36C25919R0091-005.pdf
PDF 269 KB Posted
- Solicitation number
- 36C25919R0091
About this file
36C25919R0091 S02 Attachment B G-002.pdf
View the file
Other files
| File | Type | Posted |
|---|---|---|
| 36C25919C0153-000.docx | DOCX document | |
| 36C25919R0091-0003000.docx | DOCX document | |
| 36C25919R0091-0002000.docx | DOCX document | |
| 36C25919R0091-0001000.docx | DOCX document | |
| 36C25919R0091-0001004.jpg | JPG image | |
| 36C25919R0091-0001002.jpg | JPG image | |
| 36C25919R0091-0001003.jpg | JPG image | |
| 36C25919R0091-0001001.pdf | ||
| 36C25919R0091-007.pdf | ||
| 36C25919R0091-004.pdf | ||
| 36C25919R0091-001.docx | DOCX document | |
| 36C25919R0091-002.docx | DOCX document | |
| 36C25919R0091-006.pdf | ||
| 36C25919R0091-003.pdf | ||
| 36C25919R0091-000.docx | DOCX document |
Show all 15
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
ARCHITECTURAL ABBREVIATIONS
A/C AIR CONDITIONING
ACOUS ACOUSTICAL
ACT ACOUSTICAL CEILING TILE
AD AREA DRAIN
ADA AMERICANS WITH
DISABILITIES ACT
A&E ARCHITECT AND ENGINEERS
AFF ABOVE FINISH FLOOR
AFG ABOVE FINISHED GRADE
AHJ AUTHORITIES HAVING
JURISDICTION
AHU AIR HANDLING UNIT
ALT ALTERNATIVE
ALT TRANS ALTERNATIVE
TRANSPORTATION
ALUM ALUMINUM
ANOD ANODIZED
APPROX APPROXIMATE
ARCH ARCHITECTURAL
AVG AVERAGE
BB BULLETIN BOARD
BD BOARD
BG BUMPER GUARD
BLDG BUILDING
BLKG BLOCKING
BM BEAM
BO BOTTOM OF
BRG BEARING
CB CATCH BASIN
CBB CEMENTITIOUS BACKER
BOARD
CER CERAMIC
CF CUBIC FEET
CFCI CONTRACTOR FURNISH
CONTRACTOR INSTALL
CFM CUBIC FEET PER MINUTE
CG CORNER GUARD, CEILING
GRILLE
C & G CURB & GUTTER
CI CAST IRON
CIP CAST IN PLACE
CJ CONTROL JOINT
CL CENTERLINE
CLG CEILING
CMP CORRUGATED METAL PIPE
CMU CONCRETE MASONRY UNITS
CO CLEANOUT(S)
COL COLUMN
CONC CONCRETE
CONT CONTINUOUS
COORD COORDINATE
CP CONCRETE PIPE
CPT CARPET
CRS COLD ROLLED STEEL
CS CAST STONE
CSB CONCRETE SPLASH BLOCK
CSI CONSTRUCTION
SPECIFICATIONS INSTITUTE
CT CERAMIC TILE
CTR CENTER
CU FT CUBIC FEET
CUH CABINET UNIT HEATER
CY CUBIC YARD
D DRYER
DEG DEGREE
DEMO DEMOLITION
DEPT DEPARTMENT
DET DETAIL
DF DRINKING FOUNTAIN
DIA DIAMETER
DIAG DIAGONAL
DISP DISPENSER
DIV DIVISION
DN DOWN
DR DOOR
DS DOWNSPOUT
DW DISHWASHER
DWG DRAWING
E EAST
(E) EXISTING
EA EACH
EF EXHAUST FAN
EIFS EXTERIOR INSULATION
AND FINISH SYSTEM
EJ EXPANSION JOINT
EL ELEVATION
ELEC ELECTRICAL
ELEV ELEVATOR
EQ EQUAL
