Attachment A CTX Fire Damper Repair List.xlsx
XLSX spreadsheet 1 MB Posted
- Solicitation number
- 36C25727Q0050
About this file
Summary of Attachment A: CTX Fire Damper Repair List
This is a comprehensive fire damper inspection and repair list documenting deficiencies identified across multiple Veterans Affairs facilities in Waco and Temple, Texas. The document details inspection results for fire dampers (FD), smoke dampers (SD), radiant dampers (RD), and fire/smoke dampers (FS) at seven buildings: Waco Buildings 4, 7, 11, 90, and 91, and Temple Buildings 163, 202, 204, 205, 221, and 222. Each entry identifies a specific damper ID, its location by facility, building, and floor, the damper type, inspection result (Pass, Fail, or Inaccessible), the identified issue or condition, and the required correction or remediation.
Common deficiencies across all facilities include dampers that will not close or are stuck (requiring replacement), inaccessible dampers and access panels due to obstructions such as ceiling grids, light fixtures, sprinkler systems, conduit, and other infrastructure (requiring relocation of either the damper, access panel, or obstruction), missing access panels (requiring installation), dampers without installed units (requiring new damper installation), access panels that are too small or stuck shut (requiring enlargement or replacement), and dampers that cannot be located from provided plans (requiring search efforts and potential new installation). The repairs encompass multiple correction strategies including damper replacement, access panel installation or modification, relocation of dampers or panels to accessible locations, and removal of blocking infrastructure to ensure compliance with fire safety requirements.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| 36C25727Q0050.pdf | ||
| SCA WD 2015-5261 rv.31 08-17-2026.pdf | ||
| SCA WD 2015-5237 rv.32 08-17-2026.pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Waco Bldg 4
| Damper ID | Facility | Building | Floor | Damper Type | Result | Issue | Correction |
| FD-B-003 | Waco | 4 | Basement | FD | Inacessible | Install access panel | |
| FD-A-001 | Waco | 4 | Attic | FD | Fail | Damper will not close | Replace damper |
| FD-A-001A | Waco | 4 | Attic | FD | Pass | Damper has been damaged | Replace damper |
| FD-A-003 | Waco | 4 | Attic | FD | Inacessible | Access panel is too small | Install larger access panel |
| FD-A-004 | Waco | 4 | Attic | FD | Inacessible | Not accessible in current location. | Install damper and access panel in accessible location. |
| FD-A-006 | Waco | 4 | Attic | FD | Inacessible | Access panel is too small | Install larger access panel |
| FD-A-007 | Waco | 4 | Attic | FD | Inacessible | Access panel is too small | Install larger access panel |
| FD-A-008 | Waco | 4 | Attic | FD | Inacessible | Damper located too far from the access panel. | Relocate the damper closer to accessible position. |
| Dampers that can not be found | |||||||
| FD-1-010 | Waco | 4 | 1 | FD | Could not locate damper with information provided | Search for damper and if one can't be found add new damper and access panel |
Waco Bldg 7
| Damper ID | Facility | Building | Floor | Damper Type | Result | Issue / Condition | Correction |
| FD-B-004 | Waco | 7 | Basement | FD | Inaccessible | Damper cannot be accessed | Relocate damper |
| FD-B-007 | Waco | 7 | Basement | FD | Fail | Damper did not close | Replace damper |
| FD-1-001 | Waco | 7 | 1 | FD | Inaccessible | Damper could not be accessed due to hard ceiling | Install access panel in hard ceiling |
| FD-1-003 | Waco | 7 | 1 | FD | Fail | Damper will not close | Replace damper |
| FD-1-006 | Waco | 7 | 1 | FD | Inaccessible | Damper could not be accessed due to hard ceiling | Install access panel in hard ceiling |
| FD-1-013 | Waco | 7 | 1 | FD | Fail | Damper did not close | Replace damper |
| FD-2-007 | Waco | 7 | 2 | FD | Inaccessible | Damper cannot be accessed | Modify duct |
| FD-2-009 | Waco | 7 | 2 | FD | Inaccessible | Access panel would not open | Install new access panel in hard ceiling |
| FD-2-017 | Waco | 7 | 2 | FD | Inaccessible | Access panel would not open | Install new access panel in hard ceiling |
| FD-2-018 | Waco | 7 | 2 | FD | Inaccessible | Damper is located above a light fixture | Relocate light fixture or damper/access panel |
| FD-A-003 | Waco | 7 | Attic | FD | Fail | Damper broken and is zip-tied open. | Replace damper. |
| FD-A-008 | Waco | 7 | Attic | FD | Inaccessible | No access panel. | Install an access panel. |
| Dampers that can not be found | |||||||
| FD-B-006 | Waco | 7 | Basement | FD | Could not be located with information provided | Search for damper, if one is not found install new damper and access panel. |
Waco Bldg 11
| Damper ID | Facility | Building | Floor | Damper Type | Result | Issue | Correction |
| FD-1-004 | Waco | 11 | 1 | FD | Pass | Recommend installing an access panel | |
| FD-1-008 | Waco | 11 | 1 | FD | Inaccessible | Damper cannot be reached from access panel | Install access panel in different location |
| FD-1-011 | Waco | 11 | 1 | FD | Inaccessible | Light blocking access | Relocate light |
| FD-1-012 | Waco | 11 | 1 | FD | Fail | Damper will not close | Replace damper |
| FD-1-016 | Waco | 11 | 1 | FD | Fail | Damper will not close | Replace damper |
| FD-2-010 | Waco | 11 | 2 | FD | Fail | Damper will not close | Replace damper |
| FD-2-014 | Waco | 11 | 2 | FD | Inaccessible | Damper not accessible in current location | Cut in access panel on the other side of duct |
| FD-2-015 | Waco | 11 | 2 | FD | Inaccessible | Damper not accessible in current location | Relocate damper to allow access |
| FD-2-019 | Waco | 11 | 2 | FD | Inaccessible | Light blocking access | Install an access panel on the side of the duct |
| FD-A-001 | Waco | 11 | Attic | FD | Fail | Damper will not close | Install damper |
| FD-A-002 | Waco | 11 | Attic | FD | Fail | Damper will not close | Install damper |
| FD-A-004 | Waco | 11 | Attic | FD | Fail | Damper will not close | Install damper |
| FD-A-005 | Waco | 11 | Attic | FD | Fail | Damper will not close | Install damper |
| FD-A-006 | Waco | 11 | Attic | FD | Fail | Damper will not close | Install damper |
| FD-A-011 | Waco | 11 | Attic | FD | Fail | Damper will not close | Replace damper |
| FD-A-012 | Waco | 11 | Attic | FD | Fail | Damper will not close | Replace a horizontal damper |
Waco Bldg 90
| Damper ID | Facility | Building | Floor | Damper Type | Result | Issue | Correction |
| FD-B-008 | Waco | 90 | Basement | FD | Fail | damper stuck | replace damper |
| FD-B-009 | Waco | 90 | Basement | FD | Inaccessible | ceiling grid blocking access | relocate access panel |
| FD-1-001 | Waco | 90 | 1 | FD | Inaccessible | Damper located behind grill; it must be readily accessible. | Install grille with hinged access to dampers |
| FD-1-002 | Waco | 90 | 1 | FD | Inaccessible | Damper located behind grill; it must be readily accessible. | Install grille with hinged access to dampers |
| FD-1-003 | Waco | 90 | 1 | FD | Inaccessible | Damper located behind grill; it must be readily accessible. | Install grille with hinged access to dampers |
