VA CLINIC Alarm and Suppression Inventory.xlsx
XLSX spreadsheet 37 KB Posted
- Attached to
- J042--ELP FIRE ALARM TESTING SERVICES
- Solicitation number
- 36C25724Q0473
About this file
This document is an excel file containing the annual testing data for the fire alarm and suppression systems at the VA Clinic. The file covers the required frequency of testing, the total number of devices, the total number of required tests, and the percentage of devices inspected to date for fiscal years 2022, 2023, and 2024. It includes details on supervisory devices, duct detectors, electromagnetic releasing devices, heat detectors, smoke detectors, fire alarm pull boxes, audible/visible devices, transmission equipment, kitchen systems, fire extinguishers, and air-handling smoke shutdown. The document also includes information on valve tamper switches and water flow devices for the suppression systems.
The related federal contract opportunity is a solicitation from the Department of Veterans Affairs, El Paso VA Health Care System, for comprehensive inspection/maintenance/repair and testing services for the fire alarm and suppression systems at the facility. The contract will be for a one-year base period with four additional one-year optional renewals. The Statement of Work provides complete details on the required services.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| S04 Site Visit_2 4-17-24.pdf | ||
| VA Main Bldg FA 3rd quarterly.pdf | ||
| VA Main Bldg 3rd quarterly.pdf | ||
| 36C25724Q0473 0001_1.docx | DOCX document | |
| Amendment 36C25724Q0473 0001.pdf | ||
| S02 36C25724Q0473.pdf | ||
| S02 36C25724Q0473.pdf | ||
| P07 WD 2015-5229 Rev 22 dated 12-26-23 El Paso.pdf | ||
| 36C25724Q0473_1.docx | DOCX document |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Annual Testing FY 2024
| Fiscal Year 2024 VA CLINIC Annual Testing - GOAL: 100% OF DEVICES WILL BE TESTED AS REQUIRED BY CODE | ||||||||||||||||||
| 1st Floor | 4th Floor | 3rd Floor | 2nd Floor | |||||||||||||||
| ALARM DEVICES | Required Frequency | Total # of Devices | Total # of Required Tests | OCT | NOV | DEC | JAN | FEB | MAR | APR | MAY | JUN | JUL | AUG | SEP | # Inspected To Date | % Tested To Date | |
| EP # 1 | Supervisory Devices (Dec, Mar, Jun, Sep) | quarterly | 4 | 16 | 4 | 4 | 25.00% | |||||||||||
| EP #3 | Duct detectors (Dec, Mar, Jun, Sep) | annually | 30 | 30 | 2 | 2 | 6.67% | |||||||||||
| EP #1 | Electromagnetic releasing devices (Dec, Mar, Jun, Sep) | annually | 10 | 10 | 0 | 0 | 0.00% | |||||||||||
| EP # 3 | Heat detectors (Dec, Mar, Jun, Sep) | annually | 25 | 25 | 5 | 5 | 20.00% | |||||||||||
| EP # 1 | Smoke detectors (Dec, Mar, Jun, Sep) | annually | 45 | 45 | 10 | 10 | 22.22% | |||||||||||
| EP # 1 | Fire alarm pull boxes (Dec, Mar, Jun, Sep) | annually | 97 | 97 | 16 | 16 | 16.49% | |||||||||||
| EP #4 | Audible/Visible Devices-(Chimes) (Dec, Mar, Jun, Sep) | annually | 186 | 186 | 36 | 36 | 19.35% | |||||||||||