EQUIP EQUIPMENT
EST ESTIMATED
ETS EXPOSED TO STRUCTURE
EWC ELECTRIC WATER COOLER
EXH EXHAUST
EXIST EXISTING
EXP EXPANSION
EXT EXTERIOR
FA FIRE ALARM
FAAP FIRE ALARM ANNUNCIATOR PANEL
FACP FIRE ALARM CONTROL PANEL
FCU FAN COIL UNIT
FD FLOOR DRAIN
FDN FOUNDATION
FE FIRE EXTINGUISHER
FEC FIRE EXTINGUISHER CABINET
FF FINISH FLOOR
FF & E FURNITURE FIXTURES & EQUIPMENT
FIN FINISH
FIXT FIXTURE
FL FLOW LINE
FLR FLOOR
FLUOR FLUORESCENT
FO FINISH OPENING
FOS FACE OF STUD
FR FIRE RATED
FSP FIRE STANDPIPE
FT FOOT / FEET
FTG FOOTING
FURR FURRING
FV FIELD VERIFY
FVC FIRE VALVE CABINET
FWC FABRIC WALLCOVERING
GA GAUGE
GALV GALVANIZED
GB GRAB BAR
GC GENERAL CONTRACTOR
GD GARBAGE DISPOSAL
GF CMU GROUND FACE CMU
GFCI GROUND FAULT CIRCUIT
INTERRUPTER
GI GALVANIZED IRON
GL GLASS
GL BLK GLASS BLACK
GLU LAM GLUE LAMINATED WOOD
GND GROUND
GT GROUT
GWB GYPSUM WALL BOARD
HAZ MAT HAZARDOUS MATERIALS
HB HOSE BIB
HC HOLLOW CORE
HCP HANDICAPPED
HDR HEADER
HDW HARDWARE
HDWD HARDWOOD
HGT HEIGHT
HM HOLLOW METAL
HORIZ HORIZONTAL
HR HOUR, HANDRAIL
HT HEIGHT
HVAC HEATING, VENTILATING & AIR
CONDITIONING
IBC INTERNATIONAL BUILDING CODE
ID INSIDE DIAMETER
IG INSULATING GLASS
IN INCH
INCAN INCANDESCENT
INFO INFORMATION
INSUL INSULATION
INT INTERIOR
INV INVERT
ITG INSULATED TEMPERED GLASS
JAN JANITOR
J-BOX JUNCTION BOX
JT JOINT
L LONG
LAV LAVATORY
LB(S) # POUND(S)
LF LINEAL FEET
LLV LONG LEG VERTICAL
LT LIGHT
LVR LOUVER
M & BH MOP AND BROOM HOLDER
MAINT MAINTENANCE
MATL MATERIAL
MAX MAXIMUM
MB MARKER BOARD
MECH MECHANICAL
MEP MECHANICAL, ELECTRICAL, PLUMBING
MFR MANUFACTURER
MH MANHOLE
MIN MINIMUM
MIRR MIRROR
MISC MISCELLANEOUS
MO MASONRY OPENING
MSB MOP SERVICE BASIN
MTD MOUNTED
MTL METAL
N NORTH
NA NOT APPLICABLE
NECY NECESSARY
NIC NOT IN CONTRACT
NO NUMBER
NOM NOMINAL
NTS NOT TO SCALE
OC ON CENTER
OD OUTSIDE DIAMETER,
OVERFLOW DRAIN
OFCI OWNER FURNISHED
CONTRACTOR INSTALLED
OFOI OWNER FURNISHED
OWNER INSTALLED
OH OPPOSITE HAND
OPN OPENING
OPP OPPOSITE
ORD OVERFLOW ROOF DRAIN
P PLASTIC
PARTN PARTITION
PBD PARTICLE BOARD
PCC PRECAST CONCRETE
PL PLATE
PLAM PLASTIC LAMINATE
PLAS PLASTER
PLYWD PLYWOOD
PR PAIR
PRCST PRECAST
PREFAB PREFABRICATED
PROP PROPERTY
PSF POUNDS PER SQUARE FOOT
PSI POUNDS PER SQUARE INCH
PT PAINT
PT CONC POST-TENSIONED CONCRETE
PTD PAPER TOWEL DISPENSER
PTL PORCELAIN TILE
PVC POLYVINYL CHLORIDE
QA QUALITY ASSURANCE
QT QUARRY TILE