| FD-1-004 | Waco | 90 | 1 | FD | Inaccessible | Damper located behind grill; it must be readily accessible. | Install grille with hinged access to dampers |
| FD-1-005 | Waco | 90 | 1 | FD | Inaccessible | Damper located behind grill; it must be readily accessible. | Install grille with hinged access to dampers |
| FD-1-006 | Waco | 90 | 1 | FD | Inaccessible | Damper located behind grill; it must be readily accessible. | Install grille with hinged access to dampers |
| FD-1-007 | Waco | 90 | 1 | FD | Inaccessible | Damper located behind grill; it must be readily accessible. | Install grille with hinged access to dampers |
| FD-1-008 | Waco | 90 | 1 | FD | Inaccessible | Damper located behind grill; it must be readily accessible. | Install grille with hinged access to dampers |
| FD-1-010 | Waco | 90 | 1 | FD | Inaccessible | damper cannot be reached from access panel. | modify duct or relocate access panel or damper. |
| FD-1-011 | Waco | 90 | 1 | FD | Fail | dampers stuck | replace dampers |
| FD-1-015 | Waco | 90 | 1 | FD | Inaccessible | Damper located behind grill; it must be readily accessible. | Install grille with hinged access to dampers |
| FD-1-016 | Waco | 90 | 1 | FD | Inaccessible | Damper located behind grill; it must be readily accessible. | Install grille with hinged access to dampers |
| FD-1-017 | Waco | 90 | 1 | FD | Inaccessible | Damper located behind grill; it must be readily accessible. | Install grille with hinged access to dampers |
| FD-1-018 | Waco | 90 | 1 | FD | Inaccessible | Damper located behind grill; it must be readily accessible. | Install grille with hinged access to dampers |
| FD-1-019 | Waco | 90 | 1 | FD | Inaccessible | Damper located behind grill; it must be readily accessible. | Install grille with hinged access to dampers |
| FD-1-020 | Waco | 90 | 1 | FD | Inaccessible | Damper located behind grill; it must be readily accessible. | Install grille with hinged access to dampers |
| FD-1-021 | Waco | 90 | 1 | FD | Inaccessible | Damper located behind grill; it must be readily accessible. | Install grille with hinged access to dampers |
| FD-1-022 | Waco | 90 | 1 | FD | Inaccessible | Damper located behind grill; it must be readily accessible. | Install grille with hinged access to dampers |
| FD-1-025 | Waco | 90 | 1 | FD | Inaccessible | access panel will not open due to toilet partition | relocate access panel or damper |
| FD-2-001 | Waco | 90 | 2 | FD | Inaccessible | Damper located behind grill; it must be readily accessible. | Install grille with hinged access to dampers |
| FD-2-002 | Waco | 90 | 2 | FD | Inaccessible | Damper located behind grill; it must be readily accessible. | Install grille with hinged access to dampers |
| FD-2-003 | Waco | 90 | 2 | FD | Inaccessible | Damper located behind grill; it must be readily accessible. | Install grille with hinged access to dampers |
| FD-2-004 | Waco | 90 | 2 | FD | Inaccessible | Damper located behind grill; it must be readily accessible. | Install grille with hinged access to dampers |
| FD-2-005 | Waco | 90 | 2 | FD | Inaccessible | Damper located behind grill; it must be readily accessible. | Install grille with hinged access to dampers |
| FD-2-006 | Waco | 90 | 2 | FD | Inaccessible | Damper located behind grill; it must be readily accessible. | Install grille with hinged access to dampers |
| FD-2-007 | Waco | 90 | 2 | FD | Inaccessible | Damper located behind grill; it must be readily accessible. | Install grille with hinged access to dampers |
| FD-2-008 | Waco | 90 | 2 | FD | Inaccessible | Damper located behind grill; it must be readily accessible. | Install grille with hinged access to dampers |
| FD-2-010 | Waco | 90 | 2 | FD | Fail | damper stuck | replace damper |
| FD-2-011 | Waco | 90 | 2 | FD | Inaccessible | Damper located behind grill; it must be readily accessible. | Install grille with hinged access to dampers |
| FD-2-012 | Waco | 90 | 2 | FD | Inaccessible | Damper located behind grill; it must be readily accessible. | Install grille with hinged access to dampers |
| FD-2-013 | Waco | 90 | 2 | FD | Inaccessible | Damper located behind grill; it must be readily accessible. | Install grille with hinged access to dampers |
| FD-2-014 | Waco | 90 | 2 | FD | Inaccessible | Damper located behind grill; it must be readily accessible. | Install grille with hinged access to dampers |
| FD-2-015 | Waco | 90 | 2 | FD | Inaccessible | Damper located behind grill; it must be readily accessible. | Install grille with hinged access to dampers |
| FD-2-016 | Waco | 90 | 2 | FD | Inaccessible | Damper located behind grill; it must be readily accessible. | Install grille with hinged access to dampers |
| FD-2-017 | Waco | 90 | 2 | FD | Inaccessible | Damper located behind grill; it must be readily accessible. | Install grille with hinged access to dampers |
| FD-2-018 | Waco | 90 | 2 | FD | Inaccessible | Damper located behind grill; it must be readily accessible. | Install grille with hinged access to dampers |
| FD-2-020 | Waco | 90 | 2 | FD | Fail | damper stuck | replace damper |
| FD-A-001 | Waco | 90 | Attic | FD | Inaccessible | no access panel | install access panel |
| FD-A-002 | Waco | 90 | Attic | FD | Inaccessible | access panel stuck closed | replace access panel |
| FD-A-003 | Waco | 90 | Attic | FD | Inaccessible | access panel stuck closed | install new panel top of duct |
| FD-A-004 | Waco | 90 | Attic | FD | Fail | damper stuck | replace damper |
| FD-A-005 | Waco | 90 | Attic | FD | Inaccessible | access panel stuck closed | replace access panel |
| FD-A-006 | Waco | 90 | Attic | FD | Inaccessible | access panel stuck closed | replace access panel |
Waco Bldg 91
| Damper ID | Facility | Building | Floor | Damper Type | Result | Issue | Correction |
| FD-1-004 | Waco | 91 | 1 | FD | Fail | access door stuck | replace access door |
| FD-2-006 | Waco | 91 | 2 | FD | Fail | falling apart | replace damper |
| FD-2-007 | Waco | 91 | 2 | FD | Inaccessible | no access | install access panel |
| FD-2-008 | Waco | 91 | 2 | FD | Fail | will not close | replace damper |
| FD-2-009 | Waco | 91 | 2 | FD | Fail | will not close | replace damper |
| FD-2-010 | Waco | 91 | 2 | FD | Fail | will not close | replace damper |
| FD-A-001 | Waco | 91 | Attic | FD | Fail | Damper will not close due to fire/smoke duct detector wires | Get wires out of the duct and into a conduit |
| FD-A-004 | Waco | 91 | Attic | FD | Inaccessible | not accessible | install new access panel side of duct |
| FD-A-005 | Waco | 91 | Attic | FD | Fail | damper will not close | replace damper |
| FD-A-006 | Waco | 91 | Attic | FD | Inaccessible | not accessible | modify duct |
| FD-A-012 | Waco | 91 | Attic | FD | Inaccessible | turning vanes in way, access door too small | modify duct |
| FD-A-024 | Waco | 91 | Attic | FD | Fail | will not close | replace damper |
| FD-A-028 | Waco | 91 | Attic | FD | Fail | stuck closed | replace damper |
| FD-A-038 | Waco | 91 | Attic | FD | Fail | broken track | replace damper |
| FD-A-039 | Waco | 91 | Attic | FD | Inaccessible | access panel stuck | replace access panel |
