36C25919R0086-0005003.pdf

PDF 38 KB Posted

Attached to
Renovate 7 East (VA-19-00024846)
Solicitation number
36C25919R0086
Issued by

About this file

36C25919R0086 0005 7East 088000.pdf

View the file

Other files

File Type Posted
36C25919C0174-000.docx DOCX document
36C25919R0086-0010000.docx DOCX document
36C25919R0086-0010001.pdf PDF
36C25919R0086-0009001.pdf PDF
36C25919R0086-0009000.docx DOCX document
36C25919R0086-0008000.docx DOCX document
36C25919R0086-0008001.pdf PDF
36C25919R0086-0007000.docx DOCX document
36C25919R0086-0006003.pdf PDF
36C25919R0086-0006001.pdf PDF
36C25919R0086-0006002.pdf PDF
36C25919R0086-0006000.docx DOCX document
36C25919R0086-0005002.pdf PDF
36C25919R0086-0005001.pdf PDF
36C25919R0086-0005000.docx DOCX document
36C25919R0086-0005006.pdf PDF
36C25919R0086-0005004.pdf PDF
36C25919R0086-0005005.pdf PDF
36C25919R0086-0004000.docx DOCX document
36C25919R0086-0003001.pdf PDF
36C25919R0086-0003000.docx DOCX document
36C25919R0086-0002000.docx DOCX document
36C25919R0086-0002002.pdf PDF
36C25919R0086-0002001.pdf PDF
36C25919R0086-0001001.pdf PDF
36C25919R0086-0001000.docx DOCX document
36C25919R0086-016.pdf PDF
36C25919R0086-022.pdf PDF
36C25919R0086-009.pdf PDF
36C25919R0086-020.pdf PDF
36C25919R0086-008.pdf PDF
36C25919R0086-011.pdf PDF
36C25919R0086-040.pdf PDF
36C25919R0086-003.docx DOCX document
36C25919R0086-005.pdf PDF
36C25919R0086-035.pdf PDF
36C25919R0086-032.pdf PDF
36C25919R0086-024.pdf PDF
36C25919R0086-038.pdf PDF
36C25919R0086-006.pdf PDF
36C25919R0086-028.pdf PDF
36C25919R0086-018.pdf PDF
36C25919R0086-036.pdf PDF
36C25919R0086-029.pdf PDF
36C25919R0086-044.pdf PDF
36C25919R0086-030.pdf PDF
36C25919R0086-042.pdf PDF
36C25919R0086-004.pdf PDF
36C25919R0086-026.pdf PDF
36C25919R0086-019.pdf PDF
Show 40 more

Latest 50 of 71 listed here. See the rest on GovTribe.

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

OKLAHOMA CITY VA HEALTH CARE SYSTEM

OKLAHOMA CITY, OKLAHOMA

635-16-101 RENOVATE 7 EAST

RFI #1 / 4-16-2019

10-01-15

08 80 00 - 1

SECTION 08 80 00

GLAZING

PART 1 - GENERAL

1.1 DESCRIPTION:

A. This section specifies the following:

1. Glass.

2. Glazing materials and accessories for both facto ry and field glazed assemblies.

1.2 RELATED WORK:

A. Factory glazed by manufacturer in following unit s:

1. Mirrors: Section 10 28 00, TOILET, BATH, AND LAU NDRY ACCESSORIES.

1.3 LABELS:

A. Temporary labels:

1. Provide temporary label on each light of glass i dentifying manufacturer or brand and glass type, quality and n ominal thickness.

2. Label in accordance with NFRC label requirements .

3. Temporary labels are to remain intact until glas s is approved by

Contracting Officer Representative (COR).

B. Permanent labels:

1. Locate in corner for each pane.

2. Label in accordance with ANSI Z97.1 and SGCC lab el requirements.

a. Tempered glass.

b. Laminated glass or have certificate for panes wi thout permanent label.

c. Organic coated glass.

1.4 PERFORMANCE REQUIREMENTS:

A. General: Design glazing system consistent with guidance and practices presented in the GANA Glazing Manual, GANA Laminate d Glazing Manual, and GANA Sealant Manual, as applicable to project. Installed glazing is to withstand applied loads, thermal stresses, therm al movements, building movements, permitted tolerances, and combi nations of these conditions without failure, including loss or glass breakage attributable to defective manufacture, fabrication, or installation;

failure of sealants or gaskets to remain watertight and airtight;

deterioration of glazing materials; unsafe engageme nt of the framing

08 80 00 - 2 system; deflections beyond specified limits; or oth er defects in construction.

