VA CLINIC Alarm and Suppression Inventory.xlsx

XLSX spreadsheet 37 KB Posted

Attached to
J042--ELP FIRE ALARM TESTING SERVICES
Solicitation number
36C25724Q0473
Issued by

About this file

This document is an excel file containing the annual testing data for the fire alarm and suppression systems at the VA Clinic. The file covers the required frequency of testing, the total number of devices, the total number of required tests, and the percentage of devices inspected to date for fiscal years 2022, 2023, and 2024. It includes details on supervisory devices, duct detectors, electromagnetic releasing devices, heat detectors, smoke detectors, fire alarm pull boxes, audible/visible devices, transmission equipment, kitchen systems, fire extinguishers, and air-handling smoke shutdown. The document also includes information on valve tamper switches and water flow devices for the suppression systems.

The related federal contract opportunity is a solicitation from the Department of Veterans Affairs, El Paso VA Health Care System, for comprehensive inspection/maintenance/repair and testing services for the fire alarm and suppression systems at the facility. The contract will be for a one-year base period with four additional one-year optional renewals. The Statement of Work provides complete details on the required services.

View the file

Other files

File Type Posted
S04 Site Visit_2 4-17-24.pdf PDF
VA Main Bldg FA 3rd quarterly.pdf PDF
VA Main Bldg 3rd quarterly.pdf PDF
36C25724Q0473 0001_1.docx DOCX document
Amendment 36C25724Q0473 0001.pdf PDF
S02 36C25724Q0473.pdf PDF
S02 36C25724Q0473.pdf PDF
P07 WD 2015-5229 Rev 22 dated 12-26-23 El Paso.pdf PDF
36C25724Q0473_1.docx DOCX document

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Annual Testing FY 2024

Fiscal Year 2024 VA CLINIC Annual Testing - GOAL: 100% OF DEVICES WILL BE TESTED AS REQUIRED BY CODE
1st Floor4th Floor3rd Floor2nd Floor
ALARM DEVICESRequired FrequencyTotal # of DevicesTotal # of Required TestsOCTNOVDECJANFEBMARAPRMAYJUNJULAUGSEP# Inspected To Date% Tested To Date
EP # 1Supervisory Devices (Dec, Mar, Jun, Sep)quarterly4164425.00%
EP #3Duct detectors (Dec, Mar, Jun, Sep)annually3030226.67%
EP #1Electromagnetic releasing devices (Dec, Mar, Jun, Sep)annually1010000.00%
EP # 3Heat detectors (Dec, Mar, Jun, Sep)annually25255520.00%
EP # 1Smoke detectors (Dec, Mar, Jun, Sep)annually4545101022.22%
EP # 1Fire alarm pull boxes (Dec, Mar, Jun, Sep)annually9797161616.49%
EP #4Audible/Visible Devices-(Chimes) (Dec, Mar, Jun, Sep)annually186186363619.35%
EP # 4Audible/Visible Devices- (Speakers) (Dec, Mar, Jun, Sep)annually186186353518.82%
EP # 4Visible devices (strobes) (Dec, Mar, Jun, Sep)annually142142333323.24%
EP # 5Transmission Equipment for Fire Department Notification (Dec, Mar, Jun, Sep)quarterly141125.00%
EP # 10Automatic kitchen systems (Mar, Sep)semi-annual12000.00%
EP # 11Carbon Dioxide & other gaseous Systems (Inergen)annually0000100.00%
EP # 16Fire Extinguishers (monthly) (Jan-Dec)Monthly128153638438425.00%
EP # 16Fire Extinguishers (annually) (Sep)annually128128000.00%
EP # 19Air-handling smoke shutdown (Dec, Mar, Jun, Sep)annually2525228.00%
Totalsannual1008243252400052821.71%
1ST QUARTER2ND QUARTER3RD QUARTER4TH QUARTER
SUPPRESSION DEVICESRequired FrequencyTotal # of DevicesTotal # of Required testsOCTNOVDECJANFEBMARAPRMAYJUNJULAUGSEP# Inspected to Date% Tested To Date
EP # 2Valve tamper switchessemi-annual37148373725.00%
EP #2Water flow devicessemi-annual1664161625.00%
Totals53212535353535325.00%