R R-VALUE (INSULATION),
RADIUS, RISER
RB RESILIENT BASE
RCP REFLECTED CEILING PLAN
RD ROOF DRAIN
RE: REFERENCE
REBAR REINFORCING BAR
REC RECESSED
RECPT RECEPTACLE
REF REFRIGERATOR
REG REGISTER
REINF REINFORCE
REQD REQUIRED
RESIL RESILIENT
REV REVISION
RH ROOF HATCH
RM ROOM
RO ROUGH OPENING
RT RUBBER STAIR TREAD
S SOUTH
SAF SEAMLESS ACRYLIC FLOORING
SAP SUSPENDED ACOUSTICAL PANELS
SAT SUSPENDED ACOUSTICAL TILE
SB SPLASHBLOCK
SC SEALED CONCRETE, SOLID CORE
SCHED SCHEDULE
SCP SCUPPER
SD SOAP DISPENSER
SEAL SEALER
SECT SECTION
SF SQUARE FOOT
SF CMU SPLIT-FACE CMU
SHR SHOWER
SHT SHEET
SHTG SHEATHING
SIM SIMILAR
SL SLOPE
SLD SOLID SURFACE
SLV SHORT LEG VERTICAL
SND SANITARY NAPKIN DISPOSER
SNV SANITARY NAPKIN VENDOR
SPECS SPECIFICATIONS
SQ SQUARE
SS STAINLESS STEEL
STC SOUND TRANSMISSION CLASS
STD STANDARD
STL STEEL
STOR STORAGE
STRUC STRUCTURAL
SUSP SUSPENDED
SV SHEET VINYL
SYM SYMMETRICAL
SYS SYSTEM
T TREAD
TB TACKBOARD
T&B TOP AND BOTTOM
T&G TONGUE AND GROOVE
TBD TO BE DETERMINED
TD TUBULAR DAYLIGHTING DEVICE
TEL TELEPHONE
TEMP TEMPERATURE
TG TEMPERED GLASS,
TONGUE & GROOVE,
TRANSFER GRILLE
THRU THROUGH
TO TOP OF
TOC TOP OF CONCRETE
TOM TOP OF MASONRY
TOS TOP OF STEEL
TOW TOP OF WALL
TTD TOILET TISSUE DISPENSER
TV TELEVISION
TYP TYPICAL
UGND UNDERGROUND
UL UNDERWRITERS LABORATORY
UNFIN UNFINISHED
UNO UNLESS NOTED OTHERWISE
URN URINAL
VB VINYL BASE
VCT VINYL COMPOSITION TILE
VERT VERTICAL
VIF VERIFY IN FIELD
VTR VENT THROUGH ROOF
VWC VINYL WALL COVERING
W WEST
W/ WITH
W/O WITHOUT
WC WATER CLOSET
WD WOOD
WDP WOOD PANELING
WDW WINDOW
WF WIDE FLANGE
WGL WIRED GLASS
WH WATER HEATER
WR WASTE RECEPTACLE,
WATER RESISTANT
WS WATER STOP
WSCT WAINSCOTT
WT WEIGHT
WWF WELDED WIRE FABRIC
XX-XX
XX
X
X XXXX
X
X
X XXXXX
PARTITION TYPE
IDENTIFIER
FRAME IDENTIFIER
EQUIPMENT IDENTIFIER
REVISION INDICATOR
ROOM NAME
EXTERIOR ELEVATION
REFERENCE
INTERIOR ELEVATION
REFERENCE
ARCHITECTURAL DRAWING SYMBOLS
N
NORTH ARROW
MATCH LINE
ROOM IDENTIFIER
SHEET LOCATION
ROOM NUMBER
VIEW NUMBER
XX KEYNOTE
1 View Name A101
1/8" = 1'-0"
Room name
S1
SPECIALTIES AND
EQUIPMENT IDENTIFIER
XX
/SEE DRAWING
MATCHLINE
## X###
1. ATTENTION ALL USERS OF THESE DRAWINGS, GENERAL
CONTRACTORS, SUB CONTRACTORS, MANUFACTURERS,
SUPPLIERS: CAREFULLY AND THOROUGHLY REVIEW THESE
GENERAL NOTES. IT IS YOUR RESPONSIBILITY TO KNOW AND
ADHERE TO THESE REQUIREMENTS.