B. Glazing Unit Design: Design glass, including en gineering analysis meeting requirements of authorities having jurisdic tion. Thicknesses listed are minimum. Coordinate thicknesses with fra ming system manufacturers.

1. Design glass in accordance with ASTM E1300, and for conditions beyond the scope of ASTM E1300, by a properly subst antiated structural analysis.

1.5 SUBMITTALS:

A. In accordance with Section 01 33 23, SHOP DRAWIN GS, PRODUCT DATA, AND

SAMPLES.

B. Manufacturer's Certificates:

1. Certificate stating that fire-protection and fir e-resistive glazing units meet code requirements for fire-resistance-ra ted assembly and applicable safety glazing requirements.

2. Certificate on solar heat gain coefficient when value is specified.

3. Certificate on "R" value when value is specified .

D. Manufacturer Warranty.

E. Manufacturer's Literature and Data:

1. Glass, each kind required.

2. Glazing cushion.

3. Sealing compound.

F. Samples:

1. Size: 305 mm by 305 mm (12 inches by 12 inches).

G. Preconstruction Adhesion and Compatibility Test Report: Submit glazing sealant manufacturer’s test report indicating glazi ng sealants were tested for adhesion to glass and glazing channel su bstrates and for compatibility with glass and other glazing material s.

1.6 DELIVERY, STORAGE AND HANDLING:

A. Delivery: Schedule delivery to coincide with gla zing schedules so minimum handling of crates is required. Do not open crates except as required for inspection for shipping damage.

B. Storage: Store cases according to printed instru ctions on case, in areas least subject to traffic or falling objects. Keep storage area clean and dry.

08 80 00 - 3

C. Handling: Unpack cases following printed instruc tions on case. Stack individual windows on edge leaned slightly against upright supports with separators between each.

D. Protect laminated security glazing units against face and edge damage during entire sequence of fabrication, handling, an d delivery to installation location. Provide protective covering on exposed faces of glazing plastics, and mark inside as "INTERIOR FACE " or "PROTECTED

FACE":

1. Treat security glazing as fragile merchandise, a nd packaged and shipped in export wood cases with width end in upri ght position and blocked together in a mass. Storage and handling to comply with manufacturer's directions and as required to preven t edge damage or other damage to glazing resulting from effects of m oisture, condensation, temperature changes, direct exposure to sun, other environmental conditions, and contact with chemical solvents.

2. Protect sealed-air-space insulating glazing unit s from exposure to abnormal pressure changes, as could result from sub stantial changes in altitude during delivery by air freight. Provide temporary breather tubes which do not nullify applicable warr anties on hermetic seals.

3. Temporary protections: The glass front and polyc arbonate back of glazing are to be temporarily protected with compat ible, peelable, heat-resistant film which will be peeled for inspec tions and re-applied and finally removed after doors and wind ows are installed at destination. Since many adhesives will attack po lycarbonate, the film used on exposed polycarbonate surfaces is to b e approved and applied by manufacturer.

4. Edge protection: To cushion and protect glass cl ad, and polycarbonate edges from contamination or foreign m atter, the four (4) edges are to be sealed the depth of glazin g with continuous standard-thickness thermoplastic rubber tape. Alter natively, continuous channel shaped extrusion of thermoplasti c rubber are to be used, with flanges extending into face sides of glazing.

5. Protect "Constant Temperature" units including e very unit where glass sheet is directly laminated to or directly se aled with metal-tube type spacer bar to polycarbonate sheet, from exposures to

08 80 00 - 4 ambient temperatures outside the range of 16 to 24 degrees C (60 to

75 degrees F), during the fabricating, handling, sh ipping, storing, installation, and subsequent protection of glazing.

1.7 PROJECT CONDITIONS:

Field Measurements: Field measure openings before ordering tempered glass products to assure for proper fit of field me asured products.

1.8 WARRANTY:

A. Construction Warranty: Comply with the FAR claus e 52.246-21 “Warranty of Construction”.

B. Manufacturer Warranty: Manufacturer shall warran ty their glazing from the date of installation and final acceptance by th e Government as follows. Submit manufacturer warranty.

