT TEMPERATURE TRANSMITTER, AVERAGING ELEMENT
FT FLOW TRANSMITTER
IT CURRENT TRANSMITTER
CT CONDUCTIVITY TRANSMITTER
SPS STATIC PRESSURE SENSOR
SD SMOKE DETECTOR
PDT PRESSURE DIFFERENTIAL TRANSMITTER
KR LOCAL RECORDING TIME CLOCK (RUNTIME)
TSL TEMPERATURE SWITCH, LOW (FREEZESTAT)
HS HAND SWITCH (HAND-OFF-AUTO SWITCH)
ZC VALVE OR DAMPER POSITION CONTROLLER
LC LEVEL CONTROLLER
LT LEVEL TRANSMITTER
PDS PRESSURE DIFFERENTIAL SWITCH
TSH TEMPERATURE SWITCH, HIGH (FREEZESTAT)
EPT ELECTRONIC TO PNEUMATIC TRANSDUCER
AT CARBON DIOXIDE TRANSMITTER
CARBON MONOXIDE TRANSMITTER
CO2
AT
CO
OCCUPANCY SENSORAT
OC
LTCP LOCAL TEMPERATURE CONTROL PANEL
HVAC HVAC CONTROL PANEL
ECC
INTEGRATE CONTROL POINT ON REMOTE
GRAPHICS WORKSTATION AT ENERGY
CONTROL CENTER
TC
TEMPERATURE CONTROLLER. SEE
SEQUENCE OF OPERATION
VSMC VARIABLE SPEED MOTOR CONTROLLER
PC
PRESSURE CONTROLLER. SEE SEQUENCE
OF OPERATION
SC
SPEED CONTROLLER. SEE SEQUENCE OF
OPERATION
FC
FLOW CONTROLLER. SEE SEQUENCE OF
OPERATION
PSH PRESSURE SWITCH HIGH
FSH FLOW SWITCH HIGH
PSL PRESSURE SWITCH LOW
KC
TIME CLOCK CONTROLLING EQUIPMENT ON
A SCHEDULE
FSL FLOW SWITCH LOW
A
TEMPERATURE SENSING ELEMENT FOR
TRANSMITTING TEMPERATURE TO EMCS
(PROVIDE 12 INCHES MINIMUM
LENGTH IN DUCT WHEN SPACE PERMITS.)
SENSOR WITH AVERAGING ELEMENT
TO TRANSMIT TEMPERATURE TO EMCS
MOTOR STARTER
M
ELECTRIC OPERATED CONTROL
DAMPER/OR VALVE
BAS BUILDING AUTOMATION SYSTEM
02/27/2019 DD MR
M-002
MECHANICAL SYMBOLS AND
LEGENDS
VEG 18.11
660-CSI-109
500 FOOTHILL DRIVE SALT LAKE CITY, UT 84148
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
F i l e
P a t h
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
321 4 5 6 7 8 9 10
Project Director
Issued: Date:
750 W HAMPDEN AVE.
SUITE #300
ENGLEWOOD, CO 80110
(720) 550-6307
WWW.VALHALLAENGINEERING.COM
CONSULTANTS: ARCHITECT/ENGINEERS: STAMP: CONSTRUCTION DOCUMENTS
HWRHWRHWRHWR
HWS HWS HWS HWS
H W
R H
W R
H W
S
3534a33a 3534a33a
Q1
P1
Q1
P1
DD02/27/2019
A. CONTRACTOR SHALL FIELD VERIFY AND PROVIDE ROUTING REQUIRED TO OFFSET AROUND
EXISTING FIELD CONDITIONS AND NEW WORK.
A. EXISTING CONDITIONS ARE SHOWN FOR GENERAL LOCATION ONLY. CONTRACTOR SHALL FIELD
VERIFY ACTUAL LOCATION AND ARRANGEMENT.
PROVIDE DUCT-MOUNTED HEATING WATER COIL INTO SUPPLY DUCTWORK. CONNECT TO
EXISTING HEATING WATER PIPING IN CORRIDOR PER DETAIL 3. INCORPORATE INTO
EXISTING CONTROLS.
PROVIDE NEW ROOM PRESSURE INDICATOR, TSI RP-10 OR APPROVED EQUAL. SET FOR
NEGATIVE PRESSURE NORMAL WITH ALARM TO ROOM AND EXISTING DDC CONTROLS.