2. DO NOT PRESUME THAT YOUR SCOPE OF WORK IS
SINGULARLY DEFINED. YOUR SCOPE OF WORK IS DEFINED
THROUGHOUT THE ENTIRE SET OF DRAWINGS AND
SPECIFICATIONS AND IS NOT CONTAINED IN JUST ONE SERIES
OF DRAWINGS OR DIVISION OF SPECIFICATIONS. YOU MUST
REVIEW THE ENTIRE SET OF CONTRACT DOCUMENTS TO
DETERMINE YOUR SCOPE OF WORK.
3. THE CONTRACTOR SHALL VISIT THE SITE AND BECOME
FAMILIAR WITH SITE CONDITIONS AS THEY MAY AFFECT
CARRYING OUT THE WORK AS DESCRIBED IN THESE
CONTRACT DOCUMENTS. THE CONTRACTOR SHALL
INVESTIGATE, VERIFY, AND BE RESPONSIBLE FOR ALL
CONDITIONS OF THE PROJECT, AND NOTIFY THE ARCHITECT
OF ANY CONDITIONS THAT REQUIRE MODIFICATION BEFORE
PROCEEDING WITH THE WORK.
4. THE CONTRACTOR SHALL PROVIDE ALL MATERIALS,
EQUIPMENT, LABOR, AND SERVICES NECESSARY TO PROVIDE
FULLY OPERATIONAL ASSEMBLIES AND COMPLETE THE WORK.
5. ALL PERSONS DIRECTLY OR INDIRECTLY ASSOCIATED WITH
THE PROJECT SHALL BE FAMILIAR WITH THE RULES AND
REGULATIONS OF THE OCCUPATIONAL SAFETY AND HEALTH
ACT, AND IMPLEMENT THOSE RULES AS THEY APPLY TO THIS
PROJECT.
6. THE GENERAL CONTRACTOR SHALL FOLLOW AND OBEY ALL
FEDERAL, STATE AND LOCAL CODES, LAWS, SAFETY
REGULATIONS AND HAZARDOUS WASTE LAWS, ETC.
7. CONTRACTOR SHALL SUBMIT CONFORMATION OF ORDERED
MATERIALS OR ITEMS NECESSARY TO COMPLETE THE
PROJECT WITH PROJECTED DELIVERY DATE GREATER THAN
FOUR WEEKS.
8. ALL SUBCONTRACTORS SHALL SUBMIT SHOP DRAWINGS AS
REQUIRED FOR APPROVAL PRIOR TO COMMENCING ANY
WORK.
9. THE GENERAL CONTRACTOR SHALL BE RESPONSIBLE FOR THE
COORDINATION OF ALL TRADES AND THE PREVENTION OF
CONFLICTS BETWEEN ALL TRADES.
10. DURING TIMES WHERE EXISTING SPRINKLER SYSTEM MAY BE
SHUT-DOWN TO ALLOW SPINKLER MODIFICATION;
CONTRACTOR SHALL SUPPLY FIRE WATCH ACCORDING TO
SPEC SECTION 01 35 26 SAFETY REQUIREMENTS - SEE
SECTION 1.13K FOR SPECIFICS.
GENERAL REQUIREMENTS
1. EXISTING CONDITIONS ARE DETAILED FOR EASE OF
CONSTRUCTION AND BASED OFF EXISTING DRAWINGS.
CONTRACTOR TO FULLY INVESTIGATE EXISTING CONDITIONS
PRIOR TO ANY WORK.
2. THESE DRAWINGS WERE PRODUCED USING THE
CONSTRUCTION SPECIFICATIONS INSTITUTE’S UNIFORM
DRAWING SYSTEM AND THE NATIONAL CAD STANDARD AS
GUIDES.