1. Bullet resistive plastic material to remain visi bly clear without discoloration for 10 years.

2. Insulating glass units to remain sealed for ten (10) years.

3. Laminated glass units to remain laminated for fi ve (5) years.

4. Polycarbonate to remain clear and ultraviolet li ght stabilized for five (5) years.

5. Insulating plastic to not have more than 6 perce nt decrease in light transmission and be ultraviolet light stabilized fo r ten (10) years.

1.9 APPLICABLE PUBLICATIONS:

A. Publications listed below form a part of this sp ecification to extent referenced. Publications are referenced in text by basic designation only.

B. American Architectural Manufacturers Association (A AMA):

800.....................Test Methods for Sealants

810.1-77................Expanded Cellular Glazing T ape

C. American National Standards Institute (ANSI):

Z97.1-14................Safety Glazing Material Use d in

Building - Safety Performance Specifications and Methods of Test

D. American Society of Civil Engineers (ASCE):

7-10....................Wind Load Provisions

E. ASTM International (ASTM):

C542-05(R2011)..........Lock-Strip Gaskets

08 80 00 - 5

C716-06.................Installing Lock-Strip Gaske ts and Infill

Glazing Materials

C794-10.................Adhesion-in-Peel of Elastom eric Joint Sealants

C864-05(R2011)..........Dense Elastomeric Compressi on Seal Gaskets, Setting Blocks, and Spacers

C920-14a................Elastomeric Joint Sealants

C964-07(R2012)..........Standard Guide for Lock-Str ip Gasket Glazing

C1036-11(R2012).........Flat Glass

C1048-12................Heat-Treated Flat Glass-Kin d HS, Kind FT Coated and Uncoated Glass.

C1172-14................Laminated Architectural Fla t Glass

C1349-10................Standard Specification for Architectural Flat

Glass Clad Polycarbonate

C1376-10................Pyrolytic and Vacuum Deposi tion Coatings on

Flat Glass

D635-10.................Rate of Burning and/or Exte nt and Time of

Burning of Self-Supporting Plastic in a

Horizontal Position

D4802-10................Poly (Methyl Methacrylate) Acrylic Plastic

Sheet

E84-14..................Surface Burning Characteris tics of Building

Materials

E119-14.................Standard Test Methods for F ire Test of Building

Construction and Material

E1300-12a...............Load Resistance of Glass in Buildings

E1886-13a...............Standard Test Method for Pe rformance of

Exterior Windows, Curtain Walls, Doors, and

Impact Protective Systems Impacted by

Missile(s) and Exposed to Cyclic Pressure

Differentials

E1996-14a...............Standard Specification for Performance of

Exterior Windows, Curtain Walls, Doors, and

Impact Protective Systems Impacted by Windborne

Debris in Hurricanes

08 80 00 - 6

E2141-12................Test Methods for Assessing the Durability of

Absorptive Electrochromic Coatings on Sealed

Insulating Glass Units

E2190-10................Insulating Glass Unit

E2240-06................Test Method for Assessing t he Current-Voltage

Cycling Stability at 90 Degree C (194 Degree F) of Absorptive Electrochromic Coatings on Sealed

Insulating Glass Units

E2241-06................Test Method for Assessing t he Current-Voltage

Cycling Stability at Room Temperature of

Absorptive Electrochromic Coatings on Sealed

Insulating Glass Units

E2354-10................Assessing the Durability of Absorptive

Electrochromic Coatings within Sealed

Insulating Glass Units

E2355-10................Test Method for Measuring t he Visible Light

Transmission Uniformity of an Absorptive

Electrochromic Coating on a Glazing Surface

F1233-08................Standard Test Method for Se curity Glazing

Materials and Systems

F1642-12................Test Method for Glazing and Glazing Systems

Subject to Airblast Loadings

E. Code of Federal Regulations (CFR):

16 CFR 1201-10..........Safety Standard for Archite ctural Glazing

Materials

F. Glass Association of North America (GANA):

2010 Edition............GANA Glazing Manual

2008 Edition............GANA Sealant Manual

2009 Edition............GANA Laminated Glazing Refe rence Manual

2010 Edition............GANA Protective Glazing Ref erence Manual

G. International Code Council (ICC):

IBC.....................International Building Code

H. Insulating Glass Certification Council (IGCC)

I. Insulating Glass Manufacturer Alliance (IGMA):

TB-3001-13..............Guidelines for Sloped Glazi ng

08 80 00 - 7

TM-3000.................North American Glazing Guid elines for Sealed

Insulating Glass Units for Commercial and

Residential Use

J. Intertek Testing Services – Warnock Hersey (ITS- WHI)

K. National Fire Protection Association (NFPA):

80-16...................Fire Doors and Windows

252-12..................Fire Tests of Door Assembli es

257-12..................Standard on Fire Test for W indow and Glass

Block Assemblies

L. National Fenestration Rating Council (NFRC)

M. Safety Glazing Certification Council (SGCC) 2012 :

Certified Products Directory (Issued Semi-Annually ).