| FD-A-049 | Waco | 91 | Attic | FD | Fail | will not close completely | replace damper |
| FD-A-050 | Waco | 91 | Attic | FD | Inaccessible | no access | install access door, spiral duct |
| FD-A-051 | Waco | 91 | Attic | FD | Inaccessible | no access | install access door, spiral duct |
| FD-A-052 | Waco | 91 | Attic | FD | Fail | will not close completely | replace damper |
| Dampers that can not be found | |||||||
| FD-1-002 | Waco | 91 | 1 | FD | Fail | Damper cannot be located with information provided | Search for damper, if one is not found install new damper and access panel. |
Waco Bldg 94
| Damper ID | Facility | Building | Floor | Damper Type | Result | Issue / Condition | Correction |
| FD-1-002 | Waco | 94 | 1 | FD | Fail | Damper broken. | Replace damper. |
| FD-2-004 | Waco | 94 | 2 | FD | Inaccessible | Fire sprinkler blocking access | Relocate access panel |
| FD-2-012 | Waco | 94 | 2 | FD | Inaccessible | Obstructed by light fixture. | Relocate light fixture. |
| Unlabeled - 2 | Waco | 94 | 2 | FD | Inaccessible | Not labeled. Damper is about 5' from the access panel. | Rm 2B-125; Install access panel closer to the damper. |
| Dampers that can not be found | |||||||
| FD-1-004 | Waco | 94 | 1 | FD | Cannot locate with information provided. | Search for damper, if one can not be located add new damper and access panel. | |
| FD-2-009 | Waco | 94 | 2 | FD | Cannot locate with information provided. | Search for damper, if one can not be located add new damper and access panel. | |
| FD-2-010 | Waco | 94 | 2 | FD | Cannot locate with information provided. | Search for damper, if one can not be located add new damper and access panel. | |
| FD-2-011 | Waco | 94 | 2 | FD | Cannot locate with information provided. | Search for damper, if one can not be located add new damper and access panel. |
Temple Bldg 163
| Damper ID | Facility | Building | Floor | Damper Type | Result | Issue | Correction |
| SD-B-009 | Temple | 163 | Basement | SD | Fail | No Damper | Install Damper |
| FD-B-020 | Temple | 163 | Basement | FS | Fail | Damper would not close | Replace damper, install new access door; Corrected "FS" to "FD |
| FD-B-026 | Temple | 163 | Basement | FD | Fail | Damper Not Installed | Install damper |
| SD-B-028 | Temple | 163 | Basement | SD | Fail | Damper Did Not Close Correctly | Replace Damper |
| SD-B-029 | Temple | 163 | Basement | SD | Fail | Damper Did Not Close Correctly | Replace Damper |
| FD-1-003 | Temple | 163 | 1 | FD | Inaccessible | Facilities could not turn unit down | Reinspect when facilities can turn unit down. Contingency amount is being added in case of an issue after inspection. |
| FD-1-009 | Temple | 163 | 1 | FD | Inaccessible | No Access Panel | Install Access Panel |
| FD-1-010 | Temple | 163 | 1 | FD | Inaccessible | No Access Panel | Install Access Panel |
Required
| FD-1-011 | Temple | 163 | 1 | FD | Inaccessible | Cable trays prevent access | Move Access Panel |
| FD-1-031 | Temple | 163 | 1 | FD | Inaccessible | Ceiling grid and desk blocking access | Move Access Panel |
| FD-2-010 | Temple | 163 | 2 | FD | Inaccessible | Conduit blocks the access panel | Modify duct, move conduit or install new access panel |
| FD-2-012 | Temple | 163 | 2 | FD | Inaccessible | Access panel cannot be reached | Relocate access panel |
| FD-3-002 | Temple | 163 | 3 | FD | Fail | No Damper | Install Damper |
| FD-3-007 | Temple | 163 | 3 | FD | Fail | Damper Stuck | Replace Damper |
| FD-3-008 | Temple | 163 | 3 | FS | Inaccessible | Access panel taped shut | Install new access panel; "FS" changed to "FD" |
| FD-3-009 | Temple | 163 | 3 | FS | Inaccessible | Access panel taped shut | Install new access panel; "FS" changed to "FD" |
| FD-3-010 | Temple | 163 | 3 | FD | Inaccessible | Infrastructure blocking access panel | Relocate access panel or damper |
| FD-4-004 | Temple | 163 | 4 | FD | Inaccessible | No Access Panel | Install Access Panel |
| FD-4-008 | Temple | 163 | 4 | FD | Fail | No Damper | Install Damper |
| FD-4-014 | Temple | 163 | 4 | FD | Fail | Damper Stuck | Replace Damper |
| FD-4-015 | Temple | 163 | 4 | FD | Inaccessible | No Access Panel | Install Access Panel |
| FD-4-016 | Temple | 163 | 4 | FD | Fail | Damper would not close | Replace damper |
| FD-4-017 | Temple | 163 | 4 | FD | Inaccessible | Access panel Sealed Shut | Replace access panel |
| FD-4-018 | Temple | 163 | 4 | FD | Inaccessible | Access panel Sealed Shut | Replace access panel |
| FD-4-019 | Temple | 163 | 4 | FD | Inaccessible | Access panel sealed | Replace access panel |
| FD-5-007 | Temple | 163 | 5 | FD | Inaccessible | Access Panel Too Small | Replace Access Panel |
| FS-5-008 | Temple | 163 | 5 | FS | Fail | Damper Stuck | Replace Damper |
| FS-5-010 | Temple | 163 | 5 | FS | Fail | Bad actuator | Replace actuator |
| FD-5-018 | Temple | 163 | 5 | FD | Inaccessible | Infrastructure blocking access panel | Move Access Panel |
| FD-5-031 | Temple | 163 | 5 | FD | Fail | Damper Not Installed | Install Damper |
| FD-P-002 | Temple | 163 | 6 | FD | Inaccessible | Access panel sealed shut | Replace access panel |
| FD-P-003 | Temple | 163 | 6 | FD | Fail | Broken Damper | Replace Damper |
| FD-P-004 | Temple | 163 | 6 | FD | Fail | Damper Stuck | Replace Damper |
| FD-P-005 | Temple | 163 | 6 | FD | Fail | Damper Stuck | Replace Damper |
| FD-P-006 | Temple | 163 | 6 | FD | Fail | Damper Stuck | Replace Damper |
| Dampers that can not be found | |||||||
| FS-B-027 | Temple | 163 | Basement | FS | Cannot locate with information provided | Cut in acess panel and install damper if necessary | |
| SD-B-030 | Temple | 163 | Basement | SD | Cannot locate with information provided | Cut in acess panel and install damper if necessary | |
| FD-2P-001 | Temple | 163 | 2 | FD | Cannot locate with information provided | Cut in acess panel and install damper if necessary | |
| FD-2P-002 | Temple | 163 | 2 | FD | Cannot locate with information provided | Cut in acess panel and install damper if necessary | |
| FD-2P-003 | Temple | 163 | 2 | FD | Cannot locate with information provided | Cut in acess panel and install damper if necessary | |
| FD-2P-004 | Temple | 163 | 2 | FD | Cannot locate with information provided | Cut in acess panel and install damper if necessary | |
| FD-4-009 | Temple | 163 | 4 | FD | Cannot locate with information provided; VAV is currenly in damper location | Cut in acess panel and install damper if necessary | |
| FD-4-010 | Temple | 163 | 4 | FD | Cannot locate with information provided; walls are not fire rated | Cut in acess panel and install damper if necessary |
Temple Bldg 202
| Damper ID | Facility | Building | Floor | Damper Type | Result | Issue | Correction |
| FD-1-031 | Temple | 202 A&B | 1 | FD | Inaccessible | ceiling grid and smoke detector blocks access panel | relocate access panel |
| FD-1-052 | Temple | 202 A&B | 1 | FD | Fail | actuator failed | replace actuator |
| FD-1-061 | Temple | 202 A&B | 1 | FD | Fail | Damper does not close | Replace damper |
| FD-1-062 | Temple | 202 A&B | 1 | FD | Fail | Dampers would not close | replace actuator |
| FD-1-003 | Temple | 202 C&D | 1 | FD | Inaccessible | no access panel | install access panel |