| EP # 4 | Audible/Visible Devices- (Speakers) (Dec, Mar, Jun, Sep) | annually | 186 | 186 | 35 | 35 | 18.82% | |||||||||||
| EP # 4 | Visible devices (strobes) (Dec, Mar, Jun, Sep) | annually | 142 | 142 | 33 | 33 | 23.24% | |||||||||||
| EP # 5 | Transmission Equipment for Fire Department Notification (Dec, Mar, Jun, Sep) | quarterly | 1 | 4 | 1 | 1 | 25.00% | |||||||||||
| EP # 10 | Automatic kitchen systems (Mar, Sep) | semi-annual | 1 | 2 | 0 | 0 | 0.00% | |||||||||||
| EP # 11 | Carbon Dioxide & other gaseous Systems (Inergen) | annually | 0 | 0 | 0 | 0 | 100.00% | |||||||||||
| EP # 16 | Fire Extinguishers (monthly) (Jan-Dec) | Monthly | 128 | 1536 | 384 | 384 | 25.00% | |||||||||||
| EP # 16 | Fire Extinguishers (annually) (Sep) | annually | 128 | 128 | 0 | 0 | 0.00% | |||||||||||
| EP # 19 | Air-handling smoke shutdown (Dec, Mar, Jun, Sep) | annually | 25 | 25 | 2 | 2 | 8.00% | |||||||||||
| Totals | annual | 1008 | 2432 | 524 | 0 | 0 | 0 | 528 | 21.71% | |||||||||
| 1ST QUARTER | 2ND QUARTER | 3RD QUARTER | 4TH QUARTER | |||||||||||||||
| SUPPRESSION DEVICES | Required Frequency | Total # of Devices | Total # of Required tests | OCT | NOV | DEC | JAN | FEB | MAR | APR | MAY | JUN | JUL | AUG | SEP | # Inspected to Date | % Tested To Date | |
| EP # 2 | Valve tamper switches | semi-annual | 37 | 148 | 37 | 37 | 25.00% | |||||||||||
| EP #2 | Water flow devices | semi-annual | 16 | 64 | 16 | 16 | 25.00% | |||||||||||
| Totals | 53 | 212 | 53 | 53 | 53 | 53 | 53 | 25.00% |
ANNUAL TESTING DATA FY 2023
| Fiscal Year 2023 VA CLINIC Annual Testing - GOAL: 100% OF DEVICES WILL BE TESTED AS REQUIRED BY CODE | ||||||||||||||||||
| 1st Floor | 4th Floor | 3rd Floor | 2nd Floor | |||||||||||||||
| ALARM DEVICES | Required Frequency | Total # of Devices | Total # of Required Tests | OCT | NOV | DEC | JAN | FEB | MAR | APR | MAY | JUN | JUL | AUG | SEP | # Inspected To Date | % Tested To Date | |
| EP # 1 | Supervisory Devices (Dec, Mar, Jun, Sep) | quarterly | 4 | 16 | 4 | 4 | 4 | 4 | 16 | 100.00% | ||||||||
| EP #3 | Duct detectors (Dec, Mar, Jun, Sep) | annually | 30 | 30 | 2 | 10 | 8 | 10 | 30 | 100.00% | ||||||||
| EP #1 | Electromagnetic releasing devices (Dec, Mar, Jun, Sep) | annually | 10 | 10 | 0 | 10 | 0 | 0 | 10 | 100.00% | ||||||||
| EP # 3 | Heat detectors (Dec, Mar, Jun, Sep) | annually | 25 | 25 | 5 | 20 | 0 | 0 | 25 | 100.00% | ||||||||
| EP # 1 | Smoke detectors (Dec, Mar, Jun, Sep) | annually | 45 | 45 | 10 | 12 | 12 | 11 | 45 | 100.00% | ||||||||
| EP # 1 | Fire alarm pull boxes (Dec, Mar, Jun, Sep) | annually | 97 | 97 | 16 | 18 | 32 | 31 | 97 | 100.00% | ||||||||
| EP #4 | Audible/Visible Devices-(Chimes) (Dec, Mar, Jun, Sep) | annually | 186 | 186 | 36 | 18 | 83 | 49 | 186 | 100.00% | ||||||||
| EP # 4 | Audible/Visible Devices- (Speakers) (Dec, Mar, Jun, Sep) | annually | 186 | 186 | 35 | 19 | 83 | 49 | 186 | 100.00% | ||||||||
| EP # 4 | Visible devices (strobes) (Dec, Mar, Jun, Sep) | annually | 142 | 142 | 33 | 16 | 76 | 17 | 142 | 100.00% | ||||||||