N. Underwriters Laboratories, Inc. (UL):

9-08(R2009).............Fire Tests of Window Assemb lies

263-14..................Fire Tests of Building Cons truction and

Materials

752-11..................Bullet-Resisting Equipment.

O. Unified Facilities Criteria (UFC):

4-010-01-03(R2007)......DOD Minimum Antiterrorism S tandards for

Buildings

P. U.S. Veterans Administration:

Physical Security Design Manual for VA Facilities (VAPSDG); Life Safety

Protected

Physical Security Design Manual for VA Facilities (VAPSDG); Mission

Critical Facilities

Architectural Design Manual for VA Facilities (VAS DM)

Q. Environmental Protection Agency (EPA):

40 CFR 59(2014).........National Volatile Organic C ompound Emission

Standards for Consumer and Commercial Products

PART 2 - PRODUCT

2.1 GLASS:

A. Provide minimum thickness stated and as addition ally required to meet performance requirements.

1. Provide minimum 6 mm (1/4 inch) thick glass unit s unless otherwise indicated.

08 80 00 - 8

B. Obtain glass units from single source from singl e manufacturer for each glass type.

C. Clear Glass:

1. ASTM C1036, Type I, Class 1, Quality q4.

2.2 HEAT-TREATED GLASS:

A. Roller Wave Limits for Heat-Treated Glass: Orien t all roller wave distortion parallel to bottom surface of glazing, a nd provide units complying with the following limitations:

1. Measurement Parallel to Line: Maximum peak to v alley 0.203 mm

(0.008 inch).

2. Measurement Perpendicular to Line: Maximum 0.025 4 mm (0.001 inch).

3. Bow/Warp: Maximum 50 percent of bow and warp all owed by ASTM C1048.

B. Clear Heat Strengthened Glass:

1. ASTM C1048, Kind HS, Condition A, Type I, Class 1, Quality q3.

C. Clear Tempered Glass:

1. ASTM C1048, Kind FT, Condition A, Type I, Class 1, Quality q3.

2.3 GLAZING ACCESSORIES:

A. As required to supplement the accessories provid ed with the items to be glazed and to provide a complete installation. Ferr ous metal accessories exposed in the finished work are to hav e a finish that will not corrode or stain while in service. Fire rated g lazing to be installed with glazing accessories in accordance wi th the manufacturer’s installation instructions.

B. Setting Blocks: ASTM C864:

1. Silicone type.

2. Channel shape; having 6 mm (1/4 inch) internal d epth.

3. Shore A hardness of 80 to 90 Durometer.

4. Block lengths: 50 mm (2 inches) except 100 to 15 0 mm (4 to 6 inches) for insulating glass.

5. Block width: Approximately 1.6 mm (1/16 inch) le ss than the full width of the rabbet.

6. Block thickness: Minimum 4.8 mm (3/16 inch). Thi ckness sized for rabbet depth as required.

C. Spacers: ASTM C864:

1. Channel shape having a 6 mm (1/4 inch) internal depth.

08 80 00 - 9

2. Flanges not less 2.4 mm (3/32 inch) thick and we b 3 mm (1/8 inch) thick.

3. Lengths: 25 to 76 mm (1 to 3 inches).

4. Shore A hardness of 40 to 50 Durometer.

D. Glazing Tapes:

1. Semi-solid polymeric based closed cell material exhibiting pressure-sensitive adhesion and withstanding exposu re to sunlight, moisture, heat, cold, and aging.

2. Shape, size and degree of softness and strength suitable for use in glazing application to prevent water infiltration.

3. Complying with AAMA 800 for the following types:

a. AAMA 810.1, Type 1, for glazing applications in which tape acts as the primary sealant.

b. AAMA 810.1, Type 2, for glazing applications in which tape is used in combination with a full bead of liquid seal ant.

E. Spring Steel Spacer: Galvanized steel wire or st rip designed to position glazing in channel or rabbeted sash with s tops.