ANNUAL TESTING DATA FY 2023

Fiscal Year 2023 VA CLINIC Annual Testing - GOAL: 100% OF DEVICES WILL BE TESTED AS REQUIRED BY CODE
1st Floor4th Floor3rd Floor2nd Floor
ALARM DEVICESRequired FrequencyTotal # of DevicesTotal # of Required TestsOCTNOVDECJANFEBMARAPRMAYJUNJULAUGSEP# Inspected To Date% Tested To Date
EP # 1Supervisory Devices (Dec, Mar, Jun, Sep)quarterly416444416100.00%
EP #3Duct detectors (Dec, Mar, Jun, Sep)annually303021081030100.00%
EP #1Electromagnetic releasing devices (Dec, Mar, Jun, Sep)annually10100100010100.00%
EP # 3Heat detectors (Dec, Mar, Jun, Sep)annually25255200025100.00%
EP # 1Smoke detectors (Dec, Mar, Jun, Sep)annually45451012121145100.00%
EP # 1Fire alarm pull boxes (Dec, Mar, Jun, Sep)annually97971618323197100.00%
EP #4Audible/Visible Devices-(Chimes) (Dec, Mar, Jun, Sep)annually18618636188349186100.00%
EP # 4Audible/Visible Devices- (Speakers) (Dec, Mar, Jun, Sep)annually18618635198349186100.00%
EP # 4Visible devices (strobes) (Dec, Mar, Jun, Sep)annually14214233167617142100.00%
EP # 5Transmission Equipment for Fire Department Notification (Dec, Mar, Jun, Sep)quarterly1411114100.00%
EP # 10Automatic kitchen systems (Mar, Sep)semi-annual1201012100.00%
EP # 11Carbon Dioxide & other gaseous Systems (Inergen)annually0000000100.00%
EP # 16Fire Extinguishers (monthly) (Jan-Dec)Monthly12815363843843843841536100.00%
EP # 16Fire Extinguishers (annually) (Sep)annually128128000989876.56%
EP # 19Air-handling smoke shutdown (Dec, Mar, Jun, Sep)annually2525268925100.00%
Totalsannual10082432524515687664240298.77%
1ST QUARTER2ND QUARTER3RD QUARTER4TH QUARTER
SUPPRESSION DEVICESRequired FrequencyTotal # of DevicesTotal # of Required testsOCTNOVDECJANFEBMARAPRMAYJUNJULAUGSEP# Inspected to Date% Tested To Date
EP # 1Valve tamper switchessemi-annual3714837373737148100.00%
EP #1Water flow devicessemi-annual16641616161664100.00%
Totals5321253535353212100.00%