| EP # 5 | Transmission Equipment for Fire Department Notification (Dec, Mar, Jun, Sep) | quarterly | 1 | 4 | 1 | 1 | 1 | 1 | 4 | 100.00% | ||||||||
| EP # 10 | Automatic kitchen systems (Mar, Sep) | semi-annual | 1 | 2 | 0 | 1 | 0 | 1 | 2 | 100.00% | ||||||||
| EP # 11 | Carbon Dioxide & other gaseous Systems (Inergen) | annually | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 100.00% | ||||||||
| EP # 16 | Fire Extinguishers (monthly) (Jan-Dec) | Monthly | 128 | 1536 | 384 | 384 | 384 | 384 | 1536 | 100.00% | ||||||||
| EP # 16 | Fire Extinguishers (annually) (Sep) | annually | 128 | 128 | 0 | 0 | 0 | 98 | 98 | 76.56% | ||||||||
| EP # 19 | Air-handling smoke shutdown (Dec, Mar, Jun, Sep) | annually | 25 | 25 | 2 | 6 | 8 | 9 | 25 | 100.00% | ||||||||
| Totals | annual | 1008 | 2432 | 524 | 515 | 687 | 664 | 2402 | 98.77% | |||||||||
| 1ST QUARTER | 2ND QUARTER | 3RD QUARTER | 4TH QUARTER | |||||||||||||||
| SUPPRESSION DEVICES | Required Frequency | Total # of Devices | Total # of Required tests | OCT | NOV | DEC | JAN | FEB | MAR | APR | MAY | JUN | JUL | AUG | SEP | # Inspected to Date | % Tested To Date | |
| EP # 1 | Valve tamper switches | semi-annual | 37 | 148 | 37 | 37 | 37 | 37 | 148 | 100.00% | ||||||||
| EP #1 | Water flow devices | semi-annual | 16 | 64 | 16 | 16 | 16 | 16 | 64 | 100.00% | ||||||||
| Totals | 53 | 212 | 53 | 53 | 53 | 53 | 212 | 100.00% |
ANNUAL TESTING DATA FY 2022
| 2022 VA CLINIC GOAL: 100% OF DEVICES WILL BE TESTED AS REQUIRED BY CODE | ||||||||||||||||||
| 4th Floor | 3rd Floor | 2nd Floor | 1st Floor | |||||||||||||||
| 1ST QUARTER | 2ND QUARTER | 3RD QUARTER | 4TH QUARTER | |||||||||||||||
| ALARM DEVICES | Required Frequency | Total # of Devices | Total # of Required Tests | OCT | NOV | DEC | JAN | FEB | MAR | APR | MAY | JUN | JUL | AUG | SEP | # Inspected To Date | % Tested To Date | |
| EP # 1 | Supervisory Devices | quarterly | 4 | 16 | 4 | 4 | 4 | 4 | 16 | 100.00% | ||||||||
| EP #1 | Duct detectors | annually | 30 | 30 | 10 | 8 | 10 | 2 | 30 | 100.00% | ||||||||
| EP #1 | Electromagnetic releasing devices | annually | 17 | 17 | 17 | 0 | 0 | 0 | 17 | 100.00% | ||||||||
| EP # 1 | Heat detectors | annually | 25 | 25 | 20 | 0 | 0 | 5 | 25 | 100.00% | ||||||||
| EP # 1 | Smoke detectors | annually | 72 | 72 | 30 | 23 | 5 | 14 | 72 | 100.00% | ||||||||
| EP # 1 | Fire alarm pull boxes | annually | 77 | 77 | 19 | 18 | 26 | 14 | 77 | 100.00% | ||||||||
| EP # 2 | Audible/Visible Devices-(Chimes) | annually | 187 | 187 | 19 | 86 | 46 | 36 | 187 | 100.00% | ||||||||
| EP # 2 | Audible/Visible Devices- (Speakers) | annually | 187 | 187 | 19 | 86 | 46 | 36 | 187 | 100.00% | ||||||||
| EP # 2 | Visible devices (strobes) | annually | 93 | 93 | 17 | 26 | 17 | 33 | 93 | 100.00% | ||||||||
| EP # 3 | Transmission Equipment for Fire Department Notification | quarterly | 1 | 4 | 1 | 1 | 1 | 1 | 4 | 100.00% | ||||||||
| EP # 10 | Automatic kitchen systems | semi-annual | 1 | 2 | 0 | 0 | 1 | 1 | 2 | 100.00% | ||||||||
