36C25727Q0050 0001.pdf

PDF 175 KB Posted

Attached to
CTX Life Safety Assessment and Fire Damper Inspection
Solicitation number
36C25727Q0050
Issued by

About this file

This is Amendment 0001 to Solicitation 36C25727Q0050, issued by the Department of Veterans Affairs Network Contracting Office 17 in Temple, Texas on November 12, 2026. The amendment modifies a solicitation for Life Safety Assessment, Fire Damper Inspection, Testing and Repair services at the Temple and Waco VA Medical Center campuses.

The amendment provides three substantive updates: (1) site visit information for November 18, 2026, with separate times and locations for Waco Campus (10:00 AM CST, Building 99, Room 109) and Temple Campus (1:30 PM CST, Building 53, Room 115), with point of contact Greg Williams at 254-624-7849; (2) clarification that no bid bond, performance bond, or payment bond is required, and references to bonding in CLIN 0003 have been removed; and (3) government responses to 35 vendor questions addressing scope clarification, pricing structure, fire damper repair requirements, engineer qualifications, contingency items, work scheduling, deliverables specifications, labor standards compliance, and insurance requirements. Key responses confirm that Attachment A repairs are included in the firm-fixed-price CLIN 0002, newly discovered work requires written Contracting Officer authorization, fire-damper work at both campuses must proceed simultaneously within 180 days, applicable wage determinations must be followed, and CAD drawings and 10 hard-copy sets of reports per campus are required deliverables. All other terms and conditions of the original solicitation remain unchanged.

View the file

Other files

File Type Posted
Attachment A CTX Fire Damper Repair List.xlsx XLSX spreadsheet
36C25727Q0050.pdf PDF
SCA WD 2015-5261 rv.31 08-17-2026.pdf PDF
SCA WD 2015-5237 rv.32 08-17-2026.pdf PDF

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

5. PROJECT NUMBER (if applicable)

CODE 7. ADMINISTERED BY

2. AMENDMENT/MODIFICATION NUMBER

CODE

6. ISSUED BY

8. NAME AND ADDRESS OF CONTRACTOR

4. REQUISITION/PURCHASE REQ. NUMBER 3. EFFECTIVE DATE

9A. AMENDMENT OF SOLICITATION NUMBER

9B. DATED

PAGE OF PAGES

10A. MODIFICATION OF CONTRACT/ORDER NUMBER

10B. DATED

BPA NO. 1. CONTRACT ID CODE

FACILITY CODE CODE

Offers must acknowledge receipt of this amendment prior to the hour and date specified in the solicitation or as amended, by one of the following methods:

The above numbered solicitation is amended as set forth in Item 14. The hour and date specified for receipt of Offers

E. IMPORTANT:

is extended,

(a) By completing Items 8 and 15, and returning __________ copies of the amendment; (b) By acknowledging receipt of this amendment on each copy of the offer submitted; or (c) By separate letter or electronic communication which includes a reference to the solicitation and amendment numbers. FAILURE OF YOUR ACKNOWLEDGMENT TO BE RECEIVED AT THE PLACE DESIGNATED FOR THE RECEIPT OF OFFERS PRIOR TO THE HOUR AND DATE SPECIFIED MAY is not extended.

12. ACCOUNTING AND APPROPRIATION DATA

(REV. 11/2016)

is required to sign this document and return ___________ copies to the issuing office. is not, A. THIS CHANGE ORDER IS ISSUED PURSUANT TO: (Specify authority) THE CHANGES SET FORTH IN ITEM 14 ARE MADE IN THE CONTRACT ORDER NO. IN ITEM 10A.

15C. DATE SIGNED

B. THE ABOVE NUMBERED CONTRACT/ORDER IS MODIFIED TO REFLECT THE ADMINISTRATIVE CHANGES SET FORTH IN ITEM 14, PURSUANT TO THE AUTHORITY OF FAR 43.103(b).

RESULT IN REJECTION OF YOUR OFFER. If by virtue of this amendment you desire to change an offer already submitted, such change may be made by letter or electronic communication, provided each letter or electronic communication makes reference to the solicitation and this amendment, and is received prior to the opening hour and date specified.

