About this file

36C25819B0023 0001 S02 Bridge 1 120 V 20 Amp pwr Med Gas Panel r.pdf

View the file

Other files

File Type Posted
36C25819B0023-0003002.pdf PDF
36C25819B0023-0003003.pdf PDF
36C25819B0023-0003000.docx DOCX document
36C25819B0023-0003001.pdf PDF
36C25819B0023-0002011.pdf PDF
36C25819B0023-0002012.pdf PDF
36C25819B0023-0002010.docx DOCX document
36C25819B0023-0002013.pdf PDF
36C25819B0023-0001005.pdf PDF
36C25819B0023-0001004.pdf PDF
36C25819B0023-0001003.pdf PDF
36C25819B0023-0001002.pdf PDF
36C25819B0023-0001000.docx DOCX document
36C25819B0023-001.docx DOCX document
36C25819B0023-011.pdf PDF
36C25819B0023-007.pdf PDF
36C25819B0023-006.pdf PDF
36C25819B0023-002.pdf PDF
36C25819B0023-003.pdf PDF
36C25819B0023-010.pdf PDF
36C25819B0023-004.pdf PDF
36C25819B0023-008.pdf PDF
36C25819B0023-005.pdf PDF
36C25819B0023-009.pdf PDF
36C25819B0023-000.docx DOCX document
Show all 25

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

R.F.I.

(REQUEST FOR INFORMATION)

Project #: 605-331 RFI #: C – 122

Project Name: Intensive Care Unit Consolidation Date Requested: 4/24/17

Solicitation No.: VA262-15-J-6178 Reference: Med gas Alarm panels

Drawing:

Drawing PP101

Specification Section:

DESCRIPTION OF PROBLEM OR INFORMATION REQUESTED

ISSUE:

1- Electrical drawing doesn't show any power for Med gas Alarm panels, as per the cut sheet is required 115 volt or 230 VAC primary power .Please specified the circuit will use for that.

2- This is not enough space between studs in are showing on the plan to be install.

3- This is no height for the Alarm panels

PROPOSED SOLUTION:

For number 2 Stacked or side by side when relocate to column #13.

OWNER RESPONSE

OWNER TRACKING No.: AMEND No.:

VA Project Engineer/Manager: Date:

Please provide circuit 2EX2-13 for alarm panel, proposed solution for number 2 is acceptable, Nasser Nejati @IMEG-TTG 4/24/17

Panels can be mounted between 42" to 48" max. a.f.f.

KAL, 4/25/2017

Description of Work

POWER FOR - MED GAS PANEL

As directed by RFI# C-122 provide 120 volt 20 amp power for Med Gas panel.

Furnish and install conduit, supports, wire and back box and connection to panel.

Using circuit 2EX2-13