3. ANY INDICATION OF PROJECT LIMITS OR LINES OF
DEMARCATION ARE SHOWN FOR THE CONVENIENCE OF THE
CONTRACTOR, AND ARE NOT TO BE TAKEN LITERALLY.
ACTUAL CONTRACT LIMITS ARE TO BE DETERMINED BY THE
CONTRACTOR AND APPROVED BY THE OWNER BEFORE
ACTUAL CONSTRUCTION WORK BEGINS.
4. DRAWINGS ARE PREPARED USING DIMENSIONS AND PRODUCT
CONFIGURATIONS OR DETAILS OF SPECIFIC MANUFACTURES.
DIMENSIONS AND DETAILS FOR SPECIFIC PRODUCTS MAY
CHANGE BEFORE THEY ARE ACTUALLY INCORPORATED INTO
THE WORK, AND PRODUCTS BY OTHER MANUFACTURERS MAY
ALSO BE ACCEPTABLE. THEREFORE, ACTUAL INSTALLATION
DETAILS AND DIMENSIONS MAY DIFFER FROM THOSE SHOWN.
CONTRACTOR SHALL VERIFY INSTALLATION REQUIREMENTS
FOR ALL PRODUCTS TO BE INCORPORATED IN THE WORK
(INCLUDING PARTITION THICKNESSES FOR RECESSED OR
SEMI-RECESSED PRODUCTS), AND IS RESPONSIBLE FOR
ACCOMMODATING AND COORDINATING CHANGES TO OTHER
MATERIALS OR PRODUCTS THAT ARE NECESSARY BECAUSE
OF THESE DIFFERENCES.
5. THE DRAWINGS AND SPECIFICATIONS ARE SEPARATED INTO
DISCIPLINES FOR CONVENIENCE. THE SEPARATIONS USED
HEREIN ARE USED ONLY FOR THE PURPOSES OF
CONVENIENCE AND REFERENCE AND IN NO WAY DO THEY
DEFINE OR LIMIT THE SCOPE OR INTENT OF ANY PART OF THE
DRAWINGS, OR THE DRAWINGS AND SPECIFICATIONS AS A
WHOLE. THE FACT THAT THE DRAWINGS ARE SEPARATED IN
NO WAY SUGGESTS THAT THE WORK IS NOT TO BE
CONSTRUCTED AS A COMPLETE, INTEGRATED AND UNIFIED
WHOLE.
6. THE DRAWINGS AND SPECIFICATIONS, INCLUDING DRAWINGS
PREPARED BY SPECIFIC ENGINEERING DISCIPLINES (SUCH AS
CIVIL, STRUCTURAL, MECHANICAL, ELECTRICAL, ETC.) ARE
COMPLEMENTARY; ITEMS SHOWN IN ANY ONE LOCATION IN
THE DRAWINGS SHALL BE CONSIDERED TO BE REQUIREMENTS
OF THE CONTRACTOR FOR CONSTRUCTION. IN THE EVENT OF
AN INCONSISTENCY BETWEEN THE DRAWINGS AND
SPECIFICATIONS, OR WITHIN EITHER DOCUMENTS, THE
CONTRACTOR SHALL SEEK CLARIFICATION OR
INTERPRETATION FROM THE ARCHITECT PRIOR TO BIDDING.
WHERE INCONSISTENCIES ARE NOT CLARIFIED PRIOR TO
BIDDING, AND WHERE THE ACTUAL SOLUTION OR INTENT
CANNOT BE REASONABLY INFERRED, THE CONTRACTOR
SHALL PROVIDE THE BETTER QUALITY OR GREATER QUANTITY
OF WORK.
7. USE OF THE WORD “VERIFY” POINTS OUT A SITUATION WHICH
MUST BE CONFIRMED PRIOR TO PROCEEDING WITH THE
WORK, FABRICATION OF EQUIPMENT, OR ORDERING MATERIAL.
NOTIFY THE ARCHITECT OF ANY DISCREPANCY.