| EP # 11 | Carbon Dioxide & other gaseous Systems (Inergen) | annually | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 100.00% | ||||||||
| EP # 12 | Fire Extinguishers (monthly) | Monthly | 128 | 1536 | 384 | 384 | 384 | 384 | 1536 | 100.00% | ||||||||
| EP # 12 | Fire Extinguishers (annually) | annually | 128 | 128 | 0 | 0 | 0 | 128 | 128 | 100.00% | ||||||||
| EP # 15 | Air-handling smoke shutdown | annually | 30 | 30 | 10 | 8 | 10 | 2 | 30 | 100.00% | ||||||||
| Totals | annual | 980 | 2404 | 550 | 644 | 1210 | 660 | 2404 | 100.00% | |||||||||
| 4TH QUARTER | 1ST QUARTER | 2ND QUARTER | 3RD QUARTER | |||||||||||||||
| SUPPRESSION DEVICES | Required Frequency | Total # of Devices | Total # of Required tests | OCT | NOV | DEC | JAN | FEB | MAR | APR | MAY | JUN | JUL | AUG | SEP | # Inspected to Date | % Tested To Date | |
| EP # 1 | Valve tamper switches | semi-annual | 37 | 148 | 37 | 37 | 37 | 37 | 148 | 100.00% | ||||||||
| EP #1 | Water flow devices | semi-annual | 16 | 64 | 16 | 16 | 16 | 16 | 64 | 100.00% | ||||||||
| Totals | 212 | 53 | 53 | 53 | 53 | 212 | 100.00% |
&22ANNUAL FIRE ALARM COMPONENT TESTING
Pull
| # | Address | DeviceType | Location | |||
| Pass | Fail | |||||
| 1 | 01030126 | 3_4_ALARM_218 | PULL | 3RD FLR PULL - N.E. STAIRWELL # 5 EXIT | ||
| 2 | 01030129 | 3_4_ALARM_221 | PULL | 3RD FLR PULL- PRIMARYCARE 'C' NORTH EXIT | ||
| 3 | 01030130 | 3_3_ALARM_222 | PULL | 3RD FL PULL-RADIOLOGYW. EXIT-DRESS ROOMS | ||
| 4 | 01030131 | 3_2_ALARM_223 | PULL | 3RD FL PULL-SPECIALTYCLINIC 1 N.E RM A-350 | ||
| 5 | 01030132 | 3_2_ALARM_224 | PULL | 3RD FL PULL-SPECIALTYCLINIC 1 N.W. RM A375 | ||
| 6 | 01030133 | 3_4_ALARM_225 | PULL | 3RD FLR PULL- EAST CORR-SPECIALTY CLINIC | ||
| 7 | 01030134 | 3_5_ALARM_226 | PULL | 3RD FLR PULL- EAST CORR-SPECIALTY CLINIC | ||
| 8 | 01030135 | 3_2_ALARM_227 | PULL | 3RD FL PULL-SPECIALTYCLINIC 1 EAST EXIT | ||
| 9 | 01030136 | 3_2_ALARM_228 | PULL | 3RD FL PULL-SPECIALTYCLINIC 1 WEST EXIT | ||
| 10 | 01030137 | 3_4_ALARM_229 | PULL | 3RD FLR PULL-PRIMARY CARE 'B' EAST CORR. | ||
| 11 | 01030138 | 3_5_ALARM_230 | PULL | 3RD FLR PULL- PRIMARYCARE 'A' EAST CORR. | ||
| 12 | 01030139 | 3_5_ALARM_231 | PULL | 3RD FLR PULL- S.E. EXIT BY LIFE SUPPORT | ||
| 13 | 01030140 | 3_1_ALARM_232 | PULL | 3RD FLR PULL MAIN LOBBY | ||
| 14 | 01030141 | 3_1_ALARM_233 | PULL | 3RD FLR PULL- S.W. CORR. EXIT BY CASHIER | ||
| 15 | 01030144 | 3_1_ALARM_236 | PULL | 3RD FLR PULL- S.W. CORR./VOLUNTARY SVCS. | ||
| 16 | 01030145 | 3_2_ALARM_237 | PULL | 3RD FLR PULL- S.W. CORR./ VOLUNTARY SVCS | ||
| 17 | 01030146 | 3_2_ALARM_238 | PULL | 3RD FLR PULL- EYE CLINIC NORTH EXIT | ||
| 18 | 01030147 | 3_2_ALARM_239 | PULL | 3RD FLR PULL - EYE CLINIC MAIN EXIT PULL | ||
| 19 | 01030148 | 3_1_ALARM_240 | PULL | 3RD FLR PULL- INFO SVCS. SOUTH EXIT | ||
| 20 | 01030149 | 3_1_ALARM_241 | PULL | 3RD FLR PULL-INFO SVCS. NORTH EXIT | ||