C. THIS SUPPLEMENTAL AGREEMENT IS ENTERED INTO PURSUANT TO AUTHORITY OF:

D. OTHER

Contractor

16C. DATE SIGNED

14. DESCRIPTION OF AMENDMENT/MODIFICATION

16B. UNITED STATES OF AMERICA

Except as provided herein, all terms and conditions of the document referenced in Item 9A or 10A, as heretofore changed, remains unchanged and in full force and effect.

15A. NAME AND TITLE OF SIGNER 16A. NAME AND TITLE OF CONTRACTING OFFICER

15B. CONTRACTOR/OFFEROR

STANDARD FORM 30 PREVIOUS EDITION NOT USABLE

Prescribed by GSA - FAR (48 CFR) 53.243

(Type or print) (Type or print)

(Organized by UCF section headings, including solicitation/contract subject matter where feasible.)

(Number, street, county, State and ZIP Code)

(If other than Item 6)

(Specify type of modification and authority)

(such as changes in paying office, appropriation date, etc.)

(If required)

(SEE ITEM 11)

(SEE ITEM 13)

(X)

CHECK

ONE

13. THIS ITEM APPLIES ONLY TO MODIFICATIONS OF CONTRACTS/ORDERS,

IT MODIFIES THE CONTRACT/ORDER NO. AS DESCRIBED IN ITEM 14.

11. THIS ITEM ONLY APPLIES TO AMENDMENTS OF SOLICITATIONS

AMENDMENT OF SOLICITATION/MODIFICATION OF CONTRACT

(Signature of person authorized to sign) (Signature of Contracting Officer)

1 10

0001 11-12-2026

36C257

Department Of Veterans Affairs Network Contracting Office 17

1901 Veterans Memorial Drive Temple TX 76504

To all Offerors/Bidders

36C25727Q0050

11-03-2026

X

X X

X 1

Project: Life Safety Assessment, Fire Damper Inspection, Testing and Repair

The purpose of this amendment is to:

1. Provide site visit information for this requirement

2. Remove references to bonding requirements from the solicitation and clarify bid bond, performance bond or payment bond is not required

3. Publish the Government's responses to vendor questions received during the solicitation period.

All other terms and conditions of the solicitation remain unchanged.

36C25727Q0050 0001

SF-30 Continuation Page(s)

1. Site Visit Information Date: November 18, 2026 Waco Campus

• Time: 10:00 AM CST

• Location: Building 99, Room 109

Temple Campus

• Time: 1:30 PM CST

• Location: Building 53, Room 115

Point of Contact: Greg Williams, 254-624-7849

2. Clarification Regarding Bonding

1.00 JB __________________ __________________

Contingency/Bonding/Overhead/Mobilization/ICRA for Temple and Waco Campuses IAW SOW.

No bid bond, performance bond, or payment bond is required for this solicitation. Offerors shall not include bonding costs in their quotations. References to bonding in CLIN 0003 have been removed by this amendment.

3. Technical Questions and Government Responses Question 1

Can you please provide inspection reports and life safety plans?

Government Response: Existing inspection reports, life-safety plans, drawings, and prior Statement of Conditions documentation will be provided to the successful contractor after award.

Question 2

Can you please provide the square footage for each building included within the Temple and Waco VA Medical Center campuses?

Government Response: No. Building square footage is not required to prepare an offer under this solicitation. Offerors shall rely on the information provided in the solicitation. Building square footage is not a required basis of pricing and is not provided as part of the solicitation package.

Question 3

Attachment A lists 459 repair items (348 Temple, 111 Waco). Of these, 84 are conditional (for example, "if no damper, install a damper") and 47 are listed as "can not be found."

Will VA use unit prices or an allowance for these? How many access panels and pipe or duct reroutes beyond Attachment A should offerors price, given that the SOW says "multiple"?

Government Response: Contractors shall price the requirements stated in the SOW and Attachment A. Newly discovered work outside the defined scope is conditional upon field verification and requires written authorization from the Contracting Officer before performance.

Question 4

The SOW states outages are "subject to nights, weekends, and holidays." About what share of the work should be priced after hours? Also, which code editions apply? Section 3.2 lists NFPA 80, 92, 99 and 101, while Section 4.0 lists NFPA 80, 105, 90A and 101; neither gives a year.

Government Response: The Government has not established a fixed percentage of work to be performed after hours. Work hours will depend on the operational impact of each outage.

