About this file

36C25819B0023 0001 S02 Bridge 2 Door Hardware Changes (60_ Complete).pdf

View the file

Other files

File Type Posted
36C25819B0023-0003002.pdf PDF
36C25819B0023-0003003.pdf PDF
36C25819B0023-0003000.docx DOCX document
36C25819B0023-0003001.pdf PDF
36C25819B0023-0002011.pdf PDF
36C25819B0023-0002012.pdf PDF
36C25819B0023-0002010.docx DOCX document
36C25819B0023-0002013.pdf PDF
36C25819B0023-0001005.pdf PDF
36C25819B0023-0001004.pdf PDF
36C25819B0023-0001003.pdf PDF
36C25819B0023-0001001.pdf PDF
36C25819B0023-0001000.docx DOCX document
36C25819B0023-001.docx DOCX document
36C25819B0023-011.pdf PDF
36C25819B0023-007.pdf PDF
36C25819B0023-006.pdf PDF
36C25819B0023-002.pdf PDF
36C25819B0023-003.pdf PDF
36C25819B0023-010.pdf PDF
36C25819B0023-004.pdf PDF
36C25819B0023-008.pdf PDF
36C25819B0023-005.pdf PDF
36C25819B0023-009.pdf PDF
36C25819B0023-000.docx DOCX document
Show all 25

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

“Void” the re-certification

For door 2D18 install per AE response. For door 2D21 install per AE response. Conflict resolution of hardware was called out in spec section 08 71 00 1.6.B. Double doors at C288A do not need card reader. Door ST02-8 needs card readers on both sides. Entering from stairwell requires card reader to unlock door. Exiting to stairwell requires deactivating local alarm for enough time to exit without triggering it. -Alonso Acosta, COR @VALL 11-29-17

Design Intensive Care Unit Consolidation

N

C

D

S

U B

M I T

T A

L

12-J MAUCHLY

IRVINE, CALIFORNIA 92618

TEL: (949) 450-8420

FAX: (949) 450-8424

A R C H I T E C T U R E + E N G I N E E R I N G C O N S T R U C T I O N M A N A G E M E N T

DOOR SCHEDULE

DOOR SCHEDULE - ALTERNATE BID

DOOR SCHEDULE

VA Loma Linda Healthcare Center VA Project 605-331 Loma Linda, California Design Intensive Care Unit Consolidation

DOOR HARDWARE

08 71 00-1

SECTION 08 71 00

PART 1 - GENERAL

1.1 SUMMARY

A. Section Includes:

1. Door Hardware, including electric hardware.

2. Power supplies for electric hardware

3. Low energy door operators plus sensors and actuators

4. Remote button release hardware

B. Related Sections:

1. Section 08 11 13, HOLLOW METAL DOORS AND FRAMES

2. Section 08 14 23, HIGH IMPACT RESISTANT WOOD DOORS

3. Division 21, FIRE SUPPRESSION

4. Division 26, ELECTRICAL

5. Division 28, ELECTRONIC SAFETY AND SECURITY

C. Specific Omissions: Hardware for the following is specified or indicated elsewhere.

1. Windows

2. Cabinets, including open wall shelving and locks

3. Signs

4. Toilet accessories, including grab bars

5. Installation

6. Rough hardware

7. Conduit, junction boxes and wiring

8. Sliding aluminum ICU doors

9. Corner guards

1.2 REFERENCES

Use date of standard in effect as of Bid Date.

A. American National Standards Institute – ANSI 156.18 – Materials and Finishes

B. BHMA – Builders Hardware Manufacturers Association

C. DHI – Door and Hardware Institute

D. NFPA – National Fire Protection Association

1. NFPA 80 – Fire Doors and Windows

2. NFPA 101 – Life Safety Code

3. NFPA 105 – Smoke and Draft Control Door Assemblies

4. NFPA 252 – Fire Tests of Door Assemblies

08 71 00-2

E. UL – Underwriters Laboratories

1. UL10C – Positive Pressure Fire Tests of Door Assemblies

2. UL 305 – Panic Hardware

F. WHI – Warnock Hersey Incorporated

G. International Building Code

H. Applicable local codes

I. SDI – Steel Door Institute

J. WI – Woodwork Institute

K. AWI – Architectural Woodwork Institute

L. NAAMM – National Association of Architectural Metal Manufacturers

1.3 SUBMITTALS & SUBSTITUTIONS

A. SUBMITTALS: Submit six copies of schedule per Section 01 33 23, SHOP DRAWINGS, PRODUCT DATA, AND SAMPLES. Only submittals printed one sided will be accepted and reviewed. Organize vertically formatted schedule into “Hardware Sets” with index of doors and headings, indicating complete designations of every item required for each door or opening. Include following information:

1. Type, style, function, size, quantity and finish of hardware items

2. Use BHMA Finish codes per ANSI A156.18.

3. Name, part number and manufacturer of each item

4. Fastenings and other pertinent information

5. Description of door location using space names and numbers as published in the drawings.

6. Explanation of abbreviations, symbols, and codes contained in schedule.

7. Mounting locations for hardware

8. Door and frame sizes, handing, materials, fire-rating and degrees of swing

9. List of manufacturers used and their nearest representative with address and phone number

10. Catalog cuts

11. Wiring diagrams

12. Manufacturer’s technical data and installation instructions for electronic hardware

B. Bid and submit manufacturer’s updated/improved item if scheduled item is discontinued.

C. Deviations: Highlight, encircle or otherwise identify deviations from “Schedule of Finish

Hardware” on submittal with notations clearly designating those portions as deviating from this section.

D. If discrepancy between drawings and scheduled material in this section, bid the more expensive of the two choices, note the discrepancy in the submittal and request direction from Architect for resolution.

08 71 00-3

E. Substitutions per Division 1. Include product data and indicate benefit to the Project.

Furnish operating samples on request.

F. Furnish as-built/as-installed schedule with closeout documents, including keying schedule, wiring diagrams, manufacturers’ installation, adjustment and maintenance information, and supplier’s final inspection report.

1.4 QUALITY ASSURANCE

A. Qualifications:

1. Hardware supplier: Direct factory contract supplier who employs a certified

Architectural Hardware Consultant (AHC), available at reasonable times during course of work for project hardware consultation to Owner, Architect and

Contractor.

a) Responsible for detailing, scheduling and ordering of finish hardware.

Detailing implies that the submitted schedule of hardware is correct and complete for the intended function and performance of the openings.

B. Hardware: Free of defects, blemishes and excessive play. Obtain each kind of hardware

(latch and locksets, exit devices, hinges and closers) from one manufacturer.

C. Exit Doors: Operable from inside with single motion without the use of a key or special knowledge or effort.

D. Fire-Rated Openings: NFPA 80 compliant. Hardware UL10C / California State Fire

Marshal Standard 12-7-4 (positive pressure) compliant for given type/size opening and degree of label. Provide proper latching hardware, non-flaming door closers, approved-bearing hinges, and resilient seals. Coordinate with wood door section for required intumescent seals. Furnish openings complete.

1. Note: scheduled resilient seals may exceed selected door manufacturer’s requirements.

2. See 2.6.E for added information regarding resilient and intumescent seals.

E. Furnish hardware items required to complete the work in accordance with specified performance level and design intent, complying with manufacturers’ instructions.

1.5 DELIVERY, STORAGE AND HANDLING

A. Delivery: coordinate delivery to appropriate locations (shop or field).

1. Permanent keys and cores: secured delivery direct to Owner’s representative.

B. Acceptance at Site: Items individually packaged in manufacturers’ original containers, complete with proper fasteners and related pieces. Clearly mark packages to indicate contents, locations in hardware schedule and door numbers.

C. Storage: Provide securely locked storage area for hardware, protect from moisture, sunlight, paint, chemicals, dust, excessive heat and cold, etc.

08 71 00-4

1.6 PROJECT CONDITIONS AND COORDINATION

A. Where exact types of hardware specified are not adaptable to finished shape or size of members requiring hardware, provide suitable types having as nearly as practical the same operation and quality as type specified, subject to Architect’s approval.

B. Coordination: Coordinate hardware with other work. Furnish hardware items of proper design for use on doors and frames of the thickness, profile, swing, security and similar requirements indicated, as necessary for proper installation and function, regardless of omissions or conflicts in the information on the Contract Documents. Furnish related trades with the following information:

1. Location of embedded and attached items to concrete.

2. Location of wall-mounted hardware, including wall stops.

3. Location of finish floor materials and floor-mounted hardware.

4. Locations for conduit and raceways as needed for electrical, electronic and electro-pneumatic hardware items. Fire/life-safety system interfacing. Point-to-point wiring diagrams plus riser diagrams to related trades.

5. Manufacturer templates to door and frame fabricators.

C. Check Shop Drawings for doors and entrances to confirm that adequate provisions will be made for proper hardware installation. Do not order hardware until the submittal has been reviewed by the frame and door suppliers for compatibility with their products.

1.7 WARRANTY

A. Part of respective manufacturers’ regular terms of sale. Provide manufacturers’ written warranties:

1. Extra Heavy Duty Cylindrical Lock: Seven years

2. Exit Devices: Three years mechanical

One year electrical

3. Closers: Ten years

4. Hinges: One year

5. Other Hardware Two years

1.8 COMMISSIONING

A. Conduct these tests prior to request for certificate of substantial completion:

1. With installer present, test door hardware operation with climate control system at rest and while in full operation.

2. With installer, access control contractor and electrical contractor present, test electrical hardware systems for satisfactory operation.

3. With installer and electrical contractor present, test hardware interfaced with fire/life-safety system for proper operation and release.

08 71 00-5

PART 2 - PRODUCTS

2.1 MANUFACTURERS

A. Manufacturers and their abbreviations used in this schedule:

BES Best Access Systems

GLY Glynn-Johnson Hardware

IVE

KEE

H. B. Ives

Keedex, Inc.

KNC K.N. Crowder Mfg., Inc.

LCN LCN Closers

NGP National Guard Products

PEM

SCH

Pemko

Schlage Lock Company

SCE

VON

Schlage Electronics

Von Duprin

2.2 HINGING METHODS

A. Drawings typically depict doors at 90 degrees; doors will actually swing to maximum allowable. Use wide-throw conventional or continuous hinges as needed up to 203.2 mm

(8 inches) in width to allow door to stand parallel to wall for true 180-degree opening.

Advise Architect if 203.2 mm (8 inches) width is insufficient.

B. Conform to manufacturer’s published hinge selection standard for door dimensions, weight and frequency, and to hinge selection as scheduled. Where manufacturer’s standard exceeds the scheduled product, furnish the heavier of the two choices and notify Architect of deviation from scheduled hardware.

2.3 LOCKSETS, LATCHSETS, DEADBOLTS

A. Extra Heavy Duty Cylindrical Locks and Latches: as scheduled.

1. Chassis: cylindrical design, corrosion-resistant plated cold-rolled steel, through-bolted.

2. Locking Spindle: stainless steel, integrated spring and spindle design.

3. Latch Retractors: forged steel. Balance of inner parts: corrosion-resistant plated steel, or stainless steel.

4. Latchbolt: solid steel.

5. Backset: 69.85 mm (2-3/4 inches) typically, more or less as needed to accommodate frame, door or other hardware.

6. Lever Trim: accessible design, independent operation, spring-cage supported, minimum 50.8 mm (2 inches) clearance from lever mid-point to door face.

7. Electric operation: Manufacturer-installed continuous duty solenoid.

08 71 00-6

8. Strikes: 1.626 mm (16 gage) curved steel, bronze or brass with 25.4 mm (1 inch) deep box construction, lips of sufficient length to clear trim and protect clothing.

9. Lock Series and Design: Schlage ND series, “Rhodes” design.

10. Certifications:

a) ANSI A156.2, 1994, Series 4000, Grade 1.

b) UL listed for ‘A’ label and lesser class single doors up to 1220 x 2440 mm (4 x 8 feet).

2.4 EXIT DEVICES / PANIC HARDWARE

A. General features:

1. Independent lab-tested 1,000,000 cycles.

2. Push-through push-pad design. No exposed push-pad fasteners, no exposed cavities when operated. Return stroke fluid dampeners and rubber bottoming dampeners, plus anti-rattle devices.

3. 19.05 mm (0.75 inch) throw deadlocking latchbolts.

4. End caps: impact-resistant, flush-mounted. No raised edges or lips to catch carts or other equipment.

5. No exposed screws to show through glass doors.

6. Non-handed basic device design with center case interchangeable with all functions, no extra parts required to effect change of function.

7. Releasable in normal operation with 66.7 N (15 lbf) maximum operating force per

California State Fire Marshal Standard 12-10-3, and with 142.29 N (32 lbf) maximum pressure under 1111.64 N (250 lbf) load to the door.

8. Where devices span over door lite frame and the face of the selected lite manufacturer’s frame is raised from the face of the door, furnish panic hardware manufacturer’s fitted shims or glass-bead kits at no additional cost to the project.

9. Comply with NFPA 101, Section 7.2.1.7 and IBC Section 1008.1.10.

B. Specific features:

1. Lever Trim: breakaway type, forged brass or bronze escutcheon min 3.3 mm (0.130 inch) thickness, compression spring drive, match lockset lever design.

2. Fire-Labeled Devices: UL label indicating “Fire Exit Hardware”. Vertical rod devices less bottom rod (LBR) unless otherwise scheduled.

3. Electrically Operated Devices: Single manufacturer source for electric latch retraction devices, electrically controlled trim, power transfers, power supplies, monitoring switches and controls.

2.5 CLOSERS

A. Surface Closers:

08 71 00-7

1. Full rack-and-pinion type cylinder with removable non-ferrous cover and cast iron body. Double heat-treated pinion shaft, single piece forged piston, chrome-silicon steel spring.

2. ISO 2000 certified. Units stamped with date-of-manufacture code.

3. Independent lab-tested 10,000,000 cycles.

4. Non-sized and adjustable. Place closers inside building, stairs and rooms.

5. Plates, brackets and special templating when needed for interface with particular header, door and wall conditions and neighboring hardware.

6. Advanced Variable Backcheck (AVB): Where scheduled, these units commence backcheck at approximately 45 degrees.

7. Adjustable to open with not more than 22.23 N (5.0 lbf) pressure to open at exterior doors and 22.23 N (5.0 lbf) at interior doors. As allowed per California

Building Code, Section 1133B.2.5, local authority may increase the allowable pressure for fire doors to achieve positive latching, but not to exceed 66.7 N (15 lbf).

8. Separate adjusting valves for closing speed, latching speed and backcheck, fourth valve for delayed action where scheduled.

9. Non-flaming fluid, will not fuel door or floor covering fires.

10. Pressure Relief Valves (PRV) not permitted.

B. Low-Energy Door Operators: Comply with ANSI/BHMA 156.19. Electric power-open, hydraulically checked spring power closing. Modular construction. Finished metal cover.

Field-adjustable opening force, opening speed, time-open, closing and latching speeds.

Door reopens and timing cycle restores if system reactuated during closing cycle.

Breakaway clutch protection from forced closing. Door, frame, motor and drive train protected by attenuated initiation of opening cycle.

1. Self-contained low-voltage power supply, terminal strip and sequencing for incorporation of electric hardware with system operation.

2.6 OTHER HARDWARE

A. Automatic Flush Bolts: Low operating force design.

B. Overhead Stops: Non-plastic mechanisms and finished metal end caps. Field-changeable hold-open, friction and stop-only functions.

C. Kick Plates: Four beveled edges, 1.27 mm (0.050 inches) minimum thickness, height and width as scheduled. Sheet-metal screws of bronze or stainless steel to match other hardware.

D. Door Stops: Provide stops to protect walls, casework or other hardware.

08 71 00-8

1. Unless otherwise noted in Hardware Sets, provide floor type with appropriate fasteners. Where floor type cannot be used, provide wall type. If neither can be used, provide overhead type.

2. Locate overhead stops for maximum possible opening. Consult with Owner for furniture locations. Minimum: 90 degrees stop / 95 degrees deadstop. Note degree of opening in submittal.

E. Seals: Finished to match adjacent frame color. Resilient seal material: polyurethane, polypropylene, nylon brush, silicone rubber or solid high-grade neoprene as scheduled.

Do not furnish vinyl seal material. UL label applied to seals on rated doors. Substitute products: certify that the products equal or exceed specified material’s thickness and durability.

1. Proposed substitutions: Submit for approval; see Section 01 33 23, SHOP

DRAWINGS, PRODUCT DATA, AND SAMPLES.

2. Solid neoprene: MIL Spec. R6855-CL III, Grade 40

3. Fire-rated Doors, Resilient Seals: UL10C / UBC Standard 7-2 (1997) compliant.

Coordinate with selected door manufacturers' and selected frame manufacturers' requirements. Where rigid housed resilient seals are scheduled in this section and the selected door manufacturer only requires an adhesive-mounted resilient seal, furnish rigid housed seal at minimum, or both the rigid housed seal plus the adhesive applied seal. Adhesive applied seals alone are deemed insufficient for this project where rigid housed seals are scheduled.

4. Fire-rated Doors, Intumescent Seals: Furnished by selected door manufacturer.

Furnish fire-labeled opening assembly complete and in full compliance with

UL10C / UBC Standard 7-2 (1997). Where required, intumescent seals vary in requirement by door type and door manufacture -- careful coordination required.

F. Thresholds: As scheduled and per details. Comply with IBC Section 1008.1.7.

Substitute products: certify that the products equal or exceed specified material’s thickness. Proposed substitutions: submit for approval; see Section 01 33 23, SHOP

DRAWINGS, PRODUCT DATA, AND SAMPLES.

1. Fire-rated openings, 90 minutes or less duration: Use thresholds to interrupt floor covering material under the door where that material has a critical radiant flux value less than 0.22 watts per square centimeter, per NFPA 253. Use threshold unit as scheduled. If none scheduled, request direction from Architect.

2. Acoustic openings: Set units in full bed of Division-7-compliant, leave no air space between threshold and substrate.

3. Plastic plugs with wood or sheet metal screws are not an acceptable substitute for specified fastening methods.

08 71 00-9

4. Fasteners: Generally, exposed screws to be Phillips or Robertson drive. Pinned

TORX drive at high security areas. Flat head sleeve anchors (FHSL) may be slotted drive. Sheet metal and wood screws: full-thread. Sleeve nuts: Full length to prevent door compression.

G. Silencers: Interior hollow metal frames, 3 for single doors, 4 for pairs of doors. Omit where adhesive mounted seal occurs. Leave no unfilled/uncovered pre-punched silencer holes.

2.7 FINISH

A. Generally BHMA 626 Satin Chromium

1. Areas using BHMA 626 to have push-plates, pulls and protection plates of BHMA

630, Satin Stainless Steel, unless otherwise noted.

B. Door closers: Factory powder coated to match other hardware, unless otherwise noted.

C. Aluminum items: Match predominant adjacent material. Seals to coordinate with frame color.

2.8 KEYING REQUIREMENTS

A. Key System: Match existing system. Initiate and conduct meeting(s) with Owner to determine system structure, furnish Owner’s written approval of the system. Furnish temporary construction-keyed and permanent cylinders. Contractor to demonstrate to the

Owner that temporary keys no longer operate the locking cylinders at the end of the project. Permanent keys and cores: use secured shipment direct from point of origination to Owner.

1. For estimate: 3 keys per change combination, 5 master keys per group, 5 grand-master keys, 3 control keys

2. For estimate: VKC stamping plus “Do Not Duplicate”

B. Bitting List: Use secured shipment direct from point of origination to Owner upon completion.

PART 3 - EXECUTION

3.1 ACCEPTABLE INSTALLERS

A. Can read and understand manufacturers’ templates, suppliers’ hardware schedules and printed installation instructions. Can readily distinguish drywall screws from manufacturers’ furnished fasteners. Available to meet with manufacturers’ representatives and related trades to discuss installation of hardware.

3.2 PREPARATION

A. Ensure that walls and frames are square and plumb before hardware installation. Make corrections before commencing hardware installation.

08 71 00-10

B. Locate hardware per SDI-100 and applicable building, fire, life-safety, accessibility, and security codes.

1. Notify Architect of code conflicts before ordering material.

2. Locate levers, key cylinders, t-turn pieces, touchbars, and other operable portions of latching hardware between 864 and 1118 mm (34 and 44 inches) above the finished floor, per ABAAS Section 404.2.7 and IBC Section 1008.1.9.2.

3. Where new hardware is to be installed near existing doors/hardware scheduled to remain, match locations of existing hardware.

C. Overhead stops: Before installing, determine proposed locations of furniture items, fixtures, and other items to be protected by the overhead stop's action.

3.3 INSTALLATION

A. Install hardware per manufacturer’s instructions and recommendations. Do not install surface-mounted items until finishes have been completed on substrate. Set units level, plumb and true to line and location. Adjust and reinforce attachment substrate for proper installation and operation. Remove and reinstall or replace work deemed defective by

Architect.

1. Gaskets: Install jamb-applied gaskets before closers, overhead stops, rim strikes, etc.; fasten hardware over and through these seals. Install sweeps across bottoms of doors before astragals, cope sweeps around bottom pivots, trim astragals to tops of sweeps.

2. When hardware is to be attached to existing metal surface and insufficient reinforcement exists, use RivNuts, NutSerts, or similar anchoring device for screws.

3. Use manufacturers' fasteners furnished with hardware items, or submit Request for Substitution with Architect.

4. Replace fasteners damaged by power-driven tools.

B. Locate floor stops no more than 101.6 mm (4 inches) from walls and not within paths of travel. See Paragraph 2.2 regarding hinge widths, door should be well clear of point of wall reveal. Point of door contact no closer to the hinge edge than half the door width.

Where situation is questionable or difficult, contact Architect for direction.

C. Core concrete for exterior door stop anchors. Set anchors in approved non-shrink grout.

D. Locate overhead stops for minimum 90 degrees and maximum allowable degree of swing.

E. Drill pilot holes for fasteners in wood doors and/or frames. Centerpunch hole locations before using self-drilling type screws to prevent skating. Replace screws that are not centered in their holes.

08 71 00-11

3.4. ADJUSTING

A. Adjust and check for proper operation and function. Replace units, which cannot be adjusted to operate freely and smoothly.

1. Hardware damaged by improper installation or adjustment methods: repair or replace to Owner’s satisfaction.

2. Adjust doors to fully latch with no more than 4.45 N (1 lbf) of pressure.

3. Adjust delayed-action closers on fire-rated doors to fully close from fully-opened position in no more than 10 seconds.

4. Adjust door closers per Article 1.9, this Section.

B. Inspection: Use hardware supplier’s consultant or consultant’s agent. Include supplier's report with closeout documents.

C. Final inspection: Installer to provide letter to Owner that upon completion installer has visited the Project and has accomplished the following:

1. Re-adjust hardware.

2. Evaluate maintenance procedures and recommend changes or additions, and instruct Owner’s personnel.

3. Identify items that have deteriorated or failed.

4. Submit written report identifying problems.

3.5 DEMONSTRATION

A. Demonstrate mechanical hardware and electrical, electronic, and pneumatic hardware systems, including adjustment and maintenance procedures.

3.6 PROTECTION/CLEANING

A. Cover installed hardware, protect from paint, cleaning agents, weathering, carts/barrows, etc. Remove covering materials and clean hardware just prior to substantial completion.

B. Clean adjacent wall, frame and door surfaces soiled from installation/reinstallation process.

3.7 SCHEDULE OF FINISH HARDWARE

A. See door schedule in drawings for hardware set assignments.

SpeXtra: 44553-5

Hardware Group No. 01

Qty Description Catalog Number Finish Mfr

6 EA HW HINGE 5BB1HWSC 5 652 IVE

2 EA OFFSET HINGE COS_FM TP X FULL HEIGHT ALUM PEM

2 EA ELEC PANIC

HARDWARE

QEL+-9827-EO-LBR 4’ 626 VON

2 EA POWER TRANSFER EPT10 689 VON

2 EA ARMORED DR LOOP K-DLA ALUM KEE

08 71 00-12

1 EA SURF. AUTO

OPERATOR

9553 DOUBLE EGRESS ANCLR LCN

2 EA SURF. AUTO

OPERATOR

9542-DD ANCLR LCN

2 EA ACTUATOR, WALL

MOUNT

8310-836T 630 LCN

2 EA KICK PLATE 8400 10" X 2" LDW B4E 630 IVE

2 EA WALL STOP WS407CCV 630 IVE

2 EA SILENCER SR64 GRY IVE

1 EA POWER SUPPLY PS914 900-2RS LGR VON

Free Egress at all times. Pressing Push Bar retracts panic latchbolts. No lever trim. Pressing actuator will retract panic latchbolts and automatically open both doors at the same time.

Hardware Group No. 01A

Qty Description Catalog Number Finish Mfr

6 EA HW HINGE 5BB1HWSC 5 652 IVE

2 EA OFFSET HINGE COS_FM TP X FULL HEIGHT ALUM PEM

2 EA ELEC PANIC

HARDWARE

QEL+-9827-EO-LBR 4’ 626 VON

2 EA POWER TRANSFER EPT10 689 VON

2 EA ARMORED DR LOOP K-DLA ALUM KEE

1 EA SURF. AUTO

OPERATOR

9553 DOUBLE EGRESS ANCLR LCN

2 EA SURF. AUTO

OPERATOR

9542-DD ANCLR LCN

2 EA ACTUATOR, WALL

MOUNT

8310-836T 630 LCN

2 EA KICK PLATE 8400 10" X 2" LDW B4E 630 IVE

2 EA WALL STOP WS407CCV 630 IVE

2 EA SWITCH CONV KIT RX2 SWITCH KIT VON

2 EA DR CONTACT SWITCH 679-05HM BLK SCE

1 EA DELAY EGRESS

EMLOCK

1511T SDC

1 EA POWER SUPPLY PS914 900-2RS LGR VON

Free Egress at all times. Pressing Push Bar retracts panic latchbolts. No lever trim. Pressing actuator will retract panic latchbolts and automatically open both doors at the same time.

RFI C-138 OPENING C-271

Panic device to add RX2 switch kit Card reader and wiring to provide by access control system SECURE SIDE – RX2 switch to active delayed egress maglock NON SECURE SIDE – RX2 to shunt the alarm system and deactivate delay egress maglock SECURE SIDE - Card reader to interface with wall mounted actuator and deactivate delay egress maglock, shunt RX switch, and activate auto door operator.

NON SECURE SIDE – wall mounted actuator or push bar RX switch to deactivate delay egress maglock and active auto door operator.

08 71 00-13

Hardware Group No. 03

6 EA HW HINGE 5BB1HW 5 X 4.5 652 IVE

2 EA CONT HINGE CFM X FULL HEIGHT ALUM PEM

1 EA FIRE EXIT HARDWARE 9827-EO-F-LBR-499F 626 VON

1 EA FIRE EXIT HARDWARE 9827-L-BE-F-996-06 626 LBR

2 EA SURFACE CLOSER 4011 DEL 689 LCN

2 EA KICK PLATE 8400 10" X 1" LDW B4E 630 IVE

2 EA WALL STOP WS407CCV 630 IVE

1 SET SEALS 5050B 22’ BRN NGP

1 SET ASTRAGAL 137NA CL NGP

Hardware Group No. 03A

6 EA HW HINGE 5BB1HW 4.5 X 4.5 652 IVE

2 EA CONT HINGE CFM X FULL HEIGHT ALUM PEM

1 EA PANIC HARDWARE 9827-EO-LBR-499F 626 VON

1 EA PANIC HARDWARE 9827-L-BE-996-06 626 LBR

2 EA SURFACE CLOSER 4011 DEL 689 LCN

2 EA KICK PLATE 8400 10" X 1" LDW B4E 630 IVE

2 EA WALL STOP WS407CCV 630 IVE

Hardware Group No. 03B

6 EA HW HINGE 5BB1HW 4.5 X 4.5 652 IVE

2 EA ELECTRIFIED HINGE 5BB1HW 4.5 X 4.5 TW8 652 IVE

2 EA CONT HINGE CFM X PT X FULL HEIGHT ALUM PEM

2 EA POWER TRANSFER EPT10 689 VON

1 EA ELEC FIRE EXIT

HARDWARE

QEL+-9827-L-DT-F-LBR-996-06-499F 626 VON

08 71 00-14

1 EA ELEC FIRE EXIT

HARDWARE

QEL+-9827-L-NL-F-996-06 626 VON

1 EA SFIC RIM CYLINDER 12E72RP3 626 BES

1 EA PERMANENT CORE 1C7D2 626 BES

2 EA SURFACE CLOSER 4011 DEL 689 LCN

2 EA KICK PLATE 8400 10" X 1" LDW B4E 630 IVE

2 EA WALL STOP WS407CCV 630 IVE

1 SET SEALS 5050B 20’ BRN NGP

1 EA POWER SUPPLY PS914 900-2RS LGR VON

CARD READER & WIRING PART OF ACCESS CONTROL SECTION.

Hardware Group No. 04

2 EA HW HINGE 5BB1HW 5 X 4.5 652 IVE

1 EA ELECTRIC HW HINGE 5BB1HW 5 X 4.5 TW8 652 IVE

1 EA CONT HINGE CFM X PT X FULL HEIGHT ALUM PEM

1 EA POWER TRANSFER EPT10 689 VON

1 EA EU STOREROOM LOCK ND80BDCDEU RHO XN123-062 626 SCH

1 EA PERMANENT CORE 1C7D2 626 BES

1 EA SURFACE CLOSER 4011 DEL 689 LCN

1 EA KICK PLATE 8400 10" X 2" LDW B4E 630 IVE

1 EA FLOOR STOP FS436 626 IVE

1 SET SEALS 5050B 18’ BRN NGP

1 EA POWER SUPPLY PS902 LGR SCE

CARD READER & WIRING PART OF ACCESS CONTROL SECTION.

Hardware Group No. 05A

Qty Description Catalog Number Finish Mfr

6 EA HW HINGE 5BB1HW 5 X 4.5 652 IVE

2 EA CONT HINGE CFM X FULL HEIGHT ALUM PEM

2 EA CONT HINGE CFM X PT X FULL HEIGHT ALUM PEM

2 EA POWER TRANSFER EPT10 689 VON

1 EA PANIC HARDWARE 9827-EO-LBR-499F 4’ 626 VON

1 EA PANIC HARDWARE 9827-L-996-06-299F 4’ 626 VON

2 EA SWITCH CONV KIT RX2 SWITCH KIT VON

2 EA DR CONTACT SWITCH 679-05HM BLK SCE

1 EA ELECTRIFIED TRIM E996L-06 FAIL SECURE 626BLK SCE

1 EA SFIC RIM CYLINDER 80-116 626 SCH

1 EA PERMANENT CORE 1C7D2 626 BES

2 EA SURFACE CLOSER 4111 DEL SCUSH 689 LCN

2 EA KICK PLATE 8400 10" X 1" LDW B4E 630 IVE

08 71 00-15

1 SET ASTRAGAL 137NA 84” CL NGP

RFI C-140 OPENING C288A

Panic device to add RX2 switch kit Card reader and wiring to provide by access control system SECURE SIDE – card reader to activate electrified lever trim and deactivate alarm system and security system NON SECURE SIDE – RX2 to deactivate the alarm system and security system revised

Hardware Group No. 06

Qty Description Catalog Number Finish Mfr

3 EA HW HINGE, SWING

CLEAR

5BB1HWSC 5 652 IVE

1 EA OFFSET HINGE COS_FM X FULL HEIGHT ALUM PEM

1 EA CLASSROOM LOCK ND70BDCD RHO 626 SCH

1 EA PERMANENT CORE 1C7D2 626 BES

1 EA SURFACE CLOSER 4011 DEL 689 LCN

1 EA KICK PLATE 8400 10" X 2" LDW B4E 630 IVE

Hardware Group No. 07

3 EA HW HINGE, SWING

CLEAR

5BB1HWSC 5 652 IVE

1 EA OFFSET HINGE COS_FM X FULL HEIGHT ALUM PEM

1 EA PASSAGE SET ND10S RHO 626 SCH

1 EA OH STOP 106S 630 GLY

3 EA SILENCER SR64 GRY IVE

Hardware Group No. 08

3 EA HINGE 5BB1 4.5 X 4.5 652 IVE

1 EA CONT HINGE CFM X FULL HEIGHT ALUM PEM

1 EA ENTRANCE LOCK ND53BDCD RHO 626 SCH

1 EA PERMANENT CORE 1C7D2 626 BES

1 EA FLOOR STOP FS436 626 IVE

Hardware Group No. 08A

08 71 00-16

3 EA HINGE 5BB1 4.5 X 4.5 652 IVE

1 EA CONT HINGE CFM X FULL HEIGHT ALUM PEM

1 EA ENTRANCE LOCK ND53BDCD RHO 626 SCH

1 EA PERMANENT CORE 1C7D2 626 BES

1 EA SURFACE CLOSER 4011 DEL 689 LCN

1 EA FLOOR STOP FS436 626 IVE

Hardware Group No. 09

3 EA HINGE 5BB1 4.5 X 4.5 652 IVE

1 EA CONT HINGE CFM X FULL HEIGHT ALUM PEM

1 EA PASSAGE SET ND10S RHO 626 SCH

Hardware Group No. 10

3 EA HINGE 5BB1 4.5 X 4.5 652 IVE

1 EA CONT HINGE CFM X FULL HEIGHT ALUM PEM

1 EA PASSAGE SET ND10S RHO 626 SCH

1 EA SURFACE CLOSER 4011T BUMP 689 LCN

Hardware Group No. 11

3 EA HINGE 5BB1 4.5 X 4.5 652 IVE

1 EA CONT HINGE CFM X FULL HEIGHT ALUM PEM

1 EA PRIVACY LOCK ND40S RHO 626 SCH

1 EA SURFACE CLOSER 4111 DEL SCUSH 689 LCN

Hardware Group No. 12

3 EA HINGE 5BB1 4.5 X 4.5 652 IVE

1 EA CONT HINGE CFM X FULL HEIGHT ALUM PEM

1 EA PRIVACY LOCK ND40S RHO 626 SCH

08 71 00-17

1 EA SURFACE CLOSER 4011 DEL 689 LCN

1 EA MOP PLATE 8400 4" X 1" LDW B4E 630 IVE

1 EA WALL STOP WS407CCV 630 IVE

Hardware Group No. 13

3 EA HINGE 5BB1 4.5 X 4.5 652 IVE

1 EA CONT HINGE CFM X FULL HEIGHT ALUM PEM

1 EA PRIVACY LOCK ND40S RHO 626 SCH

1 EA WALL STOP WS407CCV 630 IVE

3 EA SILENCER SR64 GRY IVE

Hardware Group No. 14

ALL HARDWARE PROVIDED BY DOOR MANUFACTURER.

Hardware Group No. 15

6 EA HW HINGE, SWING

CLEAR

5BB1HWSC 5 652 IVE

2 EA OFFSET HINGE COS_FM X FULL HEIGHT ALUM PEM

1 EA CONST LATCHING

BOLT

FB61T (USA) 630 IVE

1 EA HOSPITAL PRIVACY ND44S RHO 626 SCH

2 EA OH STOP 104S-ADJ 630 GLY

2 EA KICK PLATE 8400 10" X 1" LDW (11”) B4E 630 IVE

2 EA KICK PLATE 8400 10” X 1” LDW (35”) B4E 628 IVE

1 EA ASTRAGAL 158NA 84” CL NGP

2 EA SILENCER SR64 GRY IVE

1 EA WALL BUMPER WS407CCV (INACTIVE LEAF) 630 IVE

Hardware Group No. 15A

Qty Description Catalog Number Finish Mfr

1 EA TRACK SYSTEM C-105-4 KNC

1 EA HANDICAP DOOR LOCK C-92L-HL 626 KNC

1 EA FLUSH PULL C90B 626 KNC

1 SET ASTRAGAL 137NA CL NGP

2 EA DOOR SWEEP 601A CL NGP

Hardware Group No. 18

08 71 00-18

3 EA HINGE 5BB1 4.5 X 4.5 652 IVE

1 EA CONT HINGE CFM X FULL HEIGHT ALUM PEM

1 EA PASSAGE SET ND10S RHO 626 SCH

1 EA SURFACE CLOSER 4011 689 LCN

1 EA KICK PLATE 8400 10" X 2" LDW B4E 630 IVE

Hardware Group No. 19

3 EA HW HINGE 5BB1HW 4.5 X 4.5 652 IVE

1 EA CONT HINGE CFM X FULL HEIGHT ALUM PEM

1 EA STOREROOM LOCK ND80BDCD RHO 626 SCH

1 EA PERMANENT CORE 1C7D2 626 BES

1 EA OH STOP 904S 630 GLY

1 EA ARMOR PLATE 8400 34" X 2" LDW B4E 630 IVE

1 EA EDGE GUARD 7305 84" EDGE WD

(CUT AS REQ.)

US32D IVE

Hardware Group No. 20

3 EA HINGE 5BB1 4.5 X 4.5 652 IVE

1 EA CONT HINGE CFM X FULL HEIGHT ALUM PEM

1 EA STOREROOM LOCK ND80BDCD RHO 626 SCH

1 EA PERMANENT CORE 1C7D2 626 BES

1 EA SURFACE CLOSER 4111 DEL 689 LCN

1 EA WALL STOP WS407CCV 630 IVE

1 SET SEALS 5050B 17’ BRN NGP

Hardware Group No. 20A

3 EA HINGE 5BB1 4.5 X 4.5 652 IVE

1 EA CONT HINGE CFM X FULL HEIGHT ALUM PEM

1 EA CONT HINGE CFM X PT FULL HEIGHT ALUM PEM

1 EA POWER TRANSFER EPT10 689 VON

1 EA STOREROOM LOCK ND80BDCD RHO 626 SCH

1 EA EU STOREROOM LOCK ND80BDCDEU RHO XN123-062 626 SCH

1 EA PERMANENT CORE 1C7D2 626 BES

1 EA SURFACE CLOSER 4111 DEL 689 LCN

08 71 00-19

Hardware Group No. 22A

3 EA HINGE 5BB1 4.5 X 4.5 652 IVE

1 EA CONT HINGE CFM X FULL HEIGHT ALUM PEM

1 EA CLASSROOM LOCK ND70BDCD RHO 626 SCH

1 EA PERMANENT CORE 1C7D2 626 BES

1 EA SURFACE CLOSER 4011 DEL 689 LCN

1 EA KICK PLATE 8400 10" X 2" LDW B4E 630 IVE

SET CLOSER DELAY TO 10 SECONDS.

Hardware Group No. 22B

3 EA HINGE 5BB1 4.5 X 4.5 652 IVE

1 EA CONT HINGE CFM X PT FULL HEIGHT ALUM PEM

1 EA POWER TRANSFER EPT10 689 VON

1 EA CLASSROOM LOCK ND70BDCD RHO 626 SCH

1 EA EU STOREROOM LOCK ND80BDCDEU RHO XN123-062 626 SCH

1 EA PERMANENT CORE 1C7D2 626 BES

1 EA SURFACE CLOSER 4011 DEL 689 LCN

1 EA KICK PLATE 8400 10" X 2" LDW B4E 630 IVE

1 EA FLOOR STOP FS436 626 IVE

SpeXtra: 268166

Hardware Group No. 23

Qty

Description

Catalog Number

Finish

Mfr

DOOR HARDWARE

08 71 00-20

1 EA TRACK SYSTEM C105-4 KITS AL KNC

1 EA FASCIA C110 AL KNC

1 EA HANDICAP DOOR LOCK C-92L X (2) C90HL 630 KNC

2 EA LUSH PULL C90B 630 KNC

1 EA SEAL 137NA 628 NGP

1 EA DOOR SWEEP 601A 628 NGP

DOOR SIZE TO BE LARGER THAN OPENING SIZE

DOOR WIDTH TO BE 36" WIDE OVERLAPPING ONE JAMB TO PROVIDE 34" CLEAR WIDTH

HANDICAP DOOR LOCK WITH 2 HANDLE LEVER C90HL

HANDICAP DOOR LOCK STRIKE LATCH TO CUSTOM STRIKE BRACKET

- - - END - - -

Quantity Part# Description

2 HINGES

PEMKO #CFM83HD1 x ACC8 ALUM. FINISH (MARK #2018 & 2D21)

2 LOCKS

SCHLAGE #ND80BDCEU RHO x N123-062 ELEC. STOREROOM CYL. LOCK 626

FINISH (MARK #2018 & 2D21)

2 INSTALLATION

DRILL WIRE CHASE FROM ELEC. CYL. LOCK TO HINGE EDGE (MARK #2018 &

2D21)

3 AUXILIARY HARDWARE

VON-DUPRIN #PS902 POWER SUPPLY (MARK #2D18, 2D21, & ST02-8)

1 AUXILIARY HARDWARE

VON-DUPRIN #040065-00 RX-QEL BASEPLATE CONVERTION KIT - 4' (MARK

#ST02-8)

1 AUXILIARY HARDWARE

KEEDEX #K-DL38A ARMORED DOOR LOOP 3/8" 1.D. FLEX (18") ALUM. FINISH

(MARK #ST02-8)

TRIM

VON-DUPRIN #996L-NL-06 LEVER TRIM US26D FINISH (MARK #ST02-8)

INSTALLATION

ADDED LABOR TO INSTALL NEW REQUESTED HDWE. AT EXISTING MARK #ST02-

8, DRILL FRAME TO PULL WIRE THROUGH, PULL WIRE THROUGH WIRE CHASE,

MAKE HINGE AND LOCK WIRE CONNECTION AT MARK #'S 2D18 & 2D21 (6

HOURS X $75 PER HOUR)

Security Solutions Proposal LA16-047 CO3 December 6, 2017

Proprietary Information Prepared for VA Loma Linda – Herman Construction

Use or disclosure of data contained on this sheet is subject to the restriction on the title page of this proposal

Schedule I

Scope of work

Security Solutions offers to provide equipment, installation, termination and programming, per RFI#140 response for (1) In/Out card reader and (1) Local alarm to be installed at Stairwell ST2-8. The card reader installed within the stairwell will allow access employees using their PIV badge. The card reader installed within the suite will connect to a local alarm that will sound and will send an alarm event to the Police department notifying them that a person without access has opened that door. Door

C288A does not require a card reader, so a credit is included for that door, as requested by VA Loma Linda:

Building Access Control System Components

Qty. Description

1 -1 Single Reader Interface Module

2 -1 PIV II Card Reader, FIPS 201 compliant

3 -0.25 22/4 Cable, Plenum, Yellow

4 -0.25 18/2 Cable, Plenum, Green

5 -0.25 22/6 Cable, Plenum, Purple

6 -0.25 22/4 Cable, Plenum, Orange

7 -1 Resistor

8 2 Reader Interface Module

9 2 PIV II Card Reader, FIPS 201 compliant

10 0.75 22/4 Cable, Plenum, Yellow

11 0.75 18/2 Cable, Plenum, Green

12 0.75 22/6 Cable, Plenum, Purple

13 0.75 22/4 Cable, Plenum, Orange

14 1 Exit Local Alarm

15 2 Resistor

16 2 Hoffman Enclosure 12.00 x 12.00 x 4.00

17 2 Hoffman Back Panel 10.25 x 10.25

18 2 Hoffman Lock Kit

19 2 Tamper Switch for Hoffman enclosures & Power supplies

20 1 Misc: Fuses, tamper switches, EOL resistors