F. Glazing Clips: Galvanized steel spring wire desi gned to hold glass in position in rabbeted sash without stops.

SPEC WRITER NOTE: Points are for wood sash.

G. Glazing Points (Sprigs): Pure zinc stock, thin, flat, triangular or diamond shaped pieces, 6 mm (1/4 inch) minimum size .

H. Glazing Gaskets: ASTM C864:

1. Firm dense wedge shape for locking in sash.

2. Soft, closed cell with locking key for sash key.

3. Flanges may terminate above the glazing-beads or terminate flush with top of beads.

I. Lock-Strip Glazing Gaskets: ASTM C542, shape, si ze, and mounting as indicated.

J. Glazing Sealants: ASTM C920, silicone neutral cu re:

1. Type S.

2. Class 25 or 50 as recommended by manufacturer fo r application.

3. Grade NS.

4. Shore A hardness of 25 to 30 Durometer.

08 80 00 - 10

L. Neoprene, EPDM, or Vinyl Glazing Gasket: ASTM C8 64.

1. Channel shape; flanges may terminate above the g lazing channel or flush with the top of the channel.

2. Designed for dry glazing.

M. Color:

1. Color of glazing compounds, gaskets, and sealant s used for aluminum color frames to match color of the finished aluminu m and be nonstaining.

2. Color of other glazing compounds, gaskets, and s ealants which will be exposed in the finished work and unpainted are t o be black, gray, or neutral color.

PART 3 - EXECUTION

3.1 EXAMINATION:

A. Verification of Conditions:

1. Examine openings for glass and glazing units; de termine they are proper size; plumb; square; and level before instal lation is started.

2. Verify that glazing openings conform with detail s, dimensions and tolerances indicated on manufacturer is approved sh op drawings.

B. Review for conditions which may adversely affect glass and glazing unit installation, prior to commencement of installation . Do not proceed with installation until unsatisfactory conditions h ave been corrected.

C. Verify that wash down of adjacent masonry is com pleted prior to erection of glass and glazing units.

3.2 PREPARATION:

A. For sealant glazing, prepare glazing surfaces in accordance with

GANA Sealant Manual.

B. Determine glazing unit size and edge clearances by measuring the actual unit to receive the glazing.

C. Shop fabricate and cut glass with smooth, straig ht edges of full size required by openings to provide GANA recommended ed ge clearances.

D. Verify that components used are compatible.

E. Clean and dry glazing surfaces.

F. Prime surfaces scheduled to receive sealants, as determined by preconstruction sealant-substrate testing.

08 80 00 - 11

3.3 INSTALLATION – GENERAL:

A. Install in accordance with GANA Glazing Manual, GANA Sealant Manual, IGMA TB-3001, and IGMA TM-3000 unless specified oth erwise.

B. Glaze in accordance with recommendations of glaz ing and framing manufacturers, and as required to meet the Performa nce Test

Requirements specified in other applicable sections of specifications.

C. Set glazing without bending, twisting, or forcin g of units.

D. Do not allow glass to rest on or contact any fra ming member.

E. Glaze doors and operable sash, in a securely fix ed or closed and locked position, until sealant, glazing compound, or putty has thoroughly set.

F. Tempered Glass: Install with roller distortions in horizontal position unless otherwise directed.

3.4 INSTALLATION - DRY METHOD (TAPE AND GASKET SPLI NE GLAZING):

A. Cut glazing spline to length; install on glazing pane. Seal corners by butting and sealing junctions with butyl sealant.

B. Place setting blocks at 1/4 points with edge blo ck no more than 150 mm

(6 inches) from corners.

C. Rest glazing on setting blocks and push against fixed stop with sufficient pressure to attain full contact.

D. Install removable stops without displacing glazi ng spline. Exert pressure for full continuous contact.

E. Do not exceed edge pressures stipulated by glass manufacturers for installing glass lites.

F. Trim protruding tape edge.

3.5 REPLACEMENT AND CLEANING:

A. Clean new glass surfaces removing temporary labe ls, paint spots, and defacement after approval by COR.

B. Replace cracked, broken, and imperfect glass, or glass which has been installed improperly.

C. Leave glass, putty, and other setting material i n clean, whole, and acceptable condition.

3.6 PROTECTION:

A. Protect finished surfaces from damage during ere ction, and after completion of work. Strippable plastic coatings on colored anodized finish are not acceptable.

- - - E N D - - -