| FD-1-009 | Temple | 202 C&D | 1 | FD | Inaccessible | access door too small to reach the damper | install larger access door |
| SD-1-010 | Temple | 202 C&D | 1 | SD | Fail | damper broken | replace damper |
| FD-1-016 | Temple | 202 C&D | 1 | FD | Fail | damper would not close | replace damper |
| SD-1-018 | Temple | 202 C&D | 1 | SD | Fail | bad actuator | replace actuator |
| FD-1-027 | Temple | 202 C&D | 1 | FD | Fail | access door too small to reach the damper | install larger access door |
| FD-1-031 | Temple | 202 C&D | 1 | FD | Fail | damper would not close | replace actuator |
| FS-1-035 | Temple | 202 C&D | 1 | FS | Inaccessible | no access panel | install access panel |
| FD-1-036 | Temple | 202 C&D | 1 | FD | Fail | damper would not close | replace actuator |
| FD-2-011 | Temple | 202 C&D | 2 | FD | Fail | no access panel | install access panel |
| FD-2-012 | Temple | 202 C&D | 2 | FD | Fail | no access panel | install access panel |
| FD-P-005 | Temple | 202C | P | FD | Fail | Damper stuck | Provide larger access panel and new damper |
| FD-P-006 | Temple | 202C | P | FD | Fail | Damper stuck | Provide larger access panel and new damper |
| FD-P-009 | Temple | 202C | P | FD | Fail | Damper stuck | Provide larger access panel and new damper |
| FD-P-010 | Temple | 202C | P | FD | Fail | Damper stuck | Provide larger access panel and new damper |
| FD-P-011 | Temple | 202C | P | FD | Fail | Damper stuck | Provide larger access panel and new damper |
| FD-P-014 | Temple | 202 | P | FD | Inaccessible | no access panel | install access panel |
| FD-P-015 | Temple | 202 | P | FD | Inaccessible | no access panel | install access panel |
| FD-P-017 | Temple | 202 | P | FD | Inaccessible | no access panel | install access panel |
| FD-P-018 | Temple | 202 | P | FD | Inaccessible | no access panel | install access panel |
| FD-P-019 | Temple | 202 | P | FD | Inaccessible | no access panel | install access panel |
| FD-P-020 | Temple | 202 | P | FD | Inaccessible | no access panel | install access panel |
| FD-P-021 | Temple | 202 | P | FD | Inaccessible | no access panel | install access panel |
| FD-P-022 | Temple | 202 | P | FD | Fail | damper broken | replace damper |
| SD-P-026 | Temple | 202 | P | SD | Inaccessible | no access panel | install access panel |
| FD-P-027 | Temple | 202 | P | FD | Inaccessible | access panel too small to reach the damper | install larger access door |
| FD-P-031 | Temple | 202 | P | FD | Inaccessible | access panel too small to reach the damper | install larger access door |
| FD-P-032 | Temple | 202 | P | FD | Inaccessible | access panel too small to reach the damper | install larger access door |
| FD-P-033 | Temple | 202 | P | FD | Inaccessible | access panel too small to reach the damper | install larger access door |
| FD-P-045 | Temple | 202 | P | FD | Inaccessible | damper cannot be accessed from access panel location | relocate access panel |
| FD-P-046 | Temple | 202 | P | FD | Inaccessible | damper cannot be accessed from access panel location | relocate access panel |
| Dampers that could not be found | |||||||
| SD-1-055 | Temple | 202 A&B | 1 | SD | Cannot find damper with information provided | Cut in access panel and install damper if necessary | |
| FD-1_002 | Temple | 202 C&D | 1 | FD | Cannot find damper with information provided | Cut in access panel and install damper if necessary | |
| FD-1-012 | Temple | 202 C&D | 1 | FD | Cannot find damper with information provided | Cut in access panel and install damper if necessary | |
| FD-1-017 | Temple | 202 C&D | 1 | FD | Cannot find damper with information provided | Cut in access panel and install damper if necessary | |
| FD-1-040 | Temple | 202 C&D | 1 | FD | Cannot find damper with information provided | Cut in access panel and install damper if necessary | |
| FD-2-022 | Temple | 202 C&D | 2 | FD | No fire rated walls above ceiling; cannot locate damper with information provided | Cut in access panel and install damper if necessary | |
| FD-2-023 | Temple | 202 C&D | 2 | FD | No fire rated walls above ceiling; cannot locate damper with information provided | Cut in access panel and install damper if necessary | |
| FD-2-024 | Temple | 202 C&D | 2 | FD | No fire rated walls above ceiling; cannot locate damper with information provided | Cut in access panel and install damper if necessary | |
| FD-2-025 | Temple | 202 C&D | 2 | FD | No fire rated walls above ceiling; cannot locate damper with information provided | Cut in access panel and install damper if necessary | |
| FD-P-024 | Temple | 202 | P | FD | could not be located with information provided | Cut in access panel and install damper if necessary |
Temple Bldg 204
| Damper ID | Facility | Building | Floor | Damper Type | Result | Issue | Correction |
| FD-1-001 | Temple | 204 | 1 | FD | Inaccessible | access panel hits ceiling grid | Move access panel |
| FD-1-004 | Temple | 204 | 1 | FD | Fail | damper stuck | Replace damper |
| FD-1-005 | Temple | 204 | 1 | FD | Inaccessible | access panel hits ceiling grid | Move access panel |
| FD-1-010 | Temple | 204 | 1 | FD | Fail | damper stuck | replace damper |
| FD-1-014 | Temple | 204 | 1 | FD | Fail | damper stuck | replace damper |
| FD-1-015 | Temple | 204 | 1 | FD | Inaccessible | Computer infrastructure blocking access | Move access panel |
| FD-1-016 | Temple | 204 | 1 | FD | Inaccessible | built in desk blocking access | relocate damper |
| FD-1-019 | Temple | 204 | 1 | FD | Inaccessible | conduit blocking access to the damper | Move access panel/Conduit |
| FD-1-020 | Temple | 204 | 1 | FD | Inaccessible | conduit blocking access to the damper | Move access panel/Conduit |
| FD-1-021 | Temple | 204 | 1 | FD | Inaccessible | light and ceiling grid blocking access | Move access panel/light |
| FD-1-022 | Temple | 204 | 1 | FD | Inaccessible | light and ceiling grid blocking access | Move access panel/light |
| FD-1-023 | Temple | 204 | 1 | FD | Inaccessible | light and ceiling grid blocking access | Move access panel/light |
| FD-1-024 | Temple | 204 | 1 | FD | Inaccessible | light and ceiling grid blocking access | Move access panel/light |
| FD-1-029 | Temple | 204 | 1 | FD | Fail | damper stuck | replace damper |
| FD-1-033 | Temple | 204 | 1 | FD | Inaccessible | access panel hits ceiling grid | Move access panel |
| FD-1-034 | Temple | 204 | 1 | FD | Inaccessible | access panel cannot be reached | relocate damper |
| FD-1-046 | Temple | 204 | 1 | FD | Inaccessible | cannot reach. Sprinkler pipe and duct is in the way | relocate damper/ relocate access panel |
| FD-1-0AB | Temple | 204 | 1 | FD | Inaccessible | Multiple items above ceiling prevent access | Multiple items above ceiling will need to be moved to allow access. Electrica, grid, duct, sprinkler, etc. |
| FD-1-00Q | Temple | 204 | 1 | FD | Inaccessible | desk blocking ladder access, cannot reach | relocate desk/damper |
| FD-1-00R | Temple | 204 | 1 | FD | Inaccessible | desk blocking ladder access, cannot reach | relocate desk/damper |
| FD-1-00S | Temple | 204 | 1 | FD | Inaccessible | desk blocking ladder access, cannot reach | relocate desk/damper |