8. THE GENERAL CONTRACTOR SHALL BE RESPONSIBLE FOR
NOTIFYING THE ARCHITECT IMMEDIATELY SHOULD ANY
DISCREPANCIES BE FOUND IN THE DRAWINGS AND
SPECIFICATIONS.
9. DO NOT SCALE THE DRAWINGS. DRAWINGS SCALES AS
INDICATED ARE FOR REFERENCE ONLY AND ARE NOT
INTENDED TO ACCURATELY DEPICT ACTUAL OR DESIGNATE
CONDITIONS. WRITTEN DIMENSIONS SHALL GOVERN.
10. ALL DIMENSIONS INDICATED ARE TO FACES OF
CMU/STUD/STRUCTURAL MATERIALS OR COLUMN GRID LINES
UNLESS NOTED OTHERWISE. MASONRY DIMENSIONS ARE
MODULAR IN THAT THEY INCLUDE THE GROUT JOINT. ROUGH
OPENINGS ALLOW FOR SHIM SPACE.
11. THE TERM “ALIGN” REFERS TO LOCATING DIFFERENT
COMPONENTS OF CONSTRUCTION TO PROVIDE A FLUSH
FINISH SURFACE.
GENERAL DRAWING AND DIMENSION NOTES
1. PROVIDE SEALANT AT ALL JOINTS OR CRACKS WHICH OCCUR
WHERE DISSIMILAR MATERIALS INTERSECT PERPENDICULAR
TO EACH OTHER, AND THE INTERSECTION IS EXPOSED TO
VIEW, UNLESS INDICATED OTHERWISE ON THE DRAWINGS.
2. WHERE DOORS IN PARTITIONS ARE NOT DIMENSIONALLY
LOCATED ON THE PLANS, PROVIDE A MINIMUM HINGE SIDE
JAMB DIMENSION OF 6” FROM DOOR OPENING TO ADJACENT
PERPENDICULAR WALL.
3. PROVIDE CONTROL JOINT IN ALL GYPSUM BOARD WALLS
GREATER THAN 30’ LONG. PLACE CONTROL JOINTS AT
CORNERS OF DOORS OR WINDOWS.
4. ALL SURFACES AND SUBSTRATES SHALL BE PREPARED FOR
INSTALLATION PER MANUFACTURER'S RECOMMENDED
INSTRUCTIONS, UNO.
5. PROVIDE ALL BLOCKING (WOOD OR 16 G.A. GALVANIZED SHEET
METAL) AS REQUIRED FOR THE ATTACHMENT OF
MISCELLANEOUS EQUIPMENT INCLUDING BUT NOT LIMITED TO:
TOILET ACCESSORIES, DOOR HARDWARE, ELECTRICAL
DEVICES, KITCHEN EQUIPMENT, GRAB BARS, HAND RAILS, AND
CASEWORK.
6. THE GENERAL CONTRACTOR SHALL BE RESPONSIBLE FOR
FINAL CLEAN UP FOLLOWING EACH PHASE AND UPON
COMPLETION.
7. NO UTILITY SERVICE INTERRUPTION SHALL OCCUR WITHOUT
THE PRIOR WRITTEN APPROVAL OF THE OWNER. ALL
REQUEST FOR UTILITY SERVICE INTERRUPTION SHALL
INCLUDE A COMPLETED “UTILITY SYSTEMS SERVICE/OUTAGE
NOTIFICATION” FORM. ALL UTILITY SERVICE INTERRUPTIONS
SHALL OCCUR AFTER NORMAL HOURS OF MEDICAL CENTER
OPERATION. ALL UTILITY SERVICES INTERRUPTION
PROCEDURES SHALL COMPLY WITH THE GENERAL
REQUIREMENTS SPECIFICATIONS.
8. CONTRACTOR TO PATCH AND REPAIR AREAS AFFECTED BY
DEMOLITION AND CONSTRUCTION ACTIVITIES. MATCH
EXISTING ADJACENT CONSTRUCTION AND FINISH.
CONTRACTOR TO FIELD. VERIFY SCOPE OF WORK.