| 21 | 01030150 | 3_3_ALARM_242 | PULL | 3RD FL PULL-RADIOLOGYX-RAY WEST EXIT | ||
| 22 | 01030152 | 3_3_ALARM_390 | PULL | 3RD FLR RADIOLOGY LABNORTHWEST EXIT PULL | ||
| 23 | 01030153 | 3_3_ALARM_391 | PULL | 3RD FLR RADIOLOGY S.W. EXIT BY DRESSING | ||
| 24 | 01030154 | 3_3_ALARM_392 | PULL | 3RD FLR LAB PULL EXIT TO WAITING AREA | ||
| 25 | 01030155 | 3_3_ALARM_393 | PULL | 3RD FLR RADIOLOGY RECEPTION AREA | ||
| 26 | 01030156 | 3_3_ALARM_394 | PULL | 3RD FLR PULL E.R. EXIT | ||
| 27 | 01030158 | 3_1_ALARM_395 | PULL | 3RD FLR PULL PRIMARY SUPPORT EXIT | ||
| 28 | 01030159 | 3_1_ALARM_396 | PULL | 3RD FL PULL PRIMCARE SUPPORT TEAM HALL | ||
| 29 | 01030160 | 3_1_ALARM_397 | PULL | 3RD FL VOLUNTEER RECEPTION OFFICE EXIT | ||
| 30 | 01040126 | 3_6_PULL_1045 | PULL | 3RD FLR ANNEX - PULL SKYWALK | ||
| 31 | 01040188 | 3_6_PULL_1038 | PULL | 3RD FLR ANNEX - PULL SOUTH WEST STAIRWELL | ||
| 32 | 01040191 | 3_6_PULL_1041 | PULL | 3RD FLR ANNEX - PULL NORTH STAIRWELL |
Smoke
| # | Address | DeviceType | Location | |||
| Pass | Fail | |||||
| 1 | 01030001 | 3_3_NORTH_ELEV_3 | SMOKE | 3RD FLR SMOKE NORTH ELEVATOR LOBBY | X | |
| 2 | 01030002 | 3_4_ALARM_201 | SMOKE | 3RD FLR SMOKE - N.E. CORR. BY ROOM B-362 | X | |
| 3 | 01030007 | 3_4_ALARM_206 | SMOKE | 3RD FLR SMOKE- EAST CORR.-PRIMARY CARE B | X | |
| 4 | 01030008 | 3_4_3RD_FLR_ALARM_207 | SMOKE | 3RD FLR SMOKE IN HALLBY SPECIALTY CLINIC | X | |
| 5 | 01030009 | 3_5_SOUTH_SVC_ELEV_3 | SMOKE | 3RD FLR SMOKE - SOUTHSERVICE ELEV. LOBBY | X | |
| 6 | 01030010 | 3_5_ALARM_209 | SMOKE | 3RD FLR SMOKE- EAST CORR.- BY ELEV. LOBBY | X | |
| 7 | 01030011 | 3_5_ALARM_210 | SMOKE | 3RD FLR SMOKE-PRIMARYCARE 'A' EAST CORR. | X | |
| 8 | 01030016 | 3_1_ALARM_215 | SMOKE | 3RD FLR SMOKE- WEST CORR. -VOLUNTARY SVCS | X | |
| 9 | 01030017 | 3_1_SOUTH_PASS_ELEV_3 | SMOKE | 3RD FLR SMOKE - SOUTHPASSENGER ELEV. LOBBY | X | |
| 10 | 01030018 | 3_3_ALARM_217 | SMOKE | 3RD FLR SMOKE - WEST CORR. - NORTH SIDE | X | |
| 11 | 01040035 | 3_6_ALARM_1014 | SMOKE | 3RD FLR ANNEX - SMOKETEL/COMM RM. 303 | X | |
| 12 | 01040036 | 3_6_ALARM_1015 | SMOKE | 3RD FLR ANNEX - SMOKEELECTRICAL RM. 305 | X | |
| 13 | 01040037 | 3_6_ANNEX_ELEV_SMOKE_3 | SMOKE | 3RD FLR ANNEX - SMOKEELEVATOR LOBBY | X |
Duct
| # | Address | DeviceType | Location | |||
| Pass | Fail | |||||
| 1 | 01030003 | 3_4_AHU_3_2_SUPP | DUCT | 3RD FLR-DUCT DETECTORAHU-3.2 SUPPLY SIDE | ||
| 2 | 01030004 | 3_4_AHU_3_2_RET | DUCT | 3RD FLR-DUCT DETECTORAHU-3.2 RETURN SIDE | ||
| 3 | 01030005 | 3_4_AHU_3_1_SUPP | DUCT | 3RD FLR-DUCT DETECTORAHU-3.1 SUPPLY SIDE | ||
| 4 | 01030006 | 3_4_AHU_3_1_RET | DUCT | 3RD FLR DUCT DETECTORAHU 3.1 RETURN SIDE | ||
| 5 | 01030012 | 3_2_AHU_3_3_SUPP | DUCT | 3RD FLR-DUCT DETECTORAHU-3.3 SUPPLY SIDE | ||
| 6 | 01030013 | 3_2_AHU_3_3_RET | DUCT | 3RD FLR-DUCT DETECTORAHU-3-3 RETURN SIDE | ||
| 7 | 01030014 | 3_2_AHU_3_4_RET | DUCT | 3RD FLR DUCT DETECTORAHU-3.4 RETURN SIDE | ||
| 8 | 01030015 | 3_2_AHU_3_4_SUPP | DUCT | 3RD FLR-DUCT DETECTORAHU-3.4 SUPPLY SIDE |