| FD-1-00V | Temple | 204 | 1 | FD | Inaccessible | access panel hits ceiling grid | Move access panel |
| FD-01-065 | Temple | 204 | 1 | FD | Inaccessible | access panel hits ceiling grid | Move access panel |
| FD-01-066 | Temple | 204 | 1 | FD | Inaccessible | access panel hits ceiling grid | Move access panel |
| FD-01-079 | Temple | 204 | 1 | FD | Fail | damper stuck | replace damper |
| FD-01-081 | Temple | 204 | 1 | FD | Fail | damper stuck | replace damper |
| FD-1-00A | Temple | 204 | 1 | FD | Fail | damper stuck | replace damper |
| FD-1-00F | Temple | 204 | 1 | FD | Inaccessible | damper cannot be reached from the access panel | install access panel closer to the damper |
| FD-1-00G | Temple | 204 | 1 | FD | Inaccessible | damper cannot be reached from the access panel | install access panel closer to the damper |
| FD-1-00H | Temple | 204 | 1 | FD | Inaccessible | damper cannot be reached from the access panel | install access panel closer to the damper |
| FD-1-00I | Temple | 204 | 1 | FD | Inaccessible | damper cannot be reached from the access panel | install access panel closer to the damper |
| FS-2-001 | Temple | 204 | 2 | FS | Inaccessible | no access panel in duct | install access panel |
| FS-2-002 | Temple | 204 | 2 | FS | Inaccessible | no access panel in duct | install access panel |
| FS-2-009 | Temple | 204 | 2 | FS | Fail | damper did not close | replace actuator |
| FS-2-010 | Temple | 204 | 2 | FS | fail | damper did not close | replace actuator |
| FS-3-001 | Temple | 204 | 3 | FS | Inaccessible | cable track, ceiling grid block access. Cannot reach | relocate access panel |
| FS-3-004 | Temple | 204 | 3 | FS | Inaccessible | no access panel | install access panel |
| FS-3-012 | Temple | 204 | 3 | FS | Fail | bad actuator | replace actuator |
| FS-5-001 | Temple | 204 | 5 | FS | Fail | bad actuator | replace actuator, relocate access panel |
| FS-5-002 | Temple | 204 | 5 | FS | Inaccessible | no access panel in duct | install access panel |
| FS-5-010 | Temple | 204 | 5 | FS | Fail | bad actuator | replace actuator |
| FS-5-011 | Temple | 204 | 5 | FS | Fail | bad actuator | replace actuator |
| FS-6-003 | Temple | 204 | 6 | FS | Fail | bad actuator relay | replace relay |
| FS-6-004 | Temple | 204 | 6 | FS | Fail | bad actuator relay | replace relay |
| FS-6-015 | Temple | 204 | 6 | FS | Fail | bad actuator | replace actuator |
| Dampers that can not be found | |||||||
| FD-1-0814 | Temple | 204 | 1 | FD | Cannot be located with information provided | Try to locate damper per plans, cut in access panel and install damper if necessary |
Temple Bldg 205
| Damper ID | Facility | Building | Floor | Damper Type | Result | Issue | Correction |
| FD-2-001 | Temple | 205 | 2 | FD | Inaccessible | no actual ceiling access door, no actual access panel on duct | Install new access panel for duct and ceiling |
| FD-3-001 | Temple | 205 | 3 | FD | Inaccessible | Ceiling access door would not open. | Install new ceiling access door. |
Temple Bldg 221
| Damper ID | Facility | Building | Floor | Damper Type | Result | Issue | Correction |
| FD-1A-120A | Temple | 221A | 1 | FD | no damper | install damper | |
| FD-1A-120B | Temple | 221A | 1 | FD | no damper | install damper | |
| FD-1B-105A | Temple | 221B | 1 | FD | Inaccessible | No access panel | Cut in access panel, if no damper, install a damper |
| FD-1B-107A | Temple | 221B | 1 | FD | Inaccessible | No access panel | Cut in access panel, if no damper, install a damper |
| FD-1B-109A | Temple | 221B | 1 | FD | Inaccessible | No access panel | Cut in access panel, if no damper, install a damper |
| FD-1B-111A | Temple | 221B | 1 | FD | Inaccessible | No access panel | Cut in access panel, if no damper, install a damper |
| FD-1B-113A | Temple | 221B | 1 | FD | Inaccessible | No access panel | Cut in access panel, if no damper, install a damper |
| FD-1B-117A | Temple | 221B | 1 | FD | Inaccessible | No access panel | Cut in access panel, if no damper, install a damper |
| FD-1B-120A | Temple | 221B | 1 | FD | No damper | Install damper and access panel | |
| FD-1B-121A | Temple | 221B | 1 | FD | Inaccessible | No access panel | Cut in access panel, if no damper, install a damper |
| FD-1B-123A | Temple | 221B | 1 | FD | Inaccessible | No access panel | Cut in access panel, if no damper, install a damper |
| FD-1B-125A | Temple | 221B | 1 | FD | Inaccessible | No access panel | Cut in access panel, if no damper, install a damper |
| FD-1B-127A | Temple | 221B | 1 | FD | Inaccessible | No access panel | Cut in access panel, if no damper, install a damper |
| FD-1B-129A | Temple | 221B | 1 | FD | Inaccessible | No access panel | Cut in access panel, if no damper, install a damper |
| FD-1C-105A | Temple | 221C | 1 | FD | Inaccessible | No access panel | Cut in access panel, if no damper, install a damper |
| FD-1C-107A | Temple | 221C | 1 | FD | Inaccessible | No access panel | Cut in access panel, if no damper, install a damper |
| FD-1C-109A | Temple | 221C | 1 | FD | Inaccessible | No access panel | Cut in access panel, if no damper, install a damper |
| FD-1C-111A | Temple | 221C | 1 | FD | Inaccessible | No access panel | Cut in access panel, if no damper, install a damper |
| FD-1C-113A | Temple | 221C | 1 | FD | Inaccessible | No access panel | Cut in access panel, if no damper, install a damper |
| FD-1C-117A | Temple | 221C | 1 | FD | Inaccessible | No access panel | Cut in access panel, if no damper, install a damper |
| FD-1C-120A | Temple | 221C | 1 | FD | no damper | Install fire damper and access panel | |
| FD-1C-120B | Temple | 221C | 1 | FD | no damper | Install fire damper and access panel | |
| FD-1C-121A | Temple | 221C | 1 | FD | Inaccessible | No access panel | Cut in access panel, if no damper, install a damper |
| FD-1C-123A | Temple | 221C | 1 | FD | Inaccessible | No access panel | Cut in access panel, if no damper, install a damper |
| FD-1C-125A | Temple | 221C | 1 | FD | Inaccessible | No access panel | Cut in access panel, if no damper, install a damper |
| FD-1C-127A | Temple | 221C | 1 | FD | Inaccessible | No access panel | Cut in access panel, if no damper, install a damper |
| FD-1C-129A | Temple | 221C | 1 | FD | Inaccessible | No access panel | Cut in access panel, if no damper, install a damper |
| FD-1D-105A | Temple | 221D | 1 | FD | Inaccessible | No access panel | Cut in access panel, if no damper, install a damper |
| FD-1D-107A | Temple | 221D | 1 | FD | Inaccessible | No access panel | Cut in access panel, if no damper, install a damper |
| FD-1D-109A | Temple | 221D | 1 | FD | Inaccessible | No access panel | Cut in access panel, if no damper, install a damper |
| FD-1D-111A | Temple | 221D | 1 | FD | Inaccessible | No access panel | Cut in access panel, if no damper, install a damper |
| FD-1D-113A | Temple | 221D | 1 | FD | Inaccessible | No access panel | Cut in access panel, if no damper, install a damper |
| FD-1D-117A | Temple | 221D | 1 | FD | Inaccessible | No access panel | Cut in access panel, if no damper, install a damper |
| FD-1D-120A | Temple | 221D | 1 | FD | no damper | Install damper and access panel | |