GENERAL CONSTRUCTION NOTES
MANUFACTURER'S TRADE NAMES AND NUMBERS USED
HEREIN ARE ONLY TO IDENTIFY CHARACTER, COLORS,
FINISHES, TEXTURES AND PATTERNS AS THE BASIS OF
DESIGN. PRODUCTS OF AUTHORIZED EQUAL
MANUFACTURER'S EQUIVALENT TO QUALITY, COLORS,
FINISHES, TEXTURES AND PATTERNS OF MANUFACTURERS
LISTED THAT MEET THE REQUIREMENTS OF TECHNICAL
SPECIFICATIONS IN EVERY RESPECT MAY BE ACCEPTABLE
WITH SUBMITTAL OF A COMPLETED SUBSTITUTION
REQUEST CONTAINING ALL PRODUCT DATA, TESTING AND
ACTUAL SAMPLES AND UPON APPROVAL IN WRITING BY
CONTRACTING OFFICER.
INFECTION CONTROL PLAN NOTES
INFECTION CONTROL PROJECT INFORMATION
CONSTRUCTION ACTIVITY - FIRE RISK: TYPE A
PATIENT RISK GROUP: LOW
CLASS OF PRECAUTION MATRIX: I
PROVIDE TEMPORARY 1 HR FIRE RATED SMOKE BARRIER WALL
CONSTRUCTION PER NFPA 241. REFER TO DETAIL 6/G002.
PROVIDE TEMPORARY INFECTION CONTROL CONSTRUCTION DOOR WITH CARD
READER ACCESS. REFER TO ELEVATION 8/G-002
REFER TO LIST OF REQUIRED INFECTION CONTROL PRECAUTIONS OUTLINED
BY CLASS IN SPECIFICATION 013526 AND ADDITIONAL INFORMATION.
REFER TO DRAWINGS, SPECIFICATIONS AND DOOR HARDWARE SCHEDULE
FOR ADDITIONAL INFORMATION.
PROJECT SHALL BE COMPLETED IN ASINGLE PHASE
COORDINATE FULL SCOPE OF WORK WITH ENGINEERING DRAWINGS AND
FIELD VERIFICATION. CONTRACTOR IS RESPONSIBLE FOR SCOPE OF ABOVE
CEILING WORK REQUIRED ABOVE AND BELOW THE FLOOR PLATE OF THE
PROJECT BOUNDARY.
COORDINATE LOCATION OF TEMPORARY INFECTION CONTROL (IC) BARRIER
WALL CONSTRUCTION AND INFECTION CONTROL (IC) MEASURES WITH COR
AND PATIENT SAFETY/ INFECTION CONTROL REPRESENTATIVE. TEMPORARY
IC BARRIER WALL CONSTRUCTION LOCATIONS IN DRAWINGS ARE
APPROXIMATE. CONTRACTOR SHALL PROVIDE DRAWING TO COR AND
PATIENT SAFETY/ INFECTION CONTROL REPRESENTATIVE ONCE ICRA
PROTOCOLS AND PLAN IS APPROVED.
SCHEDULE AND TIME OF CONSTRUCTION WORK TO BE APPROVED BY COR
AND NURSING STAFF BEFORE CONSTRUCTION MAY BEGIN. PROVIDE PHASING
INFORMATION FOR ABOVE CEILING WORK IN THE CONTRACTOR PROVIDED
CMP SCHEDULE FOR WORK ALSO REQUIRED ABOVE AND BELOW THE FLOOR
PLATE OF THE PROJECT BOUNDARY.
ABOVE CEILING WORK SHALL TAKE PLACE BETWEEN THE HOURS OF 5:00 PM
AND 5:00 AM. IN AREAS THAT REQUIRE ABOVE CEILING WORK WHERE
CEILINGS ARE TO REMAIN, CEILING TILES SHALL BE REMOVED AND STORED IN
A SAFE MANOR UNTIL CEILING TILES CAN BE REINSTALLED. DAMAGED AND
BROKEN CEILING TILES SHALL BE REPLACED BY CONTRACTOR.