COORDINATE CLEARANCE OF NEW ROOM PRESSURE INDICATOR WITH "RADIATION IN USE"
SIGN.
GENERAL NOTES:
GENERAL NOTES - DEMOLITION:
KEY NOTES:
MR
MECHANICAL PIPING PLANS
MP101
VEG 18.11
660-CSI-109
500 FOOTHILL DRIVE SALT LAKE CITY, UT 84148
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
F i l e
P a t h
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
321 4 5 6 7 8 9 10
Project Director
Issued: Date:
750 W HAMPDEN AVE.
SUITE #300
ENGLEWOOD, CO 80110
(720) 550-6307
WWW.VALHALLAENGINEERING.COM
CONSULTANTS: ARCHITECT/ENGINEERS: STAMP: CONSTRUCTION DOCUMENTS
(Contract Deliverable CD3-100%)
SPEC CT SITE PREP
Plan
North
SCALE: 1/4" = 1'-0"
1' 2' 4' 8' 16'0
MECHANICAL PIPING PLAN
1E11A
TOILET
(STAFF)
1E09B
X-RAY B
1E07
DRAW STATION
1E09
TECH STATION
1E05
READING ROOM
1E08
X-RAY
1E10
X-RAY
Plan
North
1E11A
TOILET
(STAFF)
1E09B
X-RAY B
1E07
DRAW STATION
1E09
TECH STATION
1E05
READING ROOM
1E08
X-RAY
1E10
X-RAY
Plan
North
SCALE: 1/4" = 1'-0"
1' 2' 4' 8' 16'0
MECHANICAL PIPING DEMO PLAN
DEMO FLOOR-MOUNTED FAN COIL UNIT AND CAP CHILLED WATER PIPING AT MAIN.
DEMO EXISTING "BALL-IN-THE-WALL" NEGATIVE AIR PRESSURE VISUAL DETECTOR. PATCH
TO MATCH EXISTING WALL TYPE.
DEMOLITION KEY NOTES:
WATER COIL
AIR VENT WHEN COIL
IS NOT SELF-VENTING
DRAIN WHEN COIL IS NOT
SELF-DRAINING
TEST PLUG (TYP.)
PIPE HANGER SHALL SUPPORT
PIPING INDEPENDENT OF COIL
REDUCER, IF REQUIRED
DRAIN
NOTE:
1. PROVIDE MODULATING CONTROL VALVE TO MAINTAIN SPACE CONDITIONS
THROUGH EXISTING DDC SYSTEM.
2. WHEN COIL IS INCLUDED IN CASING MOUNTED ON VIBRATION ISOLATORS THE
FIRST TWO HANGERS FOR EACH PIPE SHALL BE SPRING & NEOPRENE TYPE.
TYPE "H" FOR 4"Ø PIPE & SMALLER. TYPE "H-P" FOR 5"Ø PIPE & LARGER.
3. PIPING SHALL BE INSTALLED IN SUCH MANNER THAT IT WILL NOT BLOCK THE
SWING OR USE OF ACCESS DOORS OR PANELS; NEITHER SHALL IT BLOCK THE
SERVICING OF FILTERS, VALVES, OR EQUIPMENT.
4. THE FLOW ELEMENT MAY BE INSTALLED IN THE SUPPLY PIPING IF THE
REQUIRED MINIMUM UPSTREAM AND DOWNSTREAM DIMENSIONS CANNOT BE
OBTAINED IN THE RETURN PIPING.
FE
TITEMPERATURE
INDICATION TO
ECC
SCALE: NO SCALE
WATER COILS PIPING CONNNECTIONS
MV
MV MV
1/2"
True
RC
DB
P
VFD
G
R
A
V
W
WH
T
S
HVS
LVS
P T
D
DP#__
LP
C
TC
T T
C C
W W
B B
C
S
H
S
J
J
PB
P
SYMBOLS & ABBREVIATIONS
02/27/2019 TL BWW
E-001
NA
VEG 18.11
660-CSI-109
500 FOOTHILL DRIVE SALT LAKE CITY, UT 84148
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
F i l e
P a t h
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
321 4 5 6 7 8 9 10
Project Director
Issued: Date:
750 W HAMPDEN AVE.
SUITE #300
ENGLEWOOD, CO 80110
(720) 550-6307
WWW.VALHALLAENGINEERING.COM
CONSULTANTS: ARCHITECT/ENGINEERS: STAMP: CONSTRUCTION DOCUMENTS
(Contract Deliverable CD3-100%)
SPEC CT SITE PREP
NEUT OR N
NC
NEUTRAL
NFPA NATIONAL FIRE PROTECTION ASSOCIATION
NIC NOT IN CONTRACT
NL NIGHT LIGHT
NO NORMALLY OPEN
NS NO SCALE
NTS NOT TO SCALE
OC ON CENTER
OD OUTSIDE DIAMETER
OL OVERLOAD
P POLE
PA PUBLIC ADDRESS
PB PULL BOX OR PANEL BOARD
PBPU PREFABRICATED BEDSIDE PATIENT UNIT
PCB POLYCHLORINATED BIPHENYL
PEC PHOTOELECTRIC CELL
PED PEDESTAL
PEND PENDANT
PF POWER FACTOR
PH PHASE
PNL PANEL
PT POTENTIAL TRANSFORMER
PVC POLYVINYL CHLORIDE (PLASTIC)
PWR POWER
RCP REFLECTED CEILING PLAN
REC RECESSED
RECPT RECEPTACLE
REQ REQUIRED
RGS RIGID GALVANIZED STEEL
RM ROOM
RMS ROOT MEAN SQUARE
SCC SHORT CIRCUIT CAPACITY
SES SERVICE ENTRANCE SECTION
SD SMOKE DETECTOR
SF SQUARE FOOT (FEET)
SHT SHEET
SI INTERNATIONAL SYSTEM OF UNITS
SPEC SPECIFICATION
SPST SINGLE POLE, SINGLE THROW
SURF SURFACE
SW SWITCH
SWBD SWITCHBOARD
SWGR SWITCHGEAR
TEL TELEPHONE
TP TWISTED PAIR
TPS TWISTED PAIR SHIELDED
TTB TELEPHONE TERMINAL BOARD
TV TELEVISION
TYP TYPICAL
UFD UNDERFLOOR DUCT
UGND UNDERGROUND
UL UNDERWRITERS LABORATOY
UON UNLESS OTHERWISE NOTED
UPS UNINTERRUPTIBLE POWER SUPPLY
UTIL UTILITY
V VOLT
VA VOLT·AMPERE
VAR VOLT AMPERE REACTIVE
VFD VARIABLE FREQUENCY DRIVE
VOLT VOLTAGE
W WATT
WH WATER HEATER
WP WEATHERPROOF
XFER TRANSFER
XFMR TRANSFORMER
DRSW DOOR SWITCH
DS DISCONNECT SWITCH
DWG DRAWING
EL ELEVATION
ELEC ELECTRIC OR ELECTRICAL
ELEV ELEVATOR
EMCP EMERGENCY MONITORING CONTROL PANEL
EMER EMERGENCY
EMI ELECTROMAGNETIC INTERFERENCE
EMT ELECTRICAL METALLIC TUBING
ENCL ENCLOSURE
EPO EMERGENCY POWER OFF
EPRF EXPLOSION PROOF
ESMT EASEMENT
EWC ELECTRIC WATER COOLER
EWH ELECTRIC WATER HEATER
EXST EXISTING
FA FIRE ALARM
FAAP FIRE ALARM ANNUNCIATOR PANEL
FABL FIRE ALARM BELL
FABX FIRE ALARM BOX
FACP FIRE ALARM CONTROL PANEL
FC FOOTCANDLE
FIXT FIXTURE
FLA FULL LOAD AMPS
FLEX FLEXIBLE METALLIC CONDUIT
FLT FLOODLIGHT
FLUOR FLUORESCENT
FLUOR
FIX
FLUORESCENT FIXTURE
FOUTT TELEPHONE FLOOR OUTLET
FP FIRE PROTECTION
FT FEET OR FOOT
FU SW FUSED SWITCH
FVNR FULL VOLTAGE NON-REVERSING
FVR FULL VOLTAGE REVERSING
G OR GND ELECTRICAL GROUND
GEN GENERATOR
GFCI GROUND FAULT CIRCUIT INTERRUPTER
GTB GROUND TERMINAL BOX
HID HIGH INTENSITY DISCHARGE
HOA HAND-OFF-AUTOMATIC
HP HORSEPOWER
HT HEIGHT
HZ HERTZ
IESNA ILLUMINATION ENGINEERING SOCIETY OF
NORTH AMERICA
IMC…