For bids estimate 15% after hours. The applicable standards are NFPA 80, NFPA 92, NFPA 99, NFPA 101, NFPA 105, NFPA 90A, applicable NFPA codes, Joint Commission requirements, and local building and fire codes.

Question 5

May the Fire Protection Engineer be a named subcontractor rather than the prime? Does VA treat the damper, access-panel and grille replacements under CLIN 0002 as materials/other direct costs excluded from the 50% limitation on subcontracting for services?

Government Response: The Fire Protection Engineer may be a qualified subcontractor, provided the individual satisfies all solicitation qualification requirements and the contractor remains fully responsible for contract performance.

Question 6

CLIN 0003 is titled "Contingency/Bonding/Overhead/Mobilization/ICRA," yet no bond clause appears in the solicitation. Please confirm whether any bid, performance or payment bond is required.

Government Response: No bid, performance, or payment bond requirement is identified in the supplied documents. Unless the solicitation is amended to include the applicable bonding clauses and requirements, offerors should not assume that a bond is required.

Question 7

Reference: Section B.3, SOW Section 3.0, Scope – Statement of Condition (SOC), Page 5

The SOC scope does not state whether fire and smoke barriers must be inspected above the ceiling. Please confirm whether this is required for the SOC. If it is, please state the expected extent: for example, a percentage sample (such as 10%), renovated areas only, or all barriers.

Please also confirm that patient rooms are excluded as an infection control precaution.

Government Response: The SOW requires a comprehensive life-safety assessment and SOC documentation. Offerors shall assess accessible conditions necessary to complete the SOC while complying with approved ICRA controls.

Question 8

Fire Protection Engineer Qualifications - Reference: Section B.3, SOW Section 3.0, Page 5 ("Fire Protection Engineer Qualification Requirements"); SOW Page 7 ("licensed, experienced engineers")

(a) SOW Section 3.0 requires a "Fire Protection Engineer" who is "a Life Safety Specialist with NFPA 99 or NFPA 101 Technical Committee certification" with at least 10 years of experience conducting life safety assessments. Please confirm that a person with all of the following meets this requirement:

• Bachelor of Science in Fire Protection Engineering

• Principal Member of the NFPA 99 (Health Care Facilities Code) Technical Committee

• Certified Life Safety Specialist – Health Care (CLSS-HC)

• More than 15 years of healthcare life safety assessment and SOC experience, including prior triennial SOC surveys at the Temple and Waco VAMCs

(b) Page 7 states that "licensed, experienced engineers" shall prepare redline updates of the Construction Documents. Please confirm that a Professional Engineer (PE) license is not required to prepare SOC documentation or life safety drawing redlines under this solicitation.

Government Response: (a) The described individual appears to satisfy the stated experience and subject-matter qualifications because the individual is identified as a Fire Protection Engineering graduate, a principal member of the NFPA 99 Technical Committee, a Certified Life Safety Specialist–Health Care, and has more than 15 years of relevant experience. Final responsibility determinations will be based on the documentation submitted with the offer.

(b) The SOW requires a Fire Protection Engineer who is a Life Safety Specialist with qualifying NFPA 99 or NFPA 101 technical-committee credentials and at least 10 years of life-safety assessment experience. It also requires licensed, experienced engineers to prepare redline updates. The supplied SOW does not expressly state that a PE seal is required for SOC documentation or record-drawing redlines.

Question 9

CLIN 0002 Pricing Structure - Reference: Section B.2, Price/Cost Schedule, CLIN 0002, Page 4; SOW Section 3.2, Page 6 (Attachment A repairs)

CLIN 0002 combines fire damper testing and repairs as one lump-sum job. Attachment A lists the repairs from the previous inspection. The scope of those repairs, and of any new deficiencies found during testing, can't be fully confirmed until field verification. Will VA accept separate pricing within CLIN 0002 for (a) damper inspection/testing and (b) Attachment A repairs? Or will VA accept unit pricing by repair type, such as damper replacement, access panel installation, or MEP rerouting?

Government Response: CLIN 0002 remains a single firm-fixed-price requirement covering fire-damper inspection, testing, and the repairs identified in Attachment A. Offerors may include supporting internal price breakdowns in their proposals, but such breakdowns do not create separate payable sub-CLINs or unit-priced items unless the solicitation is amended. Newly discovered deficiencies outside the stated scope shall not be performed without written Contracting Officer authorization.