EXIT/ACCESS FOR ADJACENT OPERATIONAL AREAS SHALL BE MAINTAINED
DURING NORMAL BUSINESS HOURS. SEE SPECIFICATION FOR HOURS OF
OPERATION.
// WORK REQUIRING VIBRATION OR LOAD NOISE SHALL TAKE PLACE BETWEEN
THE HOURS OF 5:00 PM AND 5:00 AM. EVERY EFFORT SHALL BE MADE TO
KEEP NOISE AND VIBRATION TO A MINIMUM. //
PROVIDE THE FOLLOWING INFECTION CONTROL MEASURES, A 24"X36" STICKY
WALK OFF MAT AND HAND SANITIZER AT EACH TEMPORARY DOOR LOCATION.
MAT SHALL BE REPLACED OR CLEANED AS NECESSARY
PROVIDE THE VA AND OSHA REQUIRED TEMPORARY SIGNAGE AT EACH
TEMPORARY DOOR LOCATION.
CONTRACTOR SHALL SUPPLY SPILL KIT. SPILL KIT TO INCLUDE SHOP VAC,
MULTI-PURPOSE SPILL CONTROL SORBENTS TO ABSORB NON AGGRESSIVE
LIQUIDS UP TO 30 GALLONS.
ALL NEW MATERIAL MOVED THROUGH THE FACILITY SHALL BE COVERED WITH
4 MIL. POLY SHEET.
ALL DEMOLITION MATERIAL SHALL BE REMOVED FROM THE PROJECT
BOUNDARY THROUGH THE FACILITY TO DUMPSTER ALONG VA APPROVED
ROUTE IN ENCLOSED DUMPSTER CART DESIGNED FOR SUCH PURPOSED
WITH A LID.
ALL MATERIAL, DEBRIS AND HAZARDOUS MATERIALS SHALL BE PROPERLY
STORED IN DESIGNATED AREAS AND APPROVED CONTAINERS. FLAMMABLE
MATERIALS SHALL NOT BE STORED IN THE FACILITY.
PROVIDE CONTAINMENT CART FOR ABOVE CEILING ACCESS OUTSIDE
PROJECT BOUNDARY.
A
B
C
D
E
F
G
H
I
J
K
L
M
N
O
P
INFECTION CONTROL GENERAL NOTES
PHASING GENERAL NOTES
A
B
C
D
PROJECT AREAS TO BE OCCUPIED BY STAFF AND VETERANS THROUGHOUT
CONSTRUCTION.
PROJECT SHALL BE COMPLETED DURING NIGHT SHIFTS, 5:00 PM TO 5:00 AM.
COORDINATE WITH COR. ALL WORK TO BE COMPLETED AND OPEN FOR PUBLIC
USE AT THE END OF EACH NIGHT'S WORK.
CONSTRUCTION WORK BEHIND TEMPORARY CONSTRUCTION PARTITIONS
SHALL BE COMPLETED DURING NIGHT SHIFTS, 5:00 PM TO 5:00 AM.
REFER TO SPECIFICATION 01 00 00 FOR INFORMATION ON WORK DURATION
FOR EACH PHASE AND AREA OF WORK.
NOTES APPLY TO PLANS ON AS109
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
Consultant:
C U s e rs
\K n ie h a u s \D o c u m e n ts
\1 .1
.0
V A
G ra n d
J u n c ti o n
F ir e
B a rr ie r M it ig a ti o n
V k n ie h a u s g u id o n d e s ig n .c o m
.r v t
/1
/2
:0
:3
A
M
G-002
ABBREVIATIONS AND SYMBOLS
GUIDON DESIGN INC.
905 N. CAPITOL AVENUE SUITE 100
INDIANAPOLIS, IN 46204
317-800-6388
JAMES GOODEN
FIRE BARRIER MITIGATION,
BUILDING 1
GRAND JUNCTION, CO
575-17-102
BLDG 1
11/19/2018 JG KN
100% BID DOCUMENTS
Revisions: Date:
| Sheets |
| G-002 - ABBREVIATIONS AND SYMBOLS |