ANNUAL TESTING DATA FY 2022

2022 VA CLINIC GOAL: 100% OF DEVICES WILL BE TESTED AS REQUIRED BY CODE
4th Floor3rd Floor2nd Floor1st Floor
1ST QUARTER2ND QUARTER3RD QUARTER4TH QUARTER
ALARM DEVICESRequired FrequencyTotal # of DevicesTotal # of Required TestsOCTNOVDECJANFEBMARAPRMAYJUNJULAUGSEP# Inspected To Date% Tested To Date
EP # 1Supervisory Devicesquarterly416444416100.00%
EP #1Duct detectorsannually303010810230100.00%
EP #1Electromagnetic releasing devicesannually17171700017100.00%
EP # 1Heat detectorsannually25252000525100.00%
EP # 1Smoke detectorsannually7272302351472100.00%
EP # 1Fire alarm pull boxesannually77771918261477100.00%
EP # 2Audible/Visible Devices-(Chimes)annually18718719864636187100.00%
EP # 2Audible/Visible Devices- (Speakers)annually18718719864636187100.00%
EP # 2Visible devices (strobes)annually93931726173393100.00%
EP # 3Transmission Equipment for Fire Department Notificationquarterly1411114100.00%
EP # 10Automatic kitchen systemssemi-annual1200112100.00%
EP # 11Carbon Dioxide & other gaseous Systems (Inergen)annually0000000100.00%
EP # 12Fire Extinguishers (monthly)Monthly12815363843843843841536100.00%
EP # 12Fire Extinguishers (annually)annually128128000128128100.00%
EP # 15Air-handling smoke shutdownannually303010810230100.00%
Totalsannual980240455064412106602404100.00%
4TH QUARTER1ST QUARTER2ND QUARTER3RD QUARTER
SUPPRESSION DEVICESRequired FrequencyTotal # of DevicesTotal # of Required testsOCTNOVDECJANFEBMARAPRMAYJUNJULAUGSEP# Inspected to Date% Tested To Date
EP # 1Valve tamper switchessemi-annual3714837373737148100.00%
EP #1Water flow devicessemi-annual16641616161664100.00%
Totals21253535353212100.00%

&22ANNUAL FIRE ALARM COMPONENT TESTING

Pull

#AddressDeviceTypeLocation
PassFail
1010301263_4_ALARM_218PULL3RD FLR PULL - N.E. STAIRWELL # 5 EXIT
2010301293_4_ALARM_221PULL3RD FLR PULL- PRIMARYCARE 'C' NORTH EXIT
3010301303_3_ALARM_222PULL3RD FL PULL-RADIOLOGYW. EXIT-DRESS ROOMS
4010301313_2_ALARM_223PULL3RD FL PULL-SPECIALTYCLINIC 1 N.E RM A-350
5010301323_2_ALARM_224PULL3RD FL PULL-SPECIALTYCLINIC 1 N.W. RM A375
6010301333_4_ALARM_225PULL3RD FLR PULL- EAST CORR-SPECIALTY CLINIC
7010301343_5_ALARM_226PULL3RD FLR PULL- EAST CORR-SPECIALTY CLINIC
8010301353_2_ALARM_227PULL3RD FL PULL-SPECIALTYCLINIC 1 EAST EXIT
9010301363_2_ALARM_228PULL3RD FL PULL-SPECIALTYCLINIC 1 WEST EXIT
10010301373_4_ALARM_229PULL3RD FLR PULL-PRIMARY CARE 'B' EAST CORR.
11010301383_5_ALARM_230PULL3RD FLR PULL- PRIMARYCARE 'A' EAST CORR.
12010301393_5_ALARM_231PULL3RD FLR PULL- S.E. EXIT BY LIFE SUPPORT
13010301403_1_ALARM_232PULL3RD FLR PULL MAIN LOBBY
14010301413_1_ALARM_233PULL3RD FLR PULL- S.W. CORR. EXIT BY CASHIER
15010301443_1_ALARM_236PULL3RD FLR PULL- S.W. CORR./VOLUNTARY SVCS.
16010301453_2_ALARM_237PULL3RD FLR PULL- S.W. CORR./ VOLUNTARY SVCS
17010301463_2_ALARM_238PULL3RD FLR PULL- EYE CLINIC NORTH EXIT
18010301473_2_ALARM_239PULL3RD FLR PULL - EYE CLINIC MAIN EXIT PULL
19010301483_1_ALARM_240PULL3RD FLR PULL- INFO SVCS. SOUTH EXIT
20010301493_1_ALARM_241PULL3RD FLR PULL-INFO SVCS. NORTH EXIT
21010301503_3_ALARM_242PULL3RD FL PULL-RADIOLOGYX-RAY WEST EXIT
22010301523_3_ALARM_390PULL3RD FLR RADIOLOGY LABNORTHWEST EXIT PULL
23010301533_3_ALARM_391PULL3RD FLR RADIOLOGY S.W. EXIT BY DRESSING
24010301543_3_ALARM_392PULL3RD FLR LAB PULL EXIT TO WAITING AREA
25010301553_3_ALARM_393PULL3RD FLR RADIOLOGY RECEPTION AREA
26010301563_3_ALARM_394PULL3RD FLR PULL E.R. EXIT
27010301583_1_ALARM_395PULL3RD FLR PULL PRIMARY SUPPORT EXIT
28010301593_1_ALARM_396PULL3RD FL PULL PRIMCARE SUPPORT TEAM HALL
29010301603_1_ALARM_397PULL3RD FL VOLUNTEER RECEPTION OFFICE EXIT
30010401263_6_PULL_1045PULL3RD FLR ANNEX - PULL SKYWALK
31010401883_6_PULL_1038PULL3RD FLR ANNEX - PULL SOUTH WEST STAIRWELL
32010401913_6_PULL_1041PULL3RD FLR ANNEX - PULL NORTH STAIRWELL