Question 10

Repair list versus full scope - Source: B.2, p. 4; B.3, pp. 5-6; Attachment A, all worksheets

Please confirm whether all work described in Attachment A is included in the firm-fixed price for

CLIN 0002.

Government Response: Yes. The SOW directs the contractor to make all repairs identified in Attachment A from the previous fire-damper inspection and then reinspect the repaired dampers. Those repairs are included in the stated inspection, testing, and repair scope.

Conditional repairs remain subject to field verification of the condition described in Attachment A.

Question 11

Unknown dampers and new installations - Source: B.3, pp. 5-6; Attachment A, Waco Bldgs 4/7/94; Temple Bldgs 163/221/222

It is certain that new deficiencies will be discovered during the required testing. Will the government provide all bidders a single not-to-exceed amount in a CLIN to cover all newly discovered deficiencies?

Government Response: The contractor shall document newly discovered deficiencies in the required weekly report. Work beyond the defined SOW and Attachment A scope shall not proceed without written authorization from the Contracting Officer.

Question 12

Unknown dampers and new installations - Source: B.3, pp. 5-6; Attachment A, Waco Bldgs 4/7/94; Temple Bldgs 163/221/222

Attachment A contains “cannot locate/no damper” conditions and instructions to install new dampers if not found. Please confirm whether contractors must include replacement/new dampers, design of new penetrations, fire-rated assembly work and any necessary permitting within the fixed price, or whether those items require separate authorization.

Government Response: Attachment A instructions requiring the contractor to locate a damper and, if no damper exists, install a damper and access panel are part of the listed repair scope, subject to field verification. The contractor shall include the labor and materials necessary to complete the listed correction. Any condition requiring engineered redesign, a new penetration, extensive fire-rated assembly reconstruction, or work materially beyond the listed correction must be presented to the COR and Contracting Officer before performance.

Question 13

MEP Relocation - Source: B.3, p. 5

The solicitation states “Contractors shall make accessible Fire Dampers obstructed by MEP (i.e.

rerouting systems impacting access to thoroughly inspect operational functionality of the damper.” Is the VA saying that if a damper is obstructed from a mechanical, electrical, or plumbing system, it is the contractor’s responsibility to re-route that system in order to inspect the damper at no additional cost?

Government Response: Yes, ordinary MEP relocation or reconfiguration necessary to make a damper accessible is within the stated scope. Attachment A includes examples involving relocation or modification of lights, conduit, sprinkler components, ducts, ceiling grids, and access panels. When access would require considerable structural or MEP realignment, the contractor shall stop and submit the condition for Government review rather than proceed without authorization.

Question 14

Excluded access / credit procedure - Source: B.3, p. 6, access and credit paragraphs

The SOW requires access through MEP reconfiguration but also calls for a credit where access is impossible without “considerable” structural/MEP realignment. Please define the threshold, who authorizes exclusion, and how the credit is calculated from the three lump-sum CLINs.

Government Response: A location may be considered impossible to access when inspection or repair would require considerable structural alteration or considerable MEP realignment beyond the access work contemplated by the SOW and Attachment A. The contractor shall document the conditions, proposed approach, cost effect, and photographs and submit them to the COR. The Contracting Officer is the only official authorized to approve exclusion of work and establish the amount of any credit. Any credit will be negotiated based on the omitted labor, material, equipment, and associated costs.

Question 15

Damper inventory and campus building differences - Source: B.3, p. 5, Scope SOC and 3.1

Please reconcile the SOW building lists and quantities, including Temple Bldg 221 (65 fire and 180 radiant dampers), Temple Bldg 216 (SOC only), Waco Bldg 93 (testing only), and Waco Bldg 99 (SOC only). Are radiant dampers included in testing, repairs, labeling and the same turnover reports?

Government Response: Attachment A includes substantial radiant-damper corrective work.

Radiant dampers are included in the applicable inspection, repair, labeling, and turnover-report requirements. Exact counts must be field verified.

Question 16

Attachment A status and verification - Source: B.3, p. 6; Attachment A, Waco Bldg 4/11; Temple Bldg 221

Please confirm whether Attachment A entries described as “Pass” but requiring replacement/access work, and entries with blank Result fields, are mandatory repair items.

Government Response: Yes. An Attachment A entry is a repair item when its issue or correction field calls for corrective work, even if the prior result is shown as “Pass” or the result field is blank.

Question 17

Outages, ICRA and night work - Source: B.3, p. 6, ICRA and outages; p. 7, POP

Please specify which areas will require after-hours work, anticipated ICRA classification/barrier level, outage duration and whether VA personnel will provide shutdowns/restarts.

Government Response: The Government has not predetermined every area requiring after-hours work, the ICRA classification for every location, or the duration of each outage. These requirements depend on location, patient-care impact, infection-control risk, and the contractor’s proposed means and methods. For bids estimate level 3 or 4 for ICRA.

Question 18

Outages, ICRA and night work - Source: B.3, p. 6, ICRA and outages; p. 7, POP

How will required two-week outage notice be accommodated within the 180-day simultaneous-campus schedule?

Government Response: The contractor shall incorporate the two-week outage-notice requirement into its project schedule and submit outage requests sufficiently early to maintain the 180-day period of performance. Work at the Temple VAMC and Waco VAMC is required to proceed simultaneously. The contractor should sequence field verification, ICRA coordination, access work, testing, repairs, reinspection’s, and deliverables so that outage-dependent work does not delay overall completion.

Question 19

Engineering and 24x18 CAD deliverables - Source: B.3, pp. 6-7, Deliverables

Please specify the required extent of engineer-produced redline construction documents and 24x18 CAD drawings: as-built markups only, or sealed engineering/design of new/relocated dampers and MEP systems? Can equivalent electronic deliverables replace all or part of the 10 hard-copy sets per campus?

Government Response: Redline updates shall accurately document field-verified damper locations, access points, repairs, replacements, and relevant changes resulting from this scope.

The requirement is for accurate record-condition or as-built markups. Contractors are not required to perform sealed engineering design for unanticipated new systems or major MEP relocations. The stated deliverable remains 10 hard-copy 24-by-18-inch sets per campus and CAD drawings on three USB drives per campus.

Question 20

Labor and applicable material requirements - Source: Section D, p. 24; C.1, p. 8; B.3, pp. 5-6

Please confirm that Service Contract Labor Standards determinations 2015-5237 (Bell/Coryell) and 2015-5261 (Falls/McLennan) apply to service labor at their respective campuses, and whether any Davis-Bacon construction wage determination or Buy American requirement applies to new damper/duct/structural work.

Government Response: Contractors shall comply with the wage determination and acquisition clauses incorporated into the solicitation.

Question 21

Bonding - CLIN 0003 includes bonding. However, there is no information about the bonding requirements within the solicitation. Is bonding required and if so, what are the requirements?

Government Response: Unless the solicitation is amended to provide the applicable clause, penal amount, and submission requirements, bonding is not required.

Question 22

Deliverables - Source: Section B.6, p. 6

The deliverables for fire damper testing and inspection reports states that CAD drawings are required. Is this correct?

Government Response: Yes. The SOW requires CAD drawings as part of the fire-damper testing and inspection deliverables.

Question 23

Source: SOW 3.0 (p. 5) - Provide gross square footage per building for all listed Temple and Waco buildings.

Government Response: The SOW states that prior SOC documentation, drawings, and inspection reports will be provided after award. Contractors shall attend the required site visit and field-verify the conditions affecting their proposed level of effort.

Question 24

Source: SOW 3.0 vs. 3.1 (p. 5)

Building lists differ: the Waco SOC list includes Bldgs 1 and 99 but the damper list omits them and adds Bldg 93; the Temple SOC list includes Bldg 216 but the damper list omits it. Confirm the correct lists.

Government Response: The lists address different scopes. For SOC work, the contractor shall use the lists in Section 3.0. For fire-damper testing and labeling, the contractor shall use the lists in Section 3.1. Therefore, Waco Buildings 1 and 99 and Temple Building 216 are included in the SOC scope but are not listed in the damper-testing scope. Waco Building 93 is included in the damper-testing scope but is not listed for SOC work.

Question 25

Source: SOW 5.0 (p. 6)

Existing SOC/LS drawings: CAD format, date of last update, compliance with VA CAD standards, and percentage of square footage renovated since. Can these be provided before the quote?

Government Response: Prior SOC documentation, drawings, and inspection reports will be provided upon award.

Question 26

Source: SOW 6.0 (p. 6)

Confirm that 10 hard-copy sets per site apply to both the SOC and damper reports, the binder format, and the 24x18 sheet size.

Government Response: Yes. The SOW requires the SOC documentation and the fire-damper testing and inspection reports in 24-by-18-inch hard-copy format, 10 sets per campus, together with CAD drawings on three USB drives per campus. The SOC documentation is also required in binder format.

Question 27

Source: SOW 3.1 (p. 5)

Weekly deficiency report format and recipient? Are repairs found during testing to be completed under this contract or quoted separately?

Government Response: The weekly deficiency report shall identify each damper by ID, facility, building, floor, and location and shall state the damper type, inspection date, result, issue, recommended correction, status, and any required Government coordination. It should be submitted electronically to the COR and any additional recipients designated after award.

Attachment A repairs are included in the contract. Newly discovered deficiencies shall be reported promptly and shall not be treated as separately authorized work unless the Contracting Officer issues written direction.

Question 28

Source: C.7 (VAAR 852.219-75)

Confirm whether the VAAR 852.219-75 services limit (50%) or the special trade construction limit applies to damper repair work.

Government Response: The solicitation is currently issued under NAICS 561621 and identifies this requirement as a service contract. VAAR 852.219-75 is incorporated under the services category.

Question 29

Source: Period of Performance

NTP + 180 days: are there interim milestones? Can SOC and damper work proceed in parallel at both campuses?

Government Response: The contractor shall provide and maintain a schedule that supports outage notice, ICRA coordination, inspections, repairs, reinspections, and final deliverables. The SOW expressly requires fire-damper repairs at the Temple VAMC and Waco VAMC to be performed simultaneously.

Question 30

Source: General

Is a pre-quote site visit planned?

Government Response: Yes. The SOW requires the contractor to conduct a site visit before bidding to become familiar with facility conditions and the scope. The Contracting Officer will provide the date, time, meeting location, registration requirements, and site-access instructions through the solicitation or an amendment.

Question 31

Source: C.2(d)

Confirm whether the insurance asbestos-exclusion requirement applies to the prime only or to all subcontractors.

Government Response: The prime contractor remains responsible for satisfying all contract insurance requirements and ensuring that subcontractor activities are appropriately insured.

Question 32

Can you please provide a total square footage for all buildings located at the Temple and Waco VAMC's?

Government Response: Total square footage for all buildings at the Temple VAMC and Waco VAMC is not provided in the supplied solicitation documents. If the Government elects to provide total or building-level square footage, it will be distributed to all offerors by amendment.

Question 33

The SOW states:

“Must be a Life Safety Specialist with NFPA 99 or NFPA 101 Technical Committee certification and possess a minimum of 10 years’ experience conducting life safety assessments.”

Our proposed Fire Protection Engineer has 32 years of experience in the industry. However, our understanding is that NFPA Technical Committees do not issue certifications.

Could you please clarify what specific certification or credential the VA is requiring?

Additionally, would a licensed Fire Protection Engineer with 32 years of relevant industry experience satisfy this qualification requirement?

Government Response: For this requirement, the contractor shall demonstrate that the proposed Fire Protection Engineer is a qualified Life Safety Specialist with relevant NFPA 99 or NFPA 101 technical committee experience or credentials and at least 10 years of life-safety assessment experience. A licensed Fire Protection Engineer with 32 years of relevant experience may satisfy the requirement if the submission documents the individual’s life-safety qualifications, applicable technical-committee experience or equivalent subject-matter credentials, licenses, certifications, and relevant project history. Final acceptability will be determined during evaluation.

Question 34

We are currently reviewing Solicitation 36C25727Q0050 for the Life Safety Assessment and Fire Damper Services at the Temple and Waco VA Medical Centers.

Would it be possible to provide floor plans and the approximate square footage for each building included in the Statement of Condition (SOC) assessment scope?

This information would help our team accurately estimate the level of effort and provide competitive pricing for the SOC portion of the project.

Government Response: The SOW states that prior SOC documentation, drawings, and inspection reports will be provided after award. Contractors shall attend the required site visit and field-verify the conditions affecting their proposed level of effort.

Question 35

I have all the credentials and experience to do the fire and smoke damper inspection, please let me know what steps to take to get there.

Government Response: Qualified personnel should demonstrate compliance with the requirements identified in the solicitation through the offer submission, including technical capability information, licenses, certifications, permits, and other applicable documentation required by Section E.2, Offer Submittal Instructions.