| FD-1D-120B | Temple | 221D | 1 | FD | no damper | Install damper and access panel | |
| FD-1D-121A | Temple | 221D | 1 | FD | Inaccessible | No access panel | Cut in access panel, if no damper, install a damper |
| FD-1D-123A | Temple | 221D | 1 | FD | Inaccessible | No access panel | Cut in access panel, if no damper, install a damper |
| FD-1D-125A | Temple | 221D | 1 | FD | Inaccessible | No access panel | Cut in access panel, if no damper, install a damper |
| FD-1D-127A | Temple | 221D | 1 | FD | Inaccessible | No access panel | Cut in access panel, if no damper, install a damper |
| FD-1D-129A | Temple | 221D | 1 | FD | Inaccessible | No access panel | Cut in access panel, if no damper, install a damper |
| RD-2A-01 | Temple | 221A | 2 | RD | Inaccessible | Not accessible | Replace grille with one that opens on the face |
| RD-2A-02 | Temple | 221A | 2 | RD | Inaccessible | Not accessible | Replace grille with one that opens on the face |
| RD-2A-03 | Temple | 221A | 2 | RD | Inaccessible | damper cannot be accessed | install access panel or relocate damper |
| RD-2A-05 | Temple | 221A | 2 | RD | Inaccessible | damper cannot be accessed | install access panel or relocate damper |
| RD-2A-06 | Temple | 221A | 2 | RD | Inaccessible | damper cannot be accessed | install access panel or relocate damper |
| RD-2A-07 | Temple | 221A | 2 | RD | Inaccessible | damper cannot be accessed | install access panel or relocate damper |
| RD-2A-09 | Temple | 221A | 2 | RD | Inaccessible | Not accessible | Replace grille with one that opens on the face |
| RD-2A-10 | Temple | 221A | 2 | RD | Fail | Damper broken | replace damper |
| RD-2A-11 | Temple | 221A | 2 | RD | Inaccessible | damper cannot be accessed | install access panel or relocate damper |
| RD-2A-12 | Temple | 221A | 2 | RD | Inaccessible | damper cannot be accessed | install access panel or relocate damper |
| RD-2A-13 | Temple | 221A | 2 | RD | Inaccessible | damper cannot be accessed | install access panel or relocate damper |
| RD-2A-14 | Temple | 221A | 2 | RD | Inaccessible | damper cannot be accessed | install access panel or relocate damper |
| RD-2A-15 | Temple | 221A | 2 | RD | Inaccessible | damper cannot be accessed | install access panel or relocate damper |
| RD-2A-16 | Temple | 221A | 2 | RD | Inaccessible | damper cannot be accessed | install access panel or relocate damper |
| RD-2A-17 | Temple | 221A | 2 | RD | Inaccessible | damper cannot be accessed | install access panel or relocate damper |
| RD-2A-18 | Temple | 221A | 2 | RD | Inaccessible | damper cannot be accessed | install access panel or relocate damper |
| RD-2A-19 | Temple | 221A | 2 | RD | Inaccessible | damper cannot be accessed | install access panel or relocate damper |
| RD-2A-20 | Temple | 221A | 2 | RD | Inaccessible | Not accessible | Replace grille with one that opens on the face |
| RD-2A-21 | Temple | 221A | 2 | RD | Inaccessible | Not accessible | Replace grille with one that opens on the face |
| RD-2A-22 | Temple | 221A | 2 | RD | Inaccessible | Not accessible | Replace grille with one that opens on the face |
| RD-2A-23 | Temple | 221A | 2 | RD | Inaccessible | Not accessible | Replace grille with one that opens on the face |
| RD-2A-24 | Temple | 221A | 2 | RD | Inaccessible | damper cannot be accessed | install access panel or relocate damper |
| RD-2A-26 | Temple | 221A | 2 | RD | Inaccessible | damper cannot be accessed | install access panel or relocate damper |
| RD-2A-27 | Temple | 221A | 2 | RD | Inaccessible | damper cannot be accessed | install access panel or relocate damper |
| RD-2A-28 | Temple | 221A | 2 | RD | Inaccessible | damper cannot be accessed | install access panel or relocate damper |
| RD-2A-29 | Temple | 221A | 2 | RD | Inaccessible | Not accessible | Replace grille with one that opens on the face |
| RD-2A-30 | Temple | 221A | 2 | RD | Inaccessible | Not accessible | Replace grille with one that opens on the face |
| RD-2A-31 | Temple | 221A | 2 | RD | Inaccessible | Not accessible | Replace grille with one that opens on the face |
| RD-2A-32 | Temple | 221A | 2 | RD | Inaccessible | damper cannot be accessed | install access panel or relocate damper |
| RD-2A-34 | Temple | 221A | 2 | RD | Inaccessible | damper cannot be accessed | install access panel or relocate damper |
| RD-2A-36 | Temple | 221A | 2 | RD | Inaccessible | damper cannot be accessed | install access panel or relocate damper |
| RD-2A-39 | Temple | 221A | 2 | RD | Inaccessible | damper cannot be accessed | install access panel or relocate damper |
| RD-2A-42 | Temple | 221A | 2 | RD | Inaccessible | damper cannot be accessed | install access panel or relocate damper |
| RD-2A-43 | Temple | 221A | 2 | RD | Inaccessible | damper cannot be accessed | install access panel or relocate damper |
| RD-2A-44 | Temple | 221A | 2 | RD | Inaccessible | damper cannot be accessed | install access panel or relocate damper |
| RD-2A-45 | Temple | 221A | 2 | RD | Inaccessible | damper cannot be accessed | install access panel or relocate damper |
| RD-2A-47 | Temple | 221A | 2 | RD | Inaccessible | damper cannot be accessed | install access panel or relocate damper |
| RD-2A-49 | Temple | 221A | 2 | RD | Inaccessible | damper cannot be accessed | install access panel or relocate damper |
| RD-2A-50 | Temple | 221A | 2 | RD | Inaccessible | damper cannot be accessed | install access panel or relocate damper |
| RD-2A-52 | Temple | 221A | 2 | RD | Fail | damper stuck | replace damper |
| RD-2A-53 | Temple | 221A | 2 | RD | Inaccessible | Not accessible | Replace grille with one that opens on the face |
| RD-2A-54 | Temple | 221A | 2 | RD | Fail | Damper broken | replace damper |
| RD-2A-55 | Temple | 221A | 2 | RD | Inaccessible | damper cannot be accessed | install access panel or relocate damper |
| RD-2A-56 | Temple | 221A | 2 | RD | Inaccessible | damper cannot be accessed | install access panel or relocate damper |
| RD-2A-57 | Temple | 221A | 2 | RD | Inaccessible | Not accessible | Replace grille with one that opens on the face |
| RD-2A-59 | Temple | 221A | 2 | RD | Fail | no damper | install damper |
| FD-2A-120H | Temple | 221A | 2 | FD | Inaccessible | damper cannot be accessed | Install larger access panel |
| FD-2A-250H | Temple | 221A | 2 | FD | Fail | Damper is broken | replace damper |
| RD-2B-01 | Temple | 221B | 2 | RD | Inaccessible | No access panel | Cut in access panel, if no damper, install a damper |
| RD-2B-03 | Temple | 221B | 2 | RD | Inaccessible | Not accessible | Replace grille with one that opens on the face |
| RD-2B-04 | Temple | 221B | 2 | RD | Fail | damper stuck | replace damper |
| RD-2B-06 | Temple | 221B | 2 | RD | Inaccessible | damper cannot be accessed | install access panel or relocate damper |
| RD-2B-07 | Temple | 221B | 2 | RD | Inaccessible | damper cannot be accessed | install access panel or relocate damper |
| RD-2B-09 | Temple | 221B | 2 | RD | Inaccessible | damper cannot be accessed | install access panel or relocate damper |
| RD-2B-10 | Temple | 221B | 2 | RD | Inaccessible | damper cannot be accessed | install access panel or relocate damper |
| RD-2B-12 | Temple | 221B | 2 | RD | Inaccessible | damper cannot be accessed | install access panel or relocate damper |
| RD-2B-13 | Temple | 221B | 2 | RD | Inaccessible | Not accessible | Replace grille with one that opens on the face |
| RD-2B-14 | Temple | 221B | 2 | RD | Inaccessible | Not accessible | Replace grille with one that opens on the face |
| RD-2B-15 | Temple | 221B | 2 | RD | Inaccessible | Not accessible | Replace grille with one that opens on the face |
| RD-2B-16 | Temple | 221B | 2 | RD | Inaccessible | Not accessible | Replace grille with one that opens on the face |
| RD-2B-17 | Temple | 221B | 2 | RD | Inaccessible | Not accessible | Replace grille with one that opens on the face |
| RD-2B-18 | Temple | 221B | 2 | RD | Inaccessible | damper cannot be accessed | install access panel or relocate damper |
| RD-2B-19 | Temple | 221B | 2 | RD | Inaccessible | damper cannot be accessed | install access panel or relocate damper |
| RD-2B-20 | Temple | 221B | 2 | RD | Inaccessible | damper cannot be accessed | install access panel or relocate damper |
| RD-2B-21 | Temple | 221B | 2 | RD | Inaccessible | damper cannot be accessed | install access panel or relocate damper |
| RD-2B-23 | Temple | 221B | 2 | RD | Inaccessible | Not accessible | Replace grille with one that opens on the face |
| RD-2B-26 | Temple | 221B | 2 | RD | Inaccessible | Not accessible | Replace grille with one that opens on the face |
| RD-2B-27 | Temple | 221B | 2 | RD | Inaccessible | Not accessible | Replace grille with one that opens on the face |
| RD-2B-35 | Temple | 221B | 2 | RD | Inaccessible | Not accessible | Replace grille with one that opens on the face |
| RD-2B-39 | Temple | 221B | 2 | RD | Inaccessible | Not accessible | Replace grille with one that opens on the face |
| RD-2B-40 | Temple | 221B | 2 | RD | Inaccessible | Not accessible | Replace grille with one that opens on the face |
| RD-2B-42 | Temple | 221B | 2 | RD | Inaccessible | Not accessible | Replace grille with one that opens on the face |
| RD-2B-43 | Temple | 221B | 2 | RD | Inaccessible | Not accessible | Replace grille with one that opens on the face |
| RD-2B-44 | Temple | 221B | 2 | RD | Inaccessible | Not accessible | Replace grille with one that opens on the face |
| RD-2B-46 | Temple | 221B | 2 | RD | Inaccessible | Not accessible | Replace grille with one that opens on the face |
| RD-2B-47 | Temple | 221B | 2 | RD | Inaccessible | Not accessible | Replace grille with one that opens on the face |
| RD-2B-48 | Temple | 221B | 2 | RD | Inaccessible | Not accessible | Replace grille with one that opens on the face |
| RD-2B-49 | Temple | 221B | 2 | RD | Inaccessible | Not accessible | Replace grille with one that opens on the face |
| RD-2B-50 | Temple | 221B | 2 | RD | Inaccessible | Not accessible | Replace grille with one that opens on the face |
| RD-2B-51 | Temple | 221B | 2 | RD | Fail | damper stuck | replace damper |
| RD-2B-52 | Temple | 221B | 2 | RD | Inaccessible | Not accessible | Replace grille with one that opens on the face |
| RD-2B-53 | Temple | 221B | 2 | RD | Inaccessible | Not accessible | Replace grille with one that opens on the face |
| RD-2B-54 | Temple | 221B | 2 | RD | Inaccessible | Not accessible | Replace grille with one that opens on the face |
| RD-2B-55 | Temple | 221B | 2 | RD | Inaccessible | Not accessible | Replace grille with one that opens on the face |
| RD-2B-56 | Temple | 221B | 2 | RD | Inaccessible | Not accessible | Replace grille with one that opens on the face |
| RD-2B-57 | Temple | 221B | 2 | RD | Inaccessible | Not accessible | Replace grille with one that opens on the face |
| RD-2B-58 | Temple | 221B | 2 | RD | Inaccessible | Not accessible | Replace grille with one that opens on the face |
| RD-2B-59 | Temple | 221B | 2 | RD | Inaccessible | Not accessible | Replace grille with one that opens on the face |
| RD-2C-01 | Temple | 221C | 2 | RD | Inaccessible | No access panel | Cut in access panel, if no damper, install a damper |
| RD-2C-03 | Temple | 221C | 2 | RD | Inaccessible | No access panel | Cut in access panel, if no damper, install a damper |
| RD-2C-05 | Temple | 221C | 2 | RD | Inaccessible | No access panel | Cut in access panel, if no damper, install a damper |
| RD-2C-07 | Temple | 221C | 2 | RD | Inaccessible | Not accessible | Replace grille with one that opens on the face |
| RD-2C-09 | Temple | 221C | 2 | RD | Inaccessible | Not accessible | Replace grille with one that opens on the face |
| RD-2C-13 | Temple | 221C | 2 | RD | Inaccessible | Not accessible | Replace grille with one that opens on the face |
| RD-2C-15 | Temple | 221C | 2 | RD | Inaccessible | Not accessible | Replace grille with one that opens on the face |
| RD-2C-16 | Temple | 221C | 2 | RD | Inaccessible | Not accessible | Replace grille with one that opens on the face |
| RD-2C-18 | Temple | 221C | 2 | RD | Fail | grill reducer preventing operation | Install a straight piece of duct between the reducer and grille |
| RD-2C-19 | Temple | 221C | 2 | RD | Fail | grill reducer preventing operation | Install a straight piece of duct between the reducer and grille |
| RD-2C-21 | Temple | 221C | 2 | RD | Inaccessible | Not accessible | Replace grille with one that opens on the face |
| RD-2C-23 | Temple | 221C | 2 | RD | Inaccessible | Not accessible | Replace grille with one that opens on the face |
| RD-2C-25 | Temple | 221C | 2 | RD | Fail | Grill reducer preventing operation | Install a straight piece of duct between the reducer and grille |
| RD-2C-28 | Temple | 221C | 2 | RD | Fail | Grill reducer preventing operation | Install a straight piece of duct between the reducer and grille |
| RD-2C-32 | Temple | 221C | 2 | RD | Fail | Damper catching on duct | Install a straight piece of duct between the reducer and grille |
| RD-2C-34 | Temple | 221C | 2 | RD | Inaccessible | Not accessible | Replace grille with one that opens on the face |
| RD-2C-37 | Temple | 221C | 2 | RD | Fail | Duct is bent / broken RD | Fix duct and replace radiant damper |
| RD-2C-38 | Temple | 221C | 2 | RD | Fail | Damper broken | Replace Damper |
| RD-2C-40 | Temple | 221C | 2 | RD | Inaccessible | Not accessible | Replace grille with one that opens on the face |
| RD-2C-41 | Temple | 221C | 2 | RD | Fail | grill reducer preventing operation | Install a straight piece of duct between the reducer and grille |
| RD-2C-42 | Temple | 221C | 2 | RD | no damper | Install ound radiant damper | |
| RD-2C-43 | Temple | 221C | 2 | RD | no damper | Install round radiant damper | |
| RD-2C-44 | Temple | 221C | 2 | RD | Fail | grill reducer preventing operation | Install a straight piece of duct between the reducer and grille |
| RD-2C-45 | Temple | 221C | 2 | RD | Fail | grill reducer preventing operation | Install a straight piece of duct between the reducer and grille |
| RD-2C-47 | Temple | 221C | 2 | RD | Inaccessible | Not accessible | Replace grille with one that opens on the face |
| RD-2C-48 | Temple | 221C | 2 | RD | Fail | grill reducer preventing operation | Install a straight piece of duct between the reducer and grille |
| RD-2C-49 | Temple | 221C | 2 | RD | Fail | grill reducer preventing operation | Install a straight piece of duct between the reducer and grille |
| RD-2C-50 | Temple | 221C | 2 | RD | Inaccessible | Not accessible | Replace grille with one that opens on the face |
| RD-2C-52 | Temple | 221C | 2 | RD | Inaccessible | Not accessible | Replace grille with one that opens on the face |
| RD-2C-60 | Temple | 221C | 2 | RD | Inaccessible | Not accessible | Replace grille with one that opens on the face |
| RD-2C-60 | Temple | 221C | 2 | RD | Inaccessible | Not accessible | Replace grille with one that opens on the face |
| RD-2C-61 | Temple | 221C | 2 | RD | Inaccessible | Not accessible | Replace grille with one that opens on the face |
| RD-2C-61 | Temple | 221C | 2 | RD | Inaccessible | Not accessible | Replace grille with one that opens on the face |
| RD-2C-62 | Temple | 221C | 2 | RD | Inaccessible | Not accessible | Replace grille with one that opens on the face |
| RD-2C-62 | Temple | 221C | 2 | RD | Inaccessible | Not accessible | Replace grille with one that opens on the face |
| RD-2C-63 | Temple | 221C | 2 | RD | Inaccessible | Not accessible | Replace grille with one that opens on the face |
| RD-2C-63 | Temple | 221C | 2 | RD | Inaccessible | Not accessible | Replace grille with one that opens on the face |
| RD-2C-64 | Temple | 221C | 2 | RD | Inaccessible | Not accessible | Replace grille with one that opens on the face |
| RD-2C-64 | Temple | 221C | 2 | RD | Inaccessible | Not accessible | Replace grille with one that opens on the face |
| RD-2C-65 | Temple | 221C | 2 | RD | Inaccessible | Not accessible | Replace grille with a grille that opens on the face |
| RD-2C-66 | Temple | 221C | 2 | RD | Inaccessible | Not accessible | Replace grille with a grille that opens on the face |
| RD-2D-05 | Temple | 221D | 2 | RD | Fail | damper stuck | replace damper |
| RD-2D-08 | Temple | 221D | 2 | RD | Inaccessible | Not accessible | Replace grille with one that opens on the face |
| RD-2D-10 | Temple | 221D | 2 | RD | Fail | damper stuck | replace damper |
| RD-2D-11 | Temple | 221D | 2 | RD | Fail | no damper | install a damper |
| RD-2D-14 | Temple | 221D | 2 | RD | Fail | no damper | install a damper |
| RD-2D-17 | Temple | 221D | 2 | RD | Fail | no damper | install a damper |
| RD-2D-27 | Temple | 221D | 2 | RD | Fail | damper stuck | replace damper |
| RD-2D-33 | Temple | 221D | 2 | RD | Inaccessible | Not accessible | Replace grille with one that opens on the face |
| RD-2D-34 | Temple | 221D | 2 | RD | Inaccessible | Not accessible | Replace grille with one that opens on the face |
| RD-2D-36 | Temple | 221D | 2 | RD | Inaccessible | Not accessible | Replace grille with one that opens on the face |
| RD-2D-37 | Temple | 221D | 2 | RD | Inaccessible | Not accessible | Replace grille with one that opens on the face |
| RD-2D-39 | Temple | 221D | 2 | RD | Inaccessible | Not accessible | Replace grille with one that opens on the face |
| RD-2D-40 | Temple | 221D | 2 | RD | Inaccessible | Not accessible | Replace grille with one that opens on the face |
| RD-2D-42 | Temple | 221D | 2 | RD | Inaccessible | Not accessible | Replace grille with one that opens on the face |
| RD-2D-43 | Temple | 221D | 2 | RD | Inaccessible | Not accessible | Replace grille with one that opens on the face |
| RD-2D-50 | Temple | 221D | 2 | RD | Inaccessible | Not accessible | Replace grille with one that opens on the face |
| RD-2D-55 | Temple | 221D | 2 | RD | No damper | Install damper | |
| Dampers that could not be found | |||||||
| FD-1A-105A | Temple | 221A | 1 | FD | Cannot locate damper with information provided | Cut in access panel and add damper if needed | |
| FD-1A-107A | Temple | 221A | 1 | FD | Cannot locate damper with information provided | Cut in access panel and add damper if needed | |
| FD-1A-109A | Temple | 221A | 1 | FD | Cannot locate damper with information provided | Cut in access panel and add damper if needed | |
| FD-1A-111A | Temple | 221A | 1 | FD | Cannot locate damper with information provided | Cut in access panel and add damper if needed | |
| FD-1A-113A | Temple | 221A | 1 | FD | Cannot locate damper with information provided | Cut in access panel and add damper if needed | |
| FD-1A-117A | Temple | 221A | 1 | FD | Cannot locate damper with information provided | Cut in access panel and add damper if needed | |
| FD-1A-121A | Temple | 221A | 1 | FD | Cannot locate damper with information provided | Cut in access panel and add damper if needed | |
| FD-1A-123A | Temple | 221A | 1 | FD | Cannot locate damper with information provided | Cut in access panel and add damper if needed | |
| FD-1A-125A | Temple | 221A | 1 | FD | Cannot locate damper with information provided | Cut in access panel and add damper if needed | |
| FD-1A-127A | Temple | 221A | 1 | FD | Cannot locate damper with information provided | Cut in access panel and add damper if needed | |
| FD-1A-129A | Temple | 221A | 1 | FD | Cannot locate damper with information provided | Cut in access panel and add damper if needed | |
| RD-2A-04 | Temple | 221A | 2 | RD | Cannot locate damper with information provided | Cut in access panel and add damper if needed | |
| FD-2A-113B | Temple | 221A | 2 | FD | Cannot locate damper with information provided | Cut in access panel and add damper if needed | |
| FD-2B-XXXX | Temple | 221B | 2 | FD | Cannot locate damper with information provided | Cut in access panel and add damper if needed | |
| FD-2B-114C | Temple | 221B | 2 | FD | Cannot locate damper with information provided | Cut in access panel and add damper if needed | |
| FD-2C-XXXX | Temple | 221C | 2 | FD | Cannot locate damper with information provided | Cut in access panel and add damper if needed | |
| FD-2C-120H | Temple | 221C | 2 | FD | Cannot locate damper with information provided | Cut in access panel and add damper if needed | |
| FD-2C-224A | Temple | 221C | 2 | FD | Cannot locate damper with information provided | Cut in access panel and add damper if needed | |
| FD-2D-113D | Temple | 221D | 2 | FD | Cannot locate damper with information provided | Cut in access panel and add damper if needed | |
| FD-2D-XX | Temple | 221D | 2 | FD | Cannot locate damper with information provided | Cut in access panel and add damper if needed | |
| RD-2A-25 | Temple | 221A | 2 | RD | Cannot locate damper with information provided | Cut in access panel and add damper if needed |
Temple Bldg 222
| Damper ID | Facility | Building | Floor | Damper Type | Result | Issue | Correction |
| FD-1-004 | Temple | 222 | 1 | FD | Fail | no fire damper or access panel installed | install fire damper and/or access panel |
| FD-1-008 | Temple | 222 | 1 | FD | Inaccessible | Damper cannot be tested because the access panel is too small | Install larger access panel |
| FD-2-004 | Temple | 222 | 2 | FD | Inaccessible | Pipes and ceiling grid blocking access panel | Relocate damper or access panel |
| FD-3-002 | Temple | 222 | 3 | FD | Inaccessible | Access panel too small | Install larger access panel |
| FD-3-003 | Temple | 222 | 3 | FD | Inaccessible | access panel too close to other duct, cannot get ladder to it | Relocate damper or access panel |
image1.jpeg image2.jpeg