Smoke

#AddressDeviceTypeLocation
PassFail
1010300013_3_NORTH_ELEV_3SMOKE3RD FLR SMOKE NORTH ELEVATOR LOBBYX
2010300023_4_ALARM_201SMOKE3RD FLR SMOKE - N.E. CORR. BY ROOM B-362X
3010300073_4_ALARM_206SMOKE3RD FLR SMOKE- EAST CORR.-PRIMARY CARE BX
4010300083_4_3RD_FLR_ALARM_207SMOKE3RD FLR SMOKE IN HALLBY SPECIALTY CLINICX
5010300093_5_SOUTH_SVC_ELEV_3SMOKE3RD FLR SMOKE - SOUTHSERVICE ELEV. LOBBYX
6010300103_5_ALARM_209SMOKE3RD FLR SMOKE- EAST CORR.- BY ELEV. LOBBYX
7010300113_5_ALARM_210SMOKE3RD FLR SMOKE-PRIMARYCARE 'A' EAST CORR.X
8010300163_1_ALARM_215SMOKE3RD FLR SMOKE- WEST CORR. -VOLUNTARY SVCSX
9010300173_1_SOUTH_PASS_ELEV_3SMOKE3RD FLR SMOKE - SOUTHPASSENGER ELEV. LOBBYX
10010300183_3_ALARM_217SMOKE3RD FLR SMOKE - WEST CORR. - NORTH SIDEX
11010400353_6_ALARM_1014SMOKE3RD FLR ANNEX - SMOKETEL/COMM RM. 303X
12010400363_6_ALARM_1015SMOKE3RD FLR ANNEX - SMOKEELECTRICAL RM. 305X
13010400373_6_ANNEX_ELEV_SMOKE_3SMOKE3RD FLR ANNEX - SMOKEELEVATOR LOBBYX

Duct

#AddressDeviceTypeLocation
PassFail
1010300033_4_AHU_3_2_SUPPDUCT3RD FLR-DUCT DETECTORAHU-3.2 SUPPLY SIDE
2010300043_4_AHU_3_2_RETDUCT3RD FLR-DUCT DETECTORAHU-3.2 RETURN SIDE
3010300053_4_AHU_3_1_SUPPDUCT3RD FLR-DUCT DETECTORAHU-3.1 SUPPLY SIDE
4010300063_4_AHU_3_1_RETDUCT3RD FLR DUCT DETECTORAHU 3.1 RETURN SIDE
5010300123_2_AHU_3_3_SUPPDUCT3RD FLR-DUCT DETECTORAHU-3.3 SUPPLY SIDE
6010300133_2_AHU_3_3_RETDUCT3RD FLR-DUCT DETECTORAHU-3-3 RETURN SIDE
7010300143_2_AHU_3_4_RETDUCT3RD FLR DUCT DETECTORAHU-3.4 RETURN SIDE
8010300153_2_AHU_3_4_SUPPDUCT3RD FLR-DUCT DETECTORAHU-3.4 SUPPLY SIDE

File details come from the government source that